197
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Design, Engineering,manufacturing, Supply, Erection,
Testing& commissioning of 33/11KV Power Transformer,
Oilimmersed, ONAN cooled outdoor type, 3-phase, 50 Hz,
VectorGroup-Dyn-II, delta-star step down with off load tap
changerhaving range of +10% to -10% in steps of 2.5% each on
HVwinding with first filling of EHV grade insulating oil as
perspecification including supply & erection of 90lb rail
pole,3.5mtr long, 2nos for each transformer as rail track
etc.asrequired conforming to relevant ISS as per design
drawingdetailed herein after in this document.
a. 7.5MVA Nos 0 Nos 0
Supply, erection, testing & commissioning of 33 KV,
800A,manually operated horizontal rotating type double break,
triple pole Gang operated isolator complete with postinsulator,
arching horns, mechanical interlocking arrangementetc.as per
relevant ISS(For Rampur S/S and at NSRCC end).
a) With earth switch. No 2 No 2b) Without earth switch. No 1 No
1
3
Supply, erection, testing & commissioning of 33 KV
SinglePhase, outdoor type 2 Core C.T of ratio 300 / 1-1 Amp
withsuitable burden & class of accuracy complete with
associatedterminal box connecting link etc. ( for 33 KV
outgoingfeeder)(For RampurS/S)
No 3 No 3
Name of Work:- Implementation of R-APDRP (Part-B) Scheme under
Agartala Project(Town Pratapgarh Area):
Design,Engineering,Manufacturing, Supply,testing ,Delivery,
Erection,Testing at site & commissioning of 33/11 KV, 2X7.5
MVA,Indoor Type Power Sub-Station at NSRCC, Netaji
Chowmuhani,Agartala with associated 33KV Underground Rampur
Substation- NSRCC S/C Line, 33 KV Bay at Rampur including Control
room and boundary wall atNSRCC.
Supply ErectionItem Sl. No
Description of Item
Schedule of Work
SCHEDULE-A
1
2
197
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
4
Supply, erection, testing & commissioning of 10KA, 30
KV,Station Valve type metal oxide heavy duty Lightning
SurgeArrestor suitable for operation on 33KV Sytem conformingto ISI
: 3070 (P-1) / 1974 and amendments thereafter and asrequired (1 set
at Rampur S/S end and 1 set at NSRCC end).
No 6 No 6
Supply, erection, testing & commissioning of 33 KV,
1000A,750 MVA rupturing capacity, outdoor Vacuum CircuitBreaker
complete with motor operated spring closing (Local /Remote)
arrangement with all accessories including latticesupport
structure,foundation bolts,G.I. nuts & bolts,washersetc. as
required and as per relevant ISS complete operative on110V DC at
Rampur Substation end .
a) For 33 KV Rampur-NSRCC UG Feeder. No 1 No 1
Supply, erection, testing & commissioning of 33 KV
control& relay panel, simplex type complete with differential
relay,2-over current and 1- Earth fault combined relay,
Auxiliaryrelay, 1- voltmeter, 3- ammeter, CT operated static
trivectormeter, internal panel wiring, simaphore for Vacuum
Circuitbreaker & isolator, Mimic bus diagram (Metal size 4mm
thickX 10mm width).
b) For 33 KV Rampur. No 1 No 1
i) Supply and Erection of Galvanised steel structure and
Nuts,Bolts, spring washer etc. as required for 33 KV tower,
grantry,post insulator and equpments. a) Steel structure b) Nuts
&bolts, spring washer and foundation bolts etc
Lot 1 Lot 1
6
5
-
199
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
ii) Supply, erection, testing & commissioning of sub-
stationbusbar & stringing materials for 33 KV bus at Rampur
end.a)ACSR 7/1.57/6/4.72 mm (DOG ) conductor. b) 40mm dia.Al. pipe
for equipments bus current carrying capacity400Amps. c) 7/3.15mm
earth wire for substation shielding. d)Ball & socket type 70
KN, 11KV disc Insulator. e) Al. tensionclamps. 3 -U bolt type,
ball& socket type, suitable for70KNDisc Insulator and ACSR DOG
conductor. f )"T"/ "I" / otherClamp/power connector suitable for
ACSR DOG Conductorand Al. tube as required.
Lot 1 Lot 1
Design, Engineering,manufacturing, Supply, erection,
testing& commissioning of 33KV, 1250A, 31.5 KA for 3 Sec.Metal
Clad withdrawable type indoor VCB,highly reliable, and totally
enclosed product under compartmentalisedconstruction combined with
positive safety interlocks for safedraw in/draw out of VCB
trolley/carriage including draw outtype PT Compartment (with dual
rating PT33KV/1.732/110V/1.732-110 V/1.732) in VCB Trolley
withstandard integrated protection relays( both numerical
&electromechanical) as per IEC62271-100/200, 12 windowalarm
& annunciation system and SCADA compatible controlsystem,power
pack,series trip arrangement, internal arc testedas per
IEC62271-200 including integral earth switch andmotor operated
spring charged mechanism, mounted ontruck carriage, complete with
self contained mechanism withmechanica & electrical indications
of operational status &auxiliary switch as required as per
standard requirementspecified in Technical specification section in
the documentincluding supply of 1No 2.5 KV Motorised Meggar.
7
8
199
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
a) Incoming Feeder with CT (CTR: 300/1-1A) at NSRCC end. Nos 1
Nos 1
b) Outgoing feeder for Transformers with CT (CTR:
300-150/1-1-1A)
Nos 2 Nos 2
c) Spare Incoming CT (CTR: 300/1-1A) at NSRCC end Nos 1 Nos
1
Design, Engineering, Supply, Testing & commissioning of
11KV, 800Amps continuos rated current, 350 MVA rupturing capacity
Indoor Vaccum Circuit Breaker, complete withControl & Relay
Pannel Simplex type with 3Phase panneltop mounted PT of ratio:
11000 /110Volt,110 Volt DCactuated electrical closing mechanism and
internal wiring,Numerical as well as electromechanical protection
by 2-Overcurrent & 1-earth fault combined ( Micom or other
reputedmake) digital & electromechanical relays for
integratedprotection,1 no.electromechanical AREVA Master TripRelay,
auxiliary relays as required,1 no.L&T / SECUREmake "Tri-
Vector" Meter(SCADA compatible) 3- Ammeter, 1 -Voltmeter, 1 -C.T
operated static KW meter ,with panel bus mounted C.T and integral
earthing facilityincluding inernal arc tested panel conforming to
relevantISS/IEC as reqd.including standard indication facilities as
perrequirement detailed herein after including supply of ABC
drypowder type 2nos, 5kg each and 2Nos each, CO₂ cylindertype with
pressure indicator fire extinguisher .
a. Incoming pannel with (CTR: 900-450/1-1-0.577A) Nos 2 Nos
2
9
-
201
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
10
Design, Engineering, Supply, Testing & commissioning of
11KV, 800 Amps continuos rated current, 350 MVA rupturing capacity
Indoor Vaccum Circuit Breaker( for outgoingfeeder) , complete with
1 set of CT of ratio 300/1-1, Control & Relay Pannel Simplex
type with 110 Volt DC actuatedelectrical closing/tripping mechanism
and internal wiring, 2-Over current & 1-earth fault combined
Micom digital relay,1 no.electromechanical AREVA Master Trip Relay,
auxiliaryrelays as required,1 no.L&T / SECURE make "Tri-
Vector"Meter(SCADA compatible), 3- Ammeter, 1 -Voltmeter, 1 -C.T
operated static KW meter , with panel bus mounted C.Tand integral
earthing facility including inernal arc tested panelConforming to
relevant ISS/IEC as reqd.including standardindication facilities as
per requirement detailed herein after.
Nos 5 Nos 5
11
Design, Engineering, Supply, Erection, Testing
&commissioning of 110V DC, 240Ah Capacity Sealed andMaintenance
Free(SMF) VRLA Battery Bank comprising of60 Nos. 2.2 Volt each Cell
(out of 60 cells, 5 Nos. beingspare) complete with all accessories
conforming to relevantISS as per latest amendment detailed in the
technicalspecification section of the document.
Set 1 Set 1
201
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
12
Design, Engineering,manufacturing, Supply, Erection, Testingat
site & commissioning of 415 VAC(plus minus 10%)nominal input
Voltage,50 HZ(plus minus 5%),110 Volt DCOutput with adjustable
range, 40A thyristor controlled float cum boost charger(with less
than 2% RMS ripple content,without battery connected)less than 60db
noise levelconstant voltage processed Battery charger compatible
foraforesaid VRLA battery Bank Conforming to relevant ISS andlatest
amendment complete with standard protection as per IP-54 to 20 as
per IS-2147,built in DCDB, standard indicationsand controls
including switches,temperature range of 50degree centigrade and
painted by RAL 7032 etc. as requireddetailed in technical
specification section of this document.
Nos 1 Nos 1
13
Design, manufacture, testing at works, transport to
site,insurance, erection and commissioning of 110Volt
D.C.Distribution Boards (DCDB) with dust tight ,verminproof,
gasketed door, enclosure made of sheet steel 2 mm.thick CRCA,
painted by powder coated paint RAL 7032with Aluminium busbar of
40x6 mm complete with(L&T/GE/C&S/HAVELLS make 1x160 A TP
MCCB, 1x32 ADC DP MCB, 6x16 A DC DP MCB, analog Volt &
Amperemeter,LED indication,Mains failure and Earth fault Relay
etc.including all control and protection gears complete as
perrequirement and asdetailed in technical specification sectionin
the document.
Nos 1 Nos 1
-
203
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
14
Design, manufacture, testing at works, transport to
site,insurance, storage, erection and commissioning of( L &
T/SECURE/GE make) 415 Volts, A.C. 50 Hz A.C. DistributionBoard
complete with 300 Amp. TPN with link in incomingsupply, 3
nos.300/5(15 VA) CT,300 Amp Aluminiumbusbar,1x100A TPN,3x63 A
TPN,2x32A TPN,3x63 ADP,5x32 A DP as per requrement including
provision forVoltage,Ampere indications and L&T/SECURE makeKWH
mete and accessories as described in technicalspecification.
Nos 1 Nos 1
1100 Volts grade PVC insulated PVC sheathed, 2.5sq.mm.( stranded
copper conductor) control cable witharmouring of following capacity
& core as per IS:1554(Part-I)1988.a) 2 Core 2.5mm2 b) 4 Core
2.5mm2 c) 7 Core 2.5mm2 d) 12Core 2.5mm2
Lot 1 Lot 1
16
Design, Engineering,manufacturing, Supply, laying in positionin
cable trench, Testing & commissioning of Single Core, 19/33 KV,
185 Sq. mm. XLPE insulated, screened armouredpower cable as per
TSECL approved design, drawing,specification and as reqd. as per
direction of Eng-In-Chargeand as detailed herein after in this
document.
