65
Torrino assiale ad anello - motore UNEL-MECRing axial roof fans - IEC motor
APPLICATIONS ROOF-AM line is designed to extract large volumes of air in roof installations,without long ducts. For instance: ventilation of industrial buildings (factories,warehouses etc.), stock farms and electrical equipments etc.
RANGE This line consists of 7 sizes with impeller from 500 up to 1000 mm.
ADVANTAGES This line is characterized by the wide round shaped nozzles in both inletand outlet, warranty of reduced noise level and high efficiency. Besidesthese fans allow the effective operation either in exhaust or supply duty.Electric motor is easily accessible for wiring and maintenance operations,manufactured according to international standards assuring reliabilityand the long-term economic recovery of the unit simply repairing orreplacing the motor itself.
CONSTRUCTION Ring casing with double wide round shaped nozzle, and baseresistant to the atmospheric agents.Upper cover in techno-polymer resistant to the atmosphericagents.Protection grid on outlet side in steel rod, manufactured accordingto UNI 9219.Inside protection grid (in lack of shutter or ducts).Impeller with high efficiency airfoil blades. Hub in die-castaluminum alloy. Balancing according to UNI ISO 1940. Variablepitch angle in still position.Asynchronous electric motor, protection IP 55, Class F insulated,service S1, construction according to IEC/EEC (UNEL-MEC)standard.Arrangement 4 (impeller directly coupled to motor shaft).
TECHNICAL SPECIFICATIONS ROOF-AM standard
Conveyed air: clean, not abrasive.Temperature of conveyed air: -20C / +50C.Voltage: three phase version (T) 400V-3Ph.
Single phase version (M) 230V-1Ph.Frequency: 50Hz.Working as exhaust fan.
ACCESSORIES Inlet gravity shutter, only for exhaust fans (GS-RO).Service switch.Outer terminal box (OTB).Support base for corrugate roof covering (SB).Silencer (SIL-RO).Counter base (CB).Inlet grid (PG) mandatory for use in free air.Service switch (SW).
ON REQUEST Intake versions.Versions wi th air f low 100% reversible (ROOF-REV).Versions with three phase double polarity electric motor.Versions with casing and base in stainless steel or aluminum.Explosion proof versions (Roof-AM Atex)Versions with metal sheet cover.
APPLICAZIONII torrini serie ROOF-AM sono destinati ad impieghi in cui necessitanograndi portate daria, in applicazioni a tetto, senza lunghe canalizzazioni.Ad esempio: ventilazione di edifici industriali (stabilimenti, magazzini),allevamenti, sala macchine, ecc.
G A M M ALa serie costituita da 7 grandezze con diametro girante da 500 a1000mm.
PECULIARIT La serie ROOF-AM caratterizzata dalla presenza di imbocchi ad ampioraggio di curvatura, sia all'ingresso che all'uscita dell'aria, i quali garantisconomassima silenziosit ed elevati rendimenti aeraulici, inoltre essi consentonol'efficace utilizzo del torrino come estrattore o come immissore. Il motore facilmente raggiungibile sia per effettuare il primo collegamento elettricosia per esigenze di manutenzione. Il motore costruito seguendo standardinternazionali garantendo cos affidabilit ed a lungo termine un economicorecupero del ventilatore semplicemente riparando o sostituendo il motorestesso.
COSTRUZIONE Convogliatore ad anello con doppio bordo ad ampio raggio dicurvatura e base dancoraggio in lamiera dacciaio, protetta contro
gli agenti atmosferici.Cappello in tecnopolimero resistente agli agenti atmosferici.Rete antivolatile ed antinfortunistica esterna, realizzata a norme
UNI EN 294 in filo dacciaio e protetta contro gli agenti atmosferici.Rete di protezione interna (in assenza di serranda o canalizzazione)Girante ad alto rendimento con pale a profilo alare, ad angolodi calettamento variabile da fermo. Mozzo in fusione d'alluminio.Equilibratura secondo norme UNI ISO 1940.Motore elettrico asincrono a corrente alternata, protezione IP55, isolamento Cl F, servizio S1, costruzione conforme al le specif iche norme IEC/EEC (UNEL-MEC).Esecuzione 4 (accoppiamento diretto con girante a sbalzo).
