Page 1: BOILER PROPORTIONAL FEED WATER SYSTEM - …...Boiler Feed Water Flow = The sum of boiler max. steam capacity and boiler blowdown amounts. Note 2: Boiler pressure difference (bar) the

rev.0519

BOILER PROPORTIONAL FEED WATER SYSTEM

Page 2: BOILER PROPORTIONAL FEED WATER SYSTEM - …...Boiler Feed Water Flow = The sum of boiler max. steam capacity and boiler blowdown amounts. Note 2: Boiler pressure difference (bar) the

BOILER PROPORTIONAL FEED WATER SYSTEM

Level Device KP01 3RBody Stainless SteelElectrodes Staineless Steel Case Aluminium Injection Connection 3/4” BSP Threaded

238 °C Max. Working Temp. Max. Working Pres. 32 bar

PRODUCT FEATURES

Level Control Valve Body Max. Working Temp.Pressure Class Actuator Type ConnectionController

Stevi 35.448-E Premio Plus 5kN 1.0619+N Cast Iron450 °CPN 402.2 KN, 5 KN, 12 KN...FlangedAyvaz ADK-100

It is not possible to read a certain water level in the boiler during steam production by the classical water level indicator. When the steam is produced, the water level is composed of bubbles of steam-water mixture and the water level cannot be detected due to the fact that the water level is in motion. The water level outside the boiler is lower than the actual water level in the boiler. The water level outside the boiler is lower than the actual water level in the boiler. The reason for this is that, the water density is higher at outside level indicator.

Factors affecting the difference between the actual water level and the water level read from the outside indicator:

1- Boiler steam capacity2- Height of boiler level indicator according to the boiler3- Chemical properties of boiler water4- Length of the sensor casing below the water level

The operation of the feed pump and the control of low and high water levels are only possible with the level control sensors immersed in the boiler.

The advantages of systems are:1- Measuring sensors measure the actual level due to their presence in the boiler.2- Self-test level sensors eliminate the need to test the system every day.3- The systems of these sensors are safe because they are composed of moving elements and no maintenance is required.

In modern boilers, level control and feeding of boiler water are carried out with the help of sensitive and safe sensor systems.

BOILER WATER LEVEL

Boiler Water Level

KP01 3R

Capacitive Proportional

Level Electrode

High Alarm

Valve Off

Valve On

Low Alarm

Collector

BOILER

Page 3: BOILER PROPORTIONAL FEED WATER SYSTEM - …...Boiler Feed Water Flow = The sum of boiler max. steam capacity and boiler blowdown amounts. Note 2: Boiler pressure difference (bar) the

BOILER PROPORTIONAL FEED WATER SYSTEM

PROPORTIONAL SYSTEMS

The water level falling at the rate of steam generation is reinforced by a proportionally controlled valve.

The amount of water supplied to the boiler is much less than the amount of water in the boiler, there is no fluctuation in

the amount of steam production and boiler pressure.

Proportional control ensures that the vapor in the boiler is constant at a constant pressure. In this system, the feed pump operates continuously and the unused water is returned to the feed water tank with the by-pass line.

The closing pressure of the actuator to be selected must be at least equal to the pump discharge pressure.

Note 1: Boiler Feed Water Amount (kg/h)Boiler Feed Water Flow = The sum of boiler max. steam capacity and boiler blowdown amounts.

Note 2: Boiler pressure difference (bar) the pressure difference in the valve is the difference between the pump pressure at the maximum flow and the boiler.

SYSTEM SPECIFICATIONS

a) Advantages

• Constant steam flow rate and constant pressure• Efficient operation of the burner• Less thermal stresses in the boiler housing• Low steam humidity• Possibility of a central feed pumping station• Reduced wear and long life on the pump and burner

In this system, the valve is switched on and off and the low alarm levels are controlled via the controller. The controller detects the height of the water in the boiler according to the current intensity from the sensor. Sensors 500-600-900 etc. different lengths.

