Lightning Protection of Buildings: Guidance to MS IEC ... · Promoting Research, Applications and Education on Lightning Lightning Protection of Buildings: Guidance to MS IEC 62305

Post on 21-Jan-2021

10 Views

Category:

Documents

1 Downloads

Preview:

Click to see full reader

Transcript

PromotingResearch,ApplicationsandEducationonLightning

LightningProtectionofBuildings:GuidancetoMSIEC62305andUpdatesfrom

WorkingGroup/ResearchInstitute

ProfessorMohdZainalAbidinAbKadir,PhDPEngCEngCELPUPMChair,IECTC81:LightningProtection(NationalMirrorComm)ImmediatePastChair,IEEEPESMalaysiaChapterChair,MNC-CIGREC4:SystemTechnicalPerformanceWGCommittee:IEEE1410;CIGREC4.23,C4.27

- seen at few hundred meters - less than 1 m to over 1 km

Flashover

Return stroke current

Channel Base

Current Striking

Distance

Coupling

Electromagnetic Field

P

z

2

PromotingResearch,ApplicationsandEducationonLightning

THECIRCULAR

3

PromotingResearch,ApplicationsandEducationonLightning

THEGUIDEBOOK

4

MSIEC62305(2007)

•  MSIEC62305-1:2007-Generalprinciples

•  MSIEC62305-2:2007-Riskmanagement

•  MSIEC62305-3:2007-Physicaldamagetostructuresandlife hazard

•  MSIEC62305-4:2007-Electricalandelectronicsystemswithin structures

PromotingResearch,ApplicationsandEducationonLightning5

PromotingResearch,ApplicationsandEducationonLightning

§ OriginsofLightningProtectionSystems§ GeneralPrinciple§ RiskAssessment§ LightningProtectionSystem§ SurgeProtection§ InspectionandMaintenanceofLPS§ UpdatesfromWG/ResearchInst.§ ConcludingRemarks

PRESENTATIONOUTLINES

6

7

ORIGINSOFLIGHTNINGPROTECTION

PromotingResearch,ApplicationsandEducationonLightning

- Earliestliteratureavailable:1752(BenjaminFranklin)- He consequently published the first instruction for lightningprotection:

“Themethodisthis:Provideasmallironrod(maybemadeoftherodironusedbytheNailers)butofsuchlength,thatoneendbeingthreeorfourfeetinthemoistground,theothermaybesixoreightfeetabovethetallestpartofthebuilding.Totheupperendoftherod,fastenaboutafootofbrasswire,thesizeofacommonknittingneedle,sharpenedtoafinepoint;therodmaybesecuredtothehousebyafewsmallstaples.Ifthehousebelong,theremaybearodandpointeachendandamiddlingwirealongtheridgefromoneto theother.Ahousethus furnishedwillnotbedamagedbylightning, itbeingattractedbythepointsandpassingthroughthemetalintothegroundwithouthurtinganything..”[1][1] B Franklin. “How to secure houses from lightning”, Poor Richards’s Almanac,reproduced in Benjamin Franklin’s Experiments, edited by I. Bernard Cohen,HarvardUniversityPress,1941.

8 PromotingResearch,ApplicationsandEducationonLightning

Earlyfieldtrialsandinvestigationoffailures:BoardHouseatPurfleet,Essex,England

- Reported by Nickson [2] where lightning protection was installed and struck shortly thereafter. Yet the lightning rod was not struck. - Investigation revealed another metallic object was struck and lightning conducted to ground. - This incident caused the first reconsideration of lightning protection technology and it’s techniques.

[2] E Nickson (Store-keeper at Purfleet), “XV. Sundry papers relative to an accident from lightning at Purfleet, May 15, 1777. Report to the Secretary of the Royal Society”. Phil. Trans., Royal Soc., LXVIII, for 1778, Part. 1, pp 232-235.

9 PromotingResearch,ApplicationsandEducationonLightning

KnowledgegainedfromPurfleetincident

- Lightning-damaged corner of the Board House was not adequately protected by the closest lightning rod, installed above the centre of the 44-foot (13.5m) high building with a tip-height of 27 feet (~8m) above and horizontal distance of 37 feet (~11m) from the lightning strike point [3]. - This incident drove the first recommendations for lightning protection systems concerning bonding of incidental metal and the first consideration concerning the effective range of strike terminations. It also set off the blunt vs. pointed air terminal arguments.

[3] RH Golde, “Lightning”, Vol. 2, Academic Press London, 1977, pp 546 provides a pictorial description of Purfleet..

