Life Safety Dampers
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 2/51
TODAY’S AGENDA
• Life Safety Dampers - What are they???
• A Couple of Hot Videos
• Codes / Where are the dampers???
• Unique Products and Special
applications
• Accessories
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 3/51
Fire Damper A device used to restrict the passage of flame through the duct work
of an air system. A fire damper is installed in a fire rated wall or
floor and closes automatically to maintain the integrity of thatpartition.
STATIC RATED:
DYNAMIC RATED:
Acceptable for penetrations rated less than 3 hours
No Airflow Through Damper
With Airflow Through Damper
1 ½ Hr :
3 Hr : Acceptable for penetrations rated 3 hours or greater
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 4/51
B style C style – Most Free Area
O style –Oval Duct
R style – Round Duct
FD / FSD STYLES
BC Style
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 5/51
Smoke Damper A device used to restrict the spread of smoke in an
HVAC system which shut down in the event of a fire.
Leakage Class I – 8 cfm @ 4” w.g.
Leakage Class II – 20 cfm @ 4” w.g.Leakage Class III – 80 cfm @ 4” w.g.
Velocity Ratings start at 2000 fpm @ 4” w.g. and increase at 1000
fpm and at 2” w.g.
Temperature Rating 250° or 350°
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 6/51
Smoke Control Systems
• Engineered Smoke Control
Strategically located fireand smoke dampers open
or close to channel HVAC
air into selected areas -creating high and low
pressures
• Passive Smoke Control
Close upon detection of
smoke
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 7/51
Smoke detector Actuator
Smoke Barrier
24” max.
from wall
Typical Smoke Damper Application
TS 150Firestst
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 8/51
Combination Fire/Smoke Damper
A device which functions as both a fire damper, and a smoke
smoke damper.
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 9/51
Mounting angles
Break away connections
Sleeve
Damper within the plane of fire barrier
Typical Combination
Fire & Smoke Damper
Application
Fire barrier
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 10/51
Break away connections
Sleeve
Damper in fire barrier
Typical Combination
Fire & Smoke Damper
Application
Mounting angles
EFL
(Electronic Fuse Link)
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 11/51
Ceiling Damper (aka Radiation Damper) A device used to protect the HVAC opening in in a fire rated horizontally
rated ceiling assembly. A ceiling damper closes automatically to restrict the
passage of flame and heat.
Protected area
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 12/51
Ruskin CFD7 (R)T
Design L-586
Square or Round Available
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 13/51
Fire Smoke Damper1 hr. Rated
Dampers
Corridor Damper
Combination Fire/Smoke dampers
used specifically
for tunnel corridor construction
When the walls and
ceiling form a tunnel,
the wall fire rating
need not extend
above
the top of the rated
ceiling assembly
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 14/51
Dynamic Closure under Higher Velocities and Pressures
Minimum operational requirements for Fire Dampers, Smoke Dampersand Combination Fire Smoke Dampers: 2000 fpm @ 4” wg
Max. size- 72 X 48 or 48 X 72
Max. Size- 64 X 96 or 120 X 48
Max. Size- 120 X 96 w/ elec. Act / 144 X 96 w/ pneu. actuators
4000 FPM / 4” wg – Max. Size 24 X 24
Fire Damper - curtain type
Fire Damper – multi blade type
4000 FPM / 8” wg – Max. Size 64 X 48
3000 FPM / 4” wg – Max. Size 120 X 36
4000 FPM / 4” wg – Max. Size 48 X 24
4000 FPM / 8” wg – Max. Size 24 X 24
Combination Fire/Smoke Damper
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 15/51
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 16/51
Fire Test Video
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 17/51
Ceiling Fire
Dampers
Smoke
Damper
Fire Damper
Exterior Wall
FSDHorizontal (in concrete)
Bottom of Shaft
FSD in Shaft Walls
Fire Barrier
CODES and
STANDARDS
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 18/51
FIRE AND SMOKE PROTECTION(Minimum Code Requirements)
• Fire Walls
• Fire Barriers
• Shaft Enclosures
• Fire Partitions
• Corridors
• Smoke Barriers
• Horizontal Assemblies
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 19/51
FIRE DAMPERS –Where are they used?
