  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    1/54

    Outputs

    Radio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non StandardMaintenance

    A50023-X4005-A2-4-7619

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    2/54

    2 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    f Important Notice on Product SafetyElevated voltages are inevitably present at specific points in this electrical equipment. Some of theparts may also have elevated operating temperatures.

    Non-observance of these conditions and the safety instructions can result in personal injury or in prop-erty damage.

    Therefore, only trained and qualified personnel may install and maintain the system.

    The system complies with the standard EN 60950 / IEC 60950. All equipment connected has to complywith the applicable safety standards.

    The same text in German:Wichtiger Hinweis zur Produktsicherheit

    In elektrischen Anlagen stehen zwangslufig bestimmte Teile der Gerte unter Spannung. Einige Teileknnen auch eine hohe Betriebstemperatur aufweisen.

    Eine Nichtbeachtung dieser Situation und der Warnungshinweise kann zu Krperverletzungen undSachschden fhren.

    Deshalb wird vorausgesetzt, dass nur geschultes und qualifiziertesPersonal die Anlagen installiert undwartet.

    Das System entspricht den Anforderungen der EN 60950 / IEC 60950. Angeschlossene Gertemssen die zutreffenden Sicherheitsbestimmungen erfllen.

    Trademarks:

    All designations used in this document can be trademarks, the use of which by third parties for theirown purposes could violate the rights of their owners.

    Copyright (C) Siemens AG 2003-2003.

    Issued by the Information and Communication Networks Group

    Hofmannstrae 51

    D-81359 Mnchen

    Technical modifications possible.

    Technical specifications and features are binding only insofar as

    they are specifically and expressly agreed upon in a written contract.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    3/54

    A50023-X4005-A2-4-7619 3

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    Issues

    Change indications (Ind.):

    N = new; G = modified; 0 = deleted;

    Document Title Page(s) Issue/Ind.

    MMN:UMR 3.0 . . . . . . . . 1... 54 4/ N

    This document consists of a total of 54 Pages.

    Issue History

    IssueNumber

    Date of Is-sue

    Reason for Update

    Draft1 Jan. 2003 First Draft release.

    1

    2

    3

    4 Dec. 2003 FEKAT correction CU9965

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    4/54

    4 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    5/54

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    6/54

    6 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    3.5 unauthorizedAccessAttempt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

    3.6 sbsOimFileTransferControl . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

    3.7 outOfHoursActivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

    3.8 authenticationFailure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 524 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

    4.1 Specific Problems for the Alarm List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    7/54

    A50023-X4005-A2-4-7619 7

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    1 IntroductionThe goal of this manual is to describe all alarms and system informations which can gen-

    erated by the Radio Commander.

    The software attempts to provide a precise error description for each alarm containing

    all informations for the operator and manufacturer for rapid localization, investigation

    and elimination of the fault. There is no relation between the number of described faults

    and their frequency of occurrence in the system.

    This manual is organized according to the error ID's.

    Error ceased messages clears all alarms for a certain probable cause of one object.

    Error ID:

    Shows the Error ID for the notification

    MOC:Identifies the managed object class of the fault or error.

    Version:

    Format not yet defined.

    Error information:

    This gives a detailed overview about the occurred error:

    Values:

    communicationAlarm

    environmentalAlarmequipmentAlarm

    qualityOfServiceAlarm

    processingErrorAlarm

    Identifies the probable cause of the fault or error. The probable cause is taken out of

    a predefined set of values defined for each alarm type.

    This is a short description of the error.

    According to the CCITT Rec. X.733 all alarm notifications produced in switching sys-

    tems have to be classified concerning the severity of their impact on the NE's func-

    tionality.

    Values: indeterminate, critical, major, minor, warning

    Gives information about the reached threshold.

    Currently not used.

    This field will be used to give reason for the occurred error/event. According to

    CCITT X.733 this part, when present, allows a free form text description to be re-

    ported.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    8/54

    8 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    Immediate defense action:

    This section describes the defense action accomplished by the software every time the

    particular Failure Event occurs. The defense action is accomplished to attempt to solve

    or at least to overcome the problem.n.a. is reported if no defense action is associated to the Failure Event.

    Proposed repair actions:

    Describes the actions the operator must perform to attempt to solve the problem.

    Every time that a diagnostic on a faulty object fails, the operator has to replace the faulty

    module (specified in the Test Report) following the procedure described in the according

    maintenance manual.

    Error description:

    Concise description of the probable cause of the error.

