Upflow/Downflow Horizontal Right or Left Gas-Fired Furnace Silver 80h High Efficiency AUD1A040A9H21B, AUD1A040G9H21A AUD1B060A9H31B, AUD1B060G9H31A AUD1B080A9H31B, AUD1B080G9H31A AUD1C080A9H41B, AUD1C080G9H41A AUD1B100A9H31B, AUD1B100G9H31A AUD1C100A9H51B, AUD1C100G9H51A AUD1D120A9H51B, AUD1D120G9H51A AUD1D140A9H51B, AUD1D140G9H51A ADD1B060A9H31B, ADD1B080A9H31B ADD1C100A9H51B, ADD1D120A9H51B Single Stage, High Efficiency Motor PUB. NO. 12-1237-11 *Horizontal Conversion for these furnaces may be left or right side rotation. Upflow / Horizontal* Downflow / Horizontal*
20
Embed
Upflow/Downflow Horizontal Right or Left Gas-Fired Furnace
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Upflow/Downflow Horizontal Right or LeftGas-Fired Furnace
Silver 80h High Efficiency AUD1A040A9H21B, AUD1A040G9H21AAUD1B060A9H31B, AUD1B060G9H31AAUD1B080A9H31B, AUD1B080G9H31AAUD1C080A9H41B, AUD1C080G9H41AAUD1B100A9H31B, AUD1B100G9H31AAUD1C100A9H51B, AUD1C100G9H51AAUD1D120A9H51B, AUD1D120G9H51AAUD1D140A9H51B, AUD1D140G9H51AADD1B060A9H31B, ADD1B080A9H31BADD1C100A9H51B, ADD1D120A9H51B Single Stage, High Efficiency Motor
PUB. NO. 12-1237-11
*Horizontal Conversion for these furnaces may be left or right side rotation.
Natural Gas ModelsCentral heating furnace designs are certified by the American Gas Associa-tion for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
Safe OperationThe Integrated System Control has solid state devices, which continuously moni-tor for presence of flame, when the sys-tem is in the heating mode of operation. Dual solenoid combination gas valve and regulator provide extra safety.
Quick HeatingDurable, cycle tested, heavy gauge alu-minized steel heat exchanger quickly transfers heat to provide warm condi-tioned air to the structure.
Burners Multi-port In-shot burners will give years of quiet and efficient service. All models can be converted to L.P. gas.
Integrated System ControlExclusively designed operational pro-gram provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self-diagnostics for ease of service. Also contains connec-tion points for E.A.C./humidifier.
Air DeliveryThe multispeed, high efficiency, di-rect drive blower motor, with sufficient airflow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed.
StylingHeavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchang-er section of the cabinet is completely lined with foil faced fiberglass insulation. This results in quiet and efficient opera-tion due to the excellent acoustical and insulating qualities of fiberglass.
Features And General OperationThe Silver 80h High Efficiency Gas Furnaces employ a Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service ac-cess. a. Low energy power venter. b. Vent proving differential switch.
POWER CONN. — V/Ph/Hz4Ampacity (In Amps)Max. Overcurrent Protection (Amps)
PIPE CONN. SIZE (IN.)
DUCT CONN.
DIMENSIONSCrated (In.)Uncrated
WEIGHTShipping (Lbs.)/Net (Lbs.)
AUD1A040A9H21B
AUD1A040G9H21A
40000
32000
80.030 - 60
DIRECT10 x 6
14
SEE FAN PERF. TABLE1/2
1080 115/1/60
6.8
CENTRIFUGALDIRECT - 11/50 - 3180
115/1/601.09
YesHigh Velocity
1 - 14 X 25 - 1 IN.
4 ROUND
ALUMINIZED STEEL TYPE 1
20
2 - 452 - 56
REDUNDANT - SINGLE STAGE
HOT SURFACE
IN-SHOT2
115/1/6010.315
1/2
SEE OUTLINE DRAWING
H X W X D41-3/4 X 16-1/2 X 30-1/2
SEE OUTLINE DRAWING
119/110
AUD1B060A9H31B
AUD1B060G9H31A
60000
47000
80.030 - 60
DIRECT10 x 7
14
SEE FAN PERF. TABLE1/2
1075115/1/60
6.8
CENTRIFUGALDIRECT - 11/50 - 3180
115/1/601.09
YesHigh Velocity
1 - 17 X 25 - 1 IN.
