38
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.In the interests of development and improvement of the product, we reserve the right to change the specification.
Boi
ler
Con
trol
s
BCS1 Blowdown System Pipeline Set
TI-P403-57-US 12.10
Blowdownfromboiler
Blowdownto heat recovery
system
M10S2 ball valve
M10S2 ball valve
strainer
PT2 plug tail
CP10 sensor S10 sensorchamber
1/4" BSP plug
BCV1 blowdown valve
LCV1 check valve
• For TDS systems with probe in pipeline• Complete pipeline kit - choice of controller• Suitable for boiler pressures of 203 psig (14 bar g)• For blowdown rates up to 1,300 lb/h (590 kg/h)
DescriptionThe BCS1 pipeline set is a kit of components selected to enablestraightforward installation of a TDS control system where the probeassembly is to be mounted in the pipeline, rather than directly in theboiler shell.The BCS1 pipeline set consists of the following items:1 x S10 sensor chamber ½" NPT.1 x CP10 sensor and gasket. (UL Listed)1 x PT2 plug tail. (3/8" BSP, UL Listed)1 x Sensor chamber plug ¼" BSP.1 x BCV1 solenoid valve 120 V, UL Listed, CSA.1 x LCV1 check valve ½" NPT.1 x y type cast iron strainer (1/2" NPT, 20 Mesh).2 x M10S2 ball valves ½" NPT.Alternative products are available, but not as part of a kit.A controller is also required, and should be selected from the SpiraxSarco range.The BC3150 and BC3250 are all suitable, and offer a choice of fea-tures. Full details are available in separate literature.Main features are listed opposite.
MaterialsS10 sensor chamber Stainless steel BS 970 303 S31CP10 sensor body and pin Stainless steel BS 970 303 S31PT2 plug tail Brass bodySensor chamber plug Carbon steelBCV1 solenoid valve Brass body, stainless steel seat, PTFE seal.LCV1 check valve BronzeStrainer Cast ironM10S2 ball valve Zinc plated forged carbon steelSee individual product literature for further information.
BC3150• TUV type approved as a TDS limiter• 4 wire compensated conductivity measurement• Compensated temperature and scale detection• Pulsed probe conditioning cycle• Automatic detection of temperature input (Pt100)• Automatic purge on calibration• Isolated 0-20mA or 4-20mA for retransmission• Switchable alarm latch• Integrated infrared communications• Versatile mounting options: DIN rail, Panel or Chassis
BC3250• Avoids boiler damage and product contamination• Can sense conductivities down to 1 S/cm at 77ºF• Condensate temperature compensation for greater accuracy• Isolated 0-20 mA or 4-20 mA output• Inbuilt, infrared communications port• Modbus EIA (RS) 485 for external communications• Versatile mounting options: DIN rail, Panel or Chassis• Switchable alarm latch
Boi
ler B
low
dow
n&
CC
D
46
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.In the interests of development and improvement of the product, we reserve the right to change the specification.
Boi
ler
Con
trol
s
BC3150Blowdown Controller
DescriptionThe BC3150 is a blowdown controller for steam boilers. It controls TDS (total dissolved solids – salts in solution) by opening and closing a blowdown valve. It works in conjunction with a Spirax Sarco conductivity sensor, a boiler blowdown valve or condensate dump valve.The product can be panel, DIN rail or chassis mounted and powered by a 99 – 264 Vac mains supply.The front panel has a 3 digit LCD and a five-button keypad.The product has no battery. The programmed settings are held in non-volatile memory (Flash) and are written to after changing a parameter and pressing the OK key.
Principal features:
- Blowdown controller with temperature compensation.
- Type approved as a TDS limiter and controller.
- Works with CP10, CP30 or CP32 conductivity probes.
- Wide range: 1-9990 µS/cm or ppm – (x1, x 10, x 100 x 1000).
- LCD display with direct probe condition indicator.
- Infrared communications.
ApprovalsThis product complies with the Electromagnetic Compatibility Directive 2004 / 108 / EC and all its requirements.
The BC3150 is suitable for Class A Environments (e.g. industrial). A fully detailed EMC assessment has been made and has the reference number UK Supply BH BC3150 2008.
The BC3150 complies with the Low Voltage Directive by meeting the standards of:
- EN 61010-1:2001 safety requirements for electrical equipment for measurement, control, and laboratory use.
The BC3150 has been type-tested as a TDS controller and limiter by meeting the standard:
- Vd TÜV Equipment for Water Control 100 (07.2006).
- The BC3150 is UL listed (open).
FunctionAll ranges and operating parameters are selected using the software menu.
Commissioning is carried out using the two lower buttons.Once fully commissioned, the TDS value is displayed in μS/cm (or ppm if selected).
If the water conductivity exceeds the Set Point level, the TDS value shown on the display will alternate with 'bld', and the valve relay will be energised until the conductivity drops below 5% of full scale (FS) below the set point.
If the water conductivity exceeds the alarm level, the TDS value will alternate with 'AL' , and the valve relay will be energised until the conductivity drops 3% (FS) below the alarm level.
If the system is carrying out a purge, The TDS value will alternate with 'Pur', and the valve relay will be energised until the conductivity drops 5% (FS) below the set point.
InputsThe BC3150 can accept a signal from a Spirax Sarco conductivity probe (CP10, CP30, or CP32).
A Pt100 temperature sensor may be connected to provide temperature compensation (2% / °C). This is recommended if the boiler is working at varying pressures, or for other applications, such as condensate monitoring or coil boilers, where the temperature may vary. If a Pt100 is not fitted, the product uses a default temperature of 184°C (10 bar g). OutputsPulsed output - For smaller boilers where the capacity of the blowdown valve is relatively high compared to the boiler size, the blowdown may be set to pulsed, rather than continuous output, opening for 10 seconds, and closing for 20 seconds. This slows the rate at which the boiler water is removed so that the level is not unduly affected, avoiding the risk of triggering a low water alarm.
Other featuresTo prevent unwanted or inadvertent changes being made, all commissioning parameters are protected with a pass code. The BC3150 can communicate via an infrared link between adjacent controllers.
