Inspection of Fire Protection Measures and Fire Fighting Capability at Nuclear Power Plants
A PUBLICATIONWITHIN THE NUSS PROGRAMME
VWfi INTERNATIONAL ATOMIC ENERGY AGENCY, VIENNA, 1994
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
CATEGORIES IN THE IAEA SAFETY SERIES
A new hierarchical categorization scheme has been introduced, according to which the publications in the IAEA Safety Series are grouped as follows:
Safety Fundamentals (silver cover)
Basic objectives, concepts and principles to ensure safety.
Safety Standards (red cover)
Basic requirem ents which must be satisfied to ensure safety for particular activities o r application areas.
Safety Guides (green cover)
Recom m endations, on the basis o f international experience, relating to the fulfilm ent o f basic requirem ents.
Safety Practices (blue cover)
Practical examples and detailed methods which can be used for the application o f Safety Standards or Safety Guides.
Safety Fundamentals and Safety Standards are issued with the approval o f the IAEA Board o f G overnors; Safety Guides and Safety Practices are issued under the authority o f the D irector General o f the IAEA.
An additional category, Safety Reports (purple cover), com prises independent reports o f expert groups on safety m atters, including the development o f new principles, advanced concepts and m ajor issues and events. These reports are issued under the authority o f the D irector General of the IAEA.
There are other publications o f the IAEA which also contain inform ation im portant to safety, in particular in the Proceedings Series (papers presented at symposia and conferences), the Technical Reports Series (emphasis on technological aspects) and the IAEA -TECDO C Series (inform ation usually in a prelim inary form).
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
INSPECTION OF FIRE PROTECTION MEASURES
AND FIRE FIGHTING CAPABILITY AT NUCLEAR POWER PLANTS
A Safety Practice
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
The following States are Members of the International Atomic Energy Agency:AFGHANISTAN ICELAND PERUALBANIA INDIA PHILIPPINESALGERIA INDONESIA POLANDARGENTINA IRAN, PORTUGALARMENIA ISLAMIC REPUBLIC OF QATARAUSTRALIA IRAQ ROMANIAAUSTRIA IRELAND RUSSIAN FEDERATIONBANGLADESH ISRAEL SAUDI ARABIABELARUS ITALY SENEGALBELGIUM JAMAICA SIERRA LEONEBOLIVIA JAPAN SINGAPOREBRAZIL JORDAN SLOVAKIABULGARIA KAZAKHSTAN SLOVENIACAMBODIA KENYA SOUTH AFRICACAMEROON KOREA, REPUBLIC OF SPAINCANADA KUWAIT SRI LANKACHILE LEBANON SUDANCHINA LIBERIA SWEDENCOLOMBIA LIBYAN ARAB JAMAHIRIYA SWITZERLANDCOSTA RICA LIECHTENSTEIN SYRIAN ARAB REPUBLICCOTE D’IVOIRE LITHUANIA THAILANDCROATIA LUXEMBOURG THE FORMER YUGOSLAVCUBA MADAGASCAR REPUBLIC OF MACEDONCYPRUS MALAYSIA TUNISIACZECH REPUBLIC MALI TURKEYDENMARK MARSHALL ISLANDS UGANDADOMINICAN REPUBLIC MAURITIUS UKRAINEECUADOR MEXICO UNITED ARAB EMIRATESEGYPT MONACO UNITED KINGDOM OFEL SALVADOR MONGOLIA GREAT BRITAIN ANDESTONIA MOROCCO NORTHERN IRELANDETHIOPIA MYANMAR UNITED REPUBLICFINLAND NAMIBIA OF TANZANIAFRANCE NETHERLANDS UNITED STATES OF AMERGABON NEW ZEALAND URUGUAYGERMANY NICARAGUA UZBEKISTANGHANA NIGER VENEZUELAGREECE NIGERIA VIET NAMGUATEMALA NORWAY YUGOSLAVIAHAITI PAKISTAN ZAIREHOLY SEE PANAMA ZAMBIAHUNGARY PARAGUAY ZIMBABWE
The Agency’s Statute was approved on 23 October 1956 by the Conference on the Statute of the IAEA held at United Nations Headquarters, New York; it entered into force on 29 July 1957. The Headquarters of the Agency are situated in Vienna. Its principal objective is “ to accelerate and enlarge the contribution of atomic energy to peace, health and prosperity throughout the world” .
© IAEA, 1994Permission to reproduce or translate the information contained in this publication may be
obtained by writing to the International Atomic Energy Agency, Wagramerstrasse 5, P.O. Box 100, A-1400 Vienna, Austria.
Printed by the IAEA in Austria October 1994
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
SAFETY SERIES No. 50-P-6
INSPECTION OF FIRE PROTECTION MEASURES
AND FIRE FIGHTING CAPABILITY AT NUCLEAR POWER PLANTS
A Safety Practice
INTERNATIONAL ATOMIC ENERGY AGENCY VIENNA, 1994
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
VIC Library Cataloguing in Publication Data
Inspection of fire protection measures and fire fighting capability at nuclear power plants : a safety practice. — Vienna : International Atomic Energy Agency, 1994.
p. ; 24 cm. — (Safety series, ISSN 0074-1892 ; 50-P-6) STI/PUB/967 ISBN 92-0-103994-8 Includes bibliographical references.
1. Nuclear power plants—Fires and fire prevention. I. International Atomic Energy Agency, n . Series.
VICL 94-00101
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FOREWORD
In 1974, the IAEA established a special Nuclear Safety Standards (NUSS) programme under which a number of Codes and Safety Guides have been produced in the areas of governmental organization, siting, design, operation and quality assurance. The NUSS Codes and Guides are a collection of basic and derived requirements for the safety of nuclear power plants with thermal neutron reactors. They have been developed in a complex process which ensures the best possible international consensus.
In order to present further details on the application and interpretation and on the limitations of individual concepts in the NUSS Codes and Safety Guides, a series of Safety Practice publications have been initiated. It is hoped that many Member States will benefit from the experience presented in these books.
The present publication has been developed with the help of experts from regulatory, operating and engineering organizations, all with practical experience in the field of fire protection of nuclear power plants. The publication outlines practices for inspecting the fire protection measures at nuclear power plants in accordance with Safety Series No. 50-SG-D2 (Rev. 1), Fire Protection in Nuclear Power Plants, and includes a comprehensive fire safety inspection checklist of the specific elements to be addressed when evaluating the adequacy and effectiveness of the fire protection measures and manual fire fighting capability available at operating nuclear power plants. The publication will be useful not only to regulators and safety assessors but also to operators and designers.
The book addresses a specialized topic and it is recommended that it be used in conjunction with Safety Guide No. 50-SG-D2 (Rev. 1).
The IAEA is grateful to all the experts who helped in the drafting and reviewing of this publication.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
CONTENTS
1. INTRODUCTION .......................................................................................... 1
1.1. Background .......................................................................................... 11.2. Objective .............................................................................................. 11.3. Scope .................................................................................................... 21.4. Structure .............................................................................................. 2
2. METHODOLOGY ........................................................ ............................... 2
2.1. Document review ............................................................................... 32.2. Personnel interviews .......................................................................... 42.3. Direct observation ............................................................................. 4
3. EVALUATION AND CONCLUSIONS .................................................... 5
4. INSPECTION CHECKLIST ........................................................................ 7
BIBLIOGRAPHY .................................................................................................... 55
CONTRIBUTORS TO DRAFTING AND REVIEW ...................................... 57
LIST OF NUSS PROGRAMME TITLES .......................................................... 59
SELECTION OF IAEA PUBLICATIONS RELATING TO THESAFETY OF NUCLEAR POWER PLANTS .............................................. 63
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
1. INTRODUCTION
1.1. BACKGROUND
Safety Series No. 50-SG-D2 (Rev. 1), Fire Protection in Nuclear Power Plants, was developed as part of the IAEA Nuclear Safety Standards (NUSS) programme. The Guide established the specific concepts of fire protection related to the design, layout and construction of nuclear power plants. The Guide discussed, inter alia, the recommended concepts for designing the fire detection and fire extinguishing systems and for protecting the plant, as well as the associated main requirements for manual fire fighting.
It is recognized that effective fire protection includes a number of distinct elements that must be integrated into a comprehensive fire safety policy. As a minimum, these elements cover organization; a fire prevention programme, including the administrative control procedures; a comprehensive fire hazard analysis; provision for passive fire protection measures; installation of reliable and effective fire detection and extinguishing systems and equipment (including a degree of redundancy, where necessary, to cover the single failure criterion as defined in para. 531 of Safety Series No. 50-SG-D2 (Rev. 1)); periodic inspection, maintenance and testing of all the fire protection measures (both passive and active) provided; a quality assurance programme; and the manual fire fighting capability. To determine the adequacy of the fire protection essential for safety at a nuclear power plant, all these elements must be assessed.
Although comprehensive evaluation of the overall fire safety arrangements requires a thorough review of all the elements listed above, there is value in applying selected elements separately for specific situations. This Safety Practice supplements Safety Guide 50-SG-D2 (Rev. 1) by providing a detailed fire safety inspection checklist to determine whether the requirements for the fire protection measures and fire fighting capability (including manual fire fighting) have been fulfilled in an operating nuclear power plant. The Guide should be used as a primary reference in the application of this Safety Practice.
1.2. OBJECTIVE
The purpose o f this publication is to outline the practices for inspecting the fire protection measures at nuclear power plants in accordance with Safety Series No. 50-SG-D2 (Rev. 1), and includes a comprehensive checklist of the specific elements to be addressed when evaluating the adequacy and effectiveness of the fire protection measures and manual fire fighting capability provided at operating nuclear power plants. The document will be useful not only to regulators and safety assessors but also to operators and designers.
1
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
1.3. SCOPE
This Safety Practice provides a methodology and the basis for inspecting the fire protection measures and manual fire fighting capability at nuclear power plants, and for assessing their adequacy. The fire safety inspection checklist reflects the current international practices for inspecting fire safety and provides an objective structure for assessing three elements of fire protection at nuclear power plants: the passive fire protection measures; the design and installation of fire detection and fixed fire extinguishing systems and equipment; and the manual fire fighting capability. This assessment will determine whether the fire protection measures and manual fire fighting capability provided at the plant are in accordance with internationally acceptable practices.
1.4. STRUCTURE
Section 2 describes the methodology to be followed when applying the checklist, including discussion on the specific written documents to be reviewed, the purpose and value of personal interviews with plant personnel, and the necessity of direct visual observation of plant conditions, with a walkdown inspection of the plant.
Section 3 discusses the basis for evaluating each aspect of plant fire protection as ‘satisfactory’, ‘needs further evaluation’ or ‘unsatisfactory’, and describes the important issues to be considered when making recommendations for their improvement.
Section 4 provides a detailed fire safety inspection checklist for determining the adequacy of the fire protection measures and manual fire fighting capability provided at the plant.
2. METHODOLOGY
It is intended that inspection of the techniques used for fire protection and fire fighting be performed by a small group of professional fire safety specialists with experience directly applicable to fire protection in nuclear power plants. The combined experience of the team of technical specialists should include expertise in fire protection system design, knowledge of the fire protection codes and standards, knowledge of the manual fire fighting techniques and experience in fire protection engineering. Judgements of performance are based on the expertise of the individual technical specialists. Therefore, this inspection is not intended to be a formal audit against a single set of codes and standards, but rather a technical exchange of
2
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
experience and practices at the working level with the aim of improving the reliability and effectiveness of the measures and capability currently provided by the nuclear power plant.
The key objectives of the fire safety inspection are:
(1) To provide the plant with an independent assessment of the effectiveness of the fire protection measures and manual fire fighting capability;
(2) To provide plant management with specific recommendations and suggestions for improvement in areas where performance falls short of internationally acceptable practices;
(3) To provide key personnel at the plant with the opportunity of discussing their experience and practices in fire protection with technical experts who have significant experience in this field.
To be most effective when evaluating the overall fire safety arrangements provided at the plant, the assessment should cover all areas of the site, including the nuclear island and the balance of plant facilities, e.g. the turbine building. However, the primary concern of this publication is the adequacy of the fire protection measures and manual fire fighting capability with respect to the plant systems, equipment and components that are essential for achieving and maintaining safe shutdown of the plant. For the purpose of this Safety Practice, safe shutdown of the plant covers removal of residual heat following initial shutdown and prevention of the release of radioactive materials, as defined in para. 306 of Safety Series No. 50-C-D (Rev. 1), and in para. 202 of Safety Series No. 50-SG-D2 (Rev. 1).
Three primary methods are used to acquire the information needed to assess the effectiveness of the fire protection measures and manual fire fighting capability provided at the plant, and to make specific recommendations for their improvement: a review of written material; interviews with plant personnel; and direct visual observation of the measures and capability.
The fire safety specialists address topics in sufficient detail and to the extent necessary to enable them to make an informed judgement of each item in the checklist. The weaknesses identified are addressed to the degree required to document the specialists’ concerns with sufficient detail and accuracy to make their concerns clearly understandable, and then recommendations are made for addressing these weaknesses. Similarly, the good practices observed during the inspection process are documented for the benefit of other nuclear power plants, and are described in the specialists’ notes in sufficient detail to be readily understood.
2.1. DOCUMENT REVIEW
The specific documents to be reviewed by the technical specialists vary, depending on their availability and on the circumstances at each nuclear power plant.
3
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
It is generally agreed that the documents listed below are important elements of overall plant fire safety. However, the absence of one or more of these review documents should not preclude use of the checklist as an effective tool for assessing the adequacy of the fire protection measures and manual fire fighting capability installed at the plant. The documents to be reviewed include: the fire protection regulatory requirements; the comprehensive fire hazard analysis; the safety evaluation report for fire protection; the fire protection administrative control procedures; the surveillance, maintenance and test procedures for the fire protection systems and equipment; the fire protection system and equipment details and drawings; the fire event records and investigative reports; the training records of on-site and off-site personnel, as applicable; the plant arrangement drawings, including identification of the fire compartment boundaries (as constructed, covering modifications); and the fire emergency plan, including co-ordination with off-site services.
2.2. PERSONNEL INTERVIEWS
Interviews with plant personnel are carried out at all levels with a view to:
(1) Providing additional information not addressed by the documentation;(2) Answering questions and satisfying concerns arising out of the review
documents;(3) Forming a judgement of the plant personnel’s understanding of the fire protec
tion equipment and measures provided, and of their own duties and responsibilities for fire protection;
(4) Forming a judgement of the plant personnel’s competence and professionalism regarding fire protection.
Interviews also provide an opportunity for an exchange of information between technical specialists and plant personnel. These interviews should be seen as part of a constructive dialogue with plant personnel and not as an interrogation. Properly conducted, such interviews play an important role in the inspection process.
2.3. DIRECT OBSERVATION
Site inspection of actual plant conditions is a significant part of the review process. Most of the time allocated to the inspection process should be used to review the fire protection measures and the actual fire fighting capability provided at the plant. Observation of existing conditions includes:
(1) A walkdown inspection of all the relevant plant areas, with emphasis placed on those areas that are important to safe shutdown of the plant, and on any adjacent areas which may form a potential fire hazard to those safety important areas;
4
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
(2) The combustible fire load and the general housekeeping conditions;(3) The control of ignition sources;(4) The adequacy and integrity of the passive fire protection measures (fire rated
barriers, fire doors, fire dampers, fire barrier penetration seals);(5) The design and installation of the fire detection and fire extinguishing systems
and equipment;(6) The maintenance of the active and passive fire protection measures, based on
visual evaluation;(7) The manual fire fighting capability, including witnessing an unannounced fire
drill at the plant.
On the basis of the results obtained from the review documents, personnel interviews and direct observations, the technical specialists form a judgement of the adequacy of the measures and capability provided at the plant, and then make recommendations for correcting those deficiencies that were identified during the inspection. The important areas cover:
(a) The technical knowledge and skills of the manager and staff responsible for the overall fire safety of the plant;
(b) The adequacy of the passive fire protection measures provided;(c) The effectiveness of the fire protection systems and equipment installed at the
plant, to provide the level of protection required (both system design and operability);
(d) The availability and effectiveness of the manual fire fighting personnel (both on-site and off-site).
3. EVALUATION AND CONCLUSIONS
The fire safety inspection checklist provides a means of evaluating the fire protection measures and manual fire fighting capability in place at the nuclear power plant. It is recognized that effective fire protection must include additional elements such as a comprehensive fire hazard analysis; a fire prevention programme, including the administrative control procedures; periodic inspection, maintenance and testing of the systems and equipment; and a quality assurance programme. These elements are to be addressed specifically in two separate documents currently in preparation at the IAEA: Evaluation of Fire Hazard Analysis for Nuclear Power Plants, and Assessment of the Implementation and Effectiveness of the Overall Fire Safety Arrangements of Nuclear Power Plants.
5
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
The checklist for inspecting the fire protection measures and manual fire fighting capability is divided into eight sections:
A. Fire confinement (passive fire protection measures);B. Fire detection and alarm systems;C. Fixed fire extinguishing systems — General;D. Water based fire extinguishing systems;E. Gaseous fire extinguishing systems;F. Foam and dry powder fire extinguishing systems;G. Fire water supply;H. Manual fire fighting capability.
Regarding the safe shutdown requirements (as defined in para. 202 of Safety Series No. 50-SG-D2 (Rev. 1)), each aspect of plant fire protection and the corresponding protection measures, as identified in the checklist, are evaluated. This evaluation leads to one of three conclusions:
(1) Satisfactory, which means that the particular fire protection measure isprovided in accordance with internationally acceptable practices. No enhancements are required. When a particular item is determined to be satisfactory, generally no record of specific comments is required. However, in certain cases it may be desirable to record specific details that form the basis for such a determination. It is also important to identify good practices that may be beneficial to other nuclear power plants.
(2) Needs further evaluation, which means either that the particular fire protection measure does not meet the requirements, or that further details will have to be provided before a definite judgement is made. In both cases, a specific recommendation is made on how to resolve the issue.
(3) Unsatisfactory, which means that the particular fire protection measure is notprovided in accordance with internationally acceptable practices. This couldarise from the use of inadequate material, systems or equipment; the inadequate fire resistance of specific components; an inappropriate design approach, etc. Each statement is accompanied by an explanation of the technical basis for such a determination.
For each item identified in the inspection checklist, the technical specialists identify the ‘objective evidence’ examined in order to determine the category into which the item falls. Examples of appropriate objective evidence are the documents reviewed (reference the specific document numbers), the personnel interviewed (identify the names and responsibilities) and the plant conditions observed (describe the specific locations and details).
Furthermore, specific recommendations are made on how to correct the deficient conditions. Each recommendation is made after giving appropriate consideration to the specific deficiency needing attention, the indirect aspects related to the
6
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
deficiency and the root cause analysis of the basic cause of the deficiency; the results of this analysis may indicate the need for a higher level recommendation.
4. INSPECTION CHECKLIST
The fire safety inspection checklist has been prepared for fire safety inspections of a nuclear power plant by professional fire safety specialists. The methodology and contents of the checklist may also be used by regulatory or specialized third party organizations to conduct fire safety inspections of nuclear power plants. In addition, the checklist may be useful to the management of a nuclear power plant as a listing of the numerous elements that must be evaluated in order to determine the adequacy of the fire protection measures and manual fire fighting capability. The checklist will also provide guidance to a nuclear power plant for conducting a self- assessment of fire safety. However, it should not be used by non-specialists in fire protection, and self-assessment should not be considered a substitute for an independent fire safety inspection.
The checklist is intended for a small group of fire safety specialists specifically qualified by education and practical experience to evaluate the adequacy and effectiveness of the fire protection measures (both passive and active) and manual fire fighting capability provided at the plant. The checklist provides a listing of the fire protection elements to be considered. It is not all inclusive and should not limit the investigations of the fire safety specialists; rather, it should be considered as a minimum listing of items to be included in inspection and assessment.
7
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIRE SAFETY INSPECTION CHECKLIST
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs furtherUnsat.evaluation
A. Fire confinement (passive fire protection measures)
A.I. Fire confinement by compartmentalization (fire containment approach)
A .1.1. Identification of those fire compartments which contain nuclear safe shutdown systems or equipment, or which adjoin or present outside exposure to compartments containing nuclear safe shutdown systems or equipment. Refer to the plant specific fire hazards analysis for identification of those compartment boundaries which require a specific fire resistance rating, and for the technical justification which provides the basis for the absence of a fire rated compartment boundary.
A .1.2. Determination of the fire rating:
(a) Location and use;(b) Fire load in the compartment and in adjacent
compartments.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
Itemidentifier
Inspection item description
AdequacyComments and objective
evidence reviewedSat.
Needs further evaluation
Unsat.
A .1.3. Fixed fire barriers (fire compartment boundaries such as walls, floors; ceiling, electrical and mechanical penetration seals):
(a) Identification of the fixed fire barriers (lists, drawings, etc.);
(b) The fire rating requirements of those components used in the construction of the fire compartment boundaries;
(c) Qualification of the component (original installation and modifications):— The test method used to determine the fire rating
(independent testing laboratory approval or third party certification);
— Extrapolation of the test results to configuration of the actual installation;
— The installation procedure is in accordance with the manufacturer’s instructions;
— Installation is by qualified personnel specifically trained to install such components;
— The fire rating of the components is consistent with that of the fire compartment boundaries;
(d) The integrity of the fixed fire barrier components has not been compromised.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIRE SAFETY INSPECTION CHECKLIST (cont.)
Itemidentifier Inspection item description
AdequacyComments and objective
evidence reviewedSat. Needs further evaluation Unsat.
A. 1.4. Fire barrier closures (fire doors, fire dampers, sewers,drains, smoke vents):
(a) Identification of the fire barrier closures (lists, drawings, etc.);
(b) The fire rating requirements of those components used in the construction of the fire compartment boundaries;
(c) Qualification of the component (original installation and modifications):— The test method used to determine the fire rating
(independent testing laboratory approval or third party certification);
— Extrapolation of the test results to configuration of the actual installation;
— The installation procedure is in accordance with the manufacturer’s instructions;
— Installation is by qualified personnel specifically trained to install such components;
— The fire rating of the components is consistent with that of the associated fire compartment boundaries;
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
Item Inspection item descriptionAdequacy
Comments and objective evidence reviewedidentifier Sat. Needs further
evaluation Unsat.
A.1.4.(cont.)
(d) The integrity and operability of the fire barrier closures have not been compromised and the components are in the normal operating position;
(e) Where applicable, components are arranged to facilitate maintenance and inspection.
A.2. Fire confinement by distance (fire influence approach)
A.2.1. Refer to the plant specific fire hazards analysis for identifier tion of those fire areas where separation by distance is provided (lists, drawings, etc.).
A.2.2. Determination of the fire loads, including the transient combustibles.
A.2.3. The requirements of separation by distance are based on accepted standards or on documented technical justification.
A.2.4. Separation distances are free from combustibles and ignition sources — identify the specific separation distance to be m aintained m.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIRE SAFETY INSPECTION CHECKLIST (cont.)
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs furtherUnsat.
evaluation
A. 3. Locally applied separating elements (fire influence approach)
A.3.1. Identification of the locally applied separating elements, including the permanent separating elements, fire resistant coatings, sleeves and temporary separating elements (lists, drawings, etc.). Refer to the plant specific fire hazards analysis for identification of those areas where locally applied separating elements are provided, and for the technical justification which provides the basis for the use and/or absence of such elements.
A.3.2. Determination of the fire rating:
(a) Location and use;(b) Fire load (geometry and configuration, as well as
quantity).
A.3.3. Qualification of the locally applied separating element (original installation and modifications):
(a) The test method used to determine the fire rating and functionality (independent testing laboratory approval or third party certification);
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
Itemidentifier
Inspection item description
AdequacyComments and objective
evidence reviewedSat.
Needs further evaluation
Unsat.
A.3.3.(cont.)
A.3.4.
(b) Extrapolation of the test results to configuration of the actual installation;
(c) The installation procedure is in accordance with the manufacturer’s instructions;
(d) Installation is by qualified personnel specifically trained to install such elements.
The integrity of the locally applied separating elements has not been compromised.
B.
B .l.
B.1.1.
Fire detection and alarm systems
Fire detector location
In general, all areas throughout the plant should be provided with fire detection equipment. Refer to the plant specific fire hazards analysis for identification of those specific exceptions where technical justifications have been developed for the absence of fire detection equipment.
B.2.
B.2.1.
Fire detection equipment
The categories of detector (or combinations thereof) are appropriate for the hazard(s):
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
F IR E SAFETY IN SPECTIO N C H EC K LIST (cont.)
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
B.2.1.(cont.)
(a) Heat;(b) Smoke;(c) Flame;(d) Gas sampling;(e)' Flammable gas.
B.2.2. Qualification of the fire detection equipment (independent testing laboratory approval or third party certification).
B.3. Fire detection systems
B.3.1. The detection system design and installation standard has been used (name standard).
B.3.2. Detection system design and installation, including primary and secondary power supplies.
B.3.3. The number of detectors provided for each system covers the protected hazard area.
B.3.4. Placing and location of detectors:
(a) Structural or equipment obstructions;(b) Ventilation impact/impairment;
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
B.3.4.(cont)
(c) Distance to ceiling;(d) Distance to the protected hazard area.
B.3.5. Local annunciation is provided (audible, visual). ■
B.3.6. Remote annunciation is provided at a constantly attended location (specify location).
B.3.7. Actuation by fire detection is provided, where appropriate, for:
(a) Fire door closure;(b) Fire damper closure;(c) Fire extinguishing system activation;(d) Equipment interaction/shutdown;(e) Ventilation control.
B.3.8. Special problem cases have been considered for:
(a) Cable routes below raised floor areas;(b) Cable routes above false ceilings;(c) Cable routes within the containment;(d) Areas with high radiation levels.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIR E SAFETY IN SPECTIO N C H EC K LIST (cont.)
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
B.4. Fire alarm systems .
B.4.1. Central panel location is constantly attended (specify location).
B.4.2. Qualification of the alarm system equipment (independent testing laboratory approval or third party certification).
B.4.3. The alarm system design and installation standard has been used (name standard).
B.4.4. Alarm system design and installation, including primary and secondary power supplies.
B.4.5. Sequence of alarms is registered on the central panel.
B.4.6. Fire alarms take precedence over system fault signals.
B.4.7. Local annunciation panels are provided:
(a) Quantity (specify quantities and types);(b) Location (specify locations);(c) All electrical circuits are fully supervised to indicate fault
conditions;(d) Battery backup is provided for each local panel.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation Unsat.
B.4.8. Link to/from the central panel:
(a) Alarm receipt;(b) Manual activation of the fire control installations;(c) Manual activation of the fire pumps for the water supply;(d) Direct from the individual detectors, where provided;(e) To the plant fire brigade from the control room.
B.4.9. Link,to outside organizations.
B.4.10. Manual fire alarm call points:
(a) Quantity provided;(b) Location in hazard areas and in all normal exit paths;(c) Travel distance to the manual fire alarm call points;(d) Direct actions resulting from the manual fire alarm call
points (specify actions);(e) Indirect action via the central alarm receiving facility.
C. Fixed fire extinguishing systems — General
C .l. Fixed fire extinguishing system location and selection
C.1.1. Fixed fire extinguishing systems are installed in all those areas where a significant fire load exists. Refer to the plant
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
F IR E SAFETY IN SPECTIO N C H EC K LIST (cont.)
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
C.1.1.(cont.)
specific fire hazards analysis for identification of those specific exceptions where technical justifications have been developed for the absence of fire extinguishing systems.
C.1.2. The extinguishing medium selected is appropriate for the hazard(s):
(a) Water;(b) Gaseous;(c) Foam;(d) Dry powder.
C.1.3. Appropriate notification of extinguishing system actuation.
D. W ater based fire extinguishing systems
D .L Automatic sprinkler systems (closed heads)
D.1.1. Qualification of the sprinkler system equipment (independent testing laboratory approval or third party certification).
D .l .2. The sprinkler system design and installation standard has been used (name standard).
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
Inspection item description
Adequacy
Sat.Needs further
evaluationUnsat.
Comments and objective evidence reviewed
Type of sprinkler system installed:
(a) Wet pipe;(b) Dry pipe;(c) Pre-action (specify the actuation method).
Sprinkler system design and installation:
(a) Design density and area of application (specify details);(b) Hydraulic calculations (unless pipe schedule);(c) Type of sprinkler heads (specify manufacturer, model
number and other details);(d) Temperature rating of sprinkler heads;(e) Placing and location of sprinkler heads to accommodate
structural and equipment obstructions to discharge the water flow pattern;
(f) Distance from sprinkler heads to ceiling;(g) Spacing of sprinkler heads;(h) Additional sprinklers installed below equipment that
obstructs the water flow pattern;(i) Pipe installation;(j) Dimension of piping;(k) Impact protection for piping, where needed;(1) Pipe supports;(m) As-built drawings are available for review.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIR E SAFETY IN SPECTIO N CH EC K LIST (cont.)
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
D.1.5. Analysis of the extinguishing effects (the effect of extinguishing system actuation and possible adverse consequences have been evaluated).
D.2. Deluge system (open nozzles)
D.2.1. Qualification of the deluge system equipment (independent testing laboratory approval or third party certification).
D.2.2. The deluge system design and installation standard has been used (name standard).
D.2.3. Deluge system design and installation:
(a) Design density and area of application (specify details);(b) Hydraulic calculations (unless pipe schedule);(c) Type of nozzles (specify manufacturer, model number
and other details);(d) Placing and location of nozzles;(e) Coverage of nozzles;(f) Pipe installation;(g) Dimension of piping;(h) Impact protection for piping, where needed;
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
D.2.3.(cont.)
(i) Pipe supports;(j) Simultaneous system operation, where appropriate; (k) Drainage factors;(1) As-built drawings are available for review.
D.2.4. Deluge system actuation method:
(a) Manual (identification and, location of the release devices);
(b) Automatic detection type is suitable for the hazard(s) (specify details).
D.2.5. Detection system design and installation (refer to Section B, Fire detection and alarm systems, for details).
D.2.6. Analysis of the extinguishing effects (effect of system actuation and possible adverse consequences have been evaluated).
E. Gaseous fire extinguishing systems
E l . Carbon dioxide (CO2) systems
E. 1.1. Qualification of the C 02 system equipment (independent testing laboratory approval or third party certification).
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIR E SAFETY IN SPECTIO N C H EC K LIST (cont.)
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
E.1.2. The C 0 2 system design and installation standard has been used (name standard).
E.1.3. Total flooding C 02 system design:
(a) Evacuation interlocks (time delays allowed for evacuation);
(b) Pre-fire warning alarm arrangement (visual, audible);(c) System interlocks to ensure closed compartment:
— Fire damper closure;— Ventilation system shutdown;— Fire door closure;— Other;
(d) System calculation method;(e) Initial design concentration;(f) Design concentration is maintained for minimum duration;(g) Availability of a secondary C 02 gas supply.
E.1.4. C 02 system actuation method:
(a) Manual (identification and location of the release devices);(b) Automatic detection type is suitable for the hazard(s)
(specify details).
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
E.1.5. Detection system design and installation (refer to Section B, Fire detection and alarm systems, for details).
E.1.6. Local application C 02 system design:
(a) Buildup of C 02 concentration (discharge rate);(b) Means of system actuation (provide details).
E.1.7. The consequences of system actuation have been evaluated:
(a) Thermal shock potential;(b) Effect on personnel;(c) Overpressurization (for closed compartments).
E.2. Halon systems
E.2.1. Type of halon gas used (1301, 1211, etc.).
E.2.2. Qualification of the halon system equipment (independent testing laboratory approval or third party certification).
E.2.3. The halon system design and installation standard has been used (name standard).
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIR E SAFETY IN SPECTIO N C H EC K LIST (cont.)
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs furtherUnsat.
evaluation
E.2.4. Total flooding halon system design:
(a) Evacuation interlocks (time delays allowed for evacuation);
(b) Pre-fire warning alarm arrangement (visual, audible);(c) System interlocks to ensure closed compartment:
— Fire damper closure;— Ventilation system shutdown;— Fire door closure;— Other;
(d) System calculation method;(e) Initial design concentration;(f) Design concentration is maintained for minimum
duration;(g) Availability of a secondary halon gas supply.
E.2.5. Halon system actuation method:
(a) Manual (identification and location of the release devices);
(b) Automatic detection type is suitable for the hazard(s) (specify details);
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation Unsat.
E.2.5.(cont.)
(c) Abort switch, if installed, is of the ‘dead man’ type and is located inside the protected compartment (a dead man type switch is one that requires constant pressure on a spring loaded switch to maintain the abort function; when the pressure is released, the system reverts to the normal operational sequence).
E.2.6. Detection system design and installation (refer to Section B, Fire detection and alarm systems, for details).
E.2.7. Local application halon system design:
(a) Buildup of gas concentration (discharge rate);(b) Means of system actuation (provide details).
E.2.8. The consequences of system actuation have been evaluated:
(a) Effect on personnel;(b) Corrosion potential from decomposition by-products.
E.3. Other gas extinguishing systems
E.3.1. Type of gas(es) used.
E.3.2. Qualification of the gas system equipment (independent testing laboratory approval or third party certification).
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIR E SAFETY IN SPECTIO N C H EC K LIST (cont.)
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
E.3.3. The gas system design and installation standard has been used (name standard).
E.3.4. Total flooding gas system design:
(a) Evacuation interlocks (time delays allowed for evacuation);
(b) Pre-fire warning alarm arrangement (visual, audible);(c) System interlocks to ensure closed compartment:
— Fire damper closure;— Ventilation system shutdown;— Fire door closure;— Other;
(d) System calculation method;(e) Initial design concentration;(f) Design concentration is maintained for minimum duration;(g) Availability of a secondary gas supply.
E.3.5. Gas system actuation method:
(a) Manual (identification and location of the release devices);(b) Automatic detection type is suitable for the hazard(s)
(specify details).
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
Item Inspection item description
AdequacyComments and objective
identifier Sat.Needs further
evaluationUnsat.
evidence reviewed
E.3.6. Detection system design and installation (refer to Section B, Fire detection and alarm systems, for details).
E.3.7. Local application gas system design:
(a) Buildup of gas concentration (discharge rate);(b) Means of system actuation (provide details).
E.3.8. The consequences of gas system actuation have been evaluated:
(a) Thermal shock potential;(b) Effect on personnel;(c) Overpressurization (for closed compartments);(d) Corrosion potential from decomposition by-products.
F. Foam and dry powder fire extinguishing systems
F .l. Foam systems
F.1.1. The foam concentrate type (protein based, synthetic, aqueous film forming foam (AFFF), film forming fluoroprotein, alcohol resistant, etc.).
F.1.2. The foam expansion ratio (specify low, medium or high).
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FERE SAFETY IN SPECTIO N C H EC K LIST (cont.)
Itemidentifier
Inspection item description
F .l .3. Qualification of the foam system equipment (independenttesting laboratory approval or third party certification).
F .l .4. The foam system design and installation standard has beenused (name standard).
F .l .5. The post-discharge cleanup and corrosion plan.
F.1.6. Foam system design and installation:
(a) Type of system (balanced pressure, pumped proportioning, etc.);
(b) Type of foam nozzles (aeration type nozzles or sprinkler head, if AFFF);
(c) Placing and location of discharge heads/nozzles to accommodate structural and equipment obstructions;
(d) Spacing of heads/nozzles;(e) Heads/nozzles installed below equipment that obstructs
the discharge pattern;(f) Area of coverage and application rate are suitable for the
hazard(s) (specify details);(g) Hydraulic calculations (unless pipe schedule);
AdequacyComments and objective
evidence reviewedSat.
Needs further evaluation
Unsat.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation Unsat.
F.1.6.(cont.)
(h) Pipe installation;(i) Dimension of piping;(j) Impact protection for piping, where needed; (k) Pipe supports;(1) As-built drawings are available for review.
F.1.7. The quantity and quality of the foam concentrate are sufficient for the minimum duration required:
(a) Penetration;(b) Accessibility;(c.) Q uan tity o f foam m n r e n t r a t f availahlp. I.;
(d) Available foam concentrate is sufficient for the required duration;
(e) Shelf-life (periodic foam quality test records are available, where appropriate).
F.1.8. Protection of the closed compartment (high expansion foam systems):
(a) Quantity of input points;(b) Time required to flood compartment;(c) Time delays and alarms are provided for personnel
evacuation.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIR E SAFETY IN SPECTIO N C H EC K LIST (cont.)
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
F .l .9. Foam system actuation method:
(a) Manual (identification and location of the release devices);
(b) Automatic detection type is suitable for the hazard(s) (specify details).
F . l .10. Detection system design and installation (refer to Section B, Fire detection and alarm systems, for details).
F . l . 11. Water supply for foam system:
(a) Source reliability and adequacy of capacity;(b) Hydraulically proven (pressure, flow and application
rates);(c) Impact protection for supply piping, where needed.
F . l . 12. Analysis of the extinguishing effects (the effect of foam system actuation and possible adverse consequences have been evaluated).
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
ItemInspection item description
AdequacyComments and objective
identifierSat.
Needs further evaluation
Unsat.evidence reviewed
F.2. Dry powder systems
F.2.1. Dry powder type (specify type, manufacturer and chemical composition).
F.2.2. Qualification of the dry powder system equipment (independent testing laboratory approval or third party certification).
F.2.3. The dry powder system design and installation standard has been used (name standard).
F.2.4. The post-discharge cleanup and corrosion plan.
F.2.5. Open space protection:
(a) Penetration;(b) Accessibility;(c) Impact of wind/environmental factors.
F.2.6. Protection of the closed compartment:
(a) Access points;(b) Compartment area is occupied by personnel;(c) Time delay is provided for personnel evacuation;(d) Pre-fire warning alarm arrangement (audible, visual).
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIR E SAFETY IN SPECTIO N C H EC K LIST (cont.)
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
¥ .2 .1 . Propellant (specify C 02, nitrogen, etc.).
F.2.8. Placing and location of discharge nozzles.
F.2.9. Area of protection is suitable for the hazard(s).
F.2.10. Pipe installation:
(a) Dimension of piping;(b) Pipe supports.
F .2.11. Dry powder system actuation method:
(a) Manual (identification and location of the release devices);
(b) Automatic detection type is suitable for the hazard(s) (specify details).
F.2.12. Detection system design and installation (refer to Section B, Fire detection and alarm systems, for details).
F.2.13. Analysis of the extinguishing effects (the effect of dry powder system actuation and possible adverse consequences have been evaluated).
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation Unsat.
G. Fire water supply
G .l. Water source
G.1.1. Water supply is adequate for the fire load and available at the appropriate flow rate for fire fighting.
G.1.2. Type of water supply:
(a) Potable;(b) Untreated;(c) Brackish;(d) Deionized;(e) Sea.
G.1.3. Water storage tanks (on-site, off-site):
(a) Capacity (each tank) m3; fh'l F.levation above plant grade. m;(c\ Fill rate. m3/h;W) Distance from area to be protected m;(e) Method used to prevent freezing;(f) Method for ensuring an adequate fire water supply, where
combined usage is allowed;(g) Method used to ensure that the minimum water level is
maintained (gauging, low level alarms, etc.).
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
F IR E SAFETY IN SPECTIO N C H EC K LIST (cont.)
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
G.1.4. Open water source:
(a) River;(b) Lake;(c) Sea;(d) Source is protected from freezing.
G.1.5. Subsurface water source:
(a l We.ll (specify dep th m l;
fh) S ustained p u m p in g capac ity ( m 3/h );
(c) Minimum duration that such a capacity is available ( h).
G.2. Supply and distribution pipe
G.2.1. The supply pipe design and installation standard has been used (name standard).
