Top Banner
Lecture 10 - Page 1 of 6 Lecture 10 – Column Base Plates Columns must transmit vertical loads to the concrete footing. An intermediary steel base plate is used to distribute this column load without crushing the concrete . The design of steel base plates is based on the following: AISC Spec. Chapter J8 (p. 16.1-70) AISC Part 14 Base Plate thickness Concrete resistance to crushing Steel column Anchor rods (4 min. per OSHA) See AISC p. 14-9 Steel base plate Applied load “P”
354

Structural Analysis and Design Lectures

Oct 30, 2014

Download

Documents

gugi

structural analysis and design lectures
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Structural Analysis and Design Lectures

Lecture 10 - Page 1 of 6

Lecture 10 – Column Base Plates Columns must transmit vertical loads to the concrete footing. An intermediary steel base plate is used to distribute this column load without crushing the concrete.

The design of steel base plates is based on the following:

• AISC Spec. Chapter J8 (p. 16.1-70) • AISC Part 14

Base Plate thickness

Concrete resistance to crushing

Steel column

Anchor rods (4 min. per OSHA) See AISC p. 14-9

Steel base plate

Applied load “P”

Page 2: Structural Analysis and Design Lectures

Lecture 10 - Page 2 of 6

The design of a base plate involves the following steps:

Pp = Nominal bearing strength of concrete = 0.85f’cA1 Design Bearing strength of concrete:

φcPp where φc = 0.60 LRFD

c

pPΩ

where Ωc = 2.50 ASD

where: f’c = specified compressive strength of concrete, KSI A1 = area of steel base plate concentrically loaded on conc, in2 = BN (where B and N use whole inches if possible)

m = 2

95.0 dN −

n = 280.0 fbB −

n n

m

m

0.80bf

bf

B

N 0.95d d

See AISC p. 14-5

Page 3: Structural Analysis and Design Lectures

Lecture 10 - Page 3 of 6

tmin = minimum base plate thickness per AISC p. 14-6: =

y

pu

Ff

Lt9.0

2min =

where: BNP

f upu =

Pu = factored axial load, kips Fy = base plate steel yield stress m L = larger of

n

y

pa

Ff

Lt33.3

min =

where: BNP

f apa =

Pa = service axial load, kips

Fy = base plate steel yield stress m L = larger of

n

LRFD ASD

Page 4: Structural Analysis and Design Lectures

Lecture 10 - Page 4 of 6

Example (LRFD) GIVEN: A W14x82 A992 column has a factored axial load Pu = 700 KIPS. It bears on a steel base plate using A36 steel. The footing has concrete f’c = 3000 PSI. REQUIRED: Design the column base plate.

Step 1 – Determine required base plate area, A1 to avoid conc. crushing:

φcPp = Design bearing strength of concrete = 0.6Pp = 0.6(0.85f’cA1) Re-arranging to solve for A1:

A1 = )'85.0(6.0 c

u

fP

= ))3(85.0(6.0

700KSI

KIPS

A1 = 457.5 in2

Step 2 – Determine “Optimized” base plate dimensions:

28.095.0 fbd −

=∆

= 2

)"1.10(8.0)"3.14(95.0 −

= 2.75” N ≈ ∆+1A ≈ "75.25.457 2 +in ≈ 24.14” TRY N = 24” and B = 20” (Area = 480 in2 > 457.5 in2)

d and bf → from properties p. 1-22

Page 5: Structural Analysis and Design Lectures

Lecture 10 - Page 5 of 6

Step 3 – Determine “m” and “n”:

m = 2

95.0 dN −

= 2

)"3.14(95.0"24 −

= 5.2”

n = 280.0 fbB −

= 2

)"1.10(80.0"20 −

= 5.96”

Step 4 – Determine minimum base plate thickness, tmin:

y

pu

Ff

Lt9.0

2min =

where: Pu = factored axial load, kips = 700 Kips

BNP

f upu =

= )"24)("20(

700Kips = 1.46 KSI

m = 5.2” L = larger of

n = 5.96”

)36(9.0)46.1(2"96.5min KSI

KSIt =

= 1.79” → use 1⅞” thick plate

use

Base plate yield stress

Page 6: Structural Analysis and Design Lectures

Lecture 10 - Page 6 of 6

Step 5 – Draw “Summary Sketch”:

20”

24”

1 "87 thick A36 steel base plate

W14x82 A992 col. centered on plate

Page 7: Structural Analysis and Design Lectures

Lecture 12 - Page 1 of 9

Lecture 12 – Bolted Connections Below is a typical bolt and the terms given to the parts of a bolt:

Bolts used in structural steel fasteners fall within 2 categories – see AISC Table 2-5 p. 2-41:

1) Carbon steel bolts – These bolts achieve their total strength from shear

(or tension) strength across the diameter of the bolt. They are relatively low-strength and are used primarily for low-load applications such as for anchor rods. The typical carbon steel bolt used in structural steel buildings is ASTM A307 and F1554 for use in anchor rods.

2) High-strength bolts – These bolts are used for high-load connections

and obtain their total strength from the shear strength across the diameter of the bolt PLUS the friction developed between the nut and joined steel surfaces. In order to achieve the friction capacity, these bolts are tensioned to 70% of the ultimate tensile strength of the material according to the table below. ASTM A325 and A490 bolts are typically used.

The LRFD references the design of bolted connections in the following:

• AISC Spec. Chapter J3 (p. 16.1-102) • AISC Part 7 • AISC Part 9 • AISC Part 10

Page 8: Structural Analysis and Design Lectures

Lecture 12 - Page 2 of 9

Possible Bolted Shear Failure Mechanisms: There are 4 basic types of failure mechanisms for bolted connections under shear:

1) Bolt Shear:

This is probably the most obvious failure mode. It occurs when the applied load exceeds the shear capacity through the bolt. The design shear strength is dictated in AISC Table J3.2 p. 16.1-104 and AISC Table 7-1 p. 7-22. Possible remedies include using a larger diameter bolt, higher grade of bolt or more bolts.

Bolt shear failure

Result

Page 9: Structural Analysis and Design Lectures

Lecture 12 - Page 3 of 9

2) Edge Tear-Out:

This occurs when the bolt is located too close to the edge of the plate in the direction of load. A minimum required edge distance, Le, is dictated in AISC Table J3.4 p. 16.1-107. Possible remedies include increasing the edge distance or reducing the bolt diameter.

Le

Edge Distance failure

Page 10: Structural Analysis and Design Lectures

Lecture 12 - Page 4 of 9

3) Bearing Failure:

This type of failure occurs when one of the plates is too thin or not strong enough for the applied loads. The design bearing strength at bolt holes is dictated in AISC p. 16.1-111 and AISC Table 7-5 p. 7-28 and AISC Table 7-6 p. 7-30. Possible remedies increasing the plate thickness, use a higher grade of steel or using larger diameter bolts.

Bearing failure

Thin plate

Page 11: Structural Analysis and Design Lectures

Lecture 12 - Page 5 of 9

4) Net Section Failure:

A net section failure occurs when there are too many bolt holes perpendicular to the line of action – resulting in too little material to carry the load. Think of Swiss cheese. The minimum spacing of bolts is dictated in AISC J3.2 p. 16.1-106 as not less than 2⅔ times the nominal bolt diameter, preferably 3 times the bolt diameter. Usually 3” is used as the nominal bolt spacing for bolts < 1” in diameter.

Net section failure

Page 12: Structural Analysis and Design Lectures

Lecture 12 - Page 6 of 9

Types of Bolted Connections

1) Bearing-Type Connections:

A bearing-type connection is the most common type of bolted connection. It is used in most simple-shear connections and in situations when loosening or fatigue due to vibration or load fluctuations are NOT design considerations. In these connections, bolts are tightened to the “snug-tight” condition, as defined as the tightness attained by a few impacts of an impact wrench or the full effort of an iron worker using an ordinary spud wrench. The design strength of bearing-type fasteners is per AISC Eq. J3-1 p. 16.1-108.

2) Slip-Critical Connections:

A slip-critical connection is one in which loosening due to vibration or load reversals are to be considered. Also, holes that are oversize or slotted shall be designed as slip-critical connections. Bolts that are used in slip-critical connections must be pre-tensioned per AISC Table J3.1 p. 16.1-103. In addition, the design strength of the connection must be checked in accordance with AISC J3.8, J3.9 and J3.10 p. 16.1-109 thru 111. As an alternative, AISC Table 7-3 and 7-4 p. 7-24 thru 27 can be used.

See AISC Table J3.3 p. 16.1-105 for hole dimensions

Page 13: Structural Analysis and Design Lectures

Lecture 12 - Page 7 of 9

Design Strength of Bearing-Type Fasteners

From AISC J3.6 p. 16.1-108, the design tension or shear strength of a high-strength bolt or threaded part is:

Design strength of bolt = φRn LRFD

Allowable strength of bolt = Ω

nR ASD

where: Rn = FnAb

φ = 0.75 LRFD Ω = 2.00 ASD

Fn = nominal tensile or shear stress of fastener, KSI = from Table J3.2 p. 16.1-104 Ab = x-sect. nominal area of unthreaded body of bolt, in2

Shear Plane:

The shear plane is the plane in which the various connected parts are in contact.

Load

Threads Not excluded from shear plane “N”

Threads eXcluded from shear plane “X”

Single-shear

Load

Double-shear

Page 14: Structural Analysis and Design Lectures

Lecture 12 - Page 8 of 9

Example 1 (LRFD) GIVEN: A ¾” diameter ASTM A325-N bolt in single-shear is subjected to a factored load of 14 KIPS. REQUIRED: Determine the design shear strength of the bolt considering bolt shear ONLY, and comment if the bolt is acceptable.

Step 1 – Determine design shear strength of bolt:

Design shear strength = φRn

where: φ = 0.75 Rn = nominal shear strength of fastener = FnAb Fn = from Table J3.2 p. 16.1-104 = 48 KSI (threads Not excluded) Ab = nominal area of unthreaded body of bolt, in2

= 2

4Dπ

= 2)"75.0(4π

= 0.44 in2

Design shear strength = (0.75)(48 KSI)(0.44 in2) Design shear strength = 15.8 KIPS > 14 KIPS → Acceptable

Pu = 14 KIPS

¾” dia. A325-N bolt

Page 15: Structural Analysis and Design Lectures

Lecture 12 - Page 9 of 9

Example 2 (LRFD) GIVEN: Same as Example 1 REQUIRED: Determine bolt design shear using AISC Table 7-1 p. 7-22.

Step 1 – Refer to Table 7-1:

ASTM A325 Thread condition = “N” Loading = “S” (Single shear) Bolt Diameter, db = ¾”

Design shear strength = 15.9 KIPS

Page 16: Structural Analysis and Design Lectures

Lecture 13 - Page 1 of 5

Lecture 13 – Bolted Connections (cont.) In the previous lecture, we looked at general strength considerations of bolted connections. In this lecture we will look at a typical all-bolted beam-to-girder shear connection to see practical bolted connection considerations.

where: Cope = cut distance of beam flange necessary to clear girder flange and “K” distance, usually 1½”, 2” or 3” K = distance between top of flange to edge of start of flat web = from beam properties AISC Part 1 Lev = required minimum vertical edge distance in direction of load = from AISC Table J3.4 p. 16.1-107 S = bolt center-to-center spacing from AISC J3.3 p. 16.1-106 = 2⅔ times nominal bolt diameter (minimum) = 3 times bolt diameter (preferred) = 3” (typical for bolts up to 1” diameter)

CopeLev

SS

K

Angle gage “g” from AISC p. 1-46 = Leh

Connection angles

Beam

Girder

Page 17: Structural Analysis and Design Lectures

Lecture 13 - Page 2 of 5

Example (LRFD) GIVEN: A W16x40 A992 steel beam “A” frames into a W18x55 A992 steel girder “B”. The applied floor Service DL = 80 PSF and the applied floor Service LL = 100 PSF. Use ¾” diameter A325-X bolts with standard bolt holes and double-angle A36 L3x3x¼ connection angles. The beam is coped at top flange only. REQUIRED: Design the all-bolted beam-to-girder connection and provide a summary sketch.

Step 1 – Determine factored beam end reaction:

wu = 1.2[6’(80 PSF) + 40 PLF] + 1.6[6’(100 PSF)] = 1584 PLF = 1.6 KLF

Beam end reaction = 2Lwu

= 2

)"0'30(6.1 −KLF

= 24 KIPS

W18

x55

Gird

er “B

W16x40 Beam “A”

4 @

6’-0

” = 2

4’-0

30’-0”

Beam weight

Page 18: Structural Analysis and Design Lectures

Lecture 13 - Page 3 of 5

Step 2 – Use AISC Table 10-1 “All-Bolted Double-Angle Connections”, p. 10-22:

These tables incorporate all design considerations for typical all-bolted double-angle connections.

W16x40 Beam

¾” Bolts

See Step 3

See Step 5

See Step 5

See Step 7

See Step 8

See Step 9

Page 19: Structural Analysis and Design Lectures

Lecture 13 - Page 4 of 5

Step 3 – Check Bolt and Angle Design Strength:

From Table above,

ASTM A325 Thread Cond. = X Angle thickness = ¼”

Step 4 – Determine minimum required cope:

The minimum required vertical edge distance must be greater than the “K” distance for either the girder or the beam.

W18x55 girder “Kdet” = 1 "165 from AISC p. 1-18

W16x40 beam “Kdet” = 1 "163 from AISC p. 1-20

Step 5 – Determine vertical edge distance, Lev:

For compactness, use Lev = 1¼” (See Table J3.4 p. 16.1-107)

Step 6 – Determine angle gage for L3x3x¼ = Leh:

From AISC p. 1-46 → g1 = Leh = 1¾” Step 7 – Check Beam Web Design Strength:

From Table above,

Hole Type = STD Leh = 1¾” Lev = 1¼”

The web thickness, tw of a W16x40 = 0.305” from AISC p. 1-20 W16x40 web design strength = 0.305”(200 KIPS/inch) = 61 KIPS > 24 KIPS → OK

Bolt and angle design strength = 76.4 KIPS > 24 KIPS

Use cope = 1½”

Beam web design strength = 200 KIPS per inch thickness

Page 20: Structural Analysis and Design Lectures

Lecture 13 - Page 5 of 5

Step 8 – Check girder Support Design Strength:

From Table above,

Support Design Strength per Inch Thickness = 526 KIPS

The web thickness, tw of a W18x55 = 0.390” from AISC p. 1-18

W18x55 web design strength = 0.390”(526 KIPS/inch) = 205 KIPS > 24 KIPS → OK

Step 9 – Determine bolt spacing S:

Preferred bolt spacing S = 3 x bolt diameter = 3(¾”) = 2¼” Use S = 3” from Table above > 2¼” → OK

Step 10 – Draw summary sketch of connection design:

1¼”

Cope = 1½”Lev = 1¼”S = 3”S = 3”

Angle gage = 1¾”

2 - L 3x3x¼ x 8½” long A36 connection angles with 9 - ¾” A325-X bolts in STD holes

W16x40 Beam

W18x55 Girder

Page 21: Structural Analysis and Design Lectures

Lecture 14 - Page 1 of 6

Lecture 14 – Welded Connections

Welding is a procedure that involves fusing two pieces of steel together by melting a sacrificial “flux” electrode to two pieces, thereby joining the pieces permanently together. They have some distinct advantages over bolted connections including:

• Welded joints are more rigid than bolted joints • Can directly connect pieces without the need for connection plates • Welds do not create holes in member (i.e., no need to check

fracture on net area) • Can join odd-shaped pieces together

Welds also have some disadvantages which may preclude their use, including:

• Welds are brittle, not ductile like bolted connections • Very labor intensive • Skilled labor required • Quality control is difficult to inspect • Potential fire hazard in areas of welding

Fillet Welds: The most common type of weld for structural steel connections is the “fillet” weld. This type of weld joins 2 pieces with flat faces at 900 angles. Some examples of fillet welds and their weld symbols are shown below:

Page 22: Structural Analysis and Design Lectures

Lecture 14 - Page 2 of 6

Page 23: Structural Analysis and Design Lectures

Lecture 14 - Page 3 of 6

A closer inspection through the fillet weld itself is shown below to indicate some of the dimensions of a weld:

The most common type of fillet welding process is “Arc” welding, or sometime called “stick” welding. This process involves running an electric current through a sacrificial electrode creating an arc of extremely high temperature that fuses the steel pieces together. The electrode (stick) has a coating called a “flux” that, when subject to heat, produces a cloud acting as a barrier to impurities in the air entering the molten metal. A diagram of arc welding process is below:

Page 24: Structural Analysis and Design Lectures

Lecture 14 - Page 4 of 6

Some examples of other welds are shown below:

Page 25: Structural Analysis and Design Lectures

Lecture 14 - Page 5 of 6

Minimum & Maximum Size of Fillet Welds:

Below is a table relating the minimum size of fillet weld to the thickness of material to be welded per AISC Table J2.4 p. 16.1-96:

Material thickness of the

thicker part joined: Minimum size of fillet weld:

Up to ¼” inclusive 1/8” Over ¼” to ½” 3/16” Over ½” to ¾” ¼”

Over ¾” 5/16”

Maximum size of a fillet weld = See AISC p. 16.1-96 paragraph 2b = Thickness of thinner part up to ¼” thick

= Thickness – 1/16” over ¼” thick Design SHEAR Strength of Fillet Welds:

From AISC p. 16.1-98 Weld available strength = Rn LRFD Design Strength = φRn

= FwAw ASD Allowable strength = Ω

nR

where: φ = 0.75 for shear from AISC Table J2.5 p. 16.1-100 Ω = 2.00 for shear from AISC Table J2.5 p. 16.1-100 Fw = nominal strength of weld electrode, Table J2.5 = 0.60FEXX FEXX = weld electrode strength = 70 KSI for E70XX electrodes Aw = effective cross-sectional area of weld, in2 = cos(450) x (Weld Size) x (Weld Length)

Page 26: Structural Analysis and Design Lectures

Lecture 14 - Page 6 of 6

Example (LRFD) GIVEN: Two ¼” thick A36 steel plates fillet welded as shown below. Use E70XX weld electrodes. REQUIRED: Determine the maximum factored load, Pu, that can be applied based on shear strength of the welds.

Step 1 – Determine total length of fillet welds:

Total length = 2(4”) = 8”

Step 2 – Determine design shear strength of welds: Weld design strength = φRn

where: φ = 0.75 for shear from AISC Table J2.5 Rn = FwAw

Fw = nominal strength of weld electrode = 0.60FEXX FEXX = weld electrode strength, Table 8-3 p. 8-65 = 70 KSI for E70XX electrodes Aw = effective cross-sectional area of weld, in2 = cos(450) x (Weld Size) x (Weld Length)

Weld design strength = 0.75(0.60(70 KSI))(cos(450)(3/16”)(8”)) Weld design strength = Pu = 33.4 KIPS

4” 3/16

Pu

Page 27: Structural Analysis and Design Lectures

Lecture 15 - Page 1 of 7

Lecture 15 – Welded Connections (cont.) The design of a typical all-welded double-angle simple shear connection will be investigated. Similar to an all-bolted connection, the AISC manual makes use of a one-stop-shopping design aid Table 10-3 p. 10-48 for all design considerations. An example design of a typical all-welded double-angle simple shear connection is as follows: Example 1 (LRFD) GIVEN: A W21x44 A992 girder with a factored end reaction = 87 KIPS has 2 – L3x3x3/8 connection angles shop-welded to the girder web and field-welded to the W12x58 A992 column flange as shown. REQUIRED: Design the connection and provide a summary sketch.

2X weld size

Weld B

L = ?

Weld A 3/16

L2x2x¼ erection angle shop-welded to col. flange

W21x44 Girder

W12x58 Column

¼

L = ? 2 – L3x3x3/8 connection angles

Minimum Web thickness

Page 28: Structural Analysis and Design Lectures

Lecture 15 - Page 2 of 7

Step 1 – Refer to AISC Table 10-3 p. 10-48 for design info:

See Step 2

See Step 5

See Step 3

See Step 4

Page 29: Structural Analysis and Design Lectures

Lecture 15 - Page 3 of 7

Step 2 – Determine minimum length “L” by checking Weld B strength:

From Table above, using a ¼” weld, choose a length “L” such that φRn > 87 KIPS

Use Lmin = 12” → φRn = 99 KIPS > 87 KIPS OK

Step 3 - Determine minimum length “L” by checking Weld A strength:

From Table above, using a 3/16” weld, choose a length “L” such that φRn > 87 KIPS

Use Lmin = 7” → φRn = 92.9 KIPS > 87 KIPS OK

Step 4 – Check minimum required column flange thickness for Weld B:

The flange thickness, tf for a W12x58 column = 0.640” From Table above, using a ¼” weld, the required minimum support thickness = 0.190” < 0.640” OK

Step 5 – Check minimum girder web thickness for Weld A:

The web thickness, tw for a W21x44 beam = 0.350” From Table above, using a 3/16” weld, the required minimum web thickness = 0.286” < 0.350” OK

Step 6 – Determine angle length:

Since the minimum length of Weld B = 12” which is greater than the minimum length of Weld A → use 12” long angles.

Page 30: Structural Analysis and Design Lectures

Lecture 15 - Page 4 of 7

Step 7 – Draw summary sketch:

W12x58 Column

1¼”

Weld B

12”

Weld A 3/16

L2x2x¼ erection angle shop-welded to col. flange

W21x44 Girder

¼

12” 2 – L3x3x3/8 connection angles

2(¼”) = ½”

Page 31: Structural Analysis and Design Lectures

Lecture 15 - Page 5 of 7

Eccentric Loading on Weld: Table 10-3 assumes that the loading is approximately concentric. In other words, there is no moment acting on the weld. In industrial or other situations, connections are applied eccentrically to a column which creates moment on the column as well as the connection. AISC Tables 8-4 thru 8-11 can be used for design of eccentrically-loaded welded connections. Example 2 (LRFD) GIVEN: A ½” plate is welded to the flange of a column as shown below. This plate carries a cantilevered factored load of 25 KIPS. REQUIRED: Determine if the weld is adequate to carry the eccentric loading.

Pu = 25 KIPS 16”

¼

¼

L = 8”

4”

Pu

Concentric Load on Weld Group

Pu

Eccentric Load on Weld Group

½” Plate

Column flange

Page 32: Structural Analysis and Design Lectures

Lecture 15 - Page 6 of 7

Step 1 – Refer to AISC Table 8-5 p. 8-72:

See Step 2

See Step 3

See Step 4

See Step 3

Page 33: Structural Analysis and Design Lectures

Lecture 15 - Page 7 of 7

Step 2 – Determine coefficient “k”:

Since “L” = 8”

kL = 4” k(8”) = 4” k = 0.5

Step 3 – Determine coefficient “a”:

Since “L” = 8”

aL = 16” k(8”) = 16” a = 2.0

Step 4 – Determine coefficient “C”:

k = 0.5 a = 2.0

Step 5 – Determine maximum permissible Pu:

From Table above

Lmin = DCC

Pu

Rearranging and solving for Pu: Pu = LφCC1D = (8”)(0.75)(0.821)(1.0)(4)

Pu = 19.7 KIPS < 25 KIPS → UNACCEPTABLE

Use “C” = 0.821

where: φ = 0.75 C = 0.821 C1 = 1.0 (AISC p. 8-65) D = 4 - 1/16ths

ERROR in AISC Manual!!!

Page 34: Structural Analysis and Design Lectures

Lecture 16 - Page 1 of 13

Lecture 16 – AISC Code of Standard Practice Design, fabrication, and erection of steel-framed buildings should incorporate provisions of the AISC “Code of Standard Practice for Steel Buildings and Bridges” and is found in AISC Spec. Section 16.3 and also online at www.AISC.org. It was first published in 1924 and is now in its 6th edition, dated March 7, 2005. It provides a useful framework for the understanding of the acceptable standards for the construction of structural steel structures. It is useful for owners, architects, engineers, contractors, fabricators, construction managers and anyone else involved with construction using structural steel. The Code also serves as a basis for technical project specifications, typically CSI Specification Section 05100 – Structural Steel (see Lecture 17). A summary of the Code of Standard Practice is given below. GLOSSARY

Definitions and abbreviations of relevant terms used throughout the Code. Some important, (but often vague) definitions include:

• AESS – Architecturally Exposed Structural Steel • Contract Documents • Design Drawings • EOR – Engineer-of-Record • Erection Drawings • Erector • Fabricator • Inspector • Owner • Owner’s Designated Representative for Construction • Owner’s Designated Representative for Design • RCSC – Research Council on Structural Connections • RFI – written Request for Information • SER – Structural Engineer-of-Record • Shop Drawings • Specifications • SSPC – Society for Protective Coatings (formerly Steel Structures

Painting Council) • Steel Detailer • Structural Steel

Page 35: Structural Analysis and Design Lectures

Lecture 16 - Page 2 of 13

Section 1 – GENERAL PROVISIONS

1.1 – Scope The Code shall govern the fabrication and erection of structural steel (unless otherwise noted in Contract Documents).

1.2 – Referenced Specifications, Codes and Standards

• AISC Manual of Steel Construction • AISC Seismic Provisions • AISC Specification • ASTM (lots of referenced standards) • AWS D1.1 – Structural Welding Code • RCSC Specification – Specification for Structural Joints using

ASTM A325 or A490 Bolts • SSPC – Steel Structures Painting Council

1.3 – Units

Either U.S. customary or metric units will be used. Each system shall be independent of the other.

1.4 – Design Criteria

The AISC Specification shall be used in the absence of other design criteria.

1.5 – Responsibility for Design

• If the Owner’s Designated Representative for Design provides the design, the Fabricator and Erector are NOT responsible for building code conformance of the design.

• If the Owner enters a contract with the Fabricator for

design/build, then the Fabricator IS responsible for building code conformance of the design.

1.6 – Patents and Copyrights

The EOR is responsible for obtaining patents and copyrights of design.

Page 36: Structural Analysis and Design Lectures

Lecture 16 - Page 3 of 13

1.7 – Existing Structures

Demolition, protection, field dimensions and/or abatement or removal of hazardous are NOT the responsibility of the Fabricator or Erector.

1.8 – Means, Methods and Safety of Erection

• Erector is responsible for erection of frame. • SER is responsible for structural adequacy of completed

project. Section 2 – CLASSIFICATION OF MATERIALS

Structural Steel shall consist of the following typical elements:

• Anchor Rods that will receive structural steel • Base Plates & bearing plates • Beams • Bracing (permanent) • Columns • Connections • Fasteners for connecting structural steel • Girders • Hangers • Lintels • Shear stud connectors • Trusses

Section 3 – DESIGN DRAWINGS AND SPECIFICATIONS

3.1 – Structural Design Drawings and Specifications

Structural design drawings shall consider design loads and forces in the completed project.

Drawings must show:

• Size, section, location and material grade of all members • Geometry and working points necessary for layout • Floor elevations • Column centers and offsets • Camber requirements for beams (if required) • Permanent bracing, stiffeners, reinforcement • Connection details or data that can be used by fabricator for

design including ASD or LRFD methodology • Data relating to non-Structural steel elements that interact

with frame • Painting requirements of Structural steel

Page 37: Structural Analysis and Design Lectures

Lecture 16 - Page 4 of 13

3.2 – Architectural, Electrical and Mechanical Design Drawings

Other trades’ design drawings may be used to show structural steel elements for purposes of defining detail configurations and other construction information, however, ALL STRUCTURAL INFO. MUST BE SHOWN ON STRUCTURAL DRAWINGS.

3.3 – Discrepancies

• Discrepancies discovered in the Contract Documents shall be resolved by the EOR in a timely manner so as not to delay the Fabricator’s work.

Discrepancies between: Which Governs:

Design Drawings Specifications Design Drawings Scaled graphic drawings Written info in drawing Written info in drawings Arch., Elect., Mech. Drawings

Structural Drawings Structural Drawings

3.4 – Legibility of Design Drawings

Design Drawings must be legible and drawn to a scale of not smaller than 1/8” = 1’-0” (unless clarity of the drawing is carefully considered), larger as necessary to convey detailed information.

3.5 – Revisions to Design Drawings and Specifications

All revisions must be communicated either by issuing new Design Drawings and Specifications or by re-issuing existing Design Drawings and Specifications. Revisions must be clearly and individually indicated, dated and identified by a revision number. These revised sketches become “amendments” to the Contract Drawings.

3.6 – Fast-Track Project Delivery

Release of structural Design Drawings and Specifications shall constitute a release for construction, regardless of the status of the architectural, electrical, mechanical, or any other trades’ documents.

Page 38: Structural Analysis and Design Lectures

Lecture 16 - Page 5 of 13

Section 4 – SHOP AND ERECTION DRAWINGS

4.1 – Owner Responsibility

The Owner shall furnish the complete structural Design Drawings and Specifications to the Fabricator in a TIMELY MANNER.

4.2 – Fabricator Responsibility

Fabricator shall produce Shop Drawings and Erection Drawings. Fabricators are permitted to use the services of independent detailers.

4.3 – Use of CAD and/or Copies of Design Drawings

Fabricator shall NOT reproduce any part of the Design Drawings as part of the Shop or Erection Drawings without the express written permission of Owner’s Designated Representative for Design.

4.4 – Approval

Shop and Erection Drawings must be submitted to Owner’s Representative for Design for review and approval and returned to Fabricator within 14 calendar days.

Page 39: Structural Analysis and Design Lectures

Lecture 16 - Page 6 of 13

Section 5 – MATERIALS

5.1 – Mill Materials

Fabricator is permitted to order materials upon receipt of Contract Documents that have been issued for construction. If mill materials do not meet ASTM A6 tolerances, Fabricator is permitted to make corrective procedures.

5.2 – Stock Materials

Fabricator may use stock materials if they meet with required ASTM specifications. Certified mill test reports are used as evidence of record of quality of material.

Section 6 – SHOP FABRICATION AND DELIVERY

6.1 – Identification of Material

Materials used for special requirements shall be marked by the supplier as specified by ASTM A6 prior to delivery to Fabricator’s shop or point of use.

6.2 – Preparation of Material

Thermal cutting of material is permitted. Surfaced specified as “finished” shall have a roughness in accordance with ANSI/ASME B46.1 that is less than or equal to 500.

6.3 – Fitting and Fastening

Projecting elements of connection materials need not be straightened in the connecting plane. Backing bars and runoff tabs shall be used to produce as required to produce sound welds, and do not need be removed unless specifically designated in the Contract Documents.

Page 40: Structural Analysis and Design Lectures

Lecture 16 - Page 7 of 13

6.4 – Fabrication Tolerances

The following tolerances are to be used:

Member Type: Tolerance Variation: Both ends finished for contact bearing Length = ± 1/32” Members < 30’-0” Length = ± 1/16” Members > 30’-0” Length = ± 1/8” All members Straightness < 1/1000 axial length Beam length < 50’-0” Camber variation = 0 → ½” Beam length > 50’-0” Camber variation = 0 → ½” + 1/8” per

10’-0” additional length beyond 50’-0”

6.5 – Shop Cleaning and Painting

Structural steel that does not require shop paint shall be cleaned of oil, grease, dirt and any foreign material. Structural steel requiring shop painting shall be free of oil, grease, dirt and any foreign material; as well as meeting the requirements of SSPC-SP2.

6.6 – Marking and Shipping of Materials

Erection marks shall be painted to all structural steel members. Connection members shall be shipped in separate closed containers according to grade, length and diameter.

6.7 – Delivery of Materials

Steel shall be delivered in a sequence that will permit efficient and economical fabrication and erection.

Section 7 – ERECTION

7.1 – Method of Erection

Structural steel shall be erected using methods and a sequence that will permit efficiency and economy.

Page 41: Structural Analysis and Design Lectures

Lecture 16 - Page 8 of 13

7.2 – Job-Site Conditions

Owner’s Representative for Construction shall provide the following:

• Access road for deliveries and movement of materials • Adequate obstruction-free space for operation of Erector’s

equipment • Adequate storage space

7.3 – Foundations, Piers and Abutments

Owner’s Representative for Construction shall be responsible for accurate location, suitability and access to all foundations, piers and abutments.

7.4 – Building Lines and Bench Marks

Owner’s Representative for Construction shall be responsible for accurate location of building lines and benchmarks and shall furnish the Fabricator with a plan containing such information.

7.5 – Installation of Anchor Rods and Other Embedded Items

Owner’s Representative for Construction shall be responsible for setting in accordance with Embedment Drawings. The variation in location shall be as follows:

Item: Variation in Dimension: Centers of any 2 anchor rods within an anchor rod group

< 1/8”

Centers of adjacent anchor rod groups < ¼” Elevation of tops of anchor rods ± ½” Accumulated variation between centers of anchor rod groups

< ¼” per 100’-0” not to exceed a total of 1”

7.6 – Installation of Bearing Devices

All leveling plates, nuts, washers and bearing plates that can be handled without crane are set to line and grade by the Owner’s Representative for Construction (otherwise set by Erector).

7.7 – Grouting

Grouting shall be the responsibility of the Owner’s Representative for Construction. The usual method for supporting columns during erection is by use of leveling nuts and washers or shims.

Page 42: Structural Analysis and Design Lectures

Lecture 16 - Page 9 of 13

7.8 – Field Connection Material

Fabricator shall provide field connection details consistent with Contract Documents.

7.9 – Loose Material

Unless otherwise noted, loose structural steel items that are not connected to the steel frame by the Owner’s Representative for Construction without assistance from Fabricator.

7.10 – Temporary Support of Structural Steel Frames

The Owner’s Designated Representative for Design shall identify the following:

• Lateral load resisting system and connecting diaphragm elements providing stability in the completed structure

• Any special erection conditions that are required by the design concept, such as use of jacks, shores, etc.

7.11 – Safety Protection

The Erector shall provide floor coverings, handrails, walkways and other protection for the Erector’s personnel in accordance with all applicable safety regulations. Unless otherwise specified, the Erector is permitted to remove such safety protection form areas where the erection operations are completed. Safety protection for other trades that are not under the direct employment of the Erector shall be the responsibility of the Owner’s Representative for Construction.

7.12 – Structural Steel Frame Tolerances

The accumulation of the mill tolerances (Section 6.4) and fabrication tolerances shall not cause the erection tolerances (Section 7-13) to be exceeded.

Page 43: Structural Analysis and Design Lectures

Lecture 16 - Page 10 of 13

7.13 – Erection Tolerances

Erection tolerances are referenced from Work Points and Work Lines defined as:

• Members other than horizontal members, the member work point is the actual center of the member at each end of the shipping piece.

• Horizontal members work point shall be the actual centerline of the top flange or top surface at each end.

• Work line is defined a s a straight line that connects the member work points.

Member: Erection Tolerance:

Column tolerance deviation from plumb ± 1/500 distance between work points not to exceed 1” total for first 20 stories

Individual straight piece (other than column) connecting to column

+ 3/16” - 5/16”

Adjustable members ± 3/8”

7.14 – Correction of Errors

Correction of minor misfits by means of reaming, grinding, drawing of elements into line by drift pins, welding or cutting shall be considered normal erection operations. Errors that cannot be corrected by these means must be promptly reported to the Owner’s Designated Representative for Design and Construction.

7.15 – Cuts, Alterations and Holes for Other Trades

The Fabricator or the Erector may NOT cut, drill or otherwise alter their work to accommodate other trades unless work is specified in the Contract Documents.

7.16 – Handling and Storage

The Erector shall take reasonable care in the proper handling and storage of structural steel during erection to avoid excess dirt and foreign matter. However, it is not the Erector’s responsibility to remove dirt or other foreign material that may accumulate during normal erection procedures.

Page 44: Structural Analysis and Design Lectures

Lecture 16 - Page 11 of 13

7.17 – Field Painting

The Fabricator or the Erector is NOT responsible to paint field bolts, or to touch-up abrasions of the shop coat, or to perform any field painting.

7.18 – Final Cleaning Up

Upon completion and acceptance, the Erector shall remove any of the Erector’s falsework, scaffolding, rubbish and temporary structures.

Section 8 – QUALITY ASSURANCE

8.1 – General The Fabricator shall maintain a quality assurance program to assure that the work is performed in accordance with this Code.

8.2 – Inspection of Mill Material

Certified mill test reports shall constitute sufficient evidence that the mill product satisfies material order requirements.

8.3 – Non-Destructive Testing

As per Contract Documents.

8.4 – Surface Preparation and Shop Painting Inspection

As per Contract Documents.

8.5 – Independent Inspection

• Fabricator and Erector shall provide the Inspector with access to all places where work is being performed, and a minimum of 24 hours notice must be given prior to commencement of work.

• Inspector shall inspect work at shop as much as possible. • Field inspections should be performed as promptly as

possible. • Deficiencies discovered by Inspector shall be reported to

Fabricator and Erector as soon as possible. • The Inspector shall NOT approve of any deviations from the

Contract Documents without written approval from the Owner’s Designated Representative for Design and Construction.

Page 45: Structural Analysis and Design Lectures

Lecture 16 - Page 12 of 13

Section 9 – CONTRACTS

9.1 – Types of Contracts

• Lump sum price • Price per pound • Price per item • Unit price

9.2 – Calculation of Weights

Weight is determined by calculation of gross weight of materials as shown on the Shop Drawings. This does NOT include shop and field weld metal or protective coatings. Deductions shall not be made for holes, copes, drilling or other removals for connections. Steel unit weight = 490 lb/ft3.

9.3 – Revisions to Contract Documents

Revisions to Contract Drawings shall be confirmed by change order or extra work order, and shall constitute authorization by the Owner that the revision is released for construction.

9.4 – Contract Price Adjustment

When the scope of work and responsibilities of the Fabricator and the Erector are changed, an appropriate modification to the contract price shall be made. Requests for contract price adjustments shall be presented to the Owner and approved/disapproved in a timely manner.

9.5 – Scheduling

The contract schedule shall state when the Design Drawings will be released for construction so that erection can start at the designated time and continue without interference or delay.

9.6 – Terms of Payment

Terms of payment shall be outlined in the Contract Documents.

Page 46: Structural Analysis and Design Lectures

Lecture 16 - Page 13 of 13

Section 10 – ARCHITECTURALLY EXPOSED STRUCTURAL STEEL

The rapidly increasing use of exposed structural steel as an aesthetic design medium has prompted the use of additional requirements that apply to these members. Typically they call for closer dimensional tolerances and smoother finished surfaces than for ordinary structural steel. 10.1 – General Requirements

When members are specifically designated in the Design Drawings as “Architecturally Exposed Structural Steel”, the requirements in Sections 1 through 9 shall apply as modified in Section 10.

10.2 – Fabrication

Permissible tolerances shall conform to ASTM A6.

• All copes, miters and cuts in surfaces exposed to view shall be made with uniform gaps of 1/8”.

• All welds exposed to view shall not project more than 1/16”

above the surface.

• Seams of hollow structural sections (HSS) shall be oriented away from view.

10.3 – Delivery of Materials

Fabricator shall take extra care and precautions to avoid bending, twisting or otherwise damaging the structural steel.

