DNV GL © 04 September 2019 SAFER, SMARTER, GREENERDNV GL ©
04 September 2019
Prepared by DNV GL- Power System Advisory
ENERGY
Sub-Synchronous Control Interaction
Overview of Modeling, Risk Assessment and Countermeasures
1
Farshid Salehi, Farshid.Salehi@dnvgl.com
&Mike Tabrizi,
Mike.Tabrizi@dnvgl.com
mailto:Farshid.Salehi@dnvgl.commailto:Mike.Tabrizi@dnvgl.com
-
DNV GL © 04 September 20192
150+ years
100+countries
100,000customers
12,500employees
MARITIME DIGITAL
SOLUTIONS
BUSINESS
ASSURANCE
ENERGYOIL & GAS
Who We Are?
5%of revenue spent on R&D
Stiftelsen Det Norske Veritas is a free-standing, autonomous and
independent foundation whose purpose is to safeguard life, property
and the environment.
DNV GL – An Independent Multi-Disciplinary, Multi-Industry
Global Advisory Firm
-
DNV GL © 04 September 2019
3
DNV GL Energy – NA
DNV GL Energy
Power System Advisory
Market & Resource
Integration
Energy Market Analysis (IE or
OE)
Resource siting & Integration
Commercial & Industrial
Transmission & Distribution
Grid Expansion
Regional Compliance
Regulatory Compliance
Distribution Analysis
Operational Excellence
NERC Compliance
Management, Auditing &
Documentation
Energy Storage
Independent Engineering
Owners Engineering
Renewable Advisory
EE Program Development & Implementation
Measurements & labs
-
DNV GL © 04 September 2019
Agenda
▪Background & History
▪Modeling & Study Approach
▪SSI Countermeasures
–Detection Solutions
–Mitigation Solutions
4
-
DNV GL © 04 September 20195
Background & History
-
DNV GL © 04 September 2019
Mohave Incident (1970)An example of Sub-synchronous Torsional
Interaction
▪ Mohave generator: 1,580 MW coal-fired in
NV.
▪ Gradually growing vibration that eventually
fractured a shaft section.
▪ First investigations incorrectly determined
cause. After 2nd failure in 1971 cause was
identified as Sub-synchronous Resonance
interaction with nearby series capacitors.
▪ An electrical resonance at 30.5 Hz excited a
mechanical resonance at 30.1 Hz.
▪ Problem was resolved by reducing
compensation percentage and installing a
torsional relay.
6
-
DNV GL © 04 September 2019
Example of Sub-synchronous Oscillations for Wind Farms
▪ ERCOT SSCI EVENT (2009, 2017)
▪ China SSCI EVENT (2012)
▪ Minnesota SSCI EVENT
7
Fault Recorder, South Texas Event, 2009
-
DNV GL © 04 September 2019
Classification of Sub-Synchronous Interaction (SSI)
8
Classification of Simple synchronous Interaction
A. E. Leon, J. A. Solsona, "Sub-synchronous interaction damping
control for DFIG wind turbines," IEEE Trans. Power System, vol. 30,
no. 1, pp. 419-428, Jan. 2015.
-
DNV GL © 04 September 2019
Induction Generation Effect
▪ A series compensated line has a natural frequency at 𝑓𝑠𝑠𝑟 = 𝑓𝑠
ൗ𝑋𝑐
𝑋𝐿,
▪ 𝑆𝑠𝑠𝑟 =𝑓𝑠𝑠𝑟−𝑓𝑟
𝑓𝑠𝑠𝑟
▪ Where, 𝑓𝑟 is the electrical frequency of rotor.
9
Simplified Sub-Synchronous Equivalent Model of DFIG
L. Fan, R. Kavasseri, Z. L. Miao, C. Zhu, "Modeling of
DFIG-based wind farms for SSR analysis," IEEE Trans. Power
Delivery, vol. 25, no. 4, pp. 2073-2082, Oct. 2010.