10 PromotingResearch,ApplicationsandEducationonLightning

11

GENERALPRINCIPLE

PromotingResearch,ApplicationsandEducationonLightning

PromotingResearch,ApplicationsandEducationonLightning

Thepropagationofadownwardsteppedleaderandtheinterceptionwithatreeonearth

12

13 PromotingResearch,ApplicationsandEducationonLightning

The short stroke current (impulse) asspecifiedinMSIEC62305-1-2007

The long stroke current (continuingc u r r e n t ) s p e c i fi ed i n MS I E C62305-1:2007. Tlong can vary between 2msto1000ms.

LightningCurrent

Comparisonofreturn-strokepeakcurrents(thelargestpeak,inkA)forfirststrokesinnegativedownwardlightning

References Location Sample size

Percent exceeding tabulated value σlogI (base

10)

Remarks

95% 50% 5%

Berger et al. (1975) Switzerland 101 14 30 (~30) 80 0.26 Direct measurements on 70-m towers

Anderson and Eriksson (1980)

Switzerland

80 14 31 69 0.21 Direct measurements on 70-m towers

Dellera et al. (1985) Italy 42 - 33 - 0.25 Direct measurements on 40-m towers

Geldenhuys et al. (1989)

South Africa 29 7* 33 (43) 162* 0.42 Direct measurements on a 60-m mast

Takami and Okabe (2007)

Japan 120 10 29** 85 0.28** Direct measurements on 40- to 140-m transmission-line towers

Visacro et al. (2011) Brazil 38 21 45 94 0.20 Direct measurements on a 60-m mast

Anderson and Eriksson (1980)

Switzerland (N=125), Australia (N=18), Czechoslovakia

(N=123), Poland (N=3), South Africa (N=11), Sweden (N=14),

and USA (N=44)

338 9*

30 (34) 101*

0.32 Combined direct and indirect (magnetic link) measurements

CIGRE Report 63 (1991)

Switzerland (N=125), Australia (N=18), Czechoslovakia

(N=123), Poland (N=3), South Africa (N=81), Sweden (N=14),

and USA (N=44)

408 - 31 (33) - 0.21 Same as Anderson and Eriksson’s (1980) sample plus 70 additional measurements from South Africa

The95%,50%,and5%valuesaredeterminedusingthelognormalapproximationtotheactualdata,with50%valuesintheparenthesesbeingbasedontheactualdata.σlogIisthestandarddeviationofthelogarithm(base10)ofpeakcurrentinkA.*AsreportedbyTakamiandOkabe(2007).**26kAand0.32aftercompensationforthe9-kAlowermeasurementlimit.

14

PromotingResearch,ApplicationsandEducationonLightning

MSIEC62305-2:2007page87,AnnexA,specifyapproximaterelationshipofthelightningdensityNgwithkerauniclevelthunderdaysTdfortemperatelandonly.Ng=0.1Td

whereNgisthegroundflashdensityinflashesperkm2peryearTdisthenumberofdayswiththunderperyear

LightningSeverity

15

3-5% Direct Strike 1-2% Contact Injury 30-35% Side Splash / Flash 50-55% Ground Current 10-15% Upward Streamer

InjuryMechanisms

PromotingResearch,ApplicationsandEducationonLightning16

17 PromotingResearch,ApplicationsandEducationonLightning

LightningInjuries/Fatalities

Basedonthenoofvictims*

*AsofSept2015

Year Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total2008 3 0 0 3 3 2 0 0 0 0 9 0 202009 0 0 0 0 13 6 0 0 0 8 0 5 322010 0 0 0 2 0 0 0 0 9 2 0 0 132011 1 2 1 0 0 3 3 12 2 1 4 1 302012 0 5 1 56 7 1 5 5 1 0 5 0 862013 0 12 1 2 0 0 2 1 2 0 0 0 202014 0 0 4 1 2 0 0 0 0 2 2 0 112015 0 0 0 12 4 0 1 1 5 0 0 0 23Total 4 19 7 76 29 12 11 19 19 13 20 6 235

NO PLACE OUTSIDE is safe when

thunderstorms are in the area

LightningSafety

PromotingResearch,ApplicationsandEducationonLightning

www.celp.upm.edu.my

19

LIGHTNINGRISKASSESSMENT

PromotingResearch,ApplicationsandEducationonLightning

20 PromotingResearch,ApplicationsandEducationonLightning

Ø To reduce the potential for damage effectively andeconomically.

