Disconnects - NorthEast Electrical Distributors | Official … Spec.pdf · 2013-12-04 · Voltage Short Circuit Dimensions ... Disconnects Data Sheet: 1154 Type EP Cooper Bussmann
Post on 11-Jun-2018
215 Views
Preview:
Transcript
303
Disconnects
Disconnects
Section ContentsPage
Safety Module™ fused disconnect switch . . . . . . . . 304Coordination Module™ fused lighting and appliance panelboard . . . . . . . . . . . . . . . . . . . . . . . . 305Power Module™ — all-in-one elevator disconnect . . 306Fusible disconnects Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .307
30A Base & DIN rail mount switches . . . . . . . . . . . 308-309
60-100A Base & DIN rail mount switches . . . . . . . . . . . 310
Accessories for 60-100A switches . . . . . . . . . . . . . . . . 311
200-800A Base & DIN rail mount switches . . . . . . 312-313
30–800A, 600V 3-Pole enclosed switches . . . . . . . 314-315
30–800A 2-, 4- & 6-Pole enclosed switches . . . . . 316-317
Non-fusible disconnectsOverview for non-fusible switches . . . . . . . . . . . . . 318-319
16-100A Base & DIN rail mount switches . . . . . . . 320-321
16-100A door mounted switches . . . . . . . . . . . . . . . . . 322
400-800A switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323
Accessories for 400-800A switches . . . . . . . . . . . . . . . 324
16–80A, 600V 3-Pole enclosed switches . . . . . . . . . . . 325
16A-3150A, 600V 3-Pole enclosed switches . . . . . . . . . 326
16-400A 2-, 4- & 6-Pole enclosed switches . . . . . . 327-328
A/C Disconnects — fused and non-fused . . . . . . . . . 329Fused, dead front disconnect switches . . . . . . . . . . 330
RED indicates NEW information
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp304
Disconnects
Safety Module™ fused disconnect switch
SM363 _ _
Cooper Bussmann Safety Module™
SpecificationsDescription: A fused disconnect featuring enhanced safetyfeatures and use of the Cooper Bussmann CUBEFuse™.Optional rejection kits prevent overfusing 30 and 60 amp circuits. Padlockable handle and door interlock provide safetyduring maintenance procedures. Viewing window permitsviewing CUBEFuse permanent fuse indication status without opening the door.
Poles: 3
Enclosures: NEMA 1, 3R, 12 and 4X
Ratings:Volts: — 600Vac
Amps: — 0-100A
IR: — 50kA
Agency Information: CE, UL Listed and cUL Listed.
Features and Benefits• easyID™ fuse viewing window allows maintenance
personnel to quickly identify open fuses — without openingthe enclosure.
• Wide amp range in one unit provides installation flexibility —one Safety Module™ covers 1-100A applications.
• Rejection kits prevent overfusing 30A and 60A circuits.• Optional internal safety barrier covers all energized parts to
provide added protection against electrical hazards — evenwith the enclosure door open.
Accessories• Optional internal safety barriers• Solid neutral terminal• Auxiliary contacts• Rejection kits for 30 and 60 amp applications
Catalog Numbers
Catalog Amp NEMA Max. Hp Rating Dimensions (in)** Short CircuitNumbers* Rating Enclosure 240V 480V 600V Height Width Depth RatingSM363FG 100 1 20 40 50 16 8 5 50kASM363FR 100 3R 20 40 50 16 12 5 50kASM363FD 100 12 20 40 50 16 10 6 50kASM363FX 100 4XSS 20 40 50 16 12 6 50kA
* For safety barrier/rejection plate, add the suffix “B” to the catalog number, then add either; 1 for 30A, 2 for 60A or 3 for 100A. Example: SM363FGB3.NEMA 1 enclosures also available in gray. To order, place suffix “G” to the end of catalog number. Example: SM363FGG.NEMA 3R & 12 only available in gray.
** Does not include mounting tabs or handle. See Data Sheet for full dimensional data.
Coordination Module* Branch CircuitVoltage Short Circuit Dimensions (in) Main Device Amp Number of
Catalog Numbers Rating Rating Height Width Depth Type Amp Rating Rating CircuitsEP2M23012GCC 120/208 100kA** 36 28 5 3⁄4 MLO 200 30 12EP2M23024GCC 120/208 100kA** 38 28 5 3⁄4 MLO 200 30 24EP2M23036GCC 120/208 100kA** 48 28 5 3⁄4 MLO 200 30 36EP2M23042GCC 120/208 100kA** 48 28 5 3⁄4 MLO 200 30 42EP4M23012GCC 277/480 100kA*** 36 28 5 3⁄4 MLO 200 30 12EP4M23024GCC 277/480 100kA*** 36 28 5 3⁄4 MLO 200 30 24EP4M23036GCC 277/480 100kA*** 48 28 5 3⁄4 MLO 200 30 36EP4M23042GCC 277/480 100kA*** 48 28 5 3⁄4 MLO 200 30 42
* Meets UL 67 (Panelboards) and UL 50 (Cabinets and Boxes).** When protected by upstream LPN-RK 100A max. LPJ 200A max. or JJN 200A max., otherwise 10kA.*** When protected by upstream LPN-RK 200A max. LPJ 200A max. or JJN 200A max., otherwise 14kA.
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 305
Coordination Module™ fused lighting and appliance panelboard
Disconnects
Disconnects
Data Sheet: 1154
Type EP
Cooper Bussmann Coordination Module™
SpecificationsDescription: A fused lighting and appliance panelboard forbranch circuit applications. Specifically designed to meet the2005 NEC® Code requirements for selective coordination forEmergency, Legally Required Standby and Essential ElectricalSystems per 700.27, 701.18, and 517.26 when properly coordi-nated with the upstream overcurrent protective device feeder.
Circuits: 12, 24, 36, 42
Enclosure: NEMA 1
Ratings:Volts: — 120/208 or 277/480Vac
Branch Circuit Amps: — 0-30A
Short Circuit Rating : — 100kA
Agency Information: UL67, UL 50.
Features and Benefits• Complies with the new 2005 NEC® Selective Coordination
Requirements for Emergency, Legally Required Standby andEssential Electrical Systems per 700.27, 701.18, and 517.26when properly coordinated with the upstream overcurrent protective device feeder. Per the 2005 NEC®: Coordination(Selective) is the localization of an overcurrent condition torestrict outages to the circuit or equipment affected, accomplished by the choice of overcurrent protective devicesand their ratings or settings.
• Ensures system uptime with the goal of safety of human life during emergencies or for essential health care functions.
• Provides a fast and easy solution to meeting new coordinationCode requirements. Simply utilize published fuse selective coordination ratios to select the correct upstream fuse ratings.
• Offers significant savings compared to other fused panels andselectively coordinated circuit breaker systems.
Typical Applications• Hospitals• Schools• Commercial and industrial facilities
Catalog Numbers
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp306
Disconnects
Power Module™ — all-in-one elevator disconnect
PS Data Sheet: 1145 PMP Data Sheet: 1146
PMPPower Module™ Panel for multiple elevator applications
PSPower Module™ Switch for single elevator applications
PS & PMP
Cooper Bussmann® Power Module™
SpecificationsDescription: Fusible power switch with shunt trip and firesafety interface to allow for single point tie in with fire alarmsystem.
Ratings:Volts:— 600Vac, 3Ø
Amps:— 30-400A (PS)
— 30-400A (PMP feeder switches)
— 400-800A (PMP main switches*)
IR:— 200,000A rms*Contact Cooper Bussmann for applications greater than 800A.
Agency Information: Complies with NFPA 70 (NEC®;National Electrical Code®), ANSI/ASME A17.1 (Safety Codefor Elevators and Escalators), NFPA 72 (National Fire AlarmCode®)
— Power Module Switch; UL Listed (UL 98) Enclosed andDead front switch Guide 96NK3917, File E182262, NEMA 1,UL 50 Listed enclosure**, ULc per Canadian StandardsC22.2, No. 0-M91-CAN/CSA C22.2, No. 4-M89 Enclosedswitch.
**NEMA 12, 3R, and 4 enclosures also available
— Power Module Panel; UL Listed (UL 67) Panel Boards or(UL 891) Dead Front Switchboard, File E181664, ULc perCanadian Standards, Service Entrance Rated.
Features and Benefits• Internally powered, relay activated shunt trip system.• Mechanically interlocked auxiliary contact.• Self-contained adherence to elevator consensus standards,
NFPA 70 (NEC®). NFPA 72, ANSI/ASME 17.1.
Typical Applications• Elevator Disconnects• Computer Room Shunt Trip Disconnect• Fire Safety Interface Relay
Accessories• For added safety, use the Cooper Bussmann SAMI™ fuse
covers to improve maintenance personnel protection (OSHA 1910.333, paragraph C).
Ordering
The Cooper Bussmann Power Module switch and panel arefactory configured to the specific application. Contact yourCooper Bussmann representative to place your order. Haveall relevant electrical and circuit information on hand.
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 307
Disconnects
Disconnects
Overview for fusible disconnect switches
CFD30J3 CFD60J3 FD200J3FD400J3
Agency Information: UL listed, CSA certified, IEC rated, CE marked.
Catalog Numbers3-pole CFD30CC3 CFD30J3 CFD60J3 CFD100J3 FD200J3 FD400J3 FD600J3 FD800L3
General Purpose Amp Ratings
A 30 30 60 100 200 400 600 800
Approvals(1)2-pole N/A N/A N/A UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC3-pole UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC4-pole UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC
Technical Ratings (UL,CSA)
Max operating voltage V 600 600 600 600 600 600 600 600Max horsepower ratingThree phase 200-208V hp 5/7.5 5/7.5 15 25 50 100/125 150 200
240V hp 7.5 7.5 15 30 60 125 200 250480V hp 15 15 30 60 125 250 400 500600V hp 20 20 50 75 150 350 500 600
Single phase 120V hp 2 2 — — — — — —240V hp 3 3 — — — — — —
UL fuse class CC J J J J,T J,T J,T L
Technical Ratings (IEC)Rated insulation and operationalvoltage. ac20 and dc20(2) 1000 1000 750 750 1000 1000 1000 1000Rated thermal current, Ith
ac 20/dc 20 open A 32 32 63 125 250 400 630 800ac 20/dc 20 enclosed A 32 32 63 125 250 400 600 720ac 21A ≤500V A 32 32 63 125 250 400 630 800
≤690V A 32 32 63 125 250 400 630 800Rated operational power ac 23
400/415V kW 14/15 14/15 30 80/90 132/140 210/230 315/340 350/380690V kW 25 25 60 132 230 330 540 600
Physical CharacteristicsWeight 3-pole switch lb 1.54 1.54 2.86 3.30 15.21 17.2 37.48 37.48
4-pole lb 1.98 1.98 3.52 3.96 17.4 19.4 46.3 46.3Dimension 3-pole H in 3.82 3.82 3.94 5.66 7.87 7.87 11.42 11.42
W in 4.17 4.17 5.63 7.06 10.31 11.22 14.69 14.69D in 4.21 4.21 5.04 5.09 7.83 8.11 9.21 9.21
AccessoriesDouble break contacts S S S S S S S SFuse cover S S S • S S S STerminal lug kit Integral Integral Integral BDTL24 BDTL25 BDTL26 BDTL27 BDTL27Terminal shroud Not required Not required Not required • • • • •Auxiliary contact • • • • • • • •Handle UL/NEMA type
Type 1, 3R, 12 • • • • • • • •Type 1, 3R, 4, 4X, 12 • • • • • • • •
Conversion kit6-pole • • • • • • • •Transfer • • • • • • • •Bypass — — — — • • • •Mechanical interlock • • — — • • • •
Electrical interlock — — — — • • • •
S = Standard• = Available— = Not available(1) UL listed switches are also CSA certified(2) 1000V IEC 408
CFD30CC3 to FD800L3
CFD100J3
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp308
Disconnects
30A Base & DIN rail mount fusible disconnect switches
Catalog Shaft Length Mounting Depth(1)Numbers in (mm) in inchesCDS85S 3.3 (85) 5.5-5.7CDS105S 4.1 (105) 5.5-6.5CDS120S 4.7 (120) 5.5-7.1CDS130S 5.1 (130) 5.5-7.5CDS180S 7.1 (180) 6.3-9.4CDS250S 9.8 (250) 9.1-12.2CDS330S 13.0 (330) 12.2-15.4(1) Mounting depth is the distance from the outside of the door to the
disconnect switch mounting plate. Shaft can be cut to desired length.
