Genco Genco

Customer

DiscomDiscomDiscom

Genco

Open access in Transmission

Traders

Open access in Distribution

Traders

Customer

Customer

New structure in Deregulated Environment

These changes require the following:

1) Monitoring system wide information and commands via data communication system

2) To send selected local information to control center, customer, market participants.

3) Monitor critical real time information for taking security related operation .

4) To support Power Trading and spot market.

4) Reliable and fast communications among IED’s ( Intelligent Electronic Devices viz Relays, Meters, Fault recorders, RTU’s etc.) for exchanging information and change in settings as part of wide area protection system .

5) Dissemination of billing and other related calculations from Generation to Distribution for to various agencies including information for DMS & EMS.

7) To perform effective co-ordination through communications , Communication Protocols used are expected to be high speed ,reliable , fault tolerant and intelligent enabled.

8) The Protocols are to be accomplished for both local ( LAN) and wide area communications (WAN).

9) The protocols should be thin, flexible and have provisions for accommodating future requirements.

10) Safe , secured and reliable transmission of information.

11) Protecting information network from Hacking & misuse.

12. Information about the power system gives the utility the strength to be more successful and competitive in a free market .

13.In this environment information becomes a strategic requirement when fast decisions are required.

Multifunction MeterArgus

Delta

Duobias-M Ohmega SEL-311C M-3425

Fault AnalysisReyevo / SEL5601 / IPSCOM

Remote Center

Engineering ToolISAGRAPH

HMIEvent Printer Hard Copy Printer

Ethernet LAN

ER1000 Station Controller

What is Protocol ?

When Intelligent Devices communicate with each other, there needs to be a common set of rules and instructions that each device follows.

A specific set of communication rules is called a protocol.

* The diversity of Equipments and Manufacturers lead to a increase of Proprietary Protocols

• Computer to Computer data communication standards have been developed over past few decades.

• Well known model for this purpose is the 7 Layer OSI ( Open System Interconnection) reference model.

•This model provides encapsulation of the relevant data with in a packet.

• This model provide isolation of application program from system and media. But adds significant overhead in processing power and bandwidth utilisation.

Application

Presentation

Sessions

Transport

NetworkData link

Physical 1

23

55

6

4

7

OSI 7 Layer Model

Functionality of different layers•Application Layer: This provides the interface and services that support user application. Ex. E-mail, WWW, SMTP.

• Presentation Layer: This layer responsible for data encryption, data compression .Ex JPG, MPEG etc

• Sessions Layer: Responsible for setting up the communication link and manages the sessions. It could provide connection oriented and connectionless services.

Functionality of different layers•Transportation Layer: Responsible for flow control, Packet size, error free delivery with proper sequence.

• Network layer: Route determination takes place in this layer. Translation of IP address to physical address ( NIC) also takes place here.

• Data link layer : Responsible for data movement across the actual physical link.

• Physical Layer: It defines the physical aspect of how the cabling is hooked.

Application

Presentation

Session

Transport

Network

Data Link

Physical

7

6

5

4

3

2

1

7

6

5

4

3

2

1

•••

•••

•••

•••

•••

•••

•••

•••

•••

2

1

2

1

2

1

2

1

3 3

7 LAYER System X

Intermediate System A

System Y

Physical Media

•••••••••••••••••••••••••••••••••••••••••••••••••••••••

•••••••••••••••••••••••••••••••••••••••••••••••••••••••

•••••••••••••••••••••••••••••••••••••••••••••••••••••••

Peer communication Protocols

Intermediate System B

Physical Media Physical Media

•••••••••••••••••••••••••••••••••••••••••••••••••••••••

• Due to addition of many layer

overhead and bandwidth goes

higher.

•It is not suitable for SCADA application.

• Most of the Protocols follows various flavours of this model.

Need For Standards

* Protocol is a set of rules that governs how message containing data and control information are assembled at a source for their transmission across the network and then dissembled when they reach their destination.

* The communication protocol allows two devices to communicate with each other. Each device involved in the communication must essentially support not only the same protocol but also the same version of the protocol. Any differences involved in the implementation of protocol at the either of ends will result in the communication errors.

