-
C4-1R 1/12
6. СОВЕТУВАЊЕОхрид, 4 - 6 октомври 2009
Herbert Haidvogl Roman Lechner EVN Netz GmbH, A-2344 Maria
Enzersdorf, EVN Platz 1
Standards on electricity distribution - examples
ABSTRACT
This paper focuses on generally applicable standards and their
introduction in the Republic of Macedonia. On the way to become
member of EC it is necessary for the candidate country to implement
a number of European Standards. They are often prepared on the
state of art in EC and require also suitable legal and technical
environment. One difference is e.g. electrical networks in EEC are
from the technical point of view old and partly overloaded.
According to the standards it is necessary to invest in upgrading
the network. But also customers of electricity can be influenced by
the standards. Old electrical devices often are not able to work
properly with new defined values e.g. rated voltage of
standards.
Especially standards with influence to the public as EN 50160,
EN 61000-3-XX, pr EN 50522 (earthing of power installations) and
related topics to protection against electrical shocks should be
discussed in detail.
Bodies for standardisation in the field of electricity are IEC
(International Electrotechnical Commission) and CENELEC (European
Committee for Electrotechnical Standardisation) in the region of EU
worldwide IEC and IEEE. Additionally there are national bodies for
standardisation. In 2008 about 5425 IEC-standards were available
and 483 standards where published. A number of 1976 are in
progress. On the European level in 2008 about 5220 European
standards and 305 harmonization documents were available. 483 EN
and 10 HD where published. In the draft phase are 959. 861 prEN
(projet EN) and prHD where published in 2008 [1]. This high number
of published documents is a huge challenge for the body of national
standardisation institute because it has to act quickly and
accurate. This body should also be a representative in the
international standardisation organisations.
The main field of electricity has a very spread spectrum. It
includes production of electrical energy, electromagnetic
compatibility, lighting protection, effect of current, safety,
electric apparatuses for different fields of application,
insulation coordination and measurements. All this topics imply
self-evident standardisation. The focus should now be on “Standard
voltages, current ratings and frequency” and also on “Equipment
specifications and requirements”.
Keywords: Standards, European Standards, IEC, CENELEC, CE, EE,
EN50160, EN61000, IEC 61936, EN 50522, supply quality, power
installations, earthing, operational earthing, protection earthing,
voltage regulation, voltage drop, three winding transformer,
prefabricated transformerstation, neutral point treatment,
measurements
1 SUPPLY QUALITY
Standard voltages, current ratings and frequency for low voltage
(up to 1 kV) and medium voltage (1 kV up to 35 kV) networks are
fixed in IEC 60038 “IEC standard voltages” [2], EN 50160 “Voltage
characteristics of electricity supplied by public distribution
networks” [3] and also in EN
-
MAKO CIGRE 2009 C4-1R 2/12
61000-3-3 [4], -3-11 [5], -3-12 [6] all together deal with
electromagnetic compatibility and limits for voltage
distortion.
1.1 Nominal voltage
In the standard 60038 of IEC nominal voltage of systems, highest
and lowest voltages of system voltage (under normal conditions) and
also rated and highest voltages for equipment are fixed. Nominal
voltages for networks are the “input” for the EN 50160 which
generally focuses the main characteristics of voltage at network
users supply terminal in public low and middle voltage electricity
distribution system under normal operating conditions. The nominal
voltage is fixed in this standard to 230/400 V on the other side in
some EE countries this value is 220/380 V. If still used older
devices of customers are designed for this standard voltage
introduction of new EN and IEC standard could cause a lot of
problems. Devices which fulfil the requirements of EN 50160 and all
other relevant European Standards are signed with the CE mark which
is not only a sign for electrical devices.
1.2 Important characteristic of supply quality
Table 1 shows an excerpt of EN 50160 with important values and
parameters. In this table the main responsibility for the values
either the TSO (Transmission System Operator) or DSO (Distribution
System Operator) can be found in the last column.
