4 3 ABBREVIATIONS GENERAL STRUCTURAL NOTES CODE: DESIGN SOIL PRESSURE: REINFORCED CONCRETE: FOOTINGS: BEAMS AND SLABS: GROUT: DRILL-IN ADHESIVE BOLTS: CONCRETE COVER: DRILL-IN EXPANSION BOLTS: STRUCTURAL STEEL: STEEL DECKING: MISCELLANEOUS: SPECIAL INSPECTIONS: ANCHOR RODS: STRUCTURAL OBSERVATION: SHEET INDEX LEGEND SCREW ANCHORS: COLD-FORMED LIGHT GAGE STEEL FRAMING: FOUNDATION PILING: HELICAL PIERS MICROPILES TRANSVERSE STRUCTURAL STEEL TUBING UNLESS OTHERWISE NOTED UNREINFORCED MASONRY ULTRASONIC TEST UNDERWRITERS LABORATORY WEEP HOLE VERTICAL INSIDE FACE VERTICAL OUTSIDE FACE WEST; W SERIES STEEL SHAPE WATERPROOF; WORK POINT WEAKENED PLANE JOINT W SERIES STEEL SHAPE WELDED WIRE FABRIC WEIGHT; STRUCTURAL TEE FROM VERTICAL EACH FACE YARD WITH WIDE; WOOD WITHOUT TRANSV VERTICAL TYPICAL TEMPERATURE; TEMPORARY TOP OF STEEL; TOP OF SLAB TOP OF WALL THREADED TOP OF CONCRETE THICK THROUGH TOP (BEAM AND JOIST DIAMETER; ROUND AND AT FOOT; FEET INCH; INCHES NUMBER; POUND PERPENDICULAR X-SECT CROSS SECTION TOP AND BOTTOM EXTRA STRONG X-STRONG KSF K JT JST IN INT INCL ID IF HORIZ HP HSB HEF GND GR GYP GWB GEN GIRD FT GALV FUT GA FS FTG KIPS PER SQUARE FOOT KIP; KIPS (1000 POUNDS) JOINT JOIST GYPSUM WALL BOARD HORIZONTAL EACH FACE HIGH POINT; HP STEEL SHAPE HIGH STRENGTH BOLT HORIZONTAL INSIDE FACE INCLUDE INTERIOR INSIDE DIAMETER INCH; INCHES FAR SIDE FOOT; FEET FOOTING GAGE; GAUGE GALVANIZED GENERAL GIRDER FUTURE GYPSUM GROUND GRADE FLR FP FIN FF FLG FEMA FDN EXP EXT ENCL ENGR EQUIP EQJ ES EW EQ ELEC ELEV EXJ EL EA EB EF (E) E DP DWG DWL DIA DIAPH DIM DN do DIAG CTSK DEPT DBL DET CTR CU CONC CONN CONSTR CONT CONTR CTJ FEDERAL EMERCENCY MANAGEMENT AGENCY FIREPROOF; FULL PENETRATION EXPANSION EXTERIOR FOUNDATION FAR FACE FLANGE FINISH; FINISHED FLOOR ELECTRICAL ELEVATION (VIEW); ELEVATOR ENCLOSURE ENGINEER EACH FACE EXPANSION BOLT EXPANSION JOINT ELEVATION (HEIGHT) EQUIPMENT EACH SIDE EACH WAY EARTHQUAKE JOINT EQUAL EACH CONTRACTION JOINT DIAMETER DIAGONAL DIAPHRAGM DIMENSION DRAWING EXISTING DOWEL EAST DEEP DOWN DITTO CONCRETE CONNECTION CONSTRUCTION CONTINUOUS CONTRACTOR CENTER COUNTERSUNK CONTROL JOINT; DOUBLE DEPARTMENT DETAIL CUBIC WWF YD WPJ WT W/O WD WH WP W W/ VEF VERT VOF VIF URM UT UON UL TS TYP SPACE; SPACES; SPACING SPECIFICATION STAINLESS STEEL SHORT SLOTTED HOLE STRUCTURAL TEE FROM S SERIES STEEL SHAPE STANDARD STIFFENER STRUCTURAL SUSPENDED SHEAR WALL TOC TOW THD TOS TEMP THK THRU T SUPT SUSP SW SUPPORT STRUCT STIFF STIRR STL STA STD SQ SSL SS ST SPA SPEC SP STATION STEEL STIRRUP SPIRAL SQUARE PARTIAL PENETRATION POUNDS PER SQUARE INCH POLYVINYLCHLORIDE POUNDS PER SQUARE FOOT REFERENCE REINFORCING REQUIRED ROUGH OPENING SHAPE SCHEDULE SHEAR PLATE REINFORCED; REINFORCEMENT; SOUTH; S SERIES STEEL SHORT LEGS BACK TO BACK SHT SLBB SIM SCHED SECT SH PL RO S REINF REQD SECTION SHEET SIMILAR REF R PVC PP PSF PSI PLC(S) PLWD RADIUS PLACE(S) PLYWOOD & BTWN C L COL CMU CJP CLR CG CJ CIP C BLDG BSMT BOT BRG BM B L B AGGR ARCH APPROX ASTM AWS @ ALUM ALT AITC AISC ADDL ACI AB BOTTOM (BEAM AND JOIST SCHEDULES ONLY) CONSTRUCTION JOINT COMPLETE JOINT PENETRATION CONCRETE MASONRY UNIT BETWEEN CENTER LINE COLUMN AMERICAN STANDARD CHANNEL CENTER OF GRAVITY CAST-IN-PLACE CLEAR BUILDING LINE BUILDING BOTTOM BEARING BASEMENT BEAM AMERICAN CONCRETE INSTITUTE STEEL CONSTRUCTION TIMBER CONSTRUCTION ARCHITECT; ARCHITECTURAL AMERICAN SOCIETY FOR TESTING MATERIAL AMERICAN WELDING SOCIETY AGGREGATE ALTERNATE; ALTERNATIVE ALUMINUM AMERICAN INSTITUTE OF AMERICAN INSTITUTE OF APPROXIMATE; APPROXIMATELY ANCHOR BOLT ADDITIONAL MANUFACTURER MFR MANUFACTURING MISCELLANEOUS STRUCTURAL TEE FROM M SERIES STEEL SHAPE MOUNTED NEAR FACE NEAR SIDE ON CENTER NOT IN CONTRACT NOT TO SCALE OUTSIDE FACE OPPOSITE PERPENDICULAR OPTION; OPTIONAL PLATE (STEEL); PROPERTY LINE NS OPNG PERP P/C PL OPP OPT OC OF NTS OA OPENING PRECAST OVERALL MTL No NOM NIC NF MTD MT MFRG MISC MIN METAL NORTH NUMBER NOMINAL MINIMUM LONG LEG BACK TO BACK LONG LEGS HORIZONTAL LONG LEGS VERTICAL LONGITUDINAL LONG SLOTTED HOLES MISCELLANEOUS STEEL SHAPE MASONRY MECHANICAL MACHINE BOLT MEMBRANE MISCELLANEOUS CHANNEL LONGIT MAS MECH MEMB MC MAX MATL MB L LT WT LT LSH MAXIMUM MATERIAL LIGHT STRUCTURAL STEEL ANGLE LB LLBB LLH LLV POUND ABV ABOVE CANT CANTILEVER CLG CEILING COMPOSITE COMP COMPLETE PENETRATION CP DL DEAD LOAD DEMO DEMOLISH; DEMOLITION DEFORMED BAR ANCHOR DBA EXIST EXISTING FIG FIGURE FLAT BAR FB HAS HEADED ANCHOR STUD KSI KIPS PER SQUARE INCH INFO INFORMATION INCORPORATE INC LVL DESIGN LRFD LOAD RESISTANCE FACTOR LL LF LIVE LOAD LINEAL FEET MF MEZZ MEZZANINE MOMENT FRAME OVS OVHD OVERSIZED OVERHEAD OD OUTSIDE DIAMETER PHASE PH PCF POUNDS PER CUBIC FOOT ' " # REM RET RETAINING REMAINDER SLAB ON GRADE SOG SKETCH SK T&B SPECIAL MOMENT RESISTING SMRF FRAME HOLDOWN HD STEEL SHAPE SYMMETRICAL SYMM CDF CONTROL DENSITY FILL ABT ABOUT ADJACENT; ADJUST ADJ (A) ABOVE (AT BEAMS OR COLUMNS) (B) BELOW (AT BEAMS OR COLUMNS) HT HEIGHT HSS HOLLOW STRUCTURAL SECTION ICC INTERNATIONAL CODE COUNCIL IBC INTERNATIONAL BUILDING CODE DESIGN LIVE LOADS: SNOW DRIFT FLOORS PARTITIONS CORRIDORS MECHANICAL FLOORS WIND SEISMIC THE FOLLOWING NOTES APPLY UNLESS INDICATED OTHERWISE: E 1 EQUIVALENT LATERAL FLUID PRESSURE CANTILEVERED WALLS BASEMENT WALL INTERNATIONAL BUILDING CODE, 2006 EDITION. DS D1 O 0 ROOF SNOW LOAD "KWIK BOLT TZ" BY HILTI FASTENING SYSTEMS, "STRONG BOLT" BY SIMPSON STRONG-TIE ANCHOR SYSTEMS OR APPROVED EQUAL. ICC CERTIFICATION REQUIRED. SPECIAL INSPECTION REQUIRED. "HIT HY20" ADHESIVE ANCHOR SYSTEM FOR UNREINFORCED MASONRY OR BRICK WITH CAVITIES; "HIT RE 500-SD" ADHESIVE ANCHOR SYSTEM FOR SOLID MASONRY OR CONCRETE, BY HILTI FASTENING SYSTEMS, "SET XP" HIGH STRENGTH EPOXY FOR SOLID MASONRY OR CONCRETE, BY SIMPSON STRONG-TIE ANCHOR SYSTEMS OR APPROVED EQUAL. ICC CERTIFICATION REQUIRED. SPECIAL INSPECTION REQUIRED. = SEISMIC DESIGN CATEGORY D. I = 1.5, Ss = 1.527, S = 0.523 S = 1.018, S = 0.453 SPECIAL STEEL CONCENTRIC BRACED FRAMES R = 6, = 2, Cd = 5 STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL, CIVIL, ELECTRICAL AND MECHANICAL DRAWINGS FOR BIDDING AND CONSTRUCTION. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS FOR COMPATIBILITY BEFORE PROCEEDING AND NOTIFY THE ARCHITECT AND STRUCTURAL ENGINEER OF ANY DISCREPANCIES. REFER TO ARCHITECTURAL DRAWINGS FOR WALL OPENINGS, ARCHITECTURAL TREATMENT AND DIMENSIONS NOT SHOWN. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR SIZE AND LOCATION OF DUCT OPENINGS, PIPING, CONDUITS, ETC, NOT SHOWN. SHOP DRAWINGS SHALL BE SUBMITTED AND REVIEWED PRIOR TO FABRICATION. PROVIDE TEMPORARY ERECTION BRACING AND SHORING AS REQUIRED FOR STABILITY OF THE STRUCTURE DURING ALL PHASES OF CONSTRUCTION. REFER TO SPECIFICATIONS FOR INFORMATION NOT CONTAINED IN THESE GENERAL NOTES. STRUCTURAL OBSERVATION SHALL BE PROVIDED BY THE STRUCTURAL ENGINEER OF RECORD PER IBC SECTION 1709 FOR GENERAL CONFORMANCE TO THE APPROVED CONSTRUCTION DOCUMENTS AT SIGNIFICANT CONSTRUCTION STAGES AND AT COMPLETION OF THE STRUCTURAL SYSTEM. ALL OBSERVED DEFICIENCIES SHALL BE REPORTED IN WRITING TO THE OWNER'S REPRESENTATIVE AND BUILDING OFFICIAL. THE STRUCTURAL OBSERVER SHALL SUBMIT TO THE BUILDING OFFICIAL A WRITTEN STATEMENT THAT THE SITE VISITS HAVE BEEN MADE AND IDENTIFY REPORTED DEFICIENCIES WHICH, TO THE BEST OF THE STRUCTURAL OBSERVER'S KNOWLEDGE, HAVE NOT BEEN RESOLVED. LIGHT WEIGHT LEVEL M N SCHEDULES ONLY) PROVIDE SPECIAL INSPECTIONS IN ACCORDANCE WITH IBC CHAPTER 17 FOR THE FOLLOWING: HELICAL PIERS FOUNDATION PILING REINFORCED CONCRETE STRUCTURAL WELDING HIGH STRENGTH BOLTING ANCHOR RODS DRILL-IN ADHESIVE BOLTS DRILL-IN EXPANSION BOLTS SCREW ANCHORS FOUNDATION PILES MICROPILES cm CENTIMETER kg KILOGRAM kN KILONEWTON KILOPASCAL kPa MPa MEGAPASCAL Pa PASCAL = 25 PSF (1.196 kN/m ) 2 = ASCE 7-05 = 80 PSF (3.830 kN/m ) 2 = 20 PSF (0.958 kN/m ) 2 = 100 PSF (4.788 kN/m ) 2 = 75 PSF (3.591 kN/m ) + EQUIPMENT WEIGHT 2 = 85 MPH (3 SECOND GUST), EXPOSURE B, qs = 13.2 PSF (0.632 kN/m ), Iw = 1.15 2 mm m METER MILIMETER = 41 PSF (0.200 kN/m ) 2 = 75 PSF (0.367 kN/m ) 2 FOOTINGS 3" (76mm). WALLS EXPOSED TO EARTH OR WEATHER 1 1/2" (38mm) FOR #5 (#16) BARS AND SMALLER, 2" (51mm) FOR #6 (#19) BARS AND LARGER. INTERIOR WALLS 1" (25mm). BEAMS AND COLUMNS 1 1/2" (38mm) TO STIRRUPS OR TIES. SLABS AND JOISTS 1" (25mm). SLABS ON GRADE 1 1/2" (38mm). PROVIDE 2-#5 (2-#16) LONGITUDINAL BOTTOM BARS IN WALL FOOTINGS. PROVIDE CORNER BARS OF SAME SIZE AND NUMBER AT CORNERS AND INTERSECTIONS, LAP 40 DIAMETER EACH LEG. PROVIDE VERTICAL DOWELS OF SAME SIZE, NUMBER AND SPACING AS WALL VERTICAL BARS WITH A 90 DEGREE STANDARD HOOK AT THE BOTTOM OF THE FOOTING. RIGIDLY SUPPORT BARS WITH CONCRETE BLOCKS OR APPROVED ACCESSORIES. PROVIDE #5 (#16) SUPPORT BARS ALL SLABS. WHERE MAIN SLAB BARS ARE PARALLEL TO A SUPPORT, PROVIDE #4 @ 12 (#13 @ 305mm) TOP BARS EXTENDING 2'-0" (610mm) BEYOND EACH FACE OF SUPPORT INTO SLAB. WHERE SLAB IS ON ONE SIDE ONLY, PROVIDE A 90 DEGREE STANDARD HOOK AT DISCONTINUOUS FACE. AT SLAB OPENINGS OVER 12" (305mm) SQUARE, PROVIDE TWO ADDITIONAL BOTTOM MAIN SLAB BARS OR 2-#5 (2-#16) MINIMUM ON ALL FOUR SIDES OF THE OPENING EXTENDING 40 DIAMETER PAST OPENING. PROVIDE 1-#5x4'-0" (1-#16x1219mm) DIAGONAL BOTTOM BAR ALL FOUR CORNERS. PROVIDE SLAB TEMPERATURE BARS AS FOLLOWS: 4" (102mm) SLABS, #3 @ 15 (#10 @ 381mm) BOTTOM, 5" (127mm) SLABS, #4 @ 18 (#13 @ 457mm) BOTTOM, 6" (152mm) SLABS, #4 @ 18 (#13 @ 457mm) BOTTOM, 7" (178mm) SLABS, #4 @ 15 (#13 @ 381mm) BOTTOM, 8" (203mm) SLABS, #3 @ 18 (#10 @ 457mm) TOP, #4 @ 18 (#13 @ 457mm) BOTTOM, 9" (229mm) SLABS, #3 @ 18 (#10 @ 457mm) TOP, #4 @ 18 (#13 @ 457mm) BOTTOM, 10" (254mm) SLABS, #3 @ 16 (#10 @ 406mm) TOP, #4 @ 18 (#13 @ 457mm) BOTTOM, 11" (279mm) SLABS, #4 @ 18 (#13 @ 457mm) TOP, #4 @ 18 (#13 @ 457mm) BOTTOM, 12" (305mm) SLABS, #4 @ 18 (#13 @ 457mm) TOP, #4 @ 18 (#13 @ 457mm) BOTTOM. GROUT - 5000 PSI (35 MPa) MINIMUM 7-DAY CUBE STRENGTH PER ASTM C1157-00. GROUT TO BE PREMIXED, NON-SHRINK "MASTERFLOW 928 GROUT" BY MASTER BUILDERS OR APPROVED EQUAL. ICC CERTIFICATION REQUIRED. USE SPECIFIC GROUT MIX RECOMMENDED BY MANUFACTURER FOR EACH GROUT APPLICATION AND FOLLOW MANUFACTURER'S INSTRUCTIONS. ANCHOR RODS, ASTM F1554, GRADE 36 (250 MPa). SPECIAL INSPECTION REQUIRED. SET ALL ANCHOR RODS BY TEMPLATE. ALL CONCRETE - f'c = 4000 PSI, (30 MPa), MAXIMUM W/C = .44, MINIMUM 6 SACKS OF CEMENT PER CUBIC YARD. SUBMIT MIX DESIGN. SEE SPECIFICATIONS FOR ADMIXTURES. SPECIAL INSPECTION REQUIRED. SEE ARCHITECTURAL DRAWINGS FOR ALL GROOVES, NOTCHES, CHAMFERS, FEATURE STRIPS, COLOR, TEXTURE AND ALL OTHER FINISH DETAILS AT ALL EXPOSED CONCRETE SURFACES, UNLESS OTHERWISE NOTED. PR0VIDE 3/4" (19mm) CHAMFER STRIPS AT ALL EXPOSED CONCRETE EDGES. UNLESS OTHERWISE NOTED, REINFORCING STEEL SHALL CONFORM TO ASTM A615 A615m, GRADE 60 (420mm). SUBMIT REINFORCING STEEL SHOP DRAWINGS WITH DETAILS PER ACI 315 MANUAL OF STANDARD PRACTICE. MECHANICAL AND WELDED SPLICES SHALL MEET THE CRITERIA OF ACI 318-05 SECTION 12.14.3. STAGGER SPLICES OF ADJACENT BARS 2'-0" (610mm) OC. ALL MECHANICAL SPLICES SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ICC CERTIFICATION REQUIRED. ASTM A706/A706M, GRADE 60 (420 MPa), REINFORCING STEEL SHALL BE USED FOR: - WELDED OR FIELD-BENT BARS, WELDED WIRE FABRIC PER ASTM A185. FURNISH IN FLAT SHEETS, NOT ROLLS. LAP EDGES 1 1/2 MESH MINIMUM. ALL STEEL ASTM A992/A992M, Fy = 50 KSI (345 MPa), EXCEPT HOLLOW STRUCTURAL SECTIONS TO BE ASTM A500 GRADE B,Fy = 46 KSI (317 MPa) AND CHANNELS, ANGLES, PLATES AND BARS TO BE ASTM A36/A36M, Fy = 36 KSI (250 MPa). SPECIAL INSPECTION REQUIRED. FABRICATION AND ERECTION PER AISC SPECIFICATIONS. SUBMIT SHOP DRAWINGS. WELDING PER AWS D1.1. MINIMUM SIZE WELDS 3/16" (5mm) CONTINUOUS FILLET. WELDERS CERTIFIED PER WABO FOR ROD AND POSITION. HIGH-STRENGTH BOLTS PER ASTM A325. TYPICAL BOLTED CONNECTIONS - BEARING TYPE. TENSION HIGH-STRENGTH BOLTS BY DIRECT TENSION INDICATOR METHOD USING LOAD INDICATOR WASHERS INSTALLED PER MANUFACTURER'S INSTRUCTIONS OR BY TURN OF THE NUT METHOD. APPLY ONE COAT OF SHOP PAINT TO ALL STEEL EXCEPT FOR SURFACES EMBEDDED IN CONCRETE, AREAS TO BE FIELD WELDED OR SURFACES WITH SPRAY-ON FIREPROOFING. 3000 PSF (143.6 kN/m ) MAX DEAD + LIVE LOAD. SITE CLASS C. 2 CAST FOOTINGS ON COMPACTED STRUCTURAL FILL, 1'-6" (457mm) MINIMUM BELOW FINISHED GRADE CAST SLAB ON GRADE OVER MIN 12" STRUCTURAL FILL. CONSULT SOILS REPORT BY OTTO ROSENAU & ASSOCIATES, INC, DATED APRIL 24, 2008 WITH MAY 1, MAY 12 AND SEPTEMBER 30, 2009 ADDENDUMS, FOR FOUNDATION AND EXCAVATION INFORMATION. SECTION MARK DETAIL MARK REVISION MARK SECTION NUMBER DETAIL NUMBER 2 FOOTING MARK SUB-SECTION MARK DETAIL NUMBER CHANGE OF SLOPE IN TOP OF SLAB SHEET WHERE DETAIL IS DRAWN SHEET WHERE SECTION IS DRAWN STEP IN ELEVATION OF SLAB SUB-SECTION NUMBER 2 SS-5.01 2 B 3A 3A CHANGE OF SLAB THICKNESS 5" (127mm) 5" (127mm) SS-5.01 SS-0.01 GENERAL NOTES, LEGEND AND ABBREVIATIONS SS-1.01 FOUNDATION PLAN SS-1.02 ROOF FRAMING PLAN SS-2.01 BRACED FRAME ELEVATIONS AND DETAILS SS-5.01 FOUNDATION AND PILE CAP DETAILS SS-5.02 STEEL FRAMING DETAILS SS-5.03 STEEL FRAMING DETAILS SS-5.04 COLD-FORMED STEEL FRAMING DETAILS SS-1.03 PENTHOUSE ROOF FRAMING PLAN CONCRETE RESIST A 25 PSF UPLIFT. OVER 3 SPANS MINIMUM. DIAPHRAGM SHEAR CAPACITY - 900PLF. ANCHOR TO SUPPORTS TO ROOF DECKING - "3 x 18 GA N24 TYPE, Imin = 1.330 IN PER FOOT, Smin = 0.689 IN PER FOOT, CONTINUOUS STEEL DECKING DESIGNED, MANUFACTURED AND INSTALLED PER STEEL DECK INSTITUTE