10.4 – Erection

Erector shall take extra care and precautions to minimize damage during handling and erection procedures. Unless otherwise noted, AESS members shall be plumbed, leveled and aligned to a tolerance that is ½ that of non-AESS members.

Page 47: Structural Analysis and Design Lectures

Lecture 17 - Page 1 of 8

Lecture 17 – Structural Steel Specifications Project-specific construction documents generally consist of two items:

• Design Drawings • Specifications

The Design Drawings graphically present the specific design of the structure. However, they do not indicate the specific requirements relating to:

• Materials • Submittals • Job conditions • Testing & inspection • Execution of work

CSI – Construction Specifications Institute

The CSI was founded in 1948 in an effort to organize trade-specific specifications into a uniform, industry accepted format. It developed the “MasterFormat”, a breakdown of all construction-related activities into 16 divisions as follows:

Division 1 – General Requirements Division 2 – Site Construction Division 3 – Concrete Division 4 – Masonry Division 5 – Metals Division 6 – Wood and Plastics Division 7 – Thermal and Moisture Protection Division 8 – Doors and Windows Division 9 – Finishes Division 10 – Specialties Division 11 – Equipment Division 12 – Furnishings Division 13 – Special Construction Division 14 – Conveying Systems Division 15 – Mechanical Division 16 – Electrical

Each division has been further refined into multiple sub-divisions (as shown for Division 5 above). To obtain samples of specifications, go to http://www.ogs.state.ny.us/dnc/generalInfo/masterspecdefault.htm In addition to technical specifications, the CSI MasterFormat is used by most of the construction industry for purposes of cost estimating, contractor qualifications, product research and supply ordering.

05050 – Basic Metal Materials 05100 – Structural Steel 05200 – Metal Joists 05300 – Metal Deck 05400 – Cold-Formed Metal Framing 05500 – Metal Fabrications 05600 – Hydraulic Fabrications 05650 – Railroad Track & Accessories 05700 – Ornamental Metal 05800 – Expansion Control 05900 – Metal Restoration & Cleaning

Page 48: Structural Analysis and Design Lectures

Lecture 17 - Page 2 of 8

Section 05100 – Structural Steel

PART 1 - GENERAL 1.1 WORK INCLUDED

A. Labor, materials, equipment, services and transportation required to complete structural steel work on the Drawings, as specified herein or both. Structural steel work is that work defined in AISC “Code of Standard Practice for Steel Buildings and Bridges”, dated March 7, 2005, plus work listed below and shown on structural drawings.

1. Structural steel beams, columns, girders, trusses, and other main

structural components and systems. 2. Furnishing and installation of bracing (temporary and permanent),

struts, brackets, stiffeners, anchors, support angles for metal deck, hangers, shear studs, and all other miscellaneous steel support members necessary to complete this Section.

3. Design, fabrication and installation of bolted and welded connections and splices.

4. Furnishing and installation of column base plates and bearing plates.

5. Furnishing and installation of anchor rods and loose leveling plates. 6. Furnishing and installation of openings (unreinforced and

reinforced) in structural steel required to accommodate mechanical, plumbing, and electrical work.

7. Furnishing and application of shop primer, paint, including finish coat(s) when required, and field touch-up paint for designated structural steel items.

1.2 QUALITY ASSURANCE

A. Comply with latest editions of: 1. American Institute of Steel Construction (AISC) Publications:

a. Manual of Steel Construction: Includes "Specification for Structural Steel Buildings – Load and Resistance Factor Design (LRFD)", "Code of Standard Practice for Steel Buildings and Bridges", "Specification for Structural Joints Using ASTM A325 or A490 Bolts".

b. “Building Code of New York State” by New York State Department of State Division of Code Enforcement and Administration.

2. American Welding Society, Inc. (AWS): AWS D1.1 "Structural Welding Code - Steel".

3. American Hot Dip Galvanizers Association, Inc.; Zinc Institute Inc.: "Inspection Manual for Hot Dip Galvanized Products".

4. Society for Protective Coatings (SSPC): "Surface Preparation Specifications".

Page 49: Structural Analysis and Design Lectures

Lecture 17 - Page 3 of 8

5. Exposed Structural Steel: All exposed structural steel is classified as Architecturally Exposed Structural Steel (AESS) as defined by AISC. Comply with AESS quality requirements for all exposed structural steel.

B. Qualifications for Welding Work

1. Qualify welding processes and welding operators in accordance with AWS Standards.

2. Provide certification that welders to be employed in the Work have satisfactorily passed AWS qualification tests to perform the type of welding within previous 12 months.

C. Qualifications for Fabricator and Erector

1. Fabricator and erector of structural steel shall have not less than 3 years experience in fabrication and erection of structural steel.

2. Submit written description of ability. 1.3 TESTING SERVICES

A. The Contractor shall employ a testing laboratory acceptable to Architect to perform the following tests: 1. Visual inspection of all welds according to AWS. 2. Magnetic particle inspection according to ASTM E709 for 10

percent of all shop and field welds. 3. Ultrasonic inspection according to ASTM E587 for all shop or field

full penetration welds. 4. Inspection of field-assembled high-strength bolted connections. 5. Inspection of erected columns for plumbness within tolerances

specified. 6. Inspection of headed studs. 7. Visual inspection of all erected steel for damage.

B. Weld Inspector shall be certified in accordance with AWS.

1. Submit resumes of technicians who will perform work showing evidence of one year minimum experience on similar work.

1.4 SUBMITTALS

A. General: Review of submittals will be for general consideration only. Compliance with requirements for materials, fabrication, erection and dimensioning of structural steel shall be Contractor's responsibility.

B. Connections: Submit proposed connection types for review before

preparing detailed shop drawings.

C. Shop Drawings - Submit detailed drawings showing: (NOTE: Design drawings shall NOT be used as shop drawings) 1. Column layout plans. 2. Floor and roof framing plans.

Page 50: Structural Analysis and Design Lectures

Lecture 17 - Page 4 of 8

3. Shop erection details including cuts, copes, connections, holes, bolts and other pertinent information.

4. Welds with size, length and type. 5. Anchor bolt locations. 6. Location of shop welded masonry anchors. Coordinate with

Division 4. 7. Shop finishing information.

D. Material Data: Submit laboratory test reports and other data as

required to show compliance with Specifications. Submit producer's or manufacturer's specifications and installation instructions for the following products. 1. Structural steel, including certified copies of mill reports covering

chemical and physical properties. 2. High-strength bolts including nuts and washers. 3. Unfinished bolts and nuts. 4. Structural steel primer paint. 5. Welding electrodes.

1.5 JOB CONDITIONS

A. Store material in horizontal position on supports above ground. B. Protect from elements and keep free of dirt and debris. C. Handle material carefully so as not to bend or mar. D. Repair or replace damaged materials.

PART 2 - PRODUCTS 2.1 MATERIALS

A. Rolled Steel Plates, Angles, Channels, M shapes, HP shapes and Bars: ASTM A36.

B. W Shapes: ASTM A992. C. HSS Steel Rectangular, Square and Round: ASTM A500, Grade B. D. Steel Pipe: ASTM A53 Grade B. E. Unfinished Bolts, Nuts and Washers: ASTM A307, Grade A. F. High-strength Bolts, Nuts and Washers: ASTM A325 or A490. G. Direct Tension Indicating Washers: ASTM F959-85. H. Headed Studs: ASTM A108, Grades 1015 – 1020, minimum field = 50

KSI. I. Anchor Rods, Nuts and Washers: ASTM F1554. J. Non-Shrink Bedding Mortar for Bearing and Base Plates: CRD-C 621,

Type D “Masterflow 713” from Master Builders (or equivalent). K. Neoprene Bearing Pads: ASTM D412; 70 Durometer Hardness, 2500

PSI Tensile. L. Weld Electrodes: E70XX and in accordance with AWS. M. Expansion Bolts: ¾” Diameter stainless steel with ultimate capacities in

4000 PSI concrete of 16,000 lbs. in shear and 16,000 lbs. in tension; minimum embedment of 6” “Kwik Bolt II” from Hilti Corp. (or equivalent).

Page 51: Structural Analysis and Design Lectures

Lecture 17 - Page 5 of 8

N. Steel Primer Paint: Fabricator's standard rust-inhibitive primer. or

None. Bare steel only except where exposed items to be primed are identified on Drawings.

or Series 10-1009 grey primer by Tnemec or accepted equal.

O. Hot Dipped Galvanizing: Hot-dip galvanize after fabrication in

accordance with ASTM A123. Restraighten members after galvanizing, if necessary, to be square and true.

P. Weld-on Masonry Anchors: No. 317 continuous weld-on anchor rod by Heckmann Building Products for columns and No. 315 anchor rod for beams, plain steel or accepted equal.

Q. Below Grade Coating: #46H-413 coal tar epoxy by Tnemec or accepted equal.

R. Cold Galvanizing: Galvilite Cold Galvanizing Compound by Z.R.C. Products Company or accepted equal.

2.2 FABRICATION

A. Fabricate structural steel in strict accordance with reviewed shop drawings and referenced standards.

B. Fabricate and assemble structural material in shop to greatest extent

possible.

C. Provide camber as indicated on Drawings. Where no camber is indicated, fabricate steel with mill camber up.

D. Provide holes for securing other work to structural steel framing. Cut,

drill or punch holes perpendicular to metal surfaces. Do not flame cut holes or enlarge holes by burning. Drill holes in base and bearing plates.

E. Finish and weld column bases to column base plates.

F. Anchor Rods: Furnish anchor rods, leveling plate and/or other devices

necessary for setting anchoring rods required for securing structural steel to foundation, concrete or masonry.

G. Hot dip galvanize all lintels in exterior masonry work or as noted on

drawings. 2.3 SHOP PAINTING

A. Shop paint only structural steel work which will be exposed to view and finish painted. Do not paint steel embedded in concrete or mortar or receive a spray on fireproofing. Do not paint surfaces which are to be

Page 52: Structural Analysis and Design Lectures

Lecture 17 - Page 6 of 8

welded, including metal deck. Do not paint contact surfaces of high-strength bolted connections or finished bearing surfaces such as bearing plates and column base plates.

B. For steel to be shop primed and not exposed to view, remove loose rust and mill scale by mechanical means in accordance with SSPC-SP3 "Power Tool Cleaning". For steel to be galvanized or primed and finish painted, remove all dirt, grease, rust and loose mill scale in accordance with SSPC-SP6 “Commercial Blast Cleaning”, unless recommended otherwise by paint manufacturer.

C. Immediately after surface preparation, apply structural steel primer

paint in accordance with manufacturer's instructions but not less than a uniform dry-film thickness of 2 mils. Use painting methods which will result in full coverage of joints, corners, edges and exposed surfaces.

D. Apply below grade coating to column bases and columns to be placed

below top of finished floor.

E. Apply two coats of cold galvanizing compound to achieve a minimum dry-film thickness of 3 mils. in accordance with manufacturer’s recommendations.

2.4 CONNECTIONS

A. Weld or bolt shop connections.

B. Bolt field connections as shown on drawings.

C. No one-sided or other eccentric connections will be permitted, unless shown on Drawings.

D. Minimum Capacity of Beam Connections: For connections not detailed,

provide connection capacity of the nominal full section shear capacity Vn for the given steel member as dictated in AISC Steel Construction Manual. A minimum factored shear capacity of 10 kips shall be provided for all secondary beams. For beam and girders with shear studs, provide a connection capacity of at least 125 percent of uniform load values unless indicated otherwise on drawings.

E. Provide snug-tight unfinished threaded fasteners for bolted bearing connections of secondary framing members to primary members; including, but not limited to, girts, door framing systems, roof opening and other framing systems taking only nominal stresses and in no way reacting in stress on primary members.

F. Provide high-strength fasteners for all principal bolted connections,

unless otherwise indicated.

Page 53: Structural Analysis and Design Lectures

Lecture 17 - Page 7 of 8

G. Provide bearing bolt (X) fastener for all structural connections.

H. Use only connections which are published by AISC. Do not modify published connection details unless accepted by Engineer.

I. Use AISC “Single-Plate Shear Connections” for beam connections to face of tubes and column flanges which have a width of 6 inches or less.

J. Use AISC “Framed Beam Connections” for beam connections to face of tubes and column flanges which have a width greater than 6 inches, and for beam-to-beam connections.

PART 3 - EXECUTION 3.1 INSPECTION

A. Examine conditions under which work shall be erected. Do not proceed until all unsatisfactory conditions are corrected.

3.2 ERECTION

A. Set structural frames accurately to lines and elevations indicated. Align and adjust various members forming part of a complete frame or structure before permanently fastening.

B. Clean bearing surfaces and other surfaces before assembly that will be

in permanent contact after assembly.

C. Perform necessary adjustments to compensate for discrepancies in elevations and alignment. Level and plumb individual members of structure within specified tolerances.

D. Splice members only where shown or specified.

E. Maintain work in a stable condition during erection.

F. The use of gas cutting torches in field to correct fabricating errors is

prohibited.

G. Tighten bearing bolt (X) connections to snug-tight condition. 3.3 TOLERANCES

A. Tolerances shall be within limits in AISC "Code of Standard Practice".

B. Fabrication and mill tolerance shall be within limits in AISC Standard Mill Practice.

Page 54: Structural Analysis and Design Lectures

Lecture 17 - Page 8 of 8

3.4 TOUCH-UP PAINTING A. After erection is complete, touch-up paint damaged shop priming coats

and welded areas. Remove weld slag before applying touch-up paint.

B. Touch-up below grade coatings to all portions of structural steel embedded within concrete slabs on grades.

3.5 TEMPORARY SHORING AND BRACING

A. Provide temporary shoring and bracing members as required, with connections of sufficient strength, to bear imposed loads.

B. Remove temporary members and connections when permanent

members are in place and final connections are made.

C. Provide temporary guy lines to achieve proper alignment of structures as erection proceeds.

3.6 PROTECTION

A. Do not use members for storage or working platforms until permanently secured.

B. Do not exceed load capacity of members with construction loads.

END OF SECTION

Page 55: Structural Analysis and Design Lectures

Lecture 18 - Page 1 of 10

Lecture 18 – Open Web Steel Joists Open web steel joists, or “Bar Joists” are very efficient structural members commonly used to support roofs, and to a lesser degree, floors.

Roof construction of Clark Field House facility at SUNY Delhi

Steel joists are NOT considered structural steel. As such, they are manufactured as proprietary structural members by various manufacturers. The Steel Joist Institute, SJI, is an organization founded in 1928 that was established to set standards for manufacture, design and construction of joists. It recognizes manufacturers who comply with their standards. Some of the larger SJI recognized manufacturers include Vulcraft, Canam Steel Corp. and SMI Joist Company.

Page 56: Structural Analysis and Design Lectures

Lecture 18 - Page 2 of 10

K-Series Joists

The most commonly-used joist style is the so-called “K” series. It has a depth ranging from 8” up to 30” and is used economically to span up to 60’-0”. A typical K series joist is as shown below:

A typical designation is 18K3

Section Number = Relative size of members Actual depth

in inches K series

Page 57: Structural Analysis and Design Lectures

Lecture 18 - Page 3 of 10

Steel joists are fastened to its supporting members usually by field-welding as shown below:

Unlike structural steel beams, steel joists must use bridging placed perpendicular to the span to obtain its stability. This bridging can be one of 2 types:

• Horizontal Bridging • Diagonal Bridging

Bridging requirements are shown in the Vulcraft Joist Catalog p. 9 and 35 and is a function of the Section Number and span. Joists using horizontal bridging is shown below:

Page 58: Structural Analysis and Design Lectures

Lecture 18 - Page 4 of 10

LH and DLH Series Joists

The LH series joists have depths ranging between 18” and 48” and are suitable for spans up to 96’-0”. The DLH series joists have depths ranging between 52” and 72” and are suitable for spans up to 144’-0”. They are not as commonly used as K series joists, but provide an inexpensive alternative to spanning longer distances than the K series joists. One difference between K series joists is the required end bearing width and height are 6” and 5” respectively for the LH and DLH (vs. 4” and 2½” for the K series).

A typical designation is 32LH10

Section Number = Relative size of members Actual depth

in inches LH series

Page 59: Structural Analysis and Design Lectures

Lecture 18 - Page 5 of 10

Joist Girders

Joist girders are designed to carry the end reactions from equally-spaced joists applied to the panel points. Typical depths of joist girders range from 20” up to 96” with spans of 100’-0” or more.

A typical joist girder connection to steel column is shown below:

Page 60: Structural Analysis and Design Lectures

Lecture 18 - Page 6 of 10

Example 1 GIVEN: A roof framing bay is as shown below. The service loads are as follows:

• Service Dead Load = 16 PSF • Service Roof Live Load = 25 PSF • Service Snow Load = 35 PSF • Service Wind Uplift = -12 PSF

REQUIRED: Design the K series joists assuming the maximum joist spacing = 6’-0” (based on metal roof deck). Assume the joist + accessories weighs 10 PLF.

Step 1 – Determine joist orientation and spacing:

It is best to orient the joists in the short direction for strength. For economy, use a joist spacing = 6’-0” giving 10 even spaces.

36’-0”

60’-0”

Page 61: Structural Analysis and Design Lectures

Lecture 18 - Page 7 of 10

Step 2 – Determine maximum uniformly distributed total service load:

Utilizing the 6 allowable stress design load combinations from the IBC Section 1605.3.1:

1) D 2) D + L 3) D + L + (Lr or S or R) 4) D + (W or 0.7E) + L + (Lr or S or R) 5) 0.6D + W 6) 0.6D + 0.7E

where: D = Dead Load = 6’(16 PSF) + 10 PLF = 106 PLF Lr = Roof Live Load = 6’(25 PSF) = 150 PLF S = Snow Load = 6’(35 PSF) = 210 PLF W = Wind Load = 6’(-12 PSF) = -72 PLF

Check all 6 load combinations and select “worst” case total load:

1) D = 106 PLF 2) D + L = 106 PLF 3) D + L + (Lr or S or R) = 106 + 150 = 256 PLF 4) D + (W or 0.7E) + L + (Lr or S or R) = 106 + 210 = 316 PLF 5) 0.6D + W = 0.6(106) + (-72) = -8.4 PLF 6) 0.6D + 0.7E = 0.6(106) = 64 PLF

Use

Page 62: Structural Analysis and Design Lectures

Lecture 18 - Page 8 of 10

Step 3 – Select lightest joist from Vulcraft K series Load Table p. 12:

Total Load = 316 PLF Live Load = Total Load – Dead Load = 316 PLF – 106 PLF = 210 PLF Span = 36’-0”

Possibilities:

Joist Size: Total Load: Live Load: Wt/ft: 24K8 346 222 11.5 26K7 340 240 10.9 28K6 330 252 11.4 30K7 395 323 12.3

Select 26K7 joist as the lightest from the list above

Step 4 – Select lightest joist from “Economical Joist Guide” p. 109:

For length = 36’, start at the top of the list and read down until Total load > 316 PLF and Live load > 210 PLF

Select 28K6 → Total load = 330, Live load = 252

Use 28K6 Joist for Final Design Step 5 – Determine Bridging requirements, assume horizontal bridging:

From Vulcraft p. 9 → Section Number = 6 Joist spacing = 6’-0” From Vulcraft p. 35 → Section Number = 6 Span = Over 29’ thru 39’

Use 1¼ x 7/64 equal leg angle bridging, good for up to joist spacing = 6’-3”

Use 3 Rows of Bridging

Page 63: Structural Analysis and Design Lectures

Lecture 18 - Page 9 of 10

Step 6 – Draw Summary Sketch of Roof Framing Plan:

3 rows of L1¼x7/64 horizontal bridging equally spaced

28K

6@

6’-0

36’-0”

10 spaces @ 6’-0” = 60’-0”

Page 64: Structural Analysis and Design Lectures

Lecture 18 - Page 10 of 10

Example 2 GIVEN: The roof framing bay from Example 1. REQUIRED: Design the lightest weight 60’-0” span joist girder.

Step 1 – Determine 28K6 joist end reactions:

Joist end reaction = 2

wL

= 2

)"0'36)(316( −PLF

= 5688 LBS. = 5.7 KIPS → USE 6 KIPS

Step 2 – Select joist girder depth from Vulcraft p. 87:

Girder span = 60’-0” Joist Spaces = 10N @ 6.00’ Load on Each Panel Point = 6 KIPS

Use 72G 10N 6.0K Joist Girder

28K6

@6’

-0”

36’-0”

10 spaces @ 6’-0” = 60’-0”

Joist Girder

Select 72” girder depth → wt. = 35 PLF

Page 65: Structural Analysis and Design Lectures

Lecture 19 - Page 1 of 8

Lecture 19 – Steel Deck Steel deck, or sometimes called “metal deck” is used in steel framed construction as an intermediate structural system to distribute floor and roof loads to supporting beams. Decking is typically fastened to the steel supporting members by either puddle welds or powder-actuated fasteners. Although made of steel, it is NOT considered to be structural steel. Decking is corrugated having a typical cross-section resembling: The Steel Deck Institute, SDI, was established in 1939 in an effort to regulate the design, manufacture and installation of steel deck. Manufacturers complying with SDI specifications include Vulcraft, Canam Steel Corp. and United Steel Deck, Inc. Types of Steel Deck

There are 3 general types of steel deck → roof deck, non-composite floor deck and composite deck. 1. Roof Deck

Roof deck is used primarily to carry lightweight roof construction. It is characterized by having relatively narrow bottom flutes so that there is a wider top flute to maximize the surface contact with rigid insulation. It comes in heights ranging from 1” up to 3” and in thicknesses ranging from 24 gage (thinnest) up to 16 gage (thickest). Depending on the section, roof decking can span as much as 15’-0”. Acoustical deck is available to control sound transmission through the decking. It is used for auditoriums, schools, etc., and is obtained by adding fiber sound-absorbing batts between the vertical webs of the decking. In addition, roof deck is available as “cellular” deck for use in placing electrical services or exposed underside. Data relating to roof deck may be found in the Vulcraft catalog p. 3 – 18.

Panel width = 24” → 36”

Deck height Top flute

Bottom flute

Page 66: Structural Analysis and Design Lectures

Lecture 19 - Page 2 of 8

Roof Deck Fastened to Steel Bar Joist

Roof Deck screwed or puddle-welded to top chord of steel joist

Built-up roof membrane

Rigid Insulation

Page 67: Structural Analysis and Design Lectures

Lecture 19 - Page 3 of 8

2. Non-Composite Floor Deck

This type of deck essentially acts as a form to carry the concrete slab. It offers no additional strength to the structural steel beam as composite construction would. It ranges in height from 5/8” up to 3” and thicknesses of 26 gage up to 16 gage with spans up to 15’-0”. It is also available as acoustical deck or as “cellular” deck. Data relating to roof deck may be found in the Vulcraft catalog p. 19 - 40.

Welded wire mesh in concrete slab

Page 68: Structural Analysis and Design Lectures

Lecture 19 - Page 4 of 8

3. Composite Floor Deck

Similar to non-composite deck, except composite deck is used for composite steel construction. Typically, the decking has built-in perforations that aids in the bonding to concrete.

Composite Floor Deck with headed shear studs welded to beams

Page 69: Structural Analysis and Design Lectures

Lecture 19 - Page 5 of 8

Roof Deck Example GIVEN: A 1½” Type “F” (intermediate rib) roof deck is to be used in a 3-span condition with a 7’-0” span. The SERVIVE roof loads are as follows:

• SERVIVE roof Dead Load = 15 PSF • SERVICE roof Live Load = 20 PSF • SERVICE roof Snow Load = 40 PSF • SERVICE roof Wind Load = -8 PSF (uplift)

REQUIRED: Design the lightest-weight 1½” Type “F” roof deck using the Vulcraft catalog.

Step 1 – Determine maximum unif. load on deck:

Utilizing the 6 allowable stress design load combinations from the IBC Section 1605.3.1:

1) D 2) D + L 3) D + L + (Lr or S or R) 4) D + (W or 0.7E) + L + (Lr or S or R) 5) 0.6D + W 6) 0.6D + 0.7E

where: D = Dead Load = 15 PSF Lr = Roof Live Load = 20 PSF S = Snow Load = 40 PSF W = Wind Load = -8 PSF

7’-0”

3 spans (min.)

7’-0” 7’-0”

Steel roof deck

Steel support beams

Page 70: Structural Analysis and Design Lectures

Lecture 19 - Page 6 of 8

Check all 6 load combinations and select “worst” case total load:

1) D = 15 PSF 2) D + L = 15 PSF 3) D + L + (Lr or S or R) = 15 + 20 = 35 PSF 4) D + (W or 0.7E) + L + (Lr or S or R) = 15 + 40 = 55 PSF 5) 0.6D + W = 0.6(15) + (-8) = 1 PSF 6) 0.6D + 0.7E = 0.6(15) = 9 PSF

Step 2 – Refer to the Vulcraft Catalog page 4 for 1½” Type F deck:

From Table above, use Vulcraft 1½” Type F 19 Gage Roof Deck → Allow. Load = 59 PSF > 55 PSF

3 span

Use

7’-0” span

Page 71: Structural Analysis and Design Lectures

Lecture 19 - Page 7 of 8

Non-Composite Floor Deck Example GIVEN: A floor framing plan for an office building is as shown below. The slab is 5” normal-weight concrete over “2.0 C Conform” non-composite 2” deck as manufactured by Vulcraft. The superimposed SERVICE live load = 50 PSF and a total superimposed SERVICE dead load (excluding slab weight) = 38 PSF. REQUIRED: Design the lightest weight 2.0 C Conform non-composite deck assuming 3-span condition.

Step 1 – Determine the uniform load on the decking:

Utilizing the 6 allowable stress design load combinations from the IBC Section 1605.3.1:

1) D 2) D + L 3) D + L + (Lr or S or R) 4) D + (W or 0.7E) + L + (Lr or S or R) 5) 0.6D + W 6) 0.6D + 0.7E

where: D = Dead Load = Slab wt. + Superimposed Dead Load = 51 PSF + 38 PSF = 89 PSF L= FloorLive Load = 50 PSF

Using Load Combination 2 from above:

Total Uniform Load = D + L = 89 PSF + 50 PSF = 139 PSF

4 @ 6’-0” = 24’-0”

See Vulcraft catalog p. 28 for slab wt.

Page 72: Structural Analysis and Design Lectures

Lecture 19 - Page 8 of 8

Step 2 – Refer to “Allowable Uniform Load” table from Vulcraft p. 29:

No. of Spans = 3 Clear Span = 6’-0” Total Uniform Load = 139 PSF

Step 3 – Refer to “Reinf. Conc. Slab Allow. Loads” table Vulcraft p. 28:

Total Slab Depth = 5” Clear Span = 6’-0” Superimposed Unif. Load = Total Load – Slab Wt. = 139 PSF – 51 PSF = 88 PSF

5”

Use 2C20 → Allowable unif. load = 173 PSF > 139 PSF

Use 6x6-W2.1xW2.1 W.W.F. → Allow. load = 107 PSF > 88 PSF

Steel support beam

5” conc. slab over 2” - 20 Gage non-composite metal deck reinf. with 6x6-W2.1xW2.1 W.W.F.

Page 73: Structural Analysis and Design Lectures

Lecture 2 - Page 1 of 8

Lecture 2 – Steel properties and ASD & LRFD principles General Steel Properties:

Structural steel used in buildings uses carbon steel. It is a mixture of mostly iron (98%+) and carbon (0.15% - 0.59%), as well as a percentage of other alloys used to enhance certain properties. Some of the alloys used include silicon, manganese, nickel, sulfur and phosphorus. Different steels exhibit stress-strain relationships as shown below:

As designers of structural steel, we are most interested in the following 3 properties:

a) Modulus of elasticity = 29,000 KSI b) Yield stress = Fy c) Ultimate stress = Fu

Page 74: Structural Analysis and Design Lectures

Lecture 2 - Page 2 of 8

Typical structural shapes: (ref. AISC p. 1-3 thru 1-8)

1) I shapes are categorized into 4 groups – “W”, “M”, “S”, and “HP” 2) Channels – “C” and “MC” 3) Angles – “L” 4) Structural Tees – cut from I shapes, “WT”, “MT” and “ST” 5) Hollow Structural Section – “HSS” rectangular and round 6) Steel pipe

Refer to AISC p. 1-10 thru 1-115 for dimensions and structural properties of the above-noted structural shapes and combination of shapes. Refer to AISC Table 2-3 (page 2-39) for a list of appropriate structural steel ASTM designations for various structural shapes. In general, the following ASTM designations are commonly used: ASTM

Designation Fy (KSI) Fu (KSI) Applicable structural shapes

A36 36 58 M, S, C, MC, L, plates A572 50 65 HP A992 50 65 W A53 35 60 Pipe

A500, Gr. B 42 58 HSS round A500, Gr. B 46 58 HSS rectangular

A588 50 70 Corrosion-resistant for all rolled shapes

Advantages of Steel-Framed Structures:

1) High-strength 2) Excellent quality control, predictability 3) Ductility 4) Speed of erection 5) Lightweight 6) Can be easily modified

Disadvantages of Steel-Framed Structures:

1) Fireproofing 2) Corrosion 3) Need for bracing 4) Semi-skilled labor (ironworkers, welders) 5) Subject to vibration 6) Temperature effects - brittle below -600F - rapid reduction of “E” above 7000F

Page 75: Structural Analysis and Design Lectures

Lecture 2 - Page 3 of 8

Load and Resistance Factor Design (LRFD) see AISC p. 2-6 and 16.1-213 thru 217

The LRFD was developed in the 1980s as an alternative design method to the tried-and-true Allowable Stress Design (ASD) method. It is based on a “limit state” philosophy. A limit state is a term used to describe a condition in which the structure ceases to perform as intended. A “strength limit state” defines the safety against failure due to loading and a “serviceability limit state” is a functional requirement such as deflection, drift or vibration. In general, the LRFD method uses a statistical approach in determining factored loads that are compared against ultimate member strengths. In other words:

ΣλiQi < φRn

where: λI =load factor Qi = working or service load (see IBC ch. 16) φ = reduction factor, see AISC p. 2-10 = 0.90 for limit-states involving yielding = 0.75 for limit-states involving rupture Rn = nominal resistance strength of member

If plotted on a probability graph, 2 bell curves would emerge, one being the probability of loads and the other being the probability of a member’s strength being realized.

Overlap = failure

Probability of member strength, Rn

Probability of loads, ΣQi

Page 76: Structural Analysis and Design Lectures

Lecture 2 - Page 4 of 8

LRFD Load Factors: see AISC p. 2-8 The following 6 load factors are used to obtain the most severe “factored” loads:

1) 1.4D 2) 1.2D + 1.6L + 0.5(Lr or S or R) 3) 1.2D + 1.6(Lr or S or R) + (0.5L or 0.8W) 4) 1.2D + 1.6W + 0.5L + 0.5(Lr or S or R) 5) 1.2D + 1.0E + 0.5L + 0.2S 6) 0.9D + (1.6W or 1.0E)

where: D = service dead loads L = service floor live load Lr = service roof live load S = snow load R = rainwater load W = wind load E = earthquake load Example 1 GIVEN: A flat roof is framed with 24’-0” long W18x40 beams spaced 8’-0” o.c. The service applied roof dead load is 25 PSF and the applied service roof live load = 20 PSF (per IBC ch. 16). The service wind load on the flat roof is -8 PSF (uplift). REQUIRED: 1) Determine the maximum LRFD factored uniform load on the beam, wu. 2) Determine the maximum LRFD factored moment on the beam, Mu.

24’-0”

wu

W18

x40

W18

x40

Typ.

W18

x40

24’-0”

8’-0” Roof Framing Plan Beam Loading F.B.D

Page 77: Structural Analysis and Design Lectures

Lecture 2 - Page 5 of 8

Step 1 – Determine D, Lr and W in terms of PLF:

D = DL(Trib. Width) + Beam wt. = 25 PSF(8 ft) + 40 PLF = 240 PLF Lr = LL(Trib. Width) = 20 PSF(8 ft) = 160 PLF W = -8 PSF(8 ft) = -64 PLF

Step 2 – Determine maximum FACTORED uniform load, wu:

1) 1.4D 1.4(240 PLF) = 336 PLF

2) 1.2D + 1.6L + 0.5(Lr or S or R) 1.2(240 PLF) + 0.5(160 PLF) = 368 PLF

3) 1.2D + 1.6(Lr or S or R) + (0.5L or 0.8W) 1.2(240 PLF) + 1.6(160 PLF) = 544 PLF ← USE

4) 1.2D + 1.6W + 0.5L + 0.5(Lr or S or R) 1.2(240 PLF) + 1.6(-64 PLF) + 0.5(160 PLF) = 266 PLF

5) 1.2D + 1.0E + 0.5L + 0.2S 1.2(240 PLF) = 288 PLF 6) 0.9D + (1.6W or 1.0E)

0.9(240 PLF) + 1.6(-64) = 114 PLF OR 318 PLF

Step 3 – Determine maximum FACTORED moment on beam, Mu:

Mu = 8

2Lwu

= 8

)"0'24)(544( 2−PLF

= 39,168 ft-lb Mu = 39.2 kip-ft

Page 78: Structural Analysis and Design Lectures

Lecture 2 - Page 6 of 8

Allowable Stress Design (ASD) See AISC p. 2-7 and 16.1-216 thru 217

The Allowable Stress Design (ASD) method is based on the concept that the stress levels in a component do not exceed established specific allowable stresses under service loads. For any single component, there may be several different allowable stress limits that must be checked. The basic design equation for ASD is as follows:

Ω≤Σ n

iRQ

where: λI =load factor Qi = working or service load (see IBC ch. 16) Rn = nominal resistance strength of member Ω = safety factor, see AISC p. 2-10 = 1.67 for limit-states involving yielding = 2.00 for limit-states involving rupture

=φ5.1

ASD Load Factors: see AISC p. 2-9

The following 7 load factors are used to obtain the most severe loads:

1) D 2) D+L 3) D+(Lr or S or R) 4) D+0.75L+0.75(Lr or S or R) 5) D+(W or 0.7E) 6) D+0.75(W or 0.7E)+0.75L+0.75(Lr or S or R) 7) 0.6D+(W or 0.7E)

where: D = service dead loads L = service floor live load Lr = service roof live load S = snow load R = rainwater load W = wind load E = earthquake load

Page 79: Structural Analysis and Design Lectures

Lecture 2 - Page 7 of 8

Example 2 GIVEN: Similar to Example 1, a flat roof is framed with 24’-0” long W18x40 beams spaced 8’-0” o.c. The service applied roof dead load is 25 PSF and the applied service roof live load = 20 PSF (per IBC ch. 16). The service wind load on the flat roof is -8 PSF (uplift). REQUIRED: 1) Determine the maximum ASD service uniform load on the beam, w. 2) Determine the maximum ASD service moment on the beam, Mmax.

Step 1 – Determine D, Lr and W in terms of PLF:

D = DL(Trib. Width) + Beam wt. = 25 PSF(8 ft) + 40 PLF = 240 PLF Lr = LL(Trib. Width) = 20 PSF(8 ft) = 160 PLF W = -8 PSF(8 ft) = -64 PLF

Step 2 – Determine maximum SERVICE uniform load, w:

1) D 240 PLF

2) D+L 240 PLF + 0 = 240 PLF

3) D+(Lr or S or R) 240 PLF + 160 PLF = 400 PLF ← USE

W18

x40

W18

x40

Typ.

W18

x40

24’-0”

8’-0” Roof Framing Plan

Page 80: Structural Analysis and Design Lectures

Lecture 2 - Page 8 of 8

4) D+0.75L+0.75(Lr or S or R) 240 PLF + 0 + 0.75(160 PLF) = 360 PLF

5) D+(W or 0.7E) 240 PLF + (-64 PLF) = 176 PLF 240 PLF – (-64 PLF) = 304 PLF

6) D+0.75(W or 0.7E)+0.75L+0.75(Lr or S or R)

240 PLF + 0.75(-64 PLF) + 0 + 0.75(160 PLF) = 312 PLF

7) 0.6D+(W or 0.7E) 0.6(240 PLF) + (-64 PLF) = 80 PLF 0.6(240 PLF) – (-64 PLF) = 208 PLF

Step 3 – Determine maximum SERVICE moment on beam, Mmax:

Mmax = 8

2wL

= 8

)"0'24)(400( 2−PLF

= 28,800 ft-lb Mmax = 28.8 kip-ft

Page 81: Structural Analysis and Design Lectures

Lecture 21 - Page 1 of 8

Lecture 21 – Reinforced Concrete Properties Reinforced concrete structures are typified by their strength, beauty, bulk and longevity. It is the material of choice for many structures where these characteristics are required. Concrete-framed structures have many desirable advantages over other construction materials including:

• Concrete can be “molded” to form almost any imaginable shape • The entire building can be made of concrete – walls, floors, structure • Concrete frames are inherently stable (vs. steel & wood) • Concrete structures are heavy – excellent for wind-prone areas • Concrete is a readily-available material • Concrete is very fire-resistant • Weather-resistant (if built properly) • Relatively inexpensive material

However, reinforced concrete structures have several shortcomings which may preclude it as a building material, including:

• Very labor-intensive • Quality control • Formwork • Longer construction schedule due to curing time • Much larger, heavier member sizes (vs. steel-framed) • Poor insulation values

Page 82: Structural Analysis and Design Lectures

Lecture 21 - Page 2 of 8

Concrete Materials:

Concrete is a mixture of the following materials:

1. Portland Cement – The active ingredient that “glues” the other materials together, conforming to ASTM C 150-99a. The raw materials used in portland cement consist mainly of limestone, and clays & shales. Different types of Portland cement include:

a) Type I – General purpose b) Type II – Moderate sulfate protection and lower heat of

hydration c) Type III – High-early strength d) Type IV – Low heat of hydration used for massive concrete

structures such as dams e) Type V – High sulfate resistance

2. Water – Water is necessary to create the chemical reaction of

hardening the cement called “hydration.” It should be clean and free from any impurities (i.e., potable).

3. Aggregates – Fine (sand) and coarse (gravel). Conforming to

ASTM C 33.

4. Admixtures – Other ingredients added to enhance properties:

a) Air Entrainment – Tiny bubbles used to reduce cracking in concrete subject to freeze-thaw cycles. Conforming to ASTM C 260 with an air content of 4% - 8% by volume.

b) Superplasticizers – Also called “High Range Water Reducers”, used to increase concrete’s flow (workability) instead of adding water. Conforming to ASTM C 494 Type F.

c) Retarders – Used to slow the hydration process. Conforming to ASTM C494 Type D.

d) Accelerators – Used to speed-up the curing process, conforming to ASTM C494 Type C or E.

e) Insulating beads – Increases the “R” value, but diminishes strength.

f) Fly Ash – The byproduct of coal-burning electric generating plants. Used to decrease the amount of portland cement required. Conforming to ASTM C 618 Class F.

g) Colors – Can be mixed to produce any desirable color.