-
DNV GL © 04 September 2019
Sub-Synchronous Control Interaction
▪ Sub-Synchronous Control Interaction (SSCI): is the result
of
energy exchange between power electronic control systems and
series compensated lines within a sub-synchronous frequency
range, usually 5-55Hz in a 60Hz synchronous frequency
system.
– The SSCI is not related to the shaft system and torsional
mode.
– This is purely electrical phenomena and builds up very
fast.
– The frequency of oscillation is not fixed and varies under
differentcontrol parameters and system operating conditions.
– The Phenomena has been documented for Wind farm, Solar
plantand HVDC in radial condition with series compensated
lines.
– Type 3 wind farms have the most penetration and are
morevulnerable to SSCI.
10
-
DNV GL © 04 September 2019
Sub-Synchronous Control Interaction
▪ In the rotor current control loop of the DFIG, the
proportional gain of the PI
controller can be interpreted as a resistance term added to the
rotor circuit [a],
[b]. Therefore, this proportional gain increases the negative
equivalent resistance
of the rotor, resulting in a lower damping or instability at a
sub-synchronous
resonant frequency. This aggravation of the Induction Generation
Effect (IGE)
produced by the rotor current control loop is called SSCI
[b].
▪ [a] Z.Miao,“Impedance-model-based SSR analysis for type3 wind
generator and series-compensated network,” IEEE Trans. Energy
Convers., vol. 27, no. 4, pp.
984–991, Dec. 2012.
▪ [b] A. E. Leon, "Integration of DFIG-based wind farms into
series-compensated transmission systems," IEEE Trans. Sustainable
Energy, vol. 7, no. 2, pp. 451-459,
Apr. 2016.
11
-
DNV GL © 04 September 201912
Modelling & Analysis
-
DNV GL © 04 September 2019
Modeling techniques for SSI Analysis
▪Detail State Space modelling
𝑥∙ = 𝑓 𝑥, 𝑢 & 𝑦 = 𝑔(𝑥, 𝑢)
▪ Impedance modelling (Transfer function)
–This is analytical technique, 𝑍 𝑠 =𝑉(𝑠)
𝐼(𝑠)
▪Detail EMT modelling
13
-
DNV GL © 04 September 2019
Applications of Detail State Space Model
14
Performing SSI Screening
Evaluating the impact of different parameters and state on SSI
mode (Sensitivity Analysis &
Participation factor)
Tuning of control parameters
-
DNV GL © 04 September 2019
DFIG Detailed State Space Modelling
15
Block Diagram of Detailed DFIG Connected to Series Compensated
Line
-
DNV GL © 04 September 2019
Detailed State Space Modelling & SSI vulnerability
Assessment
▪ Detail Models can be utilized for following purposes:
– Quick SSI screening
– Evaluating the impact of different parameters on SSCI
– Tuning of control parameters
16
Radial Test System
-
DNV GL © 04 September 2019
State Space Modelling–Transient Simulation and FFT for 70%
Compensation
17
Acti
ve P
ow
er (
MW
)R
eacti
ve P
ow
er (
Mvar)
Active & reactive power for 70% compensation FFT result for
70% compensation
-
DNV GL © 04 September 2019
State Space Modelling – Transient Simulation and FFT for 50%
Compensation
18
Acti
ve P
ow
er (
MW
)R
eacti
ve P
ow
er (
Mvar)
Active & reactive power for 50% compensation FFT result for
50% compensation
-
DNV GL © 04 September 2019
State Space Modelling – Transient Simulation and FFT for 30%
Compensation
19
Acti
ve P
ow
er (
MW
)R
eacti
ve P
ow
er (
Mvar)
Active & reactive power for 30% compensation FFT result for