Selector Handle 30A UL fuse Class J, CCFor a complete assembly, please select one of each:
• 1 switch• 1 shaft• 1 handle
CFD30J3 + CDS180S + CDH3S
CFD30J3
CDS_ _S
UL General Fuse Maximum Horsepower Rating TerminalCatalog Purpose Type Three Phase Lugs WireNumbers Poles Amp Rating 600V 200V 208V 240V 480V 600V Size/TypeCFD30J3 3 30 J 5 7.5 7.5 15 20 #18 – 8/CUCFD30CC3 3 30 CC 5 7.5 7.5 15 20 #18 – 8/CUCFD30J4 4 30 J 5 7.5 7.5 15 20 #18 – 8/CUCFD30CC4 4 30 CC 5 7.5 7.5 15 20 #18 – 8/CU
CDH3S, 5S CDH4S, 6S
Selector Handles — For use with shafts � 0.20 x 0.20" (� 5 x 5 mm)All marked both O/I & Off/On
Catalog NEMA IECNumbers Type Type Color Defeatable PadlockableCDH3S 1,3R,12 IP65 Black — YesCDH4S 1,3R,12 IP65 Red/Yellow — YesCDH5S 1,3R,12 IP65 Black Yes YesCDH6S 1,3R,12 IP65 Red/Yellow Yes Yes
Shafts — For use with CDH selector handles � 0.20 x 0.20" (� 5 x 5 mm)
30A/600V Switches
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 309
Disconnects
Disconnects
30A Base & DIN rail mount fusible disconnect switches
Catalog Shaft length Mounting Depth (1)Number in (mm) in inchesCDS48P 5.9 (150) 4.9-8.9CDS67P 6.7 (170) 5.9-9.7CDS49P 10.4 (265) 9.5-13.4CDS50P 15.8 (400) 15.0-18.7CDS99P 19.7 (500) 20.5-22.6(1) Mounting depth is the distance from the outside of the door to the
disconnect switch mounting plate. Shaft can be cut to desired length.
Catalog NEMA IEC LengthNumbers Type Type Color Marking in (mm) Defeatable PadlockableBDH104 1,3R,12 IP65 Black O/I&Off/On 1.8 (45) Yes YesBDH105 1,3R,12 IP65 Red/Yellow O/I&Off/On 1.8 (45) Yes YesBDH106 1,3R,12 IP65 Black O/I&Off/On 2.6 (65) Yes YesBDH107 1,3R,12 IP65 Red/Yellow O/I&Off/On 2.6 (65) Yes YesCDHXB65 1,3R,4,4X,12 IP65 Black O/I&Off/On 2.6 (65) Yes YesCDHXY65 1,3R,4,4X,12 IP65 Red/Yellow O/I&Off/On 2.6 (65) Yes YesBDH106T 1,3R,12 IP65 Black Off/On/Test 2.6 (65) Yes YesBDH107T 1,3R,12 IP65 Red/Yellow Off/On/Test 2.6 (65) Yes Yes
Pistol Handle 30A UL fuse Class J, CCFor a complete assembly, please select one of each:
• 1 switch• 1 shaft• 1 handle
CDS__ __P
CFD30J3 + CDS67P + BDH106
BDH104, 106 BDH105, 107
5.20"132mm
Catalog NEMA LengthNumber Type Color Marking in (mm) PadlockableBDH79 1 Black O/I/Test 5.2 (132) Yes
BDH795.20"/132mm
BDH79 Mounted DepthBDH79 Mounted
CFD30J3
UL General Fuse Maximum Horsepower Rating TerminalCatalog Purpose Type Three Phase Lugs WireNumbers Poles Amp Rating 600V 200V 208V 240V 480V 600V Size/TypeCFD30J3 3 30 J 5 7.5 7.5 15 20 #18 – 8/CUCFD30CC3 3 30 CC 5 7.5 7.5 15 20 #18 – 8/CUCFD30J4 4 30 J 5 7.5 7.5 15 20 #18 – 8/CUCFD30CC4 4 30 CC 5 7.5 7.5 15 20 #18 – 8/CU
30A/600V Switches
ShaftsFor use with pistol handles � 0.20 x 0.20" (� 5 x 5 mm)
Pistol HandlesFor use with shafts � 0.20 x 0.20" (� 5 x 5 mm)
Direct Mount HandleMounts directly to switch, no shaft necessary
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp310
Disconnects
Twisted ShaftsRotates handle 45° � 0.24 x 0.24" (� 6 x 6 mm)Catalog Shaft Length Mounting Depth (1)Numbers in (mm) in inchesBDST4 5.1 (130 4.8-7.8BDST25 8.3 (210 8.0-11.0BDST29 11.4 (290 11.0-14.0BDST30 14.2 (360 13.8-16.8(1) Mounting depth is the distance from the outside of the door to the disconnectswitch mounting plate. Shaft can be cut to desired length.
Shafts — � 0.24 x 0.24" (� 6 x 6 mm)Catalog Shaft Length Mounting Depth (1)Numbers in (mm) in inchesBDS150 5.9 (150) 5.5-8.5BDS210 8.3 (210) 8.0-11.0BDS290 11.4 (290) 11.0-14.0BDS360 14.2 (360) 13.8-16.8BDS430 16.9 (430) 16.5-19.7(1) Mounting depth is the distance from the outside of the door to the disconnectswitch mounting plate. Shaft can be cut to desired length.
60-100A Base & DIN rail mount fusible disconnectswitches
BDH59, 61
BDH58, 60
Pistol Handle 60-100A UL fuse Class JFor a complete assembly, please select one of each:
• 1 switch• 1 shaft• 1 handle• 1 terminal lug kit
CFD60J3 CFD100J3
BDST__
BDS__
CFD60J3 + BDS210 + BDH59
60—100A/600V SwitchesUL General UL Fuse Maximum Horsepower Rating
Catalog Purpose Type Three PhaseNumber Poles Amp Rating 600V 200V 208V 240V 480V 600VCFD60J3 3 60 J 15 15 15 30 50CFD100J3 3 100 J 25 25 30 60 75CFD60J4 4 60 J 15 15 15 30 50CFD100J4 4 100 J 25 25 30 60 75
Pistol Handles — � 0.24 x 0.24" (� 6 x 6 mm)Catalog NEMA IEC LengthNumbers Type Type Color in (mm) Marking Defeatable PadlockableBDH58 1,3R,12 IP65 Black 2.6 (65) O/I & Off/On Yes YesBDH59 1,3R,12 IP65 Red/Yel 2.6 (65) O/I & Off/On Yes YesBDH60 1,3R,12 IP65 Black 3.1 (80) O/I & Off/On Yes YesBDH61 1,3R,12 IP65 Red/Yel 3.1 (80) O/I & Off/On Yes YesCDHXB86 1,3R,4,4X,12 IP65 Black 3.1 (80) O/I & Off/On Yes YesCDHXY86 1,3R,4,4X,12 IP65 Red/Yel 3.1 (80) O/I & Off/On Yes Yes
Direct Mount HandleMounts directly to switch, no shaft necessaryCatalog NEMANumber Type Color Marking Length(mm) PadlockableCDH4 1 Black O/I/Test 50 Yes
CDH4
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 311
Disconnects
Disconnects
Accessories for 60-100A fusible disconnect switches
NDNA100
CDAUX10 CDAUX01K
BDTL24
CFC60J
CFCVR100
CFTS100
CFZ1
Terminal Lug KitCatalog Wire TerminalNumbers For Use On: Wire Size Type Lugs Per KitIntegral CFD60J_ #14-4 CU —BDTL24 CFD100J_ #14-2/0 CU/AL 6
Auxiliary ContactsCatalog AC Thermal AC RatedNumbers Description For Use On: Amp Rating VoltageCDAUX10 1 NO 10 600CDAUX01K 1 NC CFD60 – CFD100 10 600
Replacement Fuse ClipCatalog Number Description For Use On:CFC60J Removable fuse carrier CFD60
Replacement Fuse CoversCatalog Number Description For Use On:CFCVR100 Transparent fuse cover CFD100
Terminal ShroudCatalogNumber Description For Use On:CFTS100 Includes one terminal shroud for line or load side CFD100, 1-Pole
Terminal PolesCatalog AC Thermal AC RatedNumbers Description For Use On: Amp Rating VoltageCFZ1 Detachable neutral CFD60 63 600CFZ2 mounts on side of switch or DIN rail CFD100 125
DIN RailCatalog LengthNumbers Description For Use On: in(cm)NDNA100 35mm Aluminum DIN Rail CFD60 39.4 (100)
“T” Type Fuse Adapter KitCatalog Number Description For Use On:BDTA1 100A, 600V CFD100
BDTA1
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp312
Disconnects
Twisted Shafts
Rotates handle 45° � 0.47 x 0.47" (� 12 x 12 mm)Catalog Shaft Length Mounting Depth (1)Number in (mm) in inches
For use on FD200J_ – FD400J_BDS28045 11.0 (280) 10.2-14.5BDS32545 12.8 (325) 12.0-16.3BDS46545 18.3 (465) 17.5-21.9
For use on FD600J_ – FD800J_BDS28045 11.0 (280) 11.2-14.0BDS32545 12.8 (325) 13.0-15.8BDS46545 18.3 (465) 18.5-21.3(1) Mounting depth is the distance from the outside of the door to the
disconnect switch mounting plate. Shaft can be cut to desired length.
Shafts — � 0.47 x 0.47" (� 12 x 12 mm)Catalog Shaft Length Mounting Depth(1)Number in (mm) in inches
For use on FD200J_ – FD400J_BDS220 8.7 (220) 7.9-12.2BDS250 9.8 (250) 9.1-13.4BDS280 11.0 (280) 10.2-14.5BDS325 12.8 (325) 12.0-16.3BDS395 15.6 (395) 14.8-19.1BDS465 18.3 (465) 17.5-21.9BDS535 21.1 (535) 20.3-24.6
For use on FD600J_ – FD800J_BDS250 9.8 (250) 10.0-12.8BDS280 11.0 (280) 11.2-14.0BDS325 12.8 (325) 13.0-15.8BDS395 15.6 (395) 15.8-18.6BDS465 18.3 (465) 18.5-21.3BDS535 21.1 (535) 21.1-24.1(1) Mounting depth is the distance from the outside of the door to the
disconnect switch mounting plate. Shaft can be cut to desired length.