G.2.2. Supply and distribution piping system installation:
(a) Pipe material (specify type);(b) Lining material for ferrous pipe (specify type);(c) Pipe joining method (specify);(d) Pipework, supports or brackets.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
G.2.3. Protection of the supply and distribution piping system:
(a) Against freeze-up;(b) Against mechanical damage;(c) Against ground movement;(d) Cathodic protection.
G.3. Ring main
G.3.1. Reliability of the piping arrangement (ageing, corrosion, tuberculation, looped mains, spur mains, isolation valves, etc.).
G.3.2. The ring main piping design and installation standard has been used (name standard).
G.3.3. Diameter nf the ring main piping mm.
G.3.4. Ring main piping system installation:
(a) Pipe material (specify type);(b) Lining material used for ferrous pipe (specify type);(c) Pipe joining method (specify).
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIR E SAFETY IN SPECTIO N CH EC K LIST (cont.)
Itemidentifier
Inspection item description
Adequacy
Sat.Needs further
evaluationUnsat.
Comments and objective evidence reviewed
G.3.5. Maximum design flow rate (including fixed system demandand hose stream allocation)________ L/min.
G.3.6. Water supply allocation for manual hose stream use________ L/min.
G.3.7. Water supply allocation for water based fixed fireextinguishing systems:
(a) Individual system allocation:
System description Flow rate(L/min)
(b) Branching-off points are hydraulically balanced;(c) Allocation to non-fire process water systems, if
a n y ________ L/min.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation Unsat.
G.3.8. Isolation valves:
(a) Location and spacing of valves;(b) Positive valve position indication is provided;(c) Valves are supervised (visual, electrical).
G.4. Fire pumps
G.4.1. Qualification of the fire pump system equipment (independent testing laboratory approval or third party certification).
G.4.2. The fire pump design and installation standard has been used (name standard).
G.4.3. The number of fire pumps.
G.4.4. The single failure criterion is applied.
G.4.5. Location and arrangement of fire pumps:
(a) Separate the fire compartment provided for each pump;
(b) Common area for all the pumps;(c) Pumps exposed to other fire hazards.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIR E SAFETY INSPECTION CH EC K LIST (cont.)
Item Inspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
G.4.6. Flow and pressure rating of each fire pump:
I./min at bar;
T./min at bar
G.4.7. The maximum available pressure from each fire pump:
(a) Compatible with the installed piping;(b) Compatible with the off-site water supplies.
G.4.8. The pump startup and stop method for each pump:
(a) Automatic (give details);(b) Supervised for power failure and pump running;(c) Manual stop.
G.4.9. The pump driver is appropriate for the intended use:
(a) Diesel engine (specify manufacturer, model number, power rating, etc.);
(b) Electric motor (specify power rating and motor type);(c) Reliability of the electric motor power supply.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
Itemidentifier
Inspection item description
AdequacyComments and objective
evidence reviewedSat.
Needs further evaluation
Unsat.
G.4.10. The fire pump control is appropriate for the intended use:
(a) Type (specify);(b) Location;(c) Qualification of equipment;(d) Battery backup is provided.
G.5.
G.5.1.
G.5.2.
Pressure maintenance pumps (jockey pumps)
The number and location of pumps.
The flow and pressure rating of each pump:
r./min at har;
T./min at har
G.6.
G.6.1.
G.6.2.
G.6.3.
Pressure tanks
The number and individual capacity of tanks:
m .
Operating pressure har
Air supply (compressor, plant air, etc.).
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIR E SAFETY IN SPECTIO N CH EC K LIST (cont.)
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifier Sat.Needs further
evaluationUnsat.
G.6.4. Water supply (give details).
G.7. Outdoor hydrants
G.7.1. The number of hydrants.
G.7.2. The sparing between Hydrants m.
G.7.3. Accessibility for fire brigade use and hose connection compatibility.
G.7.4. Type of hydrant installed:
(a) Ground hydrant (below grade);(b) Pillar hydrant (above grade);(c) Number of outlets for hose connections; (H) Outlet diameter mm;(e) Connected to wet or dry supply systems.
G.7.5. Isolation valve is provided in each hydrant branch.
G.7.6. Impact protection is provided around each pillar hydrant and all the ground hydrants are indicated clearly.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
Adequacy
Sat.Needs further
evaluationUnsat.
Comments and objective evidence reviewed
Inspection item description
Indoor water supply installations
Rising mains:
(a) Wet or dry type;(b) Number;(c) Dimension________ mm;(d) Location and accessibility.
Hose reels/stations for fire fighting:
(a) Number;(b) Location and accessibility;(c) Design flow ra te ________ L/min;(d) Nozzle diam eter____ mm;(e) Nozzle type (fog, straight stream);(f) Shut-off nozzle;(g) Hose type (cotton, synthetic);(h) Hose length________ m;(i) Hose reel or hose station type;(j) Control valve operation for charging the unit.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIR E SAFETY IN SPECTIO N CH EC K LIST (cont.)
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
H. Manual fire fighting capability
H .l. Organization
H.1.1. Establishment of an immediate action fire fighting team, where available.
H.1.2. Composition of the plant fire brigade (on-site personnel):
(a) Brigade leader;(b) Operations personnel;(c) Health physics personnel;(d) Maintenance personnel;(e) Security personnel.
H.1.3. Composition of the off-site fire brigade:
(a) Full time fire fighters;(b) Volunteer fire fighters.
H.1.4. Co-ordination of efforts (on-site, off-site):
(a) Line of authority at fire scene — a written agreement is provided and a liaison officer to the off-site fire brigade is identified;
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
Itemidentifier
Inspection item description
AdequacyComments and objective
evidence reviewedSat.
Needs further evaluation
Unsat.
H.1.4.(cont.)
H.1.5.
(b) Responsibilities of the on-site and off-site brigades are formally established;
(c) Availability/accessibility of radiation monitoring;(d) Dosimeters and access control badges are provided;(e) Means by which the off-site brigades gain access to the
site and the rendezvous points are established;(0 Site access is formally verified by practice drills.
Off-site brigade:
(a) Definite availability for response to plant emergencies:— Adequate reinforcements are available to meet the
radiation levels expected to be encountered;(b) Estimated response time (time to respond to the plant
entrance, to the access plant security and to reach the fire location with the appropriate equipment):— First attendance. min;— Reinforcements min.
H.2.
H.2.1.
Manpower
On-site response:
(a) Immediate action of the fire fighting team (minimum nnmher nf personnel available for response
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIR E SAFETY IN SPECTIO N C H EC K LIST (cont.)
Itemidentifier
Inspection item description
AdequacyComments and objective
evidence reviewedSat.
Needs further evaluation
Unsat.
H.2.1.(cont.)
H.2.2.
(b) Plant fire brigade (minimum number of personnelavailable for response );
(c) Minimum number of trained personnel to be available at all times is adequate for the type of installation.
Off-site response:
(a) Degree of confidence in the minimum adequate response of trained personnel;
(b) Absolute minimum number of personnel who will respond to the plant fire:— day— night
H.3.
H.3.1.
Training programme
Overall training programme — on-site personnel and off-site fire brigade:
(a) Training programme;(b) Formal lesson plans are developed and used;(c) Adequate training aids and resources are available
(reference books, films, videos).
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
H.3.2. Training programme covers all the necessary topics:
(a) Basic nuclear training;(b) Identification of fire hazard;(c) Familiarization of plant;(d) Identification and familiarity with the installed fire
protection equipment;(e) Type of fires expected in nuclear power plants and the
proper method of fighting each type of fire;(f) Proper use of personal protective clothing, including a
self-contained breathing apparatus and the compatible breathing apparatus procedures (on-site personnel and off-site fire brigade);
(g) Use of communication, lighting and ventilation equipment;(h) Methods of fighting fires inside buildings and confined
spaces with limited visibility;(i) Review of detailed pre-fire fighting strategies;(j) Radiological protection — plant procedures and individual
dosimeters.
H.3.3. Classroom training sessions include:
(a) Basic fire training;(b) Regular contingency training;
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIR E SAFETY IN SPECTIO N C H EC K LIST (cont.)
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
H.3.3.(cont.)
(c) Development fire training;(d) Leadership for strategy, tactics and command.
H.3.4. Regular hot fire practice (hands on) training, including fire fighting in confined spaces under extreme conditions of heat/smoke.
H.3.5. All members receive both initial classroom and hot fire practice (hands on) training before assignment to the fire brigade.
H.4. Fire drill practice sessions
H.4.1. Frequent drills are conducted to ensure competency:
(a) Individual fire brigade members (on-site and off-site);(b) Fire brigade as a team.
H.4.2. Drills are performed on night shifts and are occasionally unannounced.
H.4.3. Each fire drill is pre-planned and a thorough critique made by the fire brigade members (and qualified observers, where applicable).
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
H.4.4. Fire drills are conducted in all areas of the plant, including those areas that contain safe shutdown related equipment.
H.4.5. Off-site response groups periodically participate in plant fire drills and receive tours of the plant for familiarity.
H.4.6. All training efforts are documented thoroughly for each fire brigade member, with the detailed records retained and fully accessible.
H.5. Pre-fire fighting strategies
H.5.1. Detailed pre-fire fighting strategies are developed for all plant areas but, in particular, for those areas that contain the equipment needed for safe shutdown of the plant (including those areas which could expose safe shutdown equipment).
H.5.2. Strategies are documented formally and kept up to date.
H.5.3. Strategies are used in routine fire drills and classroom training sessions.
H.5.4. A copy of the strategies is given to the off-site fire brigade response team.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIR E SAFETY IN SPECTIO N CH EC K LIST (cont.)
Itemidentifier
Inspection item description
H.5.5. A copy of the strategies is available to the on-site fire brigadeleader and control room personnel, and is accessible during fire emergencies.
H.5.6. Strategies include all the appropriate information on firefighting techniques, including the following, as a minimum:
(a) Diagram of the area;(b) List of the fire hazards and explosion risks;(c) Description of the fire protection measures provided;(d) Access routes, escape routes;(e) Details of the vital plant equipment needed for safe
shutdown;(f) Special equipment needed for fire fighting and personal
protection;(g) Radiological/toxic concerns;(h) Ventilation system operation;(i) Special considerations;(j) Water supplies.
