Top Banner
SPS SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS
8

SPS SINGLE PHASE & THREE PHASE STAND ALONE POWER … · SPS | SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS The Magellan Stand Alone Power System combines renewable energy

Mar 08, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: SPS SINGLE PHASE & THREE PHASE STAND ALONE POWER … · SPS | SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS The Magellan Stand Alone Power System combines renewable energy

SPS

SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS

Page 2: SPS SINGLE PHASE & THREE PHASE STAND ALONE POWER … · SPS | SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS The Magellan Stand Alone Power System combines renewable energy

11MAGELLAN POWER ENERGY STORAGE | magellanpower.com.au

SPS | SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS

The Magellan Stand Alone Power System combines renewable energy sources and batteries together with a generator to provide remote farms or communities with safe, clean, reliable, sustainable and cost-effective electrical power that is not affected by natural disasters such as fire and flood.

The Magellan SPS is designed to operate independently of the grid and maximise the use of renewable energy.

Using high-efficiency Lithium batteries, smart microgrid and high-reliability power electronics, the Magellan Stand Alone Power Systems are maintenance free, intelligent and designed to supply high-quality, stable power to remote communities.

FEATURES:

Rugged Industrial Design 25 Year Service Life Smart Microgrid Minimising Generator Run Time Stores Solar & Generator Power Compliant with AS4509 High Efficiency Lithium Batteries Pure Sinewave Inverter Output Bumpless Power Transfer from Solar/

Battery/ Generator Optional Remote Monitoring Air-conditioned Battery Enclosure

Page 3: SPS SINGLE PHASE & THREE PHASE STAND ALONE POWER … · SPS | SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS The Magellan Stand Alone Power System combines renewable energy

12 MAGELLAN POWER ENERGY STORAGE | magellanpower.com.au

SPS | SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS

COMPONENTS OF STAND ALONE POWERTHESE INCLUDE:

PV Panels A Magellan Inverter/ Charger Lithium Batteries Diesel Generator

All components of the Magellan Stand Alone Power System are chosen for their durability and reliability in harsh conditions.

Operational diagram (left) showing the system and the way it is connected to a house or community.

Page 4: SPS SINGLE PHASE & THREE PHASE STAND ALONE POWER … · SPS | SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS The Magellan Stand Alone Power System combines renewable energy

13MAGELLAN POWER ENERGY STORAGE | magellanpower.com.au

SPS | SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS

EXAMPLE APPLICATIONS:

Regional Communities

Farms

Rural Homes

Mining Camps

Magellan Power’s Microgrid Controller (left)

Page 5: SPS SINGLE PHASE & THREE PHASE STAND ALONE POWER … · SPS | SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS The Magellan Stand Alone Power System combines renewable energy

14 MAGELLAN POWER ENERGY STORAGE | magellanpower.com.au

INVERTER SYSTEM SPECIFICATION

Rated Power 5-10kVA / 1 PHASE

Configuration Bidirectional Conversion

Housing To suit equipment rating and application

AC Output

Voltage Nominal 230/240VAC

AC Grid Voltage Range 207V - 264V

AC Grid Frequency Range 45Hz - 55Hz

Voltage Regulation ±1%

Frequency 50 ± 0.1Hz

Waveform Sinusoidal

THD Less than 5%

Power Factor 0.9 lag to 0.9 lead

Phase Single

Standards As per AS 62040, AS3100, AS4509

AC Current THD Less than 5% as per AS 4777

Communication Interface Modbus RTU (RS232/RS485), USB, Modbus TCP (Ethernet)Distributed Network Protocol 3 (Ethernet) Inbuilt website (Ethernet)

Ambient Temperature 0° to 50°C

MonitoredSystemParameters

Battery State-of-Charge, Current, Cell Voltage & Temperature, Inverter Voltage, Current, Watts, VARs & Temperature Mains Voltage, Current, Watts, VAR, Power Factor & Frequency

In-builtDiagnosticSystem

Periodic Data Logging into Non-Volatile Memory. (200 days of logged data at 15 minute intervals) (2 years of logged data at 1 hour interval) Battery SOC, Voltage, Current, Power & Temperature, Mains Voltage, Power & VARs, Power Factor Inverter Voltage, Temperature, Power & VARs Min & Max Cell Voltage, Fault Event Recorder.

