Page 1: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

1

26-May-2008NEC Islamabad

Telenor-NEC Microwave Quality Standard

Page 2: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 2

NEC Internal Use OnlyNEC Internal Use Only

2

DateDocument Number

Version Number

Creator Approval Sender Send to;

  16-OCT-07   TP-NEC-QLS   00  NEC

Kawakubo  NEC ISB

Yanagidare GMNEC Kawakubo

   Region

Coordinator

  22-OCT-07   TP-NEC-QLS   01  NEC

Kawakubo  NEC ISB

Yanagidare GMNEC Kawakubo

   Region

Coordinator

  13-DEC-07   TP-NEC-QLS   02  NEC

Glenn Marciano  NEC ISB Kawakubo

NEC Glenn

Marciano    Region

Coordinators

09-June-08 TP-NEC-QLS 03

NEC Gulraiz, Shafique, Zulfiqar, Usman, Attaullah

NEC-ISB

H Ishii AttaullahImplementation,QAQC,O&M

Name of Documentation ;   Telenor-NEC MW Quality Standard

Page 3: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 3

NEC Internal Use OnlyNEC Internal Use Only

3

Safety Guidelines for Equipment Installation

When performing hazardous work or entering potentially hazardous area wear protective equipment, such as safety belt / head or eye protection.

Smoking or open flame are prohibited on operation area.

Properly remove and dispose of all unused hazardous materials.

Comply with hazardous material documentation and reporting requirement.

After using power tool or any other equipment, they must be cleaned and put in storage on daily basis.

Keep all tool within designated work area.

When cutting any kind of material safety glasses must be used .

When handling conducting cable, the cable ends must be taped & insulated.

All accidents on-site must be reported to appropriate personal immediately.

Page 4: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 4

NEC Internal Use OnlyNEC Internal Use Only

4

Indoor Installation Work flow

IDU Installation

Grounding of Equipment

End

IDU Installation

C-node Installation

19" Rack Installation

DDF Installation

Cable layout & Termination

Grounding of Equipment

Labeling of Equipment

DC PDP Installation

Start

End

Page 5: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 5

NEC Internal Use OnlyNEC Internal Use Only

5

Assemble the 19" rack.

Position the rack as per floor plan.

Mark the four holes with two base plates.

Drill the marked hole.

Fix the Rawal bolts.

Installed the rack (Distance from rear wall at least 200mm).

Check the leveling of the rack.

Install the grounding bus bar at upper rear side of 19" rack.

Install the blind panel in front of grounding bus bar.

Separate grounding of 19" rack should be done in shortest possible route.

19" Transmission Rack

Page 6: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 6

NEC Internal Use OnlyNEC Internal Use Only

6

19" Transmission Rack

19” rack with installed equipment 19” rack

Site ID on 19” rack

Blind Panel at front of bus bar

Base plate

Improper installation of bus bar

Page 7: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 7

NEC Internal Use OnlyNEC Internal Use Only

7

• Grounding bus bar at rear of rack

• Grounding for 19" Rack

• Blind panel of grounding bus bar

• Label for IDU

• Label for Power cable

• Link budget

19" Transmission Rack

Page 8: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 8

NEC Internal Use OnlyNEC Internal Use Only

8

Rack grounding

19" Transmission Rack

Page 9: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 9

NEC Internal Use OnlyNEC Internal Use Only

9

DC PDB Installation

DC PDB with 10 branch circuit breakers. DC PDB installation with four screws Grounding of DC PDB. Labeling of branch circuit breakers. Power & grounding cables separately routed. Circuit breaker for IDU & C-Node is 6 amperes.

PDB Grounding

0 VDC

-Ve 48V DC

Branch CB labeled with Far end ID

6 Amps circuit breaker for IDU & C-node

DC PDB Inner viewDC PDB Installation in 19’’ rack

Page 10: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 10

NEC Internal Use OnlyNEC Internal Use Only

10

Rectifier Circuit breakers for NEC Equipment

32 amperes circuit breaker for DC PDB with 5 branch circuit breakers and 60 amperes circuit breaker for DC PDB with 10 branch circuit breakers.

Rectifier CBs for NEC Equipment at out door site Rectifier CBs for NEC Equipment at indoor site

Page 11: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 11

NEC Internal Use OnlyNEC Internal Use Only

11

Indoor Unit Installation

Before installing IDU in 19" rack ,should be retighten the screws of bracket while correcting two brackets to 90º for IDU mount horizontally.