AdequacyComments and objective
evidence reviewedSat.Needs further
evaluationUnsat.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
H.6. Fire fighting equipment and resources
H.6.1. A full set of protective clothing is available for all the fire brigade members.
H.6.2. Protective clothing includes, as a minimum, coat, trousers, gloves, boots and helmet; the clothing gives protection in flashover conditions and, where necessary, protects against radiological contamination.
H.6.3. Protective clothing is available in the required sizes for each brigade member.
H.6.4. A self-contained breathing apparatus is available for each brigade member likely to be involved in the fire fighting operations.
H.6.5. Spare air bottles are available (at least two for each self- contained breathing apparatus set).
H.6.6. Radiation monitoring equipment is available, including personal dosimeters.
H.6.7. Fire brigades are equipped for fire fighting with a hose, nozzles, ladders, lighting equipment, lines and pumps.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIR E SAFETY IN SPECTIO N CH EC K LIST (cont.)
Item Inspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
H.6.8. Adequate portable radios compatible for use in areas containing safe shutdown equipment are provided for fire brigade communications.
H.6.9. Use of radio frequencies by other plant groups avoids impact on fire brigade operations.
H.6.10. The portable radio communication system is designed to provide communication throughout all the plant areas — even in remote areas (dead spots).
H.6.11. The portable radio sets provided for plant fire brigade use can communicate with the control room, with links to the off-site fire brigade response team.
H.6.12. The on-site fire brigade equipment is located in a well controlled, accessible central plant location (specify
. location).
H.6.13. All the fire brigade equipment is checked regularly and is well maintained.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
H.7.
H.7.1.
Fire extinguishers (mobile and portable)
The type and number of extinguishers used throughout the plant (i.e. water, C 0 2, halon, foam and dry powder) are adequate and are well sited, tested and maintained.
H.7.2. The extinguisher type selected is appropriate for the protected fire hazard areas in the plant.
H.7.3. Qualification of the extinguisher equipment (independent testing laboratory approval or third party certification).
H.8. Access to fire fighting equipment
H.8.1. Equipment locations are marked clearly.
H.8.2. Escape routes are identified through:
(a) Signposting;(b) Orientation;(c) Plans and instructions.
H.8.3. Where ventilation systems are provided for use by the fire brigade for smoke and heat removal, the operational method is identified clearly and such systems are tested and maintained regularly.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIR E SAFETY IN SPECTIO N C H EC K LIST (cont.)
ItemInspection item description
AdequacyComments and objective
evidence reviewedidentifierSat.
Needs further evaluation
Unsat.
H.9. Fire incident records
H.9.1. Records for all the fire incidents at the plant (large, small, actual fires and false alarms) are retained and easily accessible.
H.9.2. Incident records verify adequate response by the fire brigade services.
H.9.3.
H.9.4.
Records include the cause of fire, the method of extinction, the damage to plant and equipment and the effect on safe shutdown equipment.
The response times recorded include the times for immediate action fire fighting teams, on-site plant fire brigade response and off-site fire brigade response.
H.10.
H.10.1.
An unannounced fire drill is conducted during inspection
Fire drill location in plant.
H.10.2. Fire drill scenario (describe scenario).
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
Itemidentifier
Inspection item description
H.10.3. On-site fire brigade:
(a) The fire brigade response tim e________ min(time required to achieve a minimum staffing level at the fire scene, with full protective clothing and a self- contained breathing apparatus, as well as hose line(s) ready to attack the simulated fire);
(b) The number of on-site fire brigade membersresponding________ ;
(c) The brigade members are familiar with the protective clothing, fire fighting equipment, self-contained breathing apparatus and communications equipment;
(d) The brigade members are familiar with the plant areas, the safe shutdown equipment and the nuclear hazards;
(e) The fire brigade leader demonstrates good leadership skills, strategy and tactics, effective communications, knowledge of plant operation and nuclear considerations, and effective operation and use of the available fire protection systems and equipment.
Off-site fire brigade (if called):
(a) Call out arrangements;(b) Time to respond to plant entrance (________ min);
Adequacy
Sat.Needs further
evaluationUnsat.
Comments and objective evidence reviewed
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
FIR E SAFETY IN SPECTIO N C H EC K LIST (cont.)
Itemidentifier
Inspection item description
AdequacyComments and objective
evidence reviewedSat.
Needs further evaluation
Unsat.
H.10.4.(cont.)
H.10.5.
(c) Time to access the plant security and to reach the fire drill location with the appropriate equipment( additional mini;
(d) The number of off-site fire brigade members responding;(e) The brigade members are familiar with the protective
clothing, fire fighting equipment and self-contained breathing apparatus, and the communications equipment is compatible;
(f) The brigade members are familiar with the plant areas, the safe shutdown equipment and the nuclear hazards.
Co-ordination between on-site and off-site brigades during thedrill:
(a) Effective liaison is provided between the groups;(b) A definite line of authority is established and accepted by
each group;(c) Effective utilization of the available resources;(d) Compatibility of equipment and procedures;(e) Co-operation with the liaison engineers.
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
BIBLIOGRAPHY
INTERNATIONAL ATOMIC ENERGY AGENCY, Code on the Safety of Nuclear Power Plants: Design, Safety Series No. 50-C-D (Rev. 1), IAEA, Vienna (1988).
INTERNATIONAL ATOMIC ENERGY AGENCY, Fire Protection in Nuclear Power Plants, Safety Series No. 50-SG-D2 (Rev. 1), IAEA, Vienna (1992).
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION, Fire Protection — Vocabulary, Part 1: General Terms and Phenomena of Fire, ISO 8421-1, ISO, Geneva (1987).
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION, Fire Protection — Vocabulary, Part 2: Structural Fire Protection, ISO 8421-2, ISO, Geneva (1987).
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION, Fire Protection - Vocabulary, Part 3: Fire Detection and Alarm, ISO 8421-3, ISO, Geneva (1989).
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION, Fire Protection — Vocabulary, Part 4: Fire Extinction Equipment, ISO 8421-4, ISO, Geneva (1990).
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION, Fire Protection — Vocabulary, Part 5: Smoke Control, ISO 8421-5, ISO, Geneva (1988).
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION, Fire Protection - Vocabulary, Part 6: Evacuation and Means of Escape, ISO 8421-6, ISO, Geneva (1987).
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION, Fire Protection — Vocabulary, Part 7: Explosion Detection and Suppression Means, ISO 8421-7, ISO, Geneva (1987).
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION, Fire Protection — Vocabulary, Part 8: Terms Specific to Fire Fighting, Rescue Services and Handling Hazardous Materials, ISO 8421-8, ISO, Geneva (1990).
NATIONAL FIRE PROTECTION ASSOCIATION, Standards for Fire Protection for Light Water Nuclear Power Plants, NFPA Standards No. 803, NFPA, Quincy, MA (1988).
NATIONAL NUCLEAR RISKS INSURANCE POOLS AND ASSOCIATIONS, International Guidelines for the Fire Protection of Nuclear Power Plants, Revised edition, NNRIPA, Zurich (1983).
UNITED STATES NUCLEAR REGULATORY COMMISSION, Branch Technical Position on Fire Protection, BTP-CMEB 9.5.1, Standard Review Plan, Rep. NUREG-0800, NRC, Washington, DC (1981).
55
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
UNITED STATES NUCLEAR REGULATORY COMMISSION, Fire Protection Guidelines for Nuclear Power Plants, Revision 1, Regulatory Guide 1.120, NRC, Washington, DC (1977).
UNITED STATES NUCLEAR REGULATORY COMMISSION, Fire Protection Program for Nuclear Power Facilities Operating Prior to January, 1979, Code of Federal Regulations Title 10, Part 50, Appendix R, NRC, Washington, DC (1993).
56
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
CONTRIBUTORS TO DRAFTING AND REVIEW
Agapov, A.
Cottaz, M.
Derewnicki, K.P.
Dhobley, R.R.
Enzmann, H.F.
Gorza, E.
Hashimi, J.A.
Hogg, A.B.C.
Kabanov, L.
Kaercher, M.
Kelemen, I.
Magnusson, T.I.
Marttila, J.J.
Mowrer, D.S.
Notley, D.P.
Pilette, C.
Smith, F.M.
Spencer, D.
Svensson, S.
Minatom, Russian Federation
Institut de protection et de surete nucleaire, France
AEA Technology, United Kingdom
Bhabha Atomic Research Centre, India
Swiss Pool for the Insurance of Nuclear Risks, Switzerland
Tractebel S.A., Belgium
Permanent Mission of Pakistan to the IAEA, Austria
Nuclear Electric, United Kingdom
International Atomic Energy Agency
Electricity de France, France
ETV-Eroterv Rt, Hungary
Vattenfall AB, Ringhals Nuclear Power Plant, Sweden
Finnish Centre for Radiation and Nuclear Safety, Finland
HSB Professional Loss Control, Inc.,United States of America
Science Applications International Corporation, United States of America
Atomic Energy Control Board, Canada
AEA Technology, United Kingdom
Home Office, United Kingdom
Swedish Rescue Services Board, Sweden
57
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
Vandewalle, A.
van Dijk, W.J.M.
Zhang, L.
Zhong, W.
AIB-Vincotte Nuclear, Belgium
Ministerie van Binnenlandse Zaken, Netherlands
Permanent Mission of China to the IAEA, Austria
International Atomic Energy Agency
Technical Committee Meeting
Vienna, Austria: 8-12 March 1993
Consultants Meetings
Vienna Austria: 11-15 May 1992, 8-12 March 1993, 14-18 February 1994
58
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
LIST OF NUSS PROGRAMME TITLES
It should be noted that some books in the series may be revised in the near future.
Those that have already been revised are indicated by the addition o f ‘(Rev. 1 ) ’ to the number.
