Approved by: M.E. Warren SHEET NAME: TITLE PAGE & DRAWING INDEX Drawn by: E.A. Datu ISSUE DATES & REVISIONS: DWG NO: 1.00 07/15/15 AS-BUILT WATER SOURCE HEAT PUMP LOOP CONTROL DWG# DESCRIPTION DATE REMARKS 1.00 TITLE PAGE & DRAWING INDEX 07/15/15 2.00 LEGEND, NOTES, SEQUENCE OF OPERATIONS 07/15/15 3.00 BLDG-A (SOUTH) VFD NETWORK 07/15/15 DRAWING INDEX 4.00 CONDENSER WATER SYSTEM LOOP - BLDG-A (SOUTH) 07/15/15 5.00 BLDG-A SOUTH TOWER DDC-32X-1 CONTROLLER WIRING DETAILS 07/15/15 AS-BUILT Water Source Heat Pump Main Loop COOLING WATER LOOP CONTROL AND AUTOMATION SYSTEM
5

Water Source HP Loop_Controls

Apr 12, 2017

Download

Documents

Elenzer Datu
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Water Source HP Loop_Controls

Approved by:M.E. Warren

SHEET NAME:

TITLE PAGE & DRAWING INDEX

Drawn by: E.A. Datu

ISSUE DATES & REVISIONS:

DWG NO:

1.00

07/15/15 AS-BUILT

WATER SOURCE HEAT PUMP LOOP CONTROL

DWG# DESCRIPTION DATE REMARKS

1.00 TITLE PAGE & DRAWING INDEX 07/15/15

2.00 LEGEND, NOTES, SEQUENCE OF OPERATIONS 07/15/15

3.00 BLDG-A (SOUTH) VFD NETWORK 07/15/15

DRAWING INDEX

4.00 CONDENSER WATER SYSTEM LOOP - BLDG-A (SOUTH) 07/15/15

5.00 BLDG-A SOUTH TOWER DDC-32X-1 CONTROLLER WIRING DETAILS 07/15/15

AS-BUILT

Water Source Heat Pump

Main Loop

COOLING WATER LOOP CONTROL AND

AUTOMATION SYSTEM

Page 2: Water Source HP Loop_Controls

Approved by:M.E. Warren

SHEET NAME:

LEGEND/NOTES/SEQUENCE

Drawn by: E.A. Datu

ISSUE DATES & REVISIONS:

DWG NO:

2.00

07/15/15 AS-BUILT

SEQUENCE OF OPERATIONS

BULB TYPE TEMPERATURESENSING ELEMENT

AVERAGING TYPETEMPERATURE SENSING

VAPOR TENSIONTEMPERATURE SENSING

BULB TYPE TEMPERATURE

UNDER SHIELD IN

INSIDE SEPARABLE

AIR PRESSURE GAGE

DRAWING REVISION SYMBOLWITH APPROPRIATE NUMBERUSE NUMBERS 1,2,3-ETC.

CONTINUATION SYMBOLFROM ONE SHEET TOANOTHER USE LETTERS

BULB TYPE TEMPERATURESENSING ELEMENT LOCATED

SENSING ELEMENT LOCATED

BUILDING'SSTRUCTURE HAS TO BE ROMOVED TO GAIN ACCESS TO THE JUNCTION BOX.

INSTRUMENT IDENTIFICATIONNUMBER IN-LINE RESTRICTOR .005" A,B,C,-ETC.

A

DEVICE LEGEND

DRAWING)

PNEUMATIC TUBE TERMINALWITH APPROPRIATE NUMBER

ELECTRICAL WIRETERMINAL WITH APPROPRIATE NUMBER

SPECIAL TERMINALS WITHAPPROPRIATE NUMBER(MUST BE IDENTIFIED ON

ITEM LOCATED INCONTROL PANEL

ITEM LOCATED INMOTOR STARTER

ITEM LOCATED AT AC UNIT

ITEM LOCATED ONPANEL FACE

OPTIONAL LOCATION

IN-LINE RESTRICTOR .007"

1280

TUBE AT 80 PSIG

ELECTRICAL WIRE

CONNECTED LINES OR

CROSSING LINES OR WIRES,NOT CONNECTED

ELECTRIC WIRE IN CONDUIT(STROKES INDICATE NO. OF WIRES)