SPECIFICHE TECNICHE ROOF-AM standard
Aria convogliata: pulita o leggermente polverosa, non abrasiva.Temperatura aria convogliata: -20C / +50CTensione dalimentazione: versione trifase (T) 400V-3Ph
versione monofase (M) 230V-1PhFrequenza: 50Hz.Funzionamento in estrazione.
ACCESSORI Serranda a gravit, solo in estrazione (GS-RO).Interruttore di servizio.Morsettiera esterna (OTB).Basi d'appoggio su coperture ondulate (SB).Silenziatore (SIL-RO).Controbase a murare (CB).Rete lato girante (PG) obbligatoria nellutilizzo a bocca libera.Interruttore di servizio (SW).
A RICHIESTA Versioni per funzionamento in immissione.Versioni con flusso dellaria effettivamente reversibile (ROOF-REV).Versioni con motore elettrico a doppia polarit.Versioni con convogliatore e base in acciaio inossidabile o alluminio.Versioni ATEX (Roof-AM Atex).Versioni con cappello in metallo.
66
ROOF-AMROOF-AM
ROOF-AM PrestazioniPerformances
Modello Portata - Flow rate Pm In max Mot. LpModel (m3/h) (kW) (A) (H) dB(A)
504 T 7.200 0,55 1,6 80 60564 T 10.500 0,75 2 80 61634 T 14.000 1,1 2,8 90S 66
4 poli/poles (1500 rpm) - trifase/three-phase (3Ph-400V 50Hz)
1 mm H2O= 9,8 Pa
Modello Portata - Flow rate Pm In max Mot. LpModel (m3/h) (kW) (A) (H) dB(A)
808B T 16.500 0,75 2,3 100 57908A T 18.800 0,75 2,3 100 57
1008A T 22.500 1,1 3,4 100L 60
8 poli/poles (750 rpm) - trifase/three-phase (3Ph-400V 50Hz)
Modello Portata - Flow rate Pm In max Mot. LpModel (m3/h) (kW) (A) (H) dB(A)
506 T 5.100 0,18 0,7 71 49566 T 6.900 0,25 1 71 52
636A T 9.500 0,37 1,3 80 57636B T 10.500 0,55 1,8 80 59716A T 12.500 0,75 2,2 90S 59716B T 16.000 1,1 3 90 61806 T 20.000 1,5 4 100 62906 T 25.000 1,5 4 100 63
1006 T 30.000 2,2 5 112 66
6 poli/poles (1000 rpm) - trifase/three-phase (3Ph-400V 50Hz)
8.000
16
7.0006.0005.000
2
0
6
4
12
8
10
14
636A
17.000 19.00012.00010.0009.000 15.000
716 A
22.000 24.000 26.000
806
29.000 31.000
906 1006
Q (m3/h)
636 B
716 B
67
6
3
1
4
2
5
6.000 8.000 10.000 12.000
0
13.000 14.000 21.000 23.00016.000 19.000
8
9
908A1008A
Ps (
mm
H2O
)
808B
26.000
Q (m3/h)
504
0
10
4.0003.000 5.000 6.000 12.0007.000 8.000 9.000 14.000 16.000
2
4
6
8
12
14
16
564
634
Q (m3 /h)
Ps (
mm
H2O
)
Ps (
mm
H2O
)
566
506
Le prestazioni indicate nei diagrammi si riferiscono ad aria alla temperatura di 15C ed allaltitudine di O mt s.l.m. , e sono state ottenute in installazioni di tipo C in assenza di reti e accessori .Performance shown in the selection diagrams refer to air at 15C temperature and 0 mt a.s.l. altitude, and they were obtained in installation type C with no grid nor accessories.