200-800A Base & DIN rail mount fusible disconnect switches
Pistol Handle 200-800A UL fuse Class J, T, LFor a complete assembly, please select one ofeach:
• 1 switch• 1 shaft• 1 handle• 1 terminal lug kit
FD600J3FD800L3
FD200J3 + BDS280 + BDH114 + BDTL25
FD400J3
BDS_45
BDS_
200—800A, 600V SwitchesUL General UL Fuse Maximum Horsepower Rating
Catalog Purpose Type Three PhaseNumber Poles Amp Rating 600V 200V 208V 240V 480V 600VFD200J2 2 200 J(1) — — — — —FD400J2 2 400 J(1) — — — — —FD600J2 2 600 J(1) — — — — —FD800L2 2 800 L — — — — —FD200J3 3 200 J(1) 50 50 60 125 150FD400J3 3 400 J(1) 100 125 125 250 350FD600J3 3 600 J(1) 150 150 200 400 500FD800L3 3 800 L 200 200 250 500 600FD200J4 4 200 J(1) 50 50 60 125 150FD400J4 4 400 J(1) 100 125 125 250 350FD600J4 4 600 J(1) 150 150 200 400 500FD800L4 4 800 L 200 200 250 500 600(1) J type fuse clips are standard. If 600V Type “T” clips are desired, please order a "T" type fuse adapter kit.
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 313
Disconnects
Disconnects
200-800A Base & DIN rail mount fusible disconnect switches
BDTA
BDTL25
BDTL175BDTL175/400
BDTL26
BDTL27
Pistol Handles — � 0.47 x 0.47" (� 12 x 12 mm)Catalog NEMA IEC LengthNumbers Type Type Color in (mm) Marking Defeatable PadlockableBDH112 1,3R,12 IP65 Black 4.9 (125) O/I & Off/On Yes YesBDH113 1,3R,12 IP65 Red/Yellow 4.9 (125) O/I & Off/On Yes YesBDH114 1,3R,12 IP65 Black 5.7 (145) O/I & Off/On Yes YesBDH115 1,3R,12 IP65 Red/Yellow 5.7 (145) O/I & Off/On Yes YesBDH116 1,3R,12 IP65 Black 6.9 (175) O/I & Off/On Yes YesBDH117 1,3R,12 IP65 Red/Yellow 6.9 (175) O/I & Off/On Yes YesCDHXB12 1,3R,4,4X,12 IP65 Black 5.7 (145) O/I & Off/On Yes YesCDHXY12 1,3R,4,4X,12 IP65 Red/Yellow 5.7 (145) O/I & Off/On Yes YesCDHXB22 1,3R,4,4X,12 IP65 Black 6.9 (175) O/I & Off/On Yes YesCDHXY22 1,3R,4,4X,12 IP65 Red/Yellow 6.9 (175) O/I & Off/On Yes YesBDH8 1,3R,4,4X,12 IP65 Metal 8.7 (220) Off/On — Yes
Terminal Lug KitCatalog Wire TerminalNumbers For Use On: Wire Size Type Lugs Per KitBDTL25 FD200J_ #6 – 300 kcmil CU/AL 6BDTL175 FD200J (6) #14 – 6 kcmil CU/AL 3BDTL26 FD400J_ #2 – 600 kcmil CU/AL 6BDTL175/400 FD600J – FD800L (12) #14 – 16–600 kcmil CU/AL 3BDTL27 FD600J_ & FD800L_ (2) #2 – 600 kcmil CU/AL 6
“T” Type Fuse Adapter KitCatalog AC Thermal AC RatedNumber Poles For Use On: Amp Rating VoltageBDTA2 3 FD200J_ 200 600BDTA4 3 FD400J_ 400 600BDTA6 3 FD600J_ 600 600BDTA8 3 FD800J_ 800 600
BDH112
Protect the Promise of CustomerSatisfaction
Our customer satisfaction team answers your calls8:00 a.m. – 4:30 p.m. for all US time zones,receiving and responding to an average of 1600calls and 700 emails every day.
We also offer emergency after-hours service.
Phone: 636-527-3877email: busscustsat@cooperbussmann.comToll-free fax: 800-544-2570Emergency after-hour phone: 314-995-1342
Did You Know?
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp314
Disconnects
Catalog NumbersUL General Fuse Catalog Numbers (1)Purpose Class NEMA/UL Enclosure TypeAmp Rating Type 4X Plastic 12 7 & 930 J EFJ30P-3PB6 EFJ302-3PB6 EFJ307-3PB30 CC EFC30P-3PB6 EFC302-3PB6 EFC307-3PB60 J(2) EFJ60P-3PB8 EFJ602-3PB6 EFJ607-3PB100 J(2) EFJ100P-3PB8 EFJ1002-3PB8 EFJ1007-3PB200 J(2) EFJ200P-3PB4 EFJ2002-3PB4 EFJ2007-3PB400 J(2) EFJ400P-3PB4 EFJ4002-3PB4 EFJ4007-3PB600 J(2) EFJ600P-3PB4 EFJ6002-3PB4 EFJ6007-3PB800 J(2) EFL800P-3PB4 EFL8002-3PB4 EFL8007-3PB(1) Fusible switches are UL listed to the UL98 standard.(2) 600V T type fuse clips may be substituted at no charge. Please change the second character of the catalognumber from "J" to "T."
30–800A, 600V 3-Pole enclosed fusible disconnect switches
Catalog NumbersUL General Fuse Catalog Numbers (1)Purpose Class/ NEMA/UL Enclosure TypeAmp Rating Type 1 3R 4 4X Stainless30 J EFJ301-3PB6 EFJ303-3PB6 EFJ304-3PB6 EFJ30X-3PB630 CC EFC301-3PB6 EFC303-3PB6 EFC304-3PB6 EFC30X-3PB660 J(2) EFJ601-3PB6 EFJ603-3PB6 EFJ604-3PB8 EFJ60X-3PB8100 J(2) EFJ1001-3PB8 EFJ1003-3PB8 EFJ1004-3PB8 EFJ100X-3PB8200 J(2) EFJ2001-3PB4 EFJ2003-3PB4 EFJ2004-3PB4 EFJ200X-3PB4400 J(2) EFJ4001-3PB4 EFJ4003-3PB4 EFJ4004-3PB4 EFJ400X-3PB4600 J(2) EFJ6001-3PB4 EFJ6003-3PB4 EFJ6004-3PB4 EFJ600X-3PB4800 J(2) EFL8001-3PB4 EFL8003-3PB4 EFL8004-3PB4 EFL800X-3PB4(1) Fusible switches are UL listed to the UL98 standard.(2) 600V T type fuse clips may be substituted at no charge. Please change the second character of the catalog number from "J" to "T."
Pistol Handle NEMA 1, 3R, 4 and 4X, ULfuse Class J, CC
NEMA 4X, 12 and 7&9, UL fuse Class J, CC
EFJ30X-3PB6
CFD30J3
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 315
Disconnects
Disconnects
30–800A, 600V 3-Pole enclosed fusible disconnect switches
Switch RatingsUL General Maximum Horsepower RatingPurpose Single Phase Three Phase Wire Size For For WireAmp Rating 120V 200V 240V 200V 208V 240V 480V 600V Terminal Lugs Type Approval(1)30 2 3 5 5 7.5 7.5 15 20 #18 – 8 CU CSA, UL60 3 7.5 10 15 15 15 30 50 #14 – 4 CU CSA, UL100 5 10 15 25 25 30 60 75 #14 – 2/0 CU/AL CSA, UL200 — — — 50 50 60 125 150 #6 – 300 kcmil CU/AL CSA, UL400 — — — 100 125 125 250 350 #2 – 600 kcmil CU/AL CSA, UL600 — — — 150 150 200 400 500 (2) #2 – 600 kcmil CU/AL CSA, UL800 — — — 200 200 250 500 600 (2) #2 – 600 kcmil CU/AL CSA, UL(1) Fusible switches are UL listed to the UL98 standard.
Handle RatingsCatalog Catalog Amp Handle NEMANumbers No. Suffix Range Type Rating Color Marking Defeatable PadlockableCDH5S BJ 30 Selector 1,3R,12 Black 0/I & Off/On Yes YesCDH6S YJ 30 Selector 1,3R,12 Red/Yel 0/I & Off/On Yes YesBDH106 B6 30 Pistol 1,3R,12 Black 0/I & Off/On Yes YesBDH107 Y6 30 Pistol 1,3R,12 Red/Yel 0/I & Off/On Yes YesCDHXB65 B6 30 Pistol 1,3R,4,4X,12 Black 0/I & Off/On Yes YesCDHXY65 Y6 30 Pistol 1,3R,4,4X,12 Red/Yel 0/I & Off/On Yes YesBDH58 B6 60-100 Pistol 1,3R,12 Black 0/I & Off/On Yes YesBDH59 Y6 60-100 Pistol 1,3R,12 Red/Yel 0/I & Off/On Yes YesBDH60 B8 60-100 Pistol 1,3R,12 Black 0/I & Off/On Yes YesBDH61 Y8 60-100 Pistol 1,3R,12 Red/Yel 0/I & Off/On Yes YesCDHXB86 B8 60-100 Pistol 1,3R,4,4X,12 Black 0/I & Off/On Yes YesCDHXY86 Y8 60-100 Pistol 1,3R,4,4X,12 Red/Yel 0/I & Off/On Yes YesBDH114 B4 200-800 Pistol 1,3R,12 Black 0/I & Off/On Yes YesBDH115 Y4 200-800 Pistol 1,3R,12 Red/Yel 0/I & Off/On Yes YesBDH116 B7 200-800 Pistol 1,3R,12 Black 0/I & Off/On Yes YesBDH117 Y7 200-800 Pistol 1,3R,12 Red/Yel 0/I & Off/On Yes YesCDHXB12 B4 200-800 Pistol 1,3R 4,4X,12 Black 0/I & Off/On Yes YesCDHXY12 Y4 200-800 Pistol 1,3R 4,4X,12 Red/Yel 0/I & Off/On Yes YesCDHXB22 B7 200-800 Pistol 1,3R 4,4X,12 Black 0/I & Off/On Yes YesCDHXY22 Y7 200-800 Pistol 1,3R 4,4X,12 Red/Yel 0/I & Off/On Yes YesBDH8 8 200-800 Pistol 1,3R 4,4X,12 Metal 0/I & Off/On No Yes
Easy Internet Access to Product andTechnical Information
All of the following functions are available on-line atwww.cooperbussmann.com:• Product cross-reference• Product catalogs• Technical specification sheets• Current events/news releases• Training seminar schedule• Training modules• Technical software solutions
Did You Know?