Table 1: Excerpt of EN 50160
Attribute of the supply voltage
Values Measuring and analysis parameter
resp
onsi
bilit
y
LV MV sample rate
observation period
percent
frequency 49,5Hz … 50,5 Hz 47 Hz … 52 Hz mean value 10 s 1 week
99,5 % 100 % TSO
voltage variation
Un = 230 V ± 10 % Uc ± 10 % r.m.s. 10 min 1 week 95 %
TSO DSO
Interruptions (short and long)
below 1 % of Uc 10 up to 100 10 up to 50
r.m.s. 10 ms 1 year 100 % DSO
rapid voltage variation
5 % of Un max. 10 %
4 % of Uc max. 6 % r.m.s. 10 ms 1 day 100 % DSO
flicker Plt < 1 Flicker- algorithmus 2 h 1 week 100 % DSO
harmonic voltage reference: Un, Uc
THD max. 8 % r.m.s. 10 min 1 week 95 % DSO
supply voltage unbalance
0 % … 2 % special cases 3 % r.m.s. 10 min 1 week 95 % DSO
As mentioned the implementation of a new standard has influence
on both the customer’s and the supplier’s side. Tolerance of
frequency is small and indicates a deficit or a surplus of
electrical power in the grid not only locally but also because of
interconnection of national transmission grids in
-
MAKO CIGRE 2009 C4-1R 3/12
the UCTE network. Frequency can only be out of range if there
are big events in the UCTE network. Such events will be managed
according to UCTE handbook [7] and if this fails stability of
network can not be ensured and a black out can happen.
Rapid voltage variation in the supply voltage as mentioned in
the EN 50160 are mainly caused either by load changes in the
installation of the users or by switching in the system.
All this parameters can be influenced by technical solution
either on utility’s or customer’s side. On utility side this means
upgrading of the power lines and transformers, building of
additional substations, distribution transformer stations and new
overhead or cable lines. To achieve those standard requirements a
lot of investments are necessary and their implementation need many
years for realisation due to financing, getting permissions and
limited capacity of resources.
1.3 Distribution and Transmission Codes (rulebooks)
Additional to IEC and CENELEC standards it could be helpful to
publish guideline or rulebooks e.g. as Distribution Code and
Transmission Code. The connection of new power plants or
generators, necessary performance of customer equipment, such as
electrical motors, welding machines, compensation devices for
reactive load and e.g. rules on judging of voltage characteristics
should be regulated. In the Republic of Macedonia the Transmission
Grid Code and Distribution Grid Code is a good basis but
adjustments according to new standards and practical experience
should be done.
For example power plants e.g. wind generators could be obliged
to stay connected to the network in case of a voltage dip and
support actively voltage level during fault time. That could also
mean new power plants should be able to manage reactive power in a
wide range which is in the moment a big challenge for some type of
generator (e.g. solar power plants). In former times the concept
was to regulate on the MPP (maximum power point) that means cos(φ)
near to one. Now rectifiers should be able to deliver reactive
power on request.
National examples for such technical guidelines are the Germany
SDLV (Systemdienst-leistungsverordnung) and TR (Technische
Richtlinien) of FGW [8] and the Austrian TOR (Technisch
Organisatorische Richtlinien) of the Austrian regulatory board
[9].
Within rulebooks (Grid codes) guidelines for connection of
devices to low voltage and medium voltage networks are defined.
There are also specifications for connections to high voltage level
and if the rated power of a new generator exceeds 5 MW. For such
cases e.g. it is fixed when DSO has to inform the TSO. Both will
investigate the case and prepare an economic and technical
acceptable proposal.
Investments have also to be covered by network appropriate
tariffs and approved by the regulator.
2 GRID IMPEDANCE
EN 61000-3-XX “Electromagnetic Compatibility” regulates the
limitation of voltage changes, voltage fluctuations and flicker in
low voltage networks public systems. There are differences in rated
current per phase. EN 61000-3-3 for rated current per phase ≤ 16 A,
EN 61000-3-11 for rated current per phase ≤ 75 A and EN 61000-3-12
currents per phase >16 A and < 75 A. In these standards the
testing procedures for devices are regulated. Impedances and
corresponding short circuit power are laid down and could be used
both for testing and for improving of grid as an aim.
This short circuit power can be seen as an indicator of
stiffness of a certain network on short circuit conditions.
Stiffness in this case means that the network is robust against
flicker and other voltage fluctuations. Aim should be to provide a
minimum of short circuit power at each location in power grids.