S K L M N O

KP01

1 2 3 4 5 6 7- + - N L

N

P

1 2 3 4 5 6 7 8 9

24 V

Mak

s. 5

0mA Se

ns�r

Be

slem

esi

NO NC C

veya Lojik ��k���Kontrol, Alarm

Output-3

5A@250V � niversal Proses Giri�iADK-100

! CAT II

RULE � IKI�MODUL�

10 11 12 13 14 15 16 17 18

AKIM � IKI�MODUL�(4-20 mA)

Sigo

rtaN

ot-1

Haberle�meModul�(RS-232(standart)/RS-485(opsiyonel))

Giri�/��k��Mod� l�-1

Giri�/��k��Mod�l�-2

N L(-) (+)

HariciSigorta Not-2

Not

-3

Anahtar�Besleme

100...240V 50/60 Hz

PREMIO - Plus 24 V AC/DC

MBLDC

X68X67

24 V DC

90 v .. 264 V AC, 47...63 Hz127V .. 370V DC

N L- +

G��

N L- +

24 V AC/DC

L0VX51

X52

X59

X60

L

k�rm�z�

mavi

0V12-250V AC12-250V DC -

.

L+

12-250V AC12-250V DC

0V-

L+

3-P

Stop

YinX53

X54

Yin- +

12-250 V AC/DC3-P

0-10 V4-20 mA

Yin

Power Connection Diagram

Page 4: BOILER PROPORTIONAL FEED WATER SYSTEM - …...Boiler Feed Water Flow = The sum of boiler max. steam capacity and boiler blowdown amounts. Note 2: Boiler pressure difference (bar) the

BOILER PROPORTIONAL FEED WATER SYSTEM

3D APPLICATION SAMPLE

Bellow Sealed Valve

The pump in the proportional feed water system operates continuously and sends the required feed water to the boiler. The KP01-3R sends a signal to 3 way motorized valve to open or shutdown signal when not needed. When the boiler reaches the sufficient water level, it sends a shut-off signal to the valve and sends the feed water to the tank by the by-pass line. It is a system that continues in this way continuously. A two-way motorized valve can also be used as an alternative to the replacement of the three-way motorized valve.

Manometer

ADK-100

Safety Valve

Steam Line

Feed Water Tank

By-pass Line

Feed WaterPump

Strainers

MGK-33 MonoblockValve

KP01-3R

3 Way Motorized Valve

Checkvalve

Haci Ayvaz M.E. Dubai/U.A.ETel: +971 563550822

+971 [email protected]

Ayvaz ChinaCixi City/ChinaTel: +86 0574 5897 3851 [email protected]

Ayvaz Kazakhstan LLPAlmaty/KazakhstanTel: +7 (727) 327 97 [email protected]

Ayvaz NIsperih/BulgariaTel: +359 8431 27 32 o ffi [email protected]

Ayvaz SerbiaBelgrad/SerbiaTel: +381 61 658 70 52 [email protected]

ConaCaserta/ItalyTel: +39 0823 187 [email protected]

Ayvaz RussiaMoscow/RussiaTel: +74959951728 [email protected]

Ayvaz GermanyViernheim/GermanyTel: +49 [email protected]

Ayvaz UkraineKiev/Ukraine Tel: +380 44 390 57 57 [email protected]

TricorrWarsaw/PolandTel: [email protected]

Ayvaz BaküBakü/Azerbaijan Tel: +99(455) [email protected]

HEAD OFFICE - FACTORYAtatürk Sanayi Bölgesi Hadımköy Mahallesi Mustafa İnan Caddesi No: 44 Arnavutköy - İSTANBULTel: +90 212 771 01 45 (pbx) | Fax: +90 212 771 47 [email protected] | www.ayvaz.com

2018

- N

on

co

ntr

act

ua

l do

cum

en

t -

Re

pro

du

ctio

n f

orb

idd

en

wit

ho

ut

pri

or

au

tho

riza

tio

n


Related Documents