This feature enables the parameters of this product (OEM) to be passed to a product fitted with RS485 (user).
The BC3150 is always an IR slave – No set-up or adjustment is needed.
An isolated 4 - 20 mA output is provided as standard, and may be used for remote display of the TDS level or as an output to a computerised management system.
BC3150
x1000
x100
x10
OK
ALCLN
LCD display
5 button display
Clamping screw
Clamping screw
TI-P403-91-US 07.10
Boi
ler
Con
trol
sB
oile
r Blo
wdo
wn
& C
CD
47
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222© Spirax Sarco, Inc. 2001
TI-P403-91-US 07.10
BC3150Blowdown Controller
Technical data BC3150 Mains voltage range 99 Vac to 264 Vac at 50/60 HzPower supply
Power consumption 7.5 W (maximum)
General Indoor use only
Maximum altitude 2 000 m (6 562 ft) above sea level
Ambient temperature limits 0 - 55°C (32-131°F)
Maximum relative humidity 80% up to 31°C (88°F) decreasing linearly to 50% at 40°C(104°F)
Overvoltage category III 2 (as supplied)
Pollution degree
3 (when installed in an enclosure) - Minimum of IP54 or UL50 / NEMA Type 3, 3S, 4, 4X, 6, 6P or 13.
Enclosure rating NEMA type 4 hose down only (UL approval) and Environmental (front panel only) IP65 (verified by TRAC Global)
Electrical safety EN 61010-1
LVD (safety) UL61010-1
CAN / CSA C22.2 No. 61010-1
EMC Immunity/Emissions Suitable for heavy industrial locations
Enclosure Material Polycarbonate
Front panel Material Silicone rubber, 60 shore.
Solder Tin / lead (60 / 40%)
Rising clamp plug-in terminal blocks with screw connectors. Termination Caution: Use only the connectors supplied by Spirax Sarco Ltd. -
Mains
Safety and Approvals may be compromised otherwise.
and signal
Cable size 0.2 mm² (24 AWG) to 2.5 mm² (12 AWG).
connector
Stripping length 5 - 6 mm (0.2")
Type High temperature
Shield type Screened
Gauge 1 – 1.5 mm² (18 - 16 AWG) TDS probe 0 - 9.99 range - 10 metres (33ft)
Maximum length 0 - 99.90 range - 30 metres (100ft)
0-999.0 range and 0-9990 ranges - 100 metres (328ft) Recommended type Prysmian (Pirelli) FP200, Delta Crompton Firetuf OHLS
Type High temperature, twisted
Shield type Screened
Pt100 probe Number of cores 3
cable / wire Gauge 1 - 1.5 mm² (18 - 16 AWG)
Maximum length 100 m (328 ft)
Recommended type Various
Type Twisted pair
4 - 20 mA
Shield type Screened
output
Number of pairs 1
cable / wires Gauge 0.23 - 1 mm² (24 - 18 AWG)
Maximum length 100 m (328 ft)
Recommended type Various
Cable / wireandconnectordata
Boi
ler B
low
dow
n&
CC
D
48
Boi
ler
Con
trol
s
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
BC3150Blowdown Controller
Probe types CP10, CP30 and CP32
0 – 9.99 ppm or µS/cm
0 – 99.9 ppm or µS/cm
Water
Ranges
0 – 999 ppm or µS/cm
conductivity
0 – 9990 ppm or µS/cm
Accuracy ±2.5% FSD (possibly > in high EM locations)
µS/cm to ppm conversion 0.7 Neutralising factor 0.7 Input Resolution 0.1% FSD
technical Drive: ac – 4 wires
data Sensor type Pt100 – Class B or better
Range 0 - 250°C
(With Pt100 not fitted – Temperature user programmed temperature 100 - 250°C, 1°C steps)
compensation Accuracy ±2.5% FSD – system accuracy ±5%
(TC) Resolution 0.1% FSD
Drive: dc – 3 wires
Probe
Maximum voltage 32 Vdc
cleaning Drive Pulsed (1 second on, 1 second off)
Time 20 seconds
Minimum current 0 mA
Maximum current 20 mA
Open circuit voltage (maximum)
19 Vdc
4 - 20 mA Resolution 0.1% FSD
Maximum output load 500 ohm
Isolation 100 V
Output Output rate 10 / second
technical Contacts 2 x single pole changeover relays (SPCO)
data Voltage ratings (maximum) 250 Vac
Resistive load 3 amp @ 250 Vac
Inductive load 1 amp @ 250 Vac
Relays ac motor load
¼ HP (2.9 amp) @ 250 Vac
1/10 HP (3 amp) @ 120 Vac
Pilot duty load C300 (2.5 amp) - control circuit / coils
Electrical life (operations) 3 x 105 or greater depending on load
Mechanical life (operations) 30 x 106
Technical data BC3150 (continued)
TI-P403-91-US 07.10
Boi
ler
Con
trol
sB
oile
r Blo
wdo
wn
& C
CD
49
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P403-91-US 07.10
BC3150Blowdown Controller
Safety information, installation and maintenanceWarning: This document does not contain sufficient information to install the unit safely. The unit operates at a potentially fatal mains voltage. Before attempting to install the unit read the Installation and Maintenance Instructions supplied with it.
Caution: before installing and connecting the power ensure there is no condensation within the unit. The product may be installed on a DIN rail, on a chassis plate, or in a panel cutout. A bezel is supplied.
The product must be installed in a suitable industrial control panel or fireproof enclosure to provide impact and environmental protection. A minimum of IP54 (EN 60529) or Type 3, 3S, 4, 4X, 6, 6P and 13 (UL50/NEMA 250) is required. Spirax Sarco can provide suitable plastic or metal enclosures
Do not install the product outdoors without additional weather protection.
Do not attempt to open the product - it is sealed and has no replaceable parts or internal switches.
Do not cover or obstruct the infrared beam between products.
No special servicing, preventative maintenance or inspection of the product is required.
Boiler water level controls and level alarms do, however, require testing and inspection.
Dimensions / weight (approximate) in mm and g.Weight 475 g. (1 lb)
How to specifyBlowdown controller with LCD display and five-button keypad, and infrared communications.
