September 2009 ACC-SVP01B-EN

BACnettrade Communication Interface (BCI-I)for IntelliPaktrade and Commercial Self-contained

Integration Guide

2 ACC-SVP01B-EN bull BCI0I Integration Guide

Copyright

copy 2009 Trane All rights reserved

This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part without the written permission of Trane Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change

Trademarks

IntelliPak Tracer Trane and the Trane logo are trademarks of Trane in the United States and other countries All trademarks referenced in this document are the trademarks of their respective owners

Table of Contents

ACC-SVP01B-EN bull BCI-I Integration Guide 3

Overview 4

Ordering Numbers 4

BACnet Protocol 4

BCI-I Configuration 5

Overview 5

Starting a Session of Tracer TU and Direct Connection 5

IP Units Configuration 6

BACnet Object Configuration 7

Change Baud Rate 7

Change Device ID 7

Stand-alone or BAS Operation 8IntelliPak Control Configuration 8BAS Unit Control 8Periodic Update of BAS Values 9BAS Communication Failure 9

InputOutput Commands and Calculations 9System Control Command 9Filter Timer Reset Command 9Diagnostics Reset Command 10Setpoint Calculations 10Timestamp Configuration 11

BCI IntelliPak Rotary Switches and LEDs 12

Rotary Switches 12

LEDs Description Behavior and Troubleshooting 13

BACnet Data Points and Configuration Property Definitions 17

BACnet Protocol Implementation Conformance Statement (PICS) 17Standardized Device Profile (Annex L) 17Interoperability Building Blocks (Annex K) 17Segmentation Capability 18Object Types 19

BACnet Protocol 22Data Link Layer Options 22Device Address Binding 22Networking Options 22

Object Data Points and Diagnostic Data Points 24

Additional Resources 44

Glossary 45

4 ACC-SVP01B-EN bull BCI-I Integration Guide

Overview

The BACnet Communication Interface for IntelliPak (BCI-I) is comprised of a Tracertrade UC400 controller with interface software It is a non-programmable communications module that allows heating ventilation and air-conditioning (HVAC) equipment to communicate on a BACnet communications network

This guide provides

bull A list of ordering numbers

bull A brief overview of the BACnettrade protocol

bull BCI-I configuration information

bull A explanation of the BCI-I device rotary switches and LEDs

bull Data point configuration property definitions

bull Tables listing object data points

bull Additional resources

bull A glossary of terms

Note Users of this guide should have basic knowledge of BACnet protocol For more detailed information about this protocol visit the company web site listed under ldquoAdditional Resourcesrdquo p 44

Ordering Numbers

BACnet Protocol

The Building Automation and Control Network (BACnet and ANSIASHRAE Standard 135-2004) protocol is a standard that allows building automation systems or components from different manufacturers to share information and control functions BACnet provides building owners the capability to connect various types of building control systems or subsystems together for a variety of reasons In addition multiple vendors can use this protocol to share information for monitoring and supervisory control between systems and devices in a multi-vendor interconnected system

The BACnet protocol identifies standard objects (data points) called BACnet objects Each object has a defined list of properties that provide information about that object BACnet also defines a number of standard application services that are used to access data and manipulate these objects and provides a clientserver communication between devices For more information on BACnet protocol refer to ldquoAdditional Resourcesrdquo p 44

BACnet Testing Laboratory (BTL) Certification

The BCI-I supports the BACnet communication protocol and has been designed to meet the requirements of the application-specific control profile For more details refer to the BTL web site at wwwbacnetassociationorg

Order Number Description

X13651544-010 IntelliPak I for software and hardware

C175218460010 IntelliPak I II and CSC for field-installed kit

ACC-SVP01B-EN bull BCI-I Integration Guide 5

BCI-I Configuration

BCI-I Configuration

This section will provide the following information when configuring the BCI-I

bull Overview

bull Starting a session of Tracer TU and direct connection

bull Resetting to factory default

bull Configuring IP units

bull Configuring BACnet objects

bull Changing baud rate and device ID

bull Inputoutput and equipment functions

Overview

The BCI-I device is designed as a self-configuring controller to accommodate the many possible equipment configuration options available in the IntelliPak line of equipment This self-configuring device eliminates the need for the BAS technician having to create BACnet objects minimizes the risk of object configuration errors and allows the IntelliPak unit to be quickly installed in the BAS

The self-configuration process only creates objects that are appropriate for the feature set of the specific IntelliPak unit the BCI-I is connected to Once this process is complete the device exits factory mode and enters the normal mode of operation At this point the self-configuration process will not start when power is applied to the device

The set of objects listed in Table 3 p 24 through Table 10 p 31 are the super set of all possible objects supported by the IntelliPak line of equipment The BAS technician should query the device for the list of actual objects that have been created in the device

Starting a Session of Tracer TU and Direct Connection

Tracer TU is the service tool software that allows the technician to modify the operation of the device and to discover the BACnet objects present in the device To modify the device or discover objects the user must first connect to Tracer TU as follows

WARNING Remove power from the HVAC equipment before opening electrical control panel

1 Connect a USB cable directly between the laptop PC and the service port located on the front of the BCI-I device When connecting to the controller for the first time the Found New Hardware Wizard appears Follow the wizard instructions to install the USB hardware driver

2 Click either the Tracer TU desktop icon or the Tracer TU program item in the Tracer TU group on the Start menu The Tracer TU splash screen appears briefly followed by the Connect dialog box

3 Select the Direct Connection (Via USB cable) radio button if it is not already selected

4 Click the Connect button and the Tracer TU main page will appear after successful connection

Note The BCI-I may be powered via the USB cable or 24 Vac from the HVAC unit Concurrent connection of unit power and the USB cable will not harm the BCI-I device

For more detailed information about direct connection to Tracer TU refer to the Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

6 ACC-SVP01B-EN bull BCI-I Integration Guide

BCI-I Configuration

Reset to Factory Default

Factory default mode is the only mode the technician can use to set the units of measure for the device or to scan the IntelliPak unit to create BACnet objects The process of putting the device in factory default mode must be run prior to executing units of measure configuration or the object self-configuration process

WARNING Remove power from the HVAC equipment before

opening electrical control panel

To reset the controller to factory defaultunconfigured state

1 Power down the unit The IMC buss must not be active during reset

2 Establish the connection between Tracer TU and the device Follow the procedure ldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

3 From the Utilities menu select Controller and then Controller Settings The Controller Settings page appears

4 On the controller settings page there is a gray bar at the bottom with SaveCancel buttons Move the cursor near the left edge of the bar keeping the cursor inside the bar Click on this area and a Clear Controller button will appear in the upper right portion of the page

5 Click the Clear Controller button and a pop-up window will appear asking for confirmation to reset the device Click Yes

6 After a few seconds a pop-up will appear confirming that the controller has been reset and indicating that the controller will be rebooted Click OK

After the controller boots up it will be in factory default state The units of measure is SI (metric) the MSTP baud rate is 76800 and there will be no BACnet objects present in the controller

The controller must be in this state prior to changing the units of measure or self-configuring the device If using inch-pound units of measure proceed to the next section ldquoIP Units Configuration otherwise proceed to ldquoBACnet Object Configuration

IP Units Configuration

The BCI-I supports both inch-pound and SI (metric) units of measure The factory default units of measure is SI The device allows only a change of units for all objects as a whole Mixed units of measure is not allowed If the controller is not in factory default state follow the previous procedure ldquoReset to Factory Defaultrdquo p 6

To change the units of measure in the device

1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Controller Units frame

3 In the Device Units box of the frame select IP units of measure radio button and then click Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Select OK

4 Exit Tracer TU and cycle power to the controller by disconnecting the USB plug and then reconnecting the plug After the controller boots up it will be in factory default state the units of measure is IP the MSTP baud rate is 76800 and there will be no BACnet objects present in the controller

ACC-SVP01B-EN bull BCI-I Integration Guide 7

BCI-I Configuration

BACnet Object Configuration

Configuring BACnet objects is a self-configuring process If the controller is not in factory default state follow the previous procedure ldquoReset to Factory Defaultrdquo p 6

1 Remove the USB cable plug from the device

2 Apply power to the HVAC equipment After the device boots up the self-configuration process will begin No further user action is required

Note Do not remove power while the device is in self-configuration mode This typically takes 2 to 4 minutes to complete Once complete the device enters normal operating mode

Change Baud Rate

The BCI-I device supports four baud rates 9600 19200 38400 and 76800 baud The default baud rate is 76800 baud The baud rate can be modified with Tracer TU

WARNING Remove power from the HVAC equipment before opening electrical control panel

To change baud rate

1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Protocol frame

3 Click on the drop down arrow for the Baud Rate list and select the desired baud rate

4 Click Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Click OK

5 Exit Tracer TU and disconnect the USB cable plug

6 Apply power to the HVAC equipment

Change Device ID

By default the BCI-I device sets its device ID to the same value as the one defined by the rotary switches (MSTP MAC address) on the front of the device Refer to the section ldquoRotary Switchesrdquo p 12 For simple networks this is an easy method to guarantee unique device IDs across the link

The device also supports the full range of device ID values as specified by the BACnet Standard Systems that require a more complex device ID convention are supported with Tracer TU which has the ability to set the device ID via software configuration

WARNING Remove power from the HVAC equipment before opening electrical control panel

The process for soft setting the device ID is as follows

1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Protocol frame

3 In the device ID box select the check box next to Use Software Device ID to enable the functionality The swipe-and-type box becomes available

4 Type in the desired device ID

8 ACC-SVP01B-EN bull BCI-I Integration Guide

BCI-I Configuration

5 Click the Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Click OK

6 Exit Tracer TU and disconnect the USB service plug

7 Apply power to the HVAC equipment

Stand-alone or BAS Operation

The control system on HVAC equipment has the ability to operate the unit as a stand-alone system or as part of a building automation system The BCI-I (either factory or field installed) by default is configured for stand-alone operation This configuration enables the HVAC equipment to operate prior to the commissioning of the unit into the BAS

IntelliPak Control Configuration

The IntelliPak control system must be configured at the human interface (HI) to support unit control from the BAS The technician should setverify the following configuration properties as illustrated below The technician should also verify that the BAS Module Comm Failure diagnostic is not present

BAS Unit Control

The BCI-I provides a method for a BAS to control the operation of HVAC equipment This method consists of BACnet objects that the BAS can access to control and monitor the status of equipment There are two sets of objects

bull Output objects used by the BAS to provide command setpoint and sensor information to the IntelliPak unit

bull Input objects provide IntelliPak status information to the BAS See tables 3 to 11 for the list of objects supported

The system allows the BAS technician to define the amount of control that the BAS system will apply to the unit This is done by configuring the state of the Out of Service property of the output objects If the property is set to True the equipment will use a corresponding local value for control If the property is set to False the local value is ignored and the BAS-supplied value is used for control The BAS value is provided to the IntelliPak by writing to the present value property of the corresponding output object The factory default value for the Out of Service property of these objects is True

1 Configuration Menu

2 Setup Menu

3 Diagnostics Menu

Software Revision NumberBAS Communications BACnet 1801

Configuration - Model Num Digit 34BAS Communication Module Installed

Unit Control BASNETWORK

Active Diagnostic - - Auto ResetNone

Human Interface Representation

ACC-SVP01B-EN bull BCI-I Integration Guide 9

BCI-I Configuration

Periodic Update of BAS Values

The BCI-I device requires the BAS system to provide a periodic update to the sensor values This is required to protect against a loss of communication between the BAS and the BCI-I By BACnet definition the present value of the object will maintain the last value written to it regardless of the amount of time that has elapsed since the last write If communication is lost for several minutes or longer the present value of BAS-supplied sensor objects may no longer represent the current state of environmental conditions This may result in decreased occupant comfort and damage to building systems

BAS Communication Failure

The BCI-I is designed to minimize communication failure mode It does this by monitoring the length of time that has elapsed since the last write to the present value of the sensor object If the length of time exceeds a predefined limit the BCI-I will place the object into the fault state and revert to a unit-supplied sensor value for control At power up the sensor objects are set to a fault state and they will remain in this state until a write is detected The minimum periodic refresh rate for the objects is defined in Table 3 p 24 The following list is a set of sensor values that can be supplied by the BAS

bull Space Static Pressure BAS

bull Space Air Temperature BAS

bull Discharge Air Temperature BAS

bull Duct Static Air Pressure BAS

bull Outdoor Air Temperature BAS

bull Outdoor Air Humidity BAS

bull Outdoor Airflow BAS

bull Space CO2 Concentration BAS

bull Space Humidity BAS

InputOutput Commands and Calculations

This section will provide the following information about certain inputs and outputs that perform unique control commands and calculations

bull System control command

bull Filter timer and diagnostic reset commands

bull Setpoint calculations

System Control Command

Binary Output Object 1 has a special importance in the system The object allows the BAS to command the unit to run in a local or BAS control mode When the present value property of the object is set to Local Control the IntelliPak unit will enter local control and ignore BAS supplied values In this mode the unit will use local sensor and setpoint values When the object present value property is set to BAS Control the IntelliPak unit will use the values supplied by the BAS system for unit control

Filter Timer Reset Command

The BCI-I uses the Filter Runtime Hours object (AI 6) to generate a diagnostic when its present value is greater than the Filter Runtime Hours Setpoint (AV 1) present value The procedure for resetting the timer is as follows

10 ACC-SVP01B-EN bull BCI-I Integration Guide

BCI-I Configuration

The BAS will change the state of the Filter Timer Reset Command object (BO 13) to the active state Upon the change to active state the BCI-I will set the present value of the Filter Runtime Hours object to zero and then set the Reset Command object back to the inactive state

Diagnostics Reset Command

The IntelliPak control system monitors the operation of the HVAC equipment If an abnormal condition is detected a diagnostic message is displayed on the human interface of the equipment control panel In addition the set of internal diagnostics is mapped to the set of BACnet binary input objects as listed in Table 9 p 31 The corresponding BI object will change state from inactive to active when the diagnostic is detected The object has been configured to send a BACnet event message to external BACnet devices as defined by the protocol

The BAS has the ability to reset internal diagnostics by controlling the state of the Diagnostic Reset Command object (BO 14) The procedure for resetting diagnostics is as follows

The BAS will change the state of the Diagnostic Reset to the active state Upon the change to active state the IntelliPak control system will reset all internal diagnostics and set the state of all of the diagnostic objects to inactive Upon completion of this action the BCI-I will set the present value of the Diagnostic Reset Command object back to the inactive state

Setpoint Calculations

The equipment has the ability to perform two basic control functions

bull Space air temperature control

bull Discharge air temperature control

When the unit is configured for discharge air control it controls the temperature of the air leaving the unit to the discharge air temperature setpoint

When the unit is configured for space air temperature control it controls the air temperature of the space that contains the space air temperature sensor This value may be provided by wiring the sensor to the unit or via a sensor value provided by the BAS

The drawing below describes how the various temperature setpoints are calculated for space temperature control When the unit is in an occupied mode the active space temperature setpoint is calculated based on the space temperature setpoint and the two setpoint offset values In unoccupied mode the unoccupied heating and cooling setpoints are used as the active setpoint

ACC-SVP01B-EN bull BCI-I Integration Guide 11

BCI-I Configuration

Timestamp Configuration

The BCI-C device has a software-derived clock that maintains the time and date The device requires the current time to enable it to record a timestamp when an event or a change in state is detected by a BACnet object However in the event of a power loss the device does not maintain this time and date information At powerup the device time and date will default to 1200 pm Jan 1 1970 To minimize the possibility that the unit timestamp is not representing the actual time the BAS should be setup to periodically synchronize the device time clock with the BAS clock using the BACnet TimeSynchronization service

12 ACC-SVP01B-EN bull BCI-I Integration Guide

BCI IntelliPak Rotary Switches and LEDs

BCI IntelliPak Rotary Switches and LEDs

This section provides information about the BCI-I rotary switches and LED displays

Rotary Switches

There are three rotary switches on the front of the BCI-I device that are used to define a three-digit address when the BCI-I is installed on a BACnet communications network The three-digit address setting is the BACnet MAC address

Note All devices are MSTP masters with valid MAC addresses of 001 to 127 for BACnet

Figure 1 Setting rotary switches

ADDRESS0 1

23

456

78

9

x1

0 1

23

456

78

9

x10

0 1

23

456

78

9

x100

Before

After

0

5

1

3

6

29

487

Example of before and after setting addresses

Use a 18 inch flathead screwdriver to set rotary switches

Important Each device on the BACnetMSTP link must have a unique rotary switch setting otherwise communication problems will occur

ACC-SVP01B-EN bull BCI-I Integration Guide 13

BCI IntelliPak Rotary Switches and LEDs

LEDs Description Behavior and Troubleshooting

There are 15 LEDs on the front of the BCI-I unit However LEDs BO1 through BO9 are not used for the BCI-I controller Figure 2 shows the locations of each LED The following table provides a description of each LED activity an indication or troubleshooting tips for each and any notes

Figure 2 LED locations

SERVICE

IMCLINK

RX

TX

Marquee LED

Table 1 LED Activities and Troubleshooting Tips

LED Name ActivitiesIndication or Troubleshooting

Tip (Denoted in Bullets) Notes

Marquee LED

Shows solid green when the unit is powered and no problems exist

Indicates normal operation

Shows solid red when the unit is powered but represents low power or a

malfunction

bull If low power could be under voltage or the microprocessor has malfunction Follow the troubleshoot procedure ldquo24 Vac Measurementrdquo p 15 to measure for the expected value range

bull If malfunction unpower and then repower unit to bring the device back up to normal operation

Shows blinking red when an a BACnet object is in a fault condition

Alarm when an alarm is triggered for example when a point goes into fault condition because of point failure or there is an indication of a custom alarm in TGP2

Shows blinking green when the device does not detect the IMC buss

bull Verify that the IPC wiring harness is connected to the IMC link terminals

bull Verify the polarity of the IPC wiring harness at the unit terminals

LED not lit

Indicates power is OFF or there is a malfunction

bull OFF or malfunction cycle the power

14 ACC-SVP01B-EN bull BCI-I Integration Guide

BCI IntelliPak Rotary Switches and LEDs

Link and IMC

TX blinks greenBlinks at the data transfer rate when the unit transfers data to other devices on the link

TX LED Regardless of connectivity or not this LED will constantly blink as it continually looks for devices to communicate to

LED not litDetermine if for example a Tracer SC or BACnet device is trying to talk to the controller or if it is capable of talking to the controller Also determine if the communication status shows down all of the time

Refer to ldquoGround Measurementsrdquo p 16 for a check-out procedure

RX blinks yellow

Blinks at the data transfer rate when the unit receives data from other devices on the link

bull ON solid yellow indicates there is reverse polarity

LED not lit

Indicates that the controller is not detecting communication

bull Not lit cycle the power to reestablish communication

Service

Shows solid greenIndicates someone is pressing this LED or the controller is not operating normally

Press and hold during power up to place controller into boot code or press and hold for a count of approximately 10 seconds to clear the Device ID

What is Boot Code When the UC400 is placed into boot code the system will not run any applications such as trending scheduling and TGP2 runtime

Blinks green

Indicates controllers is not accessing application software

bull Restore using TU service tool

LED not lit Indicates controller is operating normally

Binary 01 to Binary 09 Not Used

Table 1 LED Activities and Troubleshooting Tips

LED Name ActivitiesIndication or Troubleshooting

Tip (Denoted in Bullets) Notes

ACC-SVP01B-EN bull BCI-I Integration Guide 15

BCI IntelliPak Rotary Switches and LEDs

24 Vac Measurement

General Information Checkout Procedure Measurement Expected Value

Checking the voltage that is powering the UC400 is often a necessary step when commissioning or troubleshooting Operational issues and LED operation may result in a need to measure the input power

When troubleshooting it is faster to take measurements while the load is in place If Step 1 indicates an out-of-specification voltage disconnect the UC400 and measure the AC voltage across the transformer These measurements can direct the technician towards the problem source

Step 1

Measure AC voltage with the UC400 connected Perform this measurement while the unit is under load

200 Vac le Vac le 300 Vac

Step 2

Measure AC voltage with the UC400 unconnected Perform this measurement while the unit is not under load

200 Vac le Vac le 300 Vac

16 ACC-SVP01B-EN bull BCI-I Integration Guide

BCI IntelliPak Rotary Switches and LEDs

Ground Measurements

General Information and Checkout Procedure Measurement Expected Value

Method 1AC voltage between shield conductors and device chassis ground- the voltage difference between BACnet MSTP device chassis ground connections should be close to zero If the voltage difference is greater that 40 Vac there will be marginal communication or intermittent communication problems If the voltage difference is greater that 70 Vac some devices will no longer communicate

Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

Vac le 20 V

Method 2AC voltage between earth ground and device chassis ground- the chassis ground of the UC400 needs to be connected to earth ground by some route

Note Do not assume that the building frame is a valid earth ground

Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

Vac le 40 V (Must comply with National Electrical Codetradeand local electrical codes)

ACC-SVP01B-EN bull BCI-I Integration Guide 17

BACnet Data Points and Configuration Property Definitions

BACnet Data Points and Configuration Property

Definitions

The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MSTP This section includes information about

bull BACnet protocol implementation conformance statement (PICS)

bull Object types descriptions and configuration (refer to Table 2 p 19)

bull BACnet protocol data link layers device address binding networking options and character sets

bull Object data points and configurations

BACnet Protocol Implementation Conformance Statement (PICS)

Standardized Device Profile (Annex L)

Interoperability Building Blocks (Annex K)

Profile Description Supported Profile

BACnet Advanced Application Controller (B-AAC)

BACnet Application Specific Controller (B-ASC)

BACnet Building Controller (B-BC)

BACnet Operator Workstation (B-OWS)

BACnet Smart Actuator (B-SA)

BACnet Smart Sensor (B-SS)

Data Sharing Description Supported BIBB

Data Sharing-COV-B (DS-COV-B)

Data Sharing-ReadProperty-A (DS-RP-A)

Data Sharing-ReadProperty-B (DS-RP-B)

Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)

Data Sharing-WriteProperty-A (DS-WP-A)

Data Sharing-WriteProperty-B (DS-WP-B)

Data Sharing-WritePropertyMultiple-B (DS-WPM-B)

Alarm and Event Management Description Supported BIBB

Alarm and Event-ACKI-B (AE-ACK-B)

Alarm and Event-Alarm Summary-B (AE-ASUM-B)

Alarm and Event-Enrollment Summary-B (AE-ESUM-B)

Alarm and Event-Information-B (AE-INFO-B)

Alarm and Event-Notification Internal-B (AE-N-I-B)

18 ACC-SVP01B-EN bull BCI-I Integration Guide

BACnet Data Points and Configuration Property Definitions

Segmentation Capability

Trending Description Supported BIBB

Trending-Automated Trend Retrieval-B (T-ATR-B)

Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

Device Management Description Supported BIBB

Device Management-Backup and Restore-B (DM-BR-B)

Device Management-Device Communication Control-B (DM-DCC-B)

Device Management-Dynamic Device Binding-A (DM-DDB-A)

Device Management-Dynamic Device Binding-B (DM-DDB-B)

Device Management-Dynamic Object Binding-B (DM-DOB-B)

Device Management-List Manipulation-B (DM-LM-B)

Device Management-Object Creation and Deletion-B (DM-OCD-B)

Device Management-Private Transfer-A (DM-PT-A)

Device Management-Private Transfer-B (DM-PT-B)

Device Management-Reinitialize Device-B (DM-RD-B)

Device Management-TimeSynchronization-B (DM-TS-B)

Segmentation Description Supported Segment

Segmented Requests Window Size 1

Segmented Responses Window Size 1

ACC-SVP01B-EN bull BCI-I Integration Guide 19

BACnet Data Points and Configuration Property Definitions

Object Types

Table 2 Descriptions and configurations

Object Type Required Properties Read Properties Written(a) Optional Properties Read

Ability to Create

Ability to Delete

Analog Input

bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

Yes Yes only user created objects

Analog Output

bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

Yes Yes only user created objects

Analog Value

bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

Yes Yes only user created objects

Binary Input

bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

Yes Yes only user created objects

20 ACC-SVP01B-EN bull BCI-I Integration Guide

BACnet Data Points and Configuration Property Definitions

Binary Output

bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

Yes Yes only user created objects

Binary Value

bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

Yes Yes only user created objects

Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

None None

Event Enrollment Object

bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

bull None Yes Yes only user created objects

Table 2 Descriptions and configurations (continued)

Object Type Required Properties Read Properties Written(a) Optional Properties Read

Ability to Create

Ability to Delete

ACC-SVP01B-EN bull BCI-I Integration Guide 21

BACnet Data Points and Configuration Property Definitions

Multistate Input

bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

Yes Yes only user created objects

Multistate Output

bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

Yes Yes only user created objects

Multistate Value

bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

Yes Yes only user created objects

Notification Class

bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

None Yes Yes only user created objects

Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

Yes Yes only user created objects

(a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

Table 2 Descriptions and configurations (continued)

Object Type Required Properties Read Properties Written(a) Optional Properties Read

Ability to Create

Ability to Delete

22 ACC-SVP01B-EN bull BCI-I Integration Guide

BACnet Data Points and Configuration Property Definitions

BACnet Protocol

Data Link Layer Options

Device Address Binding

Networking Options

Data Link Layer Description Supported Option

ANSIATA 8781 25 Mb ARCNET (Clause 8)

ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

BACnet IP (Annex J)

BACnet IP (Annex J) Foreign Device

ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

LonTalk (Clause 11) Medium

MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

MSTP Slave (Clause 9) Baud Rate(s)

Other

Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

Device Address Binding Supported

Static Device Binding Supported

Networking DescriptionsSupported

Option

Annex H BACnet Tunneling

BACnetIP Broadcast Management Device (BBMD)

Does the BBMD Support Registrations by Foreign Devices

Router

ACC-SVP01B-EN bull BCI-I Integration Guide 23

BACnet Data Points and Configuration Property Definitions

Character Sets

Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

Character Set Descriptions Supported

ANSI X34

IBMMicrosoft DBCS

ISO 10646 (UCS-4)

ISO 10646 (UCS2)

ISO 8859-1

JIS C 6226

24 ACC-SVP01B-EN bull BCI-I Integration Guide

Object Data Points and Diagnostic Data Points

Object Data Points and Diagnostic Data Points

For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

Table 3 Analog Output

Object Identifier Object Name Description Units Valid Range

Refresh Rate

(Sec)

Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

Percent (98) 0 to 100 NA

Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

Degrees-Fahrenheit (64) 500 to 900 NA

Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

Degrees-Fahrenheit (64) 400 to 900 NA

Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

Degrees-Fahrenheit (64) 400 to 1800 NA

Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

070 to 510 (Ipak II) NA

Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

003 to 030-002 to 030 (enhanced StatiTrac)

NA

Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

-028 to 050-067 to 067 (enhanced StatiTrac)

900

Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

00 to 79 (Ipak II) 900

Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

ACC-SVP01B-EN bull BCI-I Integration Guide 25

Object Data Points and Diagnostic Data Points

Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

Cooling temperature setpoint used for control in unoccupied mode

Degrees-Fahrenheit (64) 520 to 880 NA

Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

Heating temperature setpoint used for control in unoccupied mode

Degrees-Fahrenheit (64) 500 to 900 NA

Table 4 Analog Input

Object Identifier Object Name Description Units (Listed Are Defaults)

Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

Table 3 Analog Output (continued)

Object Identifier Object Name Description Units Valid Range

Refresh Rate

(Sec)

26 ACC-SVP01B-EN bull BCI-I Integration Guide

Object Data Points and Diagnostic Data Points

Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

Analog Input 54 Morning Warmup Air Temperature Setpoint Active

The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

Table 4 Analog Input (continued)

Object Identifier Object Name Description Units (Listed Are Defaults)

ACC-SVP01B-EN bull BCI-I Integration Guide 27

Object Data Points and Diagnostic Data Points

Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

Table 5 Analog Value

Object Identifier Object Name Description Units Valid Range

Analog Value 1 Filter Runtime Hours Setpoint

The setpoint value used by the filter run hours calculation

Hours (71) 0 to 10000

Table 4 Analog Input (continued)

Object Identifier Object Name Description Units (Listed Are Defaults)

28 ACC-SVP01B-EN bull BCI-I Integration Guide

Object Data Points and Diagnostic Data Points

Table 6 Multistate Output

BCI-I Object Identifier Object Name Description Object States

Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

1 = Flow2 = No Flow3 = Auto

Table 7 Multistate Input

BCI-I Object Identifier Object Name Description Object States

Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

Multi-State Input 9 Economizer Type General description of the equipment economizer system

1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

Multi-State Input 10 Condenser Type General description of the equipment condenser system

1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

ACC-SVP01B-EN bull BCI-I Integration Guide 29

Object Data Points and Diagnostic Data Points

Multi-State Input 15 Economizer Decision Method

Unit method to determine when the economizer system is enabled

1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

1 = Idle2 = On3 = Cancel

Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

1 = Off2 = On3 = Not Present

Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

1 = Off2 = On3 = Not Present

Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

1 = Off2 = On3 = Not Present

Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

1 = Off|2 = On3 = Not Present

Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

1 = Off2 = On3 = Not Present

Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

1 = Off2 = On3 = Not Present

Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

1 = Off2 = On3 = Not Present

Table 7 Multistate Input (continued)

BCI-I Object Identifier Object Name Description Object States

30 ACC-SVP01B-EN bull BCI-I Integration Guide

Object Data Points and Diagnostic Data Points

Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

1 = Off2 = On3 = Not Present

Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

1 = Off2 = On3 = Not Present

Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

1 = Off2 = On3 = Not Present

Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

1= Off2= On3= Not Present

Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

Multi-State Input 43 Outdoor Air Damper Status

Indicates the operating state of the outdoor damper

1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

1 = Disabled2 = Enabled3 = Not Present

Table 8 Binary Output

Object Identifier Object Name DescriptionRelinquish Default Object States

Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

Active = BAS Control

Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

Active = Heating Locked Out

Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

Active = Cooling Locked Out

Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

Active = Enabled

Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

Active = On

Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

Inactive Inactive = DisabledActive = Enabled

Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

Active = Reset

Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

Active = Reset

Table 7 Multistate Input (continued)

BCI-I Object Identifier Object Name Description Object States

ACC-SVP01B-EN bull BCI-I Integration Guide 31

Object Data Points and Diagnostic Data Points

Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

Active = Auto

Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

Active = Auto

Table 9 Binary Input

Object Identifier Object Name Description Object States

Binary Input 1 System Control Status Indicates the control system currently in command of the unit

Inactive = Standalone controlActive = BAS control

Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

Inactive = NormalActive = Locked Out

Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

Inactive = AutoActive = Open

Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

Inactive = InactiveActive = Active

Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

Inactive = DisabledActive = Enabled

Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

Inactive = DisabledActive = Enabled

Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

Inactive = InactiveActive = Active

Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

Inactive = No FlowActive = Flow

Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

Inactive = InactiveActive = Active

Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

Inactive = InactiveActive = Active

Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

Inactive = InactiveActive = Active

Binary Input 161 Evaporator Frost Protection Circuit 1 Status

The status of evaporator frost protection function for circuit 1

Inactive = InactiveActive = Active

Binary Input 162 Evaporator Frost Protection Circuit 2 Status

The status of evaporator frost protection function for circuit 2

Inactive = InactiveActive = Active

Binary Input 163 Evaporator Frost Protection Circuit 3 Status

The status of evaporator frost protection function for circuit 3

Inactive = InactiveActive = Active

Binary Input 164 Evaporator Frost Protection Circuit 4 Status

The status of evaporator frost protection function for circuit 4

Inactive = InactiveActive = Active

Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

Inactive = De-energizedActive = Energized

Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

Inactive = InactiveActive = Active

Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

Inactive = ClosedActive = Open

Table 10 Diagnostics Binary Input

Object Identifier(a) Object Name Description

Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

Binary Input 31 (use Object Identifier for RT or CSC)

Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

Binary Input 31 (use Object Identifier for FAU)

Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

Table 8 Binary Output

Object Identifier Object Name DescriptionRelinquish Default Object States

32 ACC-SVP01B-EN bull BCI-I Integration Guide

Object Data Points and Diagnostic Data Points

Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

Binary Input 58 (use Object Identifier for RT or CSC)

Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

Binary Input 58 (use Object Identifier for FAU)

Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

Table 10 Diagnostics Binary Input (continued)

Object Identifier(a) Object Name Description

ACC-SVP01B-EN bull BCI-I Integration Guide 33

Object Data Points and Diagnostic Data Points

Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

Binary Input 86 (use Object Identifier for RT I-pak II)

Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

Binary Input 121 (use Object Identifier for RT)

Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

Binary Input 121 (use Object Identifier for FAU)

Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

Table 10 Diagnostics Binary Input (continued)

Object Identifier(a) Object Name Description

34 ACC-SVP01B-EN bull BCI-I Integration Guide

Object Data Points and Diagnostic Data Points

Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

(a) Object States Inactive = normal and Active = foreign language specific

Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

Object Identifier(a) Object Name Description

Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

Analog Input 80 Cabinet Style Describes the cabinet style of the unit

Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

Multi-State Input 10 Condenser Type General description of the equipment condenser system

Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

Table 10 Diagnostics Binary Input (continued)

Object Identifier(a) Object Name Description

ACC-SVP01B-EN bull BCI-I Integration Guide 35

Object Data Points and Diagnostic Data Points

Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

Analog Input 81 Cool Type Describes the cooling type installed in the unit

Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

Object Identifier(a) Object Name Description

36 ACC-SVP01B-EN bull BCI-I Integration Guide

Object Data Points and Diagnostic Data Points

Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

Multi-State Input 9 Economizer Type General description of the equipment economizer system

Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

Multi-State Input 36 Final Filter Status Indicates the final filter media state

Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

Object Identifier(a) Object Name Description

ACC-SVP01B-EN bull BCI-I Integration Guide 37

Object Data Points and Diagnostic Data Points

Binary Output 16 Humidification Command Command the operating state of the humidification system

NC 3 HVAC-Advisory HVAC-Advisory

NC 1 HVAC-Critical HVAC-Critical

NC 4 HVAC-Information HVAC-Information

NC 2 HVAC-Service Required HVAC-Service Required

Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

Multi-State Input 34 Prefilter Status Indicates the prefilter media state

Analog Input 82 Preheat Type Describes the heating type installed in the unit

Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

Analog Input 83 Reheat Type Describes the reheat type installed in the unit

Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

Multi-State Input 42 Return Fan Status Indicates the state of the return fan

Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

Object Identifier(a) Object Name Description

38 ACC-SVP01B-EN bull BCI-I Integration Guide

Object Data Points and Diagnostic Data Points

Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

Analog Input 15 Space Temperature Active The space temperature currently used for unit control

Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

Binary Input 1 System Control Status Indicates the control system currently in command of the unit

Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

Binary Input 3 Unit Status Indicates the current state of the unit

Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

(a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

Object Identifier(a) Object Name Description

Table 12 Diagnostic Objects Sorted by Object Name

Object Identifier(a) Object Name ValueRange Description

BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

ACC-SVP01B-EN bull BCI-I Integration Guide 39

Object Data Points and Diagnostic Data Points

BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

Table 12 Diagnostic Objects Sorted by Object Name (continued)

Object Identifier(a) Object Name ValueRange Description

40 ACC-SVP01B-EN bull BCI-I Integration Guide

Object Data Points and Diagnostic Data Points

BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

Table 12 Diagnostic Objects Sorted by Object Name (continued)

Object Identifier(a) Object Name ValueRange Description

ACC-SVP01B-EN bull BCI-I Integration Guide 41

Object Data Points and Diagnostic Data Points

BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

BI 121 (use Object Identifier for RT)

Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

BI 58 (use Object Identifier for RT or CSC)

Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

BI 31 (use Object Identifier for RT CSC)

Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

BI 121 (use Object Identifier for FAU)

Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

B1 31 (use Object Identifier for FAU)

Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

Table 12 Diagnostic Objects Sorted by Object Name (continued)

Object Identifier(a) Object Name ValueRange Description

42 ACC-SVP01B-EN bull BCI-I Integration Guide

Object Data Points and Diagnostic Data Points

BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

1 = active Diagnostic Vel Press Sensor (Rear)

BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

Table 12 Diagnostic Objects Sorted by Object Name (continued)

Object Identifier(a) Object Name ValueRange Description

ACC-SVP01B-EN bull BCI-I Integration Guide 43

Object Data Points and Diagnostic Data Points

BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

BI 58 (use Object Identifier for FAU)

Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

(a) BI=Binary Input

Table 12 Diagnostic Objects Sorted by Object Name (continued)

Object Identifier(a) Object Name ValueRange Description

44 ACC-SVP01B-EN bull BCI-I Integration Guide

Additional Resources

Additional Resources

Use the following documents and links as additional resources

bull Product support online

bull wwwbacnetorg

bull wwwbacnetassociationorg

bull wwwashraeorg

bull Tracer TU Help online

bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

Note For further assistance contact your local Trane sales office

ACC-SVP01B-EN bull BCI-I Integration Guide 45

Glossary

A

ASHRAE

See American Society of Heating Refrigeration and Air-conditioning Engineers

American Society of Heating Refrigeration and Air-

conditioning Engineers

An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

BBACnettrade

See Building Automation Control network

BACnet interoperability building blocks

A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

BACnet object

An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

baud rate

The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

BIBB

See BACnet interoperability building blocks

Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

advocates BACnet protocol for use in system-level control devices

device

A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

Device ID

The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

Iinteroperability

The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

Pprotocol

A set of rules (language) that governs the exchange of data over a digital communications system

S

stand-alone operation

Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

wwwtranecom

For more information contact your local Trane office or e-mail us at comforttranecom

Literature Order Number ACC-SVP01B-EN

Date September 2009

Supersedes ACC-SVP01A-EN

Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

  • Table of Contents
  • Overview
  • Ordering Numbers
  • BACnet Protocol
  • BCI-I Configuration
    • Overview
    • Starting a Session of Tracer TU and Direct Connection
    • Reset to Factory Default
    • IP Units Configuration
    • BACnet Object Configuration
    • Change Baud Rate
    • Change Device ID
    • Stand-alone or BAS Operation
      • IntelliPak Control Configuration
      • BAS Unit Control
      • Periodic Update of BAS Values
      • BAS Communication Failure
        • InputOutput Commands and Calculations
          • System Control Command
          • Filter Timer Reset Command
          • Diagnostics Reset Command
          • Setpoint Calculations
          • Timestamp Configuration
              • BCI IntelliPak Rotary Switches and LEDs
                • Rotary Switches
                • LEDs Description Behavior and Troubleshooting
                • 24 Vac Measurement
                • Ground Measurements
                  • BACnet Data Points and Configuration Property Definitions
                    • BACnet Protocol Implementation Conformance Statement (PICS)
                      • Standardized Device Profile (Annex L)
                      • Interoperability Building Blocks (Annex K)
                      • Segmentation Capability
                      • Object Types
                        • BACnet Protocol
                          • Data Link Layer Options
                          • Device Address Binding
                          • Networking Options
                          • Character Sets
                              • Object Data Points and Diagnostic Data Points
                              • Additional Resources
                              • Glossary

    2 ACC-SVP01B-EN bull BCI0I Integration Guide

    Copyright

    copy 2009 Trane All rights reserved

    This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part without the written permission of Trane Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change

    Trademarks

    IntelliPak Tracer Trane and the Trane logo are trademarks of Trane in the United States and other countries All trademarks referenced in this document are the trademarks of their respective owners

    Table of Contents

    ACC-SVP01B-EN bull BCI-I Integration Guide 3

    Overview 4

    Ordering Numbers 4

    BACnet Protocol 4

    BCI-I Configuration 5

    Overview 5

    Starting a Session of Tracer TU and Direct Connection 5

    IP Units Configuration 6

    BACnet Object Configuration 7

    Change Baud Rate 7

    Change Device ID 7

    Stand-alone or BAS Operation 8IntelliPak Control Configuration 8BAS Unit Control 8Periodic Update of BAS Values 9BAS Communication Failure 9

    InputOutput Commands and Calculations 9System Control Command 9Filter Timer Reset Command 9Diagnostics Reset Command 10Setpoint Calculations 10Timestamp Configuration 11

    BCI IntelliPak Rotary Switches and LEDs 12

    Rotary Switches 12

    LEDs Description Behavior and Troubleshooting 13

    BACnet Data Points and Configuration Property Definitions 17

    BACnet Protocol Implementation Conformance Statement (PICS) 17Standardized Device Profile (Annex L) 17Interoperability Building Blocks (Annex K) 17Segmentation Capability 18Object Types 19

    BACnet Protocol 22Data Link Layer Options 22Device Address Binding 22Networking Options 22

    Object Data Points and Diagnostic Data Points 24

    Additional Resources 44

    Glossary 45

    4 ACC-SVP01B-EN bull BCI-I Integration Guide

    Overview

    The BACnet Communication Interface for IntelliPak (BCI-I) is comprised of a Tracertrade UC400 controller with interface software It is a non-programmable communications module that allows heating ventilation and air-conditioning (HVAC) equipment to communicate on a BACnet communications network

    This guide provides

    bull A list of ordering numbers

    bull A brief overview of the BACnettrade protocol

    bull BCI-I configuration information

    bull A explanation of the BCI-I device rotary switches and LEDs

    bull Data point configuration property definitions

    bull Tables listing object data points

    bull Additional resources

    bull A glossary of terms

    Note Users of this guide should have basic knowledge of BACnet protocol For more detailed information about this protocol visit the company web site listed under ldquoAdditional Resourcesrdquo p 44

    Ordering Numbers

    BACnet Protocol

    The Building Automation and Control Network (BACnet and ANSIASHRAE Standard 135-2004) protocol is a standard that allows building automation systems or components from different manufacturers to share information and control functions BACnet provides building owners the capability to connect various types of building control systems or subsystems together for a variety of reasons In addition multiple vendors can use this protocol to share information for monitoring and supervisory control between systems and devices in a multi-vendor interconnected system

    The BACnet protocol identifies standard objects (data points) called BACnet objects Each object has a defined list of properties that provide information about that object BACnet also defines a number of standard application services that are used to access data and manipulate these objects and provides a clientserver communication between devices For more information on BACnet protocol refer to ldquoAdditional Resourcesrdquo p 44

    BACnet Testing Laboratory (BTL) Certification

    The BCI-I supports the BACnet communication protocol and has been designed to meet the requirements of the application-specific control profile For more details refer to the BTL web site at wwwbacnetassociationorg

    Order Number Description

    X13651544-010 IntelliPak I for software and hardware

    C175218460010 IntelliPak I II and CSC for field-installed kit

    ACC-SVP01B-EN bull BCI-I Integration Guide 5

    BCI-I Configuration

    BCI-I Configuration

    This section will provide the following information when configuring the BCI-I

    bull Overview

    bull Starting a session of Tracer TU and direct connection

    bull Resetting to factory default

    bull Configuring IP units

    bull Configuring BACnet objects

    bull Changing baud rate and device ID

    bull Inputoutput and equipment functions

    Overview

    The BCI-I device is designed as a self-configuring controller to accommodate the many possible equipment configuration options available in the IntelliPak line of equipment This self-configuring device eliminates the need for the BAS technician having to create BACnet objects minimizes the risk of object configuration errors and allows the IntelliPak unit to be quickly installed in the BAS

    The self-configuration process only creates objects that are appropriate for the feature set of the specific IntelliPak unit the BCI-I is connected to Once this process is complete the device exits factory mode and enters the normal mode of operation At this point the self-configuration process will not start when power is applied to the device

    The set of objects listed in Table 3 p 24 through Table 10 p 31 are the super set of all possible objects supported by the IntelliPak line of equipment The BAS technician should query the device for the list of actual objects that have been created in the device

    Starting a Session of Tracer TU and Direct Connection

    Tracer TU is the service tool software that allows the technician to modify the operation of the device and to discover the BACnet objects present in the device To modify the device or discover objects the user must first connect to Tracer TU as follows

    WARNING Remove power from the HVAC equipment before opening electrical control panel

    1 Connect a USB cable directly between the laptop PC and the service port located on the front of the BCI-I device When connecting to the controller for the first time the Found New Hardware Wizard appears Follow the wizard instructions to install the USB hardware driver

    2 Click either the Tracer TU desktop icon or the Tracer TU program item in the Tracer TU group on the Start menu The Tracer TU splash screen appears briefly followed by the Connect dialog box

    3 Select the Direct Connection (Via USB cable) radio button if it is not already selected

    4 Click the Connect button and the Tracer TU main page will appear after successful connection

    Note The BCI-I may be powered via the USB cable or 24 Vac from the HVAC unit Concurrent connection of unit power and the USB cable will not harm the BCI-I device

    For more detailed information about direct connection to Tracer TU refer to the Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

    6 ACC-SVP01B-EN bull BCI-I Integration Guide

    BCI-I Configuration

    Reset to Factory Default

    Factory default mode is the only mode the technician can use to set the units of measure for the device or to scan the IntelliPak unit to create BACnet objects The process of putting the device in factory default mode must be run prior to executing units of measure configuration or the object self-configuration process

    WARNING Remove power from the HVAC equipment before

    opening electrical control panel

    To reset the controller to factory defaultunconfigured state

    1 Power down the unit The IMC buss must not be active during reset

    2 Establish the connection between Tracer TU and the device Follow the procedure ldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

    3 From the Utilities menu select Controller and then Controller Settings The Controller Settings page appears

    4 On the controller settings page there is a gray bar at the bottom with SaveCancel buttons Move the cursor near the left edge of the bar keeping the cursor inside the bar Click on this area and a Clear Controller button will appear in the upper right portion of the page

    5 Click the Clear Controller button and a pop-up window will appear asking for confirmation to reset the device Click Yes

    6 After a few seconds a pop-up will appear confirming that the controller has been reset and indicating that the controller will be rebooted Click OK

    After the controller boots up it will be in factory default state The units of measure is SI (metric) the MSTP baud rate is 76800 and there will be no BACnet objects present in the controller

    The controller must be in this state prior to changing the units of measure or self-configuring the device If using inch-pound units of measure proceed to the next section ldquoIP Units Configuration otherwise proceed to ldquoBACnet Object Configuration

    IP Units Configuration

    The BCI-I supports both inch-pound and SI (metric) units of measure The factory default units of measure is SI The device allows only a change of units for all objects as a whole Mixed units of measure is not allowed If the controller is not in factory default state follow the previous procedure ldquoReset to Factory Defaultrdquo p 6

    To change the units of measure in the device

    1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

    2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Controller Units frame

    3 In the Device Units box of the frame select IP units of measure radio button and then click Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Select OK

    4 Exit Tracer TU and cycle power to the controller by disconnecting the USB plug and then reconnecting the plug After the controller boots up it will be in factory default state the units of measure is IP the MSTP baud rate is 76800 and there will be no BACnet objects present in the controller

    ACC-SVP01B-EN bull BCI-I Integration Guide 7

    BCI-I Configuration

    BACnet Object Configuration

    Configuring BACnet objects is a self-configuring process If the controller is not in factory default state follow the previous procedure ldquoReset to Factory Defaultrdquo p 6

    1 Remove the USB cable plug from the device

    2 Apply power to the HVAC equipment After the device boots up the self-configuration process will begin No further user action is required

    Note Do not remove power while the device is in self-configuration mode This typically takes 2 to 4 minutes to complete Once complete the device enters normal operating mode

    Change Baud Rate

    The BCI-I device supports four baud rates 9600 19200 38400 and 76800 baud The default baud rate is 76800 baud The baud rate can be modified with Tracer TU

    WARNING Remove power from the HVAC equipment before opening electrical control panel

    To change baud rate

    1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

    2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Protocol frame

    3 Click on the drop down arrow for the Baud Rate list and select the desired baud rate

    4 Click Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Click OK

    5 Exit Tracer TU and disconnect the USB cable plug

    6 Apply power to the HVAC equipment

    Change Device ID

    By default the BCI-I device sets its device ID to the same value as the one defined by the rotary switches (MSTP MAC address) on the front of the device Refer to the section ldquoRotary Switchesrdquo p 12 For simple networks this is an easy method to guarantee unique device IDs across the link

    The device also supports the full range of device ID values as specified by the BACnet Standard Systems that require a more complex device ID convention are supported with Tracer TU which has the ability to set the device ID via software configuration

    WARNING Remove power from the HVAC equipment before opening electrical control panel

    The process for soft setting the device ID is as follows

    1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

    2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Protocol frame

    3 In the device ID box select the check box next to Use Software Device ID to enable the functionality The swipe-and-type box becomes available

    4 Type in the desired device ID

    8 ACC-SVP01B-EN bull BCI-I Integration Guide

    BCI-I Configuration

    5 Click the Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Click OK

    6 Exit Tracer TU and disconnect the USB service plug

    7 Apply power to the HVAC equipment

    Stand-alone or BAS Operation

    The control system on HVAC equipment has the ability to operate the unit as a stand-alone system or as part of a building automation system The BCI-I (either factory or field installed) by default is configured for stand-alone operation This configuration enables the HVAC equipment to operate prior to the commissioning of the unit into the BAS

    IntelliPak Control Configuration

    The IntelliPak control system must be configured at the human interface (HI) to support unit control from the BAS The technician should setverify the following configuration properties as illustrated below The technician should also verify that the BAS Module Comm Failure diagnostic is not present

    BAS Unit Control

    The BCI-I provides a method for a BAS to control the operation of HVAC equipment This method consists of BACnet objects that the BAS can access to control and monitor the status of equipment There are two sets of objects

    bull Output objects used by the BAS to provide command setpoint and sensor information to the IntelliPak unit

    bull Input objects provide IntelliPak status information to the BAS See tables 3 to 11 for the list of objects supported

    The system allows the BAS technician to define the amount of control that the BAS system will apply to the unit This is done by configuring the state of the Out of Service property of the output objects If the property is set to True the equipment will use a corresponding local value for control If the property is set to False the local value is ignored and the BAS-supplied value is used for control The BAS value is provided to the IntelliPak by writing to the present value property of the corresponding output object The factory default value for the Out of Service property of these objects is True

    1 Configuration Menu

    2 Setup Menu

    3 Diagnostics Menu

    Software Revision NumberBAS Communications BACnet 1801

    Configuration - Model Num Digit 34BAS Communication Module Installed

    Unit Control BASNETWORK

    Active Diagnostic - - Auto ResetNone

    Human Interface Representation

    ACC-SVP01B-EN bull BCI-I Integration Guide 9

    BCI-I Configuration

    Periodic Update of BAS Values

    The BCI-I device requires the BAS system to provide a periodic update to the sensor values This is required to protect against a loss of communication between the BAS and the BCI-I By BACnet definition the present value of the object will maintain the last value written to it regardless of the amount of time that has elapsed since the last write If communication is lost for several minutes or longer the present value of BAS-supplied sensor objects may no longer represent the current state of environmental conditions This may result in decreased occupant comfort and damage to building systems

    BAS Communication Failure

    The BCI-I is designed to minimize communication failure mode It does this by monitoring the length of time that has elapsed since the last write to the present value of the sensor object If the length of time exceeds a predefined limit the BCI-I will place the object into the fault state and revert to a unit-supplied sensor value for control At power up the sensor objects are set to a fault state and they will remain in this state until a write is detected The minimum periodic refresh rate for the objects is defined in Table 3 p 24 The following list is a set of sensor values that can be supplied by the BAS

    bull Space Static Pressure BAS

    bull Space Air Temperature BAS

    bull Discharge Air Temperature BAS

    bull Duct Static Air Pressure BAS

    bull Outdoor Air Temperature BAS

    bull Outdoor Air Humidity BAS

    bull Outdoor Airflow BAS

    bull Space CO2 Concentration BAS

    bull Space Humidity BAS

    InputOutput Commands and Calculations

    This section will provide the following information about certain inputs and outputs that perform unique control commands and calculations

    bull System control command

    bull Filter timer and diagnostic reset commands

    bull Setpoint calculations

    System Control Command

    Binary Output Object 1 has a special importance in the system The object allows the BAS to command the unit to run in a local or BAS control mode When the present value property of the object is set to Local Control the IntelliPak unit will enter local control and ignore BAS supplied values In this mode the unit will use local sensor and setpoint values When the object present value property is set to BAS Control the IntelliPak unit will use the values supplied by the BAS system for unit control

    Filter Timer Reset Command

    The BCI-I uses the Filter Runtime Hours object (AI 6) to generate a diagnostic when its present value is greater than the Filter Runtime Hours Setpoint (AV 1) present value The procedure for resetting the timer is as follows

    10 ACC-SVP01B-EN bull BCI-I Integration Guide

    BCI-I Configuration

    The BAS will change the state of the Filter Timer Reset Command object (BO 13) to the active state Upon the change to active state the BCI-I will set the present value of the Filter Runtime Hours object to zero and then set the Reset Command object back to the inactive state

    Diagnostics Reset Command

    The IntelliPak control system monitors the operation of the HVAC equipment If an abnormal condition is detected a diagnostic message is displayed on the human interface of the equipment control panel In addition the set of internal diagnostics is mapped to the set of BACnet binary input objects as listed in Table 9 p 31 The corresponding BI object will change state from inactive to active when the diagnostic is detected The object has been configured to send a BACnet event message to external BACnet devices as defined by the protocol

    The BAS has the ability to reset internal diagnostics by controlling the state of the Diagnostic Reset Command object (BO 14) The procedure for resetting diagnostics is as follows

    The BAS will change the state of the Diagnostic Reset to the active state Upon the change to active state the IntelliPak control system will reset all internal diagnostics and set the state of all of the diagnostic objects to inactive Upon completion of this action the BCI-I will set the present value of the Diagnostic Reset Command object back to the inactive state

    Setpoint Calculations

    The equipment has the ability to perform two basic control functions

    bull Space air temperature control

    bull Discharge air temperature control

    When the unit is configured for discharge air control it controls the temperature of the air leaving the unit to the discharge air temperature setpoint

    When the unit is configured for space air temperature control it controls the air temperature of the space that contains the space air temperature sensor This value may be provided by wiring the sensor to the unit or via a sensor value provided by the BAS

    The drawing below describes how the various temperature setpoints are calculated for space temperature control When the unit is in an occupied mode the active space temperature setpoint is calculated based on the space temperature setpoint and the two setpoint offset values In unoccupied mode the unoccupied heating and cooling setpoints are used as the active setpoint

    ACC-SVP01B-EN bull BCI-I Integration Guide 11

    BCI-I Configuration

    Timestamp Configuration

    The BCI-C device has a software-derived clock that maintains the time and date The device requires the current time to enable it to record a timestamp when an event or a change in state is detected by a BACnet object However in the event of a power loss the device does not maintain this time and date information At powerup the device time and date will default to 1200 pm Jan 1 1970 To minimize the possibility that the unit timestamp is not representing the actual time the BAS should be setup to periodically synchronize the device time clock with the BAS clock using the BACnet TimeSynchronization service

    12 ACC-SVP01B-EN bull BCI-I Integration Guide

    BCI IntelliPak Rotary Switches and LEDs

    BCI IntelliPak Rotary Switches and LEDs

    This section provides information about the BCI-I rotary switches and LED displays

    Rotary Switches

    There are three rotary switches on the front of the BCI-I device that are used to define a three-digit address when the BCI-I is installed on a BACnet communications network The three-digit address setting is the BACnet MAC address

    Note All devices are MSTP masters with valid MAC addresses of 001 to 127 for BACnet

    Figure 1 Setting rotary switches

    ADDRESS0 1

    23

    456

    78

    9

    x1

    0 1

    23

    456

    78

    9

    x10

    0 1

    23

    456

    78

    9

    x100

    Before

    After

    0

    5

    1

    3

    6

    29

    487

    Example of before and after setting addresses

    Use a 18 inch flathead screwdriver to set rotary switches

    Important Each device on the BACnetMSTP link must have a unique rotary switch setting otherwise communication problems will occur

    ACC-SVP01B-EN bull BCI-I Integration Guide 13

    BCI IntelliPak Rotary Switches and LEDs

    LEDs Description Behavior and Troubleshooting

    There are 15 LEDs on the front of the BCI-I unit However LEDs BO1 through BO9 are not used for the BCI-I controller Figure 2 shows the locations of each LED The following table provides a description of each LED activity an indication or troubleshooting tips for each and any notes

    Figure 2 LED locations

    SERVICE

    IMCLINK

    RX

    TX

    Marquee LED

    Table 1 LED Activities and Troubleshooting Tips

    LED Name ActivitiesIndication or Troubleshooting

    Tip (Denoted in Bullets) Notes

    Marquee LED

    Shows solid green when the unit is powered and no problems exist

    Indicates normal operation

    Shows solid red when the unit is powered but represents low power or a

    malfunction

    bull If low power could be under voltage or the microprocessor has malfunction Follow the troubleshoot procedure ldquo24 Vac Measurementrdquo p 15 to measure for the expected value range

    bull If malfunction unpower and then repower unit to bring the device back up to normal operation

    Shows blinking red when an a BACnet object is in a fault condition

    Alarm when an alarm is triggered for example when a point goes into fault condition because of point failure or there is an indication of a custom alarm in TGP2

    Shows blinking green when the device does not detect the IMC buss

    bull Verify that the IPC wiring harness is connected to the IMC link terminals

    bull Verify the polarity of the IPC wiring harness at the unit terminals

    LED not lit

    Indicates power is OFF or there is a malfunction

    bull OFF or malfunction cycle the power

    14 ACC-SVP01B-EN bull BCI-I Integration Guide

    BCI IntelliPak Rotary Switches and LEDs

    Link and IMC

    TX blinks greenBlinks at the data transfer rate when the unit transfers data to other devices on the link

    TX LED Regardless of connectivity or not this LED will constantly blink as it continually looks for devices to communicate to

    LED not litDetermine if for example a Tracer SC or BACnet device is trying to talk to the controller or if it is capable of talking to the controller Also determine if the communication status shows down all of the time

    Refer to ldquoGround Measurementsrdquo p 16 for a check-out procedure

    RX blinks yellow

    Blinks at the data transfer rate when the unit receives data from other devices on the link

    bull ON solid yellow indicates there is reverse polarity

    LED not lit

    Indicates that the controller is not detecting communication

    bull Not lit cycle the power to reestablish communication

    Service

    Shows solid greenIndicates someone is pressing this LED or the controller is not operating normally

    Press and hold during power up to place controller into boot code or press and hold for a count of approximately 10 seconds to clear the Device ID

    What is Boot Code When the UC400 is placed into boot code the system will not run any applications such as trending scheduling and TGP2 runtime

    Blinks green

    Indicates controllers is not accessing application software

    bull Restore using TU service tool

    LED not lit Indicates controller is operating normally

    Binary 01 to Binary 09 Not Used

    Table 1 LED Activities and Troubleshooting Tips

    LED Name ActivitiesIndication or Troubleshooting

    Tip (Denoted in Bullets) Notes

    ACC-SVP01B-EN bull BCI-I Integration Guide 15

    BCI IntelliPak Rotary Switches and LEDs

    24 Vac Measurement

    General Information Checkout Procedure Measurement Expected Value

    Checking the voltage that is powering the UC400 is often a necessary step when commissioning or troubleshooting Operational issues and LED operation may result in a need to measure the input power

    When troubleshooting it is faster to take measurements while the load is in place If Step 1 indicates an out-of-specification voltage disconnect the UC400 and measure the AC voltage across the transformer These measurements can direct the technician towards the problem source

    Step 1

    Measure AC voltage with the UC400 connected Perform this measurement while the unit is under load

    200 Vac le Vac le 300 Vac

    Step 2

    Measure AC voltage with the UC400 unconnected Perform this measurement while the unit is not under load

    200 Vac le Vac le 300 Vac

    16 ACC-SVP01B-EN bull BCI-I Integration Guide

    BCI IntelliPak Rotary Switches and LEDs

    Ground Measurements

    General Information and Checkout Procedure Measurement Expected Value

    Method 1AC voltage between shield conductors and device chassis ground- the voltage difference between BACnet MSTP device chassis ground connections should be close to zero If the voltage difference is greater that 40 Vac there will be marginal communication or intermittent communication problems If the voltage difference is greater that 70 Vac some devices will no longer communicate

    Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

    Vac le 20 V

    Method 2AC voltage between earth ground and device chassis ground- the chassis ground of the UC400 needs to be connected to earth ground by some route

    Note Do not assume that the building frame is a valid earth ground

    Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

    Vac le 40 V (Must comply with National Electrical Codetradeand local electrical codes)

    ACC-SVP01B-EN bull BCI-I Integration Guide 17

    BACnet Data Points and Configuration Property Definitions

    BACnet Data Points and Configuration Property

    Definitions

    The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MSTP This section includes information about

    bull BACnet protocol implementation conformance statement (PICS)

    bull Object types descriptions and configuration (refer to Table 2 p 19)

    bull BACnet protocol data link layers device address binding networking options and character sets

    bull Object data points and configurations

    BACnet Protocol Implementation Conformance Statement (PICS)

    Standardized Device Profile (Annex L)

    Interoperability Building Blocks (Annex K)

    Profile Description Supported Profile

    BACnet Advanced Application Controller (B-AAC)

    BACnet Application Specific Controller (B-ASC)

    BACnet Building Controller (B-BC)

    BACnet Operator Workstation (B-OWS)

    BACnet Smart Actuator (B-SA)

    BACnet Smart Sensor (B-SS)

    Data Sharing Description Supported BIBB

    Data Sharing-COV-B (DS-COV-B)

    Data Sharing-ReadProperty-A (DS-RP-A)

    Data Sharing-ReadProperty-B (DS-RP-B)

    Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)

    Data Sharing-WriteProperty-A (DS-WP-A)

    Data Sharing-WriteProperty-B (DS-WP-B)

    Data Sharing-WritePropertyMultiple-B (DS-WPM-B)

    Alarm and Event Management Description Supported BIBB

    Alarm and Event-ACKI-B (AE-ACK-B)

    Alarm and Event-Alarm Summary-B (AE-ASUM-B)

    Alarm and Event-Enrollment Summary-B (AE-ESUM-B)

    Alarm and Event-Information-B (AE-INFO-B)

    Alarm and Event-Notification Internal-B (AE-N-I-B)

    18 ACC-SVP01B-EN bull BCI-I Integration Guide

    BACnet Data Points and Configuration Property Definitions

    Segmentation Capability

    Trending Description Supported BIBB

    Trending-Automated Trend Retrieval-B (T-ATR-B)

    Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

    Device Management Description Supported BIBB

    Device Management-Backup and Restore-B (DM-BR-B)

    Device Management-Device Communication Control-B (DM-DCC-B)

    Device Management-Dynamic Device Binding-A (DM-DDB-A)

    Device Management-Dynamic Device Binding-B (DM-DDB-B)

    Device Management-Dynamic Object Binding-B (DM-DOB-B)

    Device Management-List Manipulation-B (DM-LM-B)

    Device Management-Object Creation and Deletion-B (DM-OCD-B)

    Device Management-Private Transfer-A (DM-PT-A)

    Device Management-Private Transfer-B (DM-PT-B)

    Device Management-Reinitialize Device-B (DM-RD-B)

    Device Management-TimeSynchronization-B (DM-TS-B)

    Segmentation Description Supported Segment

    Segmented Requests Window Size 1

    Segmented Responses Window Size 1

    ACC-SVP01B-EN bull BCI-I Integration Guide 19

    BACnet Data Points and Configuration Property Definitions

    Object Types

    Table 2 Descriptions and configurations

    Object Type Required Properties Read Properties Written(a) Optional Properties Read

    Ability to Create

    Ability to Delete

    Analog Input

    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

    bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

    bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

    Yes Yes only user created objects

    Analog Output

    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

    bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

    bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

    Yes Yes only user created objects

    Analog Value

    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

    bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

    bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

    Yes Yes only user created objects

    Binary Input

    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

    bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

    bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

    Yes Yes only user created objects

    20 ACC-SVP01B-EN bull BCI-I Integration Guide

    BACnet Data Points and Configuration Property Definitions

    Binary Output

    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

    bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

    bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

    Yes Yes only user created objects

    Binary Value

    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

    bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

    bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

    Yes Yes only user created objects

    Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

    bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

    bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

    None None

    Event Enrollment Object

    bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

    bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

    bull None Yes Yes only user created objects

    Table 2 Descriptions and configurations (continued)

    Object Type Required Properties Read Properties Written(a) Optional Properties Read

    Ability to Create

    Ability to Delete

    ACC-SVP01B-EN bull BCI-I Integration Guide 21

    BACnet Data Points and Configuration Property Definitions

    Multistate Input

    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

    bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

    bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

    Yes Yes only user created objects

    Multistate Output

    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

    bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

    bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

    Yes Yes only user created objects

    Multistate Value

    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

    bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

    bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

    Yes Yes only user created objects

    Notification Class

    bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

    bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

    None Yes Yes only user created objects

    Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

    bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

    bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

    Yes Yes only user created objects

    (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

    Table 2 Descriptions and configurations (continued)

    Object Type Required Properties Read Properties Written(a) Optional Properties Read

    Ability to Create

    Ability to Delete

    22 ACC-SVP01B-EN bull BCI-I Integration Guide

    BACnet Data Points and Configuration Property Definitions

    BACnet Protocol

    Data Link Layer Options

    Device Address Binding

    Networking Options

    Data Link Layer Description Supported Option

    ANSIATA 8781 25 Mb ARCNET (Clause 8)

    ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

    BACnet IP (Annex J)

    BACnet IP (Annex J) Foreign Device

    ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

    LonTalk (Clause 11) Medium

    MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

    MSTP Slave (Clause 9) Baud Rate(s)

    Other

    Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

    Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

    Device Address Binding Supported

    Static Device Binding Supported

    Networking DescriptionsSupported

    Option

    Annex H BACnet Tunneling

    BACnetIP Broadcast Management Device (BBMD)

    Does the BBMD Support Registrations by Foreign Devices

    Router

    ACC-SVP01B-EN bull BCI-I Integration Guide 23

    BACnet Data Points and Configuration Property Definitions

    Character Sets

    Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

    Character Set Descriptions Supported

    ANSI X34

    IBMMicrosoft DBCS

    ISO 10646 (UCS-4)

    ISO 10646 (UCS2)

    ISO 8859-1

    JIS C 6226

    24 ACC-SVP01B-EN bull BCI-I Integration Guide

    Object Data Points and Diagnostic Data Points

    Object Data Points and Diagnostic Data Points

    For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

    Table 3 Analog Output

    Object Identifier Object Name Description Units Valid Range

    Refresh Rate

    (Sec)

    Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

    Percent (98) 0 to 100 NA

    Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

    Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

    Degrees-Fahrenheit (64) 500 to 900 NA

    Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

    BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

    Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

    Degrees-Fahrenheit (64) 400 to 900 NA

    Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

    Degrees-Fahrenheit (64) 400 to 1800 NA

    Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

    070 to 510 (Ipak II) NA

    Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

    003 to 030-002 to 030 (enhanced StatiTrac)

    NA

    Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

    -028 to 050-067 to 067 (enhanced StatiTrac)

    900

    Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

    Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

    Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

    00 to 79 (Ipak II) 900

    Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

    Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

    Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

    Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

    Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

    Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

    Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

    Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

    Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

    Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

    ACC-SVP01B-EN bull BCI-I Integration Guide 25

    Object Data Points and Diagnostic Data Points

    Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

    Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

    Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

    Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

    Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

    Cooling temperature setpoint used for control in unoccupied mode

    Degrees-Fahrenheit (64) 520 to 880 NA

    Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

    Heating temperature setpoint used for control in unoccupied mode

    Degrees-Fahrenheit (64) 500 to 900 NA

    Table 4 Analog Input

    Object Identifier Object Name Description Units (Listed Are Defaults)

    Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

    Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

    Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

    Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

    Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

    Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

    Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

    Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

    Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

    Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

    Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

    Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

    Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

    Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

    Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

    Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

    Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

    Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

    Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

    Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

    Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

    Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

    Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

    Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

    Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

    Table 3 Analog Output (continued)

    Object Identifier Object Name Description Units Valid Range

    Refresh Rate

    (Sec)

    26 ACC-SVP01B-EN bull BCI-I Integration Guide

    Object Data Points and Diagnostic Data Points

    Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

    Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

    Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

    Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

    Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

    Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

    Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

    Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

    Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

    Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

    Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

    Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

    Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

    Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

    Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

    Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

    Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

    Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

    Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

    Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

    Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

    Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

    Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

    Analog Input 54 Morning Warmup Air Temperature Setpoint Active

    The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

    Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

    The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

    Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

    Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

    Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

    Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

    Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

    Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

    Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

    Table 4 Analog Input (continued)

    Object Identifier Object Name Description Units (Listed Are Defaults)

    ACC-SVP01B-EN bull BCI-I Integration Guide 27

    Object Data Points and Diagnostic Data Points

    Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

    Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

    Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

    Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

    The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

    Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

    Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

    Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

    Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

    Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

    Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

    Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

    Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

    Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

    Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

    Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

    Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

    Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

    Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

    Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

    Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

    Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

    Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

    Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

    Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

    Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

    Table 5 Analog Value

    Object Identifier Object Name Description Units Valid Range

    Analog Value 1 Filter Runtime Hours Setpoint

    The setpoint value used by the filter run hours calculation

    Hours (71) 0 to 10000

    Table 4 Analog Input (continued)

    Object Identifier Object Name Description Units (Listed Are Defaults)

    28 ACC-SVP01B-EN bull BCI-I Integration Guide

    Object Data Points and Diagnostic Data Points

    Table 6 Multistate Output

    BCI-I Object Identifier Object Name Description Object States

    Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

    Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

    1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

    Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

    Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

    1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

    Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

    1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

    Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

    1 = Flow2 = No Flow3 = Auto

    Table 7 Multistate Input

    BCI-I Object Identifier Object Name Description Object States

    Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

    1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

    Multi-State Input 9 Economizer Type General description of the equipment economizer system

    1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

    Multi-State Input 10 Condenser Type General description of the equipment condenser system

    1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

    Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

    1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

    ACC-SVP01B-EN bull BCI-I Integration Guide 29

    Object Data Points and Diagnostic Data Points

    Multi-State Input 15 Economizer Decision Method

    Unit method to determine when the economizer system is enabled

    1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

    Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

    Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

    Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

    1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

    Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

    1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

    Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

    1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

    Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

    1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

    Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

    1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

    Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

    1 = Idle2 = On3 = Cancel

    Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

    1 = Off2 = On3 = Not Present

    Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

    1 = Off2 = On3 = Not Present

    Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

    1 = Off2 = On3 = Not Present

    Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

    1 = Off|2 = On3 = Not Present

    Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

    1 = Off2 = On3 = Not Present

    Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

    1 = Off2 = On3 = Not Present

    Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

    1 = Off2 = On3 = Not Present

    Table 7 Multistate Input (continued)

    BCI-I Object Identifier Object Name Description Object States

    30 ACC-SVP01B-EN bull BCI-I Integration Guide

    Object Data Points and Diagnostic Data Points

    Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

    1 = Off2 = On3 = Not Present

    Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

    1 = Off2 = On3 = Not Present

    Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

    Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

    Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

    Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

    Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

    1 = Off2 = On3 = Not Present

    Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

    1= Off2= On3= Not Present

    Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

    Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

    Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

    Multi-State Input 43 Outdoor Air Damper Status

    Indicates the operating state of the outdoor damper

    1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

    Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

    1 = Disabled2 = Enabled3 = Not Present

    Table 8 Binary Output

    Object Identifier Object Name DescriptionRelinquish Default Object States

    Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

    Active = BAS Control

    Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

    Active = Heating Locked Out

    Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

    Active = Cooling Locked Out

    Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

    Active = Enabled

    Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

    Active = On

    Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

    Inactive Inactive = DisabledActive = Enabled

    Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

    Active = Reset

    Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

    Active = Reset

    Table 7 Multistate Input (continued)

    BCI-I Object Identifier Object Name Description Object States

    ACC-SVP01B-EN bull BCI-I Integration Guide 31

    Object Data Points and Diagnostic Data Points

    Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

    Active = Auto

    Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

    Active = Auto

    Table 9 Binary Input

    Object Identifier Object Name Description Object States

    Binary Input 1 System Control Status Indicates the control system currently in command of the unit

    Inactive = Standalone controlActive = BAS control

    Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

    Inactive = NormalActive = Locked Out

    Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

    Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

    Inactive = AutoActive = Open

    Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

    Inactive = InactiveActive = Active

    Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

    Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

    Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

    Inactive = DisabledActive = Enabled

    Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

    Inactive = DisabledActive = Enabled

    Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

    Inactive = InactiveActive = Active

    Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

    Inactive = No FlowActive = Flow

    Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

    Inactive = InactiveActive = Active

    Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

    Inactive = InactiveActive = Active

    Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

    Inactive = InactiveActive = Active

    Binary Input 161 Evaporator Frost Protection Circuit 1 Status

    The status of evaporator frost protection function for circuit 1

    Inactive = InactiveActive = Active

    Binary Input 162 Evaporator Frost Protection Circuit 2 Status

    The status of evaporator frost protection function for circuit 2

    Inactive = InactiveActive = Active

    Binary Input 163 Evaporator Frost Protection Circuit 3 Status

    The status of evaporator frost protection function for circuit 3

    Inactive = InactiveActive = Active

    Binary Input 164 Evaporator Frost Protection Circuit 4 Status

    The status of evaporator frost protection function for circuit 4

    Inactive = InactiveActive = Active

    Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

    Inactive = De-energizedActive = Energized

    Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

    Inactive = InactiveActive = Active

    Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

    Inactive = ClosedActive = Open

    Table 10 Diagnostics Binary Input

    Object Identifier(a) Object Name Description

    Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

    Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

    Binary Input 31 (use Object Identifier for RT or CSC)

    Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

    Binary Input 31 (use Object Identifier for FAU)

    Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

    Table 8 Binary Output

    Object Identifier Object Name DescriptionRelinquish Default Object States

    32 ACC-SVP01B-EN bull BCI-I Integration Guide

    Object Data Points and Diagnostic Data Points

    Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

    Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

    Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

    Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

    Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

    Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

    Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

    Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

    Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

    Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

    Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

    Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

    Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

    Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

    Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

    Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

    Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

    Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

    Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

    Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

    Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

    Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

    Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

    Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

    Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

    Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

    Binary Input 58 (use Object Identifier for RT or CSC)

    Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

    Binary Input 58 (use Object Identifier for FAU)

    Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

    Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

    Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

    Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

    Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

    Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

    Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

    Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

    Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

    Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

    Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

    Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

    Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

    Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

    Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

    Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

    Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

    Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

    Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

    Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

    Table 10 Diagnostics Binary Input (continued)

    Object Identifier(a) Object Name Description

    ACC-SVP01B-EN bull BCI-I Integration Guide 33

    Object Data Points and Diagnostic Data Points

    Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

    Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

    Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

    Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

    Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

    Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

    Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

    Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

    Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

    Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

    Binary Input 86 (use Object Identifier for RT I-pak II)

    Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

    Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

    Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

    Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

    Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

    Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

    Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

    Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

    Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

    Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

    Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

    Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

    Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

    Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

    Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

    Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

    Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

    Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

    Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

    Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

    Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

    Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

    Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

    Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

    Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

    Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

    Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

    Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

    Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

    Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

    Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

    Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

    Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

    Binary Input 121 (use Object Identifier for RT)

    Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

    Binary Input 121 (use Object Identifier for FAU)

    Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

    Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

    Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

    Table 10 Diagnostics Binary Input (continued)

    Object Identifier(a) Object Name Description

    34 ACC-SVP01B-EN bull BCI-I Integration Guide

    Object Data Points and Diagnostic Data Points

    Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

    Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

    Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

    Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

    Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

    Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

    Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

    Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

    Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

    Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

    Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

    Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

    Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

    Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

    Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

    Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

    Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

    Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

    Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

    Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

    Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

    Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

    Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

    Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

    Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

    Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

    (a) Object States Inactive = normal and Active = foreign language specific

    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

    Object Identifier(a) Object Name Description

    Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

    Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

    Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

    Analog Input 80 Cabinet Style Describes the cabinet style of the unit

    Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

    Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

    Multi-State Input 10 Condenser Type General description of the equipment condenser system

    Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

    Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

    Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

    Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

    Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

    Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

    Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

    Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

    Table 10 Diagnostics Binary Input (continued)

    Object Identifier(a) Object Name Description

    ACC-SVP01B-EN bull BCI-I Integration Guide 35

    Object Data Points and Diagnostic Data Points

    Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

    Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

    Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

    Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

    Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

    Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

    Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

    Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

    Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

    Analog Input 81 Cool Type Describes the cooling type installed in the unit

    Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

    Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

    Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

    Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

    Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

    Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

    Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

    Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

    Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

    Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

    Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

    Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

    Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

    Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

    Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

    Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

    Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

    Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

    Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

    Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

    Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

    Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

    Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

    Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

    Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

    Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

    Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

    Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

    Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

    Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

    Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

    Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

    Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

    Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

    Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

    Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

    Object Identifier(a) Object Name Description

    36 ACC-SVP01B-EN bull BCI-I Integration Guide

    Object Data Points and Diagnostic Data Points

    Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

    Multi-State Input 9 Economizer Type General description of the equipment economizer system

    Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

    Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

    Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

    Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

    Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

    Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

    Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

    Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

    Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

    Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

    Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

    Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

    Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

    Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

    Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

    Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

    Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

    Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

    Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

    Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

    Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

    Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

    Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

    Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

    Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

    Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

    Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

    Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

    Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

    Multi-State Input 36 Final Filter Status Indicates the final filter media state

    Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

    Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

    Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

    Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

    Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

    Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

    Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

    Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

    Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

    Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

    Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

    Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

    Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

    Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

    Object Identifier(a) Object Name Description

    ACC-SVP01B-EN bull BCI-I Integration Guide 37

    Object Data Points and Diagnostic Data Points

    Binary Output 16 Humidification Command Command the operating state of the humidification system

    NC 3 HVAC-Advisory HVAC-Advisory

    NC 1 HVAC-Critical HVAC-Critical

    NC 4 HVAC-Information HVAC-Information

    NC 2 HVAC-Service Required HVAC-Service Required

    Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

    Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

    Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

    Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

    Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

    Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

    Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

    Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

    Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

    Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

    Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

    Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

    Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

    Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

    Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

    Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

    Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

    Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

    Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

    Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

    Multi-State Input 34 Prefilter Status Indicates the prefilter media state

    Analog Input 82 Preheat Type Describes the heating type installed in the unit

    Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

    Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

    Analog Input 83 Reheat Type Describes the reheat type installed in the unit

    Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

    Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

    Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

    Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

    Multi-State Input 42 Return Fan Status Indicates the state of the return fan

    Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

    Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

    Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

    Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

    Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

    Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

    Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

    Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

    Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

    Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

    Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

    Object Identifier(a) Object Name Description

    38 ACC-SVP01B-EN bull BCI-I Integration Guide

    Object Data Points and Diagnostic Data Points

    Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

    Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

    Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

    Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

    Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

    Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

    Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

    Analog Input 15 Space Temperature Active The space temperature currently used for unit control

    Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

    Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

    Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

    Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

    Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

    Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

    Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

    Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

    Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

    Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

    Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

    Binary Input 1 System Control Status Indicates the control system currently in command of the unit

    Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

    Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

    Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

    Binary Input 3 Unit Status Indicates the current state of the unit

    Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

    Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

    Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

    Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

    Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

    Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

    Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

    (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

    Object Identifier(a) Object Name Description

    Table 12 Diagnostic Objects Sorted by Object Name

    Object Identifier(a) Object Name ValueRange Description

    BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

    BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

    ACC-SVP01B-EN bull BCI-I Integration Guide 39

    Object Data Points and Diagnostic Data Points

    BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

    BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

    BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

    BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

    BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

    BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

    BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

    BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

    BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

    BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

    BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

    BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

    BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

    BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

    BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

    BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

    BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

    BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

    BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

    BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

    BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

    BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

    BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

    BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

    BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

    BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

    BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

    BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

    BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

    Table 12 Diagnostic Objects Sorted by Object Name (continued)

    Object Identifier(a) Object Name ValueRange Description

    40 ACC-SVP01B-EN bull BCI-I Integration Guide

    Object Data Points and Diagnostic Data Points

    BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

    BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

    BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

    BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

    BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

    BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

    BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

    BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

    BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

    BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

    BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

    BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

    BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

    BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

    BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

    BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

    BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

    BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

    BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

    BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

    BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

    BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

    BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

    BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

    BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

    BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

    BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

    BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

    BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

    Table 12 Diagnostic Objects Sorted by Object Name (continued)

    Object Identifier(a) Object Name ValueRange Description

    ACC-SVP01B-EN bull BCI-I Integration Guide 41

    Object Data Points and Diagnostic Data Points

    BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

    BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

    BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

    BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

    BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

    BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

    BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

    BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

    BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

    BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

    BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

    BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

    BI 121 (use Object Identifier for RT)

    Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

    BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

    BI 58 (use Object Identifier for RT or CSC)

    Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

    BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

    BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

    BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

    BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

    BI 31 (use Object Identifier for RT CSC)

    Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

    BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

    BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

    BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

    BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

    BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

    BI 121 (use Object Identifier for FAU)

    Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

    B1 31 (use Object Identifier for FAU)

    Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

    BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

    BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

    Table 12 Diagnostic Objects Sorted by Object Name (continued)

    Object Identifier(a) Object Name ValueRange Description

    42 ACC-SVP01B-EN bull BCI-I Integration Guide

    Object Data Points and Diagnostic Data Points

    BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

    BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

    BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

    BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

    BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

    BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

    BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

    BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

    BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

    BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

    BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

    BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

    BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

    BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

    BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

    BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

    BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

    BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

    BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

    BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

    BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

    BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

    BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

    1 = active Diagnostic Vel Press Sensor (Rear)

    BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

    Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

    BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

    BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

    BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

    BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

    BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

    Table 12 Diagnostic Objects Sorted by Object Name (continued)

    Object Identifier(a) Object Name ValueRange Description

    ACC-SVP01B-EN bull BCI-I Integration Guide 43

    Object Data Points and Diagnostic Data Points

    BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

    BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

    BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

    BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

    BI 58 (use Object Identifier for FAU)

    Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

    (a) BI=Binary Input

    Table 12 Diagnostic Objects Sorted by Object Name (continued)

    Object Identifier(a) Object Name ValueRange Description

    44 ACC-SVP01B-EN bull BCI-I Integration Guide

    Additional Resources

    Additional Resources

    Use the following documents and links as additional resources

    bull Product support online

    bull wwwbacnetorg

    bull wwwbacnetassociationorg

    bull wwwashraeorg

    bull Tracer TU Help online

    bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

    bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

    Note For further assistance contact your local Trane sales office

    ACC-SVP01B-EN bull BCI-I Integration Guide 45

    Glossary

    A

    ASHRAE

    See American Society of Heating Refrigeration and Air-conditioning Engineers

    American Society of Heating Refrigeration and Air-

    conditioning Engineers

    An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

    BBACnettrade

    See Building Automation Control network

    BACnet interoperability building blocks

    A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

    BACnet object

    An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

    baud rate

    The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

    BIBB

    See BACnet interoperability building blocks

    Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

    advocates BACnet protocol for use in system-level control devices

    device

    A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

    Device ID

    The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

    Iinteroperability

    The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

    Pprotocol

    A set of rules (language) that governs the exchange of data over a digital communications system

    S

    stand-alone operation

    Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

    wwwtranecom

    For more information contact your local Trane office or e-mail us at comforttranecom

    Literature Order Number ACC-SVP01B-EN

    Date September 2009

    Supersedes ACC-SVP01A-EN

    Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

    • Table of Contents
    • Overview
    • Ordering Numbers
    • BACnet Protocol
    • BCI-I Configuration
      • Overview
      • Starting a Session of Tracer TU and Direct Connection
      • Reset to Factory Default
      • IP Units Configuration
      • BACnet Object Configuration
      • Change Baud Rate
      • Change Device ID
      • Stand-alone or BAS Operation
        • IntelliPak Control Configuration
        • BAS Unit Control
        • Periodic Update of BAS Values
        • BAS Communication Failure
          • InputOutput Commands and Calculations
            • System Control Command
            • Filter Timer Reset Command
            • Diagnostics Reset Command
            • Setpoint Calculations
            • Timestamp Configuration
                • BCI IntelliPak Rotary Switches and LEDs
                  • Rotary Switches
                  • LEDs Description Behavior and Troubleshooting
                  • 24 Vac Measurement
                  • Ground Measurements
                    • BACnet Data Points and Configuration Property Definitions
                      • BACnet Protocol Implementation Conformance Statement (PICS)
                        • Standardized Device Profile (Annex L)
                        • Interoperability Building Blocks (Annex K)
                        • Segmentation Capability
                        • Object Types
                          • BACnet Protocol
                            • Data Link Layer Options
                            • Device Address Binding
                            • Networking Options
                            • Character Sets
                                • Object Data Points and Diagnostic Data Points
                                • Additional Resources
                                • Glossary

      Table of Contents

      ACC-SVP01B-EN bull BCI-I Integration Guide 3

      Overview 4

      Ordering Numbers 4

      BACnet Protocol 4

      BCI-I Configuration 5

      Overview 5

      Starting a Session of Tracer TU and Direct Connection 5

      IP Units Configuration 6

      BACnet Object Configuration 7

      Change Baud Rate 7

      Change Device ID 7

      Stand-alone or BAS Operation 8IntelliPak Control Configuration 8BAS Unit Control 8Periodic Update of BAS Values 9BAS Communication Failure 9

      InputOutput Commands and Calculations 9System Control Command 9Filter Timer Reset Command 9Diagnostics Reset Command 10Setpoint Calculations 10Timestamp Configuration 11

      BCI IntelliPak Rotary Switches and LEDs 12

      Rotary Switches 12

      LEDs Description Behavior and Troubleshooting 13

      BACnet Data Points and Configuration Property Definitions 17

      BACnet Protocol Implementation Conformance Statement (PICS) 17Standardized Device Profile (Annex L) 17Interoperability Building Blocks (Annex K) 17Segmentation Capability 18Object Types 19

      BACnet Protocol 22Data Link Layer Options 22Device Address Binding 22Networking Options 22

      Object Data Points and Diagnostic Data Points 24

      Additional Resources 44

      Glossary 45

      4 ACC-SVP01B-EN bull BCI-I Integration Guide

      Overview

      The BACnet Communication Interface for IntelliPak (BCI-I) is comprised of a Tracertrade UC400 controller with interface software It is a non-programmable communications module that allows heating ventilation and air-conditioning (HVAC) equipment to communicate on a BACnet communications network

      This guide provides

      bull A list of ordering numbers

      bull A brief overview of the BACnettrade protocol

      bull BCI-I configuration information

      bull A explanation of the BCI-I device rotary switches and LEDs

      bull Data point configuration property definitions

      bull Tables listing object data points

      bull Additional resources

      bull A glossary of terms

      Note Users of this guide should have basic knowledge of BACnet protocol For more detailed information about this protocol visit the company web site listed under ldquoAdditional Resourcesrdquo p 44

      Ordering Numbers

      BACnet Protocol

      The Building Automation and Control Network (BACnet and ANSIASHRAE Standard 135-2004) protocol is a standard that allows building automation systems or components from different manufacturers to share information and control functions BACnet provides building owners the capability to connect various types of building control systems or subsystems together for a variety of reasons In addition multiple vendors can use this protocol to share information for monitoring and supervisory control between systems and devices in a multi-vendor interconnected system

      The BACnet protocol identifies standard objects (data points) called BACnet objects Each object has a defined list of properties that provide information about that object BACnet also defines a number of standard application services that are used to access data and manipulate these objects and provides a clientserver communication between devices For more information on BACnet protocol refer to ldquoAdditional Resourcesrdquo p 44

      BACnet Testing Laboratory (BTL) Certification

      The BCI-I supports the BACnet communication protocol and has been designed to meet the requirements of the application-specific control profile For more details refer to the BTL web site at wwwbacnetassociationorg

      Order Number Description

      X13651544-010 IntelliPak I for software and hardware

      C175218460010 IntelliPak I II and CSC for field-installed kit

      ACC-SVP01B-EN bull BCI-I Integration Guide 5

      BCI-I Configuration

      BCI-I Configuration

      This section will provide the following information when configuring the BCI-I

      bull Overview

      bull Starting a session of Tracer TU and direct connection

      bull Resetting to factory default

      bull Configuring IP units

      bull Configuring BACnet objects

      bull Changing baud rate and device ID

      bull Inputoutput and equipment functions

      Overview

      The BCI-I device is designed as a self-configuring controller to accommodate the many possible equipment configuration options available in the IntelliPak line of equipment This self-configuring device eliminates the need for the BAS technician having to create BACnet objects minimizes the risk of object configuration errors and allows the IntelliPak unit to be quickly installed in the BAS

      The self-configuration process only creates objects that are appropriate for the feature set of the specific IntelliPak unit the BCI-I is connected to Once this process is complete the device exits factory mode and enters the normal mode of operation At this point the self-configuration process will not start when power is applied to the device

      The set of objects listed in Table 3 p 24 through Table 10 p 31 are the super set of all possible objects supported by the IntelliPak line of equipment The BAS technician should query the device for the list of actual objects that have been created in the device

      Starting a Session of Tracer TU and Direct Connection

      Tracer TU is the service tool software that allows the technician to modify the operation of the device and to discover the BACnet objects present in the device To modify the device or discover objects the user must first connect to Tracer TU as follows

      WARNING Remove power from the HVAC equipment before opening electrical control panel

      1 Connect a USB cable directly between the laptop PC and the service port located on the front of the BCI-I device When connecting to the controller for the first time the Found New Hardware Wizard appears Follow the wizard instructions to install the USB hardware driver

      2 Click either the Tracer TU desktop icon or the Tracer TU program item in the Tracer TU group on the Start menu The Tracer TU splash screen appears briefly followed by the Connect dialog box

      3 Select the Direct Connection (Via USB cable) radio button if it is not already selected

      4 Click the Connect button and the Tracer TU main page will appear after successful connection

      Note The BCI-I may be powered via the USB cable or 24 Vac from the HVAC unit Concurrent connection of unit power and the USB cable will not harm the BCI-I device

      For more detailed information about direct connection to Tracer TU refer to the Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

      6 ACC-SVP01B-EN bull BCI-I Integration Guide

      BCI-I Configuration

      Reset to Factory Default

      Factory default mode is the only mode the technician can use to set the units of measure for the device or to scan the IntelliPak unit to create BACnet objects The process of putting the device in factory default mode must be run prior to executing units of measure configuration or the object self-configuration process

      WARNING Remove power from the HVAC equipment before

      opening electrical control panel

      To reset the controller to factory defaultunconfigured state

      1 Power down the unit The IMC buss must not be active during reset

      2 Establish the connection between Tracer TU and the device Follow the procedure ldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

      3 From the Utilities menu select Controller and then Controller Settings The Controller Settings page appears

      4 On the controller settings page there is a gray bar at the bottom with SaveCancel buttons Move the cursor near the left edge of the bar keeping the cursor inside the bar Click on this area and a Clear Controller button will appear in the upper right portion of the page

      5 Click the Clear Controller button and a pop-up window will appear asking for confirmation to reset the device Click Yes

      6 After a few seconds a pop-up will appear confirming that the controller has been reset and indicating that the controller will be rebooted Click OK

      After the controller boots up it will be in factory default state The units of measure is SI (metric) the MSTP baud rate is 76800 and there will be no BACnet objects present in the controller

      The controller must be in this state prior to changing the units of measure or self-configuring the device If using inch-pound units of measure proceed to the next section ldquoIP Units Configuration otherwise proceed to ldquoBACnet Object Configuration

      IP Units Configuration

      The BCI-I supports both inch-pound and SI (metric) units of measure The factory default units of measure is SI The device allows only a change of units for all objects as a whole Mixed units of measure is not allowed If the controller is not in factory default state follow the previous procedure ldquoReset to Factory Defaultrdquo p 6

      To change the units of measure in the device

      1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

      2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Controller Units frame

      3 In the Device Units box of the frame select IP units of measure radio button and then click Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Select OK

      4 Exit Tracer TU and cycle power to the controller by disconnecting the USB plug and then reconnecting the plug After the controller boots up it will be in factory default state the units of measure is IP the MSTP baud rate is 76800 and there will be no BACnet objects present in the controller

      ACC-SVP01B-EN bull BCI-I Integration Guide 7

      BCI-I Configuration

      BACnet Object Configuration

      Configuring BACnet objects is a self-configuring process If the controller is not in factory default state follow the previous procedure ldquoReset to Factory Defaultrdquo p 6

      1 Remove the USB cable plug from the device

      2 Apply power to the HVAC equipment After the device boots up the self-configuration process will begin No further user action is required

      Note Do not remove power while the device is in self-configuration mode This typically takes 2 to 4 minutes to complete Once complete the device enters normal operating mode

      Change Baud Rate

      The BCI-I device supports four baud rates 9600 19200 38400 and 76800 baud The default baud rate is 76800 baud The baud rate can be modified with Tracer TU

      WARNING Remove power from the HVAC equipment before opening electrical control panel

      To change baud rate

      1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

      2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Protocol frame

      3 Click on the drop down arrow for the Baud Rate list and select the desired baud rate

      4 Click Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Click OK

      5 Exit Tracer TU and disconnect the USB cable plug

      6 Apply power to the HVAC equipment

      Change Device ID

      By default the BCI-I device sets its device ID to the same value as the one defined by the rotary switches (MSTP MAC address) on the front of the device Refer to the section ldquoRotary Switchesrdquo p 12 For simple networks this is an easy method to guarantee unique device IDs across the link

      The device also supports the full range of device ID values as specified by the BACnet Standard Systems that require a more complex device ID convention are supported with Tracer TU which has the ability to set the device ID via software configuration

      WARNING Remove power from the HVAC equipment before opening electrical control panel

      The process for soft setting the device ID is as follows

      1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

      2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Protocol frame

      3 In the device ID box select the check box next to Use Software Device ID to enable the functionality The swipe-and-type box becomes available

      4 Type in the desired device ID

      8 ACC-SVP01B-EN bull BCI-I Integration Guide

      BCI-I Configuration

      5 Click the Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Click OK

      6 Exit Tracer TU and disconnect the USB service plug

      7 Apply power to the HVAC equipment

      Stand-alone or BAS Operation

      The control system on HVAC equipment has the ability to operate the unit as a stand-alone system or as part of a building automation system The BCI-I (either factory or field installed) by default is configured for stand-alone operation This configuration enables the HVAC equipment to operate prior to the commissioning of the unit into the BAS

      IntelliPak Control Configuration

      The IntelliPak control system must be configured at the human interface (HI) to support unit control from the BAS The technician should setverify the following configuration properties as illustrated below The technician should also verify that the BAS Module Comm Failure diagnostic is not present

      BAS Unit Control

      The BCI-I provides a method for a BAS to control the operation of HVAC equipment This method consists of BACnet objects that the BAS can access to control and monitor the status of equipment There are two sets of objects

      bull Output objects used by the BAS to provide command setpoint and sensor information to the IntelliPak unit

      bull Input objects provide IntelliPak status information to the BAS See tables 3 to 11 for the list of objects supported

      The system allows the BAS technician to define the amount of control that the BAS system will apply to the unit This is done by configuring the state of the Out of Service property of the output objects If the property is set to True the equipment will use a corresponding local value for control If the property is set to False the local value is ignored and the BAS-supplied value is used for control The BAS value is provided to the IntelliPak by writing to the present value property of the corresponding output object The factory default value for the Out of Service property of these objects is True

      1 Configuration Menu

      2 Setup Menu

      3 Diagnostics Menu

      Software Revision NumberBAS Communications BACnet 1801

      Configuration - Model Num Digit 34BAS Communication Module Installed

      Unit Control BASNETWORK

      Active Diagnostic - - Auto ResetNone

      Human Interface Representation

      ACC-SVP01B-EN bull BCI-I Integration Guide 9

      BCI-I Configuration

      Periodic Update of BAS Values

      The BCI-I device requires the BAS system to provide a periodic update to the sensor values This is required to protect against a loss of communication between the BAS and the BCI-I By BACnet definition the present value of the object will maintain the last value written to it regardless of the amount of time that has elapsed since the last write If communication is lost for several minutes or longer the present value of BAS-supplied sensor objects may no longer represent the current state of environmental conditions This may result in decreased occupant comfort and damage to building systems

      BAS Communication Failure

      The BCI-I is designed to minimize communication failure mode It does this by monitoring the length of time that has elapsed since the last write to the present value of the sensor object If the length of time exceeds a predefined limit the BCI-I will place the object into the fault state and revert to a unit-supplied sensor value for control At power up the sensor objects are set to a fault state and they will remain in this state until a write is detected The minimum periodic refresh rate for the objects is defined in Table 3 p 24 The following list is a set of sensor values that can be supplied by the BAS

      bull Space Static Pressure BAS

      bull Space Air Temperature BAS

      bull Discharge Air Temperature BAS

      bull Duct Static Air Pressure BAS

      bull Outdoor Air Temperature BAS

      bull Outdoor Air Humidity BAS

      bull Outdoor Airflow BAS

      bull Space CO2 Concentration BAS

      bull Space Humidity BAS

      InputOutput Commands and Calculations

      This section will provide the following information about certain inputs and outputs that perform unique control commands and calculations

      bull System control command

      bull Filter timer and diagnostic reset commands

      bull Setpoint calculations

      System Control Command

      Binary Output Object 1 has a special importance in the system The object allows the BAS to command the unit to run in a local or BAS control mode When the present value property of the object is set to Local Control the IntelliPak unit will enter local control and ignore BAS supplied values In this mode the unit will use local sensor and setpoint values When the object present value property is set to BAS Control the IntelliPak unit will use the values supplied by the BAS system for unit control

      Filter Timer Reset Command

      The BCI-I uses the Filter Runtime Hours object (AI 6) to generate a diagnostic when its present value is greater than the Filter Runtime Hours Setpoint (AV 1) present value The procedure for resetting the timer is as follows

      10 ACC-SVP01B-EN bull BCI-I Integration Guide

      BCI-I Configuration

      The BAS will change the state of the Filter Timer Reset Command object (BO 13) to the active state Upon the change to active state the BCI-I will set the present value of the Filter Runtime Hours object to zero and then set the Reset Command object back to the inactive state

      Diagnostics Reset Command

      The IntelliPak control system monitors the operation of the HVAC equipment If an abnormal condition is detected a diagnostic message is displayed on the human interface of the equipment control panel In addition the set of internal diagnostics is mapped to the set of BACnet binary input objects as listed in Table 9 p 31 The corresponding BI object will change state from inactive to active when the diagnostic is detected The object has been configured to send a BACnet event message to external BACnet devices as defined by the protocol

      The BAS has the ability to reset internal diagnostics by controlling the state of the Diagnostic Reset Command object (BO 14) The procedure for resetting diagnostics is as follows

      The BAS will change the state of the Diagnostic Reset to the active state Upon the change to active state the IntelliPak control system will reset all internal diagnostics and set the state of all of the diagnostic objects to inactive Upon completion of this action the BCI-I will set the present value of the Diagnostic Reset Command object back to the inactive state

      Setpoint Calculations

      The equipment has the ability to perform two basic control functions

      bull Space air temperature control

      bull Discharge air temperature control

      When the unit is configured for discharge air control it controls the temperature of the air leaving the unit to the discharge air temperature setpoint

      When the unit is configured for space air temperature control it controls the air temperature of the space that contains the space air temperature sensor This value may be provided by wiring the sensor to the unit or via a sensor value provided by the BAS

      The drawing below describes how the various temperature setpoints are calculated for space temperature control When the unit is in an occupied mode the active space temperature setpoint is calculated based on the space temperature setpoint and the two setpoint offset values In unoccupied mode the unoccupied heating and cooling setpoints are used as the active setpoint

      ACC-SVP01B-EN bull BCI-I Integration Guide 11

      BCI-I Configuration

      Timestamp Configuration

      The BCI-C device has a software-derived clock that maintains the time and date The device requires the current time to enable it to record a timestamp when an event or a change in state is detected by a BACnet object However in the event of a power loss the device does not maintain this time and date information At powerup the device time and date will default to 1200 pm Jan 1 1970 To minimize the possibility that the unit timestamp is not representing the actual time the BAS should be setup to periodically synchronize the device time clock with the BAS clock using the BACnet TimeSynchronization service

      12 ACC-SVP01B-EN bull BCI-I Integration Guide

      BCI IntelliPak Rotary Switches and LEDs

      BCI IntelliPak Rotary Switches and LEDs

      This section provides information about the BCI-I rotary switches and LED displays

      Rotary Switches

      There are three rotary switches on the front of the BCI-I device that are used to define a three-digit address when the BCI-I is installed on a BACnet communications network The three-digit address setting is the BACnet MAC address

      Note All devices are MSTP masters with valid MAC addresses of 001 to 127 for BACnet

      Figure 1 Setting rotary switches

      ADDRESS0 1

      23

      456

      78

      9

      x1

      0 1

      23

      456

      78

      9

      x10

      0 1

      23

      456

      78

      9

      x100

      Before

      After

      0

      5

      1

      3

      6

      29

      487

      Example of before and after setting addresses

      Use a 18 inch flathead screwdriver to set rotary switches

      Important Each device on the BACnetMSTP link must have a unique rotary switch setting otherwise communication problems will occur

      ACC-SVP01B-EN bull BCI-I Integration Guide 13

      BCI IntelliPak Rotary Switches and LEDs

      LEDs Description Behavior and Troubleshooting

      There are 15 LEDs on the front of the BCI-I unit However LEDs BO1 through BO9 are not used for the BCI-I controller Figure 2 shows the locations of each LED The following table provides a description of each LED activity an indication or troubleshooting tips for each and any notes

      Figure 2 LED locations

      SERVICE

      IMCLINK

      RX

      TX

      Marquee LED

      Table 1 LED Activities and Troubleshooting Tips

      LED Name ActivitiesIndication or Troubleshooting

      Tip (Denoted in Bullets) Notes

      Marquee LED

      Shows solid green when the unit is powered and no problems exist

      Indicates normal operation

      Shows solid red when the unit is powered but represents low power or a

      malfunction

      bull If low power could be under voltage or the microprocessor has malfunction Follow the troubleshoot procedure ldquo24 Vac Measurementrdquo p 15 to measure for the expected value range

      bull If malfunction unpower and then repower unit to bring the device back up to normal operation

      Shows blinking red when an a BACnet object is in a fault condition

      Alarm when an alarm is triggered for example when a point goes into fault condition because of point failure or there is an indication of a custom alarm in TGP2

      Shows blinking green when the device does not detect the IMC buss

      bull Verify that the IPC wiring harness is connected to the IMC link terminals

      bull Verify the polarity of the IPC wiring harness at the unit terminals

      LED not lit

      Indicates power is OFF or there is a malfunction

      bull OFF or malfunction cycle the power

      14 ACC-SVP01B-EN bull BCI-I Integration Guide

      BCI IntelliPak Rotary Switches and LEDs

      Link and IMC

      TX blinks greenBlinks at the data transfer rate when the unit transfers data to other devices on the link

      TX LED Regardless of connectivity or not this LED will constantly blink as it continually looks for devices to communicate to

      LED not litDetermine if for example a Tracer SC or BACnet device is trying to talk to the controller or if it is capable of talking to the controller Also determine if the communication status shows down all of the time

      Refer to ldquoGround Measurementsrdquo p 16 for a check-out procedure

      RX blinks yellow

      Blinks at the data transfer rate when the unit receives data from other devices on the link

      bull ON solid yellow indicates there is reverse polarity

      LED not lit

      Indicates that the controller is not detecting communication

      bull Not lit cycle the power to reestablish communication

      Service

      Shows solid greenIndicates someone is pressing this LED or the controller is not operating normally

      Press and hold during power up to place controller into boot code or press and hold for a count of approximately 10 seconds to clear the Device ID

      What is Boot Code When the UC400 is placed into boot code the system will not run any applications such as trending scheduling and TGP2 runtime

      Blinks green

      Indicates controllers is not accessing application software

      bull Restore using TU service tool

      LED not lit Indicates controller is operating normally

      Binary 01 to Binary 09 Not Used

      Table 1 LED Activities and Troubleshooting Tips

      LED Name ActivitiesIndication or Troubleshooting

      Tip (Denoted in Bullets) Notes

      ACC-SVP01B-EN bull BCI-I Integration Guide 15

      BCI IntelliPak Rotary Switches and LEDs

      24 Vac Measurement

      General Information Checkout Procedure Measurement Expected Value

      Checking the voltage that is powering the UC400 is often a necessary step when commissioning or troubleshooting Operational issues and LED operation may result in a need to measure the input power

      When troubleshooting it is faster to take measurements while the load is in place If Step 1 indicates an out-of-specification voltage disconnect the UC400 and measure the AC voltage across the transformer These measurements can direct the technician towards the problem source

      Step 1

      Measure AC voltage with the UC400 connected Perform this measurement while the unit is under load

      200 Vac le Vac le 300 Vac

      Step 2

      Measure AC voltage with the UC400 unconnected Perform this measurement while the unit is not under load

      200 Vac le Vac le 300 Vac

      16 ACC-SVP01B-EN bull BCI-I Integration Guide

      BCI IntelliPak Rotary Switches and LEDs

      Ground Measurements

      General Information and Checkout Procedure Measurement Expected Value

      Method 1AC voltage between shield conductors and device chassis ground- the voltage difference between BACnet MSTP device chassis ground connections should be close to zero If the voltage difference is greater that 40 Vac there will be marginal communication or intermittent communication problems If the voltage difference is greater that 70 Vac some devices will no longer communicate

      Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

      Vac le 20 V

      Method 2AC voltage between earth ground and device chassis ground- the chassis ground of the UC400 needs to be connected to earth ground by some route

      Note Do not assume that the building frame is a valid earth ground

      Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

      Vac le 40 V (Must comply with National Electrical Codetradeand local electrical codes)

      ACC-SVP01B-EN bull BCI-I Integration Guide 17

      BACnet Data Points and Configuration Property Definitions

      BACnet Data Points and Configuration Property

      Definitions

      The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MSTP This section includes information about

      bull BACnet protocol implementation conformance statement (PICS)

      bull Object types descriptions and configuration (refer to Table 2 p 19)

      bull BACnet protocol data link layers device address binding networking options and character sets

      bull Object data points and configurations

      BACnet Protocol Implementation Conformance Statement (PICS)

      Standardized Device Profile (Annex L)

      Interoperability Building Blocks (Annex K)

      Profile Description Supported Profile

      BACnet Advanced Application Controller (B-AAC)

      BACnet Application Specific Controller (B-ASC)

      BACnet Building Controller (B-BC)

      BACnet Operator Workstation (B-OWS)

      BACnet Smart Actuator (B-SA)

      BACnet Smart Sensor (B-SS)

      Data Sharing Description Supported BIBB

      Data Sharing-COV-B (DS-COV-B)

      Data Sharing-ReadProperty-A (DS-RP-A)

      Data Sharing-ReadProperty-B (DS-RP-B)

      Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)

      Data Sharing-WriteProperty-A (DS-WP-A)

      Data Sharing-WriteProperty-B (DS-WP-B)

      Data Sharing-WritePropertyMultiple-B (DS-WPM-B)

      Alarm and Event Management Description Supported BIBB

      Alarm and Event-ACKI-B (AE-ACK-B)

      Alarm and Event-Alarm Summary-B (AE-ASUM-B)

      Alarm and Event-Enrollment Summary-B (AE-ESUM-B)

      Alarm and Event-Information-B (AE-INFO-B)

      Alarm and Event-Notification Internal-B (AE-N-I-B)

      18 ACC-SVP01B-EN bull BCI-I Integration Guide

      BACnet Data Points and Configuration Property Definitions

      Segmentation Capability

      Trending Description Supported BIBB

      Trending-Automated Trend Retrieval-B (T-ATR-B)

      Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

      Device Management Description Supported BIBB

      Device Management-Backup and Restore-B (DM-BR-B)

      Device Management-Device Communication Control-B (DM-DCC-B)

      Device Management-Dynamic Device Binding-A (DM-DDB-A)

      Device Management-Dynamic Device Binding-B (DM-DDB-B)

      Device Management-Dynamic Object Binding-B (DM-DOB-B)

      Device Management-List Manipulation-B (DM-LM-B)

      Device Management-Object Creation and Deletion-B (DM-OCD-B)

      Device Management-Private Transfer-A (DM-PT-A)

      Device Management-Private Transfer-B (DM-PT-B)

      Device Management-Reinitialize Device-B (DM-RD-B)

      Device Management-TimeSynchronization-B (DM-TS-B)

      Segmentation Description Supported Segment

      Segmented Requests Window Size 1

      Segmented Responses Window Size 1

      ACC-SVP01B-EN bull BCI-I Integration Guide 19

      BACnet Data Points and Configuration Property Definitions

      Object Types

      Table 2 Descriptions and configurations

      Object Type Required Properties Read Properties Written(a) Optional Properties Read

      Ability to Create

      Ability to Delete

      Analog Input

      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

      bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

      bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

      Yes Yes only user created objects

      Analog Output

      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

      bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

      bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

      Yes Yes only user created objects

      Analog Value

      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

      bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

      bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

      Yes Yes only user created objects

      Binary Input

      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

      bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

      bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

      Yes Yes only user created objects

      20 ACC-SVP01B-EN bull BCI-I Integration Guide

      BACnet Data Points and Configuration Property Definitions

      Binary Output

      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

      bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

      bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

      Yes Yes only user created objects

      Binary Value

      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

      bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

      bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

      Yes Yes only user created objects

      Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

      bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

      bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

      None None

      Event Enrollment Object

      bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

      bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

      bull None Yes Yes only user created objects

      Table 2 Descriptions and configurations (continued)

      Object Type Required Properties Read Properties Written(a) Optional Properties Read

      Ability to Create

      Ability to Delete

      ACC-SVP01B-EN bull BCI-I Integration Guide 21

      BACnet Data Points and Configuration Property Definitions

      Multistate Input

      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

      bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

      bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

      Yes Yes only user created objects

      Multistate Output

      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

      bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

      bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

      Yes Yes only user created objects

      Multistate Value

      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

      bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

      bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

      Yes Yes only user created objects

      Notification Class

      bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

      bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

      None Yes Yes only user created objects

      Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

      bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

      bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

      Yes Yes only user created objects

      (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

      Table 2 Descriptions and configurations (continued)

      Object Type Required Properties Read Properties Written(a) Optional Properties Read

      Ability to Create

      Ability to Delete

      22 ACC-SVP01B-EN bull BCI-I Integration Guide

      BACnet Data Points and Configuration Property Definitions

      BACnet Protocol

      Data Link Layer Options

      Device Address Binding

      Networking Options

      Data Link Layer Description Supported Option

      ANSIATA 8781 25 Mb ARCNET (Clause 8)

      ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

      BACnet IP (Annex J)

      BACnet IP (Annex J) Foreign Device

      ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

      LonTalk (Clause 11) Medium

      MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

      MSTP Slave (Clause 9) Baud Rate(s)

      Other

      Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

      Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

      Device Address Binding Supported

      Static Device Binding Supported

      Networking DescriptionsSupported

      Option

      Annex H BACnet Tunneling

      BACnetIP Broadcast Management Device (BBMD)

      Does the BBMD Support Registrations by Foreign Devices

      Router

      ACC-SVP01B-EN bull BCI-I Integration Guide 23

      BACnet Data Points and Configuration Property Definitions

      Character Sets

      Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

      Character Set Descriptions Supported

      ANSI X34

      IBMMicrosoft DBCS

      ISO 10646 (UCS-4)

      ISO 10646 (UCS2)

      ISO 8859-1

      JIS C 6226

      24 ACC-SVP01B-EN bull BCI-I Integration Guide

      Object Data Points and Diagnostic Data Points

      Object Data Points and Diagnostic Data Points

      For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

      Table 3 Analog Output

      Object Identifier Object Name Description Units Valid Range

      Refresh Rate

      (Sec)

      Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

      Percent (98) 0 to 100 NA

      Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

      Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

      Degrees-Fahrenheit (64) 500 to 900 NA

      Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

      BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

      Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

      Degrees-Fahrenheit (64) 400 to 900 NA

      Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

      Degrees-Fahrenheit (64) 400 to 1800 NA

      Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

      070 to 510 (Ipak II) NA

      Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

      003 to 030-002 to 030 (enhanced StatiTrac)

      NA

      Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

      -028 to 050-067 to 067 (enhanced StatiTrac)

      900

      Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

      Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

      Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

      00 to 79 (Ipak II) 900

      Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

      Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

      Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

      Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

      Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

      Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

      Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

      Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

      Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

      Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

      ACC-SVP01B-EN bull BCI-I Integration Guide 25

      Object Data Points and Diagnostic Data Points

      Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

      Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

      Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

      Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

      Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

      Cooling temperature setpoint used for control in unoccupied mode

      Degrees-Fahrenheit (64) 520 to 880 NA

      Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

      Heating temperature setpoint used for control in unoccupied mode

      Degrees-Fahrenheit (64) 500 to 900 NA

      Table 4 Analog Input

      Object Identifier Object Name Description Units (Listed Are Defaults)

      Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

      Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

      Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

      Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

      Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

      Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

      Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

      Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

      Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

      Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

      Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

      Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

      Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

      Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

      Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

      Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

      Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

      Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

      Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

      Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

      Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

      Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

      Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

      Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

      Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

      Table 3 Analog Output (continued)

      Object Identifier Object Name Description Units Valid Range

      Refresh Rate

      (Sec)

      26 ACC-SVP01B-EN bull BCI-I Integration Guide

      Object Data Points and Diagnostic Data Points

      Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

      Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

      Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

      Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

      Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

      Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

      Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

      Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

      Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

      Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

      Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

      Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

      Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

      Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

      Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

      Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

      Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

      Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

      Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

      Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

      Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

      Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

      Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

      Analog Input 54 Morning Warmup Air Temperature Setpoint Active

      The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

      Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

      The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

      Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

      Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

      Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

      Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

      Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

      Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

      Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

      Table 4 Analog Input (continued)

      Object Identifier Object Name Description Units (Listed Are Defaults)

      ACC-SVP01B-EN bull BCI-I Integration Guide 27

      Object Data Points and Diagnostic Data Points

      Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

      Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

      Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

      Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

      The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

      Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

      Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

      Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

      Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

      Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

      Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

      Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

      Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

      Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

      Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

      Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

      Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

      Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

      Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

      Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

      Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

      Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

      Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

      Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

      Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

      Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

      Table 5 Analog Value

      Object Identifier Object Name Description Units Valid Range

      Analog Value 1 Filter Runtime Hours Setpoint

      The setpoint value used by the filter run hours calculation

      Hours (71) 0 to 10000

      Table 4 Analog Input (continued)

      Object Identifier Object Name Description Units (Listed Are Defaults)

      28 ACC-SVP01B-EN bull BCI-I Integration Guide

      Object Data Points and Diagnostic Data Points

      Table 6 Multistate Output

      BCI-I Object Identifier Object Name Description Object States

      Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

      Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

      1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

      Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

      Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

      1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

      Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

      1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

      Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

      1 = Flow2 = No Flow3 = Auto

      Table 7 Multistate Input

      BCI-I Object Identifier Object Name Description Object States

      Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

      1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

      Multi-State Input 9 Economizer Type General description of the equipment economizer system

      1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

      Multi-State Input 10 Condenser Type General description of the equipment condenser system

      1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

      Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

      1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

      ACC-SVP01B-EN bull BCI-I Integration Guide 29

      Object Data Points and Diagnostic Data Points

      Multi-State Input 15 Economizer Decision Method

      Unit method to determine when the economizer system is enabled

      1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

      Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

      Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

      Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

      1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

      Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

      1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

      Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

      1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

      Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

      1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

      Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

      1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

      Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

      1 = Idle2 = On3 = Cancel

      Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

      1 = Off2 = On3 = Not Present

      Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

      1 = Off2 = On3 = Not Present

      Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

      1 = Off2 = On3 = Not Present

      Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

      1 = Off|2 = On3 = Not Present

      Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

      1 = Off2 = On3 = Not Present

      Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

      1 = Off2 = On3 = Not Present

      Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

      1 = Off2 = On3 = Not Present

      Table 7 Multistate Input (continued)

      BCI-I Object Identifier Object Name Description Object States

      30 ACC-SVP01B-EN bull BCI-I Integration Guide

      Object Data Points and Diagnostic Data Points

      Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

      1 = Off2 = On3 = Not Present

      Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

      1 = Off2 = On3 = Not Present

      Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

      Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

      Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

      Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

      Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

      1 = Off2 = On3 = Not Present

      Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

      1= Off2= On3= Not Present

      Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

      Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

      Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

      Multi-State Input 43 Outdoor Air Damper Status

      Indicates the operating state of the outdoor damper

      1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

      Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

      1 = Disabled2 = Enabled3 = Not Present

      Table 8 Binary Output

      Object Identifier Object Name DescriptionRelinquish Default Object States

      Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

      Active = BAS Control

      Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

      Active = Heating Locked Out

      Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

      Active = Cooling Locked Out

      Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

      Active = Enabled

      Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

      Active = On

      Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

      Inactive Inactive = DisabledActive = Enabled

      Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

      Active = Reset

      Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

      Active = Reset

      Table 7 Multistate Input (continued)

      BCI-I Object Identifier Object Name Description Object States

      ACC-SVP01B-EN bull BCI-I Integration Guide 31

      Object Data Points and Diagnostic Data Points

      Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

      Active = Auto

      Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

      Active = Auto

      Table 9 Binary Input

      Object Identifier Object Name Description Object States

      Binary Input 1 System Control Status Indicates the control system currently in command of the unit

      Inactive = Standalone controlActive = BAS control

      Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

      Inactive = NormalActive = Locked Out

      Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

      Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

      Inactive = AutoActive = Open

      Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

      Inactive = InactiveActive = Active

      Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

      Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

      Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

      Inactive = DisabledActive = Enabled

      Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

      Inactive = DisabledActive = Enabled

      Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

      Inactive = InactiveActive = Active

      Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

      Inactive = No FlowActive = Flow

      Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

      Inactive = InactiveActive = Active

      Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

      Inactive = InactiveActive = Active

      Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

      Inactive = InactiveActive = Active

      Binary Input 161 Evaporator Frost Protection Circuit 1 Status

      The status of evaporator frost protection function for circuit 1

      Inactive = InactiveActive = Active

      Binary Input 162 Evaporator Frost Protection Circuit 2 Status

      The status of evaporator frost protection function for circuit 2

      Inactive = InactiveActive = Active

      Binary Input 163 Evaporator Frost Protection Circuit 3 Status

      The status of evaporator frost protection function for circuit 3

      Inactive = InactiveActive = Active

      Binary Input 164 Evaporator Frost Protection Circuit 4 Status

      The status of evaporator frost protection function for circuit 4

      Inactive = InactiveActive = Active

      Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

      Inactive = De-energizedActive = Energized

      Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

      Inactive = InactiveActive = Active

      Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

      Inactive = ClosedActive = Open

      Table 10 Diagnostics Binary Input

      Object Identifier(a) Object Name Description

      Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

      Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

      Binary Input 31 (use Object Identifier for RT or CSC)

      Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

      Binary Input 31 (use Object Identifier for FAU)

      Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

      Table 8 Binary Output

      Object Identifier Object Name DescriptionRelinquish Default Object States

      32 ACC-SVP01B-EN bull BCI-I Integration Guide

      Object Data Points and Diagnostic Data Points

      Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

      Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

      Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

      Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

      Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

      Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

      Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

      Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

      Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

      Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

      Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

      Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

      Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

      Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

      Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

      Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

      Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

      Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

      Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

      Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

      Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

      Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

      Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

      Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

      Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

      Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

      Binary Input 58 (use Object Identifier for RT or CSC)

      Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

      Binary Input 58 (use Object Identifier for FAU)

      Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

      Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

      Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

      Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

      Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

      Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

      Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

      Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

      Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

      Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

      Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

      Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

      Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

      Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

      Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

      Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

      Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

      Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

      Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

      Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

      Table 10 Diagnostics Binary Input (continued)

      Object Identifier(a) Object Name Description

      ACC-SVP01B-EN bull BCI-I Integration Guide 33

      Object Data Points and Diagnostic Data Points

      Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

      Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

      Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

      Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

      Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

      Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

      Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

      Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

      Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

      Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

      Binary Input 86 (use Object Identifier for RT I-pak II)

      Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

      Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

      Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

      Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

      Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

      Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

      Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

      Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

      Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

      Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

      Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

      Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

      Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

      Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

      Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

      Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

      Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

      Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

      Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

      Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

      Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

      Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

      Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

      Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

      Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

      Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

      Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

      Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

      Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

      Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

      Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

      Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

      Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

      Binary Input 121 (use Object Identifier for RT)

      Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

      Binary Input 121 (use Object Identifier for FAU)

      Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

      Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

      Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

      Table 10 Diagnostics Binary Input (continued)

      Object Identifier(a) Object Name Description

      34 ACC-SVP01B-EN bull BCI-I Integration Guide

      Object Data Points and Diagnostic Data Points

      Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

      Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

      Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

      Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

      Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

      Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

      Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

      Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

      Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

      Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

      Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

      Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

      Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

      Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

      Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

      Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

      Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

      Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

      Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

      Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

      Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

      Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

      Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

      Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

      Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

      Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

      (a) Object States Inactive = normal and Active = foreign language specific

      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

      Object Identifier(a) Object Name Description

      Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

      Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

      Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

      Analog Input 80 Cabinet Style Describes the cabinet style of the unit

      Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

      Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

      Multi-State Input 10 Condenser Type General description of the equipment condenser system

      Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

      Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

      Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

      Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

      Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

      Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

      Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

      Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

      Table 10 Diagnostics Binary Input (continued)

      Object Identifier(a) Object Name Description

      ACC-SVP01B-EN bull BCI-I Integration Guide 35

      Object Data Points and Diagnostic Data Points

      Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

      Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

      Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

      Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

      Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

      Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

      Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

      Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

      Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

      Analog Input 81 Cool Type Describes the cooling type installed in the unit

      Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

      Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

      Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

      Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

      Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

      Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

      Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

      Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

      Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

      Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

      Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

      Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

      Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

      Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

      Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

      Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

      Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

      Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

      Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

      Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

      Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

      Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

      Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

      Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

      Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

      Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

      Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

      Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

      Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

      Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

      Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

      Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

      Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

      Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

      Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

      Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

      Object Identifier(a) Object Name Description

      36 ACC-SVP01B-EN bull BCI-I Integration Guide

      Object Data Points and Diagnostic Data Points

      Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

      Multi-State Input 9 Economizer Type General description of the equipment economizer system

      Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

      Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

      Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

      Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

      Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

      Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

      Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

      Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

      Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

      Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

      Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

      Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

      Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

      Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

      Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

      Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

      Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

      Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

      Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

      Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

      Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

      Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

      Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

      Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

      Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

      Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

      Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

      Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

      Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

      Multi-State Input 36 Final Filter Status Indicates the final filter media state

      Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

      Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

      Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

      Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

      Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

      Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

      Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

      Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

      Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

      Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

      Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

      Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

      Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

      Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

      Object Identifier(a) Object Name Description

      ACC-SVP01B-EN bull BCI-I Integration Guide 37

      Object Data Points and Diagnostic Data Points

      Binary Output 16 Humidification Command Command the operating state of the humidification system

      NC 3 HVAC-Advisory HVAC-Advisory

      NC 1 HVAC-Critical HVAC-Critical

      NC 4 HVAC-Information HVAC-Information

      NC 2 HVAC-Service Required HVAC-Service Required

      Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

      Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

      Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

      Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

      Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

      Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

      Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

      Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

      Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

      Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

      Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

      Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

      Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

      Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

      Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

      Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

      Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

      Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

      Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

      Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

      Multi-State Input 34 Prefilter Status Indicates the prefilter media state

      Analog Input 82 Preheat Type Describes the heating type installed in the unit

      Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

      Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

      Analog Input 83 Reheat Type Describes the reheat type installed in the unit

      Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

      Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

      Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

      Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

      Multi-State Input 42 Return Fan Status Indicates the state of the return fan

      Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

      Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

      Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

      Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

      Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

      Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

      Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

      Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

      Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

      Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

      Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

      Object Identifier(a) Object Name Description

      38 ACC-SVP01B-EN bull BCI-I Integration Guide

      Object Data Points and Diagnostic Data Points

      Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

      Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

      Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

      Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

      Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

      Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

      Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

      Analog Input 15 Space Temperature Active The space temperature currently used for unit control

      Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

      Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

      Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

      Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

      Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

      Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

      Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

      Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

      Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

      Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

      Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

      Binary Input 1 System Control Status Indicates the control system currently in command of the unit

      Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

      Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

      Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

      Binary Input 3 Unit Status Indicates the current state of the unit

      Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

      Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

      Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

      Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

      Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

      Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

      Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

      (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

      Object Identifier(a) Object Name Description

      Table 12 Diagnostic Objects Sorted by Object Name

      Object Identifier(a) Object Name ValueRange Description

      BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

      BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

      ACC-SVP01B-EN bull BCI-I Integration Guide 39

      Object Data Points and Diagnostic Data Points

      BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

      BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

      BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

      BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

      BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

      BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

      BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

      BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

      BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

      BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

      BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

      BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

      BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

      BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

      BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

      BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

      BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

      BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

      BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

      BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

      BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

      BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

      BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

      BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

      BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

      BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

      BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

      BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

      BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

      Table 12 Diagnostic Objects Sorted by Object Name (continued)

      Object Identifier(a) Object Name ValueRange Description

      40 ACC-SVP01B-EN bull BCI-I Integration Guide

      Object Data Points and Diagnostic Data Points

      BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

      BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

      BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

      BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

      BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

      BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

      BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

      BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

      BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

      BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

      BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

      BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

      BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

      BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

      BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

      BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

      BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

      BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

      BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

      BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

      BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

      BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

      BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

      BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

      BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

      BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

      BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

      BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

      BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

      Table 12 Diagnostic Objects Sorted by Object Name (continued)

      Object Identifier(a) Object Name ValueRange Description

      ACC-SVP01B-EN bull BCI-I Integration Guide 41

      Object Data Points and Diagnostic Data Points

      BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

      BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

      BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

      BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

      BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

      BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

      BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

      BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

      BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

      BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

      BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

      BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

      BI 121 (use Object Identifier for RT)

      Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

      BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

      BI 58 (use Object Identifier for RT or CSC)

      Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

      BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

      BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

      BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

      BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

      BI 31 (use Object Identifier for RT CSC)

      Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

      BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

      BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

      BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

      BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

      BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

      BI 121 (use Object Identifier for FAU)

      Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

      B1 31 (use Object Identifier for FAU)

      Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

      BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

      BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

      Table 12 Diagnostic Objects Sorted by Object Name (continued)

      Object Identifier(a) Object Name ValueRange Description

      42 ACC-SVP01B-EN bull BCI-I Integration Guide

      Object Data Points and Diagnostic Data Points

      BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

      BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

      BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

      BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

      BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

      BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

      BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

      BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

      BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

      BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

      BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

      BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

      BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

      BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

      BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

      BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

      BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

      BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

      BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

      BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

      BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

      BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

      BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

      1 = active Diagnostic Vel Press Sensor (Rear)

      BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

      Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

      BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

      BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

      BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

      BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

      BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

      Table 12 Diagnostic Objects Sorted by Object Name (continued)

      Object Identifier(a) Object Name ValueRange Description

      ACC-SVP01B-EN bull BCI-I Integration Guide 43

      Object Data Points and Diagnostic Data Points

      BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

      BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

      BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

      BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

      BI 58 (use Object Identifier for FAU)

      Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

      (a) BI=Binary Input

      Table 12 Diagnostic Objects Sorted by Object Name (continued)

      Object Identifier(a) Object Name ValueRange Description

      44 ACC-SVP01B-EN bull BCI-I Integration Guide

      Additional Resources

      Additional Resources

      Use the following documents and links as additional resources

      bull Product support online

      bull wwwbacnetorg

      bull wwwbacnetassociationorg

      bull wwwashraeorg

      bull Tracer TU Help online

      bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

      bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

      Note For further assistance contact your local Trane sales office

      ACC-SVP01B-EN bull BCI-I Integration Guide 45

      Glossary

      A

      ASHRAE

      See American Society of Heating Refrigeration and Air-conditioning Engineers

      American Society of Heating Refrigeration and Air-

      conditioning Engineers

      An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

      BBACnettrade

      See Building Automation Control network

      BACnet interoperability building blocks

      A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

      BACnet object

      An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

      baud rate

      The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

      BIBB

      See BACnet interoperability building blocks

      Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

      advocates BACnet protocol for use in system-level control devices

      device

      A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

      Device ID

      The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

      Iinteroperability

      The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

      Pprotocol

      A set of rules (language) that governs the exchange of data over a digital communications system

      S

      stand-alone operation

      Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

      wwwtranecom

      For more information contact your local Trane office or e-mail us at comforttranecom

      Literature Order Number ACC-SVP01B-EN

      Date September 2009

      Supersedes ACC-SVP01A-EN

      Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

      • Table of Contents
      • Overview
      • Ordering Numbers
      • BACnet Protocol
      • BCI-I Configuration
        • Overview
        • Starting a Session of Tracer TU and Direct Connection
        • Reset to Factory Default
        • IP Units Configuration
        • BACnet Object Configuration
        • Change Baud Rate
        • Change Device ID
        • Stand-alone or BAS Operation
          • IntelliPak Control Configuration
          • BAS Unit Control
          • Periodic Update of BAS Values
          • BAS Communication Failure
            • InputOutput Commands and Calculations
              • System Control Command
              • Filter Timer Reset Command
              • Diagnostics Reset Command
              • Setpoint Calculations
              • Timestamp Configuration
                  • BCI IntelliPak Rotary Switches and LEDs
                    • Rotary Switches
                    • LEDs Description Behavior and Troubleshooting
                    • 24 Vac Measurement
                    • Ground Measurements
                      • BACnet Data Points and Configuration Property Definitions
                        • BACnet Protocol Implementation Conformance Statement (PICS)
                          • Standardized Device Profile (Annex L)
                          • Interoperability Building Blocks (Annex K)
                          • Segmentation Capability
                          • Object Types
                            • BACnet Protocol
                              • Data Link Layer Options
                              • Device Address Binding
                              • Networking Options
                              • Character Sets
                                  • Object Data Points and Diagnostic Data Points
                                  • Additional Resources
                                  • Glossary

        4 ACC-SVP01B-EN bull BCI-I Integration Guide

        Overview

        The BACnet Communication Interface for IntelliPak (BCI-I) is comprised of a Tracertrade UC400 controller with interface software It is a non-programmable communications module that allows heating ventilation and air-conditioning (HVAC) equipment to communicate on a BACnet communications network

        This guide provides

        bull A list of ordering numbers

        bull A brief overview of the BACnettrade protocol

        bull BCI-I configuration information

        bull A explanation of the BCI-I device rotary switches and LEDs

        bull Data point configuration property definitions

        bull Tables listing object data points

        bull Additional resources

        bull A glossary of terms

        Note Users of this guide should have basic knowledge of BACnet protocol For more detailed information about this protocol visit the company web site listed under ldquoAdditional Resourcesrdquo p 44

        Ordering Numbers

        BACnet Protocol

        The Building Automation and Control Network (BACnet and ANSIASHRAE Standard 135-2004) protocol is a standard that allows building automation systems or components from different manufacturers to share information and control functions BACnet provides building owners the capability to connect various types of building control systems or subsystems together for a variety of reasons In addition multiple vendors can use this protocol to share information for monitoring and supervisory control between systems and devices in a multi-vendor interconnected system

        The BACnet protocol identifies standard objects (data points) called BACnet objects Each object has a defined list of properties that provide information about that object BACnet also defines a number of standard application services that are used to access data and manipulate these objects and provides a clientserver communication between devices For more information on BACnet protocol refer to ldquoAdditional Resourcesrdquo p 44

        BACnet Testing Laboratory (BTL) Certification

        The BCI-I supports the BACnet communication protocol and has been designed to meet the requirements of the application-specific control profile For more details refer to the BTL web site at wwwbacnetassociationorg

        Order Number Description

        X13651544-010 IntelliPak I for software and hardware

        C175218460010 IntelliPak I II and CSC for field-installed kit

        ACC-SVP01B-EN bull BCI-I Integration Guide 5

        BCI-I Configuration

        BCI-I Configuration

        This section will provide the following information when configuring the BCI-I

        bull Overview

        bull Starting a session of Tracer TU and direct connection

        bull Resetting to factory default

        bull Configuring IP units

        bull Configuring BACnet objects

        bull Changing baud rate and device ID

        bull Inputoutput and equipment functions

        Overview

        The BCI-I device is designed as a self-configuring controller to accommodate the many possible equipment configuration options available in the IntelliPak line of equipment This self-configuring device eliminates the need for the BAS technician having to create BACnet objects minimizes the risk of object configuration errors and allows the IntelliPak unit to be quickly installed in the BAS

        The self-configuration process only creates objects that are appropriate for the feature set of the specific IntelliPak unit the BCI-I is connected to Once this process is complete the device exits factory mode and enters the normal mode of operation At this point the self-configuration process will not start when power is applied to the device

        The set of objects listed in Table 3 p 24 through Table 10 p 31 are the super set of all possible objects supported by the IntelliPak line of equipment The BAS technician should query the device for the list of actual objects that have been created in the device

        Starting a Session of Tracer TU and Direct Connection

        Tracer TU is the service tool software that allows the technician to modify the operation of the device and to discover the BACnet objects present in the device To modify the device or discover objects the user must first connect to Tracer TU as follows

        WARNING Remove power from the HVAC equipment before opening electrical control panel

        1 Connect a USB cable directly between the laptop PC and the service port located on the front of the BCI-I device When connecting to the controller for the first time the Found New Hardware Wizard appears Follow the wizard instructions to install the USB hardware driver

        2 Click either the Tracer TU desktop icon or the Tracer TU program item in the Tracer TU group on the Start menu The Tracer TU splash screen appears briefly followed by the Connect dialog box

        3 Select the Direct Connection (Via USB cable) radio button if it is not already selected

        4 Click the Connect button and the Tracer TU main page will appear after successful connection

        Note The BCI-I may be powered via the USB cable or 24 Vac from the HVAC unit Concurrent connection of unit power and the USB cable will not harm the BCI-I device

        For more detailed information about direct connection to Tracer TU refer to the Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

        6 ACC-SVP01B-EN bull BCI-I Integration Guide

        BCI-I Configuration

        Reset to Factory Default

        Factory default mode is the only mode the technician can use to set the units of measure for the device or to scan the IntelliPak unit to create BACnet objects The process of putting the device in factory default mode must be run prior to executing units of measure configuration or the object self-configuration process

        WARNING Remove power from the HVAC equipment before

        opening electrical control panel

        To reset the controller to factory defaultunconfigured state

        1 Power down the unit The IMC buss must not be active during reset

        2 Establish the connection between Tracer TU and the device Follow the procedure ldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

        3 From the Utilities menu select Controller and then Controller Settings The Controller Settings page appears

        4 On the controller settings page there is a gray bar at the bottom with SaveCancel buttons Move the cursor near the left edge of the bar keeping the cursor inside the bar Click on this area and a Clear Controller button will appear in the upper right portion of the page

        5 Click the Clear Controller button and a pop-up window will appear asking for confirmation to reset the device Click Yes

        6 After a few seconds a pop-up will appear confirming that the controller has been reset and indicating that the controller will be rebooted Click OK

        After the controller boots up it will be in factory default state The units of measure is SI (metric) the MSTP baud rate is 76800 and there will be no BACnet objects present in the controller

        The controller must be in this state prior to changing the units of measure or self-configuring the device If using inch-pound units of measure proceed to the next section ldquoIP Units Configuration otherwise proceed to ldquoBACnet Object Configuration

        IP Units Configuration

        The BCI-I supports both inch-pound and SI (metric) units of measure The factory default units of measure is SI The device allows only a change of units for all objects as a whole Mixed units of measure is not allowed If the controller is not in factory default state follow the previous procedure ldquoReset to Factory Defaultrdquo p 6

        To change the units of measure in the device

        1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

        2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Controller Units frame

        3 In the Device Units box of the frame select IP units of measure radio button and then click Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Select OK

        4 Exit Tracer TU and cycle power to the controller by disconnecting the USB plug and then reconnecting the plug After the controller boots up it will be in factory default state the units of measure is IP the MSTP baud rate is 76800 and there will be no BACnet objects present in the controller

        ACC-SVP01B-EN bull BCI-I Integration Guide 7

        BCI-I Configuration

        BACnet Object Configuration

        Configuring BACnet objects is a self-configuring process If the controller is not in factory default state follow the previous procedure ldquoReset to Factory Defaultrdquo p 6

        1 Remove the USB cable plug from the device

        2 Apply power to the HVAC equipment After the device boots up the self-configuration process will begin No further user action is required

        Note Do not remove power while the device is in self-configuration mode This typically takes 2 to 4 minutes to complete Once complete the device enters normal operating mode

        Change Baud Rate

        The BCI-I device supports four baud rates 9600 19200 38400 and 76800 baud The default baud rate is 76800 baud The baud rate can be modified with Tracer TU

        WARNING Remove power from the HVAC equipment before opening electrical control panel

        To change baud rate

        1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

        2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Protocol frame

        3 Click on the drop down arrow for the Baud Rate list and select the desired baud rate

        4 Click Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Click OK

        5 Exit Tracer TU and disconnect the USB cable plug

        6 Apply power to the HVAC equipment

        Change Device ID

        By default the BCI-I device sets its device ID to the same value as the one defined by the rotary switches (MSTP MAC address) on the front of the device Refer to the section ldquoRotary Switchesrdquo p 12 For simple networks this is an easy method to guarantee unique device IDs across the link

        The device also supports the full range of device ID values as specified by the BACnet Standard Systems that require a more complex device ID convention are supported with Tracer TU which has the ability to set the device ID via software configuration

        WARNING Remove power from the HVAC equipment before opening electrical control panel

        The process for soft setting the device ID is as follows

        1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

        2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Protocol frame

        3 In the device ID box select the check box next to Use Software Device ID to enable the functionality The swipe-and-type box becomes available

        4 Type in the desired device ID

        8 ACC-SVP01B-EN bull BCI-I Integration Guide

        BCI-I Configuration

        5 Click the Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Click OK

        6 Exit Tracer TU and disconnect the USB service plug

        7 Apply power to the HVAC equipment

        Stand-alone or BAS Operation

        The control system on HVAC equipment has the ability to operate the unit as a stand-alone system or as part of a building automation system The BCI-I (either factory or field installed) by default is configured for stand-alone operation This configuration enables the HVAC equipment to operate prior to the commissioning of the unit into the BAS

        IntelliPak Control Configuration

        The IntelliPak control system must be configured at the human interface (HI) to support unit control from the BAS The technician should setverify the following configuration properties as illustrated below The technician should also verify that the BAS Module Comm Failure diagnostic is not present

        BAS Unit Control

        The BCI-I provides a method for a BAS to control the operation of HVAC equipment This method consists of BACnet objects that the BAS can access to control and monitor the status of equipment There are two sets of objects

        bull Output objects used by the BAS to provide command setpoint and sensor information to the IntelliPak unit

        bull Input objects provide IntelliPak status information to the BAS See tables 3 to 11 for the list of objects supported

        The system allows the BAS technician to define the amount of control that the BAS system will apply to the unit This is done by configuring the state of the Out of Service property of the output objects If the property is set to True the equipment will use a corresponding local value for control If the property is set to False the local value is ignored and the BAS-supplied value is used for control The BAS value is provided to the IntelliPak by writing to the present value property of the corresponding output object The factory default value for the Out of Service property of these objects is True

        1 Configuration Menu

        2 Setup Menu

        3 Diagnostics Menu

        Software Revision NumberBAS Communications BACnet 1801

        Configuration - Model Num Digit 34BAS Communication Module Installed

        Unit Control BASNETWORK

        Active Diagnostic - - Auto ResetNone

        Human Interface Representation

        ACC-SVP01B-EN bull BCI-I Integration Guide 9

        BCI-I Configuration

        Periodic Update of BAS Values

        The BCI-I device requires the BAS system to provide a periodic update to the sensor values This is required to protect against a loss of communication between the BAS and the BCI-I By BACnet definition the present value of the object will maintain the last value written to it regardless of the amount of time that has elapsed since the last write If communication is lost for several minutes or longer the present value of BAS-supplied sensor objects may no longer represent the current state of environmental conditions This may result in decreased occupant comfort and damage to building systems

        BAS Communication Failure

        The BCI-I is designed to minimize communication failure mode It does this by monitoring the length of time that has elapsed since the last write to the present value of the sensor object If the length of time exceeds a predefined limit the BCI-I will place the object into the fault state and revert to a unit-supplied sensor value for control At power up the sensor objects are set to a fault state and they will remain in this state until a write is detected The minimum periodic refresh rate for the objects is defined in Table 3 p 24 The following list is a set of sensor values that can be supplied by the BAS

        bull Space Static Pressure BAS

        bull Space Air Temperature BAS

        bull Discharge Air Temperature BAS

        bull Duct Static Air Pressure BAS

        bull Outdoor Air Temperature BAS

        bull Outdoor Air Humidity BAS

        bull Outdoor Airflow BAS

        bull Space CO2 Concentration BAS

        bull Space Humidity BAS

        InputOutput Commands and Calculations

        This section will provide the following information about certain inputs and outputs that perform unique control commands and calculations

        bull System control command

        bull Filter timer and diagnostic reset commands

        bull Setpoint calculations

        System Control Command

        Binary Output Object 1 has a special importance in the system The object allows the BAS to command the unit to run in a local or BAS control mode When the present value property of the object is set to Local Control the IntelliPak unit will enter local control and ignore BAS supplied values In this mode the unit will use local sensor and setpoint values When the object present value property is set to BAS Control the IntelliPak unit will use the values supplied by the BAS system for unit control

        Filter Timer Reset Command

        The BCI-I uses the Filter Runtime Hours object (AI 6) to generate a diagnostic when its present value is greater than the Filter Runtime Hours Setpoint (AV 1) present value The procedure for resetting the timer is as follows

        10 ACC-SVP01B-EN bull BCI-I Integration Guide

        BCI-I Configuration

        The BAS will change the state of the Filter Timer Reset Command object (BO 13) to the active state Upon the change to active state the BCI-I will set the present value of the Filter Runtime Hours object to zero and then set the Reset Command object back to the inactive state

        Diagnostics Reset Command

        The IntelliPak control system monitors the operation of the HVAC equipment If an abnormal condition is detected a diagnostic message is displayed on the human interface of the equipment control panel In addition the set of internal diagnostics is mapped to the set of BACnet binary input objects as listed in Table 9 p 31 The corresponding BI object will change state from inactive to active when the diagnostic is detected The object has been configured to send a BACnet event message to external BACnet devices as defined by the protocol

        The BAS has the ability to reset internal diagnostics by controlling the state of the Diagnostic Reset Command object (BO 14) The procedure for resetting diagnostics is as follows

        The BAS will change the state of the Diagnostic Reset to the active state Upon the change to active state the IntelliPak control system will reset all internal diagnostics and set the state of all of the diagnostic objects to inactive Upon completion of this action the BCI-I will set the present value of the Diagnostic Reset Command object back to the inactive state

        Setpoint Calculations

        The equipment has the ability to perform two basic control functions

        bull Space air temperature control

        bull Discharge air temperature control

        When the unit is configured for discharge air control it controls the temperature of the air leaving the unit to the discharge air temperature setpoint

        When the unit is configured for space air temperature control it controls the air temperature of the space that contains the space air temperature sensor This value may be provided by wiring the sensor to the unit or via a sensor value provided by the BAS

        The drawing below describes how the various temperature setpoints are calculated for space temperature control When the unit is in an occupied mode the active space temperature setpoint is calculated based on the space temperature setpoint and the two setpoint offset values In unoccupied mode the unoccupied heating and cooling setpoints are used as the active setpoint

        ACC-SVP01B-EN bull BCI-I Integration Guide 11

        BCI-I Configuration

        Timestamp Configuration

        The BCI-C device has a software-derived clock that maintains the time and date The device requires the current time to enable it to record a timestamp when an event or a change in state is detected by a BACnet object However in the event of a power loss the device does not maintain this time and date information At powerup the device time and date will default to 1200 pm Jan 1 1970 To minimize the possibility that the unit timestamp is not representing the actual time the BAS should be setup to periodically synchronize the device time clock with the BAS clock using the BACnet TimeSynchronization service

        12 ACC-SVP01B-EN bull BCI-I Integration Guide

        BCI IntelliPak Rotary Switches and LEDs

        BCI IntelliPak Rotary Switches and LEDs

        This section provides information about the BCI-I rotary switches and LED displays

        Rotary Switches

        There are three rotary switches on the front of the BCI-I device that are used to define a three-digit address when the BCI-I is installed on a BACnet communications network The three-digit address setting is the BACnet MAC address

        Note All devices are MSTP masters with valid MAC addresses of 001 to 127 for BACnet

        Figure 1 Setting rotary switches

        ADDRESS0 1

        23

        456

        78

        9

        x1

        0 1

        23

        456

        78

        9

        x10

        0 1

        23

        456

        78

        9

        x100

        Before

        After

        0

        5

        1

        3

        6

        29

        487

        Example of before and after setting addresses

        Use a 18 inch flathead screwdriver to set rotary switches

        Important Each device on the BACnetMSTP link must have a unique rotary switch setting otherwise communication problems will occur

        ACC-SVP01B-EN bull BCI-I Integration Guide 13

        BCI IntelliPak Rotary Switches and LEDs

        LEDs Description Behavior and Troubleshooting

        There are 15 LEDs on the front of the BCI-I unit However LEDs BO1 through BO9 are not used for the BCI-I controller Figure 2 shows the locations of each LED The following table provides a description of each LED activity an indication or troubleshooting tips for each and any notes

        Figure 2 LED locations

        SERVICE

        IMCLINK

        RX

        TX

        Marquee LED

        Table 1 LED Activities and Troubleshooting Tips

        LED Name ActivitiesIndication or Troubleshooting

        Tip (Denoted in Bullets) Notes

        Marquee LED

        Shows solid green when the unit is powered and no problems exist

        Indicates normal operation

        Shows solid red when the unit is powered but represents low power or a

        malfunction

        bull If low power could be under voltage or the microprocessor has malfunction Follow the troubleshoot procedure ldquo24 Vac Measurementrdquo p 15 to measure for the expected value range

        bull If malfunction unpower and then repower unit to bring the device back up to normal operation

        Shows blinking red when an a BACnet object is in a fault condition

        Alarm when an alarm is triggered for example when a point goes into fault condition because of point failure or there is an indication of a custom alarm in TGP2

        Shows blinking green when the device does not detect the IMC buss

        bull Verify that the IPC wiring harness is connected to the IMC link terminals

        bull Verify the polarity of the IPC wiring harness at the unit terminals

        LED not lit

        Indicates power is OFF or there is a malfunction

        bull OFF or malfunction cycle the power

        14 ACC-SVP01B-EN bull BCI-I Integration Guide

        BCI IntelliPak Rotary Switches and LEDs

        Link and IMC

        TX blinks greenBlinks at the data transfer rate when the unit transfers data to other devices on the link

        TX LED Regardless of connectivity or not this LED will constantly blink as it continually looks for devices to communicate to

        LED not litDetermine if for example a Tracer SC or BACnet device is trying to talk to the controller or if it is capable of talking to the controller Also determine if the communication status shows down all of the time

        Refer to ldquoGround Measurementsrdquo p 16 for a check-out procedure

        RX blinks yellow

        Blinks at the data transfer rate when the unit receives data from other devices on the link

        bull ON solid yellow indicates there is reverse polarity

        LED not lit

        Indicates that the controller is not detecting communication

        bull Not lit cycle the power to reestablish communication

        Service

        Shows solid greenIndicates someone is pressing this LED or the controller is not operating normally

        Press and hold during power up to place controller into boot code or press and hold for a count of approximately 10 seconds to clear the Device ID

        What is Boot Code When the UC400 is placed into boot code the system will not run any applications such as trending scheduling and TGP2 runtime

        Blinks green

        Indicates controllers is not accessing application software

        bull Restore using TU service tool

        LED not lit Indicates controller is operating normally

        Binary 01 to Binary 09 Not Used

        Table 1 LED Activities and Troubleshooting Tips

        LED Name ActivitiesIndication or Troubleshooting

        Tip (Denoted in Bullets) Notes

        ACC-SVP01B-EN bull BCI-I Integration Guide 15

        BCI IntelliPak Rotary Switches and LEDs

        24 Vac Measurement

        General Information Checkout Procedure Measurement Expected Value

        Checking the voltage that is powering the UC400 is often a necessary step when commissioning or troubleshooting Operational issues and LED operation may result in a need to measure the input power

        When troubleshooting it is faster to take measurements while the load is in place If Step 1 indicates an out-of-specification voltage disconnect the UC400 and measure the AC voltage across the transformer These measurements can direct the technician towards the problem source

        Step 1

        Measure AC voltage with the UC400 connected Perform this measurement while the unit is under load

        200 Vac le Vac le 300 Vac

        Step 2

        Measure AC voltage with the UC400 unconnected Perform this measurement while the unit is not under load

        200 Vac le Vac le 300 Vac

        16 ACC-SVP01B-EN bull BCI-I Integration Guide

        BCI IntelliPak Rotary Switches and LEDs

        Ground Measurements

        General Information and Checkout Procedure Measurement Expected Value

        Method 1AC voltage between shield conductors and device chassis ground- the voltage difference between BACnet MSTP device chassis ground connections should be close to zero If the voltage difference is greater that 40 Vac there will be marginal communication or intermittent communication problems If the voltage difference is greater that 70 Vac some devices will no longer communicate

        Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

        Vac le 20 V

        Method 2AC voltage between earth ground and device chassis ground- the chassis ground of the UC400 needs to be connected to earth ground by some route

        Note Do not assume that the building frame is a valid earth ground

        Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

        Vac le 40 V (Must comply with National Electrical Codetradeand local electrical codes)

        ACC-SVP01B-EN bull BCI-I Integration Guide 17

        BACnet Data Points and Configuration Property Definitions

        BACnet Data Points and Configuration Property

        Definitions

        The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MSTP This section includes information about

        bull BACnet protocol implementation conformance statement (PICS)

        bull Object types descriptions and configuration (refer to Table 2 p 19)

        bull BACnet protocol data link layers device address binding networking options and character sets

        bull Object data points and configurations

        BACnet Protocol Implementation Conformance Statement (PICS)

        Standardized Device Profile (Annex L)

        Interoperability Building Blocks (Annex K)

        Profile Description Supported Profile

        BACnet Advanced Application Controller (B-AAC)

        BACnet Application Specific Controller (B-ASC)

        BACnet Building Controller (B-BC)

        BACnet Operator Workstation (B-OWS)

        BACnet Smart Actuator (B-SA)

        BACnet Smart Sensor (B-SS)

        Data Sharing Description Supported BIBB

        Data Sharing-COV-B (DS-COV-B)

        Data Sharing-ReadProperty-A (DS-RP-A)

        Data Sharing-ReadProperty-B (DS-RP-B)

        Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)

        Data Sharing-WriteProperty-A (DS-WP-A)

        Data Sharing-WriteProperty-B (DS-WP-B)

        Data Sharing-WritePropertyMultiple-B (DS-WPM-B)

        Alarm and Event Management Description Supported BIBB

        Alarm and Event-ACKI-B (AE-ACK-B)

        Alarm and Event-Alarm Summary-B (AE-ASUM-B)

        Alarm and Event-Enrollment Summary-B (AE-ESUM-B)

        Alarm and Event-Information-B (AE-INFO-B)

        Alarm and Event-Notification Internal-B (AE-N-I-B)

        18 ACC-SVP01B-EN bull BCI-I Integration Guide

        BACnet Data Points and Configuration Property Definitions

        Segmentation Capability

        Trending Description Supported BIBB

        Trending-Automated Trend Retrieval-B (T-ATR-B)

        Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

        Device Management Description Supported BIBB

        Device Management-Backup and Restore-B (DM-BR-B)

        Device Management-Device Communication Control-B (DM-DCC-B)

        Device Management-Dynamic Device Binding-A (DM-DDB-A)

        Device Management-Dynamic Device Binding-B (DM-DDB-B)

        Device Management-Dynamic Object Binding-B (DM-DOB-B)

        Device Management-List Manipulation-B (DM-LM-B)

        Device Management-Object Creation and Deletion-B (DM-OCD-B)

        Device Management-Private Transfer-A (DM-PT-A)

        Device Management-Private Transfer-B (DM-PT-B)

        Device Management-Reinitialize Device-B (DM-RD-B)

        Device Management-TimeSynchronization-B (DM-TS-B)

        Segmentation Description Supported Segment

        Segmented Requests Window Size 1

        Segmented Responses Window Size 1

        ACC-SVP01B-EN bull BCI-I Integration Guide 19

        BACnet Data Points and Configuration Property Definitions

        Object Types

        Table 2 Descriptions and configurations

        Object Type Required Properties Read Properties Written(a) Optional Properties Read

        Ability to Create

        Ability to Delete

        Analog Input

        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

        bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

        bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

        Yes Yes only user created objects

        Analog Output

        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

        bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

        bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

        Yes Yes only user created objects

        Analog Value

        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

        bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

        bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

        Yes Yes only user created objects

        Binary Input

        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

        bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

        bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

        Yes Yes only user created objects

        20 ACC-SVP01B-EN bull BCI-I Integration Guide

        BACnet Data Points and Configuration Property Definitions

        Binary Output

        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

        bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

        bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

        Yes Yes only user created objects

        Binary Value

        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

        bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

        bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

        Yes Yes only user created objects

        Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

        bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

        bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

        None None

        Event Enrollment Object

        bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

        bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

        bull None Yes Yes only user created objects

        Table 2 Descriptions and configurations (continued)

        Object Type Required Properties Read Properties Written(a) Optional Properties Read

        Ability to Create

        Ability to Delete

        ACC-SVP01B-EN bull BCI-I Integration Guide 21

        BACnet Data Points and Configuration Property Definitions

        Multistate Input

        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

        bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

        bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

        Yes Yes only user created objects

        Multistate Output

        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

        bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

        bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

        Yes Yes only user created objects

        Multistate Value

        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

        bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

        bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

        Yes Yes only user created objects

        Notification Class

        bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

        bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

        None Yes Yes only user created objects

        Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

        bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

        bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

        Yes Yes only user created objects

        (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

        Table 2 Descriptions and configurations (continued)

        Object Type Required Properties Read Properties Written(a) Optional Properties Read

        Ability to Create

        Ability to Delete

        22 ACC-SVP01B-EN bull BCI-I Integration Guide

        BACnet Data Points and Configuration Property Definitions

        BACnet Protocol

        Data Link Layer Options

        Device Address Binding

        Networking Options

        Data Link Layer Description Supported Option

        ANSIATA 8781 25 Mb ARCNET (Clause 8)

        ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

        BACnet IP (Annex J)

        BACnet IP (Annex J) Foreign Device

        ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

        LonTalk (Clause 11) Medium

        MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

        MSTP Slave (Clause 9) Baud Rate(s)

        Other

        Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

        Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

        Device Address Binding Supported

        Static Device Binding Supported

        Networking DescriptionsSupported

        Option

        Annex H BACnet Tunneling

        BACnetIP Broadcast Management Device (BBMD)

        Does the BBMD Support Registrations by Foreign Devices

        Router

        ACC-SVP01B-EN bull BCI-I Integration Guide 23

        BACnet Data Points and Configuration Property Definitions

        Character Sets

        Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

        Character Set Descriptions Supported

        ANSI X34

        IBMMicrosoft DBCS

        ISO 10646 (UCS-4)

        ISO 10646 (UCS2)

        ISO 8859-1

        JIS C 6226

        24 ACC-SVP01B-EN bull BCI-I Integration Guide

        Object Data Points and Diagnostic Data Points

        Object Data Points and Diagnostic Data Points

        For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

        Table 3 Analog Output

        Object Identifier Object Name Description Units Valid Range

        Refresh Rate

        (Sec)

        Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

        Percent (98) 0 to 100 NA

        Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

        Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

        Degrees-Fahrenheit (64) 500 to 900 NA

        Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

        BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

        Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

        Degrees-Fahrenheit (64) 400 to 900 NA

        Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

        Degrees-Fahrenheit (64) 400 to 1800 NA

        Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

        070 to 510 (Ipak II) NA

        Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

        003 to 030-002 to 030 (enhanced StatiTrac)

        NA

        Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

        -028 to 050-067 to 067 (enhanced StatiTrac)

        900

        Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

        Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

        Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

        00 to 79 (Ipak II) 900

        Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

        Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

        Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

        Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

        Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

        Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

        Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

        Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

        Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

        Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

        ACC-SVP01B-EN bull BCI-I Integration Guide 25

        Object Data Points and Diagnostic Data Points

        Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

        Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

        Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

        Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

        Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

        Cooling temperature setpoint used for control in unoccupied mode

        Degrees-Fahrenheit (64) 520 to 880 NA

        Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

        Heating temperature setpoint used for control in unoccupied mode

        Degrees-Fahrenheit (64) 500 to 900 NA

        Table 4 Analog Input

        Object Identifier Object Name Description Units (Listed Are Defaults)

        Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

        Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

        Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

        Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

        Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

        Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

        Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

        Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

        Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

        Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

        Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

        Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

        Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

        Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

        Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

        Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

        Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

        Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

        Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

        Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

        Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

        Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

        Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

        Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

        Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

        Table 3 Analog Output (continued)

        Object Identifier Object Name Description Units Valid Range

        Refresh Rate

        (Sec)

        26 ACC-SVP01B-EN bull BCI-I Integration Guide

        Object Data Points and Diagnostic Data Points

        Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

        Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

        Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

        Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

        Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

        Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

        Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

        Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

        Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

        Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

        Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

        Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

        Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

        Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

        Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

        Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

        Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

        Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

        Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

        Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

        Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

        Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

        Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

        Analog Input 54 Morning Warmup Air Temperature Setpoint Active

        The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

        Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

        The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

        Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

        Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

        Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

        Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

        Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

        Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

        Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

        Table 4 Analog Input (continued)

        Object Identifier Object Name Description Units (Listed Are Defaults)

        ACC-SVP01B-EN bull BCI-I Integration Guide 27

        Object Data Points and Diagnostic Data Points

        Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

        Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

        Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

        Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

        The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

        Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

        Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

        Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

        Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

        Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

        Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

        Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

        Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

        Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

        Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

        Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

        Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

        Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

        Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

        Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

        Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

        Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

        Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

        Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

        Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

        Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

        Table 5 Analog Value

        Object Identifier Object Name Description Units Valid Range

        Analog Value 1 Filter Runtime Hours Setpoint

        The setpoint value used by the filter run hours calculation

        Hours (71) 0 to 10000

        Table 4 Analog Input (continued)

        Object Identifier Object Name Description Units (Listed Are Defaults)

        28 ACC-SVP01B-EN bull BCI-I Integration Guide

        Object Data Points and Diagnostic Data Points

        Table 6 Multistate Output

        BCI-I Object Identifier Object Name Description Object States

        Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

        Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

        1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

        Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

        Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

        1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

        Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

        1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

        Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

        1 = Flow2 = No Flow3 = Auto

        Table 7 Multistate Input

        BCI-I Object Identifier Object Name Description Object States

        Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

        1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

        Multi-State Input 9 Economizer Type General description of the equipment economizer system

        1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

        Multi-State Input 10 Condenser Type General description of the equipment condenser system

        1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

        Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

        1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

        ACC-SVP01B-EN bull BCI-I Integration Guide 29

        Object Data Points and Diagnostic Data Points

        Multi-State Input 15 Economizer Decision Method

        Unit method to determine when the economizer system is enabled

        1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

        Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

        Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

        Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

        1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

        Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

        1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

        Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

        1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

        Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

        1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

        Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

        1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

        Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

        1 = Idle2 = On3 = Cancel

        Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

        1 = Off2 = On3 = Not Present

        Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

        1 = Off2 = On3 = Not Present

        Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

        1 = Off2 = On3 = Not Present

        Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

        1 = Off|2 = On3 = Not Present

        Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

        1 = Off2 = On3 = Not Present

        Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

        1 = Off2 = On3 = Not Present

        Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

        1 = Off2 = On3 = Not Present

        Table 7 Multistate Input (continued)

        BCI-I Object Identifier Object Name Description Object States

        30 ACC-SVP01B-EN bull BCI-I Integration Guide

        Object Data Points and Diagnostic Data Points

        Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

        1 = Off2 = On3 = Not Present

        Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

        1 = Off2 = On3 = Not Present

        Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

        Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

        Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

        Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

        Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

        1 = Off2 = On3 = Not Present

        Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

        1= Off2= On3= Not Present

        Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

        Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

        Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

        Multi-State Input 43 Outdoor Air Damper Status

        Indicates the operating state of the outdoor damper

        1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

        Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

        1 = Disabled2 = Enabled3 = Not Present

        Table 8 Binary Output

        Object Identifier Object Name DescriptionRelinquish Default Object States

        Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

        Active = BAS Control

        Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

        Active = Heating Locked Out

        Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

        Active = Cooling Locked Out

        Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

        Active = Enabled

        Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

        Active = On

        Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

        Inactive Inactive = DisabledActive = Enabled

        Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

        Active = Reset

        Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

        Active = Reset

        Table 7 Multistate Input (continued)

        BCI-I Object Identifier Object Name Description Object States

        ACC-SVP01B-EN bull BCI-I Integration Guide 31

        Object Data Points and Diagnostic Data Points

        Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

        Active = Auto

        Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

        Active = Auto

        Table 9 Binary Input

        Object Identifier Object Name Description Object States

        Binary Input 1 System Control Status Indicates the control system currently in command of the unit

        Inactive = Standalone controlActive = BAS control

        Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

        Inactive = NormalActive = Locked Out

        Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

        Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

        Inactive = AutoActive = Open

        Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

        Inactive = InactiveActive = Active

        Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

        Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

        Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

        Inactive = DisabledActive = Enabled

        Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

        Inactive = DisabledActive = Enabled

        Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

        Inactive = InactiveActive = Active

        Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

        Inactive = No FlowActive = Flow

        Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

        Inactive = InactiveActive = Active

        Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

        Inactive = InactiveActive = Active

        Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

        Inactive = InactiveActive = Active

        Binary Input 161 Evaporator Frost Protection Circuit 1 Status

        The status of evaporator frost protection function for circuit 1

        Inactive = InactiveActive = Active

        Binary Input 162 Evaporator Frost Protection Circuit 2 Status

        The status of evaporator frost protection function for circuit 2

        Inactive = InactiveActive = Active

        Binary Input 163 Evaporator Frost Protection Circuit 3 Status

        The status of evaporator frost protection function for circuit 3

        Inactive = InactiveActive = Active

        Binary Input 164 Evaporator Frost Protection Circuit 4 Status

        The status of evaporator frost protection function for circuit 4

        Inactive = InactiveActive = Active

        Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

        Inactive = De-energizedActive = Energized

        Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

        Inactive = InactiveActive = Active

        Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

        Inactive = ClosedActive = Open

        Table 10 Diagnostics Binary Input

        Object Identifier(a) Object Name Description

        Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

        Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

        Binary Input 31 (use Object Identifier for RT or CSC)

        Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

        Binary Input 31 (use Object Identifier for FAU)

        Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

        Table 8 Binary Output

        Object Identifier Object Name DescriptionRelinquish Default Object States

        32 ACC-SVP01B-EN bull BCI-I Integration Guide

        Object Data Points and Diagnostic Data Points

        Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

        Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

        Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

        Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

        Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

        Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

        Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

        Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

        Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

        Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

        Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

        Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

        Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

        Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

        Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

        Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

        Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

        Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

        Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

        Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

        Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

        Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

        Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

        Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

        Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

        Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

        Binary Input 58 (use Object Identifier for RT or CSC)

        Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

        Binary Input 58 (use Object Identifier for FAU)

        Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

        Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

        Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

        Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

        Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

        Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

        Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

        Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

        Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

        Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

        Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

        Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

        Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

        Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

        Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

        Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

        Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

        Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

        Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

        Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

        Table 10 Diagnostics Binary Input (continued)

        Object Identifier(a) Object Name Description

        ACC-SVP01B-EN bull BCI-I Integration Guide 33

        Object Data Points and Diagnostic Data Points

        Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

        Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

        Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

        Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

        Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

        Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

        Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

        Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

        Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

        Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

        Binary Input 86 (use Object Identifier for RT I-pak II)

        Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

        Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

        Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

        Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

        Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

        Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

        Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

        Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

        Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

        Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

        Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

        Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

        Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

        Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

        Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

        Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

        Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

        Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

        Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

        Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

        Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

        Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

        Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

        Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

        Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

        Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

        Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

        Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

        Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

        Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

        Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

        Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

        Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

        Binary Input 121 (use Object Identifier for RT)

        Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

        Binary Input 121 (use Object Identifier for FAU)

        Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

        Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

        Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

        Table 10 Diagnostics Binary Input (continued)

        Object Identifier(a) Object Name Description

        34 ACC-SVP01B-EN bull BCI-I Integration Guide

        Object Data Points and Diagnostic Data Points

        Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

        Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

        Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

        Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

        Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

        Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

        Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

        Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

        Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

        Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

        Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

        Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

        Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

        Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

        Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

        Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

        Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

        Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

        Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

        Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

        Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

        Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

        Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

        Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

        Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

        Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

        (a) Object States Inactive = normal and Active = foreign language specific

        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

        Object Identifier(a) Object Name Description

        Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

        Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

        Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

        Analog Input 80 Cabinet Style Describes the cabinet style of the unit

        Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

        Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

        Multi-State Input 10 Condenser Type General description of the equipment condenser system

        Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

        Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

        Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

        Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

        Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

        Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

        Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

        Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

        Table 10 Diagnostics Binary Input (continued)

        Object Identifier(a) Object Name Description

        ACC-SVP01B-EN bull BCI-I Integration Guide 35

        Object Data Points and Diagnostic Data Points

        Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

        Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

        Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

        Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

        Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

        Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

        Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

        Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

        Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

        Analog Input 81 Cool Type Describes the cooling type installed in the unit

        Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

        Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

        Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

        Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

        Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

        Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

        Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

        Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

        Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

        Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

        Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

        Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

        Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

        Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

        Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

        Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

        Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

        Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

        Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

        Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

        Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

        Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

        Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

        Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

        Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

        Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

        Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

        Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

        Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

        Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

        Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

        Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

        Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

        Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

        Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

        Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

        Object Identifier(a) Object Name Description

        36 ACC-SVP01B-EN bull BCI-I Integration Guide

        Object Data Points and Diagnostic Data Points

        Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

        Multi-State Input 9 Economizer Type General description of the equipment economizer system

        Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

        Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

        Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

        Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

        Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

        Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

        Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

        Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

        Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

        Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

        Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

        Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

        Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

        Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

        Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

        Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

        Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

        Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

        Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

        Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

        Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

        Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

        Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

        Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

        Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

        Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

        Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

        Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

        Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

        Multi-State Input 36 Final Filter Status Indicates the final filter media state

        Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

        Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

        Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

        Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

        Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

        Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

        Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

        Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

        Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

        Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

        Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

        Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

        Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

        Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

        Object Identifier(a) Object Name Description

        ACC-SVP01B-EN bull BCI-I Integration Guide 37

        Object Data Points and Diagnostic Data Points

        Binary Output 16 Humidification Command Command the operating state of the humidification system

        NC 3 HVAC-Advisory HVAC-Advisory

        NC 1 HVAC-Critical HVAC-Critical

        NC 4 HVAC-Information HVAC-Information

        NC 2 HVAC-Service Required HVAC-Service Required

        Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

        Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

        Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

        Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

        Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

        Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

        Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

        Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

        Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

        Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

        Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

        Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

        Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

        Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

        Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

        Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

        Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

        Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

        Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

        Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

        Multi-State Input 34 Prefilter Status Indicates the prefilter media state

        Analog Input 82 Preheat Type Describes the heating type installed in the unit

        Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

        Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

        Analog Input 83 Reheat Type Describes the reheat type installed in the unit

        Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

        Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

        Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

        Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

        Multi-State Input 42 Return Fan Status Indicates the state of the return fan

        Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

        Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

        Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

        Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

        Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

        Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

        Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

        Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

        Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

        Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

        Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

        Object Identifier(a) Object Name Description

        38 ACC-SVP01B-EN bull BCI-I Integration Guide

        Object Data Points and Diagnostic Data Points

        Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

        Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

        Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

        Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

        Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

        Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

        Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

        Analog Input 15 Space Temperature Active The space temperature currently used for unit control

        Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

        Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

        Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

        Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

        Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

        Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

        Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

        Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

        Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

        Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

        Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

        Binary Input 1 System Control Status Indicates the control system currently in command of the unit

        Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

        Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

        Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

        Binary Input 3 Unit Status Indicates the current state of the unit

        Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

        Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

        Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

        Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

        Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

        Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

        Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

        (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

        Object Identifier(a) Object Name Description

        Table 12 Diagnostic Objects Sorted by Object Name

        Object Identifier(a) Object Name ValueRange Description

        BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

        BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

        ACC-SVP01B-EN bull BCI-I Integration Guide 39

        Object Data Points and Diagnostic Data Points

        BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

        BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

        BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

        BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

        BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

        BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

        BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

        BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

        BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

        BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

        BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

        BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

        BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

        BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

        BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

        BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

        BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

        BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

        BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

        BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

        BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

        BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

        BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

        BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

        BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

        BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

        BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

        BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

        BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

        Table 12 Diagnostic Objects Sorted by Object Name (continued)

        Object Identifier(a) Object Name ValueRange Description

        40 ACC-SVP01B-EN bull BCI-I Integration Guide

        Object Data Points and Diagnostic Data Points

        BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

        BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

        BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

        BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

        BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

        BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

        BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

        BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

        BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

        BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

        BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

        BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

        BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

        BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

        BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

        BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

        BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

        BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

        BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

        BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

        BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

        BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

        BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

        BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

        BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

        BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

        BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

        BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

        BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

        Table 12 Diagnostic Objects Sorted by Object Name (continued)

        Object Identifier(a) Object Name ValueRange Description

        ACC-SVP01B-EN bull BCI-I Integration Guide 41

        Object Data Points and Diagnostic Data Points

        BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

        BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

        BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

        BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

        BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

        BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

        BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

        BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

        BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

        BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

        BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

        BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

        BI 121 (use Object Identifier for RT)

        Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

        BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

        BI 58 (use Object Identifier for RT or CSC)

        Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

        BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

        BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

        BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

        BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

        BI 31 (use Object Identifier for RT CSC)

        Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

        BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

        BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

        BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

        BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

        BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

        BI 121 (use Object Identifier for FAU)

        Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

        B1 31 (use Object Identifier for FAU)

        Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

        BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

        BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

        Table 12 Diagnostic Objects Sorted by Object Name (continued)

        Object Identifier(a) Object Name ValueRange Description

        42 ACC-SVP01B-EN bull BCI-I Integration Guide

        Object Data Points and Diagnostic Data Points

        BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

        BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

        BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

        BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

        BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

        BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

        BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

        BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

        BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

        BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

        BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

        BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

        BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

        BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

        BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

        BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

        BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

        BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

        BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

        BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

        BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

        BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

        BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

        1 = active Diagnostic Vel Press Sensor (Rear)

        BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

        Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

        BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

        BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

        BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

        BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

        BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

        Table 12 Diagnostic Objects Sorted by Object Name (continued)

        Object Identifier(a) Object Name ValueRange Description

        ACC-SVP01B-EN bull BCI-I Integration Guide 43

        Object Data Points and Diagnostic Data Points

        BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

        BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

        BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

        BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

        BI 58 (use Object Identifier for FAU)

        Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

        (a) BI=Binary Input

        Table 12 Diagnostic Objects Sorted by Object Name (continued)

        Object Identifier(a) Object Name ValueRange Description

        44 ACC-SVP01B-EN bull BCI-I Integration Guide

        Additional Resources

        Additional Resources

        Use the following documents and links as additional resources

        bull Product support online

        bull wwwbacnetorg

        bull wwwbacnetassociationorg

        bull wwwashraeorg

        bull Tracer TU Help online

        bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

        bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

        Note For further assistance contact your local Trane sales office

        ACC-SVP01B-EN bull BCI-I Integration Guide 45

        Glossary

        A

        ASHRAE

        See American Society of Heating Refrigeration and Air-conditioning Engineers

        American Society of Heating Refrigeration and Air-

        conditioning Engineers

        An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

        BBACnettrade

        See Building Automation Control network

        BACnet interoperability building blocks

        A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

        BACnet object

        An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

        baud rate

        The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

        BIBB

        See BACnet interoperability building blocks

        Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

        advocates BACnet protocol for use in system-level control devices

        device

        A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

        Device ID

        The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

        Iinteroperability

        The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

        Pprotocol

        A set of rules (language) that governs the exchange of data over a digital communications system

        S

        stand-alone operation

        Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

        wwwtranecom

        For more information contact your local Trane office or e-mail us at comforttranecom

        Literature Order Number ACC-SVP01B-EN

        Date September 2009

        Supersedes ACC-SVP01A-EN

        Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

        • Table of Contents
        • Overview
        • Ordering Numbers
        • BACnet Protocol
        • BCI-I Configuration
          • Overview
          • Starting a Session of Tracer TU and Direct Connection
          • Reset to Factory Default
          • IP Units Configuration
          • BACnet Object Configuration
          • Change Baud Rate
          • Change Device ID
          • Stand-alone or BAS Operation
            • IntelliPak Control Configuration
            • BAS Unit Control
            • Periodic Update of BAS Values
            • BAS Communication Failure
              • InputOutput Commands and Calculations
                • System Control Command
                • Filter Timer Reset Command
                • Diagnostics Reset Command
                • Setpoint Calculations
                • Timestamp Configuration
                    • BCI IntelliPak Rotary Switches and LEDs
                      • Rotary Switches
                      • LEDs Description Behavior and Troubleshooting
                      • 24 Vac Measurement
                      • Ground Measurements
                        • BACnet Data Points and Configuration Property Definitions
                          • BACnet Protocol Implementation Conformance Statement (PICS)
                            • Standardized Device Profile (Annex L)
                            • Interoperability Building Blocks (Annex K)
                            • Segmentation Capability
                            • Object Types
                              • BACnet Protocol
                                • Data Link Layer Options
                                • Device Address Binding
                                • Networking Options
                                • Character Sets
                                    • Object Data Points and Diagnostic Data Points
                                    • Additional Resources
                                    • Glossary

          ACC-SVP01B-EN bull BCI-I Integration Guide 5

          BCI-I Configuration

          BCI-I Configuration

          This section will provide the following information when configuring the BCI-I

          bull Overview

          bull Starting a session of Tracer TU and direct connection

          bull Resetting to factory default

          bull Configuring IP units

          bull Configuring BACnet objects

          bull Changing baud rate and device ID

          bull Inputoutput and equipment functions

          Overview

          The BCI-I device is designed as a self-configuring controller to accommodate the many possible equipment configuration options available in the IntelliPak line of equipment This self-configuring device eliminates the need for the BAS technician having to create BACnet objects minimizes the risk of object configuration errors and allows the IntelliPak unit to be quickly installed in the BAS

          The self-configuration process only creates objects that are appropriate for the feature set of the specific IntelliPak unit the BCI-I is connected to Once this process is complete the device exits factory mode and enters the normal mode of operation At this point the self-configuration process will not start when power is applied to the device

          The set of objects listed in Table 3 p 24 through Table 10 p 31 are the super set of all possible objects supported by the IntelliPak line of equipment The BAS technician should query the device for the list of actual objects that have been created in the device

          Starting a Session of Tracer TU and Direct Connection

          Tracer TU is the service tool software that allows the technician to modify the operation of the device and to discover the BACnet objects present in the device To modify the device or discover objects the user must first connect to Tracer TU as follows

          WARNING Remove power from the HVAC equipment before opening electrical control panel

          1 Connect a USB cable directly between the laptop PC and the service port located on the front of the BCI-I device When connecting to the controller for the first time the Found New Hardware Wizard appears Follow the wizard instructions to install the USB hardware driver

          2 Click either the Tracer TU desktop icon or the Tracer TU program item in the Tracer TU group on the Start menu The Tracer TU splash screen appears briefly followed by the Connect dialog box

          3 Select the Direct Connection (Via USB cable) radio button if it is not already selected

          4 Click the Connect button and the Tracer TU main page will appear after successful connection

          Note The BCI-I may be powered via the USB cable or 24 Vac from the HVAC unit Concurrent connection of unit power and the USB cable will not harm the BCI-I device

          For more detailed information about direct connection to Tracer TU refer to the Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

          6 ACC-SVP01B-EN bull BCI-I Integration Guide

          BCI-I Configuration

          Reset to Factory Default

          Factory default mode is the only mode the technician can use to set the units of measure for the device or to scan the IntelliPak unit to create BACnet objects The process of putting the device in factory default mode must be run prior to executing units of measure configuration or the object self-configuration process

          WARNING Remove power from the HVAC equipment before

          opening electrical control panel

          To reset the controller to factory defaultunconfigured state

          1 Power down the unit The IMC buss must not be active during reset

          2 Establish the connection between Tracer TU and the device Follow the procedure ldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

          3 From the Utilities menu select Controller and then Controller Settings The Controller Settings page appears

          4 On the controller settings page there is a gray bar at the bottom with SaveCancel buttons Move the cursor near the left edge of the bar keeping the cursor inside the bar Click on this area and a Clear Controller button will appear in the upper right portion of the page

          5 Click the Clear Controller button and a pop-up window will appear asking for confirmation to reset the device Click Yes

          6 After a few seconds a pop-up will appear confirming that the controller has been reset and indicating that the controller will be rebooted Click OK

          After the controller boots up it will be in factory default state The units of measure is SI (metric) the MSTP baud rate is 76800 and there will be no BACnet objects present in the controller

          The controller must be in this state prior to changing the units of measure or self-configuring the device If using inch-pound units of measure proceed to the next section ldquoIP Units Configuration otherwise proceed to ldquoBACnet Object Configuration

          IP Units Configuration

          The BCI-I supports both inch-pound and SI (metric) units of measure The factory default units of measure is SI The device allows only a change of units for all objects as a whole Mixed units of measure is not allowed If the controller is not in factory default state follow the previous procedure ldquoReset to Factory Defaultrdquo p 6

          To change the units of measure in the device

          1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

          2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Controller Units frame

          3 In the Device Units box of the frame select IP units of measure radio button and then click Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Select OK

          4 Exit Tracer TU and cycle power to the controller by disconnecting the USB plug and then reconnecting the plug After the controller boots up it will be in factory default state the units of measure is IP the MSTP baud rate is 76800 and there will be no BACnet objects present in the controller

          ACC-SVP01B-EN bull BCI-I Integration Guide 7

          BCI-I Configuration

          BACnet Object Configuration

          Configuring BACnet objects is a self-configuring process If the controller is not in factory default state follow the previous procedure ldquoReset to Factory Defaultrdquo p 6

          1 Remove the USB cable plug from the device

          2 Apply power to the HVAC equipment After the device boots up the self-configuration process will begin No further user action is required

          Note Do not remove power while the device is in self-configuration mode This typically takes 2 to 4 minutes to complete Once complete the device enters normal operating mode

          Change Baud Rate

          The BCI-I device supports four baud rates 9600 19200 38400 and 76800 baud The default baud rate is 76800 baud The baud rate can be modified with Tracer TU

          WARNING Remove power from the HVAC equipment before opening electrical control panel

          To change baud rate

          1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

          2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Protocol frame

          3 Click on the drop down arrow for the Baud Rate list and select the desired baud rate

          4 Click Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Click OK

          5 Exit Tracer TU and disconnect the USB cable plug

          6 Apply power to the HVAC equipment

          Change Device ID

          By default the BCI-I device sets its device ID to the same value as the one defined by the rotary switches (MSTP MAC address) on the front of the device Refer to the section ldquoRotary Switchesrdquo p 12 For simple networks this is an easy method to guarantee unique device IDs across the link

          The device also supports the full range of device ID values as specified by the BACnet Standard Systems that require a more complex device ID convention are supported with Tracer TU which has the ability to set the device ID via software configuration

          WARNING Remove power from the HVAC equipment before opening electrical control panel

          The process for soft setting the device ID is as follows

          1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

          2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Protocol frame

          3 In the device ID box select the check box next to Use Software Device ID to enable the functionality The swipe-and-type box becomes available

          4 Type in the desired device ID

          8 ACC-SVP01B-EN bull BCI-I Integration Guide

          BCI-I Configuration

          5 Click the Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Click OK

          6 Exit Tracer TU and disconnect the USB service plug

          7 Apply power to the HVAC equipment

          Stand-alone or BAS Operation

          The control system on HVAC equipment has the ability to operate the unit as a stand-alone system or as part of a building automation system The BCI-I (either factory or field installed) by default is configured for stand-alone operation This configuration enables the HVAC equipment to operate prior to the commissioning of the unit into the BAS

          IntelliPak Control Configuration

          The IntelliPak control system must be configured at the human interface (HI) to support unit control from the BAS The technician should setverify the following configuration properties as illustrated below The technician should also verify that the BAS Module Comm Failure diagnostic is not present

          BAS Unit Control

          The BCI-I provides a method for a BAS to control the operation of HVAC equipment This method consists of BACnet objects that the BAS can access to control and monitor the status of equipment There are two sets of objects

          bull Output objects used by the BAS to provide command setpoint and sensor information to the IntelliPak unit

          bull Input objects provide IntelliPak status information to the BAS See tables 3 to 11 for the list of objects supported

          The system allows the BAS technician to define the amount of control that the BAS system will apply to the unit This is done by configuring the state of the Out of Service property of the output objects If the property is set to True the equipment will use a corresponding local value for control If the property is set to False the local value is ignored and the BAS-supplied value is used for control The BAS value is provided to the IntelliPak by writing to the present value property of the corresponding output object The factory default value for the Out of Service property of these objects is True

          1 Configuration Menu

          2 Setup Menu

          3 Diagnostics Menu

          Software Revision NumberBAS Communications BACnet 1801

          Configuration - Model Num Digit 34BAS Communication Module Installed

          Unit Control BASNETWORK

          Active Diagnostic - - Auto ResetNone

          Human Interface Representation

          ACC-SVP01B-EN bull BCI-I Integration Guide 9

          BCI-I Configuration

          Periodic Update of BAS Values

          The BCI-I device requires the BAS system to provide a periodic update to the sensor values This is required to protect against a loss of communication between the BAS and the BCI-I By BACnet definition the present value of the object will maintain the last value written to it regardless of the amount of time that has elapsed since the last write If communication is lost for several minutes or longer the present value of BAS-supplied sensor objects may no longer represent the current state of environmental conditions This may result in decreased occupant comfort and damage to building systems

          BAS Communication Failure

          The BCI-I is designed to minimize communication failure mode It does this by monitoring the length of time that has elapsed since the last write to the present value of the sensor object If the length of time exceeds a predefined limit the BCI-I will place the object into the fault state and revert to a unit-supplied sensor value for control At power up the sensor objects are set to a fault state and they will remain in this state until a write is detected The minimum periodic refresh rate for the objects is defined in Table 3 p 24 The following list is a set of sensor values that can be supplied by the BAS

          bull Space Static Pressure BAS

          bull Space Air Temperature BAS

          bull Discharge Air Temperature BAS

          bull Duct Static Air Pressure BAS

          bull Outdoor Air Temperature BAS

          bull Outdoor Air Humidity BAS

          bull Outdoor Airflow BAS

          bull Space CO2 Concentration BAS

          bull Space Humidity BAS

          InputOutput Commands and Calculations

          This section will provide the following information about certain inputs and outputs that perform unique control commands and calculations

          bull System control command

          bull Filter timer and diagnostic reset commands

          bull Setpoint calculations

          System Control Command

          Binary Output Object 1 has a special importance in the system The object allows the BAS to command the unit to run in a local or BAS control mode When the present value property of the object is set to Local Control the IntelliPak unit will enter local control and ignore BAS supplied values In this mode the unit will use local sensor and setpoint values When the object present value property is set to BAS Control the IntelliPak unit will use the values supplied by the BAS system for unit control

          Filter Timer Reset Command

          The BCI-I uses the Filter Runtime Hours object (AI 6) to generate a diagnostic when its present value is greater than the Filter Runtime Hours Setpoint (AV 1) present value The procedure for resetting the timer is as follows

          10 ACC-SVP01B-EN bull BCI-I Integration Guide

          BCI-I Configuration

          The BAS will change the state of the Filter Timer Reset Command object (BO 13) to the active state Upon the change to active state the BCI-I will set the present value of the Filter Runtime Hours object to zero and then set the Reset Command object back to the inactive state

          Diagnostics Reset Command

          The IntelliPak control system monitors the operation of the HVAC equipment If an abnormal condition is detected a diagnostic message is displayed on the human interface of the equipment control panel In addition the set of internal diagnostics is mapped to the set of BACnet binary input objects as listed in Table 9 p 31 The corresponding BI object will change state from inactive to active when the diagnostic is detected The object has been configured to send a BACnet event message to external BACnet devices as defined by the protocol

          The BAS has the ability to reset internal diagnostics by controlling the state of the Diagnostic Reset Command object (BO 14) The procedure for resetting diagnostics is as follows

          The BAS will change the state of the Diagnostic Reset to the active state Upon the change to active state the IntelliPak control system will reset all internal diagnostics and set the state of all of the diagnostic objects to inactive Upon completion of this action the BCI-I will set the present value of the Diagnostic Reset Command object back to the inactive state

          Setpoint Calculations

          The equipment has the ability to perform two basic control functions

          bull Space air temperature control

          bull Discharge air temperature control

          When the unit is configured for discharge air control it controls the temperature of the air leaving the unit to the discharge air temperature setpoint

          When the unit is configured for space air temperature control it controls the air temperature of the space that contains the space air temperature sensor This value may be provided by wiring the sensor to the unit or via a sensor value provided by the BAS

          The drawing below describes how the various temperature setpoints are calculated for space temperature control When the unit is in an occupied mode the active space temperature setpoint is calculated based on the space temperature setpoint and the two setpoint offset values In unoccupied mode the unoccupied heating and cooling setpoints are used as the active setpoint

          ACC-SVP01B-EN bull BCI-I Integration Guide 11

          BCI-I Configuration

          Timestamp Configuration

          The BCI-C device has a software-derived clock that maintains the time and date The device requires the current time to enable it to record a timestamp when an event or a change in state is detected by a BACnet object However in the event of a power loss the device does not maintain this time and date information At powerup the device time and date will default to 1200 pm Jan 1 1970 To minimize the possibility that the unit timestamp is not representing the actual time the BAS should be setup to periodically synchronize the device time clock with the BAS clock using the BACnet TimeSynchronization service

          12 ACC-SVP01B-EN bull BCI-I Integration Guide

          BCI IntelliPak Rotary Switches and LEDs

          BCI IntelliPak Rotary Switches and LEDs

          This section provides information about the BCI-I rotary switches and LED displays

          Rotary Switches

          There are three rotary switches on the front of the BCI-I device that are used to define a three-digit address when the BCI-I is installed on a BACnet communications network The three-digit address setting is the BACnet MAC address

          Note All devices are MSTP masters with valid MAC addresses of 001 to 127 for BACnet

          Figure 1 Setting rotary switches

          ADDRESS0 1

          23

          456

          78

          9

          x1

          0 1

          23

          456

          78

          9

          x10

          0 1

          23

          456

          78

          9

          x100

          Before

          After

          0

          5

          1

          3

          6

          29

          487

          Example of before and after setting addresses

          Use a 18 inch flathead screwdriver to set rotary switches

          Important Each device on the BACnetMSTP link must have a unique rotary switch setting otherwise communication problems will occur

          ACC-SVP01B-EN bull BCI-I Integration Guide 13

          BCI IntelliPak Rotary Switches and LEDs

          LEDs Description Behavior and Troubleshooting

          There are 15 LEDs on the front of the BCI-I unit However LEDs BO1 through BO9 are not used for the BCI-I controller Figure 2 shows the locations of each LED The following table provides a description of each LED activity an indication or troubleshooting tips for each and any notes

          Figure 2 LED locations

          SERVICE

          IMCLINK

          RX

          TX

          Marquee LED

          Table 1 LED Activities and Troubleshooting Tips

          LED Name ActivitiesIndication or Troubleshooting

          Tip (Denoted in Bullets) Notes

          Marquee LED

          Shows solid green when the unit is powered and no problems exist

          Indicates normal operation

          Shows solid red when the unit is powered but represents low power or a

          malfunction

          bull If low power could be under voltage or the microprocessor has malfunction Follow the troubleshoot procedure ldquo24 Vac Measurementrdquo p 15 to measure for the expected value range

          bull If malfunction unpower and then repower unit to bring the device back up to normal operation

          Shows blinking red when an a BACnet object is in a fault condition

          Alarm when an alarm is triggered for example when a point goes into fault condition because of point failure or there is an indication of a custom alarm in TGP2

          Shows blinking green when the device does not detect the IMC buss

          bull Verify that the IPC wiring harness is connected to the IMC link terminals

          bull Verify the polarity of the IPC wiring harness at the unit terminals

          LED not lit

          Indicates power is OFF or there is a malfunction

          bull OFF or malfunction cycle the power

          14 ACC-SVP01B-EN bull BCI-I Integration Guide

          BCI IntelliPak Rotary Switches and LEDs

          Link and IMC

          TX blinks greenBlinks at the data transfer rate when the unit transfers data to other devices on the link

          TX LED Regardless of connectivity or not this LED will constantly blink as it continually looks for devices to communicate to

          LED not litDetermine if for example a Tracer SC or BACnet device is trying to talk to the controller or if it is capable of talking to the controller Also determine if the communication status shows down all of the time

          Refer to ldquoGround Measurementsrdquo p 16 for a check-out procedure

          RX blinks yellow

          Blinks at the data transfer rate when the unit receives data from other devices on the link

          bull ON solid yellow indicates there is reverse polarity

          LED not lit

          Indicates that the controller is not detecting communication

          bull Not lit cycle the power to reestablish communication

          Service

          Shows solid greenIndicates someone is pressing this LED or the controller is not operating normally

          Press and hold during power up to place controller into boot code or press and hold for a count of approximately 10 seconds to clear the Device ID

          What is Boot Code When the UC400 is placed into boot code the system will not run any applications such as trending scheduling and TGP2 runtime

          Blinks green

          Indicates controllers is not accessing application software

          bull Restore using TU service tool

          LED not lit Indicates controller is operating normally

          Binary 01 to Binary 09 Not Used

          Table 1 LED Activities and Troubleshooting Tips

          LED Name ActivitiesIndication or Troubleshooting

          Tip (Denoted in Bullets) Notes

          ACC-SVP01B-EN bull BCI-I Integration Guide 15

          BCI IntelliPak Rotary Switches and LEDs

          24 Vac Measurement

          General Information Checkout Procedure Measurement Expected Value

          Checking the voltage that is powering the UC400 is often a necessary step when commissioning or troubleshooting Operational issues and LED operation may result in a need to measure the input power

          When troubleshooting it is faster to take measurements while the load is in place If Step 1 indicates an out-of-specification voltage disconnect the UC400 and measure the AC voltage across the transformer These measurements can direct the technician towards the problem source

          Step 1

          Measure AC voltage with the UC400 connected Perform this measurement while the unit is under load

          200 Vac le Vac le 300 Vac

          Step 2

          Measure AC voltage with the UC400 unconnected Perform this measurement while the unit is not under load

          200 Vac le Vac le 300 Vac

          16 ACC-SVP01B-EN bull BCI-I Integration Guide

          BCI IntelliPak Rotary Switches and LEDs

          Ground Measurements

          General Information and Checkout Procedure Measurement Expected Value

          Method 1AC voltage between shield conductors and device chassis ground- the voltage difference between BACnet MSTP device chassis ground connections should be close to zero If the voltage difference is greater that 40 Vac there will be marginal communication or intermittent communication problems If the voltage difference is greater that 70 Vac some devices will no longer communicate

          Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

          Vac le 20 V

          Method 2AC voltage between earth ground and device chassis ground- the chassis ground of the UC400 needs to be connected to earth ground by some route

          Note Do not assume that the building frame is a valid earth ground

          Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

          Vac le 40 V (Must comply with National Electrical Codetradeand local electrical codes)

          ACC-SVP01B-EN bull BCI-I Integration Guide 17

          BACnet Data Points and Configuration Property Definitions

          BACnet Data Points and Configuration Property

          Definitions

          The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MSTP This section includes information about

          bull BACnet protocol implementation conformance statement (PICS)

          bull Object types descriptions and configuration (refer to Table 2 p 19)

          bull BACnet protocol data link layers device address binding networking options and character sets

          bull Object data points and configurations

          BACnet Protocol Implementation Conformance Statement (PICS)

          Standardized Device Profile (Annex L)

          Interoperability Building Blocks (Annex K)

          Profile Description Supported Profile

          BACnet Advanced Application Controller (B-AAC)

          BACnet Application Specific Controller (B-ASC)

          BACnet Building Controller (B-BC)

          BACnet Operator Workstation (B-OWS)

          BACnet Smart Actuator (B-SA)

          BACnet Smart Sensor (B-SS)

          Data Sharing Description Supported BIBB

          Data Sharing-COV-B (DS-COV-B)

          Data Sharing-ReadProperty-A (DS-RP-A)

          Data Sharing-ReadProperty-B (DS-RP-B)

          Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)

          Data Sharing-WriteProperty-A (DS-WP-A)

          Data Sharing-WriteProperty-B (DS-WP-B)

          Data Sharing-WritePropertyMultiple-B (DS-WPM-B)

          Alarm and Event Management Description Supported BIBB

          Alarm and Event-ACKI-B (AE-ACK-B)

          Alarm and Event-Alarm Summary-B (AE-ASUM-B)

          Alarm and Event-Enrollment Summary-B (AE-ESUM-B)

          Alarm and Event-Information-B (AE-INFO-B)

          Alarm and Event-Notification Internal-B (AE-N-I-B)

          18 ACC-SVP01B-EN bull BCI-I Integration Guide

          BACnet Data Points and Configuration Property Definitions

          Segmentation Capability

          Trending Description Supported BIBB

          Trending-Automated Trend Retrieval-B (T-ATR-B)

          Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

          Device Management Description Supported BIBB

          Device Management-Backup and Restore-B (DM-BR-B)

          Device Management-Device Communication Control-B (DM-DCC-B)

          Device Management-Dynamic Device Binding-A (DM-DDB-A)

          Device Management-Dynamic Device Binding-B (DM-DDB-B)

          Device Management-Dynamic Object Binding-B (DM-DOB-B)

          Device Management-List Manipulation-B (DM-LM-B)

          Device Management-Object Creation and Deletion-B (DM-OCD-B)

          Device Management-Private Transfer-A (DM-PT-A)

          Device Management-Private Transfer-B (DM-PT-B)

          Device Management-Reinitialize Device-B (DM-RD-B)

          Device Management-TimeSynchronization-B (DM-TS-B)

          Segmentation Description Supported Segment

          Segmented Requests Window Size 1

          Segmented Responses Window Size 1

          ACC-SVP01B-EN bull BCI-I Integration Guide 19

          BACnet Data Points and Configuration Property Definitions

          Object Types

          Table 2 Descriptions and configurations

          Object Type Required Properties Read Properties Written(a) Optional Properties Read

          Ability to Create

          Ability to Delete

          Analog Input

          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

          bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

          bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

          Yes Yes only user created objects

          Analog Output

          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

          bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

          bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

          Yes Yes only user created objects

          Analog Value

          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

          bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

          bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

          Yes Yes only user created objects

          Binary Input

          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

          bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

          bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

          Yes Yes only user created objects

          20 ACC-SVP01B-EN bull BCI-I Integration Guide

          BACnet Data Points and Configuration Property Definitions

          Binary Output

          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

          bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

          bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

          Yes Yes only user created objects

          Binary Value

          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

          bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

          bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

          Yes Yes only user created objects

          Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

          bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

          bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

          None None

          Event Enrollment Object

          bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

          bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

          bull None Yes Yes only user created objects

          Table 2 Descriptions and configurations (continued)

          Object Type Required Properties Read Properties Written(a) Optional Properties Read

          Ability to Create

          Ability to Delete

          ACC-SVP01B-EN bull BCI-I Integration Guide 21

          BACnet Data Points and Configuration Property Definitions

          Multistate Input

          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

          bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

          bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

          Yes Yes only user created objects

          Multistate Output

          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

          bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

          bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

          Yes Yes only user created objects

          Multistate Value

          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

          bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

          bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

          Yes Yes only user created objects

          Notification Class

          bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

          bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

          None Yes Yes only user created objects

          Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

          bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

          bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

          Yes Yes only user created objects

          (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

          Table 2 Descriptions and configurations (continued)

          Object Type Required Properties Read Properties Written(a) Optional Properties Read

          Ability to Create

          Ability to Delete

          22 ACC-SVP01B-EN bull BCI-I Integration Guide

          BACnet Data Points and Configuration Property Definitions

          BACnet Protocol

          Data Link Layer Options

          Device Address Binding

          Networking Options

          Data Link Layer Description Supported Option

          ANSIATA 8781 25 Mb ARCNET (Clause 8)

          ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

          BACnet IP (Annex J)

          BACnet IP (Annex J) Foreign Device

          ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

          LonTalk (Clause 11) Medium

          MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

          MSTP Slave (Clause 9) Baud Rate(s)

          Other

          Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

          Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

          Device Address Binding Supported

          Static Device Binding Supported

          Networking DescriptionsSupported

          Option

          Annex H BACnet Tunneling

          BACnetIP Broadcast Management Device (BBMD)

          Does the BBMD Support Registrations by Foreign Devices

          Router

          ACC-SVP01B-EN bull BCI-I Integration Guide 23

          BACnet Data Points and Configuration Property Definitions

          Character Sets

          Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

          Character Set Descriptions Supported

          ANSI X34

          IBMMicrosoft DBCS

          ISO 10646 (UCS-4)

          ISO 10646 (UCS2)

          ISO 8859-1

          JIS C 6226

          24 ACC-SVP01B-EN bull BCI-I Integration Guide

          Object Data Points and Diagnostic Data Points

          Object Data Points and Diagnostic Data Points

          For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

          Table 3 Analog Output

          Object Identifier Object Name Description Units Valid Range

          Refresh Rate

          (Sec)

          Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

          Percent (98) 0 to 100 NA

          Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

          Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

          Degrees-Fahrenheit (64) 500 to 900 NA

          Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

          BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

          Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

          Degrees-Fahrenheit (64) 400 to 900 NA

          Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

          Degrees-Fahrenheit (64) 400 to 1800 NA

          Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

          070 to 510 (Ipak II) NA

          Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

          003 to 030-002 to 030 (enhanced StatiTrac)

          NA

          Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

          -028 to 050-067 to 067 (enhanced StatiTrac)

          900

          Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

          Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

          Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

          00 to 79 (Ipak II) 900

          Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

          Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

          Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

          Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

          Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

          Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

          Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

          Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

          Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

          Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

          ACC-SVP01B-EN bull BCI-I Integration Guide 25

          Object Data Points and Diagnostic Data Points

          Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

          Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

          Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

          Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

          Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

          Cooling temperature setpoint used for control in unoccupied mode

          Degrees-Fahrenheit (64) 520 to 880 NA

          Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

          Heating temperature setpoint used for control in unoccupied mode

          Degrees-Fahrenheit (64) 500 to 900 NA

          Table 4 Analog Input

          Object Identifier Object Name Description Units (Listed Are Defaults)

          Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

          Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

          Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

          Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

          Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

          Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

          Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

          Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

          Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

          Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

          Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

          Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

          Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

          Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

          Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

          Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

          Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

          Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

          Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

          Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

          Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

          Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

          Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

          Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

          Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

          Table 3 Analog Output (continued)

          Object Identifier Object Name Description Units Valid Range

          Refresh Rate

          (Sec)

          26 ACC-SVP01B-EN bull BCI-I Integration Guide

          Object Data Points and Diagnostic Data Points

          Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

          Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

          Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

          Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

          Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

          Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

          Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

          Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

          Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

          Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

          Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

          Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

          Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

          Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

          Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

          Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

          Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

          Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

          Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

          Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

          Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

          Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

          Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

          Analog Input 54 Morning Warmup Air Temperature Setpoint Active

          The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

          Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

          The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

          Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

          Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

          Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

          Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

          Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

          Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

          Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

          Table 4 Analog Input (continued)

          Object Identifier Object Name Description Units (Listed Are Defaults)

          ACC-SVP01B-EN bull BCI-I Integration Guide 27

          Object Data Points and Diagnostic Data Points

          Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

          Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

          Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

          Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

          The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

          Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

          Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

          Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

          Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

          Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

          Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

          Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

          Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

          Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

          Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

          Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

          Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

          Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

          Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

          Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

          Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

          Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

          Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

          Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

          Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

          Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

          Table 5 Analog Value

          Object Identifier Object Name Description Units Valid Range

          Analog Value 1 Filter Runtime Hours Setpoint

          The setpoint value used by the filter run hours calculation

          Hours (71) 0 to 10000

          Table 4 Analog Input (continued)

          Object Identifier Object Name Description Units (Listed Are Defaults)

          28 ACC-SVP01B-EN bull BCI-I Integration Guide

          Object Data Points and Diagnostic Data Points

          Table 6 Multistate Output

          BCI-I Object Identifier Object Name Description Object States

          Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

          Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

          1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

          Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

          Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

          1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

          Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

          1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

          Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

          1 = Flow2 = No Flow3 = Auto

          Table 7 Multistate Input

          BCI-I Object Identifier Object Name Description Object States

          Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

          1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

          Multi-State Input 9 Economizer Type General description of the equipment economizer system

          1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

          Multi-State Input 10 Condenser Type General description of the equipment condenser system

          1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

          Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

          1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

          ACC-SVP01B-EN bull BCI-I Integration Guide 29

          Object Data Points and Diagnostic Data Points

          Multi-State Input 15 Economizer Decision Method

          Unit method to determine when the economizer system is enabled

          1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

          Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

          Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

          Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

          1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

          Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

          1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

          Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

          1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

          Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

          1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

          Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

          1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

          Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

          1 = Idle2 = On3 = Cancel

          Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

          1 = Off2 = On3 = Not Present

          Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

          1 = Off2 = On3 = Not Present

          Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

          1 = Off2 = On3 = Not Present

          Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

          1 = Off|2 = On3 = Not Present

          Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

          1 = Off2 = On3 = Not Present

          Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

          1 = Off2 = On3 = Not Present

          Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

          1 = Off2 = On3 = Not Present

          Table 7 Multistate Input (continued)

          BCI-I Object Identifier Object Name Description Object States

          30 ACC-SVP01B-EN bull BCI-I Integration Guide

          Object Data Points and Diagnostic Data Points

          Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

          1 = Off2 = On3 = Not Present

          Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

          1 = Off2 = On3 = Not Present

          Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

          Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

          Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

          Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

          Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

          1 = Off2 = On3 = Not Present

          Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

          1= Off2= On3= Not Present

          Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

          Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

          Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

          Multi-State Input 43 Outdoor Air Damper Status

          Indicates the operating state of the outdoor damper

          1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

          Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

          1 = Disabled2 = Enabled3 = Not Present

          Table 8 Binary Output

          Object Identifier Object Name DescriptionRelinquish Default Object States

          Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

          Active = BAS Control

          Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

          Active = Heating Locked Out

          Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

          Active = Cooling Locked Out

          Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

          Active = Enabled

          Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

          Active = On

          Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

          Inactive Inactive = DisabledActive = Enabled

          Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

          Active = Reset

          Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

          Active = Reset

          Table 7 Multistate Input (continued)

          BCI-I Object Identifier Object Name Description Object States

          ACC-SVP01B-EN bull BCI-I Integration Guide 31

          Object Data Points and Diagnostic Data Points

          Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

          Active = Auto

          Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

          Active = Auto

          Table 9 Binary Input

          Object Identifier Object Name Description Object States

          Binary Input 1 System Control Status Indicates the control system currently in command of the unit

          Inactive = Standalone controlActive = BAS control

          Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

          Inactive = NormalActive = Locked Out

          Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

          Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

          Inactive = AutoActive = Open

          Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

          Inactive = InactiveActive = Active

          Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

          Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

          Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

          Inactive = DisabledActive = Enabled

          Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

          Inactive = DisabledActive = Enabled

          Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

          Inactive = InactiveActive = Active

          Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

          Inactive = No FlowActive = Flow

          Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

          Inactive = InactiveActive = Active

          Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

          Inactive = InactiveActive = Active

          Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

          Inactive = InactiveActive = Active

          Binary Input 161 Evaporator Frost Protection Circuit 1 Status

          The status of evaporator frost protection function for circuit 1

          Inactive = InactiveActive = Active

          Binary Input 162 Evaporator Frost Protection Circuit 2 Status

          The status of evaporator frost protection function for circuit 2

          Inactive = InactiveActive = Active

          Binary Input 163 Evaporator Frost Protection Circuit 3 Status

          The status of evaporator frost protection function for circuit 3

          Inactive = InactiveActive = Active

          Binary Input 164 Evaporator Frost Protection Circuit 4 Status

          The status of evaporator frost protection function for circuit 4

          Inactive = InactiveActive = Active

          Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

          Inactive = De-energizedActive = Energized

          Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

          Inactive = InactiveActive = Active

          Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

          Inactive = ClosedActive = Open

          Table 10 Diagnostics Binary Input

          Object Identifier(a) Object Name Description

          Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

          Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

          Binary Input 31 (use Object Identifier for RT or CSC)

          Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

          Binary Input 31 (use Object Identifier for FAU)

          Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

          Table 8 Binary Output

          Object Identifier Object Name DescriptionRelinquish Default Object States

          32 ACC-SVP01B-EN bull BCI-I Integration Guide

          Object Data Points and Diagnostic Data Points

          Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

          Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

          Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

          Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

          Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

          Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

          Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

          Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

          Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

          Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

          Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

          Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

          Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

          Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

          Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

          Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

          Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

          Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

          Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

          Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

          Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

          Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

          Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

          Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

          Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

          Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

          Binary Input 58 (use Object Identifier for RT or CSC)

          Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

          Binary Input 58 (use Object Identifier for FAU)

          Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

          Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

          Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

          Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

          Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

          Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

          Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

          Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

          Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

          Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

          Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

          Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

          Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

          Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

          Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

          Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

          Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

          Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

          Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

          Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

          Table 10 Diagnostics Binary Input (continued)

          Object Identifier(a) Object Name Description

          ACC-SVP01B-EN bull BCI-I Integration Guide 33

          Object Data Points and Diagnostic Data Points

          Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

          Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

          Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

          Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

          Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

          Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

          Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

          Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

          Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

          Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

          Binary Input 86 (use Object Identifier for RT I-pak II)

          Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

          Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

          Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

          Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

          Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

          Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

          Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

          Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

          Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

          Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

          Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

          Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

          Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

          Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

          Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

          Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

          Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

          Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

          Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

          Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

          Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

          Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

          Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

          Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

          Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

          Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

          Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

          Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

          Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

          Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

          Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

          Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

          Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

          Binary Input 121 (use Object Identifier for RT)

          Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

          Binary Input 121 (use Object Identifier for FAU)

          Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

          Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

          Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

          Table 10 Diagnostics Binary Input (continued)

          Object Identifier(a) Object Name Description

          34 ACC-SVP01B-EN bull BCI-I Integration Guide

          Object Data Points and Diagnostic Data Points

          Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

          Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

          Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

          Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

          Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

          Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

          Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

          Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

          Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

          Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

          Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

          Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

          Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

          Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

          Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

          Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

          Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

          Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

          Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

          Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

          Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

          Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

          Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

          Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

          Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

          Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

          (a) Object States Inactive = normal and Active = foreign language specific

          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

          Object Identifier(a) Object Name Description

          Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

          Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

          Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

          Analog Input 80 Cabinet Style Describes the cabinet style of the unit

          Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

          Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

          Multi-State Input 10 Condenser Type General description of the equipment condenser system

          Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

          Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

          Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

          Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

          Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

          Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

          Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

          Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

          Table 10 Diagnostics Binary Input (continued)

          Object Identifier(a) Object Name Description

          ACC-SVP01B-EN bull BCI-I Integration Guide 35

          Object Data Points and Diagnostic Data Points

          Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

          Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

          Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

          Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

          Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

          Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

          Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

          Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

          Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

          Analog Input 81 Cool Type Describes the cooling type installed in the unit

          Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

          Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

          Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

          Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

          Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

          Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

          Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

          Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

          Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

          Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

          Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

          Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

          Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

          Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

          Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

          Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

          Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

          Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

          Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

          Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

          Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

          Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

          Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

          Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

          Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

          Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

          Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

          Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

          Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

          Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

          Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

          Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

          Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

          Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

          Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

          Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

          Object Identifier(a) Object Name Description

          36 ACC-SVP01B-EN bull BCI-I Integration Guide

          Object Data Points and Diagnostic Data Points

          Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

          Multi-State Input 9 Economizer Type General description of the equipment economizer system

          Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

          Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

          Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

          Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

          Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

          Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

          Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

          Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

          Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

          Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

          Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

          Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

          Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

          Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

          Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

          Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

          Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

          Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

          Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

          Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

          Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

          Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

          Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

          Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

          Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

          Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

          Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

          Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

          Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

          Multi-State Input 36 Final Filter Status Indicates the final filter media state

          Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

          Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

          Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

          Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

          Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

          Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

          Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

          Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

          Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

          Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

          Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

          Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

          Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

          Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

          Object Identifier(a) Object Name Description

          ACC-SVP01B-EN bull BCI-I Integration Guide 37

          Object Data Points and Diagnostic Data Points

          Binary Output 16 Humidification Command Command the operating state of the humidification system

          NC 3 HVAC-Advisory HVAC-Advisory

          NC 1 HVAC-Critical HVAC-Critical

          NC 4 HVAC-Information HVAC-Information

          NC 2 HVAC-Service Required HVAC-Service Required

          Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

          Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

          Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

          Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

          Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

          Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

          Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

          Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

          Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

          Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

          Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

          Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

          Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

          Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

          Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

          Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

          Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

          Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

          Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

          Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

          Multi-State Input 34 Prefilter Status Indicates the prefilter media state

          Analog Input 82 Preheat Type Describes the heating type installed in the unit

          Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

          Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

          Analog Input 83 Reheat Type Describes the reheat type installed in the unit

          Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

          Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

          Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

          Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

          Multi-State Input 42 Return Fan Status Indicates the state of the return fan

          Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

          Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

          Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

          Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

          Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

          Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

          Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

          Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

          Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

          Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

          Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

          Object Identifier(a) Object Name Description

          38 ACC-SVP01B-EN bull BCI-I Integration Guide

          Object Data Points and Diagnostic Data Points

          Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

          Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

          Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

          Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

          Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

          Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

          Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

          Analog Input 15 Space Temperature Active The space temperature currently used for unit control

          Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

          Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

          Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

          Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

          Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

          Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

          Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

          Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

          Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

          Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

          Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

          Binary Input 1 System Control Status Indicates the control system currently in command of the unit

          Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

          Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

          Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

          Binary Input 3 Unit Status Indicates the current state of the unit

          Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

          Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

          Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

          Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

          Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

          Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

          Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

          (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

          Object Identifier(a) Object Name Description

          Table 12 Diagnostic Objects Sorted by Object Name

          Object Identifier(a) Object Name ValueRange Description

          BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

          BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

          ACC-SVP01B-EN bull BCI-I Integration Guide 39

          Object Data Points and Diagnostic Data Points

          BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

          BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

          BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

          BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

          BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

          BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

          BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

          BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

          BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

          BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

          BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

          BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

          BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

          BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

          BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

          BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

          BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

          BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

          BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

          BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

          BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

          BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

          BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

          BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

          BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

          BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

          BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

          BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

          BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

          Table 12 Diagnostic Objects Sorted by Object Name (continued)

          Object Identifier(a) Object Name ValueRange Description

          40 ACC-SVP01B-EN bull BCI-I Integration Guide

          Object Data Points and Diagnostic Data Points

          BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

          BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

          BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

          BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

          BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

          BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

          BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

          BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

          BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

          BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

          BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

          BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

          BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

          BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

          BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

          BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

          BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

          BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

          BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

          BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

          BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

          BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

          BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

          BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

          BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

          BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

          BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

          BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

          BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

          Table 12 Diagnostic Objects Sorted by Object Name (continued)

          Object Identifier(a) Object Name ValueRange Description

          ACC-SVP01B-EN bull BCI-I Integration Guide 41

          Object Data Points and Diagnostic Data Points

          BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

          BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

          BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

          BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

          BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

          BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

          BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

          BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

          BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

          BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

          BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

          BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

          BI 121 (use Object Identifier for RT)

          Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

          BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

          BI 58 (use Object Identifier for RT or CSC)

          Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

          BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

          BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

          BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

          BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

          BI 31 (use Object Identifier for RT CSC)

          Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

          BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

          BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

          BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

          BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

          BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

          BI 121 (use Object Identifier for FAU)

          Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

          B1 31 (use Object Identifier for FAU)

          Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

          BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

          BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

          Table 12 Diagnostic Objects Sorted by Object Name (continued)

          Object Identifier(a) Object Name ValueRange Description

          42 ACC-SVP01B-EN bull BCI-I Integration Guide

          Object Data Points and Diagnostic Data Points

          BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

          BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

          BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

          BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

          BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

          BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

          BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

          BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

          BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

          BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

          BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

          BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

          BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

          BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

          BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

          BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

          BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

          BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

          BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

          BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

          BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

          BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

          BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

          1 = active Diagnostic Vel Press Sensor (Rear)

          BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

          Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

          BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

          BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

          BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

          BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

          BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

          Table 12 Diagnostic Objects Sorted by Object Name (continued)

          Object Identifier(a) Object Name ValueRange Description

          ACC-SVP01B-EN bull BCI-I Integration Guide 43

          Object Data Points and Diagnostic Data Points

          BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

          BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

          BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

          BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

          BI 58 (use Object Identifier for FAU)

          Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

          (a) BI=Binary Input

          Table 12 Diagnostic Objects Sorted by Object Name (continued)

          Object Identifier(a) Object Name ValueRange Description

          44 ACC-SVP01B-EN bull BCI-I Integration Guide

          Additional Resources

          Additional Resources

          Use the following documents and links as additional resources

          bull Product support online

          bull wwwbacnetorg

          bull wwwbacnetassociationorg

          bull wwwashraeorg

          bull Tracer TU Help online

          bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

          bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

          Note For further assistance contact your local Trane sales office

          ACC-SVP01B-EN bull BCI-I Integration Guide 45

          Glossary

          A

          ASHRAE

          See American Society of Heating Refrigeration and Air-conditioning Engineers

          American Society of Heating Refrigeration and Air-

          conditioning Engineers

          An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

          BBACnettrade

          See Building Automation Control network

          BACnet interoperability building blocks

          A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

          BACnet object

          An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

          baud rate

          The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

          BIBB

          See BACnet interoperability building blocks

          Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

          advocates BACnet protocol for use in system-level control devices

          device

          A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

          Device ID

          The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

          Iinteroperability

          The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

          Pprotocol

          A set of rules (language) that governs the exchange of data over a digital communications system

          S

          stand-alone operation

          Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

          wwwtranecom

          For more information contact your local Trane office or e-mail us at comforttranecom

          Literature Order Number ACC-SVP01B-EN

          Date September 2009

          Supersedes ACC-SVP01A-EN

          Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

          • Table of Contents
          • Overview
          • Ordering Numbers
          • BACnet Protocol
          • BCI-I Configuration
            • Overview
            • Starting a Session of Tracer TU and Direct Connection
            • Reset to Factory Default
            • IP Units Configuration
            • BACnet Object Configuration
            • Change Baud Rate
            • Change Device ID
            • Stand-alone or BAS Operation
              • IntelliPak Control Configuration
              • BAS Unit Control
              • Periodic Update of BAS Values
              • BAS Communication Failure
                • InputOutput Commands and Calculations
                  • System Control Command
                  • Filter Timer Reset Command
                  • Diagnostics Reset Command
                  • Setpoint Calculations
                  • Timestamp Configuration
                      • BCI IntelliPak Rotary Switches and LEDs
                        • Rotary Switches
                        • LEDs Description Behavior and Troubleshooting
                        • 24 Vac Measurement
                        • Ground Measurements
                          • BACnet Data Points and Configuration Property Definitions
                            • BACnet Protocol Implementation Conformance Statement (PICS)
                              • Standardized Device Profile (Annex L)
                              • Interoperability Building Blocks (Annex K)
                              • Segmentation Capability
                              • Object Types
                                • BACnet Protocol
                                  • Data Link Layer Options
                                  • Device Address Binding
                                  • Networking Options
                                  • Character Sets
                                      • Object Data Points and Diagnostic Data Points
                                      • Additional Resources
                                      • Glossary

            6 ACC-SVP01B-EN bull BCI-I Integration Guide

            BCI-I Configuration

            Reset to Factory Default

            Factory default mode is the only mode the technician can use to set the units of measure for the device or to scan the IntelliPak unit to create BACnet objects The process of putting the device in factory default mode must be run prior to executing units of measure configuration or the object self-configuration process

            WARNING Remove power from the HVAC equipment before

            opening electrical control panel

            To reset the controller to factory defaultunconfigured state

            1 Power down the unit The IMC buss must not be active during reset

            2 Establish the connection between Tracer TU and the device Follow the procedure ldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

            3 From the Utilities menu select Controller and then Controller Settings The Controller Settings page appears

            4 On the controller settings page there is a gray bar at the bottom with SaveCancel buttons Move the cursor near the left edge of the bar keeping the cursor inside the bar Click on this area and a Clear Controller button will appear in the upper right portion of the page

            5 Click the Clear Controller button and a pop-up window will appear asking for confirmation to reset the device Click Yes

            6 After a few seconds a pop-up will appear confirming that the controller has been reset and indicating that the controller will be rebooted Click OK

            After the controller boots up it will be in factory default state The units of measure is SI (metric) the MSTP baud rate is 76800 and there will be no BACnet objects present in the controller

            The controller must be in this state prior to changing the units of measure or self-configuring the device If using inch-pound units of measure proceed to the next section ldquoIP Units Configuration otherwise proceed to ldquoBACnet Object Configuration

            IP Units Configuration

            The BCI-I supports both inch-pound and SI (metric) units of measure The factory default units of measure is SI The device allows only a change of units for all objects as a whole Mixed units of measure is not allowed If the controller is not in factory default state follow the previous procedure ldquoReset to Factory Defaultrdquo p 6

            To change the units of measure in the device

            1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

            2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Controller Units frame

            3 In the Device Units box of the frame select IP units of measure radio button and then click Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Select OK

            4 Exit Tracer TU and cycle power to the controller by disconnecting the USB plug and then reconnecting the plug After the controller boots up it will be in factory default state the units of measure is IP the MSTP baud rate is 76800 and there will be no BACnet objects present in the controller

            ACC-SVP01B-EN bull BCI-I Integration Guide 7

            BCI-I Configuration

            BACnet Object Configuration

            Configuring BACnet objects is a self-configuring process If the controller is not in factory default state follow the previous procedure ldquoReset to Factory Defaultrdquo p 6

            1 Remove the USB cable plug from the device

            2 Apply power to the HVAC equipment After the device boots up the self-configuration process will begin No further user action is required

            Note Do not remove power while the device is in self-configuration mode This typically takes 2 to 4 minutes to complete Once complete the device enters normal operating mode

            Change Baud Rate

            The BCI-I device supports four baud rates 9600 19200 38400 and 76800 baud The default baud rate is 76800 baud The baud rate can be modified with Tracer TU

            WARNING Remove power from the HVAC equipment before opening electrical control panel

            To change baud rate

            1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

            2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Protocol frame

            3 Click on the drop down arrow for the Baud Rate list and select the desired baud rate

            4 Click Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Click OK

            5 Exit Tracer TU and disconnect the USB cable plug

            6 Apply power to the HVAC equipment

            Change Device ID

            By default the BCI-I device sets its device ID to the same value as the one defined by the rotary switches (MSTP MAC address) on the front of the device Refer to the section ldquoRotary Switchesrdquo p 12 For simple networks this is an easy method to guarantee unique device IDs across the link

            The device also supports the full range of device ID values as specified by the BACnet Standard Systems that require a more complex device ID convention are supported with Tracer TU which has the ability to set the device ID via software configuration

            WARNING Remove power from the HVAC equipment before opening electrical control panel

            The process for soft setting the device ID is as follows

            1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

            2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Protocol frame

            3 In the device ID box select the check box next to Use Software Device ID to enable the functionality The swipe-and-type box becomes available

            4 Type in the desired device ID

            8 ACC-SVP01B-EN bull BCI-I Integration Guide

            BCI-I Configuration

            5 Click the Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Click OK

            6 Exit Tracer TU and disconnect the USB service plug

            7 Apply power to the HVAC equipment

            Stand-alone or BAS Operation

            The control system on HVAC equipment has the ability to operate the unit as a stand-alone system or as part of a building automation system The BCI-I (either factory or field installed) by default is configured for stand-alone operation This configuration enables the HVAC equipment to operate prior to the commissioning of the unit into the BAS

            IntelliPak Control Configuration

            The IntelliPak control system must be configured at the human interface (HI) to support unit control from the BAS The technician should setverify the following configuration properties as illustrated below The technician should also verify that the BAS Module Comm Failure diagnostic is not present

            BAS Unit Control

            The BCI-I provides a method for a BAS to control the operation of HVAC equipment This method consists of BACnet objects that the BAS can access to control and monitor the status of equipment There are two sets of objects

            bull Output objects used by the BAS to provide command setpoint and sensor information to the IntelliPak unit

            bull Input objects provide IntelliPak status information to the BAS See tables 3 to 11 for the list of objects supported

            The system allows the BAS technician to define the amount of control that the BAS system will apply to the unit This is done by configuring the state of the Out of Service property of the output objects If the property is set to True the equipment will use a corresponding local value for control If the property is set to False the local value is ignored and the BAS-supplied value is used for control The BAS value is provided to the IntelliPak by writing to the present value property of the corresponding output object The factory default value for the Out of Service property of these objects is True

            1 Configuration Menu

            2 Setup Menu

            3 Diagnostics Menu

            Software Revision NumberBAS Communications BACnet 1801

            Configuration - Model Num Digit 34BAS Communication Module Installed

            Unit Control BASNETWORK

            Active Diagnostic - - Auto ResetNone

            Human Interface Representation

            ACC-SVP01B-EN bull BCI-I Integration Guide 9

            BCI-I Configuration

            Periodic Update of BAS Values

            The BCI-I device requires the BAS system to provide a periodic update to the sensor values This is required to protect against a loss of communication between the BAS and the BCI-I By BACnet definition the present value of the object will maintain the last value written to it regardless of the amount of time that has elapsed since the last write If communication is lost for several minutes or longer the present value of BAS-supplied sensor objects may no longer represent the current state of environmental conditions This may result in decreased occupant comfort and damage to building systems

            BAS Communication Failure

            The BCI-I is designed to minimize communication failure mode It does this by monitoring the length of time that has elapsed since the last write to the present value of the sensor object If the length of time exceeds a predefined limit the BCI-I will place the object into the fault state and revert to a unit-supplied sensor value for control At power up the sensor objects are set to a fault state and they will remain in this state until a write is detected The minimum periodic refresh rate for the objects is defined in Table 3 p 24 The following list is a set of sensor values that can be supplied by the BAS

            bull Space Static Pressure BAS

            bull Space Air Temperature BAS

            bull Discharge Air Temperature BAS

            bull Duct Static Air Pressure BAS

            bull Outdoor Air Temperature BAS

            bull Outdoor Air Humidity BAS

            bull Outdoor Airflow BAS

            bull Space CO2 Concentration BAS

            bull Space Humidity BAS

            InputOutput Commands and Calculations

            This section will provide the following information about certain inputs and outputs that perform unique control commands and calculations

            bull System control command

            bull Filter timer and diagnostic reset commands

            bull Setpoint calculations

            System Control Command

            Binary Output Object 1 has a special importance in the system The object allows the BAS to command the unit to run in a local or BAS control mode When the present value property of the object is set to Local Control the IntelliPak unit will enter local control and ignore BAS supplied values In this mode the unit will use local sensor and setpoint values When the object present value property is set to BAS Control the IntelliPak unit will use the values supplied by the BAS system for unit control

            Filter Timer Reset Command

            The BCI-I uses the Filter Runtime Hours object (AI 6) to generate a diagnostic when its present value is greater than the Filter Runtime Hours Setpoint (AV 1) present value The procedure for resetting the timer is as follows

            10 ACC-SVP01B-EN bull BCI-I Integration Guide

            BCI-I Configuration

            The BAS will change the state of the Filter Timer Reset Command object (BO 13) to the active state Upon the change to active state the BCI-I will set the present value of the Filter Runtime Hours object to zero and then set the Reset Command object back to the inactive state

            Diagnostics Reset Command

            The IntelliPak control system monitors the operation of the HVAC equipment If an abnormal condition is detected a diagnostic message is displayed on the human interface of the equipment control panel In addition the set of internal diagnostics is mapped to the set of BACnet binary input objects as listed in Table 9 p 31 The corresponding BI object will change state from inactive to active when the diagnostic is detected The object has been configured to send a BACnet event message to external BACnet devices as defined by the protocol

            The BAS has the ability to reset internal diagnostics by controlling the state of the Diagnostic Reset Command object (BO 14) The procedure for resetting diagnostics is as follows

            The BAS will change the state of the Diagnostic Reset to the active state Upon the change to active state the IntelliPak control system will reset all internal diagnostics and set the state of all of the diagnostic objects to inactive Upon completion of this action the BCI-I will set the present value of the Diagnostic Reset Command object back to the inactive state

            Setpoint Calculations

            The equipment has the ability to perform two basic control functions

            bull Space air temperature control

            bull Discharge air temperature control

            When the unit is configured for discharge air control it controls the temperature of the air leaving the unit to the discharge air temperature setpoint

            When the unit is configured for space air temperature control it controls the air temperature of the space that contains the space air temperature sensor This value may be provided by wiring the sensor to the unit or via a sensor value provided by the BAS

            The drawing below describes how the various temperature setpoints are calculated for space temperature control When the unit is in an occupied mode the active space temperature setpoint is calculated based on the space temperature setpoint and the two setpoint offset values In unoccupied mode the unoccupied heating and cooling setpoints are used as the active setpoint

            ACC-SVP01B-EN bull BCI-I Integration Guide 11

            BCI-I Configuration

            Timestamp Configuration

            The BCI-C device has a software-derived clock that maintains the time and date The device requires the current time to enable it to record a timestamp when an event or a change in state is detected by a BACnet object However in the event of a power loss the device does not maintain this time and date information At powerup the device time and date will default to 1200 pm Jan 1 1970 To minimize the possibility that the unit timestamp is not representing the actual time the BAS should be setup to periodically synchronize the device time clock with the BAS clock using the BACnet TimeSynchronization service

            12 ACC-SVP01B-EN bull BCI-I Integration Guide

            BCI IntelliPak Rotary Switches and LEDs

            BCI IntelliPak Rotary Switches and LEDs

            This section provides information about the BCI-I rotary switches and LED displays

            Rotary Switches

            There are three rotary switches on the front of the BCI-I device that are used to define a three-digit address when the BCI-I is installed on a BACnet communications network The three-digit address setting is the BACnet MAC address

            Note All devices are MSTP masters with valid MAC addresses of 001 to 127 for BACnet

            Figure 1 Setting rotary switches

            ADDRESS0 1

            23

            456

            78

            9

            x1

            0 1

            23

            456

            78

            9

            x10

            0 1

            23

            456

            78

            9

            x100

            Before

            After

            0

            5

            1

            3

            6

            29

            487

            Example of before and after setting addresses

            Use a 18 inch flathead screwdriver to set rotary switches

            Important Each device on the BACnetMSTP link must have a unique rotary switch setting otherwise communication problems will occur

            ACC-SVP01B-EN bull BCI-I Integration Guide 13

            BCI IntelliPak Rotary Switches and LEDs

            LEDs Description Behavior and Troubleshooting

            There are 15 LEDs on the front of the BCI-I unit However LEDs BO1 through BO9 are not used for the BCI-I controller Figure 2 shows the locations of each LED The following table provides a description of each LED activity an indication or troubleshooting tips for each and any notes

            Figure 2 LED locations

            SERVICE

            IMCLINK

            RX

            TX

            Marquee LED

            Table 1 LED Activities and Troubleshooting Tips

            LED Name ActivitiesIndication or Troubleshooting

            Tip (Denoted in Bullets) Notes

            Marquee LED

            Shows solid green when the unit is powered and no problems exist

            Indicates normal operation

            Shows solid red when the unit is powered but represents low power or a

            malfunction

            bull If low power could be under voltage or the microprocessor has malfunction Follow the troubleshoot procedure ldquo24 Vac Measurementrdquo p 15 to measure for the expected value range

            bull If malfunction unpower and then repower unit to bring the device back up to normal operation

            Shows blinking red when an a BACnet object is in a fault condition

            Alarm when an alarm is triggered for example when a point goes into fault condition because of point failure or there is an indication of a custom alarm in TGP2

            Shows blinking green when the device does not detect the IMC buss

            bull Verify that the IPC wiring harness is connected to the IMC link terminals

            bull Verify the polarity of the IPC wiring harness at the unit terminals

            LED not lit

            Indicates power is OFF or there is a malfunction

            bull OFF or malfunction cycle the power

            14 ACC-SVP01B-EN bull BCI-I Integration Guide

            BCI IntelliPak Rotary Switches and LEDs

            Link and IMC

            TX blinks greenBlinks at the data transfer rate when the unit transfers data to other devices on the link

            TX LED Regardless of connectivity or not this LED will constantly blink as it continually looks for devices to communicate to

            LED not litDetermine if for example a Tracer SC or BACnet device is trying to talk to the controller or if it is capable of talking to the controller Also determine if the communication status shows down all of the time

            Refer to ldquoGround Measurementsrdquo p 16 for a check-out procedure

            RX blinks yellow

            Blinks at the data transfer rate when the unit receives data from other devices on the link

            bull ON solid yellow indicates there is reverse polarity

            LED not lit

            Indicates that the controller is not detecting communication

            bull Not lit cycle the power to reestablish communication

            Service

            Shows solid greenIndicates someone is pressing this LED or the controller is not operating normally

            Press and hold during power up to place controller into boot code or press and hold for a count of approximately 10 seconds to clear the Device ID

            What is Boot Code When the UC400 is placed into boot code the system will not run any applications such as trending scheduling and TGP2 runtime

            Blinks green

            Indicates controllers is not accessing application software

            bull Restore using TU service tool

            LED not lit Indicates controller is operating normally

            Binary 01 to Binary 09 Not Used

            Table 1 LED Activities and Troubleshooting Tips

            LED Name ActivitiesIndication or Troubleshooting

            Tip (Denoted in Bullets) Notes

            ACC-SVP01B-EN bull BCI-I Integration Guide 15

            BCI IntelliPak Rotary Switches and LEDs

            24 Vac Measurement

            General Information Checkout Procedure Measurement Expected Value

            Checking the voltage that is powering the UC400 is often a necessary step when commissioning or troubleshooting Operational issues and LED operation may result in a need to measure the input power

            When troubleshooting it is faster to take measurements while the load is in place If Step 1 indicates an out-of-specification voltage disconnect the UC400 and measure the AC voltage across the transformer These measurements can direct the technician towards the problem source

            Step 1

            Measure AC voltage with the UC400 connected Perform this measurement while the unit is under load

            200 Vac le Vac le 300 Vac

            Step 2

            Measure AC voltage with the UC400 unconnected Perform this measurement while the unit is not under load

            200 Vac le Vac le 300 Vac

            16 ACC-SVP01B-EN bull BCI-I Integration Guide

            BCI IntelliPak Rotary Switches and LEDs

            Ground Measurements

            General Information and Checkout Procedure Measurement Expected Value

            Method 1AC voltage between shield conductors and device chassis ground- the voltage difference between BACnet MSTP device chassis ground connections should be close to zero If the voltage difference is greater that 40 Vac there will be marginal communication or intermittent communication problems If the voltage difference is greater that 70 Vac some devices will no longer communicate

            Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

            Vac le 20 V

            Method 2AC voltage between earth ground and device chassis ground- the chassis ground of the UC400 needs to be connected to earth ground by some route

            Note Do not assume that the building frame is a valid earth ground

            Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

            Vac le 40 V (Must comply with National Electrical Codetradeand local electrical codes)

            ACC-SVP01B-EN bull BCI-I Integration Guide 17

            BACnet Data Points and Configuration Property Definitions

            BACnet Data Points and Configuration Property

            Definitions

            The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MSTP This section includes information about

            bull BACnet protocol implementation conformance statement (PICS)

            bull Object types descriptions and configuration (refer to Table 2 p 19)

            bull BACnet protocol data link layers device address binding networking options and character sets

            bull Object data points and configurations

            BACnet Protocol Implementation Conformance Statement (PICS)

            Standardized Device Profile (Annex L)

            Interoperability Building Blocks (Annex K)

            Profile Description Supported Profile

            BACnet Advanced Application Controller (B-AAC)

            BACnet Application Specific Controller (B-ASC)

            BACnet Building Controller (B-BC)

            BACnet Operator Workstation (B-OWS)

            BACnet Smart Actuator (B-SA)

            BACnet Smart Sensor (B-SS)

            Data Sharing Description Supported BIBB

            Data Sharing-COV-B (DS-COV-B)

            Data Sharing-ReadProperty-A (DS-RP-A)

            Data Sharing-ReadProperty-B (DS-RP-B)

            Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)

            Data Sharing-WriteProperty-A (DS-WP-A)

            Data Sharing-WriteProperty-B (DS-WP-B)

            Data Sharing-WritePropertyMultiple-B (DS-WPM-B)

            Alarm and Event Management Description Supported BIBB

            Alarm and Event-ACKI-B (AE-ACK-B)

            Alarm and Event-Alarm Summary-B (AE-ASUM-B)

            Alarm and Event-Enrollment Summary-B (AE-ESUM-B)

            Alarm and Event-Information-B (AE-INFO-B)

            Alarm and Event-Notification Internal-B (AE-N-I-B)

            18 ACC-SVP01B-EN bull BCI-I Integration Guide

            BACnet Data Points and Configuration Property Definitions

            Segmentation Capability

            Trending Description Supported BIBB

            Trending-Automated Trend Retrieval-B (T-ATR-B)

            Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

            Device Management Description Supported BIBB

            Device Management-Backup and Restore-B (DM-BR-B)

            Device Management-Device Communication Control-B (DM-DCC-B)

            Device Management-Dynamic Device Binding-A (DM-DDB-A)

            Device Management-Dynamic Device Binding-B (DM-DDB-B)

            Device Management-Dynamic Object Binding-B (DM-DOB-B)

            Device Management-List Manipulation-B (DM-LM-B)

            Device Management-Object Creation and Deletion-B (DM-OCD-B)

            Device Management-Private Transfer-A (DM-PT-A)

            Device Management-Private Transfer-B (DM-PT-B)

            Device Management-Reinitialize Device-B (DM-RD-B)

            Device Management-TimeSynchronization-B (DM-TS-B)

            Segmentation Description Supported Segment

            Segmented Requests Window Size 1

            Segmented Responses Window Size 1

            ACC-SVP01B-EN bull BCI-I Integration Guide 19

            BACnet Data Points and Configuration Property Definitions

            Object Types

            Table 2 Descriptions and configurations

            Object Type Required Properties Read Properties Written(a) Optional Properties Read

            Ability to Create

            Ability to Delete

            Analog Input

            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

            bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

            bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

            Yes Yes only user created objects

            Analog Output

            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

            bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

            bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

            Yes Yes only user created objects

            Analog Value

            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

            bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

            bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

            Yes Yes only user created objects

            Binary Input

            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

            bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

            bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

            Yes Yes only user created objects

            20 ACC-SVP01B-EN bull BCI-I Integration Guide

            BACnet Data Points and Configuration Property Definitions

            Binary Output

            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

            bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

            bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

            Yes Yes only user created objects

            Binary Value

            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

            bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

            bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

            Yes Yes only user created objects

            Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

            bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

            bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

            None None

            Event Enrollment Object

            bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

            bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

            bull None Yes Yes only user created objects

            Table 2 Descriptions and configurations (continued)

            Object Type Required Properties Read Properties Written(a) Optional Properties Read

            Ability to Create

            Ability to Delete

            ACC-SVP01B-EN bull BCI-I Integration Guide 21

            BACnet Data Points and Configuration Property Definitions

            Multistate Input

            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

            bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

            bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

            Yes Yes only user created objects

            Multistate Output

            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

            bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

            bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

            Yes Yes only user created objects

            Multistate Value

            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

            bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

            bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

            Yes Yes only user created objects

            Notification Class

            bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

            bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

            None Yes Yes only user created objects

            Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

            bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

            bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

            Yes Yes only user created objects

            (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

            Table 2 Descriptions and configurations (continued)

            Object Type Required Properties Read Properties Written(a) Optional Properties Read

            Ability to Create

            Ability to Delete

            22 ACC-SVP01B-EN bull BCI-I Integration Guide

            BACnet Data Points and Configuration Property Definitions

            BACnet Protocol

            Data Link Layer Options

            Device Address Binding

            Networking Options

            Data Link Layer Description Supported Option

            ANSIATA 8781 25 Mb ARCNET (Clause 8)

            ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

            BACnet IP (Annex J)

            BACnet IP (Annex J) Foreign Device

            ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

            LonTalk (Clause 11) Medium

            MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

            MSTP Slave (Clause 9) Baud Rate(s)

            Other

            Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

            Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

            Device Address Binding Supported

            Static Device Binding Supported

            Networking DescriptionsSupported

            Option

            Annex H BACnet Tunneling

            BACnetIP Broadcast Management Device (BBMD)

            Does the BBMD Support Registrations by Foreign Devices

            Router

            ACC-SVP01B-EN bull BCI-I Integration Guide 23

            BACnet Data Points and Configuration Property Definitions

            Character Sets

            Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

            Character Set Descriptions Supported

            ANSI X34

            IBMMicrosoft DBCS

            ISO 10646 (UCS-4)

            ISO 10646 (UCS2)

            ISO 8859-1

            JIS C 6226

            24 ACC-SVP01B-EN bull BCI-I Integration Guide

            Object Data Points and Diagnostic Data Points

            Object Data Points and Diagnostic Data Points

            For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

            Table 3 Analog Output

            Object Identifier Object Name Description Units Valid Range

            Refresh Rate

            (Sec)

            Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

            Percent (98) 0 to 100 NA

            Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

            Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

            Degrees-Fahrenheit (64) 500 to 900 NA

            Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

            BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

            Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

            Degrees-Fahrenheit (64) 400 to 900 NA

            Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

            Degrees-Fahrenheit (64) 400 to 1800 NA

            Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

            070 to 510 (Ipak II) NA

            Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

            003 to 030-002 to 030 (enhanced StatiTrac)

            NA

            Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

            -028 to 050-067 to 067 (enhanced StatiTrac)

            900

            Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

            Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

            Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

            00 to 79 (Ipak II) 900

            Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

            Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

            Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

            Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

            Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

            Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

            Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

            Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

            Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

            Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

            ACC-SVP01B-EN bull BCI-I Integration Guide 25

            Object Data Points and Diagnostic Data Points

            Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

            Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

            Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

            Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

            Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

            Cooling temperature setpoint used for control in unoccupied mode

            Degrees-Fahrenheit (64) 520 to 880 NA

            Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

            Heating temperature setpoint used for control in unoccupied mode

            Degrees-Fahrenheit (64) 500 to 900 NA

            Table 4 Analog Input

            Object Identifier Object Name Description Units (Listed Are Defaults)

            Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

            Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

            Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

            Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

            Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

            Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

            Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

            Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

            Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

            Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

            Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

            Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

            Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

            Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

            Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

            Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

            Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

            Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

            Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

            Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

            Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

            Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

            Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

            Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

            Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

            Table 3 Analog Output (continued)

            Object Identifier Object Name Description Units Valid Range

            Refresh Rate

            (Sec)

            26 ACC-SVP01B-EN bull BCI-I Integration Guide

            Object Data Points and Diagnostic Data Points

            Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

            Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

            Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

            Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

            Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

            Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

            Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

            Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

            Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

            Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

            Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

            Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

            Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

            Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

            Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

            Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

            Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

            Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

            Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

            Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

            Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

            Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

            Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

            Analog Input 54 Morning Warmup Air Temperature Setpoint Active

            The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

            Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

            The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

            Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

            Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

            Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

            Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

            Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

            Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

            Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

            Table 4 Analog Input (continued)

            Object Identifier Object Name Description Units (Listed Are Defaults)

