Transcript
2 0 0 5 E D I T I O N
FLANGED PIPE & FITTINGSDUCTILE IRON
INDUSTRIAL APPLICATIONS, WATER & WASTEWATER
3"-64"
NSF®
Certified toANSI/NSF 61
REVISED 11.05
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 2866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013
Table of ContentsFlanged Pipe and Fittings 3
Loose Flanges, FLANGE-TYTE® Gaskets and Flanged Fittings for Water or Other Liquids 7
Flanged Fittings Ductile iron 8Water 90º and 45º Bend 8Water 22-1/2º and 11-1/4º Bends 9Water Tees and Crosses 10Water Base Bends 14
Base Drilling Details 15
Flanged Fittings 16Water Base Tees 16Water Reducers 17
Manufacturer’s Standard Flanged Fittings 2090º Long Radius Bends 20Blind Flanges 21Wye Branches 22True Wyes 25Side Outlet 90º Elbows and Side Outlet Tees 26
Miscellaneous Flanged Fittings 27Flange and Flare 27Flange and Flare 90º Bends Standard and Long Radius 28Standard Sludge Shoes with Flange or Bell Ends 29
FLANGE-TYTE® Gasket For 4" through 64" Flanged Pipe and Fittings 30
Assembling Flanged Pipe and Fittings with FLANGE-TYTE® Gaskets 31
Method of Designating Outlets of Reducing Fittings in Specifications 32
Method of Designating Location of Tapped Holes for Drains When Specified 33
Combination of Standard Fittings That May be Used in Place of Special Fittings 34
Method of Reading Size of All Types of Standard and Special Fittings 35
Products for Water, Waste Waterand Fire Protection 36
NOTE: If specifiers and users believe that corrosivesoils will be encountered where our products are tobe installed, please refer to ANSI/AWWA C105/A21.5Polyethylene Encasement for Ductile Iron PipeSystems, for proper external protection procedures.
Flanged Pipe and Fittings forWater and Other Liquids
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 3866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
ANSI/AWWA C115/A21.15 Flanged Ductile-Iron Pipe with Ductile-Iron or Gray-IronThreaded Flanges.
Threaded flanged pipe conform to therequirements of ANSI/AWWA C115/A21.15.
ANSI/AWWA C151/A21.51 Ductile Iron Pipe,Centrifugally Cast, for Water.
Ductile Iron pipe used for flanging are centrifu-gally cast in accordance with the requirementsof ANSI/AWWA C151/A21.51.
ANSI/AWWA C110/A21.10 Ductile-Iron andGray-Iron Fittings, 3" through 48" (76 mmthrough 1,219 mm), For Water (3-through48" sizes) and ANSI/AWWA C153/A21.53Ductile-Iron Compact Fittings, For WaterService (54" through 64" sizes).
U.S. Pipe’s Flanged Fittings are produced ofDuctile Iron and conform to the applicablerequirements for Ductile Iron fittings specifiedin ANSI/AWWA C110/A21.10
ANSI/AWWA C116/A21.16 Protective Fusion-Bonded Epoxy Coatings for the Interior andExterior Surfaces of Ductile-Iron and Gray-Iron Fittings for Water Supply Service.
ANSI/AWWA C104/A21.4 Cement-MortarLining for Ductile-Iron and Gray-IronFittings for Water.
Coating system options include primer basecoat, fusion bonded epoxy coating inside andoutside in accordance with ANSI/AWWAC116/A21.16. Cement-mortar lining withasphaltic coating inside and outside in accordance with ANSI/AWWA C104/A21.4.
ANSI /AWWA StandardsFlanged pipe and fittings are typical components in rigid piping systems. Such systems are particularly suited for above ground installation in the following: water filtration plants, sewagedisposal plants, wastewater treatment plants, pumping stations and industrial plants. U.S. Pipegives special attention to such installations through its Customer Service Department. Theunderground use of the flanged joint is generally not recommended due to the rigidity of thejoint. Unequal settlement or other stressing of such piping may result in excessive strain on theflanges or the pipe.
Flanged Pipe with Threaded FlangesFlanged pipe are fabricated by threading plain end pipe, screwing threaded flange(s) on andmachine-tightening them. The bolt holes are aligned per ANSI/AWWA C115/A21.15. The plainend and the flange are then faced to provide a smooth surface across the end of the pipeand the face of the flange. Pipe barrels and flanges have a taper pipe thread (NPT) inaccordance with ANSI B1.20.1, with thread diameters adapted to Ductile Iron pipe standardoutside diameters. Threaded pipe and threaded flanges are individually fitted and theflanges are not interchangeable.
Flanged pipe are furnished in the following maximum lengths:
Sizes 4"-42" – 17'6"Sizes 3", 48"-64" – 19'6"
Pipe for wastewater service may be furnished in accordance with ASTM 746 StandardSpecification for Ductile Iron Gravity Sewer Pipe. The minimum class thickness for Ductile Ironflanged pipe to be threaded is class 53 for sizes up through 54" and pressure class 350 for 60"and 64" sizes. Greater pipe wall thicknesses can be furnished if so ordered.
Flanges are the solid design and are Ductile Iron in conformance with the requirements ofANSI/AWWA C110/A21.10.
Weights of flanged pipe shown are subject to a minus tolerance of not more than 10% for indi-vidual pieces. To obtain the weight of a short flanged pipe, calculate the pipe weight for thelength from face to face of the flanges and add the weight of two flanges.
The Foreword of ANSI/AWWA C115/A21.15 lists the required information and the options which ifdesired must be specified on the purchase order for flanged pipe, such as size and finished length.See the standard for more details.
Coating SystemsUnless otherwise specified, flanged pipe will be furnished with a standard thickness cement-mortar lining with asphaltic coating inside and outside. Fittings are furnished coated or uncoatedin accordance with the purchasers’ requirements.
NOTE: If a field-applied coating is required forappearance or color coding over FBE coatings, thesmooth finish must be roughened to provide ananchor pattern — a light brush blast or rougheningby coarse sandpaper is recommended.
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 4866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
AccessoriesThe gaskets and bolts to be used with flanged pipe and fittings should be selected by the pur-chaser with due consideration for the particular service and installation requirements. Flangedjoint accessories (bolts, nuts and gaskets) can be furnished by U.S. Pipe if so specified. Rubbergaskets, 1/8" thick, or U.S. Pipe FLANGE-TYTE® Gaskets (4" through 64"size) are recommendedfor normal water or sewage service.
Flange Compatibility and Pressure RatingsThe flanges of C110/A21.10, C115/A21.15 and C153/A21.53 standards conform to the drillingand facing of ANSI B16.1 Class 125 flanges. This B16.1 Class 125 designation leads some toconclude that these AWWA flanges are only rated at 125 psi service which is not correct.C110/A21.10 flanged fittings are rated for 350 psi operating pressure for 3" through 12" sizes,250 psi operating pressure for 14" through 48" sizes and C153/A21.53 fittings are rated for 150psi operating pressure for 54" through 64" sizes. These ratings are at ambient temperatures withat least a 2:1 factor of safety. Special gaskets such as U.S. Pipe’s FLANGE-TYTE® Gaskets arerequired for operating pressures greater than 250 psi.
(Flanges of Ductile Iron pipe and fittings meeting the requirements of ANSI/AWWA C115/A21.15or ANSI/AWWA C110/A21.10 cannot be joined with Class 250 ANSI B16.1 flanges.)
