SETUP MANUAL SYSDRIVE 3G3JV Compact Simplified Inverters Cat. No. I546-E1-02 0675398-6B
72
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Setup Manual 3G3JV

SETUP MANUAL

SYSDRIVE 3G3JVCompact Simplified Inverters

Cat. No. I546-E1-020675398-6B

Page 2: Setup Manual 3G3JV

Thank you for choosing this SYSDRIVE 3G3JV-series product. Proper useand handling of the product will ensure proper product performance, willlengthen product life, and may prevent possible accidents.Please read this manual thoroughly and handle and operate the productwith care.

1. To ensure safe and proper use of the OMRON Inverters, please read this SETUPMANUAL and the USER’S MANUAL (Cat. No. I528-E1) to gain sufficient knowledgeof the devices, safety information, and precautions before actual use.

2. The products are illustrated without covers and shieldings for closer look in this SET-UP MANUAL and the USER’S MANUAL. For actual use of the products, make sure touse the covers and shieldings as specified.

3. This SETUP MANUAL and other related user’s manuals are to be delivered to the ac-tual end users of the products.

4. Please keep this manual close at hand for future reference.

5. If the product has been left unused for a long time, please inquire at our sales repre-sentative.

NOTICE1. This manual describes the functions of the product and relations with other

products. You should assume that anything not described in this manual isnot possible.

2. Although care has been given in documenting the product, please contact yourOMRON representative if you have any suggestions on improving this manual.

3. The product contains potentially dangerous parts under the cover. Do not attemptto open the cover under any circumstances. Doing so may result in injury or deathand may damage the product. Never attempt to repair or disassemble the product.

4. We recommend that you add the following precautions to any instruction manualsyou prepare for the system into which the product is being installed.

Precautions on the dangers of high-voltage equipment.

Precautions on touching the terminals of the product even after power has beenturned OFF. (These terminals are live even with the power turned OFF.)

5. Specifications and functions may be changed without notice in order to improveproduct performance.

Items to Check Before UnpackingCheck the following items before removing the product from the package:

Has the correct product been delivered (i.e., the correct model number and speci-fications)?

Has the product been damaged in shipping?

Are any screws or bolts loose?

Page 3: Setup Manual 3G3JV

!

!

!

Notice:OMRON products are manufactured for use according to proper procedures by a qualifiedoperator and only for the purposes described in this manual.

The following conventions are used to indicate and classify precautions in this manual. Al-ways heed the information provided with them. Failure to heed precautions can result in inju-ry to people or damage to property.

DANGER Indicates an imminently hazardous situation which, if not avoided, will result in deathor serious injury. Additionally, there may be severe property damage.

WARNING Indicates a potentially hazardous situation which, if not avoided, could result in deathor serious injury. Additionally, there may be severe property damage.

Caution Indicates a potentially hazardous situation which, if not avoided, may result in minoror moderate injury, or property damage.

OMRON Product ReferencesAll OMRON products are capitalized in this manual. The word “Unit” is also capitalized whenit refers to an OMRON product, regardless of whether or not it appears in the proper nameof the product.

The abbreviation “Ch,” which appears in some displays and on some OMRON products,often means “word” and is abbreviated “Wd” in documentation in this sense.

The abbreviation “PC” means Programmable Controller and is not used as an abbreviationfor anything else.

Visual AidsThe following headings appear in the left column of the manual to help you locate differenttypes of information.

Note Indicates information of particular interest for efficient and convenient operation of the product.

OMRON, 2005All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted,in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the priorwritten permission of OMRON.

No patent liability is assumed with respect to the use of the information contained herein. Moreover, becauseOMRON is constantly striving to improve its high-quality products, the information contained in this manualis subject to change without notice. Every precaution has been taken in the preparation of this manual. Never-theless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for dam-ages resulting from the use of the information contained in this publication.

Page 4: Setup Manual 3G3JV

Read and Understand this ManualPlease read and understand this manual before using the product. Please consult your OMRONrepresentative if you have any questions or comments.

Warranty and Limitations of LiabilityÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

WARRANTYÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

OMRON’s exclusive warranty is that the products are free from defects in materials and workmanship fora period of one year (or other period if specified) from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDINGNON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THEPRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HASDETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIRINTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

LIMITATIONS OF LIABILITY

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIALDAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THEPRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, ORSTRICT LIABILITY.

In no event shall the responsibility of OMRON for any act exceed the individual price of the product onwhich liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMSREGARDING THE PRODUCTS UNLESS OMRON’S ANALYSIS CONFIRMS THAT THE PRODUCTSWERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TOCONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

Page 5: Setup Manual 3G3JV

Application ConsiderationsÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

SUITABILITY FOR USE

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply tothe combination of products in the customer’s application or use of the products.

At the customer’s request, OMRON will provide applicable third party certification documents identifyingratings and limitations of use that apply to the products. This information by itself is not sufficient for acomplete determination of the suitability of the products in combination with the end product, machine,system, or other application or use.

The following are some examples of applications for which particular attention must be given. This is notintended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that theuses listed may be suitable for the products:

• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditionsor uses not described in this manual.

• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medicalequipment, amusement machines, vehicles, safety equipment, and installations subject to separateindustry or government regulations.

• Systems, machines, and equipment that could present a risk to life or property.

Please know and observe all prohibitions of use applicable to the products.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE ORPROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TOADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED ANDINSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

PROGRAMMABLE PRODUCTSÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

OMRON shall not be responsible for the user’s programming of a programmable product, or anyconsequence thereof.

Page 6: Setup Manual 3G3JV

DisclaimersÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

CHANGE IN SPECIFICATIONS

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

Product specifications and accessories may be changed at any time based on improvements and otherreasons.

It is our practice to change model numbers when published ratings or features are changed, or whensignificant construction changes are made. However, some specifications of the products may bechanged without any notice. When in doubt, special model numbers may be assigned to fix or establishkey specifications for your application on your request. Please consult with your OMRON representativeat any time to confirm actual specifications of purchased products.

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

DIMENSIONS AND WEIGHTSÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

Dimensions and weights are nominal and are not to be used for manufacturing purposes, even whentolerances are shown.

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

PERFORMANCE DATA

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

Performance data given in this manual is provided as a guide for the user in determining suitability anddoes not constitute a warranty. It may represent the result of OMRON’s test conditions, and the usersmust correlate it to actual application requirements. Actual performance is subject to the OMRONWarranty and Limitations of Liability.

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

ERRORS AND OMISSIONSÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

The information in this manual has been carefully checked and is believed to be accurate; however, noresponsibility is assumed for clerical, typographical, or proofreading errors, or omissions.

Page 7: Setup Manual 3G3JV

!

!

!

!

!

!

!

!

!

General PrecautionsObserve the following precautions when using the SYSDRIVE Inverters and peripheral de-vices.This manual may include illustrations of the product with protective covers removed in orderto describe the components of the product in detail. Make sure that these protective coversare on the product before use.Consult your OMRON representative when using the product after a long period of storage.

WARNING Do not touch the inside of the Inverter. Doing so may result in electrical shock.

WARNING Operation, maintenance, or inspection must be performed after turning OFF thepower supply, confirming that the CHARGE indicator (or status indicators) are OFF,and after waiting for the time specified on the front cover. Not doing so may result inelectrical shock.

WARNING Do not damage, pull on, apply stress to, place heavy objects on, or pinch the cables.Doing so may result in electrical shock.

WARNING Do not touch the rotating parts of the motor under operation. Doing so may result ininjury.

WARNING Do not modify the product. Doing so may result in injury or damage to the product.

Caution Do not store, install, or operate the product in the following places. Doing so mayresult in electrical shock, fire or damage to the product.

Locations subject to direct sunlight. Locations subject to temperatures or humidity outside the range specified in the

specifications. Locations subject to condensation as the result of severe changes in temperature. Locations subject to corrosive or flammable gases. Locations subject to exposure to combustibles. Locations subject to dust (especially iron dust) or salts. Locations subject to exposure to water, oil, or chemicals. Locations subject to shock or vibration.

Caution Do not touch the Inverter radiator, regenerative resistor, or Servomotor while thepower is being supplied or soon after the power is turned OFF. Doing so may result ina skin burn due to the hot surface.

Caution Do not conduct a dielectric strength test on any part of the Inverter. Doing so mayresult in damage to the product or malfunction.

Caution Take appropriate and sufficient countermeasures when installing systems in the fol-lowing locations. Not doing so may result in equipment damage.

Locations subject to static electricity or other forms of noise. Locations subject to strong electromagnetic fields and magnetic fields. Locations subject to possible exposure to radioactivity. Locations close to power supplies.

Page 8: Setup Manual 3G3JV

!

!

!

!

!

!

!

!

!

!

!

!

Transportation PrecautionsCaution Do not hold by front cover or panel, instead, hold by the radiation fin (heat sink) while

transporting the product. Doing so may result in injury.

Caution Do not pull on the cables. Doing so may result in damage to the product or malfunc-tion.

Caution Use the eye-bolts only for transporting the Inverter. Using them for transporting themachinery may result in injury or malfunction.

Installation PrecautionsWARNING Provide an appropriate stopping device on the machine side to secure safety. (A

holding brake is not a stopping device for securing safety.) Not doing so may result ininjury.

WARNING Provide an external emergency stopping device that allows an instantaneous stop ofoperation and power interruption. Not doing so may result in injury.

Caution Be sure to install the product in the correct direction and provide specified clear-ances between the Inverter and control panel or with other devices. Not doing somay result in fire or malfunction.

Caution Do not allow foreign objects to enter inside the product. Doing so may result in fire ormalfunction.

Caution Do not apply any strong impact. Doing so may result in damage to the product ormalfunction.

Wiring PrecautionsWARNING Wiring must be performed only after confirming that the power supply has been

turned OFF. Not doing so may result in electrical shock.

WARNING Wiring must be performed by authorized personnel. Not doing so may result inelectrical shock or fire.

WARNING Be sure to confirm operation only after wiring the emergency stop circuit. Not doingso may result in injury.

WARNING Always connect the ground terminals to a ground of 100 Ω or less. Not connecting toa proper ground may result in electrical shock.

Page 9: Setup Manual 3G3JV

!

!

!

!

!

!

!

!

!

!

!

!

!

Caution Install external breakers and take other safety measures against short-circuiting inexternal wiring. Not doing so may result in fire.

Caution Confirm that the rated input voltage of the Inverter is the same as the AC power sup-ply voltage. An incorrect power supply may result in fire, injury, or malfunction.

Caution Connect the Braking Resistor and Braking Resistor Unit as specified in the manual.Not doing so may result in fire.

Caution Be sure to wire correctly and securely. Not doing so may result in injury or damage tothe product.

Caution Be sure to firmly tighten the screws on the terminal block. Not doing so may result infire, injury, or damage to the product.

Caution Do not connect an AC power to the U, V, or W output. Doing so may result in damageto the product or malfunction.

Caution Set the multi-function contact input parameter for NC contact terminals (e.g., 3-wiresequence) before wiring them. If the parameter’s default setting is used, the motormay start running when the input terminal S2 is turned ON.

Operation and Adjustment PrecautionsWARNING Turn ON the input power supply only after mounting the front cover, terminal covers,

bottom cover, Operator, and optional items. Not doing so may result in electricalshock.

WARNING Do not remove the front cover, terminal covers, bottom cover, Operator, or optionalitems while the power is being supplied. Doing so may result in electrical shock ordamage to the product.

WARNING Do not operate the Operator or switches with wet hands. Doing so may result inelectrical shock.

WARNING Do not touch the inside of the Inverter. Doing so may result in electrical shock.

WARNING Do not come close to the machine when using the error retry function because themachine may abruptly start when stopped by an alarm. Doing so may result in injury.

WARNING Do not come close to the machine immediately after resetting momentary powerinterruption to avoid an unexpected restart (if operation is set to be continued in theprocessing selection function after momentary power interruption is reset). Doing somay result in injury.

Page 10: Setup Manual 3G3JV

!

!

!

!

!

!

!

!

!

!

!

!

WARNING Provide a separate emergency stop switch because the STOP Key on the Operatoris valid only when function settings are performed. Not doing so may result in injury.

WARNING Be sure to confirm that the RUN signal is turned OFF before turning ON the powersupply, resetting the alarm, or switching the LOCAL/REMOTE selector. Doing sowhile the RUN signal is turned ON may result in injury.

Caution Be sure to confirm permissible ranges of motors and machines before operation be-cause the Inverter speed can be easily changed from low to high. Not doing so mayresult in damage to the product.

Caution Provide a separate holding brake when necessary. Not doing so may result in injury.

Caution Do not perform a signal check during operation. Doing so may result in injury or dam-age to the product.

Caution Do not carelessly change settings. Doing so may result in injury or damage to theproduct.

Maintenance and Inspection PrecautionsWARNING Do not touch the Inverter terminals while the power is being supplied.

WARNING Maintenance or inspection must be performed only after turning OFF the powersupply, confirming that the CHARGE indicator (or status indicators) is turned OFF,and after waiting for the time specified on the front cover. Not doing so may result inelectrical shock.

WARNING Maintenance, inspection, or parts replacement must be performed by authorizedpersonnel. Not doing so may result in electrical shock or injury.

WARNING Do not attempt to take the Unit apart or repair. Doing either of these may result inelectrical shock or injury.