SPECIFICATIONS. ICC CERTIFICATION REQUIRED. SUBMIT SHOP DRAWINGS. COMMERCIAL WEIGHT GALVANIZED FINISH ON ALL DECKING. FASTEN ROOF DECK UNITS TO STEEL AT TRANSVERSE, END AND SIDE SUPPORTS WITH 1/2" (13mm) DIAMETER SPOT WELDS AT 18" (305mm) ON CENTER. FASTEN SIDE LAPS OF ADJACENT UNITS WITH DELTAGRIP FASTENING SYSTEM AT 18" (305mm) ON CENTER. PROVIDE ADDITIONAL STEEL REINFORCEMENT AND CLOSURE PIECES AS REQUIRED FOR STRENGTH, CONTINUITY OF DECKING AND SUPPORT OF OTHER WORK. SS-9.01 DEDUCTIVE ALTERNATIVES "TITAN HD" BY SIMPSON STRONG-TIE ANCHOR SYSTEMS OR "HUS-H" BY HILTI FASTENING SYSTEMS, OR APPROVED EQUAL. ICC CERTIFICATION REQUIRED. SPECIAL INSPECTION REQUIRED. ALL COLD-FORMED LIGHT GAGE STEEL FRAMING SHALL CONFORM TO THE ANSI "SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL FRAMING MEMBERS-2001 EDITION" WITH 2004 SUPPLEMENT. ALL 16 GAGE AND HEAVIER COLD-FORMED STRUCTURAL TRACKS, STUDS, JOISTS AND STRAPS SHALL BE FORMED FROM ASTM A446, GRADE D, OR ASTM A570, GRADE E STEEL WITH A MINIMUM Fy = 50 KSI. ALL 18 GAGE AND LIGHTER COLD-FORMED STRUCTURAL TRACKS, STUDS, JOISTS AND STRAPS SHALL BE FORMED FROM ASTM A446, GRADE A, OR ASTM A570, GRADE C STEEL WITH A MINIMUM Fy = 33 KSI. ALL STUDS, TRACKS, JOISTS AND STRAPS SHALL BE GALVANIZED. FASTENINGS SHALL BE AS SHOWN ON THE DRAWINGS. FASTENINGS NOT SHOWN SHALL BE AS RECOMMENDED BY THE MANUFACTURER. STUD OR JOIST SPLICES ARE NOT PERMITTED AND STUD OR JOIST FLANGES ARE NOT TO BE CUT UNDER ANY CIRCUMSTANCES. PROVIDE LATERAL BRACING AT 2'-6" OC FOR ANY STUD WITHOUT GYPSUM WALLBOARD OR SHEATHING ON BOTH FLANGES IN AREAS WITHOUT SUCH WALL COVERINGS. LATERAL SPACING TO BE HORIZONTAL CHANNEL OR CUT TRACK AND STRAP TYPE. WELDING PER AWS D1.3 AND AISI SPECIFICATION. MINIMUM WELDS 1/8" CONTINUOUS FILLET. WELDERS CERTIFIED PER WABO SPECIFICATIONS FOR ROD AND POSITION. STEEL PIPE PILES - 4" DIAMETER STD PIPE, GRADE A53. Fy = 35 KSI (242 MPa) PILE CAPACITY = 10 TONS PER PILE, AS DETERMINED BY OTTO ROSENAU & ASSOCIATES. SPECIAL INSPECTION REQUIRED. CONSULT SOILS REPORT BY OTTO ROSENAU & ASSOCIATES, DATED APRIL 24, 2008, AND SOILS REPORT ADDENDUM DATED MAY 1, 2009 FOR FOUNDATION AND EXCAVATION INFORMATION. SS-9.02 ALTERNATE FOUNDATION AND PILE CAP PLAN SS-9.03 ALTERNATE FOUNDATION AND PILE CAP DETAILS PAF POWDER ACTUATED FASTENER SS5 SQUARE SHAFT HELICAL PIERS MANUFACTURED BY HUBBELL CORPORATION/A.B. CHANCE CO. OR APPROVED EQUAL. ICC CERTIFICATION REQUIRED. PIER CAPACITY = 12.5 TONS PER PIER. PIER UPLIFT CAPACITY = 12.5 TONS PER PIER AS DERTERMINED BY OTTO ROSENAU AND ASSOCIATES. SPECIAL INSPECTION REQUIRED. CONSULT SOILS REPORT BY OTTO ROSENAU AND ASSOCIATES, DATED APRIL 24, 2008 AND SOILS REPORT ADDENDUM DATED MAY 12, 2009 FOR FOUNDATION AND EXCAVATION INFORMATION. TITAN IBO SELF DRILLING, HOLLOW INJECTION GROUTED MICROPILES MANUFACTURED BY ISCHEBECK GMBH OR DYWI DRILL INJECTION PILES MANUFACTURED BY DYWIDAG SYSTEMS INTERNATIONAL. PILE CAPACITY = 12.5 TONS PER PILE. PILE UPLIFT CAPACITY = 12.5 TONS PER PILE AS DETERMINED BY OTTO ROSENAU AND ASSOCIATES. SPECIAL INSPECTION REQUIRED. CONSULT SOILS REPORT BY OTTO ROSENAU AND ASSOCIATES DATED APRIL 24, 2008 AND SOILS REPORT ADDENDUM DATED SEPTEMBER 30, 2009 FOR FOUNDATION AND EXCAVATION INFORMATION. D H e h R Arc itectur , Inc. n R D H ngi E , ng eeri nc. I 601 Union Street | Suite 700 | Seattle, WA 98101 | 206.826.4700 Veterans Affairs Department of MANAGEMENT CONSTRUCTION Date Dwg. of Drawn Project No. DRAWING NO. Project Title Checked Building Number Location Date Name Initials Ch. of Eng. Ch. of Staff Assoc. Dir. Director Submittal Construction For: Approved Approved: Area Project Manager Drawing Title Date BUILDING B100 VA-260-09-IB-0472 06/22/2009 BUILDING IS FULLY SPRINKLERED B100 EMERGENCY EXPANSION AT SEATTLE DIVISION OF VA PUGET SOUND HEALTH CARE SYSTEM 8 9 1 2 3 4 5 6 7 A B C D E F F E D C B 7 6 5 4 3 2 1 9 8 0 6 A three inches = one foot 0 6 2 0 6 2 one inch = one inch one inch = one inch one and one-half inches = one foot one and one-half inches = one foot 6 0 6 0 4 0 one-half inch = equals one foot 4 0 8 4 three-eighths i 0 one-quarter equals one foot three-quarters inch = one foot three-quarters inch = one foot U.S. GOVERNMENT PRINTING OFFICE:1984-440-467 1660 SOUTH COLUMBIAN WAY SEATTLE, WA 98108 VA PUGET SOUND HEALTH CARE SYSTEM - SEATTLE 16 16 8 4 8 4 0 one-eighth inch = one foot Revisions VA FORM 08-6231A,JAN 1990 0 122 GENERAL NOTES, LEGEND, AND ABBREVIATIONS SS-0.01/1 PJK ADW 63 1 1 1 AMMENDMENT 10/12/09 1
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
4 3
ABBREVIATIONS GENERAL STRUCTURAL NOTESCODE:
DESIGN SOIL PRESSURE:
REINFORCED CONCRETE:
FOOTINGS:
BEAMS AND SLABS:
GROUT:
DRILL-IN ADHESIVE BOLTS:
CONCRETE COVER:
DRILL-IN EXPANSION BOLTS:
STRUCTURAL STEEL:
STEEL DECKING:
MISCELLANEOUS:
SPECIAL INSPECTIONS:
ANCHOR RODS:
STRUCTURAL OBSERVATION:
SHEET INDEX
LEGEND
SCREW ANCHORS:
COLD-FORMED LIGHT GAGE STEEL FRAMING:
FOUNDATION PILING:
HELICAL PIERS
MICROPILESTRANSVERSESTRUCTURAL STEEL TUBING
UNLESS OTHERWISE NOTEDUNREINFORCED MASONRYULTRASONIC TEST
"KWIK BOLT TZ" BY HILTI FASTENING SYSTEMS, "STRONG BOLT" BY SIMPSON STRONG-TIE ANCHOR SYSTEMS OR APPROVED EQUAL. ICC CERTIFICATION REQUIRED. SPECIAL INSPECTION REQUIRED.
"HIT HY20" ADHESIVE ANCHOR SYSTEM FOR UNREINFORCED MASONRY OR BRICK WITH CAVITIES; "HIT RE 500-SD" ADHESIVE ANCHOR SYSTEM FOR SOLID MASONRY OR CONCRETE, BY HILTI FASTENING SYSTEMS, "SET XP" HIGH STRENGTH EPOXY FOR SOLID MASONRY OR CONCRETE, BY SIMPSON STRONG-TIE ANCHOR SYSTEMS OR APPROVED EQUAL. ICC CERTIFICATION REQUIRED. SPECIAL INSPECTION REQUIRED.
= SEISMIC DESIGN CATEGORY D. I = 1.5, Ss = 1.527, S = 0.523 S = 1.018, S = 0.453 SPECIAL STEEL CONCENTRIC BRACED FRAMES R = 6, = 2, Cd = 5
STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL, CIVIL,ELECTRICAL AND MECHANICAL DRAWINGS FOR BIDDING AND CONSTRUCTION. CONTRACTORSHALL VERIFY ALL DIMENSIONS AND CONDITIONS FOR COMPATIBILITY BEFORE PROCEEDINGAND NOTIFY THE ARCHITECT AND STRUCTURAL ENGINEER OF ANY DISCREPANCIES.
REFER TO ARCHITECTURAL DRAWINGS FOR WALL OPENINGS, ARCHITECTURAL TREATMENT ANDDIMENSIONS NOT SHOWN.
REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR SIZE AND LOCATION OF DUCTOPENINGS, PIPING, CONDUITS, ETC, NOT SHOWN.
SHOP DRAWINGS SHALL BE SUBMITTED AND REVIEWED PRIOR TO FABRICATION.
PROVIDE TEMPORARY ERECTION BRACING AND SHORING AS REQUIRED FOR STABILITY OF THESTRUCTURE DURING ALL PHASES OF CONSTRUCTION.
REFER TO SPECIFICATIONS FOR INFORMATION NOT CONTAINED IN THESE GENERAL NOTES.
STRUCTURAL OBSERVATION SHALL BE PROVIDED BY THE STRUCTURAL ENGINEER OF RECORDPER IBC SECTION 1709 FOR GENERAL CONFORMANCE TO THE APPROVED CONSTRUCTIONDOCUMENTS AT SIGNIFICANT CONSTRUCTION STAGES AND AT COMPLETION OF THE STRUCTURALSYSTEM.