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp316
Disconnects
30–800A 2-, 4- and 6-Pole enclosed fusible disconnect switches
(2) = Three-poles
2-Pole
4-Pole
6-Pole
(2)
NEMA 1, 3R and 4X for Transfer, Bypass and MechanicalInterlock Applications
Catalog NumbersUL General Catalog NumbersPurpose Switch NEMA Enclosure TypeAmp Rating Type 1 3R 4 4X Stainless30 (Class J fuses) 4-Pole(1) EFJ301-4PB6 EFJ303-4PB6 EFJ304-4PB6 EFJ30X-4PB6
6-Pole EFJ301-6PB6 EFJ303-6PB6 EFJ304-6PB6 EFJ30X-6PBTransfer EFJ301-3TB8 EFJ303-3TB8 EFJ304-3TB8 EFJ30X-3TB8Bypass EFJ301-3BB6 EFJ303-3BB6 EFJ304-3BB6 EFJ30X-3BB6Mech. interlock EFJ301-3MB6 EFJ303-3MB6 EFJ304-3MB6 EFJ30X-3MB6
30 (Class CC fuses) 4-Pole(1) EFC301-4PB6 EFC303-4PB6 EFC304-4PB6 EFC30X-4PB66-Pole EFC301-6PB6 EFC303-6PB6 EFC304-6PB6 EFC30X-6PB6Transfer EFC301-3TB8 EFC303-3TB8 EFC304-3TB8 EFC30X-3TB8Bypass EFC301-3BB6 EFC303-3BB6 EFC304-3BB6 EFC30X-3BB6Mech. interlock EFC301-3MB6 EFC303-3MB6 EFC304-3MB6 EFC30X-3MB6
60 4-Pole(1) EFJ601-4PB6 EFJ603-4PB6 EFJ604-4PB6 EFJ60X-4PB66-Pole EFJ601-6PB4 EFJ603-6PB4 EFJ604-6PB4 EFJ60X-6PB4Transfer EFJ601-3TB8 EFJ603-3TB8 EFJ604-3TB8 EFJ60X-3TB8Mech. interlock EFJ601-3MB6 EFJ603-3MB6 EFJ604-3MB6 EFJ60X-3MB6
100 2-Pole(1) EFJ1001-2PB8 EFJ1003-2PB8 EFJ1004-2PB8 EFJ100X-2PB84-Pole(1) EFJ1001-4PB8 EFJ1003-4PB8 EFJ1004-4PB8 EFJ100X-4PB86-Pole EFJ1001-6PB4 EFJ1003-6PB4 EFJ1004-6PB4 EFJ100X-6PB4Transfer EFJ1001-3TB8 EFJ1003-3TB8 EFJ1004-3TB8 EFJ100X-3TB8Mech. interlock EFJ1001-3MB8 EFJ1003-3MB8 EFJ1004-3MB8 EFJ100X-3MB8
200 2-Pole(1) EFJ2001-2PB8 EFJ2003-2PB8 EFJ2004-2PB8 EFJ200X-2PB84-Pole(1) EFJ2001-4PB4 EFJ2003-4PB4 EFJ2004-4PB4 EFJ200X-4PB46-Pole EFJ2001-6P8 EFJ2003-6P8 EFJ2004-6P8 EFJ200X-6P8Transfer EFJ2001-3TB4 EFJ2003-3TB4 EFJ2004-3TB4 EFJ200X-3TB4Bypass EFJ2001-3B6 EFJ2003-3B6 EFJ2004-3B6 EFJ200X-3B6Mech. interlock EFJ2001-3MB4 EFJ2003-3MB4 EFJ2004-3MB4 EFJ200X-3MB4
400 2-Pole(1) EFJ4001-2PB4 EFJ4003-2PB4 EFJ4004-2PB4 EFJ400X-2PB44-Pole(1) EFJ4001-4PB4 EFJ4003-4PB4 EFJ4004-4PB4 EFJ400X-4PB46-Pole EFJ4001-6P8 EFJ4003-6P8 EFJ4004-6P8 EFJ400X-6P8Transfer EFJ4001-3TB4 EFJ4003-3TB4 EFJ4004-3TB4 EFJ400X-3TB4Bypass EFJ4001-3B6 EFJ4003-3B6 EFJ4004-3B6 EFJ400X-3B6Mech. interlock EFJ4001-3MB4 EFJ4003-3MB4 EFJ4004-3MB4 EFJ400X-3MB4
600 2-Pole(1) EFJ6001-2PB4 EFJ6003-2PB4 EFJ6004-2PB4 EFJ600X-2PB44-Pole(1) EFJ6001-4PB4 EFJ6003-4PB4 EFJ6004-4PB4 EFJ600X-4PB46-Pole EFJ6001-6P8 EFJ6003-6P8 EFJ6004-6P8 EFJ600X-6P8Transfer EFJ6001-3TB4 EFJ6003-3TB4 EFJ6004-3TB4 EFJ600X-3TB4Bypass EFJ6001-3B6 EFJ6003-3B6 EFJ6004-3B6 EFJ600X-3B6Mech. interlock EFJ6001-3MB4 EFJ6003-3MB4 EFJ6004-3MB4 EFJ600X-3MB4
800 2-Pole(1) EFL8001-2PB4 EFL8003-2PB4 EFL8004-2PB4 EFL800X-2PB44-Pole(1) EFL8001-4PB4 EFL8003-4PB4 EFL8004-4PB4 EFL800X-4PB46-Pole EFL8001-6P8 EFL8003-6P8 EFL8004-6P8 EFL800X-6P8Transfer EFL8001-3TB4 EFL8003-3TB4 EFL8004-3TB4 EFL800X-3TB4Bypass EFL8001-3B6 EFL8003-3B6 EFL8004-3B6 EFL800X-3B6Mech. interlock EFL8001-3MB4 EFL8003-3MB4 EFL8004-3MB4 EFL800X-3MB4
(1) IEC rated only.
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 317
Disconnects
Disconnects
NEMA 4X, 12 and 7&9 for Transfer, Bypass andMechanical Interlock Applications
Catalog NumbersUL General Catalog NumbersPurpose Switch NEMA Enclosure TypeAmp Rating Type 4X Plastic 12 7 & 930 (Class J fuses) 4-Pole(1) EFJ30P-4PB6 EFJ302-4PB6 (2)
6-Pole EFJ30P-6PB6 EFJ302-6PB6Transfer EFJ30P-3TB8 EFJ302-3TB8Bypass EFJ30P-3BB6 EFJ302-3BB6Mech. interlock EFJ30P-3MB6 EFJ302-3MB6
30 (Class CC fuses) 4-Pole(1) EFC30P-4PB6 EFC302-4PB6 (2)6-Pole EFC30P-6PB6 EFC302-6PB6Transfer EFC30P-3TB8 EFC302-3TB8Bypass EFC30P-3BB6 EFC302-3BB6Mech. interlock EFC30P-3MB6 EFC302-3MB6
60 4-Pole(1) EFJ60P-4PB6 EFJ602-4PB6 (2)6-Pole EFJ60P-6PB4 EFJ602-6PB4Transfer EFJ60P-3TB8 EFJ602-3TB8Mech. interlock EFJ60P-3MB6 EFJ602-3MB6
100 2-Pole(1) EFJ100P-2PB8 EFJ1002-2PB8 (2)4-Pole(1) EFJ100P-4PB8 EFJ1002-4PB86-Pole EFJ100P-6PB4 EFJ1002-6PB4Transfer EFJ100P-3TB8 EFJ1002-3TB8Mech. interlock EFJ100P-3MB8 EFJ1002-3MB8
200 2-Pole(1) EFJ200P-2PB8 EFJ2002-2PB8 (2)4-Pole(1) EFJ200P-4PB4 EFJ2002-4PB46-Pole EFJ200P-6P8 EFJ2002-6P8Transfer EFJ200P-3TB4 EFJ2002-3TB4Bypass EFJ200P-3B6 EFJ2002-3B6Mech. interlock EFJ200P-3MB4 EFJ2002-3MB4
400 2-Pole(1) EFJ400P-2PB4 EFJ4002-2PB4 (2)4-Pole(1) EFJ400P-4PB4 EFJ4002-4PB46-Pole EFJ400P-6P8 EFJ4002-6P8Transfer EFJ400P-3TB4 EFJ4002-3TB4Bypass EFJ400P-3B6 EFJ4002-3B6Mech. interlock EFJ400P-3MB4 EFJ4002-3MB4
600 2-Pole(1) EFJ600P-2PB4 EFJ6002-2PB4 (2)4-Pole(1) EFJ600P-4PB4 EFJ6002-4PB46-Pole EFJ600P-6P8 EFJ6002-6P8Transfer EFJ600P-3TB4 EFJ6002-3TB4Bypass EFJ600P-3B6 EFJ6002-3B6Mech. interlock EFJ600P-3MB4 EFJ6002-3MB4
800 2-Pole(1) EFL800P-2PB4 EFL8002-2PB4 (2)4-Pole(1) EFL800P-4PB4 EFL8002-4PB46-Pole EFL800P-6P8 EFL8002-6P8Transfer EFL800P-3TB4 EFL8002-3TB4Bypass EFL800P-3B6 EFL8002-3B6Mech. interlock EFL800P-3MB4 EFL8002-3MB4
(1) IEC rated only.(2) Consult factory for pricing and availability.
30–800A 2-, 4- and 6-Pole enclosed fusible disconnect switches
(3) = Three-poles
Transfer(3)
Bypass
(3)
MechanicalInterlock
(3)
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp318
Disconnects
Overview for non-fusible disconnect switches
CDNF160CDNF30 CDNF60 CDNF100CDNF16 CDNF25 CDNF32
Catalog Number3-pole CDNF16 CDNF25 CDNF32 CDNF45 CDNF63 CDNF30 CDNF60 CDNF100 CDNF160
General Purpose Amp Rating
A 16 25 40 60 80 30 60 100 125
Approvals(1)2-pole N/A N/A N/A N/A N/A N/A N/A N/A UL983-pole UL508 UL508 UL508 UL508 UL508 UL98 UL98 UL98 UL984-pole UL508 UL508 UL508 UL508 UL508 UL98 UL98 UL98 UL98
Technical Ratings UL,CSA
Max operating voltage V 600 600 600 600 600 600 600 600 600Max horsepower ratingThree phase
200 – 208V hp 3 7.5 10 15 20 10 20 25 30240V hp 5 7.5 10 15 20 10 20 30 30480V hp 10 15 20 30 40 20 40 50 75600V hp 10 20 25 30 40 30 40 50 100
Single phase120V hp 1/2 3/4 1 2 2 2 3 5 7.5240V hp 1.5 2 3 5 5 5 7.5 15 20
Technical Ratings IECRated insulation andoperational voltageac20 and dc20 V 750 750 750 750 750 750 750 750 750Rated thermal current, Ith
ac 20/dc 20 open A 25 32 40 63 80 40 63 115 200ac 20/dc 20 enclosed A 25 32 40 63 80 40 63 115 160ac 21A 500V A 16 25 32 63 80 40 63 100 160
690V A 16 25 32 63 80 40 63 100 160Rated operational power ac23
400/415V kW 7.5 9 11 22 37 15 18.5 37 75690V kW 7.5 9 11 15 18.5 15 15 37 75
Physical Characteristics
Weight 3-pole lb 0.24 0.24 0.24 0.59 0.59 0.79 0.79 0.79 2.42Dimension 3-pole H in 2.68 2.68 2.68 3.60 3.60 3.94 3.94 3.94 5.00
W in 1.38 1.38 1.38 2.07 2.07 2.76 2.76 2.76 4.96D in 2.20 2.20 2.20 2.85 2.85 2.95 2.95 2.95 2.93
AccessoriesTerminal lug kit Integral Integral Integral Integral Integral Integral Integral Integral IntegralTerminal shroud • • • • • • • • •Auxiliary contact • • • • • • • • •Handle UL/NEMA type
Type 1, 3R, 12 • • • • • • • • •Type 1, 3R, 4, 4X, 12 • • • • • • • • •
Handle typeSelector • • • • • — — — —Pistol • • • • • • • • •
Conversion kits6-pole • • • • • • • • •Transfer • • • • • • • • •Bypass • • • • • • • • •Mechanical interlock • • • • • • • — •
Electrical interlock — — — — — — — — —• = Available— = Not available(1) UL listed switches are also CSA certified.
