Pow-R-Stock Plus Program Reference Guide
Capabilities
Unassembled Panelboards — EZ� Boxes and EZ Trims
Note: The colors shown in the tables correspond to the color coding on the trim, interior, and box product packaging labels. Be sure allthree parts match when delivering to your customer.
SINGLE-PHASE 3-WIRE 120/240 VAC
Catalog NumberInteriors (Less Main Device) Boxes Trims (NEMA� 1)
Ampere Rating Max. No. of Poles Aluminum Bus Copper Bus NEMA 1 Surface Flush NEMA 3R Enclosures100 18 PRL1A1100X18A PRL1A1100X18C EZB2036R EZT2036S EZT2036F GWPBQ2036PR 100 30 PRL1A1100X30A PRL1A1100X30C EZB2048R EZT2048S EZT2048F GWPBQ2048PR225 30 PRL1A1225X30A PRL1A1225X30C EZB2048R EZT2048S EZT2048F GWPBQ2048PR225 42 PRL1A1225X42AS PRL1A1225X42CS EZB2048R EZT2048S EZT2048F GWPBQ2048PR225 42 PRL1A1225X42A PRL1A1225X42C EZB2060R EZT2060S EZT2060F GWPBQ2060PR400 42 PRL1A1400X42A PRL1A1400X42C EZB2072R EZT2072S EZT2072F GWPBR2072PR
3-PHASE, 4-WIRE 208Y/120VAC OR 3-PHASE, 3-WIRE 240 VAC
Catalog NumberInteriors (Less Main Device) Boxes Trims (NEMA 1)
Ampere Rating Max. No. of Poles Aluminum Bus Copper Bus NEMA 1 Surface Flush NEMA 3R Enclosures100 18 PRL1A3100X18A PRL1A3100X18C EZB2036R EZT2036S EZT2036F GWPBQ2036PR 100 30 PRL1A3100X30A PRL1A3100X30C EZB2048R EZT2048S EZT2048F GWPBQ2048PR225 30 PRL1A3225X30A PRL1A3225X30C EZB2048R EZT2048S EZT2048F GWPBQ2048PR225 42 PRL1A3225X42AS PRL1A3225X42CS EZB2048R EZT2048S EZT2048F GWPBQ2048PR225 42 PRL1A3225X42A PRL1A3225X42C EZB2060R EZT2060S EZT2060F GWPBQ2060PR400 42 PRL1A3400X42A PRL1A3400X42C EZB2072R EZT2072S EZT2072F GWPBR2072PR
3-PHASE, 4-WIRE 480Y/277 VAC
Catalog NumberInteriors (Less Main Device) Boxes Trims (NEMA 1)
Ampere Rating Max. No. of Poles Aluminum Bus Copper Bus NEMA 1 Surface Flush NEMA 3R Enclosures100 18 PRL2A3100X18A PRL2A3100X18C EZB2036R EZT2036S EZT2036F GWPBQ2036PR 100 30 PRL2A3100X30A PRL2A3100X30C EZB2048R EZT2048S EZT2048F GWPBQ2048PR225 30 PRL2A3225X30A PRL2A3225X30C EZB2048R EZT2048S EZT2048F GWPBQ2048PR225 42 PRL2A3225X42AS PRL2A3225X42CS EZB2048R EZT2048S EZT2048F GWPBQ2048PR225 42 PRL2A3225X42A PRL2A3225X42C EZB2060R EZT2060S EZT2060F GWPBQ2060PR400 42 PRL2A3400X42A PRL2A3400X42C EZB2072R EZT2072S EZT2072F GWPBR2072PR
Eaton Electrical Inc.1000 Cherrington ParkwayMoon Township, PA 15108United Statestel: 1-800-525-2000www.EatonElectrical.com
© 2007 Eaton CorporationAll Rights ReservedPrinted in USAPublication No. SA01413001E / Z5279January 2007
EZ is a trademark of Eaton Corporation. NEMA is the registered trademark and service mark of theNational Electrical Manufacturers Association.
KITS — MAIN CIRCUIT BREAKER OR SUB-FEED CIRCUIT BREAKER (INCLUDES CIRCUIT BREAKER AND TERMINALS)
Max. Ampere Catalog Breaker Mounting Wire Range Voltage Rating Service Number Frame Location Al/Cu240 Vac 100 1 or 3-Ph BKED100T ED Top (1) #14 – 1/0
125 1 or 3-Ph BKED125T ED Top (1) #4 – 4/0150 1 or 3-Ph BKED150T ED Top (1) #4 – 4/0175 1 or 3-Ph BKED175T ED Top (1) #4 – 4/0 1200 1 or 3-Ph BKED200T ED Top (1) #4 – 4/0 1225 1 or 3-Ph BKED225T ED Top (1) #4 – 4/0 1
240 Vac 100 1 or 3-Ph BKED100B ED Bottom (1) #14 – 1/0125 1 or 3-Ph BKED125B ED Bottom (1) #4 – 4/0150 1 or 3-Ph BKED150B ED Bottom (1) #4 – 4/0175 1 or 3-Ph BKED175B ED Bottom (1) #4 – 4/0 1200 1 or 3-Ph BKED200B ED Bottom (1) #4 – 4/0 1225 1 or 3-Ph BKED225B ED Bottom (1) #4 – 4/0 1
480 Vac 100 1 or 3-Ph BKFD100T FD Top (1) #14 – 1/0125 1 or 3-Ph BKFD125T FD Top (1) #4 – 4/0150 1 or 3-Ph BKFD150T FD Top (1) #4 – 4/0175 1 or 3-Ph BKFD175T FD Top (1) #4 – 4/0 1200 1 or 3-Ph BKFD200T FD Top (1) #4 – 4/0 1225 1 or 3-Ph BKFD225T FD Top (1) #4 – 4/0 1
480 Vac 100 1 or 3-Ph BKFD100B FD Bottom (1) #14 – 1/0125 1 or 3-Ph BKFD125B FD Bottom (1) #4 – 4/0150 1 or 3-Ph BKFD150B FD Bottom (1) #4 – 4/0175 1 or 3-Ph BKFD175B FD Bottom (1) #4 – 4/0 1200 1 or 3-Ph BKFD200B FD Bottom (1) #4 – 4/0 1225 1 or 3-Ph BKFD225B FD Bottom (1) #4 – 4/0 1
SUMMARY OF BRANCH BREAKERS AVAILABLE
Breaker Frame No. of Poles Ampere Rating Voltage kAIC Rating Example Panel TypeBAB 1 15 – 60 120 Vac 10 BAB1020 PRL1a
2 15 – 100 120/240 Vac 10 BAB2020 PRL1aBAB H 2 15 – 100 240 Vac 10 BAB2040H PRL1a
3 15 – 100 240 Vac 10 BAB3030H PRL1aQBGF 1 15 – 30 120 Vac 10 QBGF1020 PRL1a
2 15 – 40 120/240 Vac 10 QBGF2040 PRL1aQBHW 1 15 – 60 120 Vac 22 QBHW1020 PRL1a