ROOF-AM RumorositNoise level
Livello Pressione Sonora Lp dB(A) 6mSound Pressure Level Lp dB(A) 6m
8070605040302010
063 125 250 500 1k 2k 4k 8k Total
Hz
dB(A
)
36
51 5560 61 59 56
51
66
ROOF-AM 1006
8070605040302010
0
dB(A
)
23
43 47 4753 55 49 47
59
ROOF-AM 716 A
63 125 250 500 1k 2k 4k 8k TotalHz
8070605040302010
0
dB(A
)
27
4656 54 54 54 52
44
61
ROOF-AM 564
63 125 250 500 1k 2k 4k 8k TotalHz
8070605040302010
0
dB(A
)
31
4656 57
60 63 5749
66
ROOF-AM 634
63 125 250 500 1k 2k 4k 8k TotalHz
8070605040302010
0
dB(A
)
22
3747 45
51 54 4840
57
ROOF-AM 636 A
63 125 250 500 1k 2k 4k 8k TotalHz
8070605040302010
0
dB(A
)
31
45 4956 55 53 50
45
60
ROOF-AM 1008 A
63 125 250 500 1k 2k 4k 8k TotalHz
8070605040302010
0
dB(A
)
27
42 4651 52 50 47
42
57
ROOF-AM 908 A
63 125 250 500 1k 2k 4k 8k TotalHz
8070605040302010
0
dB(A
)
32
47 5156 57 55 52
47
62
ROOF-AM 806
63 125 250 500 1k 2k 4k 8k TotalHz
8070605040302010
0
dB(A
)
33
48 5257 58 56 53
48
63
ROOF-AM 906
63 125 250 500 1k 2k 4k 8k TotalHz
8070605040302010
0
dB(A
)
46 4853 53 53 53 52 52
60
ROOF-AM 504
63 125 250 500 1k 2k 4k 8k TotalHz
Attenzione: il livello di pressione sonora riferito ad una misurazione onnidirezionale in campo libero a 6 m dal ventilatore con aspirazione canalizzatae mandata libera.Attention: sound pressure level is measured in free field at 6 m from the fan, in any direction, with ducted inlet and free outlet.
8070605040302010
0
dB(A
)
23
43 47 4753 55 49 47
59
ROOF-AM 636 B
63 125 250 500 1k 2k 4k 8k TotalHz
8070605040302010
0
dB(A
)
3337
4751 52 50 47 42
57
ROOF-AM 808 B
63 125 250 500 1k 2k 4k 8k TotalHz
8070605040302010
0
dB(A
)
31
49 5156 57 55 52
47
61
ROOF-AM 716 B
63 125 250 500 1k 2k 4k 8k TotalHz
68
8070605040302010
0
dB(A
)
26 3039
44 45 43 4035
49
ROOF-AM 506
63 125 250 500 1k 2k 4k 8k TotalHz
8070605040302010
0
dB(A
)
2933 42
47 48 46 4338
52
ROOF-AM 566
63 125 250 500 1k 2k 4k 8k TotalHz
Model A B kg*
GS-R0 50-56 690 150 9GS-R0 63-71 805 150 10
GS-R0 80 990 150 13GS-R0 90-100 1160 150 15
Dimensioni in mm/Dimensions in mm(*) Indicativo/Indicative
1 - Cappello/Cover2 - Staffe/Brackets3 - Motore/Motor4 - Rete/Grid5 - Convogliatore/Ring casing6 - Base/Base frame7 - Girante/Impeller8 - Rete (accessorio) obbligatorio per lutilizzo
a bocca liberaGrid (accessory) mandatory for free air
1
2
3
4
5
6
7
8
ROOF-AM DimensioniDimensions
Model A BxB CxC D E F kg*
50 510 760 710 1000 450 10 3856 570 760 710 1000 450 10 4263 640 930 870 1200 500 10 5871 710 930 870 1200 500 10 6780 815 1150 1050 1600 650 12 8590 915 1300 1200 1600 650 12 110100 1015 1300 1200 1600 700 12 140
Dimensioni in mm/Dimensions in mm(*) Indicativo/Indicative
69
BxB
CxC
n4 F
A
D
E
SERRANDE A GRAVIT (GS-RO)Le alette della serranda di gravit si aprono con il movimento dellaria aventilatore acceso e si richiudono per gravit al suo spegnimento evitandodispersioni di calore.