30% compensation
-
DNV GL © 04 September 2019
State Space Modelling – Transient Simulation and FFT for 10%
Compensation
20
Acti
ve P
ow
er (
MW
)R
eacti
ve P
ow
er (
Mvar)
Active & reactive power for 10% compensation FFT result for
10% compensation
-
DNV GL © 04 September 2019
State Space Modelling – Eigen Value Analysis For Screening
▪ Utilizing detail model for Screening (through Eigen value
Analysis)
21
Compensation Level
(%)
Eigen Value
frequency (Hz)
FFT Results
SSI Frequency
(Hz)
10 55.68 55.66 4.32
30 52.7 52.73 7.3
50 50.74 50.78 9.26
70 49.17 49.8 10.83
EIGENVALUE ANALYSIS RESULTS
-
DNV GL © 04 September 2019
Applications of Impedance Modelling
22
Performing SSI Screening
Evaluating the impact of different dynamic loops on SSI
-
DNV GL © 04 September 2019
Applications of EMT Modelling
23
Performing SSI Screening
Performing Detailed EMT SSI Analysis
-
DNV GL © 04 September 2019
Risk Assessment & Study Approach: Situations With SSI
Risk
▪ SSI Analysis for Generation Interconnection
– Topology Check
– Frequency Scan-Based Screening
– Detailed EMT Simulation
▪ Evaluating the Impact of Transmission Expansion Projects on
SSI
risk
– Topology Check for nearby Generation
– Sub-synchronous damping Screening
– Detailed EMT Simulation
24
-
DNV GL © 04 September 2019
SSI Analysis for Generation Interconnection: Topology Check
▪ Identifying N-X contingencies which results in radial
conditions
between the proposed generation interconnection and nearby
series compensated lines.
▪ Contingency Rank criteria is defined by ISO.
– For Example: Based on the ERCOT protocol, a generation
resource is considered to be potentially at SSI risk if there
is
contingency with outage count equal or less than 14 which
leads to radial connection between the generation and nearby
series compensated line.
▪ Graph theory based algorithm are proposed to automate the
detection of the radial contingencies.
25
-
DNV GL © 04 September 2019
SSI Analysis for Generation Interconnection: Frequency
Scan-Based Screening
▪ Frequency Scan: is Strong tool for SSI Screening
– Frequency scan provides the impedance characteristic of
wind
farm and also the transmission system as function of
frequency.
– Performing separate scan on plan side and wind farm side.
– Calculate cumulative resistance and reactance at POI to
comment on SSI vulnerability.
26
-
DNV GL © 04 September 2019
Frequency Scan- Harmonic injection
1. Bring the scanned grid to steady-state condition through an
equivalent source.
2. Inject a voltage at a frequency of interest, 𝑉𝑖𝑛𝑗(𝑓), between
the equivalent
source and the terminals of the grid.
3. Measure the voltage, 𝑉𝑚𝑒𝑎𝑠, and current, 𝐼𝑚𝑒𝑎𝑠, at the
terminals of the grid;
4. Apply the Fast-Fourier Transform (FFT) to both 𝑉𝑚𝑒𝑎𝑠 and
𝐼𝑚𝑒𝑎𝑠 to get 𝑉𝑚𝑒𝑎𝑠(𝑓) and
𝐼𝑚𝑒𝑎𝑠(𝑓) at the same frequency of the injected voltage 𝑉𝑖𝑛𝑗 𝑓
.
5. Calculate the impedance, 𝑍𝑚𝑒𝑎𝑠 𝑓 , as below:
▪ 𝑍𝑚𝑒𝑎𝑠 𝑓 =𝑉𝑚𝑒𝑎𝑠(𝑓)
𝐼𝑚𝑒𝑎𝑠(𝑓)
27
Different Steps of frequency scan-based Screening
I. B. M. Matsuo, F. Salehi, L. Zhao, Y. Zhou and W. Lee, "An
Optimized Frequency Scanning Tool for Sub-Synchronous Interaction
Analysis of Non-Linear Devices," 2019 IEEE/IAS 55th Industrial and
Commercial Power Systems Technical Conference (I&CPS), Calgary,
AB, Canada, 2019, pp. 1-7.