How to orderExample: 1 off Spirax Sarco BC3150 blowdown controller.
BC3150
x1000
x100
x10
OK
ALCLN
52 mm(2.05")
120 mm(4.72")
140 mm(5.51")
120 mm(4.72")
Boi
ler B
low
dow
n&
CC
D
50
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.In the interests of development and improvement of the product, we reserve the right to change the specification.
Boi
ler
Con
trol
s
BC3250Blowdown Controller
TI-P403-90-US 07.10
DescriptionThe BC3250 is a blowdown controller for steam boilers. It controls TDS (total dissolved solids - salts in solution) by opening and closing a blowdown valve.
It also has a timer that controls a bottom blowdown valve, to remove precipitated solids from the bottom of the boiler.
The product works in conjunction with a Spirax Sarco conductivity sensor, a boiler blowdown valve and, for condensate contamination detection, a dump valve.
It can operate on a supply voltage of between 99 - 264 Vac.
The front panel has an LCD graphics display and five-button keypad to select, view, and change functions.
In run mode (standard setting) the display is divided into three sections:i) Process variable and control parameters.ii) Information line, displays the various control states and process
units. iii) Three bar graphs, which show a percentage of full scale of: - PV Process Variable highest and lowest recorded value. - SP Set Point and hysteresis point.
- AL High Alarm and hysteresis point.
An additional filter can be selected to increase the damping effect where the probe is fitted directly in the boiler. This avoids over-frequent valve operation.
A Trend graph screen display appears if the right or left button is pressed in run mode - This displays a record of the variation in TDS over a set time.
The BC3250 can be used on a condensate contamination system. Please note that it will not detect contaminants that do not change the conductivity, e.g. oils, fats, or sugars.
The blowdown may be set to pulsed, rather than continuous output, opening for 10 seconds, and closing for 20 seconds. This avoids the risk of triggering a low water alarm in smaller boilers.
An isolated 0 - 20 or 4 - 20 mA output is provided for remote display of the TDS level or as an output to a management system.
If a switch box is fitted to the bottom blowdown valve actuator, an alarm can be configured to indicate if the bottom blowdown valve fails to close or to lift off its seat.
The BC3250 can communicate via an infrared link between adjacent controllers. It can be designated as either a master unit or a slave unit.
The unit can be panel, DIN rail or chassis mounted.
Principal features: Blowdown controller with bottom blowdown timer.- Multi-voltage 99 Vac – 264 Vac.- Display in µS/cm or ppm. - LCD graphics display of PV and sequential trend graph.- Filter for turbulent conditions.- Infrared communications.- Diagnostic / test facility.- 0/4 - 20 mA output.- EIA 485/Modbus communications.
ApprovalsThis product complies with the Electromagnetic Compatibility Directive 2004 / 108 / EC and all its requirements.
The BC3250 is suitable for Class A Environments (e.g. industrial). A fully detailed EMC assessment has been made and has the reference number UK Supply BH BC3250 2008.
The BC3250 complies with the Low Voltage Directive by meeting the standards of:- EN 61010-1:2001 safety requirements for electrical equipment for
measurement, control, and laboratory use.
The BC3250 has been type-tested as a TDS controller and limiter by meeting the standard:- Vd TÜV requirements for TDS control and limiting devices, Water Level 100 (07.2006).- UL listed (open).
FunctionInputsThe BC3250 can accept a signal from a Spirax Sarco CP10, CP30 or CP32 conductivity probe, and a Pt100 temperature sensor.
Function / outputsIf the water conductivity exceeds the Set Point, the valve relay will be energised until the conductivity drops below the Set Point. If the water conductivity exceeds the alarm level, the alarm relay will be de-energised until the conductivity drops below the alarm level.
Other features:- Test function.- Direct display of probe factor. - Commissioning parameters protected with a pass code.
OK
BC3250
100
50
0%
SP PV AL
Graphic display
5 button display
Clamping screw
Clamping screw
Boi
ler
Con
trol
sB
oile
r Blo
wdo
wn
& C
CD
51
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222© Spirax Sarco, Inc. 2001
TI-P403-90-US 07.10
BC3250Blowdown Controller
Technical data BC3250 Mains voltage range 99 Vac to 264 Vac at 50 / 60 HzPower supply
Power consumption 7.5 W (maximum)
General Indoor use only
Maximum altitude 2 000 m (6 562 ft) above sea level
Ambient temperature limits 0 - 55°C (32-131°F)
Maximum relative humidity 80% up to 31°C (88°F) decreasing linearly to 50% at 40°C
(104°F)
Overvoltage category III
2 (as supplied)
Pollution degree
3 (when installed in an enclosure) -
Minimum of IP54 or UL50 / NEMA Type 3, 3S, 4, 4X, 6, 6P or 13.
Enclosure rating NEMA type 4 hose down only (UL approval) and
Environmental (front panel only) IP65 (verified by TRAC Global)
Electrical safety EN 61010-1
LVD (safety) UL61010-1, UL 508, Clause 23.2.
CAN / CSA C22.2 No. 61010-1
EMC Immunity / Emissions Suitable for heavy industrial locations
Enclosure Material Polycarbonate
Front panel
Color Pantone 294 (blue)
Material Silicone rubber, 60 shore.
Solder Tin / lead (60 / 40%)
Rising clamp plug-in terminal blocks with screw connectors.
Termination Caution: Use only the connectors supplied by Spirax Sarco Ltd.
Mains
Safety and Approvals may be compromised otherwise.
and signal Cable size 0.2 mm² (24 AWG) to 2.5 mm² (12 AWG).
connector Stripping length 5 - 6 mm (0.2")
Type High temperature
Shield type Screened
Number of cores 4 TDS cable / wire Gauge 1 – 1.5 mm² (18 - 16 AWG) 0 - 9.99 range - 10 metres (33ft)
Maximum length 0 - 99.90 range - 30 metres (100ft)
0-999.0 range and 0-9990 ranges - 100 metres (328ft)
Recommended type
Prysmian (Pirelli) FP200,
Delta Crompton Firetuf OHLS
Type High temperature, twisted
Shield type Screened
Pt100 probe Number of cores 3
cable / wires Gauge 1 – 1.5 mm² (18 - 16 AWG)
Maximum length 100 m (328 ft)
Type Twisted pair
Shield type Screened
0/4-20 mA output(s) Number of pairs 1 cable/wire Gauge 0.23 - 1 mm² (24 - 18 AWG) Maximum length 100 m (328 ft)
Recommended type various
Type EIA RS485 twisted pair
Shield type Screened
RS485 communication Number of pairs 2 or 3 cable / wire Gauge 0.23 mm² (24 AWG) Maximum length 1200 m (4000 ft)
Recommended type Alpha Wire 6413 or 6414
LAN Cat 5 or Cat 5E ScTP (screened), FTP (foil) or STP (shielded) cable can be used, but limited to 600 m.
Boi
ler B
low
dow
n&
CC
D
52
Boi
ler
Con
trol
s
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P-403-90-US 07.10
BC3250Blowdown Controller
Probes type: CP10, CP30 and CP32
0 – 9.99 ppm or µS/cm
0 – 99.9 ppm or µS/cm
Water
Ranges
0 – 999 ppm or µS/cm
conductivity
0 – 9990 ppm or µS/cm
Accuracy ±2.5% FSD (Poss > if high EMC)
pH factor 0.50 – 1.00 (0.7 default) Neutralising factor 0.7 Input Resolution 0.1% FSD
technical Drive: ac – 4 wires
data Sensor type Pt100 – Class B or better
Range
0 - 250°C (32-482°F) (With Pt100 not fitted – user programmed Temperature temperature 100 - 250°C {212-482°F}, 1°C steps)
compensation Accuracy ±2.5% FSD – system accuracy ±5%
(TC) Resolution 1% FSD
Drive: dc – 3 wires
Input voltage range 99 – 264 Vac
Burner input Maximum current input 2 mA maximum
Probe Maximum voltage 32 Vdc
cleaning Drive ac /dc/pulsed
Minimum current 0 mA
Maximum current 20 mA
Open circuit voltage (maximum)
19 Vdc
4 - 20 mA Resolution 1% FSD
Maximum output load 500 ohm
Isolation 100 V
Output rate 10 / second
Contacts 2 x single pole changeover relays (SPCO)
Voltage ratings (maximum) 250 Vac
Resistive load 3 amp @ 250 Vac
Output Inductive load 1 amp @ 250 Vac
technical Relays ac motor load
¼ HP (2.9 amp) @ 250 Vac
data 1/10 HP (3 amp) @ 120 Vac
Pilot duty load C300 (2.5 amp) - control circuit / coils
Electrical life (operations) 3 x 105 or greater depending on load
Mechanical life (operations) 30 x 106
Physical layer RS485 4-wire full or 2-wire half duplex
Protocol Modbus RTU format
RS485 Isolation 60 Vac/dc
Receiver unit load (256 devices - maximum)
Output rate Up to 10 frames / second
Physical layer IrDA
Baud 38 400
Infrared Range 10 cm (4")
Working angle 15°
Eye safety information
Exempt from EN 60825-12: 2007 Safety of laser products - does not exceed the accessible emission limits (AEL) of Class 1
Technical data BC3250 (continued)
Boi
ler
Con
trol
sB
oile
r Blo
wdo
wn
& C
CD
53
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P-403-90-US 07.10
BC3250Blowdown Controller
Safety information, installation and maintenanceWarning: This document does not contain sufficient information to install the unit safely. The unit operates at a potentially fatal mains voltage. Before attempting to install the unit read the Installation and Maintenance Instructions supplied with it.
The product must be installed in a suitable industrial control panel or fireproof enclosure to provide impact and environmental protection. A minimum of IP54 (EN 60529) or Type 3, 3S, 4, 4X, 6, 6P and 13 (UL50/NEMA 250) is required. This product meets the requirements of clause 23.2 of UL508 and may be considered part of the 5VA rating for industrial use.
The product may be installed on a DIN rail, a chassis plate, or in a panel cut-out. A bezel is supplied.
Install the product in an environment that minimises the effects of heat, vibration, shock and electrical interference.
Do not install the product outdoors without additional weather protection.
Do not attempt to open the product - it is sealed and has no replaceable parts or internal switches.
Do not cover or obstruct the infrared beam between products.
No special servicing, preventative maintenance or inspection of the product is required.
Boiler water level controls and level alarms do, however, require testing and inspection.
Dimensions / weight (approximate) in mm and g.Weight 550 g. (1.21 lb)
How to specifyBlowdown controller with integral bottom blowdown timer and infrared comms.
How to orderExample: 1 off Spirax Sarco BC3250 blowdown controller.
OK
BC3250
100
50
0%
SP PV AL
52 mm(2.05")
120 mm(4.72")
140 mm(5.51")
120 mm(4.72")
Boi
ler B
low
dow
n&
CC
D
54
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.In the interests of development and improvement of the product, we reserve the right to change the specification.
Boi
ler
Con
trol
s
BCV1 and BCV20Blowdown Valves
TI-P403-60-US 11.11
Description The BCV1 and BCV20 valves are small bore, normally closed valves with a brass body and corrosion resistant internal components. They are primarily intended for low and medium pressure boiler blowdown applications.BCV1 and BCV20 valves are identical apart from the orifice size, the BCV1 having a 3 mm (1/8") orifice and the BCV20 a 6 mm (¼") ori-fice. Valves are supplied complete with a mains connector, which is protected to IP65 and is suitable for 3 x 1 mm² (18 AWG) cable.