Proprietary Vs Open Protocols

* Protocol, used by the vendor, the utility is restricted to one supplier for support and purchase of future devices. This presents a serious problem.

Examples of Proprietary Protocols are SPA, K-Bus, VDEW etc.

* With the arrival of open systems concept , it is desired that devices from one vendor be able to communicate with those of other vendors i.e. devices should inter-operate . To achieve interoperability one has to use industry standard open protocols.

Ex: IEC60870 -5-103,101,104, IEC61850,DNP,Modbus etc

* Migration to standard communication protocol is a very important decision that leads to cost reduction and maximized flexibility within the utility sector. Broadly benefits for the utilities are: Availability of open system connectivity > Vendor independence > Reliable products at optimized costs > Easily available knowledge and specification Benefits drawn for vendors by standardization are: > Lower costs of installation and maintenance > A large market and thus opportunity to compete on price performance instead of technical details only. > Cost effective project implementation

Advantages of Open Protocols

Interoperability Vs Interchangeability

* Interoperability is the ability of two or more IEDs from same vendor or different vendors to exchange information and uses that information for correct co-operation.

* Interchangeability is the ability to replace the device the supplied by one manufacturer with a device without making change to the other elements in the system.

Application

Presentation

Session

Transport

Network

Data Link

Physical

Application

Data Link

Physical

OSI EPA

PROTOCOL STRUCTURE

7-Layer 3-Layer

Network Technology mainly based on OSI (Open System Interconnect) which is a 7 Layer model representing networking node by dividing tasks into layers that perform specific Functions.

OSI Seven Layer architecture

Application

Presentation

Session

Transport

Network

Data Link

Physical

Application

Presentation

Session

Transport

Network

Data Link

Physical

Application

Presentation

Session

Transport

Network

Data Link

Physical

Logical Connection

Physical Connection

IEC, DNP, UCA (and even MODBUS) standards are successfullyable to adopt TCP/IP based Ethernet based technology forsubstation automation.

DNP3/TCP

TCP/UDP

IP

IEEE 802.1

IEEE 802.3

IEC 104

IEC 61850 (UCA2)

Application

Presentation

Session

Transport

Network

Data Link

Physical}Ethernet

}TCP/IP

PROTOCOL STRUCTURE for IP based Open Protocols

Link LayerLink LayerBalanced TransmissionBalanced Transmission

Master SlaveRequest Message

Response Message

(User Data, Confirm Expected)

(Acknowledgment)

[P]

[P] = Primary Frame[S] = Secondary Frame

[S]

(User Data, Confirm Expected)

(Acknowledgment)

[P]

[S]

Link LayerLink LayerBalanced TransmissionBalanced Transmission

• At the link layer, all devices are equal

• Collision avoidance by one of the following:

– Full duplex point to point connection (RS232 or four wire RS485)

– Designated master polls rest of slaves on network (two wire RS485 and disable data link confirms in slaves)

– Physical layer (CSMA/CD)

Link LayerLink LayerUnbalanced TransmissionUnbalanced Transmission

Master SlaveRequest Message

Response Message

(User Data, Confirm Expected)

(Acknowledgment)

[P]

[P] = Primary Frame[S] = Secondary Frame

[S]

(Request User Data)

(Respond User Data or NACK)

[P]

[S]

Link LayerLink LayerUnbalanced TransmissionUnbalanced Transmission

• Only Master device can transmit primary frames

• Collision avoidance is not necessary since slave device cannot initiate exchange, or retry failed messages

• If the slave device responds with NACK: requested data not availablethe master will try again until it gets data, or a response time-out occurs

Protocols used in Electrical utilities are as follows:

1) Modbus / Profibus

2) DNP ( Distributed Network Protocol )

3) IEC 60870 series

4) UCA ( Utlity Communication Architecture ) – IEC 61850 series

MODBUS

Developed in the process-control industries by MODICON , USA during 1976

- Application layer Protocol ( 7 th Layer of OSI )

- Extensively used in industrial environment

- Used in process bus of substation bay ( Relays )

- It operates on master slave type mode

- Slave node will not typically transmit data with out a request from the master.

• It was originally designed as a simple way to transfer data between controls and sensors via RS-232 interfaces.