2 15 – 100 120/240 Vac 22 QBHW2020 PRL1a2 15 – 100 240 Vac 22 QBHW2040H PRL1a3 15 – 100 240 Vac 22 QBHW3030H PRL1a
GHQ 1 15 – 20 277 Vac 14 GHQ1020 PRL2aGHB 1 15 – 100 277 Vac 14 GHB1020 PRL2a
2 15 – 100 480Y/277 Vac 14 GHB2040 PRL2a3 15 – 100 480Y/277 Vac 14 GHB3060 PRL2a
KITS — MAIN CIRCUIT BREAKER (INCLUDES CIRCUIT BREAKER AND TERMINALS)
Max. Ampere Catalog Breaker Mounting Wire RangeVoltage Rating Service Number Frame Location AI/Cu480 Vac 250 1 or 3-Ph BKKD250T KD Top (1) 250 – 500 kcmil
300 1 or 3-Ph BKKD300T KD Top (1) 250 – 500 kcmil350 1 or 3-Ph BKKD350T KD Top (1) 250 – 500 kcmil400 1 or 3-Ph BKKD400T KD Top (2) 3/0 – 250 kcmil
or (1) 3/0 – 500 kcmil 480 Vac 250 1 or 3-Ph BKKD250B KD Bottom (1) 250 – 500 kcmil
300 1 or 3-Ph BKKD300B KD Bottom (1) 250 – 500 kcmil350 1 or 3-Ph BKKD350B KD Bottom (1) 250 – 500 kcmil400 1 or 3-Ph BKKD400B KD Bottom (2) 3/0 – 250 kcmil
or (1) 3/0 – 500 kcmil
KITS — MAIN LUGS OR THROUGH-FEED LUGS
Ampere Rating Service Catalog Number Wire Range AI/Cu100 1 or 3-Ph LUGKIT100 (1) #14 – 1/0225 1 or 3-Ph LUGKIT225 (1) #6 – 300 kcmil
KITS — SERVICE ENTRANCE
Ampere Rating Service Catalog Number Panel Type100/225 1 or 3-Ph SEK1/2 PRL1a or PRL2a400 1 or 3-Ph SEK4/6 PRL1a or PRL2a
KITS — INSULATED/ISOLATED GROUND (CARTON QTY OF 5)
Ampere Rating Service Catalog Number Panel Type100/225/400 1 or 3-Ph ISOGROUND PRL1a or PRL2a
KITS — MAIN LUGS ONLY
Ampere Rating Service Catalog Number Wire Range Al/Cu400 1 or 3-Ph LUGKIT400 (2) #2 – 500 kcmil
KITS — 200% NEUTRAL
Ampere Rating Service Catalog Number Panel Type100 1 or 3-Ph 2NK100 PRL1a or PRL2a225 1 or 3-Ph 2NK225 PRL1a or PRL2a
Circuit Breaker Kits — Unassembled Panelboards
1 Order optional lug kit Catalog No. 3TA225FDK for 175 – 225 ampere ED- and FD-Frame 3-pole circuit breakers to provide terminations for (1) #6 – 300 kcmil.
July 2007
14-4
For more information visit:
www.eaton.com
CA08101001E
Panelboards
14
Pow-R-Line C Panelboards
Product Selection
Product Types
Type PRL1a
Bolt-on or Plug-on Circuit Breakers240 Vac Maximum
■
Main Lugs Only400 amperes maximum.
■
Main Circuit Breaker400 amperes maximum.
■
Branch Circuit Breakers100 amperes maximum,1-, 2- and 3-pole.
Type PRL1a
Type PRL2a
Bolt-on Circuit Breakers 240 V or 480Y/277 Vac; 125/250 Vdc Maximum
■
Main Lugs Only400 amperes maximum.
■
Main Circuit Breaker400 amperes maximum.
■
Branch Circuit Breakers100 amperes maximum,1-, 2- and 3-pole.
Type PRL2a
Type PRL3a
Bolt-on Circuit Breakers240 V, 480 V or 600 Vac; 250 Vdc Maximum
■
Main Lugs Only800 amperes maximum.
■
Main Circuit Breaker600 amperes maximum.
■
Branch Circuit Breakers225 amperes maximum,1-, 2- and 3-pole.
Type PRL3a
Type PRL4
Circuit Breakers or Fusible Switches240 V, 480 V or 600 Vac; 250 Vdc Maximum
■
Main Lugs Only1200 amperes maximum.
■
Main Circuit Breaker1200 amperes maximum.
■
Main Fusible Switch1200 amperes maximum.
■
Branch Circuit Breakers1200 amperes maximum,1-, 2- and 3-pole.
■
Branch Fusible Switches1200 amperes maximum,2- and 3-pole.
Type PRL4
Type PRL5P
Plug-on Circuit Breakers240 V, 480 V or 600 Vac; 250 Vdc Maximum
■
Main Lugs Only1200 amperes maximum.
■
Main Circuit Breaker1200 amperes maximum.
■
Branch Circuit Breakers1200 amperes maximum,1-, 2- and 3-pole.
Type PRL5P
Pow-R-Command
Bolt-on Circuit Breakers240 V or 480Y/277 Vac
■
Main Lugs Only400 amperes maximum.
■
Main Circuit Breaker400 amperes maximum.
■
Branch Circuit Breakers225 amperes maximum,1-, 2- and 3-pole.
■
Integral Power Switching Controls.
Pow-R-Command
July 2007
CA08101001E For more information visit: www.eaton.com
14-21Panelboards
14
Pow-R-Line C PanelboardsPRL1a
Product Description■ 240 Vac maximum.■ 3-phase 4-wire, 3-phase 3-wire,
1-phase 3-wire, 1-phase 2-wire.■ 400 ampere maximum mains.■ 100 ampere maximum branch
breakers.■ Bolt-on or plug-on branch breakers.■ Factory assembled.■ Refer to Page 14-5 for additional
information.
Type PRL1a
Application Description■ Lighting and appliance branch
panelboard.■ Fully rated or series rated.■ Interrupting ratings up to 200 kA
symmetrical.■ Suitable for use as Service Entrance
Equipment, when specified on the order.
■ See Pages 14-5 through 14-18 for additional information.
Standards and Certifications■ UL 67, UL 50.■ Federal Specification W-P-115c.■ Refer to Page 14-5 for additional
information.
Options and Accessories■ Refer to Page 14-46.
Layout and Sizing■ Refer to Page 14-22.