4 ROUND
ALUMINIZED STEEL TYPE 1
20
3 - 453 - 56
REDUNDANT - SINGLE STAGE
HOT SURFACE
IN-SHOT3
115/1/6010.315
1/2
SEE OUTLINE DRAWING
H X W X D41-3/4 X 19-1/2 X 30-1/2
SEE OUTLINE DRAWING
136/126
AUD1B080A9H31B
AUD1B080G9H31A
80000
63000
80.030 - 60
DIRECT10 x 8
14
SEE FAN PERF. TABLE1/2
1075115/1/60
6.8
CENTRIFUGALDIRECT - 11/50 - 3180
115/1/601.09
YesHigh Velocity
1 - 17 X 25 - 1 IN.
4 ROUND
ALUMINIZED STEEL TYPE 1
20
4 - 454 - 56
REDUNDANT - SINGLE STAGE
HOT SURFACE
IN-SHOT4
115/1/6010.315
1/2
SEE OUTLINE DRAWING
H X W X D41-3/4 X 19-1/2 X 30-1/2
SEE OUTLINE DRAWING
142/132
AUD1C080A9H41B
AUD1C080G9H41A
80000
64000
80.030 - 60
DIRECT11 x 10
14
SEE FAN PERF. TABLE3/4
1100115/1/60
8.4
CENTRIFUGALDIRECT - 11/50 - 3180
115/1/601.09
YesHigh Velocity
1 - 20 X 25 - 1 IN.
4 ROUND
ALUMINIZED STEEL TYPE 1
20
4 - 454 - 56
REDUNDANT - SINGLE STAGE
HOT SURFACE
IN-SHOT4
115/1/6012.315
1/2
SEE OUTLINE DRAWING
H X W X D41-3/4 X 23 X 30-1/2
SEE OUTLINE DRAWING
162/151
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.5 Constant torque ECM blower motor.
POWER CONN. — V/Ph/Hz4Ampacity (In Amps)Max. Overcurrent Protection (Amps)
PIPE CONN. SIZE (IN.)
DUCT CONN.
DIMENSIONSCrated (In.)Uncrated
WEIGHTShipping (Lbs.)/Net (Lbs.)
General Data
AUD1B100A9H31B
AUD1B100G9H31A
100000
80000
80.040 - 70
DIRECT10 x 8
14
SEE FAN PERF. TABLE3/4
1075115/1/60
8.4
CENTRIFUGALDIRECT - 11/50 - 3180
115/1/601.09
YesHigh Velocity
1 - 17 X 25 - 1 IN.
4 ROUND
ALUMINIZED STEEL TYPE 1
20
5 - 455 - 56
REDUNDANT - SINGLE STAGE
HOT SURFACE
IN-SHOT5
115/1/6012.315
1/2
SEE OUTLINE DRAWING
H X W X D41-3/4 X 19-1/2 X 30-1/2
SEE OUTLINE DRAWING
153/143
AUD1C100A9H51B
AUD1B100G9H31A
100000
79000
80.030 - 60
DIRECT11 x 10
14
SEE FAN PERF. TABLE1
1075115/1/60
10.9
CENTRIFUGALDIRECT - 11/50 - 3180
115/1/601.09
YesHigh Velocity
1 - 20 X 25 - 1 IN.
4 ROUND
ALUMINIZED STEEL TYPE 1
20
5 - 455 - 56
REDUNDANT - SINGLE STAGE
HOT SURFACE
IN-SHOT5
115/1/6015.420
1/2
SEE OUTLINE DRAWING
H X W X D41-3/4 X 23 X 30-1/2
SEE OUTLINE DRAWING
162/151
AUD1D120A9H51B
AUD1D120G9H51A
120000
96000
80.030 - 60
DIRECT11 x 10
14
SEE FAN PERF. TABLE1
1075115/1/60
10.9
CENTRIFUGALDIRECT - 11/50 - 3180
115/1/601.09
YesHigh Velocity
1 - 24 X 25 - 1 IN.
4 ROUND
ALUMINIZED STEEL TYPE 1
20
6 - 456 - 56
REDUNDANT - SINGLE STAGE
HOT SURFACE
IN-SHOT6
115/1/6015.420
1/2
SEE OUTLINE DRAWING
H X W X D41-3/4 X 26-1/2 X 30-1/2
SEE OUTLINE DRAWING
186/174
AUD1D140A9H51B
AUD1D140G9H51A
140000
111000
80.040 - 70
DIRECT11 x 10
14
SEE FAN PERF. TABLE1
1075115/1/60
10.9
CENTRIFUGALDIRECT - 11/50 - 3180
115/1/601.09
YesHigh Velocity
1 - 24 X 25 - 1 IN.
4 ROUND
ALUMINIZED STEEL TYPE 1
20
7 - 457 - 56
REDUNDANT - SINGLE STAGE
HOT SURFACE
IN-SHOT7
115/1/6015.420
1/2
SEE OUTLINE DRAWING
H X W X D41-3/4 X 26-1/2 X 30-1/2
SEE OUTLINE DRAWING
193/181
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.5 Constant torque ECM blower motor.
