Emergency power presentation3 - APT - Microgrids · 2019-06-26 · EMERGENCY SOURCE SOLID STATE ATS BREAKER CIRCUIT OUTPUT NORMAL BYPASS CIRCUIT BREAKER EMERGENCY BYPASS CIRCUIT BREAKER

Post on 20-May-2020

1 Views

Category:

Documents

0 Downloads

Preview:

Click to see full reader

Transcript

Emergency Back-up Power Generationfor Water & Wastewater Facilities

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Emergency Back-up power sources

• Multiple utility feeds• On site emergency power sources

– Diesel powered generator sets– Natural Gas generator sets– Bi-fuel generator sets– Gas Turbines

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Multiple Utility Feeds

• Pros– Majority of the equipment is owned and maintained by

the utility company.– Lowest cost per kWh produced during outage of the

primary feed.

• Cons– Susceptibility to failure during natural disaster higher

due to failure upstream.

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Multiple Utility Feeds

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Diesel Powered Generator Sets

• Pros– Reliable technology– High power density– On site fuel storage– Cost per kW installed

• Cons– High cost of fuel per kWh produced– Emissions

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Natural Gas Powered Generator Sets

• Pros– Low cost of fuel per kWh produced– Emissions

• Cons– Less reliable source of fuel during natural disasters– Inferior transient response– Cost per kW installed

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Bi-fuel Powered Generator Sets70% Diesel 30% Natural Gas

• Pros– Lower installation cost per kW than Natural gas engine

or Turbine– Ability to supplement diesel fuel with natural gas

during power outage, if natural gas supply remainsavailable

• Cons– Higher installation cost than diesel genset– Not commonly offered by major engine manufacturers– Additional complexity

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Natural Gas Turbines

• Pros– High power density– Better transient response than Natural gas engines

• Cons– Less reliable source of fuel during natural disasters– Higher cost per kW installed– Power output is temperature dependent

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Power Source Summary

Diesel Nat. Gas Bi-fuel Gas Turbines

Power Density *** * ** ****

Emissions * **** ** ***

Installed cost **** ** *** *

Fuel cost * **** ** ***

Transient response *** * *** ****

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Power System Design Considerations• Small power systems (<1000kW)

– Typically 480 Volts– One generator set– Automatic Transfer Switch– Automatic Transfer Switchboard

• Large power systems– Typically 4.16 kV or 12.47 kV– Automatic Transfer Switchgear– Single or Multiple generator sets– Utility Paralleling Switchgear

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Power System Design Considerations

• Neutral grounding– Solid grounded

• Most common in 480 V systems

– Low impedance grounded• Most common in medium voltage systems

– High impedance grounded• Less common• More complex to design• Generally provides higher reliability of service

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Contactor Based ATS

• Readily Available• Inexpensive• Open Transition• Requires external

protection– circuit breakers– fuses

NORMALSOURCE

OF POWER

CONTACTORTYPE ATS

EMERGENCYSOURCE OF

POWER

NORMALCIRCUIT

BREAKER

EMERGENCYCIRCUITBREAKER

OUTPUT TOCRITICAL LOADS

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

time (approx. 15 sec.)+ generator starting

Generator start delay

Outputto load

0

rated

rated

rated

sourceEmergency

sourceNormal

0

0

V(voltage)

t (time)

ATS Operation (Loss of Normal Source)

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

ATS Operation (Open Transition Return)

t (time)

(voltage)

0

0

rated

rated

rated

0

Outputto load

sourceEmergency

Normalsource

V Return to normaltime delay(5-30 min.)

Open transitiontransfer time(.05 - 3 sec.)

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.netCRITICAL LOADS

NORMALCIRCUIT

BREAKER

OF POWERSOURCENORMAL

OUTPUT TO

EMERGENCYCIRCUITBREAKER

OF POWER

EMERGENCYSOURCE

SOLIDSTATEATS

BREAKERCIRCUITOUTPUT

NORMALBYPASSCIRCUIT

BREAKER

EMERGENCYBYPASSCIRCUITBREAKER

Solid State ATS

• Very Fast transfer– (1/4 cycle)

• Very expensive• Typically used to transfer

between 2 constantlyavailable sources

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

NORMALSOURCE

OF POWEREMERGENCYSOURCE OF

POWER

NORMALCIRCUIT

BREAKER

EMERGENCYCIRCUITBREAKER

OUTPUT TOCRITICAL LOADS

CIRCUITBREAKERTYPE ATS

Circuit Breaker Based ATS

• Simple• Inexpensive• Power Switching Assy.