• Modbus now supports other communication media, including TCP/IP.

• Modbus is now an open standard, administered by the Modbus-IDA (www.modbus-ida.com).

Modbus and DNP3 Communication ProtocolsModbus and DNP3 Communication Protocols

• Modbus and DNP are both byte-oriented protocols. • Modbus is an application layer protocol, • while DNP contains Application and Data Link Layers,

with a pseudo-transport layer. • Both protocols are widely used over a variety of

physical layers, including RS-232, RS-422, RS-485, and TCP/IP.

• Modbus has a separate specification for use over TCP/IP (Modbus-TCP). With DNP, the protocol is simply encapsulated within TCP/IP.

Distributed Network Protocol 3.0

Distributed Network Protocol ( DNP) was developed by Harris, USA.

• The Distributed Networking Protocol (DNP) was originally developed by Westronic, Inc. (now GE Harris) in 1990.

• The “DNP 3.0 Basic 4” protocol specification document set was released into the public domain in 1993, and ownership of the protocol was given to the newly formed DNP Users Group in October 1993.

• DNP was specifically developed for use in Electrical Utility SCADA Applications.

• It is now the dominant protocol in electrical utility SCADA systems, and is gaining popularity in other industries, including Oil & Gas, Water, and Waste Water.

-In 1993 the responsibility for defining further DNP specification was given to DNP user Group.

- DNP is based on the earlier work of IEC TC 57

- It is based on Enhanced Performance architecture ( EPA) model

- There are 4 core documents to define DNP 3

• DNP 3.0

• Based on earlier work of IEC TC57

• Developed by GE Harris

Emergence of StandardEmergence of Standard

DNP 3.0 is an open protocol that was developed to establish interoperability between RTUs, IEDs (Intelligent Electronic Devices) and master stations. DNP was largely influenced by North and South America, together with the African and Asian regions as IEC 101 was from the European community.

DNP 3.0 is an open protocol that was developed to establish interoperability between RTUs, IEDs (Intelligent Electronic Devices) and master stations. DNP was largely influenced by North and South America, together with the African and Asian regions as IEC 101 was from the European community.

DNP 3.0 StructureDNP 3.0 Structure

• Three Layered Protocol (EPA)

• Application (Layer 7)

• Data Link (Layer 2)

• Physical (Layer 1)

This structure is similar to IEC. However, DNP3 enhances EPA by

adding a fourth layer, a pseudo transport layer that allows for message segmentation.

This structure is similar to IEC. However, DNP3 enhances EPA by

adding a fourth layer, a pseudo transport layer that allows for message segmentation.

Additional Pseudo LayerAdditional Pseudo Layer

• In addition• Pseudo Transport Layer (Layer 4)

• Support Advance RTU functions

DNP introduces a pseudo-transport layer(OSI Layer 4) to build application data messages larger than a single data link frame. In case of IEC, each 101 message should be contained in a single data link frame.

DNP introduces a pseudo-transport layer(OSI Layer 4) to build application data messages larger than a single data link frame. In case of IEC, each 101 message should be contained in a single data link frame.

• DNP3 is an open, intelligent, robust, and efficient modern SCADA protocol.

• It can request and respond with multiple data types in single messages,

• segment messages into multiple frames to ensure excellent error detection and recovery,

• include only changed data in response messages,• assign priorities to data items and request data items

periodically based on their priority, • respond without request (unsolicited),• support time synchronization and a standard time format,• allow multiple masters and peer-to-peer operations,• and allow user definable objects including file transfer. • In 1994, the IEEE Power Engineering Society’s Data

Acquisition, Monitoring and Control Subcommittee formed a Task Force to review the communication protocols being used between Intelligent Electronic Devices (IEDs) and Remote Terminal Units (RTUs) in substations.

• The IEEE Task Force found a very confusing, constantly changing environment that was increasing the cost and time to completion of substation SCADA systems.

• The IEEE Task Force collected information on approximately 140 protocols and compared them to a list of communication protocol requirements.

• This comparison resulted in a short list of protocols that met most of the requirements.

• This short list was balloted and two serial SCADA protocols tied for being the most acceptable: IEC 60870-5-101 and DNP3.