Caution Carefully handle the Inverter because it uses semiconductor elements. Carelesshandling may result in malfunction.

Caution Do not change wiring, disconnect connectors, the Operator, or optional items, or re-place fans while power is being supplied. Doing so may result in injury, damage tothe product, or malfunction.

Page 11: Setup Manual 3G3JV

Warnings for UL/cUL Marking• Do not connect or disconnect wiring, or perform signal checks while the power supply is turned ON.

• The Inverter internal capacitor is still charged even after the power supply is turned OFF. To preventelectrical shock, disconnect all power before servicing the Inverter. Then wait at least one minute afterthe power supply is disconnected and all indicators are OFF.

• Do not perform a withstand voltage test on any part of the Inverter. This electronic equipment usessemiconductors and is vulnerable to high voltage.

• Do not remove the Digital Operator or the blank cover unless the power supply is turned OFF. Nevertouch the printed control board (PCB) while the power supply is turned ON.

• The Inverter is not suitable for use on a circuit capable of delivering more than 5,000 RMS symmetricalamperes, 250 volts maximum (100-V-class Units).

• Take measures against overcurrent, overload, and overheating by using the Motor Protection Set-tings.

CAUTIONUse 75°C copper wires or equivalent.Low voltage wires shall be wired with Class I Wiring.

Motor Protection Settings

Rated Motor Current (n32)• Set the rated motor current (n32) in order to prevent the motor from burning due to overloading.

• Check the rated current on the motor nameplate and set the parameter.

• This parameter is used for the electronic thermal function for motor overload detection (OL1). By set-ting the correct parameter, the overloaded motor will be protected from burning.

n32 Rated Motor Current Changes duringoperation

No

Settingrange

0.0% to 120% (A) of ratedoutput current of Inverter

Unit ofsetting

0.1 A Default setting (see note 1)

Note 1. The standard rated current of the maximum applicable motor is the default rated motor cur-rent.

Note 2. Motor overload detection (OL1) is disabled by setting the parameter to 0.0.

Motor Protection Characteristics (n33 and n34)• This parameters setting is for motor overload detection (OL1).

n33 Motor Protection Characteristic Selection Changes duringoperation

No

Settingrange

0 to 2 Unit ofsetting

1 Default setting 0

Set ValuesValue Description

0 Protection characteristics for general-purpose induction motors

1 Protection characteristics for Inverter-dedicated motors

2 No protection

Page 12: Setup Manual 3G3JV

• This parameter is used to set the electric thermal characteristics of the motor to be connected.

• Set the parameter according to the motor.

• If a single Inverter is connected to more than one motor, set the parameter to 2 for no protection. Theparameter is also disabled by setting n32 for rated motor current to 0.0. Provide thermal relays or othermethods separately for each motor to protect equipment from overloads.

n34 Motor Protection Time Changes duringoperation

No

Settingrange

1 to 60 (min) Unit ofsetting

1 min Default setting 8

Set Values• This parameter is used to set the electronic thermal protection constant of motor overload detection

OL1.

• The default setting does not need any changes in normal operation.

• To set the parameter according to the characteristics of the motor, confirm the thermal time constantwith the motor manufacturer and set the parameter with some margin. In other words, set the value alittle shorter than the thermal time constant.

• To detect motor overloading more quickly, reduce the set value, provided that it does not cause anyapplication problems.

Page 13: Setup Manual 3G3JV

Checking Before Unpacking

Checking the ProductOn delivery, always check that the delivered product is the SYSDRIVE 3G3JV Inverter that you ordered.Should you find any problems with the product, immediately contact your nearest local salesrepresentative.

Checking the Nameplate

Inverter model

Input specificationsOutput specifications

3G3JV-A1001AC3PH 100-115V 3.2A

Checking the Model

3G3JV-A1001

Maximum applicable motor capacity

Voltage class

Installation type

Series name: 3G3JV Series

Maximum Applicable Motor Capacity001 0.1 (0.1) kW

002 0.25/0.37 (0.2) kW

Note The figures in parentheses indicate capacities for motors used outside Japan.

Voltage Class1 Single-phase 100-V AC input (100-V class)

Note The output is 3-phase 200 V AC.

Installation TypeA Panel-mounting models (IP10 min.) or

Closed wall mounting

Checking for DamageCheck the overall appearance and check for damage or scratches resulting from transportation.

Checking the AccessoriesThis manual is the only accessory provided with the 3G3JV. Set screws and other necessary parts mustbe provided by the user.

Page 14: Setup Manual 3G3JV

Table of Contents

Chapter 1. Design 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Installation 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1-1-1 Dimensions 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1-2 Removing and Mounting the Covers 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1-2 Wiring 1-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-1 Terminal Block 1-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-2 Standard Connections 1-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-3 Wiring around the Main Circuit 1-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-4 Optional Accessories 1-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1-3 Specifications 1-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Chapter 2. Preparing for Operation and Monitoring 2-1. . . . . . . . . . . . . 2-1 Using the Digital Operator 2-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-1-1 Nomenclature 2-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1-2 Accepting Operation Commands While Changing Parameters 2-4. . . . . . . . . . . . . . . . . . 2-1-3 Outline of Operation 2-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-2 Copying and Verifying Parameters 2-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2-1 Parameters Used to Copy and Verify Parameters 2-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2-2 Outline of Copying Parameters 2-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2-3 Procedures 2-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2-4 Error Messages for Copying and Verifying Parameters 2-12. . . . . . . . . . . . . . . . . . . . . . . .

Chapter 3. List of Parameters 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Chapter 4. Maintenance Operations 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 Protective and Diagnostic Functions 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-1-1 Fault Detection (Fatal Error) 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1-2 Warning Detection (Nonfatal Error) 4-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-2 Inspection and Maintenance 4-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 15: Setup Manual 3G3JV

Chapter 1

Design

1-1 Installation

1-2 Wiring

1-3 Specifications

1

Page 16: Setup Manual 3G3JV

1-2

1-1 Installation

1-1-1 Dimensions

3G3JV-A1001, -A1002 (0.1 to 0.2 kW) Single-phase 100-V AC Input

t

Rated voltage Model 3G3JV- Dimensions (mm) Weight (kg)gD t

g ( g)

Single-phase 100 V AC A1001 80 3 Approx. 0.5g p

A1002 112 5 Approx. 0.8

Installation Direction and Dimensions• Install the Inverter under the following conditions.

Ambient temperature for operation (panel-mounting): –10°C to 50°C

Humidity: 95% or less (no condensation)

• Install the Inverter in a clean location free from oil mist and dust. Alternatively, install it in a totally en-closed panel that is completely protected from floating dust.

• When installing or operating the Inverter, always take special care so that metal powder, oil, water, orother foreign matter does not get into the Inverter.

• Do not install the Inverter on inflammable material such as wood.

Direction• Install the Inverter on a vertical surface so that the characters on the nameplate are oriented upward.

Design Chapter 1

Page 17: Setup Manual 3G3JV

1-3

Dimensions• When installing the Inverter, always provide the following clearances to allow normal heat dissipation

from the Inverter.

W = 30 mm min.

Inverter

100 mm min. Air

SideInverter Inverter

100 mm min. Air

Ambient Temperature Control• To enhance operation reliability, the Inverter should be installed in an environment free from extreme

temperature changes.

• If the Inverter is installed in an enclosed environment such as a box, use a cooling fan or air conditionerto maintain the internal air temperature below 50°C.The life of the built-in electrolytic capacitors of the Inverter is prolonged by maintaining the internal airtemperature as low as possible.

• The surface temperature of the Inverter may rise approximately 30°C higher than the ambient temper-ature. Be sure to keep away equipment and wires from the Inverter as far as possible if the equipmentand wires are easily influenced by heat.

Protecting Inverter from Foreign Matter during Installation• Place a cover over the Inverter during installation to shield it from metal power produced by drilling.

Upon completion of installation, always remove the cover from the Inverter. Otherwise, ventilation willbe affected, causing the Inverter to overheat.

Design Chapter 1

Page 18: Setup Manual 3G3JV

1-4

1-1-2 Removing and Mounting the Covers

It is necessary to remove the front cover, optional cover, top protection cover, and thebottom protection cover from the Inverter to wire the terminal block.Follow the instructions below to remove the covers from the Inverter.To mount the covers, take the opposite steps.

Removing the Front Cover• Loosen the front cover mounting screws with a screwdriver.

• Press the left and right sides of the front cover in the arrow 1 directions and lift the bottom of the cover inthe arrow 2 direction to remove the front cover as shown in the following illustration.

Removing the Top and Bottom Protection Covers and Optional Cover

Removing the Top and Bottom Protection Covers• After removing the front cover, pull the top and bottom protection covers in the arrow 1 directions.

Design Chapter 1

Page 19: Setup Manual 3G3JV

1-5

Removing the Optional Cover• After removing the front cover, lift the optional cover in the arrow 2 direction based on position A as a

fulcrum.

Note The front cover functions as a terminal cover. The Digital Operator cannot be removed.

Design Chapter 1

Page 20: Setup Manual 3G3JV

1-6

1-2 Wiring

1-2-1 Terminal Block

Before wiring the terminal block, be sure to remove the front cover, top protection cover,and the bottom protection cover.

Position of Terminal Block

Ground terminal

Control circuit terminals

Main circuit output terminals

Main circuit input terminals

Ground terminal

Arrangement of Control Circuit Terminals

Design Chapter 1

Page 21: Setup Manual 3G3JV

1-7

Arrangement of Main Circuit Terminals

3G3JV-A1001, -A1002

Main Circuit Input Terminals(Upper Side)

Main Circuit Output Terminals(Lower Side)

Main Circuit TerminalsSymbol Name Description

R/L1 Power supply inputt i l

3G3JV-A1: Single-phase 100 to 115 V AC

S/L2

pp y pterminals

g p

Note Connect single-phase input to terminals R/L1 and S/L2.

U/T1 Motor output terminals 3-phase power supply output for driving motors.

V/T2

p p p pp y p g

3G3JV-A1: 3-phase 200 to 230 V ACW/T3

3G3JV A1: 3 phase 200 to 230 V AC

Ground terminal Be sure to ground the terminal under the following conditions.

3G3JV-A1: Ground at a resistance of 100 Ω or less, and connectto the power supply’s neutral phase to conform to EC Directives.

Note Be sure to connect the ground terminal directly to themotor frame ground.

Note The maximum output voltage corresponds to the power supply input voltage of the Inverter.

Design Chapter 1

Page 22: Setup Manual 3G3JV

1-8

Control Circuit TerminalsSymbol Name Function Signal level

Input S1 Forward/Stop Forward at ON. Stops atOFF.

Photocoupler8 mA at 24 V DC

S2 Multi-function input 1(S2)

Set by parameter n36(Reverse/Stop)

Note NPN is the default settingfor these terminals. Wireth b idiS3 Multi-function input 2

(S3)Set by parameter n37(Fault reset)

them by providing acommon ground. Noexternal power supply is

S4 Multi-function input 3(S4)

Set by parameter n38(External fault: Normallyopen)

external power supply isrequired. To provide anexternal power supply andwire the terminals through

i i liS5 Multi-function input 4(S5)

Set by parameter n39(Multi-step reference 1)

ga common positive line,however, set the SW7 toPNP and make sure that

SC Sequence input com-mon

Common for S1 throughS5

PNP and make sure thatthe power supply is at24 V DC ±10%.

FS Frequency referencepower supply

DC power supply for fre-quency reference use

20 mA at 12 V DC

FR Frequency reference in-put

Input terminal for fre-quency reference use

0 to 10 V DC (input impedance: 20 kΩ)

FC Frequency referencecommon

Common for frequencyreference use

( p p 0 )

Output MA Multi-function contactoutput (Normally open)

Set by parameter n40(during running)

Relay output1 A max. at 30 V DC

MB Multi-function contactoutput (Normally closed)

( g g) 30 C1 A max. at 250 V AC

MC Multi-function contactoutput common

Common for MA andMB use

AM Analog monitor output Set by parameter n44(Output frequency)

2 mA max. at 0 to 10 V DC

AC Analog monitor outputcommon

Common for AM use

Note 1. Depending on the parameter settings, various functions can be selected for multi-function in-puts and multi-function contacts outputs.

Note 2. Functions in parentheses are default settings.

Selecting Input Method• Switches SW7 and SW8, both of which are located above the control circuit terminals, are used for

input method selection.Remove the front cover and optional cover to use these switches.

Selector

Control circuit terminalblock

Design Chapter 1

Page 23: Setup Manual 3G3JV

1-9

Selecting Sequence Input Method• By using SW7, NPN or PNP input can be selected as shown below.

SW7

SW7

Selecting Frequency Reference Input MethodFrequency reference input

methodSW8 setting Frequency reference selection

(parameter n03)Voltage input V (OFF) Set value 2

Current input I (ON) Set value 3 or 4

Design Chapter 1

Page 24: Setup Manual 3G3JV

1-10

1-2-2 Standard Connections

DC reactor(optional)

Noise Filter

Single-phase 100 V AC

Forward/Stop

Multi-function input 1 (Reserve/Stop)

Multi-function input 2 (S3) (Fault Reset)Multi-function input 3 (S4) (External faultNormally open)Multi-function input 4 (S5) (Multi-step speedreference 1)

Sequence input common

Frequency reference powersupply 20 mA at +12 V

FREQadjuster

Frequency reference input

Frequency reference common

Multi-function contact outputNO

NC

Common

Analog monitor output

Analog monitor output common

(2 kΩ, 1/4 W min.)