Available sizes and pipe connections½" screwed BSP - 230 V version½" screwed BSP - 110 V version½" screwed NPT - 120 V version½" screwed NPT - 120 V version (UL/CSA Listed)
Limiting conditionsBCV1
Maximum boiler or 14 bar g (203 psi g)steam pressure (Intermittent operation)
Medium temperature range -40 to +200°C (-40 to +392°F)
Medium Water and steam
Maximum ambient temperature 55°C (130°F)
BCV1 (UL/CSA)
Maximum boiler or 9 bar g (130 psi g)steam pressure
Medium temperature range -40 to +180°C (-40 to +356°F)
Medium Water and steam
Maximum ambient temperature 55°C (130°F)
BCV20
Maximum boiler or 4 bar g (58 psi g)steam pressure
Medium temperature range -40 to +180°C (-40 to +356°F)
Medium Water and steam
Maximum ambient temperature 55°C (130°F)
Electrical data230 V version 207 V to 253 V
110 V version 99 V to 121 V
120 V version 108 V to 132 V
Frequency 50 - 60 Hz
Maximum power consumption 40 VA (inrush)
16 VA/12 W (hold)
Protection rating IP65 (Nema 4)
MaterialsBody Brass
Soft seal PTFE
Internal components Stainless steel
Boi
ler
Con
trol
sB
oile
r Blo
wdo
wn
& C
CD
55
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
BCV1 and BCV20Blowdown Valves
TI-P403-60-US 11.11© Spirax Sarco, Inc. 2001
Dimensions/weight (approximate) in mm (ins) and kg (Ibs)
A B C D E Weight
40 110 74.5 94.5 73 0.75(1.57) (4.33) (2.93) (3.72) (2.87) (1.65)
CapacitiesModel BCV1 BCV20
Orifice size 3 mm (1/8") 6 mm (¼")
Cv value 0.3 0.9
For conversion: Cv (UK) = Kv x 0.963 Cv (US) = Kv x 1.156
When used for boiler blowdown purposes, the valve will be controlling a mixture of water and flash steam, so the following capacity table applies:-
Boiler pressure bar g (psi g) Capacity kg/h (Ib/h) BCV1 BCV20
1 (14.5) 175 (385) 560 (1232)
2 (290) 250 (550) 790 (1738)
4 (580) 350 (770) 1120 (2464)
6 (870) 385 (847) -
8 (1160) 445 (979) -
10 (1450) 495 (1089) -
14 (2030) 590 (1298) -
When the BCV20 valve is used as part of the BCS2 blowdown control system, downstream of a steam trap, the following capacity table applies:-
Head Cold water Hot water capacity across valve capacity with flash steam m (ft) kg/h (Ib/h) kg/h (Ib/h)
1 (3) 253 (557) 63 (138)
2 (6) 358 (787) 90 (198)
3 (9) 438 (963) 110 (242)
5 (15) 566 (1245) 142 (312)
10 (30) 800 (1760) 200 (440)
How to specifyBCV1Solenoid valves shall be Spirax Sarco normally closed blowdown valve type BCV1 or BCV1 (UL/CSA) with brass bodies and stain-less steel valve seat with a PTFE seal.
BCV20Solenoid valves shall be Spirax Sarco normally closed, low pres-sure blowdown valve type BCV20 with brass bodies and stainless steel valve seat with a PTFE seal.
How to orderExample: 1 off Spirax Sarco BCV1 or BCV20 blowdown valve having screwed NPT connections, 120 V.
A
D
E
½" BSP/NPT½" BSP/NPT
B
C
Solenoid coil
Spring
Armature with PTFE valve seat
Spare partsThe spare parts available are detailed below. No other parts are supplied as spares.
Available spares
Armature and spring set (kit). Stock No. 4034080
Solenoid coil 230 V Stock No. 4034081
Solenoid coil 110/120 V Stock No. 4034082
How to order sparesAlways order spares by using the description given in the column headed 'Available spares' and state the valve type.Example: 1 off Armature and spring set (Stock No. 4034080) for a Spirax Spirax BCV20 blowdown valve.
Boi
ler B
low
dow
n&
CC
D
56
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.In the interests of development and improvement of the product, we reserve the right to change the specification.
Boi
ler
Con
trol
s
3/4" BCV 30 Blowdown Control Valve
TI-9-305-US 11.11
DescriptionThe Spirax Sarco BCV30 is an electrohydraulically actuated control valve for the blowdown of steam boilers or other high pressure drop, low flowrate applications.It is generally used with a blowdown controller as part of an auto-matic TDS control system.The flowrate is adjusted by limiting the spindle stroke to regulate the number of orifices that are uncovered.The valve, which is supplied adjusted to its low flowrate setting of .4’’ stroke, is especially designed to minimize seat erosion and ensure consistent tight shut-off.It can be adjusted to .6’’ stroke for medium flowrates, or to .8’’ stroke for high flowrates, by repositioning the internal cam. A valve position indicator is provided.The valve can be opened manually by turning the actuator hand-wheel clockwise.A 1/4’’ BSP tapping is provided for a sample cooler.Full installation, adjustment and maintenance information is pro-vided with the valve.
Sizes and Pipe Connections3/4’’ Flanged ANSI 300
OperationThe valve is spring loaded to the closed position.When power is applied to the actuator the valve opens to the posi-tion set by the internal limit switch.
Limiting ConditionsMaximum pressure 464 psig (32 barg)Maximum temperature 462˚F (239˚C)Maximum ambient temperature 122˚F (50˚C)Protection rating (IP54)Outdoor installation is not recommended without additional protection.
Electrical data230 V version 187 V- 264 V 50-60 Hz24 V version 19.2 V - 28 V 50-60 HZPower consumption 15 VA
• Electrohydraulically actuated valve with manual override• Cast steel body with stainless steel internals• Articulated valve cone ensures tight shut-off and correct alignment• Spring closure on power failure• Valve position indicator
1 Actuator handwheel2 Manual indicator3 Seat4 Washer (seat)5 Cone6 Cap7 Stem8 Wave spring9 Gasket10 Spring11 Chevron seal set
12 Stuffing box13 Gasket15 Plug16 Gasket20 Guide bush22 Gasket23 Plug 1/4’’ BSP25 Clamping screw26 Actuator (without limit switch assembly27 Limit switch assembly
No. Description No. Description
Approval (24V Version)UL UL-429United States Standard Electrically operated
ULC C22.2 No. 139-1982Canadian Standard Electrically operated valves
(24v Version)
1
26
2
27
25
9
3
7
12
1311
10
5
6
41615
8
22
23
Boi
ler
Con
trol
sB
oile
r Blo
wdo
wn
& C
CD
57
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
3/4" BCV 30 Blowdown Control Valve
TI-9-305-US 11.11
MaterialsValveBody Cast carbon steel DIN 17245 GS-C25Bonnet Forged steel carbon DIN 17234 C 22.8Stuffung box Martenistic stainless steel Type 431Bottom Cover Carbon steel BS 907 230 M07Internals Martenistic stainless steel Type 431 (Valve cone and seat hardened)ActuatorCasing Die cast AluminumCover ABSCylinder/piston Aluminum
Dimensions/Weights (approximate) in inches and lbs.Size A B C D Weight3/4’’ 6’’ 15-3/8’’ 5’’ 1/4’’ BSP 20 lb.
