    A D D R E S S A B L E F I R E D E T E C T I O N

    & A L A R M S Y S T E M S

    June 2000 supersedes January 2000

    8000system

    @we look @ bus iness di f ferent ly

    .

    .

    .

    .

  • 7/30/2019 System 8000

    2/10

    S Y S T E M A R C H I T E C T U R E

    Sensor

    Beam Detector

    Slave LED(mimics LED of

    next device)

    ConventionalFire Alarm

    System

    ExternalDevices

    Optic FibreMax. 1 km

    Max. 1km Max. 1km

    Call Point

    Non FireApplication

    eg.Fire Exits

    Printer

    Sounders Mimic

    9200 DetectorSeries

    Repeat

    Indicator

    4 Zone,2 Relay

    Transponder

    1 ZoneTransponder

    9000 ConventionalDetector Series

    GraphicsDisplay

    ExternalDevices

    ExternalDevices

    ExternalDevices

    ExternalDevices

    Network up to 31 panels

    Up to 7loops

    per panel

    Booster(to increasedistancesbetweenpanels)

    SounderController

    32 LED OutputsTransponder

    8000 Fire AlarmControl Panel

    Note: 1). Max. 127 devices per loop, 512 devices per panel. 2). Maximum loop length is 1km.

    3). This schematic is for guidance only please refer to product instructions during installation.

  • 7/30/2019 System 8000

    3/10

    8 0 0 0 F E A T U R E S & B E N E F I T S

    Powerful Commissioning and Servicing Tools

    A comprehensive suite of tools to support the commissioning,

    installation and maintenance of the system. This includesremote access for interrogation and service via a modem,

    wiring integrity checks and fireplan simulation.

    Multicriteria Sensing

    The multicriteria sensor detects fire in 3 different ways (Optical/Heat/Ion). Diagnosis is therefore more accurate than any singlemethod of detection.

    Create Seamless Networks

    Connect up to 31 panels together and retain control on largeor complex sites. Also, new buildings or extensions are easilyaccommodated on the existing system.

    Clear User Information

    Display information is customised to the site requirements.Messages and actions are clear and understandable to the user.

    Flexible Alarm Settings

    Sounder circuits are run off transponders on the panel loop.This saves money over conventional sounder wiring andallows flexibility since each circuit may be programmed to

    sound individually in the event of an alarm.

    Disable Button for Weekly Test

    BS 5839 calls for weekly testing of the fire alarm system.Outputs to critical plant such as boiler controls however canbe disabled simply without affecting the general test.

    Timed Solutions

    Detector functions can be switched on or off at varying timesto suit the buildings use. For instance, a detector could operateas a heat detector during periods when the building is occupiedthen as a smoke, ionisation and heat detector when no one ispresent to spot smoke.

    Flexible Input and Output Features

    System 8000 has flexible fire and non-fire switching capabilitiese.g. fire exits may be monitored. Opening such an exit couldbe registered at the control panel or activate a beacon output toalert staff.

  • 7/30/2019 System 8000

    4/10

    T E L E - D I A G N O S T I C P R O G R A M ( T E D I S )

    Interrogate, diagnose and rectify problems on the fire system without having to be present on site.

    Tedis allows an engineer to interrogate, diagnose and rectify problems on the firesystem without having to be present on site. Using a PC and modem the engineer candial into the control panel from any location even while on the move. Status

    identification and modification of the following are easily achieved;

    All control panel data Operation

    Loop device data Fault finding & rectification

    All customer specific configurations

    This advance knowledge assists the engineer to arrive on site fully prepared with therequired materials, manpower and tools to complete the work first time. Tedis can alsobe used to provide remote assistance to a user over the telephone.

    TEDIS

  • 7/30/2019 System 8000

    5/10

    Dimensions (mm)

    8 0 0 0 C O N T R O L P A N E L8 0 0 0 C O N T R O L P A N E L

    The 8000 control panel and devices aredesigned to offer an affordable solutionto the protection of buildings withcomplex fire safety needs. A text displaycombined with LED indicators willclearly pinpoint a fire or fault condition.

    An historic log remembers the latest 200events and there are printer and zonaldisplay options. Panels comply with BSEN54 and are compatible with therequirements of BS 5839 part 1. Theyare approved by the demanding VdS test-ing authority and LPC approval is

    applied for.