Page 83: Structural Analysis and Design Lectures

Lecture 21 - Page 3 of 8

Reinforced Concrete Properties:

1) Compressive Strength

The specified concrete compressive strength, f’c, is actually a stress. It is the most important structural property of concrete and is VERY DEPENDENT upon the water-to-cement ratio. This is the ratio of the weight of water divided by the weight of cement. A low w/c ratio = high f’c and high w/c ratio = low f’c. A low w/c ratio is very stiff and difficult to work with, therefore necessitating the need for superplasticizers. Normal concrete has w/c ratios ranging from about 0.23 (very strong) up to a maximum of about 0.50 but preferably should not exceed 0.45. Values of f’c are based on 28 days of curing. Typical ranges of f’c are:

f’c = 3000 PSI (slab-on-grade, footings, foundation walls) = 3500 – 5000 PSI (beams, framed slabs) = 4000 – 14000 PSI (columns)

The condition in which concrete cures affects the ultimate strength of the hardened concrete’s f’c. Allowing the freshly-placed concrete to have continuous moisture applied will significantly increase the strength, f’c. Conversely, subjecting the freshly-placed concrete to constant air will decrease the f’c. See the graph below:

Affect of moist curing on concrete strength

Page 84: Structural Analysis and Design Lectures

Lecture 21 - Page 4 of 8

2) Tensile Strength

Concrete is a brittle material and has very small tensile strength (about 10% of f’c). It is usually assumed that concrete has zero tensile strength.

3) Modulus of Elasticity – Determined by formula below:

Econc = 57000 cf ' where f’c = concrete specified compressive stress in PSI

Example: GIVEN: Concrete with f’c = 4000 PSI. REQUIRED: Determine Econc

Econc = 57000 cf ' = 57000 PSI4000 = 3,605,000 PSI Econc = 3605 KSI

Page 85: Structural Analysis and Design Lectures

Lecture 21 - Page 5 of 8

4) Reinforcing Bars – Used to carry ALL of the tension in a concrete

member, as well as helping to carry shear and compression. The steel uses for bars is typically new “billet” steel having the usual modulus of elasticity “E” = 29,000 KSI. The size of a bar refers to its diameter in 1/8ths. For example a #5 bar is ⅝” in diameter (see table below). Rebar should conform to ASTM A615 for deformed (ribbed) bars. Typical grades include:

a) Grade 60 – Has a yield stress Fy = 60 KSI, used for all bars b) Grade 40 – Has a yield stress Fy = 40 KSI, used for low-strength

applications only

Bar Size: Diameter: Area (in2): #3 ⅜” 0.11 #4 ½” 0.20 #5 ⅝” 0.31 #6 ¾” 0.44 #7 ⅞” 0.60 #8 1” 0.79 #9 1⅛” 1.00

#10 1¼” 1.27 #11 1⅜” 1.56

The following diagram shows the typical markings on a deformed reinforcing bar:

Page 86: Structural Analysis and Design Lectures

Lecture 21 - Page 6 of 8

Epoxy-coated reinforcing bars are regular bars with a shop-applied coating of epoxy. These bars have exceptional resistance to corrosion and are used in situations where there is high water/salt exposure (such as road bridge decks, marine structures, etc.). They are smooth to the touch and usually green in color. Codes allow the placement of epoxy-coated bars to be closer to the surface than regular bars because of the increased resistance to corrosion. This usually results in a thinner, lighter concrete beam or slab. Unfortunately, the epoxy coating is often scratched or damaged during construction, leaving exposed bare steel. This exposed bare steel is ripe for allowing moisture and salt deposits to enter and actually INCREASING the propagation of corrosion. For this reason, many state Departments of Transportation do not allow epoxy-coated reinforcing bars for use in bridge decks.

Bridge deck constructed with epoxy-coated reinforcing bars

Page 87: Structural Analysis and Design Lectures

Lecture 21 - Page 7 of 8

Reinforcing bars are placed a certain minimum distance away from the edge of the member to ensure that it will not be susceptible to water/salt infusion. This is referred to as cover distance. The cover distance requirements shown below are obtained from ACI 318-02 “Building Code Requirements for Structural Concrete.”

Minimum Concrete Cover Over Reinforcing Bars Condition: Minimum cover:

Concrete cast against and permanently exposed to earth 3” No. 6 through No. 18 bars 2” Concrete exposed to earth or

weather No. 5 and smaller bars 1½” No. 14 & No. 18

1½” Slabs, walls & joists

No. 11 and smaller

¾”

Beams, columns

Main reinf., stirrups, ties, spirals

1½”

No. 6 and larger

¾”

Concrete NOT exposed to earth or weather

Shells, folded plates No. 5 and

smaller ½”

Required minimum cover distance

Required minimum cover distance

Concrete member

Reinforcing bars

Page 88: Structural Analysis and Design Lectures

Lecture 21 - Page 8 of 8

5) Slump – Fresh concrete uses a slump test to determine the workability of the concrete as per ASTM C 143. It is, however, not a very useful measure of the concrete’s strength. It is possible to get very workable concrete with high slump (i.e., very fluid) with the use of superplasticizers.

The test involves taking a cone-shaped mold and pouring a sample of concrete into it. Next, the cone is removed upward and the vertical displacement of the concrete is measured.

Technicians performing a slump test on fresh concrete

Recommended Slumps for Various Types of Construction

Slump: Type of Concrete Member: Maximum Minimum

Foundation walls & footings 3” 1” Beams and walls 4” 1” Columns 4” 1” Pavements and slabs 3” 1” Mass concrete 2” 1”

Page 89: Structural Analysis and Design Lectures

Lecture 22 - Page 1 of 8

Lecture 22 – Introduction to ACI 318-02 The American Concrete Institute (ACI) is the governing agency for all concrete construction in the U.S. It was established in 1904 to serve and represent user interests in the field of concrete. The ACI publishes many different standards, but the most commonly referenced standard used by architects and engineers is the ACI 318 “Building Code Requirements for Structural Concrete.” It is updated every 7 years and the latest version is ACI 318-02 updated in 2002. Almost all Building Codes, including the IBC, refer to ACI 318 as the basis for structural design of concrete members.

Contents: PART 1—GENERAL

CHAPTER 1—GENERAL REQUIREMENTS .................................................318-9 CHAPTER 2—DEFINITIONS........................................................................ 318-19

PART 2—STANDARDS FOR TESTS AND MATERIALS

CHAPTER 3—MATERIALS.......................................................................... 318-27

Page 90: Structural Analysis and Design Lectures

Lecture 22 - Page 2 of 8

PART 3—CONSTRUCTION REQUIREMENTS

CHAPTER 4—DURABILITY REQUIREMENTS............................................ 318-41 CHAPTER 5—CONCRETE QUALITY, MIXING, AND PLACING .................318-47 CHAPTER 6—FORMWORK, EMBEDDED PIPES, AND CONSTRUCTION JOINTS .............. 318-63 CHAPTER 7—DETAILS OF REINFORCEMENT........................................ 318-69

PART 4—GENERAL REQUIREMENTS

CHAPTER 8—ANALYSIS AND DESIGN - GENERAL CONSIDERATIONS ............................318-85 CHAPTER 9—STRENGTH AND SERVICEABILITY REQUIREMENTS ...................................318-95 CHAPTER 10—FLEXURE AND AXIAL LOADS............................................318-109 CHAPTER 11—SHEAR AND TORSION....................................................... 318-139 CHAPTER 12—DEVELOPMENT AND SPLICES OF REINFORCEMENT ..............................318-187

PART 5—STRUCTURAL SYSTEMS OR ELEMENTS

CHAPTER 13—TWO-WAY SLAB SYSTEMS............................................ 318-213 CHAPTER 14—WALLS.............................................................................. 318-233 CHAPTER 15—FOOTINGS........................................................................ 318-241 CHAPTER 16—PRECAST CONCRETE .................................................... 318-249 CHAPTER 17—COMPOSITE CONCRETE FLEXURAL MEMBERS ........ 318-257 CHAPTER 18—PRESTRESSED CONCRETE........................................... 318-261 CHAPTER 19—SHELLS AND FOLDED PLATE MEMBERS...................... 318-289

PART 6—SPECIAL CONSIDERATIONS

CHAPTER 20—STRENGTH EVALUATION OF EXISTING STRUCTURES.......................... 318-297 CHAPTER 21—SPECIAL PROVISIONS FOR SEISMIC DESIGN................318-303

PART 7—STRUCTURAL PLAIN CONCRETE

CHAPTER 22—STRUCTURAL PLAIN CONCRETE ....................................318-343

COMMENTARY REFERENCES......................................................318-353

APPENDIXES

APPENDIX A—STRUT-AND-TIE MODELS ..................................................318-369 APPENDIX B—ALTERNATIVE PROVISIONS FOR REINFORCED AND PRESTRESSED CONCRETE FLEXURAL AND COMPRESSION MEMBERS ..............................................318-385 APPENDIX C—ALTERNATIVE LOAD AND STRENGTH REDUCTION FACTORS................318-393 APPENDIX D—ANCHORING TO CONCRETE.................................................318-399 APPENDIX E—NOTATION................................................................................318-427 APPENDIX F—STEEL REINFORCEMENT INFORMATION ............................318-437 INDEX.................................................................................................................318-439

Page 91: Structural Analysis and Design Lectures

Lecture 22 - Page 3 of 8

Analysis and Design – General Considerations

Design Basis:

Similar to the LRFD method in steel, concrete is designed on the basis of “Ultimate” loading. This is often referred to as “Strength” design. Factors are applied to service loads in accordance with ACI 318 Section 9.2. These factored loads are used to determine maximum factored moments, shears and other effects which are then compared to the strength of the member. Strength of member is reduced by a strength reduction factor.

Factored Load Effects < (φ)Member Strength

Load Factors:

1) 1.4(D + F) 2) 1.2(D + F + T) + 1.6(L + H) + 0.5(Lr or S or R)

3) 1.2D + 1.6(Lr or S or R) + (1.0L or 0.8W) 4) 1.2D + 1.6W + 1.0L + 0.5(Lr or S or R) 5) 1.2D + 1.0E + 1.0L + 0.2S 6) 0.9D + 1.6W + 1.6H 7) 0.9D + 1.0E + 1.6H

where: D = service dead loads

L = service live load Lr = service roof live load S = snow loads

W = wind loads R = rainwater loads E = earthquake loads F = fluid loads H = soil loads

T = Temperature, creep, settlement, shrinkage loads

Strength Reduction Factors, φ

Member Type: φ Tension member 0.90

Spiral reinforced 0.70 Compression member Tied reinforced 0.65

Flexural members (beams) 0.85 Shear and torsion 0.75 Bearing 0.65

Page 92: Structural Analysis and Design Lectures

Lecture 22 - Page 4 of 8

Example 1 GIVEN: The interior column of a 2-story concrete-framed building has the following applied service loads to the 1200 ft2 tributary area as shown:

Roof live load = 20 PSF Snow load = 45 PSF Roof superimposed dead load (not including 8” thick slab) = 16 PSF Roof wind uplift = -8 PSF Floor live load = 100 PSF Floor superimposed dead load (not including 10” thick slab) = 42 PSF

REQUIRED: Determine the maximum factored load, Pu, at the bottom of the 20” x 20” square column.

Trib. area = 1200 ft2

Page 93: Structural Analysis and Design Lectures

Lecture 22 - Page 5 of 8

Step 1 – Determine the total service loads on the roof:

a) Service roof live load, Lr = Trib. area(Roof PSF) = 1200 ft2(20 PSF)

= 24,000 lbs. = 24.0 KIPS

b) Service snow load, S = Trib. area(Floor PSF) = 1200 ft2(45 PSF) = 54,000 lbs. = 54.0 KIPS c) Service wind uplift load, W = 1200 ft2(-8 PSF) = -9,600 lbs. = -9.6 KIPS d) Service roof dead load, Droof = (Superimposed loads) + (slab wt.) = 1200 ft2(16 PSF) + 1200 ft2 ⎟

⎠⎞

⎜⎝⎛ )150(12

"8 PCF

= 19,200 lbs. + 120,000 lbs. = 139,200 lbs. = 139.2 KIPS

Step 2 – Determine the total service loads on the 2nd floor:

a) Service floor live load, L = 1200 ft2(100 PSF) = 120,000 lbs. = 120.0 KIPS

b) Service floor dead load, Dfloor = (Superimposed loads) + (slab wt.) = 1200 ft2(42 PSF) + 1200 ft2 ⎟

⎠⎞

⎜⎝⎛ )150(

12"10 PCF

= 50,400 lbs. + 150,000 lbs. = 200,400 lbs. = 200.4 KIPS

Step 3 – Determine the total service dead load of the concrete column:

Column dead load, Dcolumn = ( )( )3/1502812

"2012

"20 ftlbft⎟⎠⎞

⎜⎝⎛⎟⎠⎞

⎜⎝⎛

= 11,667 lbs. = 11.7 KIPS

Page 94: Structural Analysis and Design Lectures

Lecture 22 - Page 6 of 8

Step 4 – Sum all service dead loads together:

Total service dead load, D = Droof + Dfloor + Dcolumn = 139.2 KIPS + 200.4 KIPS + 11.7 KIPS = 351.3 KIPS

Step 5 – Check all 7 load factors, select “worst” case:

1) 1.4(D + F) 1.4(351.3) = 491.8 KIPS 2) 1.2(D + F + T) + 1.6(L + H) + 0.5(Lr or S or R) 1.2(351.3) + 1.6(120.0) + 0.5(54.0) = 640.6 KIPS ← USE

3) 1.2D + 1.6(Lr or S or R) + (1.0L or 0.8W) 1.2(351.3) + 1.6(54.0) + (1.0(120.0)) = 628.0 KIPS 4) 1.2D + 1.6W + 1.0L + 0.5(Lr or S or R) 1.2(351.3) + 1.6(-9.6) + 1.0(120.0) + 0.5(54) = 553.2 KIPS 5) 1.2D + 1.0E + 1.0L + 0.2S 1.2(351.3) + 1.0(120) + 0.2(54.0) = 552.4 KIPS 6) 0.9D + 1.6W + 1.6H 0.9(351.3) + 1.6(-9.6) = 300.8 KIPS

7) 0.9D + 1.0E + 1.6H 0.9(351.3) = 316.2 KIPS

From above, Pu = 640.6 KIPS

Page 95: Structural Analysis and Design Lectures

Lecture 22 - Page 7 of 8

Example 2 GIVEN: The cantilevered floor balcony beam/slab as shown below. The service superimposed dead load (not including concrete) = 14 PSF and the superimposed service live load = 75 PSF. REQUIRED: Determine the maximum factored moment, Mu on the cantilevered beam.

wu

16’-0”

18”

10”

14’-0”

5” slab

Beam

14’-0”

Side view of cantilevered beam

Page 96: Structural Analysis and Design Lectures

Lecture 22 - Page 8 of 8

Step 1 – Determine service dead load, D acting on beam:

Since there are 2 beams, each supports ½ of the balcony:

Weight of concrete (shaded area) = ⎟⎠⎞

⎜⎝⎛ + )

12"13)(

12"10()

12"5)('8(150

3ftlb

= 635.4 PLF Superimposed dead load on beam = 8’(14 PSF) = 112 PLF Total dead load acting on beam, D = 635.4 PLF + 112 PLF = 747.4 PLF

Step 2 – Determine service live load, L acting on beam:

Live load acting on beam = 8’(75 PSF) = 600 PLF

Step 3 – Determine factored uniform load on beam, wu: By inspection, use load factor 1.2D + 1.6L

wu = 1.2(747.4 PLF) + 1.6(600 PLF) = 1857 PLF = 1.9 KLF

Step 4 – Determine maximum factored moment on beam, Mu:

For a cantilevered beam, Mmax = Mu = 2

2Lwu

= 2

)"0'14)(9.1( 2−KLF

Mu = 186.2 KIP-FT

18”

8’-0” 16’-0”

10”

5” slab

18” – 5” slab

Page 97: Structural Analysis and Design Lectures

Lecture 23 - Page 1 of 9

Lecture 23 – Flexural Members Flexural members are those that experience primarily bending stresses, such as beams. A typical reinforced concrete beam is shown below:

Concrete cover = ¾” → 2” as per ACI reqmts.

Dep

th to

ste

el “d

Hei

ght

“h”

Width “b”

Section A-A

Hanger bars (#4 or #5 bars)

Stirrup bars (used to prevent diag. tension cracks) spaced at d/2 apart

Tension bars “As”

Page 98: Structural Analysis and Design Lectures

Lecture 23 - Page 2 of 9

Sometimes, 2 (or more) rows of main tension bars are necessary. It is important to provide minimum adequate cover around all reinforcing bars so that these bars can properly bond with the concrete. ACI 318 dictates that the minimum spacing between bars is 1.5 times the maximum concrete aggregate size. Typical concrete batches use a maximum aggregate size of ¾” diameter, so then the minimum bar spacing = 1.5(¾”) = 1⅛”. Below is a sketch of a typical concrete beam with 2 rows of tension bars:

Min. bar spacing

Min. bar spacing

Dep

th to

cen

troid

of s

teel

“d”

Hei

ght

“h”

Tension bars “As”

Page 99: Structural Analysis and Design Lectures

Lecture 23 - Page 3 of 9

As = Total cross-sectional area of all tension bars, in2 d = depth to center of tension bars, inches = h – (concrete cover) – (stirrup bar dia.) – ½(tension bar dia.)

fy = yield stress of reinforcing bars = 60 KSI for ASTM A615 Grade 60 bars = 40 KSI for ASTM A615 Grade 40 bars ρactual = actual ratio of tension steel to effective concrete area

= bdAs

ρmin = minimum allowable ratio of tension steel per ACI 318

= yf

200 where fy = PSI

Page 100: Structural Analysis and Design Lectures

Lecture 23 - Page 4 of 9

Example 1 GIVEN: A rectangular concrete beam is similar to the one shown above. Use the following:

• Height h = 20” • Width b = 12” • Concrete f’c = 4000 PSI • Concrete cover = ¾” • All bars are A615 – Grade 60 (fy = 60 KSI) • Stirrup bar = #3 • 4 - #7 Tension bars

REQUIRED: 1) Determine total area of tension bars, As. 2) Determine depth to center of tension bars, d.

3) Determine ρactual = bdAs where ρmin =

yf200 and state if it is acceptable.

Step 1 – Determine area of tension bars, As:

As = 4 bars(0.60 in2 per bar) As = 2.40 in2

Step 2 – Determine depth to tension bars, d:

d = depth to center of tension bars, inches = h – (concrete cover) – (stirrup bar dia.) – ½(tension bar dia.) = 20” – ¾” – ⅜” – ½(⅞”) d = 18.44”

Step 3 – Determine ρactual and ρmin :

ρactual = bdAs

= )"44.18)("12(

40.2 2in

ρactual = 0.0108 Since ρactual > ρmin → beam is acceptable

ρmin = yf

200

= PSI60000

200

ρmin = 0.0033

See Lect. 21 notes

Page 101: Structural Analysis and Design Lectures

Lecture 23 - Page 5 of 9

A basic understanding of beam mechanics is necessary to study concrete beam behavior. Consider a simply-supported homogeneous rectangular beam loaded by a uniformly-distributed load as shown below: Taking a section through the beam at any place along the length reveals the following stress distribution about the cross-section of the beam:

Compression

Tension

Applied loads

Span L

Neutral Axis The stress distribution

varies linearly from zero stresses at the neutral axis, to a maximum tensile or compressive stress at the extreme edges.

Homogeneous Beam

Page 102: Structural Analysis and Design Lectures

Lecture 23 - Page 6 of 9

In a reinforced concrete beam, the stress distribution is different. Above the neutral axis, the concrete carries all the compression, similar to the homogeneous beam. Below the neutral axis however, the concrete is incapable of resisting tension and must rely on the reinforcing bars to carry all the tension loads. Looking at a side view of the stress distribution of the reinforced concrete beam:

½ (a

)

b

Neutral Axis

0.85f’cb

T = Asfy T = Asfy

a = β 1

C

Compression

Tension = T

Neutral Axis The actual stress distribution

in the compression side varies non-linearly from zero stresses at the neutral axis, to a maximum compressive stress at the extreme edge.

Reinforced Concrete Beam

Reinforcing bars

Actual Stress Distribution Idealized Stress Distribution

Moment arm = Z

C

d

“Whitney” stress block

Page 103: Structural Analysis and Design Lectures

Lecture 23 - Page 7 of 9

Assuming an idealized beam, tension equals compression:

Tension = Compression Asfy = Area of Whitney stress block Asfy = 0.85f’cab

Solve for a:

a = bf

fA

c

ys

'85.0 = β1C

β1 = 0.85 for f’c < 4000 PSI

= 0.80 for f’c = 5000 PSI = 0.75 for f’c > 6000 PSI

C = depth to neutral axis from extreme compression edge

Mn = Nominal moment capacity of concrete beam = Asfy(Moment arm) = AsfyZ

= Asfy(d - )2a

Mu = Usable moment capacity of concrete beam = φMn = 0.9Mn

Mu = 0.9(Asfy(d - )2a )

Mu = 0.9Asfyd(1 - ⎥⎥⎦

⎢⎢⎣

⎡⎟⎟⎠

⎞⎜⎜⎝

c

yact

ff

'59.0

ρ)

ρbal = balanced ratio of tension steel reinforcement

= ⎟⎟⎠

⎞⎜⎜⎝

+⎟⎟⎠

⎞⎜⎜⎝

yy

c

fff

000,87000,87'85.0 1β where fy = PSI

ρmax = maximum allowable ratio of tension steel reinforcement per ACI 318 = 0.75ρbal

Page 104: Structural Analysis and Design Lectures

Lecture 23 - Page 8 of 9

Example 2 GIVEN: The concrete beam from Example 1 is used to support the loading as shown below. REQUIRED:

1. Determine the maximum factored applied moment, Mmax. 2. Determine the usable moment capacity of the beam, Mu, and determine if

it is acceptable based on Mmax. 3. Determine if the beam is acceptable based on ρmax.

Step 1 – Determine maximum factored applied moment, Mmax:

Mmax = 8

2Lwu

= 8

)"0'20)(3( 2−KLF

Mmax = 150 KIP-FT

Step 2 - Determine the usable moment capacity of the beam, Mu:

Factored uniform load wu = 3000 PLF (incl. beam wt.)

20’-0”

Mu = 0.9Asfyd(1 - ⎥⎥⎦

⎢⎢⎣

⎡⎟⎟⎠

⎞⎜⎜⎝

c

yact

ff

'59.0

ρ) where ρact = 0.0108 (see Ex. 1)

= 0.9(2.40 in2)(60 KSI)(18.44”)(1 - ⎥⎦

⎤⎢⎣

⎡⎟⎠⎞

⎜⎝⎛

KSIKSI

4)60)(0108.0(59.0 )

= 2161.4 KIP-IN Mu = 180.1 KIP-FT Since Mu = 180.1 KIP-FT > Mmax = 150 KIP-FT → beam is acceptable

Page 105: Structural Analysis and Design Lectures

Lecture 23 - Page 9 of 9

Step 3 – Determine if the beam is acceptable based on ρmax:

ρmax = maximum allowable ratio of tension steel reinforcement per ACI 318 = 0.75ρbal

ρbal = balanced ratio of tension steel reinforcement

= ⎟⎟⎠

⎞⎜⎜⎝

+⎟⎟⎠

⎞⎜⎜⎝

yy

c

fff

000,87000,87'85.0 1β where fy = PSI

where β1 = 0.85 since f’c = 4000 PSI

= ⎟⎠

⎞⎜⎝

⎛+

⎟⎠⎞

⎜⎝⎛

PSIKSIKSI

60000000,87000,87

60)4)(85.0(85.0

= 0.0285

ρmax = 0.75(0.0285) ρmax = 0.0214 > ρact = 0.0108 → beam is acceptable

Page 106: Structural Analysis and Design Lectures

Lecture 24 - Page 1 of 9

Lecture 24 – Flexural Members (cont.) Determining the usable moment capacity, Mu, of a rectangular reinforced concrete beam is accomplished by using the formula below: (see Lect. 23)

Mu = 0.9Asfyd(1 - ⎥⎥⎦

⎢⎢⎣

⎡⎟⎟⎠

⎞⎜⎜⎝

c

yact

ff

'59.0

ρ)

Designing a beam using the equation above is much more difficult. Assuming the material properties and dimensions are known, the equation above still has 2 unknown variables – As and ρact. Therefore, design of steel reinforcement for a given beam is largely one of trial-and-error. Beam Design

Design of concrete beam members is often one of trial-and-error. It’s difficult to directly solve for all the variables in a reinforced concrete beam. Usually, material properties are known as well as maximum applied factored moment, Mmax. The following Table is useful to get a “trial” beam size:

Minimum Suggested Thickness “h” of Concrete Beams & One-Way Slabs End Conditions Member:

Simply supported

One end continuous

Both ends continuous

Cantilever

Solid one-way slab L/20 L/24 L/28 L/10 Beam L/16 L/18.5 L/21 L/8

Span length L = inches Beams are usually rectangular having the width typically narrower than the height. The diagram below shows typical beam aspect ratios:

h ≈ 1.5b → 2.5b

b

Page 107: Structural Analysis and Design Lectures

Lecture 24 - Page 2 of 9

Beam Design Aid

It is still difficult to directly design a reinforced concrete beam even if dimensions and material properties are known. The use of design aids are commonly used to streamline the design process instead of laboriously using a trial-and-error approach.

The design aid shown below is used for design or analysis. Values of 2bdM u

φ

are in units of PSI. It can be used to directly solve for ρact knowing factored actual moment Mu, f’c, fy, b and d.

Table 1 - Concrete f’c = 3000 PSI, Grade 60 Bars

Page 108: Structural Analysis and Design Lectures

Lecture 24 - Page 3 of 9

Table 2 – Concrete f’c = 4000 PSI, Grade 60 Bars

Page 109: Structural Analysis and Design Lectures

Lecture 24 - Page 4 of 9

Example 1 GIVEN: A rectangular concrete beam with dimensions is shown below (stirrup bars not shown). Use concrete f’c = 4000 PSI and grade 60 bars. REQUIRED:

1) Determine the usable moment capacity Mu of the beam using formula. 2) Determine the usable moment capacity Mu of the beam using Table 2.

Step 1 – Determine usable moment capacity Mu of the beam using formula:

ρact = bdAs

= )"18)("12(

)__60.0(3 2 barperin

ρact = 0.0083

Mu = 0.9Asfyd(1 - ⎥⎥⎦

⎢⎢⎣

⎡⎟⎟⎠

⎞⎜⎜⎝

c

yact

ff

'59.0

ρ)

= 0.9(1.80 in2)(60 KSI)(18”)(1 - ⎥⎦

⎤⎢⎣

⎡⎟⎠⎞

⎜⎝⎛

KSIKSI

4)60)(0083.0(59.0 )

= 1621 KIP-IN Mu = 135 KIP-FT

d = 18”

b =12”

3 - # 7 bars

Page 110: Structural Analysis and Design Lectures

Lecture 24 - Page 5 of 9

Step 2 - Determine the usable moment capacity Mu of the beam using Table 2:

From Table 2:

At ρ = 0.0083 → PSIbdM u 4.4612 =φ

Solving for Mu:

Mu = 461.4 PSI(φbd2) = 461.4 PSI[(0.9)(12”)(18”)2] = 1,614,531 LB-IN = 1615 KIP-IN Mu = 134.6 KIP-FT

NOTE: This answer is the same as in Step 1.

Page 111: Structural Analysis and Design Lectures

Lecture 24 - Page 6 of 9

Example 2 GIVEN: The concrete beam below. Use the following:

• Concrete f’c = 4000 PSI • Steel grade 60 • Concrete cover = ¾” • #8 bars are to be used for main tension bars • #3 stirrups

REQUIRED: Design the rectangular beam such that h ≈1.5b and ρact ≈ ½ (ρmax).

Step 1 – Determine maximum factored moment, Mmax:

Mmax = 8

2Lwu

= 8

)"0'28)(2( 2−KLF

Mmax = 196 KIP-FT = 2352 KIP-IN = 2,352,000 LB-IN

wu = 2 KLF

28’-0”

Page 112: Structural Analysis and Design Lectures

Lecture 24 - Page 7 of 9

Step 2 – Select values from Table 2:

a) Select ρact = ½(ρmax) = ½(0.0214) TRY ρact = 0.0107

b) At ρ = 0.0107 → 2bdM u

φ = 581.2 PSI

Step 3 – Solve for “b” and “d” by substituting Mmax for Mu in above equation:

2bdM u

φ = 581.2 PSI

where: Mu = Mmax = 2,352,000 LB-IN φ = 0.9 d = 1.5b

PSIbb

2.581)5.1)()(9.0(

23520002 =

Solve for “b”:

PSIb

2.581)25.2)(9.0(

23520003 =

3)2.581)(25.2)(9.0(

2352000=b

b = 12.6” → Use b = 12” d = 1.5b = 1.5(12”) d ≈ 18”

Page 113: Structural Analysis and Design Lectures

Lecture 24 - Page 8 of 9

Step 4 – Select beam dimensions:

From above, use b = 12” and d ≈ 18” h = d + conc. cover + stirrup bar dia. + ½(main bar dia.) = 18” + ¾” + 3/8” + ½(1”) = 19.625” → Use h = 20”

Revised d = 20” – ¾” – ⅜” – ½(1”) = 18.375”

Step 5 – Determine required area of main tension bars:

From above, ρact = 0.0107 = bdAs

Solve for As:

As = 0.0107(b)(d) = 0.0107(12”)(18.375”) As = 2.36 in2

Step 6 – Determine number of #8 main tension bars:

No. of bars = baroneofArea

As

___

= barperin

in_8_#_79.0

36.22

2

= 2.99 bars → USE 3 - #8 bars

#3 stirrup bar dia. = 3/8” #8 main bar dia. = 1”

Page 114: Structural Analysis and Design Lectures

Lecture 24 - Page 9 of 9

Step 7 – Check beam height with “Minimum Thickness of Beams” Table: From Table:

Member type = Beam End Condition = Simply-supported

h ≈ 16L

≈ 16

)/"12)("0'28( ft−

h ≈ 21” which is approximately = 20” as designed

Step 8 – Draw “Summary Sketch” labeling all information necessary to build it:

h ≈ 16L

¾” concrete cover

20”

12”

Section A-A

2 - #4 hanger bars

#3 stirrup bars @ 9” o.c.

3 - #8 main bars

Notes: 1) Concrete f’c = 4000 PSI normal-weight 2) All bars ASTM A615 Grade 60

Page 115: Structural Analysis and Design Lectures

Lecture 25 - Page 1 of 9

Lecture 25 – T- Beams Concrete beams are often poured integrally with the slab, forming a much stronger “T” – shaped beam. These beams are very efficient because the slab portion carries the compressive loads and the reinforcing bars placed at the bottom of the stem carry the tension. A T-beam typically has a narrower stem than an ordinary rectangular beam. These stems are typically spaced from 4’-0” apart to more than 12’-0”. The slab portion above the stem is designed as a one-way slab spanning between stems (see Lecture 26).

A typical T-beam has the following dimensions and notations:

bw bw

d Overhang width

Clear distance

hf = Slab thickness

b = Effective flange width

Main tension bars at bottom of stem

Slab

NOTE: Stirrups in T-beam are required (not shown in this sketch)

Page 116: Structural Analysis and Design Lectures

Lecture 25 - Page 2 of 9

Assuming T-beams are symmetrical, the following design dimensions are used:

Overhang width = smaller

b = smaller T-Beam Analysis

T-beams are analyzed similarly to rectangular beams, except the compression area is a narrow “strip” usually located in the slab.

hf

a = Effective conc. compressive thickness

8hf or ½(Clear distance)

¼(Beam span) or (2 x overhang width) + bw

bw

Z = (d - 2a )

b = Effective flange width

d

Ac = Shaded area = Effective concrete compression area = (a)(b)

As = Total area of main tension bars

Page 117: Structural Analysis and Design Lectures

Lecture 25 - Page 3 of 9

Mu = Usable moment capacity of T-beam

= φTZ

where: φ = 0.9 T = Tension force developed in main bars = Asfy Ac = Effective concrete compression area

= cf

T'85.0

a = Effective concrete compressive thickness

= bAc

Z = Moment arm distance between center of compression to center of tension

= d - 2a

Page 118: Structural Analysis and Design Lectures

Lecture 25 - Page 4 of 9

Example 1 GIVEN: A commercial building has T-beams spaced 6’-6” (center-to-center) with a 4” concrete slab as shown in the framing plan and cross-section views below. Use the following information:

• Superimposed service floor dead load (NOT including conc. wt.) = 40 PSF • Superimposed service floor live load = 100 PSF • Concrete f’c = 3000 PSI • ASTM A615 Grade 60 bars

REQUIRED:

1) Determine the maximum factored moment, Mmax, on the T-beam. 2) Determine the usable moment capacity, Mu, for the T-beam.

A A

Typ.

6’-6”

T-be

am s

pan

= 20

’-0”

T-beam

Perimeter girder Column

Framing Plan

Page 119: Structural Analysis and Design Lectures

Lecture 25 - Page 5 of 9

Step 1 – Determine maximum factored moment, Mmax, on T-beam:

Determine area of T-beam = Slab area + Stem area = (6.5’)(0.333’) + (1’)(0.666’) = 2.83 ft2 Determine service weight of T-beam = Area of T-beam x Conc. unit wt. = 2.83 ft2(150 lb/ft3) = 425 PLF Det. factored uniform load on T-beam wu = 1.2D + 1.6L

= 1.2[(6.5’)(40 PSF) + 425 PLF] + 1.6[(6.5’)(100 PSF)] = 822 PLF + 1040 PLF = 1862 PLF → Use wu = 1.9 KLF

Det. Maximum factored moment, Mmax = 8

2Lwu

= 8

)"0'20)(9.1( 2−KLF

Mmax = 95 KIP-FT

Service Dead Load Service Live Load

8”

16”

6’-6” 4”

2 - #9 bars

Section “A-A” Thru T-Beams

Page 120: Structural Analysis and Design Lectures

Lecture 25 - Page 6 of 9

Step 2 – Determine effective concrete slab width “b”:

Overhang width = smaller

b = smaller

Step 3 – Determine effective conc. compression area Ac:

T = Tension force developed in main bars = Asfy = 2 bars(1.00 in2 per #9 bar)(60 KSI) = 120 KIPS Ac = Effective concrete compression area

= cf

T'85.0

= )3(85.0

120KSI

KIPS

= 47.1 in2

¼(Beam span) = ¼(20’-0” x 12”/ft) = 60” ← USE or (2 x overhang width) + bw = (2 x 32” + 8”) = 72”

8hf = 8(4”) = 32” ← USE or ½(Clear distance) = ½(78” – 8”) = 35”

Page 121: Structural Analysis and Design Lectures

Lecture 25 - Page 7 of 9

Step 4 – Determine usable moment capacity, Mu for the T-beam:

a = Effective concrete compressive thickness

= bAc

= "60

1.47 2in

a = 0.79”

Z = Moment arm distance between center of compression to center of tension

= d - 2a

= 16” - 2

"79.0

Z = 15.6”

Mu = φTZ = 0.9(120 KIPS)(15.6”) = 1685 KIP-IN Mu = 140.4 KIP-FT NOTE: Since Mu = 140.4 KIP-FT > Mmax = 95 KIP-FT, T-beam is ACCEPTABLE.

Page 122: Structural Analysis and Design Lectures

Lecture 25 - Page 8 of 9

Heavily-Reinforced T-Beams

T-beams with a lot of tension reinforcement may have a portion of the effective concrete area located within the stem as shown below: The location of the centroid of the effective concrete compression area is found by methods discussed in AECT 210 – Structural Theory (see Lecture 5). After the location is found, analysis is exactly the same as ordinary T-beams. Similar to ordinary rectangular reinforced concrete beams, the ACI 318 limits the amount of tension steel in T-beams so that the steel will yield prior to concrete compression failure. The maximum area of steel, As is shown in the table below.

Maximum Tensile Steel Permitted in T-Beams Concrete and Steel Properties: Formula (As = in2) Concrete f’c = 3000 PSI Steel fy = 40 KSI

As max = 0.0478[bhf + bw(0.582d – hf)]

Concrete f’c = 3000 PSI Steel fy = 60 KSI

As max = 0.0319[bhf + bw(0.503d – hf)]

Concrete f’c = 4000 PSI Steel fy = 40 KSI

As max = 0.0638[bhf + bw(0.582d – hf)]

Concrete f’c = 4000 PSI Steel fy = 60 KSI

As max = 0.0425[bhf + bw(0.503d – hf)]

bw

hf

b

Z d

As

Ac = Shaded area = Effective concrete compression area

Page 123: Structural Analysis and Design Lectures

Lecture 25 - Page 9 of 9

Example 2 GIVEN: The T-beam from Example 1. REQUIRED: Determine the maximum area of tension steel permitted, As max:

Step 1 – Determine As max:

From Example 1:

Concrete f’c = 3000 PSI Steel fy = 60 KSI b = 60” hf = 4” bw = 8”

As max = 0.0319[bhf + bw(0.503d – hf)] = 0.0319[(60”)(4”) + 8”(0.503(16”) – 4”)] As max = 8.7 in2

NOTE: This area of tension steel As = 8.7 in2 is a LOT!! In order to supply this much steel the beam would require 9 - #9 bars, 15 - #7 bars or 20 - #6 bars! It would be far better to change the beam dimensions than to try to squeeze this many bars into the beam.

Page 124: Structural Analysis and Design Lectures

Lecture 26 - Page 1 of 13

Lecture 26 – One-Way Slabs

A one-way slab is supported by parallel walls or beams, and the main tension reinforcing bars run parallel to the span. It looks like the following: The slab is designed as a series of 1’-0” wide beam “strips”. The analysis is similar to rectangular beams, except the width b = 12” and the height is usually on the order of 4” → 10”. The main tension bars are usually #4, #5 or #6 bars. There are no stirrups in slabs, however, additional bars are placed perpendicular to the main tension bars to prevent cracking during the curing process. These bars are referred to as “shrinkage” or “temperature” bars and are also usually #4 or #5 bars.

Tension rebar (parallel to span)

Slab span

Wall (or beam)

Maximum spacing between main tension bars = smaller of

Spacing reqd. for moment or 3 x slab thickness or 12”

Maximum spacing between shrinkage bars = smaller of

Spacing reqd. by analysis or 5 x slab thickness or 18”

Slab thickness

Shrinkage rebar (perpendicular to span)

Shrinkage bar spacing Tension bar

spacing

Page 125: Structural Analysis and Design Lectures

Lecture 26 - Page 2 of 13

Design of Main Tension Bars:

As previously mentioned, slabs are designed as a series of 1’-0” wide rectangular beam “strips” as shown below: Assuming the slab strip is a rectangular beam, then:

Mu = 0.9Asfyd(1 - ⎥⎥⎦

⎢⎢⎣

⎡⎟⎟⎠

⎞⎜⎜⎝

c

yact

ff

'59.0

ρ)

where: Mu = Usable moment capacity of slab strip As = Area of tension bars per 1’-0” width of slab fy = yield stress of rebar f’c = specified compressive strength of concrete

ρact = bdAs

Alternatively, the “Design Aid” Tables 1 and 2 from Lecture 24 may be used for analysis OR design.