Blowdown Valve Capacity in lb/hBoiler Pressure Low Flowrates Medium flowrates High flowratespsig .4’’ stroke (10mm) .6’’ stroke (15 mm) .8’’ stroke (20 mm)80 880 1210 1900102 1015 1565 2540145 1260 2100 3310218 1540 2540 3640290 1720 2760 3750464 2075 3090 3970
How to orderExample: Spirax Sarco BCV30 blowdown valve, 24V, flanged 3/4" ANSI 300, and approved by Underwriters Laboratory as a Listed Product.
Spare partsSpare parts are available as listed below. No other parts are available as spares.
Gasket & packing set24V (UL) Stock No. 4034480 4,9,10,11,12,13,16,20,22115/230V Stock No. 4034482 4,9,13,16,22,41
Valve cone, seat & stem set24V (UL) Stock No. 4034481 3,5,6,7,8,15115/230V Stock No. 4034483 3,5,6,7,8,15,16,45 + Gasket and packing set
Adjustable stuffing box kit115/230V Stock No. 4034484 40,42,43,44 + Gasket and packing setNote: The adjustable graphite seal system is not currently Approved for use on the UL Listed valve.
Actuator with limit switch assembly115V Stock No. 4034466230V Stock No. 403446724V (UL) Stock No. 4034468Actuator limit switch assembly: 24 (UL) /115/230V versions Stock No. 4034419
Safety InformationWARNINGYour attention is drawn to Safety Information Leaflet IM-GCM-10, as well as to any National or Regional regulations. This product is designed and constructed to withstand the forces encountered dur-ing normal use. Use of the product for any purpose other than a blowdown control valve could cause damage to the product and may cause injury or fatality to personnel.
InstallationThis document does not contain sufficient information to install the product safely. See the Installation & Maintenance Instructions provid-ed with every unit. Do not install the valve outside without additional weather protection.
MaintenanceIt is recommended that the valve is examined annually and parts replaced if necessary. For detailed maintenance instructions, see Installation & Maintenance Instructions (IM-P403-15).
B
DA
C
Sample bake-off
12
1311
20
10
UL Listed Valve Sealing Arrangement
45
© Spirax Sarco, Inc. 2003
Boi
ler B
low
dow
n&
CC
D
58
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.In the interests of development and improvement of the product, we reserve the right to change the specification.
Boi
ler
Con
trol
s
Limiting ConditionsMaximum pressure 464 psig (32 barg)Maximum temperature 462˚F (239˚C)Maximum ambient temperature 122˚F (50˚C)Protection rating IP54 (NEMA 3S)
1-1/2" BCV 30 Blowdown Control Valve
TI-P403-72-US 07.03
DescriptionThe Spirax Sarco BCV30 is an electrohydraulically actuated control valve for the blowdown of steam boilers or other high pressure drop, low flowrate applications.It is generally used with a blowdown controller as part of an automatic TDS control system.The flowrate is adjusted by limiting the spindle stroke to regulate the size of the orifices that are uncovered.The valve, which is supplied adjusted to a flowrate setting of 0.4’’ stroke, is especially designed to minimize seat erosion and ensure consistent tight shut-off.It can be adjusted to give different flowrates by repositioning the internal cam. A valve position indicator is provided.The valve can be opened manually by turning the actuator handwheel clockwise.A 1/4’’ plug at the base of the valve may be removed to allow a sam-ple cooler to be fitted (available from Spirax Sarco).
Sizes and Pipe Connections1-1/2’’ Flanged BS1560 Class 300
OperationThe valve is spring loaded to the closed position.When power is applied to the actuator the valve opens to the position set by the internal limit switch. Stroking time for the full 0.8" stroke is approximately 2 minutes to open and 8 seconds to close.
• Electrohydraulically actuated valve with manual override• Cast steel body with stainless steel internals• Articulated valve cone ensures tight shut-off and correct alignment• Spring closure on power failure• Valve position indicator
Approval UL UL-429United States Standard Electrically operated
ULC C22.2 No. 139-1982Canadian Standard Electrically operated valves
MaterialsValve MaterialBody Cast carbon steel DIN 17245 GS-C25Bonnet Forged steel carbon DIN 17243 C 22.8Stuffing box Martensitic stainless steel/ ASTM A276 assembly graphite seals 316LBottom Cover Carbon steel BS 970 230 M07Internals Martensitic stainless steel Type 431 components (valve cone and seat hardened)Guide bush Phosphor bronze BS EN 12163 CW451KCasing Die cast AluminumCover ABSCylinder/piston AluminumStem Martensitic stainless steel ASTM A276 431
Electrical dataSupply 19 V - 28 V 50-60 HZPower consumption 16 VA
Casting
Stem
Bonnet
Body
Internalcomponents Bottom cover
Cover
Cylinder/piston
Stuffing box assembly
Guide bush
Boi
ler
Con
trol
sB
oile
r Blo
wdo
wn
& C
CD
59
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
1-1/2" BCV 30 Blowdown Control Valve
TI-P403-72-US 07.03
Dimensions/Weights (approximate) in inches and lbs. Size A B C D Weight1-1/2" 7.5" 18.9’’ 7.0’’ 1/4" BSP 49
Capacity
Boiler Blowdown valve capacity lb/h Presure 0.2" 0.4" 0.6" 0.8" (psig) stroke stroke stroke stroke 72.5 990 6394 7607 7827 101.5 1047 7276 9040 9922 145 1102 8158 10473 12017 217.5 1212 10032 14222 15765 290 1764 12678 17860 19073 464 2866 18522 22711 24365
Spare partsSpare parts are available as listed below. No other parts are available as spares.Available spares
Gasket & stem seal set Stock No. 4034880 9, 13, 40, 41, 42, 43, 44
Valve head, seat & stem set Stock No. 4034881 3, 4, 6, 7, 8, 22
Actuator with limit Stock No. 4034768 24V (UL)switch assembly
Actuator limit Stock No. 4034419switch assembly
Safety InformationWARNINGThis product is designed and constructed to withstand the forc-es encountered during normal use. Use of the product for any purpose other than a blowdown control valve could cause dam-age to the product and may cause injury or fatality to personnel.