POWER CONN. — V/Ph/Hz4Ampacity (In Amps)Max. Overcurrent Protection (Amps)
PIPE CONN. SIZE (IN.)
DUCT CONN.
DIMENSIONSCrated (In.)Uncrated
WEIGHTShipping (Lbs.)/Net (Lbs.)
ADD1B060A9H31B
60000
48000
80.025 - 55
DIRECT10 x 7
14
SEE FAN PERF. TABLE1/2
1075115/1/60
6.8
CENTRIFUGALDIRECT - 11/50 - 3180
115/1/601.09
YesHigh Velocity
2 - 14 X 20 - 1 IN
4 ROUND
ALUMINIZED STEEL TYPE 1
20
3 - 453 - 56
REDUNDANT - SINGLE STAGE
HOT SURFACE
IN-SHOT3
115/1/6010.315
1/2
SEE OUTLINE DRAWING
H X W X D41 X 19-1/2 X 29-1/2
SEE OUTLINE DRAWING
136 / 126
ADD1B080AH931B
80000
64000
80.035 - 65
DIRECT10 x 8
14
SEE FAN PERF. TABLE1/2
1075115/1/60
6.8
CENTRIFUGALDIRECT - 11/50 - 3180
115/1/601.09
YesHigh Velocity
2 - 14 X 20 - 1 IN
4 ROUND
ALUMINIZED STEEL TYPE 1
20
4 - 454 - 56
REDUNDANT - SINGLE STAGE
HOT SURFACE
IN-SHOT4
115/1/6010.315
1/2
SEE OUTLINE DRAWING
H X W X D41-3/4 X 18-1/2 X 29-1/2
SEE OUTLINE DRAWING
146 / 135
ADD1C100A9H51B
100000
81000
80.030 - 60
DIRECT11 x 10
14
SEE FAN PERF. TABLE1
1075115/1/60
10.9
CENTRIFUGALDIRECT - 11/50 - 3180
115/1/601.09
YesHigh Velocity
2 - 16 X 20 - 1 IN
4 ROUND
ALUMINIZED STEEL TYPE 1
20
5 - 455 - 56
REDUNDANT - SINGLE STAGE
HOT SURFACE
IN-SHOT5
115/1/6015.420
1/2
SEE OUTLINE DRAWING
H X W X D41-3/4 X 22 X 29-1/2
SEE OUTLINE DRAWING
167/155
ADD1D120A9H51B
120000
96000
80.035 - 65
DIRECT11 x 10
14
SEE FAN PERF. TABLE1
1075115/1/60
10.9
CENTRIFUGALDIRECT - 11/50 - 3180
115/1/601.09
YesHigh Velocity
2 - 16 X 20 - 1 IN
4 ROUND
ALUMINIZED STEEL TYPE 1
20
6 - 456 - 56
REDUNDANT - SINGLE STAGE
HOT SURFACE
IN-SHOT6
115/1/6015.420
1/2
SEE OUTLINE DRAWING
H X W X D41 X 25-1/2 X 29-1/2
SEE OUTLINE DRAWING
189 / 176
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.5 Constant torque ECM blower motor.
12-1237-11 9
Performance Data
AUD1-H Airflow
FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins.w.g.)
MODEL SPEED TAP 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
AUD1A040A9H21BAUD1A040G9H21A
4 - HIGH - Black3 - MED-HIGH - Blue2 - MED-LOW - Yellow1 - LOW - Red
1121926761750
1094896720644
1067866678538
1039837648499
1011808617459
983783583415
955757548371
929723514337
902689479303
AUD1B060A9H31BAUD1B060G9H31A
4 - HIGH - Black3 - MED-HIGH - Blue2 - MED-LOW - Yellow1 - LOW - Red
136011881040942
132911521003873
12981116966803
12681089931771
12381062896739
12081031861699
11781000826659
1147962787619
1116924747579
AUD1B080A9H31BAUD1B080G9H31A
4 - HIGH - Black3 - MED-HIGH - Blue2 - MED-LOW - Yellow1 - LOW - Red
1440124911791048
140612191143989
137211891106929
134511581078888
131811271050847
128710911010802
12551055970757
12191019929708
1183982887658
AUD1C080A9H41BAUD1C080G9H41A
4 - HIGH - Black3 - MED-HIGH - Blue2 - MED-LOW - Yellow1 - LOW - Red
1755151913691300
1717147812651161
1678143611611021
163913941115965
160013511068909
156113091023860
15221267978810
14811225925754
14391182871697
AUD1B100A9H31BAUD1B100G9H31A
4 - HIGH - Black3 - MED-HIGH - Blue2 - MED-LOW - Yellow1 - LOW - Red
1380128311761029
135512581142996
133012321108962
130512041081928
128011761054894
124811441019855
12161112983816
11911084947756
11651056911696
AUD1C100A9H51BAUD1C100G9H51A
4 - HIGH - Black3 - MED-HIGH - Blue2 - MED-LOW - Yellow1 - LOW - Red
2195199818131630
2154195917781590
2113191917421550
2076188317031511
2038184716641471
1992181416301434
1945178115951396
1876174415601361
1807170615251325
AUD1D120A9H51BAUD1D120G9H51A
4 - HIGH - Black3 - MED-HIGH - Blue2 - MED-LOW - Yellow1 - LOW - Red
2119196317511579
2091192917121541
2062189516731502
2029185716381459
1996181816021416
1959178515661378
1921175115291340
1887171614901293
1852168114511246
AUD1D140A9H51BAUD1D140G9H51A
4 - HIGH - Black3 - MED-HIGH - Blue2 - MED-LOW - Yellow1 - LOW - Red
2130193517521576
2096189617111533
2062185716691490
2023182416321452
1984179015941413
1952175015511375
1919170915071336
1884167314721295
1849163614361254
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
BLOWER OPERATION OF UNIT NO. 2 IS SYNCRONIZEDWITH UNIT NO. 1 VIA SIGNALS
FROM TWIN CONNECTION.