    1.1 Abbreviations

    Abbr. Meaning

    BSC Base Station Controller

    BSS Base Station Subsystems

    CLI Command Line Interface

    GUI Graphical User Interface

    LAN Local Area NetworkLMT Local Maintenance Terminal

    (m) Value is mandatory

    MOC Managed Object Class

    MSC Mobile Services Switching Center

    n.a. Not available

    NE Network Element

    (o) Value is optional

    OMP Operating and Maintenance Processor

    OMT Operating and Maintenance Terminal

    PCM Puls Code Modulation

    RC Radio Commander

    SMLC Serving Mobile Location Center

    WAN Wide Area Network

    Tab. 1.1 Abbreviations

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    9/54

    A50023-X4005-A2-4-7619 9

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    2 Alarms

    2.1 Time of Network Element out of sync with OMC (500)Error ID: 500

    MOC: DNODEB, DRNC, DBSS

    Version: n.a.

    Error information: equipmentAlarm

    gsmClockSynchronisa-tionProblem

    Time of Network Elementout of sync with OMC

    warning

    (o)

    (o)

    reason: NE time is out ofsync with RCtime, NEtimeset. Date and Time:outOfSyncBy:

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    No action required

    Error description: The error is generated in case the BSC, RNC or NodeN clockis not synchronized with the OMP clock.Periodic time check must be activated explicitly from GUI orCLI session.At the configured time intervals, OMP checks whether theclock of each NE connected is synchronized with the OMP. Ifthe difference is bigger than a predefined threshold, then date& time of the BSC, RNC or NodeB are set and this error is gen-erated.Note: at the time the O-link, Ift-R or Itf B connection is estab-lished, date & time of the BSC, RNC or NodeB are set withoutgenerating an alarm, even if the threshold was exceeded

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    10/54

    10 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    2.2 SW Recovery Action (501)

    Error ID: 501

    MOC: OMP, OMT

    Version: n.a.

    Error information: processingErrorAlarm

    softwareProgramAbnormallyTer-minated

    SW recovery action

    warning

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    no repair action necessary - automatic recovery, take alarm asnotice

    Error description: RC initiates autonomous SW recovery action

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    11/54

    A50023-X4005-A2-4-7619 11

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    2.3 Disk Generic HW Error (502)

    Error ID: 502

    MOC: HDD

    Version: n.a.

    Error information: equipmentAlarm

    gsmDiskProblem

    Disk Generic HW Error

    critical

    (o)

    (o)

    (o)

    Immediate defenseaction:

    Try to make a back-up of all data.

    Proposed repair ac-tions:

    1.Locate the effected disk.2.Contact local SUN service or local staff to replace the faultydisk and provide the following information: Effected OMP. Type of effected disk.3.Make sure that after have replaced thedisk therelatedalarmis ceased. If the alarm after few minutes is still active contactlocal SUN service or local staff. Otherwise give hddReplace

    command available on CLI/GUI.

    Error description: A physical error was detected in the hard disk.The followingcases are possible:

    OMP failure on disk with system software

    No redundancy/mirroring, only one diskMay be that the RC stops working. Then it is not longer possi-ble to access/maintain of the RC and the connected radio sub-systems.Redundancy/mirroring, two or more disks

    The system switches automatically to redundant disk. Thesystem and RC will continue working.

    OMP failure on disk with RC data

    No redundancy/mirroring, only one diskThe RC stops working immediately. It is not longer possible toaccess/maintain of the RC and the connected radio sub-systems.Redundancy/mirroring, two or more disksThe system switches automatically to redundant disk. Thesystem and RC will continue working.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    12/54

    12 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    2.4 Mirror/SubMirror Failure (503)

    Error ID: 503

    MOC: DATAUNIT

    Version: n.a.

    Error information: equipmentAlarm

    gsmDiskProblem

    Mirror/SubMirror failure

    critical

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    1. Locate the effected disk on OMP: execute metastat andmetadb SDS maintenance commands to see what is/are thespecific problem within Solstice Disk Suite Object (Mirror/Sub-mirror). See Solstice Disksuite 4.2 User's Guide for further de-tails.2. Contact local SUN service or local staff.Provide the error message and exact information from the pre-vious step.

    Error description: Solstice Disk Suite Object (Mirror/Submirror) malfunction.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    13/54

    A50023-X4005-A2-4-7619 13

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    2.5 MetaDb Failure (504)

    Error ID: 504

    MOC: DISKLAYOUT

    Version: n.a.