ALL OBSERVED DEFICIENCIES SHALL BE REPORTED IN WRITING TO THE OWNER'S REPRESENTATIVEAND BUILDING OFFICIAL. THE STRUCTURAL OBSERVER SHALL SUBMIT TO THE BUILDING OFFICIALA WRITTEN STATEMENT THAT THE SITE VISITS HAVE BEEN MADE AND IDENTIFY REPORTEDDEFICIENCIES WHICH, TO THE BEST OF THE STRUCTURAL OBSERVER'S KNOWLEDGE, HAVE NOTBEEN RESOLVED.
LIGHT WEIGHTLEVEL
M
N
SCHEDULES ONLY)
PROVIDE SPECIAL INSPECTIONS IN ACCORDANCE WITH IBC CHAPTER 17 FOR THE FOLLOWING:
HELICAL PIERS FOUNDATION PILING REINFORCED CONCRETE STRUCTURAL WELDING HIGH STRENGTH BOLTING ANCHOR RODS DRILL-IN ADHESIVE BOLTS DRILL-IN EXPANSION BOLTS SCREW ANCHORS FOUNDATION PILES MICROPILES
FOOTINGS 3" (76mm). WALLS EXPOSED TO EARTH OR WEATHER 1 1/2" (38mm) FOR #5 (#16) BARS AND SMALLER, 2" (51mm) FOR #6 (#19) BARS AND LARGER. INTERIOR WALLS 1" (25mm). BEAMS AND COLUMNS 1 1/2" (38mm) TO STIRRUPS OR TIES. SLABS AND JOISTS 1" (25mm). SLABS ON GRADE 1 1/2" (38mm).
PROVIDE 2-#5 (2-#16) LONGITUDINAL BOTTOM BARS IN WALL FOOTINGS. PROVIDE CORNER BARS OF SAME SIZE AND NUMBER AT CORNERS AND INTERSECTIONS, LAP 40 DIAMETER EACH LEG. PROVIDE VERTICAL DOWELS OF SAME SIZE, NUMBER AND SPACING AS WALL VERTICAL BARS WITH A 90 DEGREE STANDARD HOOK AT THE BOTTOM OF THE FOOTING.
RIGIDLY SUPPORT BARS WITH CONCRETE BLOCKS OR APPROVED ACCESSORIES. PROVIDE #5 (#16) SUPPORT BARS ALL SLABS.
WHERE MAIN SLAB BARS ARE PARALLEL TO A SUPPORT, PROVIDE #4 @ 12 (#13 @ 305mm) TOP BARS EXTENDING 2'-0" (610mm) BEYOND EACH FACE OF SUPPORT INTO SLAB. WHERE SLAB IS ON ONE SIDE ONLY, PROVIDE A 90 DEGREE STANDARD HOOK AT DISCONTINUOUS FACE.
AT SLAB OPENINGS OVER 12" (305mm) SQUARE, PROVIDE TWO ADDITIONAL BOTTOM MAIN SLAB BARS OR 2-#5 (2-#16) MINIMUM ON ALL FOUR SIDES OF THE OPENING EXTENDING 40 DIAMETER PAST OPENING. PROVIDE 1-#5x4'-0" (1-#16x1219mm) DIAGONAL BOTTOM BAR ALL FOUR CORNERS.
GROUT - 5000 PSI (35 MPa) MINIMUM 7-DAY CUBE STRENGTH PER ASTM C1157-00. GROUT TO BE PREMIXED, NON-SHRINK "MASTERFLOW 928 GROUT" BY MASTER BUILDERS OR APPROVED EQUAL. ICC CERTIFICATION REQUIRED. USE SPECIFIC GROUT MIX RECOMMENDED BY MANUFACTURER FOR EACH GROUT APPLICATION AND FOLLOW MANUFACTURER'S INSTRUCTIONS.
ANCHOR RODS, ASTM F1554, GRADE 36 (250 MPa). SPECIAL INSPECTION REQUIRED. SET ALL ANCHOR RODS BY TEMPLATE.
ALL CONCRETE - f'c = 4000 PSI, (30 MPa), MAXIMUM W/C = .44, MINIMUM 6 SACKS OF CEMENTPER CUBIC YARD. SUBMIT MIX DESIGN. SEE SPECIFICATIONS FOR ADMIXTURES.SPECIAL INSPECTION REQUIRED.
SEE ARCHITECTURAL DRAWINGS FOR ALL GROOVES, NOTCHES, CHAMFERS, FEATURE STRIPS,COLOR, TEXTURE AND ALL OTHER FINISH DETAILS AT ALL EXPOSED CONCRETE SURFACES,UNLESS OTHERWISE NOTED. PR0VIDE 3/4" (19mm) CHAMFER STRIPS AT ALL EXPOSEDCONCRETE EDGES.
UNLESS OTHERWISE NOTED, REINFORCING STEEL SHALL CONFORM TO ASTM A615 A615m,GRADE 60 (420mm). SUBMIT REINFORCING STEEL SHOP DRAWINGS WITH DETAILS PER ACI 315MANUAL OF STANDARD PRACTICE.
MECHANICAL AND WELDED SPLICES SHALL MEET THE CRITERIA OF ACI 318-05 SECTION 12.14.3.STAGGER SPLICES OF ADJACENT BARS 2'-0" (610mm) OC. ALL MECHANICAL SPLICES SHALL BEINSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ICC CERTIFICATIONREQUIRED.
ASTM A706/A706M, GRADE 60 (420 MPa), REINFORCING STEEL SHALL BE USED FOR:- WELDED OR FIELD-BENT BARS,
WELDED WIRE FABRIC PER ASTM A185. FURNISH IN FLAT SHEETS, NOT ROLLS. LAP EDGES1 1/2 MESH MINIMUM.
ALL STEEL ASTM A992/A992M, Fy = 50 KSI (345 MPa), EXCEPT HOLLOW STRUCTURAL SECTIONS TOBE ASTM A500 GRADE B,Fy = 46 KSI (317 MPa) AND CHANNELS, ANGLES, PLATES AND BARS TO BEASTM A36/A36M, Fy = 36 KSI (250 MPa). SPECIAL INSPECTION REQUIRED. FABRICATION ANDERECTION PER AISC SPECIFICATIONS. SUBMIT SHOP DRAWINGS.
WELDING PER AWS D1.1. MINIMUM SIZE WELDS 3/16" (5mm) CONTINUOUS FILLET. WELDERSCERTIFIED PER WABO FOR ROD AND POSITION.
HIGH-STRENGTH BOLTS PER ASTM A325. TYPICAL BOLTED CONNECTIONS -BEARING TYPE. TENSION HIGH-STRENGTH BOLTS BY DIRECT TENSION INDICATORMETHOD USING LOAD INDICATOR WASHERS INSTALLED PER MANUFACTURER'SINSTRUCTIONS OR BY TURN OF THE NUT METHOD.
APPLY ONE COAT OF SHOP PAINT TO ALL STEEL EXCEPT FOR SURFACESEMBEDDED IN CONCRETE, AREAS TO BE FIELD WELDED OR SURFACES WITHSPRAY-ON FIREPROOFING.
3000 PSF (143.6 kN/m ) MAX DEAD + LIVE LOAD. SITE CLASS C.2
CAST FOOTINGS ON COMPACTED STRUCTURAL FILL, 1'-6" (457mm) MINIMUM BELOW FINISHED GRADE CASTSLAB ON GRADE OVER MIN 12" STRUCTURAL FILL. CONSULT SOILS REPORT BY OTTO ROSENAU & ASSOCIATES, INC,DATED APRIL 24, 2008 WITH MAY 1, MAY 12 AND SEPTEMBER 30, 2009 ADDENDUMS, FOR FOUNDATION AND EXCAVATIONINFORMATION.
SECTION MARK
DETAIL MARK
REVISION MARK
SECTION NUMBER
DETAIL NUMBER
2
FOOTING MARK
SUB-SECTION MARK
DETAIL NUMBER
CHANGE OF SLOPE INTOP OF SLAB
SHEET WHERE DETAILIS DRAWN
SHEET WHERE SECTIONIS DRAWN
STEP IN ELEVATIONOF SLAB
SUB-SECTIONNUMBER
2SS-5.01
2
B
3A 3A
CHANGE OF SLABTHICKNESS
5" (127mm)
5" (1
27m
m)
SS-5.01
SS-0.01 GENERAL NOTES, LEGEND AND ABBREVIATIONS
SS-1.01 FOUNDATION PLAN
SS-1.02 ROOF FRAMING PLAN
SS-2.01 BRACED FRAME ELEVATIONS AND DETAILS
SS-5.01 FOUNDATION AND PILE CAP DETAILS
SS-5.02 STEEL FRAMING DETAILS
SS-5.03 STEEL FRAMING DETAILS
SS-5.04 COLD-FORMED STEEL FRAMING DETAILS
SS-1.03 PENTHOUSE ROOF FRAMING PLAN
CONCRETE
RESIST A 25 PSF UPLIFT.OVER 3 SPANS MINIMUM. DIAPHRAGM SHEAR CAPACITY - 900PLF. ANCHOR TO SUPPORTS TOROOF DECKING - "3 x 18 GA N24 TYPE, Imin = 1.330 IN PER FOOT, Smin = 0.689 IN PER FOOT, CONTINUOUS
STEEL DECKING DESIGNED, MANUFACTURED AND INSTALLED PER STEEL DECK INSTITUTESPECIFICATIONS. ICC CERTIFICATION REQUIRED. SUBMIT SHOP DRAWINGS. COMMERCIALWEIGHT GALVANIZED FINISH ON ALL DECKING.
FASTEN ROOF DECK UNITS TO STEEL AT TRANSVERSE, END AND SIDE SUPPORTS WITH1/2" (13mm) DIAMETER SPOT WELDS AT 18" (305mm) ON CENTER. FASTEN SIDE LAPS OFADJACENT UNITS WITH DELTAGRIP FASTENING SYSTEM AT 18" (305mm) ON CENTER.
PROVIDE ADDITIONAL STEEL REINFORCEMENT AND CLOSURE PIECES AS REQUIRED FORSTRENGTH, CONTINUITY OF DECKING AND SUPPORT OF OTHER WORK.
SS-9.01 DEDUCTIVE ALTERNATIVES
"TITAN HD" BY SIMPSON STRONG-TIE ANCHOR SYSTEMS OR "HUS-H" BY HILTI FASTENING SYSTEMS, OR APPROVED EQUAL. ICC CERTIFICATION REQUIRED. SPECIAL INSPECTION REQUIRED.
ALL COLD-FORMED LIGHT GAGE STEEL FRAMING SHALL CONFORM TO THE ANSI "SPECIFICATIONFOR THE DESIGN OF COLD-FORMED STEEL FRAMING MEMBERS-2001 EDITION" WITH 2004SUPPLEMENT. ALL 16 GAGE AND HEAVIER COLD-FORMED STRUCTURAL TRACKS, STUDS, JOISTSAND STRAPS SHALL BE FORMED FROM ASTM A446, GRADE D, OR ASTM A570, GRADE E STEEL WITHA MINIMUM Fy = 50 KSI. ALL 18 GAGE AND LIGHTER COLD-FORMED STRUCTURAL TRACKS, STUDS,JOISTS AND STRAPS SHALL BE FORMED FROM ASTM A446, GRADE A, OR ASTM A570, GRADE CSTEEL WITH A MINIMUM Fy = 33 KSI. ALL STUDS, TRACKS, JOISTS AND STRAPS SHALL BEGALVANIZED. FASTENINGS SHALL BE AS SHOWN ON THE DRAWINGS. FASTENINGS NOT SHOWNSHALL BE AS RECOMMENDED BY THE MANUFACTURER.