CDNF16 to CDNF160
Agency Information: UL listed, CSA certified, IEC rated, CE marked
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 319
Disconnects
Disconnects
Overview for non-fusible disconnect switches
Catalog Number3-pole BDNF175A BDNF200A BDNF400 BDNF600A BDNF800A BDNF1200 BDNF1600 BDNF2000 BDNF3150
General Purpose Amp Rating
A 175 200 400 600 800 1200 1600 2000 3150
Approvals(1)2-pole UL508 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC IEC3-pole UL508 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC IEC4-pole IEC IEC UL98 & IEC UL98 & IEC IEC IEC IEC IEC IEC
Technical Ratings UL, CSA
Max operating voltage V 600 600 600 600 600 600 600 600 600Max horsepower ratingThree phase
200 – 208V hp 30 60 100 150 200 — — — —240V hp 40 75 125 200 250 — — — —480V hp 75 150 250 400 500 — — — —600V hp 100 200 350 500 600 — — — —
Single phase120V hp — — — — — — — — —240V hp — — — — — — — — —
Technical Ratings IECRated insulation andoperational voltage.ac20 and dc20 V 1000 1000 1000 1000 1000 1000 1000 1000 1000Rated thermal current, Ith
ac 20/dc 20open A 200 315 630 800 1250 1600 2500 2500 3150ac 20/dc 20 enclosed A 200 270 630 720 1250 1600 2300 2300 2600ac 21A 500V A 200 250 630 800 1250 1600 2500 2500 3150
690V A 200 250 630 800 1250 1600 2500 2500 3150Rated operational power ac23
400/415V kW 90 132 315 355 400 400 400 400 400690V kW 170 200 355 355 — — — — —
Physical Characteristics
Weight 3-pole lb 6.61 6.61 13.66 13.66 35.9 38.55 127.7 127.7 127.7Dimension 3-pole H in 8.35 8.35 11.81 11.77 19.09 19.09 25.04 25.04 25.04
W in 7.83 8.62 10.24 11.93 14.29 14.29 18.43 18.43 18.43D in 4.55 4.55 5.12 5.12 4.92 4.92 10.67 10.67 10.67
AccessoriesTerminal lug kit BDTL25 BDTL25 BDTL26 BDTL27 BDTL30 BDTL28 BDTL28 BDTL28/2 BDTL28/2Terminal shroud • • • • • • — — —Auxiliary contact • • • • • • • • •Handle UL/NEMA type
Type 1, 3R, 12 • • • • • • • • •Type 1, 3R, 4, 4X, 12 • • • • • • • • •
Handle typeSelector — — — — — — — — —Pistol • • • • • • • • •
Conversion kits6-pole • • • • • • — — —Transfer • • • • • • — — —Bypass • • • • • • — — —Mechanical interlock • • • • • • • • •
Electrical interlock • • • • • • • • •S = Standard feature• = Available— = Not available(1) UL listed switches are also CSA certified.
BDNF200ADNF400A
BDNF600A
BDNF800ABDNF1200 BDNF1600 BDNF2000 BDNF3150
BDNF175A
BDNF175A to BDNF3150
Agency Information: UL listed, CSA certified, IEC rated, CE marked
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp320
Disconnects
16-100A Base & DIN rail mount non-fusibledisconnect switches
Selector Handle 16-100A 3-PoleFor a complete assembly, please select one of each:
• 1 switch• 1 shaft• 1 handle
CDNF30CDNF60CDNF100
CDNF60 + CDS85S + CDH3S
CDNF16CDNF25CDNF32
CDS_ S
CDH15SCDH3S CDH6S
CDMC1
OPMRH CDBY68419/1
UL General Maximum Horsepower RatingCatalog Purpose IEC AC21 Single Phase Three Phase Terminal LugsNumbers Amp Rating Amp Rating 120V 240V 240V 480V 600V Wire Size/TypeCDNF16 16 16 1⁄2 1.5 5 10 10 #18-8/CUCDNF25 25 25 3⁄4 2 7.5 15 20 #18-8/CUCDNF32 40 40 1 3 10 20 25 #18-8/CUCDNF45 60 63 2 5 15 30 30 #14-4/CUCDNF63 80 80 2 5 20 40 40 #14-4/CUCDNF30 30 40 2 5 10 20 30 #14-4/CUCDNF60 60 63 3 7.5 20 40 40 #14-4/CUCDNF100 100 115 5 15 30 50 50 #8-1/0/CU(1) A snap-on fourth pole may be added.
All marked both O/I & Off/OnCatalog Numbers NEMA Type IEC Type Color Defeatable PadlockableCDH1S(3) 1 IP54 Black — —CDH2S(3) 1 IP54 Red/Yellow — —CDH15S(3) 1 IP54 Black — YesCDH16S(3) 1 IP54 Red/Yellow — YesCDH3S 1,3R,12 IP65 Black — YesCDH4S 1,3R,12 IP65 Red/Yellow — YesCDH5S 1,3R,12 IP65 Black Yes YesCDH6S 1,3R,12 IP65 Red/Yellow Yes Yes(3) Not suitable for use with CDNF30, 60, 100.
Mounting Depth(2) in inchesCDNF16 CDNF30CDNF25 CDNF45 CDNF60CDNF32 CDNF63 CDNF100CDH1S CDH3S CDH1S CDH3S CDH3S
Shaft CDH2S CDH4S CDH2S CDH4S CDH4SCatalog Length CDH15S CDH5S CDH15S CDH5S CDH5SNumbers in (mm) CDH16S CDH6S CDH16S CDH6S CDH6SCDS85S 3.3 (85) 4.2-5.0 3.6-4.3 4.9-5.6 4.4-5.0 3.9-4.9CDS105S 4.1 (105) 5.0-5.8 4.4-5.1 5.7-6.4 5.1-5.8 4.7-5.7CDS120S 4.7 (120) 5.6-6.4 5.0-5.8 6.3-7.0 5.7-6.4 5.3-6.3CDS130S 5.1 (130) 6.0-6.7 5.4-6.1 6.7-7.4 6.1-6.8 5.6-6.7CDS180S 7.1 (180) 7.1-8.7 7.4-8.1 8.6-9.4 8.1-8.7 7.6-8.6CDS250S 9.8 (250) 10.7-11.5 10.1-10.8 11.4-12.1 10.9-11.5 10.4-11.4CDS330S 13 (330) 13.8-14.6 13.3-14.0 14.6-15.3 14.0-14.7 13.5-14.5(2) Mounting depth is the distance from the outside of door to the disconnect switch mounting plate. Shaft can be cut to desired length.
Mounts directly to switch; no shaft necessaryCatalog Numbers NEMA Type Color For Use On: Length (inches) PadlockableOPMRH 1 Red CDNF16, 25, 32 1.0 —CDBY68306(3) 1 Red CDNF30, 45, 60, 63,100 1.4 —CDBY68419/1(3) 1 Red CDNF30, 45, 60, 63,100 1.6 Yes(5)CDMC1 Metal collar — CDNF16 – CDNF100 — —CDSWM5X8 Set screw — CDNF16, 25, 30, 32, 45, 60, 63, 100 — —(4) 0.1875" (3/16") diameter shackle required.(5) Set screw CDSWM5X8 needed with replacement knobs CDBY__.
16—100A/600V 3 Pole(1) Switches
Shafts — For use with CDH selector handles � 0.20 x 0.20" (� 5 x 5 mm)
Selector Handles — For use with shafts � 0.20 x 0.20" (� 5 x 5 mm)
Replacement Knob
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 321
Disconnects
Disconnects
Twisted Shafts — Rotates handle 45° � 0.20 x 0.20" (� 5 x 5 mm)Mounting Depth(1) in inches
Shaft CDNF16 CDNF30Catalog Length CDNF25 CDNF45 CDNF60Numbers in (mm) CDNF32 CDNF63 CDNF100CDS48T 5.9 (150) 6.2-6.7 6.9-7.4 6.4-7.4CDS67T 6.7 (170) 7.0-7.5 7.7-8.1 7.2-8.1CDS49T 10.4 (265) 10.7-11.3 11.4-11.9 10.9-11.9CDS50T 15.8 (400) 16.0-16.6 16.8-17.2 16.2-17.2(1) Mounting depth is the distance from the outside of door to the disconnect switch
mounting plate. Shaft can be cut to desired length.
Mounting Depth(1) in inchesShaft CDNF16 CDNF30
Catalog Length CDNF25 CDNF45 CDNF60Numbers in (mm) CDNF32 CDNF63 CDNF100CDS48P 5.9 (150) 6.2-6.7 6.9-7.4 6.4-7.4CDS67P 6.7 (170) 7.0-7.5 7.7-8.1 7.2-8.1CDS49P 10.4 (265) 10.7-11.3 11.4-11.9 10.9-11.9CDS50P 15.8 (400) 16.0-16.6 16.8-17.2 16.2-17.2CDS99P 19.7 (500) 20.0-20.5 20.7-21.1 20.1-21.1(1) Mounting depth is the distance from the outside of door to the disconnect switch
mounting plate. Shaft can be cut to desired length.
16-100A Base & DIN rail mount non-fusibledisconnect switches
Pistol Handle 16-100A 3-PoleFor a complete assembly, please select one of each:
• 1 switch• 1 shaft• 1 handle
CDNF60 + CDS85S + BDH104, 106
CDS_P
BDH107BDH104, 106
CDS_T
CDNF30CDNF60CDNF100
CDNF16CDNF25CDNF32
UL General Maximum Horsepower RatingCatalog Purpose IEC AC21 Single Phase Three Phase Terminal LugsNumbers Amp Rating Amp Rating 120V 240V 240V 480V 600V Wire Size/TypeCDNF16 16 16 1⁄2 1.5 5 10 10 #18-8/CUCDNF25 25 25 3⁄4 2 7.5 15 20 #18-8/CUCDNF32 40 40 1 3 10 20 25 #18-8/CUCDNF45 60 63 2 5 15 30 30 #14-4/CUCDNF63 80 80 2 5 20 40 40 #14-4/CUCDNF30 30 40 2 5 10 20 30 #14-4/CUCDNF60 60 63 3 7.5 20 40 40 #14-4/CUCDNF100 100 115 5 15 30 50 50 #8-1/0/CU(1) A snap-on fourth pole may be added.
Catalog LengthNumber NEMA Type IEC Type Color Marking in (mm) Defeatable PadlockableBDH104 1,3R,12 IP65 Black O/I & Off/On 1.8 (45) Yes YesBDH105 1,3R,12 IP65 Red/Yel O/I & Off/On 1.8 (45) Yes YesBDH106 1,3R,12 IP65 Black O/I & Off/On 2.6 (65) Yes YesBDH107 1,3R,12 IP65 Red/Yel O/I & Off/On 2.6 (65) Yes YesCDHXB65 1,3R,12,4,4X IP66 Black O/I & Off/On 2.6 (65) Yes YesCDHXY65 1,3R,12,4,4X IP66 Red/Yel O/I & Off/On 2.6 (65) Yes Yes
16—100A/600V 3-Pole(1) Switches
Shafts — For use with pistol handles � 0.20 x 0.20" (� 5 x 5 mm)
Pistol Handles — For use with shafts � 0.20 x 0.20" (� 5 x 5 mm)
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp322
Disconnects
16-100A door mounted non-fusible disconnect switches
Selector Handle 16-100A 3-PoleFor a complete assembly, please select one of each:
• 1 switch• 1 handle
Note: Door mounted switches do not provide door interlock.
CDH8SCDH12S
CDNF45D + CDH9S
CDNF16DCDNF25DCDNF32D
CDH9SCDH13S
CDH17SCDH19S
CDH10SCDH14S
UL General Maximum Horsepower RatingCatalog Purpose IEC AC21 Single Phase Three Phase Terminal LugsNumber Amp Rating Amp Rating 120V 240V 240V 480V 600V Wire Size/TypeCDNF16D 16 16 1⁄2 1.5 5 10 10 #18-8/CUCDNF25D 25 25 3⁄4 2 7.5 15 20 #18-8/CUCDNF32D 40 40 1 3 10 20 25 #18-8/CUCDNF45D 60(4) 63 2 5 15 30 30 #14-4/CUCDNF63D 80(4) 80 2 5 20 40 40 #14-4/CUCDNF30D 30(4) 40 2 5 10 20 30 #14-4/CUCDNF60D 60(4) 63 3 7.5 20 40 40 #14-4/CUCDNF100D 100(4) 115 5 15 30 50 50 #8-1/0/CU(1) A snap-on fourth pole may be added.(2) Door mounted switches do not require shafts.(3) CDNF16, 25, 32, 45 & 63 door mounted switches will not accept pistol handles.(4) CDNF45 & 63 door mounted switches can only use screw mounted handles.