3-phase 200 V AC

Note 1. The braking resistor cannot be connected because no braking transistor is incorporated.

Note 2. A DC Reactor can be connected in series between the R input and L1 terminal or between theS input and L2 terminal to use it as an AC reactor.

DC Reactor Wiring Example

Noise FilterDC Reactor

Single-phase 100 V AC

Applicable Noise FiltersInverter Applicable Filter Specifications

3G3JV-A1001 3G3JV-PRS1010J (f i h 0 1 kW 0 2 kW)

10 A at 250 V AC, single-phase

3G3JV-A1002 (for either 0.1 kW or 0.2 kW), g p

Applicable DC ReactorsInverter Applicable Reactor Specifications

3G3JV-A1001 3G3HV-PUZDAB5.4A8MH 5.4 A, 8 mH

3G3JV-A1002 3G3HV-PUZDAB18A3MH 18 A, 3 mH

Design Chapter 1

Page 25: Setup Manual 3G3JV

1-11

Example of 3-wire Sequence Connections

Stopswitch(NC)

RUNswitch(NO)

Direction switch

RUN input (Operates with the stop switch and RUN switch closed.)

Stop input (Stops with the stop switch opened.)

Forward/Stop reference (Forward with the direction switch openedand reverse with the direction switch closed.)

Sequence input common

Note Set parameter n37 for 3-wire sequence input.

1-2-3 Wiring around the Main Circuit

Wire Size, Terminal Screw, Screw Tightening Torque, and Molded-caseCircuit Breaker Capacities

• For the main circuit and ground, always use 600-V polyvinyl chloride (PVC) cables.

• If any cable is long and may cause voltage drops, increase the wire size according to the cable length.

Single-phase 100-V AC ModelModel3G3JV-

Terminal symbol Terminalscrew

Screwtightening

torque(Nm)

Wire size(mm2)

Recommendedwire size (mm2)

A1001 R/L1, S/L2, U/T1, V/T2, W/T3 M3.5 0.8 to 1.0 0.75 to 2 2

A1002 R/L1, S/L2, U/T1, V/T2, W/T3 M3.5 0.8 to 1.0 0.75 to 2 2

Wiring

Control CircuitTerminal symbol Terminal

screwScrew tighteningtorque Nm (lbin)

Wire size mm2 (AWG)

Recommendedwire size

mm2 (AWG)MA, MB, MC M3 0.5 to 0.6 (4.4 to 5.3) Stranded wire:

0.5 to 1.25 (20 to 16)

Single wire:0.5 to 1.25 (20 to 16)

0.75 (18)

S1 to S5, SC, FS,FR, FC, AM, AC

M2 0.22 to 0.25 (2 to 2.2) Stranded wire:0.5 to 0.75 (20 to 18)

Single wire:0.5 to 1.25 (20 to 16)

0.75 (18)

Design Chapter 1

Page 26: Setup Manual 3G3JV

1-12

1-2-4 Optional AccessoriesOption Specifications Model

EMC-compliantN i Fil

For A1001 3G3JV-PRS1010JpNoise Filter For A1002DC Reactor For A1001 3G3HV-PUZDAB5, 4A8MH

For A1002 3G3HV-PUZDAB18A3MH

DIN Track Mounting Bracket --- 3G3IV-PEZZ08122AAdapter Panel Standard installation 3G3JV-PSI232Jp

Removable 3G3JV-PSI232JCOperator Cable 1 m 3G3IV-PCN126p

3 m 3G3IV-PCN326Digital Operator Without adjuster (with case) 3G3IV-PJVOP146g p

With adjuster Main Unit 3G3IV-PJVOP140j

Case 3G3IV-PEZZ08386

Design Chapter 1

Page 27: Setup Manual 3G3JV

1-13

1-3 Specifications

100-V AC Models 3G3JV-A1001 3G3JV-A1002Power

lRated voltage and power supply Single-phase 100 to 115 V AC at 50/60 Hz

supply Allowable voltage fluctuation –15 to 10%Allowable frequency fluctuation ±5%Input current (for rated output) (A) 3.2 6.2

Heating radiation (W) 14.6 21.1

Weight (kg) 0.5 0.8

Cooling method Natural cooling

Maximum motor capacity (kW) 0.1 0.2Output

ifiRated output capacity (kVA) 0.3 0.6p

specifica-tions

Rated output current (A) 0.8 1.6tions

Rated output voltage (V) Three-phase 200 to 230 V (Handles twice the input volt-age.)

Maximum output frequency 400 Hz (Set in a parameter.)Controlcharacter-

Power supply harmonics counter-measures

DC Reactor (optional) can be connected.

istics Control method Sine wave PWM (V/f control)Carrier frequency 2.5 to 10.0 kHz (Switched in steps.)

Frequency control range 0.1 to 400 HzFrequency precision (tempera-

h i i )Digital reference: ±0.01% (–10 to 50°C)q y p ( p

ture characteristics) Analog reference: ±0.5% (25°C ±10°C)Frequency setting resolution Digital reference: 0.1 Hz (less than 100 Hz), 1 Hz (100 Hz

or greater)Analog reference: 0.06 Hz/60 Hz (equivalent to 1/1000)

Output frequency resolution 0.01 Hz (data processing resolution)Overload capacity 150% of rated output current for 1 minExternal frequency set signal Switchable: 0 to 10 V DC (20 kΩ), 4 to 20 mA (250 Ω), 0 to

20 mA (250 Ω), or frequency adjustmentAcceleration/deceleration times 0.0 to 999 s (Acceleration and deceleration times set sepa-

rately: Switches between 2 settings.)Braking torque Approx. 20%

Note: A Braking Resistor or Braking Resistor Unit cannot beconnected.

Voltage/frequency characteristics User-set V/f pattern

Design Chapter 1

Page 28: Setup Manual 3G3JV

1-14

3G3JV-A10023G3JV-A1001100-V AC ModelsProtectivef i

Motor protection Protection by electronic thermalfunctions Instantaneous overcurrent

protectionStops at approx. 250% of rated output current.

Overload protection Stops in 1 min at approximately 150% of rated output cur-rent.

Overvoltage protection Stops when main-circuit DC voltage is approximately 410 V.Undervoltage protection Stops when main-circuit DC voltage is approximately 160 V.Momentary power interruptioncompensation (selection)

None (Stops at 15 ms or longer.)Select between continuing operation if power is restoredwithin approx. 0.5 s or continuing operation regardless oflength of interruption.

Radiation fin overheated Detected at 110°C ±10°CGrounding protection Rated output current level protectionCharge indicator CHARGE indicator lights until the main circuit DC voltage

reaches 50 V or less.Environ- Location Indoors (with no corrosive gas, dust, etc.)ment Ambient operating temperature –10 to 50°C

Ambient operating humidity 95% max. (with no condensation)Storage temperature –20 to 60°CAltitude 1,000 m max.Insulation resistance 5 MΩ min. (Do not carry out any insulation resistance or

withstand voltage tests.)Vibration resistance 9.8 m/s2 max. between 10 and 20 Hz, 2.0 m/s2 max. be-

tween 20 and 50 HzDegree of protection Mounted in a panel (equivalent to IP20)

Design Chapter 1

Page 29: Setup Manual 3G3JV

Chapter 2

Preparing forOperation andMonitoring

2-1 Using the Digital Operator

2-2 Copying and Verifying Parameters

2

Page 30: Setup Manual 3G3JV

2-2

2-1 Using the Digital Operator

2-1-1 Nomenclature

Data display

Keys

IndicatorsSetting/Monitor item indicators

FREQ adjuster

Appearance Name FunctionData display Displays relevant data items, such as frequency reference,

output frequency, and parameter set values.

FREQ adjuster Sets the frequency reference within a range between 0 Hzand the maximum frequency.

FREF indicator The frequency reference can be monitored or set while thisindicator is lit.

FOUT indicator The output frequency of the Inverter can be monitoredwhile this indicator is lit.

IOUT indicator The output current of the Inverter can be monitored whilethis indicator is lit.

MNTR indicator The values set in U01 through U10 are monitored whilethis indicator is lit.

F/R indicator The direction of rotation can be selected while thisindicator is lit, when operating the Inverter with the RUNKey.

LO/RE indicator The operation of the Inverter through the Digital Operatoror according to the parameters set is selectable while thisindicator is lit.

Note This status of this indicator can be only monitoredwhile the Inverter is in operation. Any RUN commandinput is ignored while this indicator is lit.

PRGM indicator The parameters in n01 through n79 can be set ormonitored while this indicator is lit.

Note While the Inverter is in operation, the parameters canbe only monitored and only some parameters can bechanged. The RUN command input is ignored whilethis indicator is lit.

Mode Key Switches the setting and monitor item indicators insequence.

Parameter setting being made is canceled if this key ispressed before entering the setting.

Increment Key Increases multi-function monitor numbers, parameternumbers, and parameter set values.

Preparing for Operation and Monitoring Chapter 2

Page 31: Setup Manual 3G3JV

2-3

Appearance FunctionNameDecrement Key Decreases multi-function monitor numbers, parameter

numbers, and parameter set values.

Enter Key Enters multi-function monitor numbers, parameternumbers, and internal data values after they are set orchanged.

RUN Key Starts the Inverter running when the 3G3FV is in operationwith the Digital Operator.

STOP/RESET Key Stops the Inverter unless n06 is set to disable the STOPKey. Functions as a Reset Key when an Inverter erroroccurs. (See note.)

Note For safety’s reasons, the reset will not work while a RUN command (forward or reverse) is in ef-fect. Wait until the RUN command is OFF before resetting the Inverter.

Preparing for Operation and Monitoring Chapter 2

Page 32: Setup Manual 3G3JV

2-4

2-1-2 Accepting Operation Commands While ChangingParameters

With the default settings, the Inverter will not accept operation commands when param-eter settings are being changed. This functions as a safety measure to prevent the motorfrom rotating if the operation command is mistakenly set to ON when changing parame-ters.Depending on the operating conditions, however, the user may want to have operationcommands accepted even while parameters are being changed. In that case, changethe following settings.

Using the Indicators to Determine When Operation Commands Can BeAccepted

The indicators on the Digital Operator can be used to determine if operation commands will be acceptedor not while changing parameters.

Green: Operation commands will be accepted if the indicator lights green.

Red: Operation commands will not be accepted after the Inverter stops if an indicator lights red.

Therefore, if the indicator lights red when changing parameters or when switching between local andremote operation, operation will continue, but once the Inverter stops, the Inverter will not operate evenif the operation command is set to ON again.

The FREF indicator will light when the power supply is turned ON.

Indicator Color Name Acceptance of operationcommands

Duringoperation

Stopped

FREF Green Frequency Reference/Monitor Yes Yes

FOUT Green Output Frequency MonitorIOUT Green Output Current MonitorMNTR Green Multi–function MonitorF/R Green Operator RUN command forward/reverse

operation selectionLO/RE Red Local/Remote Selection Yes No (See note.)

PRGM Red Parameter Number/Setting

( )

Note Perform the settings given in the following description to have operation commands acceptedwhile the red indicator is lit (i.e., while changing parameters or switching between local and re-mote.)

Set n01 (Parameter write–prohibit selection/parameter initialization) to 5.

The default value for n01 is 1.

Operation commands will not be accepted when n01 itself is being changed.

Some parameters cannot be changed during operation. Those parameters cannot be changedduring operation even if the setting for n01 is changed.

When n01 is changed to 5, an operation command will be accepted even when changing pa-rameters, such as during trial operation. Thoroughly check safety before changing any setting.

Preparing for Operation and Monitoring Chapter 2

Page 33: Setup Manual 3G3JV

2-5

2-1-3 Outline of Operation

Selecting Indicators

Whenever the Mode Key is pressed, an indicator is lit in sequence beginning with theFREF indicator. The data display indicates the item corresponding to the indicator se-lected.The FOUT or IOUT indicator will be lit by turning the Inverter on again if the Inverter isturned off while the FOUT or IOUT indicator is lit. The FREF indicator will be lit by turningthe Inverter on again if the Inverter is turned off while an indicator other than the FOUR orIOUT indicator is lit.

Power On

FREF (Frequency Reference)Monitors and sets the frequency reference.

FOUT (Output Frequency)Monitors the output frequency.Note This indicator will be lit by turning the Inverter on again if the Inverter

is turned off while this indicator is lit.

IOUT (Output Current)Monitors the output current.Note This indicator will be lit by turning the Inverter on again if the Inverter

is turned off while this indicator is lit.

MNTR (Multi-function Monitor)Monitors the values set in U01 through U10.

F/R (Forward/Reverse Rotation)Selects the direction of rotation.

LO/RE (Local/Remote)Selects the operation of the Inverter through the Digital Operator oraccording to the parameters.

PRGM (Parameter Setting)Monitors or sets the values in n01 through n79.

The FREF indicator is lit again.

Preparing for Operation and Monitoring Chapter 2

Page 34: Setup Manual 3G3JV

2-6

Example of Multi-function Display

Key sequence Indicator Display ExplanationPower On

Press the Mode Key repeatedly until the MNTRindicator is lit.