STUD OR JOIST SPLICES ARE NOT PERMITTED AND STUD OR JOIST FLANGES ARE NOT TO BE CUTUNDER ANY CIRCUMSTANCES. PROVIDE LATERAL BRACING AT 2'-6" OC FOR ANY STUD WITHOUTGYPSUM WALLBOARD OR SHEATHING ON BOTH FLANGES IN AREAS WITHOUT SUCH WALLCOVERINGS. LATERAL SPACING TO BE HORIZONTAL CHANNEL OR CUT TRACK AND STRAP TYPE.
WELDING PER AWS D1.3 AND AISI SPECIFICATION. MINIMUM WELDS 1/8" CONTINUOUS FILLET.WELDERS CERTIFIED PER WABO SPECIFICATIONS FOR ROD AND POSITION.
PILE CAPACITY = 10 TONS PER PILE, AS DETERMINED BY OTTO ROSENAU & ASSOCIATES.SPECIAL INSPECTION REQUIRED. CONSULT SOILS REPORT BY OTTO ROSENAU &ASSOCIATES, DATED APRIL 24, 2008, AND SOILS REPORT ADDENDUM DATED MAY 1, 2009FOR FOUNDATION AND EXCAVATION INFORMATION.
PIER CAPACITY = 12.5 TONS PER PIER. PIER UPLIFT CAPACITY = 12.5 TONS PER PIER AS DERTERMINEDBY OTTO ROSENAU AND ASSOCIATES. SPECIAL INSPECTION REQUIRED. CONSULT SOILS REPORT BYOTTO ROSENAU AND ASSOCIATES, DATED APRIL 24, 2008 AND SOILS REPORT ADDENDUM DATED MAY 12, 2009FOR FOUNDATION AND EXCAVATION INFORMATION.
TITAN IBO SELF DRILLING, HOLLOW INJECTION GROUTED MICROPILES MANUFACTURED BY ISCHEBECKGMBH OR DYWI DRILL INJECTION PILES MANUFACTURED BY DYWIDAG SYSTEMS INTERNATIONAL.
PILE CAPACITY = 12.5 TONS PER PILE. PILE UPLIFT CAPACITY = 12.5 TONS PER PILE AS DETERMINED BYOTTO ROSENAU AND ASSOCIATES. SPECIAL INSPECTION REQUIRED. CONSULT SOILS REPORT BY OTTO ROSENAUAND ASSOCIATES DATED APRIL 24, 2008 AND SOILS REPORT ADDENDUM DATED SEPTEMBER 30, 2009 FORFOUNDATION AND EXCAVATION INFORMATION.
DH ehR A r c i t e c t u r , In c.nRDH ng iE ,n ge e r i n c .I
601 Union Street | Suite 700 | Seattle, WA 98101 | 206.826.4700
Vet
eran
s Af
fairs
Dep
artm
ent o
f
MANAGEMENTCONSTRUCTION
Date
Dwg. of
Drawn
Project No.
DRAWING NO.
Project Title
CheckedBuilding Number
Location
DateName Initials
Ch. of Eng.
Ch. of Staff
Assoc. Dir.
Director
Submittal
Construction
For:Approved
Approved: Area Project Manager
Drawing Title
Date
BUILDING B100
VA-260-09-IB-0472
06/22/2009
BUILDING IS FULLY SPRINKLERED
B100 EMERGENCY EXPANSION ATSEATTLE DIVISION OF VA PUGET SOUND
HEALTH CARE SYSTEM
8 911 2 3 4 5 6 7
ABB
CD
EFF
ED
CB
76543211 98
06
Athree inches = one foot
0066
2200
6622
one inch = one inch
one inch = one inch
one and one-half inches = one foot
one and one-half inches = one foot
60
60
4400
one-half inch = equals one foot
4400
8844
three-eighths i
0
one-quarter equals one foot
three-quarters inch = one foot
three-quarters inch = one foot
U.S. GOVERNMENT PRINTING OFFICE:1984-440-467
1660 SOUTH COLUMBIAN WAY SEATTLE, WA 98108VA PUGET SOUND HEALTH CARE SYSTEM - SEATTLE
5588 mm 3175 mm 6833 mm 5004 mm 4064 mm 4293 mm 3658 mm 4623 mm 2946 mm 3708 mm
1638 mm635 mm2007 mm1499 mm
3048
mm
3633 mm
1727 mm
914 mm737 mm4877 mm
737 mm
165 mm 787 mm
1563
mm
1346 mm 1397 mm
HSS5X5X
1/2
HSS5X5X
1/2
HSS5X5X
1/2
HSS5X5X
1/2
HSS5X5X
1/2
HSS5X5X
1/2
HSS5X5X
1/2
( )-2' - 6"
HA
7SS-5.01/1
CURB PERARCH, TYP
HSS5X5X
1/2
( )-3' - 0"
HC
2'-0" SQx1'-0" DPFTG EXTENSIONHSS5X
5X1/2
4' - 0 1/2"
1' -
2 1/
2"
3' -
8"
19SS-5.01/1TYP
TYP1' - 2"
5' -
5 1/
2"
5' -
6 1/
8"
TYP1' - 2"
TYP1' - 2"
TYP
1' -
2"
TYP
1' -
2"
HELICAL PILE ORMICROPILE, TYP
BATTERED HELICALPILE OR MICROPILE,TYP
( )-2' - 6"
HF
PLAN NOTES:(TYPICAL UNLESS OTHERWISE NOTED)1. CONTRACTOR TO VERIFY EXISTING FOUNDATIONS CONDITIONS.2. REFER TO SHEET SS-5.01 FOR TYPICAL FOUNDATION AND SLAB ON GRADE DETAILS.3. INDICATES PILE CAP TYPE. SEE SCHEDULE ON SS-5.01.
4.(##'-##") INDICATES BOTTOM OF PILE CAP ELEVATION. ELEVATIONS REPRESENT MINIMUM DEPTH AND ARE FOR ESTIMATING PURPOSES ONLY. ACTUAL ELEVATIONS ARE SUBJECT TO CONDITIONS AND SHALL BE DETERMINED IN THE FIELD BY THE GEOTECHNICAL ENGINEER.5. BACKFILL SHALL BE COMPACTED TO 95%. REFER TO GEOTECHNICAL REPORT.6. BF# INDICATES BRACED FRAME TYPE. REFER TO SS-2.01 FOR ELEVATIONS AND DETAILS.7. REFER TO ARCHITECTURAL DRAWINGS FOR CURTAIN WALL COLUMN LOCATIONS.8. REFER TO ARCHITECTURAL DRAWINGS FOR SLAB EDGE DIMENSIONS NOT SHOWN.9. A REPRESENTATIVE FROM OTTO ROSENAU AND ASSOCIATES SHALL BE ONSITE DURING PILE INSTALLATION AND TESTNG TO VERIFY PILE INSTALLATIONS AND CAPACITIES.
XX
DH ehR A r c i t e c t u r , In c.nRDH ng iE ,n ge e r i n c .I
601 Union Street | Suite 700 | Seattle, WA 98101 | 206.826.4700
Vet
eran
s Af
fairs
Dep
artm
ent o
f
MANAGEMENTCONSTRUCTION
Date
Dwg. of
Drawn
Project No.
DRAWING NO.
Project Title
CheckedBuilding Number
Location
DateName Initials
Ch. of Eng.
Ch. of Staff
Assoc. Dir.
Director
Submittal
Construction
For:Approved
Approved: Area Project Manager
Drawing Title
Date
BUILDING B100
VA-260-09-IB-0472
06/22/2009
BUILDING IS FULLY SPRINKLERED
B100 EMERGENCY EXPANSION ATSEATTLE DIVISION OF VA PUGET SOUND
HEALTH CARE SYSTEM
8 911 2 3 4 5 6 7
ABB
CD
EFF
ED
CB
76543211 98
06
Athree inches = one foot
0066
2200
6622
one inch = one inch
one inch = one inch
one and one-half inches = one foot
one and one-half inches = one foot
60
60
4400
one-half inch = equals one foot
4400
8844
three-eighths i
0
one-quarter equals one foot
three-quarters inch = one foot
three-quarters inch = one foot
U.S. GOVERNMENT PRINTING OFFICE:1984-440-467
1660 SOUTH COLUMBIAN WAY SEATTLE, WA 98108VA PUGET SOUND HEALTH CARE SYSTEM - SEATTLE
PLAN NOTES:(TYPICAL UNLESS OTHERWISE NOTED)1. CONTRACTOR TO VERIFY EXISTING CONDITIONS.2. REFER TO SHEETS SS-5.02 AND SS-5.03 FOR TYPICAL STEEL FRAMING DETAILS.3. REFER TO SHEET SS-5.04 FOR TYPICAL COLD-FORMED STEEL FRAMING DETAILS.4. BF# INDICATES BRACED FRAME TYPE. REFER TO SHEET SS-2.01 FOR ELEVATIONS AND DETAILS.5. REFER TO MECHANICAL, ELECTRICAL AND ARCHITECTURAL DRAWINGS FOR DUCT LAYOUT AND OPENING/PENETRATION SIZES AND LOCATIONS.6. BEAMS ARE EQUALLY SPACED UNLESS DIMENSIONED OTHERWISE.
DH ehR A r c i t e c t u r , In c.nRDH ng iE ,n ge e r i n c .I
601 Union Street | Suite 700 | Seattle, WA 98101 | 206.826.4700
Vet
eran
s Af
fairs
Dep
artm
ent o
f
MANAGEMENTCONSTRUCTION
Date
Dwg. of
Drawn
Project No.
DRAWING NO.
Project Title
CheckedBuilding Number
Location
DateName Initials
Ch. of Eng.
Ch. of Staff
Assoc. Dir.