Span

Tension bars

d h

b = 12”

Slab strip

Support beam

Page 126: Structural Analysis and Design Lectures

Lecture 26 - Page 3 of 13

Example 1 GIVEN: A one-way slab has a simple span = 8’-0” and the following materials and loads:

• Concrete f’c = 4000 PSI • #4 Grade 60 main tension bars and shrinkage bars • Concrete cover = ¾” • Superimposed floor SERVICE dead load = 38 PSF (not incl. slab wt.) • Superimposed floor SERVIVE live load = 125 PSF

REQUIRED: Design the slab, including thickness, main tension bars & shrinkage bars.

Step 1 – Determine slab thickness “h” based on Table below:

Minimum Suggested Thickness “h” of Concrete Beams & One-Way Slabs End Conditions Member:

Simply supported

One end continuous

Both ends continuous

Cantilever

Solid one-way slab L/20 L/24 L/28 L/10 Beam L/16 L/18.5 L/21 L/8

Span length L = inches

h = 20L

= 20

)/"12("0'8 ft−

= 4.8” → USE 5” Thick Slab

Span = 8’-0”

Tension bars

d h = ?

b = 12”

Slab strip

Support beam

Page 127: Structural Analysis and Design Lectures

Lecture 26 - Page 4 of 13

Step 2 – Determine maximum factored moment, Mmax, on slab:

Factored uniform load wu = 1.2D + 1.6L = 1.2(superimposed dead load + slab wt.) + 1.6(live load)

= 1.2(1’(38 PSF) + (5/12)(150 PCF)) + 1.6(1’(125 PSF)) = 120.6 PLF + 200 PLF = 320.6 PLF = 0.32 KLF

Maximum factored moment Mmax = 8

2Lwu

= 8

)"0'8)(32.0( 2−KLF

Mmax = 2.56 KIP-FT

= 30.72 KIP-IN = 30,720 LB-IN

Step 3 – Determine depth to tension bars “d”:

d = h” – conc. cover – ½(Tension bar dia.) = 5” – ¾” – ½(4/8”) = 4”

5” d

b = 12”

NOTE: No stirrups are required in slabs

Page 128: Structural Analysis and Design Lectures

Lecture 26 - Page 5 of 13

Step 4 – Using Design Aid Table 2 (see Lecture 24), determine As:

Determine the corresponding ρ from 2bdM u

φ:

2bdM u

φ = 2)"4)("12)(9.0(

720,30 INLB −

= 177.8 PSI

Use ρact = ρmin = 0.0033

ρact = bdAs

Solve for As:

As = ρact(b)(d) = 0.0033(12”)(4”) = 0.16 in2 per 1’-0” width of slab

Step 5 – Determine #4 bar tension bar spacing reqd. for moment:

Bar spacing reqd. = 12” ⎟⎟⎠

⎞⎜⎜⎝

s

s

AbaroneperA ___

= 12” ⎟⎟⎠

⎞⎜⎜⎝

⎛2

2

16.0_4_#_20.0

inbarperin

= 15” apart

Page 129: Structural Analysis and Design Lectures

Lecture 26 - Page 6 of 13

Step 6 – Determine MAXIMUM tension bar spacing requirements per ACI-318:

Use #4 Tension bars @ 12” o.c.

Step 7 – Determine “Shrinkage bar requirements by analysis”:

Shrinkage bar As = 0.0020bh = 0.0020(12”)(5”)

= 0.12 in2 per 1’-0” width

Bar spacing reqd. = 12” ⎟⎟⎠

⎞⎜⎜⎝

s

s

AbaroneperA ___

= 12” ⎟⎟⎠

⎞⎜⎜⎝

⎛2

2

12.0_4_#_20.0

inbarperin

= 20” apart

Spacing reqd. for moment or 3 x slab thickness or 12”

Maximum spacing between main tension bars = smaller of

= smaller of

15” (see prev. page) or 3 x 5” = 15” or 12” ← USE

Page 130: Structural Analysis and Design Lectures

Lecture 26 - Page 7 of 13

Step 8 – Determine MAXIMUM shrink. bar spacing requirements per ACI-318:

Use #4 Shrinkage bars @ 18” o.c.

Step 9 – Draw “Summary Sketch”:

Maximum spacing between shrinkage bars = smaller of

Spacing reqd. by analysis or 5 x slab thickness or 18”

= smaller of

20” (see prev. pages) or 5 x 5” = 25” or 18” ← USE

#4 Tension rebar placed at bottom of slab

Slab span = 8’-0”

Wall (or beam)

5”

#4 Shrinkage rebar placed in center of slab

#4 Shrinkage bar spacing = 18” o.c. Tension bar

spacing = 12” o.c.

Page 131: Structural Analysis and Design Lectures

Lecture 26 - Page 8 of 13

Continuous (Mult-span) Slabs

Concrete structural members are typically poured integrally together. Beams and slabs often span multiple supports and are not “simply-supported” as steel and wood framed beams are. As discussed in AECT 210 Lecture 15, these concrete beams and slabs are continuous and have both positive moments and negative moments. The location of tension bars in the members is related to the location of moment:

Tension bars are located in the BOTTOM for Mpos Tension bars are located in the TOP for Mneg

2- Equal Span Condition:

0.375L 0.375L

)(1289 2wLM pos = )(

1289 2wLM pos =

R1 R2 R3 L L

w

Moment Diagram

)(81 2wLM neg −=

Bars at top

Page 132: Structural Analysis and Design Lectures

Lecture 26 - Page 9 of 13

3- Equal Span Condition: Rebar Placement: At the transition between the Mpos and Mneg zones, a minimum overlap of bars is required per ACI 318. These overlaps are required for developing the full bar strength in tension. The friction developed between the concrete and the ribs of the rebar must equal the tensile strength of the bar. The necessary length of the bar embedment to achieve this friction force is called the “Development Length”, Ld, and is specified as a multiple of bar diameters. For example, the Ld for a Grade 60 rebar and concrete f’c = 4000 PSI = 38 x bar diameter.

Ld

Tensile Strength

Mpos = 0.025(wL2) Mpos = 0.08(wL2) Mpos = 0.08(wL2)

0.5L 0.5L 0.4L

R4 R2 R3 R1

w

L L L

0.4L

Mneg = -0.1(wL2) Mneg = -0.1(wL2)

Bars at top

Friction force

Rebar Tensile strength = Friction force

Page 133: Structural Analysis and Design Lectures

Lecture 26 - Page 10 of 13

Below are schematic cross-sections of required overlap dimensions for bar placement in continuous slabs (beams are similar):

Page 134: Structural Analysis and Design Lectures

Lecture 26 - Page 11 of 13

Example 2 GIVEN: A 1’-0” wide “strip” concrete slab that is 6” thick and a 3-span condition is shown below. All loads shown are already factored and includes slab weight. Use concrete f’c = 4000 PSI and Grade 60 bars. Use “d” = 5”. REQUIRED: Determine if the slab reinforcing steel is adequate for both the positive moments and negative moments.

Step 1 – Determine maximum factored POSITIVE moment, Mpos:

From above, Mpos = 0.08(wL2) = 0.08(1.0 KLF)(9’-0”)2 = 6.48 KIP-FT

Step 2 - Determine maximum factored NEGATIVE moment, Mneg:

From above, Mpos = -0.1(wL2) = -0.1(1.0 KLF)(9’-0”)2 = -8.1 KIP-FT

Mpos = 0.025(wL2) Mpos = 0.08(wL2) Mpos = 0.08(wL2)

0.5L 0.5L 0.4L

6” R2 R3 R1

wu = 1.0 KLF

L = 9’-0” L = 9’-0” L = 9’-0”

0.4L

Mneg = -0.1(wL2) Mneg = -0.1(wL2)

#5 @ 10” o.c. bars at top of slab

#4 @ 8” o.c. bars at bottom of slab

Page 135: Structural Analysis and Design Lectures

Lecture 26 - Page 12 of 13

Step 3 – Determine usable moment capacity of slab in POSITIVE moment:

The slab is reinforced with #4 @ 8” o.c.: We must get the reinforcement As in terms of 12” width of slab:

As per 1’-0” width = 12” ⎟⎟⎠

⎞⎜⎜⎝

⎛Spacing

barperAs __

= 12” ⎟⎟⎠

⎞⎜⎜⎝

⎛"8

_4_#_20.0 2 barperin

As = 0.30 in2 per 1’-0” width of slab

Determine ρact = bdAs

= )"5)("12(

30.0 2in

= 0.005 Determine Mu by formula:

Mu = 0.9Asfyd(1 - ⎥⎥⎦

⎢⎢⎣

⎡⎟⎟⎠

⎞⎜⎜⎝

c

yact

ff

'59.0

ρ)

= 0.9(0.30 in2)(60 KSI)(5”)(1 - ⎥⎦

⎤⎢⎣

⎡⎟⎠⎞

⎜⎝⎛

KSI4)60)(005.0(59.0 )

= 77.4 KIP-IN Mu = 6.45 KIP-FT ≈ Mpos = 6.48 KIP-FT → ACCEPTABLE

8”

6” d = 5”

b = 12”

#4 @ 8” o.c. at BOTTOM of slab

Page 136: Structural Analysis and Design Lectures

Lecture 26 - Page 13 of 13

Step 4 – Determine usable moment capacity of slab in NEGATIVE moment:

The slab is reinforced with #5 @ 10” o.c.: We must get the reinforcement As in terms of 12” width of slab:

As per 1’-0” width = 12” ⎟⎟⎠

⎞⎜⎜⎝

⎛Spacing

barperAs __

= 12” ⎟⎟⎠

⎞⎜⎜⎝

⎛"10

_5_#_31.0 2 barperin

As = 0.37 in2 per 1’-0” width of slab

Determine ρact = bdAs

= )"5)("12(

37.0 2in

= 0.0061 Determine Mu by formula:

Mu = 0.9Asfyd(1 - ⎥⎥⎦

⎢⎢⎣

⎡⎟⎟⎠

⎞⎜⎜⎝

c

yact

ff

'59.0

ρ)

= 0.9(0.37 in2)(60 KSI)(5”)(1 - ⎥⎦

⎤⎢⎣

⎡⎟⎠⎞

⎜⎝⎛

KSI4)60)(0061.0(59.0 )

= 94.5 KIP-IN

Mu = 7.88 KIP-FT < Mneg = 8.1 KIP-FT → NOT ACCEPTABLE

10”

6” d = 5”

b = 12”

#5 @ 10” o.c. at TOP of slab

Page 137: Structural Analysis and Design Lectures

Lecture 27 - Page 1 of 13

Lecture 27 – Two-Way Slabs Two-way slabs have tension reinforcing spanning in BOTH directions, and may take the general form of one of the following:

Types of Two-Way Slab Systems

Page 138: Structural Analysis and Design Lectures

Lecture 27 - Page 2 of 13

The following Table may be used to determine minimum thickness of various two-way slabs based on deflection:

Minimum Suggested Thickness “h” for Two-Way Slabs Two-Way Slab System: Minimum Thickness h:

Flat plate Ln/30 Flat plate with spandrel beams Ln/33 Flat slab Ln/33 Flat slab with spandrel beams Ln/36 Two-way beam-supported slab Ln/33

Ln = clear distance in long direction Flat Plates

Flat plates are the most common type of two-way slab system. It is commonly used in multi-story construction such as hotels, hospitals, offices and apartment buildings. It has several advantages:

• Easy formwork • Simple bar placement • Low floor-to-floor heights

Direct Design Method of Flat Plates per ACI 318-02

Two-way slabs are inherently difficult to analyze by conventional methods of statics because of the two-way bending occurring. Accurately determining the moments on a two-way slab is typically accomplished by finite element computer analysis.

Computer analysis of two-way slab

Page 139: Structural Analysis and Design Lectures

Lecture 27 - Page 3 of 13

The ACI 318 code allows a direct design method that can be used in most typical situations. However, the following limitations apply:

1. Must have 3 or more continuous spans in each direction. 2. Slab panels must be rectangular with a ratio of the longer span to

shorter span(measured as centerline-to-centerline of support) not greater than 2.0.

3. Successive span lengths in each direction must not differ by more than 1/3 of the longer span.

4. Columns must not be offset by more than 10% of the span (in direction of offset) from either axis between centerlines of successive columns.

5. Loads must be uniformly distributed, with the unfactored live load not more than 2 times the unfactored dead load (L/D < 2.0).

Design Strips

a) L1 > L2:

Mid

dle

Stri

p

L1

L2/4

Mid

dle

Stri

p

L2 L2

L2/4

Inte

rior C

olum

n S

trip

Ext

erio

r Col

umn

Stri

p

Inte

rior C

olum

n S

trip

L2/4

Column (typ.)

Page 140: Structural Analysis and Design Lectures

Lecture 27 - Page 4 of 13

b) L2 > L1: Design Moment Coefficients for Flat Plate Supported Directly by Columns

End Span Interior Span 1 2 3 4 5

Slab Moments

Exterior Negative

Positive First Interior

Negative

Positive Interior Negative

Total Moment

0.26Mo 0.52Mo 0.70Mo 0.35Mo 0.65Mo

Column Strip

0.26Mo 0.31Mo 0.53Mo 0.21Mo 0.49Mo

Middle Strip

0 0.21Mo 0.17Mo 0.14Mo 0.16Mo

Mo = Total factored moment per span

Mo = 8

22 nu LLw where Ln = clear span (face-to-face of cols.)in the direction of analysis

1

Mid

dle

Stri

p L1

L1/4

Mid

dle

Stri

p

L2 L2

L1/4

Inte

rior C

olum

n S

trip

Ext

erio

r Col

umn

Stri

p

Inte

rior C

olum

n S

trip

L1/4

2 3 4 5

End Span Interior Span

Page 141: Structural Analysis and Design Lectures

Lecture 27 - Page 5 of 13

Bar Placement per ACI 318-02

The actual quantity of bars required is determined by analysis (see Example below). However, usage of the Direct Design Method prescribes bar placement as shown below:

Page 142: Structural Analysis and Design Lectures

Lecture 27 - Page 6 of 13

Example 1 GIVEN: A two-way flat plate for an office building is shown below. Use the following:

• Column dimensions = 20” x 20” • Superimposed service floor Dead load = 32 PSF (not including slab weight) • Superimposed service floor Live load = 75 PSF • Concrete f’c = 4000 PSI • #4 Grade 60 main tension bars • Concrete cover = ¾”

REQUIRED: Use the “Direct Design Method” to design the two-way slab for the design strip in the direction shown.

L2 = 16’-0” L2 = 16’-0”

Col. strip

Ln

Design Strip = 16’

L2 = 16’-0”

20’-0”

20’-0”

20’-0”

L2/4 L2/4 ½ Middle strip = ½(16’ – Col. strip) ½ Middle strip

= ½(16’ – Col. strip)

Page 143: Structural Analysis and Design Lectures

Lecture 27 - Page 7 of 13

Step 1 – Determine slab thickness h:

Since it is a flat plate, from Table above, use h = 30

nL

where Ln = clear span in direction of analysis = (20’-0” x 12”/ft) – 20” = 220” = 18.33’

h = 30

"220

= 7.333” Use 8” thick slab

Step 2 – Determine factored uniform load, wu on the slab:

wu = 1.2D + 1.6L = 1.2[(32 PSF) + (8/12)(150 PCF)] + 1.6[(75 PSF)] = 278.4 PSF = 0.28 KSF

Step 3 – Check applicability of “Direct Design Method”:

1) Must have 3 or more continuous spans in each direction. YES 2) Slab panels must be rectangular with a ratio of the longer span to

shorter span(measured as centerline-to-centerline of support) not greater than 2.0. YES

3) Successive span lengths in each direction must not differ by more than

1/3 of the longer span. YES

4) Columns must not be offset by more than 10% of the span (in direction of offset) from either axis between centerlines of successive columns. YES

5) Loads must be uniformly distributed, with the unfactored live load not

more than 2 times the unfactored dead load (L/D < 2.0). YES

Column size

Slab weight

Page 144: Structural Analysis and Design Lectures

Lecture 27 - Page 8 of 13

Step 4 – Determine total factored moment per span, Mo:

Mo = 8

22 nu LLw

= 8

)'33.18)('16)(28.0( 2KSF

Mo = 188 KIP-FT

Step 5 – Determine distribution of total factored moment into col. & middle strips:

Design Moment Coefficients for Flat Plate Supported Directly by Columns

End Span Interior Span 1 2 3 4 5

Slab Moments

Exterior Negative

Positive First Interior

Negative

Positive Interior Negative

Total Moment

0.26Mo = 48.9 0.52Mo = 97.8 0.70Mo = 131.6 0.35Mo = 65.8 0.65Mo = 122.2

Column Strip

0.26Mo = 48.9 0.31Mo = 58.3 0.53Mo = 99.6 0.21Mo = 39.5 0.49Mo = 92.1

Middle Strip

0 0.21Mo = 39.5 0.17Mo = 32.0 0.14Mo = 26.3 0.16Mo = 30.1

Mo = Total factored moment per span = 188 KIP-FT

Step 6 – Determine tension steel bars for col. & middle strips:

a) Column strip for region 1 :

Factored NEGATIVE moment = 48.9 KIP-FT (see Table above) = 586.8 KIP-IN = 586,800 LB-IN

b = 96”

d 8”

d = 8” – conc. cover – ½(bar dia.) = 8” – ¾” – ½(4/8”) = 7”

Page 145: Structural Analysis and Design Lectures

Lecture 27 - Page 9 of 13

22 )"7)("96)(9.0(800,586 INLB

bdM u −

= 138.6 PSI From Lecture 24 Table 2:

Use ρmin = 0.0033

ρ = bdAs

Solve for As:

As = ρbd = (0.0033)(96”)(7”) = 2.22 in2

Number of bars required = barperA

A

s

s

__

= barperin

in_4_#_20.0

22.22

2

= 11.1 → Use 12 - #4 TOP bars

Page 146: Structural Analysis and Design Lectures

Lecture 27 - Page 10 of 13

b) Column strip for region 2 :

Factored POSITIVE moment = 58.3 KIP-FT (see Table above) = 699,600 LB-IN

22 )"7)("96)(9.0(600,699 INLB

bdM u −

= 165.2 PSI From Lecture 24 Table 2:

Use ρ = 0.0033

As = 2.22 in2 (see calcs. above) Use 12 - #4 BOTTOM bars

d = 8” – conc. cover – ½(bar dia.) = 8” – ¾” – ½(4/8”) = 7”

b = 96”

d 8”

Page 147: Structural Analysis and Design Lectures

Lecture 27 - Page 11 of 13

c) Middle strip for region 2 :

Factored POSITIVE moment = 39.5 KIP-FT (see Table above) = 474,000 LB-IN

22 )"7)("96)(9.0(000,474 INLB

bdM u −

= 112.0 PSI From Lecture 24 Table 2:

Use ρ = 0.0033

As = 2.22 in2 (see calcs. above) Use 12 - #4 BOTTOM bars Use 6 - #4 Bottom bars at each ½ Middle Strip

b = 96”

d 8”

d = 8” – conc. cover – ½(bar dia.) = 8” – ¾” – ½(4/8”) = 7”

Page 148: Structural Analysis and Design Lectures

Lecture 27 - Page 12 of 13

Step 7 – Draw “Summary Sketch” plan view of bars:

4’-0”

Col. strip for region 2 12 - #4 BOTTOM bars

16’-0” 16’-0”

Col. strip

16’ – 0”

16’-0”

20’-0”

20’-0”

20’-0”

4’-0”

½ Middle strip = 4’-0” ½ Middle strip = 4’-0”

Col. strip for region 1 12 - #4 TOP bars

½ Middle strip for region 2 6 - #4 BOTTOM bars

Page 149: Structural Analysis and Design Lectures

Lecture 27 - Page 13 of 13

Example 2 GIVEN: The two-way slab system from Example 1. REQUIRED: Design the steel tension bars for design strip shown (perpendicular to those in Example 1).

20’-0”

½ Middle strip = 6’-0”

½ Middle strip = 6’-0”

Col. strip = 8’-0”

16’-0” 16’-0” 16’-0”

20’-0”

20’-0”

20’-0”

Page 150: Structural Analysis and Design Lectures

Lecture 28 - Page 1 of 9

Lecture 28 – Shear in Beams Heavy loads on concrete beams produce diagonal shear cracks as shown below: Cracking in beams is normal and indicates the tension bars are actually working. Excessive cracking needs to be controlled by additional bars called stirrups placed perpendicular to the cracks as shown below:

Shear cracks in areas of high shear

Stirrup bars spanning crack

Stirrup bar spacing, s

Column (typ.)

Page 151: Structural Analysis and Design Lectures

Lecture 28 - Page 2 of 9

Stirrups may take the shape of the following typical configurations:

Design for Shear in Concrete Beams

Vertical shear is carried by the concrete shear capacity and the shear capacity provided by the stirrups. In other words:

Vu (from shear diagram) < φVc + φVs

where: Vu = factored vertical shear determined at a distance “d” away from the face of support φ = 0.75 Vc = shear strength of concrete = dbf wc'2

f’c = concrete strength, PSI bw = width of beam

Vs = shear strength provided by stirrups bars

= φφ cu VV −

Page 152: Structural Analysis and Design Lectures

Lecture 28 - Page 3 of 9

If Vs < dbf wc'4 then Max. stirrup spacing smax = smaller of

If dbf wc'4 < Vs < dbf wc'8 then Max. stirrup spacing smax = smaller of

Stirrups are required when Vu > ½(φVc) If stirrups are required,

s = s

yv

VdfA

< Smax

where: Av = area of stirrup bars crossing crack

fy = yield strength of stirrup bar (i.e., 60 KSI) d = depth to center of tension bars

2d

or 24”

4d

or 12”

Page 153: Structural Analysis and Design Lectures

Lecture 28 - Page 4 of 9

Example GIVEN: A simply-supported concrete beam having the following: (Assume the beam is adequate based on flexure)

• Concrete f’c = 4000 PSI • #3 Grade 60 U-shaped stirrup bars

REQUIRED: Determine stirrup requirements along the length of the beam.

12”

d = 18” h = 20”

20’-0”

wu = 5.6 KLF (includes beam wt.)

12” x 20” concrete beam

#3 U-shaped stirrup bars

Beam Cross-Section

Conc. column

Page 154: Structural Analysis and Design Lectures

Lecture 28 - Page 5 of 9

Step 1 – Determine maximum factored shear Vu at “d” away from face of support:

Simply-supported beam end reaction = 2Lwu

= 2

)"0'20)(6.5( −KLF

= 56 KIPS Vu at distance “d” from face of support = 56 KIPS – 1.5’(5.6 KLF) = 47.6 KIPS

Step 2 – Determine shear strength of concrete φVc:

φVc = 0.75( dbf wc'2 )

= 0.75( )"18)("12(40002 PSI = 20,492 Lbs. = 20.5 KIPS

0 0

d = 1.5’

56 KIPS

d = 18” = 1.5’

wu = 5.6 KLF

Vu = 47.6 KIPS

Shear Diagram

Page 155: Structural Analysis and Design Lectures

Lecture 28 - Page 6 of 9

Step 3 – Determine range where stirrups are required:

Stirrups are required when Vu > ½(φVc)

½(φVc) = ½(20.5 KIPS) = 10.25 KIPS

Step 4 – Determine shear strength provided by stirrups, Vs:

Vs = shear strength provided by stirrups bars

= φφ cu VV −

= 75.0

5.206.47 KIPSKIPS −

Vs = 36.1 KIPS

-10.25 KIPS

Stirrups required

Stirrups required Stirrups not required

0 0

d = 1.5’

56 KIPS

wu = 5.6 KLF

Vu = 47.6 KIPS

½(φVc) = 10.25 KIPS

d = 1.5’

-47.6 KIPS

Page 156: Structural Analysis and Design Lectures

Lecture 28 - Page 7 of 9

Step 5 – Determine stirrup spacing, s:

a) Check if Vs < dbf wc'4 36.1 KIPS < )"18)("12(40004 PSI 36.1 KIPS < 54,644 Lbs. → YES

Then:

Max. stirrup spacing smax = smaller of

b) Check spacing requirement:

s = s

yv

VdfA

< Smax

= KIPS

KSIin1.36

)"18)(60)(22.0( 2

= 6.6” → round down to 6” o.c. 6” < 9”

Use #3 Stirrup bars spaced 6” o.c.

#3 U-shaped stirrup bars

2d =

2"18 = 9”

or 24”

2 - #3 bars spanning crack

Av = 2(0.11 in2 per #3 bar) = 0.22 in2

Assumed shear crack

Page 157: Structural Analysis and Design Lectures

Lecture 28 - Page 8 of 9

Step 6 – Determine number of stirrups – assuming only ONE spacing:

Number of stirrups required = 1_

___tan+⎟⎟

⎞⎜⎜⎝

⎛spacingStirrup

requiredstirrupswhereceDis

= 1.."6

/"126.5

25.106.47

+⎟⎟⎟⎟

⎜⎜⎜⎜

⎛⎟⎠⎞

⎜⎝⎛ −

co

ftKLF

KIPSKIPS

= 14.3 stirrups → round up to 15 stirrups

Use 15 - #3 U-shaped stirrups @ 6” o.c. ea. end of beam

-10.25 KIPS

Stirrups required

Stirrups required Stirrups not required

0 0

d = 1.5’

56 KIPS

wu = 5.6 KLF

Vu = 47.6 KIPS

½(φVc) = 10.25 KIPS

d = 1.5’

-47.6 KIPS

Page 158: Structural Analysis and Design Lectures

Lecture 28 - Page 9 of 9

Step 7 – Draw “Summary Sketch”:

20’-0”

15 - #3 U-shaped stirrups at ea. end of beam

Stirrup bar spacing = 6” o.c.

12”

20”

15 - #3 Grade 60 U-shaped stirrup bars @ 6” o.c. at each end of beam

Beam Cross-Section

Page 159: Structural Analysis and Design Lectures

Lecture 29 - Page 1 of 6

Lecture 29 – Shear in Beams (cont.) As a continuation of our discussion of shear in concrete beams, let’s look at an example of a concrete girder with point loads. Example GIVEN: The 20” x 34” concrete girder as shown below. Use the following:

• Concrete f’c = 4000 PSI • #3 – Grade 60 U-shaped stirrups

REQUIRED: Determine the stirrup bar requirements. Assume only one spacing for the beam.

8’-0” 8’-0” 8’-0” 8’-0” 8’-0”

20”

d = 32” h = 34”

40’-0”

wu = 1.2 KLF

#3 U-shaped stirrup bars

Beam Cross-Section

Conc. column

25 KIPS 25 KIPS 25 KIPS 25 KIPS

Page 160: Structural Analysis and Design Lectures

Lecture 29 - Page 2 of 6

Step 1 – Draw shear diagram: Step 2 – Determine Vu at distance “d” from face of support:

Vu = 74 KIPS - )2.1(/"12"32 KLFft

= 70.8 KIPS

Step 3 – Determine shear capacity of concrete φVc:

φVc = 0.75( dbf wc'2 )

= 0.75( ))"32)("20(40002 PSI = 60,716 Lbs.

φVc = 60.7 KIPS

-74

74 64.4

39.4 29.8

4.8 -4.8

-29.8 -29.8

-39.4

8’-0” 8’-0” 8’-0” 8’-0” 8’-0”

40’-0”

wu = 1.2 KLF

Conc. column

25 KIPS 25 KIPS 25 KIPS 25 KIPS

NOTE: All loads are in Kips

Page 161: Structural Analysis and Design Lectures

Lecture 29 - Page 3 of 6

Step 4 – Determine range where stirrups are required:

Stirrups are required when Vu > ½(φVc)

½(φVc) = ½(60.7 KIPS) = 30.4 KIPS

Distance “X” = footperkipskipskips

__2.14.304.39 −

= 7.5 feet = 90”

32”

Stirrups reqd.

-74

74 64.4

39.4

29.8 4.8

-4.8

-29.8 -29.8

-39.4

8’-0” 8’-0” 8’-0” 8’-0” 8’-0”

wu = 1.2 KLF

25 KIPS 25 KIPS 25 KIPS 25 KIPS

Vu = 70.8

½(φVc) = 30.4

X

Because of symmetry → Same condition on right side of beam as left side of beam

Shear Diagram

Page 162: Structural Analysis and Design Lectures

Lecture 29 - Page 4 of 6

Step 5 – Determine shear strength provided by stirrups, Vs:

Vs = shear strength provided by stirrups bars

= φφ cu VV −

= 75.0

7.608.70 KIPSKIPS −

Vs = 13.5 KIPS

Step 6 – Determine stirrup spacing, s:

a) Check if Vs < dbf wc'4 13.5 KIPS < )"32)("20(40004 PSI 13.5 KIPS < 161,900 Lbs. → YES

Then:

Max. stirrup spacing smax = smaller of

2d =

2"32 = 16”

or 24”

Use

Page 163: Structural Analysis and Design Lectures

Lecture 29 - Page 5 of 6

b) Check spacing requirement:

s = s

yv

VdfA

< Smax

= KIPS

KSIin5.13

)"32)(60)(22.0( 2

= 31.3” > 16”

Use #3 Stirrup bars spaced 16” o.c. Step 7 – Determine number of stirrups required:

Number of stirrups required = 1_

___tan+⎟⎟

⎞⎜⎜⎝

⎛spacingStirrup

requiredstirrupswhereceDis

= 1.."16

)"_"tan()"32"96(+⎟

⎠⎞

⎜⎝⎛ +−

coXceDis

= 1.."16

"90)"32"96(+⎟

⎠⎞

⎜⎝⎛ +−

co

= 10.625 stirrups → round up to 11 stirrups Use 11 - #3 U-shaped stirrups @ 16” o.c. ea. end of beam

#3 U-shaped stirrup bars

2 - #3 bars spanning crack

Av = 2(0.11 in2 per #3 bar) = 0.22 in2

Assumed shear crack

See shear diagram

Page 164: Structural Analysis and Design Lectures

Lecture 29 - Page 6 of 6

Step 8 – Draw “Summary Sketch”:

40’-0”

11 - #3 U-shaped stirrups at ea. end of beam

Stirrup bar spacing = 16” o.c.

20”

34”

11 - #3 Grade 60 U-shaped stirrup bars @ 16” o.c. at each end of beam

Beam Cross-Section

Page 165: Structural Analysis and Design Lectures

Lecture 3 - Page 1 of 7

Lecture 3 – Tension members Steel tension members are perhaps the simplest members to design. There is no compressive, bending, shear or other stresses involved. Typical structural members that are under tension loads are:

• Trusses • Bracing • Hangers

The design of steel tension members is found in the following locations in the LRFD Manual:

• AISC Part 5 • AISC SPEC Chapter D p. 16.1-26 • AISC SPEC Chapter D p. 16.1-249

There are 2 types of failure mechanisms for tension members. The first is yielding on the gross area and the second is fracture on the net section. Yielding on Gross Area

Yielding on the gross area refers to “stretching” of the gross cross-sectional area of the member: The LRFD design strength for yielding on gross section in tension = φtPn

The ASD allowable strength for yielding on gross section in tension = Ω

nP

where: φt = 0.90 (LRFD) Ω = 1.67 (ASD) Pn = nominal strength of member = FyAg

Fy = yield stress of steel (see AISC p. 2-39) Ag = gross cross-sect. area (see AISC Part 1)

Page 166: Structural Analysis and Design Lectures

Lecture 3 - Page 2 of 7

Fracture on Net Section

Fracture on the net section refers to “breaking” the section perpendicular from the direction of force through the reduced cross-sectional area of a member, typically across the bolt holes.

The LRFD design strength for fracture on net section in tension = φtPn

The ASD allowable strength for fracture on net section in tension = Ω

nP

where: φt = 0.75 (LRFD) Ω = 2.00 (ASD) Pn = nominal strength of member = FuAe

Fu = ultimate stress of steel (see AISC p. 2-39) Ae = effective net area = AnU An = net area (see AISC p. 16.1-14) = Ag – [No. of holes(hole dia. + 1/16”)(matl. thk.)]

U = reduction factor considering “shear lag” = See AISC Table D3.1 p. 16.1-29

= 1.0 if tension load is transmitted directly to each element by means of fasteners or welds

= ⎟⎠⎞

⎜⎝⎛−

lx1 if tension load is transmitted to some but

not all of the elements by use of fasteners or welds where: x = connection eccentricity, inch l = length of connection in the direction of loading, inch

Ag = Gross area of angle An = Net area of angle

Bolt holes

Material thickness

Hole dia. + 1/16”

Page 167: Structural Analysis and Design Lectures

Lecture 3 - Page 3 of 7

Example 1 (LRFD) GIVEN: The double-angle L4x4x¼ A36 bracing member as shown below is under a FACTORED tensile load of 54 kips. The angles are bolted to the steel gusset plate using 2 – ¾” diameter bolts. REQUIRED:

1) Determine if the angles are acceptable based on yielding on gross area. 2) Determine if the angles are acceptable based on fracture on net area.

Step 1 – Determine LRFD design strength of member considering yielding:

Design strength = φtPn = 0.90(FyAg) = 0.90(36 KSI)[2 angles(1.94 in2 per angle)] = 125.7 KIPS Since 125.7 KIPS > 54 KIPS → member is acceptable

l = 3”

FACTORED

Page 168: Structural Analysis and Design Lectures

Lecture 3 - Page 4 of 7

Step 2 – Determine LRFD design strength considering fracture on net area:

Design strength = φtPn = 0.75(FuAe)

Ae = AnU Taking a cross-section perpendicular through the double-angle:

An = Ag – [No. of holes(hole dia. + 1/16”)(mat. th)] = (2)(1.94 in2) – [2 holes(¾” + 1/16”)(¼”)] = 3.47 in2

U = ⎟⎠⎞

⎜⎝⎛−

lx1

where x = 1.08” see properties AISC p. 1-43 l = Connection length = 3” (see sketch above)

= ⎟⎠⎞

⎜⎝⎛−

"3"08.11

= 0.64 Ae = AnU = 3.47 in2(0.64) = 2.22 in2

Design strength = 0.75(58 KSI)(2.22 in2) = 96.6 KIPS

Since 96.6 KIPS > 54 KIPS → member is acceptable

x

N.A. N.A.

Page 169: Structural Analysis and Design Lectures

Lecture 3 - Page 5 of 7

In the design of steel tension members the AISC recommends a maximum

permissible slenderness ratio, minrL < 300 for members other than rods, straps or

HSS (see AISC p. 16.1-26). This is not so much for structural strength – rather to provide some stiffness to reduce the undesirable effects of lateral movement. Also, since truss members and other tension members may see some load-reversal and experience some compressive loads, it is to reduce the likelihood of buckling. Example 2 (ASD) GIVEN: The bottom chord of the truss is to be designed using a single A992 W8 member. The truss has welded connections, so there is no need to check for fracture on the net area. REQUIRED: Design the lightest weight W8 member checking:

1) Slenderness ratio is not exceeded 2) Yielding on gross area

Step 1 – Determine rmin such that slenderness ratio is not exceeded:

300min

≤rL

L = 22’-0”(12” per ft) = 264” Rearranging and solve for rmin:

min300"264 r≤

Required rmin > 0.88 in. → looking at AISC p. 1-27, the smallest W8 that will work is W8x18 with ry = 1.23 in. > rmin of 0.88 in.

15’-0”

22’-0” 22’-0”

SERVICE load = 100 Kips

W8 Bottom chord

Page 170: Structural Analysis and Design Lectures

Lecture 3 - Page 6 of 7

Step 2 – Determine SERVICE tensile load on member:

By simple truss analysis, the force in the member is:

HorzLengthHorzForce

VertLengthVertForce

=

"0'22"0'15100

−=

−HorzForceKIPS

Horz Force = 146.7 KIPS

Step 3 – Design lightest W8 member considering yielding on gross area:

ASD Allowable strength for yielding = Ω

gy AF> 146.7 KIPS

where: Ω = 1.67 Fy = 50 KSI (see AISC p. 2-39) Solve for Ag:

Ag > yF

kips )(7.146 Ω

> KSI

kips50

)67.1(7.146

Ag > 4.9 in2

Use W8x18 → Area = 5.26 in2 > 4.9 in2

Step 4 – Determine the maximum allowable tensile yielding load on W8x18:

ASD Allowable strength for yielding = Ω

gy AF

= 67.1

)26.5)(50( 2inKSI

ASD Allowable strength for yielding = 157.5 Kips

AISC p. 1-26

Page 171: Structural Analysis and Design Lectures

Lecture 3 - Page 7 of 7

Step 5 – Determine the allowable tensile yielding load on W8x18 using AISC Table 5-1:

From AISC p. 5-13:

W8x18

Allowable yielding SERVICE tensile load = 157 Kips

ASD

Page 172: Structural Analysis and Design Lectures

Lecture 30 - Page 1 of 9

Lecture 30 – Development of Reinforcement, Splices, Hooks Reinforcing bars must be embedded a minimum distance into the concrete in order to achieve the full tensile capacity, T of the bar. This length is referred to as “Development Length”, Ld. The development length is based upon the BOND between the rebar and the concrete. Factors affecting this bond include the following:

• Type of ribbing on the bar • Presence of epoxy (or other ) coating • Concrete quality • Distance between bar and edge of concrete • Type of end anchorage into the concrete

Concrete

Ld

Rebar T = Asfy

Page 173: Structural Analysis and Design Lectures

Lecture 30 - Page 2 of 9

Determining Ld for Tension Bars:

a) #6 and smaller bars:

c

ybd f

fdL

'25

αβλ=

b) #7 and larger bars:

c

ybd f

fdL

'20

αβλ=

where:

db = diameter of bar fy = yield strength of bar, PSI f’c = specified concrete compressive strength, PSI α = alpha = Bar location factor = 1.3 for top reinforcement = 1.0 for all other locations β = beta = Coating factor = 1.5 for epoxy coated bars = 1.0 for uncoated bars λ = lambda = Lightweight aggregate factor = 1.3 for lightweight aggregate = 1.0 for normal weight aggregate

Page 174: Structural Analysis and Design Lectures

Lecture 30 - Page 3 of 9

Example 1 GIVEN: A #6 rebar under tension force. Assume the following conditions:

• Concrete f’c = 4000 PSI • Normal weight concrete (λ = 1.0) • ASTM A615 Grade 60 rebar • #6 rebar (γ = 0.8) • Uncoated bar (β = 1.0) • Bar location is bottom of beam (α = 1.0)

REQUIRED: Determine the development length, Ld to achieve full tensile strength of the bar.