    450 179

    206

    320

    320

    MountingBox

    MountingBox

    8000 Control Panel

    Technical Specification - Control Panel

    Mains voltage 230 V/ 50-60 Hz

    Power supply unit 12 V / 3.5 A

    Operating voltage 9 - 19 VDC

    Quiescent current consumption max. 150 mA

    Emergency power supply 12V, 2 x 12 Ah (2 x 24 Ah in extension housing)

    Operating temperature 0 C to 50 C

    Weight appr. 6.5 kg (Without batteries)

    Ingress Protection IP 30

    Max Number of loops per panel 7

    Standby period 24hrs + 30minutes alarm, upgradeable to 72 hours

    Extensionhousing for

    2 x 12V / 24Ahbatteries(optional)

    ORDER CODES

    1 Loop 788111

    1 Loop c/w 788112Zone Indication

    1 Loop c/w Printer 788113

    2 Loop 788104

    2 Loop c/w 788105Zone Indication

    2 Loop c/w Printer 788106

    All units supplied with 1 loop card.

    For customised versions see backcover.

    The control panel has aunique bypass circuit. Ina catastrophic eventsuch as a lightning strike

    damaging the micro-processor, the panel willswitch to a 2 statesystem and continue toprovide detection forthe building and itsoccupants.

    S P E C I A L F E AT U R E

  • 7/30/2019 System 8000

    6/10

    Volumatic Sensors

    Beam Duct

    Quiescent Current Receiver 8mA 45

    Transmitter 5mA

    Approximate Weight 3.2Kg 700g

    Ingress Protection IP30 IP54

    Applicable Standard BS 5839 Part 5 BS EN54

    Operating Temperature -20 to +55C -20 to +60C

    Beam Length 10 - 100m N/A

    Approvals N/A LPCB

    Dimensions (mm) Controller 120W x 110H x 300D210W x 260H x145D

    Order Code 07011-41 Housing 781453

    Venturi Tube 0.6m 781456

    Venturi Tube 1.5m 781457

    Venturi Tube 2.8m 781458

    8 0 0 0 O U T S T A T I O N S

    Sensors

    Ionisation Fixed Temperature Rate of rise Optical OT Multisensor OTI MultisensorHeat Heat

    Quiescent Current 45A 45A 45A 45A 45A 45A

    Approximate Weight 100g 100g 100g 100g 100g 100g

    Ingress Protection IP40 IP40 IP40 IP40 IP40 IP40

    Applicable Standard BS EN54, Pt 7 BS EN54, Pt 5 BS EN54, Pt 5 BS EN54, Pt 7 BS EN54,Pt 7 BS EN54, Pt 5or7

    Operating -20 to +60C -20 to +72C 54 to 62C, 1C/min -20 to +72C -20 to +72C -20 to +72C

    Temperature45 to 64C, 5C/min

    32 to 72C, 30C/min

    Approvals* VdS VdS VdS VdS VdS VdS

    Dimensions (mm) 90 dia x 61 90 dia x 61 90 dia x 61 90 dia x 61 90 dia x 61 90 dia x 61

    Order Codes 761071 761171 761271 761371 761373 761973

    * LPC pending. Contact Gent 24 for details.

    All sensors carry aunique serial number forbackwards traceability.It is therefore possibleto see a complete log ofevents for a particular

    device such as when itwas last reworked,cleaned or how manyfire conditions it hasdetected.

    S P E C I A L F E AT U R E

  • 7/30/2019 System 8000

    7/10

    P A N E L O R D E R C O D E S

    ORDER CODE

    Standard Panel. 786050

    Standard Panel complete 786150with 64 Zone Indication.

    Standard Panel complete 786450with extended LCDdisplay.

    Standard Panel complete 786550with 64 Zone indication& extended LCD display.

    Neutral front 742838

    192 Zone indication 786000

    Neutral Front 742838

    Upper Housing Options

    Lower Housing Options

    1. SELECT DOUBLE FIRST FIXHOUSING.

    2. SELECT 1 OPERATING MODULEFOR EACH HOUSING FROM THEOPTIONS LIST ON THIS PAGE.

    3. 1 LOOP CARD SUPPLIED ASSTANDARD PLEASE ORDERADDITIONAL CARDS AS REQUIRED.