Ø The general steps in risk assessment analysis are described inbelow:v Damageandlossesv Riskanditscomponentsv Riskassessmentv Riskmanagement

PromotingResearch,ApplicationsandEducationonLightning

AdoptedfromMSIEC62305-2:2007Section5.5

22

LIGHTNINGPROTECTIONSYSTEM

PromotingResearch,ApplicationsandEducationonLightning

23 PromotingResearch,ApplicationsandEducationonLightning

BasicConcept

24 PromotingResearch,ApplicationsandEducationonLightning

R

α H

Protective angle

Rolling sphere

Mesh

AirTerminationSystem

25 PromotingResearch,ApplicationsandEducationonLightning

ProtectiveAngleMethod

26 PromotingResearch,ApplicationsandEducationonLightning

MeshMethod

PromotingResearch,ApplicationsandEducationonLightning

RollingSphereMethod

Ø Rollingspheremethodissuitableforanytypeofbuilding,especiallyhighrisebuildingwithcomplexplan.

Ø ShouldconsideranimaginarysphereofradiusRwherethevalueofRdependsonthelevelofprotection

PromotingResearch,ApplicationsandEducationonLightning

RollingSphereMethod

h<60m

h>60m

Anobjectwithisolatedverticalrods;minheightoftheverticalrod=h+p

PromotingResearch,ApplicationsandEducationonLightning

AirTermination:MaterialsandDimension

PromotingResearch,ApplicationsandEducationonLightning

§  Thereareseveralavailablematerialsthatcanbeusedintheconstructionofairterminationsystem,aslongastheyfulfillsomecriteriasuchas;

§  Non-corrosive(materialstobecombined)§  Compliancewithmincross-sectionaldimensions§  Compliancewithminthickness

PromotingResearch,ApplicationsandEducationonLightning

Material Hot-dip GI

Aluminum Copper SS Mild Steel

Hot-dip GI ✔ Possible

✖ Possible Possible

Aluminum Possible ✔ ✖ Possible

✖ Copper

✖ ✖ ✔ Possible ✖

SS Possible Possible Possible ✔ Possible

Mild steel Possible ✖ ✖ Possible

Suitabilityofmaterialsforinterconnection

MaterialThickness(mm)

Ifpuncturingshouldbeavoided

Thickness(mm)Ifpuncturingis

acceptableGIandStainlessSteel 4 0.5

Aluminum 7 0.7Copper 5 0.5Zink Notrecommended 0.7

Titanium 4 0.5

PromotingResearch,ApplicationsandEducationonLightning

Minimumthicknessofbuildingcomponentsthatcanbeusedasapartof the air termination system. Note that these specifications areindependentoftheLevelofProtection

DownConductor

PromotingResearch,ApplicationsandEducationonLightning

§  Shouldconsider:

§  Minnoofdownconductor(i.e.2)§  Position§  Separation§  Bending§  Safetyclearence(mandatorytocoverthefirst1.5mlength

abovethegroundwithaninsulationmaterialtoavoidtouchpotential)

§  Accessibilityforinspection§  Naturalcomponents(Section3.5,MSIEC62305-3:2007)

KEY: (1) Air termination rod; (2) Horizontal air termination conductor; (3) Down-conductor; (4) T-type joint; (5) Cross type joint; (6) Connection to steel reinforcement rods; (7) Test joints; (8) Type B earthing arrangement, ring earth electrode; (9) Flat roof with roof fixtures; (10) T-type joint-Corrosion resistant

PromotingResearch,ApplicationsandEducationonLightning

35 PromotingResearch,ApplicationsandEducationonLightning

EarthTerminationSystem

§  todispersedthelightningcurrentintothemassoftheearth.

§  toreduceanypotentiallydangerousovervoltages.

§  Ingeneral,anearthingresistancebelow10Ω,measuredatlowfrequency,isrecommended.

§  From the view point of lightning protection, a single integrated earth-termination system ispreferableand is suitable forallpurposes, suchaslightningprotection,powersystemandtelecommunicationsystems.

§  Earth termination system shall be bonded to achieve a lightningequipotentialbondingtominimizetheaffectoflightningsideflashingandsteppotentialhazard.

PromotingResearch,ApplicationsandEducationonLightning

TypeA

Horizontal

Vertical

50cm

Electrodesthatareconnecteddirectlyattheendofthedownconductor

36

37 PromotingResearch,ApplicationsandEducationonLightning

Figure 28: The minimum length of Type A electrodes (Adopted from MS IEC 62305-3:2007).

TheminimumlengthofTypeAelectrode(AdoptedfromMSIEC62305-3:2007).