This can be achieved by using overhead and cable lines with conform
diameters and a
-
MAKO CIGRE 2009 C4-1R 4/12
maximum length of the feeders. Test assembly of the testing
procedure for the devices looks like shown in Figure 1.
Figure 1 Test assembly
M … Measurement device
S … test voltage source (includes generator G and reference
impedance
Z = RA+jXA)
Evaluation of the relevant values which are described in IEC
61000-3-3 has to be done on the impedance Z = RA+jXA.
3 VOLTAGE REGULATION ON PTR
Remote control of important grid knots should be installed more
and more in order to be able to react quickly in case of failures
and come back to normal supply conditions. Another important issue
is automatic voltage regulation of power transformers in
substations. This is a standard and regularly used measure for
transformers with two coils. Three winding transformers are often
used in EE countries which make automatic voltage regulation more
sophisticated. There are solutions offered on the market. A
compromise on the secondary or tertiary winding of the transformer
has to be accepted.
By using three winding transformers the voltage drop on costumer
side could be decreased by the step voltage directly on the
transformer. In Figure 2 this fact is shown very imposing.
Variation of the secondary and tertiary apparent power load from
zero to 100% leads to a characteristic of the voltage drop between
these two sides. That means the allowed voltage drop on the low
voltage level has to be decreased (in the example case 4.5 %) to
fulfil the requirements.
test
sample
-
MAKO CIGRE 2009 C4-1R 5/12
Figure 2 Voltage drop of a three winding transformer
This additional voltage drop depends on the used power
transformer with its characteristic parameters. To know exactly how
to parameterize the automatic voltage regulator it is necessary to
calculate each transformer with its expected load separately.
Equipment supplier provides different voltage regulation strategies
for such transformers e.g. regulating one side manually and
monitoring the other. If voltage is equal to a defined limit the
regulation process will be stopped. Second strategy is to choose
the side to be regulated by monitoring the load. The side with
heavier load will be chosen for regulation. The other side will
only be monitored.
The most common solution with two winding transformers is to
regulate on constant busbar voltage. If compensation of voltage
drop of long feeder lines is necessary voltage control at a certain
distant location could be carried out. By using communication
technology the actual data is transmitted to the regulation device
in the substation and there voltage regulation is done by tap
changer. To avoid that voltage exceeds allowed range on the other
feeders of this busbar monitoring devices have to be used.
4 NEUTRAL TREATMENT OF NETWORKS
In the context of power quality another important topic is
grounding of installations but also neutral grounding. Different
types of neutral grounding (resistor, impedance, KNOSPE, NOSPE,
isolated) define the possibilities of network operation in case of
earth fault. Two standards deal with this question. Firstly
European HD 637 S1 “power installations exceeding 1 kV a.c.” [10]
includes earthing of power installations. This standard was
implemented as national standard OVE-E8383 in Austria and as
DIN/VDE 0101 in Germany and secondly on IEC level IEC 61936-1
“Power installations exceeding 1 kV a.c.” [11]. These two standards
are now in revision and probably in 2010 new standards EN 50522 and
a revised version of IEC/EN 61936-1 as shown in Figure 3 will be
available.
U1=110 kV
U2= 35 kV
U3=10 kV
S1=31.5 MVA
S2=15.75 MVA
S3=31.5 MVA
uk12 = 10.18 %
uk23 = 5.96 %
uk31= 16.95 %
cos(φ)= 0.9ind
-
MAKO CIGRE 2009 C4-1R 6/12
Figure 3 Harmonization Process
EN 50522 in difference to HD 637 S1 covers only the chapter
dealing with earthing while all other topics relating to power
installations will be kept in EN 61936-1. There are no big changes
in both documents apart from the paragraph dealing with double
earth faults and design of earthing conductors. The standards allow
to operate network energized during earth fault conditions if
neutral treatment is isolated (limited network size) or compensated
via Petersen coil (impedance neutral grounding). If compensated the
applicable current for dimensioning of grounding equipment will be
the residual current of earth fault and if the probability of a
double earth fault is low. To switch off feeder helps to keep step
and touch voltages below limits but quality of supply will
decrease. Otherwise if step and touch voltages are kept within
tolerable limits e.g. limitation through compensation coil, grid
operation could continue and customer will not suffer supply
breaks.