WIRES

AIR LINE OR

MAIN AIR SUPPLY TUBE

DUAL AI R SUPPLY TUBEAT 15/20 PSIG

HIGH PRESSURE AIR SUPPLY

AT 20 PSIGS20

S15-20

S

7

17

ELEMENT

SOCKET/WELL

I

OUTSIDE AIR

ELEMENT

GENERAL DDC SYSTEM CONTROLS NOTES

DAMPER ANALOG

OUTPUT

STAGED

BINARY OUTPUTS

FAN VOLUME CONTROL

ANALOG OUTPUT

HIGH HUMIDITY

CONTROLLER

PRESSURE INPUTS

OUTDOOR PRESSURE

REFERENCE TIP

SUPPLY AIR STATIC

PRESSURE TIP

ROOM PRESSURE

REFERENCE TIP

AIR FLOW

MEASURING STATION

SUPPLY AIR LOW

STATIC PRESSURE TIP

TS-1M.A.L.L. PS-1

S.P.-H.L.

OUTPUT DEVICES

MOTOR STARTER

BINARY OUTPUT

CONTROL VALVE ANALOG

OUTPUT

HUMIDIFIER CONTROL

VALVE ANALOG OUTPUT

S.F.-C

V-2CHWVLV

NC

H-1HFRVLV

NC

HUMIDITY INPUTS

HE-2R.A.H.

HE-1RM-H

DUCT HUMIDITY

TRANSDUCER

ROOM HUMIDITY

TRANSDUCER

DA-4S.F.-INV

DA-1,3 D-1,3M.A.-DPR

DXC

HC-1H.D.-H.

INPUT DEVICES

ROOM TEMPERATURE

SENSOR

TEMPERATURE SENSOR

WITH SUNSHIELD

B BULB TEMPERATURE

SENSOR

LOW TEMPERATURE

SWITCH

TEMPERATURE SENSOR

WITH WELL

AVERAGING TEMPERATURE

SENSOR

TE-1O.A.T.

TE-4M.A.T.

TE-2HWS-T

TE-2R.A.T.

TEMPERATURE INPUTS

TE-1RM.-T

PT-1O.A.-A.P.

PT-2RM.-S.P.

PS-2S.P.-L.L.

F-2R-F

S.A.-S.P.

SUPPLY AIR HIGH

STATIC PRESSURE TIP

9. THE INSTALLATION OF ANY FIRE ALARM DEVICES AND RELATED EQUIPMENT SHALL BE IN

ACCORDANCEWITH NFPA 72,NFPA 90A, NFPA 101, SBCCI, AND ANY APPLICABLE ANSI STANDARDS.

3. WIRE TYPE FOR ANY 24VDC/AC CIRCUIT SHALL BE 2C/#16/TW/STRANDED/PLENUM.

2. WIRE TYPE FOR ANY 120VAC CIRCUITS SHALL BE #12/THHN.

1. WIRE TYPE FOR THE RS-485 TRANSMISSION. TRUNK SHALL BE 2C/#18/TW/SHD/STRANDED/PLENUM.

7. ALL JUNCTION BOXES SHALL BE MOUNTED IN SUCH A WAY THAT NO PERMANENT PART OF THE

5. ALL WIRE SPLICES NOT CONNECTED TO A DEVICE SHALL BE HOUSED WITHIN A

4. WIRE TYPE FOR CONNECTION TO 10K OHM THERMISTOR TEMPERATURE SENSORS SHALL

8. THE ELECTRICAL INSTALLATION OF EQUIPMENT, CONDUCTORS, AND ALL OTHER RELATED ITEMS

SHALL BE IN ACCORDANCE WITH NFPA 70.

BE 2C/#18/TW/STRANDED/PLENUM.

4"X4"X2-1/8" JUNCTION BOX.

6. ALL JUNCTION BOX COVERS SHALL BE LABELED WITH "DDC CONTROLS SYSTEM".

AS-BUILT

Water Source Heat Pump

Main Loop

COOLING WATER LOOP CONTROL AND

AUTOMATION SYSTEM

Page 3: Water Source HP Loop_Controls

Approved by:M.E. Warren

SHEET NAME:

BLDG-X (SOUTH)VFD NETWORK

Drawn by: E.A. Datu

ISSUE DATES & REVISIONS:

DWG NO:

3.00

07/15/15 AS-BUILT

(NEW NEMA-4 ENCLOSURE)

HOT WATER BOILER

120VAC

TO PACIFIC BEACON LAN/WAN

(COORDINATED)

RS485 (PORT-2)

ROOF

LAN/WAN

(BY OTHERS)