Product SelectionFormula Pricing: Base Price + Branch Circuits + Modifications = Total Price U.S. $Table 14-19. Base Prices — PRL1a
Table 14-20. Branch Circuit Breakers — PRL1a
� 1-pole breakers are rated 120 Vac maximum.� 240 volt breakers must be used on 3-phase, 3-wire, 240 volt delta systems or on the high leg of a
midpoint delta grounded system.� 50 ampere devices are available as 2-pole only.� GFCI for 5 mA personnel protection.� GFP for 30 mA equipment protection.� Arc fault circuit breaker.� Arc fault circuit breaker with GFCI. HID (High Intensity Discharge) rated breaker. Switching Neutral Breaker. 1-pole device requires 2-pole space, 2-pole device requires 3-pole space.� Solenoid operated breaker.
AmpereRating
InterruptingRating (kA Sym.)240 Vac
BreakerType
Price U.S. $
3-Phase4-Wire
1-Phase 3-Wire,1-Phase 2-Wire
3-Phase 3-Wire
Main Lug Only100225400
———
———
Main Breaker 100100100100100100100100100
10 18 22 22 42 65 65100100
BABEHDQBHWEDBEDSEDFDEDHHFD
225225225225
22 42 65100
EDBEDSEDEDH
250250250
65100200
JDHJDJDC
400400400400
65 65100200
DKKDHKDKDC
Bolt-on = BAB, QBHW, QBGF, QBHGF, QBGFEP, QBHGFEP, QBAF, QBAG, QBHAF, QBHAGPlug-on = HQP, QPHW, QPGF, QPHGF, QPGFEP, QPHGFEP
AmpereRating
InterruptingRating (kA Sym.)240 Vac �
BreakerType
Price U.S. $
1-Pole120 V
2-Pole120/240 V
2-Pole240 V �
3-Pole240 V
15 – 607080 – 10015 – 50 �
15 – 50 �
15 – 2015 – 20
10101010101010
BAB, HQPBAB, HQPBAB, HQPQBGF, QPGF �
QBGFEP, QPGFEP �
QBAF �QBAG �
15 – 6015 – 3015 – 3015 – 30
10101010
BAB-D, HQP-D BAB-C, HQP-B BABRP �BABRSP �
15 – 607080 – 10015 – 3015 – 3015 – 2015 – 20
22222222222222
QBHW, QPHWQBHW, QPHWQBHW, QPHWQBHGF, QPHGF �QBHGFEP, QPHGFEP �
QBHAF �QBHAG �
Provision — —
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9
July 2007
14-22
For more information visit: www.eaton.com CA08101001E
Panelboards
14
Pow-R-Line C PanelboardsPRL1a
Box Sizing and SelectionAssembled Circuit Breaker PanelboardsBox size and box and trim catalog numbers for all standard panelboard types are found in Table 14-21.
Instructions1. Using description of the required
panelboard, select the rating and type of main required.
2. Count the total number of branch circuit poles, including provisions, required in the panelboard. Do not count main breaker poles. Convert 2- or 3-pole branch breaker to single-poles, i.e., 3-pole breaker, count as 3 poles.
Determine sub-feed breaker orthrough-feed lug requirements.
3. Select the main ampere rating section from Table 14-21.
4. Select panelboard type from first column, main breaker frame, if applicable, from second column, and sub-feed breaker frame, if applicable, from the third column.
5. From Step #2, determine the num-ber of branch circuits in Column 4.
6. Read box size, box and trim catalog numbers across columns to the right. Specify surface or flush mounting on the order.
CabinetsFronts are code-gauge steel, ANSI-61 light gray painted finish.
Boxes are code-gauge galvanized steel without knockouts. Standard depth is 5-3/4 inches (146.1 mm). Standard width is 20 inches (508.0 mm). An optional 28-inch (711.2 mm) wide box is available.
Top and Bottom Gutters5-1/2 inches (139.7 mm) minimum.
Table 14-21. PRL1a Panelboard Sizing
� Metric box dimensions:
� Smaller panelboard box sizes are available if required. Contact Eaton for application information.
PanelboardTypes
Main Breaker Types& Mounting Position(H) = Horiz.(V) = Vert.
Sub-Feed Breaker Types& Mounting Position(H) = Horiz.(V) = Vert.
Maximum No. of Branch CircuitsIncludingProvisions
Box DimensionsInches ��
YS BoxCatalogNumber
LT TrimCatalogNumber
EZ BoxCatalogNumber
EZ TrimCatalogNumber
H W D
100 Ampere MaximumMain Breaker BAB, QBHW
(H)————
15273942
36.0048.0048.0060.00
20.0020.0020.0020.00
5.755.755.755.75
YS2036YS2048YS2048YS2060
LT2036S or FLT2048S or FLT2048S or FLT2060S or F
EZB2036REZB2048REZB2048REZB2060R
EZT2036S or FEZT2048S or FEZT2048S or FEZT2060S or F
Main Lugs orMain Breaker
EHDFD, HFD(V)
———
183042
36.0048.0048.00
20.0020.0020.00
5.755.755.75
YS2036YS2048YS2048
LT2036S or FLT2048S or FLT2048S or F
EZB2036REZB2048REZB2048R
EZT2036S or FEZT2048S or FEZT2048S or F
Main Lugs or Main Breaker with 100 A Thru-Feed Lugs or Sub- Feed Breaker
EHDFDHFD(V)
EHDFDHFD(V)
183042
48.0048.0060.00
20.0020.0020.00
5.755.755.75
YS2048YS2048YS2060
LT2048S or FLT2048S or FLT2060S or F
EZB2048REZB2048REZB2060R
EZT2048S or FEZT2048S or FEZT2060S or F
225 Ampere MaximumMain Lugs orMain Breaker
EDB, EDS, ED,EDH, FD, HFD(V)
———
183042
36.0048.0048.00
20.0020.0020.00
5.755.755.75
YS2036YS2048YS2048
LT2036S or FLT2048S or FLT2048S or F
EZB2036REZB2048REZB2048R
EZT2036S or FEZT2048S or FEZT2048S or F
JD, HJDJDC(V)
———
183042
60.0060.0072.00
20.0020.0020.00
5.755.755.75
YS2060YS2060YS2072
LT2060S or FLT2060S or FLT2072S or F
EZB2060REZB2060REZB2072R
EZT2060S or FEZT2060S or FEZT2072S or F
Main Lugs or Main Breaker with 225 A Thru-Feed Lugs or Sub-Feed Breaker
EHD, FD, HFD,EDB, EDS, ED,EDH (V)
EHD, FD, HFD,EDB, EDS, ED,EDH (V)
183042
48.0048.0060.00
20.0020.0020.00
5.755.755.75
YS2048YS2048YS2060
LT2048S or FLT2048S or FLT2060S or F
EZB2048REZB2048REZB2060R
EZT2048S or FEZT2048S or FEZT2060S or F
JD, HJDJDC(V)
EHD, FD, HFD,EDB, EDS, ED,EDH (V)