Director
Submittal
Construction
For:Approved
Approved: Area Project Manager
Drawing Title
Date
BUILDING B100
VA-260-09-IB-0472
06/22/2009
BUILDING IS FULLY SPRINKLERED
B100 EMERGENCY EXPANSION ATSEATTLE DIVISION OF VA PUGET SOUND
HEALTH CARE SYSTEM
8 911 2 3 4 5 6 7
ABB
CD
EFF
ED
CB
76543211 98
06
Athree inches = one foot
0066
2200
6622
one inch = one inch
one inch = one inch
one and one-half inches = one foot
one and one-half inches = one foot
60
60
4400
one-half inch = equals one foot
4400
8844
three-eighths i
0
one-quarter equals one foot
three-quarters inch = one foot
three-quarters inch = one foot
U.S. GOVERNMENT PRINTING OFFICE:1984-440-467
1660 SOUTH COLUMBIAN WAY SEATTLE, WA 98108VA PUGET SOUND HEALTH CARE SYSTEM - SEATTLE
16168
48
40
one-eighth inch = one foot
RevisionsVA FORM 08-6231A,JAN 1990
0
122
ROOF FRAMING PLAN
SS-1.02/1PJK ADW
1/8" = 1'-0"1 ROOF FRAMING PLAN
65
1
1
1
1
AMMENDMENT 10/12/091
#5 @ 18 2'-0"
DRILL & EPOXY6" MIN EMBED
(E) SLAB
SEE FDN PLAN & PILE CAP SCHED3" CLR
3" C
LR
FOR SIZE & REINF
TOC PER ARCH
HSS COL PER PLAN
2"2"
18" DIA CONC PIER
0"
FIN GRADE
STD HOOK
6-#5 @ EQ SPA, CIRCULARARRANGEMENT
#4x @ 12
1 1/2" (38mm)
CLR
ANCHOR BOLT & BASE PPER 1/SS-5.02
L
HSS6x6 COLSLAB BLOCKOUT PERDETAIL 6/SS-5.01
2"
EL 0'-0"
1'-0
"
TYP
2"
3" CLR
SEE FDN PLAN & PILE CAP SCHEDULE FOR SIZE & REINF
3" C
LR
18"x18" CONC PIER
3 TIES @ 4
#4x @ 12
8-#6 VERT
STD HOOK, TYP
GRID
EL 0'-0"
CONTROL JTPER 3/SS-5.01
3-#7
3-#73"
TYP
#4x @ 18
2'-0"
MAT
CH
PIL
E C
AP
DEP
TH
GRID
GRID
WP
L
L
HSS BRACE, SLOT@ GUSSET P
HSS COL
GUSSET PPER SCHED
YIELD LINE
PILE CAP PER PLAN
STD HOOK
BOT OF PILECAP PERPLAN
D
GRADE BM
GRADE BM REINF
C COLL
3"D EDGE OF
3" 3"
PILE CAP
3/16
PILE CAP PER PLAN
COL PER PLAN
FIN FLR
12
4
6"
1'-0"
SEE
GEO
TEC
H
REP
OR
T FO
RR
EFU
SAL
DEP
TH
CAP P 1/4L
NOTE:1. HELICAL PILES SHOWN. MICROPILES MAY BE USED AT CONTRACTOR'S OPTION.
HELICAL PILE ORMICROPILE, TYP
DENSE BRGSTRATA
GRID
SIZE
6'-0"x6-0"x2'-0" DP
4'-0"x4'-0"x2'-0" DP
4'-0"x4'-0"x1'-6" DP
HC
HB
HA
6-#7 EW BOT
6-#6 EW BOT
REINFORCINGTYPE
PILE CAP SCHEDULE
HE
HD
HF
PILES REMARKS
4
4
6
8
12
DIRECTION PARALLEL TO GRADE BM2 ROWS, BATTERED IN EACH
DIRECTION PARALLEL TO GRADE BM2 ROWS, BATTERED IN EACH
DIRECTION PARALLEL TO GRADE BM2 ROWS, BATTERED IN EACH
BATTER OUTWARD IN ALL DIRECTIONSARRANGE AROUND PERIMETER AND
STRUCTURAL FILLCOMPACTSUBGRADETO 95% TOA MIN DEPTHOF 12" (305mm)
6 MILVAPOR RETARDER
1. SEE PLAN FOR "T".2. SEE PLAN FOR SLAB REINFORCEMENT.3. LAP VAPOR BARRIER JOINTS 6" (152mm) MINIMUM.
SLAB ON GRADE
1'-0
" [30
5]
NOTES:1. WHEN "D" IS GREATER THAN OR EQUAL TO 2" THIS SLAB STEP DETAIL IS REQUIRED.2. SEE PLAN FOR "T" AND REINFORCEMENT.
FIN FLR
"D"3D
"D"
"T"
1'-0"
CLR
COLD JOINT
1 1/
2 " (3
8mm
)
1 1/
2 " (3
8mm
)
1. MAXIMUM SPACING OF 15'-0" (4572mm) FROM A CONTROL JOINT.2. SEE PLAN FOR "T".3. SEE PLAN FOR SLAB REINFORCEMENT.
1/2" DIA x2'-8"(13mm DIAx813mm)PLAIN DOWELS @ 18 (457mm),TYP(GREASE ONE END)
FIN FLR
NOTES:
"T"
"T"
CLR
8" 8"(203mm) (203mm)
8" (20
3mm)
ISOLATION JOINT
CONSTRUCTION ORCONTROL JT, TYP
HSS COL
PLANNOTES:
1. SUBMIT PLAN LOCATING JOINTS FOR APPROVAL PRIOR TO CONSTRUCTION.
POUR THIS PORTIONOF CONC AFTER THECOMPLETION OF THEMAIN STRUCTUREFRAMING
SLAB ON GRADE,PROVIDE SEPARATIONBETWEEN BOT OFSLAB ON GRADE ANDTOP OF FOOTING
FIN FLR
1'-6
"(4
57m
m)
6"
FIN GRADE
#5 (#16) TOP & BOT
MIN
(610mm)
#4x @ 18 (457mm)
2-0
(152mm)
CURB REINFPER 18/SS-5.02
"T"
1/8" (3mm) WD x T/4 DPPREFORMED STRIP ORSAWCUT. FILL WITHJOINT SEALANT SAWCUTWITHIN 4 (HOT WEATHER)TO 12 (COLD WEATHER)HOURS AFTER PLACEMENT
CUT 1/2 REINFACROSS CTJ
1. MAXIMUM SPACING OF 15'-0" (4572mm) FROM A CONTROL JOINT.2. SEE PLAN FOR "T".3. SEE PLAN FOR SLAB REINFORCEMENT.
FIN FLR
NOTES:
DEPRESS REINFAS REQD TOCLEAR STRIPOR SAWCUT
1" (2
5mm
)
3" (76mm)
CLR
1 1/
2 " (3
8mm
)
#4 (#13) x DOWELS@ 18 (457mm) ALL 4SIDES EPOXY GROUTINTO DRILLED HOLES
ROUGHENCOLD JOINT
1. SEE MECH DWGS FOR PAD SIZE, HEIGHT AND LOCATION.
FIN FLR
NOTE:
#4 @ 18(#13 @ 457mm) EW
CLR REINF TO MATCH
SLAB REINF
"T"
1'-0"(305mm)
TYP
"T"
1 1/
2" (3
8mm
)
TREAD & RISERSIZE SEEARCH DWGS
FIN FLR
NOTE:1. SEE PLAN FOR "T" & REINF.
CLR
CLR3" (76 mm)
CLR
3" (7
6 m
m)
FIN FLR
SLAB BLOCKOUT,SEE DET 6/SS-5.01
HSS COL ANCHOR BOLT& BASE PPER 1/SS-5.02
EL PER PLAN
GRID
L
FOR SIZE & REINF
SEE FDN PLAN & PILE CAP SCHED
DH ehR A r c i t e c t u r , In c.nRDH ng iE ,n ge e r i n c .I
601 Union Street | Suite 700 | Seattle, WA 98101 | 206.826.4700
Vet
eran
s Af
fairs
Dep
artm
ent o
f
MANAGEMENTCONSTRUCTION
Date
Dwg. of
Drawn
Project No.
DRAWING NO.
Project Title
CheckedBuilding Number
Location
DateName Initials
Ch. of Eng.
Ch. of Staff
Assoc. Dir.
Director
Submittal
Construction
For:Approved
Approved: Area Project Manager
Drawing Title
Date
BUILDING B100
VA-260-09-IB-0472
06/22/2009
BUILDING IS FULLY SPRINKLERED
B100 EMERGENCY EXPANSION ATSEATTLE DIVISION OF VA PUGET SOUND
HEALTH CARE SYSTEM
8 911 2 3 4 5 6 7
ABB
CD
EFF
ED
CB
76543211 98
06
Athree inches = one foot
0066
2200
6622
one inch = one inch
one inch = one inch
one and one-half inches = one foot
one and one-half inches = one foot
60
60
4400
one-half inch = equals one foot
4400
8844
three-eighths i
0
one-quarter equals one foot
three-quarters inch = one foot
three-quarters inch = one foot
U.S. GOVERNMENT PRINTING OFFICE:1984-440-467
1660 SOUTH COLUMBIAN WAY SEATTLE, WA 98108VA PUGET SOUND HEALTH CARE SYSTEM - SEATTLE
16168
48
40
one-eighth inch = one foot
RevisionsVA FORM 08-6231A,JAN 1990
0
122
FOUNDATION AND PILE CAP DETAILS
SS-5.01/1PJK ADW
3/4" = 1'-0"2 TYP SLAB CONSTRUCTION JOINT 3/4" = 1'-0"6 TYP ISOLATION JOINT AT COL
3/4" = 1'-0"7 TYP SLAB EDGE
3/4" = 1'-0"3 TYP SLAB CONTROL JOINT 3/4" = 1'-0"4 TYP HOUSEKEEPING PAD
3/4" = 1'-0"5 TYP STAIR ON GRADE
3/4" = 1'-0"8 TYP HSS COL TO PILE CAP 3/4" = 1'-0"11 SLAB TO (E) SLAB
3/4" = 1'-0"13 HSS CANOPY COL W/ CONC PIER 3/4" = 1'-0"14 HSS COL PILE CAP W/ CONC PIER
3/4" = 1'-0"15 GRADE BM SECTION
3/4" = 1'-0"10 TYP GRADE BEAM TO PILE CAP
3/8" = 1'-0"17 BATTERED PILE ELEVATION
3/4" = 1'-0"1 TYP SLAB ON GRADE
3/4" = 1'-0"19 TYP SLAB DEPRESSION
68
1
1
AMMENDMENT 10/12/091
68 MIL (MIN) BOT
x68 MIL
#10 SCREWS @ 2" OC,
TRACK, 50 KSI
BENT P, 50 KSIL
PANEL TO T&B TRACK
4 4 #10 SCREWS @2" OC ATBOUNDARY MEMBERPANEL EDGE
@ EDGESBRIDGING
BOUNDARY ELEMENT2 STUDS BACK TOBACK
600S200-54 STUDS
HOLDOWN ANCHORPER 22/SS-5.04
PANEL EDGES -#10 SCREWS@ 4" OC
PANEL FIELD -#10 SCREWS@ 12" OC
0.027 SHEET STEELPANEL, ONE SIDE
1. ALL SCREWS 1 1/4" LONG BUGLE HEAD SELF-DRILLING SCREWS.2. INSTALL PANELS VERTICALLY.3. INSTALL SCREWS A MINIMUM OF 3/8" FROM PANEL EDGES.4. SCREWS MUST PENETRATE AT LEAST 3 EXPOSED THREADS INTO FRAMING MEMBERS.5. PANEL WIDTH SHALL NOT BE LESS THAN 12" WIDE.
NOTES:
PROVIDE
TOP DEFLECTION TRACK
ANCHORSPER 21/SS-5.04
4" CONC SLAB
EL 15'-5"
SIMPSON S/HDU6 HOLDOWNWALL BOUNDARY
BASE TRACK
C BEAML
NOTES:
1. SEE 21/SS-5.04 FOR INFORMATION NOT CALLED OUT.2. PROVIDE HOLDOWNS AND BOUNDARY ELEMENTS AT WALL CORNERS AND DOOR OPENINGS.