• Structure of IEC 60870-5

– Three Layered Protocol(EPA)

• Application (Layer 7)

• Data Link (Layer 2)

• Physical (Layer 1)

• Why 3-Layered Structure of EPA

1) Short Reaction Time

2) Reduced Transmission Bandwidth

BW: Measure of capacity of a transmission

system. Measured in Hertz. How fast data

can flow on a given transmission path.

BW: Measure of capacity of a transmission

system. Measured in Hertz. How fast data

can flow on a given transmission path.

In Digital data transmission, BW is expressed

as data speed in bits per second. Thus, higher

the BW, more data can be transmitted.

In Digital data transmission, BW is expressed

as data speed in bits per second. Thus, higher

the BW, more data can be transmitted.

For Tele Control System that require particularlyFor Tele Control System that require particularlyFor Tele Control System that require particularlyFor Tele Control System that require particularly

• Purpose of 60870-5 Protocol

• High Integrity

• Efficient Data Transmission

• Protection Against Undetected Transmission Errors

Correct data should reach the destinationCorrect data should reach the destination

Without LossWithout Loss

• Both DNP 3.0 and IEC 60870-5-101

• Designed for Transmission of SCADA Data for Electric Power System Control

• Wide Market Acceptance

• Intended for Use in SCADA Systems Using directly Connected Serial Links

DNP 3.0 and IEC 60870-5-101DNP 3.0 and IEC 60870-5-101

• 60870-5-101 and DNP Usage

• Collection of Binary Data

• Collection of Analog Data

• Collection, freezing and Clearing of Counters

DNP 3.0 and IEC 60870-5-101DNP 3.0 and IEC 60870-5-101

• Time Synchronization

• Time-Stamping Events

• File Transfer

• Unsolicited Events Reporting

DNP 3.0 and IEC 60870-5-101DNP 3.0 and IEC 60870-5-101

IEC 60870-5 Series

It is bit serial communication standards. The standard is optimised for efficient and reliable transfer of process data and commands to and from geographically widespread systems over low-speed (up to 64 kbps) fixed and dial-up connections.

IEC 60870-5-101 –

It deals the functionality for the interoperability of telecontrol equipment of different manufactures for the communication between substations and between substation and control centres .

IEC 60870-5-102 - This standard deals with values of integrated totals which are transmitted at periodic intervals to update the energy interchanges between utilities or between heavy industry and utilities.

 

 

IEC 60870-5-103 - This deals with informative interface of protection equipment .

IEC 60870-5-104 - This present a combination of the application layer of IEC 60870-5-101 and the transport functions provided by a TCP/IP.

IEC 61850

This standard unifies UCA with European standard. It aims to design a communication system that provides interoperability between the functions to be performed in a substation.

IEC 61107 :

This specifies hardware and protocol specifications for local systems in which a hand held unit is connected to only one tariff device at a time. This specifies hardware and protocol specifications for local systems in which a hand held unit is connected to only one tariff device at a time.

     1) IEC 61107 is essentially a protocol providing a means to access (read and write) memory locations, without telling anything about how those memory locations should be filled with information.    2) IEC 61107 does neither say anything about the format and the interpretation of the data.

3) IEC 61107, developed for the purposes of local data exchange, does not follow the OSI model of layered protocols and does not have the functions provided by these layers. Therefore, although it is widely used over telephone networks, it is only possible with some compromises.

4)      IEC 61107 lacks advanced security functions.

5) Consequently, for each new meter type, even from the same manufacturer, a new device driver is required. Such drivers carry information about where and how to find the information and how to interpret it. The development of device drivers has proven to be a lengthy and costly exercise.

Communication - Interfaces & Protocols in Substation

Serial Protocols

* IEC 60870-5-103 (Protection)

* IEC 60870-5-101 (Tele Control)

* DNP 3.0 (Protection, Monitoring & Metering)

* Modbus RTU (Metering)

LAN Protocols

* IEC 60870-5-104

* DNP 3.0 over TCP/IP

* MODBUS over Ethernet ( For Industries)

* IEC 61850

* Serial (RS232/RS485/RS422)* LAN (Ethernet)

Station Level

* Serial

* Ethernet

Station Level Protocol

* IEC 60870-5-101

* IEC 60870-5-104

* DNP 3.0 over TCP/IP

* Modbus over Ethernet / Serial

Communication Protocols from Station Level Equipment.