Special Service RequirementsWhen requesting prices for flanged piping for carrying chemical solutions, please furnishcomplete information regarding the type of material to be conveyed, composition, concentration,pH, pressure and temperature.
Flanged Pipe and Fittings forWater and Other Liquids (cont.)
Ductile Iron Flanged Pipe With Threaded Flanges
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 5866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
NOTE: Actual weights of fittings, sizes 54"-64", may exceed those shown.
Special gaskets such as U.S. Pipe FLANGE-TYTE® Gaskets are required for operating pressures greater than 250 psi.* U.S. Pipe rates its 4"-24" pipe for 350 psi service with use of the FLANGE-TYTE® Gasket.** Sizes 4"-42" — weights shown for nominal 17'6" lengths 3", 48"-64" — weights shown for nominal 19'6" lengths For bolt hole details see page 6.
MAXIMUM LENGTH WEIGHT PoundsSIZE PRESSURE OUTSIDE MIN. WALL
Inches RATING DIAMETER THICKNESS Feet Inches FLANGE PIPE W/O FLANGES PIPE W/ FLANGES**psi Inches Inches Per Foot Per Length
3 250 3.96 0.31 19' 6" 7 10.9 225
4 350 * 4.80 0.32 17' 6" 13 13.8 270
6 350 * 6.90 0.34 17' 6" 17 21.4 410
8 350 * 9.05 0.36 17' 6" 28 30.1 580
10 350 * 11.10 0.38 17' 6" 38 39.2 760
12 350 * 13.20 0.40 17' 6" 58 49.2 975
14 250 15.30 0.42 17' 6" 72 60.1 1195
16 250 17.40 0.43 17' 6" 90 70.1 1405
18 250 19.50 0.44 17' 6" 90 80.6 1590
20 250 21.60 0.45 17' 6" 115 91.5 1830
24 250 25.80 0.47 17' 6" 160 114.4 2325
30 250 32.00 0.51 17' 6" 240 154.4 3185
36 250 38.30 0.58 17' 6" 350 210.3 4380
42 250 44.50 0.65 17' 6" 500 274.0 5795
48 250 50.80 0.72 19' 6" 625 346.6 8010
54 150 57.56 0.81 19' 6" 670 441.9 9955
60 150 61.61 0.83 19' 6" 1035 485.0 11525
64 150 65.67 0.87 19' 6" 1510 542.0 13590
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 6866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
DIMENSIONS Inches
SIZE BOLT HOLE BOLT QTY. OFInches OD BC T Diameter Diameter & Length BOLTS
3 7.50 6.00 .75 ± .12 3/4 5/8 x 2-1/2 4
4 9.00 7.50 .94 ± .12 3/4 5/8 x 3 8
6 11.00 9.50 1.00 ± .12 7/8 3/4 x 3-1/2 8
8 13.50 11.75 1.12 ± .12 7/8 3/4 x 3-1/2 8
10 16.00 14.25 1.19 ± .12 1 7/8 x 4 12
12 19.00 17.00 1.25 ± .12 1 7/8 x 4 12
14 21.00 18.75 1.38 ± .19 1-1/8 1 x 4-1/2 12
16 23.50 21.25 1.44 ± .19 1-1/8 1 x 4-1/2 16
18 25.00 22.75 1.56 ± .19 1-1/4 1-1/8 x 5 16
20 27.50 25.00 1.69 ± .19 1-1/4 1-1/8 x 5 20
24 32.00 29.50 1.88 ± .19 1-3/8 1-1/4 x 5-1/2 20
30 38.75 36.00 2.12 ± .25 1-3/8 1-1/4 x 6-1/2 28
36 46.00 42.75 2.38 ±.25 1-5/8 1-1/2 x 7 32
42 53.00 49.50 2.62 ± .25 1-5/8 1-1/2 x 7-1/2 36
48 59.50 56.00 2.75 ± .25 1-5/8 1-1/2 x 8 44
54 66.25 62.75 3.00 ± .25 2 1-3/4 x 8-1/2 44
60 73.00 69.25 3.12 ± .25 2 1-3/4 x 9 52
64 80.00 76.00 3.38 ± .25 2 1-3/4 x 9 52
FACING: Flanges are plain faced without projection or raised face and are furnished smooth or with shallow serrations.
BACK FACING: Flanges may be back or spot faced for compliance with flange thickness tolerances.
LAYING LENGTH DIMENSIONS: Pipe face-to-face dimensions conform to a tolerance of ±.12" for sizes 3"-64"Fittings face-to-face dimensions conform to a tolerance of ±.06" for sizes 3"-10" and ±.12" for sizes 12"-64". The largestopening governs the tolerance for all openings. Center-to-face tolerances are one half the face-to-face tolerances.
FLANGES: The bolt circle and bolt holes of these flanges match those of ANSI/AWWA C115/A21.15 and Class 125 flanges shownin ANSI B16.1 and can be joined with A21.15 and Class 125 B16.1 flanges. The flanges do not match the Class 250 flangesshown in ANSI B16.1 and cannot be joined with Class 250 B16.1 flanged fittings and valves.
Ductile Iron Flanged Pipe With Threaded Flanges Flange Details
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 7866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
CAUTION: U.S. Pipe does not recommend the practice of assembling threaded flanges onpipe in the field. As an accommodation to our customers, U.S. Pipe does provide flangedpipe with unattached threaded flanges when specified. Certain precautions must be takenwhen loose flanges are assembled to the pipe.
1. The threaded portion of the flange and the pipe are custom machined to accommodate theexact diameter of the pipe. In addition, the pipe and flange have been faced in the shopafter proper tightening of the flange on the pipe. The unscrewed loose flange must bemated only with the threaded pipe end on which it had been attached.
2. Extremely high torques are required to properly tighten screw flanges. If there is a ques-tion regarding the adequacy of the field tightening means,a trial assembly using greaseon the threads, should be made prior to making the final assembly. Because of the diffi-culty in tightening large flanges at the job sites, sizes larger than 16" should not beattempted in the field.
3. The flange should never be final assembled on the pipe without the use of a lubricant orsealant on the threads.
4. Prior to making the final assembly of the flange on the pipe, the threaded portion of theflange and the pipe must be cleaned of all foreign material such as dirt, sand or grit. A suitable solvent should be used to remove any grease or oil remaining on the threads.
5. A two part 100% solids epoxy thread sealant should be applied to the threaded portion ofthe pipe and flange using the sealant manufacturer's recommended procedure. If flangedpipe will be in seawater, it is recommended that the exposed threads be coated with Induron PE-54 epoxy or wrapped with Denso tape which is available from:
Denso North America, Inc.Houston, Texas281-821-3355
6. The flange should be tightened until the face of the flange is at least flush with the facedend of the pipe. Normally the flange can be screwed on the pipe by hand up to approxi-mately the last three threads. Tightening the remaining threads creates the seal betweenthe pipe and the flange threads. If the face of the flange is not at least flush with the endof the pipe, a proper seal between the threads will not be made. If the pipe protrudesbeyond the face, it must be faced off smooth in a machine tool.
Loose Flanges
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 8866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
FLANGE-TYTE® Gaskets and Flanged Fittings for Water or Other Liquids
U.S. Pipe FLANGE-TYTE GasketsU.S. Pipe FLANGE-TYTE Gaskets are available for 4" through 64" flanged pipe and flanged fit-tings having ANSI A21.15, ANSI/AWWA C110/A21.10or Class 125 ANSI B16.1 flanges. TheFLANGE-TYTE® Gasket is a superior gasket suitable for use in a flanged joint for water workingpressures ofup to 350 psi*. The gaskets are 1/8" thick.
See FLANGE-TYTE® Gasket details on pages 25 and 26.
Flanged Fittings for Water or Other LiquidsFlanged fittings shown on pages 8 to 25 meet all requirements of ANSI/AWWA C110/A21.10.Flanges are plain faced without projection and furnished smooth or with shallow serrations.Flanges may be back faced or spot faced for compliance with flange thickness tolerance. Theflange details are shown on page 6. The flanges are adequate for water service of 350 psi*working pressure for 24" and smaller sizes and 250 psi for sizes through 48” and 150 psi forthe larger sizes. The bolt circle and bolt holes of these flanges match those of ANSI/AWWAC115/A21.15 and Class 125 B16.1 flanges. The flanges do not match the Class 250 flangesshown in ANSI B16.1 and cannot be joined with Class 250 B16.1 flanged fittings and valves.
When ordering flanged fittings equipped with bosses and/or tappedholes, refer to and specifythe letter key on page 29, which designates location by letter.
Special flanged fittings other than those shown on pages 8 through 29 may be available onspecial order. Consult your nearest U.S. Pipe Sales Representative.
*U.S. Pipe rates its 4"-24" size flanged product at 350 psi with use of the FLANGE-TYTE®
Gasket.
U.S. PIPE ASSUMES NO RESPONSIBILITY FOR FIELD ASSEMBLY PRACTICES AND DISCLAIMS ALLLIABILITY ARISING THEREFROM.
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 9866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
NOTE: Actual weights of fittings, sizes 54"-64", may exceed those shown.
For flange details see page 6.
Sizes 3"-48" conform to ANSI/AWWA C110/A2l.10. Sizes 54"-64" conform to ANSI/AWWA C153/A21.53.
*U.S. Pipe rates its 4"-24" pipe and fittings for 350 psi service with use of the FLANGE-TYTE® Gasket.
DIMENSIONS WEIGHTPRESSURE Inches Pounds
SIZE RATING 90º 45º 90º 45ºInches psi
T A R A R
3 250 .48 5.5 4.0 3.0 3.62 25 20
4 350* .52 6.5 4.5 4.0 4.81 45 40
6 350* .55 8.0 6.0 5.0 7.25 65 55
8 350* .60 9.0 7.0 5.5 8.44 105 90
10 350* .68 11.0 9.0 6.5 10.88 165 130
12 350* .75 12.0 10.0 7.5 13.25 235 195
14 350* .66 14.0 11.5 7.5 12.06 290 220
16 350* .70 15.0 12.5 8.0 13.25 370 280
18 350* .75 16.5 14.0 8.5 14.50 450 32
20 350* .80 18.0 15.5 9.5 16.88 580 430
24 350* .89 22.0 18.5 11.0 18.12 900 630
30 250 1.03 25.0 21.5 15.0 27.75 1430 1120
36 250 1.15 28.0 24.5 18.0 35.00 2135 1755
42 250 1.28 31.0 27.5 21.0 42.45 3055 2600
48 250 1.42 34.0 30.5 24.0 49.50 4095 3580
54 150 .90 39.0 35.42 20.5 41.05 3740 2735
60 150 .94 43.0 33.34 23.5 45.48 4965 3790
64 150 .99 48.0 35.29 25.0 47.78 6745 5105
Flanged Fittings for Water 90º and 45º Bend Ductile IronThicknesses, Dimensions and Weights
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 10866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
NOTE: Actual weights of fittings, sizes 54"-64", may exceed those shown.
For flange details see page 6.
Sizes 3"-48" conform to ANSI/AWWA C110/A2l.10. Sizes 54"-64" conform to ANSI/AWWA C153/A21.53.
*U.S. Pipe rates its 4"-24" pipe and fittings for 350 psi service with use of the FLANGE-TYTE® Gasket.
DIMENSIONS WEIGHTPRESSURE Inches Pounds
SIZE RATING 22-1/2º 11-1/4º 22-1/2º 11-1/4ºInches psi
T A R A R
3 250 .48 3.0 7.56 3.0 15.25 20 20
4 350* .52 4.0 10.06 4.0 20.31 40 40
6 350* .55 5.0 15.06 5.0 30.50 55 55
8 350* .60 5.5 17.62 5.5 35.50 90 90
10 350* .68 6.5 22.62 6.5 45.69 135 135
12 350* .75 7.5 27.62 7.5 55.81 205 205
14 350* .66 7.5 25.12 7.5 50.75 225 225
16 350* .70 8.0 27.62 8.0 55.81 285 285
18 350* .75 8.5 30.19 8.5 60.94 335 335
20 350* .80 9.5 35.19 9.5 71.06 435 435
24 350* .89 11.0 37.69 11.0 76.12 640 645
30 250 1.03 15.0 57.81 15.0 116.75 1135 1150
36 250 1.15 18.0 72.88 18.0 147.25 1790 1805
42 250 1.28 21.0 88.00 21.0 177.69 2665 2680
48 250 1.42 24.0 103.06 24.0 208.12 3665 3695
54 150 .90 14.0 32.42 12.0 30.81 2260 2100
60 150 .94 14.0 39.41 10.5 44.07 2985 2665
64 150 .99 13.5 41.68 9.5 43.56 3995 3585
Flanged Fittings for Water 22-1/2º and 11-1/4º BendsDuctile Iron Thicknesses, Dimensions and Weights
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 11866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
SIZE PRESS RATING DIMENSIONS WEIGHTInches psi Inches Pounds
RUN BRANCH T T1 H J TEE CROSS
3 3 250 .48 .48 5.5 5.5 40 50
4 3 250 .52 .48 6.5 6.5 60 70
4 4 350* .52 .52 6.5 6.5 65 80
6 3 350* .55 .48 8.0 8.0 85 95
6 4 350* .55 .52 8.0 8.0 90 110
6 6 350* .55 .55 8.0 8.0 95 120
8 4 350* .60 .52 9.0 9.0 140 155
8 6 350* .60 .55 9.0 9.0 145 165
8 8 350* .60 .60 9.0 9.0 155 195
10 4 350* .68 .52 11.0 11.0 205 220
10 6 350* .68 .55 11.0 11.0 215 240
10 8 350* .68 .60 11.0 11.0 225 265
10 10 350* .80 .80 11.0 11.0 270 330
12 4 350* .75 .52 12.0 12.0 290 310
12 6 350* .75 .55 12.0 12.0 295 320
12 8 350* .75 .60 12.0 12.0 310 345
12 10 350* .87 .80 12.0 12.0 360 415
12 12 350* .87 .87 12.0 12.0 385 460
14 6 350* .66 .55 14.0 14.0 375 400
14 8 350* .66 .60 14.0 14.0 390 425
14 10 350* .66 .68 14.0 14.0 400 460
14 12 350* .66 .75 14.0 14.0 425 505
14 14 350* .66 .66 14.0 14.0 435 530
NOTE: Actual weights of fittings, sizes 54"-64", may exceed those shown.
*U.S. Pipe rates its 4"-24" pipe and fittings for 350 psi service with use of the FLANGE-TYTE® Gasket.
Flanged Fittings for Water Tees and Crosses Ductile Iron Thicknesses, Dimensions and Weights
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 12866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
Flanged Fittings for Water Tees and Crosses Ductile Iron Thicknesses, Dimensions and Weights (cont.)
