© 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power and Interface (Communication) Cables World Trade (WT)
14

© 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

Dec 30, 2015

Download

Documents

Collin Briggs
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

© 2002 Eaton Corporation. All rights reserved.

Cabling a Rackmounted9910-P33 UPS

i5 or p5 with one PDU or two (redundant) PDUs

How to Connect the Power and Interface (Communication) Cables

World Trade (WT)

Page 2: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

2

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Receiving the Rack

UPS will be installed in rack If selected “Rack Install” features in the configurator

Connections that need to be completed Power

• UPS to utility (mains)

• UPS to PDU / Devices

Interface (communications)• UPS to server(s)

Page 3: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

3

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Getting Acquainted with the P33

Location of UPS• Installed at bottom of rack

• Connections make @ rear of rack

What a P33 UPS looks like from the rear

Page 4: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

4

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Line cords & connectors

C13 connector- 10A rated (female)Rack, HD & E PDU outletsMating connector to server used onP33 and PDU Outlets

C14 connector- 10A rated (male)The inlet on most servers & optionsRack jumper cords

C19 connector- 16A rated (female)P33 Outlet

C20 connector- 16A rated (male)P33 inlet and Part of BladeCenter line

cord

Lower number is female. Power flows from female to male.

Page 5: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

5

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

PDU line cord #6656

UPS outputline cord PN

53P1968(1/2 of #9855)

Customersupplied

receptaclevaries

PDU #7188 or#9188

Power Cabling with one PDU & #9855 to 16A Plug

520 or 550 withRedundant Powersupplies #5158 or #7889 being fed

by non-redundantpower source

Server power cablesto one PDU - non- redundant

UPS inputline cord PN

varies

This example showsa server with redundantpower supplies beingpowered by one PDU.Therefore, this installationis classified as non- redundant

POWER CORD TABLEFC Description9866 CEE7 VII Type 189867 SABS 164 Type 229868 CEI 23-16 Type 259871 IEC309 P+N+G 16A Type 469872 SII 32-1971 Type 329874 SAA-AS 3112 Type 549875 IEC 60083-A5 Type 64

Page 6: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

6

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

PDU line cord #6656

UPS outputline cord PN

53P1968(1/2 of #9855)

PDU line cord #1449

PN 21H7693

Customersupplied

receptacleIEC309

P+N+G 32A

PDU #7188 or#9188

Power Cabling with one PDU & #9855 to 32A Plug

520 or 550 withRedundant Powersupplies #5158 or #7889 being fed

by non-redundantpower source

Server power cablesto one PDU - non- redundant

UPS inputline cord PN

53P1969(1/2 of #9855)

This example showsa server with redundantpower supplies beingpowered by one PDU.Therefore, this installationis classified as non- redundant

Page 7: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

7

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

PDU line cord #6656

UPS outputline cord

PN 53P1968(1/2 of #9855)

PDU line cord #1449

PN 21H7693

Customersupplied

receptacleIEC309

P+N+G 32A

PDU #7188 or#9188

Power Cabling with two PDUs

520 or 550 withRedundant Power

supplies #5158 or #7889 being fed by redundant

power sourceUPS inputline cord

PN 53P1969RedundantPDU line

cord #6656

Customersupplied

receptacleIEC309

P+N+G 32A

2nd or redundant PDU

Server power cablesto two redundant PDUs

UPS input line cordshown using 30/32Aplugs as an exampleonly.

Page 8: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

8

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Interface Cabling i5 to P33

520 or 550UPS port

P1-T1

Install i5 UPS Interface

Cable #1827(included with i5)

Install X-Slot Relay Card

#2936

Install UPS to #1827Interface CablePN 05142494

(included with #2936)Follow Relay Card Quick Start Guide directions to set UPS

monitoring functions in i5 OS

Page 9: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

9

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Interface Cabling iSeries to P33

8xx Series UPS port

“J14” or ”UPS”

Install X-Slot Relay Card

#2936

Install UPS Interface CablePN 05142494

(included with #2936)

Follow Relay Card Quick Start Guide directions to set UPS

monitoring functions in OS/400 OS

Page 10: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

10

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Interface Cabling i5 & serial to P33

520, 550 or 570UPS port

P1-T1

Install i5 UPS Interface

Cable #1827(included with

i5)

Install X-Slot Relay / SerialCard #2939

Install UPS to #1827

Interface CablePN 124902074-030

(included with #2939) Follow Relay / Serial Card Quick

Start Guide directions to set UPS monitoring functions in i5 OS and

serial (TTY) server.

Serial (TTY)server

Install UPS to serial Interface

Cable PN 124102022-

003(with #2939)

Install LanSafe Software (contained on CD)

onto server

Page 11: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

11

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Interface - p5 Options

Serial (Non-LPAR) One to three serial

connections possible

LPAR (Logical PARtitions of the p5 Operating System)

Requires a p5 Ethernet connection

Must use #2934 Web/SNMP card

Page 12: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

12

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Interface (Serial) p5

p5 520 or 550 NOTE: Must have 2-port Asynchronous

EIA - 232 PCI Adapter #5723

Install UPS serial Interface CablePN 124102022-002

(contained in P33 AccessoryKit PN 21P7229)

Follow Multi-ServerUser’s Guide to set

UPS monitoring functions

NOTE: Obtain 5200-05 Maintenancepackage (APAR IY66260) for AIX 5.2L V5.2

and the 5300-01 maint. Pkg. For AIX 5.3L V5.3(APAR IY62267) from IBM

Multi-Serial Card shown.Your P33 may have asingle serial port card.

Install LanSafe Software (contained on CD)

onto p5

Page 13: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

13

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Interface for LPARs (Ethernet) p5

p5 520 or 550 NOTE: Must have Ethernet Port

Follow ConnectUPSWeb/SMMP User’s Guide

to set UPS monitoring functions

Install ConnectUPS Web/SNMP Card

#2934

Install EthernetCable - customer

supplied

Install NetWatch Software (contained on CD)onto each LPAR

Page 14: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

14

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Completing Start-Up

You have finished the power and connectivity installation process

Continue with Start-up instructions in User’s Manuals

Questions? Contact: The local IBM office supporting your account Eaton Power Quality Global Services