            ACC-SVP01B-EN bull BCI-I Integration Guide 27

            Object Data Points and Diagnostic Data Points

            Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

            Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

            Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

            Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

            The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

            Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

            Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

            Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

            Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

            Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

            Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

            Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

            Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

            Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

            Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

            Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

            Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

            Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

            Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

            Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

            Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

            Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

            Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

            Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

            Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

            Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

            Table 5 Analog Value

            Object Identifier Object Name Description Units Valid Range

            Analog Value 1 Filter Runtime Hours Setpoint

            The setpoint value used by the filter run hours calculation

            Hours (71) 0 to 10000

            Table 4 Analog Input (continued)

            Object Identifier Object Name Description Units (Listed Are Defaults)

            28 ACC-SVP01B-EN bull BCI-I Integration Guide

            Object Data Points and Diagnostic Data Points

            Table 6 Multistate Output

            BCI-I Object Identifier Object Name Description Object States

            Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

            Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

            1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

            Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

            Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

            1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

            Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

            1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

            Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

            1 = Flow2 = No Flow3 = Auto

            Table 7 Multistate Input

            BCI-I Object Identifier Object Name Description Object States

            Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

            1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

            Multi-State Input 9 Economizer Type General description of the equipment economizer system

            1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

            Multi-State Input 10 Condenser Type General description of the equipment condenser system

            1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

            Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

            1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

            ACC-SVP01B-EN bull BCI-I Integration Guide 29

            Object Data Points and Diagnostic Data Points

            Multi-State Input 15 Economizer Decision Method

            Unit method to determine when the economizer system is enabled

            1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

            Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

            Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

            Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

            1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

            Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

            1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

            Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

            1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

            Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

            1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

            Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

            1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

            Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

            1 = Idle2 = On3 = Cancel

            Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

            1 = Off2 = On3 = Not Present

            Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

            1 = Off2 = On3 = Not Present

            Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

            1 = Off2 = On3 = Not Present

            Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

            1 = Off|2 = On3 = Not Present

            Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

            1 = Off2 = On3 = Not Present

            Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

            1 = Off2 = On3 = Not Present

            Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

            1 = Off2 = On3 = Not Present

            Table 7 Multistate Input (continued)

            BCI-I Object Identifier Object Name Description Object States

            30 ACC-SVP01B-EN bull BCI-I Integration Guide

            Object Data Points and Diagnostic Data Points

            Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

            1 = Off2 = On3 = Not Present

            Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

            1 = Off2 = On3 = Not Present

            Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

            Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

            Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

            Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

            Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

            1 = Off2 = On3 = Not Present

            Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

            1= Off2= On3= Not Present

            Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

            Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

            Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

            Multi-State Input 43 Outdoor Air Damper Status

            Indicates the operating state of the outdoor damper

            1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

            Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

            1 = Disabled2 = Enabled3 = Not Present

            Table 8 Binary Output

            Object Identifier Object Name DescriptionRelinquish Default Object States

            Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

            Active = BAS Control

            Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

            Active = Heating Locked Out

            Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

            Active = Cooling Locked Out

            Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

            Active = Enabled

            Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

            Active = On

            Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

            Inactive Inactive = DisabledActive = Enabled

            Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

            Active = Reset

            Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

            Active = Reset

            Table 7 Multistate Input (continued)

            BCI-I Object Identifier Object Name Description Object States

            ACC-SVP01B-EN bull BCI-I Integration Guide 31

            Object Data Points and Diagnostic Data Points

            Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

            Active = Auto

            Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

            Active = Auto

            Table 9 Binary Input

            Object Identifier Object Name Description Object States

            Binary Input 1 System Control Status Indicates the control system currently in command of the unit

            Inactive = Standalone controlActive = BAS control

            Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

            Inactive = NormalActive = Locked Out

            Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

            Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

            Inactive = AutoActive = Open

            Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

            Inactive = InactiveActive = Active

            Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

            Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

            Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

            Inactive = DisabledActive = Enabled

            Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

            Inactive = DisabledActive = Enabled

            Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

            Inactive = InactiveActive = Active

            Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

            Inactive = No FlowActive = Flow

            Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

            Inactive = InactiveActive = Active

            Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

            Inactive = InactiveActive = Active

            Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

            Inactive = InactiveActive = Active

            Binary Input 161 Evaporator Frost Protection Circuit 1 Status

            The status of evaporator frost protection function for circuit 1

            Inactive = InactiveActive = Active

            Binary Input 162 Evaporator Frost Protection Circuit 2 Status

            The status of evaporator frost protection function for circuit 2

            Inactive = InactiveActive = Active

            Binary Input 163 Evaporator Frost Protection Circuit 3 Status

            The status of evaporator frost protection function for circuit 3

            Inactive = InactiveActive = Active

            Binary Input 164 Evaporator Frost Protection Circuit 4 Status

            The status of evaporator frost protection function for circuit 4

            Inactive = InactiveActive = Active

            Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

            Inactive = De-energizedActive = Energized

            Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

            Inactive = InactiveActive = Active

            Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

            Inactive = ClosedActive = Open

            Table 10 Diagnostics Binary Input

            Object Identifier(a) Object Name Description

            Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

            Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

            Binary Input 31 (use Object Identifier for RT or CSC)

            Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

            Binary Input 31 (use Object Identifier for FAU)

            Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

            Table 8 Binary Output

            Object Identifier Object Name DescriptionRelinquish Default Object States

            32 ACC-SVP01B-EN bull BCI-I Integration Guide

            Object Data Points and Diagnostic Data Points

            Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

            Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

            Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

            Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

            Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

            Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

            Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

            Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

            Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

            Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

            Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

            Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

            Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

            Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

            Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

            Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

            Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

            Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

            Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

            Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

            Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

            Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

            Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

            Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

            Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

            Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

            Binary Input 58 (use Object Identifier for RT or CSC)

            Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

            Binary Input 58 (use Object Identifier for FAU)

            Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

            Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

            Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

            Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

            Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

            Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

            Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

            Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

            Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

            Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

            Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

            Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

            Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

            Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

            Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

            Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

            Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

            Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

            Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

            Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

            Table 10 Diagnostics Binary Input (continued)

            Object Identifier(a) Object Name Description

            ACC-SVP01B-EN bull BCI-I Integration Guide 33

            Object Data Points and Diagnostic Data Points

            Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

            Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

            Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

            Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

            Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

            Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

            Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

            Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

            Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

            Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

            Binary Input 86 (use Object Identifier for RT I-pak II)

            Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

            Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

            Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

            Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

            Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

            Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

            Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

            Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

            Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

            Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

            Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

            Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

            Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

            Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

            Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

            Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

            Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

            Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

            Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

            Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

            Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

            Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

            Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

            Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

            Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

            Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

            Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

            Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

            Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

            Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

            Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

            Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

            Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

            Binary Input 121 (use Object Identifier for RT)

            Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

            Binary Input 121 (use Object Identifier for FAU)

            Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

            Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

            Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

            Table 10 Diagnostics Binary Input (continued)

            Object Identifier(a) Object Name Description

            34 ACC-SVP01B-EN bull BCI-I Integration Guide

            Object Data Points and Diagnostic Data Points

            Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

            Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

            Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

            Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

            Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

            Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

            Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

            Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

            Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

            Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

            Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

            Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

            Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

            Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

            Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

            Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

            Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

            Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

            Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

            Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

            Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

            Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

            Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

            Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

            Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

            Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

            (a) Object States Inactive = normal and Active = foreign language specific

            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

            Object Identifier(a) Object Name Description

            Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

            Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

            Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

            Analog Input 80 Cabinet Style Describes the cabinet style of the unit

            Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

            Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

            Multi-State Input 10 Condenser Type General description of the equipment condenser system

            Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

            Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

            Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

            Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

            Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

            Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

            Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

            Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

            Table 10 Diagnostics Binary Input (continued)

            Object Identifier(a) Object Name Description

            ACC-SVP01B-EN bull BCI-I Integration Guide 35

            Object Data Points and Diagnostic Data Points

            Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

            Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

            Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

            Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

            Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

            Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

            Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

            Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

            Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

            Analog Input 81 Cool Type Describes the cooling type installed in the unit

            Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

            Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

            Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

            Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

            Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

            Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

            Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

            Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

            Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

            Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

            Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

            Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

            Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

            Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

            Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

            Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

            Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

            Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

            Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

            Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

            Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

            Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

            Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

            Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

            Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

            Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

            Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

            Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

            Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

            Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

            Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

            Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

            Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

            Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

            Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

            Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

            Object Identifier(a) Object Name Description

            36 ACC-SVP01B-EN bull BCI-I Integration Guide

            Object Data Points and Diagnostic Data Points

            Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

            Multi-State Input 9 Economizer Type General description of the equipment economizer system

            Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

            Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

            Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

            Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

            Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

            Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

            Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

            Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

            Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

            Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

            Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

            Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

            Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

            Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

            Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

            Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

            Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

            Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

            Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

            Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

            Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

            Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

            Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

            Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

            Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

            Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

            Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

            Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

            Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

            Multi-State Input 36 Final Filter Status Indicates the final filter media state

            Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

            Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

            Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

            Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

            Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

            Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

            Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

            Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

            Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

            Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

            Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

            Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

            Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

            Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

            Object Identifier(a) Object Name Description

            ACC-SVP01B-EN bull BCI-I Integration Guide 37

            Object Data Points and Diagnostic Data Points

            Binary Output 16 Humidification Command Command the operating state of the humidification system

            NC 3 HVAC-Advisory HVAC-Advisory

            NC 1 HVAC-Critical HVAC-Critical

            NC 4 HVAC-Information HVAC-Information

            NC 2 HVAC-Service Required HVAC-Service Required

            Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

            Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

            Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

            Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

            Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

            Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

            Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

            Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

            Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

            Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

            Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

            Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

            Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

            Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

            Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

            Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

            Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

            Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

            Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

            Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

            Multi-State Input 34 Prefilter Status Indicates the prefilter media state

            Analog Input 82 Preheat Type Describes the heating type installed in the unit

            Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

            Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

            Analog Input 83 Reheat Type Describes the reheat type installed in the unit

            Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

            Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

            Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

            Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

            Multi-State Input 42 Return Fan Status Indicates the state of the return fan

            Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

            Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

            Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

            Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

            Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

            Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

            Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

            Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

            Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

            Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

            Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

            Object Identifier(a) Object Name Description

            38 ACC-SVP01B-EN bull BCI-I Integration Guide

            Object Data Points and Diagnostic Data Points

            Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

            Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

            Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

            Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

            Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

            Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

            Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

            Analog Input 15 Space Temperature Active The space temperature currently used for unit control

            Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

            Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

            Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

            Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

            Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

            Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

            Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

            Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

            Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

            Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

            Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

            Binary Input 1 System Control Status Indicates the control system currently in command of the unit

            Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

            Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

            Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

            Binary Input 3 Unit Status Indicates the current state of the unit

            Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

            Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

            Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

            Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

            Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

            Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

            Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

            (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

            Object Identifier(a) Object Name Description

            Table 12 Diagnostic Objects Sorted by Object Name

            Object Identifier(a) Object Name ValueRange Description

            BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

            BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

            ACC-SVP01B-EN bull BCI-I Integration Guide 39

            Object Data Points and Diagnostic Data Points

            BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

            BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

            BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

            BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

            BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

            BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

            BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

            BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

            BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

            BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

            BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

            BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

            BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

            BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

            BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

            BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

            BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

            BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

            BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

            BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

            BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

            BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

            BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

            BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

            BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

            BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

            BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

            BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

            BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

            Table 12 Diagnostic Objects Sorted by Object Name (continued)

            Object Identifier(a) Object Name ValueRange Description

            40 ACC-SVP01B-EN bull BCI-I Integration Guide

            Object Data Points and Diagnostic Data Points

            BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

            BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

            BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

            BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

            BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

            BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

            BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

            BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

            BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

            BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

            BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

            BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

            BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

            BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

            BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

            BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

            BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

            BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

            BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

            BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

            BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

            BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

            BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

            BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

            BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

            BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

            BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

            BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

            BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

            Table 12 Diagnostic Objects Sorted by Object Name (continued)

            Object Identifier(a) Object Name ValueRange Description

            ACC-SVP01B-EN bull BCI-I Integration Guide 41

            Object Data Points and Diagnostic Data Points

            BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

            BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

            BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

            BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

            BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

            BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

            BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

            BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

            BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

            BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

            BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

            BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

            BI 121 (use Object Identifier for RT)

            Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

            BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

            BI 58 (use Object Identifier for RT or CSC)

            Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

            BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

            BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

            BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

            BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

            BI 31 (use Object Identifier for RT CSC)

            Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

            BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

            BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

            BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

            BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

            BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

            BI 121 (use Object Identifier for FAU)

            Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

            B1 31 (use Object Identifier for FAU)

            Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

            BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

            BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

            Table 12 Diagnostic Objects Sorted by Object Name (continued)

            Object Identifier(a) Object Name ValueRange Description

            42 ACC-SVP01B-EN bull BCI-I Integration Guide

            Object Data Points and Diagnostic Data Points

            BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

            BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

            BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

            BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

            BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

            BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

            BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

            BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

            BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

            BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

            BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

            BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

            BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

            BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

            BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

            BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

            BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

            BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

            BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

            BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

            BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

            BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

            BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

            1 = active Diagnostic Vel Press Sensor (Rear)

            BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

            Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

            BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

            BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

            BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

            BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

            BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

            Table 12 Diagnostic Objects Sorted by Object Name (continued)

            Object Identifier(a) Object Name ValueRange Description

            ACC-SVP01B-EN bull BCI-I Integration Guide 43

            Object Data Points and Diagnostic Data Points

            BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

            BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

            BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

            BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

            BI 58 (use Object Identifier for FAU)

            Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

            (a) BI=Binary Input

            Table 12 Diagnostic Objects Sorted by Object Name (continued)

            Object Identifier(a) Object Name ValueRange Description

            44 ACC-SVP01B-EN bull BCI-I Integration Guide

            Additional Resources

            Additional Resources

            Use the following documents and links as additional resources

            bull Product support online

            bull wwwbacnetorg

            bull wwwbacnetassociationorg

            bull wwwashraeorg

            bull Tracer TU Help online

            bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

            bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

            Note For further assistance contact your local Trane sales office

            ACC-SVP01B-EN bull BCI-I Integration Guide 45

            Glossary

            A

            ASHRAE

            See American Society of Heating Refrigeration and Air-conditioning Engineers

            American Society of Heating Refrigeration and Air-

            conditioning Engineers

            An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

            BBACnettrade

            See Building Automation Control network

            BACnet interoperability building blocks

            A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

            BACnet object

            An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

            baud rate

            The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

            BIBB

            See BACnet interoperability building blocks

            Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

            advocates BACnet protocol for use in system-level control devices

            device

            A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

            Device ID

            The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

            Iinteroperability

            The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

            Pprotocol

            A set of rules (language) that governs the exchange of data over a digital communications system

            S

            stand-alone operation

            Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

            wwwtranecom

            For more information contact your local Trane office or e-mail us at comforttranecom

            Literature Order Number ACC-SVP01B-EN

            Date September 2009

            Supersedes ACC-SVP01A-EN

            Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

            • Table of Contents
            • Overview
            • Ordering Numbers
            • BACnet Protocol
            • BCI-I Configuration
              • Overview
              • Starting a Session of Tracer TU and Direct Connection
              • Reset to Factory Default
              • IP Units Configuration
              • BACnet Object Configuration
              • Change Baud Rate
              • Change Device ID
              • Stand-alone or BAS Operation
                • IntelliPak Control Configuration
                • BAS Unit Control
                • Periodic Update of BAS Values
                • BAS Communication Failure
                  • InputOutput Commands and Calculations
                    • System Control Command
                    • Filter Timer Reset Command
                    • Diagnostics Reset Command
                    • Setpoint Calculations
                    • Timestamp Configuration
                        • BCI IntelliPak Rotary Switches and LEDs
                          • Rotary Switches
                          • LEDs Description Behavior and Troubleshooting
                          • 24 Vac Measurement
                          • Ground Measurements
                            • BACnet Data Points and Configuration Property Definitions
                              • BACnet Protocol Implementation Conformance Statement (PICS)
                                • Standardized Device Profile (Annex L)
                                • Interoperability Building Blocks (Annex K)
                                • Segmentation Capability
                                • Object Types
                                  • BACnet Protocol
                                    • Data Link Layer Options
                                    • Device Address Binding
                                    • Networking Options
                                    • Character Sets
                                        • Object Data Points and Diagnostic Data Points
                                        • Additional Resources
                                        • Glossary

              ACC-SVP01B-EN bull BCI-I Integration Guide 7

              BCI-I Configuration

              BACnet Object Configuration

              Configuring BACnet objects is a self-configuring process If the controller is not in factory default state follow the previous procedure ldquoReset to Factory Defaultrdquo p 6

              1 Remove the USB cable plug from the device

              2 Apply power to the HVAC equipment After the device boots up the self-configuration process will begin No further user action is required

              Note Do not remove power while the device is in self-configuration mode This typically takes 2 to 4 minutes to complete Once complete the device enters normal operating mode

              Change Baud Rate

              The BCI-I device supports four baud rates 9600 19200 38400 and 76800 baud The default baud rate is 76800 baud The baud rate can be modified with Tracer TU

              WARNING Remove power from the HVAC equipment before opening electrical control panel

              To change baud rate

              1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

              2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Protocol frame

              3 Click on the drop down arrow for the Baud Rate list and select the desired baud rate

              4 Click Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Click OK

              5 Exit Tracer TU and disconnect the USB cable plug

              6 Apply power to the HVAC equipment

              Change Device ID

              By default the BCI-I device sets its device ID to the same value as the one defined by the rotary switches (MSTP MAC address) on the front of the device Refer to the section ldquoRotary Switchesrdquo p 12 For simple networks this is an easy method to guarantee unique device IDs across the link

              The device also supports the full range of device ID values as specified by the BACnet Standard Systems that require a more complex device ID convention are supported with Tracer TU which has the ability to set the device ID via software configuration

              WARNING Remove power from the HVAC equipment before opening electrical control panel

              The process for soft setting the device ID is as follows

              1 Establish the connection between Tracer TU and the BCI-I Follow the procedureldquoStarting a Session of Tracer TU and Direct Connectionrdquo p 5

              2 From the Utilities drop-down menu select Controller and then Controller Settings The page contains four configuration frames that are minimized Expand the Protocol frame

              3 In the device ID box select the check box next to Use Software Device ID to enable the functionality The swipe-and-type box becomes available

              4 Type in the desired device ID

              8 ACC-SVP01B-EN bull BCI-I Integration Guide

              BCI-I Configuration

              5 Click the Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Click OK

              6 Exit Tracer TU and disconnect the USB service plug

              7 Apply power to the HVAC equipment

              Stand-alone or BAS Operation

              The control system on HVAC equipment has the ability to operate the unit as a stand-alone system or as part of a building automation system The BCI-I (either factory or field installed) by default is configured for stand-alone operation This configuration enables the HVAC equipment to operate prior to the commissioning of the unit into the BAS

              IntelliPak Control Configuration

              The IntelliPak control system must be configured at the human interface (HI) to support unit control from the BAS The technician should setverify the following configuration properties as illustrated below The technician should also verify that the BAS Module Comm Failure diagnostic is not present

              BAS Unit Control

              The BCI-I provides a method for a BAS to control the operation of HVAC equipment This method consists of BACnet objects that the BAS can access to control and monitor the status of equipment There are two sets of objects

              bull Output objects used by the BAS to provide command setpoint and sensor information to the IntelliPak unit

              bull Input objects provide IntelliPak status information to the BAS See tables 3 to 11 for the list of objects supported

              The system allows the BAS technician to define the amount of control that the BAS system will apply to the unit This is done by configuring the state of the Out of Service property of the output objects If the property is set to True the equipment will use a corresponding local value for control If the property is set to False the local value is ignored and the BAS-supplied value is used for control The BAS value is provided to the IntelliPak by writing to the present value property of the corresponding output object The factory default value for the Out of Service property of these objects is True

              1 Configuration Menu

              2 Setup Menu

              3 Diagnostics Menu

              Software Revision NumberBAS Communications BACnet 1801

              Configuration - Model Num Digit 34BAS Communication Module Installed

              Unit Control BASNETWORK

              Active Diagnostic - - Auto ResetNone

              Human Interface Representation

              ACC-SVP01B-EN bull BCI-I Integration Guide 9

              BCI-I Configuration

              Periodic Update of BAS Values

              The BCI-I device requires the BAS system to provide a periodic update to the sensor values This is required to protect against a loss of communication between the BAS and the BCI-I By BACnet definition the present value of the object will maintain the last value written to it regardless of the amount of time that has elapsed since the last write If communication is lost for several minutes or longer the present value of BAS-supplied sensor objects may no longer represent the current state of environmental conditions This may result in decreased occupant comfort and damage to building systems

              BAS Communication Failure

              The BCI-I is designed to minimize communication failure mode It does this by monitoring the length of time that has elapsed since the last write to the present value of the sensor object If the length of time exceeds a predefined limit the BCI-I will place the object into the fault state and revert to a unit-supplied sensor value for control At power up the sensor objects are set to a fault state and they will remain in this state until a write is detected The minimum periodic refresh rate for the objects is defined in Table 3 p 24 The following list is a set of sensor values that can be supplied by the BAS

              bull Space Static Pressure BAS

              bull Space Air Temperature BAS

              bull Discharge Air Temperature BAS

              bull Duct Static Air Pressure BAS

              bull Outdoor Air Temperature BAS

              bull Outdoor Air Humidity BAS

              bull Outdoor Airflow BAS

              bull Space CO2 Concentration BAS

              bull Space Humidity BAS

              InputOutput Commands and Calculations

              This section will provide the following information about certain inputs and outputs that perform unique control commands and calculations

              bull System control command

              bull Filter timer and diagnostic reset commands

              bull Setpoint calculations

              System Control Command

              Binary Output Object 1 has a special importance in the system The object allows the BAS to command the unit to run in a local or BAS control mode When the present value property of the object is set to Local Control the IntelliPak unit will enter local control and ignore BAS supplied values In this mode the unit will use local sensor and setpoint values When the object present value property is set to BAS Control the IntelliPak unit will use the values supplied by the BAS system for unit control

              Filter Timer Reset Command

              The BCI-I uses the Filter Runtime Hours object (AI 6) to generate a diagnostic when its present value is greater than the Filter Runtime Hours Setpoint (AV 1) present value The procedure for resetting the timer is as follows

              10 ACC-SVP01B-EN bull BCI-I Integration Guide

              BCI-I Configuration

              The BAS will change the state of the Filter Timer Reset Command object (BO 13) to the active state Upon the change to active state the BCI-I will set the present value of the Filter Runtime Hours object to zero and then set the Reset Command object back to the inactive state

              Diagnostics Reset Command

              The IntelliPak control system monitors the operation of the HVAC equipment If an abnormal condition is detected a diagnostic message is displayed on the human interface of the equipment control panel In addition the set of internal diagnostics is mapped to the set of BACnet binary input objects as listed in Table 9 p 31 The corresponding BI object will change state from inactive to active when the diagnostic is detected The object has been configured to send a BACnet event message to external BACnet devices as defined by the protocol

              The BAS has the ability to reset internal diagnostics by controlling the state of the Diagnostic Reset Command object (BO 14) The procedure for resetting diagnostics is as follows

              The BAS will change the state of the Diagnostic Reset to the active state Upon the change to active state the IntelliPak control system will reset all internal diagnostics and set the state of all of the diagnostic objects to inactive Upon completion of this action the BCI-I will set the present value of the Diagnostic Reset Command object back to the inactive state

              Setpoint Calculations

              The equipment has the ability to perform two basic control functions

              bull Space air temperature control

              bull Discharge air temperature control

              When the unit is configured for discharge air control it controls the temperature of the air leaving the unit to the discharge air temperature setpoint

              When the unit is configured for space air temperature control it controls the air temperature of the space that contains the space air temperature sensor This value may be provided by wiring the sensor to the unit or via a sensor value provided by the BAS

              The drawing below describes how the various temperature setpoints are calculated for space temperature control When the unit is in an occupied mode the active space temperature setpoint is calculated based on the space temperature setpoint and the two setpoint offset values In unoccupied mode the unoccupied heating and cooling setpoints are used as the active setpoint

              ACC-SVP01B-EN bull BCI-I Integration Guide 11

              BCI-I Configuration

              Timestamp Configuration

              The BCI-C device has a software-derived clock that maintains the time and date The device requires the current time to enable it to record a timestamp when an event or a change in state is detected by a BACnet object However in the event of a power loss the device does not maintain this time and date information At powerup the device time and date will default to 1200 pm Jan 1 1970 To minimize the possibility that the unit timestamp is not representing the actual time the BAS should be setup to periodically synchronize the device time clock with the BAS clock using the BACnet TimeSynchronization service

              12 ACC-SVP01B-EN bull BCI-I Integration Guide

              BCI IntelliPak Rotary Switches and LEDs

              BCI IntelliPak Rotary Switches and LEDs

              This section provides information about the BCI-I rotary switches and LED displays

              Rotary Switches

              There are three rotary switches on the front of the BCI-I device that are used to define a three-digit address when the BCI-I is installed on a BACnet communications network The three-digit address setting is the BACnet MAC address

              Note All devices are MSTP masters with valid MAC addresses of 001 to 127 for BACnet

              Figure 1 Setting rotary switches

              ADDRESS0 1

              23

              456

              78

              9

              x1

              0 1

              23

              456

              78

              9

              x10

              0 1

              23

              456

              78

              9

              x100

              Before

              After

              0

              5

              1

              3

              6

              29

              487

              Example of before and after setting addresses

              Use a 18 inch flathead screwdriver to set rotary switches

              Important Each device on the BACnetMSTP link must have a unique rotary switch setting otherwise communication problems will occur

              ACC-SVP01B-EN bull BCI-I Integration Guide 13

              BCI IntelliPak Rotary Switches and LEDs

              LEDs Description Behavior and Troubleshooting

              There are 15 LEDs on the front of the BCI-I unit However LEDs BO1 through BO9 are not used for the BCI-I controller Figure 2 shows the locations of each LED The following table provides a description of each LED activity an indication or troubleshooting tips for each and any notes

              Figure 2 LED locations

              SERVICE

              IMCLINK

              RX

              TX

              Marquee LED

              Table 1 LED Activities and Troubleshooting Tips

              LED Name ActivitiesIndication or Troubleshooting

              Tip (Denoted in Bullets) Notes

              Marquee LED

              Shows solid green when the unit is powered and no problems exist

              Indicates normal operation

              Shows solid red when the unit is powered but represents low power or a

              malfunction

              bull If low power could be under voltage or the microprocessor has malfunction Follow the troubleshoot procedure ldquo24 Vac Measurementrdquo p 15 to measure for the expected value range

              bull If malfunction unpower and then repower unit to bring the device back up to normal operation

              Shows blinking red when an a BACnet object is in a fault condition

              Alarm when an alarm is triggered for example when a point goes into fault condition because of point failure or there is an indication of a custom alarm in TGP2

              Shows blinking green when the device does not detect the IMC buss

              bull Verify that the IPC wiring harness is connected to the IMC link terminals

              bull Verify the polarity of the IPC wiring harness at the unit terminals

              LED not lit

              Indicates power is OFF or there is a malfunction

              bull OFF or malfunction cycle the power

              14 ACC-SVP01B-EN bull BCI-I Integration Guide

              BCI IntelliPak Rotary Switches and LEDs

              Link and IMC

              TX blinks greenBlinks at the data transfer rate when the unit transfers data to other devices on the link

              TX LED Regardless of connectivity or not this LED will constantly blink as it continually looks for devices to communicate to

              LED not litDetermine if for example a Tracer SC or BACnet device is trying to talk to the controller or if it is capable of talking to the controller Also determine if the communication status shows down all of the time

              Refer to ldquoGround Measurementsrdquo p 16 for a check-out procedure

              RX blinks yellow

              Blinks at the data transfer rate when the unit receives data from other devices on the link

              bull ON solid yellow indicates there is reverse polarity

              LED not lit

              Indicates that the controller is not detecting communication

              bull Not lit cycle the power to reestablish communication

              Service

              Shows solid greenIndicates someone is pressing this LED or the controller is not operating normally

              Press and hold during power up to place controller into boot code or press and hold for a count of approximately 10 seconds to clear the Device ID

              What is Boot Code When the UC400 is placed into boot code the system will not run any applications such as trending scheduling and TGP2 runtime

              Blinks green

              Indicates controllers is not accessing application software

              bull Restore using TU service tool

              LED not lit Indicates controller is operating normally

              Binary 01 to Binary 09 Not Used

              Table 1 LED Activities and Troubleshooting Tips

              LED Name ActivitiesIndication or Troubleshooting

              Tip (Denoted in Bullets) Notes

              ACC-SVP01B-EN bull BCI-I Integration Guide 15

              BCI IntelliPak Rotary Switches and LEDs

              24 Vac Measurement

              General Information Checkout Procedure Measurement Expected Value

              Checking the voltage that is powering the UC400 is often a necessary step when commissioning or troubleshooting Operational issues and LED operation may result in a need to measure the input power

              When troubleshooting it is faster to take measurements while the load is in place If Step 1 indicates an out-of-specification voltage disconnect the UC400 and measure the AC voltage across the transformer These measurements can direct the technician towards the problem source

              Step 1

              Measure AC voltage with the UC400 connected Perform this measurement while the unit is under load

              200 Vac le Vac le 300 Vac

              Step 2

              Measure AC voltage with the UC400 unconnected Perform this measurement while the unit is not under load

              200 Vac le Vac le 300 Vac

              16 ACC-SVP01B-EN bull BCI-I Integration Guide

              BCI IntelliPak Rotary Switches and LEDs

              Ground Measurements

              General Information and Checkout Procedure Measurement Expected Value

              Method 1AC voltage between shield conductors and device chassis ground- the voltage difference between BACnet MSTP device chassis ground connections should be close to zero If the voltage difference is greater that 40 Vac there will be marginal communication or intermittent communication problems If the voltage difference is greater that 70 Vac some devices will no longer communicate

              Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

              Vac le 20 V

              Method 2AC voltage between earth ground and device chassis ground- the chassis ground of the UC400 needs to be connected to earth ground by some route

              Note Do not assume that the building frame is a valid earth ground

              Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

              Vac le 40 V (Must comply with National Electrical Codetradeand local electrical codes)

              ACC-SVP01B-EN bull BCI-I Integration Guide 17

              BACnet Data Points and Configuration Property Definitions

              BACnet Data Points and Configuration Property

              Definitions

              The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MSTP This section includes information about

              bull BACnet protocol implementation conformance statement (PICS)

              bull Object types descriptions and configuration (refer to Table 2 p 19)

              bull BACnet protocol data link layers device address binding networking options and character sets

              bull Object data points and configurations

              BACnet Protocol Implementation Conformance Statement (PICS)

              Standardized Device Profile (Annex L)

              Interoperability Building Blocks (Annex K)

              Profile Description Supported Profile

              BACnet Advanced Application Controller (B-AAC)

              BACnet Application Specific Controller (B-ASC)

              BACnet Building Controller (B-BC)

              BACnet Operator Workstation (B-OWS)

              BACnet Smart Actuator (B-SA)

              BACnet Smart Sensor (B-SS)

              Data Sharing Description Supported BIBB

              Data Sharing-COV-B (DS-COV-B)

              Data Sharing-ReadProperty-A (DS-RP-A)

              Data Sharing-ReadProperty-B (DS-RP-B)

              Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)

              Data Sharing-WriteProperty-A (DS-WP-A)

              Data Sharing-WriteProperty-B (DS-WP-B)

              Data Sharing-WritePropertyMultiple-B (DS-WPM-B)

              Alarm and Event Management Description Supported BIBB

              Alarm and Event-ACKI-B (AE-ACK-B)

              Alarm and Event-Alarm Summary-B (AE-ASUM-B)

              Alarm and Event-Enrollment Summary-B (AE-ESUM-B)

              Alarm and Event-Information-B (AE-INFO-B)

              Alarm and Event-Notification Internal-B (AE-N-I-B)

              18 ACC-SVP01B-EN bull BCI-I Integration Guide

              BACnet Data Points and Configuration Property Definitions

              Segmentation Capability

              Trending Description Supported BIBB

              Trending-Automated Trend Retrieval-B (T-ATR-B)

              Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

              Device Management Description Supported BIBB

              Device Management-Backup and Restore-B (DM-BR-B)

              Device Management-Device Communication Control-B (DM-DCC-B)

              Device Management-Dynamic Device Binding-A (DM-DDB-A)

              Device Management-Dynamic Device Binding-B (DM-DDB-B)

              Device Management-Dynamic Object Binding-B (DM-DOB-B)

              Device Management-List Manipulation-B (DM-LM-B)

              Device Management-Object Creation and Deletion-B (DM-OCD-B)

              Device Management-Private Transfer-A (DM-PT-A)

              Device Management-Private Transfer-B (DM-PT-B)

              Device Management-Reinitialize Device-B (DM-RD-B)

              Device Management-TimeSynchronization-B (DM-TS-B)

              Segmentation Description Supported Segment

              Segmented Requests Window Size 1

              Segmented Responses Window Size 1

              ACC-SVP01B-EN bull BCI-I Integration Guide 19

              BACnet Data Points and Configuration Property Definitions

              Object Types

              Table 2 Descriptions and configurations

              Object Type Required Properties Read Properties Written(a) Optional Properties Read

              Ability to Create

              Ability to Delete

              Analog Input

              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

              bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

              bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

              Yes Yes only user created objects

              Analog Output

              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

              bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

              bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

              Yes Yes only user created objects

              Analog Value

              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

              bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

              bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

              Yes Yes only user created objects

              Binary Input

              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

              bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

              bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

              Yes Yes only user created objects

              20 ACC-SVP01B-EN bull BCI-I Integration Guide

              BACnet Data Points and Configuration Property Definitions

              Binary Output

              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

              bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

              bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

              Yes Yes only user created objects

              Binary Value

              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

              bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

              bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

              Yes Yes only user created objects

              Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

              bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

              bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

              None None

              Event Enrollment Object

              bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

              bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

              bull None Yes Yes only user created objects

              Table 2 Descriptions and configurations (continued)

              Object Type Required Properties Read Properties Written(a) Optional Properties Read

              Ability to Create

              Ability to Delete

              ACC-SVP01B-EN bull BCI-I Integration Guide 21

              BACnet Data Points and Configuration Property Definitions

              Multistate Input

              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

              bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

              bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

              Yes Yes only user created objects

              Multistate Output

              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

              bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

              bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

              Yes Yes only user created objects

              Multistate Value

              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

              bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

              bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

              Yes Yes only user created objects

              Notification Class

              bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

              bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

              None Yes Yes only user created objects

              Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

              bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

              bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

              Yes Yes only user created objects

              (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

              Table 2 Descriptions and configurations (continued)

              Object Type Required Properties Read Properties Written(a) Optional Properties Read

              Ability to Create

              Ability to Delete

              22 ACC-SVP01B-EN bull BCI-I Integration Guide

              BACnet Data Points and Configuration Property Definitions

              BACnet Protocol

              Data Link Layer Options

              Device Address Binding

              Networking Options

              Data Link Layer Description Supported Option

              ANSIATA 8781 25 Mb ARCNET (Clause 8)

              ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

              BACnet IP (Annex J)

              BACnet IP (Annex J) Foreign Device

              ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

              LonTalk (Clause 11) Medium

              MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

              MSTP Slave (Clause 9) Baud Rate(s)

              Other

              Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

              Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

              Device Address Binding Supported

              Static Device Binding Supported

              Networking DescriptionsSupported

              Option

              Annex H BACnet Tunneling

              BACnetIP Broadcast Management Device (BBMD)

              Does the BBMD Support Registrations by Foreign Devices

              Router

              ACC-SVP01B-EN bull BCI-I Integration Guide 23

              BACnet Data Points and Configuration Property Definitions

              Character Sets

              Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

              Character Set Descriptions Supported

              ANSI X34

              IBMMicrosoft DBCS

              ISO 10646 (UCS-4)

              ISO 10646 (UCS2)

              ISO 8859-1

              JIS C 6226

              24 ACC-SVP01B-EN bull BCI-I Integration Guide

              Object Data Points and Diagnostic Data Points

              Object Data Points and Diagnostic Data Points

              For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

              Table 3 Analog Output

              Object Identifier Object Name Description Units Valid Range

              Refresh Rate

              (Sec)

              Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

              Percent (98) 0 to 100 NA

              Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

              Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

              Degrees-Fahrenheit (64) 500 to 900 NA

              Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

              BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

              Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

              Degrees-Fahrenheit (64) 400 to 900 NA

              Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

              Degrees-Fahrenheit (64) 400 to 1800 NA

              Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

              070 to 510 (Ipak II) NA

              Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

              003 to 030-002 to 030 (enhanced StatiTrac)

              NA

              Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

              -028 to 050-067 to 067 (enhanced StatiTrac)

              900

              Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

              Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

              Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

              00 to 79 (Ipak II) 900

              Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

              Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

              Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

              Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

              Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

              Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

              Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

              Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

              Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

              Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

              ACC-SVP01B-EN bull BCI-I Integration Guide 25

              Object Data Points and Diagnostic Data Points

              Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

              Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

              Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

              Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

              Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

              Cooling temperature setpoint used for control in unoccupied mode

              Degrees-Fahrenheit (64) 520 to 880 NA

              Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

              Heating temperature setpoint used for control in unoccupied mode

              Degrees-Fahrenheit (64) 500 to 900 NA

              Table 4 Analog Input

              Object Identifier Object Name Description Units (Listed Are Defaults)

              Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

              Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

              Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

              Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

              Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

              Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

              Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

              Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

              Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

              Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

              Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

              Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

              Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

              Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

              Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

              Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

              Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

              Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

              Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

              Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

              Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

              Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

              Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

              Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

              Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

              Table 3 Analog Output (continued)

              Object Identifier Object Name Description Units Valid Range

              Refresh Rate

              (Sec)

              26 ACC-SVP01B-EN bull BCI-I Integration Guide

              Object Data Points and Diagnostic Data Points

              Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

              Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

              Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

              Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

              Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

              Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

              Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

              Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

              Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

              Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

              Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

              Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

              Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

              Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

              Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

              Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

              Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

              Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

              Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

              Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

              Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

              Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

              Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

              Analog Input 54 Morning Warmup Air Temperature Setpoint Active

              The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

              Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

              The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

              Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

              Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

              Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

              Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

              Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

              Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

              Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

              Table 4 Analog Input (continued)

              Object Identifier Object Name Description Units (Listed Are Defaults)

              ACC-SVP01B-EN bull BCI-I Integration Guide 27

              Object Data Points and Diagnostic Data Points

              Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

              Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

              Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

              Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

              The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

              Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

              Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

              Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

              Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

              Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

              Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

              Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

              Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

              Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

              Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

              Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

              Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

              Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

              Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

              Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

              Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

              Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

              Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

              Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

              Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

              Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

              Table 5 Analog Value

              Object Identifier Object Name Description Units Valid Range

              Analog Value 1 Filter Runtime Hours Setpoint

              The setpoint value used by the filter run hours calculation

              Hours (71) 0 to 10000

              Table 4 Analog Input (continued)

              Object Identifier Object Name Description Units (Listed Are Defaults)

              28 ACC-SVP01B-EN bull BCI-I Integration Guide

              Object Data Points and Diagnostic Data Points

              Table 6 Multistate Output

              BCI-I Object Identifier Object Name Description Object States

              Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

              Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

              1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

              Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

              Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

              1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

              Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

              1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

              Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

              1 = Flow2 = No Flow3 = Auto

              Table 7 Multistate Input

              BCI-I Object Identifier Object Name Description Object States

              Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

              1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

              Multi-State Input 9 Economizer Type General description of the equipment economizer system

              1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

              Multi-State Input 10 Condenser Type General description of the equipment condenser system

              1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

              Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

              1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

              ACC-SVP01B-EN bull BCI-I Integration Guide 29

              Object Data Points and Diagnostic Data Points

              Multi-State Input 15 Economizer Decision Method

              Unit method to determine when the economizer system is enabled

              1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

              Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

              Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

              Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

              1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

              Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

              1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

              Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

              1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

              Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

              1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

              Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

              1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

              Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

              1 = Idle2 = On3 = Cancel

              Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

              1 = Off2 = On3 = Not Present

              Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

              1 = Off2 = On3 = Not Present

              Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

              1 = Off2 = On3 = Not Present

              Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

              1 = Off|2 = On3 = Not Present

              Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

              1 = Off2 = On3 = Not Present

              Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

              1 = Off2 = On3 = Not Present

              Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

              1 = Off2 = On3 = Not Present

              Table 7 Multistate Input (continued)

              BCI-I Object Identifier Object Name Description Object States

              30 ACC-SVP01B-EN bull BCI-I Integration Guide

              Object Data Points and Diagnostic Data Points

              Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

              1 = Off2 = On3 = Not Present

              Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

              1 = Off2 = On3 = Not Present

              Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

              Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

              Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

              Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

              Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

              1 = Off2 = On3 = Not Present

              Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

              1= Off2= On3= Not Present

              Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

              Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

              Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

              Multi-State Input 43 Outdoor Air Damper Status

              Indicates the operating state of the outdoor damper

              1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

              Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

              1 = Disabled2 = Enabled3 = Not Present

              Table 8 Binary Output

              Object Identifier Object Name DescriptionRelinquish Default Object States

              Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

              Active = BAS Control

              Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

              Active = Heating Locked Out

              Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

              Active = Cooling Locked Out

              Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

              Active = Enabled

              Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

              Active = On

              Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

              Inactive Inactive = DisabledActive = Enabled

              Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

              Active = Reset

              Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

              Active = Reset

              Table 7 Multistate Input (continued)

              BCI-I Object Identifier Object Name Description Object States

              ACC-SVP01B-EN bull BCI-I Integration Guide 31

              Object Data Points and Diagnostic Data Points

              Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

              Active = Auto

              Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

              Active = Auto

              Table 9 Binary Input

              Object Identifier Object Name Description Object States

              Binary Input 1 System Control Status Indicates the control system currently in command of the unit

              Inactive = Standalone controlActive = BAS control

              Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

              Inactive = NormalActive = Locked Out

              Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

              Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

              Inactive = AutoActive = Open

              Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

              Inactive = InactiveActive = Active

              Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

              Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

              Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

              Inactive = DisabledActive = Enabled

              Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

              Inactive = DisabledActive = Enabled

              Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

              Inactive = InactiveActive = Active

              Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

              Inactive = No FlowActive = Flow

              Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

              Inactive = InactiveActive = Active

              Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

              Inactive = InactiveActive = Active

              Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

              Inactive = InactiveActive = Active

              Binary Input 161 Evaporator Frost Protection Circuit 1 Status

              The status of evaporator frost protection function for circuit 1

              Inactive = InactiveActive = Active

              Binary Input 162 Evaporator Frost Protection Circuit 2 Status

              The status of evaporator frost protection function for circuit 2

              Inactive = InactiveActive = Active

              Binary Input 163 Evaporator Frost Protection Circuit 3 Status

              The status of evaporator frost protection function for circuit 3

              Inactive = InactiveActive = Active

              Binary Input 164 Evaporator Frost Protection Circuit 4 Status

              The status of evaporator frost protection function for circuit 4

              Inactive = InactiveActive = Active

              Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

              Inactive = De-energizedActive = Energized

              Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

              Inactive = InactiveActive = Active

              Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

              Inactive = ClosedActive = Open

              Table 10 Diagnostics Binary Input

              Object Identifier(a) Object Name Description

              Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

              Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

              Binary Input 31 (use Object Identifier for RT or CSC)

              Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

              Binary Input 31 (use Object Identifier for FAU)

              Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

              Table 8 Binary Output

              Object Identifier Object Name DescriptionRelinquish Default Object States

              32 ACC-SVP01B-EN bull BCI-I Integration Guide

              Object Data Points and Diagnostic Data Points

              Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

              Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

              Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

              Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

              Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

              Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

              Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

              Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

              Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

              Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

              Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

              Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

              Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

              Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

              Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

              Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

              Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

              Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

              Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

              Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

              Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

              Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

              Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

              Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

              Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

              Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

              Binary Input 58 (use Object Identifier for RT or CSC)

              Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

              Binary Input 58 (use Object Identifier for FAU)

              Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

              Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

              Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

              Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

              Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

              Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

              Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

              Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

              Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

              Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

              Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

              Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

              Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

              Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

              Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

              Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

              Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

              Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

              Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

              Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

              Table 10 Diagnostics Binary Input (continued)

              Object Identifier(a) Object Name Description

              ACC-SVP01B-EN bull BCI-I Integration Guide 33

              Object Data Points and Diagnostic Data Points

              Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

              Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

              Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

              Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

              Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

              Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

              Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

              Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

              Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

              Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

              Binary Input 86 (use Object Identifier for RT I-pak II)

              Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

              Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

              Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

              Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

              Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

              Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

              Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

              Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

              Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

              Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

              Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

              Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

              Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

              Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

              Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

              Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

              Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

              Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

              Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

              Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

              Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

              Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

              Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

              Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

              Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

              Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

              Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

              Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

              Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

              Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

              Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

              Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

              Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

              Binary Input 121 (use Object Identifier for RT)

              Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

              Binary Input 121 (use Object Identifier for FAU)

              Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

              Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

              Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

              Table 10 Diagnostics Binary Input (continued)

              Object Identifier(a) Object Name Description

              34 ACC-SVP01B-EN bull BCI-I Integration Guide

              Object Data Points and Diagnostic Data Points

              Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

              Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

              Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

              Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

              Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

              Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

              Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

              Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

              Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

              Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

              Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

              Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

              Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

              Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

              Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

              Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

              Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

              Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

              Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

              Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

              Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

              Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

              Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

              Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

              Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

              Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

              (a) Object States Inactive = normal and Active = foreign language specific

              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

              Object Identifier(a) Object Name Description

              Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

              Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

              Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

              Analog Input 80 Cabinet Style Describes the cabinet style of the unit

              Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

              Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

              Multi-State Input 10 Condenser Type General description of the equipment condenser system

              Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

              Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

              Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

              Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

              Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

              Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

              Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

              Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

              Table 10 Diagnostics Binary Input (continued)

              Object Identifier(a) Object Name Description

              ACC-SVP01B-EN bull BCI-I Integration Guide 35

              Object Data Points and Diagnostic Data Points

              Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

              Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

              Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

              Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

              Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

              Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

              Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

              Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

              Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

              Analog Input 81 Cool Type Describes the cooling type installed in the unit

              Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

              Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

              Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

              Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

              Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

              Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

              Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

              Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

              Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

              Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

              Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

              Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

              Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

              Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

              Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

              Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

              Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

              Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

              Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

              Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

              Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

              Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

              Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

              Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

              Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

              Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

              Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

              Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

              Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

              Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

              Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

              Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

              Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

              Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

              Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

              Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

              Object Identifier(a) Object Name Description

              36 ACC-SVP01B-EN bull BCI-I Integration Guide

              Object Data Points and Diagnostic Data Points

              Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

              Multi-State Input 9 Economizer Type General description of the equipment economizer system

              Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

              Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

              Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

              Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

              Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

              Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

              Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

              Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

              Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

              Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

              Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

              Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

              Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

              Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

              Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

              Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

              Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

              Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

              Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

              Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

              Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

              Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

              Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

              Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

              Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

              Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

              Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

              Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

              Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

              Multi-State Input 36 Final Filter Status Indicates the final filter media state

              Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

              Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

              Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

              Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

              Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

              Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

              Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

              Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

              Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

              Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

              Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

              Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

              Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

              Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

              Object Identifier(a) Object Name Description

              ACC-SVP01B-EN bull BCI-I Integration Guide 37

              Object Data Points and Diagnostic Data Points

              Binary Output 16 Humidification Command Command the operating state of the humidification system

              NC 3 HVAC-Advisory HVAC-Advisory

              NC 1 HVAC-Critical HVAC-Critical

              NC 4 HVAC-Information HVAC-Information

              NC 2 HVAC-Service Required HVAC-Service Required

              Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

              Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

              Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

              Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

              Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

              Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

              Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

              Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

              Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

              Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

              Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

              Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

              Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

              Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

              Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

              Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

              Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

              Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

              Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

              Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

              Multi-State Input 34 Prefilter Status Indicates the prefilter media state

              Analog Input 82 Preheat Type Describes the heating type installed in the unit

              Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

              Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

              Analog Input 83 Reheat Type Describes the reheat type installed in the unit

              Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

              Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

              Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

              Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

              Multi-State Input 42 Return Fan Status Indicates the state of the return fan

              Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

              Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

              Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

              Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

              Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

              Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

              Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

              Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

              Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

              Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

              Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

              Object Identifier(a) Object Name Description

              38 ACC-SVP01B-EN bull BCI-I Integration Guide

              Object Data Points and Diagnostic Data Points

              Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

              Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

              Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

              Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

              Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

              Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

              Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

              Analog Input 15 Space Temperature Active The space temperature currently used for unit control

              Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

              Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

              Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

              Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

              Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

              Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

              Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

              Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

              Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

              Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

              Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

              Binary Input 1 System Control Status Indicates the control system currently in command of the unit

              Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

              Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

              Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

              Binary Input 3 Unit Status Indicates the current state of the unit

              Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

              Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

              Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

              Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

              Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

              Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

              Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

              (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

              Object Identifier(a) Object Name Description

              Table 12 Diagnostic Objects Sorted by Object Name

              Object Identifier(a) Object Name ValueRange Description

              BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

              BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

              ACC-SVP01B-EN bull BCI-I Integration Guide 39

              Object Data Points and Diagnostic Data Points

              BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

              BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

              BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

              BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

              BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

              BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

              BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

              BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

              BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

              BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

              BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

              BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

              BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

              BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

              BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

              BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

              BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

              BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

              BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

              BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

              BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

              BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

              BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

              BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

              BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

              BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

              BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

              BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

              BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

              Table 12 Diagnostic Objects Sorted by Object Name (continued)

              Object Identifier(a) Object Name ValueRange Description

              40 ACC-SVP01B-EN bull BCI-I Integration Guide

              Object Data Points and Diagnostic Data Points

              BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

              BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

              BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

              BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

              BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

              BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

              BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

              BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

              BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

              BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

              BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

              BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

              BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

              BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

              BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

              BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

              BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

              BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

              BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

              BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

              BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

              BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

              BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

              BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

              BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

              BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

              BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

              BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

              BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

              Table 12 Diagnostic Objects Sorted by Object Name (continued)

              Object Identifier(a) Object Name ValueRange Description

              ACC-SVP01B-EN bull BCI-I Integration Guide 41

              Object Data Points and Diagnostic Data Points

              BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

              BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

              BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

              BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

              BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

              BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

              BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

              BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

              BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

              BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

              BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

              BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

              BI 121 (use Object Identifier for RT)

              Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

              BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

              BI 58 (use Object Identifier for RT or CSC)

              Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

              BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

              BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

              BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

              BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

              BI 31 (use Object Identifier for RT CSC)

              Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

              BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

              BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

              BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

              BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

              BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

              BI 121 (use Object Identifier for FAU)

              Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

              B1 31 (use Object Identifier for FAU)

              Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

              BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

              BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

              Table 12 Diagnostic Objects Sorted by Object Name (continued)

              Object Identifier(a) Object Name ValueRange Description

              42 ACC-SVP01B-EN bull BCI-I Integration Guide

              Object Data Points and Diagnostic Data Points

              BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

              BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

              BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

              BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

              BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

              BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

              BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

              BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

              BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

              BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

              BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

              BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

              BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

              BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

              BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

              BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

              BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

              BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

              BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

              BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

              BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

              BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

              BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

              1 = active Diagnostic Vel Press Sensor (Rear)

              BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

              Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

              BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

              BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

              BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

              BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

              BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

              Table 12 Diagnostic Objects Sorted by Object Name (continued)

              Object Identifier(a) Object Name ValueRange Description

              ACC-SVP01B-EN bull BCI-I Integration Guide 43

              Object Data Points and Diagnostic Data Points

              BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

              BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

              BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

              BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

              BI 58 (use Object Identifier for FAU)

              Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

              (a) BI=Binary Input

              Table 12 Diagnostic Objects Sorted by Object Name (continued)

              Object Identifier(a) Object Name ValueRange Description

              44 ACC-SVP01B-EN bull BCI-I Integration Guide

              Additional Resources

              Additional Resources

              Use the following documents and links as additional resources

              bull Product support online

              bull wwwbacnetorg

              bull wwwbacnetassociationorg

              bull wwwashraeorg

              bull Tracer TU Help online

              bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

              bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

              Note For further assistance contact your local Trane sales office

              ACC-SVP01B-EN bull BCI-I Integration Guide 45

              Glossary

              A

              ASHRAE

              See American Society of Heating Refrigeration and Air-conditioning Engineers

              American Society of Heating Refrigeration and Air-

              conditioning Engineers

              An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

              BBACnettrade

              See Building Automation Control network

              BACnet interoperability building blocks

              A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

              BACnet object

              An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

              baud rate

              The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

              BIBB

              See BACnet interoperability building blocks

              Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

              advocates BACnet protocol for use in system-level control devices

              device

              A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

              Device ID

              The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

              Iinteroperability

              The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

              Pprotocol

              A set of rules (language) that governs the exchange of data over a digital communications system

              S

              stand-alone operation

              Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

              wwwtranecom

              For more information contact your local Trane office or e-mail us at comforttranecom

              Literature Order Number ACC-SVP01B-EN

              Date September 2009

              Supersedes ACC-SVP01A-EN

              Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

              • Table of Contents
              • Overview
              • Ordering Numbers
              • BACnet Protocol
              • BCI-I Configuration
                • Overview
                • Starting a Session of Tracer TU and Direct Connection
                • Reset to Factory Default
                • IP Units Configuration
                • BACnet Object Configuration
                • Change Baud Rate
                • Change Device ID
                • Stand-alone or BAS Operation
                  • IntelliPak Control Configuration
                  • BAS Unit Control
                  • Periodic Update of BAS Values
                  • BAS Communication Failure
                    • InputOutput Commands and Calculations
                      • System Control Command
                      • Filter Timer Reset Command
                      • Diagnostics Reset Command
                      • Setpoint Calculations
                      • Timestamp Configuration
                          • BCI IntelliPak Rotary Switches and LEDs
                            • Rotary Switches
                            • LEDs Description Behavior and Troubleshooting
                            • 24 Vac Measurement
                            • Ground Measurements
                              • BACnet Data Points and Configuration Property Definitions
                                • BACnet Protocol Implementation Conformance Statement (PICS)
                                  • Standardized Device Profile (Annex L)
                                  • Interoperability Building Blocks (Annex K)
                                  • Segmentation Capability
                                  • Object Types
                                    • BACnet Protocol
                                      • Data Link Layer Options
                                      • Device Address Binding
                                      • Networking Options
                                      • Character Sets
                                          • Object Data Points and Diagnostic Data Points
                                          • Additional Resources
                                          • Glossary

                8 ACC-SVP01B-EN bull BCI-I Integration Guide

                BCI-I Configuration

                5 Click the Save button in the lower right corner of the window A pop-up will display indicating that changes were saved to the controller Click OK

                6 Exit Tracer TU and disconnect the USB service plug

                7 Apply power to the HVAC equipment

                Stand-alone or BAS Operation

                The control system on HVAC equipment has the ability to operate the unit as a stand-alone system or as part of a building automation system The BCI-I (either factory or field installed) by default is configured for stand-alone operation This configuration enables the HVAC equipment to operate prior to the commissioning of the unit into the BAS

                IntelliPak Control Configuration

                The IntelliPak control system must be configured at the human interface (HI) to support unit control from the BAS The technician should setverify the following configuration properties as illustrated below The technician should also verify that the BAS Module Comm Failure diagnostic is not present

                BAS Unit Control

                The BCI-I provides a method for a BAS to control the operation of HVAC equipment This method consists of BACnet objects that the BAS can access to control and monitor the status of equipment There are two sets of objects

                bull Output objects used by the BAS to provide command setpoint and sensor information to the IntelliPak unit

                bull Input objects provide IntelliPak status information to the BAS See tables 3 to 11 for the list of objects supported

                The system allows the BAS technician to define the amount of control that the BAS system will apply to the unit This is done by configuring the state of the Out of Service property of the output objects If the property is set to True the equipment will use a corresponding local value for control If the property is set to False the local value is ignored and the BAS-supplied value is used for control The BAS value is provided to the IntelliPak by writing to the present value property of the corresponding output object The factory default value for the Out of Service property of these objects is True

                1 Configuration Menu

                2 Setup Menu

                3 Diagnostics Menu

                Software Revision NumberBAS Communications BACnet 1801

                Configuration - Model Num Digit 34BAS Communication Module Installed

                Unit Control BASNETWORK

                Active Diagnostic - - Auto ResetNone

                Human Interface Representation

                ACC-SVP01B-EN bull BCI-I Integration Guide 9

                BCI-I Configuration

                Periodic Update of BAS Values

                The BCI-I device requires the BAS system to provide a periodic update to the sensor values This is required to protect against a loss of communication between the BAS and the BCI-I By BACnet definition the present value of the object will maintain the last value written to it regardless of the amount of time that has elapsed since the last write If communication is lost for several minutes or longer the present value of BAS-supplied sensor objects may no longer represent the current state of environmental conditions This may result in decreased occupant comfort and damage to building systems

                BAS Communication Failure

                The BCI-I is designed to minimize communication failure mode It does this by monitoring the length of time that has elapsed since the last write to the present value of the sensor object If the length of time exceeds a predefined limit the BCI-I will place the object into the fault state and revert to a unit-supplied sensor value for control At power up the sensor objects are set to a fault state and they will remain in this state until a write is detected The minimum periodic refresh rate for the objects is defined in Table 3 p 24 The following list is a set of sensor values that can be supplied by the BAS

                bull Space Static Pressure BAS

                bull Space Air Temperature BAS

                bull Discharge Air Temperature BAS

                bull Duct Static Air Pressure BAS

                bull Outdoor Air Temperature BAS

                bull Outdoor Air Humidity BAS

                bull Outdoor Airflow BAS

                bull Space CO2 Concentration BAS

                bull Space Humidity BAS

                InputOutput Commands and Calculations

                This section will provide the following information about certain inputs and outputs that perform unique control commands and calculations

                bull System control command

                bull Filter timer and diagnostic reset commands

                bull Setpoint calculations

                System Control Command

                Binary Output Object 1 has a special importance in the system The object allows the BAS to command the unit to run in a local or BAS control mode When the present value property of the object is set to Local Control the IntelliPak unit will enter local control and ignore BAS supplied values In this mode the unit will use local sensor and setpoint values When the object present value property is set to BAS Control the IntelliPak unit will use the values supplied by the BAS system for unit control

                Filter Timer Reset Command

                The BCI-I uses the Filter Runtime Hours object (AI 6) to generate a diagnostic when its present value is greater than the Filter Runtime Hours Setpoint (AV 1) present value The procedure for resetting the timer is as follows

                10 ACC-SVP01B-EN bull BCI-I Integration Guide

                BCI-I Configuration

                The BAS will change the state of the Filter Timer Reset Command object (BO 13) to the active state Upon the change to active state the BCI-I will set the present value of the Filter Runtime Hours object to zero and then set the Reset Command object back to the inactive state

                Diagnostics Reset Command

                The IntelliPak control system monitors the operation of the HVAC equipment If an abnormal condition is detected a diagnostic message is displayed on the human interface of the equipment control panel In addition the set of internal diagnostics is mapped to the set of BACnet binary input objects as listed in Table 9 p 31 The corresponding BI object will change state from inactive to active when the diagnostic is detected The object has been configured to send a BACnet event message to external BACnet devices as defined by the protocol

                The BAS has the ability to reset internal diagnostics by controlling the state of the Diagnostic Reset Command object (BO 14) The procedure for resetting diagnostics is as follows

                The BAS will change the state of the Diagnostic Reset to the active state Upon the change to active state the IntelliPak control system will reset all internal diagnostics and set the state of all of the diagnostic objects to inactive Upon completion of this action the BCI-I will set the present value of the Diagnostic Reset Command object back to the inactive state

                Setpoint Calculations

                The equipment has the ability to perform two basic control functions

                bull Space air temperature control

                bull Discharge air temperature control

                When the unit is configured for discharge air control it controls the temperature of the air leaving the unit to the discharge air temperature setpoint

                When the unit is configured for space air temperature control it controls the air temperature of the space that contains the space air temperature sensor This value may be provided by wiring the sensor to the unit or via a sensor value provided by the BAS

                The drawing below describes how the various temperature setpoints are calculated for space temperature control When the unit is in an occupied mode the active space temperature setpoint is calculated based on the space temperature setpoint and the two setpoint offset values In unoccupied mode the unoccupied heating and cooling setpoints are used as the active setpoint

                ACC-SVP01B-EN bull BCI-I Integration Guide 11

                BCI-I Configuration

                Timestamp Configuration

                The BCI-C device has a software-derived clock that maintains the time and date The device requires the current time to enable it to record a timestamp when an event or a change in state is detected by a BACnet object However in the event of a power loss the device does not maintain this time and date information At powerup the device time and date will default to 1200 pm Jan 1 1970 To minimize the possibility that the unit timestamp is not representing the actual time the BAS should be setup to periodically synchronize the device time clock with the BAS clock using the BACnet TimeSynchronization service

                12 ACC-SVP01B-EN bull BCI-I Integration Guide

                BCI IntelliPak Rotary Switches and LEDs

                BCI IntelliPak Rotary Switches and LEDs

                This section provides information about the BCI-I rotary switches and LED displays

                Rotary Switches

                There are three rotary switches on the front of the BCI-I device that are used to define a three-digit address when the BCI-I is installed on a BACnet communications network The three-digit address setting is the BACnet MAC address

                Note All devices are MSTP masters with valid MAC addresses of 001 to 127 for BACnet

                Figure 1 Setting rotary switches

                ADDRESS0 1

                23

                456

                78

                9

                x1

                0 1

                23

                456

                78

                9

                x10

                0 1

                23

                456

                78

                9

                x100

                Before

                After

                0

                5

                1

                3

                6

                29

                487

                Example of before and after setting addresses

                Use a 18 inch flathead screwdriver to set rotary switches

                Important Each device on the BACnetMSTP link must have a unique rotary switch setting otherwise communication problems will occur

                ACC-SVP01B-EN bull BCI-I Integration Guide 13

                BCI IntelliPak Rotary Switches and LEDs

                LEDs Description Behavior and Troubleshooting

                There are 15 LEDs on the front of the BCI-I unit However LEDs BO1 through BO9 are not used for the BCI-I controller Figure 2 shows the locations of each LED The following table provides a description of each LED activity an indication or troubleshooting tips for each and any notes

                Figure 2 LED locations

                SERVICE

                IMCLINK

                RX

                TX

                Marquee LED

                Table 1 LED Activities and Troubleshooting Tips

                LED Name ActivitiesIndication or Troubleshooting

                Tip (Denoted in Bullets) Notes

                Marquee LED

                Shows solid green when the unit is powered and no problems exist

                Indicates normal operation

                Shows solid red when the unit is powered but represents low power or a

                malfunction

                bull If low power could be under voltage or the microprocessor has malfunction Follow the troubleshoot procedure ldquo24 Vac Measurementrdquo p 15 to measure for the expected value range

                bull If malfunction unpower and then repower unit to bring the device back up to normal operation

                Shows blinking red when an a BACnet object is in a fault condition

                Alarm when an alarm is triggered for example when a point goes into fault condition because of point failure or there is an indication of a custom alarm in TGP2

                Shows blinking green when the device does not detect the IMC buss

                bull Verify that the IPC wiring harness is connected to the IMC link terminals

                bull Verify the polarity of the IPC wiring harness at the unit terminals

                LED not lit

                Indicates power is OFF or there is a malfunction

                bull OFF or malfunction cycle the power

                14 ACC-SVP01B-EN bull BCI-I Integration Guide

                BCI IntelliPak Rotary Switches and LEDs

                Link and IMC

                TX blinks greenBlinks at the data transfer rate when the unit transfers data to other devices on the link

                TX LED Regardless of connectivity or not this LED will constantly blink as it continually looks for devices to communicate to

                LED not litDetermine if for example a Tracer SC or BACnet device is trying to talk to the controller or if it is capable of talking to the controller Also determine if the communication status shows down all of the time

                Refer to ldquoGround Measurementsrdquo p 16 for a check-out procedure

                RX blinks yellow

                Blinks at the data transfer rate when the unit receives data from other devices on the link

                bull ON solid yellow indicates there is reverse polarity

                LED not lit

                Indicates that the controller is not detecting communication

                bull Not lit cycle the power to reestablish communication

                Service

                Shows solid greenIndicates someone is pressing this LED or the controller is not operating normally

                Press and hold during power up to place controller into boot code or press and hold for a count of approximately 10 seconds to clear the Device ID

                What is Boot Code When the UC400 is placed into boot code the system will not run any applications such as trending scheduling and TGP2 runtime

                Blinks green

                Indicates controllers is not accessing application software

                bull Restore using TU service tool

                LED not lit Indicates controller is operating normally

                Binary 01 to Binary 09 Not Used

                Table 1 LED Activities and Troubleshooting Tips

                LED Name ActivitiesIndication or Troubleshooting

                Tip (Denoted in Bullets) Notes

                ACC-SVP01B-EN bull BCI-I Integration Guide 15

                BCI IntelliPak Rotary Switches and LEDs

                24 Vac Measurement

                General Information Checkout Procedure Measurement Expected Value

                Checking the voltage that is powering the UC400 is often a necessary step when commissioning or troubleshooting Operational issues and LED operation may result in a need to measure the input power

                When troubleshooting it is faster to take measurements while the load is in place If Step 1 indicates an out-of-specification voltage disconnect the UC400 and measure the AC voltage across the transformer These measurements can direct the technician towards the problem source

                Step 1

                Measure AC voltage with the UC400 connected Perform this measurement while the unit is under load

                200 Vac le Vac le 300 Vac

                Step 2

                Measure AC voltage with the UC400 unconnected Perform this measurement while the unit is not under load

                200 Vac le Vac le 300 Vac

                16 ACC-SVP01B-EN bull BCI-I Integration Guide

                BCI IntelliPak Rotary Switches and LEDs

                Ground Measurements

                General Information and Checkout Procedure Measurement Expected Value

                Method 1AC voltage between shield conductors and device chassis ground- the voltage difference between BACnet MSTP device chassis ground connections should be close to zero If the voltage difference is greater that 40 Vac there will be marginal communication or intermittent communication problems If the voltage difference is greater that 70 Vac some devices will no longer communicate

                Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                Vac le 20 V

                Method 2AC voltage between earth ground and device chassis ground- the chassis ground of the UC400 needs to be connected to earth ground by some route

                Note Do not assume that the building frame is a valid earth ground

                Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                Vac le 40 V (Must comply with National Electrical Codetradeand local electrical codes)

                ACC-SVP01B-EN bull BCI-I Integration Guide 17

                BACnet Data Points and Configuration Property Definitions

                BACnet Data Points and Configuration Property

                Definitions

                The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MSTP This section includes information about

                bull BACnet protocol implementation conformance statement (PICS)

                bull Object types descriptions and configuration (refer to Table 2 p 19)

                bull BACnet protocol data link layers device address binding networking options and character sets

                bull Object data points and configurations

                BACnet Protocol Implementation Conformance Statement (PICS)

                Standardized Device Profile (Annex L)

                Interoperability Building Blocks (Annex K)

                Profile Description Supported Profile

                BACnet Advanced Application Controller (B-AAC)

                BACnet Application Specific Controller (B-ASC)

                BACnet Building Controller (B-BC)

                BACnet Operator Workstation (B-OWS)

                BACnet Smart Actuator (B-SA)

                BACnet Smart Sensor (B-SS)

                Data Sharing Description Supported BIBB

                Data Sharing-COV-B (DS-COV-B)

                Data Sharing-ReadProperty-A (DS-RP-A)

                Data Sharing-ReadProperty-B (DS-RP-B)

                Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)

                Data Sharing-WriteProperty-A (DS-WP-A)

                Data Sharing-WriteProperty-B (DS-WP-B)

                Data Sharing-WritePropertyMultiple-B (DS-WPM-B)

                Alarm and Event Management Description Supported BIBB

                Alarm and Event-ACKI-B (AE-ACK-B)

                Alarm and Event-Alarm Summary-B (AE-ASUM-B)

                Alarm and Event-Enrollment Summary-B (AE-ESUM-B)

                Alarm and Event-Information-B (AE-INFO-B)

                Alarm and Event-Notification Internal-B (AE-N-I-B)

                18 ACC-SVP01B-EN bull BCI-I Integration Guide

                BACnet Data Points and Configuration Property Definitions

                Segmentation Capability

                Trending Description Supported BIBB

                Trending-Automated Trend Retrieval-B (T-ATR-B)

                Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

                Device Management Description Supported BIBB

                Device Management-Backup and Restore-B (DM-BR-B)

                Device Management-Device Communication Control-B (DM-DCC-B)

                Device Management-Dynamic Device Binding-A (DM-DDB-A)

                Device Management-Dynamic Device Binding-B (DM-DDB-B)

                Device Management-Dynamic Object Binding-B (DM-DOB-B)

                Device Management-List Manipulation-B (DM-LM-B)

                Device Management-Object Creation and Deletion-B (DM-OCD-B)

                Device Management-Private Transfer-A (DM-PT-A)

                Device Management-Private Transfer-B (DM-PT-B)

                Device Management-Reinitialize Device-B (DM-RD-B)

                Device Management-TimeSynchronization-B (DM-TS-B)

                Segmentation Description Supported Segment

                Segmented Requests Window Size 1

                Segmented Responses Window Size 1

                ACC-SVP01B-EN bull BCI-I Integration Guide 19

                BACnet Data Points and Configuration Property Definitions

                Object Types

                Table 2 Descriptions and configurations

                Object Type Required Properties Read Properties Written(a) Optional Properties Read

                Ability to Create

                Ability to Delete

                Analog Input

                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                Yes Yes only user created objects

                Analog Output

                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

                bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                Yes Yes only user created objects

                Analog Value

                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                Yes Yes only user created objects

                Binary Input

                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                Yes Yes only user created objects

                20 ACC-SVP01B-EN bull BCI-I Integration Guide

                BACnet Data Points and Configuration Property Definitions

                Binary Output

                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

                bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

                bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                Yes Yes only user created objects

                Binary Value

                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                Yes Yes only user created objects

                Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

                bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

                bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

                None None

                Event Enrollment Object

                bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

                bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

                bull None Yes Yes only user created objects

                Table 2 Descriptions and configurations (continued)

                Object Type Required Properties Read Properties Written(a) Optional Properties Read

                Ability to Create

                Ability to Delete

                ACC-SVP01B-EN bull BCI-I Integration Guide 21

                BACnet Data Points and Configuration Property Definitions

                Multistate Input

                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                Yes Yes only user created objects

                Multistate Output

                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

                bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

                bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                Yes Yes only user created objects

                Multistate Value

                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                Yes Yes only user created objects

                Notification Class

                bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

                bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

                None Yes Yes only user created objects

                Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

                bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

                bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

                Yes Yes only user created objects

                (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

                Table 2 Descriptions and configurations (continued)

                Object Type Required Properties Read Properties Written(a) Optional Properties Read

                Ability to Create

                Ability to Delete

                22 ACC-SVP01B-EN bull BCI-I Integration Guide

                BACnet Data Points and Configuration Property Definitions

                BACnet Protocol

                Data Link Layer Options

                Device Address Binding

                Networking Options

                Data Link Layer Description Supported Option

                ANSIATA 8781 25 Mb ARCNET (Clause 8)

                ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

                BACnet IP (Annex J)

                BACnet IP (Annex J) Foreign Device

                ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

                LonTalk (Clause 11) Medium

                MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

                MSTP Slave (Clause 9) Baud Rate(s)

                Other

                Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

                Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

                Device Address Binding Supported

                Static Device Binding Supported

                Networking DescriptionsSupported

                Option

                Annex H BACnet Tunneling

                BACnetIP Broadcast Management Device (BBMD)

                Does the BBMD Support Registrations by Foreign Devices

                Router

                ACC-SVP01B-EN bull BCI-I Integration Guide 23

                BACnet Data Points and Configuration Property Definitions

                Character Sets

                Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

                Character Set Descriptions Supported

                ANSI X34

                IBMMicrosoft DBCS

                ISO 10646 (UCS-4)

                ISO 10646 (UCS2)

                ISO 8859-1

                JIS C 6226

                24 ACC-SVP01B-EN bull BCI-I Integration Guide

                Object Data Points and Diagnostic Data Points

                Object Data Points and Diagnostic Data Points

                For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

                Table 3 Analog Output

                Object Identifier Object Name Description Units Valid Range

                Refresh Rate

                (Sec)

                Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

                Percent (98) 0 to 100 NA

                Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

                Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

                Degrees-Fahrenheit (64) 500 to 900 NA

                Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

                BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

                Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

                Degrees-Fahrenheit (64) 400 to 900 NA

                Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

                Degrees-Fahrenheit (64) 400 to 1800 NA

                Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

                070 to 510 (Ipak II) NA

                Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

                003 to 030-002 to 030 (enhanced StatiTrac)

                NA

                Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

                -028 to 050-067 to 067 (enhanced StatiTrac)

                900

                Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

                00 to 79 (Ipak II) 900

                Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

                Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

                Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

                Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

                Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

                Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

                Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

                Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

                Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

                ACC-SVP01B-EN bull BCI-I Integration Guide 25

                Object Data Points and Diagnostic Data Points

                Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                Cooling temperature setpoint used for control in unoccupied mode

                Degrees-Fahrenheit (64) 520 to 880 NA

                Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                Heating temperature setpoint used for control in unoccupied mode

                Degrees-Fahrenheit (64) 500 to 900 NA

                Table 4 Analog Input

                Object Identifier Object Name Description Units (Listed Are Defaults)

                Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                Table 3 Analog Output (continued)

                Object Identifier Object Name Description Units Valid Range

                Refresh Rate

                (Sec)

                26 ACC-SVP01B-EN bull BCI-I Integration Guide

                Object Data Points and Diagnostic Data Points

                Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                Table 4 Analog Input (continued)

                Object Identifier Object Name Description Units (Listed Are Defaults)

                ACC-SVP01B-EN bull BCI-I Integration Guide 27

                Object Data Points and Diagnostic Data Points

                Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                Table 5 Analog Value

                Object Identifier Object Name Description Units Valid Range

                Analog Value 1 Filter Runtime Hours Setpoint

                The setpoint value used by the filter run hours calculation

                Hours (71) 0 to 10000

                Table 4 Analog Input (continued)

                Object Identifier Object Name Description Units (Listed Are Defaults)

                28 ACC-SVP01B-EN bull BCI-I Integration Guide

                Object Data Points and Diagnostic Data Points

                Table 6 Multistate Output

                BCI-I Object Identifier Object Name Description Object States

                Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                1 = Flow2 = No Flow3 = Auto

                Table 7 Multistate Input

                BCI-I Object Identifier Object Name Description Object States

                Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                Multi-State Input 9 Economizer Type General description of the equipment economizer system

                1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                Multi-State Input 10 Condenser Type General description of the equipment condenser system

                1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                ACC-SVP01B-EN bull BCI-I Integration Guide 29

                Object Data Points and Diagnostic Data Points

                Multi-State Input 15 Economizer Decision Method

                Unit method to determine when the economizer system is enabled

                1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                1 = Idle2 = On3 = Cancel

                Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                1 = Off2 = On3 = Not Present

                Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                1 = Off2 = On3 = Not Present

                Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                1 = Off2 = On3 = Not Present

                Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                1 = Off|2 = On3 = Not Present

                Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                1 = Off2 = On3 = Not Present

                Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                1 = Off2 = On3 = Not Present

                Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                1 = Off2 = On3 = Not Present

                Table 7 Multistate Input (continued)

                BCI-I Object Identifier Object Name Description Object States

                30 ACC-SVP01B-EN bull BCI-I Integration Guide

                Object Data Points and Diagnostic Data Points

                Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                1 = Off2 = On3 = Not Present

                Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                1 = Off2 = On3 = Not Present

                Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                1 = Off2 = On3 = Not Present

                Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                1= Off2= On3= Not Present

                Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                Multi-State Input 43 Outdoor Air Damper Status

                Indicates the operating state of the outdoor damper

                1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                1 = Disabled2 = Enabled3 = Not Present

                Table 8 Binary Output

                Object Identifier Object Name DescriptionRelinquish Default Object States

                Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                Active = BAS Control

                Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                Active = Heating Locked Out

                Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                Active = Cooling Locked Out

                Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                Active = Enabled

                Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                Active = On

                Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                Inactive Inactive = DisabledActive = Enabled

                Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                Active = Reset

                Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                Active = Reset

                Table 7 Multistate Input (continued)

                BCI-I Object Identifier Object Name Description Object States

                ACC-SVP01B-EN bull BCI-I Integration Guide 31

                Object Data Points and Diagnostic Data Points

                Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                Active = Auto

                Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                Active = Auto

                Table 9 Binary Input

                Object Identifier Object Name Description Object States

                Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                Inactive = Standalone controlActive = BAS control

                Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                Inactive = NormalActive = Locked Out

                Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                Inactive = AutoActive = Open

                Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                Inactive = InactiveActive = Active

                Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                Inactive = DisabledActive = Enabled

                Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                Inactive = DisabledActive = Enabled

                Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                Inactive = InactiveActive = Active

                Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                Inactive = No FlowActive = Flow

                Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                Inactive = InactiveActive = Active

                Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                Inactive = InactiveActive = Active

                Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                Inactive = InactiveActive = Active

                Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                The status of evaporator frost protection function for circuit 1

                Inactive = InactiveActive = Active

                Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                The status of evaporator frost protection function for circuit 2

                Inactive = InactiveActive = Active

                Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                The status of evaporator frost protection function for circuit 3

                Inactive = InactiveActive = Active

                Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                The status of evaporator frost protection function for circuit 4

                Inactive = InactiveActive = Active

                Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                Inactive = De-energizedActive = Energized

                Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                Inactive = InactiveActive = Active

                Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                Inactive = ClosedActive = Open

                Table 10 Diagnostics Binary Input

                Object Identifier(a) Object Name Description

                Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                Binary Input 31 (use Object Identifier for RT or CSC)

                Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                Binary Input 31 (use Object Identifier for FAU)

                Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                Table 8 Binary Output

                Object Identifier Object Name DescriptionRelinquish Default Object States

                32 ACC-SVP01B-EN bull BCI-I Integration Guide

                Object Data Points and Diagnostic Data Points

                Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                Binary Input 58 (use Object Identifier for RT or CSC)

                Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                Binary Input 58 (use Object Identifier for FAU)

                Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                Table 10 Diagnostics Binary Input (continued)

                Object Identifier(a) Object Name Description

                ACC-SVP01B-EN bull BCI-I Integration Guide 33

                Object Data Points and Diagnostic Data Points

                Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                Binary Input 86 (use Object Identifier for RT I-pak II)

                Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                Binary Input 121 (use Object Identifier for RT)

                Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                Binary Input 121 (use Object Identifier for FAU)

                Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                Table 10 Diagnostics Binary Input (continued)

                Object Identifier(a) Object Name Description

                34 ACC-SVP01B-EN bull BCI-I Integration Guide

                Object Data Points and Diagnostic Data Points

                Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                (a) Object States Inactive = normal and Active = foreign language specific

                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                Object Identifier(a) Object Name Description

                Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                Multi-State Input 10 Condenser Type General description of the equipment condenser system

                Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                Table 10 Diagnostics Binary Input (continued)

                Object Identifier(a) Object Name Description

                ACC-SVP01B-EN bull BCI-I Integration Guide 35

                Object Data Points and Diagnostic Data Points

                Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                Analog Input 81 Cool Type Describes the cooling type installed in the unit

                Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                Object Identifier(a) Object Name Description

                36 ACC-SVP01B-EN bull BCI-I Integration Guide

                Object Data Points and Diagnostic Data Points

                Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                Multi-State Input 9 Economizer Type General description of the equipment economizer system

                Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                Multi-State Input 36 Final Filter Status Indicates the final filter media state

                Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                Object Identifier(a) Object Name Description

                ACC-SVP01B-EN bull BCI-I Integration Guide 37

                Object Data Points and Diagnostic Data Points

                Binary Output 16 Humidification Command Command the operating state of the humidification system

                NC 3 HVAC-Advisory HVAC-Advisory

                NC 1 HVAC-Critical HVAC-Critical

                NC 4 HVAC-Information HVAC-Information

                NC 2 HVAC-Service Required HVAC-Service Required

                Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                Analog Input 82 Preheat Type Describes the heating type installed in the unit

                Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                Object Identifier(a) Object Name Description

                38 ACC-SVP01B-EN bull BCI-I Integration Guide

                Object Data Points and Diagnostic Data Points

                Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                Binary Input 3 Unit Status Indicates the current state of the unit

                Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                Object Identifier(a) Object Name Description

                Table 12 Diagnostic Objects Sorted by Object Name

                Object Identifier(a) Object Name ValueRange Description

                BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                ACC-SVP01B-EN bull BCI-I Integration Guide 39

                Object Data Points and Diagnostic Data Points

                BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                Object Identifier(a) Object Name ValueRange Description

                40 ACC-SVP01B-EN bull BCI-I Integration Guide

                Object Data Points and Diagnostic Data Points

                BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                Object Identifier(a) Object Name ValueRange Description

                ACC-SVP01B-EN bull BCI-I Integration Guide 41

                Object Data Points and Diagnostic Data Points

                BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                BI 121 (use Object Identifier for RT)

                Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                BI 58 (use Object Identifier for RT or CSC)

                Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                BI 31 (use Object Identifier for RT CSC)

                Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                BI 121 (use Object Identifier for FAU)

                Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                B1 31 (use Object Identifier for FAU)

                Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                Object Identifier(a) Object Name ValueRange Description

                42 ACC-SVP01B-EN bull BCI-I Integration Guide

                Object Data Points and Diagnostic Data Points

                BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                1 = active Diagnostic Vel Press Sensor (Rear)

                BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                Object Identifier(a) Object Name ValueRange Description

                ACC-SVP01B-EN bull BCI-I Integration Guide 43

                Object Data Points and Diagnostic Data Points

                BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                BI 58 (use Object Identifier for FAU)

                Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                (a) BI=Binary Input

                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                Object Identifier(a) Object Name ValueRange Description

                44 ACC-SVP01B-EN bull BCI-I Integration Guide

                Additional Resources

                Additional Resources

                Use the following documents and links as additional resources

                bull Product support online

                bull wwwbacnetorg

                bull wwwbacnetassociationorg

                bull wwwashraeorg

                bull Tracer TU Help online

                bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                Note For further assistance contact your local Trane sales office

                ACC-SVP01B-EN bull BCI-I Integration Guide 45

                Glossary

                A

                ASHRAE

                See American Society of Heating Refrigeration and Air-conditioning Engineers

                American Society of Heating Refrigeration and Air-

                conditioning Engineers

                An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                BBACnettrade

                See Building Automation Control network

                BACnet interoperability building blocks

                A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                BACnet object

                An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                baud rate

                The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                BIBB

                See BACnet interoperability building blocks

                Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                advocates BACnet protocol for use in system-level control devices

                device

                A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                Device ID

                The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                Iinteroperability

                The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                Pprotocol

                A set of rules (language) that governs the exchange of data over a digital communications system

                S

                stand-alone operation

                Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                wwwtranecom

                For more information contact your local Trane office or e-mail us at comforttranecom

                Literature Order Number ACC-SVP01B-EN

                Date September 2009

                Supersedes ACC-SVP01A-EN

                Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                • Table of Contents
                • Overview
                • Ordering Numbers
                • BACnet Protocol
                • BCI-I Configuration
                  • Overview
                  • Starting a Session of Tracer TU and Direct Connection
                  • Reset to Factory Default
                  • IP Units Configuration
                  • BACnet Object Configuration
                  • Change Baud Rate
                  • Change Device ID
                  • Stand-alone or BAS Operation
                    • IntelliPak Control Configuration
                    • BAS Unit Control
                    • Periodic Update of BAS Values
                    • BAS Communication Failure
                      • InputOutput Commands and Calculations
                        • System Control Command
                        • Filter Timer Reset Command
                        • Diagnostics Reset Command
                        • Setpoint Calculations
                        • Timestamp Configuration
                            • BCI IntelliPak Rotary Switches and LEDs
                              • Rotary Switches
                              • LEDs Description Behavior and Troubleshooting
                              • 24 Vac Measurement
                              • Ground Measurements
                                • BACnet Data Points and Configuration Property Definitions
                                  • BACnet Protocol Implementation Conformance Statement (PICS)
                                    • Standardized Device Profile (Annex L)
                                    • Interoperability Building Blocks (Annex K)
                                    • Segmentation Capability
                                    • Object Types
                                      • BACnet Protocol
                                        • Data Link Layer Options
                                        • Device Address Binding
                                        • Networking Options
                                        • Character Sets
                                            • Object Data Points and Diagnostic Data Points
                                            • Additional Resources
                                            • Glossary

                  ACC-SVP01B-EN bull BCI-I Integration Guide 9

                  BCI-I Configuration

                  Periodic Update of BAS Values

                  The BCI-I device requires the BAS system to provide a periodic update to the sensor values This is required to protect against a loss of communication between the BAS and the BCI-I By BACnet definition the present value of the object will maintain the last value written to it regardless of the amount of time that has elapsed since the last write If communication is lost for several minutes or longer the present value of BAS-supplied sensor objects may no longer represent the current state of environmental conditions This may result in decreased occupant comfort and damage to building systems

                  BAS Communication Failure

                  The BCI-I is designed to minimize communication failure mode It does this by monitoring the length of time that has elapsed since the last write to the present value of the sensor object If the length of time exceeds a predefined limit the BCI-I will place the object into the fault state and revert to a unit-supplied sensor value for control At power up the sensor objects are set to a fault state and they will remain in this state until a write is detected The minimum periodic refresh rate for the objects is defined in Table 3 p 24 The following list is a set of sensor values that can be supplied by the BAS

                  bull Space Static Pressure BAS

                  bull Space Air Temperature BAS

                  bull Discharge Air Temperature BAS

                  bull Duct Static Air Pressure BAS

                  bull Outdoor Air Temperature BAS

                  bull Outdoor Air Humidity BAS

                  bull Outdoor Airflow BAS

                  bull Space CO2 Concentration BAS

                  bull Space Humidity BAS

                  InputOutput Commands and Calculations

                  This section will provide the following information about certain inputs and outputs that perform unique control commands and calculations

                  bull System control command

                  bull Filter timer and diagnostic reset commands

                  bull Setpoint calculations

                  System Control Command

                  Binary Output Object 1 has a special importance in the system The object allows the BAS to command the unit to run in a local or BAS control mode When the present value property of the object is set to Local Control the IntelliPak unit will enter local control and ignore BAS supplied values In this mode the unit will use local sensor and setpoint values When the object present value property is set to BAS Control the IntelliPak unit will use the values supplied by the BAS system for unit control

                  Filter Timer Reset Command

                  The BCI-I uses the Filter Runtime Hours object (AI 6) to generate a diagnostic when its present value is greater than the Filter Runtime Hours Setpoint (AV 1) present value The procedure for resetting the timer is as follows

                  10 ACC-SVP01B-EN bull BCI-I Integration Guide

                  BCI-I Configuration

                  The BAS will change the state of the Filter Timer Reset Command object (BO 13) to the active state Upon the change to active state the BCI-I will set the present value of the Filter Runtime Hours object to zero and then set the Reset Command object back to the inactive state

                  Diagnostics Reset Command

                  The IntelliPak control system monitors the operation of the HVAC equipment If an abnormal condition is detected a diagnostic message is displayed on the human interface of the equipment control panel In addition the set of internal diagnostics is mapped to the set of BACnet binary input objects as listed in Table 9 p 31 The corresponding BI object will change state from inactive to active when the diagnostic is detected The object has been configured to send a BACnet event message to external BACnet devices as defined by the protocol

                  The BAS has the ability to reset internal diagnostics by controlling the state of the Diagnostic Reset Command object (BO 14) The procedure for resetting diagnostics is as follows

                  The BAS will change the state of the Diagnostic Reset to the active state Upon the change to active state the IntelliPak control system will reset all internal diagnostics and set the state of all of the diagnostic objects to inactive Upon completion of this action the BCI-I will set the present value of the Diagnostic Reset Command object back to the inactive state

                  Setpoint Calculations

                  The equipment has the ability to perform two basic control functions

                  bull Space air temperature control

                  bull Discharge air temperature control

                  When the unit is configured for discharge air control it controls the temperature of the air leaving the unit to the discharge air temperature setpoint

                  When the unit is configured for space air temperature control it controls the air temperature of the space that contains the space air temperature sensor This value may be provided by wiring the sensor to the unit or via a sensor value provided by the BAS

                  The drawing below describes how the various temperature setpoints are calculated for space temperature control When the unit is in an occupied mode the active space temperature setpoint is calculated based on the space temperature setpoint and the two setpoint offset values In unoccupied mode the unoccupied heating and cooling setpoints are used as the active setpoint

                  ACC-SVP01B-EN bull BCI-I Integration Guide 11

                  BCI-I Configuration

                  Timestamp Configuration

                  The BCI-C device has a software-derived clock that maintains the time and date The device requires the current time to enable it to record a timestamp when an event or a change in state is detected by a BACnet object However in the event of a power loss the device does not maintain this time and date information At powerup the device time and date will default to 1200 pm Jan 1 1970 To minimize the possibility that the unit timestamp is not representing the actual time the BAS should be setup to periodically synchronize the device time clock with the BAS clock using the BACnet TimeSynchronization service

                  12 ACC-SVP01B-EN bull BCI-I Integration Guide

                  BCI IntelliPak Rotary Switches and LEDs

                  BCI IntelliPak Rotary Switches and LEDs

                  This section provides information about the BCI-I rotary switches and LED displays

                  Rotary Switches

                  There are three rotary switches on the front of the BCI-I device that are used to define a three-digit address when the BCI-I is installed on a BACnet communications network The three-digit address setting is the BACnet MAC address

                  Note All devices are MSTP masters with valid MAC addresses of 001 to 127 for BACnet

                  Figure 1 Setting rotary switches

                  ADDRESS0 1

                  23

                  456

                  78

                  9

                  x1

                  0 1

                  23

                  456

                  78

                  9

                  x10

                  0 1

                  23

                  456

                  78

                  9

                  x100

                  Before

                  After

                  0

                  5

                  1

                  3

                  6

                  29

                  487

                  Example of before and after setting addresses

                  Use a 18 inch flathead screwdriver to set rotary switches

                  Important Each device on the BACnetMSTP link must have a unique rotary switch setting otherwise communication problems will occur

                  ACC-SVP01B-EN bull BCI-I Integration Guide 13

                  BCI IntelliPak Rotary Switches and LEDs

                  LEDs Description Behavior and Troubleshooting

                  There are 15 LEDs on the front of the BCI-I unit However LEDs BO1 through BO9 are not used for the BCI-I controller Figure 2 shows the locations of each LED The following table provides a description of each LED activity an indication or troubleshooting tips for each and any notes

                  Figure 2 LED locations

                  SERVICE

                  IMCLINK

                  RX

                  TX

                  Marquee LED

                  Table 1 LED Activities and Troubleshooting Tips

                  LED Name ActivitiesIndication or Troubleshooting

                  Tip (Denoted in Bullets) Notes

                  Marquee LED

                  Shows solid green when the unit is powered and no problems exist

                  Indicates normal operation

                  Shows solid red when the unit is powered but represents low power or a

                  malfunction

                  bull If low power could be under voltage or the microprocessor has malfunction Follow the troubleshoot procedure ldquo24 Vac Measurementrdquo p 15 to measure for the expected value range

                  bull If malfunction unpower and then repower unit to bring the device back up to normal operation

                  Shows blinking red when an a BACnet object is in a fault condition

                  Alarm when an alarm is triggered for example when a point goes into fault condition because of point failure or there is an indication of a custom alarm in TGP2

                  Shows blinking green when the device does not detect the IMC buss

                  bull Verify that the IPC wiring harness is connected to the IMC link terminals

                  bull Verify the polarity of the IPC wiring harness at the unit terminals

                  LED not lit

                  Indicates power is OFF or there is a malfunction

                  bull OFF or malfunction cycle the power

                  14 ACC-SVP01B-EN bull BCI-I Integration Guide

                  BCI IntelliPak Rotary Switches and LEDs

                  Link and IMC

                  TX blinks greenBlinks at the data transfer rate when the unit transfers data to other devices on the link

                  TX LED Regardless of connectivity or not this LED will constantly blink as it continually looks for devices to communicate to

                  LED not litDetermine if for example a Tracer SC or BACnet device is trying to talk to the controller or if it is capable of talking to the controller Also determine if the communication status shows down all of the time

                  Refer to ldquoGround Measurementsrdquo p 16 for a check-out procedure

                  RX blinks yellow

                  Blinks at the data transfer rate when the unit receives data from other devices on the link

                  bull ON solid yellow indicates there is reverse polarity

                  LED not lit

                  Indicates that the controller is not detecting communication

                  bull Not lit cycle the power to reestablish communication

                  Service

                  Shows solid greenIndicates someone is pressing this LED or the controller is not operating normally

                  Press and hold during power up to place controller into boot code or press and hold for a count of approximately 10 seconds to clear the Device ID

                  What is Boot Code When the UC400 is placed into boot code the system will not run any applications such as trending scheduling and TGP2 runtime

                  Blinks green

                  Indicates controllers is not accessing application software

                  bull Restore using TU service tool

                  LED not lit Indicates controller is operating normally

                  Binary 01 to Binary 09 Not Used

                  Table 1 LED Activities and Troubleshooting Tips

                  LED Name ActivitiesIndication or Troubleshooting

                  Tip (Denoted in Bullets) Notes

                  ACC-SVP01B-EN bull BCI-I Integration Guide 15

                  BCI IntelliPak Rotary Switches and LEDs

                  24 Vac Measurement

                  General Information Checkout Procedure Measurement Expected Value

                  Checking the voltage that is powering the UC400 is often a necessary step when commissioning or troubleshooting Operational issues and LED operation may result in a need to measure the input power

                  When troubleshooting it is faster to take measurements while the load is in place If Step 1 indicates an out-of-specification voltage disconnect the UC400 and measure the AC voltage across the transformer These measurements can direct the technician towards the problem source

                  Step 1

                  Measure AC voltage with the UC400 connected Perform this measurement while the unit is under load

                  200 Vac le Vac le 300 Vac

                  Step 2

                  Measure AC voltage with the UC400 unconnected Perform this measurement while the unit is not under load

                  200 Vac le Vac le 300 Vac

                  16 ACC-SVP01B-EN bull BCI-I Integration Guide

                  BCI IntelliPak Rotary Switches and LEDs

                  Ground Measurements

                  General Information and Checkout Procedure Measurement Expected Value

                  Method 1AC voltage between shield conductors and device chassis ground- the voltage difference between BACnet MSTP device chassis ground connections should be close to zero If the voltage difference is greater that 40 Vac there will be marginal communication or intermittent communication problems If the voltage difference is greater that 70 Vac some devices will no longer communicate

                  Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                  Vac le 20 V

                  Method 2AC voltage between earth ground and device chassis ground- the chassis ground of the UC400 needs to be connected to earth ground by some route

                  Note Do not assume that the building frame is a valid earth ground

                  Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                  Vac le 40 V (Must comply with National Electrical Codetradeand local electrical codes)

                  ACC-SVP01B-EN bull BCI-I Integration Guide 17

                  BACnet Data Points and Configuration Property Definitions

                  BACnet Data Points and Configuration Property

                  Definitions

                  The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MSTP This section includes information about

                  bull BACnet protocol implementation conformance statement (PICS)

                  bull Object types descriptions and configuration (refer to Table 2 p 19)

                  bull BACnet protocol data link layers device address binding networking options and character sets

                  bull Object data points and configurations

                  BACnet Protocol Implementation Conformance Statement (PICS)

                  Standardized Device Profile (Annex L)

                  Interoperability Building Blocks (Annex K)

                  Profile Description Supported Profile

                  BACnet Advanced Application Controller (B-AAC)

                  BACnet Application Specific Controller (B-ASC)

                  BACnet Building Controller (B-BC)

                  BACnet Operator Workstation (B-OWS)

                  BACnet Smart Actuator (B-SA)

                  BACnet Smart Sensor (B-SS)

                  Data Sharing Description Supported BIBB

                  Data Sharing-COV-B (DS-COV-B)

                  Data Sharing-ReadProperty-A (DS-RP-A)

                  Data Sharing-ReadProperty-B (DS-RP-B)

                  Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)

                  Data Sharing-WriteProperty-A (DS-WP-A)

                  Data Sharing-WriteProperty-B (DS-WP-B)

                  Data Sharing-WritePropertyMultiple-B (DS-WPM-B)

                  Alarm and Event Management Description Supported BIBB

                  Alarm and Event-ACKI-B (AE-ACK-B)

                  Alarm and Event-Alarm Summary-B (AE-ASUM-B)

                  Alarm and Event-Enrollment Summary-B (AE-ESUM-B)

                  Alarm and Event-Information-B (AE-INFO-B)

                  Alarm and Event-Notification Internal-B (AE-N-I-B)

                  18 ACC-SVP01B-EN bull BCI-I Integration Guide

                  BACnet Data Points and Configuration Property Definitions

                  Segmentation Capability

                  Trending Description Supported BIBB

                  Trending-Automated Trend Retrieval-B (T-ATR-B)

                  Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

                  Device Management Description Supported BIBB

                  Device Management-Backup and Restore-B (DM-BR-B)

                  Device Management-Device Communication Control-B (DM-DCC-B)

                  Device Management-Dynamic Device Binding-A (DM-DDB-A)

                  Device Management-Dynamic Device Binding-B (DM-DDB-B)

                  Device Management-Dynamic Object Binding-B (DM-DOB-B)

                  Device Management-List Manipulation-B (DM-LM-B)

                  Device Management-Object Creation and Deletion-B (DM-OCD-B)

                  Device Management-Private Transfer-A (DM-PT-A)

                  Device Management-Private Transfer-B (DM-PT-B)

                  Device Management-Reinitialize Device-B (DM-RD-B)

                  Device Management-TimeSynchronization-B (DM-TS-B)

                  Segmentation Description Supported Segment

                  Segmented Requests Window Size 1

                  Segmented Responses Window Size 1

                  ACC-SVP01B-EN bull BCI-I Integration Guide 19

                  BACnet Data Points and Configuration Property Definitions

                  Object Types

                  Table 2 Descriptions and configurations

                  Object Type Required Properties Read Properties Written(a) Optional Properties Read

                  Ability to Create

                  Ability to Delete

                  Analog Input

                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                  bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                  bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                  Yes Yes only user created objects

                  Analog Output

                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

                  bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                  bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                  Yes Yes only user created objects

                  Analog Value

                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                  bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                  bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                  Yes Yes only user created objects

                  Binary Input

                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                  bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                  bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                  Yes Yes only user created objects

                  20 ACC-SVP01B-EN bull BCI-I Integration Guide

                  BACnet Data Points and Configuration Property Definitions

                  Binary Output

                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

                  bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

                  bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                  Yes Yes only user created objects

                  Binary Value

                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                  bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                  bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                  Yes Yes only user created objects

                  Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

                  bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

                  bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

                  None None

                  Event Enrollment Object

                  bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

                  bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

                  bull None Yes Yes only user created objects

                  Table 2 Descriptions and configurations (continued)

                  Object Type Required Properties Read Properties Written(a) Optional Properties Read

                  Ability to Create

                  Ability to Delete

                  ACC-SVP01B-EN bull BCI-I Integration Guide 21

                  BACnet Data Points and Configuration Property Definitions

                  Multistate Input

                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                  bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                  bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                  Yes Yes only user created objects

                  Multistate Output

                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

                  bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

                  bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                  Yes Yes only user created objects

                  Multistate Value

                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                  bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                  bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                  Yes Yes only user created objects

                  Notification Class

                  bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

                  bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

                  None Yes Yes only user created objects

                  Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

                  bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

                  bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

                  Yes Yes only user created objects

                  (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

                  Table 2 Descriptions and configurations (continued)

                  Object Type Required Properties Read Properties Written(a) Optional Properties Read

                  Ability to Create

                  Ability to Delete

                  22 ACC-SVP01B-EN bull BCI-I Integration Guide

                  BACnet Data Points and Configuration Property Definitions

                  BACnet Protocol

                  Data Link Layer Options

                  Device Address Binding

                  Networking Options

                  Data Link Layer Description Supported Option

                  ANSIATA 8781 25 Mb ARCNET (Clause 8)

                  ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

                  BACnet IP (Annex J)

                  BACnet IP (Annex J) Foreign Device

                  ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

                  LonTalk (Clause 11) Medium

                  MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

                  MSTP Slave (Clause 9) Baud Rate(s)

                  Other

                  Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

                  Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

                  Device Address Binding Supported

                  Static Device Binding Supported

                  Networking DescriptionsSupported

                  Option

                  Annex H BACnet Tunneling

                  BACnetIP Broadcast Management Device (BBMD)

                  Does the BBMD Support Registrations by Foreign Devices

                  Router

                  ACC-SVP01B-EN bull BCI-I Integration Guide 23

                  BACnet Data Points and Configuration Property Definitions

                  Character Sets

                  Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

                  Character Set Descriptions Supported

                  ANSI X34

                  IBMMicrosoft DBCS

                  ISO 10646 (UCS-4)

                  ISO 10646 (UCS2)

                  ISO 8859-1

                  JIS C 6226

                  24 ACC-SVP01B-EN bull BCI-I Integration Guide

                  Object Data Points and Diagnostic Data Points

                  Object Data Points and Diagnostic Data Points

                  For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

                  Table 3 Analog Output

                  Object Identifier Object Name Description Units Valid Range

                  Refresh Rate

                  (Sec)

                  Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

                  Percent (98) 0 to 100 NA

                  Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

                  Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

                  Degrees-Fahrenheit (64) 500 to 900 NA

                  Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

                  BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

                  Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

                  Degrees-Fahrenheit (64) 400 to 900 NA

                  Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

                  Degrees-Fahrenheit (64) 400 to 1800 NA

                  Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

                  070 to 510 (Ipak II) NA

                  Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

                  003 to 030-002 to 030 (enhanced StatiTrac)

                  NA

                  Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

                  -028 to 050-067 to 067 (enhanced StatiTrac)

                  900

                  Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                  Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                  Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

                  00 to 79 (Ipak II) 900

                  Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                  Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

                  Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

                  Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

                  Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

                  Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

                  Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

                  Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

                  Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

                  Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

                  ACC-SVP01B-EN bull BCI-I Integration Guide 25

                  Object Data Points and Diagnostic Data Points

                  Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                  Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                  Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                  Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                  Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                  Cooling temperature setpoint used for control in unoccupied mode

                  Degrees-Fahrenheit (64) 520 to 880 NA

                  Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                  Heating temperature setpoint used for control in unoccupied mode

                  Degrees-Fahrenheit (64) 500 to 900 NA

                  Table 4 Analog Input

                  Object Identifier Object Name Description Units (Listed Are Defaults)

                  Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                  Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                  Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                  Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                  Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                  Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                  Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                  Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                  Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                  Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                  Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                  Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                  Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                  Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                  Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                  Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                  Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                  Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                  Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                  Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                  Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                  Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                  Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                  Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                  Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                  Table 3 Analog Output (continued)

                  Object Identifier Object Name Description Units Valid Range

                  Refresh Rate

                  (Sec)

                  26 ACC-SVP01B-EN bull BCI-I Integration Guide

                  Object Data Points and Diagnostic Data Points

                  Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                  Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                  Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                  Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                  Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                  Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                  Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                  Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                  Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                  Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                  Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                  Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                  Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                  Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                  Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                  Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                  Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                  Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                  Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                  Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                  Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                  Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                  Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                  Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                  The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                  Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                  The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                  Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                  Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                  Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                  Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                  Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                  Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                  Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                  Table 4 Analog Input (continued)

                  Object Identifier Object Name Description Units (Listed Are Defaults)

                  ACC-SVP01B-EN bull BCI-I Integration Guide 27

                  Object Data Points and Diagnostic Data Points

                  Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                  Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                  Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                  Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                  The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                  Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                  Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                  Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                  Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                  Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                  Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                  Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                  Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                  Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                  Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                  Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                  Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                  Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                  Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                  Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                  Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                  Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                  Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                  Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                  Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                  Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                  Table 5 Analog Value

                  Object Identifier Object Name Description Units Valid Range

                  Analog Value 1 Filter Runtime Hours Setpoint

                  The setpoint value used by the filter run hours calculation

                  Hours (71) 0 to 10000

                  Table 4 Analog Input (continued)

                  Object Identifier Object Name Description Units (Listed Are Defaults)

                  28 ACC-SVP01B-EN bull BCI-I Integration Guide

                  Object Data Points and Diagnostic Data Points

                  Table 6 Multistate Output

                  BCI-I Object Identifier Object Name Description Object States

                  Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                  Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                  1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                  Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                  Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                  1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                  Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                  1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                  Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                  1 = Flow2 = No Flow3 = Auto

                  Table 7 Multistate Input

                  BCI-I Object Identifier Object Name Description Object States

                  Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                  1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                  Multi-State Input 9 Economizer Type General description of the equipment economizer system

                  1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                  Multi-State Input 10 Condenser Type General description of the equipment condenser system

                  1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                  Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                  1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                  ACC-SVP01B-EN bull BCI-I Integration Guide 29

                  Object Data Points and Diagnostic Data Points

                  Multi-State Input 15 Economizer Decision Method

                  Unit method to determine when the economizer system is enabled

                  1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                  Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                  Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                  Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                  1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                  Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                  1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                  Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                  1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                  Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                  1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                  Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                  1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                  Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                  1 = Idle2 = On3 = Cancel

                  Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                  1 = Off2 = On3 = Not Present

                  Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                  1 = Off2 = On3 = Not Present

                  Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                  1 = Off2 = On3 = Not Present

                  Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                  1 = Off|2 = On3 = Not Present

                  Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                  1 = Off2 = On3 = Not Present

                  Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                  1 = Off2 = On3 = Not Present

                  Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                  1 = Off2 = On3 = Not Present

                  Table 7 Multistate Input (continued)

                  BCI-I Object Identifier Object Name Description Object States

                  30 ACC-SVP01B-EN bull BCI-I Integration Guide

                  Object Data Points and Diagnostic Data Points

                  Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                  1 = Off2 = On3 = Not Present

                  Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                  1 = Off2 = On3 = Not Present

                  Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                  Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                  Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                  Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                  Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                  1 = Off2 = On3 = Not Present

                  Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                  1= Off2= On3= Not Present

                  Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                  Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                  Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                  Multi-State Input 43 Outdoor Air Damper Status

                  Indicates the operating state of the outdoor damper

                  1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                  Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                  1 = Disabled2 = Enabled3 = Not Present

                  Table 8 Binary Output

                  Object Identifier Object Name DescriptionRelinquish Default Object States

                  Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                  Active = BAS Control

                  Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                  Active = Heating Locked Out

                  Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                  Active = Cooling Locked Out

                  Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                  Active = Enabled

                  Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                  Active = On

                  Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                  Inactive Inactive = DisabledActive = Enabled

                  Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                  Active = Reset

                  Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                  Active = Reset

                  Table 7 Multistate Input (continued)

                  BCI-I Object Identifier Object Name Description Object States

                  ACC-SVP01B-EN bull BCI-I Integration Guide 31

                  Object Data Points and Diagnostic Data Points

                  Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                  Active = Auto

                  Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                  Active = Auto

                  Table 9 Binary Input

                  Object Identifier Object Name Description Object States

                  Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                  Inactive = Standalone controlActive = BAS control

                  Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                  Inactive = NormalActive = Locked Out

                  Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                  Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                  Inactive = AutoActive = Open

                  Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                  Inactive = InactiveActive = Active

                  Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                  Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                  Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                  Inactive = DisabledActive = Enabled

                  Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                  Inactive = DisabledActive = Enabled

                  Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                  Inactive = InactiveActive = Active

                  Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                  Inactive = No FlowActive = Flow

                  Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                  Inactive = InactiveActive = Active

                  Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                  Inactive = InactiveActive = Active

                  Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                  Inactive = InactiveActive = Active

                  Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                  The status of evaporator frost protection function for circuit 1

                  Inactive = InactiveActive = Active

                  Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                  The status of evaporator frost protection function for circuit 2

                  Inactive = InactiveActive = Active

                  Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                  The status of evaporator frost protection function for circuit 3

                  Inactive = InactiveActive = Active

                  Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                  The status of evaporator frost protection function for circuit 4

                  Inactive = InactiveActive = Active

                  Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                  Inactive = De-energizedActive = Energized

                  Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                  Inactive = InactiveActive = Active

                  Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                  Inactive = ClosedActive = Open

                  Table 10 Diagnostics Binary Input

                  Object Identifier(a) Object Name Description

                  Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                  Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                  Binary Input 31 (use Object Identifier for RT or CSC)

                  Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                  Binary Input 31 (use Object Identifier for FAU)

                  Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                  Table 8 Binary Output

                  Object Identifier Object Name DescriptionRelinquish Default Object States

                  32 ACC-SVP01B-EN bull BCI-I Integration Guide

                  Object Data Points and Diagnostic Data Points

                  Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                  Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                  Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                  Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                  Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                  Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                  Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                  Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                  Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                  Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                  Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                  Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                  Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                  Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                  Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                  Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                  Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                  Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                  Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                  Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                  Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                  Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                  Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                  Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                  Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                  Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                  Binary Input 58 (use Object Identifier for RT or CSC)

                  Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                  Binary Input 58 (use Object Identifier for FAU)

                  Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                  Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                  Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                  Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                  Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                  Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                  Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                  Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                  Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                  Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                  Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                  Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                  Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                  Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                  Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                  Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                  Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                  Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                  Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                  Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                  Table 10 Diagnostics Binary Input (continued)

                  Object Identifier(a) Object Name Description

                  ACC-SVP01B-EN bull BCI-I Integration Guide 33

                  Object Data Points and Diagnostic Data Points

                  Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                  Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                  Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                  Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                  Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                  Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                  Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                  Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                  Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                  Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                  Binary Input 86 (use Object Identifier for RT I-pak II)

                  Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                  Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                  Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                  Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                  Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                  Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                  Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                  Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                  Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                  Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                  Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                  Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                  Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                  Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                  Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                  Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                  Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                  Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                  Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                  Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                  Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                  Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                  Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                  Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                  Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                  Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                  Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                  Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                  Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                  Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                  Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                  Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                  Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                  Binary Input 121 (use Object Identifier for RT)

                  Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                  Binary Input 121 (use Object Identifier for FAU)

                  Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                  Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                  Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                  Table 10 Diagnostics Binary Input (continued)

                  Object Identifier(a) Object Name Description

                  34 ACC-SVP01B-EN bull BCI-I Integration Guide

                  Object Data Points and Diagnostic Data Points

                  Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                  Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                  Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                  Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                  Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                  Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                  Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                  Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                  Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                  Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                  Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                  Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                  Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                  Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                  Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                  Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                  Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                  Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                  Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                  Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                  Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                  Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                  Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                  Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                  Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                  Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                  (a) Object States Inactive = normal and Active = foreign language specific

                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                  Object Identifier(a) Object Name Description

                  Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                  Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                  Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                  Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                  Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                  Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                  Multi-State Input 10 Condenser Type General description of the equipment condenser system

                  Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                  Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                  Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                  Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                  Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                  Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                  Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                  Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                  Table 10 Diagnostics Binary Input (continued)

                  Object Identifier(a) Object Name Description

                  ACC-SVP01B-EN bull BCI-I Integration Guide 35

                  Object Data Points and Diagnostic Data Points

                  Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                  Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                  Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                  Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                  Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                  Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                  Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                  Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                  Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                  Analog Input 81 Cool Type Describes the cooling type installed in the unit

                  Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                  Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                  Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                  Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                  Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                  Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                  Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                  Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                  Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                  Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                  Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                  Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                  Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                  Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                  Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                  Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                  Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                  Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                  Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                  Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                  Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                  Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                  Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                  Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                  Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                  Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                  Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                  Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                  Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                  Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                  Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                  Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                  Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                  Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                  Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                  Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                  Object Identifier(a) Object Name Description

                  36 ACC-SVP01B-EN bull BCI-I Integration Guide

                  Object Data Points and Diagnostic Data Points

                  Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                  Multi-State Input 9 Economizer Type General description of the equipment economizer system

                  Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                  Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                  Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                  Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                  Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                  Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                  Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                  Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                  Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                  Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                  Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                  Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                  Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                  Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                  Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                  Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                  Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                  Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                  Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                  Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                  Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                  Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                  Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                  Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                  Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                  Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                  Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                  Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                  Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                  Multi-State Input 36 Final Filter Status Indicates the final filter media state

                  Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                  Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                  Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                  Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                  Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                  Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                  Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                  Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                  Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                  Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                  Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                  Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                  Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                  Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                  Object Identifier(a) Object Name Description

                  ACC-SVP01B-EN bull BCI-I Integration Guide 37

                  Object Data Points and Diagnostic Data Points

                  Binary Output 16 Humidification Command Command the operating state of the humidification system

                  NC 3 HVAC-Advisory HVAC-Advisory

                  NC 1 HVAC-Critical HVAC-Critical

                  NC 4 HVAC-Information HVAC-Information

                  NC 2 HVAC-Service Required HVAC-Service Required

                  Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                  Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                  Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                  Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                  Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                  Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                  Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                  Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                  Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                  Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                  Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                  Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                  Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                  Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                  Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                  Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                  Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                  Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                  Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                  Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                  Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                  Analog Input 82 Preheat Type Describes the heating type installed in the unit

                  Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                  Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                  Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                  Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                  Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                  Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                  Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                  Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                  Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                  Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                  Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                  Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                  Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                  Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                  Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                  Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                  Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                  Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                  Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                  Object Identifier(a) Object Name Description

                  38 ACC-SVP01B-EN bull BCI-I Integration Guide

                  Object Data Points and Diagnostic Data Points

                  Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                  Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                  Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                  Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                  Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                  Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                  Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                  Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                  Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                  Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                  Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                  Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                  Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                  Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                  Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                  Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                  Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                  Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                  Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                  Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                  Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                  Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                  Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                  Binary Input 3 Unit Status Indicates the current state of the unit

                  Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                  Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                  Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                  Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                  Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                  Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                  Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                  (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                  Object Identifier(a) Object Name Description

                  Table 12 Diagnostic Objects Sorted by Object Name

                  Object Identifier(a) Object Name ValueRange Description

                  BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                  BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                  ACC-SVP01B-EN bull BCI-I Integration Guide 39

                  Object Data Points and Diagnostic Data Points

                  BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                  BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                  BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                  BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                  BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                  BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                  BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                  BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                  BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                  BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                  BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                  BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                  BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                  BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                  BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                  BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                  BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                  BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                  BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                  BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                  BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                  BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                  BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                  BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                  BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                  BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                  BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                  BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                  BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                  Object Identifier(a) Object Name ValueRange Description

                  40 ACC-SVP01B-EN bull BCI-I Integration Guide

                  Object Data Points and Diagnostic Data Points

                  BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                  BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                  BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                  BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                  BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                  BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                  BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                  BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                  BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                  BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                  BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                  BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                  BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                  BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                  BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                  BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                  BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                  BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                  BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                  BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                  BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                  BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                  BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                  BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                  BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                  BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                  BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                  BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                  BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                  Object Identifier(a) Object Name ValueRange Description

                  ACC-SVP01B-EN bull BCI-I Integration Guide 41

                  Object Data Points and Diagnostic Data Points

                  BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                  BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                  BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                  BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                  BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                  BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                  BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                  BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                  BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                  BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                  BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                  BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                  BI 121 (use Object Identifier for RT)

                  Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                  BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                  BI 58 (use Object Identifier for RT or CSC)

                  Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                  BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                  BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                  BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                  BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                  BI 31 (use Object Identifier for RT CSC)

                  Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                  BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                  BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                  BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                  BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                  BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                  BI 121 (use Object Identifier for FAU)

                  Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                  B1 31 (use Object Identifier for FAU)

                  Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                  BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                  BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                  Object Identifier(a) Object Name ValueRange Description

                  42 ACC-SVP01B-EN bull BCI-I Integration Guide

                  Object Data Points and Diagnostic Data Points

                  BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                  BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                  BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                  BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                  BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                  BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                  BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                  BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                  BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                  BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                  BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                  BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                  BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                  BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                  BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                  BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                  BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                  BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                  BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                  BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                  BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                  BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                  BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                  1 = active Diagnostic Vel Press Sensor (Rear)

                  BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                  Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                  BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                  BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                  BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                  BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                  BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                  Object Identifier(a) Object Name ValueRange Description

                  ACC-SVP01B-EN bull BCI-I Integration Guide 43

                  Object Data Points and Diagnostic Data Points

                  BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                  BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                  BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                  BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                  BI 58 (use Object Identifier for FAU)

                  Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                  (a) BI=Binary Input

                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                  Object Identifier(a) Object Name ValueRange Description

                  44 ACC-SVP01B-EN bull BCI-I Integration Guide

                  Additional Resources

                  Additional Resources

                  Use the following documents and links as additional resources

                  bull Product support online

                  bull wwwbacnetorg

                  bull wwwbacnetassociationorg

                  bull wwwashraeorg

                  bull Tracer TU Help online

                  bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                  bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                  Note For further assistance contact your local Trane sales office

                  ACC-SVP01B-EN bull BCI-I Integration Guide 45

                  Glossary

                  A

                  ASHRAE

                  See American Society of Heating Refrigeration and Air-conditioning Engineers

                  American Society of Heating Refrigeration and Air-

                  conditioning Engineers

                  An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                  BBACnettrade

                  See Building Automation Control network

                  BACnet interoperability building blocks

                  A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                  BACnet object

                  An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                  baud rate

                  The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                  BIBB

                  See BACnet interoperability building blocks

                  Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                  advocates BACnet protocol for use in system-level control devices

                  device

                  A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                  Device ID

                  The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                  Iinteroperability

                  The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                  Pprotocol

                  A set of rules (language) that governs the exchange of data over a digital communications system

                  S

                  stand-alone operation

                  Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                  wwwtranecom

                  For more information contact your local Trane office or e-mail us at comforttranecom

                  Literature Order Number ACC-SVP01B-EN

                  Date September 2009

                  Supersedes ACC-SVP01A-EN

                  Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                  • Table of Contents
                  • Overview
                  • Ordering Numbers
                  • BACnet Protocol
                  • BCI-I Configuration
                    • Overview
                    • Starting a Session of Tracer TU and Direct Connection
                    • Reset to Factory Default
                    • IP Units Configuration
                    • BACnet Object Configuration
                    • Change Baud Rate
                    • Change Device ID
                    • Stand-alone or BAS Operation
                      • IntelliPak Control Configuration
                      • BAS Unit Control
                      • Periodic Update of BAS Values
                      • BAS Communication Failure
                        • InputOutput Commands and Calculations
                          • System Control Command
                          • Filter Timer Reset Command
                          • Diagnostics Reset Command
                          • Setpoint Calculations
                          • Timestamp Configuration
                              • BCI IntelliPak Rotary Switches and LEDs
                                • Rotary Switches
                                • LEDs Description Behavior and Troubleshooting
                                • 24 Vac Measurement
                                • Ground Measurements
                                  • BACnet Data Points and Configuration Property Definitions
                                    • BACnet Protocol Implementation Conformance Statement (PICS)
                                      • Standardized Device Profile (Annex L)
                                      • Interoperability Building Blocks (Annex K)
                                      • Segmentation Capability
                                      • Object Types
                                        • BACnet Protocol
                                          • Data Link Layer Options
                                          • Device Address Binding
                                          • Networking Options
                                          • Character Sets
                                              • Object Data Points and Diagnostic Data Points
                                              • Additional Resources
                                              • Glossary

                    10 ACC-SVP01B-EN bull BCI-I Integration Guide

                    BCI-I Configuration

                    The BAS will change the state of the Filter Timer Reset Command object (BO 13) to the active state Upon the change to active state the BCI-I will set the present value of the Filter Runtime Hours object to zero and then set the Reset Command object back to the inactive state

                    Diagnostics Reset Command

                    The IntelliPak control system monitors the operation of the HVAC equipment If an abnormal condition is detected a diagnostic message is displayed on the human interface of the equipment control panel In addition the set of internal diagnostics is mapped to the set of BACnet binary input objects as listed in Table 9 p 31 The corresponding BI object will change state from inactive to active when the diagnostic is detected The object has been configured to send a BACnet event message to external BACnet devices as defined by the protocol

                    The BAS has the ability to reset internal diagnostics by controlling the state of the Diagnostic Reset Command object (BO 14) The procedure for resetting diagnostics is as follows

                    The BAS will change the state of the Diagnostic Reset to the active state Upon the change to active state the IntelliPak control system will reset all internal diagnostics and set the state of all of the diagnostic objects to inactive Upon completion of this action the BCI-I will set the present value of the Diagnostic Reset Command object back to the inactive state

                    Setpoint Calculations

                    The equipment has the ability to perform two basic control functions

                    bull Space air temperature control

                    bull Discharge air temperature control

                    When the unit is configured for discharge air control it controls the temperature of the air leaving the unit to the discharge air temperature setpoint

                    When the unit is configured for space air temperature control it controls the air temperature of the space that contains the space air temperature sensor This value may be provided by wiring the sensor to the unit or via a sensor value provided by the BAS

                    The drawing below describes how the various temperature setpoints are calculated for space temperature control When the unit is in an occupied mode the active space temperature setpoint is calculated based on the space temperature setpoint and the two setpoint offset values In unoccupied mode the unoccupied heating and cooling setpoints are used as the active setpoint