Mtr 0 Mtr. 175
17
Design, Engineering, manufacturing ,Supply, laying in position
in cable trench, Testing & commissioning of Single Core,6.35/11
KV(E), 400 Sq. mm. XLPE insulated armoured powercable in cable
trench as per TSECL approved design, drawing,specification and as
reqd. as per direction of Eng-In-Chargeand as detailed herein after
in this document.
Mtr 0 Mtr. 300
15
203
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
18
Design, Engineering,manufacturing, testing at works,
Supply,laying in position in trench, Testing & commissioning
ofThree Core, 6.35/11 KV, 240 Sq. mm. XLPE insulatedarmoured power
cable in trench with supply of 1No Hyduliccrimping tool (capable of
crimping from range of 50 sqmm to400 sqmm size socket) as per
relevant ISS and detailed in theTechnical specification Section in
the document and directionof Eng-In-Charge.
Mtr 0 Mtr. 240
19
Design, Engineering, Supply, Testing & commissioning
&joints of Indoor type heat shrink end jointing kit for Single
core, 185 Sq.mm. Size, XLPE insulated Power Cable ofgrade
19//33KV(E), as per IS 7098 Part-II 1985 and latestammended.
Nos 16 Nos 16
20
Design, Engineering, Supply, Testing & commissioning
&joints of 0utdoor type heat shrink end jointing kit for Single
core, 185 Sq.mm. Size, XLPE insulated Power Cable ofgrade
19//33KV(E), as per IS 7098 Part-II 1985 and latestammended.
Nos 16 Nos 16
21
Design, Engineering, Supply, Testing & commissioning
&joints of Outdoor type heat shrink end jointing kit for
Singlecore, 400 Sq.mm. Size, XLPE insulated Power Cable ofgrade
6.35/11 KV(E). as per IS 7098 Part-II 1985 and latestammended.
Nos 16 Nos 16
22
Design, Engineering, Supply, Testing & commissioning
&joints of Indoor type heat shrink end jointing kit for
Singlecore, 400 Sq.mm. Size, XLPE insulated Power Cable ofgrade
6.35/11 KV(E). as per IS 7098 Part-II 1985 and latestammended.
Nos 16 Nos 16
-
205
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
23
Design, Engineering, Supply, Testing & commissioning
&joints of Out door type heat shrink end jointing kit for Three
core, 240 Sq.mm. Size, XLPE insulated Power Cable ofgrade 6.35/11
KV(E), as per IS 7098 Part-II 1985 and latestammended.
Set 6 Set 6
24
Design, Engineering, Supply, Testing & commissioning
&joints of Indoor type heat shrink end jointing kit for Three
core, 240 Sq.mm. Size, XLPE insulated Power Cable ofgrade 6.35/11
KV(E). as per IS 7098 Part-II 1985 and latestammended.
Nos 6 Set 6
25
Design, manufacturing, supply, erection, testing
&commissioning of 11 KV, 600 ampere rated outdoor typestandard
3 way Kiosk (CNC m/c fabricated and made of 3.25mm sheet) suitable
for11 KV cable termination as per relevantISS and IP with copper
Busbar and accessories as per TSECLspecification and erection
standard ( including grouting ofkiosk legs/support) as detailed
herein after.
Nos 2 Nos. 2
a) 9 KV, 5 KA, single pole, Metal oxide gapless surge type
LAsuitable for nominal system voltage of 11 KV, 3-Ph., 50 HzAC
supply, creepage distance 600 mm. conforming to ISS:3070 /
1985.
Nos 12 Nos. 12
b) 9 Mtr. Long steel tubular pole of designation 410-
SP-31conforming to ISS: 2713 / 1980 with base plate complete.
Nos 8 Nos. 8
c ) Steel materials ( channels size 100X50X50x6mm & 75X40X40
X6mm).
MT 1.089 MT 1.089
d ) Steel materials (Angles size 75 X 40 X6mm ). MT 0.15 MT
0.15e)45 KN, 11KV disc insulator with disc fittings. Nos 90 Nos 90f
) 11 KV, 10 KN pin insulator including G.I. pin. Nos 18 Nos 18g) 11
KV 3 pole GOS ( Air break type ) -400A. Set 8 Set 8h) 11KV 3 pole
DOF for station transformer 200A. Set 1 Set 1
SCHEDULR -"B"( 11 KV outgoing bus bar) .
26
205
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
i) Nuts & bolts assorted size Kg 30 Kg 30j) 50X6 mm M.S flat
for clamp Nos 67 Nos 67k ) ACSR (Rabbit ) 6/1/3.35 mm. Km 0.01 Km
0.01l ) Suitable for ACSR Rabbit conductor PG Clamp Nos 36 Nos
36
Design,Engineering, testing, manufacturing ,commissioning and
Supply of 3 Core, 19/33 KV, XLPEinsulated armoured power cable.a)
300sqmm Mtr. 0 Mtr. 0
2
Supply of 150 mm nominal bore (outer side dia: Min163.9mm &
Max. 166.5mm, Waii thickness: 5.40mm,21.30Kg /mtr.) heavy duty
(C-Class) make best quality GIPIPE as per ISS 1239(Pt-1)-2004,
equvalent to BS 1387/1985of different length as per requirement of
engineering for usingat road crossing/river crossing/cherra
crossing/Water supplypoint/Pipi Line/Telefhone line and riser to
feeder pilar, polesetc.
Mtr 200 Mtr 0
3
Boring for Laying of 150mm nominal bore (outer side dia:Min
163.9mm & Max. 166.5mm, Waii thickness: 5.40mm,21.30Kg/mtr.)
heavy duty (C-Class) make best quality GIPIPE direct into the earth
at a depth of 1100 mm below theground surface without affecting the
existing road by manualdigging / drilling either horizontally or
diagonally as requiredfor road crossing/ Water supply
line/Telcomunication line/GasPipe line crossing etc. as per
direction of Engineer- In Charge.
Mtr 0 Mtr 160
4Supply of 160mm outer diameter HDPE pipe( PE-80 grade)
ofworking presure 6 kgf /sq.cm. having minimum wall thickness9.1 to
10.3 mm.
Mtr 0 Mtr 0
SCHEDULE - "C" (33KV LINE, UG Cable)
1
-
207
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
5
Laying of 3 phase,3 core 300 sq.mm. 33 KV XLPE insulatedpower
cable below the road surface through HDPE piipe byAll Terrain
Horizontal Directional Dilling / Digging Machineacross & along
the road and road crossing without affectingthe existing Road
Surface at a depth of minimum 1100 mm. oras per site requirement of
TSECL depending on approvedroute survey with supply of HDPE Pipe
.
Mtr 0 Mtr 200
6
Erection, fitting-fixing of 150 mm dia GI PIPE of
differentlength as per engineering requirement above groud level:
for Rising of cable to pole/ feeder pillar /transformer and fitting
-fixing on pole,cross arm by MS Clamp and nut and bolts(including
supply of Clamp & Nut-Bolts) as required.
Mtr 0 Mtr 40
7
Laying and Commissioning of 1 no, 3 Core, 300sqmm, 19/33KV, XLPE
insulated armoured power cable direct into earthincluding
excavation of earth upto a depth of 1200mm (Widthof the trench 60
cm.) including 1st class brick protection oftwo layer flat brick
soling , 300 mm. sand (River sand)cushioning and refilling and
ramming the excavated soil asper direction of Engineer in
charge.
Mtr 0 Mtr. 2600
8
Laying and Commissioning of 3 Core, 19/33 KV,300 Sq.mm. XLPE
insulated power cable below the road surfacethrough already laid GI
PIPE without affecting roadsurface at a depth of minimum 1100 mm or
as per siterequirement of TSECL depending on approved layout.
Mtr 0 Mtr 160
9
Laying and Commissioning of 3 Core, 19/33 KV,300 Sq.mm. XLPE
insulated power cable above the ground level asrisers to poles,
transformer & feeder pillar through GI PIPEas per site
requirement and approved layout.
Mtr 0 Mtr 40
207
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
10Supply & jointing of Outdoor type heat shrink cable
endtermination kit for 19/33 KV(E), 3-core,300 Sq.mm. XLPEinsulated
Cable.
Nos 5 Nos 5
11Supply & jointing of Indoor type heat shrinkable
endtermination kit for 19/33 KV(E), 3-core, 300 Sq.mm.
XLPEinsulated Cable.
Nos 2 Nos 1
12Supply & joints of straight Through heat shrink cable
typejointing kit for 33 KV XLPE insulated cable, 300 Sq.mm.
Size.
Nos 16 Nos 16
13
Manufacturing,Construction and Erection of T-shapedPillar(made
of pre-cast RCC) for cable route ID MARKINGengraved with caption
"33 KV U.G.LINE"/"STRAIGHTTRHOUGH JOINT" of size(Pillar-3 ft. X
0.33 ft. X 0.33 ft.)and (T-section-1 ft.X0.33 ft.) by excavating
earth includingrequired painting of the of the engraved caption in
black overyellow background as per technical requirement, direction
ofthe Engineer-in-Charge. The Pillar shall be embedded in earthby
1.5 ft.
Nos 18 Nos 18
Supply & erection of fire fighting equipments with
completeaccessories .
a) G.I bucket - 10 ltrs capacity with wooden / iron stand. No. 6
No. 6
b) Portable fire extinguisher using CO2 with pressureindicator:
-5Kg.
No. 3 No. 3
c) ABC powder fire extinguisher "Mono Ammoniumphosphate".i) 5-
Kg No. 2 No. 2ii) 2- Kg No. 2 No. 2
15Supply, erection, testing & commissioning of 100
KVA,11/0.43 KV, DY- 11 distribution transformer for station
load.
No. 1 No. 1
14
-
209
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
16Supply & erection of 7.5 Mtr long GI support (heavy
dutytype) having bottom length 4 mtr. of dia 65 mm and upperlength
of 3 mtr. and 40 mm. dia.
No. 16 No. 16
17Supply & erection of Switchyard lighting complete
with250W, 230V, HPSV luminaries with switchgear complete.
Unit 12 Unit 12
18 Supply of Shock treatment chart (Laminated ) No. 2 No. 019
Supply of Artificial respirator No. 2 No. 0
20Supply Rubber insulating mat at 15 KV tested of size
(1X2)mtr.
No. 8 No. 0
21Supply of Oill filtration plant of capacity 250 G.P.H.(NIRMAL
BRAND / John Fowler).
No. 1 No. 0
22Supply of Hand driven Insulation Tester 5KV (WACOmake),10000
Mohm minimum.
No. 1 No. 0
23Supply of Hand driven Insulation Tester 2.5KV (WACOmake),10000
Mohm minimum.
No. 1 No. 0
2433 KV discharge Rod of 3 section made of fibre glass
tubecomplete with all accessaries as per specification.
Set 2 Set 0
25Crimping tool AAKASH-100 Capacity 6 mmsqr- 400 mm sqr.Weight
5.8 Kg.
No. 1 No. 0
26Supply of 40mm dia hot Dip perforated G.I pipe of length 3mtr
and providing earthing as per latest ISS: at 33 KV &11KV switch
yard.
