SB Encased Systems Breakers 800A—5000A Frame Ratings Information and Instruction Guide
66

SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

May 08, 2018

Download

Documents

trinhnhan
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

SB Encased Systems Breakers

800A—5000A Frame Ratings

Information and Instruction Guide

Page 2: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

IMPORTANTThe information contained herein is general in nature and not intended for spe-cific application purposes. It does not relieve the user of responsibility to usesound practices in application, installation, operation, and maintenance of theequipment purchased. Siemens reserves the right to make changes in the spec-ifications shown herein or to make improvements at any time without notice orobligations. Should a conflict arise between the general information contained inthis publication and the contents of drawings or supplementary material or both,the latter shall take precedence.

NOTE*Authorized and qualified personnel—

For the purpose of this manual a qualified person is one who is familiar with theinstallation, construction or operation of the equipment and the hazardsinvolved. In addition, he has the following qualifications:

(a) is trained and authorized to de-energize, clear, ground, and tag circuitsand equipment in accordance with established safety practices.

(b) is trained in the correct care and use of protective equipment such as rub-ber gloves, hard hat, safety glasses or face shields, flash clothing, etc., inaccordance with established safety practices.

(c) is trained in rendering first aid.

SUMMARYThese instructions do not purport to cover all details or variations in equipment,nor to provide for every possible contingency to be met in connection withinstallation, operation, or maintenance. Should further information be desired orshould particular problems arise which are not covered sufficiently for the pur-chaser’s purposes, the matter should be referred to the local sales office, listedon back of this instruction guide.

The contents of this instruction manual should not become part of or modifyany prior or existing agreement, commitment or relationship. The sales con-tract contains the entire obligation of Siemens Energy & Automation, Inc. Thewarranty contained in the contract between the parties is the sole warranty ofSiemens Energy & Automation, Inc. Any statements contained herein do notcreate new warranties or modify the existing warranty.

Circuit breaker indicators shown in this booklet are for illustration purposes only.Circuit breakers are to be installed in “Discharged” and “Open” positions only.

Page 3: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

1

SB Encased Systems Breakers

Table of Contents

General Information 2-5

Description 6-7

Stationary and Moveable Drawout Elements 6Electronic Trip Units for Siemens SB Encased Breakers 7

Frame Installation Instructions 8-10

Stationary Drawout Element 8Movable Drawout Element 9Fixed Mounted 10

Installation Instructions 11-14

Electronic Trip Unit 11Rating Plug 13

Operating Instructions 15-25

Operating the SB Encased Systems Breaker 15Manipulating the Moveable Drawout Element 18

Internal Accessories 26-30

Preliminary Installation Procedures 26Preparation for Installation of Electric Motor Operator 28External Accessories

31-34

Siemens ACCESS Communications 31Universal Test Kit (TS-31) 34

Outline Dimension Drawings 35-54

1200A Stationary Drawout Element 351200A Moveable Drawout 371200A Fixed-Mounted 392000A Stationary Drawout 412000A Moveable Drawout 432000A Fixed-Mounted 453200A, 4000A, and 5000A Stationary Drawout 473200A, 4000A, and 5000A Moveable Drawout 493200A Fixed-Mounted 514000A and 5000A Fixed-Mounted 53

Electrical Schematics 55-60

Accessory Ratings 61

Solenoid Coil Resistances 62

Primary Current Injection and Field Testing for SB Breakers 62

NOTE: Information related to specific frame types and catalog numbers does not guarantee product availability. Technical informationmay change due to product revisions. Consult Siemens sales office concerning any variation of information contained herein.

Page 4: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

2

General Information

Introduction

Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers (MCCB)and Low Voltage Power Circuit Breakers (LVPCB).

Modern computer-aided design and manufacturing tools wereused to effectively blend the technologies of the MCCB andLVPCB. This combination has resulted in a family of encasedsystems circuit breakers that exhibit the most desirable char-acteristics of each of the parent technologies. Included inthese characteristics are high interrupting capacities, highwithstand capabilities (magnetic stress), high-shorttimecapabilities (overcurrent heating), and high mechanical andelectrical endurances without maintenance.

Applications for SB breakers include main, tie, feeder, andemergency source breakers in industrial plants, large commer-cial complexes, and medical and health care facilities. The circuitbreakers are constructed for either fixed or drawout installation.They can be physically grouped in central distribution switch-boards or used separately in stand-alone applications.

The SB breaker is equipped with a two-step stored energymechanism for closing and opening the breaker contacts. Aftera closing operation, sufficient energy is retained in the two-stepstored energy mechanism to perform the tripping function. Themechanism may be charged manually with the integrated low-force charging handle or electrically with the optional electricmotor operator. Pushbuttons, switches, and color-coded indica-tors allow for easy close and open operations

.

Siemens Encased Systems Breakers

One piece moldedbase and cover forstructural integrity.

Integral key interlock.

Breaker operatingcontrols groupedin central escutcheon.

Compact dimensions allow 6-highmounting of 800 and 1200 amperebreakers and 4-high mounting of2000 ampere breakers in a standardswitchboard section.

Meets or exceeds applicableUL and CSA requirements.

U-shaped charging handleallows the user to easilycharge the mechanismfrom any angle.

Manual close buttonand charging handleare interlocked.

Extended line/load bus for2000 through 5000 ampere frames.

Sealable trip unit cover.

Completely insulated/encasedconstruction.

Color keyed label indicatesa choice of three interruptingratings.

Mounting holes are outboardfor ease of access and areidentical for 400 through2000 ampere frames.

Page 5: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

3

General Information

Frame Sizes and Frame Ampere Ratings

SB breakers come in four frame sizes with MAX ratingsranging from 400A to 5000A. All frames are rated for 100%continuous operation.

Frame Size and Rating Combinations

Rating Plugs

SB breakers use interchangeable rating plugs. The rating plugampere values (I

n

) allows the effective ampere rating of thebreaker to be customized for specific applications. A label onthe front of the breaker identifies the rating plugs that may beused with that particular breaker.

Available Rating Plugs

Interruption and Short Time Ratings

Three short circuit interruption ratings are available for specificapplications. The interruption ratings and short-time ratings aregiven in the following table.

UL 489 Interruption and Short Time Ratings

IEC 947-2 Ratings (SBS Units Only)

The interruption rating of the SB breaker is specified on thefront cover label and is further identified by a color bar at thetop left of the breaker label.

Blue

indicates the alternate or the lowest interrupting cate-gory (1200–2000A frames). Black indicates the standard inter-rupting rating. Red indicates the highest available interruptingrating for the SB breaker.

Overcurrent Protection Configurations

Siemens Electronic Trip Units for SB breakers are available inseven overcurrent protection configurations to meet specificprotection requirements. Six trip units come equipped withAdjustable Continuous Current and Long Time Delay func-tions. Optional protection configurations are:

Protection Configuration Identifier

Long Time/Short Time LSLong Time/Instantaneous LILong Time/Short Time/Instantaneous LSILong Time/Short Time/Ground Fault LSGLong Time/Instantaneous/Ground Fault LIGLong/Short Time/Instantaneous/Ground Fault LSIGFixed Long Time/Instantaneous MLI

The trip unit that may be used with a specific circuit breaker isidentified on the front cover label.

RMS Current Sensing

The trip unit executes the breaker’s overcurrent fault protec-tion functions. Its adjustment flexibility allows you to accom-modate load changes and other protection requirements whilestill assuring optimum coordination.

A standard trip unit feature is RMS current sensing. RMSsensing measures the true heating potential of the currentwaveform. It allows for more accurate overcurrent protectionand eliminates nuisance tripping due to harmonic distortion ofthe current waveform.

Breaker Frame Ampere Size Breaker MAX Ampere Rating

1200 Amperes

(SBA, SBS only)

400, 800, 1200

2000 Amperes 800 (SBH only), 1200, 1600, 2000

3200 Amperes 2500, 3200

5000 Amperes 2500, 3200, 4000, 5000

MAX Rating Rating Plug Ampere Values (I

n

)

400 200, 225, 250, 300, 350, 400

800 400, 450, 500, 600, 700, 800

1200 600, 700, 800, 1000, 1200

1600 800, 1000, 1200, 1600

2000 1000, 1200, 1600, 2000

2500 1600, 2000, 2500

3200 1600, 2000, 2500, 3000, 3200

4000 2000, 2500, 3000, 3200, 4000

5000 2500, 3000, 3200, 4000, 5000

Breaker Frame Size

1200 2000 3200 5000

Type SBA Alternative Interrupt Rating (Blue Label)

240 V AC 480 V AC 600 V AC

65 kA 65 kA 42 kA

85 kA 65 kA 50kA

— —

Type SBS Standard Interrupt Rating (Black Label)

240 V AC 480 V AC 600 V AC

100 kA 100 kA 50 kA

100 kA 100 kA 65 kA

150 kA 100 kA 85 kA

150 kA 100 kA 85 kA

Type SBH High Interrupt Rating (Red Label)

240 V AC480 V AC 600 V AC

—200 kA 150 kA 100 kA

200 kA 150 kA 100 kA

200 kA 150 kA 100 kA

Short Time Rating (t=0.5 seconds)

25 kA 35 kA 50 kA 65 kA

Voltage 50/60 HzFrame Sizes

1200 2000 3200 5000

Type SBS Standard Interrupt Rating (Black Label)

415 V AC lcu lcslcw

100 kA 100 kA 25 kA

100 kA 100 kA 35 kA

100 kA 100 kA 50 kA

100 kA 100 kA 65 kA

690 V AC lcu lcslcw

65 kA 65 kA25 kA

65 kA 65 kA 35 kA

65 kA 65 kA 50 kA

65 kA 65 kA 65 kA

Page 6: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

4

General Information

NOTE: For more information on other standard andoptional trip unit features, see Siemens Electronic TripUnits for SB Encased Systems Breakers Information andInstruction Guide Bulletin IPIM-2203 and the Sentron Sys-tems Breaker Energy Communicating Trip UnitInformation and Instruction Guide Bulletin IPIM-2208.

The SB breakers incorporate several installation, operation,and safety features.

Insulated – Encased Construction

The SB breaker’s housing, internal barrier, and front cover aremolded from a thermoset material with a high-dielectricstrength (electrical insulation). The one piece molded case(base and housing) provides enhanced structural integrity. Amidbarrier provides outer wall reinforcement, integral arc baf-fling, and insulation/isolation between the two compartmentsof the circuit breaker.

This patented construction provides a higher interruptingcapacity within a smaller housing than can be achieved bymore conventional construction. The electrical insulation prop-erty of the thermoset material enhances operational safety.The insulated case physically isolates and electrically insulatesusers from the internal high voltage contacts.

The arc chambers and main contact structure are encased inthe back compartment. The trip unit, controls, springs of thestored energy mechanism, and optional internal accessoriesare located in the front compartment. Access to the frontcompartment is by the removable front cover. Since the barrierbetween the two compartments is made from the same insu-lating thermoset material as the housing, the user is physicallyisolated and electrically insulated from the main breaker mech-anism and contacts when the front cover is removed.

Photo of 2000A Frame Shown for Illustration Purposes Only

Page 7: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

5

General Information

Compact Size

For space-limited installations, the 1200A and 2000A framesoffer a common width of 15

1

/

2

inches, a common depth ofonly 12

1

/

8

inches, a common mounting footprint, and com-mon bus center lines. This compact, shallow depth (even withdrawout breakers) permits stacking of six 800A or 1200Abreakers or four 2000A breakers in a standard switchboard.This packaging is made possible by the insulated-encasedconstruction and thermal performance of the SB breaker. Evenwhen operated at 100% of the frame rating, no additionalventilation is required for the 1200A and 2000A frames.

Possible Number of Frames in a 90-inch Switchboard.