183042
60.0072.0072.00
20.0020.0020.00
5.755.755.75
YS2060YS2072YS2072
LT2060S or FLT2072S or FLT2072S or F
EZB2060REZB2072REZB2072R
EZT2060S or FEZT2072S or FEZT2072S or F
400 Ampere MaximumMain Lugs orMain Breaker
DK, KD, HKD,KDC(V)
———
183042
60.0060.0072.00
20.0020.0020.00
5.755.755.75
YS2060YS2060YS2072
LT2060S or FLT2060S or FLT2072S or F
EZB2060REZB2060REZB2072R
EZT2060S or FEZT2060S or FEZT2072S or F
Main Lugs or Main Breaker with 225 A Thru-Feed Lugs or Sub- Feed Breaker
DK, KD, HKD,KDC(V)
EHD, FD, HFD,EDB, EDS, ED,EDH (V)
183042
60.0072.0072.00
20.0020.0020.00
5.755.755.75
YS2060YS2072YS2072
LT2060S or FLT2072S or FLT2072S or F
EZB2060REZB2072REZB2072R
EZT2060S or FEZT2072S or FEZT2072S or F
Main Lugs or Main Breaker with 400 A Thru-Feed Lugs or Sub- Feed Breaker
DK, KD, HKD,KDC(V)
JD, HJD, JDC,DK, KD,HKD, KDC(V)
183042
72.0090.0090.00
20.0020.0020.00
5.755.755.75
YS2072YS2090YS2090
LT2072S or FLT2090S or FLT2090S or F
EZB2072REZB2090REZB2090R
EZT2072S or FEZT2090S or FEZT2090S or F
Catalog Number Dimensions in mm
YS Box EZ Box Height Width Depth
YS2036YS2048YS2060YS2072YS2090
EZB2036REZB2048REZB2060REZB2072REZB2090R
914.41219.21524.01828.82286.0
508.0508.0508.0508.0508.0
146.1146.1146.1146.1146.1
July 2007
CA08101001E For more information visit: www.eaton.com
14-23Panelboards
14
Pow-R-Line C PanelboardsPRL2a
Product Description■ 480Y/277 Vac maximum (125 Vdc).■ 3-phase 4-wire, 3-phase 3-wire,
1-phase 3-wire, 1-phase 2-wire.■ 400 ampere maximum mains.■ 100 ampere maximum branch
breakers.■ Bolt-on branch breakers.■ Factory assembled.■ Refer to Page 14-5 for additional
Information.
Type PRL2a
Application Description■ Lighting and appliance branch
panelboard.■ Fully rated or series rated.■ Interrupting ratings up to 200 kA
symmetrical.■ Suitable for use as Service Entrance
Equipment, when specified on the order.
■ See Pages 14-5 through 14-18 for additional information.
Standards and Certifications■ UL 67, UL 50.■ Federal Specification W-P-115c.■ Refer to Page 14-5 for additional
information.
Options and Accessories■ Refer to Page 14-46.
Layout and Sizing■ Refer to Page 14-24.
Product SelectionFormula Pricing: Base Price + Branch Circuits + Modifications = Total Price U.S. $Table 14-22. Base Prices — PRL2a
� These system voltages apply only to 240 volts.
Table 14-23. Branch Circuit Breakers — PRL2a
� Interrupting ratings in this column are applicable to 120 Vac for 1-pole breakers.� At 480 volts, must be used on 480Y/277 volts grounded wye systems only.� Solenoid operated breaker.� GFP for 30 mA equipment protection. Requires 2-pole spaces. 277 Vac only.� HID (High Intensity Discharge) rated breaker.
Ampere Rating
Interrupting Rating(kA Symmetrical)
BreakerType
Price U.S. $
240 Vac 480Y/277 Vac 125/250 Vdc 3-Phase4-Wire
1-Phase 3-Wire �,1-Phase 2-Wire
3-Phase3-Wire �
Main Lug Only100225400
———
———
———
———
Main Breaker100100
65 18
14 14
1410
GHBEHD
100100100
65100200
35 65100
102222
FDHFDFDC
225225225225
65 65100200
— 35 65100
—102222
EDFDHFDFDC
250250250
65100200
35 65100
102222
JDHJDJDC
400400400
65100200
35 65100
102222
KDHKDKDC
AmpereRating
Interrupting Rating(kA Symmetrical)
BreakerType
Price U.S. $
240 Vac � 480Y/277 Vac 125/250 Vdc 1-Pole 2-Pole 3-Pole
15 – 2015 – 2025 – 6070 – 10015 – 3015 – 2015 – 30
65656565656565
14141414251414
—141414———
GHQ �
GHB �
GHB �
GHB �
HGHB �
GHQRSP �GHBS ��
15 – 6015 – 20
——
1414
——
GHBGFEP ��
GHBHID ��
Provision — — — —
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9
July 2007
14-24
For more information visit: www.eaton.com CA08101001E
Panelboards
14
Pow-R-Line C PanelboardsPRL2a
Box Sizing and SelectionAssembled Circuit Breaker PanelboardsBox size and box and trim catalog numbers for all standard panelboard types are found in Table 14-24.
Instructions1. Using description of the required
panelboard, select the rating and type of main required.
2. Count the total number of branch circuit poles, including provisions, required in the panelboard. Do not count main breaker poles. Convert 2- or 3-pole branch breaker to single-poles, i.e., 3-pole breaker, count as 3 poles.
Determine sub-feed breaker orthrough-feed lug requirements.
3. Select the main ampere rating section from Table 14-24.
4. Select panelboard type from first column, main breaker frame, if applicable, from second column, and sub-feed breaker frame, if applicable, from the third column.
5. From Step #2, determine the num-ber of branch circuits in Column 4.
6. Read box size, box and trim catalog numbers across columns to the right. Specify surface or flush mounting on the order.
CabinetsFronts are code-gauge steel, ANSI-61 light gray painted finish.
Boxes are code-gauge galvanized steel without knockouts. Standard depth is 5-3/4 inches (146.1 mm). Standard width is 20 inches (508.0 mm). An optional 28-inch (711.2 mm) wide box is available.
Top and Bottom Gutters5-1/2 inches (139.7 mm) minimum.
Table 14-24. PRL2a Panelboard Sizing
� Metric box dimensions:
� Smaller panelboard box sizes are available if required. Contact Eaton for application information.
PanelboardTypes
Main Breaker Types & Mounting Position(H) = Horiz.(V) = Vert.
Sub-Feed Breaker Types & Mounting Position(H) = Horiz.(V) = Vert.
Maximum No. of Branch CircuitsIncludingProvisions
Box DimensionsInches ��
YS BoxCatalogNumber
LT TrimCatalogNumber
EZ BoxCatalogNumber
EZ TrimCatalogNumberH W D
100 Ampere MaximumMain Breaker BAB, QBHW
(H)————
15273942
36.0048.0048.0060.00
20.0020.0020.0020.00
5.755.755.755.75
YS2036YS2048YS2048YS2060
LT2036S or FLT2048S or FLT2048S or FLT2060S or F
EZB2036REZB2048REZB2048REZB2060R
EZT2036S or FEZT2048S or FEZT2048S or FEZT2060S or F
Main Lugs orMain Breaker
EHDFD, HFD(V)
———
183042
36.0048.0048.00
20.0020.0020.00
5.755.755.75
YS2036YS2048YS2048
LT2036S or FLT2048S or FLT2048S or F
EZB2036REZB2048REZB2048R
EZT2036S or FEZT2048S or FEZT2048S or F
Main Lugs or Main Breaker with 100 A Thru-Feed Lugs or Sub- Feed Breaker
EHDFDHFD(V)
EHDFDHFD(V)
183042
48.0048.0060.00
20.0020.0020.00
5.755.755.75
YS2048YS2048YS2060
LT2048S or FLT2048S or FLT2060S or F
EZB2048REZB2048REZB2060R
EZT2048S or FEZT2048S or FEZT2060S or F
225 Ampere MaximumMain Lugs orMain Breaker
EDB, EDS, ED,EDH, FD, HFD(V)
———
183042
36.0048.0048.00
20.0020.0020.00
5.755.755.75
YS2036YS2048YS2048
LT2036S or FLT2048S or FLT2048S or F
EZB2036REZB2048REZB2048R
EZT2036S or FEZT2048S or FEZT2048S or F
JD, HJDJDC(V)
———
183042
60.0060.0072.00
20.0020.0020.00
5.755.755.75
YS2060YS2060YS2072
LT2060S or FLT2060S or FLT2072S or F
EZB2060REZB2060REZB2072R
EZT2060S or FEZT2060S or FEZT2072S or F
Main Lugs or Main Breaker with 225 A Thru-Feed Lugs or Sub-Feed Breaker
EHD, FD, HFD,EDB, EDS, ED,EDH (V)
EHD, FD, HFD,EDB, EDS, ED,EDH (V)
183042
48.0048.0060.00
20.0020.0020.00
5.755.755.75
YS2048YS2048YS2060
LT2048S or FLT2048S or FLT2060S or F
EZB2048REZB2048REZB2060R
EZT2048S or FEZT2048S or FEZT2060S or F
JD, HJDJDC(V)
EHD, FD, HFD,EDB, EDS, ED,EDH (V)
183042
60.0072.0072.00
20.0020.0020.00
5.755.755.75
YS2060YS2072YS2072
LT2060S or FLT2072S or FLT2072S or F
EZB2060REZB2072REZB2072R
EZT2060S or FEZT2072S or FEZT2072S or F
400 Ampere MaximumMain Lugs orMain Breaker
DK, KD, HKD,KDC(V)
———
183042
60.0060.0072.00
20.0020.0020.00
5.755.755.75
YS2060YS2060YS2072
LT2060S or FLT2060S or FLT2072S or F
EZB2060REZB2060REZB2072R
EZT2060S or FEZT2060S or FEZT2072S or F
Main Lugs or Main Breaker with 225 A Thru-Feed Lugs or Sub- Feed Breaker
DK, KD, HKD,KDC(V)
EHD, FD, HFD,EDB, EDS, ED,EDH (V)
183042
60.0072.0072.00
20.0020.0020.00
5.755.755.75
YS2060YS2072YS2072
LT2060S or FLT2072S or FLT2072S or F
EZB2060REZB2072REZB2072R
EZT2060S or FEZT2072S or FEZT2072S or F
Main Lugs or Main Breaker with 400 A Thru-Feed Lugs or Sub- Feed Breaker
DK, KD, HKD,KDC(V)
JD, HJD, JDC,DK, KD,HKD, KDC(V)
183042
72.0090.0090.00
20.0020.0020.00
5.755.755.75
YS2072YS2090YS2090
LT2072S or FLT2090S or FLT2090S or F
EZB2072REZB2090REZB2090R
EZT2072S or FEZT2090S or FEZT2090S or F
Catalog Number Dimensions in mm
YS Box EZ Box Height Width Depth
YS2036YS2048YS2060YS2072YS2090
EZB2036REZB2048REZB2060REZB2072REZB2090R
914.41219.21524.01828.82286.0
508.0508.0508.0508.0508.0
146.1146.1146.1146.1146.1
July 2007
CA08101001E For more information visit: www.eaton.com
14-45Panelboards
14
Pow-R-Line C PanelboardsBoxes and Trims
Boxes and Trims Only — Type 1Table 14-49. Types PRL1a, PRL2a and PRL3a (400 Amperes Maximum)
� EZ box must be used with EZ trim.
Table 14-50. Type PRL3a (600 Amperes)
� EZ box must be used with EZ trim.
Table 14-51. Type PRL3a (800 Amperes)
Box Dimensions Height YS Box LT Trim EZ Box � EZ Trim �
Inches mm CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
20.00-inch W x 5.75-inch D(508.0 mm W x 146.1 mm D)
36.0042.0048.0060.0072.0090.00
914.41066.81219.21524.01828.82286.0
YS2036YS2042YS2048YS2060YS2072YS2090
LT2036S or FLT2042S or FLT2048S or FLT2060S or FLT2072S or FLT2090S or F
EZB2036REZB2042REZB2048REZB2060REZB2072REZB2090R
EZT2036S or FEZT2042S or FEZT2048S or FEZT2060S or FEZT2072S or FEZT2090S or F
Box Dimensions Height YS Box LT Trim EZ Box � EZ Trim �
Inches mm CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
20.00-inch W x 5.75-inch D(508.0 mm W x 146.1 mm D)
36.0048.0060.0072.0090.00
914.41219.21524.01828.82286.0
YS2036YS2048YS2060YS2072YS2090
LTV2036S or FLTV2048S or FLTV2060S or FLTV2072S or FLTV2090S or F
EZB2036REZB2048REZB2060REZB2072REZB2090R
EZTV2036S or FEZTV2048S or FEZTV2060S or FEZTV2072S or FEZTV2090S or F
Box Dimensions Height YS Box LT Trim
Inches mm CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
28.00-inch W x 5.75-inch D(711.2 mm W x 146.1 mm D)
36.0048.0060.0072.0090.00
914.41219.21524.01828.82286.0
YS2836YS2848YS2860YS2872YS2890
LTV2836S or FLTV2848S or FLTV2860S or FLTV2872S or FLTV2890S or F
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9
July 2007
CA08101001E For more information visit: www.eaton.com
14-63Panelboards
14
Pow-R-CommandBranch Circuit Breakers
BABRP Remote Control Circuit Breaker GHBS Remote Control Circuit Breaker
Table 14-126. Branch Circuit Breakers — 480Y/277 Volt Maximum
� 1-pole breaker rated 120 Vac. 2-pole breaker rated 120/240 Vac.� 1-pole breakers are rated 277 Vac maximum. 2- and 3-pole breakers are rated 480Y/277 Vac maximum.� 50 ampere devices are available as 2-pole only.� GFCI for 5 mA personnel protection.� GFP for 30 mA equipment protection.� Arc fault circuit breaker.� Arc fault circuit breaker with GFCI. For use on 480Y/277 Vac maximum.� Maximum lug size, 4/0 AWG Al/Cu in 20-inch (508.0 mm) wide box. 300 kcmil lug available in 28-inch (711.2 mm) wide box.