DNP 3.0

* Supports Balanced Transmission Services

* Supports

- Time Synchronization - Time-stamped events - Freeze/Clear Counters - Select before operate - Unsolicited Responses

IEC 870-5-101: Basic Telecontrol Tasks

• Protocol Standard for the telecontrol of Electrical Power Transmission Systems. • Permanent Directly Connected (Serial) Link between Telecontrol stations.

• Supports both Balanced/Unbalanced Transmissions

• Frame Type FT1.2 (1 Byte Checksum error check)

IEC 60870-5-104

• This protocol standard is developed to Provide Network access for IEC 870-5-101

• Application Layer remains same.

• Does not use the Link Layer functions of IEC 870-5-101.

• Some APCI (Application Protocol Control Information) Added to 101 ASDU To suitable for network transportation

Modbus Over Ethernet / Serial

• Modbus Over Ethernet protocol if useful in sending Modbus messages on LAN / WAN network.

• Additional of 6 Bytes as a MBAP Header to basic Modbus over serial frame.

• Slave Address byte of serial Modbus frame is replaced with Unit Identifier.

IEC 870-5-103

• Companion Standard for Interface of Protection Equipment's • Unbalanced Master Slave Serial Protocol.

• Protective Relays Act as Slave Devices.

• Station Controller as a Master. • Physical Interface may be RS232,RS485 (or) Fiber Optic.

• Status indications,Measurement values, time-tagged events, control commands and clock synchronization Can be transferred between Master & Slave Devices .

Future ( IEC 61850 / UCA )

Standard for communication network and systems in Substation.

Intended to integrate

* Protection System * Control System* Substation Field Devices * Interface to Supervisory Control and Data Acquisition(SCADA) of Control Center* One of the most important features of IEC 61850 is that it covers not only communication, but also qualitative properties of engineering tools, measures for quality management, and configuration management & Conformance testing.

IEC 60870-1-103 / DNP 3.0 Modbus / IEC 61850

Communication Standards Within the Substation

What to Expect from Vendor on Protocols in their Devices??

IEC-60870-5-103 protocol

* Communication Settings supported (Baudrate, Parity, IED address range config.). *Function Types supported (both Standard, Private). *COT Supported. *ASDU Type supported for each type of Tag or Parameter or information. *Information number (Standard, Private) for each parameter or tag & description for the same. *Any private ASDU ( ASDU 254,255 )implementation? If so then details.* Interoperability Table if any

DNP3.0 Protocol

* Details of Communication Interface supported.* DNP Levels Supported.* Data Scaling Range if any?*Data Retrieval Method supported (unsolicited/polled static/exception).*Object Type & variations supported.

*Data Map (Index number ) of each parameter.

Modbus (RTU) Protocol

*Details of Communication Interface supported.*Relay Address range supported.*Function Types supported.*Address range for each parameter.*Data Type(16 bit(integer),32 bitz(long int), etc)*Multiplication factors if any.*Parameters type (Read only/read/write).

HMI # 1 HMI # 2

Ethernet LAN

Remote Control Center

400 & 220 kV Bay Control Units

Typical Architecture of ERSA System

Protective Relays Tariff Meter

ER 1000

MV Architecture

Modbus

Multifunction MetersHardwired I/O’s for protection and Equipment Status

Station Controller

Local HMI

Remote HMI

Bay Control & Protection Units

IEC 103 Master DNP 3.0 Master Modbus Master

DNP 3.0 / IEC 101 / IEC 104 / Modbus serial or Ethernet [ Slave components]

Local HMIRemote Control Center

IEC 60870-5-103 Slave Components

Modbus Slave Components

DNP 3.0 Slave Components

Hardwired Analog/Digital I/O’s for protection and Equipment Status

ER 1000 Station Controller/Communication Gateway

ER 1000

Functionality's & Requirement of station Controller

•Communication Gateway

•Protocol Converter

•Virtual RTU

•Data Concentrator

•Automation Unit

•Wired I/O’s

•Open H/W architecture and OS

•IEC 61131-3 compliant PLC programming

•Highly modular and hence easily expandable

•Superior architecture compared to a PC based architecture

•Can work in any extreme environmental conditions

* Present the state and operational Details of the field equipment in a user friendly manner through a powerful GUI

•Control and monitor the field equipment, protection IED’s locally or remotely •Inbuilt -Energy Management System with communicable Multifunction Meters.