Example: Three 1200A and two 2000A breaker combination is possible.

When operated at 100% of the frame rating, 4000A and5000A frames require 66 in

2

of ventilation space in the top andbottom of the front cover. The 3200A frames require no addi-tional ventilation. Detailed outline drawings of the breakersand drawout elements are included in the Outline Dimensionssection starting on page 36.

Bus Spacing and Connections

Specific installation features of SB breakers include commonpole spacings and vertical connections. These pole spacingsallow for a standard bus connection as specified in UL 891.Detailed outline drawings are contained in the Outline Dimen-sions section starting on page 36.

Two-Step Stored Energy Mechanism

A two-step stored energy mechanism is used to close andopen the breaker. Energy is initially stored in the main springsof the stored energy mechanism. When the breaker is closed,spring energy is consumed and sufficient energy is retained inthe breaker to perform the tripping function.

The stored energy mechanism may be charged manually(standard) or electrically (optional). Pushbutton controls allowfor easy opening and closing. Color-coded indicators clearlydisplay the opened or closed status of the circuit breaker andcharged or discharged status of the stored energy mecha-nism. Once the breaker is closed, the mechanism can berecharged. The breaker is now prepared for a rapid open-closeor open-close-open operation.

Main Stored Energy Spring in Front Compartment

Centralized Controls

The manual charging handle, pushbutton control switches, andcolor-coded indicators are grouped in the central escutcheonon the front cover. The U-shaped construction of the charginghandle provides for a firm grip regardless of the position of thebreaker in the switchboard. For safety, the charging handle andpush-to-close pushbutton are interlocked. This interlockprevents the breaker from being closed unless the charginghandle is in the stowed position, the position to which it willautomatically return when it is released. The interlock alsoprevents the breaker from being manually charged if the Closebutton is depressed. Operating instructions for the storedenergy mechanism and controls are in the Operating Instruc-tions section starting on page 15.

Centralized Controls and Color-Coded Indicators

2000

A Si

ze F

ram

es

1200A Size Frames

0 1 2 3 4 5 6

0 —

✓ ✓ ✓ ✓ ✓ ✓

1

✓ ✓ ✓ ✓ ✓

2

✓ ✓ ✓ ✓

3

✓ ✓

4

Page 8: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

6

Description

Stationary and Moveable Drawout Elements

Simplified Minimum Depth Drawout Mechanism

The two elements of a drawout constructed SB Encased Sys-tems Breaker are the stationary drawout element and themoveable drawout element. The stationary drawout elementmounts from the front or bottom into a standard switchboard.Bottom mounting flanges are provided for optional mountingarrangements. The moveable drawout element mounts ontothe stationary drawout element’s two extension rails. Thisallows the moveable drawout element to be racked in and outof the stationary drawout element. For inspections, the move-able drawout element must be removed from the extensionrails to a work area. Refer to outline drawings of the two typesof drawout elements starting on page 36.

Each moveable drawout element has four positions: (1) Con-nected, (2) Test, (3) Unlocked (only), and (4) Unlocked/With-drawn. A racking mechanism with a low-force pump handlemoves the moveable drawout element between the con-nected, test, and unlocked positions. The pump handle is anintegral part of the racking mechanism, and no auxiliary rackingdevice or tool is required. In the unlocked position the move-able drawout element is disengaged from the racking mecha-nism. The moveable drawout element can be easily pulledbetween the unlocked position and the withdrawn position. Acolor-coded indicator displays the connect, test, and unlockedpositions of the moveable drawout element.

Stationary Drawout Element

The integral pump handle and two levers are used to controlthe movement of the moveable drawout element. A singlerelease lever automatically locks the moveable drawout ele-ment when it reaches the test or the connected position. Themoveable drawout element is released to move to the nextposition by simply pushing and releasing the release lever.

Side View Shown

Pushing the release lever with the SB breaker contactsclosed opens the breaker. You do not have to hold therelease lever to rack the moveable drawout element. A direc-tional shift lever determines the direction the moveabledrawout element will move when the pump handle is pulled orpushed.

Secondary disconnect sliding terminal blocks for terminatinginternal accessories are mounted on the sides of the station-ary and moveable drawout elements. The secondary discon-nects are mated as the moveable drawout element is movedfrom the withdrawn position to the unlocked position. The ter-minal points of the secondary disconnects are identified onpage 59. Step-by-step instructions for operating the rackingmechanism begin on page 18.

Moveable Drawout Element

Bus Stabs

SecondaryDisconnects(right side)

ExtensionRails

Line Side

ConnectedPosition

TestPosition

Load Side

Bus Stab (InStationaryDrawoutElement)

FingerClusters Moveable

DrawoutElement

DirectionalShift Lever(on side panel)

PositionIndicator

RackingPumpHandle

ReleaseLever

Page 9: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

7

Description

Electronic Trip Units For Siemens SB Encased Systems Breakers

Trip Units

Two types of trip unit are available for the SB breakers. The TL(standard) Trip Unit features a full range of industry standardprotective settings. The new, high-performance SystemsBreaker Energy Communicating Trip Unit (SB-EC Trip Unit)offers advanced metering, protective relaying, time-stampedlogs, and power quality monitoring functions, including an inte-gral keypad and LCD graphical display for menu-driven systemconfiguration and real-time voltage and current waveform dis-plays. Both units offer unique models to provide an efficientcombination of options versus cost for each application.

Typical Trip Adjustment Unit Panel

Interchangeable Rating Plugs

SB trip units use field interchangeable rating plugs. This allowsthe ampere rating of the circuit breaker to be field-modifiedand provides security against indiscriminate changes in thebreaker’s ampere rating.

Advanced True RMS Current Sensing

The TL Trip Unit and the SB-EC Trip Unit feature advanceddigital-processing techniques to measure the true heatingcontent of the current waveform. This True RMS value ofcurrent measurement virtually eliminates nuisance trippingdue to the presence of harmonics on the distribution bus.

TL Trip Unit

The TL Trip Unit offers adjustable LI, LIG, LSI, and LSIG tripsettings and accessory ammeter and load alarm or groundcurrent meter with alarm output.

SB-EC Trip Unit

The Energy Communicating trip unit for the SB offers local andremote programming of all overcurrent trip functions as wellas power and energy measurement, advanced protectiverelays and alarms and power quality functions (harmonics andwaveform capture and display).

NOTE: For details on these trip units, refer to the SiemensTL Trip Unit Bulletin IPIM-2203 and the Siemens SB-EC TripUnit Bulletins IPIM-2208.

SB-EC Trip Unit

Rating Plug

CurveAdjustments

Fault Indicators

Built-inTest Functions

Plug-inDisplay Module

In=1000A

1000A

MAX Rating = 2000A MAX

Rating

NOTE:

Earlier model trip units may use (I ) as theRating Plug Designator and (I ) to denote (MAXRating). The designations for the current modeltrip unit are shown at left. Note, however, that thechange in designation has no effect on the switchsettings used for selecting Continuous, Long Time,Short Time, Instantaneous, and Ground Faultpickup and delay values.

n

r

Graphical

Rating Plug

BacklitLCD

WatchdogLEDs

StatusIndicators

IntegralKeypad

TS-31 TestConnector

RS-232Communi-cation Port

Page 10: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

8

Installation instructions for systems breakers, trip units, andrating plugs are presented in this section. Installation instruc-tions for accessories that may be installed in the field arepresented in the Accessories section.

Installing Drawout Constructed SB Breakers

Drawout constructed SB breakers are designed to be installedfrom the front into a switchboard with a minimum width open-ing: 19 in. (1200A and 2000A frames), 20.36 in. (3200A frame),and 28.34 in. (5000A frame). The stationary drawout elementmay be secured in the switchboard at the front and rear to ver-tical supports or at the top and bottom to horizontal supports.

Installing the Stationary Drawout Element

Prepare the switchboard for installation of the stationarydrawout element in accordance with the outline drawingslocated in the Outline Dimension Drawings section starting onpage 36. The locations of the mounting holes are depicted onthe drawings.

Carefully uncrate the stationary drawout element. Remove allpacking material with the exception of the tie wraps holdingthe extension rails in place. Depending upon the installationscheme, it may be necessary to remove the tie wraps on theextension rails just prior to securing the stationary drawoutelement in the switchboard. If the stationary drawout elementis secured to a pallet, remove the securing device.

The bottom of the stationary drawout must be secured to theswitchboard using four 3/8-inch bolts. Additional mountinghardware may be used to attach the top and front of thestationary drawout but is not required.

The stationary drawout element can be manually lifted andheld in position as it is being installed. However, if preferred,the two holes identified as lifting points on the outline drawingmay be used to attach a lifting device.

Attach lifting device to identified lifting points only.

NOTE: The two rear holes are located so that the station-ary drawout element can be easily balanced as it is beinglifted by a crane or hoist. Do not lift the stationarydrawout element using only the two top front holes. Ifpreferred, the device can be lifted using all four top holes.

Lifting devices should not be attached to any other points. Thestationary drawout element should not be lifted by the primarystabs.

Lift the stationary drawout element into position and secure itin place. Remove the lifting device.

Remove the tie wraps securing the extension rails. Check toensure that no packing or other foreign material impedes railmovement.

Frame Installation Instructions

Stationary, Moveable, and Fixed-Mounted Drawout Elements

Page 11: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

9

Frame Installation Instructions

Stationary, Moveable, and Fixed-Mounted Drawout Elements

Installing the Moveable Drawout Element

The outline drawings of the moveable drawout elements arelocated in the Outline Dimension Drawings section starting onpage 36.

Carefully uncrate the moveable drawout element and removeall packing material with the exception of the wire ties holdingthe racking pump handle in place. Items such as a label for adead front shield and keys for the SB breaker with a key inter-lock accessory may be taped to the top of the moveabledrawout element. If the moveable drawout element is securedto a pallet, remove the securing device.

Preferred lifting arrangement.

Attach the lifting device accessory as illustrated. If lifting strapsare used instead of the lifting device accessory, the liftingstraps should go between the primary contacts. In eitherarrangement, the moveable drawout element may be bal-anced as it is being lifted by a crane or hoist. The moveabledrawout element should not be lifted by the primary contacts.

Pull out the extension rails on the stationary drawout elementuntil they hit a solid stop.

Lift by using the rear guide posts (one is located on left sideand one on right).

Lift the moveable drawout element over the extension rails.For the 1200A and 2000A frame, align the moveable drawoutelement so that the support brackets straddle the inside guiderails, and carefully lower the moveable drawout element ontothe rail guides. For the 3200A and 5000A frame, align themoveable drawout element so that the rollers straddle theextension rails, and carefully lower the moveable drawoutelement onto the extension rails. Remove the lifting device.Remove the tie holding the racking pump handle.

Rollers and Rail

Page 12: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

10

Frame Installation Instructions

Stationary, Moveable, and Fixed-Mounted Drawout Elements

To correctly engage the moveable drawout element with theracking mechanism, the crank pins on the sides of the move-able drawout element must be in the Unlocked position asillustrated and the release lever must be in the Up position.During shipping and handling, the crank pins may have rotatedout of position. If so, rotate them to the correct position. Themoveable drawout element may now be moved/racked intothe stationary drawout element. Racking instructions start onpage 18.

Crank Pin in Unlocked Position

Crank Pin in Test Position

Crank Pin in Closed or Connected Position

Release Lever Mechanism

Installing Fixed-Mounted SB Breakers

Prepare the switchboard for installation of the SB breaker inaccordance with the outline drawings at the end of this sec-tion. The outline drawings are located in the Outline DimensionDrawings section starting on page 36. The locations of themounting holes and the recommended screws are depictedon the drawing. All four, six or eight mounting screws will beused to secure the breaker to the switchboard.

Carefully uncrate the breaker and remove all packing material. Ifthe breaker is secured to a pallet, remove the securing device.

