QZHR Fan Coil Fläkt Woods 9324 GB 2014.04 1 Specifications are subject of alteration without further notice. QZHR Fan Coil Functions • Horizontal installation • Cooling (2 pipes) • Heating (4 pipes or electrical heater) • Available pressure up to 160 Pa Following many years of experience in the field of heating and air conditioning, Fläkt Woods has developed a range of high pressure fan coils for concealed installation and connection to a duct system. They supply a consistent air flow with static pressure up to 160 Pa. The fan assembly has 4 speeds, 3 of them are connected. A range of 7 models to fit most conditions is available with the combination of either 3, 4 or 6 rows coils and 2 or 4 pipes configurations with additional heat exchanger. Quick Selection Cooling Entering air temperature: 27 °C dry bulb - 19 °C wet bulb. Entering water temperature: 7 °C , Δt 5 °C Size Speed Air flow m3/h Cooling kW Available pressure Pa Sound pr. L p dB(A) 14 MAX 140 6.11 75 55 24 MAX 1825 8.44 80 55 34 MAX 2440 11.18 70 60 44 MAX 3020 14.23 67 61 54 MAX 3850 18.52 70 63 64 MAX 4800 24.19 150 68 74 MAX 7100 33.09 150 72 Product Facts • 5 sizes from 13 to 76 (Q = 790 - 7435 m3/h & P = 4.28 - 40.83 kW). • 2-pipe system - 3, 4 or 6 rows coil. • 4-pipe system - 1 or 2 rows additional coil. • Centrifugal fans. • 3 connected speeds and 4 speeds available. • Easy to install and maintain. • Compliant with ERP 2013 Product code example Cassette unit QZHR-13-2-2-1
16

QZHR Fan Coil

Feb 14, