Dampers - AC - Heinen & Hopman · dampers - Ac. dampers There are different types of dampers: • Fire and smoke dampers • Air control and shut-off dampers Fire and smoke dampers
Post on 06-Oct-2020
23 Views
Preview:
Transcript
>
Ventilation Air Conditioning RefrigerationHeating
22ºCInside
OUTSIDEHUMIDITY
PROVIDED BYHEINEN & HOPMAN
35 C
90%
productsdampers - Ac
dampers
There are different types of dampers:• Fire and smoke dampers• Air control and shut-off dampers
Fire and smoke dampers Fire and smoke dampers prevent the spread of fire and smoke between fire zones, where people must have the maximum amount of time to react to possible fire. The dampers are type-approved according to A-0 (A-60).The A-60 marine fire and smoke damper complements the range of automatic fire and gas dampers and associated controls. The damper is the solution for shipboard air conditioning and ventilation systems fire safety engineering strategies.
ACFD A-60 fire and smoke dampers
Frame: AISI 316 stainless steel / galvanized steel.Thickness: 1.2, 2 or 3 mm.Blades: AISI 316 and AISI 430 options.Sizes: 100x100 ~ 1000x1000 mm.Circular connection pieces: 100 ~ 1000 mm.
air control and shut-off dampers Air control and shut-off dampers control the airflow or shut off airflow in ductwork where tightness, thermal insulation and reliability are important. The dampers meet international standards for both rectangular and circular ducts and the leakage class is accordance with the EN1751 standards.
ACCS air control and shut-off balancing dampers
Frame: AISI 316 stainless steel / galvanized steel.Thickness: 1.5 mm.Blades: AISI 316 stainless steel.Sizes: 100x100 ~ 1200x1200 mm at 50 mm intervals.Operation system: electrical, pneumatic or manual.Double section modules possible.
Control The dampers can be controlled electrically, pneumatically or manually. In case of fire, the fire and gas dampers will close automatically.
The electrically and pneumatically controlled dampers are driven by an actuator.
Belimo actuator: standard actuatorSchischek actuator: actuator used in explosion-proof areas or if the actuator must open/close within 3 sec./90°C.
To offer complete
operational security to those who
ensure ours
“ “
Alternatives available on request.Due to continuous product development, Heinen & Hopman reserves the right to introduce alterations without prior notice.
Alternatives available on request.Due to continuous product development, Heinen & Hopman reserves the right to introduce alterations without prior notice.
marine fire dampersA-60 marine fire and smoke dampers are used in air conditioning and ventilation systems, in dry filtered air. The dampers have been tested and approved for fitting to class A-60 divisions (bulkheads and decks), when suitably insulated (refer to insulation details).The dampers can be used where the maximum system pressure is up to 1500 Pa and duct velocities are limited to 15m/s. Pay particular attention to the blade rivets, where crevice corrosion will cause rapid failure of blades if not kept in check.The dampers are suitable for vertical and horizontal applications, with airflow in either direction. The dampers are normally open and failsafe to the closed position.
The dampers have two casings and blade options:1. 430 Stainless steel blades, galvanized steel casing - only suitable for installation in dry filtered systems.2. 316 Stainless steel blades, casing and drive - more suited for corrosive conditions, but even this will rapidly corrode and fail if not properly maintained, when used in air intake systems at sea. The addition of a mist eliminator is highly recommended and access must be provided for maintenance.
• Type-approved class A-60 when suitably insulated.• Available as ATEX-approved.• Optional Silicon blade seals can be provided for low leakage requirement at ambient temperature.• Electrical Thermal Release (ETR) temperature 72 ºC or Pneumatic Thermal Release (PTR) with a failsafe 74 °C fusible link.• Low weight due to patented double skin blade structure.• Automatic electrical, pneumatic or spring operation system available.• Maximum duct pressure: 1500 Pa. Maximum air velocity: 15 m/s.
dimensions and material thicknessThe dampers meet international standards for both rectangular (width B 100-1000 mm and height H 100-1000 mm, 1 mm division) and circular ducts (Ø 100-1000 mm).
