YOU ARE DOWNLOADING DOCUMENT

Please tick the box to continue:

Transcript
Page 1: Refrigeration system 2

1

2

REFRIGERATION Refrigeration: The process of cooling a substance and of maintaining it in a temperature below that of the immediate surroundings. Major Uses of Refrigeration: 1. Air Conditioning 2. Food Preservation 3. Removing of heat from substances in chemical, petroleum and petrochemical plants 4. Special applications in the manufacturing and construction industries. TON OF REFRIGERATION

It is the heat equivalent to the melting of 1 ton (2000 lb) of water ice at 0C into liquid at

0C in 24 hours.

min

KJ 211TR

hr

BTU 12,000

24

2000(144)TR

where 144 BTU/lb is the latent heat of fusion of ice CARNOT REFRIGERATION CYCLE: T QR TH Network TL QA S HEAT ADDED (T = C) QA = TH(S1-S4)

QA = TH(S) HEAT REJECTED (T = C) QR = TL (S2-S3)

QR = TL (S)

(S) = (S2-S3) =(S1-S4) NET WORK W = QR - QA

W = (TH - TL)(S) COEFFICIENT OF PERFORMANCE

LH

L

AR

A

A

TT

TCOP

QQ

QCOP

W

QCOP

3

1 4

TH

TL

R

Page 2: Refrigeration system 2

2

where: QA - refrigerating effect or refrigerating capacity QR - heat rejected W - net cycle work VAPOR COMPRESSION CYCLE Components:

Compressor

Condenser

Expansion Valve

Evaporator Processes

Compression, 1 to 2 (S = C)

Heat Rejection, 2 to 3 (T = C)

Expansion, 3 to 4 (S = C)

Heat Addition, 4 to 1 (T = C) P T 2 3 2 3 S = C h = C 4 1 4 1 h S System: COMPRESSOR (S = C)

11'1

k

1k

1

21'1

12

mRTVP

KW 1 -P

P

1)60(k

VkPW

KW 60

)hm(hW

System: CONDENSER (P = C) QR = m(h2-h3) KJ/min System: EXPANSION VALVE (h = C) h3 = h4

evaporator

Condenser

expansion

valve

compressor

1

2 3

4

QA

QR

Page 3: Refrigeration system 2

3

44

44

4

fg

f

hh

hhx

System: EVAPORATOR (P = C)

ionRefrigerat of Tons

211

)hm(hQ

KJ/min )hm(hQ

41

A

41A

DISPLACEMENT VOLUME (For Reciprocating type of compressor) a. For Single Acting

sec

m

4(60)

Nn'LDV

32

D

π

b. For Double Acting without considering piston rod

sec

m

4(60)

Nn'LDV

32

D

c. For Double Acting considering piston rod

sec

m D-2D

4(60)

LNn'V

3

22

D

π

KW PER TON OF REFRIGERATION

Ton

KW

)h-(60)(hTon

KW

41

)h-211(h12

COEFFICIENT OF PERFORMANCE

12

41

A

h-h

h-hCOP

W

QCOP

CUBIC METER/min PER TON OF REFRIGERATION A. For Single Acting

Ton-min

m

)h-4m(h

Nn'LD

Ton-min

m 3

41

23 211π

B. For double acting without considering piston rod

Ton-min

m

)h-4m(h

Nn'LD

Ton-min

m 3

41

23 211(2)π

C. For double acting considering piston rod

Ton-min

m d-2D

)h-4m(h

LNn'

Ton-min

m 3

22

41

3 211π

where; L - length of stroke, m D - diameter of bore, m d - diameter of piston rod, m N - no. of RPM n' - no. of cylinders VOLUMETRIC EFFICIENCY

Page 4: Refrigeration system 2

4

%xηk

100 P

PC - C1

100% xV

1

1

2

v

D

1'

v

where: V1' - volume flow rate at intake, m3/sec VD - displacement volume, m3/sec

v - volumetric efficiency

1 - specific volume, m3/kg

v = [1 + C - C(P2/P1)1/k] x 100% EFFICIENCY A. Compression Efficiency

100% xWork Indicated

Work Idealη

cn

B. Mechanical Efficiency

100% xWorkShaft or Brake

Work Indicatedη

m

C. Compressor Efficiency

cnη

c

c

η

100% xWorkShaft or Brake

Work Idealη

EFFECTS ON OPERATING CONDITIONS A. Effects on Increasing the Vaporizing Temperature P T h S 1. The refrigerating effect per unit mass increases. 2.The mass flow rate per ton decreases 3. The volume flow rate per ton decreases. 4. The COP increases. 5. The work per ton decreases. 6. The heat rejected at the condenser per ton decreases.