NOTE: Actual weights of fittings, sizes 54"-64", may exceed those shown.
*U.S. Pipe rates its 4"-24" pipe and fittings for 350 psi service with use of the FLANGE-TYTE® Gasket.
SIZE PRESS RATING DIMENSIONS WEIGHTInches psi Inches Pounds
RUN BRANCH T T1 H J TEE CROSS
16 6 350* .70 .55 15.0 15.0 465 490
16 8 350* .70 .60 15.0 15.0 475 520
16 10 350* .70 .68 15.0 15.0 495 555
16 12 350* .70 .75 15.0 15.0 520 605
16 14 350* .70 .66 15.0 15.0 530 620
16 16 350* .70 .70 15.0 15.0 550 665
18 6 350* .75 .55 13.0 15.5 480 505
18 8 350* .75 .60 13.0 15.5 495 535
18 10 350* .75 .68 13.0 15.5 510 560
18 12 350* .75 .75 13.0 15.5 535 610
18 14 350* .75 .66 16.5 16.5 630 720
18 16 350* .75 .70 16.5 16.5 650 765
18 18 350* .75 .75 16.5 16.5 665 795
20 6 350* .80 .55 14.0 17.0 610 635
20 8 350* .80 .60 14.0 17.0 620 665
20 10 350* .80 .68 14.0 17.0 635 685
20 12 350* .80 .75 14.0 17.0 660 735
20 14 350* .80 .66 14.0 17.0 665 745
20 16 350* .80 .70 18.0 18.0 810 915
20 18 350* .80 .75 18.0 18.0 820 945
20 20 350* .80 .80 18.0 18.0 855 1015
24 6 350* .89 .55 15.0 19.0 845 875
24 8 350* .89 .60 15.0 19.0 860 895
24 10 350* .89 .68 15.0 19.0 880 930
24 12 350* .89 .75 15.0 19.0 890 960
24 14 350* .89 .66 15.0 19.0 900 975
24 16 350* .89 .70 15.0 19.0 915 1010
24 18 350* .89 .75 22.0 22.0 1220 1365
24 20 350* .89 .80 22.0 22.0 1255 1430
24 24 350* .89 .89 22.0 22.0 1330 1570
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 13866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
Flanged Fittings for Water Tees and Crosses Ductile Iron Thicknesses, Dimensions and Weights (cont.)
NOTE: Actual weights of fittings, sizes 54"-64", may exceed those shown.
*U.S. Pipe rates its 4"-24" pipe and fittings for 350 psi service with use of the FLANGE-TYTE® Gasket.
SIZE PRESS RATING DIMENSIONS WEIGHTInches psi Inches Pounds
RUN BRANCH T T1 H J TEE CROSS
30 12 250 1.03 .75 18.0 23.0 1490 1565
30 14 250 1.03 .66 18.0 23.0 1490 1570
30 16 250 1.03 .70 18.0 23.0 1505 1605
30 18 250 1.03 .75 18.0 23.0 1515 1615
30 20 250 1.03 .80 18.0 23.0 1540 1670
30 24 250 1.03 .89 25.0 25.0 2025 2245
30 30 250 1.03 1.03 25.0 25.0 2150 2500
36 12 250 1.15 .75 20.0 26.0 2170 2240
36 14 250 1.15 .66 20.0 26.0 2175 2240
36 16 250 1.15 .70 20.0 26.0 2185 2270
36 18 250 1.15 .75 20.0 26.0 2190 2280
36 20 250 1.15 .80 20.0 26.0 2210 2325
36 24 250 1.15 .89 20.0 26.0 2255 2405
36 30 250 1.15 1.03 28.0 28.0 3000 3300
36 36 250 1.15 1.15 28.0 28.0 3160 3620
42 12 250 1.28 .75 23.0 30.0 3165 3240
42 14 250 1.28 .66 23.0 30.0 3170 3240
42 16 250 1.28 .70 23.0 30.0 3180 3270
42 18 250 1.28 .75 23.0 30.0 3185 3275
42 20 250 1.28 .80 23.0 30.0 3205 3320
42 24 250 1.28 .89 23.0 30.0 3245 3395
42 30 250 1.28 1.03 31.0 31.0 4125 4375
42 36 250 1.78 1.58 31.0 31.0 5360 5720
42 42 250 1.78 1.78 31.0 31.0 5580 6155
Flanged Fittings for Water Tees and Crosses Ductile Iron Thicknesses, Dimensions and Weights (cont.)
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 14866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
NOTE: Actual weights of fittings, sizes 54"-64", may exceed those shown.
U.S. Pipe rates its 4"-24" pipe and fittings for 350 psi service with use of the FLANGE-TYTE® Gasket.
SIZE PRESS RATING DIMENSIONS WEIGHTInches psi Inches Pounds
RUN BRANCH T T1 H J TEE CROSS
48 12 250 1.42 .75 26.0 34.0 4315 4390
48 14 250 1.42 .66 26.0 34.0 4315 4385
48 16 250 1.42 .70 26.0 34.0 4330 4415
48 18 250 1.42 .75 26.0 34.0 4330 4420
48 20 250 1.42 .80 26.0 34.0 4350 4460
48 24 250 1.42 .89 26.0 34.0 4385 4535
48 30 250 1.42 1.03 26.0 34.0 4455 4670
48 36 250 1.42 1.15 34.0 34.0 5555 5880
48 42 250 1.96 1.78 34.0 34.0 7195 7630
48 48 250 1.96 1.96 34.0 34.0 7385 8005
54 30 250 1.05 .72 31.0 37.0 4615 4800
54 36 250 1.05 .77 31.0 37.0 4695 4950
54 42 250 1.05 .88 39.0 39.0 5740 6210
54 48 250 1.05 .94 39.0 39.0 5850 6425
54 54 250 1.05 1.05 39.0 39.0 6025 6780
60 36 250 1.10 .77 33.0 42.0 6015 6330
60 42 250 1.10 .88 43.0 43.0 7380 7885
60 48 250 1.10 .94 43.0 43.0 7490 8105
60 54 250 1.10 1.05 43.0 43.0 7665 8450
60 60 250 1.10 1.10 43.0 43.0 8045 9220
64 36 250 1.16 .77 32.0 44.0 7320 7610
64 42 250 1.16 .88 48.0 45.0 9610 10085
64 48 250 1.16 .94 48.0 45.0 9710 10275
64 54 250 1.16 1.05 48.0 46.0 9915 10690
64 60 250 1.16 1.10 48.0 46.0 10285 11430
64 64 250 1.16 1.16 48.0 48.0 10995 12855
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 15866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
NOTE: Actual weights of fittings, sizes 54"-64", may exceed those shown.
For flange detail see page 6.
Dimension “R” is a finished dimension; unfinished bases will be 1/8" longer. For base drilling details see page 15. For other dimensions see page 7.
* U.S. Pipe rates its 4"-24" pipe and fittings for 350 psi service with use of the FLANGE-TYTE® Gasket.