W BM
ELEMENTW/ 6-#14 SCREWS
5/8" DIA HEADEDTHREADED ROD, 10" EMBED
2"4" CONC SLAB
EL 15'-6"
REINF, PER PLAN
EXP BOLT PER 7/SS-5.04
STUD WALL
BASE TRACK
C BEAML
RIGID INSULATION
NOTE:
1. SIMILAR WITH DECK PERPENDICULAR TO BEAM.
W BM
ROOF DECKPER PLAN
2-#4 T&B
ISOLATION JOINT
P3/8x1'-0 CONTL
#5xA706 @ 18
2"
CRIPPLE STUD
JAMB
CRIPPLE STUD
ADDITIONALANCHORAGE
BASE TRACK
INFILL STUD
HEADER TRACKS GA
HEADER MEMBERS
ANGLE
SILL
INFILL STUD
TYP BASEANCHORAGE
TO MATCH HEADER
PER SCHED
AT JAMB
SHEAR WALLCONSTRUCTION
TRACK
TOW PER ARCH
ROOF TYPE PER ARCH
ROOF DECK PER PLAN
PER 20/SS-5.04
PAF 0.145 MIN DIA@ 4" OCALTERNATING SIDES
W BM PER PLAN
1"
CONC SLAB PER PLAN
RIGID INSULATION
W BM PER PLAN
P3/8x1'-0"L
ISOLATION JOINT
6"VE
RIF
YPE
R M
ECH
6"
REBAR AND PDETAILS PER21/SS-5.04
L
EL 15'-5"
OPENINGWIDTH OPENING
WIDTH
HEADER HEADER
18 GA TRACK FOR 18, 16 GA STUDS26 GA TRACK FOR 20, 24, 25 GA STUDSSPLICE PER 16/SS-5.04
SEE DETAIL 7/SS-5.04FOR ANCHOR BOLTS
TYPI
CAL
CO
RN
ER
STU
DS
MAT
CH
JST
SPA JA
MB
STU
D(S
)
BRIDGINGWHEN REQ'D
JAM
B ST
UD
(S)
JAM
B ST
UD
(S)
TYPI
CAL
INTE
RSE
CTI
ON
12" MAX AT ENDSFOR BOLTS ANDFASTENERS
TYP STUDS ADDED AS REQ'DTO SUPPORT CONCENTRATEDLOADS BETWEEN STUDS, TYPEAS REQ'D BY LOAD, MIN 2 STUDS@ W BM UON
JAM
B ST
UD
(S)
OPENINGWIDTH
HEADER
NOTE:1. SEE DETAIL 20/SS-5.04 FOR SHEET STEEL PANEL INFORMATION.
18 GA TRACK FOR 18,16 GA STUDS, 26 GATRACK FOR 20, 24, 25 GASTUDSSPLICE PER 16/SS-5.04
GROUT OR SHIM W/STL P'S UNDER STUDSAS REQ'D AT CONC FORFULL BRG AFTER DEADLOAD IMPOSED
THE LEGEND NOTED ABOVE IS AN EXAMPLE OF HOW TO READ THESTEEL STUD MANUFACTURERS ASSOCIATION (SSMA) LIGHT GAGE MEMBERDESIGNATIONS. ACTUAL STUD SIZES, TRACK SIZES AND MILS THICKNESSESREQUIRED FOR THIS PROJECT ARE NOTED ON THE PLANS, SECTIONSAND DETAILS.
HEADER SCHEDULEMAX SPAN BOX HEADER MEMBERS REMARKS
<6'-0" AT SUPPORTPROVIDE WEB STIFFENER TO MATCH
DBL-600S200-43
SHEATHING
STUD
TRACK
CLIP TRACK FLANGEAT LAP JOINT
4-#12 SCREWS
FRAMED WALL
FINISH SURFACE
TRACK BRIDGING PIECE TO MATCHWALL STUD, CLIP FLANGE &BEND @ EA END OF WALL &MAX 8'-0" HORIZ SPA &MAX 4'-0" VERT SPA
#12 SCREWS @3" OC, SCREW
43 MIL x 1 1/2"TAUT FLAT STRAP
ATTACHMENT
TOP OR BOTTOM TRACK
STUD, MIN 10" LONG
NOTE:1. SPLICE TRACK BETWEEN STUDS, TYPICAL.
SECTION 16A-16A
16A
16A
2-#6 SCREWS MINEA FLANGE, EA SIDEOF SPLICE
TOP OR BOTTOMTRACK
STUD
CONT TRACKCLIP FLANGESAT EA STUD
2-#12 SCREWS
1. THE LIGHT GAGE FRAMING MATERIALS ARE MANUFACTURED BY ANY SSMA MEMBER MANUFACTURER IN ACCORDANCE WITH ASTM C955. MATERIAL SIZES AND GAGES INDICATED ON THE DRAWINGS. ALL LIGHT GAGE MEMBERS SHALL BE MANUFACTURED FROM SHEET STEEL AND GALVANIZED IN ACCORDANCE WITH ASTM A003, FORMALLY A653, A854, A535 AND A444, WITH A MINIMUM G60 COATING.
2. THE MINIMUM YIELD STRENGTH OF THE LIGHT GAGE FRAMING COMPONENTS SHALL BE AS FOLLOWS:
A. 16 GAGE (54 MILS) OR HEAVIER - MINIMUM 50,000 PSI B. 18 GAGE (43 MILS) OR LIGHTER - MINIMUM 33,000 PSI UNLESS OTHERWISE NOTED C. ALL TRACKS AND ACCESSORIES - MINIMUM 33,000 PSI UNLESS OTHERWISE NOTED D. SHEET STEEL PANELS - MINIMUM 33,000 PSI
3. THE LIGHT GAGE WALL STUDS AND FLOOR JOISTS SHALL BE PUNCHED. THE LIGHT GAGE FRAMING HAS BEEN DESIGNED IN ACCORDANCE WITH THE FOLLOWING CODES, LOADS AND SPECIFICATIONS:
A. IBC 2006 B. ASCE 7-05 C. AISI "SPECIFICATIONS FOR DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS"
4. ALL CONNECTIONS SHALL BE WELDED, SCREWED OR POWDER FASTENED AS INDICATED.
WELDS - ALL WELDED CONNECTIONS SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF THE AWS D1.3 SPECIFICATION FOR WELDING SHEET STEEL
SCREWS - #10 SELF DRILLING SCREWS MANUFACTURED BY GRABBER OR HILTI AND INSTALLED PER THE FASTENER MANUFACTURER'S SPECIFICATIONS. MINIMUM 1/2" LENGTH FOR LIGHT GAGE TO LIGHT GAGE CONNECTIONS, AND MINIMUM 1 1/2" LENGTH FOR LIGHT GAGE TO TIMBER CONNECTIONS. SCREWS SHALL BE SPACED A MINIMUM OF 1/2" BETWEEN ADJACENT SCREWS AND FROM THE METAL EDGES.
POWDER ACTUATED FASTENERS - 0.138 MINIMUM SHANK DIAMETER, MANUFACTURED BY RAMSET OR HILTI AND INSTALLED PER THE FASTENER MANUFACTURER'S SPECIFICATIONS. ICC CERTIFICATION REQUIRED.
PROVIDE MINIMUM 1 1/4" LONG POWDER ACTUATED FASTENER FOR LIGHT GAGE CONNECTIONS TO CONCRETE. POWDER ACTUATED FASTENERS IN CONCRETE SHALL BE SPACED A MINIMUM OF 4" BETWEEN ADJACENT POWDER ACTUATED FASTENER AND A MINIMUM OF 3" FROM CONCRETE EDGES. MINIMUM POWDER ACTUATED FASTENER EMBEDMENT IN CONCRETE SHALL BE 1/8".
PROVIDE MINIMUM 1/2" LONG POWDER ACTUATED FASTENER WITH KNURLED SHANKS FOR LIGHT GAGE CONNECTIONS TO STRUCTURAL STEEL. POWDER ACTUATED FASTENERS SHALL BE SPACED A MINIMUM OF 1 1/2" BETWEEN ADJACENT POWDER ACTUATED FASTENER IN STRUCTURAL STEEL AND A MINIMUM 1/2" FROM STEEL EDGES. THE POWDER ACTUATED FASTENER POINT SHALL BE DRIVEN COMPLETELY THROUGH THE BACK SIDE OF THE STRUCTURAL STEEL MEMBER.
MASONRY ANCHORS - 1/4" DIAMETER x 2" LONG SELF DRILLING SCREW ANCHORS MANUFACTURED BY RAMSET (TAPCON) OR HILTI (KWIK CON II) AND INSTALLED PER THE FASTENER MANUFACTURER'S SPECIFICATIONS FOR LIGHT GAGE CONNECTIONS TO CONCRETE MASONRY. ICC CERTIFICATION REQUIRED.
DRIVE-IN EXPANSION ANCHORS (MUSHROOM HEAD) - 1/4" DIAMETER x 1 1/4" LONG ZAMAC NAIL IN BY RAWI METAL HIT BY HILTI, OR HAMMER SET BY RAMSET, AND INSTALLED PER THE MANUFACTURER'S SPECIFICATIONS. ANCHORS IN CONCRETE SHALL BE SPACED A MINIMUM OF 4" BETWEEN ADJACENT ANCHORS AND A MINIMUM OF 3" FROM CONCRETE EDGES. MINIMUM ANCHOR EMBEDMENT IN CONCRETE SHALL BE 1 1/8". ICC CERTIFICATION REQUIRED.
EXPANSION ANCHORS - PROVIDE MINIMUM 3/8" DIAMETER KWIK BOLT TZ EXPANSION ANCHORS BY HILTI OR EQUAL WITH A MINIMUM 2 1/2" EMBEDMENT INTO CONCRETE. MINIMUM SPACING BETWEEN ADJACENT EXPANSION ANCHORS TO BE 5". EXPANSION ANCHORS SHALL BE LOCATED A MINIMUM OF 3" FROM CONCRETE EDGES. USE OVERSIZE WASHERS FOR ATTACHING LIGHT GAGE WITH EXPANSION ANCHORS. INSTALL PER THE MANUFACTURER'S SPECIFICATIONS FOR LIGHT GAGE CONNECTIONS TO CONCRETE. ICC CERTIFICATION REQUIRED.
5. ALL MEMBERS SHALL BE CUT SQUARELY FOR ATTACHMENT TO PERPENDICULAR MEMBERS OR SLOPE CUT AS REQUIRED FOR AN ANGULAR FIT AGAINST ABUTTING MEMBERS.
6. FIELD CUTTING OF LIGHT GAGE MEMBERS SHALL BE DONE BY SAWING OR SHEARING. TORCH CUTTING OF LIGHT GAGE MEMBERS IS NOT PERMITTED.7. DO NOT CUT OR SPLICE LIGHT GAGE FRAMING MEMBERS UNLESS OTHERWISE NOTED.
8. DO NOT BEAR OR CONNECT LIGHT GAGE MEMBERS WITHIN TWELVE INCHES OF THE PUNCHED OPENINGS IN THE MEMBER WEBS UNLESS THE MEMBERS ARE REINFORCED WITH A MINIMUM 12" LONG UNPUNCHED TRACK OR STUD AT THE PUNCH OPENING. THE TRACK OR STUD REINFORCING PIECE SHALL BE THE SAME SIZE AND GAGE AS THE PUNCHED MEMBER. FASTEN THE REINFORCING PIECE TO THE MEMBER WITH A MINIMUM OF FOUR SCREWS.