-
DNV GL © 04 September 2019
Frequency Scan- Plant Side
▪ The objective of these scans is to measure the resistance
and
reactance of the entire wind/solar project in the
sub-synchronous
(
-
DNV GL © 04 September 2019
Frequency Scan- Grid Side
▪ The 2nd step in the screening study involves conducting
detailed
frequency scans on the transmission system. These scans are
performed to identify the series resonant frequency of the
transmission system under various contingencies.
▪ For the transmission side, a sensitivity analysis with
different
compensation levels and statuses of switch shunts should be
performed as follows:
– Different compensation levels of the transmission system
– Transmission system with all critical switch shunts in
service
– Transmission system with all critical switch shunts out of
service
29
-
DNV GL © 04 September 2019
▪ Calculate cumulative resistance and reactance at POI
▪ Cumulative resistance at cross-over frequency (zero reactance)
is the index of
SSI risk
▪ If cumulative resistance at cross-over frequency is negative
or marginally
positive there is SSI risk
Frequency Scan - Cumulative Impedance
30
-
DNV GL © 04 September 2019
EMT Simulation
The results of the frequency scan analysis will be evaluated in
conjunction
with “N-x” outage counts for all contingencies to determine need
for
detailed EMT simulations..
Below are the example of criteria:
▪ If a fully radial contingency has an outage count of “N-6” or
less, detailed EMT
simulation-based studies will be conducted regardless of whether
frequency scans
depict SSR risk.
▪ Detailed EMT simulations will be performed for all
contingencies that have been
identified using the process outlined above. Following aspects
will be accounted
for while performing EMT simulations:
– Fault location – near-by or remote fault vis-à-vis the
proposed project/series
compensation location
– Fault type preceding the line outages – S-L-G or 3-Phase
fault
– Status of switched shunts between the project POI and series
compensated
lines of interest
– Presence of neighbouring renewable/conventional generation
resources
31
-
DNV GL © 04 September 2019
SSI Analysis for Transmission Expansion Project
▪ Transmission expansion projects could increase the risk and
severity of
SSI in power grid mainly by virtue of changing system
configuration,
consequently electrical distance.
▪ This section propose a method and tool to quantify the impact
of
transmission expansion projects on SSI risk.
▪ Two indices were proposed to comment on the impact of
Transmission
expansion project on SSI risk:
➢Outage count of radial contingencies
➢Sub-synchronous damping at resonant frequencies
▪ A graph-theory based SSI screening tool is developed to
quantify the
outage count associated with all grid radial contingencies.
▪ Frequency scan is utilized to estimate sub-synchronous
damping.
32
-
DNV GL © 04 September 2019
Transmission Expansion: Outage count of radial contingencies
▪ Identifying all generation resources in vicinity of both end
of
proposed project.
▪ Identifying N-X contingencies which results in radial
connection
between generation resources and nearby series compensated
line before and after proposed line.
▪ Compare the outage counts to evaluate the risk of SSI
occurrence.
▪ A graph-theory based SSI screening tool is developed to
quantify the outage count associated with all grid radial
contingencies.
Ref: F. Salehi, P. Saraf, A. Brahman and M. A. Tabrizi,
"Evaluating the Impacts of Transmission Expansion on
Sub-Synchronous Resonance Risk," 2019 IEEE Power & Energy
Society General Meeting, Atlanta, GA, 2019
33
-
DNV GL © 04 September 2019
Transmission Expansion: Sub-synchronous damping at resonant
frequencies
▪ Perform frequency scans on the grid side for all contingencies
of
interest to see how new line affects the grid
sub-synchronous
resonance.
▪ Decrease in Sub-synchronous resonance resistance lead to
less
damping and exacerbate the SSI condition.