No. 12 No. 12
27Supply and laying of GI wire, 50 X 6 mm size for
interconnection of earth electrodes and earthing terminals
ofequipments, structures as required for earthing.
Mtr. 20 No. 12
Supplying and fixing of PVC casing and capping in/c.
allaccessories as required (Make : - Presto - plast /
Precision)
a) 25 mm X 10 mm. Mtr. 0 Mtr. 180 b) 40 mm X 20 mm. Mtr. 0 Mtr.
60
1
SCHEDULE-"D" (Internal electrification of control room
209
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Supplying and drawing of PVC insulated copper conductorcable in
existing PVC casing -capping / conduit in/c. necessaryconnection as
required. (Make: - Havell's / National / Plaza.)
a) 2 X 1.5 Sq. mm. Mtr. 0 Mtr. 300 b) 2 X 4 Sq. mm. Mtr. 0 Mtr.
100 c) 2 X 6 Sq. mm. Mtr. 0 Mtr. 50
Supplying and fixing of accessories for PVC casing andcapping
in/c. necessary connection as required. Make: -Anchor / Precision /
Cona (Nice) / SSK / J.J. Deluxe (Fancy).
a) Ceiling rose. No. 0 No. 20 b) Angle lamp holder. No. 0 No. 20
c) 5/6 Amp. piano switch. No. 0 No. 50 d) 5/6 Amp. socket. No. 0
No. 8 e) 15/16 Amp.piano switch. No. 0 No. 5 f) 15/16 Amp. 5 pin
socket. No. 0 No. 5 g) Ding dong call bell. No. 0 No. 1
4
Supplying and fixing of 415 volt, 63 amp. TPN main
switch(Rewireable) front handle in/c. drilling holes on wooden
boardand connection as required. (Make: - Havells / HPL
/Standard).
No. 0 No. 2
5
Supplying and fixing of 6 ways metal enclosure for 240/415Volts
MCB (SP/SPN/DP/FP) complete with necessary bus bar,earth bar,
neutral link etc. including connection as required.(Make: - Havells
/ HPL / Standard).
No. 0 No. 2
6
Supplying and fixing of 5 to 32 Amps. rating 240 Volts 'G'Series
MCB of single pole in the existing MCB DB completewith connection
etc. as required. (Make: - Havells / HPL /Standard).
No. 0 No. 10
2
3
-
211
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
7Providing earthing with 40 mm dia. GI perforated pipe of
4.5
mtr. long with masonary enclosure on top etc. as required. No. 0
No. 2
8Extra for using salt and charcoal for pipe earth elctrode
as
required. Set. 0 Set. 2
9Providing and fixing 8 swg GI wire on surface or in conduit
pipe for loop earthing. Mtr. 0 Mtr. 10
10Providing and laying earth connection from earth electrode
with 8 swg GI wire / copper wire in 15 mm dia. G.I. pipe
fromearth electrode as required.
Mtr. 0 Mtr. 12
11Supplying and drawing of 4 sq. mm. aluminium conductor
wire for loop earthing including connection as required. Mtr. 0
Mtr. 150
12
Supplying and fixing of single box type FTL fittingscomplete
with 1 no. 40 / 36 watt copper ballast, 40/36 wattflurosent tube,
starter, holder, pf improving capacitor etc. in/c.connection as
required. (Make: - Phillips / Crompton / Bajaj).
No. 0 No. 10
13
Supplying and fixing of double box type T 5 rated energyefficent
FTL fittings complete with 2 nos. 40 / 36 watt copperballast, 2
nos. 40/36 watt flurosent tube, starter, holder, pfimproving
capacitor etc. in/c. connection as required. (Make: -Phillips /
Crompton / Bajaj).
No. 0 No. 8
14
Supplying and fixing of ceilling luminaries with 2 nos. PLS11
Watt lamp and mirror optics including necessaryconnection as
required. (Make: - Phillips, Cat no.-FCS - 31 /211).
No. 0 No. 2
Supplying and fixing of accessories for PVC casing andcapping
in/c. necessary connection as required.
0 0
a) 102 mm X 102 mm, size wooden formica board withbakelite
cover.
No. 0 No. 30
211
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
b) 102 mm X 178 mm, size wooden formica board withbakelite
cover.
No. 0 No. 8
c) 152 mm X 203 mm, size wooden formica board withbakelite
cover.
No. 0 No. 4
d) 203 mm X 300 mm, size wooden formica board withbakelite
cover.
No. 0 No. 6
e) 254 mm X 300 mm, size wooden formica board withbakelite
cover.
No. 0 No. 4
16Supplying and fixing of 300 mm sweep exhaust fan including
necessary connection as required. (Make: - Crompton /Khaitan /
USHA / Orient).
No. 0 No. 4
17Supplying and fixing of necessary shutter for 300 mm
exhaust
fan in the existing whole including necessary painting etc.
asrequired.
No. 0 No. 4
18
Supplying and fixing of 1200 mm sweep ceilling fanincluding
fixing of regulator and wiring in down rod ofstandard length etc.
as required. (Make: - Crompton / Khaitan /Orient / USHA).
No. 0 No. 12
19Supplying and fixing of 18 watt CFL in the existing angle
holder. (Make: - Phillips / Bajaj / Orpat. No. 0 No. 10
Earth work in excavation over areas (exceeding 30cm in
depth,1.5m in width as well as 10 sqm on plan) including disposal
ofexcavated earth, lead upto 50m and lift upto 1.5m, disposedearth
to be levelled and neatly dressed.
-All kinds of soilBy manual means cum 0 cum 0
15
SCHEDULE -"E" R.C.C FRAMED CONTROL ROOM BUILDING
SUBHEAD- EARTHWORK
1
-
213
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Earth work in excavation in foundation trenches or drains
(notexceeding 1.5 m in width or 10 sqm on plan) includingdressing
of sides and ramming of bottoms, lift upto 1.5 m,including getting
out the excavated soil and disposal of surplusexcavated soil as
directed, within a lead of 50 m.
-All kinds of soilBy manual means cum 0 cum 0Extra for
additional lift of 1.5m or part thereof-All kinds of soil cum 0 cum
0
Filling available excavated earth (excluding rock) in
trenches,plinth, sides of foundations etc. in layers not exceeding
20cmin depth, consolidating each deposited layer by ramming
andwatering, lead up to 50 m and lift upto 1.5 m.
-All kinds of soil cum 0 cum 0
5
Supplying and filling in plinth, under floor, foundations
etc.with sand (fine) from local quarry with all lifts
includingspreading in horizontal layers, watering, grading to
requiredslope, ramming, consolidating and compacting each layer
byusing plate compactor or by any suitable method complete.
cum 0 cum 0
Supplying chemical emulsion in sealed containers
includingdelivery as specified.Chlorpyriphos/Lindane emulsifiable
concentrate of 20% Litre 0 Litre 0
2
3
4
6
213
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Diluting and injecting chemical emulsion for PRE-CONSTRUCTIONAL
anti-termite treatment (excluding thecost of chemical emulsion) and
continuous chemical barrierunder and alround the column pits, wall
trenches, basementexcavation, top surface of plinth filling,
junction of wall andfloor, along the external perimeter of
building, expansionjoints, over the top surface of consolidated
earth of whichapron is to be laid, surroundings of pipes and
conduits etc.complete as per specification. The work should be
carried outas per IS: 6313 (Part II)- Latest revision [Plinth area
of thebuilding at ground floor only shall be measured for
payment]
With Chlorpyriphos/Lindane E.C. 20% with 1% concentration. sqm 0
sqm 0
Providing and laying in position cement concrete of
specifiedgrade excluding the cost of centring and shuttering -
-All work upto plinth level:1:4:8 ( 1 Cement: 4 fine sand : 8
graded stone aggregate 40mm nominal size)
cum 0 cum 0
1:3:6 ( 1 Cement: 3 fine sand : 6 graded stone aggregate 40mm
nominal size)
cum 0 cum 0
1:2:4 ( 1 Cement: 2 fine sand : 4 graded stone aggregate 20mm
nominal size)
cum 0 cum 0
Providing and laying in position specified grade of
reinforcedcement concrete excluding the cost of centring,
shuttering,finishing and reinforcement--All work upto plinth
level:1:1½:3 ( 1 Cement: 1½ fine sand : 3 graded stone aggregate
20mm nominal size)
cum 0 cum 0
7
SUBHEAD-CEMENT CONCRETE WORKS
8
SUBHEAD-R.C.C WORK
9
-
215
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Reinforced cement concrete work in walls (any
thickness),including attached pilasters, buttresses, plinth and
skirtingcourses, fillets, columns, pillars, piers, abutments, posts
andstruts etc. upto floor five level excluding cost of
centring,shuttering, finishing and reinforcement-
In walls (any thickness), including attached
pilasters,buttresses, piers, abutments etc.1:1½:3 ( 1 Cement: 1½
fine sand : 3 graded stone aggregate 20mm nominal size)
cum 0 cum 0
In plinth and skirting courses, fillets, columns, pillars,
postsand struts1:1½:3 ( 1 Cement: 1½ fine sand : 3 graded stone
aggregate 20mm nominal size)
cum 0 cum 1.01
Reinforced cement concrete work in beams, suspended floors,roofs
having slope upto 15° landings, balconies, shelves,chajjas,
lintels, bands, plain window sills, staircases and spiralstair
cases upto floor five level excluding the cost of
centring,shuttering, finishing and reinforcement-
RCC work in suspended floors, roofs having slope upto
15°landings, balconies, shelves and chajjas.1:1½:3 ( 1 Cement: 1½
fine sand : 3 graded stone aggregate 20mm nominal size)
cum 0 cum 0
RCC work in beams, lintels, bands, plain window sills,staircases
and spiral staircases excluding precast spiralstaircase. 1:1½:3 ( 1
Cement: 1½ fine sand : 3 graded stone aggregate 20mm nominal
size)
cum 0 cum 0
Providing and laying upto floor five level reinforced
cementconcrete work in kerbs, steps and the like excluding the cost
ofcentring, shuttering, finishing and reinforcement-
10
11
12
215
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
1:1½:3 ( 1 Cement: 1½ fine sand : 3 graded stone aggregate 20mm
nominal size)
cum 0 cum 0.47
13
Providing, hoisting and fixing upto floor five level
precastreinforced cement concrete work in shelves including
settingin cement mortar 1:3(1cement : 3 fine sand), cost of
requiredcentring, shuttering, finishing with neat cement punning
onexposed surfaces complete, but excluding cost ofreinforcement
with cement concrete 1:2:4 (1cement : 2 finesand : 4 graded stone
aggregate 20mm nominal size).
cum 0 cum 0.83
Centering shuttering including struttings, propping etc.