1. GOVERNMENTAL ORGANIZATION
50-C-G (Rev. 1) Code on the safety of nuclear power plants: Governmental organization
Safety Guides
Qualifications and training of staff of the regulatory body for nuclear power plants
Information to be submitted in support of licensing applications for nuclear power plants
Conduct of regulatory review and assessment during the licensing process for nuclear power plants
Inspection and enforcement by the regulatory body for nuclear power plants
Preparedness of public authorities for emergencies at nuclear power plants
Licences for nuclear power plants: Content, format and legal considerations
Regulations and guides for nuclear power plants
50-SG-G1
50-SG-G2
50-SG-G3
50-SG-G4
50-SG-G6
50-SG-G8
50-SG-G9
2. SITING
50-C-S (Rev. 1) Code on the safety of nuclear power plants: Siting
Safety Guides
50-SG-S1 (Rev. 1) Earthquakes and associated topics in relation to nuclearpower plant siting
50-SG-S3 Atmospheric dispersion in nuclear power plant siting
50-SG-S4 Site selection and evaluation for nuclear power plantswith respect to population distribution
1988
1979
1979
1980
1980
1982
1982
1984
1988
1991
1980
1980
59
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
50-SG-S6
50-SG-S7
50-SG-S8
50-SG-S9
50-SG-S10A
50-SG-S10B
50-SG-S11A
50-SG-S11B
3. DESIGN
50-C-D (Rev. 1)
50-SG-D1
50-SG-D2 (Rev. 1)
50-SG-D3
50-SG-D4
50-SG-D5
50-SG-D6
50-SG-D7 (Rev. 1)
50-SG-D8
50-SG-S5
50-SG-D9
60
External man-induced events in relation to nuclear power plant siting
Hydrological dispersion of radioactive material in relation to nuclear power plant siting
Nuclear power plant siting: Hydrogeological aspects
Safety aspects of the foundations of nuclear power plants
Site survey for nuclear power plants
Design basis flood for nuclear power plants on river sites
Design basis flood for nuclear power plants on coastal sites
Extreme meteorological events in nuclear power plant siting, excluding tropical cyclones
Design basis tropical cyclone for nuclear power plants
Code on the safety of nuclear power plants: Design
Safety Guides
Safety functions and component classification for BWR, PWR and PTR
Fire protection in nuclear power plants
Protection system and related features in nuclear power plants
Protection against internally generated missiles and their secondary effects in nuclear power plants
External man-induced events in relation to nuclear power plant design
Ultimate heat sink and directly associated heat transport systems for nuclear power plants
Emergency power systems at nuclear power plants
Safety-related instrumentation and control systems for nuclear power plants
Design aspects of radiation protection for nuclear power plants
1985
1984
1986
1984
1983
1983
1981
1984
1988
1979
1992
1980
1980
1982
1981
1991
1984
1985
1981
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
50-SG-D10 Fuel handling and storage systems in nuclear power plants
50-SG-D11 General design safety principles for nuclear power plants
50-SG-D12 Design of the reactor containment systems in nuclearpower plants
50-SG-D13 Reactor coolant and associated systems in nuclear powerplants
50-SG-D14 Design for reactor core safety in nuclear power plants
50-SG-D15 Seismic design and qualification for nuclear power plants
4. OPERATION
50-C-0 (Rev. 1) Code on the safety of nuclear power plants: Operation
Safety Guides
50-SG-01 (Rev. 1) Staffing of nuclear power plants and the recruitment,training and authorization of operating personnel
50-SG-02 In-service inspection for nuclear power plants
50-SG-03 Operational limits and conditions for nuclear power plants
50-SG-04 Commissioning procedures for nuclear power plants
50-SG-05 Radiation protection during operation of nuclearpower plants
50-SG-06 Preparedness of the operating organization (licensee)for emergencies at nuclear power plants
50-SG-07 (Rev. 1) Maintenance of nuclear power plants
50-SG-08 (Rev. 1) Surveillance of items important to safety in nuclearpower plants
50-SG-09 Management of nuclear power plants for safe operation
50-SG-010 Core management and fuel handling for nuclearpower plants
50-SG-011 Operational management of radioactive effluents andwastes arising in nuclear power plants
5. QUALITY ASSURANCE
50-C-QA (Rev. 1) Code on the safety of nuclear power plants:Quality assurance
1984
1986
1985
1986
1986
1992
1988
1991
1980
1979
1980
1983
1982
1990
1990
1984
1985
1986
1988
61
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
Safety Guides
50-SG-QA1 Establishing of the quality assurance programme for anuclear power plant project
50-SG-QA2 Quality assurance records system for nuclearpower plants
50-SG-QA3 Quality assurance in the procurement of items andservices for nuclear power plants
50-SG-QA4 Quality assurance during site construction of nuclearpower plants
50-SG-QA5 (Rev. 1) Quality assurance during commissioning and operation of nuclear power plants
50-SG-QA6 Quality assurance in the design of nuclear power plants
50-SG-QA7 Quality assurance organization for nuclear power plants
50-SG-QA8 Quality assurance in the manufacture of items fornuclear power plants
50-SG-QA10 Quality assurance auditing for nuclear power plants
50-SG-QA11 Quality assurance in the procurement, design andmanufacture of nuclear fuel assemblies
SAFETY PRACTICES
50-P-l Application of the single failure criterion
50-P-2 In-service inspection of nuclear power plants:A manual
50-P-3 Data collection and record keeping for themanagement of nuclear power plant ageing
50-P-4 Procedures for conducting probabilistic safetyassessments of nuclear power plants (Level 1)
50-P-5 Safety assessment of emergency power systems fornuclear power plants
1979
1979
1981
1986
1981
1983
1981
1980
1983
1990
1991
1991
1992
1992
1984
62
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
SELECTION OF IAEA PUBLICATIONS RELATING TO THE SAFETY OF
NUCLEAR POWER PLANTS
SAFETY SERIES
9
67
69
72
73
75-INSAG-1
75-INSAG-2
75-INSAG-3
75-INSAG-4
75-INSAG-5
75-INSAG-6
75-INSAG-7
77
79
81
84
86
Basic safety standards for radiation protection,1982 edition
Assigning a value to transboundary radiation exposure
Management of radioactive wastes from nuclear power plants
Principles for establishing intervention levels for the protection of the public in the event of a nuclear accident or radiological emergency
Emergency preparedness exercises for nuclear facilities: Preparation, conduct and evaluation
Summary report on the post-accident review meeting on the Chernobyl accident
Radionuclide source terms from severe accidents to nuclear power plants with light water reactors
Basic safety principles for nuclear power plants
Safety culture
The safety of nuclear power
Probabilistic safety assessment
The Chernobyl accident: Updating of INSAG-1
Principles for limiting releases of radioactive effluents into the environment
Design of radioactive waste management systems at nuclear power plants
Derived intervention levels for application in controlling radiation doses to the public in the event of a nuclear accident or radiological emergency: Principles, procedures and data
Basic principles for occupational radiation monitoring
Techniques and decision making in the assessment of off-site consequences of an accident in a nuclear facility
1985
1985
1985
1985
1986
1987
1988
1991
1992
1992
1993
1986
1986
1986
1982
1987
1987
63
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
93 Systems for reporting unusual events in nuclear power plants
94 Response to a radioactive materials release having a transboundary impact
97 Principles and techniques for post-accident assessment and recovery in a contaminated environment of a nuclear facility
98 On-site habitability in the event of an accident at a nuclear facility:Guidance for assessment and improvement
101 Operational radiation protection: A guide to optimization
103 Provision of operational radiation protection services at nuclear power plants
104 Extension of the principles of radiation protection to sources of potential exposure
105 The regulatory process for the decommissioning of nuclear facilities
106 The role of probabilistic safety assessmentand probabilistic safety criteria in nuclear power plant safety
TECHNICAL REPORTS SERIES
237 Manual on quality assurance programme auditing
239 Nuclear power plant instrumentation and control:A guidebook
242 Qualification of nuclear power plant operationspersonnel: A guidebook
249 Decontamination of nuclear facilities to permitoperation, inspection, maintenance, modification or plant decommissioning
262 Manual on training, qualification and certificationof quality assurance personnel
267 Methodology and technology of decommissioningnuclear facilities
1989
1989
1989
1990
1990
1990
1990
1992
1989
1984
1984
1984
1985
1986
1986
64
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
268
271
274
282
292
294
296
299
300
301
306
307
327
328
330
334
338
354
1986
1987
1987
1988
1988
1989
1989
1989
1989
1989
1989
1989
1991
1991
1992
1992
1992
1993
Manual on maintenance of systems and components important to safety
Introducing nuclear power plants into electrical power systems of limited capacity: Problems and remedial measures
Design of off-gas and air cleaning systems at nuclear power plants
Manual on quality assurance for computer software related to the safety of nuclear power plants
Design and operation of off-gas cleaning and ventilation systems in facilities handling low and intermediate level radioactive material
Options for the treatment and solidification of organic radioactive wastes
Regulatory inspection of the implementation of quality assurance programmes: A manual
Review of fuel element developments for water cooled nuclear power reactors
Cleanup of large areas contaminated as a result of a nuclear accident
Manual on quality assurance for installation and commissioning of instrumentation, control and electrical equipment in nuclear power plants
Guidebook on the education and training of technicians for nuclear power
Management of abnormal radioactive wastes at nuclear power plants
Planning for cleanup of large areas contaminated as a result of a nuclear accident
Grading of quality assurance requirements: A manual
Disposal of waste from the cleanup of large areas contaminated as a result of a nuclear accident
Monitoring programmes for unrestricted release related to decommissioning of nuclear facilities
Methodology for the management of ageing of nuclear power plant components important to safety
Reactivity accidents
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
367 Software important to safety in nuclear power plants