EN/IEC 61936-1-2010 is intended as replacement of HD 637 S1 and
also IEC 61936-1 2002 which includes a regulative for design and
construction of power installations.
Because of differences in earthing philosophy between Europe and
North America different chapters will be written. A more global one
is included in IEC 61936-1 2010 and for Europe a more precise one
will be written separately in EN 50522.
3.1 EVN Experience on earthing systems from Bulgaria
Results of an 20 kV network which consists of about 40 km cable
lines and 200 km overhead lines connected to an 110/20 kV
substation which was alternately operated with resistance (R) and
resonant neutral grounding and with equipment to increase residual
current (L) were analysed. These results are given in Figure 4. In
case of resonant neutral (L) grounding feeder tripping by earth
fault detection system (IE) decreases to zero but tripping by
over-current protection I> and I>> increases a little. In
case of resistor earthing (R) each earth fault leads to a feeder
trip and supply interruption for customers. The using of resonant
neutral grounding improves supply quality. Detection of location
along feeder by using this method is not simple although affected
feeder in substation could be detected automatically. Normally the
system operator has to do switching (so called earth fault
detection switching) to find and switch off the network parts with
earth fault. During this time step and touch voltages have to be
kept within given limits. For physical reasons voltage in “two
healthy phases” increases by 3 and reaches phase to phase voltage
between phase and earth. Weak insulations in grid e.g. old cables
or arrestors could be destroyed.
As it can be seen that introduction of resonant neutral
grounding increases the quality of supply on the other hand
operation of such networks is more difficult than networks where
earth faults are switched off within a short time. Step and touch
voltages in case of an earth fault have to be decreased to a non
dangerous level as can be found in future in EN 50522 and nowadays
in HD 637 S1. To reach this aim efficient earthing systems have to
be built and checked regularly.
-
MAKO CIGRE 2009 C4-1R 7/12
Figure 4 Results neutral grounding
3.2 Earthing system and touch voltage
Earthing systems can be differentiated in the operational
earthing of the transformer and low voltage grid and the protection
earthing system. In urban areas the two systems are connected and
in rural areas they are operated separately. The “Technical
Recommendations Nr. 7”of the Republic of Macedonia, which where
based on the JUS standards from the former Republic of Yugoslavia
chapter 4, 5 and 6, states how earthing systems have to be built.
Chapter 4 is for substations 35/10 kV, and chapter 5 is for 20/0.4
kV and 10/0.4 kV transformer stations with cable grid. In this case
both earthing systems have to be connected. In chapter 6 rules for
construction of earthing in stations 20/0.4 kV or 10/0.4 kV with LV
overhead line grid are defined. The following points have to be
taken into account.
If the earthing systems are not connected and MV network is
operated by resistant earthing:
– The distance between the earthing systems has to be at minimum
20 m.
– The potential difference between the systems has to be less
than 40 % and the voltage on the protection earthing system is less
than 1200 V.
Operation mode R
Operation mode L
operational
operational
Successfull AR
Switch off
Successfull AR
Switch off
-
MAKO CIGRE 2009 C4-1R 8/12
– The area where the station is located has to be urban.
If the MV network is operated with isolated neutral grounding
the earthing system of distribution transformer has to be
obligatory connected.
3.3 Result of measurement of step and touch voltage in DT
A distribution transformer station in Macedonia was chosen for
measurements in order to check if earthing systems of stations
described in chapter 5 can be connected and what are the related
step and touch voltages
Figure 5 shows the arrangement for the measurements of step and
touch voltages. A current was injected in a switched off 10-kV
overhead line in a distance and this simulates an earth fault
current. For practical reasons 50 A could be injected. Measurements
of step and touch voltage were done in the surrounding of
transformer station. If earth fault current in reality is 300 amps
a calculation of step and touch voltages could easily performed.
Earthing resistance was determined by using common measuring
methods.
Results are as given below:
– Connected systems 0.83 Ω.
– Separated systems 1.68 Ω for protection earth and 1.15 Ω for
earthing of transformer station.