Page 12: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 12

NEC Internal Use OnlyNEC Internal Use Only

12

IDU must be installed with four screw, along with washers. All screws must be securely tighten. All screws must be of same size ( M5 ). IDU must be separately grounded with bus bar. Grounding thimble must be properly crimped. IDU must be labeled with far end ID.

Indoor Unit Installation

Page 13: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 13

NEC Internal Use OnlyNEC Internal Use Only

13

Space between two IDUs

Space between two IDUs must be 1 U* for radiation of heat.

Space between two units will be1 U

*1U = 1.75inches = 44.45mm

Page 14: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 14

NEC Internal Use OnlyNEC Internal Use Only

14

C-Node Installation Unpack and inspect received equipment for any damage and missing material Site preparation as per define layout. Mount C-node sub rack in 19" rack. Fasten the sub rack to the 19" rack with appropriate (M6) screws. Ensure proper length and routing of fiber/E1s cables. Use Flexible pipe for fiber patch cord when laid out of 19" rack .

C-Node tributary/E1 cables arrangement Fiber patch cord Use Flexible pipe for fiber patch cord when laid out of 19" rack .

Page 15: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 15

NEC Internal Use OnlyNEC Internal Use Only

15

DDF Installation

The E1 cable is to be stripped with sufficient length to reach DDF, unused wires to be cut and PVC tape must be used at the ends.

The E1 cable must be arranged and neatly run around the 19" rack to the DDF panel.

No extra cable should be left in side the rack. Grounding of DDF/DDP must be ensured. DDF/DDP should be installed at bottom of rack.

Cable arrangement on DDF panel rear view Cable arrangement on DDF panel front view

Page 16: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 16

NEC Internal Use OnlyNEC Internal Use Only

16

DDF Grounding /Labeling

Ensure Labeling of E1s on the DDF. Hang DDF plan for O&M activity.

E1s patching on DDF

DDF grounding

DDF grounding

Page 17: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 17

NEC Internal Use OnlyNEC Internal Use Only

17

Cable layout &Termination

E1s cable and DC, AC power cable must be run separately along the cable rack as standard rule for cable management.

Use flexible pipe for power cable/ optical fiber patch cords. Use surge arrestor for IF cable. All grounding cable must be of shortest possible length.

Cable layout Flexible pipe for fiber patch cord

Grounding Cable Surge Arrestors

Page 18: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 18

NEC Internal Use OnlyNEC Internal Use Only

18

Cable layout/Termination

NMS & E1s Cable layout

IF cable layout

IDU Power cable

Page 19: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 19

NEC Internal Use OnlyNEC Internal Use Only

19

Cable Color and Size

Application color Dia /size

IDU grounding Yellow - Green 6mm

C-Node grounding Yellow - Green 6mm

DC PDB grounding Yellow - Green 6mm

DDF grounding Yellow - Green 6mm

Surge arrestor grounding Yellow - Green 2.5mm

ODU grounding Yellow - Green 6mm

19“ rack grounding Yellow - Green 10mm

DC PDB Power from rectifier* Red - Black 10mm

IDU DC Power cable Red - Black 1.5mm

C-Node Power cable** Red - Grey 1.5mm

* For sites in MSC the DC PDB power cable is blue, black** Prefabricated power cable with black jacket

Page 20: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 20

NEC Internal Use OnlyNEC Internal Use Only

20

Grounding of Equipment

Page 21: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 21

NEC Internal Use OnlyNEC Internal Use Only

21

Common Rule for Equipment Grounding

Yellow-Green color grounding cable. Should be laid with shortest length. Thimbles must be as per cable size. Use proper crimping tool to crimp the thimble. Grounding resistance less than 10 ohm. Ground connections must be securely tighten. No multiple connections with single point / thimble.

In case there is no point available for the grounding, it should be informed to the TP implementation team.

Grounding of surge arrestors.

Page 22: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 22

NEC Internal Use OnlyNEC Internal Use Only

22

Labeling of equipment

Following equipment labeling is mandatory for effective O&M activity.

19" rack with near end site ID. Each hop with far end site ID. IF cables for main /stand by system. E1s cables . Fiber patch cords for end to end connectivity. Power cables for main/stand by system. Rectifier circuit breaker for NEC equipment. DC PDB branch circuit breaker with far end ID. Surge arrestor for main/stand by system. DC PDB labeling if more than one PDB is installed at the site.