368 Accident management programmes in nuclear power plants:A Guidebook
369 Management for excellence in nuclear power plant performance: A manual
372 Development and implementation of computerized operatorsupport systems in nuclear installations
IAEA-TECDOC SERIES
303 Manual on the selection of appropriate quality assuranceprogrammes for items and services of a nuclear power plant
308 Survey of probabilistic methods in safety and riskassessment for nuclear power plant licensing
332 Safety aspects of station blackout at nuclear power plants
341 Developments in the preparation of operating proceduresfor emergency conditions of nuclear power plants
348 Earthquake resistant design of nuclear facilities withlimited radioactive inventory
355 Comparison of high efficiency particulate filter testingmethods
377 Safety aspects of unplanned shutdowns and trips
379 Atmospheric dispersion models for application inrelation to radionuclide releases
387 Combining risk analysis and operating experience
390 Safety assessment of emergency electric power systemsfor nuclear power plants
416 Manual on quality assurance for the survey, evaluation andconfirmation of nuclear power plant sites
424 Identification of failure sequences sensitive to human error
425 Simulation of a loss of coolant accident
443 Experience with simulator training for emergencyconditions
1994
1994
1994
1994
1984
1984
1985
1985
1985
1985
1986
1986
1986
1986
1987
1987
1987
1987
66
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
450
451
458
497
498
499
508
510
522
523
525
529
538
540
542
543
547
550
553
444
561
Improving nuclear power plant safety through operator aids
Dose assessments in nuclear power plant siting
Some practical implications of source term reassessment
OSART results
OSART results II
Good practices for improved nuclear power plant performance
Models and data requirements for human reliability analysis
Survey of ranges of component reliability data for use in probabilistic safety assessment
Status of advanced technology and design for water cooled reactors: Heavy water reactors
A probabilistic safety assessment peer review:Case study on the use of probabilistic safety assessment for safety decisions
Probabilistic safety criteria at the safety function/system level
Guidebook on training to establish and maintainthe qualification and competence of nuclear power plantoperations personnel
User requirements for decision support systems used for nuclear power plant accident prevention and mitigation
Human error classification and data collection
Safety aspects of nuclear power plant ageing
Use of expert systems in nuclear safety
Procedures for conducting independent peer reviews of probabilistic safety assessment
The use of probabilistic safety assessment in the relicensing of nuclear power plants for extended lifetimes
Safety of nuclear installations: Future direction
Computer codes for Level 1 probabilistic safety assessment
Reviewing computer capabilities in nuclear power plants
1987
1988
1988
1988
1989
1989
1989
1989
1989
1989
1989
1989
1989
1990
1990
1990
1990
1990
1990
1990
1990
67
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
570
581
586
590
591
592
593
599
600
605
611
618
631
632
635
640
648
658
659
660
68
OSART mission highlights 1988-1989
Safety implications of computerized process control in nuclear power plants
Simulation of a loss of coolant accident with rupture in the steam generator hot collector
Case study on the use of PSA methods:Determining safety importance of systems and components at nuclear power plants
Case study on the use of PSA methods:Backfitting decisions
Case study on the use of PSA methods:Human reliability analysis
Case study on the use of PSA methods:Station blackout risk at Millstone Unit 3
Use of probabilistic safety assessment to evaluate nuclear power plant technical specifications
Numerical indicators of nuclear power plant safety performance
OSART good practices: 1986-1989
Use of plant specific PSA to evaluate incidents at nuclear power plants
Human reliability data collection and modelling
Reviewing reactor engineering and fuel handling: Supplementary guidance and reference material for IAEA OSARTs
ASSET guidelines: Revised 1991 edition
OSART guidelines: 1992 edition
Ranking of safety issues for WWER-440 model 230 nuclear power plants
Procedures for conducting common cause failure analysis in probabilistic safety assessment
Safety related maintenance in the framework of the reliability centered maintenance concept
Reactor pressure vessel embrittlement
Expert systems in the nuclear industry
1990
1991
1991
1991
1991
1991
1991
1991
1991
1991
1991
1991
1992
1991
1992
1992
1992
1992
1992
1992
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
669
670
672
681
694
710
711
712
719
722
724
737
740
742
743
744
749
751
Case study on the use of PSA methods: Assessment of technical specifications for the reactor protection system instrumentation
Pilot studies on management of ageing of nuclear power plant components: Results of Phase I
Safety aspects of nuclear power plant automation and robotics
OSART mission highlights: 1989-1990
Safety assessment of proposed improvements of RBMK nuclear power plants
Applicability of the leak before break concept
Use of probabilistic safety assessment for nuclear installations with large inventory of radioactive material
Safety aspects of designs for future light water reactors (evolutionary reactors)
Defining initiating events for purposes of probabilistic safety assessment
Safety assessment o f design solutions and proposed improvements to Smolensk Unit 3 RBMK nuclear power plant
Probabilistic safety assessment for seismic events
Advances in reliability analysis and probabilistic safety assessment for nuclear power reactors
Modelling and data prerequisites for specific applications of PSA in the management of nuclear plant safety
Design basis and design features of WWER-440 model 213 nuclear power plants: Reference plant: Bohunice V2 (Slovakia)
ASCOT Guidelines
OSART Guidelines — 1994 Edition
Generic initiating events for PSA for WWER reactors
PSA for shutdown mode for nuclear power plants
1992
1992
1993
1993
1993
1993
1993
1993
1993
1993
1994
1994
1994
1994
1994
1994
1994
1992
69
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
PROCEEDINGS SERIES
STI/PUB/673 IAEA safety codes and guides (NUSS) in the light of 1985current safety issues
STI/PUB/700 Source term evaluation for accident conditions 1986
STI/PUB/701 Emergency planning and preparedness for nuclear 1986facilities
STI/PUB/716 Optimization of radiation protection 1986
STI/PUB/759 Safety aspects of the ageing and maintenance of 1988nuclear power plants
STI/PUB/761 Nuclear power performance and safety 1988
STI/PUB/782 Severe accidents in nuclear power plants 1988
STI/PUB/783 Radiation protection in nuclear energy 1988
STI/PUB/785 Feedback of operational safety experience 1989from nuclear power plants
STI/PUB/803 Regulatory practices and safety standards 1989for nuclear power plants
STI/PUB/824 Fire protection and fire fighting in nuclear installations 1989
STI/PUB/825 Environmental contamination following a 1990major nuclear accident
STI/PUB/826 Recovery operations in the event of a nuclear accident or 1990radiological emergency
STI/PUB/843 Balancing automation and human action in nuclear 1991power plants
STI/PUB/878 Probabilistic safety assessment for operational safety — 1992PSA 91
STI/PUB/880 The safety of nuclear power: Strategy for the future 1992
STI/PUB/945 International nuclear safeguards 1994: Vision for the future 1994
70
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
HOW TO ORDER IAEA PUBLICATIONS
☆ ☆ In the United States of America and Canada, the exclusive sales agent forIAEA publications, to whom all orders and inquiries should be addressed, is:
UNIPUB, 4611-F Assembly Drive, Lanham, MD 20706-4391, USA
☆ ☆ In the following countries IAEA publications may be purchased from the sourceslisted below, or from major local booksellers. Payment may be made in local currency or with UNESCO coupons.
ARGENTINA
AUSTRALIABELGIUM
CHILE
CHINA
FRANCE
GERMANY
HUNGARYINDIA
ISRAELITALY
JAPANNETHERLANDS
PAKISTANPOLAND
ROMANIA RUSSIAN FEDERATION
SLOVAK REPUBLIC SOUTH AFRICA
SPAIN
SWEDEN UNITED KINGDOM
YUGOSLAVIA
Comisidn Nacional de Energfa Atdmica, Avenida del Libertador 8250, RA-1429 Buenos AiresHunter Publications, 58A Gipps Street, Collingwood, Victoria 3066 Service Courrier UNESCO, 202, Avenue du Roi, B-1060 Brussels Comisidn Chilena de Energfa Nuclear, Venta de Publicaciones, Amunategui 95, Casilla 188-D, Santiago IAEA Publications in Chinese:China Nuclear Energy Industry Corporation, Translation Section,P.O. Box 2103, BeijingIAEA Publications other than in Chinese:China National Publications Import & Export Corporation,Deutsche Abteilung, P.O. Box 88, BeijingOffice International de Documentation et Librairie, 48, rue Gay-Lussac, F-75240 Paris Cedex 05UNO-Verlag, Vertriebs- und Verlags GmbH, Dag Hammarskj6ld-Haus, Poppelsdorfer Allee 55, D-53115 Bonn Librotrade Ltd., Book Import, P.O. Box 126, H-1656 Budapest Oxford Book and Stationery Co., Scindia House, New Delhi-110 001 YOZMOT Literature Ltd., P.O. Box 56055, IL-61560 Tel Aviv Libreria Scientifica Dott. Lucio di Biasio “ AEIOU” ,Via CoroneHi 6, 1-20146 MilanMaruzen Company, Ltd, P.O. Box 5050, 100-31 Tokyo International Martinus Nijhoff International, P.O. Box 269, NL-2501 AX The Hague Swets and Zeitlinger b.v., P.O. Box 830, NL-2610 SZ Lisse Mirza Book Agency, 65, Shahrah Quaid-e-Azam, P.O. Box 729, Lahore 3 Ars Polona, Foreign Trade Enterprise,Krakowskie Przedmieicie 7, PL-00-068 Warsaw llexim, P.O. Box 136-137, Bucharest Mezhdunarodnaya Kniga, Sovinkniga-EA,Dimitrova 39, SU-113 095 MoscowAlfa Publishers, Hurbanovo ndmestie 3, SQ-815 89 Bratislava Van Schaik Bookstore (Pty) Ltd, P.O. Box 724, Pretoria 0001 Diaz de Santos, Lagasca 95, E-28006 Madrid Diaz de Santos, Baimes 417, E-08022 Barcelona Fritzes Information Centre, S-106 47 Stockholm HMSO, Publications Centre, Agency Section,51 Nine Elms Lane, London SW8 5DRJugoslovenska Knjiga, Terazije 27, P.O. Box 36, YU-11001 Belgrade
☆ ☆ Orders (except for customers in Canada and the USA) and requests for information may also be addressed directly to:
Sales and Promotion Unit ^ International Atomic Energy Agency
Wagramerstrasse 5, P.O. Box 100, A-1400 Vienna, Austria
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
94-03877
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
ISBN 92-0-103994-8 ISSN 0074-1892
This publication is no longer valid Please see http://www-ns.iaea.org/standards/
top related