Selector HandlesAll marked both O/I & Off/OnCatalog NEMANumbers Type IEC Type Color Defeatable Padlockable
Snap-on mounting — for use on CDNF16, 25, 32DCDH7S 1 IP54 Black — —CDH8S 1 IP54 Red/Yellow — —CDH19S 1 IP54 Black — YesCDH20S 1 IP54 Red/Yellow — YesCDH9S 1,3R,12 IP65 Black — YesCDH10S 1,3R,12 IP65 Red/Yellow — Yes
Screw mounting — for use on CDNF16, 32, 45 & 63DCDH11S 1 IP54 Black — —CDH12S 1 IP54 Red/Yellow — —CDH17S 1 IP54 Black — YesCDH18S 1 IP54 Red/Yellow — YesCDH13S 1,3R,12 IP65 Black — YesCDH14S 1,3R,12 IP65 Red/Yellow — Yes
Pistol Grip Handle AdapterCatalogNumber Description For Use On:CDHZX6 Adapter piece for pistol grip handle CDNF30, CDNF60, CDNF100
16—100A/600V 3 Pole(1)(2)(3) Switches
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 323
Disconnects
Disconnects
400-800A non-fusible disconnect switches
Twisted shafts — Rotates handle 45° � 0.47 x 0.47" (� 12 x 12 mm)Catalog Shaft Length Mounting Depth(1)Numbers in (mm) in InchesBDS28045 11.0 (280) 10.2-14.5BDS32545 12.8 (325) 12.0-16.3BDS46545 18.3 (465) 17.5-21.9(1) Mounting depth is the distance from the outside of the door to the disconnect switch mounting plate. Shaft can be cut to desired length.
Shafts — for use with pistol handles � 0.47 x 0.47" (� 12 x 12 mm)Catalog Shaft Length Mounting Depth(1)Numbers in (mm) in InchesBDS280 11.0 (280) 10.2-14.5BDS325 12.8 (325) 12.0-16.3BDS395 15.6 (395) 14.8-19.1BDS465 18.3 (465) 17.5-21.9BDS535 21.1 (535) 20.3-24.6(1) Mounting depth is the distance from the outside of the door to the disconnect switch mounting plate. Shaft can be cut to desired length.
Pistol Handle 400-800A 2-, 3- and 4-PoleFor a complete assembly, please select one of each:
• 1 switch• 1 handle• 1 shaft• 1 terminal lug kit
400-800A/600V SwitchesUL General
Catalog Purpose IEC AC21 Maximum Horsepower RatingNumber Poles Amp Rating Amp Rating 200V 208V 240V 480V 600VBDNF4002 2 400 630 — — — — —BDNF600A2 2 600 800 — — — — —BDNF800A2 2 800 1250 — — — — —BDNF400 3 400 630 100 100 125 250 350BDNF600A 3 600 800 150 150 200 400 500BDNF800A 3 800 1250 200 200 250 500 600BDNF4004 4 400 630 100 100 125 250 350BDNF600A4 4 600 800 150 150 200 400 500BDNF800A4 4 — 1250 200 200 250 500 600
Pistol Handles — for use with shafts � 0.47 x 0.47” (� 12 x 12 mm)Catalog LengthNumber NEMA type IEC type Color in (mm) Marking Defeatable PadlockableBDH112 1,3R,12 IP65 Blk 4.9 (125) O/I & Off/On Yes YesBDH113 1,3R,12 IP65 R/Y 4.9 (125) O/I & Off/On Yes YesBDH114 1,3R,12 IP65 Blk 5.7 (145) O/I & Off/On Yes YesBDH115 1,3R,12 IP65 R/Y 5.7 (145) O/I & Off/On Yes YesBDH116 1,3R,12 IP65 Blk 6.9 (175) O/I & Off/On Yes YesBDH117 1,3R,12 IP65 R/Y 6.9 (175) O/I & Off/On Yes YesCDHXB12 1,3R,4,4X,12 IP66 Blk 5.7 (145) O/I & Off/On Yes YesCDHXY12 1,3R,4,4X,12 IP66 R/Y 5.7 (145) O/I & Off/On Yes YesCDHXB22 1,3R,4,4X,12 IP66 Blk 6.9 (175) O/I & Off/On Yes YesBDH8 1,3R,4,4X,12 IP65 Metal 8.7 (220) Off/On — Yes
Terminal Lug KitsCatalog LugsNumbers For Use On: Wire Size/Type Per KitBDTL26 BDNF400 #2-600 kcmil/CU/AL 6BDTL262 BDNF400 (2) #2-500 kcmil/CU/AL 6BDTL27 BDNF600A (2) #2-600 kcmil/CU/AL 6BDTL30 BDNF800A (2) #2-600 kcmil/CU/AL 6BDTL32 BDNF800A1 (8) 2/0 + (2)#2 600 kcmil/CU/AL 3BDTL175/400 BDNF400-BDNF600A(1) (12) #14-6/CU/AL 3(1) A load side distribution lug eliminates the need to purchase, install and wire a separate distribution block.
BDS280
BDS_45
BDNF400 + BDS280 + BDH114 + BDTL26
BDNF600ABDNF800A
BDH112-117
BDTL26BDTL27
BDTL30
BDTL32 BDTL175/400
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp324
Disconnects
Accessories for 400-800A non-fusibledisconnect switches
Auxiliary Contacts (2)Catalog AC ThermalAC RatedNumbers Description For Use On: Amp Rating VoltageBDAUX1 1 NO + 1 NC BDNF400 – 10 600BDAUX2 2 NO + 2 NC BDNF800A 10 600BDAUX3 4 NO + 4 NC BDNF800A 10 600BDAUX4 2 NO BDNF800A 10 600BDAUX5 4 NO BDNF800A 10 600BDAUX6 8 NO BDNF800A 10 600(2) UL File E57057
Terminal PolesCatalog AC Thermal AC RatedNumber Description For Use On: Amp Rating VoltageBDZX85 Detachable neutral BDNF400 – 400 600
mounts on side of BDNF600A 400 600switch or DIN rail
Terminal ShroudsCatalogNumbers Description For Use On:BDTS4 Includes one BDNF400BDTS6A shroud for line or BDNF600ABDTS8A load side BDNF800A
Handle Support BracketCatalogNumbers Description For Use On:BDZX73 Allows handle to be directly BDNF400 –
mounted to switch BDNF600ABDZX71 behind the door BDNF800A
BDAUX1-6
BDZX85
BDZX85
BDZX71
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 325
Disconnects
Disconnects
16–80A, 600V 3-Pole enclosed non-fusible disconnectswitches
ENF321-3PBJ
Selector Handle NEMA 1, 3R, 4 & 4XCatalog Numbers
UL General Catalog NumbersPurpose NEMA Enclosure Type (1)Amp Rating 1 3R 4 4X Stainless16 ENF161-3PBJ ENF163-3PBJ ENF164-3PBJ ENF16X-3PBJ25 ENF251-3PBJ ENF253-3PBJ ENF254-3PBJ ENF25X-3PBJ40 ENF321-3PBJ ENF323-3PBJ ENF324-3PBJ ENF32X-3PBJ60 ENF451-3PBJ ENF453-3PBJ ENF454-3PBJ ENF45X-3PBJ80 ENF631-3PBJ ENF633-3PBJ ENF634-3PBJ ENF63X-3PBJ(1) Enclosures are rated as listed, selector handles are only NEMA rated 1, 3R, 12. The overall NEMA rating of
an enclosed switch with a selector handle is 1, 3R, 12.
Selector Handle NEMA 4X and 12, IEC IP65Catalog Numbers
UL General Catalog NumbersPurpose NEMA Enclosure Type IEC Enclosure TypeAmp Rating 4X Plastic(1) 12(1) IP65 Plastic16 ENF16P-3PBJ ENF162-3PBJ ENF16E-3PBJ25 ENF25P-3PBJ ENF252-3PBJ ENF25E-3PBJ40 ENF32P-3PBJ ENF322-3PBJ ENF32E-3PBJ60 ENF45P-3PBJ ENF452-3PBJ ENF45E-3PBJ80 ENF63P-3PBJ ENF632-3PBJ ENF63E-3PBJ(1) Enclosures are rated as listed, selector handles are only NEMA rated 1, 3R, 12. The overall
NEMA rating of an enclosed switch with a selector handle is 1, 3R, 12.ENF252-3PYJ
ENF16E-3PBJ ENF45E-3PBJ
Selector Handle Ratings, 600VAmp NEMA Cat. No. CatalogRating Rating Color Marking Detachable Padlockable Suffix Number16-100 1, 3R, 12 Black O/I & OFF/ON Yes Yes BJ CDH5S
1, 3R, 12 Red/Yel O/I & OFF/ON Yes Yes YJ CDH6S
NOTE: All enclosed switches come with a black handle. However, most handles can be substituted with a red/yellow handle.Please substitute the handle suffix code (1st and 2nd from last characters) with the red/yellow handle catalog number suffix listedin the table to the left. There is no additional cost for a red/yellow handle of equal rating and style.
EXAMPLE: A red/yellow selector handle for an ENF161-3PBJ can be substituted for the black selector handle by using the "YJ"suffix instead of the "BJ" suffix, new catalog #ENF161-3PYJ.
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp326
Disconnects
16A-3150A, 600V 3-Pole enclosed non-fusible disconnect switches
NOTE: All enclosed switchescome with a black handle.However, most handles canbe substituted with a red/yel-low handle. Please substi-tute the handle suffix code(1st and 2nd from last char-acters) with the red/yellowhandle catalog number suffixlisted in the table to the left.There is no additional costfor a red/yellow handle ofequal rating and style.
EXAMPLE: A red/yellow pis-tol handle for an ENF161-3PBJ can be substituted forthe black selector handle byusing the "YJ" suffix insteadof the "BJ" suffix, new cata-log #ENF161-3PYJ.
Pistol Handle NEMA 4X, 12 and 7 & 9, IEC IP65Catalog Numbers
UL General Catalog NumbersPurpose Agency NEMA Enclosure Type IEC Enclosure TypeAmp Rating Listing 4X Plastic 12 7 & 9 IP65 Plastic16 UL 508 ENF16P-3PB6 ENF162-3PB6 ENF167-3P ENF16E-3PB425 UL 508 ENF25P-3PB6 ENF252-3PB6 ENF257-3P ENF25E-3PB440 UL 508 ENF32P-3PB6 ENF322-3PB6 ENF327-3P ENF32E-3PB460 UL 508 ENF45P-3PB6 ENF452-3PB6 ENF457-3P ENF45E-3PB480 UL 508 ENF63P-3PB6 ENF632-3PB6 ENF637-3P ENF63E-3PB430 UL 98 ENF30P-3PB6 ENF302-3PB6 ENF307-3P ENF30E-3PB660 UL 98 ENF60P-3PB6 ENF602-3PB6 ENF607-3P ENF60E-3PB6100 UL 98 ENF100P-3PB6 ENF1002-3PB6 ENF1007-3P ENF100E-3PB6125 UL 98 ENF125P-3PB6 ENF1252-3PB6 ENF1257-3P ENF125E-3PB6200 UL 98 ENF200P-3PB8 ENF2002-3PB8 ENF2007-3P —400 UL 98 ENF400P-3PB4 ENF4002-3PB4 ENF4007-3P —600 UL 98 ENF600P-3PB4 ENF6002-3PB4 ENF6007-3P —800 UL 98 ENF800P-3PB4 ENF8002-3PB4 ENF8007-3P —1200 UL 98 ENF1200P-3PB4 ENF12002-3PB4 ENF12007-3P —1600 UL 98 ENF1600P-3P8 ENF16002-3P8 ENF16007-3P —2000 UL 98 ENF2000P-3P8 ENF20002-3P8 ENF20007-3 —3150(2) UL 98 ENF3150P-3P8 ENF31502-3P8 ENF31507-3P —(2) IEC rated only.
