  • ROOF TOP Pompa di Calore Aria/AriaCompressori Scroll-Disponibili con Bruciatore a GasRoof Top - Air to Air Heat PumpScroll Compressor-Available with Gas Burner

    Roof Top Pompa di Calore Aria/Ariacompressori scrollRoof Top - Air to Heat Pumpscroll compressor

  • ROOF TOP Condizionamento AutonomoROOF TOP Pompa di Calore Aria/AriaCompressori Scroll

    STRUTTURAI profilati di alluminio connessi mediante angolari pressofusi, bulloneria con trattamento anticorrosione ,base integrale zincata. Pannellatura realizzata totalmente in lamiera preverniciata.COMPRESSORI-Scroll, alternativi con resistenza carter incorporata e protezione integrale termoamperometrica completi di marmitta silenziatrice interna.-Semiermetici, alternativi con resistenza carter incorporata e protezione elettronica integrale completi di rubinetti di intercettazione e antivibrante ANACONDA sulle tubazioni di mandata ed aspirazione.VENTILATORI ASSIALI A bassa emissione sonora con pale a profilo aerodinamico, motori IP55 con protezione termica integrata.BATTERIA DI SCAMBIO ARIA ESTERNAMulticircuito, con tubi in rame ed alette in alluminio ad elevata superficie di scambio.VANO TERMICORivestito con materiale afonico bugnato alloggia compressori, circuiti frigoriferi, quadro elettrico; separato dal flusso daria consente la taratura di strumentazione e organi di controllo a macchina in moto.CIRCUITO FRIGORIFEROIndipendente per ogni compressore comprende: filtro deidratore, indicatore liquido e umidit, rubinetto linea liquido, valvola termostatica ( montata su UTA), valvola di sicurezza e valvole di servizio. Inoltre per i modelli in pompa di calore include: valvola di inversione di ciclo, valvola termostatica invernale, ricevitore di liquido separatore di aspirazione e valvole di ritegno.QUADRO ELETTRICOIn esecuzione stagna IP55 include:-sezione di potenza: sezionatore di linea con intterrutore blocco-porta, fusibili di protezione, teleavviatore compressori e ventilatori UTAMICROPROCESSORE DI CONTROLLO E STATO che comprende:seziona automatica sequenza compressori, ritardo di avviamento-visualizzazione allarmi- contatto pulito comulativo per invio segnalazione a distanza e pulsante di reset allarmi.PER I MODELLI IN POMPA DI CALORESistema di sbrinamento sdoppiato.Le sicurezze comprendono inoltre: pressostati di alta pressione a reinserimento manuale, pressostati di bassa pressione a reinserimento automatico.

    STRUTTURAI profilati di alluminio connessi mediante angolari pressofusi, bulloneria con trattamento anticorrosione ,base di supporto integrale zincata completa di tasselli antivibranti. Pannellatura realizzata in peralluman con interposto strato di materiale termoisolante. Pannellatura doppia ( a richiesta) realizzata in peralluman con interposto iniezione di poliuretano espansoTETTUCCIOParapioggia in perallumanCASSONETTO FILTRANTECon moduli estraibili a superficie ondulata in materiale di tipo sintetico rigenerabile, legato con resine ad espansione controllata EU3BATTERIA DI TRATTAMENTOMulticircuito con tubi in rame ed alette in alluminio, ampia vasca di raccolta condensa in acciaio inoxVENTILATORE CENTRIFUGOA doppia aspirazione, con pale avanti, azionato da motore trifase mediante cinghia e puleggia, il tutto connesso ad una base rigida supportata da antivibranti.FREE COOLING ( opzionale)Corredato da sezione di estrazione/espulsione/ e camera di miscela aria esterna/ ricircolo (free cooling) con serrande con alette di alluminio complete di guarnizioni e griglia parapioggia, con rete antivolatile motorizzabili (perno libero) dimensionate per il 100% della portata.Tutti i modelli sono disponibili, su richiesta, equipaggiati con refrigeranti R407c e R134a

    Tutte le macchine sono consegnate con certificato di collaudo del costruttore e sono conformi alle normative europee in materia di sicurezza CE.

  • Self contained A/C units ROOF TOPRoof Top - Air to Air Heat Pumpscroll compressor

    MOTOCONDENSING UNIT-HEAT PUMPCasing structureThe frame is made of aluminium anodized profiles with casted comers and anticorrosion treated bolts;the base is made of hot deep galvanized steel,the panels are made of peralluman plates.COMPRESSORSScroll- type, with oil heater and fully protected against thermal / electrical overheat. Also a sound device is included for low-noise operation.SEMIHERMETIC type, with oil heater and a integral electronic protection, including supply / return stop valves and anaconda vibration isolators on both supply / return refrigerant pipes.AXIAL FANSLow-noise type, with special aerodynamic profile blades, IP55 electronic motors,with internal overheat protection.CONDENSER COILMulti-circuit type,with copper tubes and high-surface aluminium fins.SERVICE SECTIONBuilt separate from the air flow and fully insulated, includes the compressors, refrigerant circuits, the electric switchboard enabling to ste the unit parameters and to service the unit while in operation.REFRIGERANT CIRCUITBuilt independent for each compressor, includes deidrating filter, switch flow and humidity alarm switch, liquid line valve, thermostatic valve ( fitted con UTA units) , safety valve and service stop valves.In addition for the units pf heat pump version there will be the special cycle inverter valve the winter thermostatic valve, the liquid receiver, supply separator and stop valve.ELECTRIC SWITCH-BOARDTotally water/air tight according IP55, includesPOWER SUPPLY SECTIONMain on/off switch with door loc.Protection fuses, compressors and fans tele switches.MICROPROCESSORIncluding the automatic sequence compressor control; start time delay; display of alarm clean contact for distance control and alarm; alarm reset push button.FOR HEAT PUMP UNITSThe safety devices include als the high pressure switch with manual reset and the low pressure switch automatic reset.