SIZE PRESSURE DIMENSIONS WEIGHTInches RATING Inches Pounds
psi R S DIAMETER T U BASE BEND BASE ONLY
3 250 4.88 5.00 .56 .50 35 10
4 350* 5.50 6.00 .62 .50 55 10
6 350* 7.00 7.00 .69 .62 85 20
8 350* 8.38 9.00 .94 .88 145 40
10 350* 9.75 9.00 .94 .88 210 45
12 350* 11.25 11.00 1.00 1.00 300 65
14 350* 12.50 11.00 1.00 1.00 360 70
16 350* 13.75 11.00 1.00 1.00 445 75
18 350* 15.00 13.50 1.12 1.12 565 115
20 350* 16.00 13.50 1.12 1.12 700 120
24 350* 18.50 13.50 1.12 1.12 1030 130
30 250 23.00 16.00 1.19 1.15 1625 190
36 250 26.00 19.00 1.25 1.15 2385 250
42 250 30.00 23.50 1.44 1.28 3465 410
48 250 34.00 25.00 1.56 1.42 4610 515
54 150 38.00 27.50 1.69 1.55 4415 675
60 150 42.00 32.00 1.88 1.75 5950 985
64 150 44.00 38.75 2.12 1.75 8155 1410
Flanged Fittings for Water Base Bends Ductile Iron Thicknesses, Dimensions and Weights
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 16866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
SIZE FITTING DIMENSIONS Inches Inches
BOLT BOLT HOLE NUMBERCIRCLE DIAMETER OF BOLTS
3 3.38 5/8 4
4 4.75 3/4 4
6 5.50 3/4 4
8 7.50 3/4 4
10 7.50 3/4 4
12 9.50 7/8 4
14 9.50 7/8 4
16 9.50 7/8 4
18 11.75 7/8 4
20 11.75 7/8 4
24 11.75 7/8 4
30 14.25 1 4
36 17.00 1 4
42 21.25 1-1/8 4
48 21.75 1-1/4 4
54 25.00 1-1/4 4
60 29.50 1-3/8 4
64 36.00 1-3/8 4
Base Drilling Details For Base Bends And Base Tees
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 17866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
NOTE: Actual weights of fittings, sizes 54"-64", may exceed those shown.
For flange details, see page 6.
Dimension "R" is a finished dimension; unfinished bases will be 1/8" longer. For base drilling details see page 15. For other dimensions see page 9.
* U.S. Pipe rates its 4"-24" pipe and fittings for 350 psi service with use of the FLANGE-TYTE® Gasket.
Flanged Fittings for Water Base Tees Ductile Iron Thicknesses, Dimensions and Weights
SIZE PRESSURE DIMENSIONS WEIGHT Inches RATING Inches Pounds
psi R S DIAMETER T U BASE BEND BASE ONLY
3 250 4.88 5.00 .56 .50 45 5
4 350* 5.50 6.00 .62 .50 70 10
6 350* 7.00 7.00 .69 .62 110 15
8 350* 8.38 9.00 .94 .88 185 30
10 350* 9.75 9.00 .94 .88 300 30
12 350* 11.25 11.00 1.00 1.00 430 45
14 350* 12.50 11.00 1.00 1.00 485 50
16 350* 13.75 11.00 1.00 1.00 600 50
18 350* 15.00 13.50 1.12 1.12 740 75
20 350* 16.00 13.50 1.12 1.12 930 75
24 350* 18.50 13.50 1.12 1.12 1410 80
30 250 23.00 16.00 1.19 1.15 2270 120
36 250 26.00 19.00 1.25 1.15 3320 160
42 250 30.00 23.50 1.44 1.28 5850 270
48 250 34.00 25.00 1.56 1.42 7720 335
54 150 38.00 27.50 1.69 1.55 6465 440
60 150 42.00 32.00 1.88 1.75 8755 710
64 150 44.00 38.75 2.12 1.75 12045 1050
* U.S. Pipe rates its 4"-24" pipe and fittings for 350 psi service with use of the FLANGE-TYTE® Gasket.
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 18866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
Flanged Fittings for Water Reducers Ductile Iron Thicknesses, Dimensions and Weights
SIZE PRESSURE RATING DIMENSIONS WEIGHTInches psi Inches Pounds
LARGE SMALL T T1 L
4 3 250 .52 .48 7 30
6 3 250 .55 .48 9 40
6 4 350* .55 .52 9 45
8 4 350* .60 .52 11 65
8 6 350* .60 .55 11 75
10 4 350* .68 .52 12 85
10 6 350* .68 .55 12 90
10 8 350* .68 .60 12 110
12 4 350* .75 .52 14 120
12 6 350* .75 .55 14 130
12 8 350* .75 .60 14 145
12 10 350* .75 .68 14 170
14 6 350* .66 .55 16 155
14 8 350* .66 .60 16 175
14 10 350* .66 .68 16 190
14 12 350* .66 .75 16 220
16 6 350* .70 .55 18 190
16 8 350* .70 .60 18 210
16 10 350* .70 .68 18 235
16 12 350* .70 .75 18 265
16 14 350* .70 .66 18 280
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 19866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
* U.S. Pipe rates its 4"-24" pipe and fittings for 350 psi service with use of the FLANGE-TYTE® Gasket.
Flanged Fittings for Water Reducers Ductile Iron Thicknesses, Dimensions and Weights (cont.)
SIZE PRESSURE RATING DIMENSIONS WEIGHTInches psi Inches Pounds
LARGE SMALL T T1 L
18 8 350* .75 .60 19 240
18 10 350* .75 .68 19 265
18 12 350* .75 .75 19 295
18 14 350* .75 .66 19 310
18 16 350* .75 .70 19 340
20 10 350* .80 .68 20 310
20 12 350* .80 .75 20 345
20 14 350* .80 .66 20 355
20 16 350* .80 .70 20 390
20 18 350* .80 .75 20 410
24 12 350* .89 .75 24 480
24 14 350* .89 .66 24 490
24 16 350* .89 .70 24 525
24 18 350* .89 .75 24 550
24 20 350* .89 .80 24 590
30 18 250 1.03 .75 30 810
30 20 250 1.03 .80 30 870
30 24 250 1.03 .89 30 970
36 20 250 1.15 .80 36 1230
36 24 250 1.15 .89 36 1345
36 30 250 1.15 1.03 36 1555
42 24 250 1.28 .89 42 1820
42 30 250 1.28 1.03 42 2060
42 36 250 1.28 1.15 42 2345
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 20866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
NOTE: Actual weights of fittings, sizes 54"-64" may exceed those shown.
Sizes 3"-48" conform to ANSI/AWWA C110/A21.10. Sizes 54"-64" conform to ANSI/AWWA C153/A21.53.
For flange details see page 6.
On reducers of certain end combinations the number of bolt holes on one flange have an odd number in one quadrant and the opposite flange has an evennumber of holes in the same quadrant so that there are only four positions in which the reducers can be placed to properly assemble with the adjacent piping. Please take particular note that flange reducers have the vertical centerline marked on the edge of the flange. If assembled with the centerline in the vertical plane, the casting will properly assemble.
Eccentric reducers with the same dimensions and weights given for concentric reducers are available when specified on purchase order.
Flanged Fittings for Water Reducers Ductile Iron Thicknesses, Dimensions and Weights (cont.)
SIZE PRESSURE RATING DIMENSIONS WEIGHTInches psi Inches Pounds
LARGE SMALL T T1 L
48 30 250 1.42 1.03 48 2625
48 36 250 1.42 1.15 48 2950
48 42 250 1.42 1.28 48 3320
54 30 150 .90 .61 32 1625
54 36 150 .90 .66 28 1680
54 42 150 .90 .76 25 1800
54 48 150 .90 .80 18 1695
60 36 150 .94 .66 32 2165
60 42 150 .94 .76 26 2190
60 48 150 .94 .80 20 2110
60 54 150 .94 .90 15 2055
64 36 150 .99 .66 35 2805
64 42 150 .99 .76 30 2870
64 48 150 .99 .80 25 2825
64 54 150 .99 .90 18 2695
64 60 150 .99 .94 17 2980
Thicknesses and Dimensions Conforming to ANSI B16.1
For sizes larger than 24" contact nearest sales office.