Lifting straps should go between the stabs.

Attach the lifting straps as illustrated. The breaker should notbe lifted by the primary stabs; the lifting straps should gobetween the stabs. In this arrangement the breaker may beeasily balanced while it is being lifted by a crane or hoist.

Lift the breaker into position and secure it with 4 mountingscrews for 1200A and 2000A frame sizes, 6 mounting screwsfor 3200A frame size, and 8 mounting screws for the 5000Aframe size torqued to 13–15 ft-lbs. Remove the lifting straps.

Page 13: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

11

Installation Instructions

Electronic Trip Unit

CAUTION!

Installation of Electronic Trip Unit

The SB breaker has a built-in interlock device that prevents thebreaker from being closed when there is not an installed tripunit. This same interlock device will trip the breaker when thetrip unit is removed.

1. Remove 8 screws from breaker front cover.

Note: If you are installing a SB-EC Trip Unit, refer to theInformation and Instruction Guide for this device (IPIM-2208).

To install the trip unit, remove the breaker’s front cover. This isdone by removing the four recessed Phillips head screws inpositions 2, 3, 6, and 7, as well as the four Phillips head screwsin positions 1, 4, 5, and 8, which hold the front cover in place.

NOTE: For more complete information on other standardand optional features of the electronic trip units, seeSiemens Electronic Trip Units for SB Encased SystemsBreakers Information and Instruction Guide Bulletin IPIM-2203 and the Sentron Systems Breaker Energy Communi-cating Trip Unit Information and Instruction GuideBulletin IPIM-2208.

2. Lift off front cover.

On trip units with ground fault protection, the ground faultselection switch on the side of the trip unit must be set to theappropriate sensing scheme—Residual or Source Ground/ZeroSequence—before installing the trip unit. The trip unit is presetat the factory to a residual sensing scheme.

3. Set ground fault selection switch.

Do not attempt to install a trip unitwith the breaker Closed or Charged.Make certain breaker is Open andDischarged as shown above. Personalinjury or mechanical damage may occur.

1

8

3

2

67

5

4

Page 14: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

12

Installation Instructions

Electronic Trip Unit

Before attempting to install the trip unit, check the label on theside of the unit to make sure that it is the correct unit for theSB breaker. A built-in rejection scheme will prevent the instal-lation of a trip unit into a breaker for which it is not intended.

4. Check label on side of trip unit.

This scheme consists of two pins on the support plate onwhich the trip unit will set and two matching holes in the bot-tom of the trip unit. If the holes in the bottom of the trip unitdo not aligned with the pins, the trip unit cannot be installed inthe SB breaker. If there is any doubt about a trip unit being thecorrect unit for a breaker, hold the trip unit upside down andcheck the alignment of the pins and holes.

5. Mate pin connectors.

Mate the connector half on the back of the trip unit with itscorresponding connector half in the breaker.

6. Lower trip unit onto support plate.

After the connector has been mated, lower (push) the trip unitonto the support plate. The pins on the support plate will fitinto the holes in the bottom of the trip unit.

7. Secure trip unit.

Secure the trip unit in place with the retaining screw located atthe top of the trip unit. Torque 6 to 8 in-lbs. If the trip unit top isnot secured correctly, the interlock will prevent the breakerfrom closing.

NOTE: Before energizing breaker, be sure to install acorrect rating plug. See page 13.

Page 15: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

13

Installation Instructions

Electronic Trip Unit Rating Plug

8. Replace circuit breaker front cover.

Replace the front cover. Then, replace the eight front coverscrews.

9. Re-install the eight screws that hold the front cover in place.

CAUTION!

Verify that breaker is Open before inserting or removing arating plug. Breaker should always be in the Open positionwhen there is no rating plug in the trip unit.

1. Remove trip unit screws that hold the transparent cover.

The rating plug and adjustments on the front panel of the tripunit are protected by a transparent cover. Before installing arating plug or setting the adjustments on the trip unit, thiscover must be removed. Unscrew the two screws that hold itin place.

2. With a small screwdriver, gently pry the cover loose at one end andremove it carefully.

Do not attempt to install a rating plugwith the breaker Closed or Charged.Make certain breaker is Open andDischarged as shown above. Personalinjury or mechanical damage may occur.

Page 16: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

14

Installation Instructions

Rating Plug

CAUTION!

3. Check label on the rating plug.

Check the rating plug label to verify that it is the correct plugfor the trip unit. If it is not a correct plug, the pins will not matewith the plug receptacle.

4. To insert rating plug, align plug with plug receptacle and press intoplace.

To

insert

a rating plug in the trip unit, align the plug with theplug receptacle and press the plug into place. The clips on theplug secure the plug, eliminating the need for screws orlatches.

To

remove

a rating plug, squeeze the clips and pull the plugfrom the plug receptacle. Because the plug is held in place bycompression, some force is required to remove the plug.

Donot close

the breaker with the rating plug removed from thetrip unit.

5. To replace the cover, bow it slightly in the middle and snap intoplace.

After the rating plug has been inserted and the necessary set-ting adjustments have been made, replace the cover by slidingthe protective shield into the top lip of the trip unit, bow itslightly in middle, and press it down with your thumb onbottom to snap shield into place. Replace the two specialretaining screws.

NOTE: For more complete information on the electronictrip units, see Siemens Electronic Trip Units for SBEncased Systems Breakers Information and InstructionGuide Bulletin IPIM-2203 and the Sentron SystemsBreaker Energy Communicating Trip Unit Information andInstruction Guide Bulletin IPIM-2208.

6. The cover may be sealed with a lead seal for tamper evidentprotection.

After the cover has been replaced, a wire may be insertedthrough the holes in the screws and secured with a meterseal. This will help prevent tampering.

Do not attempt to force an incorrectrating plug into a trip unit. Mechanicaldamage may occur. The receptacle in thetrip unit has been keyed to prevent theinsertion of an incorrect rating plug.

Page 17: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

15

Operating Instructions

Operating the SB Encased Systems Breaker

General Instructions

Instructions for charging the stored energy mechanism, clos-ing and opening the breaker, and positioning and rotating themoveable drawout elements of the drawout-constructed SBbreakers are presented in this section. The trip unit’s standardtest and monitoring functions are also presented. Theseinstructions are grouped into two parts: Operating the SBBreaker and Manipulating the Moveable Drawout Element.Before bringing the SB breaker on-line, the user should befamiliar with the test and monitoring functions. Operatinginstructions for the accessories are presented in the Accesso-ries Section.

Operating the SB Breaker

The SB breaker controls and charging handle for the storedenergy mechanism are located in the central escutcheon ofthe front panel. Standard controls are Push-to-Close and Push-to-Open pushbuttons. Color-coded indicators display thecharged/discharged status of the stored energy mechanismand the closed/open status of the breaker. Positions are avail-able in the central escutcheon for a Key Interlock and anElectric Close pushbutton.

SB Encased Systems Breaker Controls and Indicators

A

B

C

D

E

F

A. Stored energy mechanism spring charged/ spring discharged status indicator

B. Push-to-Close pushbutton

C. Position forElectric Closepushbutton

D. Circuit breaker Closed/Openstatus indicator

E. Position forKey Interlock

F. Push-to-Open pushbutton

Page 18: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

16

Operating Instructions

Operating the SB Encased Systems Breaker

Manually Charging the Stored Energy Mechanism

The stored energy mechanism may be charged with the SBbreaker open or closed. If the stored energy mechanism ischarged with the breaker open, sufficient energy is stored toclose and then open the breaker without recharging. If thestored energy mechanism is charged with the breaker closed,the operating sequence of open-close-open may be executedwithout recharging. To manually charge the stored energymechanism, pull the charging handle.

Five or six full strokes, or several partial strokes are required tofully charge the stored energy mechanism. When the storedenergy mechanism is fully charged, Spring Charged/Spring

Discharged indicator points to Spring Charged. The charginghandle returns to the stowed position when released. Whilemanually charging the breaker with the charging handle,

donot

depress the Push-to-Close or Push-to-Open push buttons.

If an optional electric motor operator is employed, the electricoperator automatically recharges the stored energy mecha-nism when the breaker is closed. If the electric operator is dis-abled, the stored energy mechanism may be chargedmanually.

CAUTION!Do not exert further downward pressure when springs are charged or handle is against bottom stop as shown in the illustration below. Potential damage to housing may occur.

To manually charge the stored energy mechanism, pull the charging handle downward five or six strokes until indicator points to“Spring Charged.”

Page 19: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

17

Operating Instructions

Operating the SB Encased Systems Breaker

Discharging the Stored Energy Mechanism Without Closing the SB Breaker

Discharging the energy in the stored energy mechanism withoutclosing the breaker creates an abnormally high shock conditionon the breaker.

Avoid this procedure except for safety and/oremergency reasons.

To discharge the energy, push and hold theOpen pushbutton and then push the Close pushbutton.

On electrically-operated breakers, the electric operator shouldbe disabled (one way is to remove the fuse) before dischargingthe stored energy. Otherwise, the electric operator automati-cally recharges the springs. To close the breaker, standard clos-ing-prevention devices require that the following: (1) a trip unitmust be installed in the SB breaker, (2) the stored energymechanism must be fully charged, and (3) the charging handlemust be in the stowed position. On drawout constructions,the release lever must be in the release-engaged position (upposition).

Accessories that inhibit the breaker from being locally closedare presented in the Accessories section. Included are a clos-ing-blocking device for use with remotely-operated circuitbreakers, key interlocks, and other locking devices.

Discharging energy from the stored energy mechanism with-out closing contacts.

Closing the SB Breaker Locally

Before the breaker can be closed, the stored energy mecha-nism must be fully charged and all of the closing-preventiondevices (and accessories) must be in the noninhibiting state orposition. In this condition, all that is required to close thebreaker is to push the Close pushbutton. When the breaker isclosed the Contacts Closed/Contacts Open indicator will pointto Contacts Closed.

Indicates that the circuit breaker is Closed with the springs inthe Charged position.

Indicates that the circuit breaker is Open with the springs inthe “Discharged” position.

Opening the SB Breaker Locally

To locally open the breaker, push the Open pushbutton. Whenthe breaker is open, the Contacts Closed/Contacts Open indi-cator will point to Contacts Open.

Built-in safety devices trip the SB breaker if the trip unit isremoved or the release lever on the drawout mechanism isdepressed. Performing the trip unit integral test in the tripmode also trips the breaker.

Page 20: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

18

Operating Instructions

Manipulating the Moveable Drawout Element

Manipulating the Moveable Drawout Element

There are four positions of the moveable drawout element.These four positions are defined as Connected, Test,Unlocked, and Unlocked/Withdrawn. The

connected

positionis the normal operating position of the breaker. In this positionthe primary stabs and secondary contacts are connected andthe moveable drawout element is locked into position. In the

test

position, the primary stabs are disconnected, the second-ary contacts are connected, and the moveable drawout ele-ment is locked into position. The

unlocked

position is atransition position between the test position and the with-drawn position.

Moveable drawout element in the Connected position.

Moveable drawout element in the Test or Unlocked position.

Moveable drawout element in the Withdrawn position.

Physically, the unlocked position and test position are thesame. However, in the unlocked position, the moveabledrawout element is disengaged from the drive mechanism.The breaker should not be tested when the moveable drawoutelement is in the unlocked position. In the

unlocked/with-drawn

position, the secondary contacts are disconnected andthe moveable drawout element is disengaged from therelease mechanism. The moveable drawout element can bepulled to the fully withdrawn position where it can beinspected or removed from the stationary drawout element.

NOTE: Relationship of finger clusters and bus will be thesame for all drawout frames. Configurations may change.