• Report Generation (Hourly, Daily, monthly, yearly), Alarms

•IED Parameterization, Disturbance Analysis.

•Online Sequence of Time Tagged Events (Source / System Time Stamp) printing and Event File Storing.

What is Simple Substation Control And Monitoring System????...

Multifunction Meters

A simple relay based substation control

SOE Printer

ER 10

Ethernet/Dialup

IEC 103

RTU

Modbus/RS485ER Relays

Serial to Fibre Optic Converter

ER Relays

RS 485/422 to RS 232 Converter

ER 10

IEC 103

Remote HMILocal Workstation

ER 05

Modbus

• Electric utilities were among the first entities to embrace data telemetery.

• Data telemetry was introduced for monitoring , Control and Protection.

• Development in communication, Computer, introduction of Intelligent Electronic Devices (IED) made information collection easier.

• Different manufacturers introduced different rules for communicating and exchanging information among their intelligent devices.

• This introduced barriers in communicating with other device manufactured by others.

IEC 62056 - Series

Data Exchange for Meter Reading- Tariff and Load control

 

  1) 62056 covers all metering functions required on the liberalised market. The functions are modelled using metering domain specific interface objects. This allows developing meters meeting exactly customer needs, using standard building blocks.

It also allows innovation and competition by enhancing functionality in a standard way as required while maintaining interoperability.

2) It ensures unique identification of all metering equipment world-wide and unambiguous identification of all data elements.

3) It ensures unambiguous interpretation of all

metering data.

4) It allows controlled and selective access by

various parties to application relevant data.

5) It provides various levels of security mechanisms

to control access to data depending on

authentication and access rights.

 6) opens the way for exchanging data over various

communication media, as the meter data model is

independent of the communication protocol stack.

7) It brings interoperability, and therefore lowers costs, as it is based on a standard data model and internationally approved standard protocols.

Itallows developing a genuine driver, as the meter describes the functions available and sends all information necessary to interpret data. This allows meter manufacturers and data collection system providers to concentrate on the applications relevant for their customers rather than on connectivity and interfaces;     9) It comes complete with a conformance testing scheme to guarantee interoperability.

IEC 60870-6, TASE.2

This deals with mechanism for exchanging time-critical data between control centres. In addition, it provides support for device control, general messaging and control of programs at a remote control centre.

IEC 61970

This deals with CIM facilities for the integration of EMS applications developed independently by different vendors, between entire EMS systems developed independently, or between an EMS system

IEC 62210

This deals with safety, security and reliability of systems in Electrical Utilities. The deregulated market has imposed new threats and safe operation is essential in a deregulated environment.

IEC 61400-25

This provides a standard for interconnection of monitoring and control systems for wind power plants

IEC 62195 TR

This report deals with Electronic communication in deregulated markets and makes a clear distinction between communications for control of energy systems and communications for the market

IEC 60870-5-104,IEC 60870-5-101,DNP3

Control Centre 1

Distribution,Customer:MeteringBilling

IEC 60870-6 (TASE.2),DNP3, IEC 60870-5-104

Substation

PowerPlant

MarketParticipantEC, EDI

ISO 9735

Server

IEC 61970 EMS

IEC 61968 DMS

IEC 60870-5-104,DNP3

Substation

IEC 60870-5-104,IEC 60870-5-101,

DNP3

ControlCentre 2

IEC 61850

IEC 62210

Possible trend in the near futureRef: CIGRE report on Substation Automation

IEC 61850

Control Centre 1

Billing

IEC 60870-6 (TASE.2)