    Error information: equipmentAlarm

    gsmDatabaseInconsistency

    MetaDb failure

    critical

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    1.Locate the affected meta DB replicas on OMP: executemetadb SDS maintenance command to see what is/are thespecific problem within Solstice Disk Suite Object (meta DBReplicas). See Solstice Disksuite 4.2 User's Guide for furtherdetails.2.Contact local SUN service or local staff.It is necessary to reconfigure the MetaDB.Provide the error message and exact information about your

    system.

    Error description: Solstice Disk Suite Object (MetaDB Replica) malfunction onOMP. RC could will stop working soon.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    14/54

    14 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    2.6 Threshold Crossed (505)

    Error ID: 505

    MOC: DATAUNIT

    Version: n.a.

    Error information: processingErrorAlarm

    gsmSystem ResourcesOverload

    Threshold crossed

    major

    (o)

    (o)

    (o)

    Immediate defenseaction:

    Do not write on this Data Unit anymore, until related alarmceases.

    Proposed repair ac-tions:

    1.) Perform fault clearance task T-15 Checking available diskspace to collect information.2.) Free some space on the involved data unit (for example de-lete old files) or expand the quota assigned to the involveddata unit (for example adding a new disk to the system), usinginformation collected from previous step.

    Error description: The involved data unit of type equal to ufs has crossed the re-lated threshold.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    15/54

    A50023-X4005-A2-4-7619 15

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    2.7 OMT-OMP Communication Failure (OMT) (506)

    Error ID: 506

    MOC: OMT

    Version: n.a.

    Error information: communicationsAlarm

    gsmLinkFailure

    OMT-OMP communication failure(OMT)

    critical

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    1. Check the network cable of the OMT:Are the network cable plugs inserted correctly into the socketsat both ends?2. Check the network connection to OMT from an UNIX shellin the primary OMP with the followingcommand:ping

    If the network connection is OK, the OMT will acknowledge.3. Check whether OMT is shutdown.If there is still no connection between OMT and OMP contactyour local staff.

    Error description: A communication failure is detected on connection with theOMT.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    16/54

    16 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    2.8 Disconnected BSS (507)

    Error ID: 507

    MOC: OLINK

    Version: n.a.

    Error information: communicationsAlarm

    gsmLinkFailure

    Disconnected BSS

    critical

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    1.) Check whether there is only one, several or all BSS resp.BSC concerned.2.) Perform fault clearance tasks T-26 Checking X.25 configu-ration, T-27 Checking X.25 link status, T-28 Tracing an X.25link, and T-32 Checking status of PCM card or T-33 Checkingstatus of HSI ports.3.) Check plugs and HSI or PCM card on the OMP using thecorresponding manuals.

    4.) Check the following processes: osinetd, osimcsd,em_cmip, x25netd5.) Check failed BSC status from LMT.

    Error description: The BSS is disconnected.There are three possibilities where the connection betweenBSS and OMP can be disturbed. This depends on how theBSS is connected to the OMP:- Direct link between OMP and BSS using HSI card (A)- WAN link between OMP and BSS using HSI card- PCM (nailed-up) link: connection from OMP to MSC usingSprite card (B)

    - PCM (nailed-up) link: connection from MSC to BSS (C)

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    17/54

    A50023-X4005-A2-4-7619 17

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    2.9 1 O-Link Down (508)

    Error ID: 508

    MOC: OLINK

    Version: n.a.

    Error information: communicationsAlarm

    gsmLost Redundancy

    1 O-link down

    major

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    1.) Check physical connection.2.) If available check the Sprite card and Sprite port.3.) Perform fault clearance task T-26 Checking X.25 configu-ration, T-27 Checking X.25 link status, T-28 Tracing an X.25link.4.) Check osinetd process.5.) Check ftcserver.luc process.6.) Check failed BSC status from LMT.

    Error description: The Olink redundancy is lost. The specified Olink is discon-nected.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    18/54

    18 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    2.10 LAN Card Failure (509)

    Error ID: 509

    MOC: OMP

    Version: n.a.

    Error information: communicationsAlarm

    gsmEquipmentFailure

    LAN Card Failure

    major

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    Check network connections of the OMP:Are the network cable plugs inserted correctly into the socketsat both ends?If the plugs are inserted correctly this alarm means that onelan card is faulted. Then contact your local staff providing theerror message and exact information about your OMP.If the plugs aren't inserted correctly, plug them in. Note that forthis version of RC the emitted alarm will not be cleared.