Graphs in Figure 6 show the results of the experiment. The
average value of step voltage as
well as of touch voltage decreases if connected. “Technical
recommendations Nr. 7” chapter 2.7 defines the acceptable touch
voltages for short and long time. Long time touch voltage should
not exceed 75 V. This limit is given in HD637 S1 and is in
accordance with prEN 50522. Only location 1 (Figure 6) could
require improvement (renewing) of earthing system to avoid too high
touch voltage.
To find an obligatory answer whether connection of earthing
systems on transformerstation with overhead line grids is possible
or not additional measurements with a representative number should
be carried out. If the results of measurement campaign show that
connection is allowed without a deficit on security these
regulations could be adapted. This would be in accordance with
Austrian experience.
-
MAKO CIGRE 2009 C4-1R 9/12
Figure 5 Arrangement for measure step voltages and touch
voltages
Touch voltage
0
10
20
30
40
50
60
70
1 2 3 4 5 6 7
measuringpoint
touc
h vo
ltag
e m
easu
red
in V
splitedconnected
Step voltage
0
0,2
0,4
0,6
0,8
1
1,2
1,4
1,6
1,8
1 2 3 4 5 6 7 8 9
measuringpoint
touc
h vo
ltag
e m
easu
red
in V
splitedconnected
Figure 6 Characteristics of touch and step voltage
a … TS
b … incoming feeder
x-c … measuring points for step voltage
x-d … measuring points for touch voltage
a
b
-
MAKO CIGRE 2009 C4-1R 10/12
5 NEW DISTRIBUTION TRANSFORMER STATIONS
By using transformer station with a high degree of
standardisation which also includes standards for the earthing
system not only economical but also technical and safety goals
could be achieved. Prefabricated transformer stations are described
in the European standard EN 62271-202 “High-voltage switchgear and
controlgear - Part 202: High-voltage/low voltage prefabricated
substation” [12]. This standard includes regulation on
– Earthing (includes also examples for earthing system)
– Calculation and testing (electrical and mechanical)
– Different types of testing routines
– Data for procurement
The big advantage of prefabricated substations is that the
assembly on the site is reduced to a minimum. So quality is much
less dependent on weather conditions. Only electrical connection to
the network (on medium and low voltage side) and to earthing system
has to be made. Installation and technologically correct connection
of earthing wires are important. Nevertheless they are underground
and could not be seen.
To speed up erection time of DT a general approve of
standardised types should be established in the Republic of
Macedonia. If every individual solution has to be permitted one by
one by the local authorities too much time is needed. In Austria,
Macedonia and Bulgaria EVN has defined a standard compact
transformer station (20/0.4 kV and 10/0.4 kV) and got a general
permission for this type in Austria. In Austria type KN1830 (3.0 m
x 1.8 m) has been installed over 2500 times within last ten years.
In Macedonia and Bulgaria this station is called FK-3. Transformer,
medium voltage switchgear and all necessary equipment for the low
voltage is installed into the concrete housing in the factory and
delivered on site.
To define the requirements of such stations it is necessary to
know well the topology of network (medium and low voltage), and the
common type of customers (important for choosing the rated power of
transformer). Normally SF6 medium voltage switchgear cells are used
which can be combined in different variants. The cubicles have to
satisfy the corresponding standards of local environment. Low
voltage feeders and equipment can be adapted to the customer needs.
Housing normally is made of concrete, metal parts should be
rustproof.
Summary of advantages:
– Equipment and arrangement of installation is safe for staff
and passer-byes (IEC EN 62271-202)
– Assembly on site can be reduced to a minimum
– Small number of different types
– Easy to use materials
– Staff is used to install and operate the transformerstation
(less failures)
– Higher availability of spare parts
– Lower acquisition costs because of higher quantities
Possible disadvantages:
– Delivery delays due to overload of production sources
-
MAKO CIGRE 2009 C4-1R 11/12
– Finding contractor who can deliver high quality product within
requested time
In summary there are more advantages of standardisation of
transformer stations although sometimes individual solutions can be
needed to cover special requests. Workers who are responsible for
building such stations have to be trained periodically how to use
the material, how to connect the cables and to install the earthing
system.
To apply EN 62271-202 is an important step to guarantee both
security of persons and supply quality.