Substation

Power Plant

Market Participant EC, EDI

ISO 9735

Server

IEC 61970 EMS

IEC 61968 DMS

IEC 61850

Substation

IEC 62056 IEC 61850

Control Centre 2

IEC 61850

IEC 62210

Possible trend in the far future

Ref: CIGRE report on Substation Automation

MeterReading &

Control

MeterReading &

Control

Utility ControlCenter

Utility ControlCenter

NetworkExpansionPlanning

NetworkExpansionPlanning

CustomerInquiry

CustomerInquiry

NetworkOperationNetwork

Operation

Records& Asset

Management

Records& Asset

Management

OperationalPlanning &

Optimization

OperationalPlanning &

Optimization

IEC 61968CompliantInterface

Architecture

IEC 61968CompliantInterface

Architecture

Maintenance&

Construction

Maintenance&

Construction

Utility BusinessSystems

(ERP, Billing, EnergyTrading, Other Systems)

Utility BusinessSystems

(ERP, Billing, EnergyTrading, Other Systems)

Corporate LAN

Corporate LAN

Distribution AutomationDistribution Automation

Substation Protection,Monitoring, & ControlSubstation Protection,Monitoring, & Control

RTU CommunicationsRTU Communications

WG 14WG 14

IEC TC57 Reference ArchitectureIEC TC57 Reference Architecture

61968 DMSSubsystem

EMS Application

61970

Control centre 60870-6

Control Centre

SCADA

Metering

Protection

PhysicalDevice

RemoteTerminal

Unit

Substation

6185061850

6185

0

60870-5 -103

SubstationAutomation

60870-5 -101

Relevant IEC StandardsRelevant IEC Standards

• Technical Committee 57– Power system control and associated communications

• Published– IEC 60870 Telecontrol equipment and systems– IEC 61334 Distribution Automation using Power Line Carrier– IEC TR 62210 Power system Control and associated Communications –

Data and Communication security– IEC 61400-25 Communication for monitoring and control of Wind Power

plants. – TR 62195 Deregulated energy market communications

• confirmed EDIFACT as a recommended standard for business transactions

• In progress– IEC 61850 Communication networks and systems in substations– IEC 61968 System Interfaces for Distribution Management– IEC 61970 Energy Management Systems Application Program Interfaces– IEC 62350 Communication systems for Distributed Energy Resources– IEC 62344 Hydro Electric Power Plants – Communication for monitoring

and control.• .

Introduction Introduction

UCAUCA

Electric Power Research Institute (EPRI) launched a concept in 1990 known as the Utility Communication Architecture or UCA. The goal behind UCA was to identify a suite of existing communication protocols that could be easily mixed and matched, provide the foundation for the functionality required to solve the utility enterprise communication issues, and be extensible for the future. After some initial revisions, the results of the project have been known as UCA 2.0. UCA 2.0 is described in a technical report TR 1550 of the IEEE [2].

Brief Description about UCA 2.0Brief Description about UCA 2.0

UCA2- SUBSTATION COMMUNICATION MODEL

Concept of 61850Concept of 61850

Comprehensive EPRI project UCA 2.0

International Agreed Goals

IEC 60870-5-101, -103, -104

IEC 61850

The basis and the way of standardizing communications in IEC 61850 are entirely new. IEC 61850 was developed from IEC 60870-5-x and UCA 2.0.

 The goal of this standard IEC 61850 “Communication networks and systems in substations” is to provide interoperability between the IED’s from different suppliers or, more precisely, between functions to be performed in a substation but residing in equipment (physical devices) from different suppliers. Interchangeability is outside the scope of this standard, but the objective of interchangeability will be supported following this standard.

 Interoperability has the following levels for devices from different suppliers:

(1) The devices shall be connectable to a common bus with a common protocol (syntax)

(2) The devices shall understand the information provided by other devices (semantics)

(3) The devices shall perform together a common or joint function if applicable (distributed functions) Since there are no constraints regarding system structure and data exchange, some static and dynamic requirements shall be fulfilled to provide interoperability.