Step 1 – Use the formula above to determine Ld:

c

ybd f

fdL

'25

αβλ=

PSI

PSILd 400025

)0.1)(0.1)(0.1)(000,60(86⎟⎠⎞

⎜⎝⎛

=

Ld = 28.5”

Concrete

Ld = 28.5”

#6 Rebar

Page 175: Structural Analysis and Design Lectures

Lecture 30 - Page 4 of 9

Assuming “normal” conditions, the following table may be used to determine development lengths of bars in tension:

Development Length Ld of Grade 60 bottom bars in normal weight concrete Condition Concrete f’c No. 6 and smaller

bars No. 7 and larger

bars 3000 PSI 44db 55db 4000 PSI 38db 47db

Clear spacing of bars > db, clear cover > db 5000 PSI 34db 42db

3000 PSI 66db 82db 4000 PSI 57db 71db

All other cases

5000 PSI 51db 64db Example 2 GIVEN: The same information as Example 1. REQUIRED: Using the table above, determine the Ld for a #6 bar.

Step 1 – Use table above to determine Ld:

Concrete f’c = 4000 PSI Clear spacing of bars > db, clear cover > db

Ld = 38db = 38(6/8”) Ld = 28.5”

Page 176: Structural Analysis and Design Lectures

Lecture 30 - Page 5 of 9

Determining Ld for Compression Bars:

The development length of bars in compression is not as large as the development length in tension because of the absence of tension cracking in the concrete.

Ldc = Development length in compression = larger of

Example 3 GIVEN: A #6 bar in compression. Use f’c = 4000 PSI and Grade 60 bars. REQUIRED: Determine the Ldc for the bar. Ldc = Development length in compression

= larger of

Ldc = 14.2”

Ldc = c

yb

f

fd

'02.0

or Ldc = 0.0003dbfy

Ldc = c

yb

f

fd

'02.0 =

PSI

PSI

4000

)000,60(86

02.0 = 14.2” ← Use

or Ldc = 0.0003dbfy = 0.0003(6/8”)(60,000 PSI) = 13.5”

Page 177: Structural Analysis and Design Lectures

Lecture 30 - Page 6 of 9

Lap Splices of Bars

Bars are generally fabricated to lengths of about 60’-0”, but transportation, workability and other concerns often require bars to be less than about 40’-0” long. For long walls, beams, slabs and other situations requiring long lengths of bars, lap splicing is commonly used. It is good practice to place laps at regions of small tension, i.e., low moment.

Ls = Length of lap splice

= 1.0Ld for “Class A” splice if the area of reinforcement provided through the splice > twice that required by analysis and not more than 50% of the total reinforcement is spliced within the lap length

= 1.3Ld for “Class B” splice if reinforcement does not meet Class A requirements

Concrete

Ls

Page 178: Structural Analysis and Design Lectures

Lecture 30 - Page 7 of 9

Hooked and Bent Bars

Hooks are used in concrete members where there is not sufficient straight length to achieve the full development length Ld. The following is a diagram showing the required lengths of bends and hooks:

Ldh = Lhbλ

Page 179: Structural Analysis and Design Lectures

Lecture 30 - Page 8 of 9

Where: Lhb = Basic development length of hook in tension

= c

b

fd

'1200

λ = 1.0 unless otherwise specified below:

= 000,60yf

if using other than Grade 60 bars

= 0.7 if side concrete cover > 2½” or end cover > 2” = 0.8 if ties or stirrups spacing < 3db = 1.3 if lightweight concrete

= s

s

AovidedAquired

_Pr_Re

Example 4 GIVEN: A #5 Grade 40 bar is in tension as shown below. Use LIGHTWEIGHT concrete with f’c = 4000 PSI. REQUIRED: Determine the min. required hook dimensions “X”, “Y” and “Z”.

Step 1 – Determine dimension “X”:

X = 12db = 12(5/8”) X = 7½”

End cover = 1½”

X

Y

Z = Ldh

Critical section

Side cover = 1½”

Page 180: Structural Analysis and Design Lectures

Lecture 30 - Page 9 of 9

Step 2 – Determine dimension “Y”:

Y = 4db since it is a #6 bar = 4(5/8”) Y = 2½”

Step 3 – Determine length of hooked bar, Lhb:

Lhb = c

b

fd

'1200

= PSI4000

"85

1200

= 11.9”

Step 4 – Determine total development length, Z = Ldh:

Ldh = Lhbλ

Where: λ = 1.0 since side cover = 1½” < 2½” = 1.3 since lightweight concrete

= PSI

f y

60000 =

PSIPSI

6000040000 = 0.67

Ldh = Lhbλ = 11.9”(1.0)(1.3)(0.67) Ldh = 10.4”

Page 181: Structural Analysis and Design Lectures

Lecture 31 - Page 1 of 7

Lecture 31 – Serviceability Serviceability refers to the structural “performance” of the finished building under service loads.

• Beam deflection • Lateral drift • Vibration

We will be focusing our discussion on beam deflection. The ACI 318-02 Code dictates that the deflections be checked on the basis of effective moment of inertia, Ie, under service loads. Before we can determine the value of the effective moment of inertia, we must first have an understanding of the gross moment of inertia, Ig, and the cracked moment of inertia, Icr. Gross Moment of Inertia Ig:

The gross moment of inertia is not appropriate for reinforced concrete beams because the concrete under the neutral axis is in tension and is ineffective. Since tension is carried by the steel rebar, the beam becomes composite and therefore must be analyzed as such (See AECT 210 – Lecture 6). The calculated value of gross moment of inertia is higher than what is actually present.

h

b

Ig = Gross moment of Inertia

= 12

3bh

Page 182: Structural Analysis and Design Lectures

Lecture 31 - Page 2 of 7

Cracked Moment of Inertia Icr:

The cracked moment of inertia takes into consideration the composite action between the concrete and steel rebar. This assumes that the concrete in the tension zone is totally ineffective, which is overly conservative. However, the cracked moment of inertia is far closer to predicting the actual moment of inertia of a reinforced concrete beam than the gross moment of inertia.

Icr = 23

)(3

ydnAbys −+

Where: n = Modular ratio

= cconc

steel

fPSI

EE

'000,57000,000,29

=

As = Area of steel rebar in tension, in2

y = b

nAbdnA

ss ⎥

⎤⎢⎣

⎡−+ 121

nAs

N.A.

y

d

b

Page 183: Structural Analysis and Design Lectures

Lecture 31 - Page 3 of 7

Effective Moment of Inertia, Ie:

The effective moment of inertia is typically used to determine the section property of the member at a specific point along the moment diagram. In most cases, the effective moment of inertia is used to determine the actual deflection of the member when comparing to Code-dictated maximums.

Ie = gcra

crg

a

cr IIMM

IMM

≤⎪⎭

⎪⎬⎫

⎪⎩

⎪⎨⎧

⎥⎥⎦

⎢⎢⎣

⎡⎟⎟⎠

⎞⎜⎜⎝

⎛−+⎟⎟

⎞⎜⎜⎝

⎛33

1

where: Mcr = moment that would initially crack the section

= t

gr

yIf

fr = modulus of rupture for the concrete = cf '5.7 yt = dist. from N.A. of uncracked cross-section to extreme tension fiber

= 2h

Ma = maximum unfactored moment at specific location along the moment diagram Ig = gross moment of inertia Icr = cracked moment of inertia

Page 184: Structural Analysis and Design Lectures

Lecture 31 - Page 4 of 7

Example 1 GIVEN: A simply-supported rectangular beam is shown below. The loads indicated are SERVICE loads. Use concrete f’c = 4000 PSI and grade 60 bars. REQUIRED:

1) Determine the gross moment of inertia Ig of the beam. 2) Determine the cracked moment of inertia Icr of the beam. 3) Determine the maximum allowable mid-span deflection of the beam

assuming ∆allow = L/360. 4) Determine the actual mid-span deflection of the beam using Ie.

d = h – conc. cover – stirrup bar dia. – ½(main tension bar dia.) = 20” – ¾” – ⅜” – ½(8/8”) = 18.375”

25’-0”

Wservice = 1500 PLF

¾” concrete cover

20”

12”

Section A-A

2 - #4 hanger bars

#3 stirrup bars @ 9” o.c.

3 - #8 main bars

Page 185: Structural Analysis and Design Lectures

Lecture 31 - Page 5 of 7

Step 1 – Determine gross moment of inertia Ig:

Ig = 12

3bh

= 12

)20)("12( 3

Ig =8000 in4

Step 2 – Determine cracked moment of inertia Icr:

Icr = 23

)(3

ydnAbys −+

Where: n = Modular ratio

= PSI

PSIfPSI

EE

cconc

steel

4000000,57000,000,29

'000,57000,000,29

==

= 8.04 As = Area of steel rebar in tension, in2 = 3 bars(0.79 in2 per #8 bar) = 2.37 in2

y = b

nAbdnA

ss ⎥

⎤⎢⎣

⎡−+ 121

= "12

1)37.2)(04.8()"375.18)("12(21)37.2)(04.8( 2

2⎥⎦

⎤⎢⎣

⎡−+

inin

= 6.2”

Page 186: Structural Analysis and Design Lectures

Lecture 31 - Page 6 of 7

Icr = 23

)(3

ydnAbys −+

= 223

)"2.6"375.18)(37.2(04.83

)"2.6)("12(−+ in

Icr = 2904 in4

Step 3 - Determine the maximum allowable mid-span deflection of the beam assuming ∆allow = L/360:

∆allow = 360L

= 360

/"12)"0'25( ft−

∆allow = 0.83”

Step 4 - Determine the effective moment of inertia Ie:

fr = modulus of rupture for the concrete = cf '5.7

= PSI40005.7 = 474.3 PSI

Mcr = moment that would initially crack the section

= t

gr

yIf

=

2"20

)8000)(3.474( PSIPSI

= 379,473 Lb-In = 379.4 KIP-In = 31.6 KIP-FT

Page 187: Structural Analysis and Design Lectures

Lecture 31 - Page 7 of 7

Ma = maximum unfactored moment at specific location along the moment diagram

= 8

2wL

= 8

)"0'25)(5.1( 2−KLF

Ma = 117.2 KIP-FT

Ie = ⎪⎭

⎪⎬⎫

⎪⎩

⎪⎨⎧

⎥⎥⎦

⎢⎢⎣

⎡⎟⎟⎠

⎞⎜⎜⎝

⎛−+⎟⎟

⎞⎜⎜⎝

⎛cr

a

crg

a

cr IMM

IMM

33

1

= gIinin ≤⎪⎭

⎪⎬⎫

⎪⎩

⎪⎨⎧

⎥⎥⎦

⎢⎢⎣

⎡⎟⎠⎞

⎜⎝⎛−+⎟

⎠⎞

⎜⎝⎛ )2904(

2.1176.311)8000(

2.1176.31 4

34

3

Ie = 3004 in4

Step 5 – Determine actual mid-span deflection using Ie:

∆act = econc IE

wL384

5 4

= )3004)(400057000(384

)/"12"0'25(12

15005

4

4

inPSI

ftxPLF−⎟

⎠⎞

⎜⎝⎛

∆act = 1.22”

Since ∆act = 1.22” > ∆allow = 0.83” → member is NOT acceptable

Page 188: Structural Analysis and Design Lectures

Lecture 33 - Page 1 of 14

Lecture 33 – Columns Concrete Columns:

Concrete is good at resisting compression but poor in resisting tension. So, it might make sense that concrete would be the material of choice for columns. It is true that concrete IS used for compression members such as columns, piers, bearing walls and pedestals. Members under pure compression could then (theoretically) be unreinforced. These members are often subject to additional forces such as moment that would put some tensile forces into the member and would thus necessitate the addition of tension reinforcement. Most columns have combined compression and bending. They are essentially a “beam-column”. The compression capacity of a reinforced column is reduced by the bending stresses on the column and vice-versa. A graph of the axial load capacity of a column vs. the moment capacity of a typical column is shown below:

Axi

al c

ompr

essi

on c

apac

ity

Bending moment capacity

Pure compression

Pure bending

Page 189: Structural Analysis and Design Lectures

Lecture 33 - Page 2 of 14

Types of Concrete Columns:

There are two types of reinforced concrete columns – tied and spiral – and refer to the type of confining bars used to contain the interior core of concrete. It has been shown that unconfined concrete core will carry MUCH LESS load than a confined core as shown below:

Unconfined core

Load

Concrete & vert. bars “explode” outward

Load

Insufficient ties

Page 190: Structural Analysis and Design Lectures

Lecture 33 - Page 3 of 14

A confined concrete core will carry substantially more load and will NOT explode outward like the unconfined concrete section will.

Tied Column:

A “Tied” concrete column is one in which individual rebar ties are used to wrap completely around the vertical bars to confine the interior core. These ties are usually #3 or #4 bars spaced per ACI requirements:

Tie Spacing = smaller of

Additionally, the ACI dictates that there must be a minimum of 4 vertical bars having a minimum area of 1% of the column cross-sectional area and a maximum of 8% of the column cross-sectional area. From a constructability standpoint, 4% is the upper maximum that can be readily achieved because of rebar congestion.

Load Load

Confined core

Minor concrete spalling, core remains intact

Least column dimension 16 x Vert. Bar Dia. 48 x Tie Bar Dia.

Page 191: Structural Analysis and Design Lectures

Lecture 33 - Page 4 of 14

A typical tied concrete column looks like the following:

Tie spacing Tie bars

Vertical bars (4 minimum)

Concrete

Page 192: Structural Analysis and Design Lectures

Lecture 33 - Page 5 of 14

Spiral Column:

A spiral column has a single rebar wrapped around the vertical bars in a spiral and is stronger than a comparable tied column. It is more labor-intensive to build than a tied column. The ACI requires a minimum of 6 vertical bars, with the same minimum and maximum areas of steel as a tied column. Spiral columns have greater ductility than a tied column. This means that a spiral column is capable of sustaining larger strain before failure than a tied column. For this reason, spiral columns are used in areas with high seismicity to prevent brittle failures. The stress-strain curve below shows the relative yield strength of a tied column and a spiral column are similar, however the strain capacity of the spiral column is much greater than that of a tied column.

Yield

Pitch = 1” → 3”

Concrete

Spiral rebar

Stress

Strain

Fracture Fracture

Spiral column

Tied column

Page 193: Structural Analysis and Design Lectures

Lecture 33 - Page 6 of 14

Column Load Capacity – Small eccentricity:

The ratio of applied moment to the applied axial load is its “eccentricity.” A small eccentricity “e” means small moment, where a large eccentricity means large moment.

e

h

Pu = applied factored axial load Pu

e

Concentric load (e = small) Eccentric load (e = large)

Mu = Pue = Small

Mu = Pue = Large

h

Side view of column

Page 194: Structural Analysis and Design Lectures

Lecture 33 - Page 7 of 14

1) Tied columns with small eccentricity:

Small eccentricity if 10.0≤he

φPn = Usable axial strength of tied column, KIPS = 0.80φc[0.85f’c(Ag-As)+fyAs]

where: φc = strength reduction factor for column = 0.65 for tied columns Ag = gross cross-sectional area of column, in2 As = total area of vertical steel bars, in2 = minimum of 4 vertical bars = 0.01Ag → 0.08Ag f’c = specified concrete compressive strength, KSI fy = yield strength of vertical steel bars, KSI

2) Spiral columns with small eccentricity:

Small eccentricity if 10.0≤he

φPn = Usable axial strength of tied column, KIPS = 0.85φc[0.85f’c(Ag-As)+fyAs]

where: φc = strength reduction factor for column = 0.70 for spiral columns Ag = gross cross-sectional area of column, in2 As = total area of vertical steel bars, in2 = minimum of 6 vertical bars = 0.01Ag → 0.08Ag f’c = specified concrete compressive strength, KSI fy = yield strength of vertical steel bars, KSI

Page 195: Structural Analysis and Design Lectures

Lecture 33 - Page 8 of 14

Spiral requirements:

y

c

c

gs f

fAA '

145.0 ⎟⎟⎠

⎞⎜⎜⎝

⎛−=ρ

2

)(4

cs

bcs

dddA

−=

where: ρs = ratio of spiral bar to gross area s = spacing of spiral bends (pitch), in Ag = gross area of column, in2

Ac = area of core, in2 = area measured out-to-out of spiral As = area of spiral bar, in2 dc = diameter of core measured out-to-out of spiral db = diameter of spiral bar

Page 196: Structural Analysis and Design Lectures

Lecture 33 - Page 9 of 14

Example 1 GIVEN: A 16” x 16” square tied concrete column has an applied factored axial load Pu = 300 KIPS and an applied factored moment Mu = 35 KIP-FT. In addition, use the following:

• Concrete f’c = 4000 PSI • 8 - #7 grade 60 vertical bars • #3 individual tie bars • Concrete cover = 1½”

REQUIRED:

1) Determine the eccentricity “e” and state whether or not it is considered to be “small eccentricity.”

2) Determine the required tie spacing. 3) Determine if the vertical bars are acceptable based on ACI requirements. 4) Determine the usable axial strength of the tied column, φPn, and state

whether or not it is acceptable.

Step 1 – Determine eccentricity and whether it is “small.”

Eccentricity e = u

u

PftM )/"12(

= KIPS

ftFTKIP300

)/"12(35 −

e = 1.4” Small eccentricity if e/h < 0.10

e/h = 1.4”/(16”) e/h = 0.0875 → it is small eccentricity

16”

16”

8 - #7 vertical bars

Page 197: Structural Analysis and Design Lectures

Lecture 33 - Page 10 of 14

Step 2 – Determine the required tie spacing:

Tie Spacing = smaller of

Step 3 – Determine if vertical bars are acceptable based on ACI:

8 vertical bars are used > 4 bars OK As = 8 bars(0.60 in2 per #7 bar)

= 4.8 in2

Min. As = 0.01Ag = 0.01(16” x 16”) = 2.56 in2 < 4.8 in2 OK

Max. As = 0.08 Ag = 0.08(16” x 16”) = 20.48 in2 > 4.8 in2 OK Step 4 - Determine the usable axial strength of the tied column, φPn:

Since e/h < 0.10 then the formula can be used: φPn = Usable axial strength of tied column, KIPS = 0.80φc[0.85f’c(Ag-As)+fyAs]

where: φc = 0.65 since it is a tied column Ag = 16” x 16” = 256 in2 As = 8 bars(0.60 in2 per #7 bar) = 4.8 in2

= 0.80(0.65)[0.85(4 KSI)(256 in2 – 4.8 in2) + (60 KSI)(4.8 in2)] φPn = 594 KIPS Since φPn = 594 KIPS > 300 KIPS → column is acceptable

Least column dimension = 16” 16 x Vert. Bar Dia. = 16(⅞”) = 14” ← USE 48 x Tie Bar Dia. = 48(⅜”) = 18”

Page 198: Structural Analysis and Design Lectures

Lecture 33 - Page 11 of 14

Example 2 GIVEN: A 14” diameter spiral column has a factored axial load Pu = 400 KIPS and a factored moment = 45 KIP-FT. In addition, use the following:

• Concrete f’c = 4000 PSI • 6 - #9 grade 60 vertical bars • #3 spiral bar • Concrete cover = 1½”

REQUIRED:

1) Determine the eccentricity “e” and state whether or not it is considered to be “small eccentricity.”

2) Determine the required spiral pitch. 3) Determine the usable axial strength of the spiral column, φPn, and state

whether or not it is acceptable.

Page 199: Structural Analysis and Design Lectures

Lecture 33 - Page 12 of 14

Step 1 – Determine eccentricity and whether it is “small.”

Eccentricity e = u

u

PftM )/"12(

= KIPS

ftFTKIP400

)/"12(45 −

e = 1.35”

Small eccentricity if he < 0.10

he =

"14"35.1

e/h = 0.096 → it is small eccentricity

Step 2 – Determine the required spiral pitch “s”:

y

c

c

gs f

fAA '

145.0 ⎟⎟⎠

⎞⎜⎜⎝

⎛−=ρ

where: Ag = 2)_(4

DiaOutsideπ

= 2)"14(4π

Ag = 153.9 in2

Ac = 2)_(4

DiaCoreπ

= 2)"11(4π

Ac = 95.0 in2

Pitch

Page 200: Structural Analysis and Design Lectures

Lecture 33 - Page 13 of 14

y

c

c

gs f

fAA '

145.0 ⎟⎟⎠

⎞⎜⎜⎝

⎛−=ρ

KSIKSI

inin

s 6041

0.959.15345.0 2

2

⎟⎟⎠

⎞⎜⎜⎝

⎛−=ρ

ρs = 0.0186

Pitch = s

2

)(4

cs

bcs

dddA

−=

2

2

)"11)(0186.0(

)"83"11)(11.0(4 ⎟⎠⎞

⎜⎝⎛−

=in

s

Pitch s = 2.08” Use pitch = 2”

Page 201: Structural Analysis and Design Lectures

Lecture 33 - Page 14 of 14

Step 3 - Determine the usable axial strength of the spiral column, φPn:

Since e/h < 0.10 then the formula can be used: φPn = Usable axial strength of spiral column, KIPS = 0.85φc[0.85f’c(Ag-As)+fyAs]

where: φc = 0.70 since it is a spiral column Ag = 153.9 in2 As = 6 bars(1.00 in2 per #9 bar) = 6.0 in2

= 0.85(0.70)[0.85(4 KSI)(153.9 in2 – 6.0 in2) + (60 KSI)(6.0 in2)] φPn = 513 KIPS Since φPn = 513 KIPS > 400 KIPS → column is acceptable

Page 202: Structural Analysis and Design Lectures

Lecture 34 - Page 1 of 12

Lecture 34 – Columns (cont.) In the previous lecture, we talked about columns having small eccentricity (i.e., small applied moment). While this may be the case for interior columns with offsetting moments, the majority of concrete columns do experience applied moments. Concrete framed buildings typically have columns that are poured monolithically with beams and slabs, thus creating a statically-indeterminate frame such as the one shown below:

The analysis of such a frame is usually quite complex and requires computer software such as STAAD or approximate analysis methods such as the Portal Method and others discussed in AECT 210 – Structural Theory Lecture 17.

Page 203: Structural Analysis and Design Lectures

Lecture 34 - Page 2 of 12

The compression capacity of a reinforced column is reduced by the bending stresses on the column and vice-versa. A graph of the axial load capacity of a column vs. the moment capacity of a typical column is shown below (from Lecture 33):

Determining points along the curve is quite laborious and typically not done using hand calculations. Instead, computer programs or design guides are used to perform column analysis and design. Below are some “Column Interaction Diagrams” that are used for column analysis and design.

Axi

al c

ompr

essi

on c

apac

ity

Bending moment capacity

Pure compression (no applied moment)

Pure bending (no applied axial load)

Page 204: Structural Analysis and Design Lectures

Lecture 34 - Page 3 of 12

Rectangular TIED Column Interaction Diagrams

Page 205: Structural Analysis and Design Lectures

Lecture 34 - Page 4 of 12

Circular SPIRAL Column Interaction Diagrams

Page 206: Structural Analysis and Design Lectures

Lecture 34 - Page 5 of 12

“Short” Column Design:

Short columns are not considered to be susceptible to the effects of buckling as are long columns. The ACI dictates that short columns satisfy the slenderness ratio as shown below:

Short column IF 22min

≤rKL

Where: K = end fixity factor

L = unbraced length in inches rmin = least radius of gyration, inches = 0.3h for rectangular or square columns = 0.25dout for circular columns where dout = outer dia.

Page 207: Structural Analysis and Design Lectures

Lecture 34 - Page 6 of 12

Example GIVEN: A 20” x 20” square interior tied column is shown below. Use concrete f’c = 4000 PSI and 8 - #8 grade 60 vertical bars and #3 ties. Concrete cover = 1½”. All loads are factored and includes beam weight. Assume the moment from the

beams acting on the column is 12

2nu Lw where Ln = clear span of attached beam,

and wu = factored unif. load. REQUIRED:

1) Determine the applied factored axial load, Pu on the middle column. Be sure to add column weight. Assume the loads from the roof above are 75% of the floor load.

2) Determine the slenderness ratio minrKL using K = 0.7 and determine if

column qualifies as “short.” 3) Determine total factored moments Mtotal applied to the column. 4) Determine if the column is acceptable based on “Column Interaction

Diagram.”

wu = 1.7 KLF wu = 2.5 KLF 46 K 46 K

14’-0”

30’-0” 22’-0”

Beam 1

20” x 20” Middle column

Beam 2

Page 208: Structural Analysis and Design Lectures

Lecture 34 - Page 7 of 12

Step 1 – Determine the total factored axial load, Pu on the middle column:

a) Beam 1:

End reaction = ½(46 K + 46 K + 1.7 KLF(22’-0”)) = 64.7 KIPS

b) Beam 2:

End reaction = ½(2.5 KLF(30’-0”)) = 37.5 KIPS

c) Column weight:

Weight = )150)("0'14(/144

"20"2022 PCF

ftinx

= 5833 Lbs. = 5.8 KIPS

Total Pu = 1.75(64.7 KIPS + 37.5 KIPS + 5.8 KIPS) Total Pu = 189 KIPS

Step 2 - Determine the slenderness ratio minrKL using K = 0.7:

minrKL =

)"20(3.0)/"12"0'14)(7.0( ftx−

minrKL = 19.6

Since KL/rmin < 22 → it is a “short” column

Page 209: Structural Analysis and Design Lectures

Lecture 34 - Page 8 of 12

Step 3 – Determine total factored moment Mtotal applied to the column:

a) Beam 1:

To determine Mmax = 12

2nu Lw we must convert point loads into

equivalent uniform load wu. From AISC LRFD Manual p. 5-160:

wu = 1.7 KLF

46 K 46 K

22’-0”

Ln = 20.33’

Page 210: Structural Analysis and Design Lectures

Lecture 34 - Page 9 of 12

wu = wuniform + wpoint

= 1.7 KLF + LfP

= 1.7 KLF + "0'22

)46(667.2−

KIPS

= 7.3 KLF

Page 211: Structural Analysis and Design Lectures

Lecture 34 - Page 10 of 12

Mmax = 12

2nu Lw

= 12

)'33.20(3.7 2KLF

MBeam 1 = 251 KIP-FT

b) Beam 2:

Mmax = 12

2nu Lw

= 12

)'33.28(5.2 2KLF

MBeam 2 = 167 KIP-FT

c) Determine Mtotal: Since these moments are offsetting each other,

Mtotal = MBeam 1 – MBeam 2

= 251 – 167

Mtotal = 84 KIP-FT

wu = 2.5 KLF

30’-0”

Ln = 28.33’

Page 212: Structural Analysis and Design Lectures

Lecture 34 - Page 11 of 12

Step 4 - Determine if the column is acceptable based on “Column Interaction Diagram.”

a) Determine e/h ratio:

e = eccentricity

= u

total

PftM )/"12(

= KIPS

ftFTKIP189

)/"12(84 −

e = 5.33”

"20"33.5

=he

he = 0.27 > 0.10 → CANNOT use small eccentricity formula

b) Determine γ:

X = concrete cover + stirrup dia. + ½(vert. bar dia.) = 1½” + ⅜” + ½(8/8”) = 2.375” γh = 20” – (X + X) = 20” – (2.375” + 2.375”) = 15.25” γ(20”) = 15.25” γ = 0.76 → USE γ = 0.75

X X λh

20”

h = 20”

8 - #8 vertical bars

Page 213: Structural Analysis and Design Lectures

Lecture 34 - Page 12 of 12

c) Use Interaction Diagram R4-60.75:

g

u

g

n

AP

AP

= "20"20

189xKIPS

g

n

APφ = 0.47 KSI

hex

AP

hex

AP

g

u

g

n =φ

= (0.47 KSI)(0.27)

hex

AP

g

nφ = 0.13 KSI

ρg = g

s

AA

= "20"20

)_8_#_79.0(_8 2

xbarperinbars

ρg = 0.016 > 0.01 → col. is acceptable

Page 214: Structural Analysis and Design Lectures

Lecture 35 - Page 1 of 9

Lecture 35 – Wall Footings All structural load-bearing walls must bear on footings. These footings in turn distribute the loads to the soil. If the loading on the soil exceeds the soil bearing capacity, undesirable settlement will occur, resulting in cracked walls, uneven floors, or potentially structural failure in extreme overloading.

Wall Footing Requirements: 1) Must distribute the loads evenly to the soil. 2) Bottom of footing must be deeper than the frost penetration or else frost

heave will occur. 3) Must be well-drained to prevent wash-out. 4) Must bear on undisturbed (or engineered) soil.

Page 215: Structural Analysis and Design Lectures

Lecture 35 - Page 2 of 9

Typical Allowable Soil Bearing Values per IBC Table 1804.2

Soil Type: Allowable Soil Bearing (qa)*: Bedrock 12,000 PSF Sedimentary and foliated rock 4,000 PSF Sandy gravel and/or gravel 3,000 PSF Sand, silty sand, clayey sand, silty gravel, clayey gravel 2,000 PSF Clay, sandy clay, silty clay, clayey silt, silt, sandy silt 1,500 PSF Organics, peat, top soil NOT Recommended for use

as footing bearing * = An increase of one-third is permitted when using alternate load combinations in

IBC Section 1605.3.2 that include wind or earthquake loads. Example GIVEN: An 8” wide load-bearing poured-in-place concrete wall is to bear on a wall footing with the following:

• Service dead load on wall (incl. wall weight) = 8000 PLF • Service live load on wall = 6000 PLF • Allowable soil bearing = qa = 3000 PSF • Depth to frost = 3’-0” below finished grade • Soil unit weight = 110 PCF • Concrete f’c = 3000 PSI • Main steel tension reinforcing = #5 grade 60 bars • Longitudinal shrinkage/temperature bars = #4 grade 60 bars • Concrete cover = 3” per ACI

REQUIRED: Design the wall footing, including dimensions, and bar requirements.

Step 1 – Determine preliminary thickness of footing:

Preliminary footing thickness ≈ 1½(Wall width) ≈ 1½(8”) ≈ 12” TRY Preliminary footing thickness = 12”

Page 216: Structural Analysis and Design Lectures

Lecture 35 - Page 3 of 9

Step 2 – Determine effective soil bearing, qe:

qe = effective soil bearing = reduced soil bearing capacity resulting from weight of footing and weight of soil above footing (overburden) = (Allowable soil bearing) – (weight of footing) – (weight of soil) = qa – ftg. wt. – soil wt.

qe = qa – (ftg. wt.) – (soil wt.) = 3000 PSF – (1’-0” thick(150 lb/ft3)) + ((2’-0” thick(110 lb/ft3)) = 3000 PSF – 150 PSF – 220 PSF qe = 2630 PSF

Finished grade

qe

1’-0”

2’-0”

Dep

th to

fros

t = 3

’-0”

Soil overburden

Page 217: Structural Analysis and Design Lectures

Lecture 35 - Page 4 of 9

Step 3 – Determine required width of footing, wf:

Footing width = wf = e

total

qP

wf = PSFPLF

263014000

wf = 5.32 feet

USE footing width = 5’-6”

qe = 2630 PSF

Ptotal = PDL + PLL = 8000 PLF + 6000 PLF = 14,000 PLF

Footing width = wf

Page 218: Structural Analysis and Design Lectures

Lecture 35 - Page 5 of 9

Step 4 – Determine soil bearing pressure for strength design, qu:

qu = Factored soil bearing pressure acting on footing

= f

LLDL

wPP )(6.1)(2.1 +

= ft

PLFPLF50.5

)6000(6.1)8000(2.1 +

qu = 3490 PSF

Step 5 – Determine minimum depth of footing, dmin based on shear:

d = footing thickness – concrete cover – ½(Bar dia.) = 12” – 3” – ½(5/8”) = 8.69”

Vu = ⎟⎟⎠

⎞⎜⎜⎝

⎛−−

22_

2dWidthWallw

q fu

= ⎟⎟⎟⎟

⎜⎜⎜⎜

−−2/"12

"69.8

2/"12"8

2'5.53490 ftftPSF

Vu = 7170 Lbs.

Footing thickness

d

#5 bar

Page 219: Structural Analysis and Design Lectures

Lecture 35 - Page 6 of 9

dmin = Minimum depth to reinforcement based on shear

= )"12('2)85.0( c

u

fV

= )"12(30002)85.0(

.7170PSI

Lbs

dmin = 6.4” < 8.69” OK

Step 6 – Determine factored soil pressure moment, Mu at face of wall: MA = Moment at point “A”

= qu(Footing overhang) ⎟⎠⎞

⎜⎝⎛

2_ overhangFooting

= 3490 PSF(2.42’) ⎟⎠⎞

⎜⎝⎛

2'42.2

MA = 10,219 FT-LB

Footing overhang = 2.42’

qu = 3490 PSF

Footing width = 5.5 ft.

0.67’

Point “A”

Isolate footing overhang and treat as if it were a cantilevered beam

Page 220: Structural Analysis and Design Lectures

Lecture 35 - Page 7 of 9

Step 7 – Determine required tension steel, As in footing:

Recalling from Lecture 24 – Design Aid Table 1:

Concrete f’c = 3000 PSI, Grade 60 bars

2bdM u

φ = 2)"69.8)("12(9.0

)/"12)(10219( ftLbFt −

= 150.4 PSI < 190.3 PSI Use ρmin = 0.0033 As = ρbd = (0.0033)(12”)(8.69”) As = 0.34 in2 per 1’-0” length of footing

Page 221: Structural Analysis and Design Lectures

Lecture 35 - Page 8 of 9

Step 8 – Determine spacing of #5 tension bars:

Spacing = ⎟⎟⎠

⎞⎜⎜⎝

s

s

AbarperA __

"12

= ⎟⎟⎠

⎞⎜⎜⎝

⎛2

2

34.0_5_#_31.0"12

inbarperin

= 10.9” Use #5 bars spacing = 10” o.c.

Step 9 – Determine longitudinal shrinkage/temperature bars:

As temp = 0.0018bh = 0.0018(5.5’ x 12”/ft)(12”) = 1.43 in2

Number of bars = barperA

A

s

s

__

= barperin

in_4_#_20.0

43.12

2

= 7.15 bars Use 8 - #4 longitudinal temperature/shrinkage bars

h = 12”

Footing width “b” = 5.5 ft.

Page 222: Structural Analysis and Design Lectures

Lecture 35 - Page 9 of 9

Step 10 – Draw “Summary Sketch”:

NOTES: 1) Conc. f’c = 3000 PSI. 2) All bars grade 60 3) Wall reinf. & dowels not shown 4) Allow. Soil bearing = 3000 PSF

8” poured-in-place conc. wall centered over footing Finished grade

5’-6”

12”

#5 bars @ 10” o.c.

8 - #4 longitudinal bars

3’-0

” min

imum

3” conc. cover

Page 223: Structural Analysis and Design Lectures

Lecture 36 - Page 1 of 8

Lecture 36 – Column Footings All columns must bear on footings. Usually these footings are square or circular for ease of design and formwork. The same general requirements and design fundamentals pertain to column footings as for wall footings, i.e.,

Column Footing Requirements: 1) Must distribute the loads evenly to the soil. 2) Bottom of footing must be deeper than the frost penetration or else frost

heave will occur. 3) Must be well-drained to prevent wash-out. 4) Must bear on undisturbed (or engineered) soil.

A typical column footing is shown below:

Page 224: Structural Analysis and Design Lectures

Lecture 36 - Page 2 of 8

Example GIVEN: A steel column rests on a 12” x 12” base plate and has the following:

• PDEAD = 120 KIPS (Service Load) • PLIVE = 100 KIPS (Service Load) • Concrete f’c = 3000 PSI • Depth to frost = 4’-0” • Allowable soil bearing = qa = 4000 PSF • Soil unit weight = 100 PCF • Use #7 grade 60 bars for all bars • Concrete cover = 3” per ACI

REQUIRED: Design the square concrete footing, including all dimensions and bars. Provide a “Summary Sketch” showing all information necessary to build it.

Step 1 – Determine “Trial” footing thickness:

Assume footing thickness ≈ 1¼(Column Width OR Base Plate Width) ≈ 1¼(12”) TRY Footing Thickness = 15”

Step 2 – Determine effective soil bearing qe:

qe = effective soil bearing pressure = reduced soil bearing due to wt. of footing & soil above footing = qa – (wt. of footing) – (wt. of soil) qe = 4000 PSF – (1.25’(150 PCF)) – (2.75’(100 PCF)) = 3538 PSF = 3.5 KSF

Finished grade

qe

1’-3”

2’-9”

Dep

th to

fros

t = 4

’-0”

Soil overburden

Page 225: Structural Analysis and Design Lectures

Lecture 36 - Page 3 of 8

Step 3 – Determine length & width of footing:

Area of footing = e

total

qP

= e

LIVEDEAD

qPP +

= KSF

KIPSKIPS5.3

)100()120( +

= 62.9 ft2

Length x Width = 62.9 ft2 Since Length = Width

(Length)2 = 62.9 ft2 Length = 7.93 feet

Use 8’-0” x 8’-0” square footing → Area = 64 ft2 > 62.9 ft2

Step 4 – Determine bearing pressure for strength design, qu:

qu = AreaFooting

PP LIVEDEAD

_)(6.1)(2.1 +

= 264)100(6.1)120(2.1

ftKIPSKIPS +

qu = 4.75 kips/ft2

Page 226: Structural Analysis and Design Lectures

Lecture 36 - Page 4 of 8

Step 5 – Determine depth to tension bars “d”:

d = Footing thickness – (concrete cover) – ½(bar diameter) = 15” – 3” – ½(7/8”) = 11.56”

Step 6 – Determine “d” required to resist 2-way punching shear:

4ob = col. width + 2(

2d )

= 12” + 2(2

"56.11 )

= 23.56” = 1.96 feet bo = 94.24”

Col. width 2

d 2d

4ob

Footing thickness = 15”

d

#7 bar

Footing thickness = 15” d

Page 227: Structural Analysis and Design Lectures

Lecture 36 - Page 5 of 8

Vu2 = 2-way punching shear

= qu(Footing area - 2

4⎟⎠⎞

⎜⎝⎛ ob )

= 4.75 KSF(64 ft2 - ( )2'96.1 ) = 285.8 KIPS = 285,800 Lbs. dreqd = required depth to tension steel for shear

= oc

u

bfV

'4)85.0(2

= )"24.94(30004)85.0(

.800,285PSILbs

dreqd = 16.3”

Since dreqd = 16.3” > 11.56” → must increase footing thickness

Revised footing thickness = h = dreqd + 3” + ½(7/8”) = 16.3” + 3” + ½(7/8”) = 19.73”

Revised footing thickness = 20”

Page 228: Structural Analysis and Design Lectures

Lecture 36 - Page 6 of 8

Step 7 – Determine moment on footing overhang, Mu:

Mu = (Footing width)(qu) 2)_( 2OverhangFooting

= (8’-0”)(4.75KSF)2

)'5.3( 2

= 232.8 Kip-Ft

8’-0”

3’-6” 3’-6” 12”

8’-0”

Footing overhang Column

baseplate

Page 229: Structural Analysis and Design Lectures

Lecture 36 - Page 7 of 8

Step 8 – Determine area of tension steel As:

2bdM u

φ = 2

)"8/7(21"3"20)/"12"0'8(9.0

)12000(8.232

⎥⎦⎤

⎢⎣⎡ −−−

−−

ftx

FtKipInchLbFtKip

= 117.9 PSI

From Lecture 24 Table at f’c = 3000 PSI → use ρmin = 0.0033 since 117.9 PSI < 190.3 PSI.

