DimensionsLength(withoutcasters) 59”Length(withcasters) 74½”Width 353/8”Height(withoutcasters) 52”Height(withcasters) 613/4”UnitWeight 1,400Lbs.

35 Ton Rental Air Handling Unit Unit Performance / Data

GeneralCAT/CLASS XXXX-XXManufacturer SmartFamilyofCoolingProductsUnitModelNumber DDA05Q EquipmentInsuranceValue NADuct/HoseConnections (1)20”Supply/(1)x20”ReturnFilterSize QTY(4)16”x20”FilterType 2”WashableMediaElectricalCertification ETLlistedforUL1995,CSA236STD22.2SinglePointPowerSupply 460V/3PH/60HZConnections SinglepointSeries16Cam-LokconnectionsCoolingAmps 11.6A(460V)HeatingAmps 11.6AUnitMFS 32AGeneratorSize 46kW

For more information, contact: 281.540.2805

35TonRentalAirHandlingUnit

UnitFeatures:

§ DirectdriveHighStaticplenumfanwith10hpTEFCmotor§ Maximumratedstaticpressureof5.6in-wg§ Ratedcoolingairflowof5,000cfmwith100%OutsideAir§ Airflowrangeof2000–5,000cfm§ Hydrophiliccoatedfinsforcooling&hotwatercoil§ Stainlesssteelhardware§ StainlessSteeldrainpan§ PermanentlyinstalleddrainpanP-trap(protectedwithinunitbase)

PackageFeatures:

§ PhasemonitorandIncorrectphaseindicatorlight(red)§ CircuitBreakersonallmotors§ BlowerVFDwithinlinestarterandbypassswitch§ SpeedPotentiometerforBlowerVFDtoadjustspeedfrom30Hzto77Hz§ Fulltubularrentalbasewithforkpockets&tie-downpoints

ü Hot-dippedgalvanized§ CoolingunitmayruninVFDorBYPASSmode§ DuctDoorsfactoryinstalledforallsupply/returnconnections§ Quietoperation

OperationProcedure:

STEP1:Confirmthatcircuitbreaker(3CB)isswitchedONandCONTROLPOWERpilotlight(1PL)islit.• Ifnot,checkphasemonitorrelay(PMR)andemergencystop(ES)button.• IfINCORRECTPHASEpilotlight(2PL)islit,checkPMRforphaserotationandvoltagesetting.STEP2:TurnVFD/OFF/BYPswitch(1SW)torequirebloweroperatingmode.• VFDRUNNINGpilotlight(3PL)litifblowerisstartedusingVFD.• BYPASSRUNNINGpilotlight(5PL)litifblowerisstartedusingbypassstarter.• Checkblowercircuitbreakeroverload(1OL)orVFDstatusifBLOWERTRIPpilotlight(4PL)islit.STEP3:SetblowerrunningspeedusingSPDADJPOT(potentiometer)

Itisthecustomer’sresponsibilitytoalwaysfollowthewrittenoperatinginstructionsoftheunitandmaintainsafeworkpractices

For more information, contact: 281.540.2805

35TonRentalAirHandlingUnitBlowerData:60HZcurvebelow.Unitmaybeoperatedabove60HZinVFDmodewithhigherairflow