For flange details see page 6.
* U.S. Pipe rates its 4"-24" pipe and fittings for 350 psi service with use of the FLANGE-TYTE® Gasket.
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 21866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
90º BEND LONG RADIUSNOMINAL PRESSURE WALL B WEIGHTS
SIZE RATING THICKNESS Inches PoundsInches psi Inches
3 250 3/8 7-3/4 28
4 350* 1/2 9 48
6 350* 9/16 11-1/2 85
8 350* 5/8 14 145
10 350* 3/4 16-1/2 230
12 350* 13/16 19 350
14 350* 7/8 21-1/2 470
16 350* 1 24 670
18 350* 1-1/16 26-1/2 840
20 350* 1-1/8 29 1080
24 350* 1-1/4 34 1640
Manufacturer’s Standard Flanged Fittings 90º Long Radius Bends Ductile Iron
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 22866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
NOTE: Actual weights of fittings, sizes 54"-64", may exceed those shown.
For bolt hole details see page 6.
*U.S. Pipe rates its 4"-24" pipe and fittings for 350 psi service with use of the FLANGE-TYTE® Gasket.
Flanges are faced and drilled in accordance with ANSI/AWWA C110/A21.10.
DIMENSIONSInches
SIZE PRESSURE RATING DIAMETER THICKNESS WALL BLIND FLANGESInches psi OF FLANGE OF FLANGE THICKNESS Pounds
O Q V
3 250 7.50 .75 .69 9
4 350 *9.00 .94 .88 16
6 350 *11.00 1.00 .94 25
8 350 *13.50 1.12 1.06 42
10 350 *16.00 1.19 1.12 63
12 350 *19.00 1.25 1.19 85
14 350 *21.00 1.38 1.31 120
16 350 *23.50 1.44 1.38 145
18 350 *25.00 1.56 1.50 185
20 350 *27.50 1.69 1.62 245
24 350 *32.00 1.88 1.81 370
30 250 38.75 2.12 1.37 500
36 250 46.00 2.38 1.58 790
42 250 53.00 2.62 1.78 1175
48 250 59.50 2.75 1.96 1585
54 150 66.25 3.00 2.23 2260
60 150 73.00 3.12 2.68 2955
64 150 80.00 3.38 2.81 3855
Manufacturer’s Standard Flanged Fittings Blind Flanges — Ductile Iron
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 23866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
*U.S. Pipe rates its 4" - 24" pipe and fittings for 350 psi service with use of the FLANGE-TYTE® Gasket.
Manufacturer’s Standard Flanged FittingsWye Branches — Ductile Iron
SIZE PRESSURE RATING DIMENSIONS WEIGHTInches psi Inches Pounds
WALL THICKNESS A B C
RUN BRANCH RUN BRANCH
3 3 250 .48 .48 10 30 10 45
4 3 250 .52 .48 12 3 12 65
4 4 350* .52 .52 12 3 12 75
6 3 350* .55 .48 14.5 3.5 14.5 100
6 4 350* .55 .52 14.5 3.5 14.5 105
6 6 350* .55 .55 14.5 3.5 14.5 120
8 4 350* .60 .52 17.5 4.5 17.5 165
8 6 350* .60 .55 17.5 4.5 17.5 175
8 8 350* .60 .60 17.5 4.5 17.5 200
10 4 350* .68 .52 20.5 5 20.5 235
10 6 350* .68 .55 20.5 5 20.5 250
10 8 350* .68 .60 20.5 5 20.5 270
10 10 350* .80 .80 20.5 5 20.5 335
12 4 350* .75 .52 24.5 5.5 24.5 350
12 6 350* .75 .55 24.5 5.5 24.5 365
12 8 350* .75 .60 24.5 5.5 24.5 390
12 10 350* .87 .80 24.5 5.5 24.5 470
12 12 350* .87 .87 24.5 5.5 24.5 515
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 24866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
Manufacturer’s Standard Flanged FittingsWye Branches — Ductile Iron (cont.)
*U.S. Pipe rates its 4" - 24" pipe and fittings for 350 psi service with use of the FLANGE-TYTE® Gasket.
SIZE PRESSURE RATING DIMENSIONS WEIGHTInches psi Inches Pounds
WALL THICKNESS A B C
RUN BRANCH RUN BRANCH
14 6 350* .82 .55 27 6 27 475
14 8 350* .82 .60 27 6 27 500
14 10 350* .82 .68 27 6 27 525
14 12 350* .82 .75 27 6 27 570
14 14 350* .82 .82 27 6 27 605
16 6 350* .89 .55 30 6.5 30 620
16 8 350* .89 .60 30 6.5 30 645
16 10 350* .89 .68 30 6.5 30 675
16 12 350* .89 .75 30 6.5 30 715
16 14 350* .89 .82 30 6.5 30 755
16 16 350* .89 .89 30 6.5 30 805
18 6 350* .96 .55 32 7 32 755
18 8 350* .96 .60 32 7 32 780
18 10 350* .96 .68 32 7 32 810
18 12 350* .96 .75 32 7 32 850
18 14 350* .96 .82 32 7 32 885
18 16 350* .96 .89 32 7 32 935
18 18 350* .96 .96 32 7 32 980
20 8 350* 1.03 .60 35 8 35 995
20 10 350* 1.03 .68 35 8 35 1025
20 12 350* 1.03 .75 35 8 35 1065
20 14 350* 1.03 .82 35 8 35 1110
20 16 350* 1.03 .89 35 8 35 1155
20 18 350* 1.03 .96 35 8 35 1200
20 20 350* 1.03 1.03 35 8 35 1265
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 25866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
*U.S. Pipe rates its 4" - 24" pipe and fittings for 350 psi service with use of the FLANGE-TYTE® Gasket.
For flange details see page 6.
Manufacturer’s Standard Flanged FittingsWye Branches — Ductile Iron (cont.)
SIZE PRESSURE RATING DIMENSIONS WEIGHTInches psi Inches Pounds
WALL THICKNESS A B C
RUN BRANCH RUN BRANCH
24 8 350* 1.16 .60 40.5 9 40.5 1470
24 10 350* 1.16 .68 40.5 9 40.5 1505
24 12 350* 1.16 .75 40.5 9 40.5 1550
24 14 350* 1.16 .82 40.5 9 40.5 1590
24 16 350* 1.16 .89 40.5 9 40.5 1640
24 18 350* 1.16 .96 40.5 9 40.5 1685
24 20 350* 1.16 1.03 40.5 9 40.5 1750
24 24 350* 1.16 1.16 40.5 9 40.5 1905
30 12 250 1.37 .75 49 10 49 2545
30 14 250 1.37 .82 49 10 49 2590
30 16 250 1.37 .89 49 10 49 2645
30 18 250 1.37 .96 49 10 49 2690
30 20 250 1.37 1.03 49 10 49 2760
30 24 250 1.37 1.16 49 10 49 2915
30 30 250 1.37 1.37 49 10 49 3225
36 12 250 1.58 .75 60 19.5 60 4490
36 14 250 1.58 .82 60 19.5 60 4545
36 16 250 1.58 .89 60 19.5 60 4610
36 18 250 1.58 .96 60 19.5 60 4670
36 20 250 1.58 1.03 60 19.5 60 4750
36 24 250 1.58 1.16 60 19.5 60 4920
36 30 250 1.58 1.37 60 19.5 60 5255
36 36 250 1.58 1.58 60 19.5 60 5740
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 26866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
Manufacturer’s Standard Flanged FittingsTrue Wyes — Ductile Iron
SIZE PRESSURE RATING DIMENSION WEIGHTInches psi Inches Pounds
WALL THICKNESS A E
3 250 3/8 5-1/2 3 30
4 350* 1/2 6-1/2 3 55
6 350* 9/16 8 3-1/2 85
8 350* 5/8 9 4-1/2 135
10 350* 3/4 11 5 210
12 350* 13/16 12 5-1/2 300
Thicknesses and Dimensions Conforming to ANSI B16.1
*U.S. Pipe rates its 4" - 24" pipe and fittings for 350 psi service with use of the FLANGE-TYTE® Gasket.