As = ρbd = (0.0033)(8’-0” x 12”/ft)(16.56”) As = 5.25 in2

Step 9 – Determine tension bar layout:

Number of bars = barperA

A

s

s

__

= barperin

in7_#_60.0

25.52

2

= 8.75 bars Use 9 - #7 bars both ways at bottom of footing

d

Page 230: Structural Analysis and Design Lectures

Lecture 36 - Page 8 of 8

Step 10 – Draw “Summary Sketch”:

NOTES: 1) Conc. f’c = 3000 PSI. 2) All bars grade 60 3) Allow. Soil bearing = 4000 PSF 4) Anchor rods not shown for clarity 5) Column protection not shown for

clarity

Steel column on 12” x 12” base plate centered over footing Finished grade

8’-0”

20”

9 - #7 bars both ways

4’-0

” min

imum

3” conc. cover

Page 231: Structural Analysis and Design Lectures

Lecture 37 - Page 1 of 7

Lecture 37 – Load-Bearing Walls The ACI recognizes the “Empirical Design Method” for the design of load-bearing concrete walls having the following limitations:

1. Wall must be solid, with a rectangular cross-section

2. Minimum wall thickness “tw” = larger of

3. Applied load eccentricity “e” (including lateral load moments) < 6wt

4. Wall must be adequately anchored at top and bottom

25uL

4” ← Interior walls only 7½” ← Exterior walls

Load-bearing Wall

Page 232: Structural Analysis and Design Lectures

Lecture 37 - Page 2 of 7

5. Must have horizontal & vertical reinforcement, with 2 rows of

reinforcing for walls with tw > 10”

#3, #4, #5 grade 60 bars → #6 and bigger grade 60 bars →

Maximum bar spacing = smaller of

6. Effective length of wall for beam reaction = Leff Leff = smaller of

7. Design factored axial strength of wall = Pn

Pn = ⎥⎥⎦

⎢⎢⎣

⎡⎟⎟⎠

⎞⎜⎜⎝

⎛−

2

321'55.0

w

ugc t

KLAfφ

where: φ = 0.70 f’c = specified concrete strength, PSI K = end fixity of walls = 1.0 for pinned-pinned = 0.70 for fixed-pinned Ag = Gross effective area of wall section, in2 = Leff x tw Lu = unbraced height of wall, inches tw = thickness of wall, inches

Center-to-center spacing of beams Width of bearing + 4tw

Vert. bars As = 0.0012(tw)(12”) Horz. bars As = 0.0020(tw)(12”)

Vert. bars As = 0.0015(tw)(12”) Horz. bars As = 0.0025(tw)(12”)

3tw or 18”

Page 233: Structural Analysis and Design Lectures

Lecture 37 - Page 3 of 7

Example GIVEN: A poured-in-place concrete wall supports W18x35 steel beams spaced 6’-0” apart and rests on 10” wide steel bearing plates. Use the following:

• Beam end reaction = 22 KIPS Service Dead Load (Not incl. wall wt.) = 15 KIPS Service Live Load

• Wind pressure on wall = 25 PSF (service load) • Concrete f’c = 4000 PSI • Use #5 grade 60 vertical and horizontal bars • Assume “K” = 1.0 for wall end fixity

REQUIRED: Design the wall using the Empirical Design Method.

Fin. Grade

PDEAD = 22 KIPS PLIVE = 15 KIPS

Win

d =

25 P

SF

Slab on grade L u

= 1

3’-0

” Wall

Steel beam

10” bearing plate

Page 234: Structural Analysis and Design Lectures

Lecture 37 - Page 4 of 7

Step 1 – Determine “Trial” thickness of wall, tw:

Minimum wall thickness “tw” = larger of

TRY tw = 8” which is > 7½” Step 2 – Determine maximum SERVICE wind moment Mwind on wall:

Assume a 1’-0” wide “strip” of wall:

Mwind = 8

2wL

= 8

)'13)("0'125( 2−PSFx

Mwind = 528 Ft-Lb per 1’-0” length of wall = 528 Ft-Lb(6’-0”) for beam spacing = 3168 Ft-Lb per 6’-0” length of wall

Step 3 – Determine the maximum SERVICE vertical load on wall Ptotal:

Ptotal = PDEAD + PLIVE = (PDEAD + wall weight) + PLIVE

= (22 KIPS + (6’-0” "0'13)150.0/"12"8

−⎟⎟⎠

⎞⎜⎜⎝

⎛KCF

ft)) + 15 KIPS

= 29.8 KIPS + 15 KIPS Ptotal = 44.8 KIPS

25uL =

25)/"12("0'13 ft− = 6.24”

4” 7½” ← Largest

Page 235: Structural Analysis and Design Lectures

Lecture 37 - Page 5 of 7

Step 4 – Determine if e/h ratio is acceptable for Empirical Design:

e = PM

= KIPS

ftFtKip8.44

)/"12(168.3 −

= 0.85 inches

The empirical design method dictates that e < 6wt

6wt =

6"8

6wt = 1.33” > 0.85” → OK to use Empirical Design Method

Step 5 – Determine applied factored axial load, Pu:

Pu = 1.2(PDEAD) + 1.6(PLIVE) = 1.2(29.8 KIPS) + 1.6(15 KIPS) = 59.8 KIPS

Step 6 – Determine factored bearing strength of concrete:

A1 = bearing contact area from beam, in2 = (bearing plate width)(tw) = (10”)(8”) = 80 in2 Concrete bearing capacity = 0.9(0.85f’cA1) = 0.9(0.85(4000 PSI)(80 in2)) Concrete bearing capacity = 244,000 Lbs > 59.8 KIPS → OK

Service wind load moment

Service axial load (see above)

Wall thickness

Page 236: Structural Analysis and Design Lectures

Lecture 37 - Page 6 of 7

Step 7 – Determine design axial strength of wall Pn:

Leff = smaller of Ag = Gross effective area of wall section, in2

= Leff x tw = (42”)(8”) = 336 in2

Pn = ⎥⎥⎦

⎢⎢⎣

⎡⎟⎟⎠

⎞⎜⎜⎝

⎛−

2

321'55.0

w

ugc t

KLAfφ

= ⎥⎥⎦

⎢⎢⎣

⎡⎟⎟⎠

⎞⎜⎜⎝

⎛−

22

)"8(32)/"12'13)(0.1(1)336)(4000)(70.0(55.0 ftxinPSI

Pn = 325,300 Lbs. > 59.8 KIPS → wall is acceptable

Step 8 – Determine vertical and horizontal bars:

#3, #4, #5 grade 60 bars →

a) Vert. bars → As = 0.0012(8”)(12”) = 0.115 in2 per 1’-0” length of wall

spacing = 12” ⎟⎟⎠

⎞⎜⎜⎝

⎛2

2

115.0_5_#_31.0

inbarperin

= 32.3” Maximum bar spacing = smaller of

USE #5 vertical bars @ 18” o.c.

Center-to-center spacing of beams = 6’(12”/ft) = 72” Width of bearing + 4tw = 10” + 4(8”) = 42” ← USE

Vert. bars As = 0.0012(tw)(12”) Horz. bars As = 0.0020(tw)(12”)

3tw = 3(8”) = 24” or 18” ← USE

Page 237: Structural Analysis and Design Lectures

Lecture 37 - Page 7 of 7

b) Horizontal bars → As = 0.0020(tw)(12”) = 0.0020(8”)(12”) = 0.192 in2

spacing = 12” ⎟⎟⎠

⎞⎜⎜⎝

⎛2

2

192.0_5_#_31.0

inbarperin

= 19.4” Maximum bar spacing = smaller of

USE #5 horizontal bars @ 18” o.c.

Step 9 – Draw “Summary Sketch”:

#5 @ 18” ea. way

18”

3tw = 3(8”) = 24” or 18” ← USE

Fin. Grade

Slab on grade

L u =

13’

-0”

8” thick concrete Wall

W18x35 Steel beam

10” bearing plate

NOTES: 1) Conc. f’c = 4000 PSI. 2) All bars grade 60 3) Footing dowels not shown

Page 238: Structural Analysis and Design Lectures

Lecture 39 - Page 1 of 12

Lecture 39 – Prestressed Concrete Prestressed concrete refers to concrete that has applied stresses induced into the member. Typically, wires or “tendons” are stretched and then blocked at the ends creating compressive stresses throughout the member’s entire cross-section. Most Prestressed concrete is precast in a plant.

Advantages of Prestressed concrete vs. non-Prestressed concrete: • More efficient members (i.e., smaller members to carry same loads) • Much less cracking since member is almost entirely in compression • Precast members have very good quality control • Precast members offer rapid field erection

Disadvantages of Prestressed concrete vs. non-Prestressed concrete:

• More expensive in materials, fabrication, delivery • Heavy precast members require large cranes • Somewhat limited design flexibility • Small margin for error • More complicated design

Typical Precast Prestressed concrete members

Page 239: Structural Analysis and Design Lectures

Lecture 39 - Page 2 of 12

Pre-Tensioned Prestressed Concrete:

Pre-tensioned concrete is almost always done in a precast plant. A pre-tensioned Prestressed concrete member is cast in a preformed casting bed. The BONDED wires (tendons) are tensioned prior to the concrete hardening. After the concrete hardens to approximately 75% of the specified compressive strength f’c, the tendons are released and axial compressive load is then transmitted to the cross-section of the member.

“Live” end “Dead” end

Tendons tensioned between bulkheads

Prestress force Ps

Casting bed

Tendons anchored at “Live” end and “Dead” end

Fresh concrete placed in bed

Tendons released at “Live” end and “Dead” end creating an axial force along length of precast member

Prestress force Ps

Hardened concrete

Step 1

Step 2

Step 3

Page 240: Structural Analysis and Design Lectures

Lecture 39 - Page 3 of 12

Post-Tensioned Prestressed Concrete:

A post-tensioned member has UNCOATED tendons cast into concrete in draped patterns. After the concrete hardens to about 75% f’c, the tendons are tensioned and try to straighten out. This creates an upward camber of the member which offsets anticipated downward deflection due to gravity loads. Post-tensioning can be accomplished on-site as necessary.

Prestress force Ps

“Live” end “Dead” end

Tendons tensioned between bulkheads

Tendons anchored at “Live” end “Dead” end

Tendons creating an upward force along length of member

Step 1

Step 2

Page 241: Structural Analysis and Design Lectures

Lecture 39 - Page 4 of 12

Analysis of Rectangular Prestressed Members:

The analysis of a member is typically done for various stages of loading under SERVICE LOADS. Stresses “f” are obtained as follows:

f = g

s

g

s

IeyP

AP

±

where: Ps = prestress force Ag = gross cross-sectional area of member e = eccentric distance between prestressing tendons and member centroid y = distance from centroid to extreme edge of member Ig = gross moment of inertia of member about N.A.

Mu = 0.9Apsfps(dp - 2a )

where: Mu = usable moment capacity of prestressed beam Aps = area of prestressed tendons

fps = ⎟⎟⎠

⎞⎜⎜⎝

⎛⎥⎦

⎤⎢⎣

⎡−

c

pup

ppu f

ff

'1

1

ρβγ

fpu = ultimate tensile strength of prestressing tendon

γp = factor based on the type of prestressing steel = 0.40 for ordinary wire strand = 0.28 for low-relaxation wire strand β1 = 0.85 for concrete f’c = 4000 PSI = 0.80 for concrete f’c = 5000 PSI

ρp = p

ps

bdA

Page 242: Structural Analysis and Design Lectures

Lecture 39 - Page 5 of 12

a = bf

fA

c

psps

'85.0

dp h

b

N.A.

yt

yb e

Aps

Rectangular Prestressed Beam

Page 243: Structural Analysis and Design Lectures

Lecture 39 - Page 6 of 12

Example GIVEN: The rectangular prestressed concrete beam as shown below. Use the following:

• Concrete f’c = 5000 PSI • Concrete strength = 75%(f’c) at time of prestressing • Aps = 3 – ½” dia. 7-wire strands @ 0.153 in2 per strand = 0.459 in2 • fpu = 270 KSI (using an ordinary 7-wire strand) • Initial prestress force, Ps = 70%(fpu)(Aps) • Service dead load, (NOT including beam weight) = 400 PLF • Service beam weight = 188 PLF • Service live load = 1500 PLF

REQUIRED:

1) Determine the location of the neutral axis and prestress eccentricity “e”. 2) Determine the moment of inertia about the neutral axis, Ig. 3) Determine the stresses during prestressing. 4) Determine the stresses during initial applied service beam weight. 5) Determine the stresses due to service applied dead load + live load. 6) Determine the final stresses due to all service loads and prestressing. 7) Determine the maximum actual factored moment on the beam Mmax. 8) Determine the factored usable moment capacity Mu of the beam.

22’-0”

16” 18”

10”

N.A.

yt

yb e

Aps = 0.459 in2

Rectangular Prestressed Beam

Page 244: Structural Analysis and Design Lectures

Lecture 39 - Page 7 of 12

Step 1 - Determine the location of the neutral axis and prestress eccentricity “e”:

Using a datum as measured from the top of the beam:

n = conc

steel

EE

= cf

PSI'000,57

000,000,29

= 7.2 nAps = 7.2(0.459 in2) = 3.30 in2

yt = )30.3()"18"10(

)30.3("16)"18"10("92

2

inxinx

++

yt = 9.13”

yb = 18” – 9.13”

yb = 8.87” e = dp – yt

= 16” – 9.13”

e = 6.87”

e

18”/2 = 9”

Datum

yt

Yb

dp =16” h = 18”

10”

nAps = 3.30 in2

Page 245: Structural Analysis and Design Lectures

Lecture 39 - Page 8 of 12

Step 2 - Determine the moment of inertia about the neutral axis, Ig:

Ig = 223

)(212

enAhybhbhpst +⎟

⎠⎞

⎜⎝⎛ −+

= 2223

)"87.6)(30.3(2"18"13.9)"18)("10(

12)"18)("10( in+⎟

⎠⎞

⎜⎝⎛ −+

= 4860 in4 + 3.0 in4 + 155.7 in4

Ig = 5018.7 in4

Step 3 – Determine the stresses during prestressing:

f = g

s

g

s

IeyP

AP

±−

where: Ps = prestress force = 70%(fpu)(Aps) = 0.70(270 KSI)(0.459 in2) = 86.8 KIPS

y = yt for tensile stresses at top of beam = yb for compressive stresses at bottom of beam

a) Check stresses at TOP of beam:

ftop = stress at top of beam

= -g

ts

g

s

IeyP

AP

+

= 47.5018)"13.9)("87.6)(8.86(

)"18"10(8.86

inKIPS

xKIPS

+−

= -0.48 KSI + 1.08 KSI

ftop = 0.60 KSI Tension

Page 246: Structural Analysis and Design Lectures

Lecture 39 - Page 9 of 12

b) Check stresses at BOTTOM of beam:

fbottom = stress at bottom of beam

= g

bs

g

s

IeyP

AP

−−

= 47.5018)"87.8)("87.6)(8.86(

)"18"10(8.86

inKIPS

xKIPS

−−

= -0.48 KSI - 1.05 KSI

fbottom = -1.53 KSI Compression

Step 4 - Determine the stresses during initial applied service beam weight:

f = g

beam

IyM )(

±

where: Mbeam = maximum unfactored moment due to beam wt.

= 8

)( 2Lwbeam

= 8

)"0'22)(188( 2−PLF

= 11,374 Lb-Ft = 11.4 KIP-FT

y = yt for compression in top = yb for tension in bottom

a) Check stresses at TOP:

ftop = g

tbeam

IyM )(

= 47.5018)"13.9))(/"12(4.11(

inftFTKIP −

ftop = -0.25 KSI Compression

Page 247: Structural Analysis and Design Lectures

Lecture 39 - Page 10 of 12

b) Check stresses at BOTTOM:

Fbottom = g

bbeam

IyM )(

+

= 47.5018)"87.8))(/"12(4.11(

inftFTKIP −

+

fbottom = 0.24 KSI Tension

Step 5 - Determine the stresses due to service applied dead load + live load:

f = g

LLDL

IyM )(+±

where: MDL+LL = maximum unfactored moment due to DL+LL

= 8

)( 2Lw LLDL+

= 8

)"0'22)(1500400( 2−+ PLFPLF

= 114,950 Lb-Ft = 115.0 KIP-FT

y = yt for compression in top = yb for tension in bottom

a) Check stresses at TOP:

ftop = g

tLLDL

IyM )(+−

= 47.5018)"13.9))(/"12(0.115(

inftFTKIP −

ftop = -2.51 KSI Compression

Page 248: Structural Analysis and Design Lectures

Lecture 39 - Page 11 of 12

b) Check stresses at BOTTOM:

fbottom = g

bLLDL

IyM )(++

= 47.5018)"87.8))(/"12(0.115(

inftFTKIP −

+

fbottom = 2.44 KSI Tension

Step 6 - Determine the final stresses due to all service loads and prestressing:

Step 7 – Determine the maximum actual factored moment on the beam Mmax:

Mmax = 8

2Lwu

wu = 1.2D + 1.6L = 1.2(400 PLF + 188 PLF) + 1.6(1500 PLF) = 3106 PLF = 3.1 KLF

Mmax = 8

)0'22(1.3 2−

Mmax = 188 KIP-FT

Initial Prestress

18” + + = + =

-0.48C +1.08T +0.35T -0.25C -2.51C -2.16C

-0.48C -1.05C +0.24T -1.29C +2.44T +1.15T

g

s

AP−

g

s

IeyP+

Beam Wt. Transfer DL + LL Final

Page 249: Structural Analysis and Design Lectures

Lecture 39 - Page 12 of 12

Step 8 - Determine the factored usable moment capacity Mu of the beam:

Mu = 0.9Apsfps(dp - 2a )

where:

fps = ⎟⎟⎠

⎞⎜⎜⎝

⎛⎥⎦

⎤⎢⎣

⎡−

c

pup

ppu f

ff

'1

1

ρβγ

fpu = ultimate tensile strength of prestressing tendon = 270 KSI

γp = factor based on the type of prestressing steel = 0.40 for ordinary wire strand β1 = 0.80 for concrete f’c = 5000 PSI

ρp = p

ps

bdA

= )"16)("10(

453.0 2in

= 0.00283

fps = ⎟⎟⎠

⎞⎜⎜⎝

⎛⎥⎦⎤

⎢⎣⎡−

KSIKSIKSI

5270)00283.0(

80.040.01270

= 249.4 KSI

a = bf

fA

c

psps

'85.0

= )"10)(5(85.0

)4.249)(453.0( 2

KSIKSIin

= 2.66”

Mu = 0.9Apsfps(dp - 2a )

= 0.9(0.453 in2)(249.4 KSI)(16” - 2

"66.2 )

= 1492 Kip-In Mu = 124.3 KIP-FT < Mmax = 188 KIP-FT → NOT ACCEPTABLE

Page 250: Structural Analysis and Design Lectures

Lecture 4 - Page 1 of 12

Lecture 4 – Beam Design for Moment Beams, or sometimes referred to as “flexure” members, are designed on the basis of moment. In ASD and LRFD, the design strength of a beam in flexure is called the “nominal flexural moment”, Mn. This Mn must be greater than the maximum applied factored (LRFD) or service (ASD) moment. Beams are designed on the basis of the following LRFD references:

• AISC Part 3 • AISC Spec Chapter F p. 16.1-44

1. Beam Design Considering Yielding:

Assuming a beam is adequately laterally braced, it will fail by yielding on the compression flange. Most beams are laterally braced by the metal decking that is attached to the compression flange as shown below:

1) LRFD Beam Design:

Design Flexural Strength = φbMn Where: φb = 0.90 Mn = nominal flexural moment = Mp = Plastic moment = FyZx

Zx = plastic section modulus = from properties

Concrete slab over metal decking

Metal decking puddle-welded to top flange of beam

Page 251: Structural Analysis and Design Lectures

Lecture 4 - Page 2 of 12

2) ASD Beam Design:

Allowable Flexural Strength = b

nMΩ

Where: Ωb = 1.67 Mn = nominal flexural moment = Mp = Plastic moment = FyZx

Zx = plastic section modulus = from properties Example 1 (LRFD) GIVEN: A W16x26 steel beam using A992 steel is continuously laterally braced, and experiences a FACTORED moment = 104 KIP-FT. REQUIRED: 1) Determine the design flexural moment, φbMn for the beam. 2) Determine if the beam is adequate.

Step 1 – Determine φbMn for the beam:

φbMn = 0.90(FyZx) since it is continuously laterally braced = 0.90(50 KSI)(44.2 in3) = 1989 KIP-IN φbMn = 165.8 KIP-FT

Step 2 – Determine if the beam is adequate:

Since φbMn = 165.8 KIP-FT > 104 KIP-FT → beam is adequate Example 2 (LRFD) GIVEN: The W16x26 beam from Example 1. REQUIRED: Determine the design flexural moment, φbMn for the beam using the LRFD “Zx” Table 3-2 (see AISC p. 3-11 thru 3-19) Step 1 – Refer to AISC p. 3-18 for W16x26:

Look in the LRFD column φbMpx = 166 KIP-FT

From properties, AISC p. 1-21

Page 252: Structural Analysis and Design Lectures

Lecture 4 - Page 3 of 12

Example 3 (ASD) GIVEN: An A992 steel beam “A” is continuously laterally braced and carries a superimposed SERVICE (i.e., not factored) floor live load = 100 PSF and a superimposed SERVICE dead load = 85 PSF. Assume initially the beam weighs 30 PLF and check your results. REQUIRED: 1) Design the lightest weight steel beam using the “Zx” Table 3-2. 2) Design the lightest weight W14 steel beam using the “Maximum Total

Uniform Load Table 3-6” (see AISC p. 3-33 thru 3-95).

Step 1 – Determine SERVICE uniform load, w on beam:

By inspecting the ASD load factors AISC p. 2-9, the maximum applied uniform load w = D + L Where: D = uniform dead load, PLF = 7’(85 PSF) + 30 PLF = 625 PLF L = uniform live load, PLF = 7’(100 PSF) = 700 PLF w = (625 PLF) + (700 PLF) = 1325 PLF = 1.325 KLF

Gird

er “A

Beam “A”

32’-0”

3@7’

-0” =

21’

-0”

Assumed beam wt.

Page 253: Structural Analysis and Design Lectures

Lecture 4 - Page 4 of 12

Step 2 – Determine maximum SERVICE moment, Ma:

Ma = 8

2wL

= 8

)'32(325.1 2KLF

Ma = 169.6 KIP-FT

Step 3 – Select lightest weight beam from Table 3-2:

From AISC p. 3-17 look under ASD column b

pxMΩ

to find a

BOLD moment that is equal or larger than the calculated Ma:

Use W16x40 → b

pxMΩ

= 182 KIP-FT > 169.6 KIP-FT

→ (NOTE: If the assumed beam weight of 30 PLF were increased to 40 PLF, the revised Ma = 170.9 KIP-FT which is still less than 182 KIP-FT)

R2 = 21.2 KIPS R1 = 21.2 KIPS

32’-0”

w = 1.325 KLF

Page 254: Structural Analysis and Design Lectures

Lecture 4 - Page 5 of 12

Step 4 – Determine total SERVICE uniform load on beam:

W = Total service load on beam, KIPS = w x span = 1.325 KLF(32’-0”) = 42.4 KIPS

Step 5 – Select lightest W14 beam using Table 3-6 “Maximum Total Uniform Load” tables:

From AISC p. 3-67, look find span = 32’ then read across to find the lightest weight beam having maximum ASD total uniform load > 42.4 KIPS. Use W14x43 → max. total unif. load = 43.4 KIPS > 42.4 KIPS → (NOTE: Using this method, the lightest possible beam is W16x40 → max. total unif. load = 45.5 KIPS > 42.4 KIPS)

Page 255: Structural Analysis and Design Lectures

Lecture 4 - Page 6 of 12

2. Beam Design Considering “Lateral-Torsional Buckling”

The compression flange of a beam behaves like a column – it is susceptible to buckling if not adequately laterally braced. This phenomenon of flange buckling of a beam is referred to as “lateral-torsional buckling.” Consider a skinny yard stick under loading. If it is not properly braced, it will twist and fail under a much smaller load than if it were adequately braced. Therefore, wider-flanged beams are better at resisting lateral-torsional buckling than narrow-flanged beams.

It has been determined that the relationship between distance between lateral bracing and moment capacity looks like the following:

Distance between lateral supports

Mom

ent c

apac

ity

Page 256: Structural Analysis and Design Lectures

Lecture 4 - Page 7 of 12

The AISC has developed graphs of LRFD and ASD beam design

moments, φbMn, and b

nMΩ

respectively, for beam shapes that has been

mathematically altered from the graph above (for simplicity), and looks like the following: (See AISC p. 5-7 and AISC p. 16.1-33)

Where: φb = 0.90 (LRFD) Ωb = 1.67 (ASD)

Lp = y

y FEr76.1 AISC p. 16.1-48

Lr = y

ts FEr7.0

π AISC p. 16.1-48

E = 29000 KSI Fy = yield stress, KSI

Mp = (FyZx) AISC p. 16.1-47 Mr = 0.7(FySx) AISC p. 16.1-269 Sx = Section modulus about “x” axis from properties

φbMp and b

pMΩ

φbMr and b

rMΩ

Mom

ent c

apac

ity

Lp Lr

Distance between lateral supports

Real curve

AISC curve

Page 257: Structural Analysis and Design Lectures

Lecture 4 - Page 8 of 12

Example 4 (LRFD) GIVEN: A W14x43 steel girder using A992 steel. It is laterally braced at Lb = 8’-0” increments by beams framing into the side. It experiences a maximum FACTORED moment, Mu = 250 KIP-FT. REQUIRED: 1) Draw the graph of design moments vs. unbraced length. 2) Determine the design moment, φbMn for an actual unbraced length Lb =

10’-0” using formula F2-2 from AISC p. 16.1-47. 3) Determine the design moment using the “Beam Available Moments vs.

Unbraced Length” graphs on AISC p. 3-125.

Step 1 – Draw graph of design moments vs. unbraced length:

From AISC p. 3-17, pick values of Lp, Lr, φbMp, and φbMr

Step 2 - Determine the design moment, φbMn for an unbraced length Lb = 8’-0” using formula F2-2 from AISC p. 16.1-32

Mn = ⎥⎥⎦

⎢⎢⎣

⎡⎟⎟⎠

⎞⎜⎜⎝

−−−

pr

pbxyppb LL

LLSFMMC )7.0(

Where: Cb = 1.0 (conservative) Mp = FyZx = (50KSI)(69.6 in3) = 3480 Kip-In

φbMn = ????

φbMrx = 164 KIP-FT

φbMpx = 261 KIP-FT

Lp = 6.68 ft. Lr = 20.0 ft.

Real curve

Lb = 10’-0”

AISC curve

Page 258: Structural Analysis and Design Lectures

Lecture 4 - Page 9 of 12

Mn = ⎥⎦

⎤⎢⎣

⎡⎟⎠⎞

⎜⎝⎛

−−

−−− )'68.6'20'68.6'10)6.62)(50(7.03480((34800.1 3inKSIInKip

= 3159 Kip-In = 263.3 Kip-Ft Therefore, since φ = 0.9: φMn = 0.9(263.3 Kip-Ft) φMn = 237 Kip-Ft

Since φMn = 237 Kip-Ft < Mu = 250 Kip-Ft, beam is UNACCEPTABLE

Page 259: Structural Analysis and Design Lectures

Lecture 4 - Page 10 of 12

Step 3 – Determine FACTORED moment strength using Table 3-10:

From AISC p. 3-125: For a W14x43 with Fy = 50 KSI Unbraced length Lb = 10’-0”

Lb = 10’-0”

φMn ≅ 237 Kip-Ft

LRFD

Page 260: Structural Analysis and Design Lectures

Lecture 4 - Page 11 of 12

Example 5 (ASD) and (LRFD) GIVEN: A steel girder is laterally braced at Lb = 10’-0, and experiences the service loads as shown below. REQUIRED: Design the lightest weight A992 wide-flange beam using the “Available Moment vs. Unbraced Length” graphs.

Step 1 – Determine ASD maximum SERVICE moment:

w = D + L = (900 PLF) + (1700 PLF) = 2600 PLF = 2.6 KLF Ma = Maximum applied SERVICE moment

= 8

2wL

= 8

)"0'30)(6.2( 2−KLF

Ma = 292.5 Kip-Ft.

30’-0”

Service DL = 900 PLF (incl. beam wt.) Service LL = 1700 PLF

Page 261: Structural Analysis and Design Lectures

Lecture 4 - Page 12 of 12

Step 2 – Determine LRFD maximum FACTORED moment:

wu = 1.2D +1.6 L = 1.2(900 PLF) + 1.6(1700 PLF) = 3800 PLF = 3.8 KLF Mu = Maximum applied FACTORED moment

= 8

2Lwu

= 8

)"0'30)(8.3( 2−KLF

Mu = 427.5 Kip-Ft.

Step 3 – Design lightest beam using “Available Moment vs. Unbraced Length” graph:

From AISC p. 3-121 and 3-119, read up from the bottom at Lb = 10’-0” and look up until you hit a solid line for the lightest weight beam exceeding 292.5 Kip-Ft (ASD) and 427.5 Kip-Ft (LRFD).

ASD:

Use W21x62 → ftKipM n −≈Ω

316

LRFD: Use W21x62 → ftKipM n −≈ 474φ

Page 262: Structural Analysis and Design Lectures

Lecture 40 - Page 1 of 14

Lecture 40 – Concrete Specifications Project-specific construction documents generally consist of two items:

• Design Drawings • Specifications

The Design Drawings graphically present the specific design of the structure. However, they do not indicate the specific requirements relating to:

• Materials • Submittals • Job conditions • Testing & inspection • Execution of work

CSI – Construction Specifications Institute

The CSI was founded in 1948 in an effort to organize trade-specific specifications into a uniform, industry accepted format. It developed the “MasterFormat”, a breakdown of all construction-related activities into 16 divisions as follows:

Division 1 – General Requirements Division 2 – Site Construction Division 3 – Concrete Division 4 – Masonry Division 5 – Metals Division 6 – Wood and Plastics Division 7 – Thermal and Moisture Protection Division 8 – Doors and Windows Division 9 – Finishes Division 10 – Specialties Division 11 – Equipment Division 12 – Furnishings Division 13 – Special Construction Division 14 – Conveying Systems Division 15 – Mechanical Division 16 – Electrical

Each division has been further refined into multiple sub-divisions (as shown for Division 3 above). To obtain samples of specifications, go to http://www.ogs.state.ny.us/dnc/masterspec/default.htm In addition to technical specifications, the CSI MasterFormat is used by most of the construction industry for purposes of cost estimating, contractor qualifications, product research and supply ordering.

03050 – Basic Concrete Materials and Methods 03100 – Concrete Forms and Accessories 03200 – Concrete Reinforcement 03300 – Cast-in-Place Concrete 03400 – Precast Concrete 03500 – Cementitious Decks and Underlayment 03600 – Grouts 03700 – Mass Concrete 03900 – Concrete Restoration and Cleaning

Page 263: Structural Analysis and Design Lectures

Lecture 40 - Page 2 of 14

Section 03300 – Cast-inPlace Concrete PART 1 - GENERAL 1.1 SUMMARY

A. Work Included: Cast-in-place concrete. 1.2 QUALITY ASSURANCE

A. Comply with the latest edition of the following: 1. ACI 301 "Specifications for Structural Concrete for Buildings" 2. ACI 302 "Guide for Concrete Floor and Slab Construction" 3. ACI 304 "Recommended Practice for Measuring, Mixing, Transporting, Placing

Concrete" 4. ACI 305 "Hot Weather Concreting" 5. ACI 306 "Cold Weather Concreting" 6. ACI 311 "Recommended Practice for Concrete Inspection" 7. ACI 315 "Details and Detailing of Concrete Reinforcement" 8. ACI 318 "Building Code Requirements for Reinforced Concrete" 9. ACI 347 "Recommended Practice for Concrete Formwork" 10. ACI SP-15 Field Reference Manual 11. CRSI "Manual of Standard Practice"

1.3 SUBMITTALS

A. Shop Drawings: Submit Shop Drawings for fabrication, bending and placement of concrete reinforcement. Show bar schedules, stirrup spacing, diagrams of bent bars, arrangements of concrete reinforcement. Include special reinforcement required for openings through concrete. Show elevations of reinforcement for all members at minimum 1/4 inch = 1'-0" scale. Show locations all construction and control joints.

B. Mix Design: Submit proposed mix designs for concrete at least 15 days before start of

concreting. Submittal shall include: cement content and type, admixture content and type, aggregate source and gradation, water content, air content, slump, and documentation of average strength by field experience or laboratory prepared trial mixtures in accordance with ACI 318 Article 4.3.

C. Product Data: Submit data and installation instructions for proprietary material.

D. Material Certificates: Submit materials certificates certifying that each material

complies with Specifications. 1.4 TESTING SERVICES

A. Employ, at Contractor's expense, a testing laboratory acceptable to Architect to perform material evaluation tests and for quality control during placement.

Page 264: Structural Analysis and Design Lectures

Lecture 40 - Page 3 of 14

B. Sample and test concrete for quality control during placement as follows:

1. Sampling Fresh Concrete: ASTM C172 except modified for slump to comply with ASTM C94.

2. Slump: ASTM C143 - one for each concrete truck, measured at point of discharge.

3. Air Content: ASTM C231 pressure method - one for each truck load of ready-mixed air-entrained concrete.

4. Temperature: Test concrete temperature hourly when ambient temperature is 40oF and below, and when 80oF and above.

5. Compressive Test Specimen: ASTM C31, one set of six standard cylinders for each compressive strength test. Store undisturbed and in an insulated box during cold weather. Deliver cylinders to lab between 24 and 48 hours after making.

6. Compressive Strength Tests: ASTM C39, one set of six cylinders for each 50 cubic yards or fraction thereof, of each concrete class placed in any one day, two lab specimens tested at 7 days, two lab specimens tested at 28 days and two specimens retained in reserve for later testing if required.

C. Test Reports

1. Forward results to Architect, Engineer and Contractor on same day that tests are made.

2. Reports of compressive strength tests shall contain the general information of project identification name and number, date of concrete placement, name of Contractor, name of concrete supplier, truck number and delivery ticket number, name of concrete testing service, concrete type and class, name of individual making specimen, location of concrete batch in structure, design compressive strength at 28 days, concrete mix proportions and materials; and the specific information of slump, air content, temperature, compressive strength and type of break for both 7-day and 28-day tests.

3. Field reports of concrete inspection shall contain general information noted above, plus ambient temperature, concrete temperature, weather, slump, air content and cylinder numbers.

D. Additional Testing

1. Testing service shall make additional tests of in-place concrete when test results indicate specified concrete strengths and other characteristics have not been attained in structure.

2. Testing service shall conduct tests to determine adequacy of concrete by cored cylinders complying with ASTM C42 or by other methods acceptable to Architect.

3. Contractor shall pay for such tests conducted, and any other additional testing required, if concrete testing confirms specified strengths have not been met.

1.5 JOB CONDITIONS

Page 265: Structural Analysis and Design Lectures

Lecture 40 - Page 4 of 14

A. Store materials so as to ensure preservation of their quality and fitness for the Work. Store reinforcement and formwork in a manner to prevent damage and accumulation of dirt.

B. Contractor shall be responsible for correction of concrete work which does not

conform to specified requirements, including strength, tolerances and finishes. Correct deficient concrete as directed by Architect.

PART 2 - PRODUCTS 2.1 MATERIALS

A. Formwork 1. Exposed Concrete: Unless otherwise shown or specified, construct formwork for

concrete surfaces, which will be exposed to view in the completed project, with form plywood, metal or other acceptable panel-type material, to provide continuous, straight, smooth exposed surfaces. Furnish in largest practicable sizes to minimize number of joints and to conform to joint system shown on Drawings. Provide form material with sufficient thickness to withstand pressure of newly-placed concrete without bow or deflection.

2. Unexposed Concrete: Form concrete surfaces which will be unexposed to view in the completed Project with plywood, lumber, metal or other acceptable material. Provide lumber dressed on at least 2 edges and 1 side for tight fit.

B. Form Ties

1. Exposed Concrete: Plastic cone snaptie, Type 3M by Superior or accepted equal. 2. Unexposed Concrete: Snap-off metal ties, designed to prevent form deflection

and prevent spalling surfaces upon removal. Portion remaining after removal shall be at least 1" from concrete surface.

C. Form Coatings: Commercial formulation form-coating compounds shall not bond

with, stain, nor adversely affect concrete surfaces, and shall not impair subsequent treatments of concrete surfaces requiring bond or adhesion, nor impede wetting of surfaces to be cured with water or curing compound.

D. Reinforcement

1. Deformed bars: ASTM A615, Grade 60. 2. Welded Wire Fabric: ASTM A185. Flat sheets only. 3. All chairs, spacers, clips, wire anchors and related items necessary to accurately

space and secure reinforcement. 4. Additional bars, if required, to anchor or space reinforcement. 5. Chairs shall be plastic booted at points of bearing on forms for exposed concrete. 6. Minimum 16-gage annealed tie wire, ASTM A82.

E. Cement: ASTM C150, Type I or Type II.

F. Aggregates: ASTM C33 and as herein specified.

Page 266: Structural Analysis and Design Lectures

Lecture 40 - Page 5 of 14

1. Fine Aggregate: Clean, sharp, natural sand free from loam, clay, lumps or other deleterious substances with less than 10% passing the #100 sieve and less than 3% passing the #200 sieve.

2. Coarse Aggregate: Clean, uncoated, processed aggregate containing no clay, mud, loam or foreign matter, as follows: a. Crushed stone: Processed from natural rock or stone for concrete slabs

meeting NYSDOT 703-0201. b. Clean, sharp, natural or processed gravel, or crushed stone, free from loam,

clay, lumps, or other deleterious substances for footings and miscellaneous concrete.

c. Maximum Aggregate Size: Footings and walls size 467. Slabs size 57 with minimum of 1800 pounds per cubic yard.

G. Water: Clean, fresh, potable.

H. Air Entraining: ASTM C260.

I. Water Reducing Admixture: ASTM C494, Type A.

J. Non Corrosive, Non Chloride Accelerator: ASTM C494, Type C or E.

K. Prohibited Admixtures: Calcium chloride, thiocyanates. Admixtures containing more

than 0.05% chloride ions are not permitted.