andremoval of form work for:Foundations, footings, bases for
columns etc. for massconcrete with timber plank
sqm 0 sqm 39.65
Walls (any thickness) including attached pilasters,
buttresses,plinth and string courses etc. using shuttering ply
sqm 0 sqm 0
Suspended floors, roofs, landings, balconies and accessplatform
with 12 mm thick shuttering ply
sqm 0 sqm 4.71
Lintels, beams, plinth beams, girders, bressumers andcantilevers
with shuttering ply
sqm 0 sqm 73.76
Columns, Pillars, Piers, Abutments, Posts and Struts
withshuttering ply
sqm 0 sqm 46.7
Spiral staircases (including landing) - cast-in-situ with ply
sqm 0 sqm 17.5
14
-
217
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
15
Providing, hoisting and fixing upto floor five level
precastreinforced cement concrete work in mouldings as in
cornices,windows sills etc. including setting in cement
mortar1:3(1cement : 3 fine sand), cost of required
centring,shuttering, finishing smooth with 6mm thick cement
plaster1:3 (1cement : 3 fine sand) on exposed surfaces complete,
butexcluding cost of reinforcement with cement concrete
1:2:4(1cement : 2 fine sand : 4 graded stone aggregate 20mmnominal
size).
cum 0 cum 0.44
Reinforcement for R.C.C. work including straightening,cutting,
bending, placing in position and binding all completeupto floor
five level.Thermo-Mechanically Treated bars/ Cold twisted
deformedsteel bars
kg 0 kg 1815.07
First class brick work in foundation and plinth including costof
all materials as required complete:-In cement mortar 1:4 ( 1 cement
: 4 fine sand ). Cum. 0 Cum. 17.56First class brick work in
superstructure above plinth level &upto floor-five level
including cost of all materials as requiredcomplete:-In cement
mortar 1:4 ( 1 cement : 4 fine sand ). Cum. 0 Cum. 0
19Half brick masonry work with first class bricks in
foundationand plinth including cost of all materials as required
complete:-
Sqm. 0 Sqm. 27.17
Half brick masonry work with first class bricks insuperstructure
upto floor five level including cost of allmaterials as required
complete:-In cement mortar 1:4 ( 1 cement : 4 fine sand ). Sqm. 0
Sqm. 17.996
16
SUBHEAD- BRICK WORK
17
18
20
217
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Extra for providing & placing in position 2 nos 6mm dia
MSbars at every 6th course of full brick masonry work
includinganchorage in joints of 75mm in each side in superstructure
forall level including cost of all materials as required
complete:-
In cement mortar 1:4 ( 1 cement : 4 fine sand ). Cum. 0 Cum.
0
Extra for providing & placing in position 2 nos 6mm dia
MSbars at every 4th course of half brick masonry work
includinganchorage in joints of 75mm in each side in superstructure
forall level including cost of all materials as required
complete:-
In cement mortar 1:4 ( 1 cement : 4 fine sand ). Sqm. 0 Sqm.
17.996
Providing wood work in frames of doors, windows,
clerestorywindows and other frames, wrought framed and fixed
inposition :Karai wood Cum 0 Cum 0.25
Providing and fixing ISI marked flush door shuttersconforming to
IS: 2202 (Part I) decorative type, core of blockboard construction
with frame of 1st class hard wood and wellmatched teak 3 ply
veneering with vertical grains or crossbands and face veneers on
both faces of shutters.
35 mm thick including ISI marked Stainless Steel butt hingeswith
necessary screws.
Sqm 0 Sqm 6.3
Providing and fixing M.S. grills of required pattern in framesof
windows etc. with M.S. flats, square or round bars etc.
allcomplete.
Fixed to openings /wooden frames with rawl plugs screws etc. Kg
0 Kg 625
21
22
SUBHEAD- WOOD WORK
23
24
25
-
219
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
26
Providing 40 × 5 mm flat iron hold fast 40 cm long
includingfixing to frame with 10 mm diameter bolts, nuts and
woodenplugs and embedding in cement concrete block 30 × 10 × 15cm
1:3:6 mix (1 cement : 3 fine sand : 6 graded stoneaggregate 20mm
nominal size)
No 0 No 18
27
Providing and fixing chromium plated brass 100 mm morticelatch
and lock with 6 levers and a pair of lever handles withnecessary
screws etc. complete (best make of approvedquality).
No 0 No 3
Providing and fixing aluminium sliding door bolts ISI
markedanodised (anodic coating not less than grade AC 10 as per IS
:1868) transparent or dyed to required colour or shade with nutsand
screws etc. complete :300x16 mm No 0 No 6Providing and fixing
aluminium tower bolts ISI markedanodised (anodic coating not less
than grade AC 10 as per IS :1868 ) transparent or dyed to required
colour or shade withnecessary screws etc. complete :300x10 mm No 0
No 4Providing and fixing aluminium handles ISI marked
anodised(anodic coating not less than grade AC 10 as per IS :
1868)transparent or dyed to required colour or shade with
necessaryscrews etc. complete :125 mm No 0 No 4
Providing and fixing aluminium hanging floor door stopper
ISImarked anodised (anodic coating not less than grade AC 10 asper
IS : 1868) transparent or dyed to required colour and shadewith
necessary screws etc. complete.
Twin rubber stopper No 0 No 4
28
29
30
31
219
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
32
Providing and fixing factory made P.V.C. door frame of size
50x47mmwith a wall thickness of 5mm, made out of extruded 5mm rigid
PVC foamsheet mitred at corners and joined with 2 Nos. of 150mm
long brackets of15x15mm M.S. square tube, the vertical door
profiles to be reinforced with19×19mm MS square tube of 19 gauge,
EPDM rubber gasket weather sealto be provided through out the frame
. The door frame to be fixed to thewall usuing MS screws of 65/100
mm size complete as per manufacturers'specification and direction
of Engineer-In-Charge.
mtr. 0 mtr. 5
Providing and fixing to existing door frames.
30mm thick factory made solid both side prelam panel PVC
doorshutter consisting of frame made out of M.S. tubes of 19
gaugethickness and size of 19mm x 19mm for styles, top & bottom
rails.M.S. frame shall have a coat of steel primers of approved
makeand manufacture . M.S. frame covered with 5mm thick heatmoulded
prelam PVC ‘C channel of size 30mm thickness, 70mmwidth out of
which 50mm shall be flat and 20mm shall be taperedin 45degree angle
on either side forming stiles; and 5mm thick,95mm wide PVC sheet
out of which 75mm shall be flat and 20mmshall be tapered in 45
degree on the inner side to form top andbottom rail and 115mm wide
PVC sheet out of which 75mm shallbe flat and 20mm shall be tapered
on both sides to form lock rail.Top, button and lock rails shall be
provided either side of thepanel. 10mm (5mm x 2 ) thick, 20mm wide
cross PVC sheet beprovided as gap insert for top rail & bottom
rail, panelling of 5mmthick both side Prelam PVC sheet to be fitted
in the M.S. framewelded/ sealed to the stiles & rails with 7mm
(5mm+2mm) thick x15mm wide PVC sheet beading on inner side, and
joined togetherwith solvent cement adhesive. An additional 5mm
thick PVC stripof 20mm width is to be stuck on the interior side of
the ‘C Channelusing PVC solvent adhesive etc. complete as per
direction ofEngineer-in-charge. manufacturer’s specification &
drawing.
sqm 0 sqm 233
-
221
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
0 0
34
Providing structural steel work in single section fixed with
orwithout connecting plate including cutting, hoisting, fixing
inposition and applying a priming coat of approved steel primerall
complete as required.
Kg. 0 Kg. 200
35
Providing and fixing in position collapsible steel shutters
withvertical channels 20x10x2mm at 100 mm centre to centre
andbraced with flat iron diagonals 20x5mm size with top andbottom
rail of T-iron 40x40x6mm with 40mm dia. steelpulleys & with
riveted bolts, nuts, locking arrangement,stoppers, handles, hold
fast /anchor bolt including embeddingin cement concrete of required
grade for fixing in position, allnecessary fittings, including
applying a priming coat ofapproved steel primer etc. complete as
required.
Sqm. 0 Sqm. 5.25
Providing and fixing 1mm thick M.S. sheet door with frame
of40x40x6mm angle iron and 3mm M.S. gusset plates at thejunctions
and corners, & with cleats with bolts & nuts,
rivets,locking arrangement, handles, hooks & eyes, pinlets
includingembedding in cement concrete of required grade for fixing
inposition, all necessary fittings, including applying a
primingcoat of approved steel primer etc. complete as
required:-
Using M.S. angels 40x40x6 mm for diagonal braces. Sqm. 0 Sqm.
2.1
SUBHEAD- STEEL WORK
36
221
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Supplying and fixing rolling shutters of approved make, madeof
required size M.S. laths interlocked together through theirentire
length and jointed together at the end by end locksmounted on
specially designed pipe shaft with brackets, sideguides and
arrangements for inside and outside locking withpush and pull
operation complete including the cost ofproviding and fixing
necessary 275mm long wire springs gradeNo.2 and M.S. top cover of
required thickness for rollingshutters & with handles, hold
fast including embedding incement concrete of required grade
required for fixing inposition, all necessary fittings, including
applying of approvedsteel primer etc. complete as required:-
80xl.25mm M.S. laths with 1.25 mm thick top cover. Sqm. 0 Sqm.
0
38Providing and fixing ball bearing for rolling shutters
(exceeding 10 sqm area ) of approved make complete asrequired.
Each 0 Each 0
39
Providing and fixing circular/ Hexagonal cast iron or M.S.sheet
box for ceiling fan clamp of internal dia 140mm, 73mmheight, top
lid of 1.5mm thick M.S. sheet with its top surfacehacked for proper
bonding, top lid shall be screwed into thecast iron/ M.S. sheet box
by means of 3.3mm dia. roundheaded screws, one lock at the corners.
Clamp shall bemade of 12mm dia M.S. bar bent to shape, including
paintingthe exposed portion as per standard drawing complete
asrequired (provided incase of low ceiling height).
Each 0 Each 0
Steel work welded in built up section/framed work
includingcutting, hoisting, fixing in position and applying a
primingcoat of approved steel primer using steel etc. complete
asrequired:-In grating, frames, guard bar, railing, brackets, gates
andsimilar works, all complete.
Kg. 0 Kg. 6.86
37
40
-
223
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Providing and laying polished vitrified floor tiles in
differentsizes ( thickness to be specified by the manufacturer )
withwater absorption less than 0.08 % and conforming to IS :15622
of approved make in all colours, shades over 20 mmthick bed of
cement mortar 1 : 4 ( 1 cement : 4 fine sand )jointed with ordinary
cement slurry including pointing withwhite cement mixed with
pigment of matching shadecomplete.Size of tile 60x60 cm sqm 0 sqm
10.5
Providing and fixing precast chequered cement concrete tiles22
mm thick, laid in footpath & courtyard, on 20 mm thick bedof
cement mortar 1 : 4 ( 1 cement : 4 fine sand ) jointed withneat
cement slurry mixed with pigment to match the shade oftiles
including rubbing and polishing complete.
