Thermal Energy Storage TES

Post on 02-Mar-2015

114 Views

Category:

Documents

2 Downloads

Preview:

Click to see full reader

Transcript

THERMAL ENERGY STORAGE TESIce Cell

INTRODUCTION

Thermal energy storage is a method that store thermal energy in energy storage reservoirs for later use

It works by creating ice at night when electricity is usually less costly, and then using the ice to cool the air in buildings during the hotter daytime periods.

Thermal energy storage is practical because the large fusion of heat of water. One metric ton of water, one cubic meter, can store 334 million joules (MJ) or 317,000 BTUs (93kWh or 26.4 ton-hours)

The advantages of thermal energy storage are Commercial electrical rates are lower at night It takes less energy to make ice when the ambient

temperature is cool at night. Source energy (energy from the chiller) is saved.

A smaller, more efficient system can do the job of a much larger unit by running for more hours.

ICE CELL

Ice cell Unit label: ice cell 1 -45 Description: TES tank Make: Dunham Bush Model: Ts 240. Type: tube in tank Capacity rated: 240 Rth ; Norminal 10800 Rth

CHILLER

Chiller Make: Dunham bush Model: WCOX128B-128B Type: horizontal screw Power input (kw) : 1227

HEAT EXCHANGER

Heat exchanger Description: heat exchanger 1 – 4 Make: Alfa Laval Model: MX25-BFG Type: Counter flow Flow rate(usgpm): Hot 2400 & cold 2400 In/out temp(F): hot 13.3c/6.6c & cold 4.4c/6.6c Heat exchanger (Rt): 1283.33

COOLING TOWER

Cooling tower Make: Polacel Type: induce draft cross flow Capacity(Rt): 2500 Water flow: 5000 IGPM Water temp(f): in(97) & out(87) Fan power: [7.5 kw x 8]

TES SYSTEM

OPERATION AND MAINTENANCE

Plan capacity: 3600 Rt equal to 2 chiller Best mode @ discharge: 1 chiller/ 1800 Rt & 1 comp/900 Rt Ice mode @ charging: 1 chiller/ 1250 Rt & 1 comp/625 Rt Ice cell stores capacity: 10800 Rth= 45 tanks 1 tank= 240 Rt. Charging capacity chiller: 1250Rt X 10 hours = 12500 Rth Min ice cell: 10800 Rth Discharge; building load: 3585Rt x 0.8 =2868 Rt

Total cooling demand= 2858 Rt x 10 hours x 0.75 = 21500 Rth [1 day]

Best mode; 1 chiller x 10 hours= 18000 Rt Sport building: 18000+ 10800=28800Rth Total sport building – total building= 28800 - 21500=7290

Rth/ 25%.

Takrif bil : C2 TES Peak time: 09:00 – 21:00 = 0.234 sen Off Peak: 21:00-09:00 = 0.133 sen. M.D [kw] rate = RM 29.00 per kw

MAINTENANCE

Daily inspection Monitor and record chiller operating parameters

in a log sheet. Any discrepancy in the way the chiller behave scan be identified and immediate measures can be taken to prevent unforeseen damage the chiller.

Monthly inspection. Check cooling tower water treatment system Check unit for traces of oil stain and refrigerant

leakage Check glycol concentration Check liquid sight glasses for proper refrigerant

charge Check sump oil level

Check pressure drop across oil filters Check motor bearings and lubricate as necessary Check water flow switch and pump interlock for

functionality Check compressor and refrigerant piping for excessive

vibration Shut unit down, open main disconnect, inspect control

panel, checking for loose wires, burned contacts, signs of overheated wires, etc.

Check and verify the functionality of all safety cutout devices where applicable.

Yearly inspection Perform monthly inspection Carryout a thorough refrigerant leak test Check compressor oil for acidity, moisture content and dissolved

solids. Replace compressor oil as necessary. Do not charge the system with excess oil. Please refer to the specific type of compressor oil as listed on the chiller nameplate or on the housing of the compressor.

Check liquid line sight glass for indication of excessive moisture content and filter drier for excessive pressure drop. Replace filter drier as necessary.

Check alignment of shaft and coupling. Check shaft seal for excessive oil leakage.

top related