Figure 7 Austrian (top) and Macedonian (bottom) type of
prefabricated transformerstation
6 CONCLUSION
On one hand introduction and apply of EN and IEC standards can
help to improve both safety for persons and supply quality.
But on the other hand it is necessary to check what the
introduction of the standards implies for relating parties. Changes
in standardisations and regulations should be prepared carefully
and if necessary implementation should be done step by step.
-
MAKO CIGRE 2009 C4-1R 12/12
Carefully should be considered:
What has to be upgraded, who has to upgrade or improve and who
has to pay for the introduction? What are the costs in detail and
what period is needed for introducing the standards? If it is
necessary transitional periods have to be defined that all
amendments can be done in a good technical and economical way.
7 LITERATURE [1] Deutsche Kommission Elektrotechnik Elektronik
Informationstechnik im DIN und VDE. “Die Kunst
der Normung” DKE Jahresbericht 2008. [2] IEC “IEC 60038 IEC
Standard voltages Edition 6.2” Geneva, 2002-07 [3] CENELEC “EN
50160 Voltage characteristics of electricity supplied by public
distribution systems”
Brussels, 2005 [4] CENELEC “EN 61000-3-3 Electromagnetic
compatibility (EMC) - Part 3-3: Limits - Limitation of
voltage changes, voltage fluctuations and flicker in public
low-voltage supply systems, for equipment with rated current ≤16 A
per phase and not subject to conditional connection” Brussels
[5] CENELEC “EN 61000-3-11 Electromagnetic compatibility (EMC) -
Part 3-11: Limits - Limitation of voltage changes, voltage
fluctuations and flicker in public low-voltage supply systems -
Equipment with rated current ≤ 75 A and subject to conditional
connection” Brussels
[6] CENELEC “EN 61000-3-12 Electromagnetic compatibility (EMC) -
Part 3-12: Limits - Limits for harmonic currents produced by
equipment connected to public low-voltage systems with input
current > 16 A and ≤ 75 A per phase” Brussels
[7] UCTE http://www.ucte.org/resources/publications/ophandbook/
Brussels [8] FGW Fördergesellschaft Windenergie e.V.
http://www.wind-fgw.de/ Kiel [9] E-Control
http://www.e-control.at/de/recht/regulierungsrecht/marktregeln-strom/tor
Vienna [10] CENELEC “HD 637 S1 Power installations exceeding 1 kV
a.c.”, Brussels, 1999 [11] IEC “IEC 61639-1 Power installations
exceeding 1 kV a.c. - Part 1: Common rules” Geneva, 2002-10 [12]
CENELEC “EN 62271-202 High-voltage switchgear and controlgear -
Part 202: High-voltage/low
voltage prefabricated substation”, Brussels, 2006-06
/ColorImageDict > /JPEG2000ColorACSImageDict >
/JPEG2000ColorImageDict > /AntiAliasGrayImages false
/CropGrayImages true /GrayImageMinResolution 300
/GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true
/GrayImageDownsampleType /Bicubic /GrayImageResolution 300
/GrayImageDepth -1 /GrayImageMinDownsampleDepth 2
/GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true
/GrayImageFilter /DCTEncode /AutoFilterGrayImages true
/GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict >
/GrayImageDict > /JPEG2000GrayACSImageDict >
/JPEG2000GrayImageDict > /AntiAliasMonoImages false
/CropMonoImages true /MonoImageMinResolution 1200
/MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true
/MonoImageDownsampleType /Bicubic /MonoImageResolution 1200
/MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000
/EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode
/MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None
] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false
/PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000
0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true
/PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ]
/PDFXOutputIntentProfile () /PDFXOutputConditionIdentifier ()
/PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped
/False
/Description > /Namespace [ (Adobe) (Common) (1.0) ]
/OtherNamespaces [ > /FormElements false /GenerateStructure
false /IncludeBookmarks false /IncludeHyperlinks false
/IncludeInteractive false /IncludeLayers false /IncludeProfiles
false /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe)
(CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector
/DocumentCMYK /PreserveEditing true /UntaggedCMYKHandling
/LeaveUntagged /UntaggedRGBHandling /UseDocumentProfile
/UseDocumentBleed false >> ]>> setdistillerparams>
setpagedevice