                    ACC-SVP01B-EN bull BCI-I Integration Guide 11

                    BCI-I Configuration

                    Timestamp Configuration

                    The BCI-C device has a software-derived clock that maintains the time and date The device requires the current time to enable it to record a timestamp when an event or a change in state is detected by a BACnet object However in the event of a power loss the device does not maintain this time and date information At powerup the device time and date will default to 1200 pm Jan 1 1970 To minimize the possibility that the unit timestamp is not representing the actual time the BAS should be setup to periodically synchronize the device time clock with the BAS clock using the BACnet TimeSynchronization service

                    12 ACC-SVP01B-EN bull BCI-I Integration Guide

                    BCI IntelliPak Rotary Switches and LEDs

                    BCI IntelliPak Rotary Switches and LEDs

                    This section provides information about the BCI-I rotary switches and LED displays

                    Rotary Switches

                    There are three rotary switches on the front of the BCI-I device that are used to define a three-digit address when the BCI-I is installed on a BACnet communications network The three-digit address setting is the BACnet MAC address

                    Note All devices are MSTP masters with valid MAC addresses of 001 to 127 for BACnet

                    Figure 1 Setting rotary switches

                    ADDRESS0 1

                    23

                    456

                    78

                    9

                    x1

                    0 1

                    23

                    456

                    78

                    9

                    x10

                    0 1

                    23

                    456

                    78

                    9

                    x100

                    Before

                    After

                    0

                    5

                    1

                    3

                    6

                    29

                    487

                    Example of before and after setting addresses

                    Use a 18 inch flathead screwdriver to set rotary switches

                    Important Each device on the BACnetMSTP link must have a unique rotary switch setting otherwise communication problems will occur

                    ACC-SVP01B-EN bull BCI-I Integration Guide 13

                    BCI IntelliPak Rotary Switches and LEDs

                    LEDs Description Behavior and Troubleshooting

                    There are 15 LEDs on the front of the BCI-I unit However LEDs BO1 through BO9 are not used for the BCI-I controller Figure 2 shows the locations of each LED The following table provides a description of each LED activity an indication or troubleshooting tips for each and any notes

                    Figure 2 LED locations

                    SERVICE

                    IMCLINK

                    RX

                    TX

                    Marquee LED

                    Table 1 LED Activities and Troubleshooting Tips

                    LED Name ActivitiesIndication or Troubleshooting

                    Tip (Denoted in Bullets) Notes

                    Marquee LED

                    Shows solid green when the unit is powered and no problems exist

                    Indicates normal operation

                    Shows solid red when the unit is powered but represents low power or a

                    malfunction

                    bull If low power could be under voltage or the microprocessor has malfunction Follow the troubleshoot procedure ldquo24 Vac Measurementrdquo p 15 to measure for the expected value range

                    bull If malfunction unpower and then repower unit to bring the device back up to normal operation

                    Shows blinking red when an a BACnet object is in a fault condition

                    Alarm when an alarm is triggered for example when a point goes into fault condition because of point failure or there is an indication of a custom alarm in TGP2

                    Shows blinking green when the device does not detect the IMC buss

                    bull Verify that the IPC wiring harness is connected to the IMC link terminals

                    bull Verify the polarity of the IPC wiring harness at the unit terminals

                    LED not lit

                    Indicates power is OFF or there is a malfunction

                    bull OFF or malfunction cycle the power

                    14 ACC-SVP01B-EN bull BCI-I Integration Guide

                    BCI IntelliPak Rotary Switches and LEDs

                    Link and IMC

                    TX blinks greenBlinks at the data transfer rate when the unit transfers data to other devices on the link

                    TX LED Regardless of connectivity or not this LED will constantly blink as it continually looks for devices to communicate to

                    LED not litDetermine if for example a Tracer SC or BACnet device is trying to talk to the controller or if it is capable of talking to the controller Also determine if the communication status shows down all of the time

                    Refer to ldquoGround Measurementsrdquo p 16 for a check-out procedure

                    RX blinks yellow

                    Blinks at the data transfer rate when the unit receives data from other devices on the link

                    bull ON solid yellow indicates there is reverse polarity

                    LED not lit

                    Indicates that the controller is not detecting communication

                    bull Not lit cycle the power to reestablish communication

                    Service

                    Shows solid greenIndicates someone is pressing this LED or the controller is not operating normally

                    Press and hold during power up to place controller into boot code or press and hold for a count of approximately 10 seconds to clear the Device ID

                    What is Boot Code When the UC400 is placed into boot code the system will not run any applications such as trending scheduling and TGP2 runtime

                    Blinks green

                    Indicates controllers is not accessing application software

                    bull Restore using TU service tool

                    LED not lit Indicates controller is operating normally

                    Binary 01 to Binary 09 Not Used

                    Table 1 LED Activities and Troubleshooting Tips

                    LED Name ActivitiesIndication or Troubleshooting

                    Tip (Denoted in Bullets) Notes

                    ACC-SVP01B-EN bull BCI-I Integration Guide 15

                    BCI IntelliPak Rotary Switches and LEDs

                    24 Vac Measurement

                    General Information Checkout Procedure Measurement Expected Value

                    Checking the voltage that is powering the UC400 is often a necessary step when commissioning or troubleshooting Operational issues and LED operation may result in a need to measure the input power

                    When troubleshooting it is faster to take measurements while the load is in place If Step 1 indicates an out-of-specification voltage disconnect the UC400 and measure the AC voltage across the transformer These measurements can direct the technician towards the problem source

                    Step 1

                    Measure AC voltage with the UC400 connected Perform this measurement while the unit is under load

                    200 Vac le Vac le 300 Vac

                    Step 2

                    Measure AC voltage with the UC400 unconnected Perform this measurement while the unit is not under load

                    200 Vac le Vac le 300 Vac

                    16 ACC-SVP01B-EN bull BCI-I Integration Guide

                    BCI IntelliPak Rotary Switches and LEDs

                    Ground Measurements

                    General Information and Checkout Procedure Measurement Expected Value

                    Method 1AC voltage between shield conductors and device chassis ground- the voltage difference between BACnet MSTP device chassis ground connections should be close to zero If the voltage difference is greater that 40 Vac there will be marginal communication or intermittent communication problems If the voltage difference is greater that 70 Vac some devices will no longer communicate

                    Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                    Vac le 20 V

                    Method 2AC voltage between earth ground and device chassis ground- the chassis ground of the UC400 needs to be connected to earth ground by some route

                    Note Do not assume that the building frame is a valid earth ground

                    Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                    Vac le 40 V (Must comply with National Electrical Codetradeand local electrical codes)

                    ACC-SVP01B-EN bull BCI-I Integration Guide 17

                    BACnet Data Points and Configuration Property Definitions

                    BACnet Data Points and Configuration Property

                    Definitions

                    The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MSTP This section includes information about

                    bull BACnet protocol implementation conformance statement (PICS)

                    bull Object types descriptions and configuration (refer to Table 2 p 19)

                    bull BACnet protocol data link layers device address binding networking options and character sets

                    bull Object data points and configurations

                    BACnet Protocol Implementation Conformance Statement (PICS)

                    Standardized Device Profile (Annex L)

                    Interoperability Building Blocks (Annex K)

                    Profile Description Supported Profile

                    BACnet Advanced Application Controller (B-AAC)

                    BACnet Application Specific Controller (B-ASC)

                    BACnet Building Controller (B-BC)

                    BACnet Operator Workstation (B-OWS)

                    BACnet Smart Actuator (B-SA)

                    BACnet Smart Sensor (B-SS)

                    Data Sharing Description Supported BIBB

                    Data Sharing-COV-B (DS-COV-B)

                    Data Sharing-ReadProperty-A (DS-RP-A)

                    Data Sharing-ReadProperty-B (DS-RP-B)

                    Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)

                    Data Sharing-WriteProperty-A (DS-WP-A)

                    Data Sharing-WriteProperty-B (DS-WP-B)

                    Data Sharing-WritePropertyMultiple-B (DS-WPM-B)

                    Alarm and Event Management Description Supported BIBB

                    Alarm and Event-ACKI-B (AE-ACK-B)

                    Alarm and Event-Alarm Summary-B (AE-ASUM-B)

                    Alarm and Event-Enrollment Summary-B (AE-ESUM-B)

                    Alarm and Event-Information-B (AE-INFO-B)

                    Alarm and Event-Notification Internal-B (AE-N-I-B)

                    18 ACC-SVP01B-EN bull BCI-I Integration Guide

                    BACnet Data Points and Configuration Property Definitions

                    Segmentation Capability

                    Trending Description Supported BIBB

                    Trending-Automated Trend Retrieval-B (T-ATR-B)

                    Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

                    Device Management Description Supported BIBB

                    Device Management-Backup and Restore-B (DM-BR-B)

                    Device Management-Device Communication Control-B (DM-DCC-B)

                    Device Management-Dynamic Device Binding-A (DM-DDB-A)

                    Device Management-Dynamic Device Binding-B (DM-DDB-B)

                    Device Management-Dynamic Object Binding-B (DM-DOB-B)

                    Device Management-List Manipulation-B (DM-LM-B)

                    Device Management-Object Creation and Deletion-B (DM-OCD-B)

                    Device Management-Private Transfer-A (DM-PT-A)

                    Device Management-Private Transfer-B (DM-PT-B)

                    Device Management-Reinitialize Device-B (DM-RD-B)

                    Device Management-TimeSynchronization-B (DM-TS-B)

                    Segmentation Description Supported Segment

                    Segmented Requests Window Size 1

                    Segmented Responses Window Size 1

                    ACC-SVP01B-EN bull BCI-I Integration Guide 19

                    BACnet Data Points and Configuration Property Definitions

                    Object Types

                    Table 2 Descriptions and configurations

                    Object Type Required Properties Read Properties Written(a) Optional Properties Read

                    Ability to Create

                    Ability to Delete

                    Analog Input

                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                    bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                    bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                    Yes Yes only user created objects

                    Analog Output

                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

                    bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                    bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                    Yes Yes only user created objects

                    Analog Value

                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                    bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                    bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                    Yes Yes only user created objects

                    Binary Input

                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                    bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                    bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                    Yes Yes only user created objects

                    20 ACC-SVP01B-EN bull BCI-I Integration Guide

                    BACnet Data Points and Configuration Property Definitions

                    Binary Output

                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

                    bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

                    bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                    Yes Yes only user created objects

                    Binary Value

                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                    bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                    bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                    Yes Yes only user created objects

                    Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

                    bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

                    bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

                    None None

                    Event Enrollment Object

                    bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

                    bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

                    bull None Yes Yes only user created objects

                    Table 2 Descriptions and configurations (continued)

                    Object Type Required Properties Read Properties Written(a) Optional Properties Read

                    Ability to Create

                    Ability to Delete

                    ACC-SVP01B-EN bull BCI-I Integration Guide 21

                    BACnet Data Points and Configuration Property Definitions

                    Multistate Input

                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                    bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                    bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                    Yes Yes only user created objects

                    Multistate Output

                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

                    bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

                    bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                    Yes Yes only user created objects

                    Multistate Value

                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                    bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                    bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                    Yes Yes only user created objects

                    Notification Class

                    bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

                    bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

                    None Yes Yes only user created objects

                    Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

                    bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

                    bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

                    Yes Yes only user created objects

                    (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

                    Table 2 Descriptions and configurations (continued)

                    Object Type Required Properties Read Properties Written(a) Optional Properties Read

                    Ability to Create

                    Ability to Delete

                    22 ACC-SVP01B-EN bull BCI-I Integration Guide

                    BACnet Data Points and Configuration Property Definitions

                    BACnet Protocol

                    Data Link Layer Options

                    Device Address Binding

                    Networking Options

                    Data Link Layer Description Supported Option

                    ANSIATA 8781 25 Mb ARCNET (Clause 8)

                    ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

                    BACnet IP (Annex J)

                    BACnet IP (Annex J) Foreign Device

                    ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

                    LonTalk (Clause 11) Medium

                    MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

                    MSTP Slave (Clause 9) Baud Rate(s)

                    Other

                    Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

                    Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

                    Device Address Binding Supported

                    Static Device Binding Supported

                    Networking DescriptionsSupported

                    Option

                    Annex H BACnet Tunneling

                    BACnetIP Broadcast Management Device (BBMD)

                    Does the BBMD Support Registrations by Foreign Devices

                    Router

                    ACC-SVP01B-EN bull BCI-I Integration Guide 23

                    BACnet Data Points and Configuration Property Definitions

                    Character Sets

                    Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

                    Character Set Descriptions Supported

                    ANSI X34

                    IBMMicrosoft DBCS

                    ISO 10646 (UCS-4)

                    ISO 10646 (UCS2)

                    ISO 8859-1

                    JIS C 6226

                    24 ACC-SVP01B-EN bull BCI-I Integration Guide

                    Object Data Points and Diagnostic Data Points

                    Object Data Points and Diagnostic Data Points

                    For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

                    Table 3 Analog Output

                    Object Identifier Object Name Description Units Valid Range

                    Refresh Rate

                    (Sec)

                    Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

                    Percent (98) 0 to 100 NA

                    Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

                    Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

                    Degrees-Fahrenheit (64) 500 to 900 NA

                    Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

                    BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

                    Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

                    Degrees-Fahrenheit (64) 400 to 900 NA

                    Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

                    Degrees-Fahrenheit (64) 400 to 1800 NA

                    Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

                    070 to 510 (Ipak II) NA

                    Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

                    003 to 030-002 to 030 (enhanced StatiTrac)

                    NA

                    Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

                    -028 to 050-067 to 067 (enhanced StatiTrac)

                    900

                    Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                    Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                    Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

                    00 to 79 (Ipak II) 900

                    Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                    Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

                    Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

                    Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

                    Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

                    Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

                    Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

                    Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

                    Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

                    Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

                    ACC-SVP01B-EN bull BCI-I Integration Guide 25

                    Object Data Points and Diagnostic Data Points

                    Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                    Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                    Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                    Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                    Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                    Cooling temperature setpoint used for control in unoccupied mode

                    Degrees-Fahrenheit (64) 520 to 880 NA

                    Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                    Heating temperature setpoint used for control in unoccupied mode

                    Degrees-Fahrenheit (64) 500 to 900 NA

                    Table 4 Analog Input

                    Object Identifier Object Name Description Units (Listed Are Defaults)

                    Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                    Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                    Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                    Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                    Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                    Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                    Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                    Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                    Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                    Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                    Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                    Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                    Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                    Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                    Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                    Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                    Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                    Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                    Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                    Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                    Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                    Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                    Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                    Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                    Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                    Table 3 Analog Output (continued)

                    Object Identifier Object Name Description Units Valid Range

                    Refresh Rate

                    (Sec)

                    26 ACC-SVP01B-EN bull BCI-I Integration Guide

                    Object Data Points and Diagnostic Data Points

                    Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                    Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                    Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                    Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                    Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                    Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                    Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                    Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                    Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                    Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                    Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                    Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                    Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                    Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                    Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                    Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                    Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                    Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                    Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                    Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                    Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                    Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                    Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                    Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                    The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                    Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                    The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                    Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                    Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                    Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                    Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                    Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                    Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                    Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                    Table 4 Analog Input (continued)

                    Object Identifier Object Name Description Units (Listed Are Defaults)

                    ACC-SVP01B-EN bull BCI-I Integration Guide 27

                    Object Data Points and Diagnostic Data Points

                    Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                    Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                    Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                    Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                    The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                    Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                    Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                    Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                    Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                    Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                    Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                    Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                    Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                    Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                    Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                    Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                    Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                    Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                    Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                    Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                    Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                    Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                    Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                    Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                    Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                    Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                    Table 5 Analog Value

                    Object Identifier Object Name Description Units Valid Range

                    Analog Value 1 Filter Runtime Hours Setpoint

                    The setpoint value used by the filter run hours calculation

                    Hours (71) 0 to 10000

                    Table 4 Analog Input (continued)

                    Object Identifier Object Name Description Units (Listed Are Defaults)

                    28 ACC-SVP01B-EN bull BCI-I Integration Guide

                    Object Data Points and Diagnostic Data Points

                    Table 6 Multistate Output

                    BCI-I Object Identifier Object Name Description Object States

                    Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                    Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                    1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                    Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                    Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                    1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                    Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                    1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                    Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                    1 = Flow2 = No Flow3 = Auto

                    Table 7 Multistate Input

                    BCI-I Object Identifier Object Name Description Object States

                    Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                    1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                    Multi-State Input 9 Economizer Type General description of the equipment economizer system

                    1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                    Multi-State Input 10 Condenser Type General description of the equipment condenser system

                    1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                    Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                    1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                    ACC-SVP01B-EN bull BCI-I Integration Guide 29

                    Object Data Points and Diagnostic Data Points

                    Multi-State Input 15 Economizer Decision Method

                    Unit method to determine when the economizer system is enabled

                    1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                    Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                    Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                    Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                    1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                    Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                    1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                    Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                    1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                    Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                    1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                    Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                    1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                    Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                    1 = Idle2 = On3 = Cancel

                    Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                    1 = Off2 = On3 = Not Present

                    Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                    1 = Off2 = On3 = Not Present

                    Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                    1 = Off2 = On3 = Not Present

                    Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                    1 = Off|2 = On3 = Not Present

                    Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                    1 = Off2 = On3 = Not Present

                    Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                    1 = Off2 = On3 = Not Present

                    Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                    1 = Off2 = On3 = Not Present

                    Table 7 Multistate Input (continued)

                    BCI-I Object Identifier Object Name Description Object States

                    30 ACC-SVP01B-EN bull BCI-I Integration Guide

                    Object Data Points and Diagnostic Data Points

                    Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                    1 = Off2 = On3 = Not Present

                    Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                    1 = Off2 = On3 = Not Present

                    Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                    Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                    Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                    Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                    Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                    1 = Off2 = On3 = Not Present

                    Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                    1= Off2= On3= Not Present

                    Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                    Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                    Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                    Multi-State Input 43 Outdoor Air Damper Status

                    Indicates the operating state of the outdoor damper

                    1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                    Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                    1 = Disabled2 = Enabled3 = Not Present

                    Table 8 Binary Output

                    Object Identifier Object Name DescriptionRelinquish Default Object States

                    Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                    Active = BAS Control

                    Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                    Active = Heating Locked Out

                    Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                    Active = Cooling Locked Out

                    Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                    Active = Enabled

                    Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                    Active = On

                    Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                    Inactive Inactive = DisabledActive = Enabled

                    Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                    Active = Reset

                    Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                    Active = Reset

                    Table 7 Multistate Input (continued)

                    BCI-I Object Identifier Object Name Description Object States

                    ACC-SVP01B-EN bull BCI-I Integration Guide 31

                    Object Data Points and Diagnostic Data Points

                    Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                    Active = Auto

                    Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                    Active = Auto

                    Table 9 Binary Input

                    Object Identifier Object Name Description Object States

                    Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                    Inactive = Standalone controlActive = BAS control

                    Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                    Inactive = NormalActive = Locked Out

                    Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                    Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                    Inactive = AutoActive = Open

                    Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                    Inactive = InactiveActive = Active

                    Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                    Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                    Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                    Inactive = DisabledActive = Enabled

                    Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                    Inactive = DisabledActive = Enabled

                    Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                    Inactive = InactiveActive = Active

                    Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                    Inactive = No FlowActive = Flow

                    Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                    Inactive = InactiveActive = Active

                    Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                    Inactive = InactiveActive = Active

                    Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                    Inactive = InactiveActive = Active

                    Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                    The status of evaporator frost protection function for circuit 1

                    Inactive = InactiveActive = Active

                    Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                    The status of evaporator frost protection function for circuit 2

                    Inactive = InactiveActive = Active

                    Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                    The status of evaporator frost protection function for circuit 3

                    Inactive = InactiveActive = Active

                    Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                    The status of evaporator frost protection function for circuit 4

                    Inactive = InactiveActive = Active

                    Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                    Inactive = De-energizedActive = Energized

                    Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                    Inactive = InactiveActive = Active

                    Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                    Inactive = ClosedActive = Open

                    Table 10 Diagnostics Binary Input

                    Object Identifier(a) Object Name Description

                    Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                    Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                    Binary Input 31 (use Object Identifier for RT or CSC)

                    Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                    Binary Input 31 (use Object Identifier for FAU)

                    Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                    Table 8 Binary Output

                    Object Identifier Object Name DescriptionRelinquish Default Object States

                    32 ACC-SVP01B-EN bull BCI-I Integration Guide

                    Object Data Points and Diagnostic Data Points

                    Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                    Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                    Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                    Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                    Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                    Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                    Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                    Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                    Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                    Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                    Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                    Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                    Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                    Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                    Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                    Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                    Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                    Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                    Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                    Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                    Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                    Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                    Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                    Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                    Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                    Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                    Binary Input 58 (use Object Identifier for RT or CSC)

                    Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                    Binary Input 58 (use Object Identifier for FAU)

                    Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                    Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                    Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                    Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                    Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                    Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                    Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                    Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                    Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                    Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                    Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                    Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                    Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                    Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                    Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                    Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                    Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                    Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                    Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                    Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                    Table 10 Diagnostics Binary Input (continued)

                    Object Identifier(a) Object Name Description

                    ACC-SVP01B-EN bull BCI-I Integration Guide 33

                    Object Data Points and Diagnostic Data Points

                    Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                    Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                    Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                    Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                    Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                    Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                    Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                    Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                    Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                    Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                    Binary Input 86 (use Object Identifier for RT I-pak II)

                    Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                    Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                    Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                    Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                    Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                    Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                    Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                    Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                    Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                    Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                    Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                    Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                    Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                    Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                    Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                    Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                    Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                    Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                    Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                    Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                    Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                    Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                    Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                    Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                    Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                    Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                    Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                    Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                    Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                    Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                    Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                    Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                    Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                    Binary Input 121 (use Object Identifier for RT)

                    Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                    Binary Input 121 (use Object Identifier for FAU)

                    Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                    Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                    Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                    Table 10 Diagnostics Binary Input (continued)

                    Object Identifier(a) Object Name Description

                    34 ACC-SVP01B-EN bull BCI-I Integration Guide

                    Object Data Points and Diagnostic Data Points

                    Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                    Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                    Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                    Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                    Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                    Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                    Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                    Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                    Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                    Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                    Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                    Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                    Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                    Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                    Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                    Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                    Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                    Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                    Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                    Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                    Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                    Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                    Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                    Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                    Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                    Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                    (a) Object States Inactive = normal and Active = foreign language specific

                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                    Object Identifier(a) Object Name Description

                    Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                    Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                    Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                    Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                    Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                    Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                    Multi-State Input 10 Condenser Type General description of the equipment condenser system

                    Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                    Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                    Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                    Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                    Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                    Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                    Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                    Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                    Table 10 Diagnostics Binary Input (continued)

                    Object Identifier(a) Object Name Description

                    ACC-SVP01B-EN bull BCI-I Integration Guide 35

                    Object Data Points and Diagnostic Data Points

                    Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                    Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                    Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                    Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                    Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                    Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                    Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                    Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                    Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                    Analog Input 81 Cool Type Describes the cooling type installed in the unit

                    Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                    Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                    Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                    Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                    Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                    Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                    Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                    Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                    Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                    Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                    Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                    Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                    Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                    Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                    Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                    Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                    Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                    Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                    Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                    Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                    Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                    Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                    Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                    Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                    Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                    Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                    Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                    Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                    Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                    Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                    Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                    Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                    Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                    Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                    Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                    Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                    Object Identifier(a) Object Name Description

                    36 ACC-SVP01B-EN bull BCI-I Integration Guide

                    Object Data Points and Diagnostic Data Points

                    Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                    Multi-State Input 9 Economizer Type General description of the equipment economizer system

                    Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                    Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                    Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                    Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                    Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                    Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                    Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                    Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                    Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                    Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                    Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                    Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                    Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                    Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                    Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                    Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                    Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                    Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                    Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                    Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                    Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                    Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                    Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                    Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                    Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                    Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                    Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                    Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                    Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                    Multi-State Input 36 Final Filter Status Indicates the final filter media state

                    Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                    Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                    Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                    Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                    Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                    Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                    Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                    Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                    Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                    Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                    Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                    Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                    Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                    Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                    Object Identifier(a) Object Name Description

                    ACC-SVP01B-EN bull BCI-I Integration Guide 37

                    Object Data Points and Diagnostic Data Points

                    Binary Output 16 Humidification Command Command the operating state of the humidification system

                    NC 3 HVAC-Advisory HVAC-Advisory

                    NC 1 HVAC-Critical HVAC-Critical

                    NC 4 HVAC-Information HVAC-Information

                    NC 2 HVAC-Service Required HVAC-Service Required

                    Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                    Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                    Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                    Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                    Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                    Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                    Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                    Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                    Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                    Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                    Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                    Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                    Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                    Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                    Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                    Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                    Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                    Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                    Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                    Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                    Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                    Analog Input 82 Preheat Type Describes the heating type installed in the unit

                    Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                    Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                    Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                    Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                    Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                    Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                    Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                    Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                    Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                    Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                    Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                    Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                    Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                    Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                    Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                    Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                    Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                    Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                    Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                    Object Identifier(a) Object Name Description

                    38 ACC-SVP01B-EN bull BCI-I Integration Guide

                    Object Data Points and Diagnostic Data Points

                    Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                    Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                    Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                    Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                    Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                    Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                    Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                    Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                    Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                    Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                    Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                    Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                    Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                    Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                    Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                    Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                    Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                    Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                    Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                    Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                    Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                    Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                    Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                    Binary Input 3 Unit Status Indicates the current state of the unit

                    Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                    Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                    Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                    Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                    Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                    Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                    Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                    (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                    Object Identifier(a) Object Name Description

                    Table 12 Diagnostic Objects Sorted by Object Name

                    Object Identifier(a) Object Name ValueRange Description

                    BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                    BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                    ACC-SVP01B-EN bull BCI-I Integration Guide 39

                    Object Data Points and Diagnostic Data Points

                    BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                    BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                    BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                    BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                    BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                    BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                    BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                    BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                    BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                    BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                    BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                    BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                    BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                    BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                    BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                    BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                    BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                    BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                    BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                    BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                    BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                    BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                    BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                    BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                    BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                    BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                    BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                    BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                    BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                    Object Identifier(a) Object Name ValueRange Description

                    40 ACC-SVP01B-EN bull BCI-I Integration Guide

                    Object Data Points and Diagnostic Data Points

                    BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                    BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                    BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                    BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                    BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                    BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                    BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                    BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                    BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                    BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                    BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                    BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                    BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                    BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                    BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                    BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                    BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                    BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                    BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                    BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                    BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                    BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                    BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                    BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                    BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                    BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                    BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                    BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                    BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                    Object Identifier(a) Object Name ValueRange Description

                    ACC-SVP01B-EN bull BCI-I Integration Guide 41

                    Object Data Points and Diagnostic Data Points

                    BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                    BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                    BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                    BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                    BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                    BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                    BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                    BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                    BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                    BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                    BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                    BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                    BI 121 (use Object Identifier for RT)

                    Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                    BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                    BI 58 (use Object Identifier for RT or CSC)

                    Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                    BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                    BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                    BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                    BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                    BI 31 (use Object Identifier for RT CSC)

                    Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                    BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                    BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                    BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                    BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                    BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                    BI 121 (use Object Identifier for FAU)

                    Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                    B1 31 (use Object Identifier for FAU)

                    Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                    BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                    BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                    Object Identifier(a) Object Name ValueRange Description

                    42 ACC-SVP01B-EN bull BCI-I Integration Guide

                    Object Data Points and Diagnostic Data Points

                    BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                    BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                    BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                    BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                    BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                    BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                    BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                    BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                    BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                    BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                    BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                    BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                    BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                    BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                    BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                    BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                    BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                    BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                    BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                    BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                    BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                    BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                    BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                    1 = active Diagnostic Vel Press Sensor (Rear)

                    BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                    Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                    BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                    BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                    BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                    BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                    BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                    Object Identifier(a) Object Name ValueRange Description

                    ACC-SVP01B-EN bull BCI-I Integration Guide 43

                    Object Data Points and Diagnostic Data Points

                    BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                    BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                    BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                    BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                    BI 58 (use Object Identifier for FAU)

                    Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                    (a) BI=Binary Input

                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                    Object Identifier(a) Object Name ValueRange Description

                    44 ACC-SVP01B-EN bull BCI-I Integration Guide

                    Additional Resources

                    Additional Resources

                    Use the following documents and links as additional resources

                    bull Product support online

                    bull wwwbacnetorg

                    bull wwwbacnetassociationorg

                    bull wwwashraeorg

                    bull Tracer TU Help online

                    bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                    bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                    Note For further assistance contact your local Trane sales office

                    ACC-SVP01B-EN bull BCI-I Integration Guide 45

                    Glossary

                    A

                    ASHRAE

                    See American Society of Heating Refrigeration and Air-conditioning Engineers

                    American Society of Heating Refrigeration and Air-

                    conditioning Engineers

                    An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                    BBACnettrade

                    See Building Automation Control network

                    BACnet interoperability building blocks

                    A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                    BACnet object

                    An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                    baud rate

                    The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                    BIBB

                    See BACnet interoperability building blocks

                    Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                    advocates BACnet protocol for use in system-level control devices

                    device

                    A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                    Device ID

                    The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                    Iinteroperability

                    The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                    Pprotocol

                    A set of rules (language) that governs the exchange of data over a digital communications system

                    S

                    stand-alone operation

                    Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                    wwwtranecom

                    For more information contact your local Trane office or e-mail us at comforttranecom

                    Literature Order Number ACC-SVP01B-EN

                    Date September 2009

                    Supersedes ACC-SVP01A-EN

                    Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                    • Table of Contents
                    • Overview
                    • Ordering Numbers
                    • BACnet Protocol
                    • BCI-I Configuration
                      • Overview
                      • Starting a Session of Tracer TU and Direct Connection
                      • Reset to Factory Default
                      • IP Units Configuration
                      • BACnet Object Configuration
                      • Change Baud Rate
                      • Change Device ID
                      • Stand-alone or BAS Operation
                        • IntelliPak Control Configuration
                        • BAS Unit Control
                        • Periodic Update of BAS Values
                        • BAS Communication Failure
                          • InputOutput Commands and Calculations
                            • System Control Command
                            • Filter Timer Reset Command
                            • Diagnostics Reset Command
                            • Setpoint Calculations
                            • Timestamp Configuration
                                • BCI IntelliPak Rotary Switches and LEDs
                                  • Rotary Switches
                                  • LEDs Description Behavior and Troubleshooting
                                  • 24 Vac Measurement
                                  • Ground Measurements
                                    • BACnet Data Points and Configuration Property Definitions
                                      • BACnet Protocol Implementation Conformance Statement (PICS)
                                        • Standardized Device Profile (Annex L)
                                        • Interoperability Building Blocks (Annex K)
                                        • Segmentation Capability
                                        • Object Types
                                          • BACnet Protocol
                                            • Data Link Layer Options
                                            • Device Address Binding
                                            • Networking Options
                                            • Character Sets
                                                • Object Data Points and Diagnostic Data Points
                                                • Additional Resources
                                                • Glossary

                      ACC-SVP01B-EN bull BCI-I Integration Guide 11

                      BCI-I Configuration

                      Timestamp Configuration

                      The BCI-C device has a software-derived clock that maintains the time and date The device requires the current time to enable it to record a timestamp when an event or a change in state is detected by a BACnet object However in the event of a power loss the device does not maintain this time and date information At powerup the device time and date will default to 1200 pm Jan 1 1970 To minimize the possibility that the unit timestamp is not representing the actual time the BAS should be setup to periodically synchronize the device time clock with the BAS clock using the BACnet TimeSynchronization service

                      12 ACC-SVP01B-EN bull BCI-I Integration Guide

                      BCI IntelliPak Rotary Switches and LEDs

                      BCI IntelliPak Rotary Switches and LEDs

                      This section provides information about the BCI-I rotary switches and LED displays

                      Rotary Switches

                      There are three rotary switches on the front of the BCI-I device that are used to define a three-digit address when the BCI-I is installed on a BACnet communications network The three-digit address setting is the BACnet MAC address

                      Note All devices are MSTP masters with valid MAC addresses of 001 to 127 for BACnet

                      Figure 1 Setting rotary switches

                      ADDRESS0 1

                      23

                      456

                      78

                      9

                      x1

                      0 1

                      23

                      456

                      78

                      9

                      x10

                      0 1

                      23

                      456

                      78

                      9

                      x100

                      Before

                      After

                      0

                      5

                      1

                      3

                      6

                      29

                      487

                      Example of before and after setting addresses

                      Use a 18 inch flathead screwdriver to set rotary switches

                      Important Each device on the BACnetMSTP link must have a unique rotary switch setting otherwise communication problems will occur

                      ACC-SVP01B-EN bull BCI-I Integration Guide 13

                      BCI IntelliPak Rotary Switches and LEDs

                      LEDs Description Behavior and Troubleshooting

                      There are 15 LEDs on the front of the BCI-I unit However LEDs BO1 through BO9 are not used for the BCI-I controller Figure 2 shows the locations of each LED The following table provides a description of each LED activity an indication or troubleshooting tips for each and any notes

                      Figure 2 LED locations

                      SERVICE

                      IMCLINK

                      RX

                      TX

                      Marquee LED

                      Table 1 LED Activities and Troubleshooting Tips

                      LED Name ActivitiesIndication or Troubleshooting

                      Tip (Denoted in Bullets) Notes

                      Marquee LED

                      Shows solid green when the unit is powered and no problems exist

                      Indicates normal operation

                      Shows solid red when the unit is powered but represents low power or a

                      malfunction

                      bull If low power could be under voltage or the microprocessor has malfunction Follow the troubleshoot procedure ldquo24 Vac Measurementrdquo p 15 to measure for the expected value range

                      bull If malfunction unpower and then repower unit to bring the device back up to normal operation

                      Shows blinking red when an a BACnet object is in a fault condition

                      Alarm when an alarm is triggered for example when a point goes into fault condition because of point failure or there is an indication of a custom alarm in TGP2

                      Shows blinking green when the device does not detect the IMC buss

                      bull Verify that the IPC wiring harness is connected to the IMC link terminals

                      bull Verify the polarity of the IPC wiring harness at the unit terminals

                      LED not lit

                      Indicates power is OFF or there is a malfunction

                      bull OFF or malfunction cycle the power

                      14 ACC-SVP01B-EN bull BCI-I Integration Guide

                      BCI IntelliPak Rotary Switches and LEDs

                      Link and IMC

                      TX blinks greenBlinks at the data transfer rate when the unit transfers data to other devices on the link

                      TX LED Regardless of connectivity or not this LED will constantly blink as it continually looks for devices to communicate to

                      LED not litDetermine if for example a Tracer SC or BACnet device is trying to talk to the controller or if it is capable of talking to the controller Also determine if the communication status shows down all of the time

                      Refer to ldquoGround Measurementsrdquo p 16 for a check-out procedure

                      RX blinks yellow

                      Blinks at the data transfer rate when the unit receives data from other devices on the link

                      bull ON solid yellow indicates there is reverse polarity

                      LED not lit

                      Indicates that the controller is not detecting communication

                      bull Not lit cycle the power to reestablish communication

                      Service

                      Shows solid greenIndicates someone is pressing this LED or the controller is not operating normally

                      Press and hold during power up to place controller into boot code or press and hold for a count of approximately 10 seconds to clear the Device ID

                      What is Boot Code When the UC400 is placed into boot code the system will not run any applications such as trending scheduling and TGP2 runtime

                      Blinks green

                      Indicates controllers is not accessing application software

                      bull Restore using TU service tool

                      LED not lit Indicates controller is operating normally

                      Binary 01 to Binary 09 Not Used

                      Table 1 LED Activities and Troubleshooting Tips

                      LED Name ActivitiesIndication or Troubleshooting

                      Tip (Denoted in Bullets) Notes

                      ACC-SVP01B-EN bull BCI-I Integration Guide 15

                      BCI IntelliPak Rotary Switches and LEDs

                      24 Vac Measurement

                      General Information Checkout Procedure Measurement Expected Value

                      Checking the voltage that is powering the UC400 is often a necessary step when commissioning or troubleshooting Operational issues and LED operation may result in a need to measure the input power

                      When troubleshooting it is faster to take measurements while the load is in place If Step 1 indicates an out-of-specification voltage disconnect the UC400 and measure the AC voltage across the transformer These measurements can direct the technician towards the problem source

                      Step 1

                      Measure AC voltage with the UC400 connected Perform this measurement while the unit is under load

                      200 Vac le Vac le 300 Vac

                      Step 2

                      Measure AC voltage with the UC400 unconnected Perform this measurement while the unit is not under load

                      200 Vac le Vac le 300 Vac

                      16 ACC-SVP01B-EN bull BCI-I Integration Guide

                      BCI IntelliPak Rotary Switches and LEDs

                      Ground Measurements

                      General Information and Checkout Procedure Measurement Expected Value

                      Method 1AC voltage between shield conductors and device chassis ground- the voltage difference between BACnet MSTP device chassis ground connections should be close to zero If the voltage difference is greater that 40 Vac there will be marginal communication or intermittent communication problems If the voltage difference is greater that 70 Vac some devices will no longer communicate

                      Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                      Vac le 20 V

                      Method 2AC voltage between earth ground and device chassis ground- the chassis ground of the UC400 needs to be connected to earth ground by some route

                      Note Do not assume that the building frame is a valid earth ground

                      Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                      Vac le 40 V (Must comply with National Electrical Codetradeand local electrical codes)

                      ACC-SVP01B-EN bull BCI-I Integration Guide 17

                      BACnet Data Points and Configuration Property Definitions

                      BACnet Data Points and Configuration Property

                      Definitions

                      The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MSTP This section includes information about

                      bull BACnet protocol implementation conformance statement (PICS)

                      bull Object types descriptions and configuration (refer to Table 2 p 19)

                      bull BACnet protocol data link layers device address binding networking options and character sets

                      bull Object data points and configurations

                      BACnet Protocol Implementation Conformance Statement (PICS)

                      Standardized Device Profile (Annex L)

                      Interoperability Building Blocks (Annex K)

                      Profile Description Supported Profile

                      BACnet Advanced Application Controller (B-AAC)

                      BACnet Application Specific Controller (B-ASC)

                      BACnet Building Controller (B-BC)

                      BACnet Operator Workstation (B-OWS)

                      BACnet Smart Actuator (B-SA)

                      BACnet Smart Sensor (B-SS)

                      Data Sharing Description Supported BIBB

                      Data Sharing-COV-B (DS-COV-B)

                      Data Sharing-ReadProperty-A (DS-RP-A)

                      Data Sharing-ReadProperty-B (DS-RP-B)

                      Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)

                      Data Sharing-WriteProperty-A (DS-WP-A)

                      Data Sharing-WriteProperty-B (DS-WP-B)

                      Data Sharing-WritePropertyMultiple-B (DS-WPM-B)

                      Alarm and Event Management Description Supported BIBB

                      Alarm and Event-ACKI-B (AE-ACK-B)

                      Alarm and Event-Alarm Summary-B (AE-ASUM-B)

                      Alarm and Event-Enrollment Summary-B (AE-ESUM-B)

                      Alarm and Event-Information-B (AE-INFO-B)

                      Alarm and Event-Notification Internal-B (AE-N-I-B)

                      18 ACC-SVP01B-EN bull BCI-I Integration Guide

                      BACnet Data Points and Configuration Property Definitions

                      Segmentation Capability

                      Trending Description Supported BIBB

                      Trending-Automated Trend Retrieval-B (T-ATR-B)

                      Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

                      Device Management Description Supported BIBB

                      Device Management-Backup and Restore-B (DM-BR-B)

                      Device Management-Device Communication Control-B (DM-DCC-B)

                      Device Management-Dynamic Device Binding-A (DM-DDB-A)

                      Device Management-Dynamic Device Binding-B (DM-DDB-B)

                      Device Management-Dynamic Object Binding-B (DM-DOB-B)

                      Device Management-List Manipulation-B (DM-LM-B)

                      Device Management-Object Creation and Deletion-B (DM-OCD-B)

                      Device Management-Private Transfer-A (DM-PT-A)

                      Device Management-Private Transfer-B (DM-PT-B)

                      Device Management-Reinitialize Device-B (DM-RD-B)

                      Device Management-TimeSynchronization-B (DM-TS-B)

                      Segmentation Description Supported Segment

                      Segmented Requests Window Size 1

                      Segmented Responses Window Size 1

                      ACC-SVP01B-EN bull BCI-I Integration Guide 19

                      BACnet Data Points and Configuration Property Definitions

                      Object Types

                      Table 2 Descriptions and configurations

                      Object Type Required Properties Read Properties Written(a) Optional Properties Read

                      Ability to Create

                      Ability to Delete

                      Analog Input

                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                      bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                      bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                      Yes Yes only user created objects

                      Analog Output

                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

                      bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                      bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                      Yes Yes only user created objects

                      Analog Value

                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                      bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                      bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                      Yes Yes only user created objects

                      Binary Input

                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                      bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                      bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                      Yes Yes only user created objects

                      20 ACC-SVP01B-EN bull BCI-I Integration Guide

                      BACnet Data Points and Configuration Property Definitions

                      Binary Output

                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

                      bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

                      bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                      Yes Yes only user created objects

                      Binary Value

                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                      bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                      bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                      Yes Yes only user created objects

                      Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

                      bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

                      bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

                      None None

                      Event Enrollment Object

                      bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

                      bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

                      bull None Yes Yes only user created objects

                      Table 2 Descriptions and configurations (continued)

                      Object Type Required Properties Read Properties Written(a) Optional Properties Read

                      Ability to Create

                      Ability to Delete

                      ACC-SVP01B-EN bull BCI-I Integration Guide 21

                      BACnet Data Points and Configuration Property Definitions

                      Multistate Input

                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                      bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                      bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                      Yes Yes only user created objects

                      Multistate Output

                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

                      bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

                      bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                      Yes Yes only user created objects

                      Multistate Value

                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                      bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                      bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                      Yes Yes only user created objects

                      Notification Class

                      bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

                      bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

                      None Yes Yes only user created objects

                      Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

                      bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

                      bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

                      Yes Yes only user created objects

                      (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

                      Table 2 Descriptions and configurations (continued)

                      Object Type Required Properties Read Properties Written(a) Optional Properties Read

                      Ability to Create

                      Ability to Delete

                      22 ACC-SVP01B-EN bull BCI-I Integration Guide

                      BACnet Data Points and Configuration Property Definitions

                      BACnet Protocol

                      Data Link Layer Options

                      Device Address Binding

                      Networking Options

                      Data Link Layer Description Supported Option

                      ANSIATA 8781 25 Mb ARCNET (Clause 8)

                      ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

                      BACnet IP (Annex J)

                      BACnet IP (Annex J) Foreign Device

                      ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

                      LonTalk (Clause 11) Medium

                      MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

                      MSTP Slave (Clause 9) Baud Rate(s)

                      Other

                      Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

                      Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

                      Device Address Binding Supported

                      Static Device Binding Supported

                      Networking DescriptionsSupported

                      Option

                      Annex H BACnet Tunneling

                      BACnetIP Broadcast Management Device (BBMD)

                      Does the BBMD Support Registrations by Foreign Devices

                      Router

                      ACC-SVP01B-EN bull BCI-I Integration Guide 23

                      BACnet Data Points and Configuration Property Definitions

                      Character Sets

                      Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

                      Character Set Descriptions Supported

                      ANSI X34

                      IBMMicrosoft DBCS

                      ISO 10646 (UCS-4)

                      ISO 10646 (UCS2)

                      ISO 8859-1

                      JIS C 6226

                      24 ACC-SVP01B-EN bull BCI-I Integration Guide

                      Object Data Points and Diagnostic Data Points

                      Object Data Points and Diagnostic Data Points

                      For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

                      Table 3 Analog Output

                      Object Identifier Object Name Description Units Valid Range

                      Refresh Rate

                      (Sec)

                      Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

                      Percent (98) 0 to 100 NA

                      Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

                      Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

                      Degrees-Fahrenheit (64) 500 to 900 NA

                      Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

                      BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

                      Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

                      Degrees-Fahrenheit (64) 400 to 900 NA

                      Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

                      Degrees-Fahrenheit (64) 400 to 1800 NA

                      Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

                      070 to 510 (Ipak II) NA

                      Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

                      003 to 030-002 to 030 (enhanced StatiTrac)

                      NA

                      Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

                      -028 to 050-067 to 067 (enhanced StatiTrac)

                      900

                      Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                      Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                      Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

                      00 to 79 (Ipak II) 900

                      Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                      Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

                      Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

                      Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

                      Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

                      Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

                      Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

                      Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

                      Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

                      Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

                      ACC-SVP01B-EN bull BCI-I Integration Guide 25

                      Object Data Points and Diagnostic Data Points

                      Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                      Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                      Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                      Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                      Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                      Cooling temperature setpoint used for control in unoccupied mode

                      Degrees-Fahrenheit (64) 520 to 880 NA

                      Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                      Heating temperature setpoint used for control in unoccupied mode

                      Degrees-Fahrenheit (64) 500 to 900 NA

                      Table 4 Analog Input

                      Object Identifier Object Name Description Units (Listed Are Defaults)

                      Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                      Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                      Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                      Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                      Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                      Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                      Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                      Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                      Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                      Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                      Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                      Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                      Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                      Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                      Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                      Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                      Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                      Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                      Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                      Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                      Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                      Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                      Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                      Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                      Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                      Table 3 Analog Output (continued)

                      Object Identifier Object Name Description Units Valid Range

                      Refresh Rate

                      (Sec)

                      26 ACC-SVP01B-EN bull BCI-I Integration Guide

                      Object Data Points and Diagnostic Data Points

                      Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                      Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                      Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                      Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                      Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                      Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                      Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                      Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                      Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                      Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                      Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                      Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                      Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                      Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                      Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                      Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                      Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                      Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                      Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                      Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                      Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                      Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                      Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                      Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                      The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                      Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                      The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                      Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                      Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                      Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                      Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                      Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                      Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                      Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                      Table 4 Analog Input (continued)

                      Object Identifier Object Name Description Units (Listed Are Defaults)

                      ACC-SVP01B-EN bull BCI-I Integration Guide 27

                      Object Data Points and Diagnostic Data Points

                      Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                      Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                      Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                      Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                      The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                      Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                      Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                      Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                      Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                      Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                      Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                      Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                      Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                      Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                      Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                      Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                      Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                      Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                      Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                      Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                      Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                      Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                      Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                      Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                      Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                      Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                      Table 5 Analog Value

                      Object Identifier Object Name Description Units Valid Range

                      Analog Value 1 Filter Runtime Hours Setpoint

                      The setpoint value used by the filter run hours calculation

                      Hours (71) 0 to 10000

                      Table 4 Analog Input (continued)

                      Object Identifier Object Name Description Units (Listed Are Defaults)

                      28 ACC-SVP01B-EN bull BCI-I Integration Guide

                      Object Data Points and Diagnostic Data Points

                      Table 6 Multistate Output

                      BCI-I Object Identifier Object Name Description Object States

                      Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                      Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                      1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                      Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                      Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                      1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                      Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                      1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                      Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                      1 = Flow2 = No Flow3 = Auto

                      Table 7 Multistate Input

                      BCI-I Object Identifier Object Name Description Object States

                      Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                      1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                      Multi-State Input 9 Economizer Type General description of the equipment economizer system

                      1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                      Multi-State Input 10 Condenser Type General description of the equipment condenser system

                      1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                      Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                      1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                      ACC-SVP01B-EN bull BCI-I Integration Guide 29

                      Object Data Points and Diagnostic Data Points

                      Multi-State Input 15 Economizer Decision Method

                      Unit method to determine when the economizer system is enabled

                      1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                      Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                      Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                      Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                      1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                      Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                      1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                      Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                      1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                      Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                      1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                      Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                      1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                      Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                      1 = Idle2 = On3 = Cancel

                      Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                      1 = Off2 = On3 = Not Present

                      Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                      1 = Off2 = On3 = Not Present

                      Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                      1 = Off2 = On3 = Not Present

                      Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                      1 = Off|2 = On3 = Not Present

                      Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                      1 = Off2 = On3 = Not Present

                      Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                      1 = Off2 = On3 = Not Present

                      Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                      1 = Off2 = On3 = Not Present

                      Table 7 Multistate Input (continued)

                      BCI-I Object Identifier Object Name Description Object States

                      30 ACC-SVP01B-EN bull BCI-I Integration Guide

                      Object Data Points and Diagnostic Data Points

                      Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                      1 = Off2 = On3 = Not Present

                      Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                      1 = Off2 = On3 = Not Present

                      Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                      Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                      Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                      Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                      Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                      1 = Off2 = On3 = Not Present

                      Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                      1= Off2= On3= Not Present

                      Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                      Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                      Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                      Multi-State Input 43 Outdoor Air Damper Status

                      Indicates the operating state of the outdoor damper

                      1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                      Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                      1 = Disabled2 = Enabled3 = Not Present

                      Table 8 Binary Output

                      Object Identifier Object Name DescriptionRelinquish Default Object States

                      Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                      Active = BAS Control

                      Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                      Active = Heating Locked Out

                      Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                      Active = Cooling Locked Out

                      Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                      Active = Enabled

                      Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                      Active = On

                      Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                      Inactive Inactive = DisabledActive = Enabled

                      Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                      Active = Reset

                      Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                      Active = Reset

                      Table 7 Multistate Input (continued)

                      BCI-I Object Identifier Object Name Description Object States

                      ACC-SVP01B-EN bull BCI-I Integration Guide 31

                      Object Data Points and Diagnostic Data Points

                      Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                      Active = Auto

                      Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                      Active = Auto

                      Table 9 Binary Input

                      Object Identifier Object Name Description Object States

                      Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                      Inactive = Standalone controlActive = BAS control

                      Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                      Inactive = NormalActive = Locked Out

                      Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                      Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                      Inactive = AutoActive = Open

                      Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                      Inactive = InactiveActive = Active

                      Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                      Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                      Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                      Inactive = DisabledActive = Enabled

                      Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                      Inactive = DisabledActive = Enabled

                      Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                      Inactive = InactiveActive = Active

                      Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                      Inactive = No FlowActive = Flow

                      Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                      Inactive = InactiveActive = Active

                      Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                      Inactive = InactiveActive = Active

                      Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                      Inactive = InactiveActive = Active

                      Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                      The status of evaporator frost protection function for circuit 1

                      Inactive = InactiveActive = Active

                      Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                      The status of evaporator frost protection function for circuit 2

                      Inactive = InactiveActive = Active

                      Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                      The status of evaporator frost protection function for circuit 3

                      Inactive = InactiveActive = Active

                      Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                      The status of evaporator frost protection function for circuit 4

                      Inactive = InactiveActive = Active

                      Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                      Inactive = De-energizedActive = Energized

                      Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                      Inactive = InactiveActive = Active

                      Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                      Inactive = ClosedActive = Open

                      Table 10 Diagnostics Binary Input

                      Object Identifier(a) Object Name Description

                      Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                      Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                      Binary Input 31 (use Object Identifier for RT or CSC)

                      Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                      Binary Input 31 (use Object Identifier for FAU)

                      Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                      Table 8 Binary Output

                      Object Identifier Object Name DescriptionRelinquish Default Object States

                      32 ACC-SVP01B-EN bull BCI-I Integration Guide

                      Object Data Points and Diagnostic Data Points

                      Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                      Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                      Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                      Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                      Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                      Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                      Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                      Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                      Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                      Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                      Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                      Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                      Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                      Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                      Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                      Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                      Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                      Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                      Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                      Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                      Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                      Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                      Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                      Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                      Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                      Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                      Binary Input 58 (use Object Identifier for RT or CSC)

                      Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                      Binary Input 58 (use Object Identifier for FAU)

                      Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                      Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                      Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                      Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                      Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                      Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                      Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                      Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                      Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                      Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                      Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                      Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                      Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                      Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                      Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                      Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                      Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                      Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                      Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                      Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                      Table 10 Diagnostics Binary Input (continued)

                      Object Identifier(a) Object Name Description

                      ACC-SVP01B-EN bull BCI-I Integration Guide 33

                      Object Data Points and Diagnostic Data Points

                      Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                      Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                      Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                      Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                      Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                      Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                      Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                      Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                      Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                      Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                      Binary Input 86 (use Object Identifier for RT I-pak II)

                      Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                      Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                      Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                      Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                      Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                      Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                      Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                      Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                      Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                      Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                      Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                      Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                      Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                      Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                      Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                      Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                      Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                      Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                      Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                      Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                      Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                      Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                      Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                      Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                      Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                      Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                      Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                      Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                      Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                      Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                      Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                      Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                      Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                      Binary Input 121 (use Object Identifier for RT)

                      Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                      Binary Input 121 (use Object Identifier for FAU)

                      Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                      Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                      Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                      Table 10 Diagnostics Binary Input (continued)

                      Object Identifier(a) Object Name Description

                      34 ACC-SVP01B-EN bull BCI-I Integration Guide

                      Object Data Points and Diagnostic Data Points

                      Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                      Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                      Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                      Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                      Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                      Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                      Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                      Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                      Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                      Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                      Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                      Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                      Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                      Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                      Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                      Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                      Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                      Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                      Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                      Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                      Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                      Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                      Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                      Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                      Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                      Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                      (a) Object States Inactive = normal and Active = foreign language specific

                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                      Object Identifier(a) Object Name Description

                      Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                      Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                      Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                      Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                      Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                      Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                      Multi-State Input 10 Condenser Type General description of the equipment condenser system

                      Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                      Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                      Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                      Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                      Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                      Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                      Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                      Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                      Table 10 Diagnostics Binary Input (continued)

                      Object Identifier(a) Object Name Description

                      ACC-SVP01B-EN bull BCI-I Integration Guide 35

                      Object Data Points and Diagnostic Data Points

                      Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                      Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                      Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                      Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                      Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                      Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                      Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                      Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                      Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                      Analog Input 81 Cool Type Describes the cooling type installed in the unit

                      Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                      Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                      Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                      Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                      Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                      Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                      Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                      Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                      Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                      Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                      Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                      Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                      Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                      Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                      Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                      Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                      Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                      Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                      Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                      Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                      Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                      Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                      Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                      Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                      Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                      Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                      Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                      Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                      Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                      Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                      Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                      Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                      Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                      Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                      Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                      Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                      Object Identifier(a) Object Name Description

                      36 ACC-SVP01B-EN bull BCI-I Integration Guide

                      Object Data Points and Diagnostic Data Points

                      Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                      Multi-State Input 9 Economizer Type General description of the equipment economizer system

                      Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                      Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                      Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                      Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                      Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                      Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                      Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                      Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                      Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                      Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                      Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                      Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                      Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                      Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                      Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                      Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                      Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                      Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                      Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                      Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                      Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                      Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                      Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                      Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                      Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                      Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                      Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                      Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                      Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                      Multi-State Input 36 Final Filter Status Indicates the final filter media state

                      Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                      Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                      Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                      Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                      Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                      Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                      Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                      Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                      Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                      Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                      Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                      Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                      Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                      Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                      Object Identifier(a) Object Name Description

                      ACC-SVP01B-EN bull BCI-I Integration Guide 37

                      Object Data Points and Diagnostic Data Points

                      Binary Output 16 Humidification Command Command the operating state of the humidification system

                      NC 3 HVAC-Advisory HVAC-Advisory

                      NC 1 HVAC-Critical HVAC-Critical

                      NC 4 HVAC-Information HVAC-Information

                      NC 2 HVAC-Service Required HVAC-Service Required

                      Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                      Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                      Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                      Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                      Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                      Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                      Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                      Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                      Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                      Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                      Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                      Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                      Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                      Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                      Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                      Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                      Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                      Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                      Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                      Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                      Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                      Analog Input 82 Preheat Type Describes the heating type installed in the unit

                      Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                      Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                      Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                      Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                      Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                      Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                      Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                      Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                      Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                      Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                      Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                      Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                      Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                      Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                      Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                      Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                      Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                      Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                      Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                      Object Identifier(a) Object Name Description

                      38 ACC-SVP01B-EN bull BCI-I Integration Guide

                      Object Data Points and Diagnostic Data Points

                      Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                      Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                      Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                      Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                      Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                      Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                      Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                      Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                      Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                      Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                      Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                      Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                      Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                      Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                      Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                      Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                      Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                      Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                      Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                      Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                      Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                      Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                      Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                      Binary Input 3 Unit Status Indicates the current state of the unit

                      Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                      Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                      Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                      Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                      Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                      Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                      Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                      (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                      Object Identifier(a) Object Name Description

                      Table 12 Diagnostic Objects Sorted by Object Name

                      Object Identifier(a) Object Name ValueRange Description

                      BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                      BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                      ACC-SVP01B-EN bull BCI-I Integration Guide 39

                      Object Data Points and Diagnostic Data Points

                      BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                      BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                      BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                      BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                      BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                      BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                      BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                      BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                      BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                      BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                      BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                      BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                      BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                      BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                      BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                      BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                      BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                      BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                      BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                      BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                      BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                      BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                      BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                      BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                      BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                      BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                      BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                      BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                      BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                      Object Identifier(a) Object Name ValueRange Description

                      40 ACC-SVP01B-EN bull BCI-I Integration Guide

                      Object Data Points and Diagnostic Data Points

                      BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                      BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                      BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                      BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                      BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                      BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                      BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                      BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                      BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                      BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                      BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                      BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                      BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                      BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                      BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                      BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                      BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                      BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                      BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                      BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                      BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                      BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                      BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                      BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                      BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                      BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                      BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                      BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                      BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                      Object Identifier(a) Object Name ValueRange Description

                      ACC-SVP01B-EN bull BCI-I Integration Guide 41

                      Object Data Points and Diagnostic Data Points

                      BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                      BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                      BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                      BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                      BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                      BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                      BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                      BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                      BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                      BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                      BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                      BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                      BI 121 (use Object Identifier for RT)

                      Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                      BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                      BI 58 (use Object Identifier for RT or CSC)

                      Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                      BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                      BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                      BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                      BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                      BI 31 (use Object Identifier for RT CSC)

                      Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                      BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                      BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                      BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                      BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                      BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                      BI 121 (use Object Identifier for FAU)

                      Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                      B1 31 (use Object Identifier for FAU)

                      Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                      BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                      BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                      Object Identifier(a) Object Name ValueRange Description

                      42 ACC-SVP01B-EN bull BCI-I Integration Guide

                      Object Data Points and Diagnostic Data Points

                      BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                      BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                      BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                      BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                      BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                      BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                      BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                      BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                      BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                      BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                      BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                      BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                      BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                      BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                      BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                      BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                      BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                      BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                      BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                      BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                      BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                      BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                      BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                      1 = active Diagnostic Vel Press Sensor (Rear)

                      BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                      Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                      BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                      BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                      BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                      BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                      BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                      Object Identifier(a) Object Name ValueRange Description

                      ACC-SVP01B-EN bull BCI-I Integration Guide 43

                      Object Data Points and Diagnostic Data Points

                      BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                      BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                      BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                      BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                      BI 58 (use Object Identifier for FAU)

                      Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                      (a) BI=Binary Input

                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                      Object Identifier(a) Object Name ValueRange Description

                      44 ACC-SVP01B-EN bull BCI-I Integration Guide

                      Additional Resources

                      Additional Resources

                      Use the following documents and links as additional resources

                      bull Product support online

                      bull wwwbacnetorg

                      bull wwwbacnetassociationorg

                      bull wwwashraeorg

                      bull Tracer TU Help online

                      bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                      bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                      Note For further assistance contact your local Trane sales office

                      ACC-SVP01B-EN bull BCI-I Integration Guide 45

                      Glossary

                      A

                      ASHRAE

                      See American Society of Heating Refrigeration and Air-conditioning Engineers

                      American Society of Heating Refrigeration and Air-

                      conditioning Engineers

                      An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                      BBACnettrade

                      See Building Automation Control network

                      BACnet interoperability building blocks

                      A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                      BACnet object

                      An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                      baud rate

                      The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                      BIBB

                      See BACnet interoperability building blocks

                      Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                      advocates BACnet protocol for use in system-level control devices

                      device

                      A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                      Device ID

                      The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                      Iinteroperability

                      The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                      Pprotocol

                      A set of rules (language) that governs the exchange of data over a digital communications system

                      S

                      stand-alone operation

                      Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                      wwwtranecom

                      For more information contact your local Trane office or e-mail us at comforttranecom

                      Literature Order Number ACC-SVP01B-EN

                      Date September 2009

                      Supersedes ACC-SVP01A-EN

                      Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                      • Table of Contents
                      • Overview
                      • Ordering Numbers
                      • BACnet Protocol
                      • BCI-I Configuration
                        • Overview
                        • Starting a Session of Tracer TU and Direct Connection
                        • Reset to Factory Default
                        • IP Units Configuration
                        • BACnet Object Configuration
                        • Change Baud Rate
                        • Change Device ID
                        • Stand-alone or BAS Operation
                          • IntelliPak Control Configuration
                          • BAS Unit Control
                          • Periodic Update of BAS Values
                          • BAS Communication Failure
                            • InputOutput Commands and Calculations
                              • System Control Command
                              • Filter Timer Reset Command
                              • Diagnostics Reset Command
                              • Setpoint Calculations
                              • Timestamp Configuration
                                  • BCI IntelliPak Rotary Switches and LEDs
                                    • Rotary Switches
                                    • LEDs Description Behavior and Troubleshooting
                                    • 24 Vac Measurement
                                    • Ground Measurements
                                      • BACnet Data Points and Configuration Property Definitions
                                        • BACnet Protocol Implementation Conformance Statement (PICS)
                                          • Standardized Device Profile (Annex L)
                                          • Interoperability Building Blocks (Annex K)
                                          • Segmentation Capability
                                          • Object Types
                                            • BACnet Protocol
                                              • Data Link Layer Options
                                              • Device Address Binding
                                              • Networking Options
                                              • Character Sets
                                                  • Object Data Points and Diagnostic Data Points
                                                  • Additional Resources
                                                  • Glossary

                        12 ACC-SVP01B-EN bull BCI-I Integration Guide

                        BCI IntelliPak Rotary Switches and LEDs

                        BCI IntelliPak Rotary Switches and LEDs

                        This section provides information about the BCI-I rotary switches and LED displays

                        Rotary Switches

                        There are three rotary switches on the front of the BCI-I device that are used to define a three-digit address when the BCI-I is installed on a BACnet communications network The three-digit address setting is the BACnet MAC address

                        Note All devices are MSTP masters with valid MAC addresses of 001 to 127 for BACnet

                        Figure 1 Setting rotary switches

                        ADDRESS0 1

                        23

                        456

                        78

                        9

                        x1

                        0 1

                        23

                        456

                        78

                        9

                        x10

                        0 1

                        23

                        456

                        78

                        9

                        x100

                        Before

                        After

                        0

                        5

                        1

                        3

                        6

                        29

                        487

                        Example of before and after setting addresses

                        Use a 18 inch flathead screwdriver to set rotary switches

                        Important Each device on the BACnetMSTP link must have a unique rotary switch setting otherwise communication problems will occur

                        ACC-SVP01B-EN bull BCI-I Integration Guide 13

                        BCI IntelliPak Rotary Switches and LEDs

                        LEDs Description Behavior and Troubleshooting

                        There are 15 LEDs on the front of the BCI-I unit However LEDs BO1 through BO9 are not used for the BCI-I controller Figure 2 shows the locations of each LED The following table provides a description of each LED activity an indication or troubleshooting tips for each and any notes

                        Figure 2 LED locations

                        SERVICE

                        IMCLINK

                        RX

                        TX

                        Marquee LED

                        Table 1 LED Activities and Troubleshooting Tips

                        LED Name ActivitiesIndication or Troubleshooting

                        Tip (Denoted in Bullets) Notes

                        Marquee LED

                        Shows solid green when the unit is powered and no problems exist

                        Indicates normal operation

                        Shows solid red when the unit is powered but represents low power or a

                        malfunction

                        bull If low power could be under voltage or the microprocessor has malfunction Follow the troubleshoot procedure ldquo24 Vac Measurementrdquo p 15 to measure for the expected value range

                        bull If malfunction unpower and then repower unit to bring the device back up to normal operation

                        Shows blinking red when an a BACnet object is in a fault condition

                        Alarm when an alarm is triggered for example when a point goes into fault condition because of point failure or there is an indication of a custom alarm in TGP2

                        Shows blinking green when the device does not detect the IMC buss

                        bull Verify that the IPC wiring harness is connected to the IMC link terminals

                        bull Verify the polarity of the IPC wiring harness at the unit terminals

                        LED not lit

                        Indicates power is OFF or there is a malfunction

                        bull OFF or malfunction cycle the power

                        14 ACC-SVP01B-EN bull BCI-I Integration Guide

                        BCI IntelliPak Rotary Switches and LEDs

                        Link and IMC

                        TX blinks greenBlinks at the data transfer rate when the unit transfers data to other devices on the link

                        TX LED Regardless of connectivity or not this LED will constantly blink as it continually looks for devices to communicate to

                        LED not litDetermine if for example a Tracer SC or BACnet device is trying to talk to the controller or if it is capable of talking to the controller Also determine if the communication status shows down all of the time

                        Refer to ldquoGround Measurementsrdquo p 16 for a check-out procedure

                        RX blinks yellow

                        Blinks at the data transfer rate when the unit receives data from other devices on the link

                        bull ON solid yellow indicates there is reverse polarity

                        LED not lit

                        Indicates that the controller is not detecting communication

                        bull Not lit cycle the power to reestablish communication

                        Service

                        Shows solid greenIndicates someone is pressing this LED or the controller is not operating normally

                        Press and hold during power up to place controller into boot code or press and hold for a count of approximately 10 seconds to clear the Device ID

                        What is Boot Code When the UC400 is placed into boot code the system will not run any applications such as trending scheduling and TGP2 runtime

                        Blinks green

                        Indicates controllers is not accessing application software

                        bull Restore using TU service tool

                        LED not lit Indicates controller is operating normally

                        Binary 01 to Binary 09 Not Used

                        Table 1 LED Activities and Troubleshooting Tips

                        LED Name ActivitiesIndication or Troubleshooting

                        Tip (Denoted in Bullets) Notes

                        ACC-SVP01B-EN bull BCI-I Integration Guide 15

                        BCI IntelliPak Rotary Switches and LEDs

                        24 Vac Measurement

                        General Information Checkout Procedure Measurement Expected Value

                        Checking the voltage that is powering the UC400 is often a necessary step when commissioning or troubleshooting Operational issues and LED operation may result in a need to measure the input power

                        When troubleshooting it is faster to take measurements while the load is in place If Step 1 indicates an out-of-specification voltage disconnect the UC400 and measure the AC voltage across the transformer These measurements can direct the technician towards the problem source

                        Step 1

                        Measure AC voltage with the UC400 connected Perform this measurement while the unit is under load

                        200 Vac le Vac le 300 Vac

                        Step 2

                        Measure AC voltage with the UC400 unconnected Perform this measurement while the unit is not under load

                        200 Vac le Vac le 300 Vac

                        16 ACC-SVP01B-EN bull BCI-I Integration Guide

                        BCI IntelliPak Rotary Switches and LEDs

                        Ground Measurements

                        General Information and Checkout Procedure Measurement Expected Value

                        Method 1AC voltage between shield conductors and device chassis ground- the voltage difference between BACnet MSTP device chassis ground connections should be close to zero If the voltage difference is greater that 40 Vac there will be marginal communication or intermittent communication problems If the voltage difference is greater that 70 Vac some devices will no longer communicate

                        Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                        Vac le 20 V

                        Method 2AC voltage between earth ground and device chassis ground- the chassis ground of the UC400 needs to be connected to earth ground by some route

                        Note Do not assume that the building frame is a valid earth ground

                        Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                        Vac le 40 V (Must comply with National Electrical Codetradeand local electrical codes)

                        ACC-SVP01B-EN bull BCI-I Integration Guide 17

                        BACnet Data Points and Configuration Property Definitions

                        BACnet Data Points and Configuration Property

                        Definitions

                        The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MSTP This section includes information about

                        bull BACnet protocol implementation conformance statement (PICS)

                        bull Object types descriptions and configuration (refer to Table 2 p 19)

                        bull BACnet protocol data link layers device address binding networking options and character sets

                        bull Object data points and configurations

                        BACnet Protocol Implementation Conformance Statement (PICS)

                        Standardized Device Profile (Annex L)

                        Interoperability Building Blocks (Annex K)

                        Profile Description Supported Profile

                        BACnet Advanced Application Controller (B-AAC)

                        BACnet Application Specific Controller (B-ASC)

                        BACnet Building Controller (B-BC)

                        BACnet Operator Workstation (B-OWS)

                        BACnet Smart Actuator (B-SA)

                        BACnet Smart Sensor (B-SS)

                        Data Sharing Description Supported BIBB

                        Data Sharing-COV-B (DS-COV-B)

                        Data Sharing-ReadProperty-A (DS-RP-A)

                        Data Sharing-ReadProperty-B (DS-RP-B)

                        Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)

                        Data Sharing-WriteProperty-A (DS-WP-A)

                        Data Sharing-WriteProperty-B (DS-WP-B)

                        Data Sharing-WritePropertyMultiple-B (DS-WPM-B)

                        Alarm and Event Management Description Supported BIBB

                        Alarm and Event-ACKI-B (AE-ACK-B)

                        Alarm and Event-Alarm Summary-B (AE-ASUM-B)

                        Alarm and Event-Enrollment Summary-B (AE-ESUM-B)

                        Alarm and Event-Information-B (AE-INFO-B)

                        Alarm and Event-Notification Internal-B (AE-N-I-B)

                        18 ACC-SVP01B-EN bull BCI-I Integration Guide

                        BACnet Data Points and Configuration Property Definitions

                        Segmentation Capability

                        Trending Description Supported BIBB

                        Trending-Automated Trend Retrieval-B (T-ATR-B)

                        Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

                        Device Management Description Supported BIBB

                        Device Management-Backup and Restore-B (DM-BR-B)

                        Device Management-Device Communication Control-B (DM-DCC-B)

                        Device Management-Dynamic Device Binding-A (DM-DDB-A)

                        Device Management-Dynamic Device Binding-B (DM-DDB-B)

                        Device Management-Dynamic Object Binding-B (DM-DOB-B)

                        Device Management-List Manipulation-B (DM-LM-B)

                        Device Management-Object Creation and Deletion-B (DM-OCD-B)

                        Device Management-Private Transfer-A (DM-PT-A)

                        Device Management-Private Transfer-B (DM-PT-B)

                        Device Management-Reinitialize Device-B (DM-RD-B)

                        Device Management-TimeSynchronization-B (DM-TS-B)

                        Segmentation Description Supported Segment

                        Segmented Requests Window Size 1

                        Segmented Responses Window Size 1

                        ACC-SVP01B-EN bull BCI-I Integration Guide 19

                        BACnet Data Points and Configuration Property Definitions

                        Object Types

                        Table 2 Descriptions and configurations

                        Object Type Required Properties Read Properties Written(a) Optional Properties Read

                        Ability to Create

                        Ability to Delete

                        Analog Input

                        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                        bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                        bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                        Yes Yes only user created objects

                        Analog Output

                        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

                        bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                        bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                        Yes Yes only user created objects

                        Analog Value

                        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                        bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                        bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                        Yes Yes only user created objects

                        Binary Input

                        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                        bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                        bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                        Yes Yes only user created objects

                        20 ACC-SVP01B-EN bull BCI-I Integration Guide

                        BACnet Data Points and Configuration Property Definitions

                        Binary Output

                        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

                        bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

                        bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                        Yes Yes only user created objects

                        Binary Value

                        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                        bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                        bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                        Yes Yes only user created objects

                        Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

                        bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

                        bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

                        None None

                        Event Enrollment Object

                        bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

                        bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

                        bull None Yes Yes only user created objects

                        Table 2 Descriptions and configurations (continued)

                        Object Type Required Properties Read Properties Written(a) Optional Properties Read

                        Ability to Create

                        Ability to Delete

                        ACC-SVP01B-EN bull BCI-I Integration Guide 21

                        BACnet Data Points and Configuration Property Definitions

                        Multistate Input

                        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                        bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                        bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                        Yes Yes only user created objects

                        Multistate Output

                        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

                        bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

                        bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                        Yes Yes only user created objects

                        Multistate Value

                        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                        bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                        bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                        Yes Yes only user created objects

                        Notification Class

                        bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

                        bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

                        None Yes Yes only user created objects

                        Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

                        bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

                        bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

                        Yes Yes only user created objects

                        (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

                        Table 2 Descriptions and configurations (continued)

                        Object Type Required Properties Read Properties Written(a) Optional Properties Read

                        Ability to Create

                        Ability to Delete

                        22 ACC-SVP01B-EN bull BCI-I Integration Guide

                        BACnet Data Points and Configuration Property Definitions

                        BACnet Protocol

                        Data Link Layer Options

                        Device Address Binding

                        Networking Options

                        Data Link Layer Description Supported Option

                        ANSIATA 8781 25 Mb ARCNET (Clause 8)

                        ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

                        BACnet IP (Annex J)

                        BACnet IP (Annex J) Foreign Device

                        ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

                        LonTalk (Clause 11) Medium

                        MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

                        MSTP Slave (Clause 9) Baud Rate(s)

                        Other

                        Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

                        Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

                        Device Address Binding Supported

                        Static Device Binding Supported

                        Networking DescriptionsSupported

                        Option

                        Annex H BACnet Tunneling

                        BACnetIP Broadcast Management Device (BBMD)

                        Does the BBMD Support Registrations by Foreign Devices

                        Router

                        ACC-SVP01B-EN bull BCI-I Integration Guide 23

                        BACnet Data Points and Configuration Property Definitions

                        Character Sets

                        Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

                        Character Set Descriptions Supported

                        ANSI X34

                        IBMMicrosoft DBCS

                        ISO 10646 (UCS-4)

                        ISO 10646 (UCS2)

                        ISO 8859-1

                        JIS C 6226

                        24 ACC-SVP01B-EN bull BCI-I Integration Guide

                        Object Data Points and Diagnostic Data Points

                        Object Data Points and Diagnostic Data Points

                        For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

                        Table 3 Analog Output

                        Object Identifier Object Name Description Units Valid Range

                        Refresh Rate

                        (Sec)

                        Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

                        Percent (98) 0 to 100 NA

                        Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

                        Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

                        Degrees-Fahrenheit (64) 500 to 900 NA

                        Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

                        BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

                        Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

                        Degrees-Fahrenheit (64) 400 to 900 NA

                        Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

                        Degrees-Fahrenheit (64) 400 to 1800 NA

                        Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

                        070 to 510 (Ipak II) NA

                        Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

                        003 to 030-002 to 030 (enhanced StatiTrac)

                        NA

                        Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

                        -028 to 050-067 to 067 (enhanced StatiTrac)

                        900

                        Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                        Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                        Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

                        00 to 79 (Ipak II) 900

                        Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                        Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

                        Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

                        Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

                        Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

                        Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

                        Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

                        Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

                        Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

                        Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

                        ACC-SVP01B-EN bull BCI-I Integration Guide 25

                        Object Data Points and Diagnostic Data Points

                        Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                        Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                        Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                        Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                        Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                        Cooling temperature setpoint used for control in unoccupied mode

                        Degrees-Fahrenheit (64) 520 to 880 NA

                        Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                        Heating temperature setpoint used for control in unoccupied mode

                        Degrees-Fahrenheit (64) 500 to 900 NA

                        Table 4 Analog Input

                        Object Identifier Object Name Description Units (Listed Are Defaults)

                        Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                        Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                        Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                        Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                        Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                        Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                        Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                        Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                        Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                        Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                        Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                        Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                        Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                        Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                        Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                        Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                        Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                        Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                        Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                        Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                        Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                        Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                        Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                        Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                        Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                        Table 3 Analog Output (continued)

                        Object Identifier Object Name Description Units Valid Range

                        Refresh Rate

                        (Sec)

                        26 ACC-SVP01B-EN bull BCI-I Integration Guide

                        Object Data Points and Diagnostic Data Points

                        Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                        Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                        Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                        Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                        Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                        Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                        Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                        Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                        Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                        Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                        Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                        Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                        Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                        Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                        Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                        Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                        Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                        Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                        Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                        Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                        Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                        Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                        Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                        Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                        The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                        Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                        The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                        Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                        Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                        Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                        Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                        Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                        Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                        Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                        Table 4 Analog Input (continued)

                        Object Identifier Object Name Description Units (Listed Are Defaults)

                        ACC-SVP01B-EN bull BCI-I Integration Guide 27

                        Object Data Points and Diagnostic Data Points

                        Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                        Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                        Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                        Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                        The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                        Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                        Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                        Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                        Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                        Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                        Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                        Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                        Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                        Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                        Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                        Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                        Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                        Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                        Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                        Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                        Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                        Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                        Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                        Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                        Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                        Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                        Table 5 Analog Value

                        Object Identifier Object Name Description Units Valid Range

                        Analog Value 1 Filter Runtime Hours Setpoint

                        The setpoint value used by the filter run hours calculation

                        Hours (71) 0 to 10000

                        Table 4 Analog Input (continued)

                        Object Identifier Object Name Description Units (Listed Are Defaults)

                        28 ACC-SVP01B-EN bull BCI-I Integration Guide

                        Object Data Points and Diagnostic Data Points

                        Table 6 Multistate Output

                        BCI-I Object Identifier Object Name Description Object States

                        Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                        Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                        1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                        Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                        Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                        1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                        Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                        1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                        Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                        1 = Flow2 = No Flow3 = Auto

                        Table 7 Multistate Input

                        BCI-I Object Identifier Object Name Description Object States

                        Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                        1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                        Multi-State Input 9 Economizer Type General description of the equipment economizer system

                        1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                        Multi-State Input 10 Condenser Type General description of the equipment condenser system

                        1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                        Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                        1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                        ACC-SVP01B-EN bull BCI-I Integration Guide 29

                        Object Data Points and Diagnostic Data Points

                        Multi-State Input 15 Economizer Decision Method

                        Unit method to determine when the economizer system is enabled

                        1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                        Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                        Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                        Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                        1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                        Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                        1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                        Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                        1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                        Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                        1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                        Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                        1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                        Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                        1 = Idle2 = On3 = Cancel

                        Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                        1 = Off2 = On3 = Not Present

                        Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                        1 = Off2 = On3 = Not Present

                        Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                        1 = Off2 = On3 = Not Present

                        Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                        1 = Off|2 = On3 = Not Present

                        Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                        1 = Off2 = On3 = Not Present

                        Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                        1 = Off2 = On3 = Not Present

                        Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                        1 = Off2 = On3 = Not Present

                        Table 7 Multistate Input (continued)

                        BCI-I Object Identifier Object Name Description Object States

                        30 ACC-SVP01B-EN bull BCI-I Integration Guide

                        Object Data Points and Diagnostic Data Points

                        Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                        1 = Off2 = On3 = Not Present

                        Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                        1 = Off2 = On3 = Not Present

                        Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                        Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                        Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                        Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                        Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                        1 = Off2 = On3 = Not Present

                        Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                        1= Off2= On3= Not Present

                        Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                        Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                        Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                        Multi-State Input 43 Outdoor Air Damper Status

                        Indicates the operating state of the outdoor damper

                        1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                        Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                        1 = Disabled2 = Enabled3 = Not Present

                        Table 8 Binary Output

                        Object Identifier Object Name DescriptionRelinquish Default Object States

                        Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                        Active = BAS Control

                        Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                        Active = Heating Locked Out

                        Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                        Active = Cooling Locked Out

                        Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                        Active = Enabled

                        Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                        Active = On

                        Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                        Inactive Inactive = DisabledActive = Enabled

                        Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                        Active = Reset

                        Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                        Active = Reset

                        Table 7 Multistate Input (continued)

                        BCI-I Object Identifier Object Name Description Object States

                        ACC-SVP01B-EN bull BCI-I Integration Guide 31

                        Object Data Points and Diagnostic Data Points

                        Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                        Active = Auto

                        Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                        Active = Auto

                        Table 9 Binary Input

                        Object Identifier Object Name Description Object States

                        Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                        Inactive = Standalone controlActive = BAS control

                        Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                        Inactive = NormalActive = Locked Out

                        Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                        Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                        Inactive = AutoActive = Open

                        Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                        Inactive = InactiveActive = Active

                        Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                        Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                        Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                        Inactive = DisabledActive = Enabled

                        Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                        Inactive = DisabledActive = Enabled

                        Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                        Inactive = InactiveActive = Active

                        Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                        Inactive = No FlowActive = Flow

                        Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                        Inactive = InactiveActive = Active

                        Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                        Inactive = InactiveActive = Active

                        Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                        Inactive = InactiveActive = Active

                        Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                        The status of evaporator frost protection function for circuit 1

                        Inactive = InactiveActive = Active

                        Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                        The status of evaporator frost protection function for circuit 2

                        Inactive = InactiveActive = Active

                        Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                        The status of evaporator frost protection function for circuit 3

                        Inactive = InactiveActive = Active

                        Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                        The status of evaporator frost protection function for circuit 4

                        Inactive = InactiveActive = Active

                        Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                        Inactive = De-energizedActive = Energized

                        Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                        Inactive = InactiveActive = Active

                        Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                        Inactive = ClosedActive = Open

                        Table 10 Diagnostics Binary Input

                        Object Identifier(a) Object Name Description

                        Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                        Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                        Binary Input 31 (use Object Identifier for RT or CSC)

                        Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                        Binary Input 31 (use Object Identifier for FAU)

                        Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                        Table 8 Binary Output

                        Object Identifier Object Name DescriptionRelinquish Default Object States

                        32 ACC-SVP01B-EN bull BCI-I Integration Guide

                        Object Data Points and Diagnostic Data Points

                        Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                        Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                        Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                        Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                        Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                        Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                        Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                        Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                        Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                        Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                        Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                        Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                        Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                        Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                        Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                        Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                        Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                        Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                        Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                        Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                        Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                        Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                        Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                        Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                        Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                        Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                        Binary Input 58 (use Object Identifier for RT or CSC)

                        Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                        Binary Input 58 (use Object Identifier for FAU)

                        Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                        Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                        Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                        Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                        Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                        Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                        Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                        Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                        Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                        Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                        Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                        Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                        Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                        Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                        Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                        Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                        Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                        Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                        Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                        Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                        Table 10 Diagnostics Binary Input (continued)

                        Object Identifier(a) Object Name Description

                        ACC-SVP01B-EN bull BCI-I Integration Guide 33

                        Object Data Points and Diagnostic Data Points

                        Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                        Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                        Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                        Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                        Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                        Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                        Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                        Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                        Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                        Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                        Binary Input 86 (use Object Identifier for RT I-pak II)

                        Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                        Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                        Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                        Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                        Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                        Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                        Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                        Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                        Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                        Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                        Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                        Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                        Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                        Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                        Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                        Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                        Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                        Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                        Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                        Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                        Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                        Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                        Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                        Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                        Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                        Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                        Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                        Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                        Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                        Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                        Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                        Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                        Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                        Binary Input 121 (use Object Identifier for RT)

                        Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                        Binary Input 121 (use Object Identifier for FAU)

                        Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                        Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                        Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                        Table 10 Diagnostics Binary Input (continued)

                        Object Identifier(a) Object Name Description

                        34 ACC-SVP01B-EN bull BCI-I Integration Guide

                        Object Data Points and Diagnostic Data Points

                        Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                        Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                        Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                        Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                        Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                        Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                        Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                        Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                        Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                        Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                        Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                        Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                        Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                        Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                        Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                        Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                        Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                        Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                        Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                        Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                        Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                        Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                        Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                        Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                        Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                        Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                        (a) Object States Inactive = normal and Active = foreign language specific

                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                        Object Identifier(a) Object Name Description

                        Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                        Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                        Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                        Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                        Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                        Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                        Multi-State Input 10 Condenser Type General description of the equipment condenser system

                        Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                        Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                        Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                        Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                        Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                        Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                        Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                        Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                        Table 10 Diagnostics Binary Input (continued)

                        Object Identifier(a) Object Name Description

                        ACC-SVP01B-EN bull BCI-I Integration Guide 35

                        Object Data Points and Diagnostic Data Points

                        Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                        Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                        Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                        Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                        Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                        Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                        Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                        Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                        Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                        Analog Input 81 Cool Type Describes the cooling type installed in the unit

                        Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                        Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                        Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                        Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                        Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                        Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                        Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                        Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                        Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                        Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                        Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                        Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                        Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                        Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                        Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                        Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                        Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                        Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                        Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                        Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                        Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                        Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                        Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                        Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                        Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                        Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                        Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                        Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                        Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                        Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                        Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                        Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                        Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                        Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                        Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                        Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                        Object Identifier(a) Object Name Description

                        36 ACC-SVP01B-EN bull BCI-I Integration Guide

                        Object Data Points and Diagnostic Data Points

                        Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                        Multi-State Input 9 Economizer Type General description of the equipment economizer system

                        Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                        Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                        Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                        Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                        Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                        Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                        Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                        Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                        Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                        Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                        Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                        Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                        Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                        Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                        Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                        Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                        Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                        Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                        Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                        Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                        Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                        Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                        Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                        Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                        Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                        Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                        Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                        Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                        Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                        Multi-State Input 36 Final Filter Status Indicates the final filter media state

                        Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                        Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                        Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                        Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                        Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                        Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                        Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                        Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                        Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                        Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                        Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                        Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                        Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                        Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                        Object Identifier(a) Object Name Description

                        ACC-SVP01B-EN bull BCI-I Integration Guide 37

                        Object Data Points and Diagnostic Data Points

                        Binary Output 16 Humidification Command Command the operating state of the humidification system

                        NC 3 HVAC-Advisory HVAC-Advisory

                        NC 1 HVAC-Critical HVAC-Critical

                        NC 4 HVAC-Information HVAC-Information

                        NC 2 HVAC-Service Required HVAC-Service Required

                        Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                        Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                        Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                        Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                        Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                        Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                        Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                        Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                        Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                        Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                        Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                        Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                        Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                        Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                        Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                        Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                        Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                        Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                        Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                        Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                        Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                        Analog Input 82 Preheat Type Describes the heating type installed in the unit

                        Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                        Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                        Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                        Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                        Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                        Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                        Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                        Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                        Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                        Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                        Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                        Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                        Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                        Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                        Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                        Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                        Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                        Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                        Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                        Object Identifier(a) Object Name Description

                        38 ACC-SVP01B-EN bull BCI-I Integration Guide

                        Object Data Points and Diagnostic Data Points

                        Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                        Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                        Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                        Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                        Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                        Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                        Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                        Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                        Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                        Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                        Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                        Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                        Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                        Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                        Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                        Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                        Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                        Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                        Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                        Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                        Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                        Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                        Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                        Binary Input 3 Unit Status Indicates the current state of the unit

                        Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                        Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                        Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                        Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                        Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                        Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                        Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                        (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                        Object Identifier(a) Object Name Description

                        Table 12 Diagnostic Objects Sorted by Object Name

                        Object Identifier(a) Object Name ValueRange Description

                        BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                        BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                        ACC-SVP01B-EN bull BCI-I Integration Guide 39

                        Object Data Points and Diagnostic Data Points

                        BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                        BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                        BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                        BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                        BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                        BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                        BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                        BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                        BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                        BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                        BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                        BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                        BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                        BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                        BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                        BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                        BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                        BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                        BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                        BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                        BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                        BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                        BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                        BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                        BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                        BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                        BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                        BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                        BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                        Object Identifier(a) Object Name ValueRange Description

                        40 ACC-SVP01B-EN bull BCI-I Integration Guide

                        Object Data Points and Diagnostic Data Points

                        BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                        BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                        BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                        BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                        BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                        BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                        BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                        BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                        BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                        BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                        BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                        BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                        BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                        BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                        BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                        BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                        BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                        BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                        BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                        BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                        BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                        BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                        BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                        BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                        BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                        BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                        BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                        BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                        BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                        Object Identifier(a) Object Name ValueRange Description

                        ACC-SVP01B-EN bull BCI-I Integration Guide 41

                        Object Data Points and Diagnostic Data Points

                        BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                        BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                        BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                        BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                        BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                        BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                        BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                        BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                        BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                        BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                        BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                        BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                        BI 121 (use Object Identifier for RT)

                        Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                        BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                        BI 58 (use Object Identifier for RT or CSC)

                        Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                        BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                        BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                        BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                        BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                        BI 31 (use Object Identifier for RT CSC)

                        Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                        BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                        BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                        BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                        BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                        BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                        BI 121 (use Object Identifier for FAU)

                        Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                        B1 31 (use Object Identifier for FAU)

                        Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                        BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                        BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                        Object Identifier(a) Object Name ValueRange Description

                        42 ACC-SVP01B-EN bull BCI-I Integration Guide

                        Object Data Points and Diagnostic Data Points

                        BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                        BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                        BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                        BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                        BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                        BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                        BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                        BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                        BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                        BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                        BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                        BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                        BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                        BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                        BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                        BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                        BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                        BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                        BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                        BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                        BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                        BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                        BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                        1 = active Diagnostic Vel Press Sensor (Rear)

                        BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                        Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                        BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                        BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                        BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                        BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                        BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                        Object Identifier(a) Object Name ValueRange Description

                        ACC-SVP01B-EN bull BCI-I Integration Guide 43

                        Object Data Points and Diagnostic Data Points

                        BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                        BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                        BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                        BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                        BI 58 (use Object Identifier for FAU)

                        Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                        (a) BI=Binary Input

                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                        Object Identifier(a) Object Name ValueRange Description

                        44 ACC-SVP01B-EN bull BCI-I Integration Guide

                        Additional Resources

                        Additional Resources

                        Use the following documents and links as additional resources

                        bull Product support online

                        bull wwwbacnetorg

                        bull wwwbacnetassociationorg

                        bull wwwashraeorg

                        bull Tracer TU Help online

                        bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                        bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                        Note For further assistance contact your local Trane sales office

                        ACC-SVP01B-EN bull BCI-I Integration Guide 45

                        Glossary

                        A

                        ASHRAE

                        See American Society of Heating Refrigeration and Air-conditioning Engineers

                        American Society of Heating Refrigeration and Air-

                        conditioning Engineers

                        An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                        BBACnettrade

                        See Building Automation Control network

                        BACnet interoperability building blocks

                        A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                        BACnet object

                        An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                        baud rate

                        The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                        BIBB

                        See BACnet interoperability building blocks

                        Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                        advocates BACnet protocol for use in system-level control devices

                        device

                        A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                        Device ID

                        The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                        Iinteroperability

                        The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                        Pprotocol

                        A set of rules (language) that governs the exchange of data over a digital communications system

                        S

                        stand-alone operation

                        Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                        wwwtranecom

                        For more information contact your local Trane office or e-mail us at comforttranecom

                        Literature Order Number ACC-SVP01B-EN

                        Date September 2009

                        Supersedes ACC-SVP01A-EN

                        Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                        • Table of Contents
                        • Overview
                        • Ordering Numbers
                        • BACnet Protocol
                        • BCI-I Configuration
                          • Overview
                          • Starting a Session of Tracer TU and Direct Connection
                          • Reset to Factory Default
                          • IP Units Configuration
                          • BACnet Object Configuration
                          • Change Baud Rate
                          • Change Device ID
                          • Stand-alone or BAS Operation
                            • IntelliPak Control Configuration
                            • BAS Unit Control
                            • Periodic Update of BAS Values
                            • BAS Communication Failure
                              • InputOutput Commands and Calculations
                                • System Control Command
                                • Filter Timer Reset Command
                                • Diagnostics Reset Command
                                • Setpoint Calculations
                                • Timestamp Configuration
                                    • BCI IntelliPak Rotary Switches and LEDs
                                      • Rotary Switches
                                      • LEDs Description Behavior and Troubleshooting
                                      • 24 Vac Measurement
                                      • Ground Measurements
                                        • BACnet Data Points and Configuration Property Definitions
                                          • BACnet Protocol Implementation Conformance Statement (PICS)
                                            • Standardized Device Profile (Annex L)
                                            • Interoperability Building Blocks (Annex K)
                                            • Segmentation Capability
                                            • Object Types
                                              • BACnet Protocol
                                                • Data Link Layer Options
                                                • Device Address Binding
                                                • Networking Options
                                                • Character Sets
                                                    • Object Data Points and Diagnostic Data Points
                                                    • Additional Resources
                                                    • Glossary

                          ACC-SVP01B-EN bull BCI-I Integration Guide 13

                          BCI IntelliPak Rotary Switches and LEDs

                          LEDs Description Behavior and Troubleshooting

                          There are 15 LEDs on the front of the BCI-I unit However LEDs BO1 through BO9 are not used for the BCI-I controller Figure 2 shows the locations of each LED The following table provides a description of each LED activity an indication or troubleshooting tips for each and any notes

                          Figure 2 LED locations

                          SERVICE

                          IMCLINK

                          RX

                          TX

                          Marquee LED

                          Table 1 LED Activities and Troubleshooting Tips

                          LED Name ActivitiesIndication or Troubleshooting

                          Tip (Denoted in Bullets) Notes

                          Marquee LED

                          Shows solid green when the unit is powered and no problems exist

                          Indicates normal operation

                          Shows solid red when the unit is powered but represents low power or a

                          malfunction

                          bull If low power could be under voltage or the microprocessor has malfunction Follow the troubleshoot procedure ldquo24 Vac Measurementrdquo p 15 to measure for the expected value range

                          bull If malfunction unpower and then repower unit to bring the device back up to normal operation

                          Shows blinking red when an a BACnet object is in a fault condition

                          Alarm when an alarm is triggered for example when a point goes into fault condition because of point failure or there is an indication of a custom alarm in TGP2

                          Shows blinking green when the device does not detect the IMC buss

                          bull Verify that the IPC wiring harness is connected to the IMC link terminals

                          bull Verify the polarity of the IPC wiring harness at the unit terminals

                          LED not lit

                          Indicates power is OFF or there is a malfunction

                          bull OFF or malfunction cycle the power

                          14 ACC-SVP01B-EN bull BCI-I Integration Guide

                          BCI IntelliPak Rotary Switches and LEDs

                          Link and IMC

                          TX blinks greenBlinks at the data transfer rate when the unit transfers data to other devices on the link

                          TX LED Regardless of connectivity or not this LED will constantly blink as it continually looks for devices to communicate to

                          LED not litDetermine if for example a Tracer SC or BACnet device is trying to talk to the controller or if it is capable of talking to the controller Also determine if the communication status shows down all of the time

                          Refer to ldquoGround Measurementsrdquo p 16 for a check-out procedure

                          RX blinks yellow

                          Blinks at the data transfer rate when the unit receives data from other devices on the link

                          bull ON solid yellow indicates there is reverse polarity

                          LED not lit

                          Indicates that the controller is not detecting communication

                          bull Not lit cycle the power to reestablish communication

                          Service

                          Shows solid greenIndicates someone is pressing this LED or the controller is not operating normally

                          Press and hold during power up to place controller into boot code or press and hold for a count of approximately 10 seconds to clear the Device ID

                          What is Boot Code When the UC400 is placed into boot code the system will not run any applications such as trending scheduling and TGP2 runtime

                          Blinks green

                          Indicates controllers is not accessing application software

                          bull Restore using TU service tool

                          LED not lit Indicates controller is operating normally

                          Binary 01 to Binary 09 Not Used

                          Table 1 LED Activities and Troubleshooting Tips

                          LED Name ActivitiesIndication or Troubleshooting

                          Tip (Denoted in Bullets) Notes

                          ACC-SVP01B-EN bull BCI-I Integration Guide 15

                          BCI IntelliPak Rotary Switches and LEDs

                          24 Vac Measurement

                          General Information Checkout Procedure Measurement Expected Value

                          Checking the voltage that is powering the UC400 is often a necessary step when commissioning or troubleshooting Operational issues and LED operation may result in a need to measure the input power

                          When troubleshooting it is faster to take measurements while the load is in place If Step 1 indicates an out-of-specification voltage disconnect the UC400 and measure the AC voltage across the transformer These measurements can direct the technician towards the problem source

                          Step 1

                          Measure AC voltage with the UC400 connected Perform this measurement while the unit is under load

                          200 Vac le Vac le 300 Vac

                          Step 2

                          Measure AC voltage with the UC400 unconnected Perform this measurement while the unit is not under load

                          200 Vac le Vac le 300 Vac

                          16 ACC-SVP01B-EN bull BCI-I Integration Guide

                          BCI IntelliPak Rotary Switches and LEDs

                          Ground Measurements

                          General Information and Checkout Procedure Measurement Expected Value

                          Method 1AC voltage between shield conductors and device chassis ground- the voltage difference between BACnet MSTP device chassis ground connections should be close to zero If the voltage difference is greater that 40 Vac there will be marginal communication or intermittent communication problems If the voltage difference is greater that 70 Vac some devices will no longer communicate

                          Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                          Vac le 20 V

                          Method 2AC voltage between earth ground and device chassis ground- the chassis ground of the UC400 needs to be connected to earth ground by some route

                          Note Do not assume that the building frame is a valid earth ground

                          Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                          Vac le 40 V (Must comply with National Electrical Codetradeand local electrical codes)

                          ACC-SVP01B-EN bull BCI-I Integration Guide 17

                          BACnet Data Points and Configuration Property Definitions

                          BACnet Data Points and Configuration Property

                          Definitions

                          The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MSTP This section includes information about

                          bull BACnet protocol implementation conformance statement (PICS)

                          bull Object types descriptions and configuration (refer to Table 2 p 19)

                          bull BACnet protocol data link layers device address binding networking options and character sets

                          bull Object data points and configurations

                          BACnet Protocol Implementation Conformance Statement (PICS)

                          Standardized Device Profile (Annex L)

                          Interoperability Building Blocks (Annex K)

                          Profile Description Supported Profile

                          BACnet Advanced Application Controller (B-AAC)

                          BACnet Application Specific Controller (B-ASC)

                          BACnet Building Controller (B-BC)

                          BACnet Operator Workstation (B-OWS)

                          BACnet Smart Actuator (B-SA)

                          BACnet Smart Sensor (B-SS)

                          Data Sharing Description Supported BIBB

                          Data Sharing-COV-B (DS-COV-B)

                          Data Sharing-ReadProperty-A (DS-RP-A)

                          Data Sharing-ReadProperty-B (DS-RP-B)

                          Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)

                          Data Sharing-WriteProperty-A (DS-WP-A)

                          Data Sharing-WriteProperty-B (DS-WP-B)

                          Data Sharing-WritePropertyMultiple-B (DS-WPM-B)

                          Alarm and Event Management Description Supported BIBB

                          Alarm and Event-ACKI-B (AE-ACK-B)

                          Alarm and Event-Alarm Summary-B (AE-ASUM-B)

                          Alarm and Event-Enrollment Summary-B (AE-ESUM-B)

                          Alarm and Event-Information-B (AE-INFO-B)

                          Alarm and Event-Notification Internal-B (AE-N-I-B)

                          18 ACC-SVP01B-EN bull BCI-I Integration Guide

                          BACnet Data Points and Configuration Property Definitions

                          Segmentation Capability

                          Trending Description Supported BIBB

                          Trending-Automated Trend Retrieval-B (T-ATR-B)

                          Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

                          Device Management Description Supported BIBB

                          Device Management-Backup and Restore-B (DM-BR-B)

                          Device Management-Device Communication Control-B (DM-DCC-B)

                          Device Management-Dynamic Device Binding-A (DM-DDB-A)

                          Device Management-Dynamic Device Binding-B (DM-DDB-B)

                          Device Management-Dynamic Object Binding-B (DM-DOB-B)

                          Device Management-List Manipulation-B (DM-LM-B)

                          Device Management-Object Creation and Deletion-B (DM-OCD-B)

                          Device Management-Private Transfer-A (DM-PT-A)

                          Device Management-Private Transfer-B (DM-PT-B)

                          Device Management-Reinitialize Device-B (DM-RD-B)

                          Device Management-TimeSynchronization-B (DM-TS-B)

                          Segmentation Description Supported Segment

                          Segmented Requests Window Size 1

                          Segmented Responses Window Size 1

                          ACC-SVP01B-EN bull BCI-I Integration Guide 19

                          BACnet Data Points and Configuration Property Definitions

                          Object Types

                          Table 2 Descriptions and configurations

                          Object Type Required Properties Read Properties Written(a) Optional Properties Read

                          Ability to Create

                          Ability to Delete

                          Analog Input

                          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                          bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                          bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                          Yes Yes only user created objects

                          Analog Output

                          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

                          bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                          bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                          Yes Yes only user created objects

                          Analog Value

                          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                          bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                          bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                          Yes Yes only user created objects

                          Binary Input

                          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                          bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                          bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                          Yes Yes only user created objects

                          20 ACC-SVP01B-EN bull BCI-I Integration Guide

                          BACnet Data Points and Configuration Property Definitions

                          Binary Output

                          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

                          bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

                          bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                          Yes Yes only user created objects

                          Binary Value

                          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                          bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                          bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                          Yes Yes only user created objects

                          Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

                          bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

                          bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

                          None None

                          Event Enrollment Object

                          bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

                          bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

                          bull None Yes Yes only user created objects

                          Table 2 Descriptions and configurations (continued)

                          Object Type Required Properties Read Properties Written(a) Optional Properties Read

                          Ability to Create

                          Ability to Delete

                          ACC-SVP01B-EN bull BCI-I Integration Guide 21

                          BACnet Data Points and Configuration Property Definitions

                          Multistate Input

                          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                          bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                          bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                          Yes Yes only user created objects

                          Multistate Output

                          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

                          bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

                          bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                          Yes Yes only user created objects

                          Multistate Value

                          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                          bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                          bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                          Yes Yes only user created objects

                          Notification Class

                          bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

                          bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

                          None Yes Yes only user created objects

                          Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

                          bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

                          bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

                          Yes Yes only user created objects

                          (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

                          Table 2 Descriptions and configurations (continued)

                          Object Type Required Properties Read Properties Written(a) Optional Properties Read

                          Ability to Create

                          Ability to Delete

                          22 ACC-SVP01B-EN bull BCI-I Integration Guide

                          BACnet Data Points and Configuration Property Definitions

                          BACnet Protocol

                          Data Link Layer Options

                          Device Address Binding

                          Networking Options

                          Data Link Layer Description Supported Option

                          ANSIATA 8781 25 Mb ARCNET (Clause 8)

                          ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

                          BACnet IP (Annex J)

                          BACnet IP (Annex J) Foreign Device

                          ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

                          LonTalk (Clause 11) Medium

                          MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

                          MSTP Slave (Clause 9) Baud Rate(s)

                          Other

                          Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

                          Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

                          Device Address Binding Supported

                          Static Device Binding Supported

                          Networking DescriptionsSupported

                          Option

                          Annex H BACnet Tunneling

                          BACnetIP Broadcast Management Device (BBMD)

                          Does the BBMD Support Registrations by Foreign Devices

                          Router

                          ACC-SVP01B-EN bull BCI-I Integration Guide 23

                          BACnet Data Points and Configuration Property Definitions

                          Character Sets

                          Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

                          Character Set Descriptions Supported

                          ANSI X34

                          IBMMicrosoft DBCS

                          ISO 10646 (UCS-4)

                          ISO 10646 (UCS2)

                          ISO 8859-1

                          JIS C 6226

                          24 ACC-SVP01B-EN bull BCI-I Integration Guide

                          Object Data Points and Diagnostic Data Points

                          Object Data Points and Diagnostic Data Points

                          For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

                          Table 3 Analog Output

                          Object Identifier Object Name Description Units Valid Range

                          Refresh Rate

                          (Sec)

                          Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

                          Percent (98) 0 to 100 NA

                          Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

                          Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

                          Degrees-Fahrenheit (64) 500 to 900 NA

                          Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

                          BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

                          Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

                          Degrees-Fahrenheit (64) 400 to 900 NA

                          Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

                          Degrees-Fahrenheit (64) 400 to 1800 NA

                          Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

                          070 to 510 (Ipak II) NA

                          Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

                          003 to 030-002 to 030 (enhanced StatiTrac)

                          NA

                          Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

                          -028 to 050-067 to 067 (enhanced StatiTrac)

                          900

                          Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                          Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                          Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

                          00 to 79 (Ipak II) 900

                          Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                          Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

                          Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

                          Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

                          Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

                          Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

                          Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

                          Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

                          Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

                          Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

                          ACC-SVP01B-EN bull BCI-I Integration Guide 25

                          Object Data Points and Diagnostic Data Points

                          Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                          Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                          Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                          Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                          Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                          Cooling temperature setpoint used for control in unoccupied mode

                          Degrees-Fahrenheit (64) 520 to 880 NA

                          Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                          Heating temperature setpoint used for control in unoccupied mode

                          Degrees-Fahrenheit (64) 500 to 900 NA

                          Table 4 Analog Input

                          Object Identifier Object Name Description Units (Listed Are Defaults)

                          Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                          Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                          Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                          Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                          Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                          Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                          Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                          Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                          Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                          Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                          Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                          Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                          Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                          Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                          Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                          Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                          Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                          Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                          Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                          Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                          Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                          Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                          Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                          Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                          Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                          Table 3 Analog Output (continued)

                          Object Identifier Object Name Description Units Valid Range

                          Refresh Rate

                          (Sec)

                          26 ACC-SVP01B-EN bull BCI-I Integration Guide

                          Object Data Points and Diagnostic Data Points

                          Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                          Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                          Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                          Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                          Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                          Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                          Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                          Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                          Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                          Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                          Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                          Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                          Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                          Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                          Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                          Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                          Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                          Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                          Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                          Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                          Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                          Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                          Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                          Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                          The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                          Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                          The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                          Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                          Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                          Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                          Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                          Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                          Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                          Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                          Table 4 Analog Input (continued)

                          Object Identifier Object Name Description Units (Listed Are Defaults)

                          ACC-SVP01B-EN bull BCI-I Integration Guide 27

                          Object Data Points and Diagnostic Data Points

                          Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                          Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                          Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                          Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                          The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                          Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                          Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                          Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                          Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                          Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                          Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                          Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                          Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                          Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                          Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                          Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                          Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                          Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                          Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                          Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                          Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                          Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                          Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                          Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                          Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                          Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                          Table 5 Analog Value

                          Object Identifier Object Name Description Units Valid Range

                          Analog Value 1 Filter Runtime Hours Setpoint

                          The setpoint value used by the filter run hours calculation

                          Hours (71) 0 to 10000

                          Table 4 Analog Input (continued)

                          Object Identifier Object Name Description Units (Listed Are Defaults)

                          28 ACC-SVP01B-EN bull BCI-I Integration Guide

                          Object Data Points and Diagnostic Data Points

                          Table 6 Multistate Output

                          BCI-I Object Identifier Object Name Description Object States

                          Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                          Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                          1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                          Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                          Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                          1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                          Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                          1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                          Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                          1 = Flow2 = No Flow3 = Auto

                          Table 7 Multistate Input

                          BCI-I Object Identifier Object Name Description Object States

                          Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                          1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                          Multi-State Input 9 Economizer Type General description of the equipment economizer system

                          1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                          Multi-State Input 10 Condenser Type General description of the equipment condenser system

                          1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                          Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                          1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                          ACC-SVP01B-EN bull BCI-I Integration Guide 29

                          Object Data Points and Diagnostic Data Points

                          Multi-State Input 15 Economizer Decision Method

                          Unit method to determine when the economizer system is enabled

                          1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                          Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                          Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                          Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                          1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                          Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                          1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                          Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                          1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                          Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                          1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                          Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                          1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                          Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                          1 = Idle2 = On3 = Cancel

                          Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                          1 = Off2 = On3 = Not Present

                          Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                          1 = Off2 = On3 = Not Present

                          Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                          1 = Off2 = On3 = Not Present

                          Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                          1 = Off|2 = On3 = Not Present

                          Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                          1 = Off2 = On3 = Not Present

                          Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                          1 = Off2 = On3 = Not Present

                          Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                          1 = Off2 = On3 = Not Present

                          Table 7 Multistate Input (continued)

                          BCI-I Object Identifier Object Name Description Object States

                          30 ACC-SVP01B-EN bull BCI-I Integration Guide

                          Object Data Points and Diagnostic Data Points

                          Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                          1 = Off2 = On3 = Not Present

                          Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                          1 = Off2 = On3 = Not Present

                          Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                          Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                          Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                          Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                          Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                          1 = Off2 = On3 = Not Present

                          Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                          1= Off2= On3= Not Present

                          Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                          Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                          Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                          Multi-State Input 43 Outdoor Air Damper Status

                          Indicates the operating state of the outdoor damper

                          1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                          Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                          1 = Disabled2 = Enabled3 = Not Present

                          Table 8 Binary Output

                          Object Identifier Object Name DescriptionRelinquish Default Object States

                          Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                          Active = BAS Control

                          Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                          Active = Heating Locked Out

                          Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                          Active = Cooling Locked Out

                          Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                          Active = Enabled

                          Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                          Active = On

                          Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                          Inactive Inactive = DisabledActive = Enabled

                          Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                          Active = Reset

                          Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                          Active = Reset

                          Table 7 Multistate Input (continued)

                          BCI-I Object Identifier Object Name Description Object States

                          ACC-SVP01B-EN bull BCI-I Integration Guide 31

                          Object Data Points and Diagnostic Data Points

                          Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                          Active = Auto

                          Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                          Active = Auto

                          Table 9 Binary Input

                          Object Identifier Object Name Description Object States

                          Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                          Inactive = Standalone controlActive = BAS control

                          Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                          Inactive = NormalActive = Locked Out

                          Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                          Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                          Inactive = AutoActive = Open

                          Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                          Inactive = InactiveActive = Active

                          Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                          Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                          Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                          Inactive = DisabledActive = Enabled

                          Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                          Inactive = DisabledActive = Enabled

                          Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                          Inactive = InactiveActive = Active

                          Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                          Inactive = No FlowActive = Flow

                          Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                          Inactive = InactiveActive = Active

                          Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                          Inactive = InactiveActive = Active

                          Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                          Inactive = InactiveActive = Active

                          Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                          The status of evaporator frost protection function for circuit 1

                          Inactive = InactiveActive = Active

                          Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                          The status of evaporator frost protection function for circuit 2

                          Inactive = InactiveActive = Active

                          Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                          The status of evaporator frost protection function for circuit 3

                          Inactive = InactiveActive = Active

                          Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                          The status of evaporator frost protection function for circuit 4

                          Inactive = InactiveActive = Active

                          Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                          Inactive = De-energizedActive = Energized

                          Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                          Inactive = InactiveActive = Active

                          Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                          Inactive = ClosedActive = Open

                          Table 10 Diagnostics Binary Input

                          Object Identifier(a) Object Name Description

                          Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                          Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                          Binary Input 31 (use Object Identifier for RT or CSC)

                          Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                          Binary Input 31 (use Object Identifier for FAU)

                          Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                          Table 8 Binary Output

                          Object Identifier Object Name DescriptionRelinquish Default Object States

                          32 ACC-SVP01B-EN bull BCI-I Integration Guide

                          Object Data Points and Diagnostic Data Points

                          Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                          Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                          Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                          Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                          Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                          Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                          Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                          Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                          Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                          Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                          Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                          Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                          Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                          Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                          Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                          Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                          Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                          Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                          Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                          Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                          Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                          Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                          Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                          Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                          Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                          Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                          Binary Input 58 (use Object Identifier for RT or CSC)

                          Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                          Binary Input 58 (use Object Identifier for FAU)

                          Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                          Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                          Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                          Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                          Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                          Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                          Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                          Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                          Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                          Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                          Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                          Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                          Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                          Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                          Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                          Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                          Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                          Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                          Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                          Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                          Table 10 Diagnostics Binary Input (continued)

                          Object Identifier(a) Object Name Description

                          ACC-SVP01B-EN bull BCI-I Integration Guide 33

                          Object Data Points and Diagnostic Data Points

                          Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                          Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                          Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                          Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                          Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                          Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                          Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                          Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                          Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                          Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                          Binary Input 86 (use Object Identifier for RT I-pak II)

                          Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                          Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                          Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                          Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                          Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                          Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                          Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                          Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                          Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                          Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                          Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                          Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                          Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                          Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                          Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                          Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                          Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                          Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                          Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                          Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                          Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                          Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                          Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                          Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                          Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                          Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                          Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                          Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                          Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                          Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                          Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                          Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                          Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                          Binary Input 121 (use Object Identifier for RT)

                          Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                          Binary Input 121 (use Object Identifier for FAU)

                          Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                          Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                          Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                          Table 10 Diagnostics Binary Input (continued)

                          Object Identifier(a) Object Name Description

                          34 ACC-SVP01B-EN bull BCI-I Integration Guide

                          Object Data Points and Diagnostic Data Points

                          Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                          Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                          Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                          Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                          Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                          Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                          Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                          Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                          Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                          Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                          Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                          Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                          Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                          Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                          Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                          Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                          Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                          Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                          Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                          Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                          Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                          Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                          Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                          Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                          Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                          Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                          (a) Object States Inactive = normal and Active = foreign language specific

                          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                          Object Identifier(a) Object Name Description

                          Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                          Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                          Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                          Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                          Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                          Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                          Multi-State Input 10 Condenser Type General description of the equipment condenser system

                          Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                          Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                          Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                          Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                          Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                          Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                          Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                          Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                          Table 10 Diagnostics Binary Input (continued)

                          Object Identifier(a) Object Name Description

                          ACC-SVP01B-EN bull BCI-I Integration Guide 35

                          Object Data Points and Diagnostic Data Points

                          Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                          Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                          Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                          Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                          Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                          Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                          Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                          Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                          Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                          Analog Input 81 Cool Type Describes the cooling type installed in the unit

                          Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                          Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                          Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                          Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                          Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                          Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                          Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                          Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                          Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                          Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                          Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                          Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                          Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                          Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                          Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                          Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                          Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                          Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                          Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                          Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                          Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                          Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                          Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                          Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                          Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                          Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                          Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                          Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                          Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                          Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                          Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                          Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                          Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                          Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                          Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                          Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                          Object Identifier(a) Object Name Description

                          36 ACC-SVP01B-EN bull BCI-I Integration Guide

                          Object Data Points and Diagnostic Data Points

                          Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                          Multi-State Input 9 Economizer Type General description of the equipment economizer system

                          Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                          Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                          Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                          Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                          Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                          Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                          Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                          Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                          Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                          Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                          Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                          Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                          Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                          Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                          Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                          Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                          Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                          Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                          Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                          Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                          Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                          Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                          Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                          Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                          Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                          Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                          Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                          Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                          Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                          Multi-State Input 36 Final Filter Status Indicates the final filter media state

                          Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                          Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                          Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                          Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                          Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                          Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                          Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                          Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                          Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                          Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                          Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                          Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                          Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                          Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                          Object Identifier(a) Object Name Description

                          ACC-SVP01B-EN bull BCI-I Integration Guide 37

                          Object Data Points and Diagnostic Data Points

                          Binary Output 16 Humidification Command Command the operating state of the humidification system

                          NC 3 HVAC-Advisory HVAC-Advisory

                          NC 1 HVAC-Critical HVAC-Critical

                          NC 4 HVAC-Information HVAC-Information

                          NC 2 HVAC-Service Required HVAC-Service Required

                          Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                          Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                          Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                          Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                          Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                          Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                          Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                          Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                          Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                          Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                          Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                          Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                          Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                          Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                          Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                          Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                          Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                          Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                          Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                          Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                          Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                          Analog Input 82 Preheat Type Describes the heating type installed in the unit

                          Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                          Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                          Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                          Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                          Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                          Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                          Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                          Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                          Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                          Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                          Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                          Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                          Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                          Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                          Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                          Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                          Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                          Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                          Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                          Object Identifier(a) Object Name Description

                          38 ACC-SVP01B-EN bull BCI-I Integration Guide

                          Object Data Points and Diagnostic Data Points

                          Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                          Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                          Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                          Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                          Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                          Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                          Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                          Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                          Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                          Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                          Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                          Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                          Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                          Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                          Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                          Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                          Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                          Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                          Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                          Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                          Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                          Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                          Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                          Binary Input 3 Unit Status Indicates the current state of the unit

                          Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                          Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                          Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                          Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                          Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                          Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                          Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                          (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                          Object Identifier(a) Object Name Description

                          Table 12 Diagnostic Objects Sorted by Object Name

                          Object Identifier(a) Object Name ValueRange Description

                          BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                          BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                          ACC-SVP01B-EN bull BCI-I Integration Guide 39

                          Object Data Points and Diagnostic Data Points

                          BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                          BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                          BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                          BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                          BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                          BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                          BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                          BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                          BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                          BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                          BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                          BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                          BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                          BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                          BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                          BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                          BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                          BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                          BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                          BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                          BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                          BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                          BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                          BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                          BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                          BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                          BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                          BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                          BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                          Object Identifier(a) Object Name ValueRange Description

                          40 ACC-SVP01B-EN bull BCI-I Integration Guide

                          Object Data Points and Diagnostic Data Points

                          BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                          BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                          BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                          BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                          BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                          BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                          BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                          BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                          BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                          BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                          BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                          BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                          BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                          BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                          BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                          BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                          BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                          BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                          BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                          BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                          BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                          BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                          BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                          BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                          BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                          BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                          BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                          BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                          BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                          Object Identifier(a) Object Name ValueRange Description

                          ACC-SVP01B-EN bull BCI-I Integration Guide 41

                          Object Data Points and Diagnostic Data Points

                          BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                          BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                          BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                          BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                          BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                          BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                          BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                          BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                          BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                          BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                          BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                          BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                          BI 121 (use Object Identifier for RT)

                          Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                          BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                          BI 58 (use Object Identifier for RT or CSC)

                          Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                          BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                          BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                          BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                          BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                          BI 31 (use Object Identifier for RT CSC)

                          Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                          BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                          BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                          BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                          BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                          BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                          BI 121 (use Object Identifier for FAU)

                          Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                          B1 31 (use Object Identifier for FAU)

                          Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                          BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                          BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                          Object Identifier(a) Object Name ValueRange Description

                          42 ACC-SVP01B-EN bull BCI-I Integration Guide

                          Object Data Points and Diagnostic Data Points

                          BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                          BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                          BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                          BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                          BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                          BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                          BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                          BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                          BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                          BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                          BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                          BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                          BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                          BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                          BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                          BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                          BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                          BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                          BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                          BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                          BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                          BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                          BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                          1 = active Diagnostic Vel Press Sensor (Rear)

                          BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                          Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                          BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                          BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                          BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                          BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                          BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                          Object Identifier(a) Object Name ValueRange Description

                          ACC-SVP01B-EN bull BCI-I Integration Guide 43

                          Object Data Points and Diagnostic Data Points

                          BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                          BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                          BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                          BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                          BI 58 (use Object Identifier for FAU)

                          Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                          (a) BI=Binary Input

                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                          Object Identifier(a) Object Name ValueRange Description

                          44 ACC-SVP01B-EN bull BCI-I Integration Guide

                          Additional Resources

                          Additional Resources

                          Use the following documents and links as additional resources

                          bull Product support online

                          bull wwwbacnetorg

                          bull wwwbacnetassociationorg

                          bull wwwashraeorg

                          bull Tracer TU Help online

                          bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                          bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                          Note For further assistance contact your local Trane sales office

                          ACC-SVP01B-EN bull BCI-I Integration Guide 45

                          Glossary

                          A

                          ASHRAE

                          See American Society of Heating Refrigeration and Air-conditioning Engineers

                          American Society of Heating Refrigeration and Air-

                          conditioning Engineers

                          An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                          BBACnettrade

                          See Building Automation Control network

                          BACnet interoperability building blocks

                          A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                          BACnet object

                          An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                          baud rate

                          The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                          BIBB

                          See BACnet interoperability building blocks

                          Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                          advocates BACnet protocol for use in system-level control devices

                          device

                          A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                          Device ID

                          The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                          Iinteroperability

                          The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                          Pprotocol

                          A set of rules (language) that governs the exchange of data over a digital communications system

                          S

                          stand-alone operation

                          Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                          wwwtranecom

                          For more information contact your local Trane office or e-mail us at comforttranecom

                          Literature Order Number ACC-SVP01B-EN

                          Date September 2009

                          Supersedes ACC-SVP01A-EN

                          Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                          • Table of Contents
                          • Overview
                          • Ordering Numbers
                          • BACnet Protocol
                          • BCI-I Configuration
                            • Overview
                            • Starting a Session of Tracer TU and Direct Connection
                            • Reset to Factory Default
                            • IP Units Configuration
                            • BACnet Object Configuration
                            • Change Baud Rate
                            • Change Device ID
                            • Stand-alone or BAS Operation
                              • IntelliPak Control Configuration
                              • BAS Unit Control
                              • Periodic Update of BAS Values
                              • BAS Communication Failure
                                • InputOutput Commands and Calculations
                                  • System Control Command
                                  • Filter Timer Reset Command
                                  • Diagnostics Reset Command
                                  • Setpoint Calculations
                                  • Timestamp Configuration
                                      • BCI IntelliPak Rotary Switches and LEDs
                                        • Rotary Switches
                                        • LEDs Description Behavior and Troubleshooting
                                        • 24 Vac Measurement
                                        • Ground Measurements
                                          • BACnet Data Points and Configuration Property Definitions
                                            • BACnet Protocol Implementation Conformance Statement (PICS)
                                              • Standardized Device Profile (Annex L)
                                              • Interoperability Building Blocks (Annex K)
                                              • Segmentation Capability
                                              • Object Types
                                                • BACnet Protocol
                                                  • Data Link Layer Options
                                                  • Device Address Binding
                                                  • Networking Options
                                                  • Character Sets
                                                      • Object Data Points and Diagnostic Data Points
                                                      • Additional Resources
                                                      • Glossary

                            14 ACC-SVP01B-EN bull BCI-I Integration Guide

                            BCI IntelliPak Rotary Switches and LEDs

                            Link and IMC

                            TX blinks greenBlinks at the data transfer rate when the unit transfers data to other devices on the link

                            TX LED Regardless of connectivity or not this LED will constantly blink as it continually looks for devices to communicate to

                            LED not litDetermine if for example a Tracer SC or BACnet device is trying to talk to the controller or if it is capable of talking to the controller Also determine if the communication status shows down all of the time

                            Refer to ldquoGround Measurementsrdquo p 16 for a check-out procedure

                            RX blinks yellow

                            Blinks at the data transfer rate when the unit receives data from other devices on the link

                            bull ON solid yellow indicates there is reverse polarity

                            LED not lit

                            Indicates that the controller is not detecting communication

                            bull Not lit cycle the power to reestablish communication

                            Service

                            Shows solid greenIndicates someone is pressing this LED or the controller is not operating normally

                            Press and hold during power up to place controller into boot code or press and hold for a count of approximately 10 seconds to clear the Device ID

                            What is Boot Code When the UC400 is placed into boot code the system will not run any applications such as trending scheduling and TGP2 runtime