    Error description: On Extended Redundant OMP one lan card (or network con-nection) is faulted.OMP switched to redundant lan card and emitted this alarm toindicate this situation.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    19/54

    A50023-X4005-A2-4-7619 19

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    2.11 Possible Fault on a HSI Communication Board (510)

    Error ID: 510

    MOC: HSI_CARD

    Version: n.a.

    Error information: communicationsAlarm

    gsmEquipmentFailure

    Possible Fault on a HSI Communi-cation Board

    critical

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    1.) Check plugs and HSI card on the OMP using the corre-sponding manuals.2.) Check the following processes: osinetd, osimcsd,em_cmip, x25netd3.) Perform fault clearance tasks T-26 Checking X.25 configu-ration, T-27 Checking X.25 link status, T-28 Tracing an X.25link, and T-33 Checking status of HSI ports.

    4.) Contact your local staff to check the cables and the HSIcard itself using the corresponding manual. Provide the alarmnumber andmessage and exact information from the previousstep.

    Error description: All OLinks which are connected to the same HSI card becamefaulty.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    20/54

    20 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    2.12 Possible Fault on a PCM Communication Board (511)

    Error ID: 511

    MOC: SPRITE_CARD

    Version: n.a.

    Error information: communicationsAlarm

    gsmEquipmentFailure

    Possible Fault on a PCM Commu-nication Board

    critical

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    1.) Check plugs and PCM Card on the OMP using the corre-sponding manuals.2.) Check the following processes: osinetd, osimcsd,em_cmip, x25netd3.) Perform fault clearance tasks T-26 Checking X.25 configu-ration, T-27 Checking X.25 link status, T-28 Tracing an X.25link, and T-33 Checking status of HSI ports.

    4.) Contact your local staff to check the cables and the Spritecard itself using the corresponding manual. Provide the alarmnumber and message andexact information from the previousstep.

    Error description: All OLinks which are connected to the same PCM card be-came faulty.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    21/54

    A50023-X4005-A2-4-7619 21

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    2.13 PCM Switch Failure (512)

    Error ID: 512

    MOC: OMP

    Version: n.a.

    Error information: communicationsAlarm

    gsmEquipmentFailure

    PCM Switch failure

    critical

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    Contact your local staff to check the cables plugged in correct-ly: From OMP to PCM Switch and from PCM Switch to the net-work using the correspondent manual.

    Error description: PCM Switch failure. The connection from OMP to PCM Switch(so called Selector Unit) or from PCM Switch to the network isdisturbed.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    22/54

    22 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    2.14 External Alarm Device Failure (513)

    Error ID: 513

    MOC: EXT_ALARM_DEVICE

    Version: n.a.

    Error information: equipmentAlarm

    gsmEquipmentFailure

    External Alarm Device Failure

    major

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    1. Check the components of the alarm device panel (e.g.lamp(s), siren) using the corresponding manual.2. Check the cables whether they are plugged in correctly andinto the correct ports.

    Error description: A fault occurred on External Alarm Device Panel.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    23/54

    A50023-X4005-A2-4-7619 23

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    2.15 Log Instance Reached Warning Threshold (514)

    Error ID: 514

    MOC: RC_LOG

    Version: n.a.

    Error information: processingErrorAlarm

    Storage Capacity Problem

    Log instance reached warningthreshold

    warning

    triggeredThreshold:"SbsOim":sb-sOimCapacityAlarmThresholdobservedValue: integer (an addi-tional capacity alarm threshold ex-ceeded)

    attributeId: "SbsOim":sbsOimMax-LogSizeMegaByteattributeValue: integer (max logsize of the log instance expressedin MegaByte)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    1.) Increase the size (maxLogSize parameter) of the alarmedlog instance.2.) Increase the additional threshold value of the alarmed loginstance.

    Error description: An additional capacity threshold has been reached or exceed-edby the log instance.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    24/54

    24 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    2.16 Log Instance Reached Minor Threshold (515)

    Error ID: 515

    MOC: RC_LOG

    Version: n.a.

    Error information: processingErrorAlarm

    Storage Capacity Problem

    Log instance reached minor thres-hold

    minor

    triggeredThreshold:"SbsOim":sb-sOimCapacityAlarmThresholdobservedValue: integer (mi-norThreshold or capacity alarmthreshold exceeded)

    attributeId: "SbsOim":sbsOimMax-LogSizeMegaByteattributeValue: integer (max logsize of the log instance expressedin MegaByte)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    1.) Increase the size (maxLogSize parameter) of the alarmedlog instance.2.) Increase the minor threshold value of the alarmed log in-stance.