B
A
GRAVITY SHUTTERS (GS-RO)Blades of the shutter are opened by the airflow when the fan is operatingand they shut by gravity when the fan stops, thus avoiding heat waste.
accessori accessories
ROOF-AM AccessoriAccessories
APPLICAZIONILe basi d'appoggio ondulate SB (converse) realizzate in robustavetroresina, sono adatte per l ' installazione dei nostri torrinisu coperture costruite in lastre ondulate, evitando dannosiristagni d'acqua attorno al ventilatore e costose opere murarieo di carpenteria.
V E R S I O N ISBl e SBc: utilizzabile con torrini aventi basamento 930x930 mm(Modelli 63 e 71).
SBr: riduzione da accoppiare con basi SBI e SBc per installazioni torriniaventi basamento 760x760 mm (Modelli 50 e 56).
Le versioni SB possono essere accoppiate a lastre ondulate con pendenzafalda tipo:- SBl/1 10x146: internazionale (passo 146 mm altezza 48 mm)- SBl/2 10x177: Euro (passo 177 mm altezza 51 mm mod.)- SBc: Euro ( passo 177 mm altezza 51 mm e raggio di curvatura lastrapari a 3 metri.
INSTALLAZIONESovrapporre la conversa alla lastra a valle e sottoposizionarla a monte.Sovrapporsi di almeno un'onda e un quarto con le lastre laterali attigue.Verificare di non avere sovraccaricato eccessivamente la conversa.
70
60
60
1250
60
60
1300
177
51
146
48
SBI/1 10x146 SBI/2 10x177177
51
SBc
Basi dappoggio ondulate per torrini/Support bases for roof fans
SBl920x920
Mod. 63/71
170
R3000
2400
SBc
APPLICATIONS The support bases SB (valleys), manufactured in sturdy glass-resin, aresuitable for the installation of our roof fans on overlays built in corrugatedslabs, avoiding detrimental stagnations of water nearby the fan and costlymasonry or carpentry works.
VERSIONS SBl e SBc:to be used with roof fans having bases 930x930 mm (Models63 and 71)
SBr : Adaptor to be coupled with soaker bases SBl and SBc for installationof roof fans having base 760x760 (Models 50, 56 ).
Both versions SBl and SBc are suitable to be coupled to corrugated slabswith pitch slope type:- SBl/1 10x146: International type (pitch 146 mm height 48 mm)- SBl/2 10x177: Euro type (pitch 177 mm height 51mm)- SBc : Euro type (pitch 177 mm height 51 mm) and radius of curvatureof the sheet of 3 meters.
INSTALLATION Overlap the valley to the slab downstream and under-place it upstream.Overlap not less than one and fourth wave with the lateral adjacent slabs.Verify not to have excessively overloaded the valley
SBI - SBc per/for mod. 63-71 SBI - SBc con/with SBr per/for mod. 50-56
SBcSBI
920x920Mod. 63/71
250
1820
10%
SBr 740
ESTERNO/EXTERNAL
635ESTERNO/EXTERNAL
480
945
ESTERNO/EXTERNAL
INTERNO/INTERNAL
46180
425
SBrSB
APPLICAZIONII torrini della serie ROOF-AVE sono destinati ad impieghi in cui si necessitanograndi portate d'aria, in applicazioni a tetto. Ad esempio: ventilazione digrandi edifici industriali, hangar, centrali per la produzione di energia ecc. costituito da un convogliatore, contenente una serranda esterna, sottoil quale viene fissato un ventilatore assiale (serie DUCT-M).
G A M M ALa serie composta da 5 grandezze con diametro girante da 800 a 1250mm.
PECULIARIT La caratteristica principale di questa serie la maggior efficienza rispettoal torrino assiale a flusso orizzontale, dovuta alla minore resistenza dellaserranda rispetto a quella rappresentata dal cappello.