                            Blinks green

                            Indicates controllers is not accessing application software

                            bull Restore using TU service tool

                            LED not lit Indicates controller is operating normally

                            Binary 01 to Binary 09 Not Used

                            Table 1 LED Activities and Troubleshooting Tips

                            LED Name ActivitiesIndication or Troubleshooting

                            Tip (Denoted in Bullets) Notes

                            ACC-SVP01B-EN bull BCI-I Integration Guide 15

                            BCI IntelliPak Rotary Switches and LEDs

                            24 Vac Measurement

                            General Information Checkout Procedure Measurement Expected Value

                            Checking the voltage that is powering the UC400 is often a necessary step when commissioning or troubleshooting Operational issues and LED operation may result in a need to measure the input power

                            When troubleshooting it is faster to take measurements while the load is in place If Step 1 indicates an out-of-specification voltage disconnect the UC400 and measure the AC voltage across the transformer These measurements can direct the technician towards the problem source

                            Step 1

                            Measure AC voltage with the UC400 connected Perform this measurement while the unit is under load

                            200 Vac le Vac le 300 Vac

                            Step 2

                            Measure AC voltage with the UC400 unconnected Perform this measurement while the unit is not under load

                            200 Vac le Vac le 300 Vac

                            16 ACC-SVP01B-EN bull BCI-I Integration Guide

                            BCI IntelliPak Rotary Switches and LEDs

                            Ground Measurements

                            General Information and Checkout Procedure Measurement Expected Value

                            Method 1AC voltage between shield conductors and device chassis ground- the voltage difference between BACnet MSTP device chassis ground connections should be close to zero If the voltage difference is greater that 40 Vac there will be marginal communication or intermittent communication problems If the voltage difference is greater that 70 Vac some devices will no longer communicate

                            Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                            Vac le 20 V

                            Method 2AC voltage between earth ground and device chassis ground- the chassis ground of the UC400 needs to be connected to earth ground by some route

                            Note Do not assume that the building frame is a valid earth ground

                            Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                            Vac le 40 V (Must comply with National Electrical Codetradeand local electrical codes)

                            ACC-SVP01B-EN bull BCI-I Integration Guide 17

                            BACnet Data Points and Configuration Property Definitions

                            BACnet Data Points and Configuration Property

                            Definitions

                            The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MSTP This section includes information about

                            bull BACnet protocol implementation conformance statement (PICS)

                            bull Object types descriptions and configuration (refer to Table 2 p 19)

                            bull BACnet protocol data link layers device address binding networking options and character sets

                            bull Object data points and configurations

                            BACnet Protocol Implementation Conformance Statement (PICS)

                            Standardized Device Profile (Annex L)

                            Interoperability Building Blocks (Annex K)

                            Profile Description Supported Profile

                            BACnet Advanced Application Controller (B-AAC)

                            BACnet Application Specific Controller (B-ASC)

                            BACnet Building Controller (B-BC)

                            BACnet Operator Workstation (B-OWS)

                            BACnet Smart Actuator (B-SA)

                            BACnet Smart Sensor (B-SS)

                            Data Sharing Description Supported BIBB

                            Data Sharing-COV-B (DS-COV-B)

                            Data Sharing-ReadProperty-A (DS-RP-A)

                            Data Sharing-ReadProperty-B (DS-RP-B)

                            Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)

                            Data Sharing-WriteProperty-A (DS-WP-A)

                            Data Sharing-WriteProperty-B (DS-WP-B)

                            Data Sharing-WritePropertyMultiple-B (DS-WPM-B)

                            Alarm and Event Management Description Supported BIBB

                            Alarm and Event-ACKI-B (AE-ACK-B)

                            Alarm and Event-Alarm Summary-B (AE-ASUM-B)

                            Alarm and Event-Enrollment Summary-B (AE-ESUM-B)

                            Alarm and Event-Information-B (AE-INFO-B)

                            Alarm and Event-Notification Internal-B (AE-N-I-B)

                            18 ACC-SVP01B-EN bull BCI-I Integration Guide

                            BACnet Data Points and Configuration Property Definitions

                            Segmentation Capability

                            Trending Description Supported BIBB

                            Trending-Automated Trend Retrieval-B (T-ATR-B)

                            Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

                            Device Management Description Supported BIBB

                            Device Management-Backup and Restore-B (DM-BR-B)

                            Device Management-Device Communication Control-B (DM-DCC-B)

                            Device Management-Dynamic Device Binding-A (DM-DDB-A)

                            Device Management-Dynamic Device Binding-B (DM-DDB-B)

                            Device Management-Dynamic Object Binding-B (DM-DOB-B)

                            Device Management-List Manipulation-B (DM-LM-B)

                            Device Management-Object Creation and Deletion-B (DM-OCD-B)

                            Device Management-Private Transfer-A (DM-PT-A)

                            Device Management-Private Transfer-B (DM-PT-B)

                            Device Management-Reinitialize Device-B (DM-RD-B)

                            Device Management-TimeSynchronization-B (DM-TS-B)

                            Segmentation Description Supported Segment

                            Segmented Requests Window Size 1

                            Segmented Responses Window Size 1

                            ACC-SVP01B-EN bull BCI-I Integration Guide 19

                            BACnet Data Points and Configuration Property Definitions

                            Object Types

                            Table 2 Descriptions and configurations

                            Object Type Required Properties Read Properties Written(a) Optional Properties Read

                            Ability to Create

                            Ability to Delete

                            Analog Input

                            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                            bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                            bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                            Yes Yes only user created objects

                            Analog Output

                            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

                            bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                            bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                            Yes Yes only user created objects

                            Analog Value

                            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                            bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                            bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                            Yes Yes only user created objects

                            Binary Input

                            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                            bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                            bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                            Yes Yes only user created objects

                            20 ACC-SVP01B-EN bull BCI-I Integration Guide

                            BACnet Data Points and Configuration Property Definitions

                            Binary Output

                            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

                            bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

                            bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                            Yes Yes only user created objects

                            Binary Value

                            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                            bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                            bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                            Yes Yes only user created objects

                            Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

                            bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

                            bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

                            None None

                            Event Enrollment Object

                            bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

                            bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

                            bull None Yes Yes only user created objects

                            Table 2 Descriptions and configurations (continued)

                            Object Type Required Properties Read Properties Written(a) Optional Properties Read

                            Ability to Create

                            Ability to Delete

                            ACC-SVP01B-EN bull BCI-I Integration Guide 21

                            BACnet Data Points and Configuration Property Definitions

                            Multistate Input

                            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                            bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                            bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                            Yes Yes only user created objects

                            Multistate Output

                            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

                            bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

                            bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                            Yes Yes only user created objects

                            Multistate Value

                            bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                            bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                            bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                            Yes Yes only user created objects

                            Notification Class

                            bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

                            bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

                            None Yes Yes only user created objects

                            Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

                            bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

                            bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

                            Yes Yes only user created objects

                            (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

                            Table 2 Descriptions and configurations (continued)

                            Object Type Required Properties Read Properties Written(a) Optional Properties Read

                            Ability to Create

                            Ability to Delete

                            22 ACC-SVP01B-EN bull BCI-I Integration Guide

                            BACnet Data Points and Configuration Property Definitions

                            BACnet Protocol

                            Data Link Layer Options

                            Device Address Binding

                            Networking Options

                            Data Link Layer Description Supported Option

                            ANSIATA 8781 25 Mb ARCNET (Clause 8)

                            ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

                            BACnet IP (Annex J)

                            BACnet IP (Annex J) Foreign Device

                            ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

                            LonTalk (Clause 11) Medium

                            MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

                            MSTP Slave (Clause 9) Baud Rate(s)

                            Other

                            Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

                            Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

                            Device Address Binding Supported

                            Static Device Binding Supported

                            Networking DescriptionsSupported

                            Option

                            Annex H BACnet Tunneling

                            BACnetIP Broadcast Management Device (BBMD)

                            Does the BBMD Support Registrations by Foreign Devices

                            Router

                            ACC-SVP01B-EN bull BCI-I Integration Guide 23

                            BACnet Data Points and Configuration Property Definitions

                            Character Sets

                            Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

                            Character Set Descriptions Supported

                            ANSI X34

                            IBMMicrosoft DBCS

                            ISO 10646 (UCS-4)

                            ISO 10646 (UCS2)

                            ISO 8859-1

                            JIS C 6226

                            24 ACC-SVP01B-EN bull BCI-I Integration Guide

                            Object Data Points and Diagnostic Data Points

                            Object Data Points and Diagnostic Data Points

                            For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

                            Table 3 Analog Output

                            Object Identifier Object Name Description Units Valid Range

                            Refresh Rate

                            (Sec)

                            Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

                            Percent (98) 0 to 100 NA

                            Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

                            Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

                            Degrees-Fahrenheit (64) 500 to 900 NA

                            Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

                            BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

                            Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

                            Degrees-Fahrenheit (64) 400 to 900 NA

                            Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

                            Degrees-Fahrenheit (64) 400 to 1800 NA

                            Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

                            070 to 510 (Ipak II) NA

                            Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

                            003 to 030-002 to 030 (enhanced StatiTrac)

                            NA

                            Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

                            -028 to 050-067 to 067 (enhanced StatiTrac)

                            900

                            Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                            Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                            Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

                            00 to 79 (Ipak II) 900

                            Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                            Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

                            Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

                            Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

                            Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

                            Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

                            Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

                            Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

                            Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

                            Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

                            ACC-SVP01B-EN bull BCI-I Integration Guide 25

                            Object Data Points and Diagnostic Data Points

                            Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                            Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                            Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                            Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                            Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                            Cooling temperature setpoint used for control in unoccupied mode

                            Degrees-Fahrenheit (64) 520 to 880 NA

                            Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                            Heating temperature setpoint used for control in unoccupied mode

                            Degrees-Fahrenheit (64) 500 to 900 NA

                            Table 4 Analog Input

                            Object Identifier Object Name Description Units (Listed Are Defaults)

                            Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                            Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                            Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                            Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                            Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                            Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                            Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                            Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                            Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                            Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                            Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                            Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                            Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                            Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                            Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                            Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                            Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                            Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                            Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                            Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                            Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                            Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                            Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                            Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                            Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                            Table 3 Analog Output (continued)

                            Object Identifier Object Name Description Units Valid Range

                            Refresh Rate

                            (Sec)

                            26 ACC-SVP01B-EN bull BCI-I Integration Guide

                            Object Data Points and Diagnostic Data Points

                            Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                            Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                            Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                            Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                            Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                            Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                            Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                            Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                            Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                            Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                            Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                            Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                            Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                            Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                            Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                            Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                            Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                            Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                            Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                            Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                            Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                            Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                            Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                            Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                            The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                            Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                            The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                            Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                            Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                            Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                            Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                            Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                            Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                            Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                            Table 4 Analog Input (continued)

                            Object Identifier Object Name Description Units (Listed Are Defaults)

                            ACC-SVP01B-EN bull BCI-I Integration Guide 27

                            Object Data Points and Diagnostic Data Points

                            Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                            Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                            Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                            Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                            The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                            Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                            Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                            Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                            Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                            Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                            Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                            Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                            Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                            Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                            Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                            Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                            Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                            Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                            Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                            Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                            Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                            Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                            Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                            Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                            Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                            Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                            Table 5 Analog Value

                            Object Identifier Object Name Description Units Valid Range

                            Analog Value 1 Filter Runtime Hours Setpoint

                            The setpoint value used by the filter run hours calculation

                            Hours (71) 0 to 10000

                            Table 4 Analog Input (continued)

                            Object Identifier Object Name Description Units (Listed Are Defaults)

                            28 ACC-SVP01B-EN bull BCI-I Integration Guide

                            Object Data Points and Diagnostic Data Points

                            Table 6 Multistate Output

                            BCI-I Object Identifier Object Name Description Object States

                            Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                            Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                            1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                            Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                            Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                            1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                            Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                            1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                            Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                            1 = Flow2 = No Flow3 = Auto

                            Table 7 Multistate Input

                            BCI-I Object Identifier Object Name Description Object States

                            Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                            1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                            Multi-State Input 9 Economizer Type General description of the equipment economizer system

                            1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                            Multi-State Input 10 Condenser Type General description of the equipment condenser system

                            1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                            Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                            1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                            ACC-SVP01B-EN bull BCI-I Integration Guide 29

                            Object Data Points and Diagnostic Data Points

                            Multi-State Input 15 Economizer Decision Method

                            Unit method to determine when the economizer system is enabled

                            1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                            Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                            Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                            Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                            1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                            Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                            1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                            Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                            1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                            Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                            1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                            Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                            1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                            Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                            1 = Idle2 = On3 = Cancel

                            Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                            1 = Off2 = On3 = Not Present

                            Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                            1 = Off2 = On3 = Not Present

                            Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                            1 = Off2 = On3 = Not Present

                            Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                            1 = Off|2 = On3 = Not Present

                            Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                            1 = Off2 = On3 = Not Present

                            Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                            1 = Off2 = On3 = Not Present

                            Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                            1 = Off2 = On3 = Not Present

                            Table 7 Multistate Input (continued)

                            BCI-I Object Identifier Object Name Description Object States

                            30 ACC-SVP01B-EN bull BCI-I Integration Guide

                            Object Data Points and Diagnostic Data Points

                            Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                            1 = Off2 = On3 = Not Present

                            Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                            1 = Off2 = On3 = Not Present

                            Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                            Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                            Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                            Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                            Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                            1 = Off2 = On3 = Not Present

                            Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                            1= Off2= On3= Not Present

                            Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                            Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                            Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                            Multi-State Input 43 Outdoor Air Damper Status

                            Indicates the operating state of the outdoor damper

                            1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                            Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                            1 = Disabled2 = Enabled3 = Not Present

                            Table 8 Binary Output

                            Object Identifier Object Name DescriptionRelinquish Default Object States

                            Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                            Active = BAS Control

                            Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                            Active = Heating Locked Out

                            Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                            Active = Cooling Locked Out

                            Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                            Active = Enabled

                            Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                            Active = On

                            Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                            Inactive Inactive = DisabledActive = Enabled

                            Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                            Active = Reset

                            Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                            Active = Reset

                            Table 7 Multistate Input (continued)

                            BCI-I Object Identifier Object Name Description Object States

                            ACC-SVP01B-EN bull BCI-I Integration Guide 31

                            Object Data Points and Diagnostic Data Points

                            Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                            Active = Auto

                            Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                            Active = Auto

                            Table 9 Binary Input

                            Object Identifier Object Name Description Object States

                            Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                            Inactive = Standalone controlActive = BAS control

                            Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                            Inactive = NormalActive = Locked Out

                            Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                            Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                            Inactive = AutoActive = Open

                            Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                            Inactive = InactiveActive = Active

                            Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                            Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                            Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                            Inactive = DisabledActive = Enabled

                            Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                            Inactive = DisabledActive = Enabled

                            Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                            Inactive = InactiveActive = Active

                            Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                            Inactive = No FlowActive = Flow

                            Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                            Inactive = InactiveActive = Active

                            Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                            Inactive = InactiveActive = Active

                            Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                            Inactive = InactiveActive = Active

                            Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                            The status of evaporator frost protection function for circuit 1

                            Inactive = InactiveActive = Active

                            Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                            The status of evaporator frost protection function for circuit 2

                            Inactive = InactiveActive = Active

                            Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                            The status of evaporator frost protection function for circuit 3

                            Inactive = InactiveActive = Active

                            Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                            The status of evaporator frost protection function for circuit 4

                            Inactive = InactiveActive = Active

                            Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                            Inactive = De-energizedActive = Energized

                            Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                            Inactive = InactiveActive = Active

                            Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                            Inactive = ClosedActive = Open

                            Table 10 Diagnostics Binary Input

                            Object Identifier(a) Object Name Description

                            Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                            Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                            Binary Input 31 (use Object Identifier for RT or CSC)

                            Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                            Binary Input 31 (use Object Identifier for FAU)

                            Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                            Table 8 Binary Output

                            Object Identifier Object Name DescriptionRelinquish Default Object States

                            32 ACC-SVP01B-EN bull BCI-I Integration Guide

                            Object Data Points and Diagnostic Data Points

                            Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                            Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                            Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                            Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                            Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                            Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                            Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                            Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                            Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                            Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                            Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                            Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                            Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                            Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                            Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                            Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                            Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                            Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                            Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                            Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                            Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                            Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                            Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                            Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                            Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                            Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                            Binary Input 58 (use Object Identifier for RT or CSC)

                            Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                            Binary Input 58 (use Object Identifier for FAU)

                            Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                            Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                            Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                            Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                            Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                            Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                            Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                            Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                            Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                            Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                            Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                            Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                            Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                            Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                            Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                            Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                            Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                            Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                            Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                            Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                            Table 10 Diagnostics Binary Input (continued)

                            Object Identifier(a) Object Name Description

                            ACC-SVP01B-EN bull BCI-I Integration Guide 33

                            Object Data Points and Diagnostic Data Points

                            Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                            Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                            Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                            Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                            Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                            Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                            Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                            Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                            Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                            Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                            Binary Input 86 (use Object Identifier for RT I-pak II)

                            Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                            Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                            Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                            Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                            Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                            Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                            Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                            Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                            Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                            Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                            Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                            Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                            Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                            Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                            Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                            Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                            Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                            Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                            Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                            Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                            Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                            Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                            Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                            Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                            Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                            Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                            Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                            Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                            Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                            Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                            Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                            Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                            Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                            Binary Input 121 (use Object Identifier for RT)

                            Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                            Binary Input 121 (use Object Identifier for FAU)

                            Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                            Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                            Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                            Table 10 Diagnostics Binary Input (continued)

                            Object Identifier(a) Object Name Description

                            34 ACC-SVP01B-EN bull BCI-I Integration Guide

                            Object Data Points and Diagnostic Data Points

                            Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                            Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                            Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                            Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                            Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                            Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                            Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                            Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                            Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                            Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                            Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                            Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                            Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                            Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                            Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                            Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                            Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                            Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                            Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                            Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                            Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                            Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                            Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                            Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                            Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                            Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                            (a) Object States Inactive = normal and Active = foreign language specific

                            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                            Object Identifier(a) Object Name Description

                            Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                            Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                            Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                            Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                            Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                            Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                            Multi-State Input 10 Condenser Type General description of the equipment condenser system

                            Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                            Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                            Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                            Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                            Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                            Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                            Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                            Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                            Table 10 Diagnostics Binary Input (continued)

                            Object Identifier(a) Object Name Description

                            ACC-SVP01B-EN bull BCI-I Integration Guide 35

                            Object Data Points and Diagnostic Data Points

                            Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                            Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                            Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                            Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                            Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                            Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                            Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                            Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                            Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                            Analog Input 81 Cool Type Describes the cooling type installed in the unit

                            Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                            Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                            Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                            Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                            Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                            Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                            Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                            Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                            Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                            Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                            Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                            Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                            Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                            Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                            Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                            Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                            Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                            Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                            Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                            Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                            Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                            Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                            Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                            Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                            Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                            Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                            Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                            Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                            Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                            Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                            Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                            Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                            Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                            Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                            Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                            Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                            Object Identifier(a) Object Name Description

                            36 ACC-SVP01B-EN bull BCI-I Integration Guide

                            Object Data Points and Diagnostic Data Points

                            Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                            Multi-State Input 9 Economizer Type General description of the equipment economizer system

                            Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                            Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                            Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                            Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                            Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                            Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                            Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                            Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                            Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                            Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                            Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                            Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                            Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                            Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                            Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                            Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                            Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                            Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                            Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                            Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                            Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                            Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                            Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                            Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                            Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                            Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                            Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                            Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                            Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                            Multi-State Input 36 Final Filter Status Indicates the final filter media state

                            Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                            Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                            Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                            Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                            Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                            Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                            Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                            Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                            Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                            Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                            Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                            Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                            Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                            Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                            Object Identifier(a) Object Name Description

                            ACC-SVP01B-EN bull BCI-I Integration Guide 37

                            Object Data Points and Diagnostic Data Points

                            Binary Output 16 Humidification Command Command the operating state of the humidification system

                            NC 3 HVAC-Advisory HVAC-Advisory

                            NC 1 HVAC-Critical HVAC-Critical

                            NC 4 HVAC-Information HVAC-Information

                            NC 2 HVAC-Service Required HVAC-Service Required

                            Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                            Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                            Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                            Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                            Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                            Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                            Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                            Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                            Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                            Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                            Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                            Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                            Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                            Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                            Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                            Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                            Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                            Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                            Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                            Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                            Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                            Analog Input 82 Preheat Type Describes the heating type installed in the unit

                            Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                            Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                            Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                            Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                            Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                            Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                            Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                            Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                            Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                            Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                            Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                            Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                            Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                            Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                            Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                            Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                            Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                            Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                            Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                            Object Identifier(a) Object Name Description

                            38 ACC-SVP01B-EN bull BCI-I Integration Guide

                            Object Data Points and Diagnostic Data Points

                            Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                            Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                            Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                            Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                            Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                            Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                            Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                            Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                            Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                            Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                            Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                            Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                            Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                            Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                            Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                            Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                            Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                            Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                            Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                            Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                            Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                            Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                            Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                            Binary Input 3 Unit Status Indicates the current state of the unit

                            Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                            Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                            Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                            Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                            Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                            Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                            Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                            (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                            Object Identifier(a) Object Name Description

                            Table 12 Diagnostic Objects Sorted by Object Name

                            Object Identifier(a) Object Name ValueRange Description

                            BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                            BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                            ACC-SVP01B-EN bull BCI-I Integration Guide 39

                            Object Data Points and Diagnostic Data Points

                            BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                            BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                            BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                            BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                            BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                            BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                            BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                            BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                            BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                            BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                            BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                            BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                            BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                            BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                            BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                            BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                            BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                            BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                            BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                            BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                            BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                            BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                            BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                            BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                            BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                            BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                            BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                            BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                            BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                            Object Identifier(a) Object Name ValueRange Description

                            40 ACC-SVP01B-EN bull BCI-I Integration Guide

                            Object Data Points and Diagnostic Data Points

                            BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                            BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                            BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                            BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                            BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                            BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                            BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                            BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                            BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                            BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                            BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                            BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                            BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                            BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                            BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                            BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                            BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                            BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                            BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                            BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                            BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                            BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                            BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                            BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                            BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                            BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                            BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                            BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                            BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                            Object Identifier(a) Object Name ValueRange Description

                            ACC-SVP01B-EN bull BCI-I Integration Guide 41

                            Object Data Points and Diagnostic Data Points

                            BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                            BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                            BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                            BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                            BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                            BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                            BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                            BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                            BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                            BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                            BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                            BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                            BI 121 (use Object Identifier for RT)

                            Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                            BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                            BI 58 (use Object Identifier for RT or CSC)

                            Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                            BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                            BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                            BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                            BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                            BI 31 (use Object Identifier for RT CSC)

                            Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                            BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                            BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                            BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                            BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                            BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                            BI 121 (use Object Identifier for FAU)

                            Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                            B1 31 (use Object Identifier for FAU)

                            Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                            BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                            BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                            Object Identifier(a) Object Name ValueRange Description

                            42 ACC-SVP01B-EN bull BCI-I Integration Guide

                            Object Data Points and Diagnostic Data Points

                            BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                            BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                            BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                            BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                            BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                            BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                            BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                            BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                            BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                            BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                            BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                            BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                            BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                            BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                            BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                            BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                            BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                            BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                            BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                            BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                            BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                            BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                            BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                            1 = active Diagnostic Vel Press Sensor (Rear)

                            BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                            Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                            BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                            BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                            BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                            BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                            BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                            Object Identifier(a) Object Name ValueRange Description

                            ACC-SVP01B-EN bull BCI-I Integration Guide 43

                            Object Data Points and Diagnostic Data Points

                            BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                            BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                            BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                            BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                            BI 58 (use Object Identifier for FAU)

                            Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                            (a) BI=Binary Input

                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                            Object Identifier(a) Object Name ValueRange Description

                            44 ACC-SVP01B-EN bull BCI-I Integration Guide

                            Additional Resources

                            Additional Resources

                            Use the following documents and links as additional resources

                            bull Product support online

                            bull wwwbacnetorg

                            bull wwwbacnetassociationorg

                            bull wwwashraeorg

                            bull Tracer TU Help online

                            bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                            bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                            Note For further assistance contact your local Trane sales office

                            ACC-SVP01B-EN bull BCI-I Integration Guide 45

                            Glossary

                            A

                            ASHRAE

                            See American Society of Heating Refrigeration and Air-conditioning Engineers

                            American Society of Heating Refrigeration and Air-

                            conditioning Engineers

                            An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                            BBACnettrade

                            See Building Automation Control network

                            BACnet interoperability building blocks

                            A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                            BACnet object

                            An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                            baud rate

                            The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                            BIBB

                            See BACnet interoperability building blocks

                            Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                            advocates BACnet protocol for use in system-level control devices

                            device

                            A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                            Device ID

                            The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                            Iinteroperability

                            The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                            Pprotocol

                            A set of rules (language) that governs the exchange of data over a digital communications system

                            S

                            stand-alone operation

                            Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                            wwwtranecom

                            For more information contact your local Trane office or e-mail us at comforttranecom

                            Literature Order Number ACC-SVP01B-EN

                            Date September 2009

                            Supersedes ACC-SVP01A-EN

                            Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                            • Table of Contents
                            • Overview
                            • Ordering Numbers
                            • BACnet Protocol
                            • BCI-I Configuration
                              • Overview
                              • Starting a Session of Tracer TU and Direct Connection
                              • Reset to Factory Default
                              • IP Units Configuration
                              • BACnet Object Configuration
                              • Change Baud Rate
                              • Change Device ID
                              • Stand-alone or BAS Operation
                                • IntelliPak Control Configuration
                                • BAS Unit Control
                                • Periodic Update of BAS Values
                                • BAS Communication Failure
                                  • InputOutput Commands and Calculations
                                    • System Control Command
                                    • Filter Timer Reset Command
                                    • Diagnostics Reset Command
                                    • Setpoint Calculations
                                    • Timestamp Configuration
                                        • BCI IntelliPak Rotary Switches and LEDs
                                          • Rotary Switches
                                          • LEDs Description Behavior and Troubleshooting
                                          • 24 Vac Measurement
                                          • Ground Measurements
                                            • BACnet Data Points and Configuration Property Definitions
                                              • BACnet Protocol Implementation Conformance Statement (PICS)
                                                • Standardized Device Profile (Annex L)
                                                • Interoperability Building Blocks (Annex K)
                                                • Segmentation Capability
                                                • Object Types
                                                  • BACnet Protocol
                                                    • Data Link Layer Options
                                                    • Device Address Binding
                                                    • Networking Options
                                                    • Character Sets
                                                        • Object Data Points and Diagnostic Data Points
                                                        • Additional Resources
                                                        • Glossary

                              ACC-SVP01B-EN bull BCI-I Integration Guide 15

                              BCI IntelliPak Rotary Switches and LEDs

                              24 Vac Measurement

                              General Information Checkout Procedure Measurement Expected Value

                              Checking the voltage that is powering the UC400 is often a necessary step when commissioning or troubleshooting Operational issues and LED operation may result in a need to measure the input power

                              When troubleshooting it is faster to take measurements while the load is in place If Step 1 indicates an out-of-specification voltage disconnect the UC400 and measure the AC voltage across the transformer These measurements can direct the technician towards the problem source

                              Step 1

                              Measure AC voltage with the UC400 connected Perform this measurement while the unit is under load

                              200 Vac le Vac le 300 Vac

                              Step 2

                              Measure AC voltage with the UC400 unconnected Perform this measurement while the unit is not under load

                              200 Vac le Vac le 300 Vac

                              16 ACC-SVP01B-EN bull BCI-I Integration Guide

                              BCI IntelliPak Rotary Switches and LEDs

                              Ground Measurements

                              General Information and Checkout Procedure Measurement Expected Value

                              Method 1AC voltage between shield conductors and device chassis ground- the voltage difference between BACnet MSTP device chassis ground connections should be close to zero If the voltage difference is greater that 40 Vac there will be marginal communication or intermittent communication problems If the voltage difference is greater that 70 Vac some devices will no longer communicate

                              Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                              Vac le 20 V

                              Method 2AC voltage between earth ground and device chassis ground- the chassis ground of the UC400 needs to be connected to earth ground by some route

                              Note Do not assume that the building frame is a valid earth ground

                              Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                              Vac le 40 V (Must comply with National Electrical Codetradeand local electrical codes)

                              ACC-SVP01B-EN bull BCI-I Integration Guide 17

                              BACnet Data Points and Configuration Property Definitions

                              BACnet Data Points and Configuration Property

                              Definitions

                              The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MSTP This section includes information about

                              bull BACnet protocol implementation conformance statement (PICS)

                              bull Object types descriptions and configuration (refer to Table 2 p 19)

                              bull BACnet protocol data link layers device address binding networking options and character sets

                              bull Object data points and configurations

                              BACnet Protocol Implementation Conformance Statement (PICS)

                              Standardized Device Profile (Annex L)

                              Interoperability Building Blocks (Annex K)

                              Profile Description Supported Profile

                              BACnet Advanced Application Controller (B-AAC)

                              BACnet Application Specific Controller (B-ASC)

                              BACnet Building Controller (B-BC)

                              BACnet Operator Workstation (B-OWS)

                              BACnet Smart Actuator (B-SA)

                              BACnet Smart Sensor (B-SS)

                              Data Sharing Description Supported BIBB

                              Data Sharing-COV-B (DS-COV-B)

                              Data Sharing-ReadProperty-A (DS-RP-A)

                              Data Sharing-ReadProperty-B (DS-RP-B)

                              Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)

                              Data Sharing-WriteProperty-A (DS-WP-A)

                              Data Sharing-WriteProperty-B (DS-WP-B)

                              Data Sharing-WritePropertyMultiple-B (DS-WPM-B)

                              Alarm and Event Management Description Supported BIBB

                              Alarm and Event-ACKI-B (AE-ACK-B)

                              Alarm and Event-Alarm Summary-B (AE-ASUM-B)

                              Alarm and Event-Enrollment Summary-B (AE-ESUM-B)

                              Alarm and Event-Information-B (AE-INFO-B)

                              Alarm and Event-Notification Internal-B (AE-N-I-B)

                              18 ACC-SVP01B-EN bull BCI-I Integration Guide

                              BACnet Data Points and Configuration Property Definitions

                              Segmentation Capability

                              Trending Description Supported BIBB

                              Trending-Automated Trend Retrieval-B (T-ATR-B)

                              Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

                              Device Management Description Supported BIBB

                              Device Management-Backup and Restore-B (DM-BR-B)

                              Device Management-Device Communication Control-B (DM-DCC-B)

                              Device Management-Dynamic Device Binding-A (DM-DDB-A)

                              Device Management-Dynamic Device Binding-B (DM-DDB-B)

                              Device Management-Dynamic Object Binding-B (DM-DOB-B)

                              Device Management-List Manipulation-B (DM-LM-B)

                              Device Management-Object Creation and Deletion-B (DM-OCD-B)

                              Device Management-Private Transfer-A (DM-PT-A)

                              Device Management-Private Transfer-B (DM-PT-B)

                              Device Management-Reinitialize Device-B (DM-RD-B)

                              Device Management-TimeSynchronization-B (DM-TS-B)

                              Segmentation Description Supported Segment

                              Segmented Requests Window Size 1

                              Segmented Responses Window Size 1

                              ACC-SVP01B-EN bull BCI-I Integration Guide 19

                              BACnet Data Points and Configuration Property Definitions

                              Object Types

                              Table 2 Descriptions and configurations

                              Object Type Required Properties Read Properties Written(a) Optional Properties Read

                              Ability to Create

                              Ability to Delete

                              Analog Input

                              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                              bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                              bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                              Yes Yes only user created objects

                              Analog Output

                              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

                              bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                              bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                              Yes Yes only user created objects

                              Analog Value

                              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                              bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                              bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                              Yes Yes only user created objects

                              Binary Input

                              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                              bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                              bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                              Yes Yes only user created objects

                              20 ACC-SVP01B-EN bull BCI-I Integration Guide

                              BACnet Data Points and Configuration Property Definitions

                              Binary Output

                              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

                              bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

                              bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                              Yes Yes only user created objects

                              Binary Value

                              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                              bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                              bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                              Yes Yes only user created objects

                              Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

                              bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

                              bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

                              None None

                              Event Enrollment Object

                              bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

                              bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

                              bull None Yes Yes only user created objects

                              Table 2 Descriptions and configurations (continued)

                              Object Type Required Properties Read Properties Written(a) Optional Properties Read

                              Ability to Create

                              Ability to Delete

                              ACC-SVP01B-EN bull BCI-I Integration Guide 21

                              BACnet Data Points and Configuration Property Definitions

                              Multistate Input

                              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                              bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                              bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                              Yes Yes only user created objects

                              Multistate Output

                              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

                              bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

                              bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                              Yes Yes only user created objects

                              Multistate Value

                              bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                              bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                              bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                              Yes Yes only user created objects

                              Notification Class

                              bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

                              bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

                              None Yes Yes only user created objects

                              Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

                              bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

                              bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

                              Yes Yes only user created objects

                              (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

                              Table 2 Descriptions and configurations (continued)

                              Object Type Required Properties Read Properties Written(a) Optional Properties Read

                              Ability to Create

                              Ability to Delete

                              22 ACC-SVP01B-EN bull BCI-I Integration Guide

                              BACnet Data Points and Configuration Property Definitions

                              BACnet Protocol

                              Data Link Layer Options

                              Device Address Binding

                              Networking Options

                              Data Link Layer Description Supported Option

                              ANSIATA 8781 25 Mb ARCNET (Clause 8)

                              ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

                              BACnet IP (Annex J)

                              BACnet IP (Annex J) Foreign Device

                              ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

                              LonTalk (Clause 11) Medium

                              MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

                              MSTP Slave (Clause 9) Baud Rate(s)

                              Other

                              Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

                              Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

                              Device Address Binding Supported

                              Static Device Binding Supported

                              Networking DescriptionsSupported

                              Option

                              Annex H BACnet Tunneling

                              BACnetIP Broadcast Management Device (BBMD)

                              Does the BBMD Support Registrations by Foreign Devices

                              Router

                              ACC-SVP01B-EN bull BCI-I Integration Guide 23

                              BACnet Data Points and Configuration Property Definitions

                              Character Sets

                              Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

                              Character Set Descriptions Supported

                              ANSI X34

                              IBMMicrosoft DBCS

                              ISO 10646 (UCS-4)

                              ISO 10646 (UCS2)

                              ISO 8859-1

                              JIS C 6226

                              24 ACC-SVP01B-EN bull BCI-I Integration Guide

                              Object Data Points and Diagnostic Data Points

                              Object Data Points and Diagnostic Data Points

                              For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

                              Table 3 Analog Output

                              Object Identifier Object Name Description Units Valid Range

                              Refresh Rate

                              (Sec)

                              Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

                              Percent (98) 0 to 100 NA

                              Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

                              Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

                              Degrees-Fahrenheit (64) 500 to 900 NA

                              Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

                              BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

                              Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

                              Degrees-Fahrenheit (64) 400 to 900 NA

                              Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

                              Degrees-Fahrenheit (64) 400 to 1800 NA

                              Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

                              070 to 510 (Ipak II) NA

                              Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

                              003 to 030-002 to 030 (enhanced StatiTrac)

                              NA

                              Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

                              -028 to 050-067 to 067 (enhanced StatiTrac)

                              900

                              Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                              Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                              Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

                              00 to 79 (Ipak II) 900

                              Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                              Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

                              Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

                              Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

                              Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

                              Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

                              Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

                              Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

                              Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

                              Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

                              ACC-SVP01B-EN bull BCI-I Integration Guide 25

                              Object Data Points and Diagnostic Data Points

                              Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                              Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                              Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                              Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                              Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                              Cooling temperature setpoint used for control in unoccupied mode

                              Degrees-Fahrenheit (64) 520 to 880 NA

                              Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                              Heating temperature setpoint used for control in unoccupied mode

                              Degrees-Fahrenheit (64) 500 to 900 NA

                              Table 4 Analog Input

                              Object Identifier Object Name Description Units (Listed Are Defaults)

                              Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                              Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                              Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                              Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                              Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                              Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                              Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                              Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                              Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                              Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                              Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                              Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                              Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                              Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                              Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                              Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                              Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                              Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                              Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                              Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                              Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                              Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                              Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                              Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                              Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                              Table 3 Analog Output (continued)

                              Object Identifier Object Name Description Units Valid Range

                              Refresh Rate

                              (Sec)

                              26 ACC-SVP01B-EN bull BCI-I Integration Guide

                              Object Data Points and Diagnostic Data Points

                              Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                              Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                              Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                              Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                              Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                              Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                              Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                              Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                              Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                              Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                              Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                              Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                              Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                              Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                              Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                              Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                              Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                              Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                              Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                              Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                              Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                              Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                              Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                              Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                              The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                              Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                              The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                              Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                              Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                              Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                              Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                              Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                              Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                              Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                              Table 4 Analog Input (continued)

                              Object Identifier Object Name Description Units (Listed Are Defaults)

                              ACC-SVP01B-EN bull BCI-I Integration Guide 27

                              Object Data Points and Diagnostic Data Points

                              Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                              Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                              Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                              Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                              The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                              Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                              Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                              Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                              Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                              Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                              Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                              Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                              Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                              Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                              Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                              Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                              Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                              Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                              Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                              Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                              Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                              Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                              Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                              Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                              Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                              Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                              Table 5 Analog Value

                              Object Identifier Object Name Description Units Valid Range

                              Analog Value 1 Filter Runtime Hours Setpoint

                              The setpoint value used by the filter run hours calculation

                              Hours (71) 0 to 10000

                              Table 4 Analog Input (continued)

                              Object Identifier Object Name Description Units (Listed Are Defaults)

                              28 ACC-SVP01B-EN bull BCI-I Integration Guide

                              Object Data Points and Diagnostic Data Points

                              Table 6 Multistate Output

                              BCI-I Object Identifier Object Name Description Object States

                              Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                              Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                              1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                              Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                              Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                              1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                              Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                              1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                              Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                              1 = Flow2 = No Flow3 = Auto

                              Table 7 Multistate Input

                              BCI-I Object Identifier Object Name Description Object States

                              Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                              1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                              Multi-State Input 9 Economizer Type General description of the equipment economizer system

                              1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                              Multi-State Input 10 Condenser Type General description of the equipment condenser system

                              1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                              Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                              1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                              ACC-SVP01B-EN bull BCI-I Integration Guide 29

                              Object Data Points and Diagnostic Data Points

                              Multi-State Input 15 Economizer Decision Method

                              Unit method to determine when the economizer system is enabled

                              1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                              Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                              Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                              Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                              1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                              Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                              1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                              Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                              1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                              Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                              1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                              Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                              1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                              Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                              1 = Idle2 = On3 = Cancel

                              Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                              1 = Off2 = On3 = Not Present

                              Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                              1 = Off2 = On3 = Not Present

                              Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                              1 = Off2 = On3 = Not Present

                              Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                              1 = Off|2 = On3 = Not Present

                              Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                              1 = Off2 = On3 = Not Present

                              Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                              1 = Off2 = On3 = Not Present

                              Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                              1 = Off2 = On3 = Not Present

                              Table 7 Multistate Input (continued)

                              BCI-I Object Identifier Object Name Description Object States

                              30 ACC-SVP01B-EN bull BCI-I Integration Guide

                              Object Data Points and Diagnostic Data Points

                              Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                              1 = Off2 = On3 = Not Present

                              Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                              1 = Off2 = On3 = Not Present

                              Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                              Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                              Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                              Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                              Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                              1 = Off2 = On3 = Not Present

                              Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                              1= Off2= On3= Not Present

                              Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                              Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                              Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                              Multi-State Input 43 Outdoor Air Damper Status

                              Indicates the operating state of the outdoor damper

                              1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                              Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                              1 = Disabled2 = Enabled3 = Not Present

                              Table 8 Binary Output

                              Object Identifier Object Name DescriptionRelinquish Default Object States

                              Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                              Active = BAS Control

                              Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                              Active = Heating Locked Out

                              Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                              Active = Cooling Locked Out

                              Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                              Active = Enabled

                              Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                              Active = On

                              Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                              Inactive Inactive = DisabledActive = Enabled

                              Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                              Active = Reset

                              Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                              Active = Reset

                              Table 7 Multistate Input (continued)

                              BCI-I Object Identifier Object Name Description Object States

                              ACC-SVP01B-EN bull BCI-I Integration Guide 31

                              Object Data Points and Diagnostic Data Points

                              Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                              Active = Auto

                              Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                              Active = Auto

                              Table 9 Binary Input

                              Object Identifier Object Name Description Object States

                              Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                              Inactive = Standalone controlActive = BAS control

                              Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                              Inactive = NormalActive = Locked Out

                              Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                              Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                              Inactive = AutoActive = Open

                              Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                              Inactive = InactiveActive = Active

                              Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                              Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                              Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                              Inactive = DisabledActive = Enabled

                              Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                              Inactive = DisabledActive = Enabled

                              Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                              Inactive = InactiveActive = Active

                              Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                              Inactive = No FlowActive = Flow

                              Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                              Inactive = InactiveActive = Active

                              Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                              Inactive = InactiveActive = Active

                              Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                              Inactive = InactiveActive = Active

                              Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                              The status of evaporator frost protection function for circuit 1

                              Inactive = InactiveActive = Active

                              Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                              The status of evaporator frost protection function for circuit 2

                              Inactive = InactiveActive = Active

                              Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                              The status of evaporator frost protection function for circuit 3

                              Inactive = InactiveActive = Active

                              Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                              The status of evaporator frost protection function for circuit 4

                              Inactive = InactiveActive = Active

                              Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                              Inactive = De-energizedActive = Energized

                              Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                              Inactive = InactiveActive = Active

                              Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                              Inactive = ClosedActive = Open

                              Table 10 Diagnostics Binary Input

                              Object Identifier(a) Object Name Description

                              Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                              Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                              Binary Input 31 (use Object Identifier for RT or CSC)

                              Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                              Binary Input 31 (use Object Identifier for FAU)

                              Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                              Table 8 Binary Output

                              Object Identifier Object Name DescriptionRelinquish Default Object States

                              32 ACC-SVP01B-EN bull BCI-I Integration Guide

                              Object Data Points and Diagnostic Data Points

                              Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                              Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                              Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                              Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                              Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                              Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                              Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                              Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                              Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                              Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                              Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                              Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                              Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                              Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                              Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                              Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                              Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                              Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                              Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                              Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                              Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                              Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                              Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                              Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                              Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                              Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                              Binary Input 58 (use Object Identifier for RT or CSC)

                              Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                              Binary Input 58 (use Object Identifier for FAU)

                              Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                              Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                              Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                              Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                              Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                              Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                              Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                              Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                              Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                              Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                              Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                              Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                              Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                              Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                              Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                              Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                              Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                              Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                              Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                              Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                              Table 10 Diagnostics Binary Input (continued)

                              Object Identifier(a) Object Name Description

                              ACC-SVP01B-EN bull BCI-I Integration Guide 33

                              Object Data Points and Diagnostic Data Points

                              Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                              Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                              Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                              Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                              Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                              Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                              Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                              Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                              Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                              Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                              Binary Input 86 (use Object Identifier for RT I-pak II)

                              Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                              Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                              Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                              Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                              Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                              Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                              Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                              Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                              Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                              Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                              Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                              Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                              Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                              Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                              Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                              Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                              Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                              Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                              Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                              Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                              Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                              Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                              Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                              Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                              Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                              Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                              Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                              Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                              Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                              Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                              Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                              Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                              Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                              Binary Input 121 (use Object Identifier for RT)

                              Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                              Binary Input 121 (use Object Identifier for FAU)

                              Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                              Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                              Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                              Table 10 Diagnostics Binary Input (continued)

                              Object Identifier(a) Object Name Description

                              34 ACC-SVP01B-EN bull BCI-I Integration Guide

                              Object Data Points and Diagnostic Data Points

                              Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                              Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                              Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                              Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                              Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                              Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                              Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                              Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                              Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                              Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                              Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                              Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                              Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                              Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                              Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                              Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                              Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                              Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                              Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                              Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                              Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                              Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                              Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                              Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                              Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                              Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                              (a) Object States Inactive = normal and Active = foreign language specific

                              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                              Object Identifier(a) Object Name Description

                              Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                              Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                              Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                              Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                              Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                              Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                              Multi-State Input 10 Condenser Type General description of the equipment condenser system

                              Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                              Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                              Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                              Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                              Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                              Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                              Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                              Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                              Table 10 Diagnostics Binary Input (continued)

                              Object Identifier(a) Object Name Description

                              ACC-SVP01B-EN bull BCI-I Integration Guide 35

                              Object Data Points and Diagnostic Data Points

                              Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                              Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                              Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                              Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                              Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                              Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                              Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                              Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                              Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                              Analog Input 81 Cool Type Describes the cooling type installed in the unit

                              Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                              Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                              Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                              Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                              Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                              Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                              Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                              Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                              Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                              Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                              Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                              Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                              Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                              Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                              Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                              Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                              Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                              Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                              Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                              Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                              Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                              Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                              Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                              Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                              Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                              Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                              Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                              Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                              Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                              Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                              Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                              Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                              Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                              Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                              Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                              Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                              Object Identifier(a) Object Name Description

                              36 ACC-SVP01B-EN bull BCI-I Integration Guide

                              Object Data Points and Diagnostic Data Points

                              Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                              Multi-State Input 9 Economizer Type General description of the equipment economizer system

                              Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                              Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                              Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                              Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                              Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                              Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                              Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                              Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                              Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                              Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                              Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                              Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                              Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                              Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                              Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                              Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                              Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                              Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                              Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                              Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                              Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                              Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                              Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                              Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                              Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                              Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                              Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                              Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                              Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                              Multi-State Input 36 Final Filter Status Indicates the final filter media state

                              Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                              Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                              Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                              Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                              Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                              Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                              Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                              Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                              Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                              Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                              Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                              Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                              Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                              Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                              Object Identifier(a) Object Name Description

                              ACC-SVP01B-EN bull BCI-I Integration Guide 37

                              Object Data Points and Diagnostic Data Points

                              Binary Output 16 Humidification Command Command the operating state of the humidification system

                              NC 3 HVAC-Advisory HVAC-Advisory

                              NC 1 HVAC-Critical HVAC-Critical

                              NC 4 HVAC-Information HVAC-Information

                              NC 2 HVAC-Service Required HVAC-Service Required

                              Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                              Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                              Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                              Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                              Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                              Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                              Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                              Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                              Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                              Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                              Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                              Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                              Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                              Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                              Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                              Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                              Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                              Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                              Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                              Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                              Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                              Analog Input 82 Preheat Type Describes the heating type installed in the unit

                              Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                              Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                              Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                              Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                              Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                              Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                              Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                              Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                              Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                              Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                              Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                              Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                              Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                              Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                              Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                              Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                              Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                              Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                              Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                              Object Identifier(a) Object Name Description

                              38 ACC-SVP01B-EN bull BCI-I Integration Guide

                              Object Data Points and Diagnostic Data Points

                              Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                              Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                              Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                              Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                              Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                              Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                              Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                              Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                              Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                              Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                              Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                              Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                              Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                              Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                              Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                              Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                              Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                              Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                              Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                              Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                              Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                              Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                              Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                              Binary Input 3 Unit Status Indicates the current state of the unit

                              Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                              Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                              Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                              Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                              Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                              Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                              Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                              (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                              Object Identifier(a) Object Name Description

                              Table 12 Diagnostic Objects Sorted by Object Name

                              Object Identifier(a) Object Name ValueRange Description

                              BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                              BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                              ACC-SVP01B-EN bull BCI-I Integration Guide 39

                              Object Data Points and Diagnostic Data Points

                              BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                              BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                              BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                              BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                              BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                              BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                              BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                              BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                              BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                              BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                              BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                              BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                              BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                              BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                              BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                              BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                              BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                              BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                              BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                              BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                              BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                              BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                              BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                              BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                              BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                              BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                              BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                              BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                              BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                              Object Identifier(a) Object Name ValueRange Description

                              40 ACC-SVP01B-EN bull BCI-I Integration Guide

                              Object Data Points and Diagnostic Data Points

                              BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                              BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                              BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                              BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                              BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                              BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                              BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                              BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                              BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                              BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                              BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                              BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                              BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                              BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                              BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                              BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                              BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                              BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                              BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                              BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                              BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                              BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                              BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                              BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                              BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                              BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                              BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                              BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                              BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                              Object Identifier(a) Object Name ValueRange Description

                              ACC-SVP01B-EN bull BCI-I Integration Guide 41

                              Object Data Points and Diagnostic Data Points

                              BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                              BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                              BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                              BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                              BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                              BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                              BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                              BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                              BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                              BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                              BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                              BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                              BI 121 (use Object Identifier for RT)

                              Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                              BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                              BI 58 (use Object Identifier for RT or CSC)

                              Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                              BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                              BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                              BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                              BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                              BI 31 (use Object Identifier for RT CSC)

                              Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                              BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                              BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                              BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                              BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                              BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                              BI 121 (use Object Identifier for FAU)

                              Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                              B1 31 (use Object Identifier for FAU)

                              Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                              BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                              BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                              Object Identifier(a) Object Name ValueRange Description

                              42 ACC-SVP01B-EN bull BCI-I Integration Guide

                              Object Data Points and Diagnostic Data Points

                              BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                              BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                              BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                              BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                              BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                              BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                              BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                              BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                              BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                              BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                              BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                              BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                              BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                              BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                              BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                              BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                              BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                              BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                              BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                              BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                              BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                              BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                              BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                              1 = active Diagnostic Vel Press Sensor (Rear)

                              BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                              Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                              BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                              BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                              BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                              BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                              BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                              Object Identifier(a) Object Name ValueRange Description

                              ACC-SVP01B-EN bull BCI-I Integration Guide 43

                              Object Data Points and Diagnostic Data Points

                              BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                              BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                              BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                              BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                              BI 58 (use Object Identifier for FAU)

                              Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                              (a) BI=Binary Input

                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                              Object Identifier(a) Object Name ValueRange Description

                              44 ACC-SVP01B-EN bull BCI-I Integration Guide

                              Additional Resources

                              Additional Resources

                              Use the following documents and links as additional resources

                              bull Product support online

                              bull wwwbacnetorg

                              bull wwwbacnetassociationorg

                              bull wwwashraeorg

                              bull Tracer TU Help online

                              bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                              bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                              Note For further assistance contact your local Trane sales office

                              ACC-SVP01B-EN bull BCI-I Integration Guide 45

                              Glossary

                              A

                              ASHRAE

                              See American Society of Heating Refrigeration and Air-conditioning Engineers

                              American Society of Heating Refrigeration and Air-

                              conditioning Engineers

                              An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                              BBACnettrade

                              See Building Automation Control network

                              BACnet interoperability building blocks

                              A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                              BACnet object

                              An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                              baud rate

                              The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                              BIBB

                              See BACnet interoperability building blocks

                              Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                              advocates BACnet protocol for use in system-level control devices

                              device

                              A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                              Device ID

                              The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                              Iinteroperability

                              The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                              Pprotocol

                              A set of rules (language) that governs the exchange of data over a digital communications system

                              S

                              stand-alone operation

                              Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                              wwwtranecom

                              For more information contact your local Trane office or e-mail us at comforttranecom

                              Literature Order Number ACC-SVP01B-EN

                              Date September 2009

                              Supersedes ACC-SVP01A-EN

                              Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                              • Table of Contents
                              • Overview
                              • Ordering Numbers
                              • BACnet Protocol
                              • BCI-I Configuration
                                • Overview
                                • Starting a Session of Tracer TU and Direct Connection
                                • Reset to Factory Default
                                • IP Units Configuration
                                • BACnet Object Configuration
                                • Change Baud Rate
                                • Change Device ID
                                • Stand-alone or BAS Operation
                                  • IntelliPak Control Configuration
                                  • BAS Unit Control
                                  • Periodic Update of BAS Values
                                  • BAS Communication Failure
                                    • InputOutput Commands and Calculations
                                      • System Control Command
                                      • Filter Timer Reset Command
                                      • Diagnostics Reset Command
                                      • Setpoint Calculations
                                      • Timestamp Configuration
                                          • BCI IntelliPak Rotary Switches and LEDs
                                            • Rotary Switches
                                            • LEDs Description Behavior and Troubleshooting
                                            • 24 Vac Measurement
                                            • Ground Measurements
                                              • BACnet Data Points and Configuration Property Definitions
                                                • BACnet Protocol Implementation Conformance Statement (PICS)
                                                  • Standardized Device Profile (Annex L)
                                                  • Interoperability Building Blocks (Annex K)
                                                  • Segmentation Capability
                                                  • Object Types
                                                    • BACnet Protocol
                                                      • Data Link Layer Options
                                                      • Device Address Binding
                                                      • Networking Options
                                                      • Character Sets
                                                          • Object Data Points and Diagnostic Data Points
                                                          • Additional Resources
                                                          • Glossary

                                16 ACC-SVP01B-EN bull BCI-I Integration Guide

                                BCI IntelliPak Rotary Switches and LEDs

                                Ground Measurements

                                General Information and Checkout Procedure Measurement Expected Value

                                Method 1AC voltage between shield conductors and device chassis ground- the voltage difference between BACnet MSTP device chassis ground connections should be close to zero If the voltage difference is greater that 40 Vac there will be marginal communication or intermittent communication problems If the voltage difference is greater that 70 Vac some devices will no longer communicate

                                Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                                Vac le 20 V

                                Method 2AC voltage between earth ground and device chassis ground- the chassis ground of the UC400 needs to be connected to earth ground by some route

                                Note Do not assume that the building frame is a valid earth ground

                                Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground

                                Vac le 40 V (Must comply with National Electrical Codetradeand local electrical codes)

                                ACC-SVP01B-EN bull BCI-I Integration Guide 17

                                BACnet Data Points and Configuration Property Definitions

                                BACnet Data Points and Configuration Property

                                Definitions

                                The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MSTP This section includes information about

                                bull BACnet protocol implementation conformance statement (PICS)

                                bull Object types descriptions and configuration (refer to Table 2 p 19)

                                bull BACnet protocol data link layers device address binding networking options and character sets

                                bull Object data points and configurations

                                BACnet Protocol Implementation Conformance Statement (PICS)

                                Standardized Device Profile (Annex L)

                                Interoperability Building Blocks (Annex K)

                                Profile Description Supported Profile

                                BACnet Advanced Application Controller (B-AAC)

                                BACnet Application Specific Controller (B-ASC)

                                BACnet Building Controller (B-BC)

                                BACnet Operator Workstation (B-OWS)

                                BACnet Smart Actuator (B-SA)

                                BACnet Smart Sensor (B-SS)

                                Data Sharing Description Supported BIBB

                                Data Sharing-COV-B (DS-COV-B)

                                Data Sharing-ReadProperty-A (DS-RP-A)

                                Data Sharing-ReadProperty-B (DS-RP-B)

                                Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)

                                Data Sharing-WriteProperty-A (DS-WP-A)

                                Data Sharing-WriteProperty-B (DS-WP-B)

                                Data Sharing-WritePropertyMultiple-B (DS-WPM-B)

                                Alarm and Event Management Description Supported BIBB

                                Alarm and Event-ACKI-B (AE-ACK-B)

                                Alarm and Event-Alarm Summary-B (AE-ASUM-B)

                                Alarm and Event-Enrollment Summary-B (AE-ESUM-B)

                                Alarm and Event-Information-B (AE-INFO-B)

                                Alarm and Event-Notification Internal-B (AE-N-I-B)

                                18 ACC-SVP01B-EN bull BCI-I Integration Guide

                                BACnet Data Points and Configuration Property Definitions

                                Segmentation Capability

                                Trending Description Supported BIBB

                                Trending-Automated Trend Retrieval-B (T-ATR-B)

                                Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

                                Device Management Description Supported BIBB

                                Device Management-Backup and Restore-B (DM-BR-B)

                                Device Management-Device Communication Control-B (DM-DCC-B)

                                Device Management-Dynamic Device Binding-A (DM-DDB-A)

                                Device Management-Dynamic Device Binding-B (DM-DDB-B)

                                Device Management-Dynamic Object Binding-B (DM-DOB-B)

                                Device Management-List Manipulation-B (DM-LM-B)

                                Device Management-Object Creation and Deletion-B (DM-OCD-B)

                                Device Management-Private Transfer-A (DM-PT-A)

                                Device Management-Private Transfer-B (DM-PT-B)

                                Device Management-Reinitialize Device-B (DM-RD-B)

                                Device Management-TimeSynchronization-B (DM-TS-B)

                                Segmentation Description Supported Segment

                                Segmented Requests Window Size 1

                                Segmented Responses Window Size 1

                                ACC-SVP01B-EN bull BCI-I Integration Guide 19

                                BACnet Data Points and Configuration Property Definitions

                                Object Types

                                Table 2 Descriptions and configurations

                                Object Type Required Properties Read Properties Written(a) Optional Properties Read

                                Ability to Create

                                Ability to Delete

                                Analog Input

                                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                                bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                                bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                Yes Yes only user created objects

                                Analog Output

                                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

                                bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                                bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                Yes Yes only user created objects

                                Analog Value

                                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                                bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                                bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                Yes Yes only user created objects

                                Binary Input

                                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                                bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                                bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                                Yes Yes only user created objects

                                20 ACC-SVP01B-EN bull BCI-I Integration Guide

                                BACnet Data Points and Configuration Property Definitions

                                Binary Output

                                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

                                bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

                                bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                                Yes Yes only user created objects

                                Binary Value

                                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                                bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                                bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                                Yes Yes only user created objects

                                Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

                                bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

                                bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

                                None None

                                Event Enrollment Object

                                bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

                                bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

                                bull None Yes Yes only user created objects

                                Table 2 Descriptions and configurations (continued)

                                Object Type Required Properties Read Properties Written(a) Optional Properties Read

                                Ability to Create

                                Ability to Delete

                                ACC-SVP01B-EN bull BCI-I Integration Guide 21

                                BACnet Data Points and Configuration Property Definitions

                                Multistate Input

                                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                                bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                                bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                Yes Yes only user created objects

                                Multistate Output

                                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

                                bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

                                bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                Yes Yes only user created objects

                                Multistate Value

                                bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                                bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                                bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                Yes Yes only user created objects

                                Notification Class

                                bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

                                bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

                                None Yes Yes only user created objects

                                Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

                                bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

                                bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

                                Yes Yes only user created objects

                                (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

                                Table 2 Descriptions and configurations (continued)

                                Object Type Required Properties Read Properties Written(a) Optional Properties Read

                                Ability to Create

                                Ability to Delete

                                22 ACC-SVP01B-EN bull BCI-I Integration Guide

                                BACnet Data Points and Configuration Property Definitions

                                BACnet Protocol

                                Data Link Layer Options

                                Device Address Binding

                                Networking Options

                                Data Link Layer Description Supported Option

                                ANSIATA 8781 25 Mb ARCNET (Clause 8)

                                ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

                                BACnet IP (Annex J)

                                BACnet IP (Annex J) Foreign Device

                                ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

                                LonTalk (Clause 11) Medium

                                MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

                                MSTP Slave (Clause 9) Baud Rate(s)

                                Other

                                Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

                                Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

                                Device Address Binding Supported

                                Static Device Binding Supported

                                Networking DescriptionsSupported

                                Option

                                Annex H BACnet Tunneling

                                BACnetIP Broadcast Management Device (BBMD)

                                Does the BBMD Support Registrations by Foreign Devices

                                Router

                                ACC-SVP01B-EN bull BCI-I Integration Guide 23

                                BACnet Data Points and Configuration Property Definitions

                                Character Sets

                                Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

                                Character Set Descriptions Supported

                                ANSI X34

                                IBMMicrosoft DBCS

                                ISO 10646 (UCS-4)

                                ISO 10646 (UCS2)

                                ISO 8859-1

                                JIS C 6226

                                24 ACC-SVP01B-EN bull BCI-I Integration Guide

                                Object Data Points and Diagnostic Data Points

                                Object Data Points and Diagnostic Data Points

                                For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

                                Table 3 Analog Output

                                Object Identifier Object Name Description Units Valid Range

                                Refresh Rate

                                (Sec)

                                Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

                                Percent (98) 0 to 100 NA

                                Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

                                Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

                                Degrees-Fahrenheit (64) 500 to 900 NA

                                Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

                                BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

                                Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

                                Degrees-Fahrenheit (64) 400 to 900 NA

                                Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

                                Degrees-Fahrenheit (64) 400 to 1800 NA

                                Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

                                070 to 510 (Ipak II) NA

                                Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

                                003 to 030-002 to 030 (enhanced StatiTrac)

                                NA

                                Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

                                -028 to 050-067 to 067 (enhanced StatiTrac)

                                900

                                Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

                                00 to 79 (Ipak II) 900

                                Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

                                Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

                                Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

                                Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

                                Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

                                Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

                                Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

                                ACC-SVP01B-EN bull BCI-I Integration Guide 25

                                Object Data Points and Diagnostic Data Points

                                Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                                Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                                Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                                Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                                Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                                Cooling temperature setpoint used for control in unoccupied mode

                                Degrees-Fahrenheit (64) 520 to 880 NA

                                Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                                Heating temperature setpoint used for control in unoccupied mode

                                Degrees-Fahrenheit (64) 500 to 900 NA

                                Table 4 Analog Input

                                Object Identifier Object Name Description Units (Listed Are Defaults)

                                Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                                Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                                Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                                Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                                Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                                Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                                Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                                Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                                Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                                Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                                Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                                Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                                Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                                Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                                Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                                Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                                Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                                Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                                Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                                Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                                Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                                Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                                Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                                Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                Table 3 Analog Output (continued)

                                Object Identifier Object Name Description Units Valid Range

                                Refresh Rate

                                (Sec)

                                26 ACC-SVP01B-EN bull BCI-I Integration Guide

                                Object Data Points and Diagnostic Data Points

                                Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                                Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                                Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                                Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                                Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                                Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                                Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                                Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                                Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                                Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                                Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                                Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                                Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                                Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                                Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                                Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                                The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                                Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                                The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                                Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                                Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                                Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                                Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                                Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                                Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                                Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                                Table 4 Analog Input (continued)

                                Object Identifier Object Name Description Units (Listed Are Defaults)

                                ACC-SVP01B-EN bull BCI-I Integration Guide 27

                                Object Data Points and Diagnostic Data Points

                                Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                                Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                                Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                                Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                                The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                                Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                                Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                                Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                                Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                                Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                                Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                                Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                                Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                                Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                                Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                                Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                                Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                                Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                                Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                                Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                                Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                                Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                                Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                                Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                                Table 5 Analog Value

                                Object Identifier Object Name Description Units Valid Range

                                Analog Value 1 Filter Runtime Hours Setpoint

                                The setpoint value used by the filter run hours calculation

                                Hours (71) 0 to 10000

                                Table 4 Analog Input (continued)

                                Object Identifier Object Name Description Units (Listed Are Defaults)

                                28 ACC-SVP01B-EN bull BCI-I Integration Guide

                                Object Data Points and Diagnostic Data Points

                                Table 6 Multistate Output

                                BCI-I Object Identifier Object Name Description Object States

                                Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                                Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                                Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                                Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                1 = Flow2 = No Flow3 = Auto

                                Table 7 Multistate Input

                                BCI-I Object Identifier Object Name Description Object States

                                Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                                Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                                Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                                Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                                ACC-SVP01B-EN bull BCI-I Integration Guide 29

                                Object Data Points and Diagnostic Data Points

                                Multi-State Input 15 Economizer Decision Method

                                Unit method to determine when the economizer system is enabled

                                1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                                Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                                Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                                Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                                Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                1 = Idle2 = On3 = Cancel

                                Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                1 = Off2 = On3 = Not Present

                                Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                1 = Off2 = On3 = Not Present

                                Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                1 = Off2 = On3 = Not Present

                                Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                1 = Off|2 = On3 = Not Present

                                Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                1 = Off2 = On3 = Not Present

                                Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                1 = Off2 = On3 = Not Present

                                Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                1 = Off2 = On3 = Not Present

                                Table 7 Multistate Input (continued)

                                BCI-I Object Identifier Object Name Description Object States

                                30 ACC-SVP01B-EN bull BCI-I Integration Guide

                                Object Data Points and Diagnostic Data Points

                                Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                1 = Off2 = On3 = Not Present

                                Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                1 = Off2 = On3 = Not Present

                                Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                                Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                                Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                                Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                                Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                1 = Off2 = On3 = Not Present

                                Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                1= Off2= On3= Not Present

                                Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                                Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                                Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                                Multi-State Input 43 Outdoor Air Damper Status

                                Indicates the operating state of the outdoor damper

                                1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                                Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                1 = Disabled2 = Enabled3 = Not Present

                                Table 8 Binary Output

                                Object Identifier Object Name DescriptionRelinquish Default Object States

                                Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                                Active = BAS Control

                                Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                                Active = Heating Locked Out

                                Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                                Active = Cooling Locked Out

                                Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                                Active = Enabled

                                Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                                Active = On

                                Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                                Inactive Inactive = DisabledActive = Enabled

                                Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                                Active = Reset

                                Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                                Active = Reset

                                Table 7 Multistate Input (continued)

                                BCI-I Object Identifier Object Name Description Object States

                                ACC-SVP01B-EN bull BCI-I Integration Guide 31

                                Object Data Points and Diagnostic Data Points

                                Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                                Active = Auto

                                Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                                Active = Auto

                                Table 9 Binary Input

                                Object Identifier Object Name Description Object States

                                Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                Inactive = Standalone controlActive = BAS control

                                Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                Inactive = NormalActive = Locked Out

                                Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                                Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                Inactive = AutoActive = Open

                                Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                Inactive = InactiveActive = Active

                                Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                                Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                                Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                Inactive = DisabledActive = Enabled

                                Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                Inactive = DisabledActive = Enabled

                                Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                Inactive = InactiveActive = Active

                                Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                Inactive = No FlowActive = Flow

                                Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                Inactive = InactiveActive = Active

                                Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                Inactive = InactiveActive = Active

                                Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                Inactive = InactiveActive = Active

                                Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                                The status of evaporator frost protection function for circuit 1

                                Inactive = InactiveActive = Active

                                Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                                The status of evaporator frost protection function for circuit 2

                                Inactive = InactiveActive = Active

                                Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                                The status of evaporator frost protection function for circuit 3

                                Inactive = InactiveActive = Active

                                Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                                The status of evaporator frost protection function for circuit 4

                                Inactive = InactiveActive = Active

                                Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                Inactive = De-energizedActive = Energized

                                Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                Inactive = InactiveActive = Active

                                Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                Inactive = ClosedActive = Open

                                Table 10 Diagnostics Binary Input

                                Object Identifier(a) Object Name Description

                                Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                                Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                                Binary Input 31 (use Object Identifier for RT or CSC)

                                Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                                Binary Input 31 (use Object Identifier for FAU)

                                Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                                Table 8 Binary Output

                                Object Identifier Object Name DescriptionRelinquish Default Object States

                                32 ACC-SVP01B-EN bull BCI-I Integration Guide

                                Object Data Points and Diagnostic Data Points

                                Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                                Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                                Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                                Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                                Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                                Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                                Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                                Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                                Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                                Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                                Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                                Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                                Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                                Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                                Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                                Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                                Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                                Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                                Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                                Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                                Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                                Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                                Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                                Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                                Binary Input 58 (use Object Identifier for RT or CSC)

                                Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                                Binary Input 58 (use Object Identifier for FAU)

                                Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                                Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                                Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                                Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                                Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                                Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                                Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                                Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                                Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                                Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                                Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                                Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                                Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                                Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                                Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                                Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                                Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                                Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                                Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                                Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                                Table 10 Diagnostics Binary Input (continued)

                                Object Identifier(a) Object Name Description

                                ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                Object Data Points and Diagnostic Data Points

                                Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                Binary Input 86 (use Object Identifier for RT I-pak II)

                                Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                Binary Input 121 (use Object Identifier for RT)

                                Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                Binary Input 121 (use Object Identifier for FAU)

                                Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                Table 10 Diagnostics Binary Input (continued)

                                Object Identifier(a) Object Name Description

                                34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                Object Data Points and Diagnostic Data Points

                                Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                (a) Object States Inactive = normal and Active = foreign language specific

                                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                Object Identifier(a) Object Name Description

                                Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                Table 10 Diagnostics Binary Input (continued)

                                Object Identifier(a) Object Name Description

                                ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                Object Data Points and Diagnostic Data Points

                                Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                Object Identifier(a) Object Name Description

                                36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                Object Data Points and Diagnostic Data Points

                                Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                Object Identifier(a) Object Name Description

                                ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                Object Data Points and Diagnostic Data Points

                                Binary Output 16 Humidification Command Command the operating state of the humidification system

                                NC 3 HVAC-Advisory HVAC-Advisory

                                NC 1 HVAC-Critical HVAC-Critical

                                NC 4 HVAC-Information HVAC-Information

                                NC 2 HVAC-Service Required HVAC-Service Required

                                Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                Object Identifier(a) Object Name Description

                                38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                Object Data Points and Diagnostic Data Points

                                Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                Binary Input 3 Unit Status Indicates the current state of the unit

                                Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                Object Identifier(a) Object Name Description

                                Table 12 Diagnostic Objects Sorted by Object Name

                                Object Identifier(a) Object Name ValueRange Description

                                BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                Object Data Points and Diagnostic Data Points

                                BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                Object Identifier(a) Object Name ValueRange Description

                                40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                Object Data Points and Diagnostic Data Points

                                BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                Object Identifier(a) Object Name ValueRange Description

                                ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                Object Data Points and Diagnostic Data Points

                                BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                BI 121 (use Object Identifier for RT)

                                Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                BI 58 (use Object Identifier for RT or CSC)

                                Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                BI 31 (use Object Identifier for RT CSC)

                                Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                BI 121 (use Object Identifier for FAU)

                                Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                B1 31 (use Object Identifier for FAU)

                                Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                Object Identifier(a) Object Name ValueRange Description

                                42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                Object Data Points and Diagnostic Data Points

                                BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                1 = active Diagnostic Vel Press Sensor (Rear)

                                BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                Object Identifier(a) Object Name ValueRange Description

                                ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                Object Data Points and Diagnostic Data Points

                                BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                BI 58 (use Object Identifier for FAU)

                                Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                (a) BI=Binary Input

                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                Object Identifier(a) Object Name ValueRange Description

                                44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                Additional Resources

                                Additional Resources

                                Use the following documents and links as additional resources

                                bull Product support online

                                bull wwwbacnetorg

                                bull wwwbacnetassociationorg

                                bull wwwashraeorg

                                bull Tracer TU Help online

                                bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                Note For further assistance contact your local Trane sales office

                                ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                Glossary

                                A

                                ASHRAE

                                See American Society of Heating Refrigeration and Air-conditioning Engineers

                                American Society of Heating Refrigeration and Air-

                                conditioning Engineers

                                An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                BBACnettrade

                                See Building Automation Control network

                                BACnet interoperability building blocks

                                A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                BACnet object

                                An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                baud rate

                                The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                BIBB

                                See BACnet interoperability building blocks

                                Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                advocates BACnet protocol for use in system-level control devices

                                device

                                A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                Device ID

                                The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                Iinteroperability

                                The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                Pprotocol

                                A set of rules (language) that governs the exchange of data over a digital communications system

                                S

                                stand-alone operation

                                Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                wwwtranecom

                                For more information contact your local Trane office or e-mail us at comforttranecom

                                Literature Order Number ACC-SVP01B-EN

                                Date September 2009

                                Supersedes ACC-SVP01A-EN

                                Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                • Table of Contents
                                • Overview
                                • Ordering Numbers
                                • BACnet Protocol
                                • BCI-I Configuration
                                  • Overview
                                  • Starting a Session of Tracer TU and Direct Connection
                                  • Reset to Factory Default
                                  • IP Units Configuration
                                  • BACnet Object Configuration
                                  • Change Baud Rate
                                  • Change Device ID
                                  • Stand-alone or BAS Operation
                                    • IntelliPak Control Configuration
                                    • BAS Unit Control
                                    • Periodic Update of BAS Values
                                    • BAS Communication Failure
                                      • InputOutput Commands and Calculations
                                        • System Control Command
                                        • Filter Timer Reset Command
                                        • Diagnostics Reset Command
                                        • Setpoint Calculations
                                        • Timestamp Configuration
                                            • BCI IntelliPak Rotary Switches and LEDs
                                              • Rotary Switches
                                              • LEDs Description Behavior and Troubleshooting
                                              • 24 Vac Measurement
                                              • Ground Measurements
                                                • BACnet Data Points and Configuration Property Definitions
                                                  • BACnet Protocol Implementation Conformance Statement (PICS)
                                                    • Standardized Device Profile (Annex L)
                                                    • Interoperability Building Blocks (Annex K)
                                                    • Segmentation Capability
                                                    • Object Types
                                                      • BACnet Protocol
                                                        • Data Link Layer Options
                                                        • Device Address Binding
                                                        • Networking Options
                                                        • Character Sets
                                                            • Object Data Points and Diagnostic Data Points
                                                            • Additional Resources
                                                            • Glossary

                                  ACC-SVP01B-EN bull BCI-I Integration Guide 17

                                  BACnet Data Points and Configuration Property Definitions

                                  BACnet Data Points and Configuration Property

                                  Definitions

                                  The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MSTP This section includes information about

                                  bull BACnet protocol implementation conformance statement (PICS)

                                  bull Object types descriptions and configuration (refer to Table 2 p 19)

                                  bull BACnet protocol data link layers device address binding networking options and character sets

                                  bull Object data points and configurations

                                  BACnet Protocol Implementation Conformance Statement (PICS)

                                  Standardized Device Profile (Annex L)

                                  Interoperability Building Blocks (Annex K)

                                  Profile Description Supported Profile

                                  BACnet Advanced Application Controller (B-AAC)

                                  BACnet Application Specific Controller (B-ASC)

                                  BACnet Building Controller (B-BC)

                                  BACnet Operator Workstation (B-OWS)

                                  BACnet Smart Actuator (B-SA)

                                  BACnet Smart Sensor (B-SS)

                                  Data Sharing Description Supported BIBB

                                  Data Sharing-COV-B (DS-COV-B)

                                  Data Sharing-ReadProperty-A (DS-RP-A)

                                  Data Sharing-ReadProperty-B (DS-RP-B)

                                  Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)

                                  Data Sharing-WriteProperty-A (DS-WP-A)

                                  Data Sharing-WriteProperty-B (DS-WP-B)

                                  Data Sharing-WritePropertyMultiple-B (DS-WPM-B)

                                  Alarm and Event Management Description Supported BIBB

                                  Alarm and Event-ACKI-B (AE-ACK-B)

                                  Alarm and Event-Alarm Summary-B (AE-ASUM-B)

                                  Alarm and Event-Enrollment Summary-B (AE-ESUM-B)

                                  Alarm and Event-Information-B (AE-INFO-B)

                                  Alarm and Event-Notification Internal-B (AE-N-I-B)

                                  18 ACC-SVP01B-EN bull BCI-I Integration Guide

                                  BACnet Data Points and Configuration Property Definitions

                                  Segmentation Capability

                                  Trending Description Supported BIBB

                                  Trending-Automated Trend Retrieval-B (T-ATR-B)

                                  Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

                                  Device Management Description Supported BIBB

                                  Device Management-Backup and Restore-B (DM-BR-B)

                                  Device Management-Device Communication Control-B (DM-DCC-B)

                                  Device Management-Dynamic Device Binding-A (DM-DDB-A)

                                  Device Management-Dynamic Device Binding-B (DM-DDB-B)

                                  Device Management-Dynamic Object Binding-B (DM-DOB-B)

                                  Device Management-List Manipulation-B (DM-LM-B)

                                  Device Management-Object Creation and Deletion-B (DM-OCD-B)

                                  Device Management-Private Transfer-A (DM-PT-A)

                                  Device Management-Private Transfer-B (DM-PT-B)

                                  Device Management-Reinitialize Device-B (DM-RD-B)

                                  Device Management-TimeSynchronization-B (DM-TS-B)

                                  Segmentation Description Supported Segment

                                  Segmented Requests Window Size 1

                                  Segmented Responses Window Size 1

                                  ACC-SVP01B-EN bull BCI-I Integration Guide 19

                                  BACnet Data Points and Configuration Property Definitions

                                  Object Types

                                  Table 2 Descriptions and configurations

                                  Object Type Required Properties Read Properties Written(a) Optional Properties Read

                                  Ability to Create

                                  Ability to Delete

                                  Analog Input

                                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                                  bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                                  bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                  Yes Yes only user created objects

                                  Analog Output

                                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

                                  bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                                  bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                  Yes Yes only user created objects

                                  Analog Value

                                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                                  bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                                  bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                  Yes Yes only user created objects

                                  Binary Input

                                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                                  bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                                  bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                                  Yes Yes only user created objects

                                  20 ACC-SVP01B-EN bull BCI-I Integration Guide

                                  BACnet Data Points and Configuration Property Definitions

                                  Binary Output

                                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

                                  bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

                                  bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                                  Yes Yes only user created objects

                                  Binary Value

                                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                                  bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                                  bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                                  Yes Yes only user created objects

                                  Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

                                  bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

                                  bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

                                  None None

                                  Event Enrollment Object

                                  bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

                                  bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

                                  bull None Yes Yes only user created objects

                                  Table 2 Descriptions and configurations (continued)

                                  Object Type Required Properties Read Properties Written(a) Optional Properties Read

                                  Ability to Create

                                  Ability to Delete

                                  ACC-SVP01B-EN bull BCI-I Integration Guide 21

                                  BACnet Data Points and Configuration Property Definitions

                                  Multistate Input

                                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                                  bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                                  bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                  Yes Yes only user created objects

                                  Multistate Output

                                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

                                  bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

                                  bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                  Yes Yes only user created objects

                                  Multistate Value

                                  bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                                  bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                                  bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                  Yes Yes only user created objects

                                  Notification Class

                                  bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

                                  bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

                                  None Yes Yes only user created objects

                                  Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

                                  bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

                                  bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

                                  Yes Yes only user created objects

                                  (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

                                  Table 2 Descriptions and configurations (continued)

                                  Object Type Required Properties Read Properties Written(a) Optional Properties Read

                                  Ability to Create

                                  Ability to Delete

                                  22 ACC-SVP01B-EN bull BCI-I Integration Guide

                                  BACnet Data Points and Configuration Property Definitions

                                  BACnet Protocol

                                  Data Link Layer Options

                                  Device Address Binding

                                  Networking Options

                                  Data Link Layer Description Supported Option

                                  ANSIATA 8781 25 Mb ARCNET (Clause 8)

                                  ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

                                  BACnet IP (Annex J)

                                  BACnet IP (Annex J) Foreign Device

                                  ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

                                  LonTalk (Clause 11) Medium

                                  MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

                                  MSTP Slave (Clause 9) Baud Rate(s)

                                  Other

                                  Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

                                  Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

                                  Device Address Binding Supported

                                  Static Device Binding Supported

                                  Networking DescriptionsSupported

                                  Option

                                  Annex H BACnet Tunneling

                                  BACnetIP Broadcast Management Device (BBMD)

                                  Does the BBMD Support Registrations by Foreign Devices

                                  Router

                                  ACC-SVP01B-EN bull BCI-I Integration Guide 23

                                  BACnet Data Points and Configuration Property Definitions

                                  Character Sets

                                  Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

                                  Character Set Descriptions Supported

                                  ANSI X34

                                  IBMMicrosoft DBCS

                                  ISO 10646 (UCS-4)

                                  ISO 10646 (UCS2)

                                  ISO 8859-1

                                  JIS C 6226

                                  24 ACC-SVP01B-EN bull BCI-I Integration Guide

                                  Object Data Points and Diagnostic Data Points

                                  Object Data Points and Diagnostic Data Points

                                  For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

                                  Table 3 Analog Output

                                  Object Identifier Object Name Description Units Valid Range

                                  Refresh Rate

                                  (Sec)

                                  Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

                                  Percent (98) 0 to 100 NA

                                  Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

                                  Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

                                  Degrees-Fahrenheit (64) 500 to 900 NA

                                  Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

                                  BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

                                  Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

                                  Degrees-Fahrenheit (64) 400 to 900 NA

                                  Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

                                  Degrees-Fahrenheit (64) 400 to 1800 NA

                                  Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

                                  070 to 510 (Ipak II) NA

                                  Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

                                  003 to 030-002 to 030 (enhanced StatiTrac)

                                  NA

                                  Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

                                  -028 to 050-067 to 067 (enhanced StatiTrac)

                                  900

                                  Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                  Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                  Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

                                  00 to 79 (Ipak II) 900

                                  Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                  Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

                                  Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

                                  Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

                                  Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

                                  Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                  Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                  Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

                                  Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

                                  Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

                                  ACC-SVP01B-EN bull BCI-I Integration Guide 25

                                  Object Data Points and Diagnostic Data Points

                                  Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                                  Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                                  Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                                  Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                                  Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                                  Cooling temperature setpoint used for control in unoccupied mode

                                  Degrees-Fahrenheit (64) 520 to 880 NA

                                  Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                                  Heating temperature setpoint used for control in unoccupied mode

                                  Degrees-Fahrenheit (64) 500 to 900 NA

                                  Table 4 Analog Input

                                  Object Identifier Object Name Description Units (Listed Are Defaults)

                                  Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                                  Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                                  Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                                  Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                                  Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                                  Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                                  Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                                  Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                                  Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                                  Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                                  Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                                  Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                                  Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                                  Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                                  Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                                  Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                                  Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                                  Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                                  Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                                  Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                                  Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                                  Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                                  Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                                  Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                  Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                  Table 3 Analog Output (continued)

                                  Object Identifier Object Name Description Units Valid Range

                                  Refresh Rate

                                  (Sec)

                                  26 ACC-SVP01B-EN bull BCI-I Integration Guide

                                  Object Data Points and Diagnostic Data Points

                                  Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                                  Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                  Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                  Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                                  Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                                  Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                                  Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                                  Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                                  Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                  Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                  Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                  Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                  Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                                  Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                                  Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                                  Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                                  Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                                  Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                                  Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                                  Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                                  Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                                  Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                  Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                  Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                                  The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                                  Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                                  The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                                  Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                                  Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                                  Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                                  Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                                  Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                                  Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                                  Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                                  Table 4 Analog Input (continued)

                                  Object Identifier Object Name Description Units (Listed Are Defaults)

                                  ACC-SVP01B-EN bull BCI-I Integration Guide 27

                                  Object Data Points and Diagnostic Data Points

                                  Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                                  Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                                  Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                                  Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                                  The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                                  Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                                  Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                                  Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                                  Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                                  Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                                  Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                  Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                  Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                                  Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                                  Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                                  Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                                  Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                                  Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                                  Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                                  Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                                  Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                                  Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                                  Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                                  Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                                  Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                                  Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                                  Table 5 Analog Value

                                  Object Identifier Object Name Description Units Valid Range

                                  Analog Value 1 Filter Runtime Hours Setpoint

                                  The setpoint value used by the filter run hours calculation

                                  Hours (71) 0 to 10000

                                  Table 4 Analog Input (continued)

                                  Object Identifier Object Name Description Units (Listed Are Defaults)

                                  28 ACC-SVP01B-EN bull BCI-I Integration Guide

                                  Object Data Points and Diagnostic Data Points

                                  Table 6 Multistate Output

                                  BCI-I Object Identifier Object Name Description Object States

                                  Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                                  Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                  1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                                  Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                                  Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                  1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                  Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                  1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                  Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                  1 = Flow2 = No Flow3 = Auto

                                  Table 7 Multistate Input

                                  BCI-I Object Identifier Object Name Description Object States

                                  Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                  1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                                  Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                  1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                                  Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                  1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                                  Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                  1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                                  ACC-SVP01B-EN bull BCI-I Integration Guide 29

                                  Object Data Points and Diagnostic Data Points

                                  Multi-State Input 15 Economizer Decision Method

                                  Unit method to determine when the economizer system is enabled

                                  1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                                  Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                                  Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                                  Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                  1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                  Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                  1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                  Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                  1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                                  Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                  1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                  Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                  1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                  Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                  1 = Idle2 = On3 = Cancel

                                  Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                  1 = Off2 = On3 = Not Present

                                  Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                  1 = Off2 = On3 = Not Present

                                  Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                  1 = Off2 = On3 = Not Present

                                  Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                  1 = Off|2 = On3 = Not Present

                                  Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                  1 = Off2 = On3 = Not Present

                                  Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                  1 = Off2 = On3 = Not Present

                                  Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                  1 = Off2 = On3 = Not Present

                                  Table 7 Multistate Input (continued)

                                  BCI-I Object Identifier Object Name Description Object States

                                  30 ACC-SVP01B-EN bull BCI-I Integration Guide

                                  Object Data Points and Diagnostic Data Points

                                  Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                  1 = Off2 = On3 = Not Present

                                  Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                  1 = Off2 = On3 = Not Present

                                  Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                                  Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                                  Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                                  Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                                  Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                  1 = Off2 = On3 = Not Present

                                  Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                  1= Off2= On3= Not Present

                                  Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                                  Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                                  Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                                  Multi-State Input 43 Outdoor Air Damper Status

                                  Indicates the operating state of the outdoor damper

                                  1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                                  Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                  1 = Disabled2 = Enabled3 = Not Present

                                  Table 8 Binary Output

                                  Object Identifier Object Name DescriptionRelinquish Default Object States

                                  Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                                  Active = BAS Control

                                  Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                                  Active = Heating Locked Out

                                  Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                                  Active = Cooling Locked Out

                                  Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                                  Active = Enabled

                                  Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                                  Active = On

                                  Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                                  Inactive Inactive = DisabledActive = Enabled

                                  Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                                  Active = Reset

                                  Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                                  Active = Reset

                                  Table 7 Multistate Input (continued)

                                  BCI-I Object Identifier Object Name Description Object States

                                  ACC-SVP01B-EN bull BCI-I Integration Guide 31

                                  Object Data Points and Diagnostic Data Points

                                  Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                                  Active = Auto

                                  Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                                  Active = Auto

                                  Table 9 Binary Input

                                  Object Identifier Object Name Description Object States

                                  Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                  Inactive = Standalone controlActive = BAS control

                                  Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                  Inactive = NormalActive = Locked Out

                                  Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                                  Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                  Inactive = AutoActive = Open

                                  Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                  Inactive = InactiveActive = Active

                                  Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                                  Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                                  Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                  Inactive = DisabledActive = Enabled

                                  Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                  Inactive = DisabledActive = Enabled

                                  Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                  Inactive = InactiveActive = Active

                                  Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                  Inactive = No FlowActive = Flow

                                  Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                  Inactive = InactiveActive = Active

                                  Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                  Inactive = InactiveActive = Active

                                  Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                  Inactive = InactiveActive = Active

                                  Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                                  The status of evaporator frost protection function for circuit 1

                                  Inactive = InactiveActive = Active

                                  Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                                  The status of evaporator frost protection function for circuit 2

                                  Inactive = InactiveActive = Active

                                  Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                                  The status of evaporator frost protection function for circuit 3

                                  Inactive = InactiveActive = Active

                                  Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                                  The status of evaporator frost protection function for circuit 4

                                  Inactive = InactiveActive = Active

                                  Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                  Inactive = De-energizedActive = Energized

                                  Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                  Inactive = InactiveActive = Active

                                  Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                  Inactive = ClosedActive = Open

                                  Table 10 Diagnostics Binary Input

                                  Object Identifier(a) Object Name Description

                                  Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                                  Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                                  Binary Input 31 (use Object Identifier for RT or CSC)

                                  Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                                  Binary Input 31 (use Object Identifier for FAU)

                                  Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                                  Table 8 Binary Output

                                  Object Identifier Object Name DescriptionRelinquish Default Object States

                                  32 ACC-SVP01B-EN bull BCI-I Integration Guide

                                  Object Data Points and Diagnostic Data Points

                                  Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                                  Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                                  Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                                  Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                                  Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                                  Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                                  Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                                  Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                                  Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                                  Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                  Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                  Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                                  Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                                  Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                                  Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                                  Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                                  Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                                  Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                                  Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                                  Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                                  Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                                  Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                                  Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                                  Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                                  Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                                  Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                                  Binary Input 58 (use Object Identifier for RT or CSC)

                                  Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                                  Binary Input 58 (use Object Identifier for FAU)

                                  Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                                  Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                                  Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                                  Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                                  Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                                  Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                                  Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                                  Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                                  Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                                  Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                                  Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                                  Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                                  Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                                  Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                                  Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                                  Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                                  Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                                  Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                                  Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                                  Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                                  Table 10 Diagnostics Binary Input (continued)

                                  Object Identifier(a) Object Name Description

                                  ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                  Object Data Points and Diagnostic Data Points

                                  Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                  Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                  Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                  Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                  Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                  Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                  Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                  Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                  Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                  Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                  Binary Input 86 (use Object Identifier for RT I-pak II)

                                  Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                  Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                  Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                  Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                  Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                  Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                  Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                  Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                  Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                  Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                  Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                  Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                  Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                  Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                  Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                  Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                  Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                  Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                  Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                  Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                  Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                  Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                  Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                  Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                  Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                  Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                  Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                  Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                  Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                  Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                  Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                  Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                  Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                  Binary Input 121 (use Object Identifier for RT)

                                  Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                  Binary Input 121 (use Object Identifier for FAU)

                                  Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                  Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                  Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                  Table 10 Diagnostics Binary Input (continued)

                                  Object Identifier(a) Object Name Description

                                  34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                  Object Data Points and Diagnostic Data Points

                                  Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                  Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                  Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                  Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                  Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                  Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                  Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                  Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                  Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                  Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                  Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                  Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                  Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                  Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                  Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                  Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                  Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                  Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                  Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                  Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                  Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                  Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                  Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                  Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                  Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                  Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                  (a) Object States Inactive = normal and Active = foreign language specific

                                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                  Object Identifier(a) Object Name Description

                                  Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                  Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                  Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                  Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                  Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                  Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                  Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                  Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                  Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                  Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                  Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                  Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                  Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                  Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                  Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                  Table 10 Diagnostics Binary Input (continued)

                                  Object Identifier(a) Object Name Description

                                  ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                  Object Data Points and Diagnostic Data Points

                                  Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                  Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                  Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                  Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                  Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                  Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                  Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                  Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                  Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                  Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                  Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                  Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                  Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                  Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                  Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                  Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                  Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                  Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                  Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                  Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                  Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                  Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                  Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                  Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                  Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                  Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                  Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                  Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                  Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                  Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                  Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                  Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                  Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                  Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                  Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                  Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                  Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                  Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                  Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                  Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                  Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                  Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                  Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                  Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                  Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                  Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                  Object Identifier(a) Object Name Description

                                  36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                  Object Data Points and Diagnostic Data Points

                                  Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                  Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                  Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                  Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                  Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                  Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                  Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                  Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                  Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                  Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                  Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                  Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                  Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                  Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                  Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                  Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                  Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                  Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                  Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                  Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                  Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                  Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                  Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                  Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                  Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                  Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                  Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                  Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                  Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                  Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                  Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                  Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                  Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                  Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                  Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                  Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                  Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                  Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                  Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                  Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                  Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                  Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                  Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                  Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                  Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                  Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                  Object Identifier(a) Object Name Description

                                  ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                  Object Data Points and Diagnostic Data Points

                                  Binary Output 16 Humidification Command Command the operating state of the humidification system

                                  NC 3 HVAC-Advisory HVAC-Advisory

                                  NC 1 HVAC-Critical HVAC-Critical

                                  NC 4 HVAC-Information HVAC-Information

                                  NC 2 HVAC-Service Required HVAC-Service Required

                                  Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                  Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                  Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                  Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                  Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                  Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                  Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                  Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                  Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                  Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                  Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                  Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                  Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                  Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                  Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                  Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                  Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                  Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                  Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                  Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                  Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                  Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                  Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                  Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                  Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                  Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                  Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                  Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                  Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                  Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                  Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                  Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                  Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                  Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                  Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                  Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                  Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                  Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                  Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                  Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                  Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                  Object Identifier(a) Object Name Description

                                  38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                  Object Data Points and Diagnostic Data Points

                                  Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                  Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                  Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                  Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                  Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                  Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                  Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                  Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                  Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                  Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                  Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                  Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                  Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                  Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                  Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                  Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                  Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                  Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                  Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                  Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                  Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                  Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                  Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                  Binary Input 3 Unit Status Indicates the current state of the unit

                                  Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                  Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                  Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                  Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                  Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                  Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                  Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                  (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                  Object Identifier(a) Object Name Description

                                  Table 12 Diagnostic Objects Sorted by Object Name

                                  Object Identifier(a) Object Name ValueRange Description

                                  BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                  BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                  ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                  Object Data Points and Diagnostic Data Points

                                  BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                  BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                  BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                  BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                  BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                  BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                  BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                  BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                  BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                  BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                  BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                  BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                  BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                  BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                  BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                  BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                  BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                  BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                  BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                  BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                  BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                  BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                  BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                  BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                  BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                  BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                  BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                  BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                  BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                  Object Identifier(a) Object Name ValueRange Description

                                  40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                  Object Data Points and Diagnostic Data Points

                                  BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                  BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                  BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                  BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                  BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                  BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                  BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                  BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                  BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                  BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                  BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                  BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                  BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                  BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                  BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                  BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                  BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                  BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                  BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                  BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                  BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                  BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                  BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                  BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                  BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                  BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                  BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                  BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                  BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                  Object Identifier(a) Object Name ValueRange Description

                                  ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                  Object Data Points and Diagnostic Data Points

                                  BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                  BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                  BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                  BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                  BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                  BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                  BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                  BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                  BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                  BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                  BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                  BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                  BI 121 (use Object Identifier for RT)

                                  Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                  BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                  BI 58 (use Object Identifier for RT or CSC)

                                  Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                  BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                  BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                  BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                  BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                  BI 31 (use Object Identifier for RT CSC)

                                  Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                  BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                  BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                  BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                  BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                  BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                  BI 121 (use Object Identifier for FAU)

                                  Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                  B1 31 (use Object Identifier for FAU)

                                  Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                  BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                  BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                  Object Identifier(a) Object Name ValueRange Description

                                  42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                  Object Data Points and Diagnostic Data Points

                                  BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                  BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                  BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                  BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                  BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                  BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                  BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                  BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                  BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                  BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                  BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                  BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                  BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                  BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                  BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                  BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                  BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                  BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                  BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                  BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                  BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                  BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                  BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                  1 = active Diagnostic Vel Press Sensor (Rear)

                                  BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                  Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                  BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                  BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                  BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                  BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                  BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                  Object Identifier(a) Object Name ValueRange Description

                                  ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                  Object Data Points and Diagnostic Data Points

                                  BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                  BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                  BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                  BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                  BI 58 (use Object Identifier for FAU)

                                  Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                  (a) BI=Binary Input

                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                  Object Identifier(a) Object Name ValueRange Description

                                  44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                  Additional Resources

                                  Additional Resources

                                  Use the following documents and links as additional resources

                                  bull Product support online

                                  bull wwwbacnetorg

                                  bull wwwbacnetassociationorg

                                  bull wwwashraeorg

                                  bull Tracer TU Help online

                                  bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                  bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                  Note For further assistance contact your local Trane sales office

                                  ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                  Glossary

                                  A

                                  ASHRAE

                                  See American Society of Heating Refrigeration and Air-conditioning Engineers

                                  American Society of Heating Refrigeration and Air-

                                  conditioning Engineers

                                  An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                  BBACnettrade

                                  See Building Automation Control network

                                  BACnet interoperability building blocks

                                  A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                  BACnet object

                                  An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                  baud rate

                                  The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                  BIBB

                                  See BACnet interoperability building blocks

                                  Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                  advocates BACnet protocol for use in system-level control devices

                                  device

                                  A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                  Device ID

                                  The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                  Iinteroperability

                                  The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                  Pprotocol

                                  A set of rules (language) that governs the exchange of data over a digital communications system

                                  S

                                  stand-alone operation

                                  Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                  wwwtranecom

                                  For more information contact your local Trane office or e-mail us at comforttranecom

                                  Literature Order Number ACC-SVP01B-EN

                                  Date September 2009

                                  Supersedes ACC-SVP01A-EN

                                  Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                  • Table of Contents
                                  • Overview
                                  • Ordering Numbers
                                  • BACnet Protocol
                                  • BCI-I Configuration
                                    • Overview
                                    • Starting a Session of Tracer TU and Direct Connection
                                    • Reset to Factory Default
                                    • IP Units Configuration
                                    • BACnet Object Configuration
                                    • Change Baud Rate
                                    • Change Device ID
                                    • Stand-alone or BAS Operation
                                      • IntelliPak Control Configuration
                                      • BAS Unit Control
                                      • Periodic Update of BAS Values
                                      • BAS Communication Failure
                                        • InputOutput Commands and Calculations
                                          • System Control Command
                                          • Filter Timer Reset Command
                                          • Diagnostics Reset Command
                                          • Setpoint Calculations
                                          • Timestamp Configuration
                                              • BCI IntelliPak Rotary Switches and LEDs
                                                • Rotary Switches
                                                • LEDs Description Behavior and Troubleshooting
                                                • 24 Vac Measurement
                                                • Ground Measurements
                                                  • BACnet Data Points and Configuration Property Definitions
                                                    • BACnet Protocol Implementation Conformance Statement (PICS)
                                                      • Standardized Device Profile (Annex L)
                                                      • Interoperability Building Blocks (Annex K)
                                                      • Segmentation Capability
                                                      • Object Types
                                                        • BACnet Protocol
                                                          • Data Link Layer Options
                                                          • Device Address Binding
                                                          • Networking Options
                                                          • Character Sets
                                                              • Object Data Points and Diagnostic Data Points
                                                              • Additional Resources
                                                              • Glossary

                                    18 ACC-SVP01B-EN bull BCI-I Integration Guide

                                    BACnet Data Points and Configuration Property Definitions

                                    Segmentation Capability

                                    Trending Description Supported BIBB

                                    Trending-Automated Trend Retrieval-B (T-ATR-B)

                                    Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)

                                    Device Management Description Supported BIBB

                                    Device Management-Backup and Restore-B (DM-BR-B)

                                    Device Management-Device Communication Control-B (DM-DCC-B)

                                    Device Management-Dynamic Device Binding-A (DM-DDB-A)

                                    Device Management-Dynamic Device Binding-B (DM-DDB-B)

                                    Device Management-Dynamic Object Binding-B (DM-DOB-B)

                                    Device Management-List Manipulation-B (DM-LM-B)

                                    Device Management-Object Creation and Deletion-B (DM-OCD-B)

                                    Device Management-Private Transfer-A (DM-PT-A)

                                    Device Management-Private Transfer-B (DM-PT-B)

                                    Device Management-Reinitialize Device-B (DM-RD-B)

                                    Device Management-TimeSynchronization-B (DM-TS-B)

                                    Segmentation Description Supported Segment

                                    Segmented Requests Window Size 1

                                    Segmented Responses Window Size 1

                                    ACC-SVP01B-EN bull BCI-I Integration Guide 19

                                    BACnet Data Points and Configuration Property Definitions

                                    Object Types

                                    Table 2 Descriptions and configurations

                                    Object Type Required Properties Read Properties Written(a) Optional Properties Read

                                    Ability to Create

                                    Ability to Delete

                                    Analog Input

                                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                                    bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                                    bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                    Yes Yes only user created objects

                                    Analog Output

                                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

                                    bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                                    bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                    Yes Yes only user created objects

                                    Analog Value

                                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                                    bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                                    bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                    Yes Yes only user created objects

                                    Binary Input

                                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                                    bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                                    bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                                    Yes Yes only user created objects

                                    20 ACC-SVP01B-EN bull BCI-I Integration Guide

                                    BACnet Data Points and Configuration Property Definitions

                                    Binary Output

                                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

                                    bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

                                    bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                                    Yes Yes only user created objects

                                    Binary Value

                                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                                    bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                                    bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                                    Yes Yes only user created objects

                                    Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

                                    bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

                                    bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

                                    None None

                                    Event Enrollment Object

                                    bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

                                    bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

                                    bull None Yes Yes only user created objects

                                    Table 2 Descriptions and configurations (continued)

                                    Object Type Required Properties Read Properties Written(a) Optional Properties Read

                                    Ability to Create

                                    Ability to Delete

                                    ACC-SVP01B-EN bull BCI-I Integration Guide 21

                                    BACnet Data Points and Configuration Property Definitions

                                    Multistate Input

                                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                                    bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                                    bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                    Yes Yes only user created objects

                                    Multistate Output

                                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

                                    bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

                                    bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                    Yes Yes only user created objects

                                    Multistate Value

                                    bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                                    bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                                    bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                    Yes Yes only user created objects

                                    Notification Class

                                    bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

                                    bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

                                    None Yes Yes only user created objects

                                    Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

                                    bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

                                    bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

                                    Yes Yes only user created objects

                                    (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

                                    Table 2 Descriptions and configurations (continued)

                                    Object Type Required Properties Read Properties Written(a) Optional Properties Read

                                    Ability to Create

                                    Ability to Delete

                                    22 ACC-SVP01B-EN bull BCI-I Integration Guide

                                    BACnet Data Points and Configuration Property Definitions

                                    BACnet Protocol

                                    Data Link Layer Options

                                    Device Address Binding

                                    Networking Options

                                    Data Link Layer Description Supported Option

                                    ANSIATA 8781 25 Mb ARCNET (Clause 8)

                                    ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

                                    BACnet IP (Annex J)

                                    BACnet IP (Annex J) Foreign Device

                                    ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

                                    LonTalk (Clause 11) Medium

                                    MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

                                    MSTP Slave (Clause 9) Baud Rate(s)

                                    Other

                                    Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

                                    Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

                                    Device Address Binding Supported

                                    Static Device Binding Supported

                                    Networking DescriptionsSupported

                                    Option

                                    Annex H BACnet Tunneling

                                    BACnetIP Broadcast Management Device (BBMD)

                                    Does the BBMD Support Registrations by Foreign Devices

                                    Router

                                    ACC-SVP01B-EN bull BCI-I Integration Guide 23

                                    BACnet Data Points and Configuration Property Definitions

                                    Character Sets

                                    Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

                                    Character Set Descriptions Supported

                                    ANSI X34

                                    IBMMicrosoft DBCS

                                    ISO 10646 (UCS-4)

                                    ISO 10646 (UCS2)

                                    ISO 8859-1

                                    JIS C 6226

                                    24 ACC-SVP01B-EN bull BCI-I Integration Guide

                                    Object Data Points and Diagnostic Data Points

                                    Object Data Points and Diagnostic Data Points

                                    For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

                                    Table 3 Analog Output

                                    Object Identifier Object Name Description Units Valid Range

                                    Refresh Rate

                                    (Sec)

                                    Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

                                    Percent (98) 0 to 100 NA

                                    Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

                                    Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

                                    Degrees-Fahrenheit (64) 500 to 900 NA

                                    Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

                                    BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

                                    Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

                                    Degrees-Fahrenheit (64) 400 to 900 NA

                                    Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

                                    Degrees-Fahrenheit (64) 400 to 1800 NA

                                    Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

                                    070 to 510 (Ipak II) NA

                                    Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

                                    003 to 030-002 to 030 (enhanced StatiTrac)

                                    NA

                                    Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

                                    -028 to 050-067 to 067 (enhanced StatiTrac)

                                    900

                                    Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                    Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                    Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

                                    00 to 79 (Ipak II) 900

                                    Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                    Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

                                    Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

                                    Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

                                    Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

                                    Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                    Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                    Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

                                    Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

                                    Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

                                    ACC-SVP01B-EN bull BCI-I Integration Guide 25

                                    Object Data Points and Diagnostic Data Points

                                    Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                                    Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                                    Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                                    Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                                    Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                                    Cooling temperature setpoint used for control in unoccupied mode

                                    Degrees-Fahrenheit (64) 520 to 880 NA

                                    Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                                    Heating temperature setpoint used for control in unoccupied mode

                                    Degrees-Fahrenheit (64) 500 to 900 NA

                                    Table 4 Analog Input

                                    Object Identifier Object Name Description Units (Listed Are Defaults)

                                    Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                                    Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                                    Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                                    Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                                    Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                                    Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                                    Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                                    Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                                    Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                                    Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                                    Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                                    Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                                    Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                                    Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                                    Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                                    Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                                    Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                                    Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                                    Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                                    Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                                    Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                                    Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                                    Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                                    Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                    Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                    Table 3 Analog Output (continued)

                                    Object Identifier Object Name Description Units Valid Range

                                    Refresh Rate

                                    (Sec)

                                    26 ACC-SVP01B-EN bull BCI-I Integration Guide

                                    Object Data Points and Diagnostic Data Points

                                    Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                                    Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                    Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                    Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                                    Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                                    Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                                    Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                                    Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                                    Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                    Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                    Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                    Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                    Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                                    Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                                    Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                                    Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                                    Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                                    Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                                    Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                                    Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                                    Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                                    Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                    Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                    Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                                    The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                                    Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                                    The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                                    Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                                    Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                                    Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                                    Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                                    Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                                    Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                                    Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                                    Table 4 Analog Input (continued)

                                    Object Identifier Object Name Description Units (Listed Are Defaults)

                                    ACC-SVP01B-EN bull BCI-I Integration Guide 27

                                    Object Data Points and Diagnostic Data Points

                                    Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                                    Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                                    Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                                    Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                                    The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                                    Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                                    Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                                    Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                                    Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                                    Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                                    Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                    Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                    Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                                    Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                                    Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                                    Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                                    Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                                    Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                                    Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                                    Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                                    Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                                    Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                                    Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                                    Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                                    Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                                    Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                                    Table 5 Analog Value

                                    Object Identifier Object Name Description Units Valid Range

                                    Analog Value 1 Filter Runtime Hours Setpoint

                                    The setpoint value used by the filter run hours calculation

                                    Hours (71) 0 to 10000

                                    Table 4 Analog Input (continued)

                                    Object Identifier Object Name Description Units (Listed Are Defaults)

                                    28 ACC-SVP01B-EN bull BCI-I Integration Guide

                                    Object Data Points and Diagnostic Data Points

                                    Table 6 Multistate Output

                                    BCI-I Object Identifier Object Name Description Object States

                                    Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                                    Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                    1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                                    Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                                    Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                    1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                    Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                    1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                    Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                    1 = Flow2 = No Flow3 = Auto

                                    Table 7 Multistate Input

                                    BCI-I Object Identifier Object Name Description Object States

                                    Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                    1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                                    Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                    1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                                    Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                    1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                                    Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                    1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                                    ACC-SVP01B-EN bull BCI-I Integration Guide 29

                                    Object Data Points and Diagnostic Data Points

                                    Multi-State Input 15 Economizer Decision Method

                                    Unit method to determine when the economizer system is enabled

                                    1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                                    Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                                    Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                                    Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                    1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                    Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                    1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                    Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                    1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                                    Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                    1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                    Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                    1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                    Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                    1 = Idle2 = On3 = Cancel

                                    Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                    1 = Off2 = On3 = Not Present

                                    Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                    1 = Off2 = On3 = Not Present

                                    Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                    1 = Off2 = On3 = Not Present

                                    Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                    1 = Off|2 = On3 = Not Present

                                    Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                    1 = Off2 = On3 = Not Present

                                    Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                    1 = Off2 = On3 = Not Present

                                    Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                    1 = Off2 = On3 = Not Present

                                    Table 7 Multistate Input (continued)

                                    BCI-I Object Identifier Object Name Description Object States

                                    30 ACC-SVP01B-EN bull BCI-I Integration Guide

                                    Object Data Points and Diagnostic Data Points

                                    Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                    1 = Off2 = On3 = Not Present

                                    Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                    1 = Off2 = On3 = Not Present

                                    Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                                    Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                                    Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                                    Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                                    Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                    1 = Off2 = On3 = Not Present

                                    Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                    1= Off2= On3= Not Present

                                    Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                                    Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                                    Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                                    Multi-State Input 43 Outdoor Air Damper Status

                                    Indicates the operating state of the outdoor damper

                                    1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                                    Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                    1 = Disabled2 = Enabled3 = Not Present

                                    Table 8 Binary Output

                                    Object Identifier Object Name DescriptionRelinquish Default Object States

                                    Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                                    Active = BAS Control

                                    Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                                    Active = Heating Locked Out

                                    Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                                    Active = Cooling Locked Out

                                    Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                                    Active = Enabled

                                    Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                                    Active = On

                                    Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                                    Inactive Inactive = DisabledActive = Enabled

                                    Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                                    Active = Reset

                                    Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                                    Active = Reset

                                    Table 7 Multistate Input (continued)

                                    BCI-I Object Identifier Object Name Description Object States

                                    ACC-SVP01B-EN bull BCI-I Integration Guide 31

                                    Object Data Points and Diagnostic Data Points

                                    Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                                    Active = Auto

                                    Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                                    Active = Auto

                                    Table 9 Binary Input

                                    Object Identifier Object Name Description Object States

                                    Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                    Inactive = Standalone controlActive = BAS control

                                    Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                    Inactive = NormalActive = Locked Out

                                    Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                                    Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                    Inactive = AutoActive = Open

                                    Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                    Inactive = InactiveActive = Active

                                    Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                                    Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                                    Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                    Inactive = DisabledActive = Enabled

                                    Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                    Inactive = DisabledActive = Enabled

                                    Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                    Inactive = InactiveActive = Active

                                    Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                    Inactive = No FlowActive = Flow

                                    Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                    Inactive = InactiveActive = Active

                                    Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                    Inactive = InactiveActive = Active

                                    Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                    Inactive = InactiveActive = Active

                                    Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                                    The status of evaporator frost protection function for circuit 1

                                    Inactive = InactiveActive = Active

                                    Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                                    The status of evaporator frost protection function for circuit 2

                                    Inactive = InactiveActive = Active

                                    Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                                    The status of evaporator frost protection function for circuit 3

                                    Inactive = InactiveActive = Active

                                    Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                                    The status of evaporator frost protection function for circuit 4

                                    Inactive = InactiveActive = Active

                                    Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                    Inactive = De-energizedActive = Energized

                                    Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                    Inactive = InactiveActive = Active

                                    Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                    Inactive = ClosedActive = Open

                                    Table 10 Diagnostics Binary Input

                                    Object Identifier(a) Object Name Description

                                    Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                                    Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                                    Binary Input 31 (use Object Identifier for RT or CSC)

                                    Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                                    Binary Input 31 (use Object Identifier for FAU)

                                    Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                                    Table 8 Binary Output

                                    Object Identifier Object Name DescriptionRelinquish Default Object States

                                    32 ACC-SVP01B-EN bull BCI-I Integration Guide

                                    Object Data Points and Diagnostic Data Points

                                    Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                                    Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                                    Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                                    Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                                    Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                                    Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                                    Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                                    Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                                    Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                                    Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                    Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                    Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                                    Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                                    Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                                    Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                                    Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                                    Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                                    Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                                    Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                                    Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                                    Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                                    Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                                    Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                                    Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                                    Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                                    Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                                    Binary Input 58 (use Object Identifier for RT or CSC)

                                    Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                                    Binary Input 58 (use Object Identifier for FAU)

                                    Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                                    Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                                    Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                                    Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                                    Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                                    Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                                    Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                                    Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                                    Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                                    Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                                    Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                                    Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                                    Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                                    Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                                    Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                                    Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                                    Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                                    Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                                    Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                                    Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                                    Table 10 Diagnostics Binary Input (continued)

                                    Object Identifier(a) Object Name Description

                                    ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                    Object Data Points and Diagnostic Data Points

                                    Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                    Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                    Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                    Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                    Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                    Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                    Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                    Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                    Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                    Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                    Binary Input 86 (use Object Identifier for RT I-pak II)

                                    Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                    Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                    Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                    Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                    Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                    Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                    Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                    Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                    Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                    Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                    Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                    Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                    Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                    Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                    Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                    Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                    Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                    Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                    Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                    Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                    Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                    Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                    Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                    Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                    Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                    Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                    Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                    Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                    Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                    Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                    Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                    Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                    Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                    Binary Input 121 (use Object Identifier for RT)

                                    Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                    Binary Input 121 (use Object Identifier for FAU)

                                    Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                    Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                    Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                    Table 10 Diagnostics Binary Input (continued)

                                    Object Identifier(a) Object Name Description

                                    34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                    Object Data Points and Diagnostic Data Points

                                    Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                    Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                    Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                    Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                    Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                    Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                    Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                    Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                    Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                    Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                    Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                    Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                    Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                    Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                    Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                    Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                    Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                    Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                    Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                    Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                    Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                    Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                    Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                    Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                    Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                    Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                    (a) Object States Inactive = normal and Active = foreign language specific

                                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                    Object Identifier(a) Object Name Description

                                    Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                    Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                    Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                    Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                    Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                    Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                    Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                    Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                    Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                    Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                    Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                    Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                    Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                    Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                    Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                    Table 10 Diagnostics Binary Input (continued)

                                    Object Identifier(a) Object Name Description

                                    ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                    Object Data Points and Diagnostic Data Points

                                    Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                    Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                    Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                    Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                    Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                    Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                    Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                    Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                    Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                    Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                    Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                    Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                    Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                    Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                    Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                    Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                    Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                    Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                    Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                    Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                    Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                    Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                    Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                    Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                    Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                    Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                    Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                    Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                    Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                    Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                    Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                    Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                    Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                    Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                    Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                    Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                    Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                    Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                    Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                    Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                    Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                    Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                    Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                    Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                    Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                    Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                    Object Identifier(a) Object Name Description

                                    36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                    Object Data Points and Diagnostic Data Points

                                    Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                    Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                    Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                    Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                    Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                    Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                    Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                    Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                    Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                    Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                    Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                    Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                    Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                    Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                    Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                    Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                    Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                    Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                    Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                    Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                    Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                    Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                    Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                    Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                    Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                    Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                    Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                    Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                    Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                    Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                    Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                    Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                    Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                    Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                    Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                    Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                    Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                    Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                    Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                    Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                    Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                    Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                    Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                    Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                    Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                    Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                    Object Identifier(a) Object Name Description

                                    ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                    Object Data Points and Diagnostic Data Points

                                    Binary Output 16 Humidification Command Command the operating state of the humidification system

                                    NC 3 HVAC-Advisory HVAC-Advisory

                                    NC 1 HVAC-Critical HVAC-Critical

                                    NC 4 HVAC-Information HVAC-Information

                                    NC 2 HVAC-Service Required HVAC-Service Required

                                    Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                    Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                    Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                    Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                    Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                    Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                    Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                    Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                    Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                    Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                    Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                    Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                    Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                    Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                    Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                    Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                    Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                    Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                    Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                    Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                    Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                    Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                    Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                    Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                    Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                    Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                    Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                    Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                    Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                    Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                    Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                    Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                    Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                    Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                    Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                    Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                    Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                    Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                    Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                    Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                    Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                    Object Identifier(a) Object Name Description

                                    38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                    Object Data Points and Diagnostic Data Points

                                    Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                    Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                    Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                    Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                    Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                    Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                    Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                    Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                    Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                    Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                    Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                    Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                    Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                    Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                    Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                    Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                    Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                    Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                    Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                    Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                    Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                    Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                    Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                    Binary Input 3 Unit Status Indicates the current state of the unit

                                    Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                    Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                    Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                    Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                    Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                    Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                    Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                    (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                    Object Identifier(a) Object Name Description

                                    Table 12 Diagnostic Objects Sorted by Object Name

                                    Object Identifier(a) Object Name ValueRange Description

                                    BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                    BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                    ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                    Object Data Points and Diagnostic Data Points

                                    BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                    BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                    BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                    BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                    BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                    BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                    BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                    BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                    BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                    BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                    BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                    BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                    BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                    BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                    BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                    BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                    BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                    BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                    BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                    BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                    BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                    BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                    BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                    BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                    BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                    BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                    BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                    BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                    BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                    Object Identifier(a) Object Name ValueRange Description

                                    40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                    Object Data Points and Diagnostic Data Points

                                    BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                    BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                    BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                    BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                    BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                    BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                    BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                    BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                    BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                    BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                    BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                    BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                    BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                    BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                    BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                    BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                    BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                    BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                    BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                    BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                    BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                    BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                    BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                    BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                    BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                    BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                    BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                    BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                    BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                    Object Identifier(a) Object Name ValueRange Description

                                    ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                    Object Data Points and Diagnostic Data Points

                                    BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                    BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                    BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                    BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                    BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                    BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                    BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                    BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                    BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                    BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                    BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                    BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                    BI 121 (use Object Identifier for RT)

                                    Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                    BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                    BI 58 (use Object Identifier for RT or CSC)

                                    Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                    BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                    BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                    BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                    BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                    BI 31 (use Object Identifier for RT CSC)

                                    Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                    BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                    BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                    BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                    BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                    BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                    BI 121 (use Object Identifier for FAU)

                                    Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                    B1 31 (use Object Identifier for FAU)

                                    Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                    BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                    BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                    Object Identifier(a) Object Name ValueRange Description

                                    42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                    Object Data Points and Diagnostic Data Points

                                    BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                    BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                    BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                    BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                    BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                    BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                    BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                    BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                    BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                    BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                    BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                    BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                    BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                    BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                    BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                    BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                    BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                    BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                    BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                    BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                    BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                    BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                    BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                    1 = active Diagnostic Vel Press Sensor (Rear)

                                    BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                    Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                    BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                    BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                    BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                    BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                    BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                    Object Identifier(a) Object Name ValueRange Description

                                    ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                    Object Data Points and Diagnostic Data Points

                                    BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                    BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                    BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                    BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                    BI 58 (use Object Identifier for FAU)

                                    Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                    (a) BI=Binary Input

                                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                    Object Identifier(a) Object Name ValueRange Description

                                    44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                    Additional Resources

                                    Additional Resources

                                    Use the following documents and links as additional resources

                                    bull Product support online

                                    bull wwwbacnetorg

                                    bull wwwbacnetassociationorg

                                    bull wwwashraeorg

                                    bull Tracer TU Help online

                                    bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                    bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                    Note For further assistance contact your local Trane sales office

                                    ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                    Glossary

                                    A

                                    ASHRAE

                                    See American Society of Heating Refrigeration and Air-conditioning Engineers

                                    American Society of Heating Refrigeration and Air-

                                    conditioning Engineers

                                    An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                    BBACnettrade

                                    See Building Automation Control network

                                    BACnet interoperability building blocks

                                    A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                    BACnet object

                                    An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                    baud rate

                                    The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                    BIBB

                                    See BACnet interoperability building blocks

                                    Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                    advocates BACnet protocol for use in system-level control devices

                                    device

                                    A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                    Device ID

                                    The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                    Iinteroperability

                                    The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                    Pprotocol

                                    A set of rules (language) that governs the exchange of data over a digital communications system

                                    S

                                    stand-alone operation

                                    Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                    wwwtranecom

                                    For more information contact your local Trane office or e-mail us at comforttranecom

                                    Literature Order Number ACC-SVP01B-EN

                                    Date September 2009

                                    Supersedes ACC-SVP01A-EN

                                    Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                    • Table of Contents
                                    • Overview
                                    • Ordering Numbers
                                    • BACnet Protocol
                                    • BCI-I Configuration
                                      • Overview
                                      • Starting a Session of Tracer TU and Direct Connection
                                      • Reset to Factory Default
                                      • IP Units Configuration
                                      • BACnet Object Configuration
                                      • Change Baud Rate
                                      • Change Device ID
                                      • Stand-alone or BAS Operation
                                        • IntelliPak Control Configuration
                                        • BAS Unit Control
                                        • Periodic Update of BAS Values
                                        • BAS Communication Failure
                                          • InputOutput Commands and Calculations
                                            • System Control Command
                                            • Filter Timer Reset Command
                                            • Diagnostics Reset Command
                                            • Setpoint Calculations
                                            • Timestamp Configuration
                                                • BCI IntelliPak Rotary Switches and LEDs
                                                  • Rotary Switches
                                                  • LEDs Description Behavior and Troubleshooting
                                                  • 24 Vac Measurement
                                                  • Ground Measurements
                                                    • BACnet Data Points and Configuration Property Definitions
                                                      • BACnet Protocol Implementation Conformance Statement (PICS)
                                                        • Standardized Device Profile (Annex L)
                                                        • Interoperability Building Blocks (Annex K)
                                                        • Segmentation Capability
                                                        • Object Types
                                                          • BACnet Protocol
                                                            • Data Link Layer Options
                                                            • Device Address Binding
                                                            • Networking Options
                                                            • Character Sets
                                                                • Object Data Points and Diagnostic Data Points
                                                                • Additional Resources
                                                                • Glossary

                                      ACC-SVP01B-EN bull BCI-I Integration Guide 19

                                      BACnet Data Points and Configuration Property Definitions

                                      Object Types

                                      Table 2 Descriptions and configurations

                                      Object Type Required Properties Read Properties Written(a) Optional Properties Read

                                      Ability to Create

                                      Ability to Delete

                                      Analog Input

                                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                                      bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                                      bull Descriptionbull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                      Yes Yes only user created objects

                                      Analog Output

                                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Unitsbull Priority_Arraybull Relinquish_Default

                                      bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Min_Pres_Valuebull Max_Pres_Valuebull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                                      bull Descriptionbull Reliabilitybull Min_Pres-Valuebull Max_Pres_Valuebull COV_Incrementbull Time_Delaybull Notification _Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                      Yes Yes only user created objects

                                      Analog Value

                                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Units

                                      bull Object_Namebull Descriptionbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Notify_Type

                                      bull Descriptionbull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull COV_Incrementbull Time_Delaybull Notification_Classbull High_Limitbull Low_Limitbull Deadbandbull Limit_Enablebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                      Yes Yes only user created objects

                                      Binary Input

                                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                                      bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                                      bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                                      Yes Yes only user created objects

                                      20 ACC-SVP01B-EN bull BCI-I Integration Guide

                                      BACnet Data Points and Configuration Property Definitions

                                      Binary Output

                                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

                                      bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

                                      bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                                      Yes Yes only user created objects

                                      Binary Value

                                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                                      bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                                      bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                                      Yes Yes only user created objects

                                      Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

                                      bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

                                      bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

                                      None None

                                      Event Enrollment Object

                                      bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

                                      bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

                                      bull None Yes Yes only user created objects

                                      Table 2 Descriptions and configurations (continued)

                                      Object Type Required Properties Read Properties Written(a) Optional Properties Read

                                      Ability to Create

                                      Ability to Delete

                                      ACC-SVP01B-EN bull BCI-I Integration Guide 21

                                      BACnet Data Points and Configuration Property Definitions

                                      Multistate Input

                                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                                      bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                                      bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                      Yes Yes only user created objects

                                      Multistate Output

                                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

                                      bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

                                      bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                      Yes Yes only user created objects

                                      Multistate Value

                                      bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                                      bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                                      bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                      Yes Yes only user created objects

                                      Notification Class

                                      bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

                                      bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

                                      None Yes Yes only user created objects

                                      Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

                                      bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

                                      bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

                                      Yes Yes only user created objects

                                      (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

                                      Table 2 Descriptions and configurations (continued)

                                      Object Type Required Properties Read Properties Written(a) Optional Properties Read

                                      Ability to Create

                                      Ability to Delete

                                      22 ACC-SVP01B-EN bull BCI-I Integration Guide

                                      BACnet Data Points and Configuration Property Definitions

                                      BACnet Protocol

                                      Data Link Layer Options

                                      Device Address Binding

                                      Networking Options

                                      Data Link Layer Description Supported Option

                                      ANSIATA 8781 25 Mb ARCNET (Clause 8)

                                      ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

                                      BACnet IP (Annex J)