SW-1

CAT5e

EXISTING SIEMENS CONTROL

PANEL

VFD CTP-3

VFD CTP-4

VFD CTF-1

VFD CTF-2

VFD CW-5

VFD CWP-6

TOWER FAN-1

TOWER FAN-2

RECIRC. PUMP-P3

RECIRC. PUMP-P4

SEC. PUMP-P5

SEC. PUMP-P6

E-FLEX

E-FLEX

E-FLEX

E-FLEX

S-FLEX

S-FLEX

BACnet

BACnet

BACnet

BA

Cne

t

BACnet

BA

Cne

t

BACnet

BACnet

BACnet

BACnet

BACnet

BA

Cne

t

B-1

32X - 1

BUILDING – X (SOUTH) VFD NETWORK

BUILDING – A (SOUTH)

TCP/IP

BUILDING-A (SOUTH)

NEW COMPUTROLSDDC CONTROLLER

(MOUNT INSIDE DDC-32X NEMA-4

ENCLOSURE)

AEGIS

(EXISTING)

CAT5e CAT5e CAT5e(BY OTHERS) (BY OTHERS)(BY OTHERS)

COOLING TOWER

CHEMICAL

TREATMENT

CONTROLLER

(FUTURE)

(FUTURE)

(FUTURE)

(FUTURE)

(FUTURE)

(FUTURE) AS-BUILT

OPEN LOOP COOLING TOWER SIDE WSHP & BOILER CLOSED LOOP SIDE

Water Source Heat Pump

Main Loop

COOLING WATER LOOP CONTROL AND

AUTOMATION SYSTEM

Page 4: Water Source HP Loop_Controls

Approved by:M.E. Warren

SHEET NAME:

BLDG-X (SOUTH)CONDENSER WATER

SYSTEM LOOP

Drawn by: E.A. Datu

ISSUE DATES & REVISIONS:

DWG NO:

4.00

07/15/15 AS-BUILT

BUILDING - X CONDENSER WATER SYSTEM LOOP (SOUTH TOWER)

Water Source Heat Pump

Main Loop

BLDG-A (North)

SITE LINKS

BUILDING-B

BUILDING-C

PALMER HALL

COOLING WATER LOOP CONTROL AND

AUTOMATION SYSTEM

CTP-1

CTP-2

CWP-5

CWP-6

HX-1

B-1

VFD CTP-3

VFD CTP-4

psi

Hz SPEED

STATUS

START/STOP

Hz SPEED

STATUS

START/STOP

VFD CTF-1

VFD CTF-2

Hz SPEED

STATUS

START/STOP

Hz SPEED

STATUS

START/STOP

VFD CWP-5

VFD CWP-6

Hz SPEED

STATUS

START/STOP

Hz SPEED

STATUS

START/STOP

STATUS

START/STOP

TS-2

TS-3

TS-4DPT-1

TS-1

TS-HWS

OSA-1

oF

CTF-1 CTF-2

Delta-T

Delta-T

AS-BUILT

Page 5: Water Source HP Loop_Controls

Approved by:M.E. Warren

SHEET NAME:

BLDG-X South DDC-32X-1 CONTROLLER

WIRING DETAILS

Drawn by: E.A. Datu

ISSUE DATES & REVISIONS:

DWG NO:

5.00

AS-BUILT07/15/15

DDC-32X LOOP CONTROLLER WIRING DETAIL (BLDG-A South)

+

+

+

(24VAC) COM

(24VAC) HOT

TO ETHERNET SWITCH

SW-1

9

TR1

BLK

WHT120VAC

BR

-1

5 13C

RJ-45

DPT-1

VFD CT-1 SPEED

VFD CT-1 START/STOP, R-1 (14)

VFD CT-1 START/STOP, R-1 (13)

CT-1 FAN, CS-1 STATUS

CT-1 FAN, CS-1 STATUS

VFD CT-2 START/STOP, R-2 (13)

VFD CT-2 SPEED

VFD CT-2 SPEED

CT-2 FAN, CS-2 STATUS

CT-2 FAN, CS-2 STATUS

BOILER B-1 START/STOP

BOILER B-1 ALARM

BOILER B-1 ALARM

SUPPLY TEMPSH LD

TAPE S HLD

PRIMARY LOOP

TS-1

RETURN TEMPSH LD

TAPE S HLD

PRIMARY LOOP

TS-2

SUPPLY TEMPSH LD

TAPE S HLD

SEC. LOOP

TS-3

14

BOILER, B-1CONTROL PANEL

BOILER

ALARM

BOILER

ENABLE/DISABLE

RH2B-ULDC24V

TB4-8 COM

TB5-7 SIG

TB4-7 COM

TS-1

TS-2

TB5-15 SIG(-)