Page 5: Refrigeration system 2

5

B. Effects on Increasing the Condensing Temperature P T h S 1. The refrigerating effect per unit mass decreases. 2. The mass flow rate per ton increases. 3. the volume flow rate per ton increases. 4. The COP decreases. 5. The work per ton increases. 6. The heat rejected at the condenser per ton increases. C. Effects of Superheating the Suction Vapor P T h S When superheating produces useful cooling: 1. The refrigerating effect per unit mass increases. 2. The mass flow rate per ton decreases 3. The volume flow rate per ton decreases. 4. The COP increases. 5. The work per ton decreases. When superheating occurs without useful cooling: 1. The refrigerating effect per unit mass remains the same. 2. The mass flow rate per ton remains the same. 3. The volume flow rate per ton increases. 4. The COP decreases. 5. The work per ton decreases. 6. The heat rejected at the condenser per ton increases.

Page 6: Refrigeration system 2

6

D. Effects of Sub-cooling the Liquid P T h S 1. The refrigerating effect per unit mass increases. 2. The mass flow rate per ton decreases. 3. The volume flow rate per ton decreases. 4. The COP increases. 5. The work per ton decreases. 6. The heat rejected at the condenser per ton decreases. LIQUID-SUCTION HEAT EXCHANGER The function of the heat exchanger is: 1. To ensure that no liquid enters the compressor, and 2. To sub-cool the liquid from the condenser to prevent bubbles of vapor from impeding the flow of refrigerant through the expansion valve. QR

W

QA

Page 7: Refrigeration system 2

7

SAMPLE PROBLEMS 1. An air conditioning system of a high rise building has a capacity of 350 KW of refrigeration, uses R-12. The evaporating

and condensing temperature are 0C and 35C, respectively. Determine the following: a) mass of flash gas per kg of refrigerant circulated b) mass of R-12 circulated per second c) volumetric rate of flow under suction conditions d) compression work e) the COP 2. A single cylinder, 6.7 cm x 5.7 cm, R-22 compressor operating at 30 rps indicate a refrigerating capacity of 96.4 KW

and a power requirement of 19.4 KW at an evaporating temperature of 5C and a condensing temperature of 35C. Compute: a) the clearance volumetric efficiency if c = 5% b) the actual volumetric efficiency c)the compression efficiency ACTUAL VAPOR COMPRESSION CYCLE As the refrigerant flows through the system there will be pressure drop in the condenser, evaporator and piping. Heat losses or gains will occur depending on the temperature difference between the refrigerant and the surroundings. Compression will be polytropic with friction and heat transfer instead of isentropic. The actual vapor compression cycle may have some or all of the following items of deviation from the ideal cycle:

Superheating of the vapor in the evaporator Heat gain in the suction line from the surroundings Pressure drop in the suction line due to fluid friction Pressure drop due to wiredrawing at the compressor suction valve. Polytropic compression with friction and heat transfer Pressure drop at the compressor discharge valve. Pressure drop in the delivery line. Heat loss in the delivery line. Pressure drop in the condenser. Sub-cooling of the liquid in the condenser or sub-cooler. Heat gain in the liquid line. Pressure drop in the evaporator.

P1 = 308.6 KPa P2 = 847.7 KPa h1 = 351.48 KJ/kg v1 = 0.0554 m3/kg h2 = 368 KJ/kg h3 = h4 = 233.5 KJ/kg