U01 will be displayed.Use the Increment or Decrement Key to select themonitor item to be displayed.Press the Enter Key so that the data of the selectedmonitor item will be displayed.The monitor number display will appear again bypressing the Mode Key.

Status MonitorItem Display Display

unitFunction

U01 Frequencyreference

Hz Monitors the frequency reference. (Same as FREF)

U02 Output frequency Hz Monitors the output frequency. (Same as FOUT)

U03 Output current A Monitors the output current. (Same as IOUT)

U04 Output voltage V Monitors the internal output voltage reference value of theInverter.

U05 DC bus voltage V Monitors the DC voltage of the internal main circuit of theInverter.

U06 Input terminal --- Shows the ON/OFF status of inputs.pstatus

: Input ON : No input

Notused

Terminal S1: Forward/StopTerminal S2: Multi-function input 1 (S2)Terminal S3: Multi-function input 2 (S3)Terminal S4: Multi-function input 3 (S4)Terminal S5: Multi-function input 4 (S5)

U07 Output terminal --- Shows the ON/OFF status of outputs.pstatus

: Closed : Open

Notused

Terminal MA: Multi-function contactoutput

U09 Error log (most)

--- Displays the latest error.g (recent one)

Error

U10 Software No. --- OMRON use only.

U15 Receive data error --- The cause of the receive data error during MEMOBUScommunications can be checked. (Same as the contents ofcommunications register number 003DM.)

Preparing for Operation and Monitoring Chapter 2

Page 35: Setup Manual 3G3JV

2-7

2-2 Copying and Verifying Parameters

The 3G3IV-PJVOP140 and 3G3IV-PJOP146 Digital Operators contain an EEPROM. All Inverter parameter settings, the Inverter capacity, and the software number are re-corded in this EEPROM. The EEPROM can be used to copy parameter settings to otherInverters.Parameter settings can be copied between Inverters with the same power supply speci-fications, but some of the parameter settings are not copied.

2-2-1 Parameters Used to Copy and Verify Parameters• The following parameters are used to read, copy (write), and verify parameter settings.

Param-eterNo.

(Regis-ter No.(Hex))

Name Description Settingrange

Settingunit

Defaultsetting

Changesduringopera-

tion

n76(014C)

Parametercopy andverify func-tion

Selects the function for copying parameters.

rdy: Ready to accept the next command.

rED: Reads the Inverter parameters.

Cpy: Copies the parameter to the Inverter.

vFY: Verifies the Inverter parameters.

vA: Checks the Inverter capacity display.

Sno: Checks the software number.

rdy toSno

--- rdy No

n77(014D)

Parameterread pro-hibit selec-tion

Selects the copy-prohibit function.

Use this parameter to protect the data in theEEPROM of the Digital Operator.

0: Read prohibited for Inverter parameters.(Data cannot be written to EEPROM.)

1: Read possible for Inverter parameters.(Data can be written to EEPROM.)

0, 1 --- 0 No

Preparing for Operation and Monitoring Chapter 2

Page 36: Setup Manual 3G3JV

2-8

Display Transitions

ReadingReadingfinished

WritingWritingfinished

VerifyingVerificationfinished

Inverter capacity

OR

Software number

OR

OR

OR

OR

Note The following display is an example of the capacity displayed. The values in parentheses indicatethe capacities for European motors.

Voltage Class

1: Single-phase 100 V

Max. applicable motor capacity

0.1: 0.1 kW (0.1 kW)0.2: 0.25 kW/0.37 kW (0.2 kW)

Note The values in parentheses indicate Japanese motor capacities.

Preparing for Operation and Monitoring Chapter 2

Page 37: Setup Manual 3G3JV

2-9

2-2-2 Outline of Copying Parameters

(1) Check setting of n01

0: Writing from Digital Operator prohibited.1: Parameters can be changed (default setting).

(2) Clear prohibition of reading the copy function: n77This function protects parameters stored in the DigitalOperator.

0: Reading copy function (rEd) prohibited (default setting).1: Reading copy function (rEd) enabled.

(3) Perform the read operation for the copy function: n76

Read (rEd) the current parameter settings from the Inverterto the EEPROM in the Digital Operator.

(4) Disconnect the Digital Operator and connect it to adifferent Inverter. Always turn OFF the power supplybefore connecting or disconnecting the Digital Operatorto protect against electric shock and product failure.

(5) Perform the write operation for the copy function: n76

Write (CPy) the current parameter settings from the EE-PROM in the Digital Operator to the Inverter.

(6) Perform the verify operation for the copy function: n76

Verify (vFy) the current parameter settings between theEEPROM in the Digital Operator and the Inverter.

See operation on next page.

Same basic operation as for n01.

Set n01 to 1.

Set n77 to 1.

Set n76 to rEd.

Set n76 to CPy.

Set n76 to vFy.

Change Inverter connection.Turn ON power after check-ing wiring.

Parameters That Cannot Be Copied1. Copying is not possible between Inverters with different power supply specifications (e.g., from a

100-V Inverter to a 400-V Inverter).

2. The recorded hold output frequency and the following parameters cannot be copied:n76: Parameter copy and verify functionn77: Parameter read prohibit selectionn78: Error logn79: Software number

3. The following parameters cannot be copied if the Inverters have different capacities.n09 to n15: V/f settingsn32: Rated motor currentn46: Carrier frequency selection

Preparing for Operation and Monitoring Chapter 2

Page 38: Setup Manual 3G3JV

2-10

n64: Motor rated slipn65: Motor no-load current

2-2-3 Procedures

Changing ParametersThe setting of n01 is changed so that n76 and n77 can be displayed.

Setting n01 (Parameter Write-prohibit Selection/Parameter Initialization Parameter)Key Indicator Display Description

--- (Display after the power supply is turned ON.)

Press the Mode Key until the PRGM indicator lights. Confirm that n01 is displayed on the data display.

Press the Enter Key. The setting of the specified parameter number will bedisplayed.

Press the Increment Key until 4 is displayed. (The display willflash.)

Press the Enter Key to confirm the setting. (The display willstop flashing.)

After about 1 s The display of the parameter number will return in about 1 s.

Preparing for Operation and Monitoring Chapter 2

Page 39: Setup Manual 3G3JV

2-11

Example of Copy Function

Verifying Parameters (vFy)• The Parameter Copy and Verify Function (n76) can be set to “vFy” to compare the parameter settings

in the Digital Operator with those in the Inverter.

Verifying ParametersKey Indicator Display Description

--- (Display after the power supply is turned ON.)

Press the Mode Key until the PRGM indicator lights. Confirm that n01 is displayed on the data display.

Press the Increment/Decrement Key until “n76” isdisplayed.

Press the Enter Key. “rdy” will be displayed.

Press the Increment Key until “vFy” is displayed

Press the Enter Key. The parameter settings will becompared and the display will flash.

The parameter number of any parameter that has differentsettings will be displayed.

Press the Enter Key. The setting of the parameter in the Inverter will be displayed(flashing) first.

Press the Enter Key again. The setting of the parameter in the Digital Operator will bedisplayed (flashing) next.

Press the Increment Key. The comparison will be continued.

(Aftercomparison isfinished.)

“End” will be displayed when the comparison has beenfinished.

or Press the Mode Key or Enter Key. The display of the parameter number will return.

Preparing for Operation and Monitoring Chapter 2

Page 40: Setup Manual 3G3JV

2-12

2-2-4 Error Messages for Copying and Verifying ParametersThe errors that can be displayed when reading, writing, or verifying parameter settings are described inthe following table along with corrective actions. All of these error displays will flash on the display.

Display Name Description Corrective action Protect error An attempt was made to read

parameter settings when theParameter Read Prohibit Selectionparameter (n77) was set to 0(prohibiting reading).

Confirm that it is necessary to readthe parameter settings. If it is, changethe Parameter Read ProhibitSelection parameter (n77) to 1(enabling reading).

Read error The parameter settings could not beread normally or a low main circuitvoltage was detected while readingparameter settings.

Check the main circuit voltage andthen attempt reading again.

Checksum error A checksum error occurred for theparameters recorded in the DigitalOperator.

Read the parameter settings again torecord them in the Digital Parameter.

No data error No parameters are recorded in theDigital Operator.

Read the parameter settings to recordthem in the Digital Parameter.

Copy sourceerror

Copying or verifying parametersettings was attempted betweenInverters with different voltageclasses.

Check the voltage classes. (Theymust both be the same to copyparameter settings.)

Voltage errorwhile copying

A low main circuit voltage wasdetected while reading parametersettings.

Check the main circuit voltage andthen attempt copying again.

Capacity error Verification was attempted betweenInverters of different capacities.

Press the Enter Key to continue thecomparison.

Press the STOP/RESET Key tocancel the comparison.

Communicationserror

A communications error occurredbetween the Inverter and DigitalOperator.

Check the connection between theInverter and the Digital Operator.Correct any problems and then repeatthe operation.

Preparing for Operation and Monitoring Chapter 2

Page 41: Setup Manual 3G3JV

Chapter 3

List of Parameters

3

Page 42: Setup Manual 3G3JV

3-2

ParameterNo. (Reg-ister No.

(Hex))

Name Description Settingrange

Defaultsetting

Changesduringopera-

tion

Memo

n01

(0101)

Parame-terwrite-prohibitselec-tion/parame-ter ini-tializa-tion

Used to prohibit parameters to bewritten, sets parameters, or changethe monitor range of parameters.

Used to initialize parameters todefault values.

0: Sets or monitors parameter n01.Parameters n02 through n79 canbe monitored only.

1: Sets or monitors parameters n01through n79.

5: Operation commands can be ac-cepted at any time (n01 to n79 canbe set or referenced). (See note.)

6: Clears the error log.

8: Initializes parameters to defaultvalues in 2-wire sequence.

9: Initializes parameters to defaultvalues in 3-wire sequence.

Note Operation commands will be ig-nored in Program Mode (referto 2-1-2) when n01 is set to 0 or1. Normally set n01 to 0 or 1.

0, 1, 6, 8,9

1 No

n02

(0102)

Opera-tioncom-mandselec-tion

Used to select the input method forthe RUN and STOP commands inremote mode.

0: The RUN and STOP/RESET Keyson the Digital Operator are en-abled.

1: Multi-function inputs through thecontrol circuit terminals in 2- or3-wire sequence.

2: Operation commands viaRS-422A/485 communications areenabled.

Note The RUN command onlythrough key sequences on theDigital Operator is acceptablein local mode.

0 to 2 0 No

List of Parameters Chapter 3

Page 43: Setup Manual 3G3JV

3-3

ParameterNo. (Reg-ister No.

(Hex))

MemoChangesduringopera-

tion

Defaultsetting

Settingrange

DescriptionName

n03

(0103)

Fre-quencyrefer-enceselec-tion

Used to set the input method for thefrequency reference in remote mode.

0: Digital Operator

1: Frequency reference 1 (n21)

2: Frequency reference control circuitterminal (0 to 10 V)

3: Frequency reference control circuitterminal (4 to 20 mA)

4: Frequency reference control circuitterminal (0 to 20 mA)

6: Frequency reference viaRS-422A/485 communications

0 to 4, 6 0 No

n04

(0104)

Interrup-tionmodeselec-tion

Used to set the stopping method foruse when the STOP command is in-put.

0: Decelerates to stop in preset time.

1: Coasts to stop (with output shut offby the STOP command)

0, 1 0 No

n05

(0105)

Reverserotation-prohibitselec-tion

Used to select the operation with thereverse command input.

0: Reverse enabled.

1: Reverse disabled.

0, 1 0 No

n06

(0106)

STOP/RESETKeyfunctionselec-tion

Used to select the stop method in re-mote mode with n02 for operationmode selection set to 1.

0: STOP/RESET Key of the DigitalOperator enabled.

1: STOP/RESET Key of the DigitalOperator enabled only when theDigital Operator is selected for theRUN command.

0, 1 0 No

n07

(0107)

Fre-quencyselec-tion inlocalmode

Used to set the input method for thefrequency reference in local mode.

0: The FREQ adjuster of the DigitalOperator enabled.

1: Key sequences on the Digital Op-erator enabled.

0, 1 0 No

n08

(0108)

Key se-quentialfrequen-cy set-ting

Used to enable the Enter Key for set-ting the frequency reference with theIncrement and Decrement Keys.

0: The value is entered with the En-ter Key pressed.

1: The value is enabled when thevalue is input.

0, 1 0 No

List of Parameters Chapter 3

Page 44: Setup Manual 3G3JV

3-4

ParameterNo. (Reg-ister No.

(Hex))

MemoChangesduringopera-

tion

Defaultsetting

Settingrange

DescriptionName

n09

(0109)

Maxi-mumfrequen-cy(FMAX)

Used to set the V/f pattern as the ba-sic characteristic of the Inverter withoutput voltage per frequency set.