AmpereRating
Interrupting Rating(kA Symmetrical)
BreakerType
Price U.S. $
Breaker Provisions Only Space Only
240 Volt 480 Volt 1-Pole 2-Pole 3-Pole 1-Pole 2-Pole 3-Pole 1-Pole 2-Pole 3-Pole
Remote Controllable Branch Circuit Breakers 15 – 30 15 – 30 15 – 20 15 – 30
10 10 65 65
—— 14 14
BABRP �
BABRSP �
GHQRSP �
GHBS �
Conventional Branch Circuit Breakers — Not Controllable 15 – 60 15 – 60 70 70 80 – 100 80 – 100 15 – 50 � 15 – 50 � 15 – 20 15 – 20
10 10 10 10 10 10 10 10 10 10
——————————
BAB �
BAB-HBAB �
BAB-HBAB �
BAB-HQBGF �QBGFEP �QBAF �QBAG �
15 – 20 15 – 20 25 – 60 70 – 100
65 65 65 65
14 14 14 14
GHQ �
GHB �
GHB �
GHB �
15 – 60 70 – 100
18 18
14 14
EHDEHD
15 – 60 70 – 100110 – 150
18 18 18
14 14 14
FDBFDBFDB
15 – 60 70 – 100110 – 225
65 65 65
35 35 35
FD �FD �FD
15 – 60 70 – 100110 – 225
100100100
65 65 65
HFD �HFD �HFD
15 – 60 70 – 100110 – 225
200200200
100100100
FDCFDCFDC
100 – 225100 – 225100 – 225100 – 225100 – 225
22 42 65100200
—————
EDBEDSED �
EDH �
EDC �
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9
July 2007
14-64
For more information visit: www.eaton.com CA08101001E
Panelboards
14
Pow-R-CommandApplication Description
Figure 14-14. Pow-R-Command PRC100 Layout� All F-Frame branch breakers must be
mounted above (top) of all controllable breakers on the chassis.
� EDB, EDS, ED, EDH and EDC branch mounted breakers may be mounted with load lugs on either left or right. Specify on order.
� All add-on branch spaces must be adjacent to smart chassis poles.
� GHBS, GHQRSP and GHB breakers cannot be mixed on same chassis with BABRP, BABRSP and BAB breakers.
� Top-mounted main — only.
1-Pole � 1-Pole � 1X EHD
2-Pole � 2-Pole � 2X FDBFD
1-Pole � 3-Pole � 3X HFDFDC2-Pole �
2-Pole �� 2X EDB, EDS, ED, EDHEDC
3-Pole �� 3X EDB, EDS, ED, EDHEDC
5X12 Poles10X24 Poles
BABRPBABRSPBABGHBSGHQRSPGHB��
13XSmart Chassisincludes spacesfor 18 PolesGHBS, GHQRSP, GHB, BABRP, BABRSP, BAB��
Smart Chassis isalways located at thebottom of thepanelboard chassisimmediately below all GHBS/GHB or BABR/BABRS/BAB breakers.
Neutral Section 5X 100 – 250 A8X 400 A
Main Lug Section 2X 100 A5X 250 A8X 400 A
Main DeviceHorizontally Mounted
See branch mounted —EHD, FD, FDB,HFD, FDC, EDB, EDS, ED, EDH, EDC above
Main DeviceVertically Mounted
7X — EHD, FDB, FD,HFD, FDC, EDB, EDS,ED, EDH, EDC
7X — 100 AClass T fusible pullout
9X — 200 AClass T fusible pullout
9X — FB-P �
14X — JD, HJD, JDC
15X — DK, KD, HKD,KDC
Pow-R-CommandSmart Chassis and
18 Pole Spaces
ckt13579
11131517
ckt24681012141618
PRC100 Panel Layout Instructions1. Select:
a. Smart Chassis from Figure 14-14.
Note: Smart chassis is always located at the bottom of the panelboard chassis immediately below the bottom breaker.
b. Required mains(lugs, breaker or fuse pullout).
c. Appropriate neutral.d. Branch breakers and additional
chassis space, as needed.
2. Layout panel as shown inFigure 14-14, using appropriate “X” units. Total “X” units deter-mine box height shown in Table 14-127. (When total “X” units exceeds the number shown, use next size box size.
Layout Example1. Panel description:
a. Pow-R-Command, 3-phase, 4-wire 480Y/277 Vac, inter-rupt-ing rating of 14,000 AIC sym-metrical, 250 ampere main lugs only at bottom, surface mounted and the following branch breakers:
b. 36 – 20 ampere, 1-pole GHBS.c. 6 – 20 ampere, 1-pole GHBS
spaces.
2. Layout information from Figure 14-14:
a. Smart Chassis . . . . . . . . . = 13Xb. 24 circuit
add-on chassis. . . . . . . . . = 10Xc. 250 ampere Neutral. . . . . = 5Xd. 250 ampere Main
Lugs only . . . . . . . . . . . . . = 5XTotal Panelboard Height . . . . . . . . . . . . . . . . = 33X
3. From Table 14-127:33X Height (use 40X box).
Box Catalog Number . . . . . . . . .YS2072Trim Catalog Number . . . . . . . LT2072SORBox Catalog Number . . . . . . EZB2072RTrim Catalog Number . . . . . .EZT2072S
Table 14-127. Box Tabulation
CabinetsFronts are code-gauge steel, ANSI-61 light gray painted finish.
Boxes are code-gauge galvanized steel without knockouts. Standard depth is 5.75 inches (146.1 mm). Standard width is 20.00-inch (508.0 mm) 100 – 400 amperes.
Top and Bottom Gutters5.50 inches (139.7 mm) minimum.
Side Gutters4.00 inches (101.6 mm) minimum.