Connected Position

Test or Unlocked Position

Withdrawn Position

BusStab

FingerCluster

ConnectedTest

BusStab

FingerCluster

BusStab

FingerCluster

UnlockedTest

BusStab

FingerCluster

BusStab

FingerCluster

WithdrawnUnlocked

BusStab

FingerCluster

Page 21: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

19

Operating Instructions

Manipulating the Moveable Drawout Element

Racking ControlsA built-in, low-force pump handle and two control levers areused to rack the moveable drawout element between theConnected, Test, and Unlocked positions.

Racking Controls Locations

Directional Shift Lever The directional shift lever determines the direction the movabledrawout element will move when it is racked. The lever has threepositions: racking-out, neutral, and racking-in. When the lever is inthe racking-out position (pulled all the way out), the moveabledrawout element may be racked from the Connected position tothe Test position, and from the Test position to the Unlocked posi-tion. When the lever is set in the neutral position (located mid-way between the racking-in and racking-out positions), theracking pump handle is disengaged from the racking mechanism.In the racking-in position (pushed all the way forward), themoveable drawout element may be racked from the Unlockedposition to the Test position, and from the Test position to theConnected position.

1. Racking-out Position

2. Neutral Position

3. Racking-in Position

E. RackingPumpHandle

C. PositionIndicator

A. MoveableDrawoutElement

F. DirectionalShift Lever

D. StationaryElement

B. ReleaseLever

E

F

B

C

D

A

Page 22: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

20

Operating Instructions

Manipulating the Moveable Drawout Element

Racking Pump HandleA low-force pump handle is used to rack the moveabledrawout element. The pump handle is an integral part of theracking mechanism, eliminating the need for an auxiliary rack-ing device. If there is any resistance in returning the pumphandle to the stowed position, set the directional shift lever tothe neutral position. The racking pump handle can then bereturned to the stowed position.

Racking Pump Handle in Stowed Position

Racking Pump Handle in Full Stroke Position

Drawout Position IndicatorA color-coded indicator displays the position of the moveabledrawout element: connected (red), test (yellow), and unlocked(yellow). When the moveable drawout element is being rackedfrom one position to another position, the indicator will displaythe more critical position.

The Connected position is defined to be more critical than theTest position and the Test position to be more critical than theUnlocked position. This means that when racking the move-able drawout element from the Connected position to the Testposition, the indicator will continue to display the Connectedposition until the moveable drawout element has been rackedall the way to the Test position. Conversely, when racking fromthe Test to the Connected position, the indicator will displaythe Connected position as soon as the SB breaker is movedtoward the Connected position. The process is the same whenracking between the Test and Unlocked position.

Drawout Position Indicator

UnlockedPosition(Yellow)

TestPosition(Yellow)

ConnectedPosition(Red)

Page 23: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

21

Operating Instructions

Manipulating the Moveable Drawout Element

Fully Withdrawn and Unlocked PositionsTo move the moveable drawout element from the FullyWithdrawn position to the Unlocked position, push toward thebus connections until the moveable drawout element hits asolid stop. The secondary disconnects on both sides of themoveable and stationary drawout elements will mate as themoveable drawout element moves into the Unlocked position.When the moveable drawout element is in the Unlockedposition, the pointer on the position indicator will point to theUnlocked symbol. To move the moveable drawout elementfrom the Unlocked position to the Fully Withdrawn position,fully extend the side rails until they rest in a horizontal position.Then pull the moveable drawout element to the ends of therails.

Pushing and pulling the moveable drawout element between the Withdrawn and Unlocked postiions.

Page 24: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

22

Operating Instructions

Manipulating the Moveable Drawout Element

CAUTION!

Unlocked Position to Test PositionRacking the moveable drawout element from the Unlockedposition to the Test position engages the moveable drawoutelement with the stationary drawout element. The physicalposition of the moveable drawout element will be unchanged.Complete the steps that follow to rack the moveable drawoutelement from the Unlocked position to the Test position.

NOTE: If extension rails are pulled out, push them in untilthey hit a solid stop.

1. Push in the directional shift lever. This is the racking-in position.

2. Pull the release lever down to the release-disengaged position.(Illustrated beneath padlock device.) If the breaker contacts areclosed, pulling the release lever down will trip the breaker.

3. Pump the racking pump handle until the moveable drawout elementhas reached the Test position.

4. When the moveable drawout element reaches the Test position, therelease lever will automatically return to the release-engaged (up)position, the racking pump cannot be pumped, and the positionindicator will display that the moveable drawout element is in theTest position.

To avoid damaging the racking mecha-nism, always pull the release leverbefore racking the moveable drawoutelement.

Page 25: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

23

Operating Instructions

Manipulating the Moveable Drawout Element

CAUTION!

Test Position to Connected PositionTo rack the moveable drawout element from the Test positionto the Connected position.

1. Push in the directional shift lever. This is the racking-in position.

2. Pull the release lever down to the release-disengaged position.(Illustrated beneath padlock device.) If the breaker contacts areclosed, pulling the release lever down will trip the breaker.

3. Pump the racking pump handle until the moveable drawout elementis in the Connected position.

4. As soon as the moveable drawout element is racked from the Testposition, the position indicator will display that the moveabledrawout element is in the Connected position. However, the move-able drawout element will not be completely in the Connectedposition until the release lever has automatically returned to therelease-engaged position. Push the side rails back into the storedposition.

To avoid damaging the racking mechanism, always pull the release lever before racking the moveable drawout element.

Page 26: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

24

Operating Instructions

Manipulating the Moveable Drawout Element

CAUTION!

Connected Position to Test Position

To rack the moveable drawout element from the Connected posi-tion to the Test position, ensure that the SB breaker is open. (Ifthe breaker is closed and the release lever is moved downwardto the interlock disengaged position, the breaker will trip.)

1. Pull out the directional shift lever. This is the racking-out position.

2. Pull the release lever down to the interlock disengaged position.(Illustrated beneath the padlock device.) If the breaker contacts areclosed, this action will trip the breaker.

3. Pump the racking pump handle until the moveable drawout elementis in the Test position.

4. When the moveable drawout element reaches the Test position, therelease lever will automatically return to the interlock engaged posi-tion, the racking pump handle cannot be pumped, and the positionindicator will display that the moveable drawout element is in theTest position.

To avoid damaging the racking mecha-nism, always pull the release leverbefore racking the moveable drawoutelement.

Page 27: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

25

Operating Instructions

Manipulating the Moveable Drawout Element

CAUTION!

Test Position to Unlocked Position

Racking the moveable drawout element from the Test position tothe Unlocked position disengages the moveable drawoutelement from the stationary drawout element. The physicalposition of the moveable drawout element will be unchanged. Torack the moveable drawout element from the Test position toUnlocked position, complete the following steps:

1. Pull out the directional shift lever. This is the racking-out position.

2. Pull the release lever down to the interlock disengaged position.(Illustrated beneath the padlock device.) If the breaker contacts areclosed, this action will trip the breaker.

3. If breaker will be withdrawn: Extend side rails fully until they are ina horizontal position (3200-5000 amp only).

4. Pump the racking pump handle until the moveable drawout elementis in the Unlocked position.

5. When the moveable drawout element reaches the Unlocked posi-tion, the release lever will automatically return to the interlock en-gaged (up) position and the position indicator will display theUnlocked position. Pull out the extension rails until they hit a solidstop before pulling out the moveable drawout. (3200-5000A only).

Relative Position of Finger Clusters to Bus Stabs

BusStab

FingerCluster

UnlockedTest

BusStab

FingerCluster

To avoid damaging the racking mech-nism, always pull the release levelbefore racking the moveable drawoutelement.

Page 28: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

26

NOTE: Refer to the separate SB Accessories Installationand Instruction Guide for information on AccessoryInstallation and ratings. Refer to the separate SB TroubleShooting Guide for trouble-shooting tips.

CAUTION!

NOTE: Siemens recommends that all accessories beinstalled using the instruction information accompanyingthe accessory, or by referring to the Accessory Manuals(IPIS-00105 and IPIS-00106).

1. Before removing the cover check to be sure the circuit breaker maincontacts are open and the closing springs are discharged by firstpushing the open button.

2. Push the close button and then repeat pushing of the open button.Verify that the status indicators show Spring Discharged andContacts Open.

Mechanism can cause severeinjury when cover is removed.Before removing cover, push open button, push close button, and thenpush open button again.

CAUTION!Install all accessories with the breakerOpen and Discharged as shown above.To avoid injury or damage to equipment,do not install accessories with breakerin a Closed or Charged position.

Internal Accessories

Preliminary Installation Procedures

Page 29: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

27

Internal Accessories

Preliminary Installation Procedures

3. Remove the breaker cover by first removing the four #10 Phillipshead screws at the corners and the four 1/4” Phillips head screwsin recesses in cover.

4. Remove cover.

5. Remove the trip unit if installed, by removing trip unit retainingscrew.

6. Slide the trip unit up to clear the support bracket pins.

7. Remove the trip unit by pulling the trip unit away from the trip unitplug.

Page 30: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

28

Internal Accessories

Preparation For Installation of Internal Accessories

.

CAUTION!

NOTE: Refer to the separate SB Accessories Installationand Instruction Guide for information on AccessoryInstallation and ratings. Refer to the separate SB TroubleShooting Guide for trouble-shooting tips (IPIS-00102-0599).

Accessories

The full family of accessories available for Siemens SB breakersare presented in this section. The accessories are divided intotwo groups. Group one consists of accessories installed in thefront compartment of the circuit breaker (Internal Accessories).

Group two consists of accessories installed or used outside ofthe front compartment (External Accessories). The ExternalAccessories are installed on the exterior of the circuit breaker,on the drawout elements, or at remote locations. When theinstallation location is referred to as the right side or left side, itis with reference to the user’s right or left side when facing thefront of the breaker.

Components required to access or activate an accessory suchas a switch or indicator at a remote location are assumed to beuser supplied unless otherwise stated.

Group One – Internal Accessories

Secondary connections to remote locations are made to sec-ondary disconnects on drawout breakers and to control termi-nal blocks on fixed-mounted breakers. The terminal points forall internal accessories are illustrated in the control terminalsdiagram on page 59.

Control power connections for accessories are made throughterminal blocks mounted on the sides of the breaker. Drawoutconstructed breaker control power connections are madethrough secondary disconnects mounted on the stationary andmoving elements.

Electric Operator Troubleshooting Guide

Symptom Solutions

Motor does not run. 1. Check for springs already charged by checking spring charge indicator.

2. Check for rated voltage at LT1 (+) and LT5 (–).

3. Check motor fuse – requires 2.5A Slo-Blo fuse.

4. Check all wiring connections.

5. If the lamp connected to LT4 is blinking slowly (1 second on, 2 seconds off), manually charge breaker.

Motor runs for 20 seconds, does not charge springs, optional lamp on LT4 blinks slowly (1 second on, 2 seconds off).

1. Breaker has been partially charged manually. Complete manual charge operation with the charging handle. Electric motor operator should now be engaged for the next charge cycle.

Breaker will not close electrically. 1. Check to see if springs are charged by checking charged indicator flag.

2. Check for power on LT1 (+) and LT5 (–).

3. Check for power on LT2 (+). If power is on LT2 (+), remove and re-apply.

4. Check to see if breaker is locked in open position by either padlocking device, kirk key, or drawout interlock.

5. Check to see if breaker handle is fully seated in cover.

6. Check all wiring connections.

7. Check motor fuse – requires 2.5A Slo-Blo fuse.

8. Verify latch check switch adjustment

Lamp on LT4 blinks slowly (1 second on, 2 seconds off).

1. Manually charge breaker springs. Lamp on LT4 should remain on.

Install all accessories with the breakerOpen and Discharged as shown above.To avoid injury or damage to equipment,do not install accessories with breakerin a Closed or Charged position.