In dark shade using ordinary cement sqm 0 sqm 20
43
Providing and fixing 1st quality ceramic glazed wall
tilesconforming to IS : 15622 ( thickness to be specified by
themanufacturer ) of approved make in all colours, shades
exceptburgundy, bottle green, black of any size as approved
byEngineer-in-charge in skirting, risers of steps and dados over12
mm thick bed of cement mortar 1 : 3 ( 1 cement : 3 finesand )
jointed with ordinary cement slurry including pointingwith white
cement mixed with pigment of matching shadecomplete.
sqm 0 sqm 40
SUBHEAD-FLOORING WORK
41
42
223
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
44
Providing and laying 1st quality ceramic glazed floor tiles 300x
300 mm conforming to IS : 15622 ( thickness to be specifiedby the
manufacturer ) of approved make in colours, shadessuch as white,
ivory, grey, fume red, brown over 20 mm thickbed of cement mortar 1
: 4 ( 1 cement : 4 fine sand ) jointedwith ordinary cement slurry
including pointing with whitecement mixed with pigment of matching
shade complete.
sqm 0 sqm 7.5
Providing and fixing Kota stone in floors over 20 mm thickbed of
cement mortar 1 : 4 ( 1 cement : 4 fine sand ) jointedwith ordinary
cement slurry including pointing with ordinarycement mixed with
pigment of matching shade, includingrubbing and polishing
complete.
Kota stone slab 30mm thick sqm 0 sqm 90
Providing and fixing aluminium work for doors,
windows,ventilators, stair railing including hand rail and
partitionswith extruded built up standard tubular
sections/appropriate Z sections and other sections of approvedmake
conforming to IS: 733 and IS : 1285, fixed with rawlplugs and
screws or with fixing clips, or with expansionhold fasteners
including necessary filling up of gaps atjunctions, at top, bottom
and sides with requiredPVC/neoprene felt etc. aluminium sections
shall be smooth,rust free, straight, mitred and jointed
mechanically whereverrequired including cleat angle, aluminium snap
beading forglazing / paneling, C.P. brass / stainless steel screws,
allcomplete as per architectural drawing and the direction
ofEngineer-in-charge. (Glazing and paneling to be paid
forseparately) :-For fixed portion of approved quality:-
45
SUBHEAD-ALUMINIUM WORK
46
-
225
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Anodised aluminium (anodised transparent or dyed torequired
shade according to IS: 1868, Minimum anodiccoating of grade AC
15).
Kg. 0 Kg. 150
For shutters/ sliding shutters of doors, windows &
ventilatorsincluding providing and fixing hinges / pivots / rollers
andmaking provision for fixing fittings wherever requiredincluding
the cost of PVC / neoprene gasket required ofapproved quality (
Fittings shall be paid for separately ):-
Anodised aluminium (anodised transparent or dyed torequired
shade according to IS: 1868, Minimum anodiccoating of grade AC
15).
Kg. 0 Kg. 125
Providing and fixing glazing of approved quality in
aluminiumdoors, windows, ventilator, shutters and partition frames
withPVC / neoprene gasket etc. complete as per architecturaldrawing
and the direction of Engineer-in-charge :-
With glass/ float glass panes of 5.5 m thickness ( weight
notless than 13.50 kg / sqm )
Sqm. 0 Sqm. 6.3
With glass/ float glass panes of 4.0 m thickness ( weight
notless than 10.0 kg / sqm )
Sqm. 0 Sqm. 17.4
Providing and fixing double action hydraulic floor spring
ofapproved brand and manufacture ( conforming to IS : 6315 )for
aluminium doors including cost of cutting floors asrequired,
embedding in floors and cover plates etc. complete asper direction
of the Engineer-in-charge:-With stainless steel cover plate. Each 0
Each 1
47
48
49
225
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Providing and fixing aluminium work consisting of tee /
anglesections, of approved make conforming to IS : 733 in framesof
false ceiling including aluminium angle cleats withnecessary C.P.
brass / stainless steel sunk screws, aluminiumperimeter angles
fixed to wall with rawl plugs @ 450 mmcentre to centre and fixing
the frame work to 6 mm dia G.I.level adjusting hangers with
necessary cadmium platedmachine screws all complete as per
architectural drawing andthe direction of Engineer-in-charge (
level adjusting hangers,ceiling cleats and expansion hold fasteners
to be paid forseparately ):-
Anodised aluminium (anodised transparent or dyed to
requiredshade according to IS : 1868 , minimum anodic coating
ofgrade AC 15 ).
Kg. 0 Kg. 8.75
51
Providing and filling the gap in between aluminium frame
andadjacent RCC / brick work by providing weather siliconsealant
over backer rod of approved quality etc. complete asper
architectural drawing and direction of the Engineer-incharge:- (i)
Upto 5 mm depth and 5 mm width.
Metre 0 Metre 50
Providing and fixing 12 mm thick prelaminated three layermedium
density (exterior grade ) particle board grade-I, type IIconforming
to IS : 12823 bonded with phenol formaldehydesynthetic resin, of
approved brand and manufacture inpanelling fixed in aluminium
doors, windows, shutters andpartition frames with C.P. brass /
stainless steel screws allcomplete as per architectural drawing and
the direction ofEngineer-in-charge :-Prelaminated particle board of
approved quality withdecorative lamination on both side.
Sqm. 0 Sqm. 4.5
50
52
-
227
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Providing and fixing aluminium casement windows fastener
ofrequired length for aluminium windows with necessary screwsetc.
of approved quality complete as per direction of
Engineer-in-charge:-Anodised aluminium of grade AC 15 ). Each 0
Each 10Providing and fixing aluminium tubular handle bar of 32
mmouter dia, 3.0 mm thick and 2100 mm long with Stainless
Steelscrews etc. of approved quality complete as per direction
ofEngineer-in-charge:-Anodised aluminium of grade AC 15 ). Each 0
Each 3
55
Providing and fixing 100 mm brass locks ( best make ofapproved
quality ) with 6 levers without pair of handles foraluminium doors
including necessary cutting and making goodetc. complete as per
direction of Engineer-in-charge.
Each 0 Each 3
0 0Providing and fixing on wall face unplasticised RigidPVC rain
water pipes (working pressure 4 kg / cm2)conforming to IS : 13592
Type A including jointing withseal ring conforming to IS : 5382
leaving 10 mm gap forthermal expansion:
0 0
Single socketed pipe - 110 mm OD m 0 m 50Providing and fixing on
wall face unplasticised - PVCmoulded fittings/ accessories for
unplasticised Rigid PVCrain water pipes conforming to IS : 13592
Type A includingjointing with seal ring conforming to IS : 5382
leaving 10mm gap for thermal expansion:Coupler110 mm each 0 each
5Bend 87.5°110mm each 0 each 10
53
54
SUBHEAD- ROOFING WORK
56
57
227
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Providing and fixing unplasticised -PVC pipe clips ofapproved
design to unplasticised - PVC rain water pipes bymeans of
50x50x50mm hard wood plugs, screwed withM.S. screws of required
length including cutting brick workand fixing with cement mortar 1
: 4 (1cement : 4 fine sand)making good the wall etc. complete.
110mm each 0 each 30
12 mm cement plaster in single layer including cost ofmaterials
required and finishing even and smooth and curingcomplete.In cement
mortar 1 : 4 ( 1 cement : 4 fine sand ) sqm 0 sqm 015 mm cement
plaster in single layer including cost ofmaterials required and
finishing even and smooth and curingcomplete.In cement mortar 1 : 4
( 1 cement : 4 fine sand ) sqm 0 sqm 282.62
6 mm cement plaster in single layer including cost of
materialsrequired and finishing even and smooth and curing
complete.
In cement mortar 1 : 3 ( 1 cement : 3 fine sand ) sqm 0 sqm
58.3162 Neat cement punning. sqm 0 sqm 5.91
63Extra for providing and mixing water proofing material
incement plaster work in proportion recommended by
themanufacturers.
kg 0 kg 50
64Providing and applying plaster of paris putty of 2 mmthickness
over plastered surface to prepare the surface evenand smooth
complete.
sqm 0 sqm 460
65Applying one coat of cement primer of approved brand
andmanufacturer on wall surface complete.
sqm 0 sqm 725.82
58
SUBHEAD- FINISHING WORK
59
60
61
-
229
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
66
Finishing walls with premium acrylic smooth exterior paint
ofrequired shade of approved brand and manufacture on newwork ( two
or more coats applied @ 1.43 kg/10 sqm ) over andincluding base
coat water proofing cement paint applied @2.20 kg/10 sqm
complete.
sqm 0 sqm 225
Applying priming coat:With ready mixed pink primer of approved
brand andmanufacture on wood work ( hard & soft wood ).
sqm 0 sqm 15
With ready mixed red oxide zinc chromate primer of approvedbrand
and manufacture on steel, galvanised iron / steel work.
sqm 0 sqm 50
Finishing with epoxy paint ( two or more coats ) of
approvedbrand and manufacture at all locations prepared and applied
asper manufacturer's specification on new work includingappropriate
priming coat, preparation of surface etc. complete.
On steel work sqm 0 sqm 50
69Wall painting with plastic emulsion paint ( two or more coats
)of required colour of approved brand and manufacture on newwork to
give an even shade.
sqm 0 sqm 650.82
70Painting with black anticorrosive bitumastic paint ( two
ormore coats ) of approved brand and manufacture on new workto give
an even shade.
sqm 0 sqm 35.4
Providing and fixing water closet squatting pan (Indian typeW.C.
pan ) with 100mm sand cast Iron P or S trap, 10 litre lowlevel
white P.V.C. flushing cistern with manually controlleddevice
(handle lever) conforming to IS : 7231, with allfittings and
fixtures complete including cutting and makinggood the walls and
floors wherever required :
67
68
SUBHEAD- SANITARY WORK
71
229
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
White Vitreous china Orrisa pattern W.C. pan of size 580x440mm
with integral type foot rests.
each 0 each 1
Providing and fixing white vitreous china pedestal typewater
closet (European type W.C. pan) with seat and lid,10 litre low
level white P.V.C. flushing cistern withmanually controlled device
(handle lever), conforming to IS :7231, with all fittings and
fixtures complete including cuttingand making good the walls and
floors wherever required :
W.C. pan with ISI marked white solid plastic seat and lid each 0
each 1
Fixing white vitreous china flat back half stall urinal ofsize
580x380x350mm with white PVC automatic flushingcistern, with
fittings, standard size C.P. brass flush pipe,spreaders with unions
and clamps (all in C.P. brass) withwaste fitting as per IS : 2556,
C.I. trap with outlet gratingand other couplings in C.P. brass
including painting offittings and cutting and making good the walls
and floorswherever required :
Single half stall urinal with 5 litre P.V.C. automatic
flushingcistern.
each 0 each 2
Providing and fixing wash basin with C.I. brackets, 15 mmC.P.
brass pillar taps,32 mm C.P. brass waste of standardpattern,
including painting of fittings and brackets, cuttingand making good
the walls wherever require :
White Vitreous China Wash basin size 630x450 mm with asingle 15
mm C.P. brass pillar taps.
each 0 each 2
75Providing and fixing white vitreous china pedestal for
washbasin completely recessed at the back for the reception of
pipes and fittings.
each 0 each 1
Providing and fixing P.V.C. waste pipe for sink or wash
basinincluding P.V.C. waste fittings complete.