“X”Units
Box Height YS BoxCatalogNumber
LT TrimCatalogNumber
EZ BoxCatalogNumber
EZ TrimCatalogNumber
Inches mm
100 – 400 Amperes23X31X40X53X
48.0060.0072.0090.00
1219.21524.01828.82286.0
YS2048YS2060YS2072YS2090
LT2048S or FLT2060S or FLT2072S or FLT2090S or F
EZB2048REZB2060REZB2072REZB2090R
EZT2048S or FEZT2060S or FEZT2072S or FEZT2090S or F
July 2007
14-86
For more information visit: www.eaton.com CA08101001E
Panelboards
14
Pow-R-Stock Plus ProgramProgram Features
Pow-R-Stock Plus Offering two options to meet the demanding schedule requirements of today's customers.
Type PRL1a Panelboard
■ Factory-assembled panelboards available from your local satellite plant in 24 to 72 hours.
■ Unassembled panelboards in stock at authorized Pow-R-Stock Plus distributors.
The Product OfferingPow-R-Stock Plus panels, available either as factory-assembled or as unassembled from distributor stock, are based on the most frequently ordered panelboards, including:
■ 120/240 volt, 208Y/120 volt, and 480Y/277 volt ratings.
■ 100 through 400 ampere mains.■ Single- and 3-phase.■ Surface and flush mounted.■ Aluminum or copper bus.■ Type 1 or Type 3R enclosures.■ Service Entrance available.■ Options for 200% neutrals and
isolated ground bars.■ Full menu of branch breakers
available.
Factory-Assembled Panelboard OptionThe Pow-R-Stock Plus factory-assembled panelboard option offers key advan-tages over programs that offer only unassembled panelboards.
Reduced Installation Time■ Unassembled panelboards must be
assembled at the job site before the true installation process can begin, adding time and labor cost to the process. Pow-R-Stock Plus assem-bled panelboards are ready to install the moment they arrive at the job site.
Reduced On-Site Material Handling■ A typical 42 circuit unassembled pan-
elboard has a minimum of 46 parts to receive and handle, taking up valu-able time at the job site. A Pow-R-Stock Plus assembled panelboard is just one item to receive and handle (two if the box is shipped ahead).
Factory Warranty■ Field assembly of unassembled
panelboards adds to contractor war-ranty responsibility. Pow-R-Stock Plus assembled panelboards carry a full factory warranty.
Simplicity■ Order your Pow-R-Stock Plus Panel-
board by description and it will arrive at the job site complete. No need to worry about matching catalog num-ber kits at the job site or chasing after miscellaneous parts and pieces.
Contact your local satellite plant (see next page for a listing) for more infor-mation on the Pow-R-Stock Plus factory-assembled panelboard option.
Pow-R-Stock Plus Program Includes the EZ Trim and EZ Box
Unassembled Panelboard Option
Pow-R-Line 1a and 2a Panelboards are Designed to Provide Application Flexibility with Off-the-Shelf Service
The Pow-R-Stock Plus unassembled panelboard interior is designed specif-ically for distributor stock and field assembly. Its modular design allows for easy configuration in the field.
Top or bottom incoming, main lugs or main breaker...all with the same Pow-R-Stock Plus unassembled interior. Lug and breaker kits provide greater flexibility with fewer boxes, interiors and trims to stock.
Color-Coded Package LabelsThe box, interior and trim packaging are clearly identified with brightly colored labels (a different color for each box size). This facilitates stocking, filling orders, and matching components in the field.
Contact your local Eaton distributor for more details on the Pow-R-Stock Plus unassembled panelboard option.
Eaton DistributorsContact your Eaton sales engineer or local satellite manager and arrange to review the program details and criteria for qualification as a Pow-R-Stock Plus distributor.
July 2007
CA08101001E For more information visit: www.eaton.com
14-87Panelboards
14
Regional Manufacturing FacilitiesManufacturing Locations
Figure 14-22. Manufacturing Plant Locations
Main PlantSumter11 Corporate CircleP.O. Box 2258Sumter, SC 29150(803) 481-3131
Satellite PlantsAtlanta7000 Highlands Parkway SE Suite 102Smyrna, GA 30082Fax (770) 433-1863Phone (678) 309-4260
Baltimore6671 Santa Barbara CourtSuite FElk Ridge, MD 21227Fax (410) 796-7755Phone (410) 796-7777
Chicago959 AEC DriveWood Dale, IL 60191Fax (630) 860-3569Phone (630) 860-3500
Cleveland5565 Venture DriveUnit BParma, OH 44130Fax (216) 433-0545Phone (216) 433-0616
Dallas631 Westport ParkwaySuite 100Grapevine, TX 76051Fax (817) 251-6249Phone (817) 251-6797
Denver14101 East 33rd PlaceSuite FAurora, CO 80011Fax (303) 366-9993Phone (303) 366-2080
Hartford625 Day Hill RoadWindsor, CT 06095Fax (860) 688-4982Phone (860) 688-5330
Houston10810 West Little YorkSuite 100Houston, TX 77041Fax (713) 688-3764Phone (713) 688-8430
Los AngelesElectrical Group — Satellite11120 Philadelphia StreetMira Loma, CA 91752Fax (951) 685-3775Phone (951) 685-5788
New Jersey96 Stemmers LaneWestampton, NJ 08060Fax (609) 835-4777Phone (609) 835-4230
Orlando3827 St. Valentine WayOrlando, FL 32811Fax (407) 841-9135Phone (407) 843-3863
Phoenix921 South Park LaneTempe, AZ 85281Fax (480) 449-4223Phone (480) 449-4222
Raleigh2933 S. Miami BoulevardSuite 111Durham, NC 27703Fax (919) 572-9751Phone (919) 544-7074
St. Louis12947 Gravois RoadSt. Louis, MO 63127Fax (314) 842-2552Phone (314) 842-7662
San Francisco20923 Cabot BoulevardHayward, CA 94545Fax (510) 784-8980Phone (510) 784-8981
Seattle1604 15th Street SWSuite 114Auburn, WA 98001Fax (253) 833-5058Phone (253) 833-5021
•
•
•••
••• •
••
★•
•
•
SEATTLE
SAN FRANCISCO
LOS ANGELES
DENVER
DALLAS
HOUSTON
CHICAGO
BALTIMORELL
ATLANTAA ATT
ST. LOUIS
HARTFORD
SUMTER
CLEVELAND
•RALEIGH
•PHOENIX
RLANDOOR
EW JERSEYNE
July 2007
14-88
For more information visit: www.eaton.com CA08101001E
Panelboards
14
Regional Manufacturing FacilitiesSatellites
SatellitesA unique concept of facilities close to customer locations, assuring fast delivery of standard and custom- assembled equipment when it’s needed.