Page 31: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

29

Internal Accessories

Preparation For Installation of Internal Accessories

Removing the Left and Right Drawout Mechanism

Complete the following steps to remove the crankshaft.

1. Remove the E-rings from the bar cap pin on each side.Note: e-ring may be located on outside of plate.*Note this location for reassembly.

2. Remove the bar cap pin from each side.Note: It may be necessary to remove the bar cap pin from theopposite side. Note this orientation for reassembly.

3. Rotate the bar caps upward.

4a. Lift out the crankshaft assembly. (Rotating the crankshaft back andforth makes it easier to remove.)

4b. Using 1/4” nut driver, remove 2 screws from center recesses of leftor right mechanical assembly.

5. Take off the left and/or right mechanism assemblies (as required) byremoving the two, three or four 5/16-inch bolts and nuts on eachside.

Reinstalling the Left and Right Drawout Mechanism

Remove cover. Install cover, making sure metal clips are in place on left and right.

1. Attach the left and/or right mechanism assemblies to the breakerusing two, three or four 5/16-inch bolts and nuts. Torque the bolts to16 to 20 ft.-lbs.

Using 1/4” nut driver, reinstall the 2 screws into center recesses ofeither side mechanism assembly.

2. Rotate the bar caps upward.

Page 32: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

30

Internal Accessories

Preparation For Installation of Internal Accessories

3. Install the crankshaft assembly by positioning the crank pin any-where between the unlocked and connected positions as shownand lowering the crankshaft to the bottom of the slot. During crank-shaft assembly installation, the lock bar must be held in the properposition. This may be done by inserting a screwdriver into thedouble-D hole (if present) and pushing until a solid stop is felt. If thedouble-D hole is not present, use the rectangular cutout to gainaccess to the lockbar as shown.

.

4. Rotate the bar caps downward.

5. Install the bar cap pins through the bar caps and left and right mech-anism assemblies with the head of the pins toward the center of thebreaker.

Note: Bar cap pin should be reinstalled on the side it was originallyremoved.

6. Install an E-ring on each bar cap pin.Note: e-ring should be installed on the side of the plate that itwas orginally removed.

7. Complete steps 1 to 4 on Unlocked Position to Test Position on page22 to verify the lock bar is in the proper position. You should have topull the interlock lever down before racking the drawout, and the le-ver should return to the engaged position when the drawout reach-es the unlocked, test, or connected positions. If the interlock leverdoes not operate in this manner, the lock bar is not in the proper po-sition and step 3 above must be repeated.

Perform steps 1-5 on test position to unlocked position on page 25,returning crankshaft to correct position before breaker installation.

NOTE: Failure to ensure proper drawout operation cancause the drawout to not lock in the correct position.Injury to personnel and damage to equipment can result.

Page 33: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

31

External Accessories

Siemens ACCESS Communications System

SB Breaker Communication

All SB Circuit Breaker trip units feature two levels of communi-cation: Zone Selective Interlocking and ACCESS System open-protocol communications. The SB-EC Trip Unit is fully equippedfor direct integration into ACCESS or compatible communica-tion systems. It does not require a MTA (Muliplexer/Translatorfor ACCESS communications and Zone Interlocking) or expan-sion plug (EP).

If zone selective interlocking alone is specified for a SB-EC orTL Trip Unit, a MTZ (Muliplexer/Translator for Zone Interlock-ing) and an EP are required.

If zone selective interlocking and full ACCESS communicationsare specified for a TL Trip Unit, a MTA and an EP are required.

The MT (as in MTA and MTZ) is a minicomputer that collectdata from and transmit data to difference componentsintegrated into the ACCESS communications system. The MTcan support up to eight field devices. Multiple MTs can beconnected, although an expansion plug may be required foreach trip unit.

Siemens WinPM supervisory software (version 4.0 or later)delivers a powerful energy management system providingsophisticated monitoring capability to a host computer andother components in the electrical distribution system ataffordable cost. It also provides process control, including peakdemand, trend analysis, waveform analysis, and harmoniccalculations and displays. These functions help pinpoint energyconsumption, power quality issues, and the energy cost of anyprocess. Outages and potential outages can be quicklydiagnosed and plans can be generated for expansion andpreventative plant maintenance.

NOTE: Refer to Bulletin IPIM-2211 for additional informa-tion on the MTA and Siemens WinPM software.

Communications is accomplished via EIA-485 twisted pairwire or modem. It provides communications to a remote siteand allows access to multiple plants. WinPM uses a MicrosoftWindows dynamic data exchange (DDE) server that allowsdata exchange to other Windows-based software such asspreadsheets and word processors.

Protocol Converters are available from the Siemens ACCESSgroup for connecting a variety of open and proprietary automa-tion protocols, including Profibus DP, LonWorks, Siemens S7PLC, and many other third-party PLCs and associated net-works. The SB-EC Trip Unit’s EIA-2342 communications portprovides additional PC communications for available trip unit

data displays and trip unit configuration via Siemens SBWINsoftware. Remote open/close operation is also possible if aremote open/close relay is installed.

Expansion Plug

Factory wired when ACESS communications or ZSI is ordered forthe SB breaker from the factory.

The EP is an electronic interface and isolation module requiredto integrate a breaker into an ACCESS system. When required,one expansion plug is used for each circuit breaker in thesystem and is used to interface trip units to a MTZ or MTA.The expansion plug is always necessary for zone interlockingor full ACCESS communications for the TL Trip Unit. It is notrequired for ACCESS communications with the SB-EC TripUnit. However, an expansion plug is required for zone inter-locking with the SB-EC Trip Unit.

Expansion Plug Dimension Drawing

SB Systems Breakers

The following sections describe both types of SB trip units,the standard Type ‘TL’ unit with rotary switches, and the SBEnergy-Comm (SB-EC) Trip Unit with keypad and display. Sincethe SB-EC Trip Unit has integral communications capability, theMTA device is not

required to connect within an ACCESS sys-tem, however for SB-EC Trip Units in a ZSI system, an MTZ orMTA is required.

The type EPSB expansion plug is factory wired to the SBbreaker trip unit’s rear connector and also located near andwired to the SB breaker’s secondary terminal block for fixedmount breakers or sliding disconnects for drawout breakers.These connections are factory wired when the SB breaker isordered with the standard switch based type ‘TL’ trip unit forACCESS communications or for any trip unit with ZSI capability.

Installed ICCB SB breakers without communication capabilitymay be field upgraded for communication capability bySiemens Field Service personnel only.

Breaker Type Frame Size Mounting Type Cat. No.

SB ICCB 1200A, 2000A Fixed EPSBFMK

Drawout EPSBDMK

SB ICCB 3200A, 5000A Fixed EPSB4FMK

Drawout EPSB4DMK

Sensitrip MCCB

ALL ALL

EP

EPSB

Page 34: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

32

External Accessories

Siemens ACCESS Communications System

The

MTCSB

cable is used to connect an

MTA

or

MTZ

to an

EPSB

expansion plug via the SB breaker secondary terminalblock or sliding disconnect.

A. SB Breaker Zone Selective Interlocking (only)

1. All SB Breaker Trip Units

Components Required:

• Siemens type MTZ – one per 8 trip units• Siemens type EPSB expansion plug – one per trip unit,

factory wired• Siemens type MTCSB cable – one per trip unit

Installation:

1. When the factory-installed ZSI option is present, the

EPSB

ex-pansion plug is already wired to the breaker and secondarycontrol terminals. Connect an MTCSB cable’s spade lugsfrom the appropriate SB breaker’s secondary terminals (LB9,10, 11, & 12) to one of eight communication inputs on the MTZ.

2. If multiple MT’s are used, the “Com” terminal from the firstMT’s “SEABus Out” port must be connected to the “Com”terminal of the next MT’s “SEABus In” port on each MT beingused.

3. Based on the site’s coordination study, configure the expan-sion plug’s DIP switches for Short Time and/or Ground FaultZSI per the EP Information and Instruction Sheet.

4. Configure the MTZ to identify the zones for each breaker, perthe site’s coordination study and information and instructionsheet. Refer to figure 1 for system connections diagram.

MTC Cable

LB Breaker Terminals

FactoryWired

Factory Wired

MTCSB Cable

MTC Cable

EPC Cable

MTCSB CableRequired forZSI onlywith ECTrip Unit

RS-485 Common

Required forZSI only

FactoryWired

Factory WiredSB Breaker

WithSB-EC Trip Unit

LB Breaker Terminals

EPSB

(LB 9)(LB 10)

(LB 11)(LB 12)(LB 5)

(LB 6)(LB 7)

(A(+) B(-)IN

(A(+) B(-)OUT

Com

MT (#1) ZIIN

1 2 3 4 5 6 7 8

EP

SensitripMCCB

RS-485 (+)RS-485 (-)

ACCESS Communicationsto WinPM or DTU-3005 Protocol Converter

(A(+) B(-)IN

Com

ZIOUT

1 2 3 4 5 6 7 8

MT (#2)

EPSB

SB BreakerWith

Type ‘TL’Trip Unit

(LB 9)(LB 10)

(LB 11)(LB12)

Figure 1 System Connection Diagram

Page 35: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

33

External Accessories

Siemens ACCESS Communications System

B. SB Breaker ACCESS Communications (with or without Zone Interlocking)

1. Standard type ‘TL’ switch-based trip unit

Components Required:

• Siemens type MTZ – one per 8 trip units• Siemens type EPSB expansion plug – one per trip unit,

factory wired• Siemens type MTCSB cable – one per trip unit

Installation:

1. When the factory-installed ACCESS communications optionis present, the EPSB expansion plug is already wired to thebreaker and secondary control terminals. Connect anMTCSB cable’s spade lugs to the appropriate SB breaker’ssecondary terminals (LB9, 10, 11, & 12) then to one of eightcommunication inputs on the MTA.

2. If ZSI functionality is additionally required, per the site’scoordination study, configure the expansion plug’s DIPswitches for Short Time and/or Ground Fault ZSI per theexpansion plug’s Information and Instruction Sheet. Config-ure the MTA to identify the zones for each breaker, per thesite’s coordination study and the MTA’s instruction sheet.

3. If multiple MT’s are used, the “Com” terminal from the firstMT’s “SEABus Out” port must be connected to the “Com”terminal of the next MT’s “SEABus In” port on each MTbeing used.

4. If ZSI is not required, set the expansion plug’s DIP switchesto NO ZONE (0000), the MTA’s Device Configuration DIPswitches to NO ZONE (00) and the Device Type MTA’s DIPswitch to MCCB/ICCB (0001).

5. Connect RS-485 twisted pair communication cable to theMTA’s A(+) and B(-) terminals. Connect only one end of thecable’s shield to the MT’s GND terminal. Configure theACCESS system network, per Installing the ACCESS Sys-tem manual. An Isolated Multidrop Converter may beinstalled as an option. See figure 1 for system connectiondiagram.

2. SB-EC Trip unit

Since the SB-EC Trip Unit has direct communications with anACCESS network, no intermediate devices are required unlessZSI functionality is required.

If ZSI is required, connect as per above using an MTA if type‘TL’ SB breaker trip units or Sensitrip MCCB trip units are partof the overall system and both ACCESS communications andZSI are required.

Any application requiring only ZSI requires an MTZ configuredas above.

If multiple MT’s are used for ZSI functionality, the “Com” ter-minal from the first MT’s “SEABus Out” port must be con-nected to the “Com” terminal of the next MT’s “SEABus In”port on each MT bing used.

As referenced in the SB-EC Trip Unit Information and Instruc-tion Manual, the trip unit’s ACCESS communication lines are

located on the breakers secondary control terminals <LB5> toRS485(+), <LB6> to RS-485(-), and <LB7> to Shield/Common.Refer to figure 1 for system connection diagram.