▪ If the outage count and sub-synchronous resonant damping
show
higher SSI risk for a specific generation resource,
comprehensive
frequency scan based screening should be performed to
comment
on SSR vulnerability.
Ref: F. Salehi, P. Saraf, A. Brahman and M. A. Tabrizi,
"Evaluating the Impacts of Transmission Expansion on
Sub-Synchronous Resonance Risk," 2019 IEEE Power & Energy
Society General Meeting, Atlanta, GA, 2019
34
-
DNV GL © 04 September 2019
Reference for Example of evaluating the Impact of Transmission
Expansion project on SSI Risk
35
▪ For Further Details and example of SSR risk assessment for
transmission
expansion project, please refer to below paper by DNV GL team
which was
presented in IEEE PES General meeting Atlanta, 2019
F. Salehi, P. Saraf, A. Brahman and M. A. Tabrizi, "Evaluating
the Impacts of
Transmission Expansion on Sub-Synchronous Resonance Risk," 2019
IEEE Power &
Energy Society General Meeting, Atlanta, GA, 2019
-
DNV GL © 04 September 2019
Discussion for Transmission Expansion project
▪ The proposed approach provides a detailed methodology for
evaluating
the impact of transmission expansion projects on SSI risk
through a two-
steps approach utilizing outage count index and
sub-synchronous
damping index.
▪ The proposed methodology and developed tool were utilized on a
portion
of ERCOT grid and it was demonstrated that transmission
expansion
projects can have potential detrimental effects on SSR risk in
the
system.
▪ In this case, the results of frequency scan indicate that
proposed system
upgrades lead to more negative damping for all scenario of
operation
and consequently exacerbate the SSR condition.
▪ Finally, the results were validated using detailed EMT
simulations.
36
-
DNV GL © 04 September 2019
Questions?
37
-
DNV GL © 04 September 201938
SSI Countermeasure
-
DNV GL © 04 September 2019
Sub-Synchronous Oscillation- Countermeasures
39
Classification of Sub-Synchronous Oscillation
countermeasures
-
DNV GL © 04 September 2019
SSCI Detection- Motivation▪ The power system has recently become
more susceptible to Sub-
Synchronous Interactions (SSI) due to the high penetration
of
renewable resources and series-compensated lines.
▪ SSCI and IGE is a purely electrical and fast-growing
phenomenon.
▪ Detection of SSI is challenge because of the nature of the
signal.
40
Example of SSCI signal (Voltage & Current)
-
DNV GL © 04 September 2019
Reference for The Proposed SSCI Detection Algorithm
41
▪ The details of proposed SSCI detection algorithm can be find
in below paper:
▪ F. Salehi, I. Brandao Machado Matsuo, A. Brahman, M. Aghazadeh
Tabrizi and W.
Lee, "Sub-Synchronous Control Interaction Detection: A Real-Time
Application,"
in IEEE Transactions on Power Delivery.
doi: 10.1109/TPWRD.2019.2930400
▪ https://ieeexplore.ieee.org/document/8770097
▪
https://ieeexplore.ieee.org/document/8770097
-
DNV GL © 04 September 2019
Mitigation of Sub-Synchronous Interaction using battery
Storage
42
Hybrid Wind & Storage
Portion of ERCOT Grid
-
DNV GL © 04 September 2019
Mitigation of Sub-Synchronous Interaction using battery
Storage
43
Simplified Scheme – Radial connection between the RE and SC
-
DNV GL © 04 September 2019
Battery Storage control System with Feed Forward addition of SSI
Damping Controller
44
Storage Control Loop
-
DNV GL © 04 September 2019
Simulation Results for Hybrid Mitigation Solution
45
Without Hybrid Storage With Hybrid Storage
-
DNV GL © 04 September 2019
Questions?
46
-
DNV GL © 04 September 2019
SAFER, SMARTER, GREENER
www.dnvgl.com
Thank You