Part Material Finishing
Frame Stainless steel EN 1.4404 (AISI316L) / Galvanized steel -
Blades Stainless steel EN 1.4404 (AISI316L) -
Bearings Stainless steel EN 1.4404 (AISI316L) -
Shafts Stainless steel EN 1.4404 (AISI316L) -
Dimensions S mm
L mm
If B or H 100 till 1000 1.2 / 2 / 3 150
if Ø100 till Ø1000 1.2 / 2 / 3 230
Alternatives available on request.Due to continuous product development, Heinen & Hopman reserves the right to introduce alterations without prior notice.
Alternatives available on request.Due to continuous product development, Heinen & Hopman reserves the right to introduce alterations without prior notice.
aCCs air control and shut-off dampers
• Low closed blade leakage performance.• Temperature operation range up to +180 °C.• Maximum duct pressure: 1000 Pa. Maximum air velocity: 10 m/s.• Low close blade leakage to EN 1751 class 2 requirements.
Part Material Note
Casing Galvanized steel Stainless steel AISI316L also available
Blades Galvanized steel Silicon blade seal, suitable for 280OC
Blade gaskets Silicon Heat-proof model: LTE silicon
Duct gasket Rubber compound Circular connections
Bearings Synthetic / stainless-steel blade bearings Self-lubricated heat-proof model: stainless steel AISI316L
Drive shaft Galvanized steel Rectangular bar (15x15 mm)
W H
200 - 1200 200 - 1200
ØD WxH
200 - 1000 200 x 1000
Dimensions in mm
www.heinenhopman.com
Heinen & Hopman encourages a more
sustainable world. By providing eco-friendly solutions and serviceswe offer our clients
the option of reducing energy consumption
and thus co2 emissions. Visit
greenmanifest.info for more information.
BrazilT: +5521 3587 4241/4244E: info@br.heinenhopman.com
France - La CiotatT: +334 4204 8685E: info@heinenhopmanfrance.com
France - GrasseT: +336 3090 7786 E: info@heinenhopmanfrance.com
GermanyT:+49 4073 1680E: info@drewsmarine.com
IndiaT: +9133 6499 1293E: info@heinenhopmanindia.com
ItalyT: +3901 8745 7970E: info@it.heinenhopman.com
The Netherlands (HQ)T: +313 3299 2500E: info@heinenhopman.com
The Netherlands (rotterdam)T: +317 8890 8050E: binnenvaart@heinenhopman.nl
NorwayT: +47 6919 0900E: admin@teknotherm.no
peoples republic of ChinaT: +8621 3253 2896E: info@cn.heinenhopman.com
peoples republic of ChinaT: +86 510 8528 1763E: ivo.klaric@teknotherm.no
polandT: +489 1433 1800E: tmh@teknotherm.no
romaniaT: +402 3644 8222E: office@ro.heinenhopman.com
russiaT: +7 (4012) 308 801E: info@heinenhopman.ru
singaporeT: +65 6897 7879E: info@sg.heinenhopman.com
south KoreaT: +8270 4901 0000E: info@kr.heinenhopman.com
spainT: +349 3225 9668E: info@es.heinenhopman.com
swedenT: +46 3121 7500E: mats.uden@teknotherm.no
TurkeyT: +9021 6493 8118E: info@tr.heinenhopman.com
Uae (abu dhabi) T:+971 2550 4147E: info@caspuae.com
Uae (dubai)T: +971 4263 5453E: info@caspuae.com
Usa - Fort Lauderdale, FloridaT: +195 4463 0110E: info@arwmaritime.com
Usa - Houma, Louisiana T: +198 5876 7989E: leblanc@leblancandassociates.com
top related