hf at 0 C = 200 KJ/kg

hg at 0 C = 351.48 KJ/kg

a) 0.22 b) 2.97 kg/sec c) 0.1645 m3/sec d) 49.06 KW e) 7.14

P1 = 584 KPa P2 = 1355 KPa h1 = 407.1 KJ/kg v1 = 40.36 L/kg h2 = 428 KJ/kg

h3 = h4 =243.1 KJ/kg

a) 94.91% b) 65.6%

c) 63.33%

Page 8: Refrigeration system 2

8

condenser

Evaporator

Evaporator

MULTIPRESSURE SYSTEMS A multi-pressure system is a refrigeration system that has two or more Low - Side pressures. The low-side pressure is the pressure of the refrigerant between the expansion valve and the intake of the compressor. A multi-pressure system is distinguished from the single-pressure system, which has but one low-side pressure. Removal of Flash Gas A savings in the power requirement of a refrigeration system results if the flash gas that develops in the throttling process between the condenser and the evaporator is removed and recompressed before complete expansion. The vapor is separated from the liquid by an equipment called the Flash Tank. The separation occurs when the upward speed of the vapor is low enough for the liquid particles to drop back into the tank. Normally, a vapor speed of less than 1 m/sec will provide adequate separation. Inter-cooling Inter-cooling between two stages of compression reduces the work of compression per kg of vapor. Inter-cooling in a refrigeration system can be accomplished with a water-cooled heat exchanger or by using refrigerant. The water-cooled intercooler may be satisfactory for two-stage air compression, but for refrigerant compression the water is not usually cold enough. The alternate method uses the liquid refrigerant from the condenser to do the inter-cooling. Discharge gas from the low stage compressor bubbles through the liquid in the intercooler. Refrigerant leaves the intercooler as saturated vapor. Inter-cooling with liquid refrigerant will usually decrease the total power requirement when ammonia is the refrigerant but not when R-12 or R-22 is used. 2-Evaporators and 1-Compressor

Pressure reducing valve

Page 9: Refrigeration system 2

9

2-Compressors and 1-Evaporator

2-Compressors and 2-Evaporators

HP Compressor

LP Compressor

Condenser

Flash Tank and Intercooler

Evaporator

condenser

HP compressor

HP Evaporator

LP Compressor LP Evaporator

Flash Tank and Intercooler

Page 10: Refrigeration system 2

10

SAMPLE PROBLEMS 1. Calculate the power required by a system of one compressor serving two evaporators.

One evaporator carries a load of 35 KW at 10C and the other at a load of 70 KW at

-5C. A backpressure valve reduces the pressure in the 10C evaporator to that of the

-5C evaporator. The condensing temperature is 37C. The refrigerant is ammonia. What is the COP.

h3 = h4 = h7 = hf at 37C = 375.9 KJ/kg

h5 = h6 = hg at 10C = 1471.6 KJ/kg

h8 = hg at -5C = 1456.2 KJ/kg

by energy balance at 10C evaporator m4 = m5 = m6 = 35/(h5 - h4) = 0.0319 kg/sec

by energy balance at -5C evaporator m7 = m8 = 70/(h8 - h7) = 0.0648 kg/sec by mass and energy balance at the mixing point as shown on figure above m6h6 + m8h8 = m1h1 h1 = 1461.3 KJ/kg from chart, at S1 = S2 to P2 h2 = 1665 KJ/kg W = m1(h2 - h1) = 19.7 KW COP = 35 + 70 19.7 COP = 5.33

2. Calculate the power required in an ammonia system that serves a 210 KW

evaporator at -20C. The system uses two-stage compression with inter-cooling and removal of flash gas. The condensing temperature

is 32C. For minimum work and with perfect inter-cooling, the intermediate pressure P2 is equal to P2 = (P1P4)1/2

m7 = m8 = m1 = m2 Q = m1(h1 - h8) m1 = 0.172 kg/sec by mass and energy balance about the intercooler; m2h2 + m6h6 = m7h7 + m3h3 m3 = 0.208 kg/sec WLP = m1(h2 - h1) = 21.6 KW WHP = m3(h4 - h3) = 31.1 KW W = WHP + WLP

Page 11: Refrigeration system 2

11

CASCADE SYSTEM A cascade system combines two vapor compression units, with the condenser of the low temperature system discharging its heat to the evaporator of the high temperature system. This system can furnish refrigeration for about -100 C. There are two types of a cascade system, the closed cascade condenser and the direct contact heat exchanger. In the closed cascade condenser fluids in the low-pressure and high-pressure may be different, but in the direct contact heat exchanger the same fluid is used throughout the system. CLOSED CASCADE CONDENSER DIRECT CONTACT CONDENSER

Cascade

Condenser

HP Compressor

LP Compressor

Condenser

Evaporator

Condenser

HP Compressor

LP Compressor

Open Type

Cascade Condenser

Evaporator

Page 12: Refrigeration system 2

12

SAMPLE PROBLEMS 1. A cascade refrigerating system uses R-22 in the low-temperature unit and R-12 in the high-

temperature unit. The system develops 28 KW of refrigeration at -40C. the R-12 system

operates at -10C evaporating and 38C condensing temperature. There is a 10C overlap of temperatures in the cascade condenser. Calculate: a) the mass flow rate of R-22 (0.1485 kg/sec) b) the mass flow rate of R-12 (0.305 kg/sec) c) the power required by the R-22 compressor (5.7 KW) d) the power required by the R-12compressor (7.6 KW) h1 = 388.6 KJ/kg h5 = 347.1 KJ/kg h2 = 427 KJ/kg h6 = 372 KJ/kg h3 = h4 = 200 KJ/kg h7 = h8 = 236.5 KJ/kg 2. In a certain refrigeration system for low temperature application, a two stage operation is desirable which employs ammonia system that serves a 30 ton evaporator at -30 C. the system uses a direct contact cascade condenser, and the condenser temperature is 40 C. find the following: a) Sketch the schematic diagram of the system and draw the process on the Ph diagram b) the cascade condenser pressure in KPa for minimum work c) the mass flow rate in the high pressure and low pressure loops in kg/sec d) the total work in KW