9. THE LIGHT GAGE FRAMING HAS BEEN DESIGNED TO SUPPORT THE LOADS INDICATED IN THE GENERAL NOTES ON SHEET S-A-01. ADDITIONAL TEMPORARY BRACING AND SHORING SHALL BE PROVIDED AS REQUIRED TO STABILIZE THE FRAMING AND TO SUPPORT CONSTRUCTION LOADS. TEMPORARY BRACING SHALL REMAIN IN PLACE UNTIL PERMANENT BRACING IS INSTALLED AND/OR ADDITIONAL CONSTRUCTION LOADS ARE REMOVED.
10. THE CONTRACTOR SHALL PROVIDE LIGHT GAGE MEMBERS AT THE SIZE AND SPACING INDICATED ON THESE DRAWINGS. LARGER SIZES AND/OR CLOSER SPACING MAY BE SUBSTITUTED PROVIDED THE SUBSTITUTIONS ARE COORDINATED WITH THE PROJECT ARCHITECTURAL AND STRUCTURAL DRAWINGS.
11. SHEATHING ON THE LIGHT GAGE FRAMING SHALL BE INSTALLED AS INDICATED IN THE PROJECT CONSTRUCTION DOCUMENTS AND SPECIFICATIONS AND PER ASTM C385.
12. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH OSHA STANDARDS.
13. LIGHT GAGE JOISTS, RAFTERS AND TRUSSES SHALL ALIGN OVER BEARING WALL STUDS UNLESS DETAILED OTHERWISE.
14. HORIZONTAL BRACING SHALL BE PROVIDED WHERE GYPBOARD OR SHEATHING IS ABSENT ON ONE OR MORE SIDES OF WALL.
15. PROVIDE TRACK BRIDGES BEHIND ALL CONNECTIONS SUPPORTING WALL MOUNTED PANELS AND FIXTURES. SEE DETAIL 16/SS-5.04.
LIGHT GAGE STEELGENERAL NOTES
DH ehR A r c i t e c t u r , In c.nRDH ng iE ,n ge e r i n c .I
601 Union Street | Suite 700 | Seattle, WA 98101 | 206.826.4700
Vet
eran
s Af
fairs
Dep
artm
ent o
f
MANAGEMENTCONSTRUCTION
Date
Dwg. of
Drawn
Project No.
DRAWING NO.
Project Title
CheckedBuilding Number
Location
DateName Initials
Ch. of Eng.
Ch. of Staff
Assoc. Dir.
Director
Submittal
Construction
For:Approved
Approved: Area Project Manager
Drawing Title
Date
BUILDING B100
VA-260-09-IB-0472
06/22/2009
BUILDING IS FULLY SPRINKLERED
B100 EMERGENCY EXPANSION ATSEATTLE DIVISION OF VA PUGET SOUND
HEALTH CARE SYSTEM
8 911 2 3 4 5 6 7
ABB
CD
EFF
ED
CB
76543211 98
06
Athree inches = one foot
0066
2200
6622
one inch = one inch
one inch = one inch
one and one-half inches = one foot
one and one-half inches = one foot
60
60
4400
one-half inch = equals one foot
4400
8844
three-eighths i
0
one-quarter equals one foot
three-quarters inch = one foot
three-quarters inch = one foot
U.S. GOVERNMENT PRINTING OFFICE:1984-440-467
1660 SOUTH COLUMBIAN WAY SEATTLE, WA 98108VA PUGET SOUND HEALTH CARE SYSTEM - SEATTLE
16168
48
40
one-eighth inch = one foot
RevisionsVA FORM 08-6231A,JAN 1990
0
122
COLD-FORMED STEEL FRAMING AND DETAILS
SS-5.04/1PJK ADW
NO SCALE1 LOAD-BEARING WALL ELEVATION
NO SCALE7 BOTTOM TRACK ANCHORAGENO SCALE8 TYP CORNER WALL DETAILS
NO SCALE9 TYP DOOR HEADER
NO SCALE14 CORNER TRACK LAP CONNECTIONNO SCALE15 TYP WALL BRIDGING & BRACING
NO SCALE16 STEEL TRACK SPLICENO SCALE17 TRACK BACKING
NO SCALE20 SHEAR WALL ELEVATION 3/4" = 1'-0"
22 PENTHOUSE TO STRUCTUREAT HOLDOWN 3/4" = 1'-0"21 PENTHOUSE TO STRUCTURE
5588 mm 3175 mm 6833 mm 5004 mm 4064 mm 4293 mm 3658 mm 4623 mm 2946 mm 3708 mm
3633 mm
165 mm 787 mm
1563
mm
HSS5X5X
1/2
HSS5X5X
1/2
HSS5X5X
1/2
HSS5X5X
1/2
HSS5X5X
1/2
HSS5X5X
1/2
HSS5X5X
1/2
CURB PERARCH, TYP
HSS5X5X
1/2
( )-3' - 0"
B
( )-3' - 0"
B
( )-2' - 6"
A
( )-2' - 6"
A
( )-2' - 6"
A
( )-2' - 6"
A
( )-5' - 0"
B
( )-5' - 0"
B
( )-6' - 0"
B
( )-6' - 0"
E
( )-5' - 0"
B
( )-2' - 6"
A
( )-5' - 0"
D
( )-6' - 0"
E( )-3' - 0"
B
( )-2' - 6"
A
( )-2' - 6"
A
( )-3' - 0"
B
( )-2' - 6"
A
( )-5' - 0"
D( )-6' - 0"
C
( )-6' - 0"
C
( )-3' - 0"
C
( )-3' - 0"
C
( )-2' - 6"
A
( )-2' - 6"
A
( )-2' - 6"
A
( )-2' - 6"
A
( )-2' - 6"
A
( )-2' - 6"
A
( )-2' - 6"
A
( )-6' - 6"
A
( )-6' - 6"
A
19SS-5.01/1TYP
SLAB DEPRESSIONPER ARCH, TYP
5' -
6 1/
8"
5' -
5 1/
2"
TYP1' - 2"
TYP1' - 2"
TYP
1' -
2"
TYP
1' -
2"
TYP1' - 2"
( )-6' - 6"
A
( )-2' - 6"
F
PLAN NOTES:(TYPICAL UNLESS OTHERWISE NOTED)1. CONTRACTOR TO VERIFY EXISTING FOUNDATIONS CONDITIONS.2. REFER TO SHEET SS-5.01 FOR TYPICAL FOUNDATION AND SLAB ON GRADE DETAILS.3. INDICATES PILE CAP TYPE. SEE SCHEDULE ON SS-9.03.
4.(##'-##") INDICATES BOTTOM OF PILE CAP ELEVATION. ELEVATIONS REPRESENT MINIMUM DEPTH AND ARE FOR ESTIMATING PURPOSES ONLY. ACTUAL ELEVATIONS ARE SUBJECT TO CONDITIONS AND SHALL BE DETERMINED IN THE FIELD BY THE GEOTECHNICAL ENGINEER.5. BACKFILL SHALL BE COMPACTED TO 95%. REFER TO GEOTECHNICAL REPORT.6. BF# INDICATES BRACED FRAME TYPE. REFER TO SS-2.01 FOR ELEVATIONS AND DETAILS.7. REFER TO ARCHITECTURAL DRAWINGS FOR CURTAIN WALL COLUMN LOCATIONS.8. REFER TO ARCHITECTURAL DRAWINGS FOR SLAB EDGE DIMENSIONS NOT SHOWN.9. A REPRESENTATIVE FROM OTTO ROSENAU AND ASSOCIATES SHALL BE ONSITE DURING PILE INSTALLATION AND TESTING TO VERIFY PILE INSTALLATIONS AND CAPACITIES.
X
DH ehR A r c i t e c t u r , In c.nRDH ng iE ,n ge e r i n c .I
601 Union Street | Suite 700 | Seattle, WA 98101 | 206.826.4700
Vet
eran
s Af
fairs
Dep
artm
ent o
f
MANAGEMENTCONSTRUCTION
Date
Dwg. of
Drawn
Project No.
DRAWING NO.
Project Title
CheckedBuilding Number
Location
DateName Initials
Ch. of Eng.
Ch. of Staff
Assoc. Dir.
Director
Submittal
Construction
For:Approved
Approved: Area Project Manager
Drawing Title
Date
BUILDING B100
VA-260-09-IB-0472
06/22/2009
BUILDING IS FULLY SPRINKLERED
B100 EMERGENCY EXPANSION ATSEATTLE DIVISION OF VA PUGET SOUND
HEALTH CARE SYSTEM
8 911 2 3 4 5 6 7
ABB
CD
EFF
ED
CB
76543211 98
06
Athree inches = one foot
0066
2200
6622
one inch = one inch
one inch = one inch
one and one-half inches = one foot
one and one-half inches = one foot
60
60
4400
one-half inch = equals one foot
4400
8844
three-eighths i
0
one-quarter equals one foot
three-quarters inch = one foot
three-quarters inch = one foot
U.S. GOVERNMENT PRINTING OFFICE:1984-440-467
1660 SOUTH COLUMBIAN WAY SEATTLE, WA 98108VA PUGET SOUND HEALTH CARE SYSTEM - SEATTLE
16168
48
40
one-eighth inch = one foot
RevisionsVA FORM 08-6231A,JAN 1990
0
122
ALTERNATE FOUNDATION AND PILE CAP PLAN
SS-9.02/1Checker Author
1/8" = 1'-0"1 ALTERNATE FOUNDATION & PILE CAP PLAN
73
1
1
1
1
1
1
1
1
1
1
NOTE:ALTERNATE PIPE PILE FOUNDATION SYSTEM MAY BE USEDAT CONTRACTOR'S OPTION BASED ON ACTUAL SITECONDITIONS AND GEOTECHNICAL RECOMMENDATIONS.
1
1
AMMENDMENT 10/12/091
1'-0
" MIN
EDG
ED
ISTA
NC
E,TY
P
4" DIA STDPIPE PILEPER SCHED
PILE CAP PER SCHED
1'-0
" MIN
SPA
CIN
G
SEE
PILE
CAP
SCH
EDU
LE F
OR
QU
ANTI
TY
GRID
GRID
3/16
PILE CAP PER PLAN
COL PER PLAN
FIN FLR
12
4DENSE BRG STRATA
6"
4" DIABATTERED PILE,TYP
1'-0"
SEE
GEO
TEC
H
REP
OR
T FO
RR
EFU
SAL
DEP
TH
CAP P 1/4L
GRIDGRID
WP
HSS COL
BOT OF PILECAP PER PLAN
GRADE BM
C COLL
PILE CAP REINFPER SCHED
EL -1'-0"
STD HOOK
FTG PER PLAN
3"
1'-0"
#4x @ 18
SIZE
8'-0"x8-0"x2'-0" DP
7'-0"x7'-0"x2'-0" DP
4'-0"x4'-0"x1'-6" DP
C
B
A
8-#8 EW BOT
6-#6 EW BOT
REINFORCINGTYPE
PILE CAP SCHEDULE
E
D
F
PILES REMARKS
8
4
10
16
32
DIRECTION, PARALLEL TO GRADE BM2 ROWS, BATTERED IN EACH
DIRECTION, PARALLEL TO GRADE BM2 ROWS, BATTERED IN EACH
DIRECTION, PARALLEL TO GRADE BM2 ROWS, BATTERED IN EACH
BATTER OUTWARD IN ALL DIRECTIONSARRANGE AROUND PERIMETER,