    AIR TREATMENT SECTIONCasing structureThe frame is made of aluminium anodized profiles with casted aluminium comers and anticorrosion treated bolts; the base is made of hot deep galvanized steel, complete with antivibration supports.The panels are made of peralluman plates. Upon request the panels may be of sandwich type, with peralluman plates and expanded polyurethane insulation.PROTECTION ROOFFor outdoor protection, made of peralluman platesFILTER SECTIONEquipped with extractable modules of corrugated washable material, with addition of controlled expanded resins, efficiency classified EU3COOLING COILMulticircuit type, with copper tubes and aluminium fins and a large stainless steel condensate panCENTRIFUGAL FAN FOR AIR SUPPLYDouble inlet type, forward blades, operated by a 3-phase electric motor, through pulley and belts transmission, assembled on a sliding base with antivibration isolators.FREE-COOLING ( option)The system is complete of a double mixing box including air exhaust/ return/fresh air. Intakes,with control dampers,automatically controlled, up to 100% of the air volume.All the units are available for operation with refrigerants R407c and R134a

    All units are delivered with operation maintenance and service manual, factory test certificate and CE marking, of conformity with the European safety rules.

  • MODELLO/MODEL 10 15 20 30 40 55 70

    Capacit raffredamentoCooling capacity

    Kw 11,11 14,37 21,06 27,95 39,21 55,04 69,02

    Capacit riscaldamentoHeating capacity

    Kw 14,90 19, 20 27,30 36,00 50,70 71,30 89,40

    Alimentazione / Voltage 400V/3ph/50Hz

    COMPRESSORI/Compressors SCROLL

    Refrigerante/Refrigerant R407c

    Quantit/Quantity Nr. 1 1 1 1 1 1 1

    PotenzaassorbitaAbsorbed power

    Kw 3,8 4,8 6,2 8,1 11,5 16,2 20,4

    Corrente assorbitaAbsorbed current

    A 6,9 8,8 11,7 14,5 20,8 30,9 36,9

    SEZIONE TRATAMENTO ARIAAIR HANDLING SECTION

    Potenza assorbita ventilatoreFan absorbed power

    Kw 0,55 0,75 1,1 1,1 2,2 2,2 3,0

    Portata aria ventilatoreFan flow rate

    m/h 2000 3500 4200 4900 8000 9500 12000

    Corrente assorbita ventilatoreFan absorbed current

    A 1,6 1,8 2,7 2,7 5,2 5,2 6,6

    Prevalenza utile/Head Pa 150 150 150 150 150 180 180

    Filtrazione/Filtration TipoType

    Classe G4 efficienza 90%Grade G4 efficiency 90%

    Dimensioni/Dimensions

    Lunghezza/Length mm 2400 2700 3000 3000 3500 4000 4000

    Larghezza /Width mm 1300 1300 1300 1300 1300 1300 1300

    Altezza / Height mm 1550 1550 1850 1850 1850 1850 1850

    Peso / Weight Kg 250 415 485 500 795 930 1050

    Dati di tabella riferiti a:

    Refrigerazione:-Temp. aria esterna ( B.S.) 35C-Temp. aria batt. 1 imp. (B.S. / B.U) 27/19CRiscaldamento:(solo RTF-HP)-Temp. aria esterna (B.S./ B.U.) 7/6C-Temp. aria batt. 1 imp.( B.S.) 20 C

    Referring data table on the:

    Cooling-Outside air temperature (D.B.) 35C-System air temp. (D.B. / W.B.) 27/19CHeating(only RTF-HP)-Outside air temperature (D.B./W.B.) 7/6C-System air temp. (D.B.) 20C

    Versioni disponibili/AVAILABLE VERSIONSSIGLA/ABBREVATION DESCRIZIONE/DESCRIPTION

    ROOF-TOP Condizionatore autonomo Roof Top in versione solo freddo e pompa di caloreRoof Top independent conditioner, only cold and heating pump versions

    ROOF-TOP/HP Condizionatore autonomo Roof Top in versione solo freddo e pompa di caloreRoof Top independent conditioner, only cold and heating pump version

    ROOF-TOP/HPB Condizionatore autonomo Roof Top in versirsione solo freddo con bruciatore a gas Roof Top independent conditioner, only cold version with gas burner

  • Dati di tabella riferiti a:

    Refrigerazione:-Temp. aria esterna ( B.S.) 35C-Temp. aria batt. 1 imp. (B.S. / B.U) 27/19CRiscaldamento:(solo RTF-HP)-Temp. aria esterna (B.S./ B.U.) 7/6C-Temp. aria batt. 1 imp.( B.S.) 20 C

    Referring data table on the:

    Cooling-Outside air temperature (D.B.) 35C-System air temp. (D.B. / W.B.) 27/19CHeating(only RTF-H