Page 13: Refrigeration system 2

13

AIR CYCLE REFRIGERATION

Closed or Dense Air System

Open Air System The air cycle refrigeration system in which a gaseous refrigerant is used throughout the cycle. The compression is accomplished by a reciprocating or a centrifugal compressor as in the vapor-compression system, but condensation and evaporation is replaced by a sensible cooling and heating of the gas. An air cooler is used in place of a condenser and a refrigerator in place of an evaporator. The expansion valve is replaced by an expansion engine or turbine. The air cycle refrigeration system is ideally suited for use in air craft, because it is lighter in weight and requires less space than the vapor-compression cycle. One disadvantage of the air cycle is that it is not as efficient as the vapor-compression cycle. The air cycle refrigeration may be designed an operated either as an open or a closed system as shown above. In the closed or dense-air-system, the air refrigerant is contained within the piping or component parts of the system at all times and with the refrigerator usually maintained at pressures above atmospheric level. In the open system, the refrigerator is an actual space to be cooled with the air expanded to atmospheric pressure, circulated through the cold room and then compressed to the cooler pressure.

Cooler

Expander Compressor

Refrigerator

Cooler

Refrigerator

Page 14: Refrigeration system 2

14

IDEAL AIR REFRIGERATION CYCLE Processes: 1 to 2: Isentropic Compression 2 to 3: Constant Pressure Heat Rejection 3 to 4: Isentropic Expansion 4 to 1: Constant Pressure Heat Absorption Refrigerating Effect QA = mCp(T1-T4) Heat Rejected QR = mCp(T3-T2) Compressor Work

1P

P

k1

VkPW

k

1k

1

211

c

Expander Work

1P

P

k1

VkPW

k

1k

3

433

E

Net Work W = WC - WE

Coefficient of Performance

Work Net

Effect ingRefrigeratCOP

1

2 3

4

P

V

T

S

1

2

3

4

S = C S = C

P = C

P = C

Page 15: Refrigeration system 2

15

t1

m

tf

m

t2

m

SAMPLE PROBLEMS 1. An air cycle refrigeration system operating on a closed cycle is required to produced 50 KW of refrigeration with a cooler pressure of 1550 KPa and a refrigerator pressure of 448 KPa.

Leaving air temperature are 25C for cooler and 5C for the refrigerator. Assuming a theoretical cycle with isentropic compression and expansion, no clearance and no losses. Determine; a) the mass flow rate (0.720 kg/sec) b) the compressor displacement (0.1283 cu.m./sec) c) the expander displacement (0.0964 cu.m./sec d) the COP (2.35)

PRODUCT LOAD Cpa Cpb Q1 Q2 Q3 Q = Q1 + Q2 + Q3 Q - product load Q1 - heat to cool product from t2 to tf Q2 - heat to freeze Q3 - heat to cool product from tf to final storage temperature t2 Q1 = m Cpa (t1 - tf) KJ/min Q2 = mhL KJ/min Q3 = m Cpb (tf - t2) where: m - mass rate in kg/min

t1 - entering temperature in C

tf - freezing temperature in C

t2 - storage temperature in C

Cpa - specific heat above freezing, KJ/kg-C or KJ/kg-K

Cpb - specific heat below freezing, KJ/kg-C or KJ/kg-K hL - latent heat of freezing of product, KJ/kg Q = m [Cpa (t1 - tf) + hL + Cpb (tf - t2)] KJ/min

Tons 211

)]t - (t C h )t - (t [C m Q

2fpbLf1pa

Page 16: Refrigeration system 2

16

SAMPLE PROBLEMS

1. Compute the heat to be removed from 110 kg of lean beef if it were to be cooled from 20C to 4C, after which it is

frozen and cooled to -18C. Specific heat of beef above freezing is given as 3.23 KJ/kg-C, and below freezing is

1.68 KJ/kg-C. Freezing point of beef is -2.2C, and latent heat of fusion is 233 KJ/kg.

Given: m = 110 kg Cpa = 3.23 KJ/kg-C

t1 = 20C Cpb = 1.68 KJ/kg-C

t2 = 4C hL = 233 KJ/kg

tf =-2.2C

t3 = -18C Q = m[Cpa(t1 - t2) + Cpa(t2 - tf) + hL + Cpb(tf - t3)] Q = 36 438 KJ

PREPARED BY: ENGR. YURI G. MELLIZA


Related Documents