50.0 to400

60.0 No

n10

(010A)

Maxi-mumvoltage(VMAX)

Outputvoltage

n10(VMAX)

n13

1 to 255 200 No

n11

(010B)

Maxi-mumvoltagefrequen-cy (FA)

Fre-quency(Hz)

n13(VC)

n15(VMIN)

0 n14(FMIN)

n12(FB)

n11(FA)

n09(FMAX)

0.2 to 400 60.0 No

n12

(010C)

Middleoutputfrequen-cy (FB)

Note Set the parameters so thatthe following condition will besatisfied.14 12 11 09

( ) ( ) ( ) ( )

0.1 to 399 1.5 No

n13

(010D)

Middleoutputfrequen-cy volt-age(VC)

n14 n12 < n11 n09

Note The value set in n13 will beignored if parameters n14 andn12 are the same in value.

1 to 255 12 No

n14

(010E)

Mini-mumoutputfrequen-cy(FMIN)

0.1 to 10.0 1.5 No

n15

(010F)

Mini-mumoutputfrequen-cy volt-age(VMIN)

1 to 50(see note2)

12.0 No

n16

(0110)

Accel-erationtime 3

Acceleration time: The time requiredto go from 0% to 100% of the maxi-mum frequency.

Deceleration time: The time required

0.0 to 999 10.0 Yes

n17

(0111)

Decel-erationtime 3

Deceleration time: The time requiredto go from 100% to 0% of the maxi-mum frequency.Note The actual acceleration or de-

10.0 Yes

n18

(0112)

Accel-erationtime 4

celeration time is obtainedfrom the following formula.Acceleration/Deceleration time= (Acceleration/Deceleration

10.0 Yes

n19

(0113)

Decel-erationtime 4

= (Acceleration/Decelerationtime set value) × (Frequencyreference value) ÷ (Max. fre-quency)

10.0 Yes

List of Parameters Chapter 3

Page 45: Setup Manual 3G3JV

3-5

ParameterNo. (Reg-ister No.

(Hex))

MemoChangesduringopera-

tion

Defaultsetting

Settingrange

DescriptionName

n20

(0114)

S-shapeaccel-eration/decel-erationcharac-teristic

Used to set S-shape acceleration/de-celeration characteristics.

0: No S-shape acceleration/decelera-tion (trapezoidal acceleration/de-celeration)

1: S-shape acceleration/decelerationcharacteristic time 0.2 s

2: S-shape acceleration/decelerationcharacteristic time 0.5 s

3: S-shape acceleration/decelerationcharacteristic time 1.0 s

Note When the S-shape accelera-tion/deceleration characteristictime is set, the accelerationand deceleration times will belengthened according to theS-shape at the beginning andend of acceleration/decelera-tion.

0 to 3 0 No

List of Parameters Chapter 3

Page 46: Setup Manual 3G3JV

3-6

ParameterNo. (Reg-ister No.

(Hex))

MemoChangesduringopera-

tion

Defaultsetting

Settingrange

DescriptionName

n21

(0115)

Fre-quencyrefer-ence 1

Used to set internal frequency refer-ences.Note Frequency reference 1 is en-

abled in remote mode with

0.0 to max.frequency

6.0 Yes

n22

(0116)

Fre-quencyrefer-ence 2

abled in remote mode withn03 for frequency referenceselection set to 1.

Note These frequency referencesare selected with multi-step

0.0 Yes

n23

(0117)

Fre-quencyrefer-ence 3

are selected with multi-stepspeed references (multi-func-tion input).

0.0 Yes

n24

(0118)

Fre-quencyrefer-ence 4

0.0 Yes

n25

(0119)

Fre-quencyrefer-ence 5

0.0 Yes

n26

(011A)

Fre-quencyrefer-ence 6

0.0 Yes

n27

(011B)

Fre-quencyrefer-ence 7

0.0 Yes

n28

(011C)

Fre-quencyrefer-ence 8

0.0 Yes

n29

(011D)

Inchingfrequen-cy com-mand

Used to set the inching frequencycommand.Note The inching frequency com-

mand is selected with theinching command (multi-func-tion input). The inching fre-quency command takes pre-cedence over the multi-stepspeed reference.

6.0 Yes

List of Parameters Chapter 3

Page 47: Setup Manual 3G3JV

3-7

ParameterNo. (Reg-ister No.

(Hex))

MemoChangesduringopera-

tion

Defaultsetting

Settingrange

DescriptionName

n30

(011E)

Fre-quencyrefer-enceupperlimit

Used to set the upper and lower fre-quency reference limits in percent-age based on the maximum frequen-cy as 100%.Note If n31 is set to a value less

than the minimum output fre-

0 to 110 100 No

n31

(011F)

Fre-quencyrefer-encelowerlimit

than the minimum output fre-quency (n14), the Inverter willhave no output when a fre-quency reference less thanthe minimum output frequencyinput is input.

0 to 110 0 No

n32

(0120)

Ratedmotorcurrent

Used to set the rated motor currentfor motor overload detection (OL1)based on the rated motor current.Note Motor overload detection

(OL1) is disabled by settingthe parameter to 0.0.

Note The rated motor current isdefault to the standard ratedcurrent of the maximum appli-cable motor.

0.0 to120% ofrated out-put currentof the In-verter.

Varies withthe capac-ity.

No

n33

(0121)

Motorprotec-tioncharac-teristics

Used to set the motor overloaddetection (OL1) for the electronicthermal characteristics of the motor.

0: Protection characteristics for gen-eral-purpose induction motors

1: Protection characteristics for in-verter-dedicated motors

2: No protectionNote If a single Inverter is con-

nected to more than one mo-tor, set the parameter to 2 forno protection. The parameteris also disabled by setting n32for rated motor to 0.0.

0 to 2 0 No

List of Parameters Chapter 3

Page 48: Setup Manual 3G3JV

3-8

ParameterNo. (Reg-ister No.

(Hex))

MemoChangesduringopera-

tion

Defaultsetting

Settingrange

DescriptionName

n34

(0122)

Motorprotec-tive timesetting

Used to set the electric thermal char-acteristics of the motor to be con-nected in 1-minute increments.Note The default setting does not

require any changes in normaloperation.

Note To set the parameter accord-ing to the characteristics of themotor, check with the motormanufacturer the thermal timeconstant and set the parame-ter with some margin. In otherwords, set the value slightlyshorter than the thermal timeconstant.

Note To detect motor overloadingquicker, reduce the set value,provided that it does not causeany application problems.

1 to 60 8 No

n35

(0123)

Coolingfan op-erationfunction

Used to operate the Cooling Fan ofthe Inverter while the Inverter isturned on or only while the Inverter isin operation.

0: Rotates only while RUN commandis input and for 1 minute after In-verter stops operating

1: Rotates while Inverter is turned onNote This parameter is available

only if the Inverter incorpo-rates a Cooling Fan.

Note If the operation frequency ofthe Inverter is low, the life ofthe fan can be prolonged bysetting the parameter to 0.

0, 1 0 No

List of Parameters Chapter 3

Page 49: Setup Manual 3G3JV

3-9

Param-eterNo.

(Regis-ter No.(Hex))

Name Description Set-ting

range

Defaultsetting

Changesduringopera-

tion

Memo

n36

(0124)

Multi-func-tion input 1

Used to select the functions of multi-functioninput terminals S2 through S5.

2 to 8,10 to

2 No

(0124) p(Input ter-minal S2)

Setval-ue

Function Description0

22

n37

(0125)

Multi-func-tion input 2(Input ter-minal S3)

0 Forward/Reverserotationcommand

3-wire sequence (to beset in n37 only)

By setting n37 to 0, theset value in n36 is ig-nored and the followingsetting are forcibly made

0, 2 to8, 10to 22

5 No

n38

(0126)

Multi-func-tion input 3(Input ter-minal S4)

setting are forcibly made.S1: RUN input (RUNwhen ON)S2: STOP input (STOPwhen OFF)S3: Forward/Reverse

t ti d (OFF

2 to 8,10 to22

3 No

n39

(0127)

Multi-func-tion input 4

rotation command (OFF:Forward; ON: Reverse)

2 to 8,10 to

6 No

(0127) tion input 4(Input ter-minal S5)

2 Reverse/Stop

Reverse rotation com-mand in 2-wire sequence(Reversed with the termi-nal turned ON)

10 to22,34, 35

3 Externalfault (NO)

ON: External fault (FPdetection: is a terminalnumber)

4 Externalfault (NC)

OFF: External fault (EFdetection: is a terminalnumber)

5 Fault reset ON: Fault reset (disabledwhile RUN command isinput)

6 Multi-stepspeed ref-erence 1

Signals to select frequen-cy references 1 through8.

7 Multi-stepspeed ref-erence 2

8 Multi-stepspeed ref-erence 3

10 Inching fre-quencycommand

ON: Inching frequencycommand (taking prece-dence over the multi-stepspeed reference)

11 Accelera-tion/Decel-eration timechangeover

ON: Acceleration time 2and deceleration time 2are selected.

List of Parameters Chapter 3

Page 50: Setup Manual 3G3JV

3-10

Param-eterNo.

(Regis-ter No.(Hex))

MemoChangesduringopera-

tion

Defaultsetting

Set-ting

range

DescriptionName

n39

(0127)

Multi-func-tion input 4(Input ter-minal S5)

12 Externalbase blockcommand(NO)

ON: Output shut off(while motor coasting to astop and “bb” flashing)

2 to 8,10 to22,34, 35

6 No

)

13 Externalbase blockcommand(NC)

OFF: Output shut off(with motor free runningand “bb” flashing)

14 Searchcommand(Searchingstarts frommaximumfrequency)

ON: Speed search(Searching starts fromn09)

15 Searchcommand(Searchingstarts frompreset fre-quency)

ON: Speed search

16 Accelera-tion/Decel-eration-pro-hibit com-mand

ON: Acceleration/Decel-eration is on hold (run-ning at parameter fre-quency)

17 Local or re-mote selec-tion

ON: Local mode (oper-ated with the Digital Op-erator)

18 Commu-nications orremoteselection

ON: RS-422A/485 com-munications input isenabled.OFF: The settings of n02and n03 are enabled.

List of Parameters Chapter 3

Page 51: Setup Manual 3G3JV

3-11

Param-eterNo.

(Regis-ter No.(Hex))

MemoChangesduringopera-

tion

Defaultsetting

Set-ting

range

DescriptionName

n39

(0127)

Multi-func-tion input 4(Input ter-minal S5)

19 Emergencystop fault(NO)

The Inverter stops ac-cording to the setting inn04 for interruption modeselection with the emer-gency stop input turned

2 to 8,10 to22,34, 35

6 No

20 Emergencystop alarm(NO)

gency stop input turnedON.

NO: Emergency stop withthe contact closed.NC: Emergency stop with

21 Emergencystop fault(NC)

g y pthe contact opened.

Fault: Fault output is ONand reset with RESETinput. Alarm output is ON(no reset required)

22 Emergencystop alarm(NC)

(no reset required).

“STP” is displayed (litwith fault input ON andflashes with alarm inputON)

34 Up or downcommand

Up or down command(set in n39 only)

By setting n39 to 34, theset value in n38 is ig-nored and the followingsetting are forcibly made.S4: Up commandS5: Down command

35 Self-diag-nostic test

ON: RS-422A/485 com-munications self-diagnos-tic test (set in n39 only)

List of Parameters Chapter 3

Page 52: Setup Manual 3G3JV

3-12

Param-eterNo.

(Regis-ter No.(Hex))

MemoChangesduringopera-

tion

Defaultsetting

Set-ting

range

DescriptionName

n40

(0128)

Multi-func-tion output

Used to select the functions of multi-functionoutput terminals.

0 to 7,10 to

1 No

(0128) p(MA/MBand MCoutput ter-minals)

Setval-ue

Function Description0

18

minals)0 Fault output ON: Fault output (with

protective function work-ing)

1 Operationin progress

ON: Operation in prog-ress

2 Frequencydetection

ON: Frequency detection(with frequency referencecoinciding with output fre-quency)

3 Idling ON: Idling (at less thanmin. output frequency)

4 Frequencydetection 1

ON: Output frequency frequency detection level(n58)

5 Frequencydetection 2

ON: Output frequency frequency detection level(n58)

6 Overtorquebeing moni-tored (NO-contact out-put)

Output if any of the fol-lowing parameter condi-tions is satisfied.

n59: Overtorque detec-tion function selection

n60: Overtorque detec-tion level

61 O d7 Overturebeing moni-tored (NC-contact out-put)

n61: Overtorque detec-tion time

NO contact: ON withovertorque beingdetectedNC contact: OFF withovertorque beingdetected

8 Not used ---

910 Alarm out-

putON: Alarm being de-tected (Nonfatal error be-ing detected)

11 Base blockin progress

Base block in progress(in operation with outputshutoff)

12 RUN mode ON: Local mode (with theDigital Operator)

List of Parameters Chapter 3

Page 53: Setup Manual 3G3JV

3-13

Param-eterNo.

(Regis-ter No.(Hex))

MemoChangesduringopera-

tion

Defaultsetting

Set-ting

range

DescriptionName

n40

(0128)

Multi-func-tion output(MA/MB

C

13 Inverterready

ON: Inverter ready to op-erate (with no fault de-tected)

0 to 7,10 to18

1 No

(and MCoutput ter

14 Fault retry ON: Fault retryoutput ter-minals) 15 UV in prog-

ressON: Undervoltage beingmonitored

16 Rotating inreversedirection

ON: Rotating in reversedirection

17 Speedsearch inprogress

ON: Speed search inprogress

18 Data outputvia commu-nications

The inverter operatesmulti-function output ter-minals independently.

n41

(0129)

Frequencyreferencegain

Used to the input characteristics of analog fre-quency references.