Located at strategic locations through-out the United States, these facilities manufacture and deliver standard or custom-assembled panelboards, switchboards and enclosed circuit breakers…when and where you need them. And, when you have an emergency, they can have your equipment ready in hours.
Highly trained and experienced personnel will manage your order and ensure that you receive on-time delivery of high quality equipment that meets your specifications.
Special ConfigurationsThe unique capabilities of these plants and people can provide solutions for special products to meet special needs.
Typical examples include special dimensions, retrofit equipment and panelboard interiors to fit existing boxes.
Speedy Delivery■ Panelboards: from one to five days.■ Switchboards: between five and
10 days.■ Assembled Enclosed Circuit Breakers:
from one to 10 days.
Save Time and MoneyNo matter your location, you will save time and money when ordering from a satellite. For more information, contact your Eaton representative or authorized distributor.
Cutler-Hammer is a federally registered trademark of Eaton Corporation. CSA is a registered trademark of the Canadian Standards Association. National Electrical Code and NEC are registered trademarks of the National Fire Protection Association, Quincy, Mass. Uniform Building Code (UBC) is a trademark of the International Conference of Building Officials (ICBO). UL is a federally registered trademark of Underwriters Laboratories Inc. NEMA is the registered trademark and service mark of the National Electrical Manufacturers Association. Micarta is a registered trademark of Micarta Industrial Composites. Windows is a registered trademark of Microsoft Corporation.
Ú±® ³±®» ·²º±®³¿¬·±² ª··¬æ ©©©ò»¿¬±²»´»½¬®·½¿´ò½±³ ÎÐðïìððððïÛ
λ²»©¿´ п®¬Ð¿¹» îî Ûºº»½¬·ª»æ Ú»¾®«¿®§ îððì
Ý«®®»²¬ Ý«¬´»®óØ¿³³»® п²»´¾±¿®¼
ÐÎÔí¿ ÚóÚ®¿³» ر®·¦±²¬¿´´§ Ó±«²¬»¼ ݱ²²»½¬±® Õ·¬ ß»³¾´·»
Ì¿¾´» îíò ݱ²²»½¬±® Õ·¬ ß»³¾´·»
ÚóÚ®¿³» ¼»ª·½» ®¿¬»¼ ¿¾±ª» ïëð ¿³°»®» ³«¬ ¾» ·²¹´» ³±«²¬»¼ò Ò± ¬©·² ³±«²¬·²¹ ¿½½»°¬¿¾´»ò
ݱ²²»½¬±® µ·¬ ½±²¬¿·² °¸¿» ½±²²»½ó¬±®ô ¼»¿¼º®±²¬ ½±ª»®ô ¸¿®¼©¿®» ¿²¼ ·²¬®«½¬·±² ¬± ³±«²¬ ¾®»¿µ»®ò Ñ®¼»® ¾®»¿µ»® »°¿®¿¬»´§ ©¸»² ±®¼»®·²¹ ½±²²»½¬±® µ·¬ò
ÕÐÎÔíßÚÜí
Ü»ª·½» Ý·®½«·¬±® б´»
íóи¿» ïóи¿» Ò±¬»
Ý¿¬¿´±¹ Ò«³¾»® и¿» Ý¿¬¿´±¹ Ò«³¾»® и¿»
ÛØÜô ÚÜô ÚÜÞôØÚÜô ÚÜÝøïëð ß³°»®» Ó¿¨·³«³ Ì©·² Ó±«²¬÷
íóб´» Þ®»¿µ»®îóб´» Þ®»¿µ»®ïóб´» Þ®»¿µ»®
ÕÐÎÔíßÚÜíÕÐÎÔíßÚÜîÕÐÎÔíßÚÜï
ßñÞñÝßñÝßñÝ
OÕÐÎÔíßÚÜîÕÐÎÔíßÚÜï
OßñÝßñÝ
øî÷ ïëð ß³°»®» Ü»ª·½» Ó¿¨·³«³
ÚÜô ØÚÜô ÚÜÝô
ÛÜô ÛÜØô ÛÜÝøïéë P îîë ß³°»®» Í·²¹´» Ó±«²¬÷
íóб´» Þ®»¿µ»®
îóб´» Þ®»¿µ»®
ÕÐÎÔíßÛÜíÕÐÎÔíßÛÜî
ßñÞñÝ
ßñÝ
OÕÐÎÔíßÛÜî
O
ßñÝ
øï÷ îîë ß³°»®» Ó¿¨·³«³ Í·²¹´» Ó±«²¬»¼
PDF created with pdfFactory Pro trial version www.pdffactory.com
For more information visit: www.eatonelectrical.com RP01400001E
Renewal PartsPage 18 Effective: February 2004
Current Cutler-Hammer Panelboards
PRL1a, 2a Deadfront CoversNote: Does not apply to PRL4 sub-chassis.
Table 18. Horizontally Mounted Devices
� Order the basic drawing number, along with the equivalent H–number that’s needed(example 1C96619H01).
1C96619H01 1C96620H01
MountingArrangement
Device/Frame
DrawingNumber �
Branch CircuitQuantity
ItemNumber
QuantityRequired
Horizontal BA, BAB, QBH,QBGF, QBHGF,QBGFEP,QBHGFEP
1C96619 121830
H01H02H04
111
424854
H06H03H03 and H04
121 Each
7296
H05H07
22
GB, GHB, GHQ, GHBS
1C96620 121830
H01H02H04
111
424854
H06H03H03 and H04
121 Each
7296
H05H07
22
Table 19. Filler Covers
� Filler covers are required in addition to deadfront cover whenever MLO, SFL or TFL are specified.
� Filler covers are required in addition to deadfront cover whenever a branch provision is specified.
5155C62H01
4180B52H01
Device/Frame DrawingNumber
ItemNumber
F, J, K � 4180B52 H01
QUICKLAG, GB, GHB �
5155C62 H01
RP01400001E For more information visit: www.eatonelectrical.com
Renewal PartsEffective: February 2004 Page 19
Current Cutler-Hammer Panelboards
Panelboard Trim LocksPanelboard trims use different trim locks, see pictures below for styles and part numbers. Contact your nearest Satellite for availability on the styles listed below. See Page 4 for Satellite listings.
Table 20. Panelboard Trim LocksDescription Catalog
Number
For use on left-handed door. (Hinged on left side.) K80522
For use on right-handed door. (Hinged on right side.) K80133
T–Handle lock, at one time used on all trims over 48.00 inches (1219.2 mm) in height. Also used on outdoor NEMA 12/3R trims.
K80429
Used on PRL4 lighting and power panels as standard. 1A32258H03
Used on PRL1, 2, 3 and PRL1a, 2a, 3a lighting panels as standard. WEM 2 key.
5155C81G01
K80522K80133
K80429
1A32258H03 5155C81G01