    Error description: A minor capacity threshold has been reached or exceeded bythe log instance named.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    25/54

    A50023-X4005-A2-4-7619 25

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    2.17 Log Instance Reached Major Threshold (516)

    Error ID: 516

    MOC: RC_LOG

    Version: n.a.

    Error information: processingErrorAlarm

    Storage Capacity Problem

    Log instance reached majorthresh-old

    major

    triggeredThreshold:"SbsOim":sb-sOimCapacityAlarmThresholdobservedValue: integer (ma-jorThreshold or capacity alarmthreshold exceeded)

    attributeId: "SbsOim":sbsOimMax-LogSizeMegaByteattributeValue: integer (max logsize of the log instance expressedin MegaByte)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    1.) Increase the size (maxLogSize parameter) of the alarmedlog instance.2.) Increase the major threshold value of the alarmed log in-stance.

    Error description: A major capacity threshold has been reached or exceeded bythe log instance named.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    26/54

    26 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    2.18 Log Instance Reached Critical Threshold (517)

    Error ID: 517

    MOC: RC_LOG

    Version: n.a.

    Error information: processingErrorAlarm

    Storage Capacity Problem

    Log instance reached criticalthreshold

    critical

    triggeredThreshold:"SbsOim":sb-sOimCapacityAlarmThresholdobservedValue: integer (criticalTh-reshold or capacity alarm thresholdexceeded)

    attributeId: "SbsOim":sbsOimMax-LogSizeMegaByteattributeValue: integer (max logsize of the log instance expressedin MegaByte)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    1.) Increase the size (maxLogSize parameter) of the alarmedlog instance.2.) Increase the critical threshold value of the alarmed log in-stance.3.) If the log full condition has been reached set the logFullAc-tion to wrap for going on writing log records by dropping theoldest ones.

    Error description: A critical capacity threshold has been reached/exceeded bythe log instance or a log full condition has occurred.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    27/54

    A50023-X4005-A2-4-7619 27

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    2.19 The Agent Has Hit Configured Threshold Level (518)

    Error ID: 518

    MOC: RC

    Version: n.a.

    Error information: processingErrorAlarm

    Threshold Crossed

    The agent has hit configuredthreshold level

    minor

    thresholdLevel: integer

    (o)

    The agent has hit certain thresholdlevel

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    If critical threshold was crossed, then the operator has threepossibilities:

    1. Turn on automatic overload (if it was not activated yet), thenthe link to the overloaded agent will be automatically locked af-ter the critical threshold was crossed (Alternative 1)

    2. Turn off automatic overload handling (if it was not deactivat-ed yet), then he has the possibility to use (Alternative 2), butbe aware, the system can be really overloaded.

    3. Re-configure the overload parameters (Alternative 3), butbe aware, because the system can be really overloaded.

    Error description: An agent (BSS or RNS) has crossed the pre-configuredthreshold level of events-per-agent.The overload handling is implemented in the MPA (MessageProtocol Adapter) and it offers 4 threshold levels (warning, mi-

    nor, major, critical - selectable during installation or from main-tenance terminal) for check the overload situation on the linksor on the MPA itself. In overload situation one alarm is emittedwith severity for the corresponding thresholds level.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    28/54

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    29/54

    A50023-X4005-A2-4-7619 29

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    2.21 B-Link Corba Disconnected (520)

    Error ID: 520

    MOC: ITFB

    Version: n.a.

    Error information: communicationsAlarm

    Link Failure

    B-link Corba disconnected

    critical

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    Check Network connection.

    Error description: n.a.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    30/54

    30 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    2.22 R-Link CMISE Disconnected (521)

    Error ID: 521

    MOC: ITFR

    Version: n.a.

    Error information: communicationsAlarm

    gsmEquipmentFailure

    R-link CMISE disconnected

    critical

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    Check network connections of the OMP:Are the network cable plugs inserted correctly into the socketsat both ends?If not, plug them in; the network connection will establish itselfwithin a few seconds.If the plugs are inserted correctly or network connectiondoesn't establish then contact your local staff providing the er-ror message and exact information about your OMP.

    Error description: OMP has no access to the LAN ( lan card(s) or network con-nection(s) are faulted).This alarm will only appear on the OMT running on the OMP.The following scenarios can be the reason for this alarm:- complete RNC outage- restart of the RNC- FE problems on RNC- LAN problems

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    31/54

    A50023-X4005-A2-4-7619 31

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    2.23 SubMirror Resyncing (522)

    Error ID: 522

    MOC: DATAUNIT

    Version: n.a.