For flange details see page 6.
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 27866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
Ductile Iron Thicknesses and Dimensions Conforming to ANSI B16.1
*U.S. Pipe rates its 4"-24" pipe and fittings for 350 psi service with use of the FLANGE-TYTE® Gasket.
For flange details see page 6.
Manufacturer’s Standard Flanged Fittings — Side Outlet 90º Elbows and Side Outlet Tees
DIMENSIONS WEIGHTInches Pounds
SIZE PRESSURE RATING WALL CENTER TO SIDE OUTLET SIDE OUTLETInches psi THICKNESS FACE A 90º ELBOW TEE
3 250 3/8 5 -1/2 34 48
4 350* 1/2 6-1/2 59 82
6 350* 9/16 8 96 135
8 350* 5/8 9 150 210
10 350* 3/4 11 240 330
12 350* 13/16 12 340 470
14 350* 7/8 14 470 650
16 350* 1 15 620 850
18 350* 1-1/16 16-1/2 760 1040
20 350* 1-1/8 18 970 1330
24 350* 1-1/4 22 1510 2080
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 28866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
For flange details see page 6.
SIZE T R B L WEIGHTInches Pounds
3 .48 6 7.50 8 20
4 .52 6 9.00 8 30
6 .55 6 11.00 8 40
8 .60 8 13.50 10 70
10 .68 10 16.00 10 95
12 .75 12 19.00 12 155
14 .66 14 21.00 12 165
16 .70 16 23.50 16 240
18 .75 18 25.00 16 275
20 .80 20 27.50 18 355
24 .89 24 32.00 18 480
30 1.00 ? 38.75 18 704
36 1.15 ? 46.00 18 1245
36 1.15 ? 46.00 24 1450
42 1.28 ? 53.00 24 1534
48 1.42 ? 59.50 24 1865
54 1.54 ? 66.00 24 2300
Miscellaneous Flanged Fittings Flange and Flare — Ductile Iron
For flange details see page 6.
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 29866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
Miscellaneous Flanged Fittings Flange and Flare 90º Bends Standard and Long RadiusDuctile Iron
DIMENSIONS WEIGHT DIMENSIONS WEIGHTInches Pounds Inches Pounds
STANDARD LONG RADIUSC WALL
SIZE A B DIAMETER T SIZE A B
3 5-1/2 11 7-1/2 3/8 30 3 7-3/4 13-3/4 35
4 6-1/2 12 9 1/2 45 4 9 14-1/2 50
6 8 12 11 9/16 75 6 11-1/2 15-1/2 90
8 9 14 13-1/2 5/8 120 8 14 19 155
10 11 17 16 3/4 195 10 16-1/2 22-1/2 250
12 12 18 19 13/16 275 12 19 25 375
14 14 20 21 7/8 380 14 21-1/2 27-1/2 500
16 15 21 23-1/2 1 515 16 24 30 715
18 16-1/2 22-1/2 25 1-1/16 640 18 26-1/2 32-1/2 900
20 18 24 27-1/2 1-1/8 800 20 29 35 1140
24 22 28 32 1-1/4 1240 24 34 40 1720
30 25 32 38-3/4 1-7/16 1970 30 41-1/2 48-1/2 2920
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 30866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
DIMENSIONS WEIGHTInches Pounds
BOLT DIAMETER OF FLANGE END BELL ENDSIZE CIRCLE HOLES SLUDGE SHOE SLUDGE SHOE
A B
4 12 7/8 49 66
6 14 7/8 69 92
8 15-3/4 7/8 86 118
10 18 1 106 143
12 21 1 139 182
For bolt hole details see page 6.
For availability consult your local U.S. Pipe representative.
Miscellaneous Flanged Fittings Standard Sludge Shoes with Flange or Bell Ends — Ductile Iron
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 31866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
The FLANGE-TYTE Gasket is a superior ring gasket that can save money on installation andmaintenance costs. When properly assembled, the FLANGE-TYTE Gasket gives a completely leak-free flanged joint at a reasonable bolt torque, even at high internal operating pressures onflanged pipe, fittings, valves and hydrants.
A flange piping system can be installed with FLANGE-TYTE Gaskets and operated safely at highinternal pressures and high velocities and still handle the ever-present threat of high surgeswithout fear of gasket leaks. The FLANGE-TYTE Gasket is listed by Underwriters Laboratories.Flanged joints with FLANGE-TYTE Gaskets are approved by Factory Mutual.
Flanges must conform to ANSI/AWWA C115/A21.15 Flanged Ductile-Iron Pipe with ThreadedFlanges or ANSI/AWWA C110/A21.10 Ductile-Iron and Gray-Iron Fittings, 3" through 48", For Water.
Flanged joints sealed with FLANGE-TYTE Gaskets are rated by U.S. Pipe for 350 psi working pres-sure for the 4" through 24" sizes, 250 psi for the 36" through 48" sizes and 150 psi for the 54"through 64" sizes, based on the performance requirements of ANSI/AWWA C111/A21.11 Rubber-Gasket Joints for Ductile Iron Pressure Pipe and Fittings. These FLANGE-TYTE Gaskets qualify asa “specially designed” gasket in accordance with ANSI/AWWA C111/A21.11 which recognizes350 psi rating for 24" and smaller sizes. 30" and 36" gaskets are rated for 350 psi as amanufacturer’s standard.
Factory Mutual and Underwriters Laboratories rate the 4" through 12" size range for 250 psi.
FLANGE-TYTE Gaskets are 1/8" thick and are available in SBR, EPDM, nitrile, fluorocarbon orneoprene. The gaskets meet the material requirements of ANSI/AWWA C111/A21.11.
NOTE: The flanges used in the above testsconform to the dimensional requirements ofANSI/ASME B16.1 Class 125 Flanges as well asthe above referenced flange standards
FLANGE-TYTE® is a registered trademark of U.S.Pipe and Foundry Company.
FLANGE-TYTE® Gaskets For 4" through 64"Flanged Pipe and Fittings
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 32866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
WORKING SIZE 150 PRESSURE 350
Inches psi 250 psi psi
4 - 90 110
6 - 90 110
8 - 90 110
10 - 90 130
12 - 90 130
14 - 110 150
16 - 110 160
18 - 120 180
20 - 120 200
24 - 130 220
30 - 140 -
36 - 160 -
42 - 585 -
48 - 625 -
54 550 - -
60 600 - -
64 600 - -
Torque Values are in ft-lb.