SECTION 706 FIRE WALLS
“restricts the spread of fire and extends continuously from the foundation to or through
the roof , with sufficient structural stability under fire conditions to allow collapse of
construction on either side without collapse of the wall”
Required to have 3 hour rating for most occupancies
2 hours for certain occupancies and 4 hours for
hazardous
Protected openings when not on a lot line.
Opening size limited unless both buildings are
sprinkled
Ducts/ Air Transfer openings shall comply with Section 716
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 20/51
FIRE DAMPERS –Where are they used?
Section 707 FIRE BARRIERS
Continuous between floor levelsRating determined by occupancy
1, 2, 3, or 4 hours
Incidental use, Occupancy separations, Shafts,
Exits, Exit passageways & Fire areas
•SMOKE DAMPER required when fire barrier serves as a horizontal exit
Ducts/ Air Transfer openings shall comply with Section 716
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 21/51
FIRE DAMPERS –Where are they used?
SECTION 709 FIRE PARTITIONS
A vertical assembly of materials designed to restrict
the spread of fire in which openings are protected.
Not Continuous between f loor levels – vertical assemblies
Corridors, dwelling & sleeping unit separation, tenant separation in Malls & Elevatorlobby separation
Generally rated 1-2 hours depending on number of stories
•SMOKE DAMPER required for Corridors (exceptions)
Ducts/ Air Transfer openings shall comply with Section 716
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 22/51
FIRE and SMOKE DAMPERS –Where are they used?
SECTION 708 SHAFT ENCLOSURES
Shaft Enclosure – The wall or construction forming the boundaries of a shaft.
An enclosed space extending through one or more stories of a building,connecting vertical openings in successive floors, or floors and roof.
Used as vertical opening enclosures
Constructed as fire barriers or horizontalassemblies
Generally rated 1-2 hours depending onnumber of stories
cts/ Air Transfer openings shall comply with Section 716
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 23/51
SMOKE DAMPERS – Where are they Used?
SECTION 716 CORRIDOR ENCLOSURES
Corridor – An enclosed exit access compartment that definesand provides a path of egress travel to an exit.
Generally rated up to 1 hour
Ducts/ Air transfer openings are protectedand shall comply with section 716
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 24/51
SMOKE DAMPERS- Where are they used?
Section 710 SMOKE BARRIERS
Smoke Barrier – A continuous membrane, either vertical or horizontal,
such as a wall, floor, or ceiling assembly, which is designedand constructed to restrict the movement of smoke.
Used in Institutional
1-hour rating required
Ducts/ Air Transfer openings shall comply
with Section 716
Smoke Barrier
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 25/51
Section 711 SMOKE PARTITIONS
SMOKE DAMPERS- Where are they used?
Smoke Partit ion – A continuous membrane, either vertical or horizontal,
such as a wall, floor, or ceiling assembly, which is designed and constructedto restrict the movement of smoke.
Corridor walls in I-2 (Hospitals, Nursing homes)
Not required to have a fire-resistance rating (unlessrequired elsewhere in the code)
Ducts/ Air Transfer openings shall comply with Section716
SmokePartition
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 26/51
HORIZONTAL Assemblies(SECTION 712)
• General requirement mandates shaft enclosures foropenings in floor and roof systems (exceptions)
• Fire-resistance rating varies depending on building type of construction and occupancies being separated
• Ducts/ Air Transfer openings shall comply with Section 716• Through penetrations – FIRE DAMPER (exceptions)
• Membrane penetrations – CEILING FIRE DAMPER
(exceptions)• Non-fire resistance-rated assemblies – FIRE DAMPER(exception)
Horizontal Assembly – A fire-resistance-rated floor or roof assembly of materials designed to restrict the spread of fire in which continuity is maintained.