38 PromotingResearch,ApplicationsandEducationonLightning

TypeB

§  TypeBarrangement compriseseither a ring conductor installedexternaltothestructuretobeprotected,incontactwiththesoilforatleast80%ofitstotallength,orafoundationearthelectrode.Suchearthelectrodesmayalsobemeshed.

§  Refer to MS IEC 62305-3:2007, Section 5.4.2.2 for determining thespecificationsofTypeBarrangement.

39 PromotingResearch,ApplicationsandEducationonLightning

Generalguidancefortheselectionofmaterialforearthingsystem(AdoptedfromMSIEC62305-3:2007)

Confi

guratio

nan

dminim

umdim

ension

sofearthelectro

des

(MSIEC62

305-3:20

07pag

e55

)

40

41 PromotingResearch,ApplicationsandEducationonLightning

BackfillMaterial

§  Commonpracticetoreducetheearthresistance.

§  Fewsuchmaterialsarebentoniteandbentonite-basedcompounds,cokebreeze,graphiteandlime.

§  Fordetailsoftheselectionandusageofperformanceenhancementmaterials of earthing systems, refer IEC 62561-7 (2011): Lightningprotection system components (LPSC) - Part 7: Requirements forearthingenhancingcompounds.

42 PromotingResearch,ApplicationsandEducationonLightning

LightningProtectionMeasures(LPM)

ZonalConceptMSIEC62305-3:2007,pp.25

43 PromotingResearch,ApplicationsandEducationonLightning

BasicLPM

a.Earthingandbonding

44 PromotingResearch,ApplicationsandEducationonLightning

Integration of electronicsystems into the bondingnetwork

45 PromotingResearch,ApplicationsandEducationonLightning

C o m b i n a t i o n o fintegrationmethod-Forcomplexsystem

46 PromotingResearch,ApplicationsandEducationonLightning

Minimumcross–sectionalareaforbondingcomponents

47 PromotingResearch,ApplicationsandEducationonLightning

b.Magneticshieldingandlinerouting

§  Arisefromlightningflashesdirecttoornearbythestructure.§  Spatial shieldsmaybe grid-like, or continuousmetal shields, or comprise

thenaturalcomponentsofthestructureitself.§  Shielding of internal lines: using metallic shielded cables, metallic cable

ductandmetallicenclosureofequipmentwillminimized internal inducedsurges.

§  Routinginternallines:tominimizeinductionloopsandreducethecreationof internal surges to the structure. The loop area can be minimized byrouting the cables close to natural components of the structure, whichhavebeenearthedandbyroutingelectricalandsignallinestogether.

§  Shieldingofexternallines:toreducesurgesfrombeingconductedontotheinternalsystems.·

§  Materials and dimensions of magnetic shields shall comply with therequirementsofMSIEC62305-3:2007

48 PromotingResearch,ApplicationsandEducationonLightning

c.CoordinatedSPDprotection§  To limits the effect of internal and external surges for both power and

signallines.

§  To share the energy between them according to their energy absorbingcapability.

§  ThecharacteristicsoftheindividualSPDsaspublishedbythemanufacturerneedtobeconsidered.

§  Theprimarylightningthreatisgivenbythethreelightningcomponents:

o  Thefirstshortstrokeo  Thesubsequentshortstrokeso  Thelongstroke

§  The energy coordination is needed to avoid SPDs within a system frombeingoverstressed.

49

SURGEPROTECTION

PromotingResearch,ApplicationsandEducationonLightning

50 PromotingResearch,ApplicationsandEducationonLightning

ForoptimumperformanceofSPDs;ü  Wiringsystem, starting fromthemainpanel, is according to the

nationalcodesofpractice.

ü  Electrical safety devices such as earth fault tripping devices(RCDs, RCCBs or ELCBs), over current tripping devices (MCBs,MCCBs or thermal fuses) and voltage stabilizing devices areproperlyinstalledandareingoodcondition

ü  Electrical system has a single earthing point (close to the mainpanel)withlowearthresistancewhenmeasuredatlowfrequencyattheearthpit,

ü  Power feeds to outdoor systems are confined into dedicateddistributionboards,

51 PromotingResearch,ApplicationsandEducationonLightning

For a productive and cost effective surge protection scheme thefollowingstepsshouldbetaken:ØSystemanalysisandriskassessmentØStrategiclocationselectionforprotectivedevicesØSelectionofappropriatelycoordinatedprotectivedevicesØProperinstallationandcommissioningØRegularmaintenanceandreplacementoffaultydevicesFor installation,abuilding isdivided intoseveralzonesofprotection(referMSIEC62305-4:2007Section4)