Gain: The frequency of maximum analog input(10 V or 20 mA) in percentage based on the

0 to255

100 Yes

n42

(012A)

Frequencyreferencebias

(10 V or 20 mA) in percentage based on themaximum frequency as 100%.

Bias: The frequency of minimum analog input(0 V or 0 or 4 mA) in percentage based on themaximum frequency as 100%.

–99 to99

0 Yes

n43

(012B)

Analog fre-quencyreferencetime

Used to set the digital filter with a first-orderlag for analog frequency references to be in-put.

0.00to2.00

0.10 No

n44

(012C)

Analogmonitoroutput

Used to set the output frequency or current asa monitored item.

0: Output frequency (10-V output at max. fre-quency with n45 set to 1.00).

1: Output current (10-V output with Inverterrated output current with n45 set to 1.00)

0, 1 0 No

n45

(012D)

Analogmonitoroutput gain

Used to set the output characteristics of ana-log monitor output.

0.00to2.00

1.00 Yes

List of Parameters Chapter 3

Page 54: Setup Manual 3G3JV

3-14

Param-eterNo.

(Regis-ter No.(Hex))

MemoChangesduringopera-

tion

Defaultsetting

Set-ting

range

DescriptionName

n46

(012E)

Carrier fre-quencyselection

Used to set the carrier frequency according tothe set values, as follows:1 to 4: Carrier frequency = Set value x 2.5 kHz(fixed)7 to 9: Carrier frequency = Output frequencyratio for 1 kHz to 2.5 kHz maximum, as fol-lows:7: 1.0 to 2.5 kHz (12 times): Output frequencyx128: 1.0 to 2.5 kHz (24 times): Output frequencyx249: 1.0 to 2.5 kHz (36 times): Output frequencyx36

1 to 4,7 to 9

4 No

n47

(012F)

Momen-tary powerinterrup-tion com-pensation

Used to specify the processing that is per-formed when a momentary power interruptionoccurs.

0: Inverter stops operating

1: Inverter continues operating if power inter-ruption is 0.5 s or less.

2: Inverter restarts when power is restored.

0 to 2 0 No

n48

(0130)

Fault retry Used to set the number of times the Inverter isreset and restarted automatically in the casethe Inverter has an overvoltage fault, overcur-rent fault, or ground fault.

0 to10

0 No

n49

(0131)

Jump fre-quency 1

Used to set the frequency jump function.Outputfrequency

n51

0.0 to400

0.0 No

n50

(0132)

Jump fre-quency 2

Frequencyreference

n510.0 to400

0.0 No

n51

(0133)

Jumpwidth

reference

Note These values must satisfy the followingcondition: n49 n50

n50 n490.0 to25.5

0.0 No

n52

(0134)

DC controlcurrent

Set the DC braking current in percentage

Used to impose DC on the induction motor forbraking control.

0 to100

50 No

n53

(0135)

Interrup-tion DCcontroltime

Set the DC braking current in percentagebased on the rated current of the Inverter as100%.Outputfrequency

0.0 to25.5

0.5 No

n54

(0136)

Startup DCcontroltime

TimeMinimumoutputfrequency(n14)

n54 n53

0.0 to25.5

0.0 No

List of Parameters Chapter 3

Page 55: Setup Manual 3G3JV

3-15

Param-eterNo.

(Regis-ter No.(Hex))

MemoChangesduringopera-

tion

Defaultsetting

Set-ting

range

DescriptionName

n55

(0137)

Stall pre-ventionduring de-celeration

Used to select a function to change the decel-eration time of the motor automatically so thatthere will be no overvoltage imposed on themotor during deceleration.

0: Stall prevention during deceleration enabled

1: Stall prevention during deceleration dis-abled

0, 1 0 No

n56

(0138)

Stall pre-ventionlevel dur-ing accel-eration

Used to select a function to stop the accelera-tion of the motor automatically for stall preven-tion during acceleration.

Set the level in percentage based on the ratedcurrent of the Inverter as 100%.

30 to200

170 No

n57

(0139)

Stall pre-ventionlevel dur-ing opera-tion

Used to select a function to reduce the outputfrequency of the Inverter automatically for stallprevention during operation.

Set the level in percentage based on the ratedcurrent of the Inverter as 100%.

30 to200

160 No

n58

(013A)

Frequencydetectionlevel

Used to set the frequency to be detected.Note The parameter n40 for multi-function

output must be set for the output of fre-quency detection levels 1 and 2.

0.0 to400

0.0 No

n59

(013B)

Overtor-que detec-tion func-tion selec-tion

Used to enable or disable overtorque detec-tion and select the processing method afterovertorque detection.

0: Overtorque detection disabled

1: Overtorque detection only when speed coin-cides and operation continues (issuesalarm)

2: Overtorque detection only when speed coin-cides and output shut off (for protection)

3: Overtorque always detected and operationcontinues (issues alarm)

4: Overtorque always detected and outputshut off (for protection)

0 to 4 0 No

n60

(013C)

Overtor-que detec-tion level

Used to set overtorque detection level.

Set the level in percentage based on the ratedcurrent of the Inverter as 100%.

30 to200

160 No

n61

(013D)

Overtor-que detec-tion time

Used to set the detection time of overtorque. 0.1 to10.0

0.1 No

List of Parameters Chapter 3

Page 56: Setup Manual 3G3JV

3-16

Param-eterNo.

(Regis-ter No.(Hex))

MemoChangesduringopera-

tion

Defaultsetting

Set-ting

range

DescriptionName

n62

(013E)

UP/DOWNcommandfrequencymemory

Used to store the adjusted frequency refer-ence with the UP/DOWN function.

0: Frequency not stored

1: Frequency storedThe frequency must be on hold for 5 s ormore.

Used to store the adjusted frequency refer-ence with the UP/DOWN function.

0: Frequency not stored

1: Frequency storedThe frequency must be on hold for 5 s ormore.

Used to store the adjusted frequency refer-ence with the UP/DOWN function.

0: Frequency not stored

1: Frequency storedThe frequency must be on hold for 5 s ormore.

0, 1 0 No

n63

(013F)

Torquecompensa-tion gain

Used to set the gain of the torque compensa-tion function.

The default setting does not need anychanges in normal operation.

0.0 to2.5

1.0 Yes

n64

(0140)

Motorrated slip

Used to set the rated slip value of the motor inuse.Note Used as the constant of the slip com-

pensation function.

0.0 to20.0

Varieswith thecapac-ity.

Yes

n65

(0141)

Motor no-load cur-rent

Used to set the no-load current of the motor inuse based on the rated motor current as100%.Note Used as the constant of the slip com-

pensation function.

0 to99

Varieswith thecapac-ity.

No

n66

(0142)

Slip com-pensationgain

Used to set the gain of the slip compensationfunction.Note The slip compensation function is dis-

abled with n66 set to 0.0.

0.0 to2.5

0.0 Yes

n67

(0143)

Slip com-pensationtimeconstant

Used for the response speed of the slip com-pensation function.Note The default setting does not need any

changes in normal operation.

0.0 to25.5

2.0 No

List of Parameters Chapter 3

Page 57: Setup Manual 3G3JV

3-17

Param-eterNo.

(Regis-ter No.(Hex))

MemoChangesduringopera-

tion

Defaultsetting

Set-ting

range

DescriptionName

n68

(0144)(Seenote 1.)

RS-422A/485 com-munica-tions time-overdetectionselection

Used to set whether a communications time-over (CE) is detected if there is an interval ofmore than 2 s, and to select the method ofprocessing the detected communications time-over.

0: Detects a time-over and fatal error andcoasts to a stop.

1: Detects a time-over and fatal error anddecelerates to a stop in deceleration time 1.

2: Detects a time-over and fatal error anddecelerates to a stop in deceleration time 2.

3: Detects a time-over and nonfatal errorwarning and continues operating.

4: No time-over is detected.

0 to 4 0 No

n69

(0145)(Seenote 1.)

RS-422A/485 com-munica-tions fre-quencyreference/displayunit selec-tion

Used to the set the unit of frequency referenceand frequency-related values to be set ormonitored through communications.

0: 0.1 Hz

1: 0.01 Hz

2: Converted value based on 30,000 as max.frequency

3: 0.1% (Max. frequency: 100%)

0 to 3 0 No

n70

(0146)(Seenote 1.)

RS-422A/485 com-munica-tions Slaveaddress

Used to set the Slave address (Slave unitnumber) for communications.

0: Only receives broadcast messagesfrom the Master.

01 to 32: Slave address

00 to32

00 No

n71

(0147)(Seenote 1.)

RS-422A/485 baudrate selec-tion

Used to set the baud rate for communications.

0: 2,400 bps

1: 4,800 bps

2: 9,600 bps

3: 19,200 bps

0 to 3 2 No

n72

(0148)(Seenote 1.)

RS-422A/485 parityselection

Used to set the parity for communications.

0: Even parity

1: Odd parity

2: No parity

0 to 2 0 No

n73

(0149)(Seenote 1.)

RS-422A/485 sendwait time

Used to set the waiting period for returning aresponse after the DSR (data-send-request)message is received from the Master.

10 to65

10 No

List of Parameters Chapter 3

Page 58: Setup Manual 3G3JV

3-18

Param-eterNo.

(Regis-ter No.(Hex))

MemoChangesduringopera-

tion

Defaultsetting

Set-ting

range

DescriptionName

n74

(014A)(Seenote 1.)

RS-422A/485 RTScontrolselection

Select whether or not to enable the RTS(request-to-send) communications controlfunction.

0, 1 0 No

n75

(014B)

Low-speedcarrier fre-quency re-ductionselection

Used to select a function to reduce the carrierfrequency when Inverter is at low speed.

0: Function disabled

1: Function enabledNote Normally set n75 to 0.

0.1 0 No

n76

(014C)(Seenote 1.)

Parametercopy andverify func-tion

Selects the function to read, copy, and verifythe parameters between the memory of theInverter and that of the Digital Operator.

rdy: Ready to accept the next command.

rED: Reads the Inverter parameters.

Cpy: Copies the parameter to the Inverter.

vFY: Verifies the Inverter parameters.

vA: Checks the Inverter capacity display.

Sno: Checks the software number.

rdy toSno

rdy No

n77

(014D)(Seenote 1.)

Parameterread pro-hibit selec-tion

Selects the copy-prohibit function.

Use this parameter to protect the data in theEEPROM of the Digital Operator.

0: Read prohibited for Inverter parameters.(Data cannot be written to EEPROM.)

1: Read possible for Inverter parameters.(Data can be written to EEPROM.)

0, 1 0 No

n78

(014E)

Error log

Note “– – –” will be displayed if no error hasbeen recorded.

Note This parameter is monitored only.

Used to display the latest error recorded.

Display

--- --- ---

n79

(014F)

Softwarenumber

Used to display the software number of theInverter for OMRON’s control reference use.Note This parameter is monitored only.

--- --- ---

Note 1. The n68 to n74, n76, and n77 parameters cannot be written via RS422/485 communications.

They are read-only.

Note 2. Motor parameters depend on the Inverter capacity as shown in the following table.

List of Parameters Chapter 3

Page 59: Setup Manual 3G3JV

3-19

100-V Class, Single-phase Power Supply

Parameter No. Name Unit Default constantInverter capacity kW 0.1 0.2

n32 Rated motor current A 0.6 1.1

n64 Motor rated slip Hz 2.5 2.6

n65 Motor no-load current % 72 73

List of Parameters Chapter 3

Page 60: Setup Manual 3G3JV

Chapter 4

Maintenance Operations

4-1 Protective and Diagnostic Functions

4-2 Inspection and Maintenance

4

Page 61: Setup Manual 3G3JV

4-2

4-1 Protective and Diagnostic Functions

4-1-1 Fault Detection (Fatal Error)

The Inverter will detect the following faults if the Inverter or motor burns or the internalcircuitry of the Inverter malfunctions. When the Inverter detects a fault, the fault code willbe displayed on the Digital Operator, the fault contact output will operate, and theInverter output will be shut off causing the motor to coast to a stop. The stopping methodcan be selected for some faults, and the selected stopping method will be used withthese faults. If a fault has occurred, refer to the following table to identify and correct thecause of the fault. Use one of the following methods to reset the fault after restarting theInverter. If the operation command is being input, however, the reset signal will be ig-nored. Therefore, be sure to reset the fault with the operation command turned off. Turn on the fault reset signal. A multi-function input (n36 to n39) must be set to 5 (Fault

Reset). Press the STOP/RESET Key on the Digital Operator. Turn the main circuit power supply off and then on again.

Fault Displays and ProcessingFault

displayFault name and meaning Probable cause and remedy

Overcurrent (OC)The Inverter output current isas high as or higher than200% of the rated outputcurrent.

• A short-circuit or ground fault has occurred and at theInverter output.

→ Check and correct the motor power cable.• The V/f setting is incorrect.

→ Reduce the V/f set voltage.• The motor capacity is too large for the Inverter.

→ Reduce the motor capacity to the maximum permissiblemotor capacity.

• The magnetic contactor on the output side of the Inverterhas been opened and closed.