Summary

The following table summarizes the required

ComponentTypes per each trip unit in the system. One component pertrip unit unless otherwise otherwise noted:

Component Selection Guide

Notes:

1. It is recommended that for long, single-ended runs (over 1000 ft.),that a 120 ohm, 1/4 watt terminating resistor between the Data+ andData- terminals of the furthest devices be added. Adding a terminatorresistor is not an absolute requirement, but using it will minimize re-flected interference on the communication bus.

2. Both loop and straight RS-485 topologies are acceptable. The advan-tage of the straight topology is further distance to the last device(4000 ft.) The advantage to the loop topology is that the devices willcontinue to communicate even with a break in the line. The disadvan-tage of the loop topology is the distance to the furthest device is only2000 ft.

3. A Siemens Isolated Multi-Drop Converter (Cat. No. 18-658-852-537)may be used as an optional device used to convert four (4) RS-485communications loops to one (1) RS-232 port for host PC communi-cations.

4. Protocol converters are available from the Siemens ACCESS group toprovide plug-and-play capability with over 25 different PLC protocols(Siemens S7, Modbus, etc.), Profibus, DeviceNet, and LonWorks.

5. If multiple MT’s are used for ZSI applications, the “Com” terminalfrom the first MT’s “SEABus Out” port must be connected to the“Com” terminal of the next MT’s “SEABus In” port on each MT beingused.

6. Installed ICCB SB breakers without communication capability may befield upgraded by Siemens Field Service personnel only. MCCBbreakers may be field upgraded by Siemens Field Service or the enduser.

7. Refer to Installing the ACCESS System Installation Guide (ManualSG-6028-01) for proper system shield and grounding connectionsschemes.

Note: Refer to the MT and EPSB installation instructions included witheach device for additional information.

Trip Units and Application

Component Type

ZSI (only)with SensitripMCCB’s

ACCESSand/or ZSIwith SensitripMCCB’s

ZSI (only)with allSB-ECTrip Units

ACCESSand/or ZSI with SB-TLTrip Units

ACCESSwithSB-ECTrip Units

EP

✔ ✔

EPSB

✔ ✔

MTZ

✔ ✔

MTA

✔ ✔

EPC Cable

✔ ✔

MTC Cable

✔ ✔

MTCSB Cable

✔ ✔

When ordered with circuit breaker from the factory.

One MTA or MTZ per eight trip units when required.

Always required when multiple T’s are used. One additional cable per each additional MT.

Page 36: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

34

General Information

CAUTION!

Universal Test Kit

Operating Instructions

NOTE: Detailed instructions are supplied with the TS-31kit.

1. Remove electrical loads from circuit breaker.

2. Plug TS-31 test set into a grounded 120VAC receptacle and turn it on.The identifying turn-on message appears

3. Select the appropriate ribbon cable assembly and connect it betweenthe TS-31 and the circuit breaker. Check alignment and polarity.

4. Comply with the prompting messages. If you require guidance, referto the instructions shipped with the TS-31 test set.

5. Enter the appropriate breaker settings when prompted. If the breakerincludes instantaneous pickup, short-time functions, or ground fault,enter the appropriate breaker settings.

NOTE: Entering the wrong data will cause false tests andresults.

6. Enter the test and phase you want tested. The TS-31 reports the typeof test you selected and gives you a chance to abort the test. If youpress the letter A to abort, you are given new options.

7. Comply with the prompt to start the test. The test can require a fewseconds or several minutes, depending on which procedure isrunning.

NOTE: If the breaker trips during a test, reset it beforecontinuing.

The last setting entered into the TS-31appears in brackets onthe second line of the display. If you do not want to change anexisting setting, press ENTER. If you want to change a setting,type in the new setting and press ENTER.

Error Messages

An error message may appear if the test set senses that cur-rent is not flowing correctly in the breaker. This can occurwhen there is an open or short circuit between the TS-31 andthe breaker trip unit. Error messages also may appear:

• If you enter a type of test that is not available on the breaker being tested.

• If you select a ground-fault test and the trip unit does have ground fault.

• If you enter a setting value that does not exist.Running successive high-current, long-time tests can overheatthe test set. The unit protects itself from damage by prevent-ing further tests until it has cooled down. The display indicateswhen testing can resume.

The TS-31 warns you of possible fault coverage conflicts. Forexample, conflicts can occur if the short-time and instanta-neous pickup settings overlap or interfere with one another.

NOTE: For trip unit values, refer to the information sheetssupplied with the TS-31 kit.

External Accessories

Universal Test Kit (TS-31)

Remove electrical loads from the circuitbreaker to be tested prior to performingtests. Failure to do so can produceerroneous results and possible electricalmalfunction.

Page 37: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

35

Outline Dimension Drawing

1200A Stationary Drawout Element

LC

4X Ø.4383.25

Left Cradle Plate ShownCut Away For Clarity

3.50

2X 5.00

Provide Clearance Holes For1/4 -20 Screws For Rear Mounting (4 Req’d)

2X 3.62

2X Ø.88

See Detail A

2X 1.00

2X 3.50

26.46

2X 2.00

1.75.85

Preferred Mounting Surface

1.36

15.86

15.37Wire Path ForSecondary Contacts

8.75

Lifting Points. Do NotLift By Other Points17.50

5.00

5.00

.50

2X .54

19.00

17.38

18.50InsideCradle

20.50

4X Top4X Bottom

5.82 2.94

21.829.56

2.38 Front Cover

2.75

1.25.75

LC

Ø.228 Holes

4X Top4X Bottom

Ø.438 Optional Mounting Holes

Page 38: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

36

Outline Dimension Drawing

1200A Stationary Drawout Element

Optional RearMounting Surface

1.30

4X 2.50

Provide Clearance Holes For #8-32 ScrewsWhen Using Rear Flange Mounting Surface.(4-Req’d)

13.75

4X 5.50

4X 1.00

2X 6.88

Of BusStab

Of BusStab

20.00

10.00

8.75

2X .375

2X 1.00

8.562

12X Ø.281Front Mtg. Holes

.44

Detail AScale 1/1

3/8 -16 BusSupport Bolts

Rear View

LC

LC

LC

Page 39: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

37

Outline Dimension Drawing

1200A Moveable Drawout Element

3X Ø 1.25

1.74

2.13 .20

.94

4.56

4X.59

2.84

2X.44

2.84

4.56

.94

20.50Overall

10.25

6.88

13.75Overall

4.59

2.872.87

4.59

Front Panel CutoutMinimum Clearance (Escutcheon Dimensions)

Front View

Front View

LC LC

LC LC

LC

Page 40: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

38

Outline Dimension Drawing

1200A Moveable Drawout Element

7.75

15.50

Front Cover LocationShown Provides MinimumClearance With Breaker

.75

Breaker TestPosition

Breaker FullyWithdrawn

16.00 15.75

1.45

Breaker Handle

Drawout Handle

Front Cover

.72536°

Minimum Clearance RequiredFor Breaker Rotation

58°

10.54

R 11.52

21.82

7.82

10.31

Top View

Side View

LC

LC

Page 41: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

39

Outline Dimension Drawing

1200A Fixed-Mounted

1.13

11.13

11.38

3.37

1.00Typ.

See Detail A

11.63

12.13

15.50

5.005.00

Ø.34 HolesTyp.

2.25

2.50

.09

Detail A – 1/1 Scale

Top View

LC

Page 42: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

40

Outline Dimension Drawing

1200A Fixed-Mounted

7.82

11.00

.95Typ.

Clearance for Handle Rotation Ø .34 HolesTyp.

90°Max.

.50Typ.

1.75Typ.

3X Ø 1.25

2X .94

1.74

2.13 .204.56

4.56

4X.59

2X.44

2X2.84

1.13

.3714.00

9.75

R .125Typ.

.75

.87

7.375

14.75

12X .38 X.43 Slot

4X Ø .44Mounting Holes

.66

6X 1.32

5.00 5.00

12.00

2X5.50

.50

.375

4.59

2.872.87

4.59

Front Panel CutoutMinimum Clearance

(Escutcheon Dimensions)

For 3/8 - 16x23/4 (Min.) screws,use 2 flat washers, 1 lock washerand nut. Torque to 15 ft. lbs. max.

Side View

Front View

Front View

LC

LC

LC

LC

LC

LC

LC

LC

Page 43: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

41

Outline Dimension Drawing

2000A Stationary Drawout Element

LC

LC

2X 2.50

2X 9.75

CL

Provide Clearance Holes For #8-32 ScrewsWhen Using Rear Flange Mounting Surface.(4-Req’d)

19.75

4X 8.50

4X 5.50

4X 1.00

20.00

Of BusStab

Of BusStab

2X .375

2X 1.00

10.00

8.75

8.562Typically 16 places Ø .281Front Mtg. Holes

Optional RearMounting Surface

1.30

.44

3/8 -16 BusSupport Bolts

Detail AScale 1/1

Page 44: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

42

Outline Dimension Drawing

2000A Stationary Drawout Element

4X Top4X Bottom

4X Top4X Bottom

Ø .438 Optional Mounting Holes

8.75

17.505.00

5.00

.50

Lifting Points. Do NotLift By Other Points.

2X .54

19.00 17.38 18.50InsideCradle

Ø .228 Holes

5.82 2.94

20.50

FrontCover.75

21.82

9.56

1.252.38

2.75

Left Cradle Plate ShownCut Away For Clarity.

2X 7.12

2X 3.62

2X 2.00

3.50

3.25Provide Clearance Holes For1/4-20 Screws For RearMounting (4 Req’d)

1.36

2X Ø .88

8X Ø .438

2X .882X 4.00

2X 7.50

1.75.85

Preferred Mounting Surface

See Detail A(Page 41)

Wire Path ForSecondary Contacts.

26.4615.86

15.37

Top View

Side View

LC

LC

Page 45: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

43

Outline Dimension Drawing

2000A Moveable Drawout Element

7.75

15.50

Front Cover LocationShown Provides MinimumClearance With Breaker

.75

Breaker TestPosition

Breaker FullyWithdrawn

16.00 15.75

1.45

12.14

.725

Breaker Handle

Drawout Handle

Front Cover

21.82 10.31

7.82

R 13.50

47°

Minimum clearance requiredfor breaker rotation

58°

LC

LC

Side View

Top View

Page 46: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

44

Outline Dimension Drawing

2000A Moveable Drawout Element

Page 47: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

45

Outline Dimension Drawing

2000A Fixed Mounted

LC

7.82

Handle Clearance Rotation

2.87

2X 2.50

90° Max.

24 Ø .39 Holes1.75Typ.

2X 7.12

1.75

.88

1.13

3.37

.75Typ.

11.13

12.13

11.63

11.38

See Detail A

5.005.00

7.75

15.50

2.375

2.76

.09

3X Ø 1.25

2X .94

1.74

2.13 .204.56

4.56

4X.59

2X.44

2X2.84

4.59

2.872.87

4.59

Front Panel CutoutMinimum Clearance

Detail A

LC

LC

LC

LC

LC

Page 48: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

46

Outline Dimension Drawing

2000A Fixed Mounted

2.75

14.75

24 Ø .40 Holes

7.375

.75Typ.

5.00

Mounting Holes4X Ø .44

1.50 Typ.

1.50

5.506.375

2X4X

16.75

2X8.375

5.00

.75 14.00

R .125Typ.

9.75

2.25

15.50

For 3/8 -16x23/4 (Min.) screws,use 2 flat washers, 1 lock washerand nut. Torque to 15 ft. lbs. max.