                                      BACnet IP (Annex J) Foreign Device

                                      ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

                                      LonTalk (Clause 11) Medium

                                      MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

                                      MSTP Slave (Clause 9) Baud Rate(s)

                                      Other

                                      Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

                                      Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

                                      Device Address Binding Supported

                                      Static Device Binding Supported

                                      Networking DescriptionsSupported

                                      Option

                                      Annex H BACnet Tunneling

                                      BACnetIP Broadcast Management Device (BBMD)

                                      Does the BBMD Support Registrations by Foreign Devices

                                      Router

                                      ACC-SVP01B-EN bull BCI-I Integration Guide 23

                                      BACnet Data Points and Configuration Property Definitions

                                      Character Sets

                                      Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

                                      Character Set Descriptions Supported

                                      ANSI X34

                                      IBMMicrosoft DBCS

                                      ISO 10646 (UCS-4)

                                      ISO 10646 (UCS2)

                                      ISO 8859-1

                                      JIS C 6226

                                      24 ACC-SVP01B-EN bull BCI-I Integration Guide

                                      Object Data Points and Diagnostic Data Points

                                      Object Data Points and Diagnostic Data Points

                                      For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

                                      Table 3 Analog Output

                                      Object Identifier Object Name Description Units Valid Range

                                      Refresh Rate

                                      (Sec)

                                      Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

                                      Percent (98) 0 to 100 NA

                                      Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

                                      Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

                                      Degrees-Fahrenheit (64) 500 to 900 NA

                                      Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

                                      BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

                                      Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

                                      Degrees-Fahrenheit (64) 400 to 900 NA

                                      Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

                                      Degrees-Fahrenheit (64) 400 to 1800 NA

                                      Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

                                      070 to 510 (Ipak II) NA

                                      Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

                                      003 to 030-002 to 030 (enhanced StatiTrac)

                                      NA

                                      Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

                                      -028 to 050-067 to 067 (enhanced StatiTrac)

                                      900

                                      Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                      Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                      Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

                                      00 to 79 (Ipak II) 900

                                      Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                      Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

                                      Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

                                      Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

                                      Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

                                      Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                      Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                      Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

                                      Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

                                      Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

                                      ACC-SVP01B-EN bull BCI-I Integration Guide 25

                                      Object Data Points and Diagnostic Data Points

                                      Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                                      Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                                      Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                                      Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                                      Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                                      Cooling temperature setpoint used for control in unoccupied mode

                                      Degrees-Fahrenheit (64) 520 to 880 NA

                                      Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                                      Heating temperature setpoint used for control in unoccupied mode

                                      Degrees-Fahrenheit (64) 500 to 900 NA

                                      Table 4 Analog Input

                                      Object Identifier Object Name Description Units (Listed Are Defaults)

                                      Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                                      Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                                      Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                                      Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                                      Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                                      Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                                      Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                                      Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                                      Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                                      Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                                      Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                                      Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                                      Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                                      Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                                      Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                                      Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                                      Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                                      Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                                      Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                                      Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                                      Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                                      Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                                      Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                                      Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                      Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                      Table 3 Analog Output (continued)

                                      Object Identifier Object Name Description Units Valid Range

                                      Refresh Rate

                                      (Sec)

                                      26 ACC-SVP01B-EN bull BCI-I Integration Guide

                                      Object Data Points and Diagnostic Data Points

                                      Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                                      Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                      Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                      Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                                      Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                                      Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                                      Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                                      Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                                      Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                      Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                      Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                      Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                      Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                                      Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                                      Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                                      Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                                      Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                                      Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                                      Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                                      Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                                      Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                                      Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                      Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                      Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                                      The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                                      Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                                      The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                                      Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                                      Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                                      Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                                      Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                                      Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                                      Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                                      Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                                      Table 4 Analog Input (continued)

                                      Object Identifier Object Name Description Units (Listed Are Defaults)

                                      ACC-SVP01B-EN bull BCI-I Integration Guide 27

                                      Object Data Points and Diagnostic Data Points

                                      Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                                      Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                                      Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                                      Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                                      The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                                      Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                                      Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                                      Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                                      Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                                      Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                                      Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                      Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                      Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                                      Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                                      Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                                      Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                                      Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                                      Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                                      Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                                      Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                                      Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                                      Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                                      Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                                      Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                                      Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                                      Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                                      Table 5 Analog Value

                                      Object Identifier Object Name Description Units Valid Range

                                      Analog Value 1 Filter Runtime Hours Setpoint

                                      The setpoint value used by the filter run hours calculation

                                      Hours (71) 0 to 10000

                                      Table 4 Analog Input (continued)

                                      Object Identifier Object Name Description Units (Listed Are Defaults)

                                      28 ACC-SVP01B-EN bull BCI-I Integration Guide

                                      Object Data Points and Diagnostic Data Points

                                      Table 6 Multistate Output

                                      BCI-I Object Identifier Object Name Description Object States

                                      Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                                      Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                      1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                                      Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                                      Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                      1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                      Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                      1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                      Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                      1 = Flow2 = No Flow3 = Auto

                                      Table 7 Multistate Input

                                      BCI-I Object Identifier Object Name Description Object States

                                      Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                      1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                                      Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                      1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                                      Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                      1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                                      Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                      1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                                      ACC-SVP01B-EN bull BCI-I Integration Guide 29

                                      Object Data Points and Diagnostic Data Points

                                      Multi-State Input 15 Economizer Decision Method

                                      Unit method to determine when the economizer system is enabled

                                      1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                                      Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                                      Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                                      Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                      1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                      Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                      1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                      Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                      1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                                      Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                      1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                      Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                      1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                      Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                      1 = Idle2 = On3 = Cancel

                                      Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                      1 = Off2 = On3 = Not Present

                                      Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                      1 = Off2 = On3 = Not Present

                                      Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                      1 = Off2 = On3 = Not Present

                                      Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                      1 = Off|2 = On3 = Not Present

                                      Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                      1 = Off2 = On3 = Not Present

                                      Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                      1 = Off2 = On3 = Not Present

                                      Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                      1 = Off2 = On3 = Not Present

                                      Table 7 Multistate Input (continued)

                                      BCI-I Object Identifier Object Name Description Object States

                                      30 ACC-SVP01B-EN bull BCI-I Integration Guide

                                      Object Data Points and Diagnostic Data Points

                                      Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                      1 = Off2 = On3 = Not Present

                                      Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                      1 = Off2 = On3 = Not Present

                                      Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                                      Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                                      Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                                      Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                                      Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                      1 = Off2 = On3 = Not Present

                                      Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                      1= Off2= On3= Not Present

                                      Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                                      Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                                      Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                                      Multi-State Input 43 Outdoor Air Damper Status

                                      Indicates the operating state of the outdoor damper

                                      1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                                      Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                      1 = Disabled2 = Enabled3 = Not Present

                                      Table 8 Binary Output

                                      Object Identifier Object Name DescriptionRelinquish Default Object States

                                      Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                                      Active = BAS Control

                                      Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                                      Active = Heating Locked Out

                                      Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                                      Active = Cooling Locked Out

                                      Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                                      Active = Enabled

                                      Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                                      Active = On

                                      Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                                      Inactive Inactive = DisabledActive = Enabled

                                      Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                                      Active = Reset

                                      Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                                      Active = Reset

                                      Table 7 Multistate Input (continued)

                                      BCI-I Object Identifier Object Name Description Object States

                                      ACC-SVP01B-EN bull BCI-I Integration Guide 31

                                      Object Data Points and Diagnostic Data Points

                                      Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                                      Active = Auto

                                      Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                                      Active = Auto

                                      Table 9 Binary Input

                                      Object Identifier Object Name Description Object States

                                      Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                      Inactive = Standalone controlActive = BAS control

                                      Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                      Inactive = NormalActive = Locked Out

                                      Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                                      Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                      Inactive = AutoActive = Open

                                      Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                      Inactive = InactiveActive = Active

                                      Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                                      Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                                      Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                      Inactive = DisabledActive = Enabled

                                      Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                      Inactive = DisabledActive = Enabled

                                      Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                      Inactive = InactiveActive = Active

                                      Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                      Inactive = No FlowActive = Flow

                                      Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                      Inactive = InactiveActive = Active

                                      Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                      Inactive = InactiveActive = Active

                                      Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                      Inactive = InactiveActive = Active

                                      Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                                      The status of evaporator frost protection function for circuit 1

                                      Inactive = InactiveActive = Active

                                      Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                                      The status of evaporator frost protection function for circuit 2

                                      Inactive = InactiveActive = Active

                                      Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                                      The status of evaporator frost protection function for circuit 3

                                      Inactive = InactiveActive = Active

                                      Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                                      The status of evaporator frost protection function for circuit 4

                                      Inactive = InactiveActive = Active

                                      Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                      Inactive = De-energizedActive = Energized

                                      Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                      Inactive = InactiveActive = Active

                                      Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                      Inactive = ClosedActive = Open

                                      Table 10 Diagnostics Binary Input

                                      Object Identifier(a) Object Name Description

                                      Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                                      Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                                      Binary Input 31 (use Object Identifier for RT or CSC)

                                      Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                                      Binary Input 31 (use Object Identifier for FAU)

                                      Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                                      Table 8 Binary Output

                                      Object Identifier Object Name DescriptionRelinquish Default Object States

                                      32 ACC-SVP01B-EN bull BCI-I Integration Guide

                                      Object Data Points and Diagnostic Data Points

                                      Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                                      Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                                      Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                                      Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                                      Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                                      Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                                      Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                                      Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                                      Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                                      Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                      Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                      Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                                      Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                                      Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                                      Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                                      Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                                      Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                                      Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                                      Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                                      Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                                      Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                                      Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                                      Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                                      Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                                      Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                                      Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                                      Binary Input 58 (use Object Identifier for RT or CSC)

                                      Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                                      Binary Input 58 (use Object Identifier for FAU)

                                      Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                                      Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                                      Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                                      Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                                      Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                                      Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                                      Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                                      Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                                      Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                                      Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                                      Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                                      Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                                      Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                                      Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                                      Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                                      Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                                      Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                                      Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                                      Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                                      Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                                      Table 10 Diagnostics Binary Input (continued)

                                      Object Identifier(a) Object Name Description

                                      ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                      Object Data Points and Diagnostic Data Points

                                      Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                      Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                      Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                      Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                      Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                      Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                      Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                      Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                      Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                      Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                      Binary Input 86 (use Object Identifier for RT I-pak II)

                                      Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                      Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                      Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                      Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                      Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                      Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                      Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                      Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                      Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                      Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                      Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                      Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                      Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                      Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                      Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                      Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                      Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                      Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                      Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                      Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                      Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                      Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                      Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                      Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                      Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                      Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                      Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                      Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                      Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                      Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                      Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                      Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                      Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                      Binary Input 121 (use Object Identifier for RT)

                                      Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                      Binary Input 121 (use Object Identifier for FAU)

                                      Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                      Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                      Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                      Table 10 Diagnostics Binary Input (continued)

                                      Object Identifier(a) Object Name Description

                                      34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                      Object Data Points and Diagnostic Data Points

                                      Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                      Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                      Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                      Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                      Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                      Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                      Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                      Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                      Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                      Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                      Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                      Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                      Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                      Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                      Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                      Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                      Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                      Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                      Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                      Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                      Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                      Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                      Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                      Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                      Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                      Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                      (a) Object States Inactive = normal and Active = foreign language specific

                                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                      Object Identifier(a) Object Name Description

                                      Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                      Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                      Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                      Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                      Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                      Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                      Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                      Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                      Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                      Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                      Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                      Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                      Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                      Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                      Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                      Table 10 Diagnostics Binary Input (continued)

                                      Object Identifier(a) Object Name Description

                                      ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                      Object Data Points and Diagnostic Data Points

                                      Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                      Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                      Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                      Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                      Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                      Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                      Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                      Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                      Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                      Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                      Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                      Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                      Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                      Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                      Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                      Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                      Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                      Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                      Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                      Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                      Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                      Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                      Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                      Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                      Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                      Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                      Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                      Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                      Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                      Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                      Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                      Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                      Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                      Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                      Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                      Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                      Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                      Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                      Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                      Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                      Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                      Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                      Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                      Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                      Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                      Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                      Object Identifier(a) Object Name Description

                                      36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                      Object Data Points and Diagnostic Data Points

                                      Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                      Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                      Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                      Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                      Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                      Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                      Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                      Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                      Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                      Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                      Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                      Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                      Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                      Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                      Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                      Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                      Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                      Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                      Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                      Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                      Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                      Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                      Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                      Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                      Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                      Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                      Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                      Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                      Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                      Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                      Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                      Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                      Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                      Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                      Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                      Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                      Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                      Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                      Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                      Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                      Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                      Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                      Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                      Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                      Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                      Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                      Object Identifier(a) Object Name Description

                                      ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                      Object Data Points and Diagnostic Data Points

                                      Binary Output 16 Humidification Command Command the operating state of the humidification system

                                      NC 3 HVAC-Advisory HVAC-Advisory

                                      NC 1 HVAC-Critical HVAC-Critical

                                      NC 4 HVAC-Information HVAC-Information

                                      NC 2 HVAC-Service Required HVAC-Service Required

                                      Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                      Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                      Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                      Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                      Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                      Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                      Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                      Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                      Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                      Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                      Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                      Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                      Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                      Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                      Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                      Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                      Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                      Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                      Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                      Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                      Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                      Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                      Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                      Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                      Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                      Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                      Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                      Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                      Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                      Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                      Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                      Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                      Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                      Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                      Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                      Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                      Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                      Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                      Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                      Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                      Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                      Object Identifier(a) Object Name Description

                                      38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                      Object Data Points and Diagnostic Data Points

                                      Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                      Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                      Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                      Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                      Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                      Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                      Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                      Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                      Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                      Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                      Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                      Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                      Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                      Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                      Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                      Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                      Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                      Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                      Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                      Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                      Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                      Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                      Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                      Binary Input 3 Unit Status Indicates the current state of the unit

                                      Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                      Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                      Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                      Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                      Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                      Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                      Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                      (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                      Object Identifier(a) Object Name Description

                                      Table 12 Diagnostic Objects Sorted by Object Name

                                      Object Identifier(a) Object Name ValueRange Description

                                      BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                      BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                      ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                      Object Data Points and Diagnostic Data Points

                                      BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                      BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                      BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                      BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                      BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                      BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                      BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                      BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                      BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                      BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                      BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                      BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                      BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                      BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                      BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                      BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                      BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                      BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                      BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                      BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                      BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                      BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                      BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                      BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                      BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                      BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                      BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                      BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                      BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                      Object Identifier(a) Object Name ValueRange Description

                                      40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                      Object Data Points and Diagnostic Data Points

                                      BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                      BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                      BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                      BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                      BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                      BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                      BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                      BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                      BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                      BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                      BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                      BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                      BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                      BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                      BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                      BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                      BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                      BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                      BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                      BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                      BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                      BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                      BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                      BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                      BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                      BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                      BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                      BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                      BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                      Object Identifier(a) Object Name ValueRange Description

                                      ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                      Object Data Points and Diagnostic Data Points

                                      BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                      BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                      BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                      BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                      BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                      BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                      BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                      BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                      BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                      BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                      BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                      BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                      BI 121 (use Object Identifier for RT)

                                      Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                      BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                      BI 58 (use Object Identifier for RT or CSC)

                                      Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                      BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                      BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                      BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                      BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                      BI 31 (use Object Identifier for RT CSC)

                                      Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                      BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                      BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                      BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                      BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                      BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                      BI 121 (use Object Identifier for FAU)

                                      Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                      B1 31 (use Object Identifier for FAU)

                                      Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                      BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                      BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                      Object Identifier(a) Object Name ValueRange Description

                                      42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                      Object Data Points and Diagnostic Data Points

                                      BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                      BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                      BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                      BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                      BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                      BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                      BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                      BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                      BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                      BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                      BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                      BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                      BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                      BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                      BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                      BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                      BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                      BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                      BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                      BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                      BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                      BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                      BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                      1 = active Diagnostic Vel Press Sensor (Rear)

                                      BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                      Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                      BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                      BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                      BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                      BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                      BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                      Object Identifier(a) Object Name ValueRange Description

                                      ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                      Object Data Points and Diagnostic Data Points

                                      BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                      BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                      BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                      BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                      BI 58 (use Object Identifier for FAU)

                                      Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                      (a) BI=Binary Input

                                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                      Object Identifier(a) Object Name ValueRange Description

                                      44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                      Additional Resources

                                      Additional Resources

                                      Use the following documents and links as additional resources

                                      bull Product support online

                                      bull wwwbacnetorg

                                      bull wwwbacnetassociationorg

                                      bull wwwashraeorg

                                      bull Tracer TU Help online

                                      bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                      bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                      Note For further assistance contact your local Trane sales office

                                      ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                      Glossary

                                      A

                                      ASHRAE

                                      See American Society of Heating Refrigeration and Air-conditioning Engineers

                                      American Society of Heating Refrigeration and Air-

                                      conditioning Engineers

                                      An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                      BBACnettrade

                                      See Building Automation Control network

                                      BACnet interoperability building blocks

                                      A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                      BACnet object

                                      An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                      baud rate

                                      The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                      BIBB

                                      See BACnet interoperability building blocks

                                      Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                      advocates BACnet protocol for use in system-level control devices

                                      device

                                      A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                      Device ID

                                      The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                      Iinteroperability

                                      The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                      Pprotocol

                                      A set of rules (language) that governs the exchange of data over a digital communications system

                                      S

                                      stand-alone operation

                                      Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                      wwwtranecom

                                      For more information contact your local Trane office or e-mail us at comforttranecom

                                      Literature Order Number ACC-SVP01B-EN

                                      Date September 2009

                                      Supersedes ACC-SVP01A-EN

                                      Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                      • Table of Contents
                                      • Overview
                                      • Ordering Numbers
                                      • BACnet Protocol
                                      • BCI-I Configuration
                                        • Overview
                                        • Starting a Session of Tracer TU and Direct Connection
                                        • Reset to Factory Default
                                        • IP Units Configuration
                                        • BACnet Object Configuration
                                        • Change Baud Rate
                                        • Change Device ID
                                        • Stand-alone or BAS Operation
                                          • IntelliPak Control Configuration
                                          • BAS Unit Control
                                          • Periodic Update of BAS Values
                                          • BAS Communication Failure
                                            • InputOutput Commands and Calculations
                                              • System Control Command
                                              • Filter Timer Reset Command
                                              • Diagnostics Reset Command
                                              • Setpoint Calculations
                                              • Timestamp Configuration
                                                  • BCI IntelliPak Rotary Switches and LEDs
                                                    • Rotary Switches
                                                    • LEDs Description Behavior and Troubleshooting
                                                    • 24 Vac Measurement
                                                    • Ground Measurements
                                                      • BACnet Data Points and Configuration Property Definitions
                                                        • BACnet Protocol Implementation Conformance Statement (PICS)
                                                          • Standardized Device Profile (Annex L)
                                                          • Interoperability Building Blocks (Annex K)
                                                          • Segmentation Capability
                                                          • Object Types
                                                            • BACnet Protocol
                                                              • Data Link Layer Options
                                                              • Device Address Binding
                                                              • Networking Options
                                                              • Character Sets
                                                                  • Object Data Points and Diagnostic Data Points
                                                                  • Additional Resources
                                                                  • Glossary

                                        20 ACC-SVP01B-EN bull BCI-I Integration Guide

                                        BACnet Data Points and Configuration Property Definitions

                                        Binary Output

                                        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polaritybull Priority_Arraybull Relinquish_Default

                                        bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Event_Enablebull Acked_Transitionsbull Notify_Type

                                        bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Feedback_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                                        Yes Yes only user created objects

                                        Binary Value

                                        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Polarity

                                        bull Object_Namebull Descriptionbull Out_Of_Servicebull Inactive_Textbull Active_Textbull Present_Valuebull Reliabilitybull Change_Of_State_Countbull Elapsed_Active_Timebull Minimum_On_Timebull Minimum_Off_Timebull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Type

                                        bull Descriptionbull Inactive_Textbull Active_Textbull Change_Of_State_Timebull Change_Of_State_Countbull Time_Of_State_Count_Resetbull Elapsed_Active_Timebull Time_Of_Active_Time_Resetbull Priority_Arraybull Relinquish_Defaultbull Minimum_On_Timebull Minimum_Off_Timebull Time_Delaybull Notification_Classbull Alarm_Valuebull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stampsbull Reliability

                                        Yes Yes only user created objects

                                        Device bull Object_Identifierbull Object_Namebull Object_Typebull System_Statusbull Vendor_Namebull Vendor_Identifierbull Model_Namebull Firmware_Revisionbull Application_Software_Versionbull Protocol_Versionbull Protocol_Revisionbull Protocol_Services_Supportedbull Protocol_Object_Types_Supportedbull Object_Listbull Max_APDU_Length_Acceptedbull Segmentation_Supportedbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Device_Address_Bindingbull Database_Revision

                                        bull Object_Namebull Locationbull Descriptionbull APDU_Segment_Timeoutbull APDU_Timeoutbull Number_Of_APDU_Retriesbull Backup_Failure_Timeout

                                        bull Locationbull Descriptionbull Max_Segments_Acceptedbull APDU_Segment_Timeoutbull Max_Masterbull Max_Info_Framesbull Local_Timebull Local_Datebull Configuration_Filesbull Last_Restore_Timebull Backup_Failure_Timeoutbull Active_COV_Subscriptions

                                        None None

                                        Event Enrollment Object

                                        bull Object_Identifierbull Object_Namebull Object_Typebull Event_Typebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Statebull Event_Enablebull Acked_Transitionsbull Notification_Classbull Event_Time_Stamps

                                        bull Object_Namebull Notify_Typebull Event_Parametersbull Object_Property_Referencebull Event_Enablebull Notification_Class

                                        bull None Yes Yes only user created objects

                                        Table 2 Descriptions and configurations (continued)

                                        Object Type Required Properties Read Properties Written(a) Optional Properties Read

                                        Ability to Create

                                        Ability to Delete

                                        ACC-SVP01B-EN bull BCI-I Integration Guide 21

                                        BACnet Data Points and Configuration Property Definitions

                                        Multistate Input

                                        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                                        bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                                        bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                        Yes Yes only user created objects

                                        Multistate Output

                                        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

                                        bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

                                        bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                        Yes Yes only user created objects

                                        Multistate Value

                                        bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                                        bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                                        bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                        Yes Yes only user created objects

                                        Notification Class

                                        bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

                                        bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

                                        None Yes Yes only user created objects

                                        Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

                                        bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

                                        bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

                                        Yes Yes only user created objects

                                        (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

                                        Table 2 Descriptions and configurations (continued)

                                        Object Type Required Properties Read Properties Written(a) Optional Properties Read

                                        Ability to Create

                                        Ability to Delete

                                        22 ACC-SVP01B-EN bull BCI-I Integration Guide

                                        BACnet Data Points and Configuration Property Definitions

                                        BACnet Protocol

                                        Data Link Layer Options

                                        Device Address Binding

                                        Networking Options

                                        Data Link Layer Description Supported Option

                                        ANSIATA 8781 25 Mb ARCNET (Clause 8)

                                        ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

                                        BACnet IP (Annex J)

                                        BACnet IP (Annex J) Foreign Device

                                        ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

                                        LonTalk (Clause 11) Medium

                                        MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

                                        MSTP Slave (Clause 9) Baud Rate(s)

                                        Other

                                        Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

                                        Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

                                        Device Address Binding Supported

                                        Static Device Binding Supported

                                        Networking DescriptionsSupported

                                        Option

                                        Annex H BACnet Tunneling

                                        BACnetIP Broadcast Management Device (BBMD)

                                        Does the BBMD Support Registrations by Foreign Devices

                                        Router

                                        ACC-SVP01B-EN bull BCI-I Integration Guide 23

                                        BACnet Data Points and Configuration Property Definitions

                                        Character Sets

                                        Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

                                        Character Set Descriptions Supported

                                        ANSI X34

                                        IBMMicrosoft DBCS

                                        ISO 10646 (UCS-4)

                                        ISO 10646 (UCS2)

                                        ISO 8859-1

                                        JIS C 6226

                                        24 ACC-SVP01B-EN bull BCI-I Integration Guide

                                        Object Data Points and Diagnostic Data Points

                                        Object Data Points and Diagnostic Data Points

                                        For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

                                        Table 3 Analog Output

                                        Object Identifier Object Name Description Units Valid Range

                                        Refresh Rate

                                        (Sec)

                                        Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

                                        Percent (98) 0 to 100 NA

                                        Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

                                        Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

                                        Degrees-Fahrenheit (64) 500 to 900 NA

                                        Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

                                        BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

                                        Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

                                        Degrees-Fahrenheit (64) 400 to 900 NA

                                        Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

                                        Degrees-Fahrenheit (64) 400 to 1800 NA

                                        Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

                                        070 to 510 (Ipak II) NA

                                        Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

                                        003 to 030-002 to 030 (enhanced StatiTrac)

                                        NA

                                        Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

                                        -028 to 050-067 to 067 (enhanced StatiTrac)

                                        900

                                        Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                        Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                        Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

                                        00 to 79 (Ipak II) 900

                                        Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                        Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

                                        Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

                                        Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

                                        Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

                                        Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                        Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                        Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

                                        Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

                                        Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

                                        ACC-SVP01B-EN bull BCI-I Integration Guide 25

                                        Object Data Points and Diagnostic Data Points

                                        Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                                        Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                                        Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                                        Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                                        Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                                        Cooling temperature setpoint used for control in unoccupied mode

                                        Degrees-Fahrenheit (64) 520 to 880 NA

                                        Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                                        Heating temperature setpoint used for control in unoccupied mode

                                        Degrees-Fahrenheit (64) 500 to 900 NA

                                        Table 4 Analog Input

                                        Object Identifier Object Name Description Units (Listed Are Defaults)

                                        Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                                        Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                                        Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                                        Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                                        Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                                        Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                                        Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                                        Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                                        Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                                        Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                                        Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                                        Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                                        Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                                        Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                                        Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                                        Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                                        Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                                        Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                                        Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                                        Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                                        Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                                        Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                                        Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                                        Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                        Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                        Table 3 Analog Output (continued)

                                        Object Identifier Object Name Description Units Valid Range

                                        Refresh Rate

                                        (Sec)

                                        26 ACC-SVP01B-EN bull BCI-I Integration Guide

                                        Object Data Points and Diagnostic Data Points

                                        Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                                        Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                        Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                        Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                                        Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                                        Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                                        Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                                        Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                                        Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                        Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                        Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                        Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                        Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                                        Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                                        Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                                        Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                                        Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                                        Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                                        Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                                        Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                                        Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                                        Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                        Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                        Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                                        The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                                        Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                                        The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                                        Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                                        Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                                        Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                                        Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                                        Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                                        Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                                        Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                                        Table 4 Analog Input (continued)

                                        Object Identifier Object Name Description Units (Listed Are Defaults)

                                        ACC-SVP01B-EN bull BCI-I Integration Guide 27

                                        Object Data Points and Diagnostic Data Points

                                        Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                                        Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                                        Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                                        Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                                        The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                                        Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                                        Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                                        Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                                        Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                                        Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                                        Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                        Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                        Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                                        Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                                        Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                                        Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                                        Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                                        Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                                        Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                                        Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                                        Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                                        Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                                        Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                                        Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                                        Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                                        Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                                        Table 5 Analog Value

                                        Object Identifier Object Name Description Units Valid Range

                                        Analog Value 1 Filter Runtime Hours Setpoint

                                        The setpoint value used by the filter run hours calculation

                                        Hours (71) 0 to 10000

                                        Table 4 Analog Input (continued)

                                        Object Identifier Object Name Description Units (Listed Are Defaults)

                                        28 ACC-SVP01B-EN bull BCI-I Integration Guide

                                        Object Data Points and Diagnostic Data Points

                                        Table 6 Multistate Output

                                        BCI-I Object Identifier Object Name Description Object States

                                        Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                                        Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                        1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                                        Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                                        Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                        1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                        Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                        1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                        Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                        1 = Flow2 = No Flow3 = Auto

                                        Table 7 Multistate Input

                                        BCI-I Object Identifier Object Name Description Object States

                                        Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                        1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                                        Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                        1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                                        Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                        1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                                        Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                        1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                                        ACC-SVP01B-EN bull BCI-I Integration Guide 29

                                        Object Data Points and Diagnostic Data Points

                                        Multi-State Input 15 Economizer Decision Method

                                        Unit method to determine when the economizer system is enabled

                                        1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                                        Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                                        Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                                        Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                        1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                        Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                        1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                        Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                        1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                                        Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                        1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                        Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                        1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                        Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                        1 = Idle2 = On3 = Cancel

                                        Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                        1 = Off2 = On3 = Not Present

                                        Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                        1 = Off2 = On3 = Not Present

                                        Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                        1 = Off2 = On3 = Not Present

                                        Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                        1 = Off|2 = On3 = Not Present

                                        Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                        1 = Off2 = On3 = Not Present

                                        Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                        1 = Off2 = On3 = Not Present

                                        Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                        1 = Off2 = On3 = Not Present

                                        Table 7 Multistate Input (continued)

                                        BCI-I Object Identifier Object Name Description Object States

                                        30 ACC-SVP01B-EN bull BCI-I Integration Guide

                                        Object Data Points and Diagnostic Data Points

                                        Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                        1 = Off2 = On3 = Not Present

                                        Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                        1 = Off2 = On3 = Not Present

                                        Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                                        Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                                        Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                                        Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                                        Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                        1 = Off2 = On3 = Not Present

                                        Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                        1= Off2= On3= Not Present

                                        Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                                        Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                                        Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                                        Multi-State Input 43 Outdoor Air Damper Status

                                        Indicates the operating state of the outdoor damper

                                        1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                                        Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                        1 = Disabled2 = Enabled3 = Not Present

                                        Table 8 Binary Output

                                        Object Identifier Object Name DescriptionRelinquish Default Object States

                                        Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                                        Active = BAS Control

                                        Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                                        Active = Heating Locked Out

                                        Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                                        Active = Cooling Locked Out

                                        Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                                        Active = Enabled

                                        Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                                        Active = On

                                        Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                                        Inactive Inactive = DisabledActive = Enabled

                                        Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                                        Active = Reset

                                        Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                                        Active = Reset

                                        Table 7 Multistate Input (continued)

                                        BCI-I Object Identifier Object Name Description Object States

                                        ACC-SVP01B-EN bull BCI-I Integration Guide 31

                                        Object Data Points and Diagnostic Data Points

                                        Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                                        Active = Auto

                                        Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                                        Active = Auto

                                        Table 9 Binary Input

                                        Object Identifier Object Name Description Object States

                                        Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                        Inactive = Standalone controlActive = BAS control

                                        Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                        Inactive = NormalActive = Locked Out

                                        Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                                        Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                        Inactive = AutoActive = Open

                                        Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                        Inactive = InactiveActive = Active

                                        Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                                        Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                                        Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                        Inactive = DisabledActive = Enabled

                                        Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                        Inactive = DisabledActive = Enabled

                                        Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                        Inactive = InactiveActive = Active

                                        Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                        Inactive = No FlowActive = Flow

                                        Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                        Inactive = InactiveActive = Active

                                        Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                        Inactive = InactiveActive = Active

                                        Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                        Inactive = InactiveActive = Active

                                        Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                                        The status of evaporator frost protection function for circuit 1

                                        Inactive = InactiveActive = Active

                                        Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                                        The status of evaporator frost protection function for circuit 2

                                        Inactive = InactiveActive = Active

                                        Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                                        The status of evaporator frost protection function for circuit 3

                                        Inactive = InactiveActive = Active

                                        Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                                        The status of evaporator frost protection function for circuit 4

                                        Inactive = InactiveActive = Active

                                        Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                        Inactive = De-energizedActive = Energized

                                        Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                        Inactive = InactiveActive = Active

                                        Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                        Inactive = ClosedActive = Open

                                        Table 10 Diagnostics Binary Input

                                        Object Identifier(a) Object Name Description

                                        Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                                        Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                                        Binary Input 31 (use Object Identifier for RT or CSC)

                                        Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                                        Binary Input 31 (use Object Identifier for FAU)

                                        Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                                        Table 8 Binary Output

                                        Object Identifier Object Name DescriptionRelinquish Default Object States

                                        32 ACC-SVP01B-EN bull BCI-I Integration Guide

                                        Object Data Points and Diagnostic Data Points

                                        Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                                        Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                                        Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                                        Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                                        Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                                        Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                                        Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                                        Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                                        Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                                        Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                        Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                        Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                                        Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                                        Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                                        Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                                        Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                                        Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                                        Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                                        Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                                        Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                                        Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                                        Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                                        Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                                        Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                                        Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                                        Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                                        Binary Input 58 (use Object Identifier for RT or CSC)

                                        Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                                        Binary Input 58 (use Object Identifier for FAU)

                                        Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                                        Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                                        Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                                        Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                                        Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                                        Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                                        Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                                        Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                                        Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                                        Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                                        Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                                        Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                                        Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                                        Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                                        Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                                        Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                                        Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                                        Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                                        Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                                        Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                                        Table 10 Diagnostics Binary Input (continued)

                                        Object Identifier(a) Object Name Description

                                        ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                        Object Data Points and Diagnostic Data Points

                                        Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                        Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                        Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                        Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                        Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                        Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                        Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                        Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                        Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                        Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                        Binary Input 86 (use Object Identifier for RT I-pak II)

                                        Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                        Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                        Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                        Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                        Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                        Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                        Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                        Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                        Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                        Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                        Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                        Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                        Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                        Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                        Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                        Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                        Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                        Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                        Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                        Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                        Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                        Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                        Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                        Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                        Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                        Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                        Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                        Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                        Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                        Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                        Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                        Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                        Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                        Binary Input 121 (use Object Identifier for RT)

                                        Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                        Binary Input 121 (use Object Identifier for FAU)

                                        Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                        Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                        Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                        Table 10 Diagnostics Binary Input (continued)

                                        Object Identifier(a) Object Name Description

                                        34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                        Object Data Points and Diagnostic Data Points

                                        Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                        Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                        Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                        Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                        Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                        Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                        Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                        Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                        Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                        Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                        Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                        Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                        Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                        Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                        Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                        Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                        Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                        Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                        Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                        Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                        Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                        Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                        Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                        Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                        Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                        Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                        (a) Object States Inactive = normal and Active = foreign language specific

                                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                        Object Identifier(a) Object Name Description

                                        Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                        Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                        Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                        Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                        Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                        Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                        Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                        Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                        Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                        Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                        Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                        Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                        Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                        Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                        Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                        Table 10 Diagnostics Binary Input (continued)

                                        Object Identifier(a) Object Name Description

                                        ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                        Object Data Points and Diagnostic Data Points

                                        Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                        Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                        Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                        Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                        Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                        Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                        Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                        Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                        Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                        Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                        Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                        Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                        Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                        Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                        Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                        Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                        Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                        Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                        Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                        Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                        Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                        Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                        Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                        Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                        Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                        Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                        Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                        Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                        Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                        Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                        Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                        Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                        Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                        Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                        Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                        Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                        Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                        Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                        Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                        Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                        Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                        Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                        Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                        Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                        Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                        Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                        Object Identifier(a) Object Name Description

                                        36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                        Object Data Points and Diagnostic Data Points

                                        Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                        Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                        Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                        Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                        Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                        Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                        Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                        Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                        Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                        Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                        Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                        Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                        Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                        Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                        Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                        Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                        Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                        Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                        Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                        Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                        Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                        Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                        Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                        Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                        Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                        Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                        Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                        Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                        Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                        Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                        Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                        Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                        Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                        Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                        Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                        Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                        Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                        Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                        Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                        Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                        Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                        Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                        Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                        Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                        Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                        Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                        Object Identifier(a) Object Name Description

                                        ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                        Object Data Points and Diagnostic Data Points

                                        Binary Output 16 Humidification Command Command the operating state of the humidification system

                                        NC 3 HVAC-Advisory HVAC-Advisory

                                        NC 1 HVAC-Critical HVAC-Critical

                                        NC 4 HVAC-Information HVAC-Information

                                        NC 2 HVAC-Service Required HVAC-Service Required

                                        Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                        Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                        Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                        Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                        Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                        Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                        Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                        Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                        Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                        Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                        Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                        Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                        Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                        Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                        Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                        Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                        Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                        Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                        Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                        Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                        Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                        Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                        Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                        Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                        Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                        Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                        Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                        Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                        Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                        Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                        Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                        Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                        Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                        Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                        Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                        Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                        Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                        Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                        Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                        Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                        Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                        Object Identifier(a) Object Name Description

                                        38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                        Object Data Points and Diagnostic Data Points

                                        Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                        Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                        Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                        Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                        Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                        Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                        Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                        Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                        Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                        Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                        Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                        Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                        Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                        Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                        Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                        Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                        Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                        Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                        Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                        Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                        Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                        Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                        Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                        Binary Input 3 Unit Status Indicates the current state of the unit

                                        Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                        Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                        Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                        Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                        Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                        Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                        Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                        (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                        Object Identifier(a) Object Name Description

                                        Table 12 Diagnostic Objects Sorted by Object Name

                                        Object Identifier(a) Object Name ValueRange Description

                                        BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                        BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                        ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                        Object Data Points and Diagnostic Data Points

                                        BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                        BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                        BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                        BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                        BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                        BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                        BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                        BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                        BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                        BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                        BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                        BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                        BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                        BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                        BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                        BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                        BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                        BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                        BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                        BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                        BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                        BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                        BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                        BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                        BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                        BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                        BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                        BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                        BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                        Object Identifier(a) Object Name ValueRange Description

                                        40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                        Object Data Points and Diagnostic Data Points

                                        BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                        BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                        BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                        BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                        BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                        BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                        BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                        BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                        BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                        BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                        BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                        BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                        BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                        BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                        BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                        BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                        BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                        BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                        BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                        BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                        BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                        BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                        BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                        BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                        BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                        BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                        BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                        BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                        BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                        Object Identifier(a) Object Name ValueRange Description

                                        ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                        Object Data Points and Diagnostic Data Points

                                        BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                        BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                        BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                        BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                        BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                        BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                        BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                        BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                        BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                        BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                        BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                        BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                        BI 121 (use Object Identifier for RT)

                                        Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                        BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                        BI 58 (use Object Identifier for RT or CSC)

                                        Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                        BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                        BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                        BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                        BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                        BI 31 (use Object Identifier for RT CSC)

                                        Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                        BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                        BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                        BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                        BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                        BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                        BI 121 (use Object Identifier for FAU)

                                        Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                        B1 31 (use Object Identifier for FAU)

                                        Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                        BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                        BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                        Object Identifier(a) Object Name ValueRange Description

                                        42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                        Object Data Points and Diagnostic Data Points

                                        BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                        BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                        BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                        BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                        BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                        BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                        BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                        BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                        BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                        BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                        BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                        BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                        BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                        BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                        BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                        BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                        BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                        BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                        BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                        BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                        BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                        BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                        BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                        1 = active Diagnostic Vel Press Sensor (Rear)

                                        BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                        Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                        BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                        BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                        BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                        BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                        BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                        Object Identifier(a) Object Name ValueRange Description

                                        ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                        Object Data Points and Diagnostic Data Points

                                        BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                        BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                        BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                        BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                        BI 58 (use Object Identifier for FAU)

                                        Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                        (a) BI=Binary Input

                                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                        Object Identifier(a) Object Name ValueRange Description

                                        44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                        Additional Resources

                                        Additional Resources

                                        Use the following documents and links as additional resources

                                        bull Product support online

                                        bull wwwbacnetorg

                                        bull wwwbacnetassociationorg

                                        bull wwwashraeorg

                                        bull Tracer TU Help online

                                        bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                        bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                        Note For further assistance contact your local Trane sales office

                                        ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                        Glossary

                                        A

                                        ASHRAE

                                        See American Society of Heating Refrigeration and Air-conditioning Engineers

                                        American Society of Heating Refrigeration and Air-

                                        conditioning Engineers

                                        An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                        BBACnettrade

                                        See Building Automation Control network

                                        BACnet interoperability building blocks

                                        A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                        BACnet object

                                        An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                        baud rate

                                        The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                        BIBB

                                        See BACnet interoperability building blocks

                                        Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                        advocates BACnet protocol for use in system-level control devices

                                        device

                                        A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                        Device ID

                                        The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                        Iinteroperability

                                        The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                        Pprotocol

                                        A set of rules (language) that governs the exchange of data over a digital communications system

                                        S

                                        stand-alone operation

                                        Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                        wwwtranecom

                                        For more information contact your local Trane office or e-mail us at comforttranecom

                                        Literature Order Number ACC-SVP01B-EN

                                        Date September 2009

                                        Supersedes ACC-SVP01A-EN

                                        Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                        • Table of Contents
                                        • Overview
                                        • Ordering Numbers
                                        • BACnet Protocol
                                        • BCI-I Configuration
                                          • Overview
                                          • Starting a Session of Tracer TU and Direct Connection
                                          • Reset to Factory Default
                                          • IP Units Configuration
                                          • BACnet Object Configuration
                                          • Change Baud Rate
                                          • Change Device ID
                                          • Stand-alone or BAS Operation
                                            • IntelliPak Control Configuration
                                            • BAS Unit Control
                                            • Periodic Update of BAS Values
                                            • BAS Communication Failure
                                              • InputOutput Commands and Calculations
                                                • System Control Command
                                                • Filter Timer Reset Command
                                                • Diagnostics Reset Command
                                                • Setpoint Calculations
                                                • Timestamp Configuration
                                                    • BCI IntelliPak Rotary Switches and LEDs
                                                      • Rotary Switches
                                                      • LEDs Description Behavior and Troubleshooting
                                                      • 24 Vac Measurement
                                                      • Ground Measurements
                                                        • BACnet Data Points and Configuration Property Definitions
                                                          • BACnet Protocol Implementation Conformance Statement (PICS)
                                                            • Standardized Device Profile (Annex L)
                                                            • Interoperability Building Blocks (Annex K)
                                                            • Segmentation Capability
                                                            • Object Types
                                                              • BACnet Protocol
                                                                • Data Link Layer Options
                                                                • Device Address Binding
                                                                • Networking Options
                                                                • Character Sets
                                                                    • Object Data Points and Diagnostic Data Points
                                                                    • Additional Resources
                                                                    • Glossary

                                          ACC-SVP01B-EN bull BCI-I Integration Guide 21

                                          BACnet Data Points and Configuration Property Definitions

                                          Multistate Input

                                          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                                          bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                                          bull State_Textbull Reliabilitybull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                          Yes Yes only user created objects

                                          Multistate Output

                                          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_Statesbull Priority_Arraybull Relinquish Default

                                          bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Time_Delaybull Notification_Classbull Event_Enablebull Notify_Type

                                          bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Feedback_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                          Yes Yes only user created objects

                                          Multistate Value

                                          bull Object_Identifierbull Object_Namebull Object_Typebull Present_Valuebull Status_Flagsbull Event_Statebull Out_Of_Servicebull Number_Of_States

                                          bull Object_Namebull Descriptionbull State_Textbull Out_Of_Servicebull Present_Valuebull Reliabilitybull Priority_Arraybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Notify_Type

                                          bull State_Textbull Reliabilitybull Relinquish_Defaultbull Time_Delaybull Notification_Classbull Alarm_Valuesbull Fault_Valuesbull Event_Enablebull Acked_Transitionsbull Notify_Typebull Event_Time_Stamps

                                          Yes Yes only user created objects

                                          Notification Class

                                          bull Object_Identifierbull Object_Namebull Object_Typebull Notification_Classbull Prioritybull Ack_Requiredbull Recipient_List

                                          bull Object_Namebull Prioritybull Ack_Requiredbull Recipient_List

                                          None Yes Yes only user created objects

                                          Trend bull Object_Identifierbull Object_Namebull Object_Typebull Log_Enablebull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Total_Record_Countbull Event_State

                                          bull Object_Namebull Log_Enablebull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Log_Bufferbull Record_Countbull Notification_Thresholdbull Notification_Classbull Event_Enablebull Notify_Type

                                          bull Start_Timebull Stop_Timebull Log_DeviceObjectPropertybull Log_Intervalbull Stop_When_Fullbull Buffer_Sizebull Notification_Thresholdbull Records_Since_Notificationbull Last_Notify_Recordbull Notification_Classbull Event_Enablebull Acked_Transitionsbull Event_Time_Stamps

                                          Yes Yes only user created objects

                                          (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE

                                          Table 2 Descriptions and configurations (continued)

                                          Object Type Required Properties Read Properties Written(a) Optional Properties Read

                                          Ability to Create

                                          Ability to Delete

                                          22 ACC-SVP01B-EN bull BCI-I Integration Guide

                                          BACnet Data Points and Configuration Property Definitions

                                          BACnet Protocol

                                          Data Link Layer Options

                                          Device Address Binding

                                          Networking Options

                                          Data Link Layer Description Supported Option

                                          ANSIATA 8781 25 Mb ARCNET (Clause 8)

                                          ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

                                          BACnet IP (Annex J)

                                          BACnet IP (Annex J) Foreign Device

                                          ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

                                          LonTalk (Clause 11) Medium

                                          MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

                                          MSTP Slave (Clause 9) Baud Rate(s)

                                          Other

                                          Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

                                          Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

                                          Device Address Binding Supported

                                          Static Device Binding Supported

                                          Networking DescriptionsSupported

                                          Option

                                          Annex H BACnet Tunneling

                                          BACnetIP Broadcast Management Device (BBMD)

                                          Does the BBMD Support Registrations by Foreign Devices

                                          Router

                                          ACC-SVP01B-EN bull BCI-I Integration Guide 23

                                          BACnet Data Points and Configuration Property Definitions

                                          Character Sets

                                          Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

                                          Character Set Descriptions Supported

                                          ANSI X34

                                          IBMMicrosoft DBCS

                                          ISO 10646 (UCS-4)

                                          ISO 10646 (UCS2)

                                          ISO 8859-1

                                          JIS C 6226

                                          24 ACC-SVP01B-EN bull BCI-I Integration Guide

                                          Object Data Points and Diagnostic Data Points

                                          Object Data Points and Diagnostic Data Points

                                          For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

                                          Table 3 Analog Output

                                          Object Identifier Object Name Description Units Valid Range

                                          Refresh Rate

                                          (Sec)

                                          Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

                                          Percent (98) 0 to 100 NA

                                          Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

                                          Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

                                          Degrees-Fahrenheit (64) 500 to 900 NA

                                          Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

                                          BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

                                          Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

                                          Degrees-Fahrenheit (64) 400 to 900 NA

                                          Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

                                          Degrees-Fahrenheit (64) 400 to 1800 NA

                                          Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

                                          070 to 510 (Ipak II) NA

                                          Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

                                          003 to 030-002 to 030 (enhanced StatiTrac)

                                          NA

                                          Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

                                          -028 to 050-067 to 067 (enhanced StatiTrac)

                                          900

                                          Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                          Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                          Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

                                          00 to 79 (Ipak II) 900

                                          Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                          Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

                                          Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

                                          Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

                                          Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

                                          Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                          Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                          Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

                                          Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

                                          Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

                                          ACC-SVP01B-EN bull BCI-I Integration Guide 25

                                          Object Data Points and Diagnostic Data Points

                                          Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                                          Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                                          Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                                          Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                                          Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                                          Cooling temperature setpoint used for control in unoccupied mode

                                          Degrees-Fahrenheit (64) 520 to 880 NA

                                          Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                                          Heating temperature setpoint used for control in unoccupied mode

                                          Degrees-Fahrenheit (64) 500 to 900 NA

                                          Table 4 Analog Input

                                          Object Identifier Object Name Description Units (Listed Are Defaults)

                                          Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                                          Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                                          Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                                          Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                                          Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                                          Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                                          Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                                          Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                                          Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                                          Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                                          Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                                          Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                                          Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                                          Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                                          Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                                          Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                                          Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                                          Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                                          Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                                          Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                                          Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                                          Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                                          Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                                          Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                          Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                          Table 3 Analog Output (continued)

                                          Object Identifier Object Name Description Units Valid Range

                                          Refresh Rate

                                          (Sec)

                                          26 ACC-SVP01B-EN bull BCI-I Integration Guide

                                          Object Data Points and Diagnostic Data Points

                                          Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                                          Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                          Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                          Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                                          Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                                          Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                                          Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                                          Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                                          Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                          Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                          Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                          Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                          Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                                          Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                                          Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                                          Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                                          Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                                          Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                                          Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                                          Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                                          Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                                          Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                          Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                          Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                                          The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                                          Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                                          The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                                          Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                                          Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                                          Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                                          Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                                          Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                                          Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                                          Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                                          Table 4 Analog Input (continued)

                                          Object Identifier Object Name Description Units (Listed Are Defaults)

                                          ACC-SVP01B-EN bull BCI-I Integration Guide 27

                                          Object Data Points and Diagnostic Data Points

                                          Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                                          Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                                          Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                                          Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                                          The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                                          Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                                          Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                                          Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                                          Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                                          Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                                          Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                          Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                          Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                                          Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                                          Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                                          Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                                          Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                                          Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                                          Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                                          Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                                          Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                                          Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                                          Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                                          Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                                          Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                                          Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                                          Table 5 Analog Value

                                          Object Identifier Object Name Description Units Valid Range

                                          Analog Value 1 Filter Runtime Hours Setpoint

                                          The setpoint value used by the filter run hours calculation

                                          Hours (71) 0 to 10000

                                          Table 4 Analog Input (continued)

                                          Object Identifier Object Name Description Units (Listed Are Defaults)

                                          28 ACC-SVP01B-EN bull BCI-I Integration Guide

                                          Object Data Points and Diagnostic Data Points

                                          Table 6 Multistate Output

                                          BCI-I Object Identifier Object Name Description Object States

                                          Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                                          Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                          1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                                          Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                                          Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                          1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                          Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                          1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                          Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                          1 = Flow2 = No Flow3 = Auto

                                          Table 7 Multistate Input

                                          BCI-I Object Identifier Object Name Description Object States

                                          Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                          1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                                          Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                          1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                                          Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                          1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                                          Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                          1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                                          ACC-SVP01B-EN bull BCI-I Integration Guide 29

                                          Object Data Points and Diagnostic Data Points

                                          Multi-State Input 15 Economizer Decision Method

                                          Unit method to determine when the economizer system is enabled

                                          1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                                          Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                                          Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                                          Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                          1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                          Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                          1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                          Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                          1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                                          Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                          1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                          Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                          1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                          Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                          1 = Idle2 = On3 = Cancel

                                          Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                          1 = Off2 = On3 = Not Present

                                          Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                          1 = Off2 = On3 = Not Present

                                          Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                          1 = Off2 = On3 = Not Present

                                          Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                          1 = Off|2 = On3 = Not Present

                                          Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                          1 = Off2 = On3 = Not Present

                                          Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                          1 = Off2 = On3 = Not Present

                                          Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                          1 = Off2 = On3 = Not Present

                                          Table 7 Multistate Input (continued)

                                          BCI-I Object Identifier Object Name Description Object States

                                          30 ACC-SVP01B-EN bull BCI-I Integration Guide

                                          Object Data Points and Diagnostic Data Points

                                          Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                          1 = Off2 = On3 = Not Present

                                          Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                          1 = Off2 = On3 = Not Present

                                          Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                                          Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                                          Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                                          Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                                          Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                          1 = Off2 = On3 = Not Present

                                          Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                          1= Off2= On3= Not Present

                                          Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                                          Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                                          Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                                          Multi-State Input 43 Outdoor Air Damper Status

                                          Indicates the operating state of the outdoor damper

                                          1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                                          Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                          1 = Disabled2 = Enabled3 = Not Present

                                          Table 8 Binary Output

                                          Object Identifier Object Name DescriptionRelinquish Default Object States

                                          Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                                          Active = BAS Control

                                          Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                                          Active = Heating Locked Out

                                          Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                                          Active = Cooling Locked Out

                                          Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                                          Active = Enabled

                                          Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                                          Active = On

                                          Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                                          Inactive Inactive = DisabledActive = Enabled

                                          Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                                          Active = Reset

                                          Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                                          Active = Reset

                                          Table 7 Multistate Input (continued)

                                          BCI-I Object Identifier Object Name Description Object States

                                          ACC-SVP01B-EN bull BCI-I Integration Guide 31

                                          Object Data Points and Diagnostic Data Points

                                          Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                                          Active = Auto

                                          Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                                          Active = Auto

                                          Table 9 Binary Input

                                          Object Identifier Object Name Description Object States

                                          Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                          Inactive = Standalone controlActive = BAS control

                                          Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                          Inactive = NormalActive = Locked Out

                                          Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                                          Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                          Inactive = AutoActive = Open

                                          Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                          Inactive = InactiveActive = Active

                                          Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                                          Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                                          Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                          Inactive = DisabledActive = Enabled

                                          Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                          Inactive = DisabledActive = Enabled

                                          Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                          Inactive = InactiveActive = Active

                                          Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                          Inactive = No FlowActive = Flow

                                          Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                          Inactive = InactiveActive = Active

                                          Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                          Inactive = InactiveActive = Active

                                          Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                          Inactive = InactiveActive = Active

                                          Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                                          The status of evaporator frost protection function for circuit 1

                                          Inactive = InactiveActive = Active

                                          Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                                          The status of evaporator frost protection function for circuit 2

                                          Inactive = InactiveActive = Active

                                          Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                                          The status of evaporator frost protection function for circuit 3

                                          Inactive = InactiveActive = Active

                                          Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                                          The status of evaporator frost protection function for circuit 4

                                          Inactive = InactiveActive = Active

                                          Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                          Inactive = De-energizedActive = Energized

                                          Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                          Inactive = InactiveActive = Active

                                          Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                          Inactive = ClosedActive = Open

                                          Table 10 Diagnostics Binary Input

                                          Object Identifier(a) Object Name Description

                                          Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                                          Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                                          Binary Input 31 (use Object Identifier for RT or CSC)

                                          Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                                          Binary Input 31 (use Object Identifier for FAU)

                                          Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                                          Table 8 Binary Output

                                          Object Identifier Object Name DescriptionRelinquish Default Object States

                                          32 ACC-SVP01B-EN bull BCI-I Integration Guide

                                          Object Data Points and Diagnostic Data Points

                                          Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                                          Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                                          Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                                          Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                                          Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                                          Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                                          Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                                          Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                                          Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                                          Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                          Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                          Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                                          Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                                          Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                                          Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                                          Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                                          Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                                          Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                                          Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                                          Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                                          Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                                          Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                                          Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                                          Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                                          Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                                          Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                                          Binary Input 58 (use Object Identifier for RT or CSC)

                                          Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                                          Binary Input 58 (use Object Identifier for FAU)

                                          Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                                          Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                                          Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                                          Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                                          Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                                          Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                                          Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                                          Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                                          Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                                          Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                                          Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                                          Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                                          Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                                          Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                                          Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                                          Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                                          Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                                          Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                                          Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                                          Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                                          Table 10 Diagnostics Binary Input (continued)

                                          Object Identifier(a) Object Name Description

                                          ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                          Object Data Points and Diagnostic Data Points

                                          Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                          Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                          Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                          Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                          Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                          Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                          Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                          Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                          Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                          Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                          Binary Input 86 (use Object Identifier for RT I-pak II)

                                          Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                          Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                          Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                          Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                          Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                          Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                          Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                          Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                          Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                          Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                          Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                          Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                          Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                          Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                          Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                          Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                          Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                          Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                          Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                          Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                          Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                          Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                          Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                          Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                          Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                          Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                          Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                          Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                          Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                          Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                          Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                          Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                          Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                          Binary Input 121 (use Object Identifier for RT)

                                          Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                          Binary Input 121 (use Object Identifier for FAU)

                                          Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                          Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                          Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                          Table 10 Diagnostics Binary Input (continued)

                                          Object Identifier(a) Object Name Description

                                          34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                          Object Data Points and Diagnostic Data Points

                                          Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                          Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                          Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                          Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                          Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                          Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                          Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                          Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                          Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                          Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                          Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                          Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                          Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                          Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                          Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                          Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                          Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                          Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                          Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                          Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                          Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                          Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                          Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                          Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                          Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                          Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                          (a) Object States Inactive = normal and Active = foreign language specific

                                          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                          Object Identifier(a) Object Name Description

                                          Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                          Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                          Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                          Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                          Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                          Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                          Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                          Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                          Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                          Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                          Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                          Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                          Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                          Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                          Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                          Table 10 Diagnostics Binary Input (continued)

                                          Object Identifier(a) Object Name Description

                                          ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                          Object Data Points and Diagnostic Data Points

                                          Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                          Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                          Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                          Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                          Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                          Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                          Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                          Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                          Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                          Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                          Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                          Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                          Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                          Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                          Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                          Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                          Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                          Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                          Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                          Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                          Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                          Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                          Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                          Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                          Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                          Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                          Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                          Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                          Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                          Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                          Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                          Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                          Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                          Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                          Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                          Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                          Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                          Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                          Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                          Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                          Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                          Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                          Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                          Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                          Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                          Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                          Object Identifier(a) Object Name Description

                                          36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                          Object Data Points and Diagnostic Data Points

                                          Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                          Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                          Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                          Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                          Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                          Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                          Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                          Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                          Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                          Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                          Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                          Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                          Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                          Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                          Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                          Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                          Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                          Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                          Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                          Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                          Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                          Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                          Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                          Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                          Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                          Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                          Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                          Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                          Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                          Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                          Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                          Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                          Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                          Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                          Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                          Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                          Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                          Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                          Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                          Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                          Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                          Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                          Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                          Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                          Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                          Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                          Object Identifier(a) Object Name Description

                                          ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                          Object Data Points and Diagnostic Data Points

                                          Binary Output 16 Humidification Command Command the operating state of the humidification system

                                          NC 3 HVAC-Advisory HVAC-Advisory

                                          NC 1 HVAC-Critical HVAC-Critical

                                          NC 4 HVAC-Information HVAC-Information

                                          NC 2 HVAC-Service Required HVAC-Service Required

                                          Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                          Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                          Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                          Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                          Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                          Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                          Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                          Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                          Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                          Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                          Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                          Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                          Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                          Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                          Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                          Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                          Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                          Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                          Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                          Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                          Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                          Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                          Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                          Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                          Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                          Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                          Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                          Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                          Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                          Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                          Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                          Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                          Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                          Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                          Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                          Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                          Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                          Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                          Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                          Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                          Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                          Object Identifier(a) Object Name Description

                                          38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                          Object Data Points and Diagnostic Data Points

                                          Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                          Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                          Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                          Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                          Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                          Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                          Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                          Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                          Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                          Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                          Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                          Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                          Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                          Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                          Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                          Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                          Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                          Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                          Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                          Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                          Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                          Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                          Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                          Binary Input 3 Unit Status Indicates the current state of the unit

                                          Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                          Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                          Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                          Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                          Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                          Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                          Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                          (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                          Object Identifier(a) Object Name Description

                                          Table 12 Diagnostic Objects Sorted by Object Name

                                          Object Identifier(a) Object Name ValueRange Description

                                          BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                          BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                          ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                          Object Data Points and Diagnostic Data Points

                                          BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                          BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                          BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                          BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                          BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                          BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                          BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                          BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                          BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                          BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                          BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                          BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                          BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                          BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                          BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                          BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                          BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                          BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                          BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                          BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                          BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                          BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                          BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                          BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                          BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                          BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                          BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                          BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                          BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                          Object Identifier(a) Object Name ValueRange Description

                                          40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                          Object Data Points and Diagnostic Data Points

                                          BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                          BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                          BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                          BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                          BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                          BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                          BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                          BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                          BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                          BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                          BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                          BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                          BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                          BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                          BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                          BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                          BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                          BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                          BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                          BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                          BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                          BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                          BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                          BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                          BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                          BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                          BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                          BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                          BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                          Object Identifier(a) Object Name ValueRange Description

                                          ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                          Object Data Points and Diagnostic Data Points

                                          BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                          BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                          BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                          BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                          BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                          BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                          BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                          BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                          BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                          BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                          BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                          BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                          BI 121 (use Object Identifier for RT)

                                          Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                          BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                          BI 58 (use Object Identifier for RT or CSC)

                                          Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                          BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                          BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                          BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                          BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                          BI 31 (use Object Identifier for RT CSC)

                                          Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                          BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                          BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                          BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                          BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                          BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                          BI 121 (use Object Identifier for FAU)

                                          Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                          B1 31 (use Object Identifier for FAU)

                                          Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                          BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                          BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                          Object Identifier(a) Object Name ValueRange Description

                                          42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                          Object Data Points and Diagnostic Data Points

                                          BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                          BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                          BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                          BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                          BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                          BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                          BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                          BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                          BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                          BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                          BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                          BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                          BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                          BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                          BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                          BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                          BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                          BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                          BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                          BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                          BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                          BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                          BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                          1 = active Diagnostic Vel Press Sensor (Rear)

                                          BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                          Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                          BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                          BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                          BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                          BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                          BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                          Object Identifier(a) Object Name ValueRange Description

                                          ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                          Object Data Points and Diagnostic Data Points

                                          BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                          BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                          BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                          BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                          BI 58 (use Object Identifier for FAU)

                                          Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                          (a) BI=Binary Input

                                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                          Object Identifier(a) Object Name ValueRange Description

                                          44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                          Additional Resources

                                          Additional Resources

                                          Use the following documents and links as additional resources

                                          bull Product support online

                                          bull wwwbacnetorg

                                          bull wwwbacnetassociationorg

                                          bull wwwashraeorg

                                          bull Tracer TU Help online

                                          bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                          bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                          Note For further assistance contact your local Trane sales office

                                          ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                          Glossary

                                          A

                                          ASHRAE

                                          See American Society of Heating Refrigeration and Air-conditioning Engineers

                                          American Society of Heating Refrigeration and Air-

                                          conditioning Engineers

                                          An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                          BBACnettrade

                                          See Building Automation Control network

                                          BACnet interoperability building blocks

                                          A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                          BACnet object

                                          An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                          baud rate

                                          The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                          BIBB

                                          See BACnet interoperability building blocks

                                          Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                          advocates BACnet protocol for use in system-level control devices

                                          device

                                          A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                          Device ID

                                          The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                          Iinteroperability

                                          The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                          Pprotocol

                                          A set of rules (language) that governs the exchange of data over a digital communications system

                                          S

                                          stand-alone operation

                                          Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                          wwwtranecom

                                          For more information contact your local Trane office or e-mail us at comforttranecom

                                          Literature Order Number ACC-SVP01B-EN

                                          Date September 2009

                                          Supersedes ACC-SVP01A-EN

                                          Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                          • Table of Contents
                                          • Overview
                                          • Ordering Numbers
                                          • BACnet Protocol
                                          • BCI-I Configuration
                                            • Overview
                                            • Starting a Session of Tracer TU and Direct Connection
                                            • Reset to Factory Default
                                            • IP Units Configuration
                                            • BACnet Object Configuration
                                            • Change Baud Rate
                                            • Change Device ID
                                            • Stand-alone or BAS Operation
                                              • IntelliPak Control Configuration
                                              • BAS Unit Control
                                              • Periodic Update of BAS Values
                                              • BAS Communication Failure
                                                • InputOutput Commands and Calculations
                                                  • System Control Command
                                                  • Filter Timer Reset Command
                                                  • Diagnostics Reset Command
                                                  • Setpoint Calculations
                                                  • Timestamp Configuration
                                                      • BCI IntelliPak Rotary Switches and LEDs
                                                        • Rotary Switches
                                                        • LEDs Description Behavior and Troubleshooting
                                                        • 24 Vac Measurement
                                                        • Ground Measurements
                                                          • BACnet Data Points and Configuration Property Definitions
                                                            • BACnet Protocol Implementation Conformance Statement (PICS)
                                                              • Standardized Device Profile (Annex L)
                                                              • Interoperability Building Blocks (Annex K)
                                                              • Segmentation Capability
                                                              • Object Types
                                                                • BACnet Protocol
                                                                  • Data Link Layer Options
                                                                  • Device Address Binding
                                                                  • Networking Options
                                                                  • Character Sets
                                                                      • Object Data Points and Diagnostic Data Points
                                                                      • Additional Resources
                                                                      • Glossary

                                            22 ACC-SVP01B-EN bull BCI-I Integration Guide

                                            BACnet Data Points and Configuration Property Definitions

                                            BACnet Protocol

                                            Data Link Layer Options

                                            Device Address Binding

                                            Networking Options

                                            Data Link Layer Description Supported Option

                                            ANSIATA 8781 25 Mb ARCNET (Clause 8)

                                            ANSIATA 8781 RS-485 ARCNET (Clause 8) Baud Rate(s)

                                            BACnet IP (Annex J)

                                            BACnet IP (Annex J) Foreign Device

                                            ISO 8802-3 Ethernet (Clause 7)(10Base2 10Base5 10BaseT Fiber)

                                            LonTalk (Clause 11) Medium

                                            MSTP Master (Clause 9) Baud Rate(s) 9600 19200 38400 76800 and 115200 15 Nominal Baud Rate

                                            MSTP Slave (Clause 9) Baud Rate(s)

                                            Other

                                            Point-to-Point EIA 232 (Clause 10) Baud Rate(s) 9600 19200 38400

                                            Point-to-Point Modem (Clause 10) Baud Rate(s) 9600 19200 38400

                                            Device Address Binding Supported

                                            Static Device Binding Supported

                                            Networking DescriptionsSupported

                                            Option

                                            Annex H BACnet Tunneling

                                            BACnetIP Broadcast Management Device (BBMD)

                                            Does the BBMD Support Registrations by Foreign Devices

                                            Router

                                            ACC-SVP01B-EN bull BCI-I Integration Guide 23

                                            BACnet Data Points and Configuration Property Definitions

                                            Character Sets

                                            Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

                                            Character Set Descriptions Supported

                                            ANSI X34

                                            IBMMicrosoft DBCS

                                            ISO 10646 (UCS-4)

                                            ISO 10646 (UCS2)

                                            ISO 8859-1

                                            JIS C 6226

                                            24 ACC-SVP01B-EN bull BCI-I Integration Guide

                                            Object Data Points and Diagnostic Data Points

                                            Object Data Points and Diagnostic Data Points

                                            For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

                                            Table 3 Analog Output

                                            Object Identifier Object Name Description Units Valid Range

                                            Refresh Rate

                                            (Sec)

                                            Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

                                            Percent (98) 0 to 100 NA

                                            Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

                                            Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

                                            Degrees-Fahrenheit (64) 500 to 900 NA

                                            Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

                                            BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

                                            Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

                                            Degrees-Fahrenheit (64) 400 to 900 NA

                                            Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

                                            Degrees-Fahrenheit (64) 400 to 1800 NA

                                            Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

                                            070 to 510 (Ipak II) NA

                                            Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

                                            003 to 030-002 to 030 (enhanced StatiTrac)

                                            NA

                                            Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

                                            -028 to 050-067 to 067 (enhanced StatiTrac)

                                            900

                                            Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                            Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                            Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

                                            00 to 79 (Ipak II) 900

                                            Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                            Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

                                            Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

                                            Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

                                            Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

                                            Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                            Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                            Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

                                            Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

                                            Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

                                            ACC-SVP01B-EN bull BCI-I Integration Guide 25

                                            Object Data Points and Diagnostic Data Points

                                            Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                                            Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                                            Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                                            Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                                            Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                                            Cooling temperature setpoint used for control in unoccupied mode

                                            Degrees-Fahrenheit (64) 520 to 880 NA

                                            Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                                            Heating temperature setpoint used for control in unoccupied mode

                                            Degrees-Fahrenheit (64) 500 to 900 NA

                                            Table 4 Analog Input

                                            Object Identifier Object Name Description Units (Listed Are Defaults)

                                            Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                                            Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                                            Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                                            Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                                            Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                                            Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                                            Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                                            Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                                            Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                                            Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                                            Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                                            Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                                            Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                                            Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                                            Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                                            Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                                            Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                                            Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                                            Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                                            Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                                            Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                                            Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                                            Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                                            Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                            Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                            Table 3 Analog Output (continued)

                                            Object Identifier Object Name Description Units Valid Range

                                            Refresh Rate

                                            (Sec)

                                            26 ACC-SVP01B-EN bull BCI-I Integration Guide

                                            Object Data Points and Diagnostic Data Points

                                            Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                                            Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                            Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                            Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                                            Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                                            Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                                            Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                                            Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                                            Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                            Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                            Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                            Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                            Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                                            Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                                            Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                                            Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                                            Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                                            Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                                            Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                                            Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                                            Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                                            Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                            Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                            Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                                            The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                                            Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                                            The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                                            Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                                            Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                                            Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                                            Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                                            Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                                            Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                                            Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                                            Table 4 Analog Input (continued)

                                            Object Identifier Object Name Description Units (Listed Are Defaults)

                                            ACC-SVP01B-EN bull BCI-I Integration Guide 27

                                            Object Data Points and Diagnostic Data Points

                                            Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                                            Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                                            Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                                            Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                                            The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                                            Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                                            Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                                            Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                                            Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                                            Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                                            Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                            Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                            Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                                            Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                                            Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                                            Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                                            Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                                            Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                                            Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                                            Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                                            Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                                            Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                                            Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                                            Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                                            Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                                            Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                                            Table 5 Analog Value

                                            Object Identifier Object Name Description Units Valid Range

                                            Analog Value 1 Filter Runtime Hours Setpoint

                                            The setpoint value used by the filter run hours calculation

                                            Hours (71) 0 to 10000

                                            Table 4 Analog Input (continued)

                                            Object Identifier Object Name Description Units (Listed Are Defaults)

                                            28 ACC-SVP01B-EN bull BCI-I Integration Guide

                                            Object Data Points and Diagnostic Data Points

                                            Table 6 Multistate Output

                                            BCI-I Object Identifier Object Name Description Object States

                                            Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                                            Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                            1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                                            Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                                            Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                            1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                            Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                            1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                            Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                            1 = Flow2 = No Flow3 = Auto

                                            Table 7 Multistate Input

                                            BCI-I Object Identifier Object Name Description Object States

                                            Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                            1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                                            Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                            1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                                            Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                            1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                                            Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                            1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                                            ACC-SVP01B-EN bull BCI-I Integration Guide 29

                                            Object Data Points and Diagnostic Data Points

                                            Multi-State Input 15 Economizer Decision Method

                                            Unit method to determine when the economizer system is enabled

                                            1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                                            Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                                            Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                                            Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                            1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                            Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                            1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                            Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                            1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                                            Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                            1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                            Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                            1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                            Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                            1 = Idle2 = On3 = Cancel

                                            Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                            1 = Off2 = On3 = Not Present

                                            Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                            1 = Off2 = On3 = Not Present

                                            Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                            1 = Off2 = On3 = Not Present

                                            Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                            1 = Off|2 = On3 = Not Present

                                            Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                            1 = Off2 = On3 = Not Present

                                            Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                            1 = Off2 = On3 = Not Present

                                            Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                            1 = Off2 = On3 = Not Present

                                            Table 7 Multistate Input (continued)

                                            BCI-I Object Identifier Object Name Description Object States

                                            30 ACC-SVP01B-EN bull BCI-I Integration Guide

                                            Object Data Points and Diagnostic Data Points

                                            Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                            1 = Off2 = On3 = Not Present

                                            Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                            1 = Off2 = On3 = Not Present

                                            Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                                            Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                                            Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                                            Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                                            Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                            1 = Off2 = On3 = Not Present

                                            Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                            1= Off2= On3= Not Present

                                            Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                                            Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                                            Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                                            Multi-State Input 43 Outdoor Air Damper Status

                                            Indicates the operating state of the outdoor damper

                                            1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                                            Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                            1 = Disabled2 = Enabled3 = Not Present

                                            Table 8 Binary Output

                                            Object Identifier Object Name DescriptionRelinquish Default Object States

                                            Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                                            Active = BAS Control

                                            Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                                            Active = Heating Locked Out

                                            Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                                            Active = Cooling Locked Out

                                            Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                                            Active = Enabled

                                            Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                                            Active = On

                                            Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                                            Inactive Inactive = DisabledActive = Enabled

                                            Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                                            Active = Reset

                                            Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                                            Active = Reset

                                            Table 7 Multistate Input (continued)

                                            BCI-I Object Identifier Object Name Description Object States

                                            ACC-SVP01B-EN bull BCI-I Integration Guide 31

                                            Object Data Points and Diagnostic Data Points

                                            Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                                            Active = Auto

                                            Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                                            Active = Auto

                                            Table 9 Binary Input

                                            Object Identifier Object Name Description Object States

                                            Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                            Inactive = Standalone controlActive = BAS control

                                            Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                            Inactive = NormalActive = Locked Out

                                            Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                                            Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                            Inactive = AutoActive = Open

                                            Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                            Inactive = InactiveActive = Active

                                            Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                                            Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                                            Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                            Inactive = DisabledActive = Enabled

                                            Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                            Inactive = DisabledActive = Enabled

                                            Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                            Inactive = InactiveActive = Active

                                            Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                            Inactive = No FlowActive = Flow

                                            Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                            Inactive = InactiveActive = Active

                                            Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                            Inactive = InactiveActive = Active

                                            Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                            Inactive = InactiveActive = Active

                                            Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                                            The status of evaporator frost protection function for circuit 1

                                            Inactive = InactiveActive = Active

                                            Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                                            The status of evaporator frost protection function for circuit 2

                                            Inactive = InactiveActive = Active

                                            Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                                            The status of evaporator frost protection function for circuit 3

                                            Inactive = InactiveActive = Active

                                            Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                                            The status of evaporator frost protection function for circuit 4

                                            Inactive = InactiveActive = Active

                                            Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                            Inactive = De-energizedActive = Energized

                                            Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                            Inactive = InactiveActive = Active

                                            Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                            Inactive = ClosedActive = Open

                                            Table 10 Diagnostics Binary Input

                                            Object Identifier(a) Object Name Description

                                            Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                                            Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                                            Binary Input 31 (use Object Identifier for RT or CSC)

                                            Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                                            Binary Input 31 (use Object Identifier for FAU)

                                            Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                                            Table 8 Binary Output

                                            Object Identifier Object Name DescriptionRelinquish Default Object States

                                            32 ACC-SVP01B-EN bull BCI-I Integration Guide

                                            Object Data Points and Diagnostic Data Points

                                            Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                                            Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                                            Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                                            Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                                            Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                                            Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                                            Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                                            Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                                            Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                                            Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                            Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                            Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                                            Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                                            Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                                            Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                                            Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                                            Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                                            Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                                            Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                                            Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                                            Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                                            Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                                            Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                                            Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                                            Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                                            Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                                            Binary Input 58 (use Object Identifier for RT or CSC)

                                            Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                                            Binary Input 58 (use Object Identifier for FAU)

                                            Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                                            Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                                            Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                                            Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                                            Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                                            Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                                            Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                                            Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                                            Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                                            Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                                            Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                                            Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                                            Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                                            Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                                            Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                                            Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                                            Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                                            Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                                            Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                                            Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                                            Table 10 Diagnostics Binary Input (continued)

                                            Object Identifier(a) Object Name Description

                                            ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                            Object Data Points and Diagnostic Data Points

                                            Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                            Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                            Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                            Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                            Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                            Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                            Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                            Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                            Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                            Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                            Binary Input 86 (use Object Identifier for RT I-pak II)

                                            Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                            Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                            Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                            Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                            Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                            Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                            Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                            Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                            Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                            Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                            Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                            Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                            Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                            Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                            Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                            Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                            Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                            Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                            Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                            Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                            Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                            Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                            Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                            Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                            Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                            Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                            Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                            Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                            Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                            Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                            Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                            Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                            Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                            Binary Input 121 (use Object Identifier for RT)

                                            Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                            Binary Input 121 (use Object Identifier for FAU)

                                            Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                            Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                            Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                            Table 10 Diagnostics Binary Input (continued)

                                            Object Identifier(a) Object Name Description

                                            34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                            Object Data Points and Diagnostic Data Points

                                            Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                            Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                            Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                            Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                            Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                            Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                            Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                            Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                            Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                            Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                            Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                            Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                            Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                            Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                            Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                            Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                            Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                            Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                            Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                            Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                            Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                            Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                            Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                            Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                            Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                            Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                            (a) Object States Inactive = normal and Active = foreign language specific

                                            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                            Object Identifier(a) Object Name Description

                                            Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                            Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                            Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                            Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                            Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                            Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                            Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                            Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                            Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                            Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                            Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                            Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                            Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                            Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                            Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                            Table 10 Diagnostics Binary Input (continued)

                                            Object Identifier(a) Object Name Description

                                            ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                            Object Data Points and Diagnostic Data Points

                                            Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                            Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                            Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                            Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                            Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                            Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                            Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                            Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                            Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                            Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                            Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                            Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                            Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                            Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                            Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                            Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                            Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                            Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                            Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                            Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                            Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                            Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                            Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                            Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                            Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                            Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                            Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                            Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                            Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                            Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                            Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                            Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                            Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                            Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                            Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                            Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                            Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                            Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                            Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                            Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                            Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                            Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                            Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                            Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                            Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                            Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                            Object Identifier(a) Object Name Description

                                            36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                            Object Data Points and Diagnostic Data Points

                                            Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                            Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                            Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                            Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                            Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                            Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                            Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                            Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                            Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                            Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                            Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                            Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                            Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                            Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                            Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                            Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                            Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                            Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                            Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                            Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                            Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                            Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                            Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                            Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                            Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                            Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                            Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                            Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                            Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                            Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                            Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                            Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                            Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                            Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                            Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                            Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                            Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                            Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                            Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                            Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                            Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                            Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                            Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                            Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                            Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                            Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                            Object Identifier(a) Object Name Description

                                            ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                            Object Data Points and Diagnostic Data Points

                                            Binary Output 16 Humidification Command Command the operating state of the humidification system

                                            NC 3 HVAC-Advisory HVAC-Advisory

                                            NC 1 HVAC-Critical HVAC-Critical

                                            NC 4 HVAC-Information HVAC-Information

                                            NC 2 HVAC-Service Required HVAC-Service Required

                                            Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                            Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                            Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                            Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                            Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                            Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                            Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                            Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                            Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                            Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                            Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                            Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                            Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                            Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                            Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                            Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                            Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                            Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                            Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                            Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                            Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                            Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                            Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                            Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                            Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                            Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                            Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                            Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                            Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                            Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                            Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                            Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                            Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                            Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                            Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                            Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                            Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                            Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                            Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                            Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                            Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                            Object Identifier(a) Object Name Description

                                            38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                            Object Data Points and Diagnostic Data Points

                                            Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                            Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                            Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                            Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                            Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                            Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                            Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                            Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                            Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                            Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                            Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                            Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                            Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                            Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                            Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                            Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                            Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                            Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                            Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                            Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                            Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                            Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                            Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                            Binary Input 3 Unit Status Indicates the current state of the unit

                                            Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                            Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                            Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                            Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                            Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                            Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                            Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                            (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                            Object Identifier(a) Object Name Description

                                            Table 12 Diagnostic Objects Sorted by Object Name

                                            Object Identifier(a) Object Name ValueRange Description

                                            BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                            BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                            ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                            Object Data Points and Diagnostic Data Points

                                            BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                            BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                            BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                            BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                            BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                            BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                            BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                            BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                            BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                            BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                            BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                            BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                            BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                            BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                            BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                            BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                            BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                            BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                            BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                            BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                            BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                            BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                            BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                            BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                            BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                            BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                            BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                            BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                            BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                            Object Identifier(a) Object Name ValueRange Description

                                            40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                            Object Data Points and Diagnostic Data Points

                                            BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                            BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                            BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                            BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                            BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                            BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                            BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                            BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                            BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                            BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                            BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                            BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                            BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                            BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                            BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                            BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                            BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                            BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                            BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                            BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                            BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                            BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                            BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                            BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                            BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                            BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                            BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                            BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                            BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                            Object Identifier(a) Object Name ValueRange Description

                                            ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                            Object Data Points and Diagnostic Data Points

                                            BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                            BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                            BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                            BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                            BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                            BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                            BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                            BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                            BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                            BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                            BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                            BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                            BI 121 (use Object Identifier for RT)

                                            Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                            BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                            BI 58 (use Object Identifier for RT or CSC)

                                            Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                            BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                            BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                            BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                            BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                            BI 31 (use Object Identifier for RT CSC)

                                            Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                            BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                            BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                            BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                            BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                            BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                            BI 121 (use Object Identifier for FAU)

                                            Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                            B1 31 (use Object Identifier for FAU)

                                            Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                            BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                            BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                            Object Identifier(a) Object Name ValueRange Description

                                            42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                            Object Data Points and Diagnostic Data Points

                                            BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                            BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                            BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                            BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                            BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                            BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                            BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                            BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                            BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                            BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                            BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                            BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                            BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                            BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                            BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                            BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                            BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                            BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                            BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                            BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                            BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                            BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                            BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                            1 = active Diagnostic Vel Press Sensor (Rear)

                                            BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                            Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                            BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                            BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                            BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                            BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                            BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                            Object Identifier(a) Object Name ValueRange Description

                                            ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                            Object Data Points and Diagnostic Data Points

                                            BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                            BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                            BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                            BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                            BI 58 (use Object Identifier for FAU)

                                            Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                            (a) BI=Binary Input

                                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                            Object Identifier(a) Object Name ValueRange Description

                                            44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                            Additional Resources

                                            Additional Resources

                                            Use the following documents and links as additional resources

                                            bull Product support online

                                            bull wwwbacnetorg

                                            bull wwwbacnetassociationorg

                                            bull wwwashraeorg

                                            bull Tracer TU Help online

                                            bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                            bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                            Note For further assistance contact your local Trane sales office

                                            ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                            Glossary

                                            A

                                            ASHRAE

                                            See American Society of Heating Refrigeration and Air-conditioning Engineers

                                            American Society of Heating Refrigeration and Air-

                                            conditioning Engineers

                                            An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                            BBACnettrade

                                            See Building Automation Control network

                                            BACnet interoperability building blocks

                                            A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                            BACnet object

                                            An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                            baud rate

                                            The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                            BIBB

                                            See BACnet interoperability building blocks

                                            Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                            advocates BACnet protocol for use in system-level control devices

                                            device

                                            A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                            Device ID

                                            The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                            Iinteroperability

                                            The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                            Pprotocol

                                            A set of rules (language) that governs the exchange of data over a digital communications system

                                            S

                                            stand-alone operation

                                            Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                            wwwtranecom

                                            For more information contact your local Trane office or e-mail us at comforttranecom

                                            Literature Order Number ACC-SVP01B-EN

                                            Date September 2009

                                            Supersedes ACC-SVP01A-EN

                                            Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                            • Table of Contents
                                            • Overview
                                            • Ordering Numbers
                                            • BACnet Protocol
                                            • BCI-I Configuration
                                              • Overview
                                              • Starting a Session of Tracer TU and Direct Connection
                                              • Reset to Factory Default
                                              • IP Units Configuration
                                              • BACnet Object Configuration
                                              • Change Baud Rate
                                              • Change Device ID
                                              • Stand-alone or BAS Operation
                                                • IntelliPak Control Configuration
                                                • BAS Unit Control
                                                • Periodic Update of BAS Values
                                                • BAS Communication Failure
                                                  • InputOutput Commands and Calculations
                                                    • System Control Command
                                                    • Filter Timer Reset Command
                                                    • Diagnostics Reset Command
                                                    • Setpoint Calculations
                                                    • Timestamp Configuration
                                                        • BCI IntelliPak Rotary Switches and LEDs
                                                          • Rotary Switches
                                                          • LEDs Description Behavior and Troubleshooting
                                                          • 24 Vac Measurement
                                                          • Ground Measurements
                                                            • BACnet Data Points and Configuration Property Definitions
                                                              • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                • Standardized Device Profile (Annex L)
                                                                • Interoperability Building Blocks (Annex K)
                                                                • Segmentation Capability
                                                                • Object Types
                                                                  • BACnet Protocol
                                                                    • Data Link Layer Options
                                                                    • Device Address Binding
                                                                    • Networking Options
                                                                    • Character Sets
                                                                        • Object Data Points and Diagnostic Data Points
                                                                        • Additional Resources
                                                                        • Glossary

                                              ACC-SVP01B-EN bull BCI-I Integration Guide 23

                                              BACnet Data Points and Configuration Property Definitions

                                              Character Sets

                                              Indicates support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes (any character set)

                                              Character Set Descriptions Supported

                                              ANSI X34

                                              IBMMicrosoft DBCS

                                              ISO 10646 (UCS-4)

                                              ISO 10646 (UCS2)

                                              ISO 8859-1

                                              JIS C 6226

                                              24 ACC-SVP01B-EN bull BCI-I Integration Guide

                                              Object Data Points and Diagnostic Data Points

                                              Object Data Points and Diagnostic Data Points

                                              For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

                                              Table 3 Analog Output

                                              Object Identifier Object Name Description Units Valid Range

                                              Refresh Rate

                                              (Sec)

                                              Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

                                              Percent (98) 0 to 100 NA

                                              Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

                                              Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

                                              Degrees-Fahrenheit (64) 500 to 900 NA

                                              Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

                                              BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

                                              Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

                                              Degrees-Fahrenheit (64) 400 to 900 NA

                                              Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

                                              Degrees-Fahrenheit (64) 400 to 1800 NA

                                              Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

                                              070 to 510 (Ipak II) NA

                                              Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

                                              003 to 030-002 to 030 (enhanced StatiTrac)

                                              NA

                                              Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

                                              -028 to 050-067 to 067 (enhanced StatiTrac)

                                              900

                                              Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                              Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                              Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

                                              00 to 79 (Ipak II) 900

                                              Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                              Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

                                              Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

                                              Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

                                              Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

                                              Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                              Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                              Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

                                              Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

                                              Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

                                              ACC-SVP01B-EN bull BCI-I Integration Guide 25

                                              Object Data Points and Diagnostic Data Points

                                              Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                                              Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                                              Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                                              Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                                              Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                                              Cooling temperature setpoint used for control in unoccupied mode

                                              Degrees-Fahrenheit (64) 520 to 880 NA

                                              Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                                              Heating temperature setpoint used for control in unoccupied mode

                                              Degrees-Fahrenheit (64) 500 to 900 NA

                                              Table 4 Analog Input

                                              Object Identifier Object Name Description Units (Listed Are Defaults)

                                              Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                                              Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                                              Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                                              Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                                              Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                                              Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                                              Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                                              Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                                              Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                                              Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                                              Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                                              Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                                              Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                                              Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                                              Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                                              Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                                              Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                                              Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                                              Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                                              Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                                              Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                                              Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                                              Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                                              Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                              Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                              Table 3 Analog Output (continued)

                                              Object Identifier Object Name Description Units Valid Range

                                              Refresh Rate

                                              (Sec)

                                              26 ACC-SVP01B-EN bull BCI-I Integration Guide

                                              Object Data Points and Diagnostic Data Points

                                              Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                                              Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                              Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                              Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                                              Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                                              Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                                              Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                                              Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                                              Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                              Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                              Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                              Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                              Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                                              Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                                              Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                                              Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                                              Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                                              Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                                              Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                                              Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                                              Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                                              Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                              Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                              Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                                              The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                                              Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                                              The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                                              Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                                              Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                                              Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                                              Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                                              Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                                              Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                                              Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                                              Table 4 Analog Input (continued)

                                              Object Identifier Object Name Description Units (Listed Are Defaults)

                                              ACC-SVP01B-EN bull BCI-I Integration Guide 27

                                              Object Data Points and Diagnostic Data Points

                                              Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                                              Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                                              Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                                              Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                                              The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                                              Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                                              Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                                              Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                                              Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                                              Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                                              Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                              Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                              Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                                              Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                                              Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                                              Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                                              Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                                              Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                                              Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                                              Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                                              Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                                              Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                                              Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                                              Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                                              Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                                              Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                                              Table 5 Analog Value

                                              Object Identifier Object Name Description Units Valid Range

                                              Analog Value 1 Filter Runtime Hours Setpoint

                                              The setpoint value used by the filter run hours calculation

                                              Hours (71) 0 to 10000

                                              Table 4 Analog Input (continued)

                                              Object Identifier Object Name Description Units (Listed Are Defaults)

                                              28 ACC-SVP01B-EN bull BCI-I Integration Guide

                                              Object Data Points and Diagnostic Data Points

                                              Table 6 Multistate Output

                                              BCI-I Object Identifier Object Name Description Object States

                                              Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                                              Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                              1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                                              Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                                              Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                              1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                              Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                              1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                              Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                              1 = Flow2 = No Flow3 = Auto

                                              Table 7 Multistate Input

                                              BCI-I Object Identifier Object Name Description Object States

                                              Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                              1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                                              Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                              1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                                              Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                              1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                                              Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                              1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                                              ACC-SVP01B-EN bull BCI-I Integration Guide 29

                                              Object Data Points and Diagnostic Data Points

                                              Multi-State Input 15 Economizer Decision Method

                                              Unit method to determine when the economizer system is enabled

                                              1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                                              Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                                              Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                                              Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                              1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                              Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                              1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                              Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                              1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                                              Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                              1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                              Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                              1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                              Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                              1 = Idle2 = On3 = Cancel

                                              Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                              1 = Off2 = On3 = Not Present

                                              Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                              1 = Off2 = On3 = Not Present

                                              Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                              1 = Off2 = On3 = Not Present

                                              Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                              1 = Off|2 = On3 = Not Present

                                              Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                              1 = Off2 = On3 = Not Present

                                              Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                              1 = Off2 = On3 = Not Present

                                              Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                              1 = Off2 = On3 = Not Present

                                              Table 7 Multistate Input (continued)

                                              BCI-I Object Identifier Object Name Description Object States

                                              30 ACC-SVP01B-EN bull BCI-I Integration Guide

                                              Object Data Points and Diagnostic Data Points

                                              Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                              1 = Off2 = On3 = Not Present

                                              Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                              1 = Off2 = On3 = Not Present

                                              Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                                              Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                                              Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                                              Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                                              Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                              1 = Off2 = On3 = Not Present

                                              Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                              1= Off2= On3= Not Present

                                              Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                                              Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                                              Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                                              Multi-State Input 43 Outdoor Air Damper Status

                                              Indicates the operating state of the outdoor damper

                                              1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                                              Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                              1 = Disabled2 = Enabled3 = Not Present

                                              Table 8 Binary Output

                                              Object Identifier Object Name DescriptionRelinquish Default Object States

                                              Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                                              Active = BAS Control

                                              Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                                              Active = Heating Locked Out

                                              Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                                              Active = Cooling Locked Out

                                              Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                                              Active = Enabled

                                              Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                                              Active = On

                                              Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                                              Inactive Inactive = DisabledActive = Enabled

                                              Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                                              Active = Reset

                                              Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                                              Active = Reset

                                              Table 7 Multistate Input (continued)

                                              BCI-I Object Identifier Object Name Description Object States

                                              ACC-SVP01B-EN bull BCI-I Integration Guide 31

                                              Object Data Points and Diagnostic Data Points

                                              Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                                              Active = Auto

                                              Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                                              Active = Auto

                                              Table 9 Binary Input

                                              Object Identifier Object Name Description Object States

                                              Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                              Inactive = Standalone controlActive = BAS control

                                              Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                              Inactive = NormalActive = Locked Out

                                              Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                                              Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                              Inactive = AutoActive = Open

                                              Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                              Inactive = InactiveActive = Active

                                              Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                                              Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                                              Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                              Inactive = DisabledActive = Enabled

                                              Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                              Inactive = DisabledActive = Enabled

                                              Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                              Inactive = InactiveActive = Active

                                              Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                              Inactive = No FlowActive = Flow

                                              Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                              Inactive = InactiveActive = Active

                                              Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                              Inactive = InactiveActive = Active

                                              Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                              Inactive = InactiveActive = Active

                                              Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                                              The status of evaporator frost protection function for circuit 1

                                              Inactive = InactiveActive = Active

                                              Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                                              The status of evaporator frost protection function for circuit 2

                                              Inactive = InactiveActive = Active

                                              Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                                              The status of evaporator frost protection function for circuit 3

                                              Inactive = InactiveActive = Active

                                              Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                                              The status of evaporator frost protection function for circuit 4

                                              Inactive = InactiveActive = Active

                                              Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                              Inactive = De-energizedActive = Energized

                                              Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                              Inactive = InactiveActive = Active

                                              Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                              Inactive = ClosedActive = Open

                                              Table 10 Diagnostics Binary Input

                                              Object Identifier(a) Object Name Description

                                              Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                                              Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                                              Binary Input 31 (use Object Identifier for RT or CSC)

                                              Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                                              Binary Input 31 (use Object Identifier for FAU)

                                              Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                                              Table 8 Binary Output

                                              Object Identifier Object Name DescriptionRelinquish Default Object States

                                              32 ACC-SVP01B-EN bull BCI-I Integration Guide

                                              Object Data Points and Diagnostic Data Points

                                              Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                                              Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                                              Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                                              Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                                              Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                                              Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                                              Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                                              Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                                              Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                                              Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                              Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                              Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                                              Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                                              Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                                              Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                                              Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                                              Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                                              Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                                              Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                                              Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                                              Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                                              Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                                              Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                                              Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                                              Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                                              Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                                              Binary Input 58 (use Object Identifier for RT or CSC)

                                              Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                                              Binary Input 58 (use Object Identifier for FAU)

                                              Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                                              Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                                              Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                                              Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                                              Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                                              Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                                              Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                                              Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                                              Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                                              Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                                              Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                                              Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                                              Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                                              Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                                              Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                                              Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                                              Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                                              Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                                              Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                                              Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                                              Table 10 Diagnostics Binary Input (continued)

                                              Object Identifier(a) Object Name Description

                                              ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                              Object Data Points and Diagnostic Data Points

                                              Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                              Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                              Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                              Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                              Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                              Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                              Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                              Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                              Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                              Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                              Binary Input 86 (use Object Identifier for RT I-pak II)

                                              Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                              Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                              Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                              Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                              Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                              Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                              Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                              Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                              Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                              Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                              Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                              Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                              Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                              Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                              Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                              Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                              Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                              Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                              Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                              Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                              Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                              Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                              Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                              Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                              Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                              Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                              Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                              Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                              Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                              Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                              Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                              Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                              Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                              Binary Input 121 (use Object Identifier for RT)

                                              Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                              Binary Input 121 (use Object Identifier for FAU)

                                              Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                              Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                              Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                              Table 10 Diagnostics Binary Input (continued)

                                              Object Identifier(a) Object Name Description

                                              34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                              Object Data Points and Diagnostic Data Points

                                              Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                              Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                              Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                              Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                              Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                              Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                              Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                              Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                              Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                              Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                              Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                              Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                              Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                              Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                              Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                              Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                              Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                              Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                              Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                              Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                              Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                              Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                              Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                              Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                              Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                              Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                              (a) Object States Inactive = normal and Active = foreign language specific

                                              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                              Object Identifier(a) Object Name Description

                                              Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                              Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                              Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                              Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                              Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                              Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                              Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                              Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                              Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                              Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                              Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                              Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                              Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                              Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                              Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                              Table 10 Diagnostics Binary Input (continued)

                                              Object Identifier(a) Object Name Description

                                              ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                              Object Data Points and Diagnostic Data Points

                                              Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                              Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                              Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                              Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                              Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                              Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                              Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                              Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                              Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                              Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                              Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                              Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                              Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                              Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                              Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                              Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                              Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                              Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                              Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                              Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                              Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                              Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                              Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                              Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                              Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                              Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                              Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                              Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                              Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                              Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                              Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                              Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                              Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                              Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                              Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                              Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                              Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                              Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                              Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                              Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                              Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                              Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                              Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                              Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                              Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                              Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                              Object Identifier(a) Object Name Description

                                              36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                              Object Data Points and Diagnostic Data Points

                                              Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                              Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                              Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                              Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                              Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                              Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                              Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                              Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                              Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                              Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                              Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                              Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                              Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                              Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                              Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                              Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                              Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                              Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                              Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                              Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                              Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                              Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                              Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                              Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                              Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                              Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                              Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                              Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                              Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                              Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                              Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                              Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                              Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                              Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                              Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                              Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                              Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                              Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                              Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                              Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                              Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                              Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                              Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                              Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                              Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                              Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                              Object Identifier(a) Object Name Description

                                              ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                              Object Data Points and Diagnostic Data Points

                                              Binary Output 16 Humidification Command Command the operating state of the humidification system

                                              NC 3 HVAC-Advisory HVAC-Advisory

                                              NC 1 HVAC-Critical HVAC-Critical

                                              NC 4 HVAC-Information HVAC-Information

                                              NC 2 HVAC-Service Required HVAC-Service Required

                                              Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                              Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                              Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                              Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                              Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                              Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                              Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                              Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                              Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                              Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                              Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                              Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                              Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                              Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                              Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                              Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                              Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                              Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                              Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                              Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                              Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                              Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                              Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                              Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                              Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                              Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                              Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                              Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                              Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                              Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                              Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                              Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                              Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                              Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                              Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                              Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                              Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                              Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                              Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                              Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                              Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                              Object Identifier(a) Object Name Description

                                              38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                              Object Data Points and Diagnostic Data Points

                                              Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                              Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                              Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                              Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                              Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                              Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                              Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                              Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                              Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                              Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                              Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                              Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                              Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                              Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                              Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                              Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                              Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                              Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                              Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                              Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                              Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                              Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                              Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                              Binary Input 3 Unit Status Indicates the current state of the unit

                                              Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                              Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                              Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                              Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                              Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                              Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                              Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                              (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                              Object Identifier(a) Object Name Description

                                              Table 12 Diagnostic Objects Sorted by Object Name

                                              Object Identifier(a) Object Name ValueRange Description

                                              BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                              BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                              ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                              Object Data Points and Diagnostic Data Points

                                              BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                              BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                              BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                              BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                              BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                              BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                              BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                              BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                              BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                              BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                              BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                              BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                              BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                              BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                              BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                              BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                              BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                              BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                              BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                              BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                              BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                              BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                              BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                              BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                              BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                              BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                              BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                              BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                              BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                              Object Identifier(a) Object Name ValueRange Description

                                              40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                              Object Data Points and Diagnostic Data Points

                                              BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                              BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                              BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                              BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                              BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                              BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                              BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                              BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                              BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                              BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                              BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                              BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                              BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                              BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                              BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                              BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                              BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                              BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                              BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                              BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                              BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                              BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                              BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                              BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                              BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                              BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                              BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                              BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                              BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                              Object Identifier(a) Object Name ValueRange Description

                                              ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                              Object Data Points and Diagnostic Data Points

                                              BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                              BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                              BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                              BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                              BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                              BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                              BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                              BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                              BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                              BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                              BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                              BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                              BI 121 (use Object Identifier for RT)

                                              Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                              BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                              BI 58 (use Object Identifier for RT or CSC)

                                              Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                              BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                              BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                              BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                              BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                              BI 31 (use Object Identifier for RT CSC)

                                              Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                              BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                              BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                              BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                              BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                              BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                              BI 121 (use Object Identifier for FAU)

                                              Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                              B1 31 (use Object Identifier for FAU)

                                              Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                              BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                              BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                              Object Identifier(a) Object Name ValueRange Description

                                              42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                              Object Data Points and Diagnostic Data Points

                                              BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                              BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                              BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                              BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                              BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                              BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                              BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                              BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                              BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                              BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                              BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                              BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                              BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                              BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                              BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                              BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                              BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                              BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                              BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                              BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                              BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                              BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                              BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                              1 = active Diagnostic Vel Press Sensor (Rear)

                                              BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                              Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                              BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                              BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                              BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                              BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                              BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                              Object Identifier(a) Object Name ValueRange Description

                                              ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                              Object Data Points and Diagnostic Data Points

                                              BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                              BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                              BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                              BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                              BI 58 (use Object Identifier for FAU)

                                              Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                              (a) BI=Binary Input

                                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                              Object Identifier(a) Object Name ValueRange Description

                                              44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                              Additional Resources

                                              Additional Resources

                                              Use the following documents and links as additional resources

                                              bull Product support online

                                              bull wwwbacnetorg

                                              bull wwwbacnetassociationorg

                                              bull wwwashraeorg

                                              bull Tracer TU Help online

                                              bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                              bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                              Note For further assistance contact your local Trane sales office

                                              ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                              Glossary

                                              A

                                              ASHRAE

                                              See American Society of Heating Refrigeration and Air-conditioning Engineers

                                              American Society of Heating Refrigeration and Air-

                                              conditioning Engineers

                                              An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                              BBACnettrade

                                              See Building Automation Control network

                                              BACnet interoperability building blocks

                                              A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                              BACnet object

                                              An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                              baud rate

                                              The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                              BIBB

                                              See BACnet interoperability building blocks

                                              Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                              advocates BACnet protocol for use in system-level control devices

                                              device

                                              A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                              Device ID

                                              The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                              Iinteroperability

                                              The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                              Pprotocol

                                              A set of rules (language) that governs the exchange of data over a digital communications system

                                              S

                                              stand-alone operation

                                              Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                              wwwtranecom

                                              For more information contact your local Trane office or e-mail us at comforttranecom

                                              Literature Order Number ACC-SVP01B-EN

                                              Date September 2009

                                              Supersedes ACC-SVP01A-EN

                                              Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                              • Table of Contents
                                              • Overview
                                              • Ordering Numbers
                                              • BACnet Protocol
                                              • BCI-I Configuration
                                                • Overview
                                                • Starting a Session of Tracer TU and Direct Connection
                                                • Reset to Factory Default
                                                • IP Units Configuration
                                                • BACnet Object Configuration
                                                • Change Baud Rate
                                                • Change Device ID
                                                • Stand-alone or BAS Operation
                                                  • IntelliPak Control Configuration
                                                  • BAS Unit Control
                                                  • Periodic Update of BAS Values
                                                  • BAS Communication Failure
                                                    • InputOutput Commands and Calculations
                                                      • System Control Command
                                                      • Filter Timer Reset Command
                                                      • Diagnostics Reset Command
                                                      • Setpoint Calculations
                                                      • Timestamp Configuration
                                                          • BCI IntelliPak Rotary Switches and LEDs
                                                            • Rotary Switches
                                                            • LEDs Description Behavior and Troubleshooting
                                                            • 24 Vac Measurement
                                                            • Ground Measurements
                                                              • BACnet Data Points and Configuration Property Definitions
                                                                • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                  • Standardized Device Profile (Annex L)
                                                                  • Interoperability Building Blocks (Annex K)
                                                                  • Segmentation Capability
                                                                  • Object Types
                                                                    • BACnet Protocol
                                                                      • Data Link Layer Options
                                                                      • Device Address Binding
                                                                      • Networking Options
                                                                      • Character Sets
                                                                          • Object Data Points and Diagnostic Data Points
                                                                          • Additional Resources
                                                                          • Glossary

                                                24 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                Object Data Points and Diagnostic Data Points

                                                Object Data Points and Diagnostic Data Points

                                                For quick reference the following tables are listed two different ways Tables 2 through 9 are listed by inputoutput type and sorted by object identifier These tables provide the user with the units type for each object type Table 11 p 34 and Table 12 p 38 are sorted by object name and provide a complete list of object names types valuesranges and descriptions Not all points are available to the user The available data points are defined during self-configuration and are dependent on the type of equipment

                                                Table 3 Analog Output

                                                Object Identifier Object Name Description Units Valid Range

                                                Refresh Rate

                                                (Sec)

                                                Analog Output 1 Economizer Minimum Position Setpoint BASBAS supplied economizer position minimum setpoint value

                                                Percent (98) 0 to 100 NA

                                                Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes Degrees-Fahrenheit (64) 500 to 900 NA

                                                Analog Output 4 Morning Warmup Setpoint BASBAS supplied temperature setpoint used in morning warmup mode

                                                Degrees-Fahrenheit (64) 500 to 900 NA

                                                Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS

                                                BAS supplied daytime warmup terminate temperature setpoint Degrees-Fahrenheit (64) 500 to 870 NA

                                                Analog Output 6 Discharge Air Cooling Setpoint BASBAS supplied discharge air temperature cooling setpoint value

                                                Degrees-Fahrenheit (64) 400 to 900 NA

                                                Analog Output 7 Discharge Air Heating Setpoint BASBAS supplied discharge air temperature heating setpoint value

                                                Degrees-Fahrenheit (64) 400 to 1800 NA

                                                Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value Inches-of-water (58) 070 to 430 (Ipak I)

                                                070 to 510 (Ipak II) NA

                                                Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value Inches-of-water (58)

                                                003 to 030-002 to 030 (enhanced StatiTrac)

                                                NA

                                                Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value Inches-of-water (58)

                                                -028 to 050-067 to 067 (enhanced StatiTrac)

                                                900

                                                Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                                Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                                Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value Inches-of-water (58) 00 to 50 (Ipak I)

                                                00 to 79 (Ipak II) 900

                                                Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value Degrees-Fahrenheit (64) -395 to 2000 900

                                                Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value Percent (98) 100 to 900 900

                                                Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint Cubic-feet-per-minute (84) 0 to 60000 NA

                                                Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value Cubic-feet-per-minute (84) 0 to 65000 900

                                                Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value Parts-per-million 50 to 2200 900

                                                Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                                Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value Percent (98) 0 to 100 NA

                                                Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value Percent (98) 40 to 65 NA

                                                Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value Degrees-Fahrenheit (64) 450 to 750 NA

                                                Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value Degrees-Fahrenheit (64) 650 to 800 NA

                                                ACC-SVP01B-EN bull BCI-I Integration Guide 25

                                                Object Data Points and Diagnostic Data Points

                                                Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                                                Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                                                Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                                                Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                                                Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                                                Cooling temperature setpoint used for control in unoccupied mode

                                                Degrees-Fahrenheit (64) 520 to 880 NA

                                                Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                                                Heating temperature setpoint used for control in unoccupied mode

                                                Degrees-Fahrenheit (64) 500 to 900 NA

                                                Table 4 Analog Input

                                                Object Identifier Object Name Description Units (Listed Are Defaults)

                                                Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                                                Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                                                Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                                                Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                                                Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                                                Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                                                Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                                                Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                                                Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                                                Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                                                Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                                                Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                                                Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                                                Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                                                Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                                                Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                                                Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                                                Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                                                Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                                                Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                                                Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                                                Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                                                Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                                                Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                                Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                                Table 3 Analog Output (continued)

                                                Object Identifier Object Name Description Units Valid Range

                                                Refresh Rate

                                                (Sec)

                                                26 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                Object Data Points and Diagnostic Data Points

                                                Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                                                Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                                Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                                Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                                                Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                                                Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                                                Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                                                Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                                                Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                                Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                                Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                                Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                                Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                                                Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                                                Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                                                Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                                                Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                                                Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                                                Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                                                Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                                                Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                                                Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                                Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                                Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                                                The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                                                Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                                                The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                                                Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                                                Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                                                Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                                                Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                                                Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                                                Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                                                Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                                                Table 4 Analog Input (continued)

                                                Object Identifier Object Name Description Units (Listed Are Defaults)

                                                ACC-SVP01B-EN bull BCI-I Integration Guide 27

                                                Object Data Points and Diagnostic Data Points

                                                Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                                                Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                                                Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                                                Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                                                The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                                                Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                                                Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                                                Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                                                Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                                                Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                                                Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                                Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                                Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                                                Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                                                Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                                                Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                                                Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                                                Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                                                Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                                                Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                                                Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                                                Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                                                Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                                                Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                                                Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                                                Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                                                Table 5 Analog Value

                                                Object Identifier Object Name Description Units Valid Range

                                                Analog Value 1 Filter Runtime Hours Setpoint

                                                The setpoint value used by the filter run hours calculation

                                                Hours (71) 0 to 10000

                                                Table 4 Analog Input (continued)

                                                Object Identifier Object Name Description Units (Listed Are Defaults)

                                                28 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                Object Data Points and Diagnostic Data Points

                                                Table 6 Multistate Output

                                                BCI-I Object Identifier Object Name Description Object States

                                                Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                                                Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                                                Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                                                Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                                Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                                1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                                Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                                1 = Flow2 = No Flow3 = Auto

                                                Table 7 Multistate Input

                                                BCI-I Object Identifier Object Name Description Object States

                                                Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                                                Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                                                Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                                1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                                                Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                                                ACC-SVP01B-EN bull BCI-I Integration Guide 29

                                                Object Data Points and Diagnostic Data Points

                                                Multi-State Input 15 Economizer Decision Method

                                                Unit method to determine when the economizer system is enabled

                                                1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                                                Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                                                Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                                                Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                                1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                                Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                                Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                                                Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                                Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                                Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                1 = Idle2 = On3 = Cancel

                                                Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                1 = Off2 = On3 = Not Present

                                                Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                1 = Off2 = On3 = Not Present

                                                Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                1 = Off2 = On3 = Not Present

                                                Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                1 = Off|2 = On3 = Not Present

                                                Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                1 = Off2 = On3 = Not Present

                                                Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                1 = Off2 = On3 = Not Present

                                                Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                1 = Off2 = On3 = Not Present

                                                Table 7 Multistate Input (continued)

                                                BCI-I Object Identifier Object Name Description Object States

                                                30 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                Object Data Points and Diagnostic Data Points

                                                Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                1 = Off2 = On3 = Not Present

                                                Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                1 = Off2 = On3 = Not Present

                                                Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                                                Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                                                Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                                                Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                                                Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                1 = Off2 = On3 = Not Present

                                                Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                1= Off2= On3= Not Present

                                                Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                                                Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                                                Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                                                Multi-State Input 43 Outdoor Air Damper Status

                                                Indicates the operating state of the outdoor damper

                                                1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                                                Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                1 = Disabled2 = Enabled3 = Not Present

                                                Table 8 Binary Output

                                                Object Identifier Object Name DescriptionRelinquish Default Object States

                                                Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                                                Active = BAS Control

                                                Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                                                Active = Heating Locked Out

                                                Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                                                Active = Cooling Locked Out

                                                Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                                                Active = Enabled

                                                Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                                                Active = On

                                                Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                                                Inactive Inactive = DisabledActive = Enabled

                                                Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                                                Active = Reset

                                                Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                                                Active = Reset

                                                Table 7 Multistate Input (continued)

                                                BCI-I Object Identifier Object Name Description Object States

                                                ACC-SVP01B-EN bull BCI-I Integration Guide 31

                                                Object Data Points and Diagnostic Data Points

                                                Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                                                Active = Auto

                                                Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                                                Active = Auto

                                                Table 9 Binary Input

                                                Object Identifier Object Name Description Object States

                                                Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                Inactive = Standalone controlActive = BAS control

                                                Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                Inactive = NormalActive = Locked Out

                                                Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                                                Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                Inactive = AutoActive = Open

                                                Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                Inactive = InactiveActive = Active

                                                Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                                                Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                                                Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                Inactive = DisabledActive = Enabled

                                                Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                Inactive = DisabledActive = Enabled

                                                Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                Inactive = InactiveActive = Active

                                                Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                Inactive = No FlowActive = Flow

                                                Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                Inactive = InactiveActive = Active

                                                Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                Inactive = InactiveActive = Active

                                                Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                Inactive = InactiveActive = Active

                                                Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                                                The status of evaporator frost protection function for circuit 1

                                                Inactive = InactiveActive = Active

                                                Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                                                The status of evaporator frost protection function for circuit 2

                                                Inactive = InactiveActive = Active

                                                Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                                                The status of evaporator frost protection function for circuit 3

                                                Inactive = InactiveActive = Active

                                                Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                                                The status of evaporator frost protection function for circuit 4

                                                Inactive = InactiveActive = Active

                                                Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                Inactive = De-energizedActive = Energized

                                                Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                Inactive = InactiveActive = Active

                                                Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                Inactive = ClosedActive = Open

                                                Table 10 Diagnostics Binary Input

                                                Object Identifier(a) Object Name Description

                                                Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                                                Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                                                Binary Input 31 (use Object Identifier for RT or CSC)

                                                Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                                                Binary Input 31 (use Object Identifier for FAU)

                                                Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                                                Table 8 Binary Output

                                                Object Identifier Object Name DescriptionRelinquish Default Object States

                                                32 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                Object Data Points and Diagnostic Data Points

                                                Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                                                Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                                                Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                                                Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                                                Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                                                Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                                                Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                                                Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                                                Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                                                Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                                                Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                                                Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                                                Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                                                Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                                                Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                                                Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                                                Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                                                Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                                                Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                                                Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                                                Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                                                Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                                                Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                                                Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                                                Binary Input 58 (use Object Identifier for RT or CSC)

                                                Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                                                Binary Input 58 (use Object Identifier for FAU)

                                                Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                                                Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                                                Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                                                Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                                                Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                                                Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                                                Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                                                Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                                                Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                                                Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                                                Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                                                Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                                                Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                                                Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                                                Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                                                Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                                                Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                                                Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                                                Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                                                Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                                                Table 10 Diagnostics Binary Input (continued)

                                                Object Identifier(a) Object Name Description

                                                ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                                Object Data Points and Diagnostic Data Points

                                                Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                                Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                                Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                                Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                                Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                                Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                                Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                                Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                                Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                                Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                                Binary Input 86 (use Object Identifier for RT I-pak II)

                                                Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                                Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                                Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                                Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                                Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                                Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                                Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                                Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                                Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                                Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                                Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                                Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                                Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                                Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                                Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                                Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                                Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                                Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                                Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                                Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                                Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                                Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                                Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                                Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                                Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                                Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                                Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                                Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                                Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                                Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                                Binary Input 121 (use Object Identifier for RT)

                                                Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                                Binary Input 121 (use Object Identifier for FAU)

                                                Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                                Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                                Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                                Table 10 Diagnostics Binary Input (continued)

                                                Object Identifier(a) Object Name Description

                                                34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                Object Data Points and Diagnostic Data Points

                                                Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                                Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                                Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                                Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                                Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                                Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                                Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                                Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                                Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                                Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                                Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                                Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                                Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                                Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                                Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                                Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                                Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                                Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                                Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                                Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                                Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                                Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                                Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                                Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                                Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                                Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                                (a) Object States Inactive = normal and Active = foreign language specific

                                                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                                Object Identifier(a) Object Name Description

                                                Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                                Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                                Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                                Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                                Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                                Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                                Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                                Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                                Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                                Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                                Table 10 Diagnostics Binary Input (continued)

                                                Object Identifier(a) Object Name Description

                                                ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                                Object Data Points and Diagnostic Data Points

                                                Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                                Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                                Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                                Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                                Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                                Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                                Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                                Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                                Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                                Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                                Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                                Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                                Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                                Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                                Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                                Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                                Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                                Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                                Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                                Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                                Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                                Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                                Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                                Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                                Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                                Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                                Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                                Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                                Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                                Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                                Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                                Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                                Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                                Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                                Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                                Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                Object Identifier(a) Object Name Description

                                                36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                Object Data Points and Diagnostic Data Points

                                                Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                                Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                                Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                                Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                                Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                                Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                                Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                                Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                                Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                                Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                                Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                                Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                                Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                                Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                                Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                                Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                                Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                                Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                                Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                                Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                                Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                                Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                                Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                                Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                                Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                                Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                                Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                                Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                                Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                                Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                                Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                                Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                Object Identifier(a) Object Name Description

                                                ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                                Object Data Points and Diagnostic Data Points

                                                Binary Output 16 Humidification Command Command the operating state of the humidification system

                                                NC 3 HVAC-Advisory HVAC-Advisory

                                                NC 1 HVAC-Critical HVAC-Critical

                                                NC 4 HVAC-Information HVAC-Information

                                                NC 2 HVAC-Service Required HVAC-Service Required

                                                Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                                Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                                Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                                Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                                Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                                Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                                Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                                Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                                Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                                Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                                Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                                Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                                Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                                Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                                Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                                Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                                Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                                Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                                Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                                Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                                Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                                Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                                Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                                Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                                Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                                Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                                Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                                Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                                Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                                Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                                Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                                Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                                Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                                Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                                Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                                Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                                Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                                Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                                Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                Object Identifier(a) Object Name Description

                                                38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                Object Data Points and Diagnostic Data Points

                                                Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                                Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                                Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                                Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                                Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                                Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                                Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                                Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                                Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                                Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                                Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                                Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                                Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                                Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                                Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                                Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                                Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                                Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                                Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                                Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                                Binary Input 3 Unit Status Indicates the current state of the unit

                                                Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                                Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                                Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                                (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                Object Identifier(a) Object Name Description

                                                Table 12 Diagnostic Objects Sorted by Object Name

                                                Object Identifier(a) Object Name ValueRange Description

                                                BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                                BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                                ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                                Object Data Points and Diagnostic Data Points

                                                BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                                BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                                BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                                BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                                BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                                BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                                BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                                BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                                BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                                BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                                BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                                BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                                BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                                BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                                BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                                BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                                BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                                BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                                BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                                BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                                BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                                BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                                BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                                BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                                BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                                BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                Object Identifier(a) Object Name ValueRange Description

                                                40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                Object Data Points and Diagnostic Data Points

                                                BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                                BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                                BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                                BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                                BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                                BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                                BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                                BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                                BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                                BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                                BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                                BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                                BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                                BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                                BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                                BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                                BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                                BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                                BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                                BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                                BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                                BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                                BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                                BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                                BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                                BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                                BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                Object Identifier(a) Object Name ValueRange Description

                                                ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                Object Data Points and Diagnostic Data Points

                                                BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                BI 121 (use Object Identifier for RT)

                                                Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                BI 58 (use Object Identifier for RT or CSC)

                                                Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                BI 31 (use Object Identifier for RT CSC)

                                                Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                BI 121 (use Object Identifier for FAU)

                                                Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                B1 31 (use Object Identifier for FAU)

                                                Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                Object Identifier(a) Object Name ValueRange Description

                                                42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                Object Data Points and Diagnostic Data Points

                                                BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                1 = active Diagnostic Vel Press Sensor (Rear)

                                                BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                Object Identifier(a) Object Name ValueRange Description

                                                ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                Object Data Points and Diagnostic Data Points

                                                BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                BI 58 (use Object Identifier for FAU)

                                                Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                (a) BI=Binary Input

                                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                Object Identifier(a) Object Name ValueRange Description

                                                44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                Additional Resources

                                                Additional Resources

                                                Use the following documents and links as additional resources

                                                bull Product support online

                                                bull wwwbacnetorg

                                                bull wwwbacnetassociationorg

                                                bull wwwashraeorg

                                                bull Tracer TU Help online

                                                bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                Note For further assistance contact your local Trane sales office

                                                ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                Glossary

                                                A

                                                ASHRAE

                                                See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                American Society of Heating Refrigeration and Air-

                                                conditioning Engineers

                                                An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                BBACnettrade

                                                See Building Automation Control network

                                                BACnet interoperability building blocks

                                                A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                BACnet object

                                                An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                baud rate

                                                The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                BIBB

                                                See BACnet interoperability building blocks

                                                Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                advocates BACnet protocol for use in system-level control devices

                                                device

                                                A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                Device ID

                                                The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                Iinteroperability

                                                The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                Pprotocol

                                                A set of rules (language) that governs the exchange of data over a digital communications system

                                                S

                                                stand-alone operation

                                                Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                wwwtranecom

                                                For more information contact your local Trane office or e-mail us at comforttranecom

                                                Literature Order Number ACC-SVP01B-EN

                                                Date September 2009

                                                Supersedes ACC-SVP01A-EN

                                                Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                • Table of Contents
                                                • Overview
                                                • Ordering Numbers
                                                • BACnet Protocol
                                                • BCI-I Configuration
                                                  • Overview
                                                  • Starting a Session of Tracer TU and Direct Connection
                                                  • Reset to Factory Default
                                                  • IP Units Configuration
                                                  • BACnet Object Configuration
                                                  • Change Baud Rate
                                                  • Change Device ID
                                                  • Stand-alone or BAS Operation
                                                    • IntelliPak Control Configuration
                                                    • BAS Unit Control
                                                    • Periodic Update of BAS Values
                                                    • BAS Communication Failure
                                                      • InputOutput Commands and Calculations
                                                        • System Control Command
                                                        • Filter Timer Reset Command
                                                        • Diagnostics Reset Command
                                                        • Setpoint Calculations
                                                        • Timestamp Configuration
                                                            • BCI IntelliPak Rotary Switches and LEDs
                                                              • Rotary Switches
                                                              • LEDs Description Behavior and Troubleshooting
                                                              • 24 Vac Measurement
                                                              • Ground Measurements
                                                                • BACnet Data Points and Configuration Property Definitions
                                                                  • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                    • Standardized Device Profile (Annex L)
                                                                    • Interoperability Building Blocks (Annex K)
                                                                    • Segmentation Capability
                                                                    • Object Types
                                                                      • BACnet Protocol
                                                                        • Data Link Layer Options
                                                                        • Device Address Binding
                                                                        • Networking Options
                                                                        • Character Sets
                                                                            • Object Data Points and Diagnostic Data Points
                                                                            • Additional Resources
                                                                            • Glossary

                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 25

                                                  Object Data Points and Diagnostic Data Points

                                                  Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value Percent (98) 10 to 90 900

                                                  Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value Percent (98) 20 to 50 NA

                                                  Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode Degrees-Fahrenheit (64) 10 to 50 NA

                                                  Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode Degrees-Fahrenheit (64) 10 to 100 NA

                                                  Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS

                                                  Cooling temperature setpoint used for control in unoccupied mode

                                                  Degrees-Fahrenheit (64) 520 to 880 NA

                                                  Analog Output 32 Unoccupied Heating Temperature Setpoint BAS

                                                  Heating temperature setpoint used for control in unoccupied mode

                                                  Degrees-Fahrenheit (64) 500 to 900 NA

                                                  Table 4 Analog Input

                                                  Object Identifier Object Name Description Units (Listed Are Defaults)

                                                  Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized Percent (98)

                                                  Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized Percent (98)

                                                  Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized Percent (98)

                                                  Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized Percent (98)

                                                  Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter Hours (71)

                                                  Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed Percent (98)

                                                  Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed Percent (98)

                                                  Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position Percent (98)

                                                  Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed Percent (98)

                                                  Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position Percent (98)

                                                  Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position Percent (98)

                                                  Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint Degrees-Fahrenheit (64)

                                                  Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized Percent (98)

                                                  Analog Input 15 Space Temperature Active The space temperature currently used for unit control Degrees-Fahrenheit (64)

                                                  Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control Percent-relative-humidity (29)

                                                  Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control BTUs-per-pound (117)

                                                  Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control Degrees-Fahrenheit (64)

                                                  Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64)

                                                  Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control Percent-relative-humidity (29)

                                                  Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor Percent-relative-humidity (29)

                                                  Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit Degrees-Fahrenheit (64

                                                  Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit BTUs-per-pound (117)

                                                  Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control Degrees-Fahrenheit (64)

                                                  Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                                  Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor Degrees-Fahrenheit (64

                                                  Table 3 Analog Output (continued)

                                                  Object Identifier Object Name Description Units Valid Range

                                                  Refresh Rate

                                                  (Sec)

                                                  26 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                  Object Data Points and Diagnostic Data Points

                                                  Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                                                  Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                                  Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                                  Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                                                  Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                                                  Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                                                  Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                                                  Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                                                  Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                                  Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                                  Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                                  Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                                  Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                                                  Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                                                  Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                                                  Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                                                  Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                                                  Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                                                  Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                                                  Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                                                  Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                                                  Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                                  Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                                  Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                                                  The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                                                  Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                                                  The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                                                  Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                                                  Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                                                  Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                                                  Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                                                  Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                                                  Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                                                  Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                                                  Table 4 Analog Input (continued)

                                                  Object Identifier Object Name Description Units (Listed Are Defaults)

                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 27

                                                  Object Data Points and Diagnostic Data Points

                                                  Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                                                  Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                                                  Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                                                  Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                                                  The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                                                  Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                                                  Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                                                  Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                                                  Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                                                  Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                                                  Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                                  Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                                  Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                                                  Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                                                  Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                                                  Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                                                  Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                                                  Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                                                  Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                                                  Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                                                  Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                                                  Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                                                  Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                                                  Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                                                  Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                                                  Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                                                  Table 5 Analog Value

                                                  Object Identifier Object Name Description Units Valid Range

                                                  Analog Value 1 Filter Runtime Hours Setpoint

                                                  The setpoint value used by the filter run hours calculation

                                                  Hours (71) 0 to 10000

                                                  Table 4 Analog Input (continued)

                                                  Object Identifier Object Name Description Units (Listed Are Defaults)

                                                  28 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                  Object Data Points and Diagnostic Data Points

                                                  Table 6 Multistate Output

                                                  BCI-I Object Identifier Object Name Description Object States

                                                  Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                                                  Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                  1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                                                  Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                                                  Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                  1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                                  Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                                  1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                                  Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                                  1 = Flow2 = No Flow3 = Auto

                                                  Table 7 Multistate Input

                                                  BCI-I Object Identifier Object Name Description Object States

                                                  Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                  1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                                                  Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                  1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                                                  Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                                  1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                                                  Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                  1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 29

                                                  Object Data Points and Diagnostic Data Points

                                                  Multi-State Input 15 Economizer Decision Method

                                                  Unit method to determine when the economizer system is enabled

                                                  1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                                                  Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                                                  Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                                                  Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                                  1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                                  Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                  1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                                  Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                  1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                                                  Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                  1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                                  Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                  1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                                  Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                  1 = Idle2 = On3 = Cancel

                                                  Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                  1 = Off2 = On3 = Not Present

                                                  Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                  1 = Off2 = On3 = Not Present

                                                  Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                  1 = Off2 = On3 = Not Present

                                                  Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                  1 = Off|2 = On3 = Not Present

                                                  Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                  1 = Off2 = On3 = Not Present