Cooling (Inverter) Forced air with temperature controlled cooling fans

Maximum Humidity 95% R.H., Non Condensing

SPS | SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS

Page 6: SPS SINGLE PHASE & THREE PHASE STAND ALONE POWER … · SPS | SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS The Magellan Stand Alone Power System combines renewable energy

15MAGELLAN POWER ENERGY STORAGE | magellanpower.com.au

BATTERY SYSTEM SPECIFICATION

DESCRIPTION VALUE NOTES

Rated Capacity 25kWh -

Module Capacity 3.2kWh/6.5kWh -

Minimum Voltage 42V -

Nominal Voltage 48V -

Maximum Voltage 58.8 -

Max Continuous Charge Current

0.5C -

Duty Cycle 1 cycle per day -

Round Trip Efficiency >95% @ 23 ±3°C as a new product

Cell Cycle Life >4000 @ 23 ±3°C, 1C/1C, 80% DoD

Operational Temperature Optimal - 15°C to 50°C

Storage - - 15°C to 60°C

MAGELLAN BATTERY MODULE

DESCRIPTION VALUE NOTES

Rated Capacity 17-50kWh -

Cell Capacity To suit equipment rating -

Minimum Voltage 240V -

Nominal Voltage 256V -

Maximum Voltage 320V -

Max Continuous Charge Current

0.5C -

Duty Cycle 1 cycle per day -

Round Trip Efficiency >95% @ 23 ±3°C as a new product

Cell Cycle Life >4000 @ 23 ±3°C, 1C/1C, 80% DoD

Operational Temperature Optimal - 15°C to 50°C

Storage - - 15°C to 60°C

SPS | SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS

Page 7: SPS SINGLE PHASE & THREE PHASE STAND ALONE POWER … · SPS | SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS The Magellan Stand Alone Power System combines renewable energy

16 MAGELLAN POWER ENERGY STORAGE | magellanpower.com.au

THREE PHASE INVERTER SYSTEM SPECIFICATION

Rated Power 30kVA - 100kVA / 3 PHASE

Configuration Bidirectional Conversion

Housing To suit equipment rating and application

AC Output

Voltage Nominal 400V/415V

AC Grid Voltage Range 358V - 438V

AC Grid Frequency Range 45Hz - 55Hz

Voltage Regulation ±1%

Frequency 50 ±0.1Hz

Waveform Sinusoidal

THD Less than 5%

Power Factor 0.9 lag to 0.9 lead

Phase Three-phase, four wire

Grid Support Supports grid by providing reactive and active power compensation

Standards As per AS 62040, AS3100, AS4509

Maximum Phase Imbalance 100%

AC Current THD Less than 5% as per AS 4777

Communication Interface Modbus RTU (RS232/RS485), USB, Modbus TCP (Ethernet)Distributed Network Protocol 3 (Ethernet) Inbuilt website (Ethernet)

Ambient Temperature 0° to 50°C

MonitoredSystemParameters

Battery State-of-Charge, Current, Cell Voltage & Temperature, Inverter Voltage, Current, Watts, VARs & Temperature Mains Voltage, Current, Watts, VAR, Power Factor & Frequency

In-builtDiagnosticSystem

Periodic Data Logging into Non-Volatile Memory (200 days of logged data at 15 minute intervals) (2 years of logged data at 1 hour interval). Battery SOC, Voltage, Current, Power & Temperature, Mains Voltage, Power & VARs, Power Factor Inverter Voltage, Temperature, Power & VARs Min & Max Cell Voltage, Fault Event Recorder.

Cooling Inverter Forced air with temperature controlled cooling fans

Maximum Humidity 95% R.H., Non Condensing

SPS | SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS

Page 8: SPS SINGLE PHASE & THREE PHASE STAND ALONE POWER … · SPS | SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS The Magellan Stand Alone Power System combines renewable energy

17MAGELLAN POWER ENERGY STORAGE | magellanpower.com.au

THREE PHASE BATTERY SYSTEM SPECIFICATION

DESCRIPTION VALUE NOTES

Rated Capacity 30-500kWh -

Cell Capacity To suit equipment rating -

Minimum Voltage 240V -

Nominal Voltage 256V -

Maximum Voltage 320V -

Max Continuous ChargeCurrent

0.5C -

Duty Cycle 1 cycle per day -

Round Trip Efficiency >95% @ 23 ±3°C as a new product

Cell Cycle Life >4000 @ 23 ±3°C, 1C/1C, 80% DoD

Operational Temperature Optimal - 15°C to 50°C

Storage - - 15°C to 60°C

SPS | SINGLE PHASE & THREE PHASE STAND ALONE POWER SYSTEMS

Magellan SPS with Optional Outdoor Canopy