LC LC

LC

LC

LC

Front View

Front View

Page 49: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

47

Outline Dimension Drawing

3200A, 4000A, and 5000A Stationary Drawout Element

Location

Frame Size

3200 4000/5000

ABCDE

20.365.00

17.3818.5021.50

28.347.50

25.3826.5029.50

Frame Size

3200 5000

ABC

4X .8758X .4382X 5.00

4X 1.258X .4062X 5.00

4X 1.7512X .5622X 6.00

4000Location

B

B

A DInsideCradle

C E

6X Top6X Bottom

4X Top4X Bottom

Ø.438 Mounting Holes Ø.228 Holes

Lifting Points.Do Not Lift ByOther Points.

.25

4.00

3.00

7.3023.28

4.759.50

2X 1.25

2.75.75

Top View

3.26

Left Cradle Plate ShownCut Away For Clarity.

2X 2.50

2X 6.50

C

A

.75

2X 11.25

2X Ø1.00

B

1.75Wire Path forSecondary Contacts

15.3727.27

.50

3200 Ampere BusConfiguration

FrontCover

2X 3.00

5000 Ampere BusConfiguration

Stationary Drawout ElementTop View Dimensions

Stationary Drawout ElementSide View Dimensions

Page 50: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

48

Outline Dimension Drawing

3200A, 4000A, and 5000A Stationary Drawout Element

Stationary Drawout ElementRear View Dimensions

Rear View

4X 7.50

4X 5.00 4X 4.00

2X 17.50

4X 8.75

4X 15.00

16X Ø .281Front Mtg. Holes

A

B

C

35.00

Location

Frame Size

3200 4000/5000

ABC

2X 8.752X 10.25

20.50

2X 12.752X 14.25

28.50

Page 51: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

49

Outline Dimension Drawing

3200A, 4000A, and 5000A Moveable Drawout Element

Location

Frame Size

3200 4000/5000

AB

7.5015.00

11.5023.00

16.00.75

14.73

1.61Breaker TestPosition

A

B

Top View

Breaker FullyWithdrawn

Moveable Drawout ElementTop View Dimensions

23.28

7.76

Drawout Handle

15.15

Breaker Handle

Front CoverSide View

.50

3200 Ampere BusConfiguration

2X 3.00

5000 Ampere BusConfiguration

Page 52: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

50

Outline Dimension Drawing

3200A, 4000A, and 5000A Moveable Drawout Element

17.50

B

AOverall

35.00Overall

Front View

OfBreaker

OfBreaker3.45

5.71

3.45

5.71

2.87

2.87 8.28 8.28

Optional Panel Cutout(For Trip Unit andLabel Information)

Front Panel CutoutMinimum Clearance

Of Breaker Of Breaker

2.842.84

4X.59

2X.44

4.56

4.56

.94.94

3X Ø 1.25

Front View(Escutcheon Dimensions)

2.13 .20

1.74

Location

Frame Size

3200A 4000/5000A

AB

21.5010.75

29.5014.75

Moveable Drawout ElementFront View Dimensions

Note: Not drawn to scale Note: Not drawn to scale

Page 53: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

51

Outline Dimension Drawing

3200A Fixed-Mounted

4.91 5.69

3.98

10.25

R .12Typ.

.75 14.00

R .12Typ.

9.13

4.54

Front View(Escutcheon Dimensions)

5.00Typ.

Side View

15.12

1.00Typ. 1.25

Typ.1.12

1.75 4.00 Typ.

1.87

16.75

8X Ø.56

.75.751.75

.75

.25

Page 54: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

52

Outline Dimension Drawing

3200A Fixed-Mounted

Page 55: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

53

Outline Dimension Drawing

4000A and 5000A Fixed-Mounted

R .12Typ.

R .12Typ.

8.91 5.68

3.98

10.25

3.50 16.50

9.13

4.54

Front View(Escutcheon Dimensions)

1.25Typ.

.75

5.002.75

26.00 22.50

3.501.75

1.00

3.25

Side View

Page 56: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

54

Outline Dimension Drawing

4000A and 5000A Fixed-Mounted

23.50

20.00

12.50

5.00 .50Typ.

1.50Typ.

.87

.63

11.1311.38

11.6312.13

12.75

Top View

8X Ø .44 Mounting HolesFor 3/8 -16 x 2 3/4 (Min.) Bolts.Use 2 Flat Washers,1 Lockwasher and Nut.Torque to 15 lb. Max.

5.00

22.75

Front View

.38

3.004.75

27.50

22.50

11.00

3.00

3.50

30X Ø .41Holes

2.00

7.50

15.00

21.25

4.00

1.752.75

20.50

Page 57: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

55

Electrical Schematics

Electronic Bell Alarm, Display Module Relay (mutually exclusive devices)

Electronic Bell Alarm and Alarm Relay Combination Module

Remote Open/Close Relay

244 8 12 16 20 28 32 36

3

2

1

7

6

5

11

10

9

15

14

13

19

18

17

23

22

21

27

26

25

31

30

29

35

34

33

ALARM

TRIP

<RT12>

<RT10>

<RT11>

<RT9>

+ –

Bell Alarm Reset Switch

RT= Right Top SecondaryTerminals on Breaker.

Internal Breaker Connections

ALARM

CustomerSupplied

<RT12>

<RT10>

<RT11>

<RT9>

+ –

ControlPower

Control Power

Trip Unit Plug Shown As ViewedFrom Front Of Breaker

Electronic Bell AlarmTypes SBDMR and SB4DMR

Display Module RelayTypes SBDMR and SB4DMR

Breaker Load End

External ConnectionsBreaker Right Side

TRIP

60VA Max.1.25A Max.

150VDC/2000VAC Max.

60VA Max.1.25A Max.

150VDC/2000VAC Max.or

NOTE:Electronic Bell Alarm,Display Module Relayand Remote Indicator

Panel are mutuallyexclusive. No

combinatio of thesedevices are permitted.

244 8 12 16 20 28 32 36

3

2

1

7

6

5

11

10

9

15

14

13

19

18

17

23

22

21

27

26

25

31

30

29

35

34

33

BELLALARM

ALARM RELAY

MomentaryAlarmRelay

LatchingBell

Alarm

<RT12>

<RT10>

<RT11>

<RT9>

Trip Unit Plug Shown As ViewedFrom Front of Breaker

+ –

60VA Max.1.25A Max.

150VDC/200VAC Max.

Bell Alarm Reset Switch

RT= Right Top SecondaryTerminals on Breaker.

Internal Breaker Connections External Connections

Control Power

Electronic Bell Alarm and AlarmRelay Combination Module

SB Trip Unit

AlarmRelay

244 8 12 16 20 28 32 36

3

2

1

7

6

5

11

10

9

15

14

13

19

18

17

23

22

21

27

26

25

31

30

29

35

34

33

ALARMBell

Alarmor

AlarmRelay <RT12>

<RT10>

<RT11>

<RT9>

+ –

Bell Alarm Reset Switch

Internal Breaker Connections

<LT6>

<LT1>

ControlPower

Trip Unit Plug Shown As ViewedFrom Front Of Breaker

Types SBECDMR, SPECBA, SB4ECDMR and SB4ECBA Remote Open/Close Relay

External Connections

Open

60VA Max.1.25A Max.

150VDC/2000VAC Max.

<LT5>

<LT2>Close

Page 58: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

56

Electrical Schematics

DC Undervoltage Release Solenoid Schematic

AC Undervoltage Release Solenoid Schematic

MonitoredSource

<LT9> UVR+

UVRCoil

<LT10> UVR–

DC Undervoltage Release

Internal Breaker ConnectionsExternal Connections

Undervoltage Release Connection

+ –

Monitored Source

External Breaker ConnectionsInternal Breaker Connections

<LT9> UVRUVRCoil

<LT10> UVR

AC Undervoltage Release Schematic

Resistor

If Needed

Page 59: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

57

Electrical Schematics

Shunt Trip Schematic

Auxiliary Switch Schematic

Shunt Trip<LT7> Remote Open-Closed Indication

<LT8> Coil - (Common) COMNC <ST>

NO

<LT6> Coil+

“B” TypeClearingSwitch

Shunt TripCoil

Supplied byCustomer

Supplied byCustomer

ControlPower+ –

Auxiliary Switch 2

Auxiliary Switch 3

<RB12>

<RB9>

<RB11>

<RB10>

<RB5>

<RB6>

<RB7>

<RB8>

<RB4>

<RB3>

Aux. 1 B

Aux. 2 A

Aux. 2 A

Aux. 2 B

Aux. 2 B

Aux. 3 A

Aux. 3 A

Aux. 3 B

Aux. 3 B

Auxiliary Switch 5

Auxiliary Switch 1

Auxiliary Switch 6

<RT8>

<RT7>

<RT6>

<RT5>

<RT10>

<RT11>

<RT9>

<RT12>

<RB2>

<RB1>

Aux. 5 A

Aux. 5 B

Aux. 5 B

Aux. 6 A

Aux. 6 A

Aux. 6 B

Aux. 6 B

Aux. 1 A

Aux. 1 A

Aux. 1 B

Auxiliary Switch 4

<RT1>

<RT2>

<RT3>

<RT4>

Aux. 4 A

Aux. 4 A

Aux. 4 B

Aux. 4 B

Aux. 5 A

Auxiliary Switches

Internal Breaker ConnectionsExternal ConnectionsBreaker Right Side

Breaker Load End

To Customer'sApplications

Not availablewith SB-ECTrip Unit.

Note: Auxiliary swtiches 1A, 1B, 2A, 2B, 3A, 3B

and 6A, 6B may be ordered as 8 normally

open contacts or8 normally closed

contacts optionally.

Not availablewith Bell Alarmor Alarm RelayAccessory

Page 60: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

57A

Electrical Schematics

Page 61: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

58

Electrical Schematics

Neutral Transformer/EP/Remote Indicator Panel

Control Terminals Identification

RT1

RT2

RT3

RT5

RT6

RT7

RT8

RT4

EC EXTERNAL POWER (+12) OR AUXILIARY SWITCH

EC EXTERNAL POWER (+5) OR AUXILIARY SWITCH

PTM OR AUXILIARY SWITCH

PTM OR AUXILIARY SWITCH

PTM OR AUXILIARY SWITCH

PTM OR AUXILIARY SWITCH

EC EXTERNAL POWER (COMMON) OR AUXILIARY SWITCH

EC EXTERNAL POWER (-12) OR AUXILIARY SWITCH

SHUNT TRIP INDICATION

SHUNT TRIP POWER (+)

LT3

LT2

LT1

LT6

LT5

LT7

LT8

LT4 SPRING CHARGE INDICATION

REMOTE CLOSE POWER (+)

MOTOR OPERATOR POWER (+)

MOTOR OPERATOR POWER (-)

LOCAL ELECTRIC CLOSE POWER (+)

RT9

RT10

RT11

RT12

RB1

RB2

RB3

RB4

RB5

RB6

RB7

RB8

RB9

RB10

RB11

RB12

ALARM OUT OR AUXILIARY SWITCH

ALARM OUT OR AUXILIARY SWITCH

ALARM POWER (+) OR AUXILIARY SWITCH

ALARM POWER OR AUXILIARY SWITCH

AUXILIARY SWITCH

AUXILIARY SWITCH

AUXILIARY SWITCH

AUXILIARY SWITCH

AUXILIARY SWITCH

AUXILIARY SWITCH

AUXILIARY SWITCH

AUXILIARY SWITCH

AUXILIARY SWITCH

AUXILIARY SWITCH

AUXILIARY SWITCH

AUXILIARY SWITCH

NEUTRAL SENSOR (-)

NEUTRAL SENSOR (+)

UNDERVOLTAGE POWER (+)

UNDERVOLTAGE POWER (-)

RIP OR AUXILIARY SWITCH

NO CONNECTION

ELECTRIC INTERLOCK (CCX)

ELECTRIC INTERLOCK (CCX)

LT12

LT11

LT10

LT9

LB2

LB1

LB4

LB3

EC RS485 (-) OR RIP

EC RS485 (+) OR RIP

EC RS485 GND OR RIP

LB8

LB7

LB6

LB5

LB11

LB9

LB10

LB12 MTCSB (BLACK) OR AUXILIARY SWITCH

MTCSB (RED) OR AUXILIARY SWITCH

MTCSB (GREEN) OR AUXILIARY SWITCH

MTCSB (YELLOW) OR AUXILIARY SWITCH

RIP COMMON OR AUXILIARY SWITCH

TERMINAL BLOCKS (FIXED BREAKERS)CONTROL DISCONNECTS (DRAWOUT BREAKERS)

SHUNT TRIP POWER (-)

CONTROL TERMINALS IDENTIFICATION

"C" PHASE"A" PHASE

LEFT

POLE

CENTERPOLE

"B" PHASE

NEUTRAL SENSOR

OF BREAKER.