Brief description about IEC 61850

What does IEC 61850 achieveWhat does IEC 61850 achieve

Timesynchronisation

with SNTP

Systemconfiguration

IEC 61850

Communicationbetween

bay devices

Fault records

in Comtrad

eformat

Standardcommunication

with TCP - IPBased onEthernet standard

Standardisedlanguage fordescribingsubstation

Defines structure for protection and

control

• IEC 61850 is a global standard for“Communication Networks and Systems in Substations”

• It specifies an expandable data model and services• It does not block future development of functions

– It specifies no protection or control functions• It supports free allocation of functions to devices

– It is open for different system philosophies• It provides the Substation Configuration description Language (SCL)

– It supports comprehensive consistent system definition and engineering

• It uses Ethernet and TCP/IP for communication– Provides the broad range of features of mainstream communication– It is open for future new communication concepts

Advantages in IEC 61850?Advantages in IEC 61850?

GOOSE ??GOOSE ??

A device sends information by Multicasting. Only devices which are subscribers receive this message.In the example, Receiver Z receives the message. Receiver Y is not a subscriber.

IEC 61850 – GOOSE Principle

GOOSE Sender Device X

GOOSE Sender Device X

GOOSE ReceiverDevice Y

GOOSE ReceiverDevice Z

GOOSE ReceiverDevice Z

Eth

ern

et

GO

OS

E m

essag

e

Normal message

Fast GOOSE

Buffer for Normal Message

Overtaking path for IEC GOOSE

Difference of IEC 61850 and UCA 2.0 : fast messaging “GOOSE”

Ethernet Switch

IEC 61850 is a definite step towards unified substation communication, compared to the former IEC 60870-5-103, DNP3 and most proprietary protocols:

speed of exchanges: 100 Mbps instead of few 10kbps, enabling more data to be exchanged or a better operation or maintenance of the system,

peer-to-peer links, replacing conventional wires with no extra hardware but and also permitting the design of innovative automation schemes,

client-server relations offering flexible solutions easy to upgrade compared to master slave communications,

object oriented pre-defined names, creating a single vocabulary between users, suppliers and supplier’s devices therefore facilitating the system integration and commissioning,

XML interfaces referencing the above objects for straightforward exchanges between engineering tools in order to optimise the data consistency and minimise project lead times.

communication conformance tests that help reducing the variety of interpretation found in many legacy protocols and leading to long integration tests and tuning.

IEC 61850 Key benefits

IEC 61850 Based SAS Projects IEC 61850 Based SAS Projects PGCIL Maharanibagh GIS:

400 KV Switchyard with 5 bays (Two Main) 220 KV Switchyard with 7 bays (Two Main) Separate SA systems for 400 and 200 kV Levels. FAT completed in Dec. 2005

PGCIL Bhatapara: 400 KV Switchyard with 6 Diameters (1½ Breaker) 220 KV Switchyard with 12 bays (Two Main +Transfer) Common SA system for 400 and 220 kV Levels FAT completed in Dec. 2005

PGCIL Raigarh: 400 KV Switchyard with 8 Diameters (1½ Breaker) 220 KV Switchyard with 9 Bays (Two Main +Transfer) Common SA system for 400 and 220 kV Levels FAT completed in Jan. 2006

PGCIL Maharanibagh 400 kV S/SPGCIL Maharanibagh 400 kV S/S

REL 670

REL 670

REC 670 REL 670 Main I

7SA522 Main II

BBP Bay Units Main I, Main II

REC 670 RET 670 Main I

BBP Bay Units Main I, Main II

RET 670 Main II

REC 670

REB 500 Main I

REB 500 Main II

BusbarLine x 2 Autotransformer x 2 Auxiliaries

IEC 61850 Redundant Ring network

IEC 60870-5-101

Gateway

DR WSRedundant HMI

GPS Receiver

Ethernet SwitchEthernet SwitchEthernet Switch

Ethernet SwitchEthernet Switch

Laser Printer

DMP

REC 670

Bus Coupl. x 1

BBP Bay Units Main I, Main II

PGCIL Maharanibagh 220 kV S/SPGCIL Maharanibagh 220 kV S/S

REC 670 REL 670 Main I

7SA522 Main II

BBP Bay Unit

REC 670

BBP Bay Unit

REB 500

BusbarLine x 4Autotransformer x 2Bus Coupler x 1

IEC 61850 Redundant Ring network

IEC 60870-5-101

Gateway

DR WSRedundant HMI

Ethernet SwitchEthernet SwitchEthernet Switch

Ethernet SwitchEthernet Switch

Laser Printer

DMP