ENF25P-3PY6
ENF63X-3PB6
Pistol Handle NEMA 1, 3R, 4 & 4XCatalog Numbers
UL General Catalog NumbersPurpose Agency NEMA Enclosure TypeAmp Rating Listing 1 3R 4 4X Stainless16 UL 508 ENF161-3PB6 ENF163-3PB6 ENF164-3PB6 ENF16X-3PB625 UL 508 ENF251-3PB6 ENF253-3PB6 ENF254-3PB6 ENF25X-3PB640 UL 508 ENF321-3PB6 ENF323-3PB6 ENF324-3PB6 ENF32X-3PB660 UL 508 ENF451-3PB6 ENF453-3PB6 ENF454-3PB6 ENF45X-3PB680 UL 508 ENF631-3PB6 ENF633-3PB6 ENF634-3PB6 ENF63X-3PB630 UL98 ENF301-3PB6 ENF303-3PB6 ENF304-3PB6 ENF30X-3PB660 UL98 ENF601-3PB6 ENF603-3PB6 ENF604-3PB6 ENF60X-3PB6100 UL98 ENF1001-3PB6 ENF1003-3PB6 ENF1004-3PB6 ENF100X-3PB6125 UL98 ENF1251-3PB6 ENF1253-3PB6 ENF1254-3PB6 ENF125X-3PB6200 UL98 ENF2001-3PB8 ENF2003-3PB8 ENF2004-3PB8 ENF200X-3PB8400 UL98 ENF4001-3PB4 ENF4003-3PB4 ENF4004-3PB4 ENF400X-3PB4600 UL98 ENF6001-3PB4 ENF6003-3PB4 ENF6004-3PB4 ENF600X-3PB4800 UL98 ENF8001-3PB4 ENF8003-3PB4 ENF8004-3PB4 ENF800X-3PB41200 UL98 ENF12001-3PB4 ENF12003-3PB4 ENF12004-3PB4 ENF1200X-3PB41600 UL98 ENF16001-3P8 ENF16003-3P8 ENF16004-3P8 ENF1600X-3P82000 UL98 ENF20001-3P8 ENF20003-3P8 ENF20004-3P8 ENF2000X-3P83150(2) UL98 ENF31501-3P8 ENF31503-3P8 ENF31504-3P8 ENF3150X-3P8(2) IEC rated only.
Pistol Handle Ratings: 16-3150A, 600VAmp NEMA Cat. No. CatalogRating Rating Color Marking Detachable Padlockable Suffix Number16-100 1, 3R, 12 Black O/I & OFF/ON Yes Yes B6 BDH106
1, 3R, 12 Red/Yel O/I & OFF/ON Yes Yes Y6 BDH1071, 3R, 4, 4X, 12 Black O/I & OFF/ON Yes Yes B6 CDHXB651, 3R, 4, 4X, 12 Red/Yel O/I & OFF/ON Yes Yes Y6 CDHXY65
125 1, 3R, 12 Black O/I & OFF/ON Yes Yes B6 BDH1201, 3R, 12 Red/Yel O/I & OFF/ON Yes Yes Y6 BDH1211, 3R, 4, 4X, 12 Black O/I & OFF/ON Yes Yes B8 CDHXB861, 3R, 4, 4X, 12 Red/Yel O/I & OFF/ON Yes Yes Y8 CDHXY86
200 1, 3R, 12 Black O/I & OFF/ON Yes Yes B8 BDH1101, 3R, 12 Red/Yel O/I & OFF/ON Yes Yes Y8 BDH1111, 3R, 4, 4X, 12 Black O/I & OFF/ON Yes Yes B8 CDHXB881, 3R, 4, 4X, 12 Red/Yel O/I & OFF/ON Yes Yes Y8 CDHXY88
400-3150 1, 3R, 12 Black O/I & OFF/ON Yes Yes B4 BDH1141, 3R, 12 Red/Yel O/I & OFF/ON Yes Yes Y4 BDH1151, 3R, 12 Black O/I & OFF/ON Yes Yes B7 BDH1161, 3R, 12 Red/Yel O/I & OFF/ON Yes Yes Y7 BDH1171, 3R, 4, 4X, 12 Black O/I & OFF/ON Yes Yes B4 CDHXB121, 3R, 4, 4X, 12 Red/Yel O/I & OFF/ON Yes Yes Y4 CDHXY121, 3R, 4, 4X, 12 Black O/I & OFF/ON Yes Yes B7 CDHXB221, 3R, 4, 4X, 12 Red/Yel O/I & OFF/ON Yes Yes Y7 CDHXY221, 3R, 4, 4X, 12 Metal O/I & OFF/ON No Yes 8 BDH8
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 327
Disconnects
Disconnects
16-400A 2-, 4- and 6-Pole enclosed non-fusible disconnect switches
NEMA 4X, 12 and 7&9 for Transfer, Bypass and MechanicalInterlock ApplicationsCatalog Numbers
UL General Catalog NumbersPurpose Switch NEMA Enclosure TypeAmp Rating Type 1 3R 4 4X Stainless16 4-Pole ENF161-4PB6 ENF163-4PB6 ENF164-4PB6 ENF16X-4PB6
6-Pole ENF161-6PB6 ENF163-6PB6 ENF164-6PB6 ENF16X-6PB6Transfer ENF161-3TB8 ENF163-3TB8 ENF164-3TB8 ENF16X-3TB8Bypass ENF161-3BB8 ENF163-3BB8 ENF164-3BB8 ENF16X-3BB8Mech. interlock ENF161-3MB6 ENF163-3MB6 ENF164-3MB6 ENF16X-3MB6
25 4-Pole ENF251-4PB6 ENF253-4PB6 ENF254-4PB6 ENF25X-4PB66-Pole ENF251-6PB6 ENF253-6PB6 ENF254-6PB6 ENF25X-6PB6Transfer ENF251-3TB8 ENF253-3TB8 ENF254-3TB8 ENF25X-3TB8Bypass ENF251-3BB8 ENF253-3BB8 ENF254-3BB8 ENF25X-3BB8Mech. interlock ENF251-3MB6 ENF253-3MB6 ENF254-3MB6 ENF25X-3MB6
40 4-Pole ENF321-4PB6 ENF323-4PB6 ENF324-4PB6 ENF32X-4PB66-Pole ENF321-6PB6 ENF323-6PB6 ENF324-6PB6 ENF32X-6PB6Transfer ENF321-3TB8 ENF323-3TB8 ENF324-3TB8 ENF32X-3TB8Bypass ENF321-3BB8 ENF323-3BB8 ENF324-3BB8 ENF32X-3BB8Mech. interlock ENF321-3MB6 ENF323-3MB6 ENF324-3MB6 ENF32X-3MB6
60 4-Pole ENF451-4PB6 ENF453-4PB6 ENF454-4PB6 ENF45X-4PB66-Pole ENF451-6PB6 ENF453-6PB6 ENF454-6PB6 ENF45X-6PB6Transfer ENF451-3TB8 ENF453-3TB8 ENF454-3TB8 ENF45X-3TB8Bypass ENF451-3BB8 ENF453-3BB8 ENF454-3BB8 ENF45X-3BB8Mech. interlock ENF451-3MB6 ENF453-3MB6 ENF454-3MB6 ENF45X-3MB6
80 4-Pole ENF631-4PB6 ENF633-4PB6 ENF634-4PB6 ENF63X-4PB66-Pole ENF631-6PB6 ENF633-6PB6 ENF634-6PB6 ENF63X-6PB6Transfer ENF631-3TB8 ENF633-3TB8 ENF634-3TB8 ENF63X-3TB8Bypass ENF631-3BB8 ENF633-3BB8 ENF634-3BB8 ENF63X-3BB8Mech. interlock ENF631-3MB6 ENF633-3MB6 ENF634-3MB6 ENF63X-3MB6
30 4-Pole ENF301-4PB6 ENF303-4PB6 ENF304-4PB6 ENF30X-4PB66-Pole ENF301-6PB6 ENF303-6PB6 ENF304-6PB6 ENF30X-6PB6Transfer ENF301-3TB8 ENF303-3TB8 ENF304-3TB8 ENF30X-3TB8Bypass ENF301-3BB8 ENF303-3BB8 ENF304-3BB8 ENF30X-3BB8Mech. interlock ENF301-3MB6 ENF303-3MB6 ENF304-3MB6 ENF30X-3MB6
60 4-Pole ENF601-4PB6 ENF603-4PB6 ENF604-4PB6 ENF60X-4PB66-Pole ENF601-6PB6 ENF603-6PB6 ENF604-6PB6 ENF60X-6PB6Transfer ENF601-3TB8 ENF603-3TB8 ENF604-3TB8 ENF60X-3TB8Bypass ENF601-3BB8 ENF603-3BB8 ENF604-3BB8 ENF60X-3BB8Mech. interlock ENF601-3MB6 ENF603-3MB6 ENF604-3MB6 ENF60X-3MB6
100 4-Pole ENF1001-4PB6 ENF1003-4PB6 ENF1004-4PB6 ENF100X-4PB66-Pole ENF1001-6PB6 ENF1003-6PB6 ENF1004-6PB6 ENF100X-6PB6Transfer ENF1001-3TB8 ENF1003-3TB8 ENF1004-3TB8 ENF100X-3TB8Bypass ENF1001-3BB8 ENF1003-3BB8 ENF1004-3BB8 ENF100X-3BB8Mech. interlock ENF1001-3MB6 ENF1003-3MB6 ENF1004-3MB6 ENF100X-3MB6
125 2-Pole ENF1251-2PB6 ENF1253-2PB6 ENF1254-2PB6 ENF125X-2PB64-Pole ENF1251-4PB6 ENF1253-4PB6 ENF1254-4PB6 ENF125X-4PB66-Pole ENF1251-6PB2 ENF1253-6PB2 ENF1254-6PB4 ENF125X-6PB4Transfer ENF1251-3TB8 ENF1253-3TB8 ENF1254-3TB8 ENF125X-3TB8Bypass — — — —Mech. interlock ENF1251-3MB6 ENF1253-3MB6 ENF1254-3MB8 ENF125X-3MB8
200 2-Pole ENF2001-2PB8 ENF2003-2PB8 ENF2004-2PB8 ENF200X-2PB84-Pole ENF2001-4PB8 ENF2003-4PB8 ENF2004-4PB8 ENF200X-4PB86-Pole ENF2001-6PB4 ENF2003-6PB4 ENF2004-6PB4 ENF200X-6PB4Transfer ENF2001-3TB4 ENF2003-3TB4 ENF2004-3TB4 ENF200X-3TB4Bypass ENF2001-3BB4 ENF2003-3BB4 ENF2004-3BB4 ENF200X-3BB4Mech. interlock ENF2001-3MB8 ENF2003-3MB8 ENF2004-3MB8 ENF200X-3MB8
400 2-Pole ENF4001-2PB4 ENF4003-2PB4 ENF4004-2PB4 ENF400X-2PB44-Pole ENF4001-4PB4 ENF4003-4PB4 ENF4004-4PB4 ENF400X-4PB46-Pole ENF4001-6P8 ENF4003-6P8 ENF4004-6P8 ENF400X-6P8Transfer ENF4001-3TB4 ENF4003-3TB4 ENF4004-3TB4 ENF400X-3TB4Bypass ENF4001-3B6 ENF4003-3B6 ENF4004-3B6 ENF400X-3B6Mech. interlock ENF4001-3MB4 ENF4003-3MB4 ENF4004-3MB4 ENF400X-3MB4
(3) = Three-poles
Transfer(3)
Bypass
(3)
MechanicalInterlock
(3)
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp328
Disconnects
16-400A 2-, 4- and 6-Pole enclosed non-fusible disconnect switches
NEMA 4X, 12 and 7&9, and IEC IP65 for Transfer, Bypass andMechanical Interlock ApplicationsCatalog Numbers
UL General Catalog NumbersPurpose Switch NEMA Enclosure Type IEC Enclosure TypeAmp Rating Type 4X Plastic 12 7 & 9 IP6516 4-pole ENF16P-4PB6 ENF162-4PB6 ENF167-4P ENF16E-4PBJ
6-pole ENF16P-6PB6 ENF162-6PB6 ENF167-6P ENF16E-6PBJTransfer ENF16P-3TB8 ENF162-3TB8 ENF167-3T —Bypass ENF16P-3BB8 ENF162-3BB8 ENF167-3B —Mech. interlock ENF16P-3MB6 ENF162-3MB6 — —
25 4-pole ENF25P-4PB6 ENF252-4PB6 ENF257-4P ENF25E-4PBJ6-pole ENF25P-6PB6 ENF252-6PB6 ENF257-6P ENF25E-6PBJTransfer ENF25P-3TB8 ENF252-3TB8 ENF257-3T —Bypass ENF25P-3BB8 ENF252-3BB8 ENF257-3B —Mech. interlock ENF25P-3MB6 ENF252-3MB6 — —