L. Evaporation Retarder: Confilm by Master Builders, or accepted equal.

M. Curing Sheet Materials: ASTM C171, including waterproof paper, polyethylene film or polyethylene coated burlap.

N. Liquid Membrane Curing/Sealing Compound: Masterkure by Master Builders or

accepted equal.

O. Exterior Anti-Spalling Sealer: Penetrating Sealer 40 by Sonneborn or accepted equal.

P. Hardener: Lapidolith by Sonneborn or accepted equal.

Q. Mineral Aggregate Floor Surface Hardener: Colorcron by Master Builders or accepted equal. French gray color. Apply at rate of 1.00 pounds per square foot.

R. Joint Filler: 1/2" thick ASTM D994 premolded expansion joint filler strips; full slab

depth. Where joint is exposed and scheduled to receive sealant, provide 1/2" vinyl removable filler cap strip, 940 Series by Green Streak or accepted equal.

S. Sleeves: ASTM A120, hot-dipped galvanized.

T. Anchor Bolts: Furnished in Section 05100 and installed under this Section.

Page 267: Structural Analysis and Design Lectures

Lecture 40 - Page 6 of 14

U. Dowel Bars: 1-inch square steel bars with ¼-inch compressible foam on vertical faces; or 1-inch-diameter steel bars, greased.

V. Non-shrink Grout: Sonogrout 14 by Sonneborn, or accepted equal.

W. Water Stop: Volclay Waterstop RX, 1" x 3/4" by American Colloid Co. or accepted

equal.

X. Dovetail Slot: Standard Dovetail Slot #180, 26 gauge galvanized steel with foam filler by Heckmann Building Products or accepted equal.

2.2 PROPORTIONING AND MIX DESIGN

A. Prepare design mixes for concrete. Use independent testing facility acceptable to Architect for preparing and reporting proposed mix designs.

B. Where the concrete production facility can establish the uniformity of its production

for concrete of similar strength and materials based on recent test data, the average strength used as a basis for determining mix design proportions shall exceed the specified design strength by the requirements of ACI-318, Section 4.3.2 or ACI-301, Section 3.9.

When a concrete production facility does not have field test records for calculation of

standard deviation, the required average strength shall be at least 1,200 psi greater than the specified design strength.

C. Concrete Quality

Location

Required 28 day

Compressive Strength

Maximum Water

Cement Ratio

Air Content

Weight

Footings, foundation walls and all other below grade concrete, miscellaneous concrete.

3,000 0.55 4% - 6% 147 - 153 pcf

Interior slabs on grade and suspended slabs.

3,500 0.50 0% 147 - 153 pcf

Exterior concrete subjected to freezing and thawing, exterior slab on grade.

4,000 0.45 5% - 7% 147 - 153 pcf

Interior light weight suspended slab.

4,000 0.45 4% - 6% 114 - 120 pcf

D. Slump

1. Footings and Foundation Walls: 3" to 5". 2. Slabs: 4" maximum.

E. Ready Mix Concrete: ASTM C94.

Page 268: Structural Analysis and Design Lectures

Lecture 40 - Page 7 of 14

F. The quantity of coarse aggregate in pounds must be in the range of 1.25 to 1.5 times

the quantity of fine aggregate in pounds.

G. Fly ash may be substituted for cement for interior slabs only, at a maximum rate of 15 percent by weight. Submittals shall include actual mix design, including percentage of fly ash and test results showing that mix meets specified compressive strength, and air content. Fly ash is not permitted in cold weather concreting unless extended protection is provided. Protection and heat shall be maintained until 70 percent of specified design strength is achieved.

H. Pumping of concrete is permitted only if mix designs specifically prepared and used

previously for pumping are submitted. Pumpline shall have a 5-inch minimum inside diameter and shall be used with 5-inch pumps.

2.3 REINFORCING FABRICATION

A. Fabricate bars to required lengths, shapes and bends. Do not rebend or straighten reinforcement in a manner that shall weaken the material.

2.4 FORMWORK

A. Design formwork to support vertical and lateral loads that might be applied until such loads can be supported by concrete structure.

PART 3 - EXECUTION 3.1 INSPECTION

A. Examine conditions under which concrete shall be placed. Do not proceed with work until all unsatisfactory conditions are corrected.

3.2 NOTIFICATION

A. Notify Architect 24 hours before anticipated time of completion of reinforcement in any section.

B. Do not place concrete until reinforcement has been observed and corrections, if any,

made. 3.3 FORMWORK INSTALLATION

A. Erect, brace, and maintain formwork to support vertical and lateral loads.

B. Construct forms to sizes, lines and dimensions shown to obtain accurate alignment, location, grades, level and plumb work in finished structure.

Page 269: Structural Analysis and Design Lectures

Lecture 40 - Page 8 of 14

C. Provide for openings, offsets, keys and other features required in work. Accurately position and support items.

D. Solidly butt joints and provide backup at joints to prevent leakage of cement paste.

E. Provide crush plates or wrecking plates where stripping may damage cast concrete

surfaces.

F. Kerf wood inserts for forming keys and the like to prevent swelling and for easy removal.

G. Provide openings in concrete form to accommodate work of other trades. Determine

size and location of openings, recesses and chases from trades providing such.

H. Cleaning and Tightening: Thoroughly clean forms and adjacent surfaces to receive concrete. Remove chips, wood, sawdust, dirt or other debris just before concrete is placed. Retighten forms after concrete placement if required to eliminate concrete leaks.

I. Reuse of Forms: Clean and repair surfaces of forms to be reused in the work. Split,

frayed, delaminated, or otherwise damaged form facing material is not acceptable. Apply new form coating compound material. When forms are reused for successive concrete placement, thoroughly clean surfaces, remove fins and laitance, and tighten forms to close all joints. Align and secure joints to avoid offsets.

3.4 REINFORCEMENT PLACING

A. Clean reinforcement of loose rust, mill scale, earth, ice and other materials which reduce or destroy bond with concrete.

B. Accurately position, support and secure reinforcement against displacement by

formwork, construction or concrete placement operations. Locate and support reinforcement by metal chairs, runners, bolsters, spacers and hangers as required. Do not use brick.

C. Place reinforcement to obtain at least the minimum coverages for concrete protection.

D. Arrange, space and securely tie bars and bar supports to hold reinforcement in position

during concrete placement. Set wire ties so ends are directed into concrete, not toward exposed concrete surfaces.

E. Lap bar splices as indicated. Stagger splices in adjacent bars. Wire tie all splices.

3.5 WELDED WIRE FABRIC REINFORCEMENT PLACEMENT

A. Place welded wire fabric one-third of slab thickness below top surface of slab.

Page 270: Structural Analysis and Design Lectures

Lecture 40 - Page 9 of 14

B. Place flat sheets in as long lengths as practical. Lap adjoining sheets at least one full mesh. Offset laps to prevent continuous laps in either direction.

C. Do not continue welded wire fabric through any control joints or construction joints

for slabs on grade. 3.6 CONCRETE PLACEMENT

A. Before placing concrete, inspect and complete formwork installation, reinforcing steel and items to be embedded or cast in.

B. Notify other trades to permit installation of their work. Cooperate with other trades in

setting such work as required.

C. Install anchor bolts and sleeves.

D. Deposit concrete continuously or in layers of such thickness that no concrete shall be placed on concrete which has hardened sufficiently to cause formation of seams or planes of weakness within section. Provide construction joints if section cannot be placed continuously.

E. Deposit concrete as nearly as practicable to its final location to avoid segregation

caused by rehandling or flowing.

F. Keep excavations free of water. Do not deposit concrete in water, mud, snow or on frozen ground.

G. Maximum drop of concrete shall not exceed 5 feet. Use hopper and trunk for greater

drops.

H. Contractor shall be responsible for controlling the proper placing of all embedded pipe, conduit and other embedded items.

I. Contractor shall be responsible for finishing of all concrete slabs to proper elevations

to insure that all surface moisture will drain freely to floor drains, and that no puddle areas exist. During finishing operation, Contractor shall pay particular attention to this criterion, and shall make all efforts to obtain this. Any cost of corrections to provide for this positive drainage will be the responsibility of Contractor.

3.7 CONSOLIDATION

A. Consolidate placed concrete by mechanical vibrating equipment supplemented by hand spading, rodding or tamping.

B. Do not use vibrators to transport concrete inside formwork.

Page 271: Structural Analysis and Design Lectures

Lecture 40 - Page 10 of 14

C. At each insertion, limit duration of vibration to time necessary to consolidate concrete and complete embedment of reinforcement and other embedded items without causing segregation of mix.

D. Do not allow vibrator to come in contact with form.

3.8 SURFACE FINISHES

A. Finish of Formed Surfaces 1. Rough Form Finish: For formed concrete surfaces not exposed-to-view in the

finish work or concealed by other construction unless otherwise indicated. This is the concrete surface having texture imparted by form facing material used, with tie holes and defective areas repaired and patched and fins and other projections exceeding 1/4" in height removed.

2. Smooth Form Finish: For formed concrete surfaces exposed-to-view. This is as-cast concrete surface obtained with selected form facing material, arranged orderly and symmetrically with a minimum of seams. Repair and patch defective areas with fins or other projections completely removed and smoothed. Lightly rub all exposed surfaces to achieve a uniform appearance.

or

Lightly sandblast to expose fine aggregate with occasional exposure of coarse aggregate and to make the color uniform.

B. Monolithic Slab Finishes

1. Scratch Finish: Apply scratch finish to monolithic slab surfaces to receive concrete floor topping or mortar setting beds for tile, and other bonded applied cementitious finish flooring material. After placing slabs, roughen surface before final set with stiff brushes, brooms or rakes.

2. Trowel Finish: Apply trowel finish to monolithic slab surfaces to be exposed-to-view, and slab surfaces to be covered with carpet, resilient flooring, paint or other thin film finish coating system. After floating, begin first trowel finish operation using a power-driven trowel. Begin final troweling when surface produces a ringing sound as trowel is moved over surface. Consolidate concrete surface by final hand-trowel operation, free of trowel marks.

3. Non-Slip Broom Finish: Apply non-slip broom finish to exterior concrete platforms, steps and ramps, and elsewhere as indicated. Immediately after trowel finishing, slightly roughen concrete surface by brooming with fiber bristle broom perpendicular to main traffic route.

3.9 APPLICATION OF FLOOR SURFACE HARDENER

A. Bleed water shall not be present before or during the application of this shake.

B. Apply first shake to hand floated concrete adjacent to forms, entryways, columns and walls where moisture will be lost first. Apply two-thirds of the specified total shake

Page 272: Structural Analysis and Design Lectures

Lecture 40 - Page 11 of 14

immediately following floating of total area. Distribute evenly by hand broadcasting in all areas.

C. Finishing machines with float shoes shall be used as soon as shake has absorbed

moisture (indicated by darkening of surface and when surface is firm enough to support a float machine and operator). Float just sufficiently to bring moisture from base slab through the shake. Immediately following floating, apply remaining one-third of total specified shake in the same manner, allow the hardener to darken and machine float as specified.

D. At no time shall water be added to the surface.

E. As surface further stiffens, indicated by loss of sheen, it shall be hand or mechanically

trowled with blades relatively flat. All marks and pinholes shall be removed during the final trowel operation. Finish troweling to produce a light swirl finish to provide skid resistance.

3.10 CURING AND PROTECTION

A. Concrete shall be protected from premature drying, excessively hot or cold temperature, and mechanical injury according to provisions of ACI 301, Chapter 12. During placing, all concrete flatwork exposed to or subject to rapid evaporation of moisture under drying conditions (including hot weather, low humidity, wind and/or sunlight) shall be protected immediately following screeding with evaporation retarder applied in accordance with recommendations of manufacturer. Application shall precede and shall be in addition to curing specified below.

B. Concrete shall be maintained in a continuously moist condition for at least 7 days after

placement. Curing shall begin as soon as possible after concrete has been placed and finished. Materials and methods of curing shall be submitted to Architect for acceptance.

C. Curing and Protection: Surfaces not in contact with forms and surfaces in contact

with forms for less than seven days. Curing shall be by water curings, application of liquid membrane curing/sealing

compound or by application of curing sheet materials. Curing compounds shall be applied in accordance with manufacturer's recommendations. Liquid membrane curing compound used on floor slabs receiving applied finish flooring shall be guaranteed by the manufacturer, in writing, not to impair bonding of adhesive.

For slabs use a curing treatment of water curing, curing sheet materials, or by applying

and removing curing/sealing compound. The curing compounds must be applied immediately after final finishing. For curing by water curing or curing sheet materials, the concrete must be continually moist-cured for at least 7 days. Curing shall begin immediately after finishing.

Page 273: Structural Analysis and Design Lectures

Lecture 40 - Page 12 of 14

For other surfaces (footing, walls, etc.) curing shall be by one of the accepted curing treatments listed above.

Restore curing protection on all freshly cut joint edges and faces when sawing joints

or removing forms.

D. Concrete placed under cold weather conditions shall be cured by completely covering exposed surface of concrete with curing sheet materials with sheeting completely sealed around edges. All concrete shall be cured for a minimum of 14 days with temperatures at or above 40oF or for a minimum of 7 days with temperatures at or above 70oF.

3.11 COLD WEATHER CONCRETING

A. Place concrete during cold weather in accordance with ACI 306.

B. For cold weather concreting, (defined as a period when for more than three successive days the mean daily temperature drops below 40oF) concrete temperature shall be maintained in accordance with ACI 306.

3.12 HOT WEATHER CONCRETING

A. Place concrete in accordance with ACI 305.

B. Cool ingredients before mixing to maintain concrete temperature below 90oF at time of placement.

C. Cover reinforcing steel with water-soaked burlap if temperature of reinforcing steel

exceeds ambient air temperature.

D. Wet forms thoroughly before placing concrete. 3.13 WALL JOINTS

A. Construction Joints: Locate and install construction joints as shown on Drawings. Where construction joints are not shown, locate joints at masonry control joints. Install joints maximum of 60 feet on center in locations acceptable to Architect.

3.14 INTERIOR SLAB JOINTS

A. Construction Joints: Locate and form construction joints as shown on Drawings. Where construction joints are not shown place in locations acceptable to Architect.

B. Contraction Joints: Sawcut joints as soon as possible after finishing, generally within

4 to 16 hours. Make sample cut to determine if concrete surface is firm enough so that it is not torn or damaged by the blade.

Page 274: Structural Analysis and Design Lectures

Lecture 40 - Page 13 of 14

C. Isolation Joints: Construction isolation in slabs on grade at all points of contact with vertical surfaces and elsewhere as indicated.

3.15 EXTERIOR SLAB JOINTS

A. Expansion Joints: Locate and install expansion joints as shown on Drawings. Where expansion joints are not shown, locate and install joints a maximum of 20 feet on center in either direction.

B. Contraction Joints: Tool joints during final finishing with edging tool.

C. Isolation Joints: Construct isolation joints in slabs on grade at all points of contact

with vertical surfaces and elsewhere as indicated. 3.16 TOLERANCES

A. Footings 1. Variation of dimensions in plan: plus 2" or minus 1/2". 2. Variation of center from specified center in plan: 2 percent of footing width in

direction of variation, plus or minus 2" maximum variation. 3. Variation of bearing surface from specified elevation: plus or minus 1/2".

B. Anchor Bolts and Sleeves

1. Variation from specified location in plan: plus or minus 1/4". 2. Variation from specified elevation: plus or minus 1/2".

C. Slab on Grade

1. Surface Flatness: FF20 or greater. 2. Surface Levelness: FL17 or greater. 3. Variation from specified elevation: plus or minus 1/4".

D. Stairs

1. Variation in riser: 1/8". 2. Variation in tread: 1/8".

3.17 SLAB SEALERS

A. Interior Exposed Slabs: Apply two coats of hardener after slabs have cured a minimum of 28 days at a rate of 100 square feet/gallon; in accordance with manufacturer’s recommendations.

B. Exterior Exposed Slabs: Apply two coats of Penetrating Exterior Anti-Spalling Sealer

after slabs have cured a minimum of 28 days in accordance with manufacturer’s recommendations.

3.18 REPAIR OF SURFACES

Page 275: Structural Analysis and Design Lectures

Lecture 40 - Page 14 of 14

A. Contractor shall be responsible for cost of repairing defects.

B. Repair defective wall areas with cement mortar or proprietary patching compound, when acceptable to Architect. Cut out honeycomb, rock pockets and voids over 1/2-inch diameter back to solid concrete but in no case to a depth of less than 1 inch. Make edges of cuts perpendicular to concrete surface.

C. Repair defective interior slab areas as follows:

1. Correct flatness and levelness defects by grinding or removal and replacement of slab. Patching of low spots will not be permitted.

2. For cracks less than 1/32 inch, no repairs are required. For cracks greater than 1/32 inch, use crack repair material. For cracks over 1/8 inch, fill crack with oven-dried sand prior to application of crack repair material, as recommended by manufacturer. Contractor also has option to remove and rebuild areas of cracking. Mask cracks to limit crack repair material to crack only.

3. Curling at slab edges which exceeds 1/4 inch when measured with a 10-foot straightedge shall be made level by grinding or planing. Straightedge shall be located with its end at the slab edge, and the space between the straightedge and the slab shall be measured. If curling exceeds 1/4 inch, core drill slab at 3-foot intervals and inject non-shrink grout to fill void beneath slab.

4. Repair edge spalls which occur from shrinkage cracking or from contractor’s operations.

D. Remove and replace all exterior slabs which are cracked or do not properly drain.

END OF SECTION

Page 276: Structural Analysis and Design Lectures

Lecture 41 - Page 1 of 11

Lecture 41 – Metric Metric units are used everywhere in the world EXCEPT the USA. It is based on scientific measurements, not the length of a king’s foot or the weight of a chicken.

Metric Conversion Factors Multiply: By: To Obtain:

inches 25.4 millimeters (mm) inches 0.0254 meters (m) feet 304.8 millimeters (mm) feet 304.8 meters (m)

Length

yards 0.9144 meters (m) in2 645.2 mm2 ft2 92,909 mm2 ft2 0.0929 m2

Area

yd2 0.836 m2 in3 16,387 mm3 ft3 28,317,000 mm3 ft3 0.0283 m3 gallons 0.003785 m3 = 1000 liters

Volume

gallons 3.785 liters Weight pounds 0.454 kilograms (kg)

pounds 4.448 Newtons (N) kips 4448 Newtons (N)

Force

pounds per foot (PLF) 14.594 Newtons per meter (N/m) Lb-In 0.11299 N-m Lb-Ft 1.3559 N-m Kip-Ft 1355.9 N-m Kip-Ft 1.3559 kN-m

Moment

Kip-In 112.99 N-m Unit weight Lb per ft3 (PCF) 0.1571 kN/m3

Lb per in2 (PSI) 6895 Pascals = Pa = N/m2 Lb per in2 (PSI) 6.895 kPa = kilopascals = 1000 Pa Lb per in2 (PSI) 0.0006895 mPa = megapascals = N/mm2 Kips per in2 (KSI) 6895 kPa Kips per in2 (KSI) 6.895 mPa Lb per ft2 (PSF) 47.88 Pa Lb per ft2 (PSF) 0.04788 kPa Kips per ft2 (KSF) 47.88 kPa

Stress (pressure)

Kips per ft2 (KSF) 0.04788 mPa

Page 277: Structural Analysis and Design Lectures

Lecture 41 - Page 2 of 11

Example 1 GIVEN: All road construction projects in New York State have drawings with metric measurements. All metric drawings always use units of mm for everything. (Reminder: 1 m = 1000 mm) REQUIRED: Convert 1500 mm as shown on the drawings into feet/inch/sixteenths.

Use the conversion 1 inch = 25.4 mm

Number of inches = inchpermm

mm__4.25

1500

= 59.055118 inches = 48” + 11.055118” = 4’ + 11.055118” = 4’ + 11” + (0.055118 x 16th)

= 4’ + 11” + ths1688.0

1500 mm = 4’-11 "161

Example 2 GIVEN: The x-sectional area of a W30x211 steel beam = 62.0 in2. REQUIRED: Determine the area of the beam in units of mm2.

Use the conversion 1 inch = 25.4 mm

1 inch x 1 inch = 25.4 mm x 25.4 mm

1 in2 = 645.2 mm2 Number of mm2 = 62.0 in2 x 645.2 mm2 per in2 Area = 40,002 mm2

Page 278: Structural Analysis and Design Lectures

Lecture 41 - Page 3 of 11

Example 3 GIVEN: The tank below. REQUIRED: How many liters are in the tank?

Use the conversion 1 ft3 = 0.0283 m3 Volume = 1781 ft3(0.0283 m3 per ft3) = 50.4 m3 Volume = 50.4 m3(1000 liters per m3) Volume = 50,400 liters

7’-0”

Dia. = 18’-0”

Vol. = )'7()'18(4

= 1781 ft3 = 1781 ft3(7.48 gals per ft3) Vol. = 13324 gal.

Page 279: Structural Analysis and Design Lectures

Lecture 41 - Page 4 of 11

Example 4 GIVEN: An ASTM A325 steel bolt is capable of resisting an allowable shear stress of 30 kips per square inch (KSI) REQUIRED: What is the allowable shear stress for the bolt in units of KPa?

Use the conversions of 1 inch = 25.4 mm 1 Pa = 1 N/m2 1 kPa = 1000 Pa 1 lb = 4.448 N

30 KSI = 2130000

inlb

30 KSI = )0254.0)(0254.0(

)__448.4)(30000(mm

lbperNlb

30 KSI = )00064516.0(

)133440(2mm

N

30 KSI = 206,832,414 N/m2 30 KSI = 206,832,414 Pa 30 KSI = 206,832 kPa

Page 280: Structural Analysis and Design Lectures

Lecture 41 - Page 5 of 11

Metric Loads

All metric loads, forces and derivatives of those are in units of Newtons. Below is a sampling of typical minimum design live loads for buildings:

Minimum Uniformly Distributed Live Loads per ASCE 7-02

Occupancy: Pounds per ft2 kN/m2 (soft metric) Assembly area – fixed seats 60 2.87 Assembly area – movable seats 100 4.79 Balconies - residential 60 2.87 Bowling alleys, poolrooms, rec. areas 75 3.59 Dining rooms and restaurants 100 4.79 Gymnasium 100 4.79 Hospital – operating rooms, labs 60 2.87 Hospital – private rooms 40 1.92 Library – reading room 60 2.87 Library – stack rooms 150 7.18 Office 50 2.40 Residential 40 1.92 Schools - classrooms 40 1.92 Stadium - bleachers 100 4.79 Stores – 1st floor retail 100 4.79

Material Properties Unit Weight: Modulus Of Elasticity (E): Yield Stress (fy): Material: Lb/ft3 kN/m3 Kips/in2 kN/mm2 Kips/in2 N/mm2

Steel – A36 490 77.2 29,000 205 36 248 Steel – A992 490 77.2 29,000 205 50 345 Aluminum 170 26.7 10,000 70 28 190 Concrete (4000 psi) 150 23.6 3,600 25.4 - - Wood - SYP 37 5.8 1,600 11.3 6 42 Earth – sandy 100 15.7 - - - - Water 62.4 9.8 - - - -

Page 281: Structural Analysis and Design Lectures

Lecture 41 - Page 6 of 11

Metric Dimensions

All metric dimensions are in units of millimeters. Below are a few examples of architectural drawings in metric dimensions:

Page 282: Structural Analysis and Design Lectures

Lecture 41 - Page 7 of 11

Page 283: Structural Analysis and Design Lectures

Lecture 41 - Page 8 of 11

Example 5 – LRFD Steel Beam Analysis GIVEN: A simply-supported ASTM A992 steel W18x35 beam is loaded as shown (all loads are factored and includes beam weight). Assume the beam is continuously laterally braced. REQUIRED:

1) Determine the maximum factored moment in units of kN-m. 2) Determine the plastic section modulus, Zx of the beam in units

of mm3. 3) Determine the LRFD design moment of the beam φMn in units of

kN-m. 4) Determine if the beam is adequate in moment.

Step 1 - Determine the maximum factored moment in units of kN-m:

Mmax = 8

2Lwu

= 8

)11)(/3( 2mmkN

Mmax = 45.4 kN-m

Step 2 - Determine the plastic section modulus of the beam in units of mm3:

From LRFD properties W18x35 → Zx = 66.5 in3

Zx = 66.5 in3 x ⎟⎠⎞

⎜⎝⎛

inmmx

inmmx

inmm 4.254.254.25

Zx = 1,089,742 mm3

11 m

w = 3 kN/m

Page 284: Structural Analysis and Design Lectures

Lecture 41 - Page 9 of 11

Step 3 - Determine the LRFD design moment of the beam φMn in units of kN-m:

From LRFD:

φMn = 0.9FyZx

where: Fy = 345 N/mm2 Zx = 1,089,742 mm3

φMn = 0.9(345 N/mm2)(1,089,742 mm3) = 338,360,000 N-mm

= 338,360,000 N-mm x ⎟⎠⎞

⎜⎝⎛

mmmx

NkN

10001000

φMn = 338.4 kN-m

Step 4 - Determine if the beam is adequate in moment:

Since φMn = 338.4 kN-m > Mmax = 45.4 kN-m → beam is OK

See table above

Page 285: Structural Analysis and Design Lectures

Lecture 41 - Page 10 of 11

Example 6 – ACI Concrete Beam Analysis GIVEN: The rectangular concrete beam shown below. All loads are factored and includes beam weight. Use f’c = 25 mPa and 3 – 20 mm diameter bars having fy = 400 mPa. REQUIRED: 1) Determine the ACI 318 factored moment capacity, Mu of the beam in

units of kN-m. 2) Determine the ACI 318 factored moment capacity of the beam in units

of Kip-Feet.

Step 1 – Det. moment capacity Mu in units of kN-m:

Mu = 0.9Asfyd(1 - ⎥⎥⎦

⎢⎢⎣

⎡⎟⎟⎠

⎞⎜⎜⎝

c

yact

ff

'59.0

ρ)

where: As = 3 bars ⎟⎟⎠

⎞⎜⎜⎝

⎛4

)20( 2mmπ

= 942.5 mm2

ρact = bdAs

= )350)(250(

5.942 2

mmmmmm

= 0.0108

250

350

Page 286: Structural Analysis and Design Lectures

Lecture 41 - Page 11 of 11

Mu = 0.9Asfyd(1 - ⎥⎥⎦

⎢⎢⎣

⎡⎟⎟⎠

⎞⎜⎜⎝

c

yact

ff

'59.0

ρ)

= 0.9(942.5 mm2)(400 N/mm2)(350 mm)(1 - ⎥⎦

⎤⎢⎣

⎡⎟⎟⎠

⎞⎜⎜⎝

⎛2

2

/25/400)(0108.0(59.0

mmNmmN )

= 106,640,000 N-mm

= 106,640,000 N-mm x ⎟⎠⎞

⎜⎝⎛

mmmx

NkN

10001000

Mu = 106.6 kN-m

Step 2 – Det. moment capacity Mu in units of Kip-Feet:

Mu = 106.6 kN-m x ⎟⎠⎞

⎜⎝⎛

−−

mkNFeetKip

3559.1

Mu = 78.6 Kip-Feet

See conversion table above

Page 287: Structural Analysis and Design Lectures

Lecture 5 - Page 1 of 9

Lecture 5 – Beams – Design for Shear & Deflection Steel beams are usually designed solely on the basis of moment. This means that bending stresses are the critical design factor. However, under certain circumstances, shear and deflection must also be checked. 1. Design for Shear

Shear in steel beams generally does not control the design EXCEPT in the following two situations:

• Reduced beam cross-sectional area, as with “coped” beams

• Very heavy loads on short-span beam

Short span

Reduced Shear plane

Normal beam

Shear plane

Coped beam

Very heavy loads

Page 288: Structural Analysis and Design Lectures

Lecture 5 - Page 2 of 9

Shear in steel beams is assumed to be carried entirely by the area of the web, Aw: Design for shear is dictated in AISC Spec. G p. 16.1-64 as follows:

LRFD Factored Design shear strength = φvVn

ASD Service Allowable shear strength = v

nVΩ

where: φv = 1.00 (LRFD) Ωv = 1.50 (ASD) Vn = nominal shear strength = 0.6FyAwCv

Aw = area of web (see sketch above) = twd Cv = Web shear coefficient = 1.0 for webs of rolled “I” – shaped shapes (Conservative) = see AISC Eq. G2-3, G2-4 and G2-5 p. 16.1-65 for other conditions

d tw

Beam X-Sect Aw = Shear area in normal beam (shaded)

Aw = Shear area in coped beam (shaded)

Page 289: Structural Analysis and Design Lectures

Lecture 5 - Page 3 of 9

Example 1 (LRFD) GIVEN: A W14x26 A992 steel beam. REQUIRED: Determine the FACTORED design shear strength, φvVn for the beam.

Step 1 – Determine area of web, Aw:

Aw = twd = 0.255 in(13.9 in) = 3.54 in2

Step 2 – Determine FACTORED design shear strength:

φvVn = 1.00(0.6FyAw)Cv = 1.00(0.6(50 KSI)(3.54 in2)1.0) φvVn = 106.2 KIPS

(NOTE: The values of φvVn can be found directly in the “Maximum Total Factored Uniform Load” Table 3-6 AISC p. 3-67)

d tw

Page 290: Structural Analysis and Design Lectures

Lecture 5 - Page 4 of 9

Example 2 (ASD) GIVEN: The W12x30 A992 steel beam has a 4” cope and has the SERVICE load as shown below. Disregard beam weight. REQUIRED: 1) Determine if the beam is acceptable on the basis of shear at the coped

end. 2) Determine if the beam is acceptable on the basis of shear at the

location of the point load.

W12x30

R1 R2

Page 291: Structural Analysis and Design Lectures

Lecture 5 - Page 5 of 9

Step 1 – Determine the reaction at the left support R1:

R1 = '10

)'7(120KIPS

= 84 KIPS

Step 2 – Determine ALLOWABLE shear strength in coped web at R1:

v

nVΩ

= 50.1

6.0 vwy CAF

Aw = Area of web = twh From properties, tw = web thickness = 0.260 in. d = 12.3 in. h = d – cope = 12.3” – 4” = 8.3” Aw = twh = 0.260”(8.3”) = 2.16 in2

v

nVΩ

= 50.1

)0.1)(16.2(50(6.0 2inKSI

v

nVΩ

= 43.2 KIPS < 84 KIPS → UNACCEPTABLE

h = d - cope d tw

Page 292: Structural Analysis and Design Lectures

Lecture 5 - Page 6 of 9

Step 3 – Determine ALLOWABLE shear strength at point of load:

Since the beam is not coped at this location, the design shear

strength v

nVΩ

can be found from AISC Table 3-6 p. 3-71.

v

nVΩ

= 64.2 KIPS < 120 KIPS → UNACCEPTABLE

(Note: This example looks ONLY at shear. Very high loads also require a detailed look at connections, which will be investigated later)

Possible Fixes for High Shear:

By modifying any of the variables in the design shear equation, the capacity may be increased. These include:

• Using a higher grade of steel (increase Fy) • Use a bigger beam (increase Aw) • Weld additional plates to the web (increase Aw)

New plate welded to web of beam

Page 293: Structural Analysis and Design Lectures

Lecture 5 - Page 7 of 9

2. Design for Deflection

Building codes (such as the IBC) require that deflections in beams be held to a minimum for occupancy comfort as well as to reduce likelihood of cracking ceiling finishes such as plaster. It is considered to be a “serviceability” check. Allowable deflection limits are dictated by the codes, such as L/360 of the span.

Actual deflection is calculated using SERVICE LOADS in the formulas given in the AISC p. 3-208 thru 3-226. These actual deflections are then compared against the allowable deflection.

The following allowable deflection limits for steel construction are used by the IBC:

Construction Live Load Snow or Wind

Roof member supporting plaster ceiling L/360 L/360 Roof member supporting nonplaster ceiling L/240 L/240 Roof member supporting no ceiling L/180 L/180 Floor members L/360 -

It should be noted that the above-noted allowable deflections are minimums. Architects and engineers often reduce the deflection limit to L/480 or even L/540 to ensure that floors are not “bouncy.”

Page 294: Structural Analysis and Design Lectures

Lecture 5 - Page 8 of 9

Example 3 GIVEN: The floor framing plan below. The total superimposed service dead load = 86 PSF (not including beam weight) and the service live load = 125 PSF. REQUIRED: Determine the maximum actual mid-span deflection and compare with a Live load limit = L/480 and a Dead load + Live load limit = L/240 on the W18x35 steel beam.

Step 1 – Determine the actual max. deflection considering Live load only:

From AISC p. 3-211, the maximum deflection formula is:

∆max = EI

wL3845 4

w = uniform live load on beam = 8’(125 PSF) = 1000 PLF

∆max = )510)(29000000(384

)/"12'25(12

10005

4

4

inPSI

ftxPLF⎟⎠⎞

⎜⎝⎛

= 0.59 in.

do do

W18

x35

beam

W24x62 girder

25’-0”

4@8’-0” = 32’-0”

Page 295: Structural Analysis and Design Lectures

Lecture 5 - Page 9 of 9

Step 2 – Determine allowable deflection of L/480 for live load only:

∆allow = 480L

= 480

)/"12("0'25 ft−

= 0.625 in. Since ∆allow = 0.625” > 0.59” → beam is acceptable

Step 3 – Determine max. defl. considering Deal load + Live load:

∆max = EI

wL3845 4

w = uniform dead load + live load on beam = 8’(125 PSF + 86 PSF) + 35 PLF = 1723 PLF

∆max = )510)(29000000(384

)/"12'25(12

17235

4

4

inPSI

ftxPLF⎟⎠⎞

⎜⎝⎛

= 1.02 in.

Step 4 – Determine allowable deflection of L/240 for LL + DL:

∆allow = 240L

= 240

)/"12("0'25 ft−

= 1.25 in. Since ∆allow = 1.25” > 1.02” → beam is acceptable

Page 296: Structural Analysis and Design Lectures

Lecture 6 – Plate Girders A plate girder is a built-up beam comprised of plates welded together in the shape of an “I.” Usually they are used in situations when standard W shapes are not adequate. They are fabricated in a shop and are typically much more expensive than rolled shapes, but often cheaper than trusses. Typically, the depth of plate girders range from about 1/10 to 1/12 of the span. Plate girders are designed in AISC Spec. chapter G p. 16.1-37 and 16.1-107. The design of a plate girder will be explained in the example below. Example GIVEN: The continuously laterally-braced welded unstiffened plate girder below. All loads shown are FACTORED and includes anticipated girder weight. Use Fy = 50 KSI for web and flanges. REQUIRED: Design the plate girder.

R1 R2

wu = 10 KLF

75’-0”

Page 297: Structural Analysis and Design Lectures

Step 1 – Determine maximum factored moment, Mu and shear, Vu:

Mu = 8

2Lwu

= 8

)'75)(10( 2KLF

Mu = 7031 KIP-FT

Vu = R1 = R2 = 2

Lwu

= 2

)'75)(10( KLF

Vu = 375 KIPS

Step 2 – Determine preliminary depth of girder:

Assume depth = 10

Span

= 10

)/"12("0'75 ft−

= 90”

Step 3 – Determine height of web:

Assume the flanges are approximately 1½” thick, so:

h = depth – 2(Flange thickness) = 90” – 2(1½”) h = 87”

depth h = web ht.

Page 298: Structural Analysis and Design Lectures

Step 4 – Determine web thickness assuming girder is unstiffened (i.e., no web stiffeners):

From AISC Spec F2 p. 16.1-35 - 36:

If 3.07 260≤<wy th

FE

then design shear = φvVn

Vn = Aw

2

52.4

wth

E

Determine absolute smallest tw assuming 260≤wth

:

tw = 260

"87

= 0.33” Try tw = 3/8”:

Vn = Aw

2

52.4

wth

E

= (87” x 3/8”)

2

"8/3"87

)29000(52.4 KSI

= 79.5 KIPS < 375 KIPS → NO GOOD Try tw = 5/8”: Vn = 368 KIPS < 375 KIPS → NO GOOD Try tw = ¾”: Vn = 636 KIPS > 375 KIPS → OK Use 87” x ¾” web

Aw = Area of web

Page 299: Structural Analysis and Design Lectures

Step 5 – Preliminary flange design:

Area of flange = A f ≈ hF

M

y

u

≈ )"87)(50(

)/"12(7031KSI

ftFTKIP −

≈ 19.4 in2 TRY 1½” x 14” flange (Area of flange = 21 in2 > 19.4 in2)

Step 6 – Check tension (bottom) flange for yield strength (AISC 16.1-107:

Design strength for tension flange = φbMn

where: φb = 0.90 Mn = SxtReFy

Sxt = b

total

yI

Itotal = 23

))((212 bfw yAht

+

= 223

)"25.44)(21(212

)87("75.0in+

= 123,395 in4

Sxt = "25.44

123395 4in

= 2788.6 in3 Re = Hybrid girder factor = 1.0 if web & flange steel Fy are the same

φbMn = 0.9SxtReFy = 0.9(2788.6 in3)(1.0)(50 KSI) = 125,487 KIP-IN = 10,457 KIP-FT > Mu = 7031 KIP -FT → OK

yb

Yt

87”

Af = Area of flange

Page 300: Structural Analysis and Design Lectures

Step 7 – Check compression (top) flange for buckling (AISC p. 16.1-108):

The design strength for compression flange buckling = φbMn

where: φb = 0.90 Mn = SxcRPGReFy

Sxc = Sxt = 2788.6 in3

RPG = 1 - 0.170.53001200

+ yw

c

r

r

FE

th

aa

ar = ratio of web area to comp. flange area (< 10)

= f

w

AA

= 221

)"75.0)("87(in

= 3.1

hc = 2h

= 2

"87

= 43.5”

RPG = 1 - 0.150

2900070.5

"75.0"5.43

)1.3(30012001.3

+

= 1.11 → use 1.0 Re = 1.0

φbMn = 0.9SxcRPGReFy = 0.9(2788.6 in3)(1.0)(1.0)(50 KSI) = 125,487 KIP -IN = 10,457 KIP -FT > Mu = 7031 KIP-FT → OK

Page 301: Structural Analysis and Design Lectures

Step 8 – Summary sketch:

1½” Plate

14”

90”

1½” Plate

¾” Plate

Page 302: Structural Analysis and Design Lectures

Lecture 7 - Page 1 of 10

Lecture 7 – Composite Steel Beams Steel beams are usually used to carry a metal deck-supported concrete slab. In non-composite construction, the beam does NOT interact structurally with the slab – the slab is simply dead weight. This is because the slab is not adequately bonded to the beam.

Non-Composite Construction

The word “composite” means 2 or more different materials. In composite construction, the slab is adequately bonded to the steel beam by means of headed “shear studs” resulting in a composite beam. The concrete acts like a large “flange” in compression, while a much greater portion of the steel beam acts in tension. The result is a VERY efficient beam – as much as 40% to 60% lighter weight steel than non-composite.