72
73
74
76
-
231
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Flexible pipe32 mm dia each 0 each 4
77Providing and fixing 100 mm sand cast Iron grating for
gullytrap.
each 0 each 4
78
Providing and fixing 600x450 mm bevelled edge mirror ofsuperior
glass (of approved quality) complete with 6 mm thickhard board
ground fixed to wooden cleats with C.P. brassscrews and washers
complete.
each 0 each 2
79
Providing and fixing 600x120x5mm glass shelf with edgesround of
supported on anodised aluminium angle frame withC.P. brass brackets
and guard rail complete fixed with 40 mmlong screws, rawl plugs
etc., complete.
each 0 each 2
Providing and fixing terminal guard:100 mmSand cast iron S&S
as per IS - 3989 each 0 each 2Providing and fixing PTMT towel rail
complete with bracketsfixed to wooden cleats with CP brass screws
with concealedfitting arrangement of approved 450mm long towel rail
withtotal length of 495mm, 78mm wide and effective heightquality
and colour.600mm long towel rail with total length of 645mm,
width78mm and effective height of 88mm, weighing not less
than190gms.
each 0 each 2
82
Providing and fixing PTMT liquid soap container 109mmwide, 125mm
high and 112mm distance from wall of standardshape with bracket of
the same materials with snap fittings ofapproved quality and
colours weighing not less than 105 gms
each 0 each 2
76
80
81
231
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Providing, fixing and laying rigid UPVC pipes conforming toIS
:4985 jointing with couplers, of same class conforming toIS : 10124
( Pt-II ) with solvent cement conforming to IS :14182 including
testing of joints complete ( but excluding thecost of specials like
bend, tees etc. which will be paidseparately ) as per chapter 20 of
CPWD specification anddirection of the Engineer - in - charge.
Class - 3 ( working pressure 6.0 kg / cm2)90 mm OD Mtr. 0 Metre
45110 mm OD Mtr. 0 Metre 25
Providing, fixing and laying fabricated UPVC bend of
requireddegree conforming to IS : 10124 ( part 8 / 9 / 10 / 11 / 12
/ 13 )with solvent cement conforming to IS : 14182 includingtesting
of joints complete as per chapter 20 of CPWDspecification and
direction of the Engineer - in - charge.
90 mm OD No 0 No 10110 mm OD No 0 No 8Providing, fixing and
laying fabricated UPVC equal teeconforming to IS : 10124 ( Part 5 )
with solvent cementconforming to IS : 14182 including testing of
joints completeas per chapter 20 of CPWD specification and
direction of theEngineer - in - charge.90 x 90 mm dia No 0 No 7110
x 110 mm dia No 0 No 6Providing, fixing and laying fabricated UPVC
end capconforming toIS : 10124 ( Part 4 ) with solvent
cementconforming to IS : 14182 including testing of joints
completeas per chapter 20 of CPWD specification and direction of
theEngineer - in - charge.90 x 90 mm dia No 0 No 3110 x 110 mm dia
No 0 No 2
83
84
85
86
-
233
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
0 0
Providing and fixing G.I. pipes complete with G.I. fittings
andclamps, including cutting and making good the walls etc.
Internal work - Exposed on wall.15 mm dia. nominal bore metre 0
metre 1520 mm dia. nominal bore metre 0 metre 20Providing and
fixing G.I. pipes complete with G.I. fittingsincluding trenching
and refilling etc.External work25 mm dia. nominal bore metre 0
metre 2040 mm dia. nominal bore metre 0 metre 50Making connection
of G.I. distribution branch with G.I. mainof following sizes by
providing and fixing tee, includingcutting and threading the pipe
etc. complete :25 to 40 mm nominal bore each 0 each 2
90Making chases upto 7.5x7.5 cm in wails including makinggood
and finishing with matching surface after housing G.I.pipe etc.
metre 0 metre 15
91
Providing and placing on terrace (at all floor
levels)polyethylene water storage tank ISI : 12701 marked with
coverand suitable locking arrangement and making necessary holesfor
inlet, outlet and overflow pipes but without fittings and thebase
support for tank.
per litre 0 per litre 1000
Providing and fixing C.P. brass bib cock of approved
qualityconforming to IS:893115 mm nominal bore each 0 each
2Providing and fixing C.P. brass long body bib cock ofapproved
quality conforming to IS standards and weighing notless than 690
gms.15mm nominal bore. each 0 each 2
SUBHEAD- WATER SUPPLY INSTALLATION
87
88
89
92
93
233
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Providing and fixing C.P. brass stop cock (concealed) ofstandard
design and of approved make conforming to IS:8931.
15 mm nominal bore. each 0 each 4Providing and fixing ball valve
(brass) of approved qualitycomplete :15 mm nominal bore each 0 each
320 mm nominal bore each 0 each 225 mm nominal bore each 0 each
2Providing and fixing gun metal gate valve with C.I. wheel
ofapproved quality (screwed end):40 mm nominal bore each 0 each
1
97Providing and fixing gun metal non-return valve of
approvedquality (screwed end):Vertical 0 040 mm nominal bore each 0
each 1Providing and fixing uplasticised PVC connection pipe
withbrass unions :45 cm length 0 015 mm nominal bore each 0 each
6Providing and fixing G.I. Union in G.I. pipe including cuttingand
threading the pipe and making long screws etc. complete(New
work)
15 mm nominal bore each 0 each 4
20 mm nominal bore each 0 each 4
25 mm nominal bore each 0 each 2
40 mm nominal bore each 0 each 2
Providing and fixing PTMT grating of approved quality
andcolour.Circular type.100 mm nominal dia. each 0 each 4
94
95
96
98
99
100
101
-
235
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Constructing brick masonry chamber for underground
C.I.inspection chamber and bends with 1st class bricks in
cementmortar 1:4 (1 cement : 4 fine sand) C.I. cover with frame
(lightduty) 455x610 mm internal dimensions, total weight of
coverwith frame to be not less than 38 kg (weight of cover 23 kgand
weight of frame 15 kg) R.C.C. top slab with 1:2:4 mix (1cement :2
fine sand : 4 graded stone aggregate 20 mm nominalsize) foundation
concrete 1:5:10 (1 cement: 5 fine sand : 10graded stone aggregate
40 mm nominal size), inside plastering12 mm thick with cement
mortar 1:3 (1 cement: 3 fine sand)finished smooth with a floating
coat of neat cement on wallsand bed concrete etc. complete as per
standard design :
Inside dimensions 455x610 mm and 45 cm deep for singlepipe line
:
No 0 No 1
Inside dimensions 500x700 mm and 45 cm deep for pipe linewith
one or two inlets :
No 0 No 1
103
Making soak pit 2.5 m diameter 3.0 metre deep with 45 x 45cm dry
brick honey comb shaft with well burnt 2nd classbricks and S.W.
drain pipe 100 mm diameter, 1.8 m longcomplete as per standard
design.
No 0 No 1
Supplying and fixing C.I. cover without frame for manholes :
500 mm diameter C.I. cover (medium duty) the weight of thecover
to be not less than 58 kg.
No 0 No 2
SUBHEAD- SEWERAGE & DRAINAGE WORK
102
104
235
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Earth work in excavation over areas (exceeding 30cm in
depth,1.5m in width as well as 10 sqm on plan) including disposal
ofexcavated earth, lead upto 50m and lift upto 1.5m, disposedearth
to be levelled and neatly dressed.
-All kinds of soilBy manual means cum 0 cum 15
Earth work in excavation in foundation trenches or drains
(notexceeding 1.5 m in width or 10 sqm on plan) includingdressing
of sides and ramming of bottoms, lift upto 1.5 m,including getting
out the excavated soil and disposal of surplusexcavated soil as
directed, within a lead of 50 m.
-All kinds of soilBy manual means cum 0 cum 30
Filling available excavated earth (excluding rock) in
trenches,plinth, sides of foundations etc. in layers not exceeding
20cmin depth, consolidating each deposited layer by ramming
andwatering, lead up to 50 m and lift upto 1.5 m.
-All kinds of soil cum 0 cum 20
4
Supplying and filling in plinth, under floor, foundations
etc.with sand (fine) from local quarry with all lifts
includingspreading in horizontal layers, watering, grading to
requiredslope, ramming, consolidating and compacting each layer
byusing plate compactor or by any suitable method complete.
cum 0 cum 2.5
3
SUBHEAD-CEMENT CONCRETE WORKS
SCHEDULE -"F" R.C.C. FRAMED BOUNDARY WALL
Total Length of Boumdary Wall = 45.00 Metre.
1
2
-
237
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Providing and laying in position cement concrete of
specifiedgrade excluding the cost of centring and shuttering -
-All work upto plinth level:1:4:8 ( 1 Cement: 4 fine sand : 8
graded stone aggregate 40mm nominal size)
cum 0 cum 8
Providing and laying in position specified grade of
reinforcedcement concrete excluding the cost of centring,
shuttering,finishing and reinforcement--All work upto plinth
level:1:1½:3 ( 1 Cement: 1½ fine sand : 3 graded stone aggregate
20mm nominal size)
cum 0 cum 7.25
Reinforced cement concrete work in walls (any
thickness),including attached pilasters, buttresses, plinth and
skirtingcourses, fillets, columns, pillars, piers, abutments, posts
andstruts etc. upto floor five level excluding cost of
centring,shuttering, finishing and reinforcement-
In walls (any thickness), including attached
pilasters,buttresses, piers, abutments etc.1:1½:3 ( 1 Cement: 1½
fine sand : 3 graded stone aggregate 20mm nominal size)
cum 0 cum 4.75
In plinth and skirting courses, fillets, columns, pillars,
postsand struts1:1½:3 ( 1 Cement: 1½ fine sand : 3 graded stone
aggregate 20mm nominal size)
cum 0 cum 4.5
Reinforced cement concrete work in beams, suspended floors,roofs
having slope upto 15° landings, balconies, shelves,chajjas,
lintels, bands, plain window sills, staircases and spiralstair
cases upto floor five level excluding the cost of
centring,shuttering, finishing and reinforcement-
5
SUBHEAD-R.C.C WORK
6
7
8
237
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
RCC work in beams, lintels, bands, plain window sills,staircases
and spiral staircases excluding precast spiralstaircase. 1:1½:3 ( 1
Cement: 1½ fine sand : 3 graded stone aggregate 20mm nominal
size)
cum 0 cum 6.37
Centering shuttering including struttings, propping etc.
andremoval of form work for:Foundations, footings, bases for
columns etc. for massconcrete with timber plank
sqm 0 sqm 15
Walls (any thickness) including attached pilasters,
buttresses,plinth and string courses etc. using shuttering ply
sqm 0 sqm 36
Lintels, beams, plinth beams, girders, bressumers andcantilevers
with shuttering ply
sqm 0 sqm 56
Columns, Pillars, Piers, Abutments, Posts and Struts
withshuttering ply
sqm 0 sqm 50
Reinforcement for R.C.C. work including straightening,cutting,
bending, placing in position and binding all completeupto floor
five level.Thermo-Mechanically Treated bars/ Cold twisted
deformedsteel bars
kg 0 kg 1450
First class brick work in foundation and plinth including costof
all materials as required complete:-In cement mortar 1:4 ( 1 cement
: 4 fine sand ). Cum. 0 Cum. 10Half brick masonry work with first
class bricks insuperstructure upto floor five level including cost
of allmaterials as required complete:-In cement mortar 1:4 ( 1
cement : 4 fine sand ). Sqm. 0 Sqm. 60
9
11
12
10
SUBHEAD- BRICK WORK
-
239
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
Extra for providing & placing in position 2 nos 6mm dia
MSbars at every 4th course of half brick masonry work
includinganchorage in joints of 75mm in each side in superstructure
forall level including cost of all materials as required
complete:-
In cement mortar 1:4 ( 1 cement : 4 fine sand ). Sqm. 0 Sqm. 700
0
Steel work welded in built up section/framed work
includingcutting, hoisting, fixing in position and applying a
primingcoat of approved steel primer using steel etc. complete
asrequired:-In grating, frames, guard bar, railing, brackets, gates
andsimilar works, all complete.