40 4-Pole ENF32P-4PB6 ENF322-4PB6 ENF327-4P ENF32E-4PBJ6-Pole ENF32P-6PB6 ENF322-6PB6 ENF327-6P ENF32E-6PBJTransfer ENF32P-3TB8 ENF322-3TB8 ENF327-3T —Bypass ENF32P-3BB8 ENF323-3BB8 ENF327-3B —Mech. interlock ENF32P-3MB6 ENF322-3MB6 — —
60 4-Pole ENF45P-4PB6 ENF452-4PB6 ENF457-4P ENF45E-4PBJ6-Pole ENF45P-6PB6 ENF452-6PB6 ENF457-6P ENF45E-6PBJTransfer ENF45P-3TB8 ENF452-3TB8 ENF457-3T —Bypass ENF45P-3BB8 ENF452-3BB8 ENF457-3B —Mech. interlock ENF45P-3MB6 ENF452-3MB6 — —
80 4-Pole ENF63P-4PB6 ENF632-4PB6 ENF637-4P ENF63E-4PBJ6-Pole ENF63P-6PB6 ENF632-6PB6 ENF637-6P ENF637-6PBJTransfer ENF63P-3TB8 ENF632-3TB8 ENF637-3T —Bypass ENF63P-3BB8 ENF632-3BB8 ENF637-3B —Mech. interlock ENF63P-3MB6 ENF632-3MB6 — —
30 4-Pole ENF30P-4PB6 ENF302-4PB6 ENF307-4P ENF30E-4PB46-Pole ENF30P-6PB6 ENF302-6PB6 ENF307-6P ENF30E-6PB6Transfer ENF30P-3TB8 ENF302-3TB8 ENF307-3T —Bypass ENF30P-3BB8 ENF302-3BB8 ENF307-3B —Mech. interlock ENF30P-3MB6 ENF302-3MB6 — —
60 4-Pole ENF60P-4PB6 ENF602-4PB6 ENF607-4P ENF60E-4PB46-Pole ENF60P-6PB6 ENF602-6PB6 ENF607-6P ENF60E-6PB6Transfer ENF60P-3TB8 ENF602-3TB8 ENF607-3T —Bypass ENF60P-3BB8 ENF602-3BB8 ENF607-3B —Mech. interlock ENF60P-3MB6 ENF602-3MB6 — —
100 4-Pole ENF100P-4PB6 ENF1002-4PB6 ENF1007-4P ENF100E-4PB46-Pole ENF100P-6PB6 ENF1002-6PB6 ENF1007-6P ENF100E-6PB6Transfer ENF100P-3TB8 ENF1002-3TB8 ENF1007-3T —Bypass ENF100P-3BB8 ENF1002-3BB8 ENF1007-3B —Mech. interlock ENF100P-3MB6 ENF1002-3MB6 — —
125 2-Pole ENF125P-2PB6 ENF1252-2PB6 ENF1257-2P —4-Pole ENF125P-4PB6 ENF1252-4PB6 ENF1257-4P —6-Pole ENF125P-6PB2 ENF1252-6PB2 ENF1257-6P —Transfer ENF125P-3TB8 ENF1252-3TB8 ENF1257-3T —Bypass — — — —Mech. interlock ENF125P-3MB6 ENF1252-3MB6 — —
200 2-Pole ENF200P-2PB8 ENF2002-2PB8 ENF2007-2P —4-Pole ENF200P-4PB8 ENF2002-4PB8 ENF2007-4P —6-Pole ENF200P-6PB4 ENF2002-6PB4 ENF2007-6P —Transfer ENF200P-3TB4 ENF2002-3TB4 ENF2007-3T —Bypass ENF200P-3BB4 ENF2002-3BB4 ENF2007-3B —Mech. interlock ENF200P-3MB8 ENF2002-3MB8 — —
400 2-Pole ENF400P-2PB4 ENF4002-2PB4 ENF4007-2P —4-Pole ENF400P-4PB4 ENF4002-4PB4 ENF4007-4P —6-Pole ENF400P-6P8 ENF4002-6P8 ENF4007-6P —Transfer ENF400P-3TB4 ENF4002-3TB4 ENF4007-3T —Bypass ENF400P-3B6 ENF4002-3B6 ENF4007-3B —Mech. interlock ENF400P-3MB4 ENF4002-3MB4 — —
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 329
Disconnects
Disconnects
A/C Disconnects — fused and non-fused
Data Sheet: 1143
Series B22__
SpecificationsDescription: Fused and non-fused rainproof air conditionerpullout units.
Dimensions: See Catalog Numbers table.
Construction: NEMA 3R rainproof metal housing withweather resistant coating.
Wire Range: 14-3 AWG, AL/CU
Ratings:Phase: — Single, 2-wire
Volts: — 240Vac
Amps: — 30-60A
Agency Information: UL Listed to UL 1429, C-ULCertified, UL Guide WGEW
Features and Benefits• A/C disconnects meet NEC® Code Requirements under arti-
cles 440.14. GFCI units meet NEC® Code Requirementsunder articles 210.63, 210.8, and 406.8(B)(1).
• NEMA 3R rainproof enclosures withstand outdoor environ-ment.
• Padlockable with two-position pullout handle to lock safetyshield when in the ON position. (Not available on GF or NAunits.) For added safety, pullout handle can be stored in thecompartment in the off position.
• Easy installation: knockouts on back, bottom and both sides,Cable whip versions save labor.
Typical Applications• Residential, light industrial/commercial A/C and heat pump
service.• Spas/whirlpools, swimming pools, pump houses• Suitable for service entrance equipment applications with
field installable ground bar, kit number DPFG.
Metallic Fused DisconnectMetallic Non-Fused Disconnect
Catalog Numbers
FusedDisconnect Max Hp Rating Wire Range Enclosure Fuse Approx. Dimensions (in)
Catalog Numbers Description Rating 120V 240V 60 or 75°C CU/AL Type Class Height Width DepthB221-30F 30A, Pullout 30A 1.5 3 #14-3 NEMA 3R H or R 8 3⁄4 5 3⁄8 2 7⁄8B221-30FGF 30A, Pullout w/ GFCI 30A 1.5 3 #14-3 NEMA 3R H or R 13 7 1⁄2 4 3⁄4B222-60F 60A, Pullout 60A 3 10 #14-3 NEMA 3R H or R 8 3⁄4 5 3⁄8 2 7⁄8B222-60FGF 60A, Pullout w/ GFCI 60A 3 10 #14-3 NEMA 3R H or R 13 7 1⁄2 4 3⁄4
Non-FusedB222-60NF 60A, Pullout 60A 3 10 #14-3 NEMA 3R * 8 3⁄4 5 3⁄8 2 7⁄8B222-60NFGF 60A, Pullout w/ GFCI 60A 3 10 #14-3 NEMA 3R * 11 3⁄4 6 1⁄2 4 1⁄2B222-60NFNA 60A, Switch 60A * 10 #14-3 NEMA 3R * 8 3⁄4 5 3⁄8 3 5⁄8
Non-Fused Cable WhipB222-60NF12W 60A, Pullout w/ 1⁄2" Cable Whip 60A* 3 10 #14-3 NEMA 3R * 14 3⁄4 12 1⁄2 4B222-60NF34W 60A, Pullout w/ 3⁄4" Cable Whip 60A** 3 10 #14-3 NEMA 3R * 14 3⁄4 12 1⁄2 4
Cable Whip SpecificationsMax UpstreamWire
Pullout Overcurrent Harness Ground Hot Flexible ConduitCatalog Numbers Description Rating Protection Device Diameter Wire Size Wire Size Length (ft) Non-Metallic FittingsB222-60NF12W 60A, Pullout w/ 1⁄2" Cable Whip 60A 30A 1⁄2" #10 #10 6 1 - 90°, 1 - StraightB222-60NF34W 60A, Pullout w/ 3⁄4" Cable Whip 60A 50A 3⁄4" #8 #10 6 1 - 90°, 1 - Straight* Upstream overcurrent protection device (OCPD) not to exceed 30 Amps.**Upstream overcurrent protection device (OCPD) not to exceed 50 Amps.
B222-60NF34Wnon-fused with with cable whip
Metallic Non-FusedDisconnect with GFCIreceptacle.
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp330
Disconnects
Fused, dead front disconnect switches
15149 Series
SpecificationsDescription: Fused, dead front disconnect switches
Ratings:Volts: — 600Vac
Amps: — 0-30A
Withstand: — 200,000A RMS Sym.
Dielectric Withstand: 2200V
Motor Rating: 5hp
Poles: 2 to 3
Agency Information: UL Recognized, file E116716 forGeneral Industrial installations. Guide WFXV2. CSA certified,file LR37129-6. Examined under the new proposed standardUL 1429 which imparts a stricter set of test conditions thanthe former program that combined the applicable portions forUL 512 (Fuse Holders) and UL 98 (Enclosed Switches).
Features and Benefits• Fuse holders in the pull-out head eliminate possibility of
electric shock while changing fuse.• Accepts Class J fuses
Ordering InformationTo order, specify: 15149 + number of poles.Example: 15149-2 = 2-pole device.
Data Sheet: 1141
All-Inclusive Elevator DisconnectSimplifies Installation Plus aMultitude of Codes and Standards
When the WestinHotel chain reno-vated the historicCupples Station indowntown St.Louis, the hotel’sdesign-and-buildelectrical contrac-tor specified theCooper Bussmann
Power Module™ elevator shunt trip disconnect. Theprimary reason was the savings in man-hours witheverything in one box: the fire alarm, control wiringand power wiring; all the parts needed to interfacewith a fire alarm system in a UL 98 Listed assembly.In addition, all the codes and standards surroundingthe elevator disconnecting means – electrical, eleva-tor, fire alarm and the sprinkler system – are met,including ANSI/ASME A17.1, NFPA 72,NEC® 620.62.
The contractor faced a unique situation when theluxury hotel chain chose to revamp the old warehouse versus tearing the structure down andrebuilding. The hotel complex consists of four buildings interconnected with walkways. A total ofeight elevators were installed with eight PowerModule switches, two per building. Each 30 HP passenger elevator is fused with Cooper BussmannLow-Peak® Class J LPJ-70SP fuses while each40HP service elevator uses the Class J LPJ-90SP fuses.
Did You Know?
top related