These torque values are appropriate for usewith FLANGE TYTE® Gaskets. For correcttorque values on other gaskets, consult the gasket supplier.
The FLANGE-TYTE® Gasket for flanged pipe and fittings should be assembled using the samegeneral procedures and practices as for plain ring type flange gaskets. As with all flangeassemblies, the faces of the flanges must be free of sand, grit, grease or other foreign matter.
Horizontal LinesFor larger diameters, it may be necessary to glue the FLANGE-TYTE® Gasket to the face of one ofthe flanges prior to aligning the flanges. For smaller diameter joints the gaskets can be droppedinto the joint as it is being assembled. Align the flanges and insert several bolts in the lower halfof the flanges. Drop the FLANGE-TYTE Gasket between the two flanges so that the gasket restson the lower bolts. Insert the remaining bolts and follow the tightening procedure below.
Vertical LinesCenter the FLANGE-TYTE® Gasket on the lower flange before assembling the joint. The gasket canalso be glued to the face of the flange to keep the gasket from dislodging during the assembly.
Bolt Tightening ProcedureAfter alignment has been completed, insert the bolts and hand tighten the nuts. Keep the gapbetween the flanges approximately uniform while tightening. Tighten the bolts to the requiredtorque in several steps, alternating from one side to the other.
NOTE: If specifiers and users believe that corrosive soils will be encountered where ourproducts are to be installed, please refer toANSI/AWWA C105/A21.5, PolyethyleneEncasement for Ductile Iron Pipe Systems, for proper external protection procedures.
Bolt Torque RequirementsBolt torque required by water workingpressures are as follows:
Assembling Flanged Pipe and Fittingswith FLANGE-TYTE® Gaskets
The FLANGE-TYTE gasket is 1/8" thick
Method of Designating Outlets of Reducing Fittings in Specifications
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 33866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
NOTE: The largest opening establishes thebasic size of a reducing fitting. Thelargest opening is named first, except forbullhead tees which are reducing on bothruns and for double branch elbows whereboth branches are reducing, the outlet is the largest opening and namedlast in both cases.
In designating the openings of reducingfittings they should be read in the orderindicated by the sequence of the letters a,b, c and d. In designating the outlets ofside outlet reducing fittings the side outletis named last and in the case of the crosswhich is not shown the side outlet is designated by the letter e. Fittings of theconfigurations shown on this page that arenot covered on pages 8 through 25 may befurnished on special order. Consult yournearest U.S. Pipe representative.
NOTE: The above sketches show twoviews of the same fitting and repre-sent fittings with symmetricalshapes, with the exception of theside outlet elbow and the side out-let tee (straight sizes).
Pages 32 and 33 are extracted fromAmerican National Standard Cast-Iron Pipe Flanges and FlangedFittings (ANSI B16.1-1975), with thepermission of the publisher, TheAmerican Society of MechanicalEngineers, United EngineeringCenter, 345 East 47th Street, NewYork, N.Y. 10017. Fittings of the con-figurations shown on this page thatare not covered on pages 8 through25 may be furnished on specialorder. Consult your nearest U.S. Piperepresentative.
Method of Designating Location of Tapped Holes for Drains When Specified
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 34866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
The illustrations in the “SPECIAL” columns on this page indicate typical fittings that are often required with a combination of bell, plainend, and flange outlets. The laying dimensions of these fittings are not covered by any standard and they are therefore usually named“SPECIAL” inasmuch as they are made to order to suit certain conditions in piping installations.
To the right of each “SPECIAL” fitting is shown a combination of Standard fittings that can be used to obtain the same outlet effects asthe Specials. The laying dimensions may not be interchangeable since the dimensions of the Standard fittings are fixed whereas theSpecial can be made to a variety of desired lengths.
The use of Standard fittings wherever possible is always recommended as the most economical and such fittings can usually be shippedout of stock. In sending inquiries for fittings of dimensions deviating from the Standard, state specifically the type of outlets wanted,reading, sizes, etc., as shown on this page, and give exact dimension from the center line to outlet.
Combination of Standard FittingsThat May be Used in Place of Special Fittings
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 35866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 36866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 11.05
Method of Reading Size of All Types of Standard and Special Fittings
FLANGED PIPE & FITTINGSNSF®
Certified toANSI/NSF 61
P 37866.
DIP.
PIPE
2 0 0 5 E D I T I O N
U.S. PIPE AND FOUNDRY CO. FLANGED PIPE AND FITTINGS BRO-013 REVISED 01.06
Products for Water, Wastewater and Fire Protection
Ductile Iron Pipe SIZE RANGE
TYTON JOINT® Pipe 4"-64" Ductile Iron
Mechanical Joint Pipe 4"-12" Ductile Iron
TR FLEX® Pipe 4"-64" Ductile Iron
Flanged Pipe 3"-64" Ductile Iron
USIFLEX® Boltless Flexible Joint Pipe — 4"-48" Ductile Ironfor Subaqueous Installations
Restrained Joints
TR FLEX® Pipe 4"-64" Ductile Iron
MJ FIELD LOK® Gaskets 4"-24"
FIELD LOK 350® Gaskets 4"-24"
FIELD LOK® Gasket 30" & 36"
TR FLEX GRIPPER® Rings 4"-36" Ductile Iron
TR TELE FLEX® Assemblies 4"-24" Ductile Iron
HP LOK™ Restrained Joint 30"-42"
Ductile Iron Fittings
TYTON® Fittings 14"-64" Ductile Iron
TRIM TYTON® Fittings 4"-12" Ductile Iron
TR FLEX® Fittings and TR FLEX® Telescoping Sleeves 4"-64" Ductile Iron
Mechanical Joint Fittings 3"-48" Ductile Iron
TRIM TYTE® MJ Fittings 3"-48" Ductile Iron
Flanged Fittings 3"-64" Ductile Iron
XTRA FLEX® Couplings 4"-24" Ductile Iron
Miscellaneous Products
PROTECTO 401™ Lined Ductile Iron Pipe for 4"-64" Ductile IronDomestic Sewage and Industrial Wastes
FLANGE-TYTE® Gaskets 4"-64"
Polymeric Linings For all pipe sizes
Saddle Outlets Various Ductile Iron
Welded Outlets Various Ductile Iron
Polyethylene Encasement 4"-64"
Our products are manufactured in conformancewith National Standards so that our customersmay be assured of getting the performance andlongevity they expect. Use of accessories or other appurtenances that do not comply with recognized standards may jeopardize the performance and longevity of the project.
P.O. Box 10406Birmingham, AL 35202
866.DIP.PIPE (866.347.7473)FAX 205.254.7165www.uspipe.com
All U.S. Pipe brochures and/or products aresubject to change without further notice.
REGIONAL SALES OFFICES
EASTERN REGIONAL OFFICE(609) 387-6120 (Phone)
(609) 387-6050 (Fax)
WESTERN REGIONAL OFFICE(815) 725-7168 (Phone)
(815) 725-7165 (Fax)
PACIFIC COAST REGIONAL OFFICE(510) 441-5800 (Phone)
(510) 441-5885 (Fax)
SOUTHERN REGIONAL OFFICE(205) 254-7229 (Phone)
(205) 254-7009 (Fax)
INTERNATIONAL SALES OFFICE(205) 254-7230 (Phone)
(205) 254-7274 (Fax)
top related