Top Banner
© 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP
19

© 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

Dec 17, 2015

Download

Documents

Dorthy Gaines
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

© 2012 Eaton Corporation. All rights reserved.630 A

500 A250 A

NZM-XMC Measuring- and Communication Module

TCDISP

Page 2: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

2 2© 2012 Eaton Corporation. All rights reserved.

Saving Energy - Motivation

Save money

Save taxImprove

Company image

ISO 50001

Logistics

Production

Building

Page 3: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

3 3© 2012 Eaton Corporation. All rights reserved.

ISO 50001 - Standardisation Support for Energy Efficieny

DIN EN ISO 50001:2011-12

Requirements on energy management systemsVerification of processes for energy optimization

Improve

company image

Save taxes and fees

Certificate (DQS)

>10GWh

Energy costs >14% of added value

e.g. Germany:

>1GWh consumption(Erneuerbare-Energiengesetz)

Page 4: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

4 4© 2012 Eaton Corporation. All rights reserved.

Measuring and Analysis is the foundation

EATON provides innovation by new measuring- and logging systems

Process of ISO 50001

Page 5: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

5 5© 2012 Eaton Corporation. All rights reserved.

Innovation by XMC and BreakerVisu

XMC

Measuring System

• Simplifies wiring

Eaton Industries GmbH BreakerVisu Circuit Breaker Logging ProtocolEnergy Logging from File Name: BV_energy_RTU_d_2.2.2012.csvNetwork: Modbus-RTUSample rate: daily

Adr. 1 2 3 4 5Date Time [kWh] [kWh] [kWh] [kWh] [kWh]02.02.2012 00:00:00 4332 69061 42521 122 2232303.02.2012 00:00:00 4370 69061 42722 455 22342

Measuring Innovation

BreakerVisu

Visualisation- and Loggingsystem

• Energydata direct to Excel

Analyses Innovation

Page 6: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

6 6© 2012 Eaton Corporation. All rights reserved.

XMC: The Concept

classic compact

+ all-purpose

- high amount of wiring

+ basic setup

+ easy to install

+ attractive price

Page 7: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

7 7© 2012 Eaton Corporation. All rights reserved.

XMC: The Principal

XMC

Incorporated CTs

Dig S0 output

Voltage access

2 dig. I

2 dig. Q

Remote Control

Modbus

Display

Page 8: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

8 8© 2012 Eaton Corporation. All rights reserved.

Metering Data of MB Version

Data via Modbus and Display accessible:

Phase voltages L-N und L-L Phase currents L1,L2,L3Active power per phase and directionActive power totalReactive energy per phaseReactive energy totalReactive energy capacitive/inductiveApparent power per phaseApparent power totalPower factor (Cos Phi)FrequencyMax. Demand6 configurable alarms

Page 9: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

9 9© 2012 Eaton Corporation. All rights reserved.

Basics on Power

• Active power [Watt]• P=u*i cos phi• Real power (billing)

• Reactive Power [var]• Q=u*i sin phi• Unwanted, unusable power; bouncing between generator

and consumer

• Apparent Power [VA]• S=U*I• Needed for defining wiring and transformer dimension

G M

G M

Page 10: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

10 10© 2012 Eaton Corporation. All rights reserved.

Device versions

-S0 (Standard Version) -MB (Modbus Version)

1 dig S0 Pulse-Outputfor Active Energy

Ideal to incorporate energy data via SmartWireDarwin

2 S0 Pulse-Outputsfor Active Energy

Display interface

Fieldbus interface (Modbus)

Expandable with max 2 cards:

NZM-XMC-1AO 1 analog output

NZM-XMC-2DO-R 2 relais output

NZM-XMC-4DO-R 4 Relais output

NZM-XMC-4DI-4DO 4 dig. input + 4 dig. output

Page 11: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

11 11© 2012 Eaton Corporation. All rights reserved. 1102

.Jul.2009

S0-pulse output

Typical signal according EN 62053-31

requirements

Page 12: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

12 12© 2012 Eaton Corporation. All rights reserved.

The NZM-XMC-TC-MB Module

a new member in the family: NZM-XMC-TC-MB

XMC: Measuring and Communication Module for NZM

Transducer

Page 13: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

13 13© 2012 Eaton Corporation. All rights reserved.

XMC-TC Features and BenefitsFeatures:

• Classical external CTs and voltage wiring

• Current Range 32A to 1600A

• ModbusRTU Interface

• Compatible data set to XMC

• Energy Pulse Output S0

• Alarm output

Benefits:

• Widens the application to entire range of NZM

• Any CTs can be used (Retrofit)

• Extreme narrow installation becomes feasible

• Already supported by actual BreakerVisu

NZM 1 NZM 4NZM 3NZM 2

NZM2-XMC NZM3-XMC

160A 300A 630A 1600A

NZM-XMC-TC

XMC-TC XMC-TC

Page 14: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

14 14© 2012 Eaton Corporation. All rights reserved.

Assortment

TypeOrder Nr

Maximum rating

Maximum Cable qmm

NZM2-XMC-MB-250 156641 250 120NZM2-4-XMC-MB-250 156642 250 120

NZM2-XMC-S0 129839 300 185NZM3-XMC-S0 129960 500 185NZM2-XMC-MB 129961 300 185NZM3-XMC-MB 129962 500 185NZM2-4-XMC-S0 129963 300 185NZM3-4-XMC-S0 129964 500 185NZM2-4-XMC-MB 129965 300 185NZM3-4-XMC-MB 129966 500 185NZM3-XMC-KIT-TCP-630 153140 630 300NZM3-XMC-KIT-630 153141 630 300

NZM-XMC-TC-MB 169832 CT  

NZM-XMC-DISP 129967    

NZM-XMC-AC 129968    

NZM-XMC-USB485 158562    

Page 15: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

15 15© 2012 Eaton Corporation. All rights reserved.

Configuration XMC_Config_Tool

Page 16: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

16 16© 2012 Eaton Corporation. All rights reserved.

02.Jul.2009

Topology for other Networks

Metering BusModbus RTU PROFIBUS-DP

or

PROFINETor Ethernet

M S

M S

Gatewayto PROFINET or PROFIBUS-DP

Scada

PLC

Page 17: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

17 17© 2012 Eaton Corporation. All rights reserved.

• Voltage Measuring• Range: 40...690 V• Error: 0.49% reading + 0.01%FS

• Current Measuring

• Range: 115% ... 1% Ir

• 300A: 350...3A• 630A: 735...6.3A

• Error: 0.49% reading + 0.01% FS• Power / Energy

• Error: 0.99% reading + 0.01% FS

Technical Data

Page 18: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

18 18© 2012 Eaton Corporation. All rights reserved.

Available Sales Tools

Flyer:Capture Energy by Crcuit Breaker Communication SAP:168546 GB

FTP Server:ftp://ftp.moeller.net/CIRCUIT_BREAKER/KOMMUNIKATION/XMC_Measuring/

XMC_Config_tool

Program Samples

Support:Rainer Menden Phone:-492286022334 E-Mail:[email protected]

Daniel Jansen Phone: -492286022260 E-Mail:[email protected]

Page 19: © 2012 Eaton Corporation. All rights reserved. 630 A 500 A 250 A NZM-XMC Measuring- and Communication Module TC DISP.

19 19© 2012 Eaton Corporation. All rights reserved.