InstallationThis document does not contain sufficient information to install the product safely. See the Installation & Maintenance Instructions provid-ed with every unit. Do not install the valve outside without additional weather protection.
MaintenanceIt is recommended that the valve is examined annually and parts replaced if necessary. The gland may be adjusted if required as described in the installation and Maintenance Instructions.
Sample take-off
Note: Intermediate flowrate strokes can be set on the 1-1/2 BCV30.
AD
B
C
7
9
44
43
1342
41
3
40
4
22
8
6
How to order sparesAlways order spares by using the description given above and state the size and flange type of blowdown control valve.
Example: 1 off Gasket and stem seal set Stock No. 4034880for Spirax Sarco 1-1/2" BCV30 blowdown control valve flanged BS 1560 Class 300.
How to orderExample: 1 off Spirax Sarco 1-1/2" BCV30 blowdown control valve, 24 V, flanged BS 1560 Class 300
© Spirax Sarco, Inc. 2003
Boi
ler B
low
dow
n&
CC
D
60
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.In the interests of development and improvement of the product, we reserve the right to change the specification.
Boi
ler
Con
trol
s
TI-P403-36-US 11.11
¾" BCV31Blowdown Control Valve
DescriptionThe Spirax Sarco BCV31 is a pneumatically operated control valve for the blowdown of steam boilers. It is normally used with a control-ler as part of an automatic TDS control system, though it can also be used for other high pressure drop, low flowrate applications.The flowrate is adjusted by limiting the spindle stroke to regulate the number of orifices that are uncovered.The valve, which is specially designed to minimise seat erosion and ensure consistent tight shut-off, is supplied adjusted to its low flowrate setting of 10 mm.It can be adjusted to give 15 mm stroke for medium flowrates, or to 20 mm stroke for high flowrates. The actuator has a mechanical stroke indicator and incorporates a rolling diaphragm.A ¼" NPT plug at the base of the valve may be removed to allow a sample cooler to be fitted (available from Spirax Sarco).The BCV31 requires a regulated and filtered air supply (¼" NPT), which should be free of oil and water, and a solenoid valve, (avail-able from Spirax Sarco).
Operation:The valve is spring loaded to the closed position (spring retract), and is also held closed by the boiler pressure. When the solenoid valve opens, air is admitted to the actuator causing the valve to open to the selected stroke.
Sizes and pipe connections¾" ANSI Class 300Note: All certification /inspection requirements must be stated at the time of order placement.
Pressure /temperature limits
Maximum operating pressure 32 bar g (464 psi g)Maximum operating temperature 239°C (462°F) Maximum ambient temperature 110°C (230°F)Minimum ambient temperature 0°C (32°F)Minimum operating temperature 0°C (32°F)Air pressure range 3 to 6 bar g (44 to 87 psi g)Air consumption - normal 0.48 litres (0.017 ft³)(20mm travel)
Capacities Boiler Blowdown valve capacity kg/h (lb/h) pressure Low flowrates Medium flowrates High flowrates bar g 10 mm stroke 15 mm stroke 20 mm stroke 5 380 (838) 530 (1168) 730 (1609) 7 460 (1014) 710 (1565) 1150 (2535) 10 570 (1257) 950 (2094) 1500 (3307) 15 700 (1543) 1150 (2535) 1650 (3638) 20 780 (1720) 1250 (2756) 1700 (3748)
32 940 (2072) 1400 (3036) 1800 (3968)
�
��
���
���
������
� � �� �� �� �� �� ��
Tem
pera
ture
°C
Pressure bar g
Steam saturationcurve
MaterialsPart Material
Body Cast carbon steel DIN 17245 GS-C25
Bonnet Forged carbon steel DIN 17243 C 22.8
Stuffing box Stainless steel / ASTM A276 assembly graphite seals 316L
Bottom Carbon steel BS 970 230 MO7cover 3.1 version Forged carbon steel DIN 17243 C 22.8
Internal Stainless steel Type 431components (valve cone and seat are hardened)
Guide bush Phosphor bronze BS EN 12163 CW451K
Diaphragm housing Pressed steel
Diaphragm Reinforced NBR
Yoke SG iron
Spindle Stainless steel
Connector Carbon steel
Diaphragm housing
Diaphragm
Spindle
Yoke
Connector
Stuffing box assembly
Bonnet
Body
Internal components
Bottom cover
Guide bush
Boi
ler
Con
trol
sB
oile
r Blo
wdo
wn
& C
CD
61
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P403-36-US 11.11© Spirax Sarco, Inc. 2004
¾" BCV31Blowdown Control Valve
Dimensions/weight (approximate) in inches and pounds
Size A B C D Weight
DN20 5.9 14.2 11.7 ¼" NPT 24.7 (maximum)
Safety information, installation and maintenanceFor full details see the Installation and Maintenance Instructions supplied with the product.
Important:Your attention is drawn to Safety Information Leaflet IM-GCM-10, as well as to any national or regional regulations.
Installation note:The valve itself may be installed outdoors without additional pro-tection. The solenoid valve however, must be installed indoors, or adequately protected against outdoor conditions.
Maintenance note:We recommend that the valve and actuator are examined annually and parts replaced as necessary.
How to orderExample: 1 off Spirax Sarco ¾" BCV31 blowdown control valve having flanged ANSI 300 connections.
Spare partsThe spare parts available are shown in solid line. Parts shown in broken line are not supplied as spares.