NOTE: TRIP UNIT PLUG SHOWNAS VIEWED FROM FRONT

POLE

RIGHT

TWISTED PAIR

TWISTED PAIR

GR

EE

N

BLU

E

GR

AY

OR

AN

GE

EXPANSION PLUG

BLA

CK

RE

D

<LB6>

<LB5>

<LB4>

<LB7>

<LB8>

PANEL

<LB11> RED

MTCSB (YELLOW)

MTCSB (GREEN)

MTCSB (RED)

MTCSB (BLACK)

TO MULTIPLEXER / TRANSLATOR

CABLE TO MULTIPLEXER / TRANSLATOR

USE CAT. NO. MTCSB-XX, WHERE XX IS

THE LENGTH IN FEET.

EXTERNAL CONNECTIONS

<LB12> BLACK

<LB10> GREEN

INTERNAL BREAKER CONNECTIONS

<LB9> YELLOW

REMOTE INDICATOR

OF ELECTRONIC ALARM SWITCH

SHEET 5 FOR CONNECTION

AND LOCAL LOAD MONITOR RELAY.

ARE MUTUALLY EXCLUSIVE. NO

DEVICES IS PERMITTED. SEE

COMBINATION OF THESE

AND REMOTE INDICATOR PANEL

LOCAL LOAD MONITOR RELAY,

NOTE: ELECTRONIC ALARM SWITCH,3127

3228

35

36

11

12

15 19

16 20

73

84

23

24

2925

30

33

34

9

10

13 17

14 18

51

2

RED

GRAY

WHITE

21

22

ACTUATING

MECHANISM

(MAG LATCH)

MAGNETIC

TRIP UNIT

<LT11>

<LT12>

+X1

-X2

"N" PHASE

CEN.

+

-

2

4

5

1

3

TWISTED PAIR

+

+

+

266

Page 62: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

59

Electrical Schematics

Electric Motor Operator

Legend

1. Motor Operator Assembly

2. Remote Closing Solenoid Switch

3. Connector Strip

4. Motor Fuse Connector

5. UL Label (Not Shown)

6. DC or AC ECMC Assembly

8. B Switch Assembly (Motor Operator)

9. #10-32 UNC-2B x 1/4 PHMS

10. #10-32 UNC-2B x 3/8 PHMS (Not Shown)

11. #6-32 UNC-2B x 1/4 PHMS

12. #4-40 UNC-2B x 1/2 PHMS

13. #6 Lockwasher

14. #6-32 UNC-2B x 1/4 PHMS

15. #6-32 UNC-2B x 1/4 Type F HMS (Not Shown)

16. Cable Tie

17. Local Close Switch Assembly – optional

18. Wire Tie Adhesive Mounting Base (Not Shown)

AND TIGHTEN SET SCREW AGAINST SHAFT.

SCREWS, ALIGN LINKAGE WITH SOLENOID PLUNGER

AFTER TIGHTENING SOLENOID

SOLENOID ASSEMBLY

LT2

LT1

LT2

LT3-5LT5

LT2-4

SB

EO

24

R

Sie

men

s E

nerg

y &

Aut

omat

ion

Inc.

Ele

ctric

Ope

rato

r

Circ

uit B

reak

er A

cces

sory

Cat

. No.

List

ed

965D

PRESS

FUSE

8

12

16

11

1513

16

HEAT SHRINK

XX

XX

XX

AS

SE

MB

LY N

O.

1215

23X

XX

PC

B M

CU

AS

SY

#41

0986

A00

PW

B P

WR

AS

SY

#41

09X

XX

XX

11

3

13 15

1

NOTE:172

16

10

OPTION ONLY.

ELECTRIC CLOSE INTERLOCK

FOR USE WITH

LEFT BOTTOMWIRE CHANNEL

6

2000A & 4000A FRAMES.

SIMILAR ASSEMBLY FOR

800A FRAME ASSEMBLY SHOWN.

LB1

LB2

LT3

Page 63: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

60

Electrical Schematics

Electric Motor Operator

Electric Motor Operator Schematic

NC

SWITCH"B"

NO

NC

SWITCH

HC(HANDLE CHECK)

NO

CCX IS NOT INSTALLED.THIS WIRE IS USED WHEN

COM

COM

<LB2>

<LB1>

(CCX)

ELECTRIC CLOSING OF THE

2 AMPS MAX.120 W MAX.

-+

CONTROL POWER

CUSTOMER SUPPLIED

JUMPER BEFORE THE BREAKER CAN BE CLOSED.

BREAKER BY ADDING INTERLOCK.

IF AN INTERLOCK IS NOT NEEDED

THE CUSTOMER MUST INSTALL A

NOTE: CUSTOMER MAY PREVENT

250 VDC/200VAC MAX.

EXTERNAL CONTACT (SHOWN)

NO SWITCH

NO SWITCH

NC CAM(CAM CHECK)

NO

NCSC

NC LC

SWITCH

(LATCH CHECK)

(SPRING CHECK)

<J1-10>

<J1-7>

<J1-8>

<J1-9>J1-10

J1-8

J1-7

J1-9

<J1-3>

<J1-4>

<J1-5>

<J1-2>

<J1-1>

MC

U

J1-3

J1-4

J1-5

J1-6

J1-2

J1-1

TER

MIN

AL

PLU

G

<J1-6>

DC

PO

WE

R S

UP

PLY

BO

AR

D

<J1-11>

<J1-8>

<J1-7>

<J1-9>

<J1-10>

<J1-6>

<J1-5>

<J1-4>

<J1-1>

<J1-2>

<J1-3>

COMMONREM. CLOSE +

TER

MIN

AL P

LUG

J1-4

J1-1

J1-3

J1-2

J1-6

J1-5

J1-8

J1-7

J1-10

J1-9

J1-11

LEC

NC

COM

NO

SWITCH(LOCAL ELECTRIC CLOSE)

<LT2>

LOCAL ELECTRIC CLOSE

AVAILABLE AS FACTORY INSTALLED OPTION ONLY.

REMOTE CLOSE +

COM

COM

COM

<HC-LC><LT2-4>

<LT3>

<LT4>

<LT3>

<LT5><LT2>

<LT5><LT2>

<LT1>THIS LINE

CHARGE INDICATION

PERMISSIVE CONTROL THROUGHNOTE: CUSTOMER MAY PROVIDE <LT3-5>

<LT1> ELEC. OPER. +

MOTORCONTROLLER

LOCAL ELECTRIC CLOSE

EXTERNAL CONNECTIONS INTERNAL BREAKER CONNECTIONS

<RC+><RC->COIL

ELECTRIC OPERATOR

CLOSING

THIS WIRE IS USED

INSTALLED.

WHEN CCX IS

<LB2> CCX

FUSE2.5 A

SLO-BLO<MTR+><MTR->

<LB1> CCX24 VDC

MOTOR

<FUSE>

INTERLOCK OPTION (CCX)AVAILABLE AS FACTORY

INSTALLED OPTION ONLY.

ELECTRIC CLOSE

<L<LT3>T3>

Page 64: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

61

Accessory Ratings

Motor Operator Current Draw

Electrical Data for Remote Close Solenoid

Switch Contact Ratings

Undervoltage Release Ratings

Shunt Trip Ratings

Supply Voltage Motor Rating (Amperes)

120VAC24VDC48VDC125VDC

3333

Coil VoltageInrush Current

(Amperes)Catalog Number

120V AC (60 Hz) 9.4A

SB4RCS120

SBRCS120

24V DC

48V DC

125V DC

20.0A

10.3A

3.6A

SB4RCS24, SBRCS24

SB4RCS48, SBRCS48

SB4RCS125, SBRCS125

Supply Voltage Ampere Rating

120V AC240V AC480V AC24V DC125V DC

10.0A10.0A6.0A 3.0A0.5A

Catalog Number

Hold-in

Current

(Amperes)

Coil Voltage

SBUV12

SBUV24

SBUV48

SBUV125

SB4UV12

SB4UV24

SB4UV48

SB4UV125

0.12A

0.06A

0.03A

0.02A

12V DC

24V DC

48V DC

125V DC

SBUV120

SBUV240

SBUV480

SBUV600

SB4UV120

SB4UV240

SB4UV480

SB4UV600

0.02A

0.02A

0.02A

0.02A

120AC

240AC

480AC

600AC

Catalog Number

Inrush

Current

(Amperes)

Operating

Voltage

SBST12

SBST24

SBST48

SBST125

SB4ST12

SB4ST24

SB4ST48

SB4ST125

3.20A

3.10A

1.60A

0.64A

12V DC

24V DC

48V DC

125V DC

SBST120

SBST240

SBST480

SB4ST120

SB4ST240

SB4ST480

5.50A

3.60A

0.35A

120AC

240AC

480AC

Page 65: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

SB Solenoid Coil ResistancesSHUNT TRIP SOLENOID:

Shunt Trip Plunger O.D. = 0.310 inch+/– 5% @ 20 degrees C12 VDC – 3.6 ohms 120 VAC – 79.6 ohms24 VDC – 14.2 ohms 240 VAC – 380 ohms48 VDC – 55 ohms 480 VAC – 1163 ohms

125 VDC – 370 ohms

Shunt Trip Plunger O.D. = 0.437 inch+/– 10% @ 20 degrees C12 VDC – 4.3 ohms 120 VAC – 14 ohms24 VDC – 9 ohms 240 VAC – 48 ohms48 VDC – 34 ohms

125 VDC – 225 ohms

UNDERVOLTAGE RELAY SOLENOIDS:

+/– 5% @ 20 degrees C12 VDC – 117 ohms 48 VDC – 1822 ohms24 VDC – 460 ohms 125 VDC – 11,395 ohms*

*125 VDC Solenoid used for all VAC UVR Applications.

ELECTRIC OPERATOR CLOSING SOLENOIDS:

+/– 10% @ 20 degrees C24 VDC – 1.28 ohms 120 VDC – 35 ohms48 VDC – 5.20 ohms 125 VDC – 35 ohms

REMOTE CLOSE SOLENOIDS:

+/– 10% @ 20 degrees C24 VDC – 1.28 ohms 120 VDC – 14 ohms48 VDC – 5.20 ohms 125 VDC – 35 ohms

PRIMARY CURRENT INJECTION AND FIELD TESTING SB BREAKERS

All field testing should be in accordance with NEMA Standards Publication No. AB4.

62

Page 66: SB Encased Systems Breakers - Peterson Electric … General Information Introduction Siemens SB Encased Systems Breakers bridge the perfor-mance gap between Molded Case Circuit Breakers

Siemens Energy & Automation, Inc. Power Distribution Infrastructure Division3333 Old Milton Parkway For Production InformationAlpharetta, GA 30005 www.sea.siemens.com/power

© 2001 Siemens Energy & Automation, Inc. Order No.IPIM-2210-D Siemens is a registered trademark of Siemens AG.Specifications are subject to change without notice.

For Nearest Sales Office1.800.964.4114 www.sea.siemens.com/sales