Kg. 0 Kg. 500
Providing and fixing M.S. grills of required pattern in framesof
windows etc. with M.S. flats, square or round bars etc.
allcomplete.
Fixed to openings /wooden frames with rawl plugs screws etc. Kg
0 Kg 600
12 mm cement plaster in single layer including cost ofmaterials
required and finishing even and smooth and curingcomplete.In cement
mortar 1 : 4 ( 1 cement : 4 fine sand ) sqm 0 sqm 101.2515 mm
cement plaster in single layer including cost ofmaterials required
and finishing even and smooth and curingcomplete.In cement mortar 1
: 4 ( 1 cement : 4 fine sand ) sqm 0 sqm 101.25
18 Neat cement punning. sqm 0 sqm 36
19Applying one coat of cement primer of approved brand
andmanufacturer on wall surface complete.
sqm 0 sqm 202.5
Applying priming coat:
13
SUBHEAD- STEEL WORK
14
16
15
SUBHEAD- FINISHING WORK
17
239
-
Gross Total
Unit Qty. Rate Amount Unit Qty. Rate Amount
Supply ErectionItem Sl. No
Description of Item
With ready mixed red oxide zinc chromate primer of approvedbrand
and manufacture on steel, galvanised iron / steel work.
sqm 0 sqm 25
21
Finishing walls with acrylic smooth exterior paint of
requiredshade of approved brand and manufacture on new work ( twoor
more coats applied @ 1.67 kg/10 sqm ) over and includingbase coat
water proofing cement paint applied @ 2.20 kg/10sqm complete.
sqm 0 sqm 202.5
Finishing with epoxy paint ( two or more coats ) of
approvedbrand and manufacture at all locations prepared and applied
asper manufacturer's specification on new work includingappropriate
priming coat, preparation of surface etc. complete.
On steel work sqm 0 sqm 25
Electrical Division No-I,TSECL, Agartala
22
Dy. General Manager
20
Bid Sch.
Schedule of Work
Name of Work:- Implementation of R-APDRP (Part-B) Scheme under
Agartala Project(Town Pratapgarh Area):
Design,Engineering,Manufacturing, Supply, testing ,Delivery,
Erection,Testing at site & commissioning of 33/11 KV, 2X7.5
MVA,Indoor Type Power Sub-Station at NSRCC, Netaji Chowmuhani,
Agartala with associated 33KV Underground Rampur Substation- NSRCC
S/C Line, 33 KV Bay at Rampur including Control room and boundary
wall at NSRCC.
Item Sl. NoDescription of
ItemSupply(Agreement)Erection(Agreement)Gross
TotalSupply(Execution)Erection(Execution)Gross TotalSupply(To be
done)Erection(To be done)Gross TotalSupplyErectionGross Total
UnitQty.RateAmountUnitQty.RateAmountUnitQty.RateAmountUnitQty.RateAmountUnitQty.RateAmountUnitQty.RateAmountUnitQty.RateAmountUnitQty.RateAmount
SCHEDULE-A
1Design, Engineering,manufacturing, Supply, Erection, Testing
& commissioning of 33/11KV Power Transformer, Oil immersed,
ONAN cooled outdoor type, 3-phase, 50 Hz, Vector Group-Dyn-II,
delta-star step down with off load tap changer having range of +10%
to -10% in steps of 2.5% each on HV winding with first filling of
EHV grade insulating oil as per specification including supply
& erection of 90lb rail pole, 3.5mtr long, 2nos for each
transformer as rail track etc.as required conforming to relevant
ISS as per design drawing detailed herein after in this
document.
a.
7.5MVANos25489526.0010979052.00Nos230000.0060000.0011039052.00Nos25489526.0010979052.00Nos230000.0060000.0011039052.00Nos05489526.000.00Nos030000.000.000.00Nos0Nos0
2Supply, erection, testing & commissioning of 33 KV, 800A,
manually operated horizontal rotating type double break, triple
pole Gang operated isolator complete with post insulator, arching
horns, mechanical interlocking arrangement etc.as per relevant
ISS(For Rampur S/S and at NSRCC end).0.000.000.000.00
a) With earth
switch.No235000.0070000.00No22500.005000.0075000.00No035000.000.00No02500.000.000.00No235000.0070000.00No22500.005000.0075000.00No2No2
b) Without earth
switch.No127000.0027000.00No12000.002000.0029000.00No027000.000.00No02000.000.000.00No127000.0027000.00No12000.002000.0029000.00No1No1
3Supply, erection, testing & commissioning of 33 KV Single
Phase, outdoor type 2 Core C.T of ratio 300 / 1-1 Amp with suitable
burden & class of accuracy complete with associated terminal
box connecting link etc. ( for 33 KV outgoing feeder)(For
RampurS/S)No335800.00107400.00No32000.006000.00113400.00No035800.000.00No02000.000.000.00No335800.00107400.00No32000.006000.00113400.00No3No3
4Supply, erection, testing & commissioning of 10KA, 30 KV,
Station Valve type metal oxide heavy duty Lightning Surge Arrestor
suitable for operation on 33KV Sytem conforming to ISI : 3070 (P-1)
/ 1974 and amendments thereafter and as required (1 set at Rampur
S/S end and 1 set at NSRCC
end).No615000.0090000.00No61500.009000.0099000.00No015000.000.00No01500.000.000.00No615000.0090000.00No61500.009000.0099000.00No6No6
5Supply, erection, testing & commissioning of 33 KV, 1000A,
750 MVA rupturing capacity, outdoor Vacuum Circuit Breaker complete
with motor operated spring closing (Local / Remote) arrangement
with all accessories including lattice support structure,foundation
bolts,G.I. nuts & bolts,washers etc. as required and as per
relevant ISS complete operative on 110V DC at Rampur Substation end
.0.000.000.000.00
a) For 33 KV Rampur-NSRCC UG
Feeder.No1340000.00340000.00No115000.0015000.00355000.00No0340000.000.00No015000.000.000.00No1340000.00340000.00No115000.0015000.00355000.00No1No1
6Supply, erection, testing & commissioning of 33 KV control
& relay panel, simplex type complete with differential relay,
2-over current and 1- Earth fault combined relay, Auxiliary relay,
1- voltmeter, 3- ammeter, CT operated static trivector meter,
internal panel wiring, simaphore for Vacuum Circuit breaker &
isolator, Mimic bus diagram (Metal size 4mm thick X 10mm
width).0.000.000.000.00
b) For 33 KV
Rampur.No1349400.00349400.00No15000.005000.00354400.00No0349400.000.00No05000.000.000.00No1349400.00349400.00No15000.005000.00354400.00No1No1
7i) Supply and Erection of Galvanised steel structure and Nuts,
Bolts, spring washer etc. as required for 33 KV tower, grantry,
post insulator and equpments. a) Steel structure b) Nuts &
bolts, spring washer and foundation bolts
etcLot1352600.00352600.00Lot143500.0043500.00396100.00Lot0352600.000.00Lot043500.000.000.00Lot1352600.00352600.00Lot143500.0043500.00396100.00Lot1Lot1
ii) Supply, erection, testing & commissioning of sub-
station busbar & stringing materials for 33 KV bus at Rampur
end.a) ACSR 7/1.57/6/4.72 mm (DOG ) conductor. b) 40mm dia. Al.