Composite Construction

Headed shear studs welded thru metal deck to beam flange

Page 303: Structural Analysis and Design Lectures

Lecture 7 - Page 2 of 10

Notice that the neutral axis (N.A.) in the non-composite beam is located in the middle of the section. This indicates that half of the beam section is in tension and half is in compression. In the composite section, the compression is carried ENTIRELY by the concrete, while the tension is carried by the beam. Composite Design per LRFD

• AISC Spec Ch. I3 (p. 16.1-83) • AISC Part 3 Table 3-19 (p. 3-156 thru 189) • AISC Part 3 Table 3-21 (p. 3-207)

From a side view, a composite beam looks like the following:

Ycon

Ten.

Comp.

N.A

Non-Composite Section Composite Section

N.A

Ten.

Comp.

d

Shear stud

Concrete Metal Deck

Beam

Page 304: Structural Analysis and Design Lectures

Lecture 7 - Page 3 of 10

For LRFD composite design, the following terms are used:

where: b = Effective slab width (from AISC Spec. p. 16.1-83)

8

BeamSpan

= smaller of 2

gBeamSpacin

Distance to edge of slab

a = Effective concrete thickness ≈ 2” for initial trial size

= bf

FA

c

ys

'85.0

As = Cross-sectional area of beam

= from properties f’c = Specified concrete compressive strength = 4 KSI (usually)

Y2 = Ycon - 2a

Y2

b = Effective slab width

a Ycon

Page 305: Structural Analysis and Design Lectures

Lecture 7 - Page 4 of 10

The best way to see how the design of a composite beam is accomplished is thru an example problem:

Example 1 (LRFD) GIVEN: A floor structure using A992 steel beams and the following superimposed SERVICE loads:

• Service live load = 75 PSF • Service dead load (not incl. beam weight) = 63 PSF

In addition, use ¾” diameter shear studs, 4” concrete over 1½” metal deck and normal weight concrete f’c = 4000 PSI.

REQUIRED: Design the lightest weight W14 beam “A” using composite construction.

Step 1 – Determine factored maximum moment Mu:

wu = 1.2D + 1.6L = 1.2[8’(63 PSF + 30 PLF)] + 1.6[8’(75 PSF)] = 1601 PLF = 1.6 KLF

Mu = 8

2Lwu

= 8

)'30(6.1 2KLF

= 180 KIP-FT

Beam “A”

30’-0”

3@8’

-0” =

24’

-0”

Assumed beam weight

Page 306: Structural Analysis and Design Lectures

Lecture 7 - Page 5 of 10

Step 2 – Determine “Trial” approx. beam weight:

Approx. Beam weight =

⎥⎥⎥⎥

⎢⎢⎢⎢

⎟⎠⎞

⎜⎝⎛ −+

2285.0

)/"12(4.3

aYdF

ftM

cony

u

Assume d = 14” (since using W14) a = 2” Ycon = 4”

Approx. Beam weight =

⎥⎥⎥⎥

⎢⎢⎢⎢

⎟⎠⎞

⎜⎝⎛ −+

2"2"4

2"14)50(85.0

)/"12(1804.3KSI

ftFTKIP

= 17.28 PLF

From AISC Table 3-19 p. 3-184 → TRY W14x22

Step 3 – Determine concrete flange force, ΣQn:

ΣQn = AsFy

where: As = Area of beam = 6.49 in2 (from properties for W14x22)

ΣQn = (6.49 in2)(50 KSI) = 324.5 KIPS (NOTE: From AISC Table 3-19 p. 3-184 the value of ΣQn can be found looking at Y1 = 0.000” → ΣQn = 325 KIPS)

Page 307: Structural Analysis and Design Lectures

Lecture 7 - Page 6 of 10

Step 4 – Determine effective concrete slab width, b:

8

BeamSpan = 8

)/"12('30 ft = 45” ← USE

b = smaller of 2

gBeamSpacin = 2

)/"12('8 ft = 48”

Distance to edge of slab = N/A

Step 5 – Determine Y2 for usage in AISC Table 3-19 p. 3-184:

Y2 = Ycon - 2a

where a = bf

FA

c

ys

'85.0

= )"45)(4(85.0

325KSIKIPS

= 2.12”

Y2 = 4” - 2

"12.2

= 2.94” Use Y2 = 3”

Step 6 – Determine required beam size from AISC Table 3-19: W14x22 Y2 = 3” ΣQn = 325 KIPS

Design strength in flexure = 240 KIP-FT > 180 KIP-FT

See Table 3-19 Below

Page 308: Structural Analysis and Design Lectures

Lecture 7 - Page 7 of 10

Page 3-184

Page 309: Structural Analysis and Design Lectures

Lecture 7 - Page 8 of 10

Step 7 – Determine number of ¾” shear studs required:

Number of studs required = )(

2

studn

n

QQΣ

where: ΣQn = AsFy = 325 KIPS Qn(stud) = Nominal horz. shear strength of stud = From AISC Table 3-21 p. 3-207 = 17.2 KIPS

Number of studs required = studperKIPS

KIPS__2.17)325(2

= 37.8 studs

Use 38 – ¾” dia. studs

Step 8 – Check beam shear at coped end:

Assume beam is coped 1½”

Factored beam end reaction = 2

)'30(6.1 KLF

= 24 KIPS

13.7”

1½”

W14x22 beam

Girder

Normal wt. conc. f’c = 4 KSI Deck perpendicular 1 weak stud per rib

Page 310: Structural Analysis and Design Lectures

Lecture 7 - Page 9 of 10

Set up a ratio of φvVn for the full W14x22 beam section to the reduced beam section:

depthducedV

depthFullV nvnv

_Re_φφ

=

From AISC p. 3-67 → φvVn = 94.8 KIPS for full depth

)"5.1"7.13("7.138.94

−= nvVKIPS φ

φvVn = 84.4 KIPS > 24 KIPS for reduced section OK

Step 9 – Draw summary sketch:

30’-0” span

W14x22 A992 beam

38 – ¾” Dia. shear studs welded thru metal deck along center of beam spaced evenly along length of beam

Page 311: Structural Analysis and Design Lectures

Lecture 7 - Page 10 of 10

Example 2 GIVEN: The beam from Example 1. All loads and other conditions are the same. REQUIRED: Design lightest weight W14 Beam “A” using NON-COMPOSITE construction.

Step 1 – Determine Mu:

Mu = 180 KIP-FT

Step 2 – Design lightest weight W14 beam:

From AISC Zx Table p. 3-18:

Use W14x34 → φbMpx = 205 KIP-FT > 180 KIP-FT

(Note: The W14x34 non-composite beam is 55% heavier than a W14x22 beam that is used as a composite beam.)

Page 312: Structural Analysis and Design Lectures

Lecture 8 - Page 1 of 9

Lecture 8 – Compression members – Axially loaded Compression members are not limited to just columns. Trusses and bracing members may also be designed as compression members. We will look at compression members subject to axial compression ONLY (i.e., no other stresses). Essentially, this means that loads act thru the centroid of the member along the longitudinal length of the member as shown below:

Compression members are designed in accordance with:

• AISC Spec. Chapter E p. 16.1-32 • AISC Part 4

Axial Load

Page 313: Structural Analysis and Design Lectures

Lecture 8 - Page 2 of 9

A compression member’s strength is GREATLY determined by its unbraced length, referred to its “Effective Length” KL

where: K = Effective length factor = see AISC p. 16.1-240 = usually 1.0 assuming ends are pinned L = Distance between lateral bracing, inches.

The design strength of an axially-loaded compression member = φcPn LRFD

= c

nPΩ

ASD

where: φc = 0.90 Ωc = 1.67 Pn = nominal compressive strength = AgFcr

Ag = Gross cross-sectional area, in2 = From properties Fcr = Elastic critical buckling stress

= yFF

Fe

y

⎟⎟

⎜⎜

⎛658.0 IF

yFE

rKL 71.4min

= 0.877Fe IF yF

ErKL 71.4min

>

K = From AISC p. 16.1-240 L = Unbraced length, inches rmin = Minimum radius of gyration (from properties) E = Modulus of elasticity = 29,000 KSI

Fe = 2

min

2

⎟⎟⎠

⎞⎜⎜⎝

⎛rKL

Eπ The limiting slenderness ratio 200

min

≤rKL

Page 314: Structural Analysis and Design Lectures

Lecture 8 - Page 3 of 9

Example 1 (LRFD) GIVEN: A W12x50 using A992 is used as a column in a building. It is laterally braced at 14’-0” about both the X axis and Y axis. Use “K” = 1.0. REQUIRED: Determine the design axial compressive strength, φcPn for the column.

Step 1 – Determine if yF

ErKL 71.4min

≤ :

minrKL =

inftX

96.1)/"12"0'14)(0.1( −

= 85.7

yFE71.4 =

KSIKSI

502900071.4

= 113.4

Therefore, yF

ErKL 71.4min

Step 2 – Determine Fe:

Fe = 2

min

2

⎟⎟⎠

⎞⎜⎜⎝

⎛rKL

= ( )2

2

7.85)29000( KSIπ

= 38.97 KSI

Page 315: Structural Analysis and Design Lectures

Lecture 8 - Page 4 of 9

Step 3 – Determine Fcr:

Fcr = yFF

Fe

y

⎟⎟

⎜⎜

⎛658.0

= KSIksiksi

50658.0 97.3850

⎟⎟⎠

⎞⎜⎜⎝

= 29.2 KSI Step 4 – Determine design axial compressive strength φcPn:

φcPn = 0.90(AgFcr) = 0.90(14.6 in2)(29.2 KSI) φcPn = 383.7 KIPS

Page 316: Structural Analysis and Design Lectures

Lecture 8 - Page 5 of 9

Example 2 (LRFD) GIVEN: The truss shown below uses single A36 steel L6x4x½ angle for all members. All loads shown are factored. REQUIRED: Determine if the truss member “A” is adequate based on axial compression.

Step 1 – Determine force in Member “A”:

Length of member “A” = 22 )'6()'10( + = 11.66 feet = 139.9 inches

Force in member “A” = ⎟⎠⎞

⎜⎝⎛

'6'66.1115KIPS

= 29.2 KIPS

Step 2 – Determine slenderness factor (KL/rmin):

"864.0)"9.139(0.1

min

=rKL

= 161.9 < 200 → OK

10’-0” 10’-0”

6’-0”

30 KIPS

L6x4x½ Member “A”

Page 317: Structural Analysis and Design Lectures

Lecture 8 - Page 6 of 9

Step 3 – Determine Fcr from AISC Table 4-22 p. 4-322:

At Fy = 36 KSI and 161min

=rKL → φcFcr = 8.72 KSI

At Fy = 36 KSI and 162min

=rKL → φcFcr = 8.61 KSI

Page 4-322

Interpolating at 9.161min

=rKL

→ φcFcr = 8.62 KSI

Page 318: Structural Analysis and Design Lectures

Lecture 8 - Page 7 of 9

Step 4 – Determine design compressive strength φcPn:

φcPn = φc (AgFcr) = Ag(φcFcr) = 4.75 in2(8.62 KSI) φcPn = 40.9 KIPS > 29.2 KIPS → It is acceptable

Page 319: Structural Analysis and Design Lectures

Lecture 8 - Page 8 of 9

Example 3 (LRFD) GIVEN: A column has an unbraced length = 12’-0” and is subject to a factored axial load = 450 KIPS. Use “K” = 1.0. REQUIRED: 1) Design the lightest weight A992 W shape using AISC Table 4-1. 2) Design the lightest weight Square HSS shape using AISC Table 4-4. 3) Design the lightest weight Round HSS shape using AISC Table 4-5.

Step 1 – Design lightest W shape:

From AISC Table 4-1, the following possibilities may be used:

Shape Weight (PLF) KL Design strength φcPn (KIPS) W8x58 58 12’ 545

W10x49 49 12’ 513 W12x53 53 12’ 547 W14x53 53 12’ 465

Use W10x49 → φcPn = 513 KIPS > 450 KIPS

Step 2 – Design lightest square HSS shape: From AISC Table 4-4, the following possibilities may be used:

Shape Weight (PLF) KL Design strength φcPn (KIPS) HSS8x8x½ 48.7 12’ 479

HSS10x10x3/8 47.8 12’ 497 HSS12x12x5/16 48.8 12’ 505

Use HSS10x10x3/8 → φcPn = 497 KIPS > 450 KIPS

Step 3 – Design lightest Round HSS shape:

From AISC Table 4-5, the following possibilities may be used:

Shape Weight (PLF) KL Design strength φcPn (KIPS) HSS10.000x0.500 50.8 12’ 471 HSS10.750x0.500 54.8 12’ 516 HSS12.750x0.375 49.6 12’ 481

Use HSS12.750x0.375 → φcPn = 481 KIPS > 450 KIPS

Page 320: Structural Analysis and Design Lectures

Lecture 8 - Page 9 of 9

Example 4 (LRFD) GIVEN: Same as Example 1. A W12x50 using A992 is used as a column in a building. It is laterally braced at 14’-0” about both the X axis and Y axis. Use “K” = 1.0. REQUIRED: Determine the design axial compressive strength, φcPn for the column using AISC Table 4-1.

From Table above, φcPn = 384 Kips (same as Example 1)

Page 321: Structural Analysis and Design Lectures

Lecture 9 - Page 1 of 11

Lecture 9 – Compression Members – Combined compression & Bending In Lecture 8, we discussed axially-loaded columns and compression members loaded through the centroid. This is referred to as “concentric” loading. In reality, columns and compression members are usually loaded off the centroid referred to as “eccentric” loading, i.e., moments applied.

Eccentrically loaded columns are most common in corners or in asymmetrical loadings. Equally-loaded beam end reactions about the same axis offset each other while un-equal loads create moments as shown below:

32 K

32

K

20 K 20 K

e P P

Concentric Loading (no moment) Eccentric Loading (applied moment)

M = 0 M = Pe

Concentrically Loaded Column

32 K

20 K

Eccentrically Loaded Column

Beam end reaction

Page 322: Structural Analysis and Design Lectures

Lecture 9 - Page 2 of 11

The LRFD addresses columns and compression members under combined compression and bending in the following:

• AISC Spec Chapter H (p. 16.1-38) • AISC Part 6

In particular, AISC Spec H1 (p. 16.1-70) dictates the following interaction formulas:

a) For 2.0≥c

r

PP

0.198

≤⎟⎟⎠

⎞⎜⎜⎝

⎛++

cy

ry

cx

rx

c

r

MM

MM

PP

b) For 2.0<c

r

PP

= 0.12

≤⎟⎟⎠

⎞⎜⎜⎝

⎛++

cy

ry

cx

rx

c

r

MM

MM

PP

where: Pr = Applied axial compressive load, KIPS Pc = Available axial compressive strength of column, KIPS = φcPn where φc = 0.90 LRFD

= c

nPΩ

where Ωc = 1.67 ASD

Mrx = Applied Moment about strong axis, KIP-FT

= Pe Mcx = Available moment strength about strong axis, KIP-FT = from AISC Beam Design Moments Chart Mry = Applied Moment about weak axis, KIP-FT = Pe Mcy = Available moment strength about weak axis, KIP-FT = from AISC Spec Chapter F

Pn = FcrAg (see Lect. 8)

Page 323: Structural Analysis and Design Lectures

Lecture 9 - Page 3 of 11

As an alternative to the above equations, AISC Table 6-1 (p. 6-5 thru 6-95) can be used. In particular the interaction formulas from above may be re-written as:

a) For 2.0≥c

r

PP

pPr + bxMrx + byMry < 1.0

b) For 2.0<c

r

PP

21 pPr +

89 (bxMrx + byMry) < 1.0

where: bx by

p Example 1 (LRFD) GIVEN: A W14x68 A992 steel corner column for a two-story building has an unbraced height = 12’-0” and is subjected to the FACTORED loads applied from beam end reactions as shown in plan view below. REQUIRED: Determine if the column section is adequate under combined compression and bending.

= Formulas from AISC Table 6-1 page 6-3

146

K

180 K

See AISC p. 6-4

= From AISC Table 6-1 p. 6-5 thru 6-95

Page 324: Structural Analysis and Design Lectures

Lecture 9 - Page 4 of 11

Step 1 – Determine total applied factored axial load Pr:

Pr = Σ(Beam end reactions) = 180 KIPS + 146 KIPS = 326 KIPS

Step 2 – Determine W14x68 column axial design strength, φcPn:

From AISC Column Load Table 4-1 on p. 4-14:

At KL = 12’-0” → Pc = φcPn = 700 KIPS

Step 3 – Determine applied factored moment about strong axis, Mrx:

Workable Gages in Angle Legs, in.

Leg: 8 7 6 5 4 3½ 3 2½ 2 1¾ 1½ 1⅜ 1¼ 1 g 4½ 4 3½ 3 2½ 2 1¾ 1⅜ 1⅛ 1 ⅞ ⅞ ¾ ⅝ g1 3 2½ 2¼ 2 g2 3 3 2½ 1¾

g1

g2

g

d = 14+”

e

P = 146 KIPS

146

K

L4x4x¼ connection angle

is equivalent to →

Beam

W14x68 col.

Page 325: Structural Analysis and Design Lectures

Lecture 9 - Page 5 of 11

Mrx = Pe where: P = Beam end reaction e = eccentricity = ½(d) + angle gage = ½(14”) + 2½”

= 9½”

Mrx = (146 KIPS) ⎟⎟⎠

⎞⎜⎜⎝

⎛ft/"12

"5.9

= 115.6 KIP-FT

Step 4 – Determine factored moment about weak axis, Muy:

Mry = Pe where: P = Beam end reaction e = eccentricity = ½(tw) + angle gage = ½(½”)+ 2½”

= 2¾”

Mry = (180 KIPS) ⎟⎟⎠

⎞⎜⎜⎝

⎛ft/"12"75.2

= 41.2 KIP-FT

P = 180 KIPS

e 180 K

L4x4x¼ connection angle

Beam is equivalent to →

From AISC p. 1-46

Column web tw

From AISC p. 1-46 and above

Since L4x4 angle

Page 326: Structural Analysis and Design Lectures

Lecture 9 - Page 6 of 11

Step 5 – Determine column adequacy using interaction formula:

Check 2.0≥c

r

PP

c

r

PP =

KIPSKIPS

700326

= 0.47 > 0.20

Then: pPr + bxMrx + byMry < 1.0 From AISC p. 6-71 for W14x68 @ KL = 12’:

bx = 2.19 x 10-3 (KIP-FT)-1 by = 6.42 x 10-3 (KIP-FT)-1 p = 1.43 x 10-3 (KIPS)-1

See Below

Page 327: Structural Analysis and Design Lectures

Lecture 9 - Page 7 of 11

Page 328: Structural Analysis and Design Lectures

Lecture 9 - Page 8 of 11

Check: pPr + bxMrx + byMry < 1.0 1.43 x 10-3(326 KIPS) + 2.19 x 10-3(115.6 KIP-FT) + 6.42 x 10-3(41.2 KIP-FT) < 1.0 = 0.47 + 0.25 + 0.26 = 0.98 < 1.0 → ACCEPTABLE Use W14x68

Page 329: Structural Analysis and Design Lectures

Lecture 9 - Page 9 of 11

Example 2 (LRFD) GIVEN: A 5-story interior column with non-symmetric loads as shown typically below. Use KL = 14’-0”. Connection angles are L3x3x¼. REQUIRED: Design the lightest weight W12 column for the lowest level.

Step 1 – Determine TOTAL applied factored axial load Pr:

Pr = 4 floors(34 KIPS + 18 KIPS + 14 KIPS + 28 KIPS) = 376 KIPS

Step 2 – Determine applied factored moment about strong axis, Mrx:

Mrx = Peqe Peq = equivalent difference in load along axis = 34 KIPS – 18 KIPS = 16 KIPS

e = eccentricity = ½(d) + angle gage = ½(12”) + 1¾”

= 7¾”

Mrx = 16 KIPS ⎟⎟⎠

⎞⎜⎜⎝

⎛ft/"12"75.7

= 10.3 KIP-FT

34 K

18

K

14 K 28 K

Typical column loading (4 framed levels)

Page 330: Structural Analysis and Design Lectures

Lecture 9 - Page 10 of 11

Step 3 – Determine applied factored moment about weak axis, Mry:

Mry = Peqe Peq = equivalent difference in load along axis = 28 KIPS – 14 KIPS = 14 KIPS

e = eccentricity = ½(tw) + angle gage = ½(½”) + 1¾”

= 2”

Mry = 14 KIPS ⎟⎟⎠

⎞⎜⎜⎝

⎛ft/"12

"2

= 2.3 KIP-FT

Step 4 – Select “Trial” W12 column size:

Referring to AISC Table 4-1 p. 4-18: @ KL = 14’ → Try W12x50 φcPn = Pc = 443 KIPS > 376 KIPS

Step 5 – Determine column adequacy using interaction formula:

Check 2.0≥c

r

PP

c

r

PP =

KIPSKIPS

443376

= 0.85 > 0.20

Then: pPr + bxMrx + byMry < 1.0

Page 331: Structural Analysis and Design Lectures

Lecture 9 - Page 11 of 11

From AISC p. 6-81 for W12x50 @ KL = 14’:

bx = 3.91 x 10-3 (KIP-FT)-1 by = 11.1 x 10-3 (KIP-FT)-1 p = 2.61 x 10-3 (KIPS)-1

Check:

pPr + bxMrx + byMry < 1.0

2.61 x 10-3(376 KIPS) + 3.91 x 10-3(10.3 KIP-FT) + 11.1 x 10-3(2.3 KIP-FT) < 1.0 = 0.98 + 0.04 + 0.03 = 1.05 > 1.0 → Unacceptable cannot use W12x50

→ (NOTE: A W12x53 column is acceptable since 0.80 < 1.0)

Page 332: Structural Analysis and Design Lectures

Lecture 3 – Page 1 of 10

Lecture 3 – Flexural Members Flexural members are those that experience primarily bending stresses, such as beams. A typical rectangular reinforced concrete beam is shown below:

Concrete cover = ¾” 2” as per ACI reqmts.

Dep

th to

ste

el “d

Hei

ght

“h”

Width “b”

Section A-A

Hanger bars (usually #4 or #5 bars)

Stirrup bars (used to prevent diag. tension cracks) spaced at d/2+ apart

Tension bars “As”

Page 333: Structural Analysis and Design Lectures

Lecture 3 – Page 2 of 10

Sometimes, 2 (or more) rows of main tension bars are necessary. It is important to provide minimum adequate cover around all reinforcing bars so that these bars can properly bond with the concrete. ACI 318 dictates that the minimum spacing between bars is 1.5 times the maximum concrete aggregate size. Typical concrete batches use a maximum aggregate size of ¾” diameter, so then the minimum bar spacing = 1.5(¾”) = 1⅛”. Below is a sketch of a typical concrete beam with 2 rows of tension bars:

Min. bar spacing

Min. bar spacing

Dep

th to

cen

troid

of s

teel

“d”

Hei

ght

“h”

Tension bars “As”

Page 334: Structural Analysis and Design Lectures

Lecture 3 – Page 3 of 10

As = Total cross-sectional area of all tension bars, in2 d = depth to center of tension bars, inches = h – (concrete cover) – (stirrup bar dia.) – ½(tension bar dia.)

fy = yield stress of reinforcing bars = 60 KSI for ASTM A615 Grade 60 bars = 40 KSI for ASTM A615 Grade 40 bars actual = Rho actual = actual ratio of tension steel to effective concrete area

= bdAs

min = Rho minimum = minimum allowable ratio of tension steel per ACI 318

= yf

200 where fy = PSI

Page 335: Structural Analysis and Design Lectures

Lecture 3 – Page 4 of 10

Example 1 GIVEN: A rectangular concrete beam is similar to the one shown above. Use the following:

Height h = 20” Width b = 12” Concrete f’c = 4000 PSI Concrete cover = ¾” All bars are A615 – Grade 60 (fy = 60 KSI) Stirrup bar = #3 4 - #7 Tension bars

REQUIRED: 1) Determine total area of tension bars, As. 2) Determine depth to center of tension bars, d.

3) Determine actual = bdAs where min =

yf200 and state if it is acceptable.

Step 1 – Determine area of tension bars, As:

As = 4 bars(0.60 in2 per #7 bar) As = 2.40 in2

See Lect. 1 notes

Dep

th to

ste

el “d

Hei

ght

“h” =

20”

Width “b” = 12”

4 - #7 tension bars

#3 Stirrup bars

Page 336: Structural Analysis and Design Lectures

Lecture 3 – Page 5 of 10

Step 2 – Determine depth to tension bars, “d”:

d = depth to center of tension bars, inches = h – (concrete cover) – (stirrup bar dia.) – ½(tension bar dia.) = 20” – ¾” – ⅜” – ½(⅞”) d = 18.44”

Step 3 – Determine actual and min :

actual = bdAs

= )"44.18)("12(

40.2 2in

actual = 0.0108 Since actual > min beam is acceptable

min = yf

200

= PSI60000

200

min = 0.0033

Page 337: Structural Analysis and Design Lectures

Lecture 3 – Page 6 of 10

A basic understanding of beam mechanics is necessary to study concrete beam behavior. Consider a simply-supported homogeneous rectangular beam loaded by a uniformly-distributed load as shown below: Taking a section through the beam at any place along the length reveals the following stress distribution about the cross-section of the beam:

Compression

Tension

Applied loads

Span L

Neutral Axis The stress distribution

varies linearly from zero stresses at the neutral axis, to a maximum tensile or compressive stress at the extreme edges.

Homogeneous Beam

Page 338: Structural Analysis and Design Lectures

Lecture 3 – Page 7 of 10

In a reinforced concrete beam, the stress distribution is different. Above the neutral axis, the concrete carries all the compression, similar to the homogeneous beam. Below the neutral axis however, the concrete is incapable of resisting tension and must rely on the reinforcing bars to carry all the tension loads. Looking at a side view of the stress distribution of the reinforced concrete beam:

½ (a

)

b

Neutral Axis

0.85f’cb

T = Asfy T = Asfy

a = 1

C

Compression

Tension = T

Neutral Axis The actual stress distribution

in the compression side varies non-linearly from zero stresses at the neutral axis, to a maximum compressive stress at the extreme edge.

Reinforced Concrete Beam

Reinforcing bars

Actual Stress Distribution Idealized Stress Distribution

Moment arm = Z

C

d

“Whitney” stress block

Page 339: Structural Analysis and Design Lectures

Lecture 3 – Page 8 of 10

Assuming an idealized beam, tension equals compression:

Tension = Compression Asfy = Area of Whitney stress block Asfy = 0.85f’cab

Solve for a:

a = bf

fA

c

ys

'85.0 = 1C

1 = 0.85 for f’c < 4000 PSI

= 0.80 for f’c = 5000 PSI = 0.75 for f’c > 6000 PSI

C = depth to neutral axis from extreme compression edge

Mn = Nominal moment capacity of concrete beam = Asfy(Moment arm) = AsfyZ

= Asfy(d - )2a

Mu = Usable moment capacity of concrete beam = Mn = 0.9Mn

Mu = 0.9(Asfy(d - )2a )

Mu = 0.9Asfyd(1 -

c

yact

ff

'59.0

)

bal = balanced ratio of tension steel reinforcement

=

yy

c

fff

000,87000,87'85.0 1 where fy = PSI

max = maximum allowable ratio of tension steel reinforcement per ACI 318 = 0.75bal

Beta

Page 340: Structural Analysis and Design Lectures

Lecture 3 – Page 9 of 10

Example 2 GIVEN: The concrete beam from Example 1 is used to support the loading as shown below. REQUIRED:

1. Determine the maximum factored applied moment, Mmax. 2. Determine the usable moment capacity of the beam, Mu, and determine if

it is acceptable based on Mmax. 3. Determine if the beam is acceptable based on max.

Step 1 – Determine maximum factored applied moment, Mmax:

Mmax = 8

2Lwu

= 8

)"0'20)(3( 2KLF

Mmax = 150 KIP-FT

Step 2 - Determine the usable moment capacity of the beam, Mu:

Factored uniform load wu = 3000 PLF (incl. beam wt.)

20’-0”

Mu = 0.9Asfyd(1 -

c

yact

ff

'59.0

) where act = 0.0108 (see Ex. 1)

= 0.9(2.40 in2)(60 KSI)(18.44”)(1 -

KSIKSI

4)60)(0108.0(59.0 )

= 2161.4 KIP-IN Mu = 180.1 KIP-FT Since Mu = 180.1 KIP-FT > Mmax = 150 KIP-FT beam is acceptable

Page 341: Structural Analysis and Design Lectures

Lecture 3 – Page 10 of 10

Step 3 – Determine if the beam is acceptable based on max:

max = maximum allowable ratio of tension steel reinforcement per ACI 318 = 0.75bal

bal = balanced ratio of tension steel reinforcement

=

yy

c

fff

000,87000,87'85.0 1 where fy = PSI

where 1 = 0.85 since f’c = 4000 PSI

=

PSIKSIKSI

60000000,87000,87

60)4)(85.0(85.0

= 0.0285

max = 0.75(0.0285) max = 0.0214 > act = 0.0108 beam is acceptable

Page 342: Structural Analysis and Design Lectures

Lecture 4 – Page 1 of 13

Lecture 4 – Flexural Members (cont.) Determining the usable moment capacity, Mu, of a rectangular reinforced concrete beam is accomplished by using the formula below: (see Lect. 3)

Mu = 0.9Asfyd(1 -

c

yact

ff

'59.0

)

Designing a beam using the equation above is much more difficult. Assuming the material properties and dimensions are known, the equation above still has 2 unknown variables – As and act. Therefore, design of steel reinforcement for a given beam is largely one of trial-and-error. Beam Design

Design of concrete beam members is often one of trial-and-error. It’s impossible to directly solve for all the variables in a reinforced concrete beam. Usually, material properties are known as well as maximum applied factored moment, Mmax. The following Table is useful to get a “trial” beam size:

Minimum Suggested Thickness “h” of Concrete Beams & One-Way Slabs Member: End Conditions

Simply supported

One end continuous

Both ends continuous

Cantilever

Solid one-way slab L/20 L/24 L/28 L/10 Beam L/16 L/18.5 L/21 L/8

Span length L = inches Beams are usually rectangular having the width typically narrower than the height. The diagram below shows typical beam aspect ratios:

h L

h 1.5b 2.5b

b

NOTE: Beam cross-section dimensions “b” and “h” are USUALLY in multiples of 2” or 4” for ease of formwork.

Page 343: Structural Analysis and Design Lectures

Lecture 4 – Page 2 of 13

Beam Design Aid

It is still difficult to directly design a reinforced concrete beam even if dimensions and material properties are known. The use of design aids are commonly used to streamline the design process instead of laboriously using a trial-and-error approach.

The design aid shown below is used for design or analysis. Values of 2bdM u

are in units of PSI. It can be used to directly solve for act knowing factored actual moment Mu, f’c, fy, b and d.

Table 1 - Concrete f’c = 3000 PSI, Grade 60 Bars

Page 344: Structural Analysis and Design Lectures

Lecture 4 – Page 3 of 13

Table 2 – Concrete f’c = 4000 PSI, Grade 60 Bars

Page 345: Structural Analysis and Design Lectures

Lecture 4 – Page 4 of 13

Example 1 GIVEN: A rectangular concrete beam with dimensions is shown below (stirrup bars not shown). Use concrete f’c = 4000 PSI and grade 60 bars. REQUIRED:

1) Determine the usable moment capacity Mu of the beam using formula. 2) Determine the usable moment capacity Mu of the beam using Table 2.

Step 1 – Determine usable moment capacity Mu of the beam using formula:

act = bdAs

= )"18)("12(

)__60.0(3 2 barperin

act = 0.0083

Mu = 0.9Asfyd(1 -

c

yact

ff

'59.0

)

= 0.9(1.80 in2)(60 KSI)(18”)(1 -

KSIKSI

4)60)(0083.0(59.0 )

= 1621 KIP-IN Mu = 135 KIP-FT

d = 18”

b =12”

3 - # 7 bars

Page 346: Structural Analysis and Design Lectures

Lecture 4 – Page 5 of 13

Step 2 - Determine the usable moment capacity Mu of the beam using Table 2:

From Table 2 above:

At = 0.0083 PSIbdM u 4.4612

Solving for Mu:

Mu = 461.4 PSI(bd2) = 461.4 PSI[(0.9)(12”)(18”)2] = 1,614,531 LB-IN = 1615 KIP-IN Mu = 134.6 KIP-FT

NOTE: This answer is the same as in Step 1.

Page 347: Structural Analysis and Design Lectures

Lecture 4 – Page 6 of 13

Example 2 GIVEN: The concrete beam below. Use the following:

Concrete f’c = 4000 PSI Steel grade 60 Concrete cover = ¾” #8 bars are to be used for main tension bars #3 stirrups

REQUIRED: Design the rectangular beam such that h 1.5b and act ½ (max).

Step 1 – Determine maximum factored moment, Mmax:

Mmax = 8

2Lwu

= 8

)"0'28)(2( 2KLF

Mmax = 196 KIP-FT = 2352 KIP-IN = 2,352,000 LB-IN

wu = 2 KLF (includes anticipated beam weight = 300 PLF)

28’-0”

Page 348: Structural Analysis and Design Lectures

Lecture 4 – Page 7 of 13

Step 2 – Select values from Table 2:

a) Select act = ½(max) = ½(0.0214) TRY act = 0.0107

b) At = 0.0107 2bdM u

= 581.2 PSI

Step 3 – Solve for “b” and “d” by substituting Mmax for Mu in above equation:

2bdM u

= 581.2 PSI

where: Mu = Mmax = 2,352,000 LB-IN = 0.9 d = 1.5b

PSIbb

inLb 2.581)5.1)()(9.0(

23520002

Solve for “b”:

PSIb

2.581)25.2)(9.0(

23520003

3)2.581)(25.2)(9.0(

2352000b

b = 12.6” Use b = 12” d = 1.5b = 1.5(12”) d 18”

Page 349: Structural Analysis and Design Lectures

Lecture 4 – Page 8 of 13

Step 4 – Select beam dimensions:

From above, use b = 12” and d 18” h = d + conc. cover + stirrup bar dia. + ½(main bar dia.) = 18” + ¾” + 3/8” + ½(1”) = 19.625” Use h = 20”

Revised d = 20” – ¾” – ⅜” – ½(1”) = 18.375”

Step 5 – Determine required area of main tension bars:

From above, act = 0.0107 = bdAs

Solve for As:

As = 0.0107(b)(d) = 0.0107(12”)(18.375”) As = 2.36 in2

Step 6 – Determine number of #8 main tension bars:

No. of bars = baroneofArea

As

___

= barperin

in_8_#_79.0

36.22

2

= 2.99 bars USE 3 - #8 bars

#3 stirrup bar dia. = 3/8” #8 main bar dia. = 1”

Page 350: Structural Analysis and Design Lectures

Lecture 4 – Page 9 of 13

Step 7 – Check beam height with “Minimum Thickness of Beams” Table: From Table:

Member type = Beam End Condition = Simply-supported

h 16L

16

)/"12)("0'28( ft

h 21” which is approximately = 20” as designed

Step 8 – Check originally assumed beam weight:

It was assumed that the beam weight = 300 PLF (See Step 1). Actual beam dimensions:

Recall: VolumeWeightUnitWt → Rearranging:

))(( VolumeUnitWtBeamWeight

= (150 PCF) )"0'1(/144

"20"1222

ftin

x

Beam Weight = 250 PLF < 300 PLF (assumed) OK

h 16L

20”

12”

Page 351: Structural Analysis and Design Lectures

Lecture 4 – Page 10 of 13

Step 9 – Draw “Summary Sketch” labeling all information necessary to build it:

¾” concrete cover all around

20”

12”

Section A-A

2 - #4 hanger bars

#3 stirrup bars @ 9” o.c.

3 - #8 main bars

Notes: 1) Concrete f’c = 4000 PSI normal-weight 2) All bars ASTM A615 Grade 60

Page 352: Structural Analysis and Design Lectures

Lecture 4 – Page 11 of 13

Example 3 GIVEN: A continuous 10” x 16” concrete beam is shown below. Assume the following:

Concrete f’c = 4000 PSI Steel grade 60 Concrete cover = ¾” 2 - #9 bars are to be used for main tension bars #3 stirrups

REQUIRED:

1) Determine the magnitude of the maximum positive and negative moments (Refer to Structural Theory notes)

2) Determine if the beam is adequate based upon flexure only. Check positive & negative moments.

0.4L

wu = 2400 PLF (incl. beam wt.)

L = 20’-0” L = 20’-0”

Mpos = 0.025(wL2) Mpos = 0.08(wL2) Mpos = 0.08(wL2)

0.5L 0.5L 0.4L

R4 R2 R3 R1

L = 20’-0”

Mneg = -0.1(wL2) Mneg = -0.1(wL2)

R1 = 0.4wL R2 = 1.1wL R3 = 1.1wL R4 = 0.4wL

Page 353: Structural Analysis and Design Lectures

Lecture 4 – Page 12 of 13

Step 1 – Determine maximum positive and maximum negative moments:

a) Maximum positive moment, “Mpos”:

From above, the largest Mpos = 0.08(wL2) = 0.08(2.4 KLF)(20’-0”)2 = 76.8 Kip-Ft

b) Maximum negative moment, “Mneg”:

From above, the largest Mneg = -0.1(wL2) = -0.1(2.4 KLF)(20’-0”)2 = 96.0 Kip-Ft

Step 2 – Determine beam’s “d” dimension:

Depth “d” to center of tension steel is shown below:

d = h - conc. cover - stirrup bar dia. - ½(main bar dia.)

= 16” - ¾” - 3/8” - ½

"89

d = 14.3125”

d

¾” concrete cover all around

16”

10”

2 - #4 hanger bars

#3 stirrup bars @ 9” o.c.

2 - #9 main bars

Beam cross-section in Mpos region (upside-down in Mneg region)

#3 stirrup bar dia. = 3/8” #9 main bar dia. =

"

89

Page 354: Structural Analysis and Design Lectures

Lecture 4 – Page 13 of 13

Step 3 – Determine usable moment capacity Mu of the beam using formula:

act = bdAs

= )"3125.14)("10(

)__00.1(2 2 barperin

act = 0.01397 which is > min = 0.0033 and < max = 0.0214 OK

Mu = 0.9Asfyd(1 -

c

yact

ff

'59.0

)

= 0.9(2.00 in2)(60 KSI)(14.3125”)(1 -

KSIKSI

4)60)(01397.0(59.0 )

= 1354.6 KIP-IN Mu = 112.9 KIP-FT

Step 4 – Check if beam is adequate based upon flexure only:

a) Maximum positive moment, “Mpos”:

From above, the largest Mpos = 76.8 Kip-Ft < 112.9 Kip-Ft ACCEPTABLE b) Maximum negative moment, “Mneg”:

From above, the largest Mneg = -96.0 Kip-Ft < 112.9 Kip-Ft

ACCEPTABLE

As

As