(+)

4~20mA (TBD)

(24VDC) TB9(+)

CW D/P SENSOR

OSA-1

VFD-P1 SPEED

VFD-P2 START/STOP, R-P2 (13)VFD-P1, CS-3 STATUS

VFD-P2 SPEED

VFD-P2, CS-4 STATUS

START/STOPSPEED

(0~10VDC)(+)

(-)

Tower FanVFD CTF-2

R-2

ENABLE/

DISABLE

VFD

MOTOR

~ ~ ~

Tower FanCS-2 Status

CS-2

~ ~ ~

TB5-6 SIGCT

START/STOPSPEED

(0~10VDC)(+)

(-)

Tower FanVFD CTF-1

R-1

ENABLE/

DISABLE

VFD

MOTOR

~ ~ ~

Tower FanCS-1 Status

CS-1

~ ~ ~

TB5-3 SIGCT

RETURN TEMPSH LD

TAPE S HLD

SEC. LOOP

TS-4

SUPPLY TEMP

100-Ω Pt RTDSH LD

TAPE S HLD

B-1 HOT WATER

531-431A TS-HWS

TS-3

TS-4

TS-HWS

(24VDC) TB9(+)

OUTSIDE AIR SENSOR

DPT-1

OSA-1

START/STOPSPEED

(0~10VDC)(+)

(-)

R-P2

ENABLE/

DISABLE

VFD

MOTOR

~ ~ ~

Circ. PumpCS-4 Status

CS-4

~ ~ ~

TB5-21 SIGCT

START/STOPSPEED

(0~10VDC)(+)

(-)

R-P1

ENABLE/

DISABLE

VFD

MOTOR

~ ~ ~

Circ. PumpCS-3 Status

CS-3

~ ~ ~

TB5-18 SIGCT

Circ. PumpVFD CTP-3

Circ. PumpVFD CTP-4

VFD-P1 START/STOP, R-P1 (13)

START/STOPSPEED

(0~10VDC)(+)

(-)

R-P6

ENABLE/

DISABLE

VFD

MOTOR

~ ~ ~

Sec. PumpCS-6 Status

CS-6

~ ~ ~

TB5-27 SIGCT

START/STOPSPEED

(0~10VDC)(+)

(-)

TB4-22 COM

R-P5

ENABLE/

DISABLE

VFD

MOTOR

~ ~ ~

Sec. PumpCS-5 Status

CS-5

~ ~ ~

TB5-24 SIGCT

Circ. PumpVFD CWP-5

Circ. PumpVFD CWP-6

SPARESPARESPARESPARESPARE

REFER TO VFD NETWORK FOR RESPECTIVE

(BACnet) VFD-COMM CONNECTIONS

8

4

5

1

14

12

13

9

(-)(+)

TB5-22 SIG

TB4-25 COM

8

4

5

1

14

12

13

9

(-)(+)

TB5-25 SIGTB4-19 COM

8

4

5

1

14

12

13

9

(-)(+)

TB5-19 SIG

TB4-16 COM

8

4

5

1

14

12

13

9

(-)(+)

TB5-16 SIG

TB4-4 COM

8

4

5

1

14

12

13

9

(-)(+)

TB5-4 SIG

TB4-1 COM

8

4

5

1

14

12

13

9

(-)(+)

TB5-1 SIG

499Ω

P/N: T-PB-202-0

TS-COM

499Ω

499Ω

499Ω

499Ω

499Ω

100-Ω Pt RTD531-431A

100-Ω Pt RTD531-431A

100-Ω Pt RTD531-431A

100-Ω Pt RTD531-431A

SCREW TO

PANEL FOR GROUND

SH

2B

-05

SO

CK

ET

RH

2B

-ULD

C24

VS

H2

B-0

5 S

OC

KE

TR

H2

B-U

LD

C24

VS

H2B

-05

SO

CK

ET

RH

2B

-ULD

C24

V

SH

2B

-05

SO

CK

ET

RH

2B

-ULD

C24

V

SH

2B

-05

SO

CK

ET

RH

2B

-ULD

C24

V

SH

2B

-05

SO

CK

ET

RH

2B

-ULD

C24

V

100-Ω Pt RTD

499Ω

AS-BUILT

Water Source Heat Pump

Main Loop

COOLING WATER LOOP CONTROL AND

AUTOMATION SYSTEM