                                                  Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                  1 = Off2 = On3 = Not Present

                                                  Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                  1 = Off2 = On3 = Not Present

                                                  Table 7 Multistate Input (continued)

                                                  BCI-I Object Identifier Object Name Description Object States

                                                  30 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                  Object Data Points and Diagnostic Data Points

                                                  Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                  1 = Off2 = On3 = Not Present

                                                  Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                  1 = Off2 = On3 = Not Present

                                                  Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                                                  Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                                                  Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                                                  Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                                                  Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                  1 = Off2 = On3 = Not Present

                                                  Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                  1= Off2= On3= Not Present

                                                  Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                                                  Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                                                  Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                                                  Multi-State Input 43 Outdoor Air Damper Status

                                                  Indicates the operating state of the outdoor damper

                                                  1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                                                  Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                  1 = Disabled2 = Enabled3 = Not Present

                                                  Table 8 Binary Output

                                                  Object Identifier Object Name DescriptionRelinquish Default Object States

                                                  Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                                                  Active = BAS Control

                                                  Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                                                  Active = Heating Locked Out

                                                  Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                                                  Active = Cooling Locked Out

                                                  Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                                                  Active = Enabled

                                                  Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                                                  Active = On

                                                  Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                                                  Inactive Inactive = DisabledActive = Enabled

                                                  Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                                                  Active = Reset

                                                  Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                                                  Active = Reset

                                                  Table 7 Multistate Input (continued)

                                                  BCI-I Object Identifier Object Name Description Object States

                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 31

                                                  Object Data Points and Diagnostic Data Points

                                                  Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                                                  Active = Auto

                                                  Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                                                  Active = Auto

                                                  Table 9 Binary Input

                                                  Object Identifier Object Name Description Object States

                                                  Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                  Inactive = Standalone controlActive = BAS control

                                                  Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                  Inactive = NormalActive = Locked Out

                                                  Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                                                  Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                  Inactive = AutoActive = Open

                                                  Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                  Inactive = InactiveActive = Active

                                                  Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                                                  Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                                                  Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                  Inactive = DisabledActive = Enabled

                                                  Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                  Inactive = DisabledActive = Enabled

                                                  Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                  Inactive = InactiveActive = Active

                                                  Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                  Inactive = No FlowActive = Flow

                                                  Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                  Inactive = InactiveActive = Active

                                                  Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                  Inactive = InactiveActive = Active

                                                  Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                  Inactive = InactiveActive = Active

                                                  Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                                                  The status of evaporator frost protection function for circuit 1

                                                  Inactive = InactiveActive = Active

                                                  Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                                                  The status of evaporator frost protection function for circuit 2

                                                  Inactive = InactiveActive = Active

                                                  Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                                                  The status of evaporator frost protection function for circuit 3

                                                  Inactive = InactiveActive = Active

                                                  Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                                                  The status of evaporator frost protection function for circuit 4

                                                  Inactive = InactiveActive = Active

                                                  Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                  Inactive = De-energizedActive = Energized

                                                  Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                  Inactive = InactiveActive = Active

                                                  Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                  Inactive = ClosedActive = Open

                                                  Table 10 Diagnostics Binary Input

                                                  Object Identifier(a) Object Name Description

                                                  Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                                                  Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                                                  Binary Input 31 (use Object Identifier for RT or CSC)

                                                  Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                                                  Binary Input 31 (use Object Identifier for FAU)

                                                  Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                                                  Table 8 Binary Output

                                                  Object Identifier Object Name DescriptionRelinquish Default Object States

                                                  32 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                  Object Data Points and Diagnostic Data Points

                                                  Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                                                  Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                                                  Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                                                  Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                                                  Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                                                  Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                                                  Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                                                  Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                                                  Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                                                  Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                  Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                  Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                                                  Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                                                  Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                                                  Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                                                  Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                                                  Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                                                  Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                                                  Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                                                  Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                                                  Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                                                  Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                                                  Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                                                  Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                                                  Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                                                  Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                                                  Binary Input 58 (use Object Identifier for RT or CSC)

                                                  Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                                                  Binary Input 58 (use Object Identifier for FAU)

                                                  Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                                                  Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                                                  Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                                                  Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                                                  Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                                                  Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                                                  Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                                                  Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                                                  Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                                                  Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                                                  Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                                                  Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                                                  Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                                                  Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                                                  Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                                                  Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                                                  Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                                                  Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                                                  Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                                                  Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                                                  Table 10 Diagnostics Binary Input (continued)

                                                  Object Identifier(a) Object Name Description

                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                                  Object Data Points and Diagnostic Data Points

                                                  Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                                  Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                                  Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                                  Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                                  Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                                  Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                                  Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                                  Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                                  Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                                  Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                                  Binary Input 86 (use Object Identifier for RT I-pak II)

                                                  Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                                  Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                                  Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                                  Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                                  Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                                  Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                                  Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                                  Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                                  Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                  Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                                  Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                                  Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                                  Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                                  Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                                  Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                                  Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                                  Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                                  Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                                  Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                                  Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                                  Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                                  Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                  Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                  Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                                  Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                                  Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                                  Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                                  Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                                  Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                                  Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                                  Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                                  Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                                  Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                                  Binary Input 121 (use Object Identifier for RT)

                                                  Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                                  Binary Input 121 (use Object Identifier for FAU)

                                                  Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                                  Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                                  Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                                  Table 10 Diagnostics Binary Input (continued)

                                                  Object Identifier(a) Object Name Description

                                                  34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                  Object Data Points and Diagnostic Data Points

                                                  Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                                  Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                                  Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                                  Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                                  Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                                  Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                                  Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                                  Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                                  Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                                  Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                                  Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                                  Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                                  Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                                  Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                                  Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                                  Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                                  Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                                  Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                                  Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                                  Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                                  Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                                  Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                                  Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                                  Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                                  Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                                  Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                                  (a) Object States Inactive = normal and Active = foreign language specific

                                                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                                  Object Identifier(a) Object Name Description

                                                  Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                  Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                                  Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                                  Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                                  Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                  Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                                  Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                                  Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                  Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                                  Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                                  Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                  Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                                  Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                                  Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                  Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                                  Table 10 Diagnostics Binary Input (continued)

                                                  Object Identifier(a) Object Name Description

                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                                  Object Data Points and Diagnostic Data Points

                                                  Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                                  Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                                  Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                                  Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                                  Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                                  Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                  Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                  Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                  Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                  Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                                  Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                                  Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                                  Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                  Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                                  Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                                  Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                                  Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                                  Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                                  Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                                  Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                                  Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                  Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                                  Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                  Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                                  Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                                  Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                                  Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                                  Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                                  Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                                  Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                                  Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                                  Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                                  Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                                  Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                                  Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                                  Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                                  Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                                  Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                                  Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                  Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                  Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                  Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                                  Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                                  Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                                  Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                                  Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                  Object Identifier(a) Object Name Description

                                                  36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                  Object Data Points and Diagnostic Data Points

                                                  Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                  Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                  Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                                  Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                                  Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                                  Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                  Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                                  Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                  Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                                  Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                                  Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                  Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                  Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                                  Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                                  Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                                  Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                                  Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                                  Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                                  Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                                  Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                                  Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                                  Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                                  Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                                  Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                                  Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                  Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                                  Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                  Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                                  Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                                  Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                                  Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                                  Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                                  Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                                  Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                                  Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                                  Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                                  Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                  Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                  Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                  Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                  Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                  Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                                  Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                                  Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                                  Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                  Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                  Object Identifier(a) Object Name Description

                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                                  Object Data Points and Diagnostic Data Points

                                                  Binary Output 16 Humidification Command Command the operating state of the humidification system

                                                  NC 3 HVAC-Advisory HVAC-Advisory

                                                  NC 1 HVAC-Critical HVAC-Critical

                                                  NC 4 HVAC-Information HVAC-Information

                                                  NC 2 HVAC-Service Required HVAC-Service Required

                                                  Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                                  Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                                  Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                                  Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                  Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                  Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                                  Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                                  Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                                  Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                                  Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                                  Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                                  Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                                  Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                                  Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                                  Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                                  Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                                  Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                                  Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                                  Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                                  Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                                  Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                                  Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                                  Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                                  Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                                  Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                                  Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                                  Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                                  Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                                  Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                                  Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                                  Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                                  Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                                  Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                                  Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                                  Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                                  Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                                  Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                                  Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                                  Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                                  Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                                  Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                  Object Identifier(a) Object Name Description

                                                  38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                  Object Data Points and Diagnostic Data Points

                                                  Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                                  Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                                  Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                                  Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                                  Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                                  Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                                  Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                                  Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                                  Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                                  Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                                  Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                                  Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                                  Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                                  Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                                  Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                                  Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                                  Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                                  Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                                  Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                                  Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                  Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                  Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                  Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                                  Binary Input 3 Unit Status Indicates the current state of the unit

                                                  Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                  Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                                  Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                                  Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                  Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                  Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                  Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                                  (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                  Object Identifier(a) Object Name Description

                                                  Table 12 Diagnostic Objects Sorted by Object Name

                                                  Object Identifier(a) Object Name ValueRange Description

                                                  BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                                  BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                                  Object Data Points and Diagnostic Data Points

                                                  BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                                  BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                                  BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                                  BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                                  BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                                  BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                                  BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                                  BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                                  BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                                  BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                                  BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                                  BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                                  BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                                  BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                                  BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                                  BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                                  BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                                  BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                                  BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                                  BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                                  BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                                  BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                                  BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                                  BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                                  BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                                  BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                  BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                  BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                  BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                  Object Identifier(a) Object Name ValueRange Description

                                                  40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                  Object Data Points and Diagnostic Data Points

                                                  BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                                  BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                                  BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                                  BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                                  BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                                  BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                                  BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                                  BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                                  BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                                  BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                                  BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                                  BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                                  BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                                  BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                                  BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                                  BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                                  BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                                  BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                                  BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                                  BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                                  BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                                  BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                                  BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                                  BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                  BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                  BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                                  BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                                  BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                                  BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                  Object Identifier(a) Object Name ValueRange Description

                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                  Object Data Points and Diagnostic Data Points

                                                  BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                  BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                  BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                  BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                  BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                  BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                  BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                  BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                  BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                  BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                  BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                  BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                  BI 121 (use Object Identifier for RT)

                                                  Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                  BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                  BI 58 (use Object Identifier for RT or CSC)

                                                  Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                  BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                  BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                  BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                  BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                  BI 31 (use Object Identifier for RT CSC)

                                                  Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                  BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                  BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                  BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                  BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                  BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                  BI 121 (use Object Identifier for FAU)

                                                  Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                  B1 31 (use Object Identifier for FAU)

                                                  Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                  BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                  BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                  Object Identifier(a) Object Name ValueRange Description

                                                  42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                  Object Data Points and Diagnostic Data Points

                                                  BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                  BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                  BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                  BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                  BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                  BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                  BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                  BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                  BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                  BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                  BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                  BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                  BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                  BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                  BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                  BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                  BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                  BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                  BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                  BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                  BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                  BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                  BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                  1 = active Diagnostic Vel Press Sensor (Rear)

                                                  BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                  Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                  BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                  BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                  BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                  BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                  BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                  Object Identifier(a) Object Name ValueRange Description

                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                  Object Data Points and Diagnostic Data Points

                                                  BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                  BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                  BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                  BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                  BI 58 (use Object Identifier for FAU)

                                                  Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                  (a) BI=Binary Input

                                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                  Object Identifier(a) Object Name ValueRange Description

                                                  44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                  Additional Resources

                                                  Additional Resources

                                                  Use the following documents and links as additional resources

                                                  bull Product support online

                                                  bull wwwbacnetorg

                                                  bull wwwbacnetassociationorg

                                                  bull wwwashraeorg

                                                  bull Tracer TU Help online

                                                  bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                  bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                  Note For further assistance contact your local Trane sales office

                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                  Glossary

                                                  A

                                                  ASHRAE

                                                  See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                  American Society of Heating Refrigeration and Air-

                                                  conditioning Engineers

                                                  An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                  BBACnettrade

                                                  See Building Automation Control network

                                                  BACnet interoperability building blocks

                                                  A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                  BACnet object

                                                  An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                  baud rate

                                                  The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                  BIBB

                                                  See BACnet interoperability building blocks

                                                  Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                  advocates BACnet protocol for use in system-level control devices

                                                  device

                                                  A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                  Device ID

                                                  The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                  Iinteroperability

                                                  The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                  Pprotocol

                                                  A set of rules (language) that governs the exchange of data over a digital communications system

                                                  S

                                                  stand-alone operation

                                                  Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                  wwwtranecom

                                                  For more information contact your local Trane office or e-mail us at comforttranecom

                                                  Literature Order Number ACC-SVP01B-EN

                                                  Date September 2009

                                                  Supersedes ACC-SVP01A-EN

                                                  Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                  • Table of Contents
                                                  • Overview
                                                  • Ordering Numbers
                                                  • BACnet Protocol
                                                  • BCI-I Configuration
                                                    • Overview
                                                    • Starting a Session of Tracer TU and Direct Connection
                                                    • Reset to Factory Default
                                                    • IP Units Configuration
                                                    • BACnet Object Configuration
                                                    • Change Baud Rate
                                                    • Change Device ID
                                                    • Stand-alone or BAS Operation
                                                      • IntelliPak Control Configuration
                                                      • BAS Unit Control
                                                      • Periodic Update of BAS Values
                                                      • BAS Communication Failure
                                                        • InputOutput Commands and Calculations
                                                          • System Control Command
                                                          • Filter Timer Reset Command
                                                          • Diagnostics Reset Command
                                                          • Setpoint Calculations
                                                          • Timestamp Configuration
                                                              • BCI IntelliPak Rotary Switches and LEDs
                                                                • Rotary Switches
                                                                • LEDs Description Behavior and Troubleshooting
                                                                • 24 Vac Measurement
                                                                • Ground Measurements
                                                                  • BACnet Data Points and Configuration Property Definitions
                                                                    • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                      • Standardized Device Profile (Annex L)
                                                                      • Interoperability Building Blocks (Annex K)
                                                                      • Segmentation Capability
                                                                      • Object Types
                                                                        • BACnet Protocol
                                                                          • Data Link Layer Options
                                                                          • Device Address Binding
                                                                          • Networking Options
                                                                          • Character Sets
                                                                              • Object Data Points and Diagnostic Data Points
                                                                              • Additional Resources
                                                                              • Glossary

                                                    26 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                    Object Data Points and Diagnostic Data Points

                                                    Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control Inches-of-water (58)

                                                    Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                                    Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor Inches-of-water (58)

                                                    Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control Inches-of-water (58)

                                                    Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control Parts-per-million (96)

                                                    Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit Degrees-Fahrenheit (64)

                                                    Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit Cubic-feet-per-minute (84)

                                                    Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser Degrees-Fahrenheit (64)

                                                    Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                                    Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                                    Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64)

                                                    Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2 Degrees-Fahrenheit (64)

                                                    Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3 Degrees-Fahrenheit (64)

                                                    Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4 Degrees-Fahrenheit (64)

                                                    Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1 Degrees-Fahrenheit (64)

                                                    Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2 Degrees-Fahrenheit (64)

                                                    Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3 Degrees-Fahrenheit (64)

                                                    Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4 Degrees-Fahrenheit (64)

                                                    Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control Degrees-Fahrenheit (64)

                                                    Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor Degrees-Fahrenheit (64)

                                                    Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control Inches-of-water (58)

                                                    Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                                    Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control Degrees-Fahrenheit (64)

                                                    Analog Input 54 Morning Warmup Air Temperature Setpoint Active

                                                    The air temperature setpoint used during morning warmup mode Degrees-Fahrenheit (64)

                                                    Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active

                                                    The air temperature setpoint used to start daytime warmup mode Degrees-Fahrenheit (64)

                                                    Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize Percent (98)

                                                    Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit Cubic-feet-per-minute (84)

                                                    Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Percent (98)

                                                    Analog Input 60 Discharge Air Dewpoint Temperature Setpoint

                                                    Humidity setpoint value used during dehumidification control Degrees-Fahrenheit (64)

                                                    Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint Degrees-Fahrenheit (64)

                                                    Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control Percent (98)

                                                    Table 4 Analog Input (continued)

                                                    Object Identifier Object Name Description Units (Listed Are Defaults)

                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 27

                                                    Object Data Points and Diagnostic Data Points

                                                    Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                                                    Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                                                    Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                                                    Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                                                    The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                                                    Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                                                    Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                                                    Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                                                    Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                                                    Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                                                    Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                                    Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                                    Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                                                    Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                                                    Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                                                    Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                                                    Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                                                    Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                                                    Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                                                    Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                                                    Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                                                    Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                                                    Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                                                    Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                                                    Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                                                    Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                                                    Table 5 Analog Value

                                                    Object Identifier Object Name Description Units Valid Range

                                                    Analog Value 1 Filter Runtime Hours Setpoint

                                                    The setpoint value used by the filter run hours calculation

                                                    Hours (71) 0 to 10000

                                                    Table 4 Analog Input (continued)

                                                    Object Identifier Object Name Description Units (Listed Are Defaults)

                                                    28 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                    Object Data Points and Diagnostic Data Points

                                                    Table 6 Multistate Output

                                                    BCI-I Object Identifier Object Name Description Object States

                                                    Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                                                    Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                    1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                                                    Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                                                    Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                    1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                                    Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                                    1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                                    Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                                    1 = Flow2 = No Flow3 = Auto

                                                    Table 7 Multistate Input

                                                    BCI-I Object Identifier Object Name Description Object States

                                                    Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                    1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                                                    Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                    1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                                                    Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                                    1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                                                    Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                    1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 29

                                                    Object Data Points and Diagnostic Data Points

                                                    Multi-State Input 15 Economizer Decision Method

                                                    Unit method to determine when the economizer system is enabled

                                                    1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                                                    Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                                                    Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                                                    Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                                    1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                                    Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                    1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                                    Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                    1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                                                    Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                    1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                                    Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                    1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                                    Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                    1 = Idle2 = On3 = Cancel

                                                    Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                    1 = Off2 = On3 = Not Present

                                                    Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                    1 = Off2 = On3 = Not Present

                                                    Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                    1 = Off2 = On3 = Not Present

                                                    Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                    1 = Off|2 = On3 = Not Present

                                                    Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                    1 = Off2 = On3 = Not Present

                                                    Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                    1 = Off2 = On3 = Not Present

                                                    Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                    1 = Off2 = On3 = Not Present

                                                    Table 7 Multistate Input (continued)

                                                    BCI-I Object Identifier Object Name Description Object States

                                                    30 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                    Object Data Points and Diagnostic Data Points

                                                    Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                    1 = Off2 = On3 = Not Present

                                                    Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                    1 = Off2 = On3 = Not Present

                                                    Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                                                    Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                                                    Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                                                    Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                                                    Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                    1 = Off2 = On3 = Not Present

                                                    Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                    1= Off2= On3= Not Present

                                                    Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                                                    Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                                                    Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                                                    Multi-State Input 43 Outdoor Air Damper Status

                                                    Indicates the operating state of the outdoor damper

                                                    1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                                                    Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                    1 = Disabled2 = Enabled3 = Not Present

                                                    Table 8 Binary Output

                                                    Object Identifier Object Name DescriptionRelinquish Default Object States

                                                    Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                                                    Active = BAS Control

                                                    Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                                                    Active = Heating Locked Out

                                                    Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                                                    Active = Cooling Locked Out

                                                    Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                                                    Active = Enabled

                                                    Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                                                    Active = On

                                                    Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                                                    Inactive Inactive = DisabledActive = Enabled

                                                    Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                                                    Active = Reset

                                                    Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                                                    Active = Reset

                                                    Table 7 Multistate Input (continued)

                                                    BCI-I Object Identifier Object Name Description Object States

                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 31

                                                    Object Data Points and Diagnostic Data Points

                                                    Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                                                    Active = Auto

                                                    Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                                                    Active = Auto

                                                    Table 9 Binary Input

                                                    Object Identifier Object Name Description Object States

                                                    Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                    Inactive = Standalone controlActive = BAS control

                                                    Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                    Inactive = NormalActive = Locked Out

                                                    Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                                                    Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                    Inactive = AutoActive = Open

                                                    Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                    Inactive = InactiveActive = Active

                                                    Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                                                    Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                                                    Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                    Inactive = DisabledActive = Enabled

                                                    Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                    Inactive = DisabledActive = Enabled

                                                    Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                    Inactive = InactiveActive = Active

                                                    Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                    Inactive = No FlowActive = Flow

                                                    Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                    Inactive = InactiveActive = Active

                                                    Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                    Inactive = InactiveActive = Active

                                                    Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                    Inactive = InactiveActive = Active

                                                    Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                                                    The status of evaporator frost protection function for circuit 1

                                                    Inactive = InactiveActive = Active

                                                    Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                                                    The status of evaporator frost protection function for circuit 2

                                                    Inactive = InactiveActive = Active

                                                    Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                                                    The status of evaporator frost protection function for circuit 3

                                                    Inactive = InactiveActive = Active

                                                    Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                                                    The status of evaporator frost protection function for circuit 4

                                                    Inactive = InactiveActive = Active

                                                    Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                    Inactive = De-energizedActive = Energized

                                                    Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                    Inactive = InactiveActive = Active

                                                    Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                    Inactive = ClosedActive = Open

                                                    Table 10 Diagnostics Binary Input

                                                    Object Identifier(a) Object Name Description

                                                    Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                                                    Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                                                    Binary Input 31 (use Object Identifier for RT or CSC)

                                                    Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                                                    Binary Input 31 (use Object Identifier for FAU)

                                                    Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                                                    Table 8 Binary Output

                                                    Object Identifier Object Name DescriptionRelinquish Default Object States

                                                    32 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                    Object Data Points and Diagnostic Data Points

                                                    Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                                                    Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                                                    Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                                                    Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                                                    Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                                                    Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                                                    Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                                                    Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                                                    Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                                                    Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                    Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                    Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                                                    Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                                                    Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                                                    Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                                                    Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                                                    Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                                                    Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                                                    Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                                                    Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                                                    Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                                                    Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                                                    Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                                                    Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                                                    Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                                                    Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                                                    Binary Input 58 (use Object Identifier for RT or CSC)

                                                    Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                                                    Binary Input 58 (use Object Identifier for FAU)

                                                    Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                                                    Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                                                    Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                                                    Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                                                    Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                                                    Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                                                    Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                                                    Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                                                    Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                                                    Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                                                    Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                                                    Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                                                    Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                                                    Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                                                    Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                                                    Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                                                    Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                                                    Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                                                    Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                                                    Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                                                    Table 10 Diagnostics Binary Input (continued)

                                                    Object Identifier(a) Object Name Description

                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                                    Object Data Points and Diagnostic Data Points

                                                    Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                                    Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                                    Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                                    Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                                    Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                                    Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                                    Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                                    Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                                    Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                                    Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                                    Binary Input 86 (use Object Identifier for RT I-pak II)

                                                    Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                                    Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                                    Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                                    Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                                    Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                                    Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                                    Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                                    Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                                    Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                    Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                                    Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                                    Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                                    Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                                    Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                                    Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                                    Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                                    Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                                    Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                                    Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                                    Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                                    Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                                    Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                    Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                    Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                                    Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                                    Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                                    Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                                    Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                                    Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                                    Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                                    Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                                    Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                                    Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                                    Binary Input 121 (use Object Identifier for RT)

                                                    Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                                    Binary Input 121 (use Object Identifier for FAU)

                                                    Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                                    Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                                    Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                                    Table 10 Diagnostics Binary Input (continued)

                                                    Object Identifier(a) Object Name Description

                                                    34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                    Object Data Points and Diagnostic Data Points

                                                    Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                                    Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                                    Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                                    Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                                    Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                                    Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                                    Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                                    Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                                    Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                                    Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                                    Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                                    Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                                    Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                                    Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                                    Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                                    Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                                    Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                                    Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                                    Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                                    Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                                    Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                                    Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                                    Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                                    Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                                    Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                                    Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                                    (a) Object States Inactive = normal and Active = foreign language specific

                                                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                                    Object Identifier(a) Object Name Description

                                                    Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                    Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                                    Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                                    Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                                    Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                    Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                                    Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                                    Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                    Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                                    Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                                    Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                    Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                                    Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                                    Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                    Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                                    Table 10 Diagnostics Binary Input (continued)

                                                    Object Identifier(a) Object Name Description

                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                                    Object Data Points and Diagnostic Data Points

                                                    Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                                    Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                                    Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                                    Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                                    Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                                    Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                    Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                    Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                    Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                    Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                                    Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                                    Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                                    Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                    Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                                    Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                                    Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                                    Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                                    Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                                    Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                                    Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                                    Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                    Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                                    Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                    Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                                    Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                                    Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                                    Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                                    Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                                    Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                                    Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                                    Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                                    Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                                    Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                                    Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                                    Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                                    Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                                    Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                                    Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                                    Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                    Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                    Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                    Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                                    Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                                    Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                                    Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                                    Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                    Object Identifier(a) Object Name Description

                                                    36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                    Object Data Points and Diagnostic Data Points

                                                    Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                    Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                    Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                                    Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                                    Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                                    Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                    Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                                    Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                    Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                                    Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                                    Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                    Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                    Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                                    Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                                    Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                                    Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                                    Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                                    Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                                    Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                                    Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                                    Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                                    Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                                    Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                                    Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                                    Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                    Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                                    Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                    Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                                    Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                                    Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                                    Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                                    Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                                    Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                                    Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                                    Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                                    Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                                    Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                    Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                    Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                    Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                    Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                    Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                                    Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                                    Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                                    Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                    Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                    Object Identifier(a) Object Name Description

                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                                    Object Data Points and Diagnostic Data Points

                                                    Binary Output 16 Humidification Command Command the operating state of the humidification system

                                                    NC 3 HVAC-Advisory HVAC-Advisory

                                                    NC 1 HVAC-Critical HVAC-Critical

                                                    NC 4 HVAC-Information HVAC-Information

                                                    NC 2 HVAC-Service Required HVAC-Service Required

                                                    Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                                    Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                                    Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                                    Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                    Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                    Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                                    Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                                    Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                                    Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                                    Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                                    Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                                    Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                                    Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                                    Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                                    Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                                    Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                                    Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                                    Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                                    Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                                    Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                                    Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                                    Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                                    Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                                    Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                                    Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                                    Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                                    Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                                    Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                                    Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                                    Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                                    Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                                    Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                                    Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                                    Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                                    Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                                    Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                                    Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                                    Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                                    Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                                    Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                                    Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                    Object Identifier(a) Object Name Description

                                                    38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                    Object Data Points and Diagnostic Data Points

                                                    Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                                    Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                                    Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                                    Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                                    Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                                    Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                                    Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                                    Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                                    Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                                    Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                                    Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                                    Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                                    Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                                    Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                                    Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                                    Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                                    Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                                    Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                                    Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                                    Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                    Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                    Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                    Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                                    Binary Input 3 Unit Status Indicates the current state of the unit

                                                    Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                    Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                                    Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                                    Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                    Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                    Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                    Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                                    (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                    Object Identifier(a) Object Name Description

                                                    Table 12 Diagnostic Objects Sorted by Object Name

                                                    Object Identifier(a) Object Name ValueRange Description

                                                    BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                                    BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                                    Object Data Points and Diagnostic Data Points

                                                    BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                                    BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                                    BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                                    BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                                    BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                                    BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                                    BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                                    BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                                    BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                                    BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                                    BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                                    BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                                    BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                                    BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                                    BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                                    BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                                    BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                                    BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                                    BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                                    BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                                    BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                                    BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                                    BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                                    BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                                    BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                                    BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                    BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                    BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                    BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                    Object Identifier(a) Object Name ValueRange Description

                                                    40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                    Object Data Points and Diagnostic Data Points

                                                    BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                                    BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                                    BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                                    BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                                    BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                                    BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                                    BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                                    BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                                    BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                                    BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                                    BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                                    BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                                    BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                                    BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                                    BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                                    BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                                    BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                                    BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                                    BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                                    BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                                    BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                                    BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                                    BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                                    BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                    BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                    BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                                    BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                                    BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                                    BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                    Object Identifier(a) Object Name ValueRange Description

                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                    Object Data Points and Diagnostic Data Points

                                                    BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                    BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                    BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                    BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                    BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                    BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                    BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                    BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                    BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                    BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                    BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                    BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                    BI 121 (use Object Identifier for RT)

                                                    Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                    BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                    BI 58 (use Object Identifier for RT or CSC)

                                                    Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                    BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                    BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                    BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                    BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                    BI 31 (use Object Identifier for RT CSC)

                                                    Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                    BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                    BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                    BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                    BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                    BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                    BI 121 (use Object Identifier for FAU)

                                                    Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                    B1 31 (use Object Identifier for FAU)

                                                    Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                    BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                    BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                    Object Identifier(a) Object Name ValueRange Description

                                                    42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                    Object Data Points and Diagnostic Data Points

                                                    BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                    BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                    BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                    BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                    BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                    BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                    BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                    BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                    BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                    BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                    BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                    BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                    BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                    BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                    BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                    BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                    BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                    BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                    BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                    BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                    BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                    BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                    BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                    1 = active Diagnostic Vel Press Sensor (Rear)

                                                    BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                    Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                    BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                    BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                    BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                    BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                    BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                    Object Identifier(a) Object Name ValueRange Description

                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                    Object Data Points and Diagnostic Data Points

                                                    BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                    BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                    BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                    BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                    BI 58 (use Object Identifier for FAU)

                                                    Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                    (a) BI=Binary Input

                                                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                    Object Identifier(a) Object Name ValueRange Description

                                                    44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                    Additional Resources

                                                    Additional Resources

                                                    Use the following documents and links as additional resources

                                                    bull Product support online

                                                    bull wwwbacnetorg

                                                    bull wwwbacnetassociationorg

                                                    bull wwwashraeorg

                                                    bull Tracer TU Help online

                                                    bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                    bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                    Note For further assistance contact your local Trane sales office

                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                    Glossary

                                                    A

                                                    ASHRAE

                                                    See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                    American Society of Heating Refrigeration and Air-

                                                    conditioning Engineers

                                                    An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                    BBACnettrade

                                                    See Building Automation Control network

                                                    BACnet interoperability building blocks

                                                    A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                    BACnet object

                                                    An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                    baud rate

                                                    The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                    BIBB

                                                    See BACnet interoperability building blocks

                                                    Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                    advocates BACnet protocol for use in system-level control devices

                                                    device

                                                    A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                    Device ID

                                                    The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                    Iinteroperability

                                                    The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                    Pprotocol

                                                    A set of rules (language) that governs the exchange of data over a digital communications system

                                                    S

                                                    stand-alone operation

                                                    Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                    wwwtranecom

                                                    For more information contact your local Trane office or e-mail us at comforttranecom

                                                    Literature Order Number ACC-SVP01B-EN

                                                    Date September 2009

                                                    Supersedes ACC-SVP01A-EN

                                                    Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                    • Table of Contents
                                                    • Overview
                                                    • Ordering Numbers
                                                    • BACnet Protocol
                                                    • BCI-I Configuration
                                                      • Overview
                                                      • Starting a Session of Tracer TU and Direct Connection
                                                      • Reset to Factory Default
                                                      • IP Units Configuration
                                                      • BACnet Object Configuration
                                                      • Change Baud Rate
                                                      • Change Device ID
                                                      • Stand-alone or BAS Operation
                                                        • IntelliPak Control Configuration
                                                        • BAS Unit Control
                                                        • Periodic Update of BAS Values
                                                        • BAS Communication Failure
                                                          • InputOutput Commands and Calculations
                                                            • System Control Command
                                                            • Filter Timer Reset Command
                                                            • Diagnostics Reset Command
                                                            • Setpoint Calculations
                                                            • Timestamp Configuration
                                                                • BCI IntelliPak Rotary Switches and LEDs
                                                                  • Rotary Switches
                                                                  • LEDs Description Behavior and Troubleshooting
                                                                  • 24 Vac Measurement
                                                                  • Ground Measurements
                                                                    • BACnet Data Points and Configuration Property Definitions
                                                                      • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                        • Standardized Device Profile (Annex L)
                                                                        • Interoperability Building Blocks (Annex K)
                                                                        • Segmentation Capability
                                                                        • Object Types
                                                                          • BACnet Protocol
                                                                            • Data Link Layer Options
                                                                            • Device Address Binding
                                                                            • Networking Options
                                                                            • Character Sets
                                                                                • Object Data Points and Diagnostic Data Points
                                                                                • Additional Resources
                                                                                • Glossary

                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 27

                                                      Object Data Points and Diagnostic Data Points

                                                      Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position Percent (98)

                                                      Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature Degrees-Fahrenheit (64)

                                                      Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position Percent (98)

                                                      Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local

                                                      The local daytime warmup initiate temperature setpoint Degrees-Fahrenheit (64)

                                                      Analog Input 68 Daytime Warmup Terminate Temperature Setpoint

                                                      Temperature setpoint that will exit daytime warmup mode Degrees-Fahrenheit (64)

                                                      Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used Degrees-Fahrenheit (64)

                                                      Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used BTUs-per-pound (117)

                                                      Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence Percent (98)

                                                      Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                                      Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Degrees-Fahrenheit (64)

                                                      Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized Percent (98)

                                                      Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint Degrees-Fahrenheit (64)

                                                      Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized Percent (98)

                                                      Analog Input 80 Cabinet Style Describes the cabinet style of the unit NA

                                                      Analog Input 81 Cool Type Describes the cooling type installed in the unit NA

                                                      Analog Input 82 Preheat Type Describes the heating type installed in the unit NA

                                                      Analog Input 83 Reheat Type Describes the reheat type installed in the unit NA

                                                      Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation Parts-per-million (96)

                                                      Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation Parts-per-million (96)

                                                      Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint Percent (98)

                                                      Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor Degrees-Fahrenheit (64)

                                                      Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit Percent (98)

                                                      Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit NA

                                                      Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit NA

                                                      Table 5 Analog Value

                                                      Object Identifier Object Name Description Units Valid Range

                                                      Analog Value 1 Filter Runtime Hours Setpoint

                                                      The setpoint value used by the filter run hours calculation

                                                      Hours (71) 0 to 10000

                                                      Table 4 Analog Input (continued)

                                                      Object Identifier Object Name Description Units (Listed Are Defaults)

                                                      28 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                      Object Data Points and Diagnostic Data Points

                                                      Table 6 Multistate Output

                                                      BCI-I Object Identifier Object Name Description Object States

                                                      Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                                                      Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                      1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                                                      Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                                                      Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                      1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                                      Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                                      1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                                      Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                                      1 = Flow2 = No Flow3 = Auto

                                                      Table 7 Multistate Input

                                                      BCI-I Object Identifier Object Name Description Object States

                                                      Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                      1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                                                      Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                      1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                                                      Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                                      1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                                                      Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                      1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 29

                                                      Object Data Points and Diagnostic Data Points

                                                      Multi-State Input 15 Economizer Decision Method

                                                      Unit method to determine when the economizer system is enabled

                                                      1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                                                      Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                                                      Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                                                      Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                                      1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                                      Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                      1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                                      Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                      1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                                                      Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                      1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                                      Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                      1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                                      Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                      1 = Idle2 = On3 = Cancel

                                                      Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                      1 = Off2 = On3 = Not Present

                                                      Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                      1 = Off2 = On3 = Not Present

                                                      Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                      1 = Off2 = On3 = Not Present

                                                      Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                      1 = Off|2 = On3 = Not Present

                                                      Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                      1 = Off2 = On3 = Not Present

                                                      Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                      1 = Off2 = On3 = Not Present

                                                      Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                      1 = Off2 = On3 = Not Present

                                                      Table 7 Multistate Input (continued)

                                                      BCI-I Object Identifier Object Name Description Object States

                                                      30 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                      Object Data Points and Diagnostic Data Points

                                                      Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                      1 = Off2 = On3 = Not Present

                                                      Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                      1 = Off2 = On3 = Not Present

                                                      Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                                                      Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                                                      Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                                                      Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                                                      Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                      1 = Off2 = On3 = Not Present

                                                      Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                      1= Off2= On3= Not Present

                                                      Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                                                      Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                                                      Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                                                      Multi-State Input 43 Outdoor Air Damper Status

                                                      Indicates the operating state of the outdoor damper

                                                      1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                                                      Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                      1 = Disabled2 = Enabled3 = Not Present

                                                      Table 8 Binary Output

                                                      Object Identifier Object Name DescriptionRelinquish Default Object States

                                                      Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                                                      Active = BAS Control

                                                      Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                                                      Active = Heating Locked Out

                                                      Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                                                      Active = Cooling Locked Out

                                                      Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                                                      Active = Enabled

                                                      Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                                                      Active = On

                                                      Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                                                      Inactive Inactive = DisabledActive = Enabled

                                                      Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                                                      Active = Reset

                                                      Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                                                      Active = Reset

                                                      Table 7 Multistate Input (continued)

                                                      BCI-I Object Identifier Object Name Description Object States

                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 31

                                                      Object Data Points and Diagnostic Data Points

                                                      Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                                                      Active = Auto

                                                      Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                                                      Active = Auto

                                                      Table 9 Binary Input

                                                      Object Identifier Object Name Description Object States

                                                      Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                      Inactive = Standalone controlActive = BAS control

                                                      Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                      Inactive = NormalActive = Locked Out

                                                      Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                                                      Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                      Inactive = AutoActive = Open

                                                      Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                      Inactive = InactiveActive = Active

                                                      Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                                                      Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                                                      Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                      Inactive = DisabledActive = Enabled

                                                      Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                      Inactive = DisabledActive = Enabled

                                                      Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                      Inactive = InactiveActive = Active

                                                      Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                      Inactive = No FlowActive = Flow

                                                      Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                      Inactive = InactiveActive = Active

                                                      Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                      Inactive = InactiveActive = Active

                                                      Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                      Inactive = InactiveActive = Active

                                                      Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                                                      The status of evaporator frost protection function for circuit 1

                                                      Inactive = InactiveActive = Active

                                                      Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                                                      The status of evaporator frost protection function for circuit 2

                                                      Inactive = InactiveActive = Active

                                                      Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                                                      The status of evaporator frost protection function for circuit 3

                                                      Inactive = InactiveActive = Active

                                                      Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                                                      The status of evaporator frost protection function for circuit 4

                                                      Inactive = InactiveActive = Active

                                                      Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                      Inactive = De-energizedActive = Energized

                                                      Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                      Inactive = InactiveActive = Active

                                                      Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                      Inactive = ClosedActive = Open

                                                      Table 10 Diagnostics Binary Input

                                                      Object Identifier(a) Object Name Description

                                                      Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                                                      Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                                                      Binary Input 31 (use Object Identifier for RT or CSC)

                                                      Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                                                      Binary Input 31 (use Object Identifier for FAU)

                                                      Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                                                      Table 8 Binary Output

                                                      Object Identifier Object Name DescriptionRelinquish Default Object States

                                                      32 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                      Object Data Points and Diagnostic Data Points

                                                      Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                                                      Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                                                      Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                                                      Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                                                      Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                                                      Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                                                      Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                                                      Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                                                      Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                                                      Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                      Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                      Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                                                      Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                                                      Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                                                      Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                                                      Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                                                      Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                                                      Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                                                      Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                                                      Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                                                      Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                                                      Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                                                      Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                                                      Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                                                      Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                                                      Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                                                      Binary Input 58 (use Object Identifier for RT or CSC)

                                                      Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                                                      Binary Input 58 (use Object Identifier for FAU)

                                                      Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                                                      Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                                                      Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                                                      Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                                                      Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                                                      Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                                                      Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                                                      Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                                                      Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                                                      Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                                                      Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                                                      Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                                                      Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                                                      Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                                                      Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                                                      Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                                                      Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                                                      Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                                                      Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                                                      Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                                                      Table 10 Diagnostics Binary Input (continued)

                                                      Object Identifier(a) Object Name Description

                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                                      Object Data Points and Diagnostic Data Points

                                                      Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                                      Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                                      Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                                      Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                                      Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                                      Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                                      Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                                      Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                                      Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                                      Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                                      Binary Input 86 (use Object Identifier for RT I-pak II)

                                                      Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                                      Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                                      Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                                      Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                                      Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                                      Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                                      Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                                      Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                                      Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                      Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                                      Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                                      Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                                      Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                                      Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                                      Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                                      Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                                      Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                                      Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                                      Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                                      Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                                      Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                                      Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                      Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                      Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                                      Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                                      Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                                      Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                                      Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                                      Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                                      Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                                      Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                                      Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                                      Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                                      Binary Input 121 (use Object Identifier for RT)

                                                      Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                                      Binary Input 121 (use Object Identifier for FAU)

                                                      Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                                      Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                                      Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                                      Table 10 Diagnostics Binary Input (continued)

                                                      Object Identifier(a) Object Name Description

                                                      34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                      Object Data Points and Diagnostic Data Points

                                                      Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                                      Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                                      Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                                      Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                                      Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                                      Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                                      Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                                      Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                                      Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                                      Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                                      Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                                      Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                                      Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                                      Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                                      Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                                      Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                                      Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                                      Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                                      Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                                      Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                                      Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                                      Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                                      Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                                      Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                                      Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                                      Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                                      (a) Object States Inactive = normal and Active = foreign language specific

                                                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                                      Object Identifier(a) Object Name Description

                                                      Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                      Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                                      Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                                      Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                                      Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                      Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                                      Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                                      Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                      Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                                      Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                                      Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                      Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                                      Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                                      Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                      Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                                      Table 10 Diagnostics Binary Input (continued)

                                                      Object Identifier(a) Object Name Description

                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                                      Object Data Points and Diagnostic Data Points

                                                      Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                                      Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                                      Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                                      Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                                      Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                                      Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                      Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                      Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                      Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                      Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                                      Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                                      Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                                      Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                      Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                                      Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                                      Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                                      Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                                      Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                                      Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                                      Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                                      Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                      Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                                      Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                      Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                                      Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                                      Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                                      Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                                      Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                                      Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                                      Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                                      Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                                      Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                                      Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                                      Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                                      Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                                      Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                                      Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                                      Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                                      Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                      Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                      Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                      Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                                      Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                                      Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                                      Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                                      Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                      Object Identifier(a) Object Name Description

                                                      36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                      Object Data Points and Diagnostic Data Points

                                                      Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                      Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                      Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                                      Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                                      Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                                      Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                      Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                                      Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                      Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                                      Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                                      Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                      Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                      Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                                      Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                                      Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                                      Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                                      Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                                      Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                                      Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                                      Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                                      Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                                      Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                                      Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                                      Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                                      Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                      Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                                      Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                      Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                                      Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                                      Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                                      Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                                      Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                                      Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                                      Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                                      Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                                      Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                                      Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                      Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                      Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                      Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                      Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                      Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                                      Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                                      Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                                      Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                      Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                      Object Identifier(a) Object Name Description

                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                                      Object Data Points and Diagnostic Data Points

                                                      Binary Output 16 Humidification Command Command the operating state of the humidification system

                                                      NC 3 HVAC-Advisory HVAC-Advisory

                                                      NC 1 HVAC-Critical HVAC-Critical

                                                      NC 4 HVAC-Information HVAC-Information

                                                      NC 2 HVAC-Service Required HVAC-Service Required

                                                      Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                                      Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                                      Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                                      Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                      Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                      Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                                      Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                                      Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                                      Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                                      Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                                      Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                                      Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                                      Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                                      Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                                      Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                                      Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                                      Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                                      Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                                      Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                                      Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                                      Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                                      Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                                      Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                                      Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                                      Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                                      Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                                      Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                                      Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                                      Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                                      Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                                      Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                                      Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                                      Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                                      Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                                      Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                                      Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                                      Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                                      Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                                      Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                                      Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                                      Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                      Object Identifier(a) Object Name Description

                                                      38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                      Object Data Points and Diagnostic Data Points

                                                      Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                                      Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                                      Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                                      Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                                      Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                                      Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                                      Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                                      Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                                      Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                                      Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                                      Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                                      Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                                      Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                                      Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                                      Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                                      Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                                      Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                                      Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                                      Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                                      Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                      Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                      Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                      Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                                      Binary Input 3 Unit Status Indicates the current state of the unit

                                                      Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                      Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                                      Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                                      Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                      Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                      Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                      Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                                      (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                      Object Identifier(a) Object Name Description

                                                      Table 12 Diagnostic Objects Sorted by Object Name

                                                      Object Identifier(a) Object Name ValueRange Description

                                                      BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                                      BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                                      Object Data Points and Diagnostic Data Points

                                                      BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                                      BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                                      BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                                      BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                                      BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                                      BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                                      BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                                      BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                                      BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                                      BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                                      BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                                      BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                                      BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                                      BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                                      BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                                      BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                                      BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                                      BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                                      BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                                      BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                                      BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                                      BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                                      BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                                      BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                                      BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                                      BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                      BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                      BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                      BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                      Object Identifier(a) Object Name ValueRange Description

                                                      40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                      Object Data Points and Diagnostic Data Points

                                                      BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                                      BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                                      BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                                      BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                                      BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                                      BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                                      BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                                      BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                                      BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                                      BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                                      BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                                      BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                                      BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                                      BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                                      BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                                      BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                                      BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                                      BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                                      BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                                      BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                                      BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                                      BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                                      BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                                      BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                      BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                      BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                                      BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                                      BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                                      BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                      Object Identifier(a) Object Name ValueRange Description

                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                      Object Data Points and Diagnostic Data Points

                                                      BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                      BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                      BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                      BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                      BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                      BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                      BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                      BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                      BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                      BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                      BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                      BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                      BI 121 (use Object Identifier for RT)

                                                      Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                      BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                      BI 58 (use Object Identifier for RT or CSC)

                                                      Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                      BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                      BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                      BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                      BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                      BI 31 (use Object Identifier for RT CSC)

                                                      Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                      BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                      BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                      BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                      BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                      BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                      BI 121 (use Object Identifier for FAU)

                                                      Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                      B1 31 (use Object Identifier for FAU)

                                                      Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                      BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                      BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                      Object Identifier(a) Object Name ValueRange Description

                                                      42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                      Object Data Points and Diagnostic Data Points

                                                      BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                      BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                      BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                      BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                      BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                      BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                      BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                      BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                      BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                      BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                      BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                      BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                      BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                      BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                      BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                      BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                      BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                      BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                      BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                      BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                      BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                      BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                      BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                      1 = active Diagnostic Vel Press Sensor (Rear)

                                                      BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                      Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                      BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                      BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                      BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                      BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                      BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                      Object Identifier(a) Object Name ValueRange Description

                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                      Object Data Points and Diagnostic Data Points

                                                      BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                      BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                      BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                      BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                      BI 58 (use Object Identifier for FAU)

                                                      Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                      (a) BI=Binary Input

                                                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                      Object Identifier(a) Object Name ValueRange Description

                                                      44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                      Additional Resources

                                                      Additional Resources

                                                      Use the following documents and links as additional resources

                                                      bull Product support online

                                                      bull wwwbacnetorg

                                                      bull wwwbacnetassociationorg

                                                      bull wwwashraeorg

                                                      bull Tracer TU Help online

                                                      bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                      bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                      Note For further assistance contact your local Trane sales office

                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                      Glossary

                                                      A

                                                      ASHRAE

                                                      See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                      American Society of Heating Refrigeration and Air-

                                                      conditioning Engineers

                                                      An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                      BBACnettrade

                                                      See Building Automation Control network

                                                      BACnet interoperability building blocks

                                                      A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                      BACnet object

                                                      An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                      baud rate

                                                      The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                      BIBB

                                                      See BACnet interoperability building blocks

                                                      Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                      advocates BACnet protocol for use in system-level control devices

                                                      device

                                                      A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                      Device ID

                                                      The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                      Iinteroperability

                                                      The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                      Pprotocol

                                                      A set of rules (language) that governs the exchange of data over a digital communications system

                                                      S

                                                      stand-alone operation

                                                      Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                      wwwtranecom

                                                      For more information contact your local Trane office or e-mail us at comforttranecom

                                                      Literature Order Number ACC-SVP01B-EN

                                                      Date September 2009

                                                      Supersedes ACC-SVP01A-EN

                                                      Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                      • Table of Contents
                                                      • Overview
                                                      • Ordering Numbers
                                                      • BACnet Protocol
                                                      • BCI-I Configuration
                                                        • Overview
                                                        • Starting a Session of Tracer TU and Direct Connection
                                                        • Reset to Factory Default
                                                        • IP Units Configuration
                                                        • BACnet Object Configuration
                                                        • Change Baud Rate
                                                        • Change Device ID
                                                        • Stand-alone or BAS Operation
                                                          • IntelliPak Control Configuration
                                                          • BAS Unit Control
                                                          • Periodic Update of BAS Values
                                                          • BAS Communication Failure
                                                            • InputOutput Commands and Calculations
                                                              • System Control Command
                                                              • Filter Timer Reset Command
                                                              • Diagnostics Reset Command
                                                              • Setpoint Calculations
                                                              • Timestamp Configuration
                                                                  • BCI IntelliPak Rotary Switches and LEDs
                                                                    • Rotary Switches
                                                                    • LEDs Description Behavior and Troubleshooting
                                                                    • 24 Vac Measurement
                                                                    • Ground Measurements
                                                                      • BACnet Data Points and Configuration Property Definitions
                                                                        • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                          • Standardized Device Profile (Annex L)
                                                                          • Interoperability Building Blocks (Annex K)
                                                                          • Segmentation Capability
                                                                          • Object Types
                                                                            • BACnet Protocol
                                                                              • Data Link Layer Options
                                                                              • Device Address Binding
                                                                              • Networking Options
                                                                              • Character Sets
                                                                                  • Object Data Points and Diagnostic Data Points
                                                                                  • Additional Resources
                                                                                  • Glossary

                                                        28 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                        Object Data Points and Diagnostic Data Points

                                                        Table 6 Multistate Output

                                                        BCI-I Object Identifier Object Name Description Object States

                                                        Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system1 = Disabled2 = Enabled3 = Auto

                                                        Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                        1 = Normal2 = Pressurize3 = Depressurize4 = Purge5 = Shutdown6 = Fire

                                                        Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system1 = Disabled2 = Enabled3 = Auto

                                                        Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                        1 = Occupied2= Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                                        Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                                        1 = Auto2 = Heat3 = Morning Warmup4 = Cool5 = Night Purge6 = Precool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                                        Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                                        1 = Flow2 = No Flow3 = Auto

                                                        Table 7 Multistate Input

                                                        BCI-I Object Identifier Object Name Description Object States

                                                        Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                        1 = 1 Heat1 Cool2 = Heat Pump3 = Blower Coil4 = Unit Ventilator5 = Fan Coil6 = Rooftop7 = Air Handler8 = Vertical Self Contained9 = Unitary10 = VAV Box11 = Fan Coil

                                                        Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                        1 = None2 = 2 Position Ventilation3 = Modulation Economizer4 = 2 Position VentilationWaterside Economizer5 = Waterside Economizer6 = AirsideWaterside Economizer7 = TRAQ Damper8 = Airside Economizer and TRAQ DamperSensor9 = Waterside Economizer and TRAQ DamperSensor10 = AirsideWaterside Economizer and TRAQ DamperSensor

                                                        Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                                        1 = None2 = Air Cooled 3 = Water Cooled 4 = Evaporative

                                                        Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                        1= Inactive2= Mode A Active3= Mode B Active4= Mode C Active5= Mode D Active6= Mode E Active

                                                        ACC-SVP01B-EN bull BCI-I Integration Guide 29

                                                        Object Data Points and Diagnostic Data Points

                                                        Multi-State Input 15 Economizer Decision Method

                                                        Unit method to determine when the economizer system is enabled

                                                        1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                                                        Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                                                        Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                                                        Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                                        1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                                        Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                        1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                                        Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                        1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                                                        Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                        1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                                        Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                        1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                                        Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                        1 = Idle2 = On3 = Cancel

                                                        Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                        1 = Off2 = On3 = Not Present

                                                        Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                        1 = Off2 = On3 = Not Present

                                                        Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                        1 = Off2 = On3 = Not Present

                                                        Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                        1 = Off|2 = On3 = Not Present

                                                        Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                        1 = Off2 = On3 = Not Present

                                                        Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                        1 = Off2 = On3 = Not Present

                                                        Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                        1 = Off2 = On3 = Not Present

                                                        Table 7 Multistate Input (continued)

                                                        BCI-I Object Identifier Object Name Description Object States

                                                        30 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                        Object Data Points and Diagnostic Data Points

                                                        Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                        1 = Off2 = On3 = Not Present

                                                        Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                        1 = Off2 = On3 = Not Present

                                                        Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                                                        Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                                                        Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                                                        Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                                                        Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                        1 = Off2 = On3 = Not Present

                                                        Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                        1= Off2= On3= Not Present

                                                        Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                                                        Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                                                        Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                                                        Multi-State Input 43 Outdoor Air Damper Status

                                                        Indicates the operating state of the outdoor damper

                                                        1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                                                        Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                        1 = Disabled2 = Enabled3 = Not Present

                                                        Table 8 Binary Output

                                                        Object Identifier Object Name DescriptionRelinquish Default Object States

                                                        Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                                                        Active = BAS Control

                                                        Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                                                        Active = Heating Locked Out

                                                        Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                                                        Active = Cooling Locked Out

                                                        Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                                                        Active = Enabled

                                                        Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                                                        Active = On

                                                        Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                                                        Inactive Inactive = DisabledActive = Enabled

                                                        Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                                                        Active = Reset

                                                        Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                                                        Active = Reset

                                                        Table 7 Multistate Input (continued)

                                                        BCI-I Object Identifier Object Name Description Object States

                                                        ACC-SVP01B-EN bull BCI-I Integration Guide 31

                                                        Object Data Points and Diagnostic Data Points

                                                        Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                                                        Active = Auto

                                                        Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                                                        Active = Auto

                                                        Table 9 Binary Input

                                                        Object Identifier Object Name Description Object States

                                                        Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                        Inactive = Standalone controlActive = BAS control

                                                        Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                        Inactive = NormalActive = Locked Out

                                                        Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                                                        Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                        Inactive = AutoActive = Open

                                                        Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                        Inactive = InactiveActive = Active

                                                        Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                                                        Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                                                        Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                        Inactive = DisabledActive = Enabled

                                                        Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                        Inactive = DisabledActive = Enabled

                                                        Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                        Inactive = InactiveActive = Active

                                                        Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                        Inactive = No FlowActive = Flow

                                                        Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                        Inactive = InactiveActive = Active

                                                        Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                        Inactive = InactiveActive = Active

                                                        Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                        Inactive = InactiveActive = Active

                                                        Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                                                        The status of evaporator frost protection function for circuit 1

                                                        Inactive = InactiveActive = Active

                                                        Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                                                        The status of evaporator frost protection function for circuit 2

                                                        Inactive = InactiveActive = Active

                                                        Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                                                        The status of evaporator frost protection function for circuit 3

                                                        Inactive = InactiveActive = Active

                                                        Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                                                        The status of evaporator frost protection function for circuit 4

                                                        Inactive = InactiveActive = Active

                                                        Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                        Inactive = De-energizedActive = Energized

                                                        Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                        Inactive = InactiveActive = Active

                                                        Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                        Inactive = ClosedActive = Open

                                                        Table 10 Diagnostics Binary Input

                                                        Object Identifier(a) Object Name Description

                                                        Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                                                        Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                                                        Binary Input 31 (use Object Identifier for RT or CSC)

                                                        Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                                                        Binary Input 31 (use Object Identifier for FAU)

                                                        Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                                                        Table 8 Binary Output

                                                        Object Identifier Object Name DescriptionRelinquish Default Object States

                                                        32 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                        Object Data Points and Diagnostic Data Points

                                                        Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                                                        Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                                                        Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                                                        Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                                                        Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                                                        Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                                                        Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                                                        Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                                                        Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                                                        Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                        Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                        Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                                                        Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                                                        Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                                                        Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                                                        Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                                                        Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                                                        Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                                                        Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                                                        Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                                                        Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                                                        Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                                                        Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                                                        Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                                                        Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                                                        Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                                                        Binary Input 58 (use Object Identifier for RT or CSC)

                                                        Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                                                        Binary Input 58 (use Object Identifier for FAU)

                                                        Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                                                        Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                                                        Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                                                        Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                                                        Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                                                        Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                                                        Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                                                        Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                                                        Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                                                        Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                                                        Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                                                        Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                                                        Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                                                        Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                                                        Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                                                        Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                                                        Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                                                        Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                                                        Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                                                        Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                                                        Table 10 Diagnostics Binary Input (continued)

                                                        Object Identifier(a) Object Name Description

                                                        ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                                        Object Data Points and Diagnostic Data Points

                                                        Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                                        Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                                        Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                                        Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                                        Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                                        Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                                        Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                                        Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                                        Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                                        Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                                        Binary Input 86 (use Object Identifier for RT I-pak II)

                                                        Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                                        Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                                        Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                                        Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                                        Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                                        Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                                        Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                                        Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                                        Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                        Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                                        Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                                        Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                                        Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                                        Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                                        Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                                        Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                                        Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                                        Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                                        Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                                        Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                                        Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                                        Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                        Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                        Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                                        Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                                        Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                                        Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                                        Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                                        Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                                        Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                                        Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                                        Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                                        Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                                        Binary Input 121 (use Object Identifier for RT)

                                                        Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                                        Binary Input 121 (use Object Identifier for FAU)

                                                        Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                                        Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                                        Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                                        Table 10 Diagnostics Binary Input (continued)

                                                        Object Identifier(a) Object Name Description

                                                        34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                        Object Data Points and Diagnostic Data Points

                                                        Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                                        Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                                        Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                                        Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                                        Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                                        Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                                        Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                                        Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                                        Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                                        Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                                        Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                                        Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                                        Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                                        Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                                        Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                                        Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                                        Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                                        Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                                        Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                                        Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                                        Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                                        Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                                        Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                                        Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                                        Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                                        Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                                        (a) Object States Inactive = normal and Active = foreign language specific

                                                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                                        Object Identifier(a) Object Name Description

                                                        Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                        Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                                        Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                                        Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                                        Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                        Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                                        Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                                        Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                        Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                                        Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                                        Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                        Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                                        Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                                        Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                        Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                                        Table 10 Diagnostics Binary Input (continued)

                                                        Object Identifier(a) Object Name Description

                                                        ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                                        Object Data Points and Diagnostic Data Points

                                                        Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                                        Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                                        Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                                        Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                                        Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                                        Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                        Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                        Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                        Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                        Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                                        Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                                        Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                                        Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                        Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                                        Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                                        Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                                        Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                                        Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                                        Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                                        Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                                        Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                        Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                                        Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                        Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                                        Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                                        Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                                        Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                                        Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                                        Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                                        Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                                        Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                                        Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                                        Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                                        Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                                        Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                                        Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                                        Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                                        Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                                        Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                        Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                        Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                        Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                                        Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                                        Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                                        Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                                        Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                        Object Identifier(a) Object Name Description

                                                        36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                        Object Data Points and Diagnostic Data Points

                                                        Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                        Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                        Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                                        Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                                        Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                                        Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                        Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                                        Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                        Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                                        Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                                        Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                        Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                        Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                                        Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                                        Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                                        Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                                        Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                                        Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                                        Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                                        Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                                        Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                                        Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                                        Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                                        Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                                        Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                        Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                                        Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                        Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                                        Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                                        Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                                        Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                                        Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                                        Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                                        Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                                        Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                                        Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                                        Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                        Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                        Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                        Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                        Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                        Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                                        Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                                        Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                                        Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                        Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                        Object Identifier(a) Object Name Description

                                                        ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                                        Object Data Points and Diagnostic Data Points

                                                        Binary Output 16 Humidification Command Command the operating state of the humidification system

                                                        NC 3 HVAC-Advisory HVAC-Advisory

                                                        NC 1 HVAC-Critical HVAC-Critical

                                                        NC 4 HVAC-Information HVAC-Information

                                                        NC 2 HVAC-Service Required HVAC-Service Required

                                                        Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                                        Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                                        Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                                        Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                        Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                        Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                                        Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                                        Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                                        Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                                        Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                                        Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                                        Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                                        Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                                        Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                                        Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                                        Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                                        Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                                        Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                                        Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                                        Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                                        Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                                        Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                                        Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                                        Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                                        Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                                        Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                                        Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                                        Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                                        Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                                        Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                                        Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                                        Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                                        Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                                        Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                                        Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                                        Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                                        Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                                        Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                                        Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                                        Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                                        Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                        Object Identifier(a) Object Name Description

                                                        38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                        Object Data Points and Diagnostic Data Points

                                                        Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                                        Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                                        Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                                        Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                                        Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                                        Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                                        Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                                        Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                                        Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                                        Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                                        Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                                        Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                                        Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                                        Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                                        Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                                        Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                                        Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                                        Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                                        Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                                        Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                        Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                        Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                        Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                                        Binary Input 3 Unit Status Indicates the current state of the unit

                                                        Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                        Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                                        Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                                        Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                        Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                        Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                        Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                                        (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                        Object Identifier(a) Object Name Description

                                                        Table 12 Diagnostic Objects Sorted by Object Name

                                                        Object Identifier(a) Object Name ValueRange Description

                                                        BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                                        BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                                        ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                                        Object Data Points and Diagnostic Data Points

                                                        BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                                        BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                                        BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                                        BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                                        BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                                        BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                                        BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                                        BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                                        BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                                        BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                                        BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                                        BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                                        BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                                        BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                                        BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                                        BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                                        BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                                        BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                                        BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                                        BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                                        BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                                        BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                                        BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                                        BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                                        BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                                        BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                        BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                        BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                        BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                        Object Identifier(a) Object Name ValueRange Description

                                                        40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                        Object Data Points and Diagnostic Data Points

                                                        BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                                        BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                                        BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                                        BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                                        BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                                        BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                                        BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                                        BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                                        BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                                        BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                                        BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                                        BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                                        BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                                        BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                                        BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                                        BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                                        BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                                        BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                                        BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                                        BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                                        BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                                        BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                                        BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                                        BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                        BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                        BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                                        BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                                        BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                                        BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                        Object Identifier(a) Object Name ValueRange Description

                                                        ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                        Object Data Points and Diagnostic Data Points

                                                        BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                        BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                        BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                        BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                        BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                        BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                        BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                        BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                        BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                        BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                        BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                        BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                        BI 121 (use Object Identifier for RT)

                                                        Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                        BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                        BI 58 (use Object Identifier for RT or CSC)

                                                        Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                        BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                        BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                        BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                        BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                        BI 31 (use Object Identifier for RT CSC)

                                                        Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                        BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                        BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                        BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                        BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                        BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                        BI 121 (use Object Identifier for FAU)

                                                        Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                        B1 31 (use Object Identifier for FAU)

                                                        Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                        BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                        BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                        Object Identifier(a) Object Name ValueRange Description

                                                        42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                        Object Data Points and Diagnostic Data Points

                                                        BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                        BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                        BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                        BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                        BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                        BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                        BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                        BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                        BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                        BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                        BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                        BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                        BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                        BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                        BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                        BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                        BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                        BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                        BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                        BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                        BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                        BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                        BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                        1 = active Diagnostic Vel Press Sensor (Rear)

                                                        BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                        Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                        BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                        BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                        BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                        BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                        BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                        Object Identifier(a) Object Name ValueRange Description

                                                        ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                        Object Data Points and Diagnostic Data Points

                                                        BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                        BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                        BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                        BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                        BI 58 (use Object Identifier for FAU)

                                                        Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                        (a) BI=Binary Input

                                                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                        Object Identifier(a) Object Name ValueRange Description

                                                        44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                        Additional Resources

                                                        Additional Resources

                                                        Use the following documents and links as additional resources

                                                        bull Product support online

                                                        bull wwwbacnetorg

                                                        bull wwwbacnetassociationorg

                                                        bull wwwashraeorg

                                                        bull Tracer TU Help online

                                                        bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                        bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                        Note For further assistance contact your local Trane sales office

                                                        ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                        Glossary

                                                        A

                                                        ASHRAE

                                                        See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                        American Society of Heating Refrigeration and Air-

                                                        conditioning Engineers

                                                        An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                        BBACnettrade

                                                        See Building Automation Control network

                                                        BACnet interoperability building blocks

                                                        A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                        BACnet object

                                                        An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                        baud rate

                                                        The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                        BIBB

                                                        See BACnet interoperability building blocks

                                                        Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                        advocates BACnet protocol for use in system-level control devices

                                                        device

                                                        A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                        Device ID

                                                        The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                        Iinteroperability

                                                        The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                        Pprotocol

                                                        A set of rules (language) that governs the exchange of data over a digital communications system

                                                        S

                                                        stand-alone operation

                                                        Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                        wwwtranecom

                                                        For more information contact your local Trane office or e-mail us at comforttranecom

                                                        Literature Order Number ACC-SVP01B-EN

                                                        Date September 2009

                                                        Supersedes ACC-SVP01A-EN

                                                        Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                        • Table of Contents
                                                        • Overview
                                                        • Ordering Numbers
                                                        • BACnet Protocol
                                                        • BCI-I Configuration
                                                          • Overview
                                                          • Starting a Session of Tracer TU and Direct Connection
                                                          • Reset to Factory Default
                                                          • IP Units Configuration
                                                          • BACnet Object Configuration
                                                          • Change Baud Rate
                                                          • Change Device ID
                                                          • Stand-alone or BAS Operation
                                                            • IntelliPak Control Configuration
                                                            • BAS Unit Control
                                                            • Periodic Update of BAS Values
                                                            • BAS Communication Failure
                                                              • InputOutput Commands and Calculations
                                                                • System Control Command
                                                                • Filter Timer Reset Command
                                                                • Diagnostics Reset Command
                                                                • Setpoint Calculations
                                                                • Timestamp Configuration
                                                                    • BCI IntelliPak Rotary Switches and LEDs
                                                                      • Rotary Switches
                                                                      • LEDs Description Behavior and Troubleshooting
                                                                      • 24 Vac Measurement
                                                                      • Ground Measurements
                                                                        • BACnet Data Points and Configuration Property Definitions
                                                                          • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                            • Standardized Device Profile (Annex L)
                                                                            • Interoperability Building Blocks (Annex K)
                                                                            • Segmentation Capability
                                                                            • Object Types
                                                                              • BACnet Protocol
                                                                                • Data Link Layer Options
                                                                                • Device Address Binding
                                                                                • Networking Options
                                                                                • Character Sets
                                                                                    • Object Data Points and Diagnostic Data Points
                                                                                    • Additional Resources
                                                                                    • Glossary

                                                          ACC-SVP01B-EN bull BCI-I Integration Guide 29

                                                          Object Data Points and Diagnostic Data Points

                                                          Multi-State Input 15 Economizer Decision Method

                                                          Unit method to determine when the economizer system is enabled

                                                          1= Absolute Temperature2= Relative Temperature3= Absolute Enthalpy4= Comparative Enthalpy

                                                          Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset1= None2= Outdoor Air3= Zone

                                                          Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset1= None2= Outdoor Air3= Zone

                                                          Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                                          1 = Auto2 = Heat3 = Morning Warm-up4 = Cool5 = Night Purge6 = Pre Cool7 = Off8 = Test9 = Emergency Heat10 = Fan Only11 = Free Cool12 = Ice-Making13 = Max Heat14 = Economy Mode15 = Dehumidifying16 = Calibrate

                                                          Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                          1 = Occupied2 = Unoccupied3 = Occupied Bypass4 = Occupied Standby

                                                          Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                          1= None2= Emergency Stop3= External AutoStop4= Local HI5= Remote HI

                                                          Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                          1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                                          Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                          1= RTM Zone Sensor2= Night Setback Panel3= Human Interface4= GBAS 0-5V5= BASNetwork6= GBAS 0-10V

                                                          Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                          1 = Idle2 = On3 = Cancel

                                                          Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                          1 = Off2 = On3 = Not Present

                                                          Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                          1 = Off2 = On3 = Not Present

                                                          Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                          1 = Off2 = On3 = Not Present

                                                          Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                          1 = Off|2 = On3 = Not Present

                                                          Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                          1 = Off2 = On3 = Not Present

                                                          Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                          1 = Off2 = On3 = Not Present

                                                          Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                          1 = Off2 = On3 = Not Present

                                                          Table 7 Multistate Input (continued)

                                                          BCI-I Object Identifier Object Name Description Object States

                                                          30 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                          Object Data Points and Diagnostic Data Points

                                                          Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                          1 = Off2 = On3 = Not Present

                                                          Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                          1 = Off2 = On3 = Not Present

                                                          Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                                                          Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                                                          Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                                                          Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                                                          Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                          1 = Off2 = On3 = Not Present

                                                          Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                          1= Off2= On3= Not Present

                                                          Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                                                          Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                                                          Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                                                          Multi-State Input 43 Outdoor Air Damper Status

                                                          Indicates the operating state of the outdoor damper

                                                          1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                                                          Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                          1 = Disabled2 = Enabled3 = Not Present

                                                          Table 8 Binary Output

                                                          Object Identifier Object Name DescriptionRelinquish Default Object States

                                                          Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                                                          Active = BAS Control

                                                          Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                                                          Active = Heating Locked Out

                                                          Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                                                          Active = Cooling Locked Out

                                                          Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                                                          Active = Enabled

                                                          Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                                                          Active = On

                                                          Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                                                          Inactive Inactive = DisabledActive = Enabled

                                                          Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                                                          Active = Reset

                                                          Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                                                          Active = Reset

                                                          Table 7 Multistate Input (continued)

                                                          BCI-I Object Identifier Object Name Description Object States

                                                          ACC-SVP01B-EN bull BCI-I Integration Guide 31

                                                          Object Data Points and Diagnostic Data Points

                                                          Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                                                          Active = Auto

                                                          Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                                                          Active = Auto

                                                          Table 9 Binary Input

                                                          Object Identifier Object Name Description Object States

                                                          Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                          Inactive = Standalone controlActive = BAS control

                                                          Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                          Inactive = NormalActive = Locked Out

                                                          Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                                                          Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                          Inactive = AutoActive = Open

                                                          Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                          Inactive = InactiveActive = Active

                                                          Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                                                          Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                                                          Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                          Inactive = DisabledActive = Enabled

                                                          Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                          Inactive = DisabledActive = Enabled

                                                          Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                          Inactive = InactiveActive = Active

                                                          Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                          Inactive = No FlowActive = Flow

                                                          Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                          Inactive = InactiveActive = Active

                                                          Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                          Inactive = InactiveActive = Active

                                                          Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                          Inactive = InactiveActive = Active

                                                          Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                                                          The status of evaporator frost protection function for circuit 1

                                                          Inactive = InactiveActive = Active

                                                          Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                                                          The status of evaporator frost protection function for circuit 2

                                                          Inactive = InactiveActive = Active

                                                          Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                                                          The status of evaporator frost protection function for circuit 3

                                                          Inactive = InactiveActive = Active

                                                          Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                                                          The status of evaporator frost protection function for circuit 4

                                                          Inactive = InactiveActive = Active

                                                          Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                          Inactive = De-energizedActive = Energized

                                                          Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                          Inactive = InactiveActive = Active

                                                          Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                          Inactive = ClosedActive = Open

                                                          Table 10 Diagnostics Binary Input

                                                          Object Identifier(a) Object Name Description

                                                          Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                                                          Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                                                          Binary Input 31 (use Object Identifier for RT or CSC)

                                                          Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                                                          Binary Input 31 (use Object Identifier for FAU)

                                                          Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                                                          Table 8 Binary Output

                                                          Object Identifier Object Name DescriptionRelinquish Default Object States

                                                          32 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                          Object Data Points and Diagnostic Data Points

                                                          Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                                                          Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                                                          Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                                                          Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                                                          Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                                                          Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                                                          Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                                                          Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                                                          Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                                                          Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                          Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                          Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                                                          Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                                                          Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                                                          Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                                                          Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                                                          Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                                                          Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                                                          Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                                                          Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                                                          Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                                                          Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                                                          Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                                                          Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                                                          Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                                                          Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                                                          Binary Input 58 (use Object Identifier for RT or CSC)

                                                          Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                                                          Binary Input 58 (use Object Identifier for FAU)

                                                          Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                                                          Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                                                          Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                                                          Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                                                          Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                                                          Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                                                          Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                                                          Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                                                          Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                                                          Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                                                          Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                                                          Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                                                          Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                                                          Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                                                          Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                                                          Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                                                          Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                                                          Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                                                          Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                                                          Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                                                          Table 10 Diagnostics Binary Input (continued)

                                                          Object Identifier(a) Object Name Description

                                                          ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                                          Object Data Points and Diagnostic Data Points

                                                          Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                                          Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                                          Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                                          Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                                          Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                                          Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                                          Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                                          Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                                          Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                                          Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                                          Binary Input 86 (use Object Identifier for RT I-pak II)

                                                          Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                                          Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                                          Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                                          Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                                          Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                                          Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                                          Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                                          Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                                          Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                          Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                                          Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                                          Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                                          Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                                          Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                                          Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                                          Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                                          Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                                          Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                                          Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                                          Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                                          Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                                          Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                          Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                          Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                                          Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                                          Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                                          Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                                          Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                                          Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                                          Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                                          Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                                          Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                                          Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                                          Binary Input 121 (use Object Identifier for RT)

                                                          Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                                          Binary Input 121 (use Object Identifier for FAU)

                                                          Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                                          Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                                          Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                                          Table 10 Diagnostics Binary Input (continued)

                                                          Object Identifier(a) Object Name Description

                                                          34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                          Object Data Points and Diagnostic Data Points

                                                          Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                                          Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                                          Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                                          Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                                          Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                                          Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                                          Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                                          Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                                          Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                                          Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                                          Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                                          Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                                          Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                                          Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                                          Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                                          Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                                          Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                                          Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                                          Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                                          Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                                          Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                                          Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                                          Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                                          Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                                          Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                                          Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                                          (a) Object States Inactive = normal and Active = foreign language specific

                                                          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                                          Object Identifier(a) Object Name Description

                                                          Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                          Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                                          Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                                          Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                                          Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                          Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                                          Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                                          Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                          Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                                          Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                                          Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                          Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                                          Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                                          Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                          Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                                          Table 10 Diagnostics Binary Input (continued)

                                                          Object Identifier(a) Object Name Description

                                                          ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                                          Object Data Points and Diagnostic Data Points

                                                          Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                                          Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                                          Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                                          Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                                          Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                                          Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                          Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                          Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                          Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                          Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                                          Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                                          Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                                          Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                          Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                                          Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                                          Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                                          Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                                          Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                                          Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                                          Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                                          Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                          Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                                          Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                          Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                                          Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                                          Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                                          Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                                          Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                                          Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                                          Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                                          Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                                          Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                                          Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                                          Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                                          Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                                          Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                                          Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                                          Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                                          Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                          Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                          Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                          Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                                          Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                                          Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                                          Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                                          Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                                          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                          Object Identifier(a) Object Name Description

                                                          36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                          Object Data Points and Diagnostic Data Points

                                                          Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                          Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                          Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                                          Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                                          Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                                          Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                          Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                                          Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                          Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                                          Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                                          Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                          Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                          Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                                          Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                                          Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                                          Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                                          Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                                          Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                                          Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                                          Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                                          Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                                          Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                                          Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                                          Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                                          Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                          Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                                          Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                          Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                                          Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                                          Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                                          Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                                          Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                                          Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                                          Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                                          Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                                          Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                                          Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                          Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                          Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                          Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                          Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                          Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                                          Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                                          Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                                          Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                          Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                                          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                          Object Identifier(a) Object Name Description

                                                          ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                                          Object Data Points and Diagnostic Data Points

                                                          Binary Output 16 Humidification Command Command the operating state of the humidification system

                                                          NC 3 HVAC-Advisory HVAC-Advisory

                                                          NC 1 HVAC-Critical HVAC-Critical

                                                          NC 4 HVAC-Information HVAC-Information

                                                          NC 2 HVAC-Service Required HVAC-Service Required

                                                          Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                                          Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                                          Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                                          Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                          Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                          Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                                          Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                                          Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                                          Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                                          Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                                          Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                                          Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                                          Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                                          Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                                          Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                                          Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                                          Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                                          Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                                          Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                                          Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                                          Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                                          Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                                          Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                                          Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                                          Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                                          Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                                          Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                                          Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                                          Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                                          Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                                          Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                                          Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                                          Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                                          Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                                          Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                                          Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                                          Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                                          Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                                          Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                                          Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                                          Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                                          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                          Object Identifier(a) Object Name Description

                                                          38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                          Object Data Points and Diagnostic Data Points

                                                          Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                                          Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                                          Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                                          Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                                          Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                                          Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                                          Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                                          Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                                          Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                                          Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                                          Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                                          Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                                          Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                                          Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                                          Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                                          Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                                          Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                                          Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                                          Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                                          Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                          Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                          Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                          Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                                          Binary Input 3 Unit Status Indicates the current state of the unit

                                                          Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                          Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                                          Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                                          Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                          Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                          Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                          Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                                          (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                                          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                          Object Identifier(a) Object Name Description

                                                          Table 12 Diagnostic Objects Sorted by Object Name

                                                          Object Identifier(a) Object Name ValueRange Description

                                                          BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                                          BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                                          ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                                          Object Data Points and Diagnostic Data Points

                                                          BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                                          BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                                          BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                                          BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                                          BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                                          BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                                          BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                                          BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                                          BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                                          BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                                          BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                                          BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                                          BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                                          BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                                          BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                                          BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                                          BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                                          BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                                          BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                                          BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                                          BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                                          BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                                          BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                                          BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                                          BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                                          BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                          BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                          BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                          BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                          Object Identifier(a) Object Name ValueRange Description

                                                          40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                          Object Data Points and Diagnostic Data Points

                                                          BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                                          BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                                          BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                                          BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                                          BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                                          BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                                          BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                                          BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                                          BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                                          BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                                          BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                                          BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                                          BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                                          BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                                          BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                                          BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                                          BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                                          BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                                          BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                                          BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                                          BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                                          BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                                          BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                                          BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                          BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                          BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                                          BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                                          BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                                          BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                          Object Identifier(a) Object Name ValueRange Description

                                                          ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                          Object Data Points and Diagnostic Data Points

                                                          BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                          BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                          BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                          BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                          BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                          BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                          BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                          BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                          BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                          BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                          BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                          BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                          BI 121 (use Object Identifier for RT)

                                                          Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                          BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                          BI 58 (use Object Identifier for RT or CSC)

                                                          Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                          BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                          BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                          BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                          BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                          BI 31 (use Object Identifier for RT CSC)

                                                          Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                          BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                          BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                          BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                          BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                          BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                          BI 121 (use Object Identifier for FAU)

                                                          Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                          B1 31 (use Object Identifier for FAU)

                                                          Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                          BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                          BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                          Object Identifier(a) Object Name ValueRange Description

                                                          42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                          Object Data Points and Diagnostic Data Points

                                                          BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                          BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                          BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                          BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                          BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                          BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                          BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                          BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                          BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                          BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                          BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                          BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                          BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                          BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                          BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                          BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                          BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                          BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                          BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                          BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                          BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                          BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                          BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                          1 = active Diagnostic Vel Press Sensor (Rear)

                                                          BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                          Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                          BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                          BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                          BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                          BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                          BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                          Object Identifier(a) Object Name ValueRange Description

                                                          ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                          Object Data Points and Diagnostic Data Points

                                                          BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                          BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                          BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                          BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                          BI 58 (use Object Identifier for FAU)

                                                          Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                          (a) BI=Binary Input

                                                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                          Object Identifier(a) Object Name ValueRange Description

                                                          44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                          Additional Resources

                                                          Additional Resources

                                                          Use the following documents and links as additional resources

                                                          bull Product support online

                                                          bull wwwbacnetorg

                                                          bull wwwbacnetassociationorg

                                                          bull wwwashraeorg

                                                          bull Tracer TU Help online

                                                          bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                          bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                          Note For further assistance contact your local Trane sales office

                                                          ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                          Glossary

                                                          A

                                                          ASHRAE

                                                          See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                          American Society of Heating Refrigeration and Air-

                                                          conditioning Engineers

                                                          An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                          BBACnettrade

                                                          See Building Automation Control network

                                                          BACnet interoperability building blocks

                                                          A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                          BACnet object

                                                          An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                          baud rate

                                                          The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                          BIBB

                                                          See BACnet interoperability building blocks

                                                          Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                          advocates BACnet protocol for use in system-level control devices

                                                          device

                                                          A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                          Device ID

                                                          The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                          Iinteroperability

                                                          The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                          Pprotocol

                                                          A set of rules (language) that governs the exchange of data over a digital communications system

                                                          S

                                                          stand-alone operation

                                                          Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                          wwwtranecom

                                                          For more information contact your local Trane office or e-mail us at comforttranecom

                                                          Literature Order Number ACC-SVP01B-EN

                                                          Date September 2009

                                                          Supersedes ACC-SVP01A-EN

                                                          Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                          • Table of Contents
                                                          • Overview
                                                          • Ordering Numbers
                                                          • BACnet Protocol
                                                          • BCI-I Configuration
                                                            • Overview
                                                            • Starting a Session of Tracer TU and Direct Connection
                                                            • Reset to Factory Default
                                                            • IP Units Configuration
                                                            • BACnet Object Configuration
                                                            • Change Baud Rate
                                                            • Change Device ID
                                                            • Stand-alone or BAS Operation
                                                              • IntelliPak Control Configuration
                                                              • BAS Unit Control
                                                              • Periodic Update of BAS Values
                                                              • BAS Communication Failure
                                                                • InputOutput Commands and Calculations
                                                                  • System Control Command
                                                                  • Filter Timer Reset Command
                                                                  • Diagnostics Reset Command
                                                                  • Setpoint Calculations
                                                                  • Timestamp Configuration
                                                                      • BCI IntelliPak Rotary Switches and LEDs
                                                                        • Rotary Switches
                                                                        • LEDs Description Behavior and Troubleshooting
                                                                        • 24 Vac Measurement
                                                                        • Ground Measurements
                                                                          • BACnet Data Points and Configuration Property Definitions
                                                                            • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                              • Standardized Device Profile (Annex L)
                                                                              • Interoperability Building Blocks (Annex K)
                                                                              • Segmentation Capability
                                                                              • Object Types
                                                                                • BACnet Protocol
                                                                                  • Data Link Layer Options
                                                                                  • Device Address Binding
                                                                                  • Networking Options
                                                                                  • Character Sets
                                                                                      • Object Data Points and Diagnostic Data Points
                                                                                      • Additional Resources
                                                                                      • Glossary

                                                            30 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                            Object Data Points and Diagnostic Data Points

                                                            Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                            1 = Off2 = On3 = Not Present

                                                            Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                            1 = Off2 = On3 = Not Present

                                                            Multi-State Input 34 Prefilter Status Indicates the prefilter media state1 = Clean2 = Dirty3 = Not Present

                                                            Multi-State Input 35 Primary Filter Status Indicates the primary filter media state1 = Clean2 = Dirty3 = Not Present

                                                            Multi-State Input 36 Final Filter Status Indicates the final filter media state1 = Clean2 = Dirty3 = Not Present

                                                            Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan1= Off2= On3= Not Present

                                                            Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                            1 = Off2 = On3 = Not Present

                                                            Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                            1= Off2= On3= Not Present

                                                            Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan1= Off2= On3= Not Present

                                                            Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan1 = Off2 = On3 = Not Present

                                                            Multi-State Input 42 Return Fan Status Indicates the state of the return fan1 = Off2 = On3 = Not Present

                                                            Multi-State Input 43 Outdoor Air Damper Status

                                                            Indicates the operating state of the outdoor damper

                                                            1 = At or Below Minimum Position2 = Above Minimum Position3 = Not Present

                                                            Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                            1 = Disabled2 = Enabled3 = Not Present

                                                            Table 8 Binary Output

                                                            Object Identifier Object Name DescriptionRelinquish Default Object States

                                                            Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation Inactive Inactive = Standalone Control

                                                            Active = BAS Control

                                                            Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation Inactive Inactive = Allow Heating

                                                            Active = Heating Locked Out

                                                            Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation Inactive Inactive = Allow Cooling

                                                            Active = Cooling Locked Out

                                                            Binary Output 7 Economizer Minimum Position Command Command the unit to the minimum position operation Inactive Inactive = Disabled

                                                            Active = Enabled

                                                            Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation Inactive Inactive = Auto

                                                            Active = On

                                                            Binary Output 12 Heat or Reheat Enable CommandEnable the heating or reheating system during dehumidification mode

                                                            Inactive Inactive = DisabledActive = Enabled

                                                            Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours Inactive Inactive = Accumulating

                                                            Active = Reset

                                                            Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics Inactive Inactive = Normal

                                                            Active = Reset

                                                            Table 7 Multistate Input (continued)

                                                            BCI-I Object Identifier Object Name Description Object States

                                                            ACC-SVP01B-EN bull BCI-I Integration Guide 31

                                                            Object Data Points and Diagnostic Data Points

                                                            Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                                                            Active = Auto

                                                            Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                                                            Active = Auto

                                                            Table 9 Binary Input

                                                            Object Identifier Object Name Description Object States

                                                            Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                            Inactive = Standalone controlActive = BAS control

                                                            Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                            Inactive = NormalActive = Locked Out

                                                            Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                                                            Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                            Inactive = AutoActive = Open

                                                            Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                            Inactive = InactiveActive = Active

                                                            Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                                                            Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                                                            Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                            Inactive = DisabledActive = Enabled

                                                            Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                            Inactive = DisabledActive = Enabled

                                                            Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                            Inactive = InactiveActive = Active

                                                            Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                            Inactive = No FlowActive = Flow

                                                            Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                            Inactive = InactiveActive = Active

                                                            Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                            Inactive = InactiveActive = Active

                                                            Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                            Inactive = InactiveActive = Active

                                                            Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                                                            The status of evaporator frost protection function for circuit 1

                                                            Inactive = InactiveActive = Active

                                                            Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                                                            The status of evaporator frost protection function for circuit 2

                                                            Inactive = InactiveActive = Active

                                                            Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                                                            The status of evaporator frost protection function for circuit 3

                                                            Inactive = InactiveActive = Active

                                                            Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                                                            The status of evaporator frost protection function for circuit 4

                                                            Inactive = InactiveActive = Active

                                                            Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                            Inactive = De-energizedActive = Energized

                                                            Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                            Inactive = InactiveActive = Active

                                                            Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                            Inactive = ClosedActive = Open

                                                            Table 10 Diagnostics Binary Input

                                                            Object Identifier(a) Object Name Description

                                                            Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                                                            Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                                                            Binary Input 31 (use Object Identifier for RT or CSC)

                                                            Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                                                            Binary Input 31 (use Object Identifier for FAU)

                                                            Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                                                            Table 8 Binary Output

                                                            Object Identifier Object Name DescriptionRelinquish Default Object States

                                                            32 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                            Object Data Points and Diagnostic Data Points

                                                            Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                                                            Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                                                            Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                                                            Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                                                            Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                                                            Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                                                            Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                                                            Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                                                            Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                                                            Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                            Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                            Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                                                            Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                                                            Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                                                            Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                                                            Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                                                            Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                                                            Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                                                            Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                                                            Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                                                            Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                                                            Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                                                            Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                                                            Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                                                            Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                                                            Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                                                            Binary Input 58 (use Object Identifier for RT or CSC)

                                                            Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                                                            Binary Input 58 (use Object Identifier for FAU)

                                                            Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                                                            Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                                                            Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                                                            Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                                                            Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                                                            Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                                                            Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                                                            Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                                                            Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                                                            Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                                                            Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                                                            Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                                                            Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                                                            Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                                                            Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                                                            Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                                                            Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                                                            Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                                                            Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                                                            Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                                                            Table 10 Diagnostics Binary Input (continued)

                                                            Object Identifier(a) Object Name Description

                                                            ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                                            Object Data Points and Diagnostic Data Points

                                                            Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                                            Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                                            Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                                            Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                                            Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                                            Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                                            Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                                            Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                                            Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                                            Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                                            Binary Input 86 (use Object Identifier for RT I-pak II)

                                                            Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                                            Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                                            Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                                            Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                                            Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                                            Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                                            Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                                            Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                                            Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                            Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                                            Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                                            Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                                            Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                                            Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                                            Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                                            Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                                            Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                                            Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                                            Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                                            Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                                            Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                                            Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                            Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                            Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                                            Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                                            Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                                            Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                                            Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                                            Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                                            Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                                            Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                                            Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                                            Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                                            Binary Input 121 (use Object Identifier for RT)

                                                            Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                                            Binary Input 121 (use Object Identifier for FAU)

                                                            Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                                            Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                                            Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                                            Table 10 Diagnostics Binary Input (continued)

                                                            Object Identifier(a) Object Name Description

                                                            34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                            Object Data Points and Diagnostic Data Points

                                                            Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                                            Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                                            Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                                            Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                                            Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                                            Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                                            Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                                            Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                                            Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                                            Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                                            Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                                            Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                                            Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                                            Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                                            Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                                            Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                                            Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                                            Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                                            Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                                            Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                                            Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                                            Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                                            Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                                            Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                                            Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                                            Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                                            (a) Object States Inactive = normal and Active = foreign language specific

                                                            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                                            Object Identifier(a) Object Name Description

                                                            Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                            Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                                            Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                                            Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                                            Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                            Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                                            Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                                            Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                            Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                                            Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                                            Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                            Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                                            Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                                            Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                            Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                                            Table 10 Diagnostics Binary Input (continued)

                                                            Object Identifier(a) Object Name Description

                                                            ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                                            Object Data Points and Diagnostic Data Points

                                                            Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                                            Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                                            Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                                            Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                                            Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                                            Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                            Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                            Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                            Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                            Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                                            Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                                            Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                                            Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                            Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                                            Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                                            Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                                            Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                                            Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                                            Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                                            Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                                            Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                            Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                                            Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                            Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                                            Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                                            Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                                            Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                                            Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                                            Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                                            Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                                            Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                                            Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                                            Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                                            Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                                            Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                                            Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                                            Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                                            Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                                            Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                            Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                            Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                            Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                                            Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                                            Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                                            Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                                            Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                                            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                            Object Identifier(a) Object Name Description

                                                            36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                            Object Data Points and Diagnostic Data Points

                                                            Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                            Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                            Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                                            Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                                            Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                                            Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                            Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                                            Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                            Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                                            Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                                            Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                            Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                            Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                                            Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                                            Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                                            Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                                            Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                                            Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                                            Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                                            Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                                            Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                                            Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                                            Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                                            Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                                            Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                            Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                                            Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                            Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                                            Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                                            Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                                            Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                                            Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                                            Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                                            Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                                            Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                                            Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                                            Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                            Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                            Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                            Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                            Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                            Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                                            Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                                            Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                                            Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                            Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                                            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                            Object Identifier(a) Object Name Description

                                                            ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                                            Object Data Points and Diagnostic Data Points

                                                            Binary Output 16 Humidification Command Command the operating state of the humidification system

                                                            NC 3 HVAC-Advisory HVAC-Advisory

                                                            NC 1 HVAC-Critical HVAC-Critical

                                                            NC 4 HVAC-Information HVAC-Information

                                                            NC 2 HVAC-Service Required HVAC-Service Required

                                                            Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                                            Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                                            Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                                            Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                            Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                            Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                                            Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                                            Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                                            Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                                            Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                                            Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                                            Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                                            Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                                            Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                                            Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                                            Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                                            Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                                            Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                                            Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                                            Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                                            Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                                            Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                                            Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                                            Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                                            Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                                            Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                                            Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                                            Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                                            Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                                            Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                                            Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                                            Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                                            Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                                            Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                                            Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                                            Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                                            Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                                            Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                                            Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                                            Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                                            Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                                            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                            Object Identifier(a) Object Name Description

                                                            38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                            Object Data Points and Diagnostic Data Points

                                                            Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                                            Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                                            Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                                            Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                                            Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                                            Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                                            Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                                            Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                                            Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                                            Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                                            Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                                            Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                                            Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                                            Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                                            Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                                            Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                                            Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                                            Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                                            Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                                            Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                            Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                            Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                            Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                                            Binary Input 3 Unit Status Indicates the current state of the unit

                                                            Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                            Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                                            Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                                            Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                            Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                            Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                            Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                                            (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                                            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                            Object Identifier(a) Object Name Description

                                                            Table 12 Diagnostic Objects Sorted by Object Name

                                                            Object Identifier(a) Object Name ValueRange Description

                                                            BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                                            BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                                            ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                                            Object Data Points and Diagnostic Data Points

                                                            BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                                            BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                                            BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                                            BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                                            BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                                            BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                                            BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                                            BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                                            BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                                            BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                                            BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                                            BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                                            BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                                            BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                                            BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                                            BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                                            BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                                            BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                                            BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                                            BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                                            BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                                            BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                                            BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                                            BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                                            BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                                            BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                            BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                            BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                            BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                            Object Identifier(a) Object Name ValueRange Description

                                                            40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                            Object Data Points and Diagnostic Data Points

                                                            BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                                            BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                                            BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                                            BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                                            BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                                            BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                                            BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                                            BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                                            BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                                            BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                                            BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                                            BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                                            BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                                            BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                                            BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                                            BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                                            BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                                            BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                                            BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                                            BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                                            BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                                            BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                                            BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                                            BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                            BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                            BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                                            BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                                            BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                                            BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                            Object Identifier(a) Object Name ValueRange Description

                                                            ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                            Object Data Points and Diagnostic Data Points

                                                            BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                            BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                            BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                            BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                            BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                            BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                            BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                            BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                            BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                            BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                            BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                            BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                            BI 121 (use Object Identifier for RT)

                                                            Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                            BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                            BI 58 (use Object Identifier for RT or CSC)

                                                            Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                            BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                            BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                            BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                            BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                            BI 31 (use Object Identifier for RT CSC)

                                                            Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                            BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                            BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                            BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                            BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                            BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                            BI 121 (use Object Identifier for FAU)

                                                            Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                            B1 31 (use Object Identifier for FAU)

                                                            Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                            BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                            BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                            Object Identifier(a) Object Name ValueRange Description

                                                            42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                            Object Data Points and Diagnostic Data Points

                                                            BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                            BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                            BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                            BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                            BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                            BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                            BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                            BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                            BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                            BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                            BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                            BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                            BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                            BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                            BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                            BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                            BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                            BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                            BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                            BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                            BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                            BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                            BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                            1 = active Diagnostic Vel Press Sensor (Rear)

                                                            BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                            Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                            BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                            BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                            BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                            BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                            BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                            Object Identifier(a) Object Name ValueRange Description

                                                            ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                            Object Data Points and Diagnostic Data Points

                                                            BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                            BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                            BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                            BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                            BI 58 (use Object Identifier for FAU)

                                                            Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                            (a) BI=Binary Input

                                                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                            Object Identifier(a) Object Name ValueRange Description

                                                            44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                            Additional Resources

                                                            Additional Resources

                                                            Use the following documents and links as additional resources

                                                            bull Product support online

                                                            bull wwwbacnetorg

                                                            bull wwwbacnetassociationorg

                                                            bull wwwashraeorg

                                                            bull Tracer TU Help online

                                                            bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                            bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                            Note For further assistance contact your local Trane sales office

                                                            ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                            Glossary

                                                            A

                                                            ASHRAE

                                                            See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                            American Society of Heating Refrigeration and Air-

                                                            conditioning Engineers

                                                            An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                            BBACnettrade

                                                            See Building Automation Control network

                                                            BACnet interoperability building blocks

                                                            A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                            BACnet object

                                                            An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                            baud rate

                                                            The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                            BIBB

                                                            See BACnet interoperability building blocks

                                                            Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                            advocates BACnet protocol for use in system-level control devices

                                                            device

                                                            A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                            Device ID

                                                            The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                            Iinteroperability

                                                            The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                            Pprotocol

                                                            A set of rules (language) that governs the exchange of data over a digital communications system

                                                            S

                                                            stand-alone operation

                                                            Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                            wwwtranecom

                                                            For more information contact your local Trane office or e-mail us at comforttranecom

                                                            Literature Order Number ACC-SVP01B-EN

                                                            Date September 2009

                                                            Supersedes ACC-SVP01A-EN

                                                            Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                            • Table of Contents
                                                            • Overview
                                                            • Ordering Numbers
                                                            • BACnet Protocol
                                                            • BCI-I Configuration
                                                              • Overview
                                                              • Starting a Session of Tracer TU and Direct Connection
                                                              • Reset to Factory Default
                                                              • IP Units Configuration
                                                              • BACnet Object Configuration
                                                              • Change Baud Rate
                                                              • Change Device ID
                                                              • Stand-alone or BAS Operation
                                                                • IntelliPak Control Configuration
                                                                • BAS Unit Control
                                                                • Periodic Update of BAS Values
                                                                • BAS Communication Failure
                                                                  • InputOutput Commands and Calculations
                                                                    • System Control Command
                                                                    • Filter Timer Reset Command
                                                                    • Diagnostics Reset Command
                                                                    • Setpoint Calculations
                                                                    • Timestamp Configuration
                                                                        • BCI IntelliPak Rotary Switches and LEDs
                                                                          • Rotary Switches
                                                                          • LEDs Description Behavior and Troubleshooting
                                                                          • 24 Vac Measurement
                                                                          • Ground Measurements
                                                                            • BACnet Data Points and Configuration Property Definitions
                                                                              • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                                • Standardized Device Profile (Annex L)
                                                                                • Interoperability Building Blocks (Annex K)
                                                                                • Segmentation Capability
                                                                                • Object Types
                                                                                  • BACnet Protocol
                                                                                    • Data Link Layer Options
                                                                                    • Device Address Binding
                                                                                    • Networking Options
                                                                                    • Character Sets
                                                                                        • Object Data Points and Diagnostic Data Points
                                                                                        • Additional Resources
                                                                                        • Glossary

                                                              ACC-SVP01B-EN bull BCI-I Integration Guide 31

                                                              Object Data Points and Diagnostic Data Points

                                                              Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system Active Inactive = Disabled

                                                              Active = Auto

                                                              Binary Output 16 Humidification Command Command the operating state of the humidification system Active Inactive = Disabled

                                                              Active = Auto

                                                              Table 9 Binary Input

                                                              Object Identifier Object Name Description Object States

                                                              Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                              Inactive = Standalone controlActive = BAS control

                                                              Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                              Inactive = NormalActive = Locked Out

                                                              Binary Input 3 Unit Status Indicates the current state of the unit Inactive = OffActive = On

                                                              Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                              Inactive = AutoActive = Open

                                                              Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                              Inactive = InactiveActive = Active

                                                              Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode Inactive = InactiveActive = Active

                                                              Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration Inactive = CyclingActive = Continuous

                                                              Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                              Inactive = DisabledActive = Enabled

                                                              Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                              Inactive = DisabledActive = Enabled

                                                              Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                              Inactive = InactiveActive = Active

                                                              Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                              Inactive = No FlowActive = Flow

                                                              Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                              Inactive = InactiveActive = Active

                                                              Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                              Inactive = InactiveActive = Active

                                                              Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                              Inactive = InactiveActive = Active

                                                              Binary Input 161 Evaporator Frost Protection Circuit 1 Status

                                                              The status of evaporator frost protection function for circuit 1

                                                              Inactive = InactiveActive = Active

                                                              Binary Input 162 Evaporator Frost Protection Circuit 2 Status

                                                              The status of evaporator frost protection function for circuit 2

                                                              Inactive = InactiveActive = Active

                                                              Binary Input 163 Evaporator Frost Protection Circuit 3 Status

                                                              The status of evaporator frost protection function for circuit 3

                                                              Inactive = InactiveActive = Active

                                                              Binary Input 164 Evaporator Frost Protection Circuit 4 Status

                                                              The status of evaporator frost protection function for circuit 4

                                                              Inactive = InactiveActive = Active

                                                              Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                              Inactive = De-energizedActive = Energized

                                                              Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                              Inactive = InactiveActive = Active

                                                              Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                              Inactive = ClosedActive = Open

                                                              Table 10 Diagnostics Binary Input

                                                              Object Identifier(a) Object Name Description

                                                              Binary Input 29 Diagnostic RTM Zone Temp Sensor Failure Diagnostic RTM Zone Temp Sensor Failure

                                                              Binary Input 30 Diagnostic Supply Air Temp Sensor Fail Diagnostic Supply Air Temp Sensor Fail

                                                              Binary Input 31 (use Object Identifier for RT or CSC)

                                                              Diagnostic RTM Aux Temp Sensor Failure Diagnostic RTM Aux Temp Sensor Failure

                                                              Binary Input 31 (use Object Identifier for FAU)

                                                              Diagnostic SA Temp Sensor Fail Diagnostic SA Temp Sensor Fail

                                                              Table 8 Binary Output

                                                              Object Identifier Object Name DescriptionRelinquish Default Object States

                                                              32 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                              Object Data Points and Diagnostic Data Points

                                                              Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                                                              Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                                                              Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                                                              Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                                                              Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                                                              Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                                                              Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                                                              Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                                                              Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                                                              Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                              Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                              Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                                                              Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                                                              Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                                                              Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                                                              Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                                                              Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                                                              Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                                                              Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                                                              Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                                                              Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                                                              Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                                                              Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                                                              Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                                                              Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                                                              Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                                                              Binary Input 58 (use Object Identifier for RT or CSC)

                                                              Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                                                              Binary Input 58 (use Object Identifier for FAU)

                                                              Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                                                              Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                                                              Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                                                              Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                                                              Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                                                              Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                                                              Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                                                              Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                                                              Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                                                              Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                                                              Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                                                              Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                                                              Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                                                              Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                                                              Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                                                              Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                                                              Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                                                              Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                                                              Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                                                              Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                                                              Table 10 Diagnostics Binary Input (continued)

                                                              Object Identifier(a) Object Name Description

                                                              ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                                              Object Data Points and Diagnostic Data Points

                                                              Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                                              Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                                              Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                                              Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                                              Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                                              Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                                              Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                                              Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                                              Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                                              Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                                              Binary Input 86 (use Object Identifier for RT I-pak II)

                                                              Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                                              Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                                              Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                                              Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                                              Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                                              Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                                              Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                                              Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                                              Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                              Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                                              Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                                              Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                                              Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                                              Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                                              Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                                              Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                                              Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                                              Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                                              Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                                              Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                                              Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                                              Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                              Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                              Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                                              Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                                              Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                                              Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                                              Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                                              Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                                              Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                                              Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                                              Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                                              Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                                              Binary Input 121 (use Object Identifier for RT)

                                                              Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                                              Binary Input 121 (use Object Identifier for FAU)

                                                              Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                                              Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                                              Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                                              Table 10 Diagnostics Binary Input (continued)

                                                              Object Identifier(a) Object Name Description

                                                              34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                              Object Data Points and Diagnostic Data Points

                                                              Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                                              Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                                              Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                                              Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                                              Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                                              Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                                              Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                                              Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                                              Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                                              Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                                              Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                                              Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                                              Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                                              Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                                              Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                                              Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                                              Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                                              Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                                              Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                                              Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                                              Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                                              Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                                              Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                                              Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                                              Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                                              Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                                              (a) Object States Inactive = normal and Active = foreign language specific

                                                              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                                              Object Identifier(a) Object Name Description

                                                              Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                              Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                                              Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                                              Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                                              Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                              Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                                              Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                                              Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                              Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                                              Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                                              Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                              Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                                              Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                                              Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                              Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                                              Table 10 Diagnostics Binary Input (continued)

                                                              Object Identifier(a) Object Name Description

                                                              ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                                              Object Data Points and Diagnostic Data Points

                                                              Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                                              Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                                              Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                                              Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                                              Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                                              Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                              Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                              Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                              Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                              Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                                              Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                                              Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                                              Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                              Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                                              Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                                              Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                                              Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                                              Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                                              Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                                              Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                                              Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                              Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                                              Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                              Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                                              Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                                              Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                                              Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                                              Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                                              Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                                              Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                                              Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                                              Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                                              Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                                              Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                                              Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                                              Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                                              Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                                              Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                                              Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                              Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                              Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                              Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                                              Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                                              Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                                              Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                                              Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                                              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                              Object Identifier(a) Object Name Description

                                                              36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                              Object Data Points and Diagnostic Data Points

                                                              Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                              Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                              Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                                              Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                                              Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                                              Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                              Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                                              Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                              Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                                              Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                                              Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                              Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                              Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                                              Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                                              Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                                              Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                                              Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                                              Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                                              Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                                              Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                                              Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                                              Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                                              Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                                              Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                                              Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                              Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                                              Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                              Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                                              Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                                              Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                                              Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                                              Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                                              Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                                              Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                                              Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                                              Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                                              Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                              Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                              Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                              Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                              Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                              Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                                              Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                                              Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                                              Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                              Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                                              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                              Object Identifier(a) Object Name Description

                                                              ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                                              Object Data Points and Diagnostic Data Points

                                                              Binary Output 16 Humidification Command Command the operating state of the humidification system

                                                              NC 3 HVAC-Advisory HVAC-Advisory

                                                              NC 1 HVAC-Critical HVAC-Critical

                                                              NC 4 HVAC-Information HVAC-Information

                                                              NC 2 HVAC-Service Required HVAC-Service Required

                                                              Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                                              Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                                              Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                                              Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                              Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                              Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                                              Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                                              Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                                              Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                                              Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                                              Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                                              Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                                              Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                                              Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                                              Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                                              Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                                              Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                                              Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                                              Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                                              Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                                              Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                                              Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                                              Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                                              Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                                              Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                                              Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                                              Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                                              Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                                              Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                                              Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                                              Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                                              Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                                              Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                                              Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                                              Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                                              Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                                              Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                                              Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                                              Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                                              Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                                              Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                                              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                              Object Identifier(a) Object Name Description

                                                              38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                              Object Data Points and Diagnostic Data Points

                                                              Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                                              Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                                              Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                                              Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                                              Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                                              Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                                              Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                                              Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                                              Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                                              Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                                              Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                                              Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                                              Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                                              Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                                              Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                                              Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                                              Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                                              Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                                              Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                                              Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                              Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                              Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                              Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                                              Binary Input 3 Unit Status Indicates the current state of the unit

                                                              Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                              Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                                              Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                                              Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                              Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                              Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                              Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                                              (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                                              Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                              Object Identifier(a) Object Name Description

                                                              Table 12 Diagnostic Objects Sorted by Object Name

                                                              Object Identifier(a) Object Name ValueRange Description

                                                              BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                                              BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                                              ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                                              Object Data Points and Diagnostic Data Points

                                                              BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                                              BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                                              BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                                              BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                                              BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                                              BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                                              BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                                              BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                                              BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                                              BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                                              BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                                              BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                                              BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                                              BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                                              BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                                              BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                                              BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                                              BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                                              BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                                              BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                                              BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                                              BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                                              BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                                              BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                                              BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                                              BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                              BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                              BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                              BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                              Object Identifier(a) Object Name ValueRange Description

                                                              40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                              Object Data Points and Diagnostic Data Points

                                                              BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                                              BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                                              BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                                              BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                                              BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                                              BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                                              BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                                              BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                                              BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                                              BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                                              BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                                              BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                                              BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                                              BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                                              BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                                              BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                                              BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                                              BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                                              BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                                              BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                                              BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                                              BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                                              BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                                              BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                              BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                              BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                                              BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                                              BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                                              BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                              Object Identifier(a) Object Name ValueRange Description

                                                              ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                              Object Data Points and Diagnostic Data Points

                                                              BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                              BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                              BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                              BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                              BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                              BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                              BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                              BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                              BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                              BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                              BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                              BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                              BI 121 (use Object Identifier for RT)

                                                              Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                              BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                              BI 58 (use Object Identifier for RT or CSC)

                                                              Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                              BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                              BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                              BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                              BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                              BI 31 (use Object Identifier for RT CSC)

                                                              Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                              BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                              BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                              BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                              BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                              BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                              BI 121 (use Object Identifier for FAU)

                                                              Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                              B1 31 (use Object Identifier for FAU)

                                                              Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                              BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                              BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                              Object Identifier(a) Object Name ValueRange Description

                                                              42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                              Object Data Points and Diagnostic Data Points

                                                              BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                              BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                              BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                              BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                              BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                              BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                              BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                              BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                              BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                              BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                              BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                              BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                              BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                              BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                              BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                              BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                              BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                              BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                              BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                              BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                              BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                              BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                              BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                              1 = active Diagnostic Vel Press Sensor (Rear)

                                                              BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                              Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                              BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                              BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                              BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                              BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                              BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                              Object Identifier(a) Object Name ValueRange Description

                                                              ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                              Object Data Points and Diagnostic Data Points

                                                              BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                              BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                              BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                              BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                              BI 58 (use Object Identifier for FAU)

                                                              Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                              (a) BI=Binary Input

                                                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                              Object Identifier(a) Object Name ValueRange Description

                                                              44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                              Additional Resources

                                                              Additional Resources

                                                              Use the following documents and links as additional resources

                                                              bull Product support online

                                                              bull wwwbacnetorg

                                                              bull wwwbacnetassociationorg

                                                              bull wwwashraeorg

                                                              bull Tracer TU Help online

                                                              bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                              bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                              Note For further assistance contact your local Trane sales office

                                                              ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                              Glossary

                                                              A

                                                              ASHRAE

                                                              See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                              American Society of Heating Refrigeration and Air-

                                                              conditioning Engineers

                                                              An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                              BBACnettrade

                                                              See Building Automation Control network

                                                              BACnet interoperability building blocks

                                                              A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                              BACnet object

                                                              An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                              baud rate

                                                              The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                              BIBB

                                                              See BACnet interoperability building blocks

                                                              Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                              advocates BACnet protocol for use in system-level control devices

                                                              device

                                                              A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                              Device ID

                                                              The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                              Iinteroperability

                                                              The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                              Pprotocol

                                                              A set of rules (language) that governs the exchange of data over a digital communications system

                                                              S

                                                              stand-alone operation

                                                              Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                              wwwtranecom

                                                              For more information contact your local Trane office or e-mail us at comforttranecom

                                                              Literature Order Number ACC-SVP01B-EN

                                                              Date September 2009

                                                              Supersedes ACC-SVP01A-EN

                                                              Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                              • Table of Contents
                                                              • Overview
                                                              • Ordering Numbers
                                                              • BACnet Protocol
                                                              • BCI-I Configuration
                                                                • Overview
                                                                • Starting a Session of Tracer TU and Direct Connection
                                                                • Reset to Factory Default
                                                                • IP Units Configuration
                                                                • BACnet Object Configuration
                                                                • Change Baud Rate
                                                                • Change Device ID
                                                                • Stand-alone or BAS Operation
                                                                  • IntelliPak Control Configuration
                                                                  • BAS Unit Control
                                                                  • Periodic Update of BAS Values
                                                                  • BAS Communication Failure
                                                                    • InputOutput Commands and Calculations
                                                                      • System Control Command
                                                                      • Filter Timer Reset Command
                                                                      • Diagnostics Reset Command
                                                                      • Setpoint Calculations
                                                                      • Timestamp Configuration
                                                                          • BCI IntelliPak Rotary Switches and LEDs
                                                                            • Rotary Switches
                                                                            • LEDs Description Behavior and Troubleshooting
                                                                            • 24 Vac Measurement
                                                                            • Ground Measurements
                                                                              • BACnet Data Points and Configuration Property Definitions
                                                                                • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                                  • Standardized Device Profile (Annex L)
                                                                                  • Interoperability Building Blocks (Annex K)
                                                                                  • Segmentation Capability
                                                                                  • Object Types
                                                                                    • BACnet Protocol
                                                                                      • Data Link Layer Options
                                                                                      • Device Address Binding
                                                                                      • Networking Options
                                                                                      • Character Sets
                                                                                          • Object Data Points and Diagnostic Data Points
                                                                                          • Additional Resources
                                                                                          • Glossary

                                                                32 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                Object Data Points and Diagnostic Data Points

                                                                Binary Input 32 Diagnostic OA Temperature Sensor Fail Diagnostic OA Temperature Sensor Fail

                                                                Binary Input 33 Diagnostic Mode Input Failure Diagnostic Mode Input Failure

                                                                Binary Input 34 Diagnostic Occ Zone Cool Setpoint Fail Diagnostic Occ Zone Cool Setpoint Fail

                                                                Binary Input 35 Diagnostic Occ Zone Heat Setpoint Fail Diagnostic Occ Zone Heat Setpoint Fail

                                                                Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail

                                                                Binary Input 37 Diagnostic OA Humidity Sensor Failure Diagnostic OA Humidity Sensor Failure

                                                                Binary Input 38 Diagnostic Emergency Stop Diagnostic Emergency Stop

                                                                Binary Input 39 Diagnostic Supply Fan Failure Diagnostic Supply Fan Failure

                                                                Binary Input 40 Diagnostic ExhaustReturn Fan Failure Diagnostic ExhaustReturn Fan Failure

                                                                Binary Input 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                                Binary Input 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                                Binary Input 43 Diagnostic Low Pressure Ctl Open - Ckt1 Diagnostic Low Pressure Ctl Open - Ckt1

                                                                Binary Input 44 Diagnostic Low Pressure Ctl Open - Ckt2 Diagnostic Low Pressure Ctl Open - Ckt2

                                                                Binary Input 45 Diagnostic Cond Temp Sensor Fail - Ckt1 Diagnostic Cond Temp Sensor Fail - Ckt1

                                                                Binary Input 46 Diagnostic Cond Temp Sensor Fail - Ckt2 Diagnostic Cond Temp Sensor Fail - Ckt2

                                                                Binary Input 47 Diagnostic Compressor Trip - Ckt1 Diagnostic Compressor Trip - Ckt1

                                                                Binary Input 48 Diagnostic Compressor Trip - Ckt2 Diagnostic Compressor Trip - Ckt2

                                                                Binary Input 49 Diagnostic HEAT Aux Temp Sensor Fail Diagnostic HEAT Aux Temp Sensor Fail

                                                                Binary Input 50 Diagnostic Low Air Temp Limit Trip Diagnostic Low Air Temp Limit Trip

                                                                Binary Input 51 Diagnostic Heat Failure Diagnostic Heat Failure

                                                                Binary Input 52 Diagnostic Unocc Zone Cool Stpnt Fail Diagnostic Unocc Zone Cool Stpnt Fail

                                                                Binary Input 53 Diagnostic Unocc Zone Heat Stpnt Fail Diagnostic Unocc Zone Heat Stpnt Fail

                                                                Binary Input 54 Diagnostic SA Duct Press Setpoint Fail Diagnostic SA Duct Press Setpoint Fail

                                                                Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail

                                                                Binary Input 56 Diagnostic Space Pressure Sensor Fail Diagnostic Space Pressure Sensor Fail

                                                                Binary Input 57 Diagnostic Return Air Temp Sensor Fail Diagnostic Return Air Temp Sensor Fail

                                                                Binary Input 58 (use Object Identifier for RT or CSC)

                                                                Diagnostic Return Air RH Sensor Failure Diagnostic Return Air RH Sensor Failure

                                                                Binary Input 58 (use Object Identifier for FAU)

                                                                Diagnostic Zone Humidity Sensor Failure Diagnostic Zone Humidity Sensor Failure

                                                                Binary Input 59 Diagnostic Auto - SA High Press Limit Diagnostic Auto - SA High Press Limit

                                                                Binary Input 60 Diagnostic Man - SA High Press Limit Diagnostic Man - SA High Press Limit

                                                                Binary Input 61 Diagnostic SCM Communications Failure Diagnostic SCM Communications Failure

                                                                Binary Input 62 Diagnostic MCM Communications Failure Diagnostic MCM Communications Failure

                                                                Binary Input 63 Diagnostic HEAT Communications Failure Diagnostic HEAT Communications Failure

                                                                Binary Input 64 Diagnostic ECEM Communications Failure Diagnostic ECEM Communications Failure

                                                                Binary Input 65 Diagnostic GBAS 0-5 VDC Comm Failure Diagnostic GBAS 0-5 VDC Comm Failure

                                                                Binary Input 66 Diagnostic BACnet Module Comm Fail Diagnostic BACnet Module Comm Fail

                                                                Binary Input 67 Diagnostic BASNetwork Comm Fail Diagnostic BASNetwork Comm Fail

                                                                Binary Input 68 Diagnostic NSB Panel Communication Fail Diagnostic NSB Panel Communication Fail

                                                                Binary Input 69 Diagnostic RTM EEPROM Failure Diagnostic RTM EEPROM Failure

                                                                Binary Input 70 Diagnostic Unit HI Communications Fail Diagnostic Unit HI Communications Fail

                                                                Binary Input 71 Diagnostic VOM Communications Failure Diagnostic VOM Communications Failure

                                                                Binary Input 72 Diagnostic Compressor Contact Fail-Ckt1 Diagnostic Compressor Contact Fail-Ckt1

                                                                Binary Input 73 Diagnostic Compressor Contact Fail-Ckt2 Diagnostic Compressor Contact Fail-Ckt2

                                                                Binary Input 74 Diagnostic SA Temp Cool Setpoint Fail Diagnostic SA Temp Cool Setpoint Fail

                                                                Binary Input 75 Diagnostic SA Temp Heat Setpoint Fail Diagnostic SA Temp Heat Setpoint Fail

                                                                Binary Input 76 Diagnostic Dirty Filter Diagnostic Dirty Filter

                                                                Binary Input 77 Diagnostic NSB Zone Temp Sensor Fail Diagnostic NSB Zone Temp Sensor Fail

                                                                Table 10 Diagnostics Binary Input (continued)

                                                                Object Identifier(a) Object Name Description

                                                                ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                                                Object Data Points and Diagnostic Data Points

                                                                Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                                                Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                                                Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                                                Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                                                Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                                                Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                                                Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                                                Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                                                Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                                                Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                                                Binary Input 86 (use Object Identifier for RT I-pak II)

                                                                Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                                                Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                                                Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                                                Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                                                Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                                                Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                                                Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                                                Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                                                Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                                Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                                                Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                                                Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                                                Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                                                Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                                                Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                                                Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                                                Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                                                Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                                                Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                                                Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                                                Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                                                Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                                Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                                Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                                                Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                                                Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                                                Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                                                Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                                                Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                                                Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                                                Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                                                Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                                                Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                                                Binary Input 121 (use Object Identifier for RT)

                                                                Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                                                Binary Input 121 (use Object Identifier for FAU)

                                                                Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                                                Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                                                Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                                                Table 10 Diagnostics Binary Input (continued)

                                                                Object Identifier(a) Object Name Description

                                                                34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                Object Data Points and Diagnostic Data Points

                                                                Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                                                Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                                                Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                                                Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                                                Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                                                Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                                                Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                                                Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                                                Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                                                Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                                                Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                                                Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                                                Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                                                Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                                                Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                                                Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                                                Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                                                Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                                                Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                                                Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                                                Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                                                Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                                                Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                                                Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                                                Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                                                Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                                                (a) Object States Inactive = normal and Active = foreign language specific

                                                                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                                                Object Identifier(a) Object Name Description

                                                                Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                                Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                                                Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                                                Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                                                Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                                Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                                                Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                                                Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                                Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                                                Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                                                Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                                Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                                                Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                                                Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                                Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                                                Table 10 Diagnostics Binary Input (continued)

                                                                Object Identifier(a) Object Name Description

                                                                ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                                                Object Data Points and Diagnostic Data Points

                                                                Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                                                Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                                                Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                                                Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                                                Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                                                Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                                Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                                Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                                Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                                Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                                                Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                                                Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                                                Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                                Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                                                Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                                                Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                                                Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                                                Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                                                Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                                                Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                                                Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                                Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                                                Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                                Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                                                Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                                                Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                                                Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                                                Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                                                Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                                                Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                                                Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                                                Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                                                Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                                                Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                                                Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                                                Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                                                Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                                                Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                                                Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                                Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                                Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                                Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                                                Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                                                Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                                                Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                                                Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                                                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                Object Identifier(a) Object Name Description

                                                                36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                Object Data Points and Diagnostic Data Points

                                                                Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                                Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                                Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                                                Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                                                Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                                                Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                                Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                                                Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                                Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                                                Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                                                Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                                Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                                Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                                                Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                                                Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                                                Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                                                Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                                                Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                                                Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                                                Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                                                Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                                                Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                                                Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                                                Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                                                Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                                Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                                                Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                                Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                                                Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                                                Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                                                Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                                                Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                                                Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                                                Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                                                Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                                                Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                                                Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                                Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                                Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                                Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                                Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                                Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                                                Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                                                Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                                                Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                                Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                                                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                Object Identifier(a) Object Name Description

                                                                ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                                                Object Data Points and Diagnostic Data Points

                                                                Binary Output 16 Humidification Command Command the operating state of the humidification system

                                                                NC 3 HVAC-Advisory HVAC-Advisory

                                                                NC 1 HVAC-Critical HVAC-Critical

                                                                NC 4 HVAC-Information HVAC-Information

                                                                NC 2 HVAC-Service Required HVAC-Service Required

                                                                Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                                                Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                                                Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                                                Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                                Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                                Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                                                Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                                                Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                                                Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                                                Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                                                Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                                                Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                                                Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                                                Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                                                Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                                                Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                                                Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                                                Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                                                Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                                                Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                                                Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                                                Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                                                Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                                                Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                                                Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                                                Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                                                Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                                                Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                                                Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                                                Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                                                Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                                                Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                                                Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                                                Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                                                Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                                                Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                                                Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                                                Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                                                Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                                                Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                                                Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                                                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                Object Identifier(a) Object Name Description

                                                                38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                Object Data Points and Diagnostic Data Points

                                                                Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                                                Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                                                Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                                                Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                                                Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                                                Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                                                Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                                                Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                                                Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                                                Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                                                Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                                                Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                                                Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                                                Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                                                Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                                                Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                                                Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                                                Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                                                Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                                                Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                                Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                                Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                                Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                                                Binary Input 3 Unit Status Indicates the current state of the unit

                                                                Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                                Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                                                Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                                                Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                                Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                                Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                                Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                                                (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                                                Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                Object Identifier(a) Object Name Description

                                                                Table 12 Diagnostic Objects Sorted by Object Name

                                                                Object Identifier(a) Object Name ValueRange Description

                                                                BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                                                BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                                                ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                                                Object Data Points and Diagnostic Data Points

                                                                BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                                                BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                                                BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                                                BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                                                BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                                                BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                                                BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                                                BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                                                BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                                                BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                                                BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                                                BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                                                BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                                                BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                                                BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                                                BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                                                BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                                                BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                                                BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                                                BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                                                BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                                                BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                                                BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                                                BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                                                BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                                                BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                                BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                                BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                                BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                Object Identifier(a) Object Name ValueRange Description

                                                                40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                Object Data Points and Diagnostic Data Points

                                                                BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                                                BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                                                BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                                                BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                                                BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                                                BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                                                BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                                                BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                                                BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                                                BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                                                BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                                                BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                                                BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                                                BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                                                BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                                                BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                                                BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                                                BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                                                BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                                                BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                                                BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                                                BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                                                BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                                                BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                                BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                                BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                                                BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                                                BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                                                BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                Object Identifier(a) Object Name ValueRange Description

                                                                ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                                Object Data Points and Diagnostic Data Points

                                                                BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                                BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                                BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                                BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                                BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                                BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                                BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                                BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                                BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                                BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                                BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                                BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                                BI 121 (use Object Identifier for RT)

                                                                Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                                BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                                BI 58 (use Object Identifier for RT or CSC)

                                                                Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                                BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                                BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                                BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                                BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                                BI 31 (use Object Identifier for RT CSC)

                                                                Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                                BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                                BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                                BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                                BI 121 (use Object Identifier for FAU)

                                                                Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                                B1 31 (use Object Identifier for FAU)

                                                                Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                                BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                                BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                Object Identifier(a) Object Name ValueRange Description

                                                                42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                Object Data Points and Diagnostic Data Points

                                                                BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                                BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                                BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                                BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                                BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                                BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                                BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                                BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                                BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                                BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                                BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                                BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                                BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                                BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                                BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                                BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                                BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                                BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                                BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                                BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                                BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                                BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                                BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                                1 = active Diagnostic Vel Press Sensor (Rear)

                                                                BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                                Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                                BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                                BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                                BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                                BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                                BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                Object Identifier(a) Object Name ValueRange Description

                                                                ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                                Object Data Points and Diagnostic Data Points

                                                                BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                                BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                                BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                                BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                                BI 58 (use Object Identifier for FAU)

                                                                Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                                (a) BI=Binary Input

                                                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                Object Identifier(a) Object Name ValueRange Description

                                                                44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                Additional Resources

                                                                Additional Resources

                                                                Use the following documents and links as additional resources

                                                                bull Product support online

                                                                bull wwwbacnetorg

                                                                bull wwwbacnetassociationorg

                                                                bull wwwashraeorg

                                                                bull Tracer TU Help online

                                                                bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                                bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                                Note For further assistance contact your local Trane sales office

                                                                ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                                Glossary

                                                                A

                                                                ASHRAE

                                                                See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                                American Society of Heating Refrigeration and Air-

                                                                conditioning Engineers

                                                                An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                                BBACnettrade

                                                                See Building Automation Control network

                                                                BACnet interoperability building blocks

                                                                A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                                BACnet object

                                                                An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                                baud rate

                                                                The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                                BIBB

                                                                See BACnet interoperability building blocks

                                                                Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                                advocates BACnet protocol for use in system-level control devices