    Error information: equipmentAlarm

    gsmDiskProblem

    SubMirror Resyncing

    major

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    No Action.

    Error description: Solstice DiskSuite Submirror is resyncing, i.e. there are datatransferred from onepart of a mirror to theother, normally afterreplacing a faulty disk. The duration of resyncing depends onthe disk capacity and the amount of stored data. It can takemore than one hour.Working with the Radio Commander is not affected.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    32/54

    32 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    2.24 Network Unavailable (523)

    Error ID: 523

    MOC: OMP

    Version: n.a.

    Error information: communicationsAlarm

    gsmEquipmentFailure

    Network unavailable

    critical

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    1.) Check network connections of the OMP:2.) Are the network cable plugs inserted correctly into thesockets at both ends? If not, plug them in; the network connec-tion will establish itself within a few seconds.3.) If the plugs are inserted correctly or network connectiondoesn't establish then contact your local staff providing the er-ror message and exact information about your OMP.

    Error description: OMP has no access to the LAN ( lan card(s) or network con-nection(s) are faulted).This alarm will only appear on the OMT running on the OMP.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    33/54

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    34/54

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    35/54

    A50023-X4005-A2-4-7619 35

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    2.27 Alignment Procedure Failed (527)

    Error ID: 527

    MOC: sbsTrauEquipment, sbsBtsePico, sbsBtseP, sbsBtseEM, sb-sBtsE, sbs3gManagedElement, nbManagedElement,nb2ManagedElement (all alarms generate locally at RadioCommander)

    Version: n.a.

    Error information: processingErrorAlarm

    Software Program Abnormally

    Alignment Procedure Failed

    warning

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    Try re-aligning using commands.

    Error description: An error occurred during an alignment phase

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    36/54

    36 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    2.28 OMP-OMP Communication failure (OMP) (528)

    Error ID: 528

    MOC: OMP

    Version: n.a.

    Error information: communicationsAlarm

    gsmLinkFailure

    OMP-OMP Communication failure(OMP)

    critical

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    1. Check the network cable of the OMP:Are the network cable plugs inserted correctly into the socketsat both ends?2. Check the network connection to OMP from an UNIX shellin the primary OMP with the following command:ping If the network connection is OK, the OMP will acknowledge.

    3. Check whether OMP is shutdown. If there is still no connec-tion between primary OMP and another OMP contact your lo-cal staff.

    Error description: A communication failure is detected on connection with otherOMP.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    37/54

    A50023-X4005-A2-4-7619 37

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    2.29 NetViewer Server indeterminate notification (529)

    Error ID: 529

    MOC: OimMicrowavesEquipment

    Version: n.a.

    Error information: equipmentAlarm

    Equipment Failure

    NetViewer Server indeterminatenotification

    indeterminate

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    Open NetViewer to get more details on the NetViewer equip-ment state/status.

    Error description: An equiment notification of indeterminate severity received.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    38/54

    38 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    2.30 NetViewer Server critical notification (530)

    Error ID: 530

    MOC: OimMicrowavesEquipment

    Version: n.a.

    Error information: equipmentAlarm

    Equipment Failure

    NetViewer Server critical notifica-tion

    critical

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    Open NetViewer to get more details on the NetViewer equip-ment state/status.

    Error description: An equiment notification of critical severity received.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    39/54

    A50023-X4005-A2-4-7619 39

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    2.31 NetViewer Server major notification (531)

    Error ID: 531

    MOC: OimMicrowavesEquipment

    Version: n.a.

    Error information: equipmentAlarm

    Equipment Failure

    NetViewer Server major notification

    major

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    Open NetViewer to get more details on the NetViewer equip-ment state/status.

    Error description: An equiment notification of major severity received.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    40/54

    40 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    2.32 NetViewer Server minor notification (532)

    Error ID: 532

    MOC: OimMicrowavesEquipment

    Version: n.a.

    Error information: equipmentAlarm

    Equipment Failure

    NetViewer Server minor notifica-tion)

    minor

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    Open NetViewer to get more details on the NetViewer equip-ment state/status.

    Error description: An equiment notification of minor severity received.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    41/54

    A50023-X4005-A2-4-7619 41

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    2.33 NetViewer Server warning notification (533)

    Error ID: 533

    MOC: OimMicrowavesEquipment

    Version: n.a.