COSTRUZIONE Convogliatore esterno (AVE) costituito da pannelli in lamieracompleto di base, protetta contro gli agenti atmosferici.Serranda a gravit con alette in alluminio.Rete di protezione sulla mandata protetta contro gli agentiatmosferici.Ventilatore assiale serie DUCT-M, protetto dagli agenti atmosferici,girante con pale a profilo alare ad angolo variabile da fermo, intecnopolimero e mozzo in fusione di alluminio. Motore elettricoasincrono a corrente alternata, protezione IP55 classe F, servizioS1, costruzione conforme alle specifiche norme IEC/ EEC (UNELMEC). (Descrizione e caratteristiche tecnico-dimensionali: vedisezione DUCT-M pag.38)Esecuzione 4 (accoppiamento diretto con girante a sbalzo).
ACCESSORI Boccaglio in aspirazione (IN).Silenziatori (SIL-DU).Rete antinfortunistica piana (FPG-DU). (Obbligatorio per lutilizzoa bocca libera).Giunto antivibrante (FC-DIJ).Contro-flangia (CF-DLJ).Morsettiera esterna (OTB).Interruttore di servizio (SW).
A RICHIESTA Versioni con girante con pale in alluminio.
* Fare attenzione al carico di neve che potrebbe impedire luscita dellaria.
APPLICATIONS ROOF-AVE line is designed to extract large volumes of air, in roof installations.For instance: ventilation of big industriai plants, hangars, power plants etc.It consists of an outer casing, containing the gravity shutter, below whicha DUCT-M fan shall be fixed.
RANGE This line consists of 5 sizes with impeller diameter from 800 up to 1250mm.
ADVANTAGES The main characteristic of this line is the higher efficiency ifcompared with the axial roof fan with horizontal discharge, due to the lowerresistance of the gravity shutter compared to the cap.
CONSTRUCTION Outer casing (AVE) with steel sheet panels including base,protected against the atmospheric agents.Gravity shutter with aluminum fins.Outlet protection grid protected against the atmospheric agents.Axial fan series DUCT-M, protected against the atmosphericagents, impeller with airfoil profile blades, variable pitch anglein still position, in techno-polymer and hub in die cast aluminumalloy. Asynchronous three-phase electric motor, protectionIP55 Is. class F, service S1, construction according to IEC/EEC(UNEL MEC). (Descr ip t ion and technica l -d imensionalcharacteristics: see page 38).Arrangement 4 (directly coupled with impeller).
ACCESSORIES Inlet nozzle (IN).Silencers (SIL-DU).Flat protection grid (FPG-DU). (Mandatory for free air).Flexible connection (FC-DU).Counter flange (CF-DUOuter terminal box (OTB).Service switch (SW).
ON REQUEST Versions with die-cast aluminum blades.
* Pay attention to the snow charge that could prevent the air flow.
Torrino assiale a flusso verticaleAxial roof fan vertical discharge
71
ROOF-AVEROOF-AVE
ROOF-AVE DimensioniDimensions
Model AxA B CxC D F800 1180 680 1200 810 50900 1280 750 1380 910 501000 1430 535 1380 1010 501120 1580 600 1530 1130 601250 1760 680 1700 1260 70
Dimensioni in mm/Dimensions in mm(*) Indicativo/Indicative
RETEGRID
CONVOGLIATORE
CASING
SERRANDA
SHUTTER
BASE
BASE
CxC
VENTILATOREVedi: (DUCT-M)
FANSee: (DUCT-M)
B
D
AxA
F
72
Fare riferimento alle prestazioni dei ventilatori DUCT 800-1250 versioni 4e 6 poli. Sottrarre la perdita di carico della serranda pari a circa la met dellapressione dinamica del ventilatore corrispondente.
Refer to the performances of the fans DUCT 800-1250 4 - 6 pole versions.Deduct the pressure loss of the gravity shutter about half of the dynamicpressure of the relevant fan.
RETE (ACCESSORIOobbligatorio per lutilizzo
a bocca libera )
GRID (ACCESSORYmandatory for free air)