    4. FOR SURFACE CABLING IT ISNECESSARY TO ORDER 2 x 789310EXTENSION BOXES.

    Code 788299First Fix comprising

    double housing,2 neutral fronts and

    1 loop card

  • 7/30/2019 System 8000

    8/10

    P R I N T E R O P T I O N S

    ORDER CODE

    Standard Panel with 789398printer c/w housing.

    Standard Panel with 789399printer and take upspool c/w housing.

    Neutral front 742838

    192 Zone indication 786000

    LOOP CARDS

    Single loop card 784382

    Network card 784840

    Note: First Fix items include one

    loop card and capacity for 4 loops +

    1 network or 5 loops.

    For 6 or 7 loops it is necessary to

    order the extension module 772421.

    The printer options must bemounted in the upper housing.

    1. SELECT DOUBLE FIRST FIXHOUSING.

    2. SELECT 1 OPERATING MODULEFOR EACH HOUSING FROM THEOPTIONS LIST ON THIS PAGE.

    3. 1 LOOP CARD SUPPLIED ASSTANDARD PLEASE ORDERADDITIONAL CARDS AS REQUIRED.

    4. FOR SURFACE CABLING IT ISNECESSARY TO ORDER 3 x 789310EXTENSION BOXES.

    Code 788299First Fix comprising

    double housing,2 neutral fronts and

    1 loop card

    Printer option(supplied complete with

    housing).

  • 7/30/2019 System 8000

    9/10

    8 0 0 0 O U T S T A T I O N S

    Sensor Bases and Ancillaries Order Codes

    Sensor base 781415

    Sensor base with relay output 781417

    Sensor base with isolator 781416

    Sensor base with surface mount adaptor 781495

    Sensor lock 781496

    Sensor protective cage 781550

    Sensor base adaptor for flush mounting 781497

    Sensor base adaptor for conduits 781498

    Sensor removal tool 769804

    Sensor dust cover 789855

    Manual Call Points Note - Standard & Key operated MCPs require a surface (706080) or flush (706081) box.

    Standard IP65 Key Operated Hinged Cover

    Approximate Weight 0.17kg 470g 0.17kg

    IP Rating IP54 IP65 IP54

    Dimensions (mm) 88 square x 55 deep 123W x 120H x 80D 88 square x 55 deep

    Order Codes 706120 with isolator 706022 706021 706901

    706220 without isolator

    Sounders Note - Sounder outputs are variable dependent upon tone choice.

    Shallow Base Deep Base (IP65) Bedhead Sounder Sounder Base

    Operation Continuous Continuous Continuous Continuous

    Operating Voltage Range 9 - 28V DC 9 - 28V DC 9 - 28V DC 10 - 28V DC

    Typical Sound Output @ 1m, 12V DC 93dBA 93dBA 94dBA 87dBA

    Typical Sound Output @ 1m, 24V DC 100dBA 100dBA 97dBA 93dBA

    Current Consumption 8mA @ 12V, 8mA @ 12V, 8mA @ 12V, 8mA @ 12V,

    18mA @ 24V 18mA @ 24V 18mA @ 24V 18mA @ 24V

    IP Rating IP54 IP65 IP54 IP54

    Approximate Weight 0.29kg 0.31kg 0.11kg 0.15kg

    Dimensions (mm) 93 dia x 75 deep 93 dia x 105 deep 86 square x 42 deep 112 dia x 30 deep

    Order Code 74451-24NM 74452-24NM 74455-24NM 74456-24NM

    Transponder Interfaces

    Sounder Controller 12 Relay 32 LED 4/2 1 Zone

    Description 2 Sounder circuits 12 relay 32 outputs to drive 4 detector Single(0.5A), individually outputs LEDs zones/ 2 detector zonecontrolled sectors relay outputsAux 24V @0.5A

    Max No. per loop Up to 100 interfaces per control panel. Max 32 per zone on an analogue loop

    Approximate Weight 3.3Kg 95g 95g 380g 380g

    Ingress Protection IP31 IP50 IP50 IP50 IP50

    Battery Supply 2 x 12V 2.1 Ah

    Operating Temperature -20C to +50C -20C to +70C -20C to +70C -20C to +50C -20C to +50C

    Dimensions (mm) 317Wx248Hx83D 189Wx131Hx47D 189Wx131Hx47D 189Wx131Hx47D 189Wx131Hx47D

    Order Code 788618 788610 788611 788616 788617

    Suitable for standardand key operated

    versions

  • 7/30/2019 System 8000

    10/10

    A Caradon Company 8000/4M/6/00