52 PromotingResearch,ApplicationsandEducationonLightning

SelectionofSPDsforpowersystems

§  Wheretoinstall:mainpanel,subpanels,plugetc.§  ImpulseCurrenthandingCapacity,Iimp

§  Letthroughvoltage(Voltageprotectionlevel),Up

§  Responsetime§  MaximumContinuousOperatingVoltage(MCOV)SelectionofSPDsoncommunicationanddatalines§  Systemoperatingcurrentandvoltage§  Bandwidthandinsertionlosses§  Noofpins(lines)&cabletype§  Plugtype

53

INSPECTIONANDMAINTENANCEOFLPS

PromotingResearch,ApplicationsandEducationonLightning

54 PromotingResearch,ApplicationsandEducationonLightning

Toascertainthat;Ø TheLPSconformstothedesignbasedonthisstandard

Ø All components of the LPS are in good condition andcapable of performing their designed functions, and thatthereisnocorrosion

Ø Any recently added services or constructions areincorporatedintotheLPS.

Objectives

55 PromotingResearch,ApplicationsandEducationonLightning

Inspectionsshouldbemadeasfollows:o  During the construction of the structure, in order to check the

embeddedelectrodes

o  AftertheinstallationoftheLPS

o  Periodically at such intervals as determined with regard to thenatureofthestructuretobeprotected,i.e.corrosionproblemsandtheclassofLPS

o  Afteralterationsorrepairs,orwhenitisknownthatthestructurehasbeenstruckbylightning.

Complete guidelines of inspection and maintenance of LPS is given in MS IEC 62305-3:2007 Section 7 and Section E7

56 PromotingResearch,ApplicationsandEducationonLightning

Maintenance

Regular Inspection is among the fundamental conditions forreliable maintenance of an LPS. The property owner shall beinformedofallobservedfaultsandtheyshallberepairedwithoutdelay.Forfurtherdetailsofmaintenance,referSec7inMSIEC62305-3.

57

UPDATESFROMWG/RESEARCHINST.

PromotingResearch,ApplicationsandEducationonLightning

58 PromotingResearch,ApplicationsandEducationonLightning

§  LPSWG: Newly approved TC 81 (NationalMirror Committee) byISCECommitteeinJune2015

§  Lightning Safety: Recent Strategic Meeting in Lusaka, Zambia,organizedbyNAMS&T.Fromthismeeting;o  A Resolution for Declaration of the International Lightning

Safety Day on 28th June every year, which was unanimouslyadopted by the participants of the International Symposiumand Strategic Meeting on Lightning Protection, has beensubmittedtoUNESCO.

§  Technical Brochure: TB 549-2013: Lightning Parameters forEngineeringApplications,byWGC4.407

§  Seminar:School’sEnvironmentalSafety,organizedbyMinistryofEducationandattendedby120teachersinBesut,Terengganu.

59

CONCLUDINGREMARKS

PromotingResearch,ApplicationsandEducationonLightning

60 PromotingResearch,ApplicationsandEducationonLightning

² MSIEC62305seriesprovidecomprehensiveguidelinesonthedesignandinstallationofLPSforbuildings.

² The developed book is NOT a replacement to the existingstandards MS IEC 62305 but it is an easy guide to thosedocuments.

²  ItisalsoNOTjustasummaryofthosestandards,butprovideeasy access andquick reference to thedetaileddocuments,withsomeclearandusefulillustrations.

² Updates fromWG/ Research Inst. are useful and crucial forknowledgesharing,activityplanningandresearchprogressinlightning-relatedareas.

•  General Public: To understand the basic principles of lightningprotection

•  Engineers: To make sure that they design, select, install,superviseandenforceLPSwherethequalityandsafetyisinlinewithMSIEC62305(2007)

•  LPProviders:TounderstandtheacceptabilityandqualityoftheirsystemsareinlinewithMSIEC62305(2007)

•  LPSeekers:Tounderstandwhethertheygetthecorrectsystem

•  Management:Tounderstandwhethertheyapprovedthecorrectsystem

PromotingResearch,ApplicationsandEducationonLightning

OnGuidebook

61

62

PromotingResearch,ApplicationsandEducationonLightning

ContactUs:CentreforElectromagneticandLightningProtectionResearch(CELP)FacultyofEngineering,UPMwww.celp.upm.edu.myeng.celp@upm.edu.my