Available spares Gasket and Stock No. 4, 9, 13, 16, 22, 41 packing set 4034682 Valve cone,
Stock No. 3, 5, 6, 7, 8, 15, 16, 20
Valve seat and 4034683
+ Gasket and stem set packing set Adjustable Stock No.
40, 42, 43, 44 stuffing 4034484
+ Gasket and box kit packing set Stem seal kit 17, 18, 30 Diaphragm kit 4, 9Actuator Travel indicator kit 15, 19, 20 Spring kit 5 Linkage kit 10, 13, 14, 26, 27 (suitable for MK1 and Mk2 valves)
How to order sparesAlways order spares by using the description given above, and state the size and flange type of blowdown control valve.Example: 1 off Gasket and packing set, Stock No. 4034682, for a Spirax Sarco ¾" BCV31 blowdown control valve having flanged ANSI 300 connections.
D Sample take-offA
B
C
4443
134241
2093
4
22
68
15
7
165
40
4
5
17, 18
30
10, 13, 14, 26, 27
15, 19, 20
9
10
17, 18
Boi
ler B
low
dow
n&
CC
D
62
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.In the interests of development and improvement of the product, we reserve the right to change the specification.
Boi
ler
Con
trol
s
1-1/2" BCV 31 Blowdown Control Valve
TI-P403-74-US 11.11
DescriptionThe Spirax Sarco BCV31 is a pneumatically operated control valve for the blowdown of steam boilers. It is normally used with a con-troller as part of an automatic TDS control system, though it can also be used for other high pressure drop flowrate applications.The flowrate is adjusted by limiting the spindle stroke to regulate the size of the orifice that is uncovered.The valve, which is specially designed to minimise seat erosion and ensure consistent tight shut-off, is supplied adjusted to a flowrate setting of 10 mm.It can be adjusted to give different flowrates. The actuator has a mechanical stroke indicator and incorporates a rolling diaphragm.A ¼" NPT plug at the base of the valve may be removed to allow a sample cooler to be fitted (available from Spirax Sarco).The BCV31 requires a regulated and filtered air supply (¼" NPT), which should be free of oil and water, and a solenoid valve, (avail-able from Spirax Sarco).
Operation:The valve is spring loaded to the closed position (spring retract), and is also held closed by the boiler pressure. When the solenoid valve opens, air is admitted to the actuator causing the valve to open to the selected stroke. Sizes and pipe connectionsANSI Class 300Note: All certification / inspection requirements must be stated at the time of order placement.
Maximum operating pressure 32 bar g (464 psi g)Maximum operating temperature 239°C (462°F) Maximum ambient temperature 110°C (230°F)Minimum ambient temperature 0°C (32°F)Minimum operating temperature 0°C (32°F)Air pressure range 2.5 to 6 bar g (36 to 87 psi g)Air consumption - normal 1.606 litres (0.565 ft³)(20mm travel)
�
��
���
���
������
� � �� �� �� �� �� ��
Pressure/temperature limits
Pressure bar g
Tem
per
atur
e °C
MaterialsPart Material
Body Cast carbon steel DIN 17245 GS-C25
Bonnet Forged carbon steel DIN 17243 C 22.8
Stuffing box Stainless steel / ASTM A276 assembly graphite seals 316L
Bottom cover Carbon steel BS 970 230 MO7
Internal Stainless steel Type 431components (valve cone and seat are hardened)
Guide bush Phosphor bronze BS EN 12163 CW451K
Diaphragm housing Pressed steel
Diaphragm Reinforced NBR
Yoke SG iron
Spindle Stainless steel
Connector Carbon steel
Note: These items are clearly shown overleaf.
Capacities Boiler Blowdown valve capacity kg/h (lb/h) pressure 5 mm 10 mm 15 mm 20 mm bar g stroke stroke stroke stroke 5 450 (992) 2900 (6393) 3450 (7606) 3550 (7826) 7 475 (1047) 3300 (7275) 4100 (9039) 4500 (9921) 10 500 (1102) 3700 (8157) 4750 (10472) 5450 (12015) 15 550 (1212) 4550 (10031) 6450 (14210) 7150 (15763) 20 800 (1764) 5750 (12677) 8100 (17857) 8650 (19070) 32 1300 (2866) 8400 (18519) 10300 (22708) 11050 (24361)
Note: Intermediate flowrate strokes can be set on the 1½" BCV31.
Steam saturationcurve
Diaphram housing
Spindle
Yoke
Connector
Stuffing box assembly
Bonnet
BodyInternal
components
Bottom cover
Air connection
Boi
ler
Con
trol
sB
oile
r Blo
wdo
wn
& C
CD
63
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
1-1/2" BCV 31 Blowdown Control Valve
TI-P403-74-US 11.11© Spirax Sarco, Inc. 2003
Dimensions/weight (approximate) in inches and pounds
Size A B C D Weight
DN40 7.8 15.9 11.8 ¼" NPT 64
Spare partsThe spare parts available are shown in solid line. Parts shown in broken line are not supplied as spares.
Available spares
Gasket and Stock No. 9, 13, 40, 41, stem seal set 4034880 42, 43, 44
Valve Valve cone, Stock No.
seat and
4034882 3, 4, 6, 7, 8, 22
stem set
Stem seal kit 17, 18, 30
Diaphragm kit 4, 9
Actuator Travel indicator kit 15, 19, 20
Spring kit 5
Linkage kit 10, 13, 14, 26, 27 (suitable for MK1 and Mk2 valves)
How to order sparesAlways order spares by using the description given above, and state the size and flange type of blowdown control valve.Example: 1 off Gasket and stem seal set, Stock No. 4034880, for a Spirax Sarco 1½" BCV31 blowdown control valve having flanged ANSI 300 connections.
Safety information, installation and maintenanceFor full details see the Installation and Maintenance Instructions supplied with the product.
Important:Your attention is drawn to Safety Information Leaflet IM-GCM-10, as well as to any national or regional regulations.
Installation note:The valve itself may be installed outdoors without additional pro-tection. The solenoid valve however, must be installed indoors, or adequately protected against outdoor conditions.
Maintenance note:We recommend that the valve and actuator are examined annually and parts replaced as necessary.