– Molded or Insulated case switch• External protection required

– Molded or Insulated case cb• No external protection required

• Open Transition

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

NORMALSOURCE

OF POWEREMERGENCYSOURCE OF

POWER

NORMALCIRCUIT

BREAKER

EMERGENCYCIRCUITBREAKER

OUTPUT TOCRITICAL LOADS

CIRCUITBREAKERTYPE ATS

Automatic Transfer Switchboard

• Familiar Circuit Breakertechnology

• Open or Closed Transition– 100msec or soft transfer

• Active / PassiveSynchronization

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

time (approx. 15 sec.)+ generator starting

Generator start delay

Outputto load

0

rated

rated

rated

sourceEmergency

sourceNormal

0

0

V(voltage)

t (time)

ATSB Operation (Loss of Normal Source)

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

ATSB Operation (Closed Transition Return)

t (time)

(voltage)

0

0

rated

rated

rated

0

Outputto load

sourceEmergency

Normalsource

V Return to normaltime delay(5-30 min.)

Synchronizationtime

Closed transitionre-transfer time(.1 - 300 sec.)

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Switchgear

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Automatic Transfer Switchgear

• Integration ofemergency powersource into the plantdistribution switchgear

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Switchgear

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Switchgear

• Back-up generation ready powerdistribution system design:– Provision for connection of generators– Equipment configuration

• Electrically operated circuit breakers, CTs, PTs andother accessories.

• Segregation of the load to allow cost effective loadshedding

– Site physical layout

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Switchgear

• Utility paralleling– Load testing of generators– Peak shaving

• Single large or Multiple small generators

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Peak Shaving

Utility Load Profile

MEG

AW

ATT

S

Customer Load Profile

Hours5 10 15 20 250

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Peak Sharing

Utility Load Profile

MEG

AW

ATT

S

Customer Load Profile

Hours5 10 15 20 250

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

0

500

1000

1500

2000

2500

0:00

2:00

4:00

6:00

8:00

10:0

0

12:0

0

14:0

0

16:0

0

18:0

0

20:0

0

22:0

0

TIME

KIL

OW

ATT

S

UTILITY

GEN

Baseload Control

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

0

200

400

600

800

1000

1200

1400

1600

0:00

2:00

4:00

6:00

8:00

10:0

0

12:0

0

14:0

0

16:0

0

18:0

0

20:0

0

22:0

0

EXPORTEDUTILITYGEN

Baseload Control

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

0

500

1000

1500

2000

2500

0:00

2:00

4:00

6:00

8:00

10:0

0

12:0

0

14:0

0

16:0

0

18:0

0

20:0

0

22:0

0

KIL

OW

ATT

S

GEN

UTILITY

Import Control

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

0

500

1000

1500

2000

2500

0:00

2:00

4:00

6:00

8:00

10:0

0

12:0

0

14:0

0

16:0

0

18:0

0

20:0

0

22:0

0

EXPORTED

SITE

Export Control

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

SCADA System

• Supervisory Control And Data Acquisition• System visualization and remote control• Events and alarm logging• Email event notification• Historical data logging• Full access from remote location• Ethernet connection

– Modbus TCP (port 502) interface– Http (port 80) web browser interface

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

SCADA Interface

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Economics

• Most common source of on-site emergencypower is diesel generator set.– Typical total cost of installed power system is

between $450 and $650 per kW• Factors affecting installed cost include:

– Power system voltage– Building or outdoor enclosed equipment– Fuel storage size and configuration– Specified equipment requirements

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Economics

• Natural Gas Genset based system.– Typical total cost of installed power system is

between $850 and $1200 per kW• Factors affecting installed cost include:

– Power system voltage– Building or outdoor enclosed equipment– Specified equipment requirements

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Financing• Alternative financing options through Energy

Services Companies– Expedite Financing and Construction projects by

utilizing Alternative Energy Related financingopportunities

– Taking advantage of the latest State Legislation– Qualifying factors for alternative financing options may include:

• Savings in water consumption costs, wastewater usage costsand other operating costs, and increase of billable revenues

• Guaranteed savings, Energy, Operations and Capitalavoidance.

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

Copyright © 2006 Advanced Power Technologies, Inc. www.aptinc.net

top related