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 27/51
Other IBC Chapters
That Affect The Construction andRatings
• IBC Chapter 3“Use and Occupancy Classification”
• IBC Chapter 4“Special Use and Occupancy”
• IBC Chapter 9“Fire Protection System”
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 28/51
International Mechanical Code
(IMC)
• SECTION 607 (DUCT AND AIR TRANSFER OPENINGS)
– Basically duplicates IBC requirements for dampers and/or refers back to IBC(same exceptions)
• HAZARD EXHAUST DUCTS – Fire dampers are prohibited
• CLOTHES DRYER EXHAUST – Fire dampers are prohibited• GREASE DUCT PENETRATION – Fire dampers are not used
• DUST COLLECTION – Fire dampers are not usually applicable
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 29/51
NATIONAL FIRE PROTECTION
ASSOCIATION¾ NFPA72 - National Fire Alarm and Signaling Code
¾ NFPA80 - Standard for Fire Doors and Other Opening Protective
¾ NFPA90A - Standard for the Installation of Air-Conditioning andVentilating Systems
¾ NFPA92A - Standard for Smoke-Control Systems Utilizing Barriers
and Pressure Differences
¾ NFPA92B - Standard for Smoke Management Systems in Malls,
Atria, and Large Spaces
¾ NFPA101 - Life Safety Code®
¾NFPA105 – Standards for Smoke Door Assemblies and OtherOpening Protectives
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 30/51
Unique Products and FeaturesSpecial Applications
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 31/51
True Round
Cinch Plate replaces Mounting Angles
UL approved one side
FSDR25
Fire Damper / Smoke Damper / Combo Fire Smoke Damper
FDR25 SDR25
• 6” to 24” dia. • Lower pressure drop
• Very Low installation costs
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 32/51
FLANGED SYSTEM
BREAKAWAYWARD / DUCTMATE / NEXUS / TDC / TDF
Unique Installations
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 33/51
OUT OF WALL / FLOOR•Retrofi t Applications
•Through Penetration
•Duct Termination
Maintain
100%Free Area
Unique Installations
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 34/51
8” Max.
For Shaft Applications
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 35/51
“ GRILLE ACCESS” Models
FSD36FA/ 60FA
FSD35GA/ 36GA/ 60GA
For Shaft Applications
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 36/51
FSDFA “ Front Access”•No retaining angles required• Allows for shortest sleeve possible
• Access to actuator & other components through the grille
•Thermal insulation on damper allows out of wall installation
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 37/51
FSD60-BAL
3-Position “ Balancing” FSD
Built inpotentiometer to
20% to 100%
balance position
Allows the damper to be SET at any
position for BALANCING AIRFLOW
under normal operations, open for
SMOKE CONTROL and provides FIRE
protection simultaneously
No Control Signal
Required
Unique Installations
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 38/51
Vertical Blade Fire Smoke Damper
For applications where ducts runside by side and there is no roomfor actuator on the side of damper.
Unique Installations
FSD60V
Don’t try this with a normal damper!
FSD60M
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 39/51
FSD60MMODULATING Fire/Smoke Damper
Responds from control signal
2 to10 VDC or 4 to 20mA
Proportional Modulating Actuator
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 40/51
FD / FSD
Many Options
I di h i i f h d bl dBl d P iti
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 41/51
•Indicates the position of the damper blades
• Allows for other equipment to be turned on / off
SPH2
SP 100
Blade Position
Indicating Switches
SP 200
TS150 Fi t t
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 42/51
TS150 – FirestatFor Smoke Damper &
Combination Fire/Smoke Dampers
• Allows the damper to be reopened after the initial closure
for engineered smoke control.
• Equipped with blade position indicator
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 43/51
Damper Test Switch - DTS
Momentarily interrupts power
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 44/51
Duct Smoke Detectors
DSDF (Flow)
DSDN (No Flow)
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 45/51
• Used to control, monitor, or testdampers remotely
MPC’s-Master Control Panels
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 46/51
All your answers are here!
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 47/51
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 48/51
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 49/51
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 50/51
Autodesk®Revit ®
Ruskin Revit ® files can be found at
•www.ruskin.com•http://seek.autodesk.com
Ruskin Dampers
• Life Safety Dampers• Air Control
• Industrial/ProcessRuskin Louvers
• Drainable• Wind-Driven Rain
• Hurricane• Sun ShadesRuskin ERV Units
Building Information Modeling
7/30/2019 HH FSD 8 10
http://slidepdf.com/reader/full/hh-fsd-8-10 51/51
Thank You!