→ Rearrange the sequence so that the magnetic contactorwill not open or close while the Inverter has currentoutput.

• The output circuit of the Inverter is damaged.

→ Replace the Inverter.

Overvoltage (OV)The main circuit DC voltagehas reached the overvoltagedetection level (100-V models:410 V DC min.).

• The deceleration time is too short.

→ Increase the deceleration time.• The power supply voltage is too high.

→ Decrease the voltage so it will be within specifications.• There is excessive regenerative energy due to overshooting

at the time of acceleration.

→ Suppress the overshooting as much as possible.

Maintenance Operations Chapter 4

Page 62: Setup Manual 3G3JV

4-3

Faultdisplay

Probable cause and remedyFault name and meaning

Main circuit undervoltage(UV1)The main circuit DC voltagehas reached the undervoltagedetection level (160 V DC forthe 3G3JV-A1).

• Power supply to the Inverter has phase loss, power inputterminal screws are loose, or the power cable is discon-nected.

→ Check the above and take necessary countermeasures.• Incorrect power supply voltage

→ Make sure that the power supply voltage is withinspecifications.

• Momentary power interruption has occurred.

→ Use the momentary power interruption compensation(Set n47 so that the Inverter restarts after power isrestored)

→ Improve the power supply.• The internal circuitry of the Inverter is damaged.

→ Change the Inverter.

Radiation fin overheated(OH)The temperature of theradiation fins of the Inverterhas reached 110C ± 10C.

• The ambient temperature is too high.

→ Ventilate the Inverter or install a cooling unit.• The load is excessive.

→ Reduce the load.→ Decrease the Inverter capacity.

• The V/f setting is incorrect.

→ Reduce the V/f set voltage.• The acceleration/deceleration time is too short.

→ Increase the acceleration/deceleration time.• The ventilation is obstructed.

→ Change the location of the Inverter to meet theinstallation conditions.

• The cooling fan of the Inverter does not work.

→ Replace the cooling fan.

Maintenance Operations Chapter 4

Page 63: Setup Manual 3G3JV

4-4

Faultdisplay

Probable cause and remedyFault name and meaning

Motor overload (OL1)The electric thermal relayactuated the motor overloadprotective function.

• The load is excessive.

→ Reduce the load.→ Decrease the Inverter capacity.

• The V/f setting is incorrect.

→ Reduce the V/f set voltage.• The value in n11 for maximum voltage frequency is low.

→ Check the motor nameplate and set n11 to the ratedfrequency.

• The acceleration/deceleration time is too short.

→ Increase the acceleration/deceleration time.• The value in n32 for rated motor current is incorrect.

→ Check the motor nameplate and set n32 to the ratedcurrent.

• The Inverter is driving more than one motor.

→ Disable the motor overload detection function and installan electronic thermal relay for each of the motors.The motor overload detection function is disabled bysetting n32 to 0.0 or n33 to 2.

• The motor protective time setting in n34 is short.

→ Set n34 to 8 (the default value).

Inverter overload (OL2)The electronic thermal relayhas actuated the Inverteroverload protective function.

• The load is excessive.

→ Reduce the load.• The V/f setting is incorrect.

→ Reduce the V/f set voltage.• The acceleration/deceleration time is too short.

→ Increase the acceleration/deceleration time.• The Inverter capacity is insufficient.

→ Use an Inverter model with a higher capacity. Overtorque detection (OL3)

There has been a current ortorque the same as or greaterthan the setting in n60 forovertorque detection level andthat in n61 for overtorquedetection time. A fault hasbeen detected with n59 forovertorque detection functionselection set to 2 or 4.

• The mechanical system is locked or has a failure.

→ Check the mechanical system and correct the cause ofovertorque.

• The parameter settings were incorrect.

→ Adjust the n60 and n61 parameters according to themechanical system.Increase the set values in n60 and n61.

Ground fault (GF)The ground fault current at theoutput of the Inverter hasexceeded the rated outputcurrent of the Inverter.

• A ground fault has occurred at the Inverter output.

→ Check the connections between the Inverter and motorand reset the fault after correcting its cause.

Maintenance Operations Chapter 4

Page 64: Setup Manual 3G3JV

4-5

Faultdisplay

Probable cause and remedyFault name and meaning

External fault (EF)An external fault has beeninput from a multi-functioninput.A multi-function input 1, 2, 3,or 4 set to 3 or 4 hasoperated. The EF numberindicates the number of thecorresponding input (S2 toS5).

• An external fault was input from a multi-function input.

→ Remove the cause of the external fault.• The sequence is incorrect.

→ Check and change the external fault input sequenceincluding the input timing and NO or NC contact.

Digital Operatortransmission fault 1 (F00)An initial memory fault hasbeen detected

• The internal circuitry of the Inverter has a fault.

→ Turn the Inverter off and on.→ Replace the Inverter if the same fault occurs again.

Digital Operatortransmission fault 2 (F01)A ROM fault has beendetected.

• The internal circuitry of the Inverter has a fault.

→ Turn the Inverter off and on.→ Replace the Inverter if the same fault occurs again.

Initial memory fault (F04)An error in the built-inEEPROM of the Inverter hasbeen detected.

• The internal circuitry of the Inverter has a fault.

→ Initialize the Inverter with n01 set to 8 or 9 and turn theInverter off and on.

→ Replace the Inverter if the same fault occurs again.

Analog-to-digital converterfault (F05)An analog-to-digital converterfault has been detected.

• The internal circuitry of the Inverter has a fault.

→ Turn the Inverter off and on.→ Replace the Inverter if the same fault occurs again.

Digital Operator fault (F07)An error in the built-in controlcircuit of the Digital Operatorhas been detected.

• The internal circuitry of the Digital Operator has a fault.

→ Turn the Digital Operator off and on.→ Replace the Digital Operator if the same fault occurs

again.

Communications time-over(CE)Normal RS-422A/485communications were notestablished within 2 s. TheInverter will detect this error ifn68 (RS-422A/485communications time-overdetection selection) is set to 0,1, or 2.

• A short-circuit, ground fault, or disconnection has occurredon the communications line.

→ Check and correct the line.• The termination resistance setting is incorrect.

→ Set the termination resistance of only the Inverter locatedat each end of the network to ON.

• Noise influence.

→ Do not wire the communications line along with powerlines in the same conduit.

→ Use the twisted-pair shielded wire for thecommunications line, and ground it at the Master.

• Master’s program error.

→ Check and correct the program so that communicationswill be performed more than once every 2-s period.

• Communications circuit damage.

→ If the same error is detected as a result of aself-diagnostic test, change the Inverter.

Maintenance Operations Chapter 4

Page 65: Setup Manual 3G3JV

4-6

Faultdisplay

Probable cause and remedyFault name and meaning

Emergency stop (STP)An emergency stop alarm isinput to a multi-function input.(A multi-function input 1, 2, 3,or 4 set to 19 or 21 hasoperated.)

• An emergency stop alarm is input to a multi-function input.

→ Remove the cause of the fault.• The sequence is incorrect.

→ Check and change the external fault input sequenceincluding the input timing and NO or NC contact.

OFF Power supply error• Insufficient power supply

voltage

• Control power supply fault

• Hardware fault

• No power supply is provided.

→ Check and correct the power supply wire and voltage.• Terminal screws are loosened.

→ Check and tighten the terminal screws.• The Inverter is damaged.

→ Replace the Inverter.

Maintenance Operations Chapter 4

Page 66: Setup Manual 3G3JV

4-7

4-1-2 Warning Detection (Nonfatal Error)

The warning detection is a type of Inverter protective function that does not operate thefault contact output and returns the Inverter to its original status once the cause of theerror has been removed. The Digital Operator flashes and display the detail of the error.If a warning occurs, take appropriate countermeasures according to the table below.Note Some warnings or some cases stop the operation of the Inverter as described in

the table.

Warning Displays and ProcessingFault display Warning name and Meaning Probable cause and remedy

(flashing)Main Circuit Undervoltage (UV)The main circuit DC voltage hasreached the undervoltage detectionlevel (160 V DC for the 3G3JV-A1).

• Power supply to the Inverter has phase loss,power input terminal screws are loose, or thepower line is disconnected.

→ Check the above and take necessarycountermeasures.

• Incorrect power supply voltage

→ Make sure that the power supply voltage iswithin specifications.

(flashing)Main Circuit OvervoltageThe main circuit DC voltage hasreached the overvoltage detectionlevel (100-V models: 410 V DC min.).

• The power supply voltage is too high.

→ Decrease the voltage so it will be withinspecifications.

(flashing)Radiation fin overheated (OH)The temperature of the radiation finsof the Inverter has reached 110C ±10C.

• The ambient temperature is too high.

→ Ventilate the Inverter or install a cooling unit.

(flashing)Communications standby (CAL)No normal DSR message has beenreceived during RS-422A/4895communications.The Inverter detects this warning onlywhen RUN command selection (n02)is set to 2 or frequency referenceselection (n03) is set to 6. Until thewarning is reset, no input other thancommunications input will be ignored.

• A short-circuit, ground fault, or disconnection hasoccurred on the communications line.

→ Check and correct the line.• The termination resistance setting is incorrect.

→ Set the termination resistance of only theInverter located at each end of the network toON.

• Master’s program error.

→ Check the start of communications andcorrect the program.

• Communications circuit damage.

→ If a CAL or CE error is detected as a result ofa self-diagnostic test, change the Inverter.

(flashing)Overtorque detection (OL3)There has been a current or torque thesame as or greater than the setting inn60 for overtorque detection level andthat in n61 for overtorque detectiontime. A fault has been detected withn59 for overtorque detection functionselection set to 1 or 3.

• The mechanical system is locked or has a failure.

→ Check the mechanical system and correct thecause of overtorque.

• The parameter settings were incorrect.

→ Adjust the n60 and n61 parameters accordingto the mechanical system.Increase the set values in n60 and n61.

Maintenance Operations Chapter 4

Page 67: Setup Manual 3G3JV

4-8

Fault display Probable cause and remedyWarning name and Meaning

(flashing)Sequence error (SER)A sequence change has been inputwhile the Inverter is in operation.Local or remote selection is input whilethe Inverter is in operation.Note The Inverter coasts to a stop.

• A sequence error has occurred.

→ Check and adjust the local or remoteselection sequence as multi-function input.

(flashing)External base block (bb)The external base block command hasbeen input.Note The Inverter coasts to a stop.

• The external base block command has been in-put as multi-function input.

→ Remove the cause of external base blockinput.

• The sequence is incorrect.

→ Check and change the external fault inputsequence including the input timing and NOor NC contact.

(flashing)Forward- and reverse-rotation input(EF)The forward and reverse commandsare input to the control circuit terminalssimultaneously for 0.5 s or more.Note The Inverter stops according to

the method set in n04.

• A sequence error has occurred.

→ Check and adjust the local or remoteselection sequence.

(flashing)

Emergency stop (STP)The Digital Operator stops operating.The STOP/RESET Key on the DigitalOperator is pressed while the Inverteris operating according to the forwardor reverse command through thecontrol circuit terminals.Note The Inverter stops according to

the method set in n04.

• The parameter setting was incorrect.

→ Turn off the forward or reverse commandonce, check that the n06 parameter setting forSTOP/RESET Key function selection, andrestart the Inverter.

The emergency stop alarm signal isinput as multi-function input.A multi-function input 1, 2, 3, or 4 setto 20 or 22 has been used.Note The Inverter stops according to

the method set in n04.

• An emergency stop alarm is input to a multi-func-tion input.

→ Remove the cause of the fault.• The sequence is incorrect.

→ Check and change the external fault inputsequence including the input timing and NOor NC contact.

(flashing)Cooling fan fault (FAN)The cooling fan has been locked.

• The cooling fan wiring has a fault.

→ Turn off the Inverter, dismount the fan, andcheck and repair the wiring.

• The cooling fan in not in good condition.

→ Check and remove the foreign material ordust on the fan.

• The cooling fan is beyond repair.

→ Replace the fan.

Maintenance Operations Chapter 4

Page 68: Setup Manual 3G3JV

4-9

Fault display Probable cause and remedyWarning name and Meaning Communications time-over (CE)

Normal RS-422A/485 communicationswere not established within 2 s. TheInverter will detect this error if n68(RS-422A/485 communicationstime-over detection selection) is set to0, 1, or 2.

• A short-circuit, ground fault, or disconnection hasoccurred on the communications line.

→ Check and correct the line.• The termination resistance setting is incorrect.

→ Set the termination resistance of only theInverter located at each end of the network toON.

• Noise influence.

→ Do not wire the communications line alongwith power lines in the same conduit.

→ Use the twisted-pair shielded wire for thecommunications line, and ground it at theMaster.

• Master’s program error.

→ Check and correct the program so thatcommunications will be performed more thanonce every 2-s period.

• Communications circuit damage.

→ If the same error is detected as a result of aself-diagnostic test, change the Inverter.

(flashing)Operation error (OP)(Parameter setting error)

• The values in n36 through n39 for multi-functioninputs 1 through 4 have been duplicated.

→ Check and correct the values.

(flashing)• The V/f pattern settings do not satisfy the follow-

ing condition.n14 n12 n11 n09

→ Check and correct the set value.

(flashing)• The rated motor current set in n32 exceeds

150% of the rated output current of the Inverter.

→ Check and correct the value.