Page 23: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 23

NEC Internal Use OnlyNEC Internal Use Only

23

Outdoor Installation WorkflowOutdoor Installation Workflow

Start

Antenna Mounting

Antenna Offsetting & Assembling

Side Strut Position

Grounding

Labeling

IF Cable Run & Fixing

End

Page 24: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 24

NEC Internal Use OnlyNEC Internal Use Only

24

Antenna offsetting

Page 25: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 25

NEC Internal Use OnlyNEC Internal Use Only

25

Antenna Assembling

Unpack and inspect received equipment for any damage and verify the contents against packing list.

Page 26: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 26

NEC Internal Use OnlyNEC Internal Use Only

26

Antenna Assembling

Assemble the mounting bracket with the antenna Assemble the mounting bracket with the antenna (Different sizes of antenna requires different mounting (Different sizes of antenna requires different mounting brackets, refer to the manual that comes along with the brackets, refer to the manual that comes along with the antenna for details)antenna for details)

Page 27: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 27

NEC Internal Use OnlyNEC Internal Use Only

27

Antenna Assembling

Position the antenna to the mounting bracket then Position the antenna to the mounting bracket then place the mounting screws and tightenplace the mounting screws and tighten

Page 28: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 28

NEC Internal Use OnlyNEC Internal Use Only

28

Antenna AssemblingThere are typical four kind of connection ways There are typical four kind of connection ways

to antennato antenna

1- 1- ODU DirectODU Direct

2- Transducer2- Transducer

3- Flexible 3- Flexible WaveguideWaveguide

4- Hybrid4- Hybrid

Page 29: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 29

NEC Internal Use OnlyNEC Internal Use Only

29

Antenna Mounting

Use enough man power for lifting Use enough man power for lifting and installation of antenna.and installation of antenna.Use rope and pulley for antenna Use rope and pulley for antenna installation. installation.

Take extra care while lifting the big Take extra care while lifting the big size antenna (1.8m) or lifting the size antenna (1.8m) or lifting the antenna to high points.antenna to high points.

Hold the antenna using Rope from Hold the antenna using Rope from down side during the lifting so that down side during the lifting so that antenna do not touch the tower by the antenna do not touch the tower by the wind.wind.

Use proper PPE (Personal Protective Use proper PPE (Personal Protective Equipment) when lifting the antenna.Equipment) when lifting the antenna.

Page 30: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 30

NEC Internal Use OnlyNEC Internal Use Only

30

Take out the ODU from the box, inspect it carefully for any damage.Take out the ODU from the box, inspect it carefully for any damage.

Antenna Mounting with ODU Direct

Page 31: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 31

NEC Internal Use OnlyNEC Internal Use Only

31

Antenna Mounting with ODU Direct

Fix the ODU to the bracket with four screws (tightening torque is 4.0 Fix the ODU to the bracket with four screws (tightening torque is 4.0 N.m +/- 10% recommendation). N.m +/- 10% recommendation). Be careful not to damage the O-ring (Antenna). Be careful not to damage the O-ring (Antenna). Polarization should be according to link plan.Polarization should be according to link plan.

Page 32: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 32

NEC Internal Use OnlyNEC Internal Use Only

32

Antenna Mounting with Transducer

Assemble the antenna, fix the ODU to the bracket by tightening the M6 screws Assemble the antenna, fix the ODU to the bracket by tightening the M6 screws (four locations) & ensure it is firmly fixed. IF connector should be sealed (four locations) & ensure it is firmly fixed. IF connector should be sealed according to standard both from ODU & antenna (Transducer) side.according to standard both from ODU & antenna (Transducer) side.

Page 33: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 33

NEC Internal Use OnlyNEC Internal Use Only

33

Antenna Mounting with Flexible Waveguide

Assemble the antenna, fix the ODU to the bracket by tightening the M6 Assemble the antenna, fix the ODU to the bracket by tightening the M6 screws (four locations) & ensure it is firmly fixed. Waveguide should be screws (four locations) & ensure it is firmly fixed. Waveguide should be sealed according to standard both from ODU & antenna side.sealed according to standard both from ODU & antenna side.

Page 34: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 34

NEC Internal Use OnlyNEC Internal Use Only

34

Antenna Mounting with Hybrid

Assemble the antenna with Hybrid, fix the ODU to the bracket by tightening the Assemble the antenna with Hybrid, fix the ODU to the bracket by tightening the M6 screws (four locations) & ensure it is firmly fixed. IF connector should be M6 screws (four locations) & ensure it is firmly fixed. IF connector should be sealed according to standard both from ODU & antenna (Hybrid) side.sealed according to standard both from ODU & antenna (Hybrid) side.