                                                                device

                                                                A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                                Device ID

                                                                The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                                Iinteroperability

                                                                The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                                Pprotocol

                                                                A set of rules (language) that governs the exchange of data over a digital communications system

                                                                S

                                                                stand-alone operation

                                                                Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                                wwwtranecom

                                                                For more information contact your local Trane office or e-mail us at comforttranecom

                                                                Literature Order Number ACC-SVP01B-EN

                                                                Date September 2009

                                                                Supersedes ACC-SVP01A-EN

                                                                Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                                • Table of Contents
                                                                • Overview
                                                                • Ordering Numbers
                                                                • BACnet Protocol
                                                                • BCI-I Configuration
                                                                  • Overview
                                                                  • Starting a Session of Tracer TU and Direct Connection
                                                                  • Reset to Factory Default
                                                                  • IP Units Configuration
                                                                  • BACnet Object Configuration
                                                                  • Change Baud Rate
                                                                  • Change Device ID
                                                                  • Stand-alone or BAS Operation
                                                                    • IntelliPak Control Configuration
                                                                    • BAS Unit Control
                                                                    • Periodic Update of BAS Values
                                                                    • BAS Communication Failure
                                                                      • InputOutput Commands and Calculations
                                                                        • System Control Command
                                                                        • Filter Timer Reset Command
                                                                        • Diagnostics Reset Command
                                                                        • Setpoint Calculations
                                                                        • Timestamp Configuration
                                                                            • BCI IntelliPak Rotary Switches and LEDs
                                                                              • Rotary Switches
                                                                              • LEDs Description Behavior and Troubleshooting
                                                                              • 24 Vac Measurement
                                                                              • Ground Measurements
                                                                                • BACnet Data Points and Configuration Property Definitions
                                                                                  • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                                    • Standardized Device Profile (Annex L)
                                                                                    • Interoperability Building Blocks (Annex K)
                                                                                    • Segmentation Capability
                                                                                    • Object Types
                                                                                      • BACnet Protocol
                                                                                        • Data Link Layer Options
                                                                                        • Device Address Binding
                                                                                        • Networking Options
                                                                                        • Character Sets
                                                                                            • Object Data Points and Diagnostic Data Points
                                                                                            • Additional Resources
                                                                                            • Glossary

                                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 33

                                                                  Object Data Points and Diagnostic Data Points

                                                                  Binary Input 78 Diagnostic VOM Mode A Active Diagnostic VOM Mode A Active

                                                                  Binary Input 79 Diagnostic VOM Mode B Active Diagnostic VOM Mode B Active

                                                                  Binary Input 80 Diagnostic VOM Mode C Active Diagnostic VOM Mode C Active

                                                                  Binary Input 81 Diagnostic VOM Mode D Active Diagnostic VOM Mode D Active

                                                                  Binary Input 82 Diagnostic VOM Mode E Active Diagnostic VOM Mode E Active

                                                                  Binary Input 83 Diagnostic CO2 Sensor Failure Diagnostic CO2 Sensor Failure

                                                                  Binary Input 84 Diagnostic VCM Aux Temp Sensor Failure Diagnostic VCM Aux Temp Sensor Failure

                                                                  Binary Input 85 Diagnostic Blocked Air Return Diagnostic Blocked Air Return

                                                                  Binary Input 86 (use Object Identifier for CSC FAU I-pak I RT)

                                                                  Diagnostic Velocity Press Sensor Fail Diagnostic Velocity Press Sensor Fail

                                                                  Binary Input 86 (use Object Identifier for RT I-pak II)

                                                                  Diagnostic Vel Press Sensor (Rear) Diagnostic Vel Press Sensor (Rear)

                                                                  Binary Input 87 Diagnostic VCM Communications Failure Diagnostic VCM Communications Failure

                                                                  Binary Input 88 Diagnostic WSM Communications Failure Diagnostic WSM Communications Failure

                                                                  Binary Input 89 Diagnostic Compressor Trip - Ckt 3 Diagnostic Compressor Trip - Ckt 3

                                                                  Binary Input 90 Diagnostic Compressor Trip - Ckt 4 Diagnostic Compressor Trip - Ckt 4

                                                                  Binary Input 91 Diagnostic Exh Fan VFD Bypass Enabled Diagnostic Exh Fan VFD Bypass Enabled

                                                                  Binary Input 92 Diagnostic Cond Temp Sensor Fail - Ckt3 Diagnostic Cond Temp Sensor Fail - Ckt3

                                                                  Binary Input 93 Diagnostic Cond Temp Sensor Fail - Ckt4 Diagnostic Cond Temp Sensor Fail - Ckt4

                                                                  Binary Input 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                                  Binary Input 95 Diagnostic WSM MA Temp Sensor Failure Diagnostic WSM MA Temp Sensor Failure

                                                                  Binary Input 96 Diagnostic Enter Water Temp Sensor Fail Diagnostic Enter Water Temp Sensor Fail

                                                                  Binary Input 97 Diagnostic Water Flow Failure Diagnostic Water Flow Failure

                                                                  Binary Input 98 Diagnostic Supply Fan VFD Bypass Enable Diagnostic Supply Fan VFD Bypass Enable

                                                                  Binary Input 99 Diagnostic High CO2 Level Diagnostic High CO2 Level

                                                                  Binary Input 100 Diagnostic Low Pressure Ctl Open - Ckt4 Diagnostic Low Pressure Ctl Open - Ckt4

                                                                  Binary Input 101 Diagnostic Low Pressure Ctl Open - Ckt3 Diagnostic Low Pressure Ctl Open - Ckt3

                                                                  Binary Input 102 Diagnostic Compressor Contact Fail-Ckt4 Diagnostic Compressor Contact Fail-Ckt4

                                                                  Binary Input 103 Diagnostic Compressor Contact Fail-Ckt3 Diagnostic Compressor Contact Fail-Ckt3

                                                                  Binary Input 104 Diagnostic Evap Temp Sensor Fail - Ckt4 Diagnostic Evap Temp Sensor Fail - Ckt4

                                                                  Binary Input 105 Diagnostic Evap Temp Sensor Fail - Ckt3 Diagnostic Evap Temp Sensor Fail - Ckt3

                                                                  Binary Input 106 Diagnostic RTM Zone Humidity Sensor Fail Diagnostic RTM Zone Humidity Sensor Fail

                                                                  Binary Input 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                                  Binary Input 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                                  Binary Input 111 Diagnostic Recovery Dirty Prefilter Diagnostic Recovery Dirty Prefilter

                                                                  Binary Input 112 Diagnostic Recovery Lvg RA Sensor Fail Diagnostic Recovery Lvg RA Sensor Fail

                                                                  Binary Input 113 Diagnostic Energy Recovery Wheel Fail Diagnostic Energy Recovery Wheel Fail

                                                                  Binary Input 114 Diagnostic Cond Sump Max Level Fail Diagnostic Cond Sump Max Level Fail

                                                                  Binary Input 115 Diagnostic Cond Sump Min Level Fail Diagnostic Cond Sump Min Level Fail

                                                                  Binary Input 116 Diagnostic Cond Water Pump Fail (man) Diagnostic Cond Water Pump Fail (man)

                                                                  Binary Input 117 Diagnostic Cond Water Pump Fail (auto) Diagnostic Cond Water Pump Fail (auto)

                                                                  Binary Input 118 Diagnostic Cond Water Temp Sensor Fail Diagnostic Cond Water Temp Sensor Fail

                                                                  Binary Input 119 Diagnostic Cond Sump Heater Fail (man) Diagnostic Cond Sump Heater Fail (man)

                                                                  Binary Input 120 Diagnostic GBAS 0-10 VDC Comm Failure Diagnostic GBAS 0-10 VDC Comm Failure

                                                                  Binary Input 121 (use Object Identifier for RT)

                                                                  Diagnostic Reheat Head Press High Diagnostic Reheat Head Press High

                                                                  Binary Input 121 (use Object Identifier for FAU)

                                                                  Diagnostic SA Drying Setpoint Failure Diagnostic SA Drying Setpoint Failure

                                                                  Binary Input 122 Diagnostic Insufficient Airflow for Dehumid Diagnostic Insufficient Airflow for Dehumid

                                                                  Binary Input 123 Diagnostic SA Reheat Setpoint Failure Diagnostic SA Reheat Setpoint Failure

                                                                  Table 10 Diagnostics Binary Input (continued)

                                                                  Object Identifier(a) Object Name Description

                                                                  34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                  Object Data Points and Diagnostic Data Points

                                                                  Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                                                  Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                                                  Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                                                  Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                                                  Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                                                  Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                                                  Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                                                  Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                                                  Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                                                  Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                                                  Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                                                  Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                                                  Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                                                  Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                                                  Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                                                  Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                                                  Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                                                  Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                                                  Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                                                  Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                                                  Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                                                  Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                                                  Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                                                  Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                                                  Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                                                  Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                                                  (a) Object States Inactive = normal and Active = foreign language specific

                                                                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                                                  Object Identifier(a) Object Name Description

                                                                  Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                                  Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                                                  Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                                                  Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                                                  Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                                  Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                                                  Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                                                  Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                                  Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                                                  Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                                                  Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                                  Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                                                  Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                                                  Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                                  Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                                                  Table 10 Diagnostics Binary Input (continued)

                                                                  Object Identifier(a) Object Name Description

                                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                                                  Object Data Points and Diagnostic Data Points

                                                                  Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                                                  Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                                                  Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                                                  Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                                                  Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                                                  Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                                  Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                                  Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                                  Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                                  Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                                                  Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                                                  Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                                                  Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                                  Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                                                  Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                                                  Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                                                  Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                                                  Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                                                  Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                                                  Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                                                  Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                                  Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                                                  Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                                  Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                                                  Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                                                  Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                                                  Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                                                  Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                                                  Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                                                  Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                                                  Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                                                  Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                                                  Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                                                  Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                                                  Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                                                  Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                                                  Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                                                  Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                                                  Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                                  Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                                  Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                                  Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                                                  Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                                                  Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                                                  Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                                                  Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                                                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                  Object Identifier(a) Object Name Description

                                                                  36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                  Object Data Points and Diagnostic Data Points

                                                                  Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                                  Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                                  Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                                                  Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                                                  Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                                                  Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                                  Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                                                  Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                                  Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                                                  Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                                                  Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                                  Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                                  Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                                                  Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                                                  Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                                                  Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                                                  Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                                                  Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                                                  Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                                                  Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                                                  Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                                                  Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                                                  Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                                                  Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                                                  Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                                  Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                                                  Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                                  Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                                                  Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                                                  Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                                                  Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                                                  Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                                                  Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                                                  Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                                                  Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                                                  Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                                                  Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                                  Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                                  Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                                  Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                                  Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                                  Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                                                  Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                                                  Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                                                  Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                                  Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                                                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                  Object Identifier(a) Object Name Description

                                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                                                  Object Data Points and Diagnostic Data Points

                                                                  Binary Output 16 Humidification Command Command the operating state of the humidification system

                                                                  NC 3 HVAC-Advisory HVAC-Advisory

                                                                  NC 1 HVAC-Critical HVAC-Critical

                                                                  NC 4 HVAC-Information HVAC-Information

                                                                  NC 2 HVAC-Service Required HVAC-Service Required

                                                                  Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                                                  Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                                                  Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                                                  Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                                  Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                                  Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                                                  Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                                                  Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                                                  Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                                                  Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                                                  Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                                                  Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                                                  Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                                                  Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                                                  Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                                                  Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                                                  Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                                                  Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                                                  Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                                                  Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                                                  Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                                                  Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                                                  Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                                                  Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                                                  Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                                                  Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                                                  Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                                                  Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                                                  Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                                                  Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                                                  Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                                                  Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                                                  Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                                                  Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                                                  Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                                                  Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                                                  Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                                                  Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                                                  Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                                                  Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                                                  Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                                                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                  Object Identifier(a) Object Name Description

                                                                  38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                  Object Data Points and Diagnostic Data Points

                                                                  Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                                                  Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                                                  Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                                                  Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                                                  Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                                                  Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                                                  Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                                                  Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                                                  Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                                                  Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                                                  Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                                                  Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                                                  Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                                                  Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                                                  Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                                                  Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                                                  Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                                                  Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                                                  Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                                                  Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                                  Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                                  Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                                  Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                                                  Binary Input 3 Unit Status Indicates the current state of the unit

                                                                  Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                                  Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                                                  Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                                                  Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                                  Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                                  Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                                  Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                                                  (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                                                  Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                  Object Identifier(a) Object Name Description

                                                                  Table 12 Diagnostic Objects Sorted by Object Name

                                                                  Object Identifier(a) Object Name ValueRange Description

                                                                  BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                                                  BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                                                  Object Data Points and Diagnostic Data Points

                                                                  BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                                                  BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                                                  BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                                                  BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                                                  BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                                                  BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                                                  BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                                                  BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                                                  BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                                                  BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                                                  BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                                                  BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                                                  BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                                                  BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                                                  BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                                                  BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                                                  BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                                                  BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                                                  BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                                                  BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                                                  BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                                                  BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                                                  BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                                                  BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                                                  BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                                                  BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                                  BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                                  BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                                  BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                  Object Identifier(a) Object Name ValueRange Description

                                                                  40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                  Object Data Points and Diagnostic Data Points

                                                                  BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                                                  BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                                                  BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                                                  BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                                                  BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                                                  BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                                                  BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                                                  BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                                                  BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                                                  BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                                                  BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                                                  BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                                                  BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                                                  BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                                                  BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                                                  BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                                                  BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                                                  BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                                                  BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                                                  BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                                                  BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                                                  BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                                                  BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                                                  BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                                  BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                                  BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                                                  BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                                                  BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                                                  BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                  Object Identifier(a) Object Name ValueRange Description

                                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                                  Object Data Points and Diagnostic Data Points

                                                                  BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                                  BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                                  BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                                  BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                                  BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                                  BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                                  BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                                  BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                                  BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                                  BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                                  BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                                  BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                                  BI 121 (use Object Identifier for RT)

                                                                  Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                                  BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                                  BI 58 (use Object Identifier for RT or CSC)

                                                                  Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                                  BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                                  BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                                  BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                                  BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                                  BI 31 (use Object Identifier for RT CSC)

                                                                  Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                                  BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                                  BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                  BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                  BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                                  BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                                  BI 121 (use Object Identifier for FAU)

                                                                  Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                                  B1 31 (use Object Identifier for FAU)

                                                                  Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                                  BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                                  BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                  Object Identifier(a) Object Name ValueRange Description

                                                                  42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                  Object Data Points and Diagnostic Data Points

                                                                  BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                                  BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                                  BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                                  BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                                  BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                                  BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                                  BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                                  BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                                  BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                                  BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                                  BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                                  BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                                  BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                                  BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                                  BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                                  BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                                  BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                                  BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                                  BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                                  BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                                  BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                                  BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                                  BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                                  1 = active Diagnostic Vel Press Sensor (Rear)

                                                                  BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                                  Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                                  BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                                  BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                                  BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                                  BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                                  BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                  Object Identifier(a) Object Name ValueRange Description

                                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                                  Object Data Points and Diagnostic Data Points

                                                                  BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                                  BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                                  BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                                  BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                                  BI 58 (use Object Identifier for FAU)

                                                                  Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                                  (a) BI=Binary Input

                                                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                  Object Identifier(a) Object Name ValueRange Description

                                                                  44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                  Additional Resources

                                                                  Additional Resources

                                                                  Use the following documents and links as additional resources

                                                                  bull Product support online

                                                                  bull wwwbacnetorg

                                                                  bull wwwbacnetassociationorg

                                                                  bull wwwashraeorg

                                                                  bull Tracer TU Help online

                                                                  bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                                  bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                                  Note For further assistance contact your local Trane sales office

                                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                                  Glossary

                                                                  A

                                                                  ASHRAE

                                                                  See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                                  American Society of Heating Refrigeration and Air-

                                                                  conditioning Engineers

                                                                  An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                                  BBACnettrade

                                                                  See Building Automation Control network

                                                                  BACnet interoperability building blocks

                                                                  A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                                  BACnet object

                                                                  An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                                  baud rate

                                                                  The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                                  BIBB

                                                                  See BACnet interoperability building blocks

                                                                  Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                                  advocates BACnet protocol for use in system-level control devices

                                                                  device

                                                                  A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                                  Device ID

                                                                  The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                                  Iinteroperability

                                                                  The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                                  Pprotocol

                                                                  A set of rules (language) that governs the exchange of data over a digital communications system

                                                                  S

                                                                  stand-alone operation

                                                                  Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                                  wwwtranecom

                                                                  For more information contact your local Trane office or e-mail us at comforttranecom

                                                                  Literature Order Number ACC-SVP01B-EN

                                                                  Date September 2009

                                                                  Supersedes ACC-SVP01A-EN

                                                                  Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                                  • Table of Contents
                                                                  • Overview
                                                                  • Ordering Numbers
                                                                  • BACnet Protocol
                                                                  • BCI-I Configuration
                                                                    • Overview
                                                                    • Starting a Session of Tracer TU and Direct Connection
                                                                    • Reset to Factory Default
                                                                    • IP Units Configuration
                                                                    • BACnet Object Configuration
                                                                    • Change Baud Rate
                                                                    • Change Device ID
                                                                    • Stand-alone or BAS Operation
                                                                      • IntelliPak Control Configuration
                                                                      • BAS Unit Control
                                                                      • Periodic Update of BAS Values
                                                                      • BAS Communication Failure
                                                                        • InputOutput Commands and Calculations
                                                                          • System Control Command
                                                                          • Filter Timer Reset Command
                                                                          • Diagnostics Reset Command
                                                                          • Setpoint Calculations
                                                                          • Timestamp Configuration
                                                                              • BCI IntelliPak Rotary Switches and LEDs
                                                                                • Rotary Switches
                                                                                • LEDs Description Behavior and Troubleshooting
                                                                                • 24 Vac Measurement
                                                                                • Ground Measurements
                                                                                  • BACnet Data Points and Configuration Property Definitions
                                                                                    • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                                      • Standardized Device Profile (Annex L)
                                                                                      • Interoperability Building Blocks (Annex K)
                                                                                      • Segmentation Capability
                                                                                      • Object Types
                                                                                        • BACnet Protocol
                                                                                          • Data Link Layer Options
                                                                                          • Device Address Binding
                                                                                          • Networking Options
                                                                                          • Character Sets
                                                                                              • Object Data Points and Diagnostic Data Points
                                                                                              • Additional Resources
                                                                                              • Glossary

                                                                    34 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                    Object Data Points and Diagnostic Data Points

                                                                    Binary Input 124 Diagnostic Unocc Dehumid Setpoint Fail Diagnostic Unocc Dehumid Setpoint Fail

                                                                    Binary Input 125 Diagnostic Occ Dehumid Setpoint Failure Diagnostic Occ Dehumid Setpoint Failure

                                                                    Binary Input 126 Diagnostic Unocc Humid Setpoint Fail Diagnostic Unocc Humid Setpoint Fail

                                                                    Binary Input 127 Diagnostic Occ Humid Setpoint Failure Diagnostic Occ Humid Setpoint Failure

                                                                    Binary Input 128 Diagnostic MDM Communications Failure Diagnostic MDM Communications Failure

                                                                    Binary Input 129 Diagnostic Dirty Final Filter Diagnostic Dirty Final Filter

                                                                    Binary Input 130 Diagnostic Vel Press Sensor (Front) Fail Diagnostic Vel Press Sensor (Front) Fail

                                                                    Binary Input 131 Diagnostic High Superheat - Ckt 1 Diagnostic High Superheat - Ckt 1

                                                                    Binary Input 132 Diagnostic Low Refrigerant Charge - Ckt 1 Diagnostic Low Refrigerant Charge - Ckt 1

                                                                    Binary Input 133 Diagnostic High Superheat - Ckt 2 Diagnostic High Superheat - Ckt 2

                                                                    Binary Input 134 Diagnostic Low Refrigerant Charge - Ckt 2 Diagnostic Low Refrigerant Charge - Ckt 2

                                                                    Binary Input 139 Diagnostic MPM Communications Failure Diagnostic MPM Communications Failure

                                                                    Binary Input 140 Diagnostic TPM Communications Failure Diagnostic TPM Communications Failure

                                                                    Binary Input 141 Diagnostic Return Plenum Press Sensor Diagnostic Return Plenum Press Sensor

                                                                    Binary Input 142 Diagnostic Return Press High Limit (Man) Diagnostic Return Press High Limit (Man)

                                                                    Binary Input 143 Diagnostic Return Press High Limit (Auto) Diagnostic Return Press High Limit (Auto)

                                                                    Binary Input 144 Diagnostic Cond Press Sensor Fail Ckt 2 Diagnostic Cond Press Sensor Fail Ckt 2

                                                                    Binary Input 145 Diagnostic Cond Press Sensor Fail Ckt 1 Diagnostic Cond Press Sensor Fail Ckt 1

                                                                    Binary Input 146 Diagnostic Invalid Unit Configuration Diagnostic Invalid Unit Configuration

                                                                    Binary Input 147 Diagnostic Maintenance Required Diagnostic Maintenance Required

                                                                    Binary Input 148 Diagnostic Unit Communications Failure Diagnostic Unit Communications Failure

                                                                    Binary Input 149 Diagnostic Unit Stopped at Local HI Diagnostic Unit Stopped at Local HI

                                                                    Binary Input 150 Diagnostic Unit Stopped at Remote HI Diagnostic Unit Stopped at Remote HI

                                                                    Binary Input 151 Diagnostic RTM External Stop Diagnostic RTM External Stop

                                                                    Binary Input 166 Diagnostic Stop Status Diagnostic Stop Status

                                                                    Binary Input 233 Diagnostic Sump Min Level Cycling (man) Diagnostic Sump Min Level Cycling (man)

                                                                    (a) Object States Inactive = normal and Active = foreign language specific

                                                                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)

                                                                    Object Identifier(a) Object Name Description

                                                                    Binary Input 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit

                                                                    Multi-State Output 8 Application Mode Request BAS Command the unit to a specific application mode

                                                                    Multi-State Input 19 Application Mode Status Indicates the current application mode of the equipment

                                                                    Analog Input 80 Cabinet Style Describes the cabinet style of the unit

                                                                    Binary Input 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic

                                                                    Analog Input 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized

                                                                    Multi-State Input 10 Condenser Type General description of the equipment condenser system

                                                                    Binary Input 243 Condenser Water Drain Status Indicates the status of the condenser water drain

                                                                    Analog Input 35 Condenser Water Entering Temperature The temperature of the water entering the condenser

                                                                    Multi-State Output 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication

                                                                    Binary Input 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system

                                                                    Analog Input 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control

                                                                    Analog Input 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor

                                                                    Binary Input 24 Condenser Water Pump Status Indicates the status of the condenser water system pump

                                                                    Analog Input 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1

                                                                    Table 10 Diagnostics Binary Input (continued)

                                                                    Object Identifier(a) Object Name Description

                                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                                                    Object Data Points and Diagnostic Data Points

                                                                    Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                                                    Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                                                    Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                                                    Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                                                    Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                                                    Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                                    Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                                    Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                                    Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                                    Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                                                    Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                                                    Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                                                    Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                                    Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                                                    Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                                                    Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                                                    Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                                                    Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                                                    Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                                                    Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                                                    Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                                    Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                                                    Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                                    Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                                                    Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                                                    Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                                                    Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                                                    Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                                                    Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                                                    Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                                                    Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                                                    Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                                                    Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                                                    Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                                                    Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                                                    Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                                                    Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                                                    Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                                                    Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                                    Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                                    Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                                    Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                                                    Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                                                    Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                                                    Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                                                    Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                                                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                    Object Identifier(a) Object Name Description

                                                                    36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                    Object Data Points and Diagnostic Data Points

                                                                    Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                                    Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                                    Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                                                    Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                                                    Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                                                    Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                                    Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                                                    Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                                    Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                                                    Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                                                    Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                                    Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                                    Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                                                    Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                                                    Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                                                    Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                                                    Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                                                    Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                                                    Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                                                    Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                                                    Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                                                    Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                                                    Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                                                    Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                                                    Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                                    Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                                                    Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                                    Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                                                    Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                                                    Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                                                    Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                                                    Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                                                    Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                                                    Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                                                    Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                                                    Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                                                    Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                                    Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                                    Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                                    Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                                    Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                                    Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                                                    Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                                                    Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                                                    Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                                    Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                                                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                    Object Identifier(a) Object Name Description

                                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                                                    Object Data Points and Diagnostic Data Points

                                                                    Binary Output 16 Humidification Command Command the operating state of the humidification system

                                                                    NC 3 HVAC-Advisory HVAC-Advisory

                                                                    NC 1 HVAC-Critical HVAC-Critical

                                                                    NC 4 HVAC-Information HVAC-Information

                                                                    NC 2 HVAC-Service Required HVAC-Service Required

                                                                    Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                                                    Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                                                    Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                                                    Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                                    Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                                    Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                                                    Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                                                    Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                                                    Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                                                    Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                                                    Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                                                    Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                                                    Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                                                    Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                                                    Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                                                    Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                                                    Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                                                    Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                                                    Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                                                    Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                                                    Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                                                    Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                                                    Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                                                    Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                                                    Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                                                    Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                                                    Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                                                    Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                                                    Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                                                    Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                                                    Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                                                    Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                                                    Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                                                    Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                                                    Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                                                    Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                                                    Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                                                    Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                                                    Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                                                    Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                                                    Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                                                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                    Object Identifier(a) Object Name Description

                                                                    38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                    Object Data Points and Diagnostic Data Points

                                                                    Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                                                    Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                                                    Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                                                    Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                                                    Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                                                    Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                                                    Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                                                    Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                                                    Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                                                    Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                                                    Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                                                    Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                                                    Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                                                    Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                                                    Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                                                    Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                                                    Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                                                    Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                                                    Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                                                    Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                                    Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                                    Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                                    Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                                                    Binary Input 3 Unit Status Indicates the current state of the unit

                                                                    Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                                    Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                                                    Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                                                    Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                                    Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                                    Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                                    Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                                                    (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                                                    Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                    Object Identifier(a) Object Name Description

                                                                    Table 12 Diagnostic Objects Sorted by Object Name

                                                                    Object Identifier(a) Object Name ValueRange Description

                                                                    BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                                                    BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                                                    Object Data Points and Diagnostic Data Points

                                                                    BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                                                    BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                                                    BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                                                    BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                                                    BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                                                    BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                                                    BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                                                    BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                                                    BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                                                    BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                                                    BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                                                    BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                                                    BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                                                    BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                                                    BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                                                    BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                                                    BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                                                    BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                                                    BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                                                    BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                                                    BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                                                    BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                                                    BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                                                    BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                                                    BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                                                    BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                                    BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                                    BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                                    BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                                                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                    Object Identifier(a) Object Name ValueRange Description

                                                                    40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                    Object Data Points and Diagnostic Data Points

                                                                    BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                                                    BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                                                    BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                                                    BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                                                    BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                                                    BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                                                    BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                                                    BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                                                    BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                                                    BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                                                    BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                                                    BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                                                    BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                                                    BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                                                    BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                                                    BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                                                    BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                                                    BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                                                    BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                                                    BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                                                    BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                                                    BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                                                    BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                                                    BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                                    BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                                    BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                                                    BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                                                    BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                                                    BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                                                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                    Object Identifier(a) Object Name ValueRange Description

                                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                                    Object Data Points and Diagnostic Data Points

                                                                    BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                                    BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                                    BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                                    BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                                    BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                                    BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                                    BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                                    BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                                    BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                                    BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                                    BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                                    BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                                    BI 121 (use Object Identifier for RT)

                                                                    Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                                    BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                                    BI 58 (use Object Identifier for RT or CSC)

                                                                    Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                                    BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                                    BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                                    BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                                    BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                                    BI 31 (use Object Identifier for RT CSC)

                                                                    Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                                    BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                                    BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                    BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                    BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                                    BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                                    BI 121 (use Object Identifier for FAU)

                                                                    Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                                    B1 31 (use Object Identifier for FAU)

                                                                    Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                                    BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                                    BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                    Object Identifier(a) Object Name ValueRange Description

                                                                    42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                    Object Data Points and Diagnostic Data Points

                                                                    BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                                    BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                                    BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                                    BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                                    BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                                    BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                                    BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                                    BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                                    BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                                    BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                                    BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                                    BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                                    BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                                    BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                                    BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                                    BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                                    BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                                    BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                                    BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                                    BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                                    BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                                    BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                                    BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                                    1 = active Diagnostic Vel Press Sensor (Rear)

                                                                    BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                                    Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                                    BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                                    BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                                    BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                                    BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                                    BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                    Object Identifier(a) Object Name ValueRange Description

                                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                                    Object Data Points and Diagnostic Data Points

                                                                    BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                                    BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                                    BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                                    BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                                    BI 58 (use Object Identifier for FAU)

                                                                    Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                                    (a) BI=Binary Input

                                                                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                    Object Identifier(a) Object Name ValueRange Description

                                                                    44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                    Additional Resources

                                                                    Additional Resources

                                                                    Use the following documents and links as additional resources

                                                                    bull Product support online

                                                                    bull wwwbacnetorg

                                                                    bull wwwbacnetassociationorg

                                                                    bull wwwashraeorg

                                                                    bull Tracer TU Help online

                                                                    bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                                    bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                                    Note For further assistance contact your local Trane sales office

                                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                                    Glossary

                                                                    A

                                                                    ASHRAE

                                                                    See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                                    American Society of Heating Refrigeration and Air-

                                                                    conditioning Engineers

                                                                    An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                                    BBACnettrade

                                                                    See Building Automation Control network

                                                                    BACnet interoperability building blocks

                                                                    A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                                    BACnet object

                                                                    An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                                    baud rate

                                                                    The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                                    BIBB

                                                                    See BACnet interoperability building blocks

                                                                    Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                                    advocates BACnet protocol for use in system-level control devices

                                                                    device

                                                                    A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                                    Device ID

                                                                    The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                                    Iinteroperability

                                                                    The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                                    Pprotocol

                                                                    A set of rules (language) that governs the exchange of data over a digital communications system

                                                                    S

                                                                    stand-alone operation

                                                                    Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                                    wwwtranecom

                                                                    For more information contact your local Trane office or e-mail us at comforttranecom

                                                                    Literature Order Number ACC-SVP01B-EN

                                                                    Date September 2009

                                                                    Supersedes ACC-SVP01A-EN

                                                                    Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                                    • Table of Contents
                                                                    • Overview
                                                                    • Ordering Numbers
                                                                    • BACnet Protocol
                                                                    • BCI-I Configuration
                                                                      • Overview
                                                                      • Starting a Session of Tracer TU and Direct Connection
                                                                      • Reset to Factory Default
                                                                      • IP Units Configuration
                                                                      • BACnet Object Configuration
                                                                      • Change Baud Rate
                                                                      • Change Device ID
                                                                      • Stand-alone or BAS Operation
                                                                        • IntelliPak Control Configuration
                                                                        • BAS Unit Control
                                                                        • Periodic Update of BAS Values
                                                                        • BAS Communication Failure
                                                                          • InputOutput Commands and Calculations
                                                                            • System Control Command
                                                                            • Filter Timer Reset Command
                                                                            • Diagnostics Reset Command
                                                                            • Setpoint Calculations
                                                                            • Timestamp Configuration
                                                                                • BCI IntelliPak Rotary Switches and LEDs
                                                                                  • Rotary Switches
                                                                                  • LEDs Description Behavior and Troubleshooting
                                                                                  • 24 Vac Measurement
                                                                                  • Ground Measurements
                                                                                    • BACnet Data Points and Configuration Property Definitions
                                                                                      • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                                        • Standardized Device Profile (Annex L)
                                                                                        • Interoperability Building Blocks (Annex K)
                                                                                        • Segmentation Capability
                                                                                        • Object Types
                                                                                          • BACnet Protocol
                                                                                            • Data Link Layer Options
                                                                                            • Device Address Binding
                                                                                            • Networking Options
                                                                                            • Character Sets
                                                                                                • Object Data Points and Diagnostic Data Points
                                                                                                • Additional Resources
                                                                                                • Glossary

                                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 35

                                                                      Object Data Points and Diagnostic Data Points

                                                                      Analog Input 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2

                                                                      Analog Input 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3

                                                                      Analog Input 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4

                                                                      Analog Output 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value

                                                                      Binary Output 6 Cool Lockout Command Command the unit to prevent cooling operation

                                                                      Multi-State Input 25 Cool Output 1 Indicates the commanded state of cooling output 1

                                                                      Multi-State Input 26 Cool Output 2 Indicates the commanded state of cooling output 2

                                                                      Multi-State Input 27 Cool Output 3 Indicates the commanded state of cooling output 3

                                                                      Multi-State Input 28 Cool Output 4 Indicates the commanded state of cooling output 4

                                                                      Analog Input 81 Cool Type Describes the cooling type installed in the unit

                                                                      Analog Input 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized

                                                                      Multi-State Input 17 Cooling Reset Type Status Indicates the type of cooling reset

                                                                      Multi-State Input 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint

                                                                      Analog Input 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode

                                                                      Analog Input 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint

                                                                      Analog Input 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode

                                                                      Analog Output 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint

                                                                      Analog Input 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized

                                                                      Binary Output 15 Dehumidification Command Command the operating state of the dehumidification system

                                                                      Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control

                                                                      Binary Input 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode

                                                                      Binary Output 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics

                                                                      Binary Input 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown

                                                                      Analog Output 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value

                                                                      Analog Output 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value

                                                                      Analog Input 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control

                                                                      Analog Output 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value

                                                                      Analog Input 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint

                                                                      Analog Output 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value

                                                                      Analog Input 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control

                                                                      Analog Output 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value

                                                                      Analog Input 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit

                                                                      Analog Input 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control

                                                                      Analog Input 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control

                                                                      Analog Output 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value

                                                                      Analog Input 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor

                                                                      Analog Input 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control

                                                                      Analog Output 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value

                                                                      Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                                      Multi-State Output 1 Economizer Airside Enable BAS Command the state of the airside economizer system

                                                                      Binary Input 22 Economizer Airside Enable Status Indicates the status of the airside economizer system

                                                                      Multi-State Input 15 Economizer Decision Method Unit method to determine when the economizer system is enabled

                                                                      Binary Output 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation

                                                                      Analog Input 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize

                                                                      Analog Output 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value

                                                                      Analog Input 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint

                                                                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                      Object Identifier(a) Object Name Description

                                                                      36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                      Object Data Points and Diagnostic Data Points

                                                                      Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                                      Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                                      Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                                                      Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                                                      Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                                                      Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                                      Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                                                      Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                                      Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                                                      Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                                                      Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                                      Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                                      Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                                                      Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                                                      Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                                                      Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                                                      Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                                                      Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                                                      Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                                                      Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                                                      Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                                                      Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                                                      Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                                                      Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                                                      Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                                      Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                                                      Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                                      Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                                                      Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                                                      Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                                                      Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                                                      Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                                                      Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                                                      Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                                                      Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                                                      Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                                                      Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                                      Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                                      Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                                      Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                                      Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                                      Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                                                      Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                                                      Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                                                      Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                                      Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                                                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                      Object Identifier(a) Object Name Description

                                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                                                      Object Data Points and Diagnostic Data Points

                                                                      Binary Output 16 Humidification Command Command the operating state of the humidification system

                                                                      NC 3 HVAC-Advisory HVAC-Advisory

                                                                      NC 1 HVAC-Critical HVAC-Critical

                                                                      NC 4 HVAC-Information HVAC-Information

                                                                      NC 2 HVAC-Service Required HVAC-Service Required

                                                                      Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                                                      Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                                                      Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                                                      Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                                      Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                                      Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                                                      Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                                                      Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                                                      Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                                                      Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                                                      Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                                                      Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                                                      Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                                                      Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                                                      Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                                                      Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                                                      Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                                                      Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                                                      Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                                                      Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                                                      Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                                                      Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                                                      Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                                                      Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                                                      Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                                                      Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                                                      Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                                                      Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                                                      Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                                                      Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                                                      Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                                                      Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                                                      Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                                                      Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                                                      Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                                                      Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                                                      Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                                                      Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                                                      Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                                                      Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                                                      Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                                                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                      Object Identifier(a) Object Name Description

                                                                      38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                      Object Data Points and Diagnostic Data Points

                                                                      Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                                                      Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                                                      Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                                                      Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                                                      Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                                                      Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                                                      Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                                                      Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                                                      Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                                                      Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                                                      Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                                                      Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                                                      Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                                                      Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                                                      Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                                                      Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                                                      Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                                                      Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                                                      Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                                                      Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                                      Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                                      Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                                      Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                                                      Binary Input 3 Unit Status Indicates the current state of the unit

                                                                      Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                                      Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                                                      Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                                                      Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                                      Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                                      Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                                      Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                                                      (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                                                      Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                      Object Identifier(a) Object Name Description

                                                                      Table 12 Diagnostic Objects Sorted by Object Name

                                                                      Object Identifier(a) Object Name ValueRange Description

                                                                      BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                                                      BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                                                      Object Data Points and Diagnostic Data Points

                                                                      BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                                                      BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                                                      BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                                                      BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                                                      BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                                                      BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                                                      BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                                                      BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                                                      BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                                                      BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                                                      BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                                                      BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                                                      BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                                                      BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                                                      BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                                                      BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                                                      BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                                                      BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                                                      BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                                                      BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                                                      BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                                                      BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                                                      BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                                                      BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                                                      BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                                                      BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                                      BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                                      BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                                      BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                                                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                      Object Identifier(a) Object Name ValueRange Description

                                                                      40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                      Object Data Points and Diagnostic Data Points

                                                                      BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                                                      BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                                                      BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                                                      BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                                                      BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                                                      BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                                                      BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                                                      BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                                                      BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                                                      BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                                                      BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                                                      BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                                                      BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                                                      BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                                                      BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                                                      BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                                                      BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                                                      BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                                                      BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                                                      BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                                                      BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                                                      BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                                                      BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                                                      BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                                      BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                                      BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                                                      BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                                                      BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                                                      BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                                                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                      Object Identifier(a) Object Name ValueRange Description

                                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                                      Object Data Points and Diagnostic Data Points

                                                                      BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                                      BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                                      BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                                      BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                                      BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                                      BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                                      BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                                      BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                                      BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                                      BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                                      BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                                      BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                                      BI 121 (use Object Identifier for RT)

                                                                      Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                                      BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                                      BI 58 (use Object Identifier for RT or CSC)

                                                                      Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                                      BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                                      BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                                      BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                                      BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                                      BI 31 (use Object Identifier for RT CSC)

                                                                      Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                                      BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                                      BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                      BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                      BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                                      BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                                      BI 121 (use Object Identifier for FAU)

                                                                      Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                                      B1 31 (use Object Identifier for FAU)

                                                                      Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                                      BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                                      BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                      Object Identifier(a) Object Name ValueRange Description

                                                                      42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                      Object Data Points and Diagnostic Data Points

                                                                      BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                                      BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                                      BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                                      BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                                      BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                                      BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                                      BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                                      BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                                      BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                                      BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                                      BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                                      BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                                      BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                                      BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                                      BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                                      BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                                      BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                                      BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                                      BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                                      BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                                      BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                                      BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                                      BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                                      1 = active Diagnostic Vel Press Sensor (Rear)

                                                                      BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                                      Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                                      BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                                      BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                                      BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                                      BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                                      BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                      Object Identifier(a) Object Name ValueRange Description

                                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                                      Object Data Points and Diagnostic Data Points

                                                                      BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                                      BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                                      BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                                      BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                                      BI 58 (use Object Identifier for FAU)

                                                                      Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                                      (a) BI=Binary Input

                                                                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                      Object Identifier(a) Object Name ValueRange Description

                                                                      44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                      Additional Resources

                                                                      Additional Resources

                                                                      Use the following documents and links as additional resources

                                                                      bull Product support online

                                                                      bull wwwbacnetorg

                                                                      bull wwwbacnetassociationorg

                                                                      bull wwwashraeorg

                                                                      bull Tracer TU Help online

                                                                      bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                                      bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                                      Note For further assistance contact your local Trane sales office

                                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                                      Glossary

                                                                      A

                                                                      ASHRAE

                                                                      See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                                      American Society of Heating Refrigeration and Air-

                                                                      conditioning Engineers

                                                                      An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                                      BBACnettrade

                                                                      See Building Automation Control network

                                                                      BACnet interoperability building blocks

                                                                      A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                                      BACnet object

                                                                      An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                                      baud rate

                                                                      The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                                      BIBB

                                                                      See BACnet interoperability building blocks

                                                                      Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                                      advocates BACnet protocol for use in system-level control devices

                                                                      device

                                                                      A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                                      Device ID

                                                                      The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                                      Iinteroperability

                                                                      The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                                      Pprotocol

                                                                      A set of rules (language) that governs the exchange of data over a digital communications system

                                                                      S

                                                                      stand-alone operation

                                                                      Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                                      wwwtranecom

                                                                      For more information contact your local Trane office or e-mail us at comforttranecom

                                                                      Literature Order Number ACC-SVP01B-EN

                                                                      Date September 2009

                                                                      Supersedes ACC-SVP01A-EN

                                                                      Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                                      • Table of Contents
                                                                      • Overview
                                                                      • Ordering Numbers
                                                                      • BACnet Protocol
                                                                      • BCI-I Configuration
                                                                        • Overview
                                                                        • Starting a Session of Tracer TU and Direct Connection
                                                                        • Reset to Factory Default
                                                                        • IP Units Configuration
                                                                        • BACnet Object Configuration
                                                                        • Change Baud Rate
                                                                        • Change Device ID
                                                                        • Stand-alone or BAS Operation
                                                                          • IntelliPak Control Configuration
                                                                          • BAS Unit Control
                                                                          • Periodic Update of BAS Values
                                                                          • BAS Communication Failure
                                                                            • InputOutput Commands and Calculations
                                                                              • System Control Command
                                                                              • Filter Timer Reset Command
                                                                              • Diagnostics Reset Command
                                                                              • Setpoint Calculations
                                                                              • Timestamp Configuration
                                                                                  • BCI IntelliPak Rotary Switches and LEDs
                                                                                    • Rotary Switches
                                                                                    • LEDs Description Behavior and Troubleshooting
                                                                                    • 24 Vac Measurement
                                                                                    • Ground Measurements
                                                                                      • BACnet Data Points and Configuration Property Definitions
                                                                                        • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                                          • Standardized Device Profile (Annex L)
                                                                                          • Interoperability Building Blocks (Annex K)
                                                                                          • Segmentation Capability
                                                                                          • Object Types
                                                                                            • BACnet Protocol
                                                                                              • Data Link Layer Options
                                                                                              • Device Address Binding
                                                                                              • Networking Options
                                                                                              • Character Sets
                                                                                                  • Object Data Points and Diagnostic Data Points
                                                                                                  • Additional Resources
                                                                                                  • Glossary

                                                                        36 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                        Object Data Points and Diagnostic Data Points

                                                                        Multi-State Input 44 Economizer System Status Indicates the operating state of the waterside economizer system

                                                                        Multi-State Input 9 Economizer Type General description of the equipment economizer system

                                                                        Multi-State Output 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system

                                                                        Analog Input 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used

                                                                        Analog Input 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used

                                                                        Multi-State Output 2 Emergency Override BAS Command the unit into an emergency mode of operation

                                                                        Analog Input 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position

                                                                        Binary Input 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function

                                                                        Analog Input 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature

                                                                        Analog Input 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position

                                                                        Binary Input 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function

                                                                        Binary Input 27 Energy Recovery Status Indicates the status of the energy recover system

                                                                        Analog Input 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1

                                                                        Analog Input 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2

                                                                        Binary Input 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1

                                                                        Binary Input 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2

                                                                        Binary Input 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3

                                                                        Binary Input 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4

                                                                        Analog Input 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1

                                                                        Analog Input 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2

                                                                        Analog Input 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3

                                                                        Analog Input 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4

                                                                        Analog Input 9 Exhaust Damper Position Status Indicates the unit exhaust damper position

                                                                        Analog Input 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence

                                                                        Multi-State Input 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on

                                                                        Analog Input 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed

                                                                        Multi-State Input 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan

                                                                        Analog Input 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit

                                                                        Analog Input 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter

                                                                        Analog Value 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation

                                                                        Binary Output 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours

                                                                        Multi-State Input 36 Final Filter Status Indicates the final filter media state

                                                                        Analog Input 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint

                                                                        Analog Output 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value

                                                                        Binary Output 5 Heat Lockout Command Command the unit to prevent heating operation

                                                                        Binary Output 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode

                                                                        Multi-State Input 29 Heat Output 1 Indicates the commanded state of heating output 1

                                                                        Multi-State Input 30 Heat Output 2 Indicates the commanded state of heating output 2

                                                                        Multi-State Input 31 Heat Output 3 Indicates the commanded state of heating output 3

                                                                        Multi-State Input 32 Heat Output 4 Indicates the commanded state of heating output 4

                                                                        Multi-State Input 33 Heat Output 5 Indicates the commanded state of heating output 5

                                                                        Analog Input 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized

                                                                        Analog Input 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized

                                                                        Multi-State Input 18 Heating Reset Type Status Indicates the type of heating reset

                                                                        Multi-State Input 23 Heating Setpoint Source Indicates the source of the space heating setpoint

                                                                        Analog Input 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized

                                                                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                        Object Identifier(a) Object Name Description

                                                                        ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                                                        Object Data Points and Diagnostic Data Points

                                                                        Binary Output 16 Humidification Command Command the operating state of the humidification system

                                                                        NC 3 HVAC-Advisory HVAC-Advisory

                                                                        NC 1 HVAC-Critical HVAC-Critical

                                                                        NC 4 HVAC-Information HVAC-Information

                                                                        NC 2 HVAC-Service Required HVAC-Service Required

                                                                        Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                                                        Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                                                        Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                                                        Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                                        Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                                        Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                                                        Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                                                        Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                                                        Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                                                        Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                                                        Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                                                        Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                                                        Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                                                        Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                                                        Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                                                        Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                                                        Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                                                        Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                                                        Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                                                        Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                                                        Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                                                        Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                                                        Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                                                        Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                                                        Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                                                        Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                                                        Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                                                        Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                                                        Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                                                        Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                                                        Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                                                        Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                                                        Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                                                        Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                                                        Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                                                        Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                                                        Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                                                        Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                                                        Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                                                        Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                                                        Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                                                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                        Object Identifier(a) Object Name Description

                                                                        38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                        Object Data Points and Diagnostic Data Points

                                                                        Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                                                        Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                                                        Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                                                        Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                                                        Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                                                        Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                                                        Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                                                        Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                                                        Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                                                        Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                                                        Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                                                        Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                                                        Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                                                        Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                                                        Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                                                        Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                                                        Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                                                        Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                                                        Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                                                        Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                                        Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                                        Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                                        Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                                                        Binary Input 3 Unit Status Indicates the current state of the unit

                                                                        Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                                        Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                                                        Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                                                        Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                                        Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                                        Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                                        Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                                                        (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                                                        Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                        Object Identifier(a) Object Name Description

                                                                        Table 12 Diagnostic Objects Sorted by Object Name

                                                                        Object Identifier(a) Object Name ValueRange Description

                                                                        BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                                                        BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                                                        ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                                                        Object Data Points and Diagnostic Data Points

                                                                        BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                                                        BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                                                        BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                                                        BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                                                        BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                                                        BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                                                        BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                                                        BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                                                        BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                                                        BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                                                        BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                                                        BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                                                        BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                                                        BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                                                        BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                                                        BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                                                        BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                                                        BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                                                        BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                                                        BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                                                        BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                                                        BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                                                        BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                                                        BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                                                        BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                                                        BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                                        BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                                        BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                                        BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                                                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                        Object Identifier(a) Object Name ValueRange Description

                                                                        40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                        Object Data Points and Diagnostic Data Points

                                                                        BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                                                        BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                                                        BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                                                        BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                                                        BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                                                        BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                                                        BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                                                        BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                                                        BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                                                        BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                                                        BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                                                        BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                                                        BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                                                        BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                                                        BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                                                        BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                                                        BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                                                        BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                                                        BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                                                        BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                                                        BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                                                        BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                                                        BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                                                        BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                                        BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                                        BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                                                        BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                                                        BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                                                        BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                                                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                        Object Identifier(a) Object Name ValueRange Description

                                                                        ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                                        Object Data Points and Diagnostic Data Points

                                                                        BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                                        BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                                        BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                                        BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                                        BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                                        BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                                        BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                                        BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                                        BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                                        BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                                        BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                                        BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                                        BI 121 (use Object Identifier for RT)

                                                                        Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                                        BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                                        BI 58 (use Object Identifier for RT or CSC)

                                                                        Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                                        BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                                        BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                                        BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                                        BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                                        BI 31 (use Object Identifier for RT CSC)

                                                                        Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                                        BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                                        BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                        BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                        BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                                        BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                                        BI 121 (use Object Identifier for FAU)

                                                                        Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                                        B1 31 (use Object Identifier for FAU)

                                                                        Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                                        BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                                        BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                        Object Identifier(a) Object Name ValueRange Description

                                                                        42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                        Object Data Points and Diagnostic Data Points

                                                                        BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                                        BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                                        BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                                        BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                                        BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                                        BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                                        BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                                        BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                                        BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                                        BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                                        BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                                        BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                                        BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                                        BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                                        BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                                        BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                                        BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                                        BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                                        BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                                        BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                                        BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                                        BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                                        BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                                        1 = active Diagnostic Vel Press Sensor (Rear)

                                                                        BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                                        Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                                        BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                                        BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                                        BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                                        BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                                        BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                        Object Identifier(a) Object Name ValueRange Description

                                                                        ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                                        Object Data Points and Diagnostic Data Points

                                                                        BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                                        BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                                        BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                                        BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                                        BI 58 (use Object Identifier for FAU)

                                                                        Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                                        (a) BI=Binary Input

                                                                        Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                        Object Identifier(a) Object Name ValueRange Description

                                                                        44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                        Additional Resources

                                                                        Additional Resources

                                                                        Use the following documents and links as additional resources

                                                                        bull Product support online

                                                                        bull wwwbacnetorg

                                                                        bull wwwbacnetassociationorg

                                                                        bull wwwashraeorg

                                                                        bull Tracer TU Help online

                                                                        bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                                        bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                                        Note For further assistance contact your local Trane sales office

                                                                        ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                                        Glossary

                                                                        A

                                                                        ASHRAE

                                                                        See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                                        American Society of Heating Refrigeration and Air-

                                                                        conditioning Engineers

                                                                        An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                                        BBACnettrade

                                                                        See Building Automation Control network

                                                                        BACnet interoperability building blocks

                                                                        A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                                        BACnet object

                                                                        An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                                        baud rate

                                                                        The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                                        BIBB

                                                                        See BACnet interoperability building blocks

                                                                        Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                                        advocates BACnet protocol for use in system-level control devices

                                                                        device

                                                                        A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                                        Device ID

                                                                        The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                                        Iinteroperability

                                                                        The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                                        Pprotocol

                                                                        A set of rules (language) that governs the exchange of data over a digital communications system

                                                                        S

                                                                        stand-alone operation

                                                                        Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                                        wwwtranecom

                                                                        For more information contact your local Trane office or e-mail us at comforttranecom

                                                                        Literature Order Number ACC-SVP01B-EN

                                                                        Date September 2009

                                                                        Supersedes ACC-SVP01A-EN

                                                                        Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                                        • Table of Contents
                                                                        • Overview
                                                                        • Ordering Numbers
                                                                        • BACnet Protocol
                                                                        • BCI-I Configuration
                                                                          • Overview
                                                                          • Starting a Session of Tracer TU and Direct Connection
                                                                          • Reset to Factory Default
                                                                          • IP Units Configuration
                                                                          • BACnet Object Configuration
                                                                          • Change Baud Rate
                                                                          • Change Device ID
                                                                          • Stand-alone or BAS Operation
                                                                            • IntelliPak Control Configuration
                                                                            • BAS Unit Control
                                                                            • Periodic Update of BAS Values
                                                                            • BAS Communication Failure
                                                                              • InputOutput Commands and Calculations
                                                                                • System Control Command
                                                                                • Filter Timer Reset Command
                                                                                • Diagnostics Reset Command
                                                                                • Setpoint Calculations
                                                                                • Timestamp Configuration
                                                                                    • BCI IntelliPak Rotary Switches and LEDs
                                                                                      • Rotary Switches
                                                                                      • LEDs Description Behavior and Troubleshooting
                                                                                      • 24 Vac Measurement
                                                                                      • Ground Measurements
                                                                                        • BACnet Data Points and Configuration Property Definitions
                                                                                          • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                                            • Standardized Device Profile (Annex L)
                                                                                            • Interoperability Building Blocks (Annex K)
                                                                                            • Segmentation Capability
                                                                                            • Object Types
                                                                                              • BACnet Protocol
                                                                                                • Data Link Layer Options
                                                                                                • Device Address Binding
                                                                                                • Networking Options
                                                                                                • Character Sets
                                                                                                    • Object Data Points and Diagnostic Data Points
                                                                                                    • Additional Resources
                                                                                                    • Glossary

                                                                          ACC-SVP01B-EN bull BCI-I Integration Guide 37

                                                                          Object Data Points and Diagnostic Data Points

                                                                          Binary Output 16 Humidification Command Command the operating state of the humidification system

                                                                          NC 3 HVAC-Advisory HVAC-Advisory

                                                                          NC 1 HVAC-Critical HVAC-Critical

                                                                          NC 4 HVAC-Information HVAC-Information

                                                                          NC 2 HVAC-Service Required HVAC-Service Required

                                                                          Analog Input 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor

                                                                          Analog Input 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode

                                                                          Analog Output 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode

                                                                          Multi-State Output 7 Occupancy Mode Request BAS Command the unit into an occupancy mode

                                                                          Multi-State Input 20 Occupancy Mode Status Indicates the current occupancy mode of the unit

                                                                          Analog Output 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode

                                                                          Analog Input 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position

                                                                          Multi-State Input 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper

                                                                          Analog Input 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit

                                                                          Analog Input 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit

                                                                          Analog Input 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit

                                                                          Analog Output 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value

                                                                          Analog Input 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control

                                                                          Analog Output 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value

                                                                          Analog Input 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor

                                                                          Analog Input 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit

                                                                          Analog Output 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint

                                                                          Analog Input 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control

                                                                          Analog Output 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value

                                                                          Analog Input 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor

                                                                          Multi-State Input 34 Prefilter Status Indicates the prefilter media state

                                                                          Analog Input 82 Preheat Type Describes the heating type installed in the unit

                                                                          Multi-State Input 35 Primary Filter Status Indicates the primary filter media state

                                                                          Analog Input 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized

                                                                          Analog Input 83 Reheat Type Describes the reheat type installed in the unit

                                                                          Analog Input 26 Return Air Temperature The return air temperature value from a unit-mounted sensor

                                                                          Analog Input 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor

                                                                          Multi-State Input 40 Return Fan Proving Status Indicates the current state of the return fan

                                                                          Analog Input 10 Return Fan Speed Command Indicates the unit commanded return fan speed

                                                                          Multi-State Input 42 Return Fan Status Indicates the state of the return fan

                                                                          Binary Input 11 Service Test Mode Status Indicates if the unit is in service test mode

                                                                          Analog Output 11 Space Air Temperature BAS BAS supplied space air temperature sensor value

                                                                          Analog Input 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor

                                                                          Analog Input 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control

                                                                          Analog Output 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes

                                                                          Analog Input 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control

                                                                          Analog Output 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value

                                                                          Analog Input 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation

                                                                          Analog Input 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation

                                                                          Analog Output 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value

                                                                          Analog Input 17 Space Enthalpy The space enthalpy value from a unit-mounted control

                                                                          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                          Object Identifier(a) Object Name Description

                                                                          38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                          Object Data Points and Diagnostic Data Points

                                                                          Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                                                          Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                                                          Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                                                          Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                                                          Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                                                          Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                                                          Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                                                          Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                                                          Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                                                          Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                                                          Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                                                          Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                                                          Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                                                          Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                                                          Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                                                          Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                                                          Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                                                          Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                                                          Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                                                          Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                                          Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                                          Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                                          Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                                                          Binary Input 3 Unit Status Indicates the current state of the unit

                                                                          Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                                          Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                                                          Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                                                          Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                                          Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                                          Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                                          Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                                                          (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                                                          Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                          Object Identifier(a) Object Name Description

                                                                          Table 12 Diagnostic Objects Sorted by Object Name

                                                                          Object Identifier(a) Object Name ValueRange Description

                                                                          BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                                                          BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                                                          ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                                                          Object Data Points and Diagnostic Data Points

                                                                          BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                                                          BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                                                          BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                                                          BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                                                          BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                                                          BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                                                          BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                                                          BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                                                          BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                                                          BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                                                          BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                                                          BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                                                          BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                                                          BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                                                          BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                                                          BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                                                          BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                                                          BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                                                          BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                                                          BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                                                          BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                                                          BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                                                          BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                                                          BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                                                          BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                                                          BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                                          BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                                          BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                                          BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                                                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                          Object Identifier(a) Object Name ValueRange Description

                                                                          40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                          Object Data Points and Diagnostic Data Points

                                                                          BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                                                          BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                                                          BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                                                          BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                                                          BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                                                          BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                                                          BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                                                          BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                                                          BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                                                          BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                                                          BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                                                          BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                                                          BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                                                          BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                                                          BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                                                          BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                                                          BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                                                          BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                                                          BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                                                          BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                                                          BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                                                          BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                                                          BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                                                          BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                                          BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                                          BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                                                          BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                                                          BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                                                          BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                                                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                          Object Identifier(a) Object Name ValueRange Description

                                                                          ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                                          Object Data Points and Diagnostic Data Points

                                                                          BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                                          BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                                          BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                                          BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                                          BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                                          BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                                          BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                                          BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                                          BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                                          BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                                          BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                                          BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                                          BI 121 (use Object Identifier for RT)

                                                                          Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                                          BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                                          BI 58 (use Object Identifier for RT or CSC)

                                                                          Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                                          BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                                          BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                                          BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                                          BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                                          BI 31 (use Object Identifier for RT CSC)

                                                                          Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                                          BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                                          BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                          BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                          BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                                          BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                                          BI 121 (use Object Identifier for FAU)

                                                                          Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                                          B1 31 (use Object Identifier for FAU)

                                                                          Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                                          BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                                          BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                          Object Identifier(a) Object Name ValueRange Description

                                                                          42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                          Object Data Points and Diagnostic Data Points

                                                                          BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                                          BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                                          BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                                          BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                                          BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                                          BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                                          BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                                          BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                                          BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                                          BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                                          BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                                          BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                                          BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                                          BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                                          BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                                          BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                                          BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                                          BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                                          BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                                          BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                                          BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                                          BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                                          BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                                          1 = active Diagnostic Vel Press Sensor (Rear)

                                                                          BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                                          Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                                          BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                                          BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                                          BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                                          BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                                          BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                          Object Identifier(a) Object Name ValueRange Description

                                                                          ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                                          Object Data Points and Diagnostic Data Points

                                                                          BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                                          BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                                          BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                                          BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                                          BI 58 (use Object Identifier for FAU)

                                                                          Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                                          (a) BI=Binary Input

                                                                          Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                          Object Identifier(a) Object Name ValueRange Description

                                                                          44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                          Additional Resources

                                                                          Additional Resources

                                                                          Use the following documents and links as additional resources

                                                                          bull Product support online

                                                                          bull wwwbacnetorg

                                                                          bull wwwbacnetassociationorg

                                                                          bull wwwashraeorg

                                                                          bull Tracer TU Help online

                                                                          bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                                          bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                                          Note For further assistance contact your local Trane sales office

                                                                          ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                                          Glossary

                                                                          A

                                                                          ASHRAE

                                                                          See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                                          American Society of Heating Refrigeration and Air-

                                                                          conditioning Engineers

                                                                          An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                                          BBACnettrade

                                                                          See Building Automation Control network

                                                                          BACnet interoperability building blocks

                                                                          A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                                          BACnet object

                                                                          An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                                          baud rate

                                                                          The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                                          BIBB

                                                                          See BACnet interoperability building blocks

                                                                          Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                                          advocates BACnet protocol for use in system-level control devices

                                                                          device

                                                                          A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                                          Device ID

                                                                          The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                                          Iinteroperability

                                                                          The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                                          Pprotocol

                                                                          A set of rules (language) that governs the exchange of data over a digital communications system

                                                                          S

                                                                          stand-alone operation

                                                                          Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                                          wwwtranecom

                                                                          For more information contact your local Trane office or e-mail us at comforttranecom

                                                                          Literature Order Number ACC-SVP01B-EN

                                                                          Date September 2009

                                                                          Supersedes ACC-SVP01A-EN

                                                                          Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                                          • Table of Contents
                                                                          • Overview
                                                                          • Ordering Numbers
                                                                          • BACnet Protocol
                                                                          • BCI-I Configuration
                                                                            • Overview
                                                                            • Starting a Session of Tracer TU and Direct Connection
                                                                            • Reset to Factory Default
                                                                            • IP Units Configuration
                                                                            • BACnet Object Configuration
                                                                            • Change Baud Rate
                                                                            • Change Device ID
                                                                            • Stand-alone or BAS Operation
                                                                              • IntelliPak Control Configuration
                                                                              • BAS Unit Control
                                                                              • Periodic Update of BAS Values
                                                                              • BAS Communication Failure
                                                                                • InputOutput Commands and Calculations
                                                                                  • System Control Command
                                                                                  • Filter Timer Reset Command
                                                                                  • Diagnostics Reset Command
                                                                                  • Setpoint Calculations
                                                                                  • Timestamp Configuration
                                                                                      • BCI IntelliPak Rotary Switches and LEDs
                                                                                        • Rotary Switches
                                                                                        • LEDs Description Behavior and Troubleshooting
                                                                                        • 24 Vac Measurement
                                                                                        • Ground Measurements
                                                                                          • BACnet Data Points and Configuration Property Definitions
                                                                                            • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                                              • Standardized Device Profile (Annex L)
                                                                                              • Interoperability Building Blocks (Annex K)
                                                                                              • Segmentation Capability
                                                                                              • Object Types
                                                                                                • BACnet Protocol
                                                                                                  • Data Link Layer Options
                                                                                                  • Device Address Binding
                                                                                                  • Networking Options
                                                                                                  • Character Sets
                                                                                                      • Object Data Points and Diagnostic Data Points
                                                                                                      • Additional Resources
                                                                                                      • Glossary

                                                                            38 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                            Object Data Points and Diagnostic Data Points

                                                                            Analog Input 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control

                                                                            Analog Output 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value

                                                                            Analog Input 16 Space Humidity Active The space humidity value from a unit-mounted control

                                                                            Analog Output 25 Space Humidity BAS BAS supplied space humidity sensor value

                                                                            Analog Input 31 Space Static Air Pressure Active Space static air pressure value being used for unit control

                                                                            Analog Output 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value

                                                                            Analog Output 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value

                                                                            Analog Input 15 Space Temperature Active The space temperature currently used for unit control

                                                                            Analog Input 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module

                                                                            Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module

                                                                            Analog Input 78 Space Temperature Setpoint Local The local space temperature setpoint

                                                                            Analog Output 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode

                                                                            Binary Output 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation

                                                                            Binary Input 15 Supply Fan Configuration Status Indicates the supply fan configuration

                                                                            Multi-State Input 37 Supply Fan Proving Status Indicates the current state of the supply fan

                                                                            Analog Input 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed

                                                                            Multi-State Input 41 Supply Fan Status Indicates the state of the supply fan

                                                                            Analog Input 89 Supply Fan Type Describes the supply fan type installed in the unit

                                                                            Binary Output 1 System Control Command Command the unit to standalone- or BAS-controlled operation

                                                                            Binary Input 1 System Control Status Indicates the control system currently in command of the unit

                                                                            Multi-State Input 24 Timed Override Status Timed override request or cancel from zone sensor

                                                                            Multi-State Input 2 Trane Unit Type General description of the equipment-type classification

                                                                            Analog Input 88 Unit Energy Demand Indicates the current heatcool energy demand of the unit

                                                                            Binary Input 3 Unit Status Indicates the current state of the unit

                                                                            Multi-State Input 21 Unit Stop Source Source of the stop command that turned off the equipment

                                                                            Analog Output 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode

                                                                            Analog Output 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode

                                                                            Binary Input 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open

                                                                            Multi-State Input 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation

                                                                            Binary Input 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system

                                                                            Analog Input 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position

                                                                            (a) AI=Analog Input AO=Analog Output AV=Analog Value BI=Binary Input BO=Binary Output MI=Multistate Input MO=Multistate Output

                                                                            Table 11 All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)

                                                                            Object Identifier(a) Object Name Description

                                                                            Table 12 Diagnostic Objects Sorted by Object Name

                                                                            Object Identifier(a) Object Name ValueRange Description

                                                                            BI 59 Diagnostic Auto - SA High Press Limit 0 = inactive1 = active Diagnostic Auto - SA High Press Limit

                                                                            BI 66 Diagnostic BACnet Module Comm Fail 0 = inactive1 = active Diagnostic BACnet Module Comm Fail

                                                                            ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                                                            Object Data Points and Diagnostic Data Points

                                                                            BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                                                            BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                                                            BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                                                            BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                                                            BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                                                            BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                                                            BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                                                            BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                                                            BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                                                            BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                                                            BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                                                            BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                                                            BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                                                            BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                                                            BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                                                            BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                                                            BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                                                            BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                                                            BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                                                            BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                                                            BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                                                            BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                                                            BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                                                            BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                                                            BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                                                            BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                                            BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                                            BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                                            BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                                                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                            Object Identifier(a) Object Name ValueRange Description

                                                                            40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                            Object Data Points and Diagnostic Data Points

                                                                            BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                                                            BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                                                            BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                                                            BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                                                            BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                                                            BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                                                            BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                                                            BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                                                            BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                                                            BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                                                            BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                                                            BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                                                            BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                                                            BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                                                            BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                                                            BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                                                            BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                                                            BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                                                            BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                                                            BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                                                            BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                                                            BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                                                            BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                                                            BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                                            BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                                            BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                                                            BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                                                            BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                                                            BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                                                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                            Object Identifier(a) Object Name ValueRange Description

                                                                            ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                                            Object Data Points and Diagnostic Data Points

                                                                            BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                                            BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                                            BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                                            BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                                            BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                                            BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                                            BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                                            BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                                            BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                                            BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                                            BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                                            BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                                            BI 121 (use Object Identifier for RT)

                                                                            Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                                            BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                                            BI 58 (use Object Identifier for RT or CSC)

                                                                            Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                                            BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                                            BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                                            BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                                            BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                                            BI 31 (use Object Identifier for RT CSC)

                                                                            Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                                            BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                                            BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                            BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                            BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                                            BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                                            BI 121 (use Object Identifier for FAU)

                                                                            Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                                            B1 31 (use Object Identifier for FAU)

                                                                            Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                                            BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                                            BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                            Object Identifier(a) Object Name ValueRange Description

                                                                            42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                            Object Data Points and Diagnostic Data Points

                                                                            BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                                            BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                                            BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                                            BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                                            BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                                            BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                                            BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                                            BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                                            BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                                            BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                                            BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                                            BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                                            BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                                            BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                                            BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                                            BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                                            BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                                            BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                                            BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                                            BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                                            BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                                            BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                                            BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                                            1 = active Diagnostic Vel Press Sensor (Rear)

                                                                            BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                                            Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                                            BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                                            BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                                            BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                                            BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                                            BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                            Object Identifier(a) Object Name ValueRange Description

                                                                            ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                                            Object Data Points and Diagnostic Data Points

                                                                            BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                                            BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                                            BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                                            BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                                            BI 58 (use Object Identifier for FAU)

                                                                            Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                                            (a) BI=Binary Input

                                                                            Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                            Object Identifier(a) Object Name ValueRange Description

                                                                            44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                            Additional Resources

                                                                            Additional Resources

                                                                            Use the following documents and links as additional resources

                                                                            bull Product support online

                                                                            bull wwwbacnetorg

                                                                            bull wwwbacnetassociationorg

                                                                            bull wwwashraeorg

                                                                            bull Tracer TU Help online

                                                                            bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                                            bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                                            Note For further assistance contact your local Trane sales office

                                                                            ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                                            Glossary

                                                                            A

                                                                            ASHRAE

                                                                            See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                                            American Society of Heating Refrigeration and Air-

                                                                            conditioning Engineers

                                                                            An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                                            BBACnettrade

                                                                            See Building Automation Control network

                                                                            BACnet interoperability building blocks

                                                                            A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                                            BACnet object

                                                                            An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                                            baud rate

                                                                            The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                                            BIBB

                                                                            See BACnet interoperability building blocks

                                                                            Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                                            advocates BACnet protocol for use in system-level control devices

                                                                            device

                                                                            A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                                            Device ID

                                                                            The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                                            Iinteroperability

                                                                            The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                                            Pprotocol

                                                                            A set of rules (language) that governs the exchange of data over a digital communications system

                                                                            S

                                                                            stand-alone operation

                                                                            Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                                            wwwtranecom

                                                                            For more information contact your local Trane office or e-mail us at comforttranecom

                                                                            Literature Order Number ACC-SVP01B-EN

                                                                            Date September 2009

                                                                            Supersedes ACC-SVP01A-EN

                                                                            Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                                            • Table of Contents
                                                                            • Overview
                                                                            • Ordering Numbers
                                                                            • BACnet Protocol
                                                                            • BCI-I Configuration
                                                                              • Overview
                                                                              • Starting a Session of Tracer TU and Direct Connection
                                                                              • Reset to Factory Default
                                                                              • IP Units Configuration
                                                                              • BACnet Object Configuration
                                                                              • Change Baud Rate
                                                                              • Change Device ID
                                                                              • Stand-alone or BAS Operation
                                                                                • IntelliPak Control Configuration
                                                                                • BAS Unit Control
                                                                                • Periodic Update of BAS Values
                                                                                • BAS Communication Failure
                                                                                  • InputOutput Commands and Calculations
                                                                                    • System Control Command
                                                                                    • Filter Timer Reset Command
                                                                                    • Diagnostics Reset Command
                                                                                    • Setpoint Calculations
                                                                                    • Timestamp Configuration
                                                                                        • BCI IntelliPak Rotary Switches and LEDs
                                                                                          • Rotary Switches
                                                                                          • LEDs Description Behavior and Troubleshooting
                                                                                          • 24 Vac Measurement
                                                                                          • Ground Measurements
                                                                                            • BACnet Data Points and Configuration Property Definitions
                                                                                              • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                                                • Standardized Device Profile (Annex L)
                                                                                                • Interoperability Building Blocks (Annex K)
                                                                                                • Segmentation Capability
                                                                                                • Object Types
                                                                                                  • BACnet Protocol
                                                                                                    • Data Link Layer Options
                                                                                                    • Device Address Binding
                                                                                                    • Networking Options
                                                                                                    • Character Sets
                                                                                                        • Object Data Points and Diagnostic Data Points
                                                                                                        • Additional Resources
                                                                                                        • Glossary

                                                                              ACC-SVP01B-EN bull BCI-I Integration Guide 39

                                                                              Object Data Points and Diagnostic Data Points

                                                                              BI 67 Diagnostic BASNetwork Comm Fail 0 = inactive1 = active Diagnostic BASNetwork Comm Fail

                                                                              BI 85 Diagnostic Blocked Air Return 0 = inactive1 = active Diagnostic Blocked Air Return

                                                                              BI 83 Diagnostic CO2 Sensor Failure 0 = inactive1 = active Diagnostic CO2 Sensor Failure

                                                                              BI 72 Diagnostic Compressor Contact Fail-Ckt1 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt1

                                                                              BI 73 Diagnostic Compressor Contact Fail-Ckt2 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt2

                                                                              BI 103 Diagnostic Compressor Contact Fail-Ckt3 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt3

                                                                              BI 102 Diagnostic Compressor Contact Fail-Ckt4 0 = inactive1 = active Diagnostic Compressor Contact Fail-Ckt4

                                                                              BI 89 Diagnostic Compressor Trip - Ckt 3 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 3

                                                                              BI 90 Diagnostic Compressor Trip - Ckt 4 0 = inactive1 = active Diagnostic Compressor Trip - Ckt 4

                                                                              BI 47 Diagnostic Compressor Trip - Ckt1 0 = inactive1 = active Diagnostic Compressor Trip - Ckt1

                                                                              BI 48 Diagnostic Compressor Trip - Ckt2 0 = inactive1 = active Diagnostic Compressor Trip - Ckt2

                                                                              BI 114 Diagnostic Cond Sump Max Level Fail 0 = inactive1 = active Diagnostic Cond Sump Max Level Fail

                                                                              BI 115 Diagnostic Cond Sump Min Level Fail 0 = inactive1 = active Diagnostic Cond Sump Min Level Fail

                                                                              BI 45 Diagnostic Cond Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt1

                                                                              BI 46 Diagnostic Cond Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt2

                                                                              BI 92 Diagnostic Cond Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt3

                                                                              BI 93 Diagnostic Cond Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Cond Temp Sensor Fail - Ckt4

                                                                              BI 117 Diagnostic Cond Water Pump Fail (auto) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (auto)

                                                                              BI 116 Diagnostic Cond Water Pump Fail (man) 0 = inactive1 = active Diagnostic Cond Water Pump Fail (man)

                                                                              BI 118 Diagnostic Cond Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Cond Water Temp Sensor Fail

                                                                              BI 76 Diagnostic Dirty Filter 0 = inactive1 = active Diagnostic Dirty Filter

                                                                              BI 129 Diagnostic Dirty Final Filter 0 = inactive1 = active Diagnostic Dirty Final Filter

                                                                              BI 64 Diagnostic ECEM Communications Failure 0 = inactive1 = active Diagnostic ECEM Communications Failure

                                                                              BI 38 Diagnostic Emergency Stop 0 = inactive1 = active Diagnostic Emergency Stop

                                                                              BI 113 Diagnostic Energy Recovery Wheel Fail 0 = inactive1 = active Diagnostic Energy Recovery Wheel Fail

                                                                              BI 94 Diagnostic Ent Cond Wtr Tmp Sensor Fail 0 = inactive1 = active Diagnostic Ent Cond Wtr Tmp Sensor Fail

                                                                              BI 107 Diagnostic Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 1

                                                                              BI 108 Diagnostic Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 2

                                                                              BI 109 Diagnostic Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 3

                                                                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                              Object Identifier(a) Object Name ValueRange Description

                                                                              40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                              Object Data Points and Diagnostic Data Points

                                                                              BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                                                              BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                                                              BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                                                              BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                                                              BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                                                              BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                                                              BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                                                              BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                                                              BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                                                              BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                                                              BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                                                              BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                                                              BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                                                              BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                                                              BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                                                              BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                                                              BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                                                              BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                                                              BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                                                              BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                                                              BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                                                              BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                                                              BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                                                              BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                                              BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                                              BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                                                              BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                                                              BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                                                              BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                                                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                              Object Identifier(a) Object Name ValueRange Description

                                                                              ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                                              Object Data Points and Diagnostic Data Points

                                                                              BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                                              BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                                              BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                                              BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                                              BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                                              BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                                              BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                                              BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                                              BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                                              BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                                              BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                                              BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                                              BI 121 (use Object Identifier for RT)

                                                                              Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                                              BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                                              BI 58 (use Object Identifier for RT or CSC)

                                                                              Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                                              BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                                              BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                                              BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                                              BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                                              BI 31 (use Object Identifier for RT CSC)

                                                                              Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                                              BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                                              BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                              BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                              BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                                              BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                                              BI 121 (use Object Identifier for FAU)

                                                                              Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                                              B1 31 (use Object Identifier for FAU)

                                                                              Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                                              BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                                              BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                              Object Identifier(a) Object Name ValueRange Description

                                                                              42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                              Object Data Points and Diagnostic Data Points

                                                                              BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                                              BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                                              BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                                              BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                                              BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                                              BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                                              BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                                              BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                                              BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                                              BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                                              BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                                              BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                                              BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                                              BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                                              BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                                              BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                                              BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                                              BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                                              BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                                              BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                                              BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                                              BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                                              BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                                              1 = active Diagnostic Vel Press Sensor (Rear)

                                                                              BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                                              Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                                              BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                                              BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                                              BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                                              BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                                              BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                              Object Identifier(a) Object Name ValueRange Description

                                                                              ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                                              Object Data Points and Diagnostic Data Points

                                                                              BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                                              BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                                              BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                                              BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                                              BI 58 (use Object Identifier for FAU)

                                                                              Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                                              (a) BI=Binary Input

                                                                              Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                              Object Identifier(a) Object Name ValueRange Description

                                                                              44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                              Additional Resources

                                                                              Additional Resources

                                                                              Use the following documents and links as additional resources

                                                                              bull Product support online

                                                                              bull wwwbacnetorg

                                                                              bull wwwbacnetassociationorg

                                                                              bull wwwashraeorg

                                                                              bull Tracer TU Help online

                                                                              bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                                              bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                                              Note For further assistance contact your local Trane sales office

                                                                              ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                                              Glossary

                                                                              A

                                                                              ASHRAE

                                                                              See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                                              American Society of Heating Refrigeration and Air-

                                                                              conditioning Engineers

                                                                              An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                                              BBACnettrade

                                                                              See Building Automation Control network

                                                                              BACnet interoperability building blocks

                                                                              A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                                              BACnet object

                                                                              An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                                              baud rate

                                                                              The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                                              BIBB

                                                                              See BACnet interoperability building blocks

                                                                              Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                                              advocates BACnet protocol for use in system-level control devices

                                                                              device

                                                                              A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                                              Device ID

                                                                              The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                                              Iinteroperability

                                                                              The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                                              Pprotocol

                                                                              A set of rules (language) that governs the exchange of data over a digital communications system

                                                                              S

                                                                              stand-alone operation

                                                                              Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                                              wwwtranecom

                                                                              For more information contact your local Trane office or e-mail us at comforttranecom

                                                                              Literature Order Number ACC-SVP01B-EN

                                                                              Date September 2009

                                                                              Supersedes ACC-SVP01A-EN

                                                                              Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                                              • Table of Contents
                                                                              • Overview
                                                                              • Ordering Numbers
                                                                              • BACnet Protocol
                                                                              • BCI-I Configuration
                                                                                • Overview
                                                                                • Starting a Session of Tracer TU and Direct Connection
                                                                                • Reset to Factory Default
                                                                                • IP Units Configuration
                                                                                • BACnet Object Configuration
                                                                                • Change Baud Rate
                                                                                • Change Device ID
                                                                                • Stand-alone or BAS Operation
                                                                                  • IntelliPak Control Configuration
                                                                                  • BAS Unit Control
                                                                                  • Periodic Update of BAS Values
                                                                                  • BAS Communication Failure
                                                                                    • InputOutput Commands and Calculations
                                                                                      • System Control Command
                                                                                      • Filter Timer Reset Command
                                                                                      • Diagnostics Reset Command
                                                                                      • Setpoint Calculations
                                                                                      • Timestamp Configuration
                                                                                          • BCI IntelliPak Rotary Switches and LEDs
                                                                                            • Rotary Switches
                                                                                            • LEDs Description Behavior and Troubleshooting
                                                                                            • 24 Vac Measurement
                                                                                            • Ground Measurements
                                                                                              • BACnet Data Points and Configuration Property Definitions
                                                                                                • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                                                  • Standardized Device Profile (Annex L)
                                                                                                  • Interoperability Building Blocks (Annex K)
                                                                                                  • Segmentation Capability
                                                                                                  • Object Types
                                                                                                    • BACnet Protocol
                                                                                                      • Data Link Layer Options
                                                                                                      • Device Address Binding
                                                                                                      • Networking Options
                                                                                                      • Character Sets
                                                                                                          • Object Data Points and Diagnostic Data Points
                                                                                                          • Additional Resources
                                                                                                          • Glossary

                                                                                40 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                                Object Data Points and Diagnostic Data Points

                                                                                BI 110 Diagnostic Ent Evap Temp Sensor Fail-Ckt 4 0 = inactive1 = active Diagnostic Ent Evap Temp Sensor Fail-Ckt 4

                                                                                BI 96 Diagnostic Enter Water Temp Sensor Fail 0 = inactive1 = active Diagnostic Enter Water Temp Sensor Fail

                                                                                BI 105 Diagnostic Evap Temp Sensor Fail - Ckt3 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt3

                                                                                BI 104 Diagnostic Evap Temp Sensor Fail - Ckt4 0 = inactive1 = active Diagnostic Evap Temp Sensor Fail - Ckt4

                                                                                BI 91 Diagnostic Exh Fan VFD Bypass Enabled 0 = inactive1 = active Diagnostic Exh Fan VFD Bypass Enabled

                                                                                BI 40 Diagnostic ExhaustReturn Fan Failure 0 = inactive1 = active Diagnostic ExhaustReturn Fan Failure

                                                                                BI 120 Diagnostic GBAS 0-10 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-10 VDC Comm Failure

                                                                                BI 65 Diagnostic GBAS 0-5 VDC Comm Failure 0 = inactive1 = active Diagnostic GBAS 0-5 VDC Comm Failure

                                                                                BI 49 Diagnostic HEAT Aux Temp Sensor Fail 0 = inactive1 = active Diagnostic HEAT Aux Temp Sensor Fail

                                                                                BI 63 Diagnostic HEAT Communications Failure 0 = inactive1 = active Diagnostic HEAT Communications Failure

                                                                                BI 51 Diagnostic Heat Failure 0 = inactive1 = active Diagnostic Heat Failure

                                                                                BI 99 Diagnostic High CO2 Level 0 = inactive1 = active Diagnostic High CO2 Level

                                                                                BI 131 Diagnostic High Superheat - Ckt 1 0 = inactive1 = active Diagnostic High Superheat - Ckt 1

                                                                                BI 133 Diagnostic High Superheat - Ckt 2 0 = inactive1 = active Diagnostic High Superheat - Ckt 2

                                                                                BI 122 Diagnostic Insufficient Airflow for Dehumid 0 = inactive1 = active Diagnostic Insufficient Airflow for Dehumid

                                                                                BI 146 Diagnostic Invalid Unit Configuration 0 = inactive1 = active Diagnostic Invalid Unit Configuration

                                                                                BI 50 Diagnostic Low Air Temp Limit Trip 0 = inactive1 = active Diagnostic Low Air Temp Limit Trip

                                                                                BI 43 Diagnostic Low Pressure Ctl Open - Ckt1 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt1

                                                                                BI 44 Diagnostic Low Pressure Ctl Open - Ckt2 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt2

                                                                                BI 101 Diagnostic Low Pressure Ctl Open - Ckt3 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt3

                                                                                BI 100 Diagnostic Low Pressure Ctl Open - Ckt4 0 = inactive1 = active Diagnostic Low Pressure Ctl Open - Ckt4

                                                                                BI 132 Diagnostic Low Refrigerant Charge - Ckt 1 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 1

                                                                                BI 134 Diagnostic Low Refrigerant Charge - Ckt 2 0 = inactive1 = active Diagnostic Low Refrigerant Charge - Ckt 2

                                                                                BI 41 Diagnostic Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt1

                                                                                BI 42 Diagnostic Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive1 = active Diagnostic Lvg Evap Temp Sensor Fail - Ckt2

                                                                                BI 147 Diagnostic Maintenance Required 0 = inactive1 = active Diagnostic Maintenance Required

                                                                                BI 60 Diagnostic Man - SA High Press Limit 0 = inactive1 = active Diagnostic Man - SA High Press Limit

                                                                                BI 62 Diagnostic MCM Communications Failure 0 = inactive1 = active Diagnostic MCM Communications Failure

                                                                                BI 128 Diagnostic MDM Communications Failure 0 = inactive1 = active Diagnostic MDM Communications Failure

                                                                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                                Object Identifier(a) Object Name ValueRange Description

                                                                                ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                                                Object Data Points and Diagnostic Data Points

                                                                                BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                                                BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                                                BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                                                BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                                                BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                                                BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                                                BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                                                BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                                                BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                                                BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                                                BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                                                BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                                                BI 121 (use Object Identifier for RT)

                                                                                Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                                                BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                                                BI 58 (use Object Identifier for RT or CSC)

                                                                                Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                                                BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                                                BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                                                BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                                                BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                                                BI 31 (use Object Identifier for RT CSC)

                                                                                Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                                                BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                                                BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                                BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                                BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                                                BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                                                BI 121 (use Object Identifier for FAU)

                                                                                Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                                                B1 31 (use Object Identifier for FAU)

                                                                                Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                                                BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                                                BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                                Object Identifier(a) Object Name ValueRange Description

                                                                                42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                                Object Data Points and Diagnostic Data Points

                                                                                BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                                                BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                                                BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                                                BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                                                BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                                                BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                                                BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                                                BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                                                BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                                                BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                                                BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                                                BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                                                BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                                                BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                                                BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                                                BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                                                BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                                                BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                                                BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                                                BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                                                BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                                                BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                                                BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                                                1 = active Diagnostic Vel Press Sensor (Rear)

                                                                                BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                                                Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                                                BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                                                BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                                                BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                                                BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                                                BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                                Object Identifier(a) Object Name ValueRange Description

                                                                                ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                                                Object Data Points and Diagnostic Data Points

                                                                                BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                                                BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                                                BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                                                BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                                                BI 58 (use Object Identifier for FAU)

                                                                                Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                                                (a) BI=Binary Input

                                                                                Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                                Object Identifier(a) Object Name ValueRange Description

                                                                                44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                                Additional Resources

                                                                                Additional Resources

                                                                                Use the following documents and links as additional resources

                                                                                bull Product support online

                                                                                bull wwwbacnetorg

                                                                                bull wwwbacnetassociationorg

                                                                                bull wwwashraeorg

                                                                                bull Tracer TU Help online

                                                                                bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                                                bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                                                Note For further assistance contact your local Trane sales office

                                                                                ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                                                Glossary

                                                                                A

                                                                                ASHRAE

                                                                                See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                                                American Society of Heating Refrigeration and Air-

                                                                                conditioning Engineers

                                                                                An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                                                BBACnettrade

                                                                                See Building Automation Control network

                                                                                BACnet interoperability building blocks

                                                                                A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                                                BACnet object

                                                                                An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                                                baud rate

                                                                                The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                                                BIBB

                                                                                See BACnet interoperability building blocks

                                                                                Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                                                advocates BACnet protocol for use in system-level control devices

                                                                                device

                                                                                A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                                                Device ID

                                                                                The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                                                Iinteroperability

                                                                                The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                                                Pprotocol

                                                                                A set of rules (language) that governs the exchange of data over a digital communications system

                                                                                S

                                                                                stand-alone operation

                                                                                Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                                                wwwtranecom

                                                                                For more information contact your local Trane office or e-mail us at comforttranecom

                                                                                Literature Order Number ACC-SVP01B-EN

                                                                                Date September 2009

                                                                                Supersedes ACC-SVP01A-EN

                                                                                Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                                                • Table of Contents
                                                                                • Overview
                                                                                • Ordering Numbers
                                                                                • BACnet Protocol
                                                                                • BCI-I Configuration
                                                                                  • Overview
                                                                                  • Starting a Session of Tracer TU and Direct Connection
                                                                                  • Reset to Factory Default
                                                                                  • IP Units Configuration
                                                                                  • BACnet Object Configuration
                                                                                  • Change Baud Rate
                                                                                  • Change Device ID
                                                                                  • Stand-alone or BAS Operation
                                                                                    • IntelliPak Control Configuration
                                                                                    • BAS Unit Control
                                                                                    • Periodic Update of BAS Values
                                                                                    • BAS Communication Failure
                                                                                      • InputOutput Commands and Calculations
                                                                                        • System Control Command
                                                                                        • Filter Timer Reset Command
                                                                                        • Diagnostics Reset Command
                                                                                        • Setpoint Calculations
                                                                                        • Timestamp Configuration
                                                                                            • BCI IntelliPak Rotary Switches and LEDs
                                                                                              • Rotary Switches
                                                                                              • LEDs Description Behavior and Troubleshooting
                                                                                              • 24 Vac Measurement
                                                                                              • Ground Measurements
                                                                                                • BACnet Data Points and Configuration Property Definitions
                                                                                                  • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                                                    • Standardized Device Profile (Annex L)
                                                                                                    • Interoperability Building Blocks (Annex K)
                                                                                                    • Segmentation Capability
                                                                                                    • Object Types
                                                                                                      • BACnet Protocol
                                                                                                        • Data Link Layer Options
                                                                                                        • Device Address Binding
                                                                                                        • Networking Options
                                                                                                        • Character Sets
                                                                                                            • Object Data Points and Diagnostic Data Points
                                                                                                            • Additional Resources
                                                                                                            • Glossary

                                                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 41

                                                                                  Object Data Points and Diagnostic Data Points

                                                                                  BI 33 Diagnostic Mode Input Failure 0 = inactive1 = active Diagnostic Mode Input Failure

                                                                                  BI 139 Diagnostic MPM Communications Failure 0 = inactive1 = active Diagnostic MPM Communications Failure

                                                                                  BI 68 Diagnostic NSB Panel Communication Fail 0 = inactive1 = active Diagnostic NSB Panel Communication Fail

                                                                                  BI 77 Diagnostic NSB Zone Temp Sensor Fail 0 = inactive1 = active Diagnostic NSB Zone Temp Sensor Fail

                                                                                  BI 37 Diagnostic OA Humidity Sensor Failure 0 = inactive1 = active Diagnostic OA Humidity Sensor Failure

                                                                                  BI 32 Diagnostic OA Temperature Sensor Fail 0 = inactive1 = active Diagnostic OA Temperature Sensor Fail

                                                                                  BI 125 Diagnostic Occ Dehumid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Dehumid Setpoint Failure

                                                                                  BI 127 Diagnostic Occ Humid Setpoint Failure 0 = inactive1 = active Diagnostic Occ Humid Setpoint Failure

                                                                                  BI 34 Diagnostic Occ Zone Cool Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Cool Setpoint Fail

                                                                                  BI 35 Diagnostic Occ Zone Heat Setpoint Fail 0 = inactive1 = active Diagnostic Occ Zone Heat Setpoint Fail

                                                                                  BI 111 Diagnostic Recovery Dirty Prefilter 0 = inactive1 = active Diagnostic Recovery Dirty Prefilter

                                                                                  BI 112 Diagnostic Recovery Lvg RA Sensor Fail 0 = inactive1 = active Diagnostic Recovery Lvg RA Sensor Fail

                                                                                  BI 121 (use Object Identifier for RT)

                                                                                  Diagnostic Reheat Head Press High 0 = inactive1 = active Diagnostic Reheat Head Press High

                                                                                  BI 119 Diagnostic Reheat Sat Cond Temp Sensor 0 = inactive1 = active Diagnostic Reheat Sat Cond Temp Sensor

                                                                                  BI 58 (use Object Identifier for RT or CSC)

                                                                                  Diagnostic Return Air RH Sensor Failure 0 = inactive1 = active Diagnostic Return Air RH Sensor Failure

                                                                                  BI 57 Diagnostic Return Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Return Air Temp Sensor Fail

                                                                                  BI 141 Diagnostic Return Plenum Press Sensor 0 = inactive1 = active Diagnostic Return Plenum Press Sensor

                                                                                  BI 143 Diagnostic Return Press High Limit (Auto) 0 = inactive1 = active Diagnostic Return Press High Limit (Auto)

                                                                                  BI 142 Diagnostic Return Press High Limit (Man) 0 = inactive1 = active Diagnostic Return Press High Limit (Man)

                                                                                  BI 31 (use Object Identifier for RT CSC)

                                                                                  Diagnostic RTM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Aux Temp Sensor Failure

                                                                                  BI 69 Diagnostic RTM EEPROM Failure 0 = inactive1 = active Diagnostic RTM EEPROM Failure

                                                                                  BI 15 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                                  BI 151 Diagnostic RTM External Stop 0 = inactive1 = active Diagnostic RTM External Stop

                                                                                  BI 106 Diagnostic RTM Zone Humidity Sensor Fail 0 = inactive1 = active Diagnostic RTM Zone Humidity Sensor Fail

                                                                                  BI 29 Diagnostic RTM Zone Temp Sensor Failure 0 = inactive1 = active Diagnostic RTM Zone Temp Sensor Failure

                                                                                  BI 121 (use Object Identifier for FAU)

                                                                                  Diagnostic SA Drying Setpoint Failure 0 = inactive1 = active Diagnostic SA Drying Setpoint Failure

                                                                                  B1 31 (use Object Identifier for FAU)

                                                                                  Diagnostic SA Drying Temp Sensor Fail 0 = inactive1 = active Diagnostic SA Drying Temp Sensor Fail

                                                                                  BI 54 Diagnostic SA Duct Press Setpoint Fail 0 = inactive1 = active Diagnostic SA Duct Press Setpoint Fail

                                                                                  BI 123 Diagnostic SA Reheat Setpoint Failure 0 = inactive1 = active Diagnostic SA Reheat Setpoint Failure

                                                                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                                  Object Identifier(a) Object Name ValueRange Description

                                                                                  42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                                  Object Data Points and Diagnostic Data Points

                                                                                  BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                                                  BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                                                  BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                                                  BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                                                  BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                                                  BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                                                  BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                                                  BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                                                  BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                                                  BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                                                  BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                                                  BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                                                  BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                                                  BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                                                  BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                                                  BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                                                  BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                                                  BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                                                  BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                                                  BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                                                  BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                                                  BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                                                  BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                                                  1 = active Diagnostic Vel Press Sensor (Rear)

                                                                                  BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                                                  Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                                                  BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                                                  BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                                                  BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                                                  BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                                                  BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                                  Object Identifier(a) Object Name ValueRange Description

                                                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                                                  Object Data Points and Diagnostic Data Points

                                                                                  BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                                                  BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                                                  BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                                                  BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                                                  BI 58 (use Object Identifier for FAU)

                                                                                  Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                                                  (a) BI=Binary Input

                                                                                  Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                                  Object Identifier(a) Object Name ValueRange Description

                                                                                  44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                                  Additional Resources

                                                                                  Additional Resources

                                                                                  Use the following documents and links as additional resources

                                                                                  bull Product support online

                                                                                  bull wwwbacnetorg

                                                                                  bull wwwbacnetassociationorg

                                                                                  bull wwwashraeorg

                                                                                  bull Tracer TU Help online

                                                                                  bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                                                  bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                                                  Note For further assistance contact your local Trane sales office

                                                                                  ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                                                  Glossary

                                                                                  A

                                                                                  ASHRAE

                                                                                  See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                                                  American Society of Heating Refrigeration and Air-

                                                                                  conditioning Engineers

                                                                                  An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                                                  BBACnettrade

                                                                                  See Building Automation Control network

                                                                                  BACnet interoperability building blocks

                                                                                  A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                                                  BACnet object

                                                                                  An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                                                  baud rate

                                                                                  The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                                                  BIBB

                                                                                  See BACnet interoperability building blocks

                                                                                  Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                                                  advocates BACnet protocol for use in system-level control devices

                                                                                  device

                                                                                  A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                                                  Device ID

                                                                                  The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                                                  Iinteroperability

                                                                                  The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                                                  Pprotocol

                                                                                  A set of rules (language) that governs the exchange of data over a digital communications system

                                                                                  S

                                                                                  stand-alone operation

                                                                                  Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                                                  wwwtranecom

                                                                                  For more information contact your local Trane office or e-mail us at comforttranecom

                                                                                  Literature Order Number ACC-SVP01B-EN

                                                                                  Date September 2009

                                                                                  Supersedes ACC-SVP01A-EN

                                                                                  Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                                                  • Table of Contents
                                                                                  • Overview
                                                                                  • Ordering Numbers
                                                                                  • BACnet Protocol
                                                                                  • BCI-I Configuration
                                                                                    • Overview
                                                                                    • Starting a Session of Tracer TU and Direct Connection
                                                                                    • Reset to Factory Default
                                                                                    • IP Units Configuration
                                                                                    • BACnet Object Configuration
                                                                                    • Change Baud Rate
                                                                                    • Change Device ID
                                                                                    • Stand-alone or BAS Operation
                                                                                      • IntelliPak Control Configuration
                                                                                      • BAS Unit Control
                                                                                      • Periodic Update of BAS Values
                                                                                      • BAS Communication Failure
                                                                                        • InputOutput Commands and Calculations
                                                                                          • System Control Command
                                                                                          • Filter Timer Reset Command
                                                                                          • Diagnostics Reset Command
                                                                                          • Setpoint Calculations
                                                                                          • Timestamp Configuration
                                                                                              • BCI IntelliPak Rotary Switches and LEDs
                                                                                                • Rotary Switches
                                                                                                • LEDs Description Behavior and Troubleshooting
                                                                                                • 24 Vac Measurement
                                                                                                • Ground Measurements
                                                                                                  • BACnet Data Points and Configuration Property Definitions
                                                                                                    • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                                                      • Standardized Device Profile (Annex L)
                                                                                                      • Interoperability Building Blocks (Annex K)
                                                                                                      • Segmentation Capability
                                                                                                      • Object Types
                                                                                                        • BACnet Protocol
                                                                                                          • Data Link Layer Options
                                                                                                          • Device Address Binding
                                                                                                          • Networking Options
                                                                                                          • Character Sets
                                                                                                              • Object Data Points and Diagnostic Data Points
                                                                                                              • Additional Resources
                                                                                                              • Glossary

                                                                                    42 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                                    Object Data Points and Diagnostic Data Points

                                                                                    BI 74 Diagnostic SA Temp Cool Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Cool Setpoint Fail

                                                                                    BI 75 Diagnostic SA Temp Heat Setpoint Fail 0 = inactive1 = active Diagnostic SA Temp Heat Setpoint Fail

                                                                                    BI 61 Diagnostic SCM Communications Failure 0 = inactive1 = active Diagnostic SCM Communications Failure

                                                                                    BI 56 Diagnostic Space Pressure Sensor Fail 0 = inactive1 = active Diagnostic Space Pressure Sensor Fail

                                                                                    BI 55 Diagnostic Space Pressure Setpoint Fail 0 = inactive1 = active Diagnostic Space Pressure Setpoint Fail

                                                                                    BI 233 Diagnostic Sump Min Level Cycling (man) 0 = inactive1 = active Diagnostic Sump Min Level Cycling (man)

                                                                                    BI 36 Diagnostic Supply Air Press Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Press Sensor Fail

                                                                                    BI 30 Diagnostic Supply Air Temp Sensor Fail 0 = inactive1 = active Diagnostic Supply Air Temp Sensor Fail

                                                                                    BI 39 Diagnostic Supply Fan Failure 0 = inactive1 = active Diagnostic Supply Fan Failure

                                                                                    BI 98 Diagnostic Supply Fan VFD Bypass Enable 0 = inactive1 = active Diagnostic Supply Fan VFD Bypass Enable

                                                                                    BI 140 Diagnostic TPM Communications Failure 0 = inactive1 = active Diagnostic TPM Communications Failure

                                                                                    BI 148 Diagnostic Unit Communications Failure 0 = inactive1 = active Diagnostic Unit Communications Failure

                                                                                    BI 70 Diagnostic Unit HI Communications Fail 0 = inactive1 = active Diagnostic Unit HI Communications Fail

                                                                                    BI 149 Diagnostic Unit Stopped at Local HI 0 = inactive1 = active Diagnostic Unit Stopped at Local HI

                                                                                    BI 150 Diagnostic Unit Stopped at Remote HI 0 = inactive1 = active Diagnostic Unit Stopped at Remote HI

                                                                                    BI 124 Diagnostic Unocc Dehumid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Dehumid Setpoint Fail

                                                                                    BI 126 Diagnostic Unocc Humid Setpoint Fail 0 = inactive1 = active Diagnostic Unocc Humid Setpoint Fail

                                                                                    BI 52 Diagnostic Unocc Zone Cool Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Cool Stpnt Fail

                                                                                    BI 53 Diagnostic Unocc Zone Heat Stpnt Fail 0 = inactive1 = active Diagnostic Unocc Zone Heat Stpnt Fail

                                                                                    BI 84 Diagnostic VCM Aux Temp Sensor Failure 0 = inactive1 = active Diagnostic VCM Aux Temp Sensor Failure

                                                                                    BI 87 Diagnostic VCM Communications Failure 0 = inactive1 = active Diagnostic VCM Communications Failure

                                                                                    BI 130 Diagnostic Vel Press Sensor (Front) Fail 0 = inactive1 = active Diagnostic Vel Press Sensor (Front) Fail

                                                                                    BI 86 (use Object Identifier for Ipak II-RT) Diagnostic Vel Press Sensor (Rear) 0 = inactive

                                                                                    1 = active Diagnostic Vel Press Sensor (Rear)

                                                                                    BI 86 (use Object Identifier for Ipak I-RT CSC FAU)

                                                                                    Diagnostic Velocity Press Sensor Fail 0 = inactive1 = active Diagnostic Velocity Press Sensor Fail

                                                                                    BI 71 Diagnostic VOM Communications Failure 0 = inactive1 = active Diagnostic VOM Communications Failure

                                                                                    BI 78 Diagnostic VOM Mode A Active 0 = inactive1 = active Diagnostic VOM Mode A Active

                                                                                    BI 79 Diagnostic VOM Mode B Active 0 = inactive1 = active Diagnostic VOM Mode B Active

                                                                                    BI 80 Diagnostic VOM Mode C Active 0 = inactive1 = active Diagnostic VOM Mode C Active

                                                                                    BI 81 Diagnostic VOM Mode D Active 0 = inactive1 = active Diagnostic VOM Mode D Active

                                                                                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                                    Object Identifier(a) Object Name ValueRange Description

                                                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                                                    Object Data Points and Diagnostic Data Points

                                                                                    BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                                                    BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                                                    BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                                                    BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                                                    BI 58 (use Object Identifier for FAU)

                                                                                    Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                                                    (a) BI=Binary Input

                                                                                    Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                                    Object Identifier(a) Object Name ValueRange Description

                                                                                    44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                                    Additional Resources

                                                                                    Additional Resources

                                                                                    Use the following documents and links as additional resources

                                                                                    bull Product support online

                                                                                    bull wwwbacnetorg

                                                                                    bull wwwbacnetassociationorg

                                                                                    bull wwwashraeorg

                                                                                    bull Tracer TU Help online

                                                                                    bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                                                    bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                                                    Note For further assistance contact your local Trane sales office

                                                                                    ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                                                    Glossary

                                                                                    A

                                                                                    ASHRAE

                                                                                    See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                                                    American Society of Heating Refrigeration and Air-

                                                                                    conditioning Engineers

                                                                                    An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                                                    BBACnettrade

                                                                                    See Building Automation Control network

                                                                                    BACnet interoperability building blocks

                                                                                    A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                                                    BACnet object

                                                                                    An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                                                    baud rate

                                                                                    The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                                                    BIBB

                                                                                    See BACnet interoperability building blocks

                                                                                    Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                                                    advocates BACnet protocol for use in system-level control devices

                                                                                    device

                                                                                    A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                                                    Device ID

                                                                                    The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                                                    Iinteroperability

                                                                                    The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                                                    Pprotocol

                                                                                    A set of rules (language) that governs the exchange of data over a digital communications system

                                                                                    S

                                                                                    stand-alone operation

                                                                                    Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                                                    wwwtranecom

                                                                                    For more information contact your local Trane office or e-mail us at comforttranecom

                                                                                    Literature Order Number ACC-SVP01B-EN

                                                                                    Date September 2009

                                                                                    Supersedes ACC-SVP01A-EN

                                                                                    Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                                                    • Table of Contents
                                                                                    • Overview
                                                                                    • Ordering Numbers
                                                                                    • BACnet Protocol
                                                                                    • BCI-I Configuration
                                                                                      • Overview
                                                                                      • Starting a Session of Tracer TU and Direct Connection
                                                                                      • Reset to Factory Default
                                                                                      • IP Units Configuration
                                                                                      • BACnet Object Configuration
                                                                                      • Change Baud Rate
                                                                                      • Change Device ID
                                                                                      • Stand-alone or BAS Operation
                                                                                        • IntelliPak Control Configuration
                                                                                        • BAS Unit Control
                                                                                        • Periodic Update of BAS Values
                                                                                        • BAS Communication Failure
                                                                                          • InputOutput Commands and Calculations
                                                                                            • System Control Command
                                                                                            • Filter Timer Reset Command
                                                                                            • Diagnostics Reset Command
                                                                                            • Setpoint Calculations
                                                                                            • Timestamp Configuration
                                                                                                • BCI IntelliPak Rotary Switches and LEDs
                                                                                                  • Rotary Switches
                                                                                                  • LEDs Description Behavior and Troubleshooting
                                                                                                  • 24 Vac Measurement
                                                                                                  • Ground Measurements
                                                                                                    • BACnet Data Points and Configuration Property Definitions
                                                                                                      • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                                                        • Standardized Device Profile (Annex L)
                                                                                                        • Interoperability Building Blocks (Annex K)
                                                                                                        • Segmentation Capability
                                                                                                        • Object Types
                                                                                                          • BACnet Protocol
                                                                                                            • Data Link Layer Options
                                                                                                            • Device Address Binding
                                                                                                            • Networking Options
                                                                                                            • Character Sets
                                                                                                                • Object Data Points and Diagnostic Data Points
                                                                                                                • Additional Resources
                                                                                                                • Glossary

                                                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 43

                                                                                      Object Data Points and Diagnostic Data Points

                                                                                      BI 82 Diagnostic VOM Mode E Active 0 = inactive1 = active Diagnostic VOM Mode E Active

                                                                                      BI 97 Diagnostic Water Flow Failure 0 = inactive1 = active Diagnostic Water Flow Failure

                                                                                      BI 88 Diagnostic WSM Communications Failure 0 = inactive1 = active Diagnostic WSM Communications Failure

                                                                                      BI 95 Diagnostic WSM MA Temp Sensor Failure 0 = inactive1 = active Diagnostic WSM MA Temp Sensor Failure

                                                                                      BI 58 (use Object Identifier for FAU)

                                                                                      Diagnostic Zone Humidity Sensor Failure 0 = inactive1 = active Diagnostic Zone Humidity Sensor Failure

                                                                                      (a) BI=Binary Input

                                                                                      Table 12 Diagnostic Objects Sorted by Object Name (continued)

                                                                                      Object Identifier(a) Object Name ValueRange Description

                                                                                      44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                                      Additional Resources

                                                                                      Additional Resources

                                                                                      Use the following documents and links as additional resources

                                                                                      bull Product support online

                                                                                      bull wwwbacnetorg

                                                                                      bull wwwbacnetassociationorg

                                                                                      bull wwwashraeorg

                                                                                      bull Tracer TU Help online

                                                                                      bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                                                      bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                                                      Note For further assistance contact your local Trane sales office

                                                                                      ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                                                      Glossary

                                                                                      A

                                                                                      ASHRAE

                                                                                      See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                                                      American Society of Heating Refrigeration and Air-

                                                                                      conditioning Engineers

                                                                                      An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                                                      BBACnettrade

                                                                                      See Building Automation Control network

                                                                                      BACnet interoperability building blocks

                                                                                      A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                                                      BACnet object

                                                                                      An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                                                      baud rate

                                                                                      The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                                                      BIBB

                                                                                      See BACnet interoperability building blocks

                                                                                      Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                                                      advocates BACnet protocol for use in system-level control devices

                                                                                      device

                                                                                      A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                                                      Device ID

                                                                                      The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                                                      Iinteroperability

                                                                                      The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                                                      Pprotocol

                                                                                      A set of rules (language) that governs the exchange of data over a digital communications system

                                                                                      S

                                                                                      stand-alone operation

                                                                                      Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                                                      wwwtranecom

                                                                                      For more information contact your local Trane office or e-mail us at comforttranecom

                                                                                      Literature Order Number ACC-SVP01B-EN

                                                                                      Date September 2009

                                                                                      Supersedes ACC-SVP01A-EN

                                                                                      Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                                                      • Table of Contents
                                                                                      • Overview
                                                                                      • Ordering Numbers
                                                                                      • BACnet Protocol
                                                                                      • BCI-I Configuration
                                                                                        • Overview
                                                                                        • Starting a Session of Tracer TU and Direct Connection
                                                                                        • Reset to Factory Default
                                                                                        • IP Units Configuration
                                                                                        • BACnet Object Configuration
                                                                                        • Change Baud Rate
                                                                                        • Change Device ID
                                                                                        • Stand-alone or BAS Operation
                                                                                          • IntelliPak Control Configuration
                                                                                          • BAS Unit Control
                                                                                          • Periodic Update of BAS Values
                                                                                          • BAS Communication Failure
                                                                                            • InputOutput Commands and Calculations
                                                                                              • System Control Command
                                                                                              • Filter Timer Reset Command
                                                                                              • Diagnostics Reset Command
                                                                                              • Setpoint Calculations
                                                                                              • Timestamp Configuration
                                                                                                  • BCI IntelliPak Rotary Switches and LEDs
                                                                                                    • Rotary Switches
                                                                                                    • LEDs Description Behavior and Troubleshooting
                                                                                                    • 24 Vac Measurement
                                                                                                    • Ground Measurements
                                                                                                      • BACnet Data Points and Configuration Property Definitions
                                                                                                        • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                                                          • Standardized Device Profile (Annex L)
                                                                                                          • Interoperability Building Blocks (Annex K)
                                                                                                          • Segmentation Capability
                                                                                                          • Object Types
                                                                                                            • BACnet Protocol
                                                                                                              • Data Link Layer Options
                                                                                                              • Device Address Binding
                                                                                                              • Networking Options
                                                                                                              • Character Sets
                                                                                                                  • Object Data Points and Diagnostic Data Points
                                                                                                                  • Additional Resources
                                                                                                                  • Glossary

                                                                                        44 ACC-SVP01B-EN bull BCI-I Integration Guide

                                                                                        Additional Resources

                                                                                        Additional Resources

                                                                                        Use the following documents and links as additional resources

                                                                                        bull Product support online

                                                                                        bull wwwbacnetorg

                                                                                        bull wwwbacnetassociationorg

                                                                                        bull wwwashraeorg

                                                                                        bull Tracer TU Help online

                                                                                        bull Tracertrade TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)

                                                                                        bull Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02)

                                                                                        Note For further assistance contact your local Trane sales office

                                                                                        ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                                                        Glossary

                                                                                        A

                                                                                        ASHRAE

                                                                                        See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                                                        American Society of Heating Refrigeration and Air-

                                                                                        conditioning Engineers

                                                                                        An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                                                        BBACnettrade

                                                                                        See Building Automation Control network

                                                                                        BACnet interoperability building blocks

                                                                                        A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                                                        BACnet object

                                                                                        An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                                                        baud rate

                                                                                        The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                                                        BIBB

                                                                                        See BACnet interoperability building blocks

                                                                                        Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                                                        advocates BACnet protocol for use in system-level control devices

                                                                                        device

                                                                                        A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                                                        Device ID

                                                                                        The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                                                        Iinteroperability

                                                                                        The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                                                        Pprotocol

                                                                                        A set of rules (language) that governs the exchange of data over a digital communications system

                                                                                        S

                                                                                        stand-alone operation

                                                                                        Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                                                        wwwtranecom

                                                                                        For more information contact your local Trane office or e-mail us at comforttranecom

                                                                                        Literature Order Number ACC-SVP01B-EN

                                                                                        Date September 2009

                                                                                        Supersedes ACC-SVP01A-EN

                                                                                        Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                                                        • Table of Contents
                                                                                        • Overview
                                                                                        • Ordering Numbers
                                                                                        • BACnet Protocol
                                                                                        • BCI-I Configuration
                                                                                          • Overview
                                                                                          • Starting a Session of Tracer TU and Direct Connection
                                                                                          • Reset to Factory Default
                                                                                          • IP Units Configuration
                                                                                          • BACnet Object Configuration
                                                                                          • Change Baud Rate
                                                                                          • Change Device ID
                                                                                          • Stand-alone or BAS Operation
                                                                                            • IntelliPak Control Configuration
                                                                                            • BAS Unit Control
                                                                                            • Periodic Update of BAS Values
                                                                                            • BAS Communication Failure
                                                                                              • InputOutput Commands and Calculations
                                                                                                • System Control Command
                                                                                                • Filter Timer Reset Command
                                                                                                • Diagnostics Reset Command
                                                                                                • Setpoint Calculations
                                                                                                • Timestamp Configuration
                                                                                                    • BCI IntelliPak Rotary Switches and LEDs
                                                                                                      • Rotary Switches
                                                                                                      • LEDs Description Behavior and Troubleshooting
                                                                                                      • 24 Vac Measurement
                                                                                                      • Ground Measurements
                                                                                                        • BACnet Data Points and Configuration Property Definitions
                                                                                                          • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                                                            • Standardized Device Profile (Annex L)
                                                                                                            • Interoperability Building Blocks (Annex K)
                                                                                                            • Segmentation Capability
                                                                                                            • Object Types
                                                                                                              • BACnet Protocol
                                                                                                                • Data Link Layer Options
                                                                                                                • Device Address Binding
                                                                                                                • Networking Options
                                                                                                                • Character Sets
                                                                                                                    • Object Data Points and Diagnostic Data Points
                                                                                                                    • Additional Resources
                                                                                                                    • Glossary

                                                                                          ACC-SVP01B-EN bull BCI-I Integration Guide 45

                                                                                          Glossary

                                                                                          A

                                                                                          ASHRAE

                                                                                          See American Society of Heating Refrigeration and Air-conditioning Engineers

                                                                                          American Society of Heating Refrigeration and Air-

                                                                                          conditioning Engineers

                                                                                          An international organization of 50000 persons with chapters throughout the world The Society is organized for the sole purpose of advancing the arts and sciences of heating ventilation air conditioning and refrigeration It benefits the public with its research standards writing continuing education and publications

                                                                                          BBACnettrade

                                                                                          See Building Automation Control network

                                                                                          BACnet interoperability building blocks

                                                                                          A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality The BIBBs are grouped together into BACnet device profiles

                                                                                          BACnet object

                                                                                          An abstract representation of the physical point or points where data is input from or output to an IO device Each object may have several BACnet properties that describe the status of that object

                                                                                          baud rate

                                                                                          The number of signaling elements that occur each second during electronic data transmission At slow speeds baud indicates the number of bits per second that are transmitted For example 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps) At higher speeds multiple bits may be encoded with each electrical change For example 4800 baud may allow 9600 bits to be sent each second Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud For example a 9600 bps modem may operate at only 2400 baud

                                                                                          BIBB

                                                                                          See BACnet interoperability building blocks

                                                                                          Building Automation Control network (BACnet and ANSIASHRAE Standard 135-2004)An interoperable protocol developed specifically for the building controls industry The American National Standards Institute named it as a standard and Trane

                                                                                          advocates BACnet protocol for use in system-level control devices

                                                                                          device

                                                                                          A device is a standard BACnet object as defined by ASHRAE Standard 135-2004The Tracer UC800 contains the BACnet object

                                                                                          Device ID

                                                                                          The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302 There cannot be more than one device using the same Device ID Each of the sample applications operate as a device and requires its own device id which defaults to zero

                                                                                          Iinteroperability

                                                                                          The ability to integrate equipment from different vendors into a comprehensive automation and control system In addition digital communications between products designed independently but designed to the same communication standard

                                                                                          Pprotocol

                                                                                          A set of rules (language) that governs the exchange of data over a digital communications system

                                                                                          S

                                                                                          stand-alone operation

                                                                                          Equipment is running in a stand-alone mode when all control is provided by the equipments electronic control system The system controls the building environment to a local set of configuration and setpoint values It monitors the environmental conditions via sensors that are physically wired to the units control system

                                                                                          wwwtranecom

                                                                                          For more information contact your local Trane office or e-mail us at comforttranecom

                                                                                          Literature Order Number ACC-SVP01B-EN

                                                                                          Date September 2009

                                                                                          Supersedes ACC-SVP01A-EN

                                                                                          Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                                                          • Table of Contents
                                                                                          • Overview
                                                                                          • Ordering Numbers
                                                                                          • BACnet Protocol
                                                                                          • BCI-I Configuration
                                                                                            • Overview
                                                                                            • Starting a Session of Tracer TU and Direct Connection
                                                                                            • Reset to Factory Default
                                                                                            • IP Units Configuration
                                                                                            • BACnet Object Configuration
                                                                                            • Change Baud Rate
                                                                                            • Change Device ID
                                                                                            • Stand-alone or BAS Operation
                                                                                              • IntelliPak Control Configuration
                                                                                              • BAS Unit Control
                                                                                              • Periodic Update of BAS Values
                                                                                              • BAS Communication Failure
                                                                                                • InputOutput Commands and Calculations
                                                                                                  • System Control Command
                                                                                                  • Filter Timer Reset Command
                                                                                                  • Diagnostics Reset Command
                                                                                                  • Setpoint Calculations
                                                                                                  • Timestamp Configuration
                                                                                                      • BCI IntelliPak Rotary Switches and LEDs
                                                                                                        • Rotary Switches
                                                                                                        • LEDs Description Behavior and Troubleshooting
                                                                                                        • 24 Vac Measurement
                                                                                                        • Ground Measurements
                                                                                                          • BACnet Data Points and Configuration Property Definitions
                                                                                                            • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                                                              • Standardized Device Profile (Annex L)
                                                                                                              • Interoperability Building Blocks (Annex K)
                                                                                                              • Segmentation Capability
                                                                                                              • Object Types
                                                                                                                • BACnet Protocol
                                                                                                                  • Data Link Layer Options
                                                                                                                  • Device Address Binding
                                                                                                                  • Networking Options
                                                                                                                  • Character Sets
                                                                                                                      • Object Data Points and Diagnostic Data Points
                                                                                                                      • Additional Resources
                                                                                                                      • Glossary

                                                                                            wwwtranecom

                                                                                            For more information contact your local Trane office or e-mail us at comforttranecom

                                                                                            Literature Order Number ACC-SVP01B-EN

                                                                                            Date September 2009

                                                                                            Supersedes ACC-SVP01A-EN

                                                                                            Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice

                                                                                            • Table of Contents
                                                                                            • Overview
                                                                                            • Ordering Numbers
                                                                                            • BACnet Protocol
                                                                                            • BCI-I Configuration
                                                                                              • Overview
                                                                                              • Starting a Session of Tracer TU and Direct Connection
                                                                                              • Reset to Factory Default
                                                                                              • IP Units Configuration
                                                                                              • BACnet Object Configuration
                                                                                              • Change Baud Rate
                                                                                              • Change Device ID
                                                                                              • Stand-alone or BAS Operation
                                                                                                • IntelliPak Control Configuration
                                                                                                • BAS Unit Control
                                                                                                • Periodic Update of BAS Values
                                                                                                • BAS Communication Failure
                                                                                                  • InputOutput Commands and Calculations
                                                                                                    • System Control Command
                                                                                                    • Filter Timer Reset Command
                                                                                                    • Diagnostics Reset Command
                                                                                                    • Setpoint Calculations
                                                                                                    • Timestamp Configuration
                                                                                                        • BCI IntelliPak Rotary Switches and LEDs
                                                                                                          • Rotary Switches
                                                                                                          • LEDs Description Behavior and Troubleshooting
                                                                                                          • 24 Vac Measurement
                                                                                                          • Ground Measurements
                                                                                                            • BACnet Data Points and Configuration Property Definitions
                                                                                                              • BACnet Protocol Implementation Conformance Statement (PICS)
                                                                                                                • Standardized Device Profile (Annex L)
                                                                                                                • Interoperability Building Blocks (Annex K)
                                                                                                                • Segmentation Capability
                                                                                                                • Object Types
                                                                                                                  • BACnet Protocol
                                                                                                                    • Data Link Layer Options
                                                                                                                    • Device Address Binding
                                                                                                                    • Networking Options
                                                                                                                    • Character Sets
                                                                                                                        • Object Data Points and Diagnostic Data Points
                                                                                                                        • Additional Resources
                                                                                                                        • Glossary