SEE NOTE 4
SEE NOTE 5
ISOLATION RELAY(FIELD SUPPLIED)
SEE NOTE 4
ISOLATION RELAYSEE NOTE 4
OUTDOOR UNIT(NO TRANSFORMER)
OUTDOOR UNIT(WITH TRANSFORMER)
RC
ISOLATION RELAY(FIELD SUPPLIED)
SEE NOTE 3
B/CB/CB/C
From Dwg. 21B341423 Rev. 2
Twinning Field Wiring
18 12-1237-11
AU
D1-
H O
UT
LIN
E D
RA
WIN
G(A
LL
DIM
EN
SIO
NS
AR
E IN
INC
HE
S)
Dimensions
Ø 1
-5/8
” H
OLE
WIT
H P
LUG
Ø 1
-5/8
” H
OLE
WIT
H P
LUG
Ø 7
/8”
HO
LE W
ITH
PLU
GEL
ECTR
ICA
L C
ON
NEC
TIO
N
(ALT
ERN
ATE)
MO
DE
LD
IM "
A"
DIM
"B
"D
IM "
C"
DIM
"D
"
*UD
1A04
0A9H
21B
, *U
D1A
040G
9H21
A14
-1/2
"9-
5/8"
13-1
/4"
13"
*UD
1B06
0A9H
31B
, *U
D1B
060G
9H31
A*U
D1B
080A
9H31
B, *
UD
1B08
0G9H
31A
*U
D1B
100A
9H31
B, *
UD
1B10
0G9H
31A
17-1
/2"
9-5/
8"16
-1/4
"16
"
*UD
1C08
0A9H
41B
, *U
D1C
080G
9H41
A*U
D1C
100A
9H51
B, *
UD
1C10
0G9H
51A
21"
13-1
/16"
19-3
/4"
19-1
/2"
*UD
1D12
0A9H
51B
, *U
D1D
120G
9H51
A*U
D1D
140A
9H51
B, *
UD
1D14
0G9H
51A
24-1
/2"
15-5
/16"
23-1
/4"
23"
* M
ay b
e "T
" or
"A
"
12-1237-11 19
AD
D1-
H O
UT
LIN
E D
RA
WIN
G(A
LL
DIM
EN
SIO
NS
AR
E IN
INC
HE
S)
Dimensions
1-1/
2” X
2-1
/2”
OVA
LG
AS
CO
NN
ECTI
ON
Ø 1
-5/8
” H
OLE
WIT
H P
LUG
Ø 1
-5/8
” H
OLE
W
ITH
PLU
G (3
)
Ø 7
/8”
HO
LE W
ITH
PLU
GEL
ECTR
ICA
L C
ON
NEC
TIO
N
(ALT
ERN
ATE)
MO
DE
LD
IM "
A"
DIM
"B
"D
IM "
C"
DIM
"D
"
*DD
1B06
0A9H
31B
*DD
1B08
0A9H
31B
17-1
/2"
9-5/
8"16
-1/4
"16
"
*DD
1C10
0A9H
51B
21"
13-1
/16"
19-3
/4"
19-1
/2"
*DD
1D12
0A9H
51B
24-1
/2"
15-5
/16"
23-1
/4"
23"
* M
ay b
e "T
" or
"A
"
04/15
American Standard Heating & Air Conditioning has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
American StandardHeating & Air Conditioning6200 Troup HighwayTyler, TX 75707