    Error information: equipmentAlarm

    Equipment Failure

    NetViewer Server warning notifica-tion

    warning

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    Open NetViewer to get more details on the NetViewer equip-ment state/status.

    Error description: An equiment notification of warning severity received.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    42/54

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    43/54

    A50023-X4005-A2-4-7619 43

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    2.35 NetViewer Connection Down (535)

    Error ID: 535

    MOC: OimNetviewerLink

    Version: n.a.

    Error information: communicationsAlarm

    LinkFailure

    NetViewer Connection Down

    critical

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    1.) Check network connections of the OMP:Are the network cable plugs inserted correctly into the socketsat both ends?2.) If theplugs are inserted correctly this alarm means that onelan card is faulted. Then contact your local staff providing theerror message and exact information about your OMP. If theplugs aren't inserted correctly, plug them in. Note that for thisversion of RC the emitted alarm will not be cleared.

    Error description: The Netviewer is disconnected.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    44/54

    44 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    2.36 Local SMLC state file does not exist! (536)

    Error ID: 536

    MOC: OimSmlc

    Version: n.a.

    Error information: communicationsAlarm

    LinkFailure

    Local SMLC state file does not ex-ist

    critical

    (o)

    (o)

    (o)

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    1. Check Network connection between RC and SMLC serverAre the cable plugs inserted correctly into the sockets at bothends?2. Check the FTP script, which is responsible for the file trans-fer.

    Error description: The RC can not find/open the local SMLC state file.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    45/54

    A50023-X4005-A2-4-7619 45

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    3 Notifications

    3.1 serviceResponse (RC_LOG)

    3.2 serviceResponse (SbsOcm:session)

    Error ID: n.a.

    MOC: RC_LOG

    Version: n.a.

    Error information: serviceReport

    (m) serviceResponse

    (o) the following:

    SeeLogs on security event log in-stance

    delete log records

    (m) "DateAndTime"

    (m) "RC user login name"

    (m) "Hostname of OMT"

    (m) "Number of OMT session"

    (m) "Display of OMT session"

    (o) "The affected RC user login

    name"

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    n.a.

    Error description: A security audit trail report as described in X.740 is given.

    Error ID: n.a.

    MOC: "SbsOcm":session

    Version: n.a.

    Error information: serviceReport

    (m) serviceResponse

    (o) the following:

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    46/54

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    47/54

    A50023-X4005-A2-4-7619 47

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    3.4 serviceFailure (SbsOcm:session)

    Error information: serviceReport

    (m) serviceFailure

    (o) the following:

    SeeLogs on security event log in-stance

    delete log records

    (m) "DateAndTime"

    (m) "RC user login name"

    (m) "Hostname of OMT"

    (m) "Number of OMT session"

    (m) "Display of OMT session" (o) "The affected RC user login

    name"

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    n.a.

    Error description: A security audit trail report as described in X.740 is given.

    Error ID: n.a.

    MOC: "SbsOcm":session

    Version: n.a.

    Error information: serviceReport

    (m) serviceFailure

    (o) the following:

    (m) create User Profile

    delete User Profile

    set User Profile

    import Security Data

    export Security Data

    import Password Dictionary

    export Password Dictionary

    delete Password Dictionary

    abort User Sessionchange Own Password

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    48/54

    48 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    change System Password

    abort Unix Session

    RC login

    RC logoutSeeLogs on security event log in-stance

    delete log records

    reset Failed Login Counter

    set Global Settings

    lock Display

    unlock Display

    create Authorization Profile

    delete Authorization Profile

    set Authorization Profile

    create Subprofile

    delete Subprofile

    set Subprofile

    (m) "DateAndTime"

    (m) "RC user login name"

    (m) "Hostname of OMT"

    (m) "Number of OMT session"

    (m) "Display of OMT session"

    (o) "The affected RC user loginname"

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    n.a.

    Error description: A security audit trail report as described in X.740 is given.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    49/54

    A50023-X4005-A2-4-7619 49

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    3.5 unauthorizedAccessAttempt

    Error ID: n.a.

    MOC: "SbsOim":sbsOimAuthProfile

    Version: n.a.

    Error information: securityServiceOrMechanismVio-lation

    (m) unauthorizedAccessAttempt

    (m) warning

    (m) RC

    (m) "RC user login name"

    (m) RC (o) the following:

    (m) unauthorized entered CLIcommand

    (m) "DateAndTime"

    (m) "RC user login name"

    (m) "Hostname of OMT"

    (m) "Number of OMT session"

    (m) "Display of OMT session"

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    n.a.