pipe for equipments bus current carrying capacity 400Amps. c)
7/3.15mm earth wire for substation shielding. d) Ball & socket
type 70 KN, 11KV disc Insulator. e) Al. tension clamps. 3 -U bolt
type, ball& socket type, suitable for70KN Disc Insulator and
ACSR DOG conductor. f )"T"/ "I" / other Clamp/power connector
suitable for ACSR DOG Conductor and Al. tube as
required.Lot1125150.00125150.00Lot110200.0010200.00135350.00Lot0125150.000.00Lot010200.000.000.00Lot1125150.00125150.00Lot110200.0010200.00135350.00Lot1Lot1
8Design, Engineering,manufacturing, Supply, erection, testing
& commissioning of 33KV, 1250A, 31.5 KA for 3 Sec. Metal Clad
withdrawable type indoor VCB,highly reliable , and totally enclosed
product under compartmentalised construction combined with positive
safety interlocks for safe draw in/draw out of VCB trolley/carriage
including draw out type PT Compartment (with dual rating PT
33KV/1.732/110V/1.732-110 V/1.732) in VCB Trolley with standard
integrated protection relays( both numerical &
electromechanical) as per IEC62271-100/200, 12 window alarm &
annunciation system and SCADA compatible control system,power
pack,series trip arrangement, internal arc tested as per
IEC62271-200 including integral earth switch and motor operated
spring charged mechanism, mounted on truck carriage, complete with
self contained mechanism with mechanica & electrical
indications of operational status & auxiliary switch as
required as per standard requirement specified in Technical
specification section in the document including supply of 1No 2.5
KV Motorised Meggar.0.000.000.000.00
a) Incoming Feeder with CT (CTR: 300/1-1A) at NSRCC
end.Nos11206105.001206105.00Nos120000.0020000.001226105.00Nos01206105.000.00Nos020000.000.000.00Nos11206105.001206105.00Nos120000.0020000.001226105.00Nos1Nos1
b) Outgoing feeder for Transformers with CT (CTR:
300-150/1-1-1A)Nos2800000.001600000.00Nos215000.0030000.001630000.00Nos0800000.000.00Nos015000.000.000.00Nos2800000.001600000.00Nos215000.0030000.001630000.00Nos2Nos2
c) Spare Incoming CT (CTR: 300/1-1A) at NSRCC
endNos11206105.001206105.00Nos123750.0023750.001229855.00Nos01206105.000.00Nos023750.000.000.00Nos11206105.001206105.00Nos123750.0023750.001229855.00Nos1Nos1
9Design, Engineering, Supply, Testing & commissioning of 11
KV, 800Amps continuos rated current, 350 MVA rupturing capacity
Indoor Vaccum Circuit Breaker, complete with Control & Relay
Pannel Simplex type with 3Phase pannel top mounted PT of ratio:
11000 /110Volt,110 Volt DC actuated electrical closing mechanism
and internal wiring, Numerical as well as electromechanical
protection by 2-Over current & 1-earth fault combined ( Micom
or other reputed make) digital & electromechanical relays for
integrated protection,1 no.electromechanical AREVA Master Trip
Relay, auxiliary relays as required,1 no.L&T / SECURE make
"Tri- Vector" Meter(SCADA compatible) 3- Ammeter, 1 -Voltmeter, 1
-C.T operated static KW meter , with panel bus mounted C.T and
integral earthing facility including inernal arc tested panel
conforming to relevant ISS/IEC as reqd.including standard
indication facilities as per requirement detailed herein after
including supply of ABC dry powder type 2nos, 5kg each and 2Nos
each, CO₂ cylinder type with pressure indicator fire extinguisher
.0.000.000.000.00
a. Incoming pannel with (CTR:
900-450/1-1-0.577A)Nos2306620.00613240.00Nos210000.0020000.00633240.00Nos0306620.000.00Nos010000.000.000.00Nos2306620.00613240.00Nos210000.0020000.00633240.00Nos2Nos2
10Design, Engineering, Supply, Testing & commissioning of 11
KV, 800 Amps continuos rated current, 350 MVA rupturing capacity
Indoor Vaccum Circuit Breaker( for outgoing feeder) , complete with
1 set of CT of ratio 300/1-1, Control & Relay Pannel Simplex
type with 110 Volt DC actuated electrical closing/tripping
mechanism and internal wiring, 2-Over current & 1-earth fault
combined Micom digital relay,1 no.electromechanical AREVA Master
Trip Relay, auxiliary relays as required,1 no.L&T / SECURE make
"Tri- Vector" Meter(SCADA compatible), 3- Ammeter, 1 -Voltmeter, 1
-C.T operated static KW meter , with panel bus mounted C.T and
integral earthing facility including inernal arc tested panel
Conforming to relevant ISS/IEC as reqd.including standard
indication facilities as per requirement detailed herein
after.Nos5423588.002117940.00Nos58000.0040000.002157940.00Nos0423588.000.00Nos08000.000.000.00Nos5423588.002117940.00Nos58000.0040000.002157940.00Nos5Nos5
11Design, Engineering, Supply, Erection, Testing &
commissioning of 110V DC, 240Ah Capacity Sealed and Maintenance
Free(SMF) VRLA Battery Bank comprising of 60 Nos. 2.2 Volt each
Cell (out of 60 cells, 5 Nos. being spare) complete with all
accessories conforming to relevant ISS as per latest amendment
detailed in the technical specification section of the
document.Set1308000.00308000.00Set13500.003500.00311500.00Set0308000.000.00Set03500.000.000.00Set1308000.00308000.00Set13500.003500.00311500.00Set1Set1
12Design, Engineering,manufacturing, Supply, Erection, Testing
at site & commissioning of 415 VAC(plus minus 10%) nominal
input Voltage,50 HZ(plus minus 5%),110 Volt DC Output with
adjustable range, 40A thyristor controlled float cum boost
charger(with less than 2% RMS ripple content, without battery
connected)less than 60db noise level constant voltage processed
Battery charger compatible for aforesaid VRLA battery Bank
Conforming to relevant ISS and latest amendment complete with
standard protection as per IP-54 to 20 as per IS-2147,built in
DCDB, standard indications and controls including
switches,temperature range of 50 degree centigrade and painted by
RAL 7032 etc. as required detailed in technical specification
section of this
document.Nos1160000.00160000.00Nos12500.002500.00162500.00Nos0160000.000.00Nos02500.000.000.00Nos1160000.00160000.00Nos12500.002500.00162500.00Nos1Nos1
13Design, manufacture, testing at works, transport to site,
insurance, erection and commissioning of 110Volt D.C. Distribution
Boards (DCDB) with dust tight ,vermin proof, gasketed door,
enclosure made of sheet steel 2 mm. thick CRCA, painted by powder
coated paint RAL 7032 with Aluminium busbar of 40x6 mm complete
with (L&T/GE/C&S/HAVELLS make 1x160 A TP MCCB, 1x32 A DC DP
MCB, 6x16 A DC DP MCB, analog Volt & Ampere meter,LED
indication,Mains failure and Earth fault Relay etc. including all
control and protection gears complete as per requirement and
asdetailed in technical specification section in the
document.Nos118000.0018000.00Nos11200.001200.0019200.00Nos018000.000.00Nos01200.000.000.00Nos118000.0018000.00Nos11200.001200.0019200.00Nos1Nos1
14Design, manufacture, testing at works, transport to site,
insurance, storage, erection and commissioning of( L & T/
SECURE/GE make) 415 Volts, A.C. 50 Hz A.C. Distribution Board
complete with 300 Amp. TPN with link in incoming supply, 3
nos.300/5(15 VA) CT,300 Amp Aluminium busbar,1x100A TPN,3x63 A
TPN,2x32A TPN,3x63 A DP,5x32 A DP as per requrement including
provision for Voltage,Ampere indications and L&T/SECURE make
KWH mete and accessories as described in technical
specification.Nos198000.0098000.00Nos12000.002000.00100000.00Nos098000.000.00Nos02000.000.000.00Nos198000.0098000.00Nos12000.002000.00100000.00Nos1Nos1
151100 Volts grade PVC insulated PVC sheathed, 2.5 sq.mm.(
stranded copper conductor) control cable with armouring of
following capacity & core as per
IS:1554(Part-I)1988.0.000.000.000.00000.00
a) 2 Core 2.5mm2 b) 4 Core 2.5mm2 c) 7 Core 2.5mm2 d) 12 Core
2.5mm2Lot143020.0043020.00Lot12460.002460.0045480.00Lot043020.000.00Lot02460.000.000.00Lot143020.0043020.00Lot12460.002460.0045480.00Lot1Lot1
16Design, Engineering,manufacturing, Supply, laying in position
in cable trench, Testing & commissioning of Single Core, 19 /33
KV, 185 Sq. mm. XLPE insulated, screened armoured power cable as
per TSECL approved design, drawing, specification and as reqd. as
per direction of Eng-In-Charge and as detailed herein after in this
document.Mtr1751400.00245000.00Mtr.175400.0070000.00315000.00Mtr1751400.00245000.00Mtr.0400.000.00245000.00Mtr01400.000.00Mtr.175400.0070000.0070000.00Mtr0Mtr.175
17Design, Engineering, manufacturing ,Supply, laying in position
in cable trench, Testing & commissioning of Single Core,
6.35/11 KV(E), 400 Sq. mm. XLPE insulated armoured power cable in
cable trench as per TSECL approved design, drawing, specification
and as reqd. as per direction of Eng-In-Charge and as detailed
herein after in this
document.Mtr3001410.00423000.00Mtr.300400.00120000.00543000.00Mtr3001410.00423000.00Mtr.0400.000.00423000.00Mtr01410.000.00Mtr.300400.00120000.00120000.00Mtr0Mtr.300
18Design, Engineering,manufacturing, testing at works, Supply,
laying in position in trench, Testing & commissioning of Three
Core, 6.35/11 KV, 240 Sq. mm. XLPE insulated armoured power cable
in trench with supply of 1No Hydulic crimping tool (capable of
crimping from range of 50 sqmm to 400 sqmm size socket) as per
relevant ISS and detailed in the Technical specification Section in
the document and direction of
Eng-In-Charge.Mtr2401034.00248160.00Mtr.240400.0096000.00344160.00Mtr2401034.00248160.00Mtr.0400.000.00248160.00Mtr01034.000.00Mtr.240400.0096000.0096000.00Mtr0Mtr.240
19Design, Engineering, Supply, Testing & commissioning &
joints of Indoor type heat shrink end jointing kit for Single core,
185 Sq.mm. Size, XLPE insulated Power Cable of grade 19//33KV(E),
as per IS 7098 Part-II 1985 and latest
ammended.Nos166000.0096000.00Nos163000.0048000.00144000.00Nos06000.000.00Nos03000.000.000.00Nos166000.0096000.00Nos163000.0048000.00144000.00Nos16Nos16
20Design, Engineering, Supply, Testing & commissioning &
joints of 0utdoor type heat shrink end jointing kit for Single
core, 185 Sq.mm. Size, XLPE insulated Power Cable of grade
19//33KV(E), as per IS 7098 Part-II 1985 and latest
ammended.Nos167000.00112000.00Nos163000.0048000.00160000.00Nos07000.000.00Nos03000.000.000.00Nos167000.00112000.00Nos163000.0048000.00160000.00Nos16Nos16
21Design, Engineering, Supply, Testing & commissioning &
joints of Outdoor type heat shrink end jointing kit for Single
core, 400 Sq.mm. Size, XLPE insulated Power Cable of grade 6.35/11
KV(E). as per IS 7098 Part-II 1985 and latest
ammended.Nos166000.0096000.00Nos162500.0040000.00136000.00Nos06000.000.00Nos02500.000.000.00Nos166000.0096000.00Nos162500.0040000.00136000.00Nos16Nos16
22Design, Engineering, Supply, Testing & commissioning &
joints of Indoor type heat shrink end jointing kit for Single core,
400 Sq.mm. Size, XLPE insulated Power Cable of grade 6.35/11 KV(E).
as per IS 7098 Part-II 1985 and latest
ammended.Nos165000.0080000.00Nos162500.0040000.00120000.00Nos05000.000.00Nos02500.000.000.00Nos165000.0080000.00Nos162500.0040000.00120000.00Nos16Nos16
23Design, Engineering, Supply, Testing & commissioning &
joints of Out door type heat shrink end jointing kit for Three
core, 240 Sq.mm. Size, XLPE insulated Power Cable of grade 6.35/11
KV(E), as per IS 7098 Part-II 1985 and latest
ammended.Set65500.0033000.00Set62500.0015000.0048000.00Set05500.000.00Set02500.000.000.00Set65500.0033000.00Set62500.0015000.0048000.00Set6Set6
24Design, Engineering, Supply, Testing & commissioning &
joints of Indoor type heat shrink end jointing kit for Three core,
240 Sq.mm. Size, XLPE insulated Power Cable of grade 6.35/11 KV(E).
as per IS 7098 Part-II 1985 and latest
ammended.Nos64900.0029400.00Set62500.0015000.0044400.00Nos04900.000.00Set02500.000.000.00Nos64900.0029400.00Set62500.0015000.0044400.00Nos6Set6
25Design, manufacturing, supply, erection, testing &
commissioning of 11 KV, 600 ampere rated outdoor type standard 3
way Kiosk (CNC m/c fabricated and made of 3.25 mm sheet) suitable
for11 KV cable termination as per relevant ISS and IP with copper
Busbar and acces