(flashing)• The frequency reference upper limit set in n30

and the frequency reference lower limit set in n31do not satisfy the following condition.n30 n31

→ Check and correct the set values.

(flashing)• The jump frequencies set n49, n50 do not satisfy

the following condition.n49 n50

→ Check and correct the set values.

Maintenance Operations Chapter 4

Page 69: Setup Manual 3G3JV

4-10

4-2 Inspection and Maintenance

Daily InspectionCheck the following items while the system is operating.

• No abnormal noise or vibration in the motor

• No abnormal heat generation

• Output current monitor display is not a higher value than normal

• Cooling fan installed in Inverter is operating normally (models with fans only)

Periodic InspectionCheck the following items when performing periodic maintenance.

Always wait at least one minute after the power supply has been turned OFF and all the LED indicatorshave turned OFF before performing maintenance. Touching the terminals immediately after the poweris turned OFF may result in electric shock.

• No looseness in terminal screws

• No electroconductive dust or oil mist attached to terminal block or the Inverter’s internal parts

• No looseness in Inverter mounting screws

• No accumulation of dirt or dust on cooling fin (heat sink)

• No dust accumulated in the ventilation holes

• No abnormality in external appearance

• Cooling fan in control panel is operating normally(Check that there is no abnormal noise or vibration, and that the total ON time has not exceeded thespecified value.)

Periodic Maintenance of ComponentsThe Inverter is constructed from many components, the normal operation of which is required for theessential functionality of the Inverter. Maintenance is required for some of the electronic componentsdepending on the operating conditions. To enable the Inverter to operate normally for a long time, peri-odic inspection and component replacement must be performed to suit the service life of these compo-nents.

(Source: “Instructions for Periodic Inspection of General Purpose Inverter” (JEMA))

The guidelines for periodic inspection depend on the Inverter’s installation environment and operatingconditions.

The maintenance periods for the Inverter are listed below. Use this to determine when periodic mainte-nance is required.

The guidelines for periodic maintenance are as follows:

• Cooling fan: 2 to 3 years

• Electrolytic capacitor: 10 years

• Fuse: 10 years

These guidelines are applicable for an operating environment in which the ambient temperature is40°C, the load rate is 80%, the operating time is 8 hours per day, and the product is installed according tothe instructions in the manual.

Maintenance Operations Chapter 4

Page 70: Setup Manual 3G3JV

4-11

To extend the maintenance period, it is recommended to lower the ambient temperature and shortenthe ON time as much as possible.

Note Contact your OMRON sales representative for details on maintenance methods.

Maintenance Operations Chapter 4

Page 71: Setup Manual 3G3JV

Terms and Conditions of Sale1. Offer; Acceptance. These terms and conditions (these "Terms") are deemed

part of all quotes, agreements, purchase orders, acknowledgments, price lists,catalogs, manuals, brochures and other documents, whether electronic or inwriting, relating to the sale of products or services (collectively, the "Products")by Omron Electronics LLC and its subsidiary companies (“Omron”). Omronobjects to any terms or conditions proposed in Buyer’s purchase order or otherdocuments which are inconsistent with, or in addition to, these Terms.

2. Prices; Payment Terms. All prices stated are current, subject to change with-out notice by Omron. Omron reserves the right to increase or decrease priceson any unshipped portions of outstanding orders. Payments for Products aredue net 30 days unless otherwise stated in the invoice.

3. Discounts. Cash discounts, if any, will apply only on the net amount of invoicessent to Buyer after deducting transportation charges, taxes and duties, and willbe allowed only if (i) the invoice is paid according to Omron’s payment termsand (ii) Buyer has no past due amounts.

4. Interest. Omron, at its option, may charge Buyer 1-1/2% interest per month orthe maximum legal rate, whichever is less, on any balance not paid within thestated terms.

5. Orders. Omron will accept no order less than $200 net billing. 6. Governmental Approvals. Buyer shall be responsible for, and shall bear all

costs involved in, obtaining any government approvals required for the impor-tation or sale of the Products.

7. Taxes. All taxes, duties and other governmental charges (other than generalreal property and income taxes), including any interest or penalties thereon,imposed directly or indirectly on Omron or required to be collected directly orindirectly by Omron for the manufacture, production, sale, delivery, importa-tion, consumption or use of the Products sold hereunder (including customsduties and sales, excise, use, turnover and license taxes) shall be charged toand remitted by Buyer to Omron.

8. Financial. If the financial position of Buyer at any time becomes unsatisfactoryto Omron, Omron reserves the right to stop shipments or require satisfactorysecurity or payment in advance. If Buyer fails to make payment or otherwisecomply with these Terms or any related agreement, Omron may (without liabil-ity and in addition to other remedies) cancel any unshipped portion of Prod-ucts sold hereunder and stop any Products in transit until Buyer pays allamounts, including amounts payable hereunder, whether or not then due,which are owing to it by Buyer. Buyer shall in any event remain liable for allunpaid accounts.

9. Cancellation; Etc. Orders are not subject to rescheduling or cancellationunless Buyer indemnifies Omron against all related costs or expenses.

10. Force Majeure. Omron shall not be liable for any delay or failure in deliveryresulting from causes beyond its control, including earthquakes, fires, floods,strikes or other labor disputes, shortage of labor or materials, accidents tomachinery, acts of sabotage, riots, delay in or lack of transportation or therequirements of any government authority.

11. Shipping; Delivery. Unless otherwise expressly agreed in writing by Omron:a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship

except in “break down” situations.b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall

constitute delivery to Buyer;c. All sales and shipments of Products shall be FOB shipping point (unless oth-

erwise stated in writing by Omron), at which point title and risk of loss shallpass from Omron to Buyer; provided that Omron shall retain a security inter-est in the Products until the full purchase price is paid;

d. Delivery and shipping dates are estimates only; ande. Omron will package Products as it deems proper for protection against nor-

mal handling and extra charges apply to special conditions.12. Claims. Any claim by Buyer against Omron for shortage or damage to the

Products occurring before delivery to the carrier must be presented in writingto Omron within 30 days of receipt of shipment and include the original trans-portation bill signed by the carrier noting that the carrier received the Productsfrom Omron in the condition claimed.

13. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that theProducts will be free from defects in materials and workmanship for a period oftwelve months from the date of sale by Omron (or such other period expressedin writing by Omron). Omron disclaims all other warranties, express or implied.(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION,EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-

ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS.BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THEPRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIRINTENDED USE. Omron further disclaims all warranties and responsibility ofany type for claims or expenses based on infringement by the Products or oth-erwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obli-gation hereunder shall be, at Omron’s election, to (i) replace (in the formoriginally shipped with Buyer responsible for labor charges for removal orreplacement thereof) the non-complying Product, (ii) repair the non-complyingProduct, or (iii) repay or credit Buyer an amount equal to the purchase price ofthe non-complying Product; provided that in no event shall Omron be responsi-ble for warranty, repair, indemnity or any other claims or expenses regardingthe Products unless Omron’s analysis confirms that the Products were prop-erly handled, stored, installed and maintained and not subject to contamina-tion, abuse, misuse or inappropriate modification. Return of any Products byBuyer must be approved in writing by Omron before shipment. Omron Compa-nies shall not be liable for the suitability or unsuitability or the results from theuse of Products in combination with any electrical or electronic components,circuits, system assemblies or any other materials or substances or environ-ments. Any advice, recommendations or information given orally or in writing,are not to be construed as an amendment or addition to the above warranty.See http://oeweb.omron.com or contact your Omron representative for pub-lished information.

14. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLEFOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANYWAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM ISBASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.Further, in no event shall liability of Omron Companies exceed the individualprice of the Product on which liability is asserted.

15. Indemnities. Buyer shall indemnify and hold harmless Omron Companies andtheir employees from and against all liabilities, losses, claims, costs andexpenses (including attorney's fees and expenses) related to any claim, inves-tigation, litigation or proceeding (whether or not Omron is a party) which arisesor is alleged to arise from Buyer's acts or omissions under these Terms or inany way with respect to the Products. Without limiting the foregoing, Buyer (atits own expense) shall indemnify and hold harmless Omron and defend or set-tle any action brought against such Companies to the extent based on a claimthat any Product made to Buyer specifications infringed intellectual propertyrights of another party.

16. Property; Confidentiality. Any intellectual property in the Products is the exclu-sive property of Omron Companies and Buyer shall not attempt to duplicate itin any way without the written permission of Omron. Notwithstanding anycharges to Buyer for engineering or tooling, all engineering and tooling shallremain the exclusive property of Omron. All information and materials suppliedby Omron to Buyer relating to the Products are confidential and proprietary,and Buyer shall limit distribution thereof to its trusted employees and strictlyprevent disclosure to any third party.

17. Export Controls. Buyer shall comply with all applicable laws, regulations andlicenses regarding (i) export of products or information; (iii) sale of products to“forbidden” or other proscribed persons; and (ii) disclosure to non-citizens ofregulated technology or information.

18. Miscellaneous. (a) Waiver. No failure or delay by Omron in exercising any rightand no course of dealing between Buyer and Omron shall operate as a waiverof rights by Omron. (b) Assignment. Buyer may not assign its rights hereunderwithout Omron's written consent. (c) Law. These Terms are governed by thelaw of the jurisdiction of the home office of the Omron company from whichBuyer is purchasing the Products (without regard to conflict of law princi-ples). (d) Amendment. These Terms constitute the entire agreement betweenBuyer and Omron relating to the Products, and no provision may be changedor waived unless in writing signed by the parties. (e) Severability. If any provi-sion hereof is rendered ineffective or invalid, such provision shall not invalidateany other provision. (f) Setoff. Buyer shall have no right to set off any amountsagainst the amount owing in respect of this invoice. (g) Definitions. As usedherein, “including” means “including without limitation”; and “Omron Compa-nies” (or similar words) mean Omron Corporation and any direct or indirectsubsidiary or affiliate thereof.

Certain Precautions on Specifications and Use1. Suitability of Use. Omron Companies shall not be responsible for conformity

with any standards, codes or regulations which apply to the combination of theProduct in the Buyer’s application or use of the Product. At Buyer’s request,Omron will provide applicable third party certification documents identifyingratings and limitations of use which apply to the Product. This information byitself is not sufficient for a complete determination of the suitability of the Prod-uct in combination with the end product, machine, system, or other applicationor use. Buyer shall be solely responsible for determining appropriateness ofthe particular Product with respect to Buyer’s application, product or system.Buyer shall take application responsibility in all cases but the following is anon-exhaustive list of applications for which particular attention must be given:(i) Outdoor use, uses involving potential chemical contamination or electricalinterference, or conditions or uses not described in this document.(ii) Use in consumer products or any use in significant quantities. (iii) Energy control systems, combustion systems, railroad systems, aviationsystems, medical equipment, amusement machines, vehicles, safety equip-ment, and installations subject to separate industry or government regulations. (iv) Systems, machines and equipment that could present a risk to life or prop-erty. Please know and observe all prohibitions of use applicable to this Prod-uct. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUSRISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUTENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO

ADDRESS THE RISKS, AND THAT THE OMRON’S PRODUCT IS PROP-ERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THEOVERALL EQUIPMENT OR SYSTEM.

2. Programmable Products. Omron Companies shall not be responsible for theuser’s programming of a programmable Product, or any consequence thereof.

3. Performance Data. Data presented in Omron Company websites, catalogsand other materials is provided as a guide for the user in determining suitabil-ity and does not constitute a warranty. It may represent the result of Omron’stest conditions, and the user must correlate it to actual application require-ments. Actual performance is subject to the Omron’s Warranty and Limitationsof Liability.

4. Change in Specifications. Product specifications and accessories may bechanged at any time based on improvements and other reasons. It is our prac-tice to change part numbers when published ratings or features are changed,or when significant construction changes are made. However, some specifica-tions of the Product may be changed without any notice. When in doubt, spe-cial part numbers may be assigned to fix or establish key specifications foryour application. Please consult with your Omron’s representative at any timeto confirm actual specifications of purchased Product.

5. Errors and Omissions. Information presented by Omron Companies has beenchecked and is believed to be accurate; however, no responsibility is assumedfor clerical, typographical or proofreading errors or omissions.

Page 72: Setup Manual 3G3JV

Specifications subject to change without notice. Printed in the U.S.A.

OMRON ELECTRONICS LLC

1 Commerce DriveSchaumburg, IL 60173 847.843.7900 For US technical support or other inquiries: 800.556.6766

OMRON CANADA, INC. 885 Milner AvenueToronto, Ontario M1B 5V8416.286.6465

OMRON ON-LINEGlobal - www.omron.comUSA - www.omron247.comCanada - www.omron.caBrazil - www.omron.com.brLatin America - www.espanol.omron.com

I546-E1-02 ©2007 OMRON ELECTRONICS LLC

UNITED STATESTo locate a Regional Sales Office, local Distributor orto obtain product information, call: 847.843.7900

MEXICO SALES OFFICES

Mexico, D.F. 555.660.3144Ciudad Juárez 656.623.7083Monterrey, N.L 818.377.4281Querétaro 442.135.4510

BRAZIL SALES OFFICESao Paulo 55.11.2101.6310

ARGENTINA SALES OFFICECono Sur 54.114.787.1129

OTHER LATIN AMERICAN SALES [email protected]