    Error description: A security service or mechanism violation as described inX.736 occurred.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    50/54

    50 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    3.6 sbsOimFileTransferControl

    Error ID: n.a.

    MOC: "SbsOim":sbsOimFileTransferControl

    Version: n.a.

    Error information: "SbsOim":SbsUploadInfoType. Itdescribes the event type (startUp-load, endUpload, endConversion)which notification is related to.

    The transfer identifier assigned byRC to each upload procedure.

    The path name of the file uploaded.

    The result of the upload (success,aborted, failed, none).

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    n.a.

    Error description: This notification is used to inform the begin and the end of anupload regarding a file of measures.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    51/54

    A50023-X4005-A2-4-7619 51

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    3.7 outOfHoursActivity

    Error ID: n.a.

    MOC: "SbsOim":sbsOimUserProfile

    Version: n.a.

    Error information: timeDomainViolation

    (m) outOfHoursActivity

    (m) warning

    (m) RC

    (m) "RC user login name"

    (m) RC

    (o) the following:

    (m)command not in allowed time re-strictions

    (m) "DateAndTime"

    (m) "RC user login name"

    (m) "Hostname of OMT"

    (m) "Number of OMT session"

    (m) "Display of OMT session"

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    n.a.

    Error description: A security service or mechanism violation as described inX.736 occurred.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    52/54

    52 A50023-X4005-A2-4-7619

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    3.8 authenticationFailure

    Error ID: n.a.

    MOC: "SbsOcm":session

    Version: n.a.

    Error information: securityServiceOrMechanismVio-lation

    (m) authenticationFailure

    (m) warning

    (m) RC

    (m) "RC user login name"

    (m) RC (o) the following:

    (m) RC login failed

    RC login failed: OMT unknown

    RC login failed: OMT has inappro-priate type

    RC login failed: OMT not unlocked

    RC login failed: Display host un-known

    RC login failed: Display host not

    unlockedRC login failed: Wrong password

    RC login failed: Password expired

    RC login failed: Out of allowed timeperiod

    RC login failed: Invalid Unix userfor RC operator

    RC login failed: RC operator ac-count blocked

    (m) "DateAndTime"

    (m) "RC user login name"

    (m) "Hostname of OMT"

    (m) "Number of OMT session"

    (m) "Display of OMT session"

    Immediate defenseaction:

    n.a.

    Proposed repair ac-tions:

    n.a.

    Error description: A security service or mechanism violation as described inX.736 occurred.

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    53/54

    A50023-X4005-A2-4-7619 53

    OutputsRadio Commander BR 7.0 / UMR 3.0

    Output Manual OML:Non Standard Maintenance

    4 Appendix

    4.1 Specific Problems for the Alarm List

    Error ID Specific Problems

    502 Disk Generic HW Error

    503 Mirror/SubMirror Failure

    504 MetaDb Failure

    505 Threshold crossed

    506 OMT-OMP communication failure (OMT)

    507 Disconnected BSS

    508 1 O-Link down

    509 LAN Card Failure

    510 Possible Fault on a HSI Communication Board

    511 Possible Fault on a PCM Communication Board

    512 PCM Switch failure

    513 External Alarm Device Failure

    515 Log instance reached minor threshold

    516 Log instance reached major threshold

    517 Log instance reached critical threshold

    518 The agent has hit configured threshold level

    519 The MPA has hit configured threshold level

    520 B-link Corba disconnected

    521 R-link CMISE disconnected

    522 Sub Mirror Resyncing

    523 Network unavailable

    524 The nbManagedElementId received doesn't match the NodeB configura-tion within RC

    525 SubMirror failure

    528 OMP-OMP Communication failure (OMP)

    529 NetViewer Server indeterminate notification

    530 NetViewer Server critical notification

    531 NetViewer Server major notification

    532 NetViewer Server minor notification

    535 NetViewer Connection Down

    Tab. 4.1 Specific Problems for the Alarm List in the GUI (without warnings)

  • 8/12/2019 Rc_obr7.0 Output Manual Oml

    54/54

    Output Manual OML:Non Standard Maintenance OutputsRadio Commander BR 7.0 / UMR 3.0

    536 Local SMLC state file does not exist!

    Error ID Specific Problems

    Tab. 4.1 Specific Problems for the Alarm List in the GUI (without warnings)