Page 35: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 35

NEC Internal Use OnlyNEC Internal Use Only

35

Side Strut Position

Antenna Offsetting & Side Strut should be positioned in such a way that there should Antenna Offsetting & Side Strut should be positioned in such a way that there should be a suitable bending radius of IF cable/Waveguide, also the antenna should be free be a suitable bending radius of IF cable/Waveguide, also the antenna should be free to move 25 degrees (Left Offset) or 25 degrees (Right Offset) if requiredto move 25 degrees (Left Offset) or 25 degrees (Right Offset) if required

Page 36: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 36

NEC Internal Use OnlyNEC Internal Use Only

36

IF Cable Run and Fixing

Black UV protect tie-wrap (310×4.3 mm) used to fix IF cable by cross tightens for vertical and horizontal cable run at 1.2m intervals.

The IF cable not to be over tightened to avoid any deformation to IF cable.

1.2m1.2m

Page 37: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 37

NEC Internal Use OnlyNEC Internal Use Only

37

IF Cable Run and Fixing

IF cables installed on horizontal rack; silicon applied at porthole to ensure no water seepage

Page 38: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 38

NEC Internal Use OnlyNEC Internal Use Only

38

IF Cable Run and Fixing

2 meter IF cable loop on tower behind antenna

Page 39: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 39

NEC Internal Use OnlyNEC Internal Use Only

39

Water proofing of WG and IF cable at ODU end

Water proofing with self bonding and again with Plastic (PVC) tape

three layers each.

Page 40: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 40

NEC Internal Use OnlyNEC Internal Use Only

40

Grounding Separate grounding point used for each cable, If no space available at bus bar

then both side of grounding bus bar can be used for two groundings only.

Single point ground termination Two groundings with single point termination

Page 41: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 41

NEC Internal Use OnlyNEC Internal Use Only

41

ODU Grounding

ODU With Separate groundingsODU With Separate groundings

ODU must be separately Grounded with grounding clamp on tower.

Thimbles must be crimped with proper crimping tool.

Up to 0.6m antenna the Cable length will be at least 0.8 meter.Up to 0.6m antenna the Cable length will be at least 0.8 meter.

Ground terminations must be securely tighten at both ends.

Separate clamp for both ODUsSeparate clamp for both ODUs

Up to 1.2m antenna the Cable length will be at least 1meter.Up to 1.2m antenna the Cable length will be at least 1meter.

Thimble Crimping tool

The ODU grounding cable should be as short as possible.The ODU grounding cable should be as short as possible.

Page 42: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 42

NEC Internal Use OnlyNEC Internal Use Only

42

IF Cable Grounding

At Horizontal cable TrayAt Horizontal cable TrayAt vertical cable TrayAt vertical cable Tray

IF cable grounding depends on the height of tower for more than 20 meter height; First grounding will be at vertical cable tray and second will be on horizontal cable tray prior to enter into Roxtec porthole .For less than 20 meter IF grounding will one time on vertical or horizontal cable tray depending on availability of grounding bus bar.

Page 43: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 43

NEC Internal Use OnlyNEC Internal Use Only

43

IF Cable Grounding

Grounding kits must be properly terminated with each IF cable.

Separate grounding point of bus bar should be used for each IF cable.

Water proofing with self bonding followed by PVC tape three layers each time.

Thimble must be crimped with proper crimping tool and securely tighten with grounding bus bar

Black UV protect tie-wrap (310×4.3 mm) used at both ends of grounding kit for each IF cable.

Half of each turn must cover previous turn of tape while wrapping tape on the grounding kits

PVC tape wrappingSelf bonding tape wrapping PVC tape wrapping and black tie on both ends

Page 44: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 44

NEC Internal Use OnlyNEC Internal Use Only

44

Labeling

Antenna Direction Label with Far end Site IDAntenna Direction Label with Far end Site ID

Page 45: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 45

NEC Internal Use OnlyNEC Internal Use Only

45

Labeling

ODU metal label and Direction Tag tied with IF cableODU metal label and Direction Tag tied with IF cable

Page 46: NEC Internal Use Only 1 26-May-2008 NEC Islamabad Telenor-NEC Microwave Quality Standard.

NEC Internal Use Only

Page 46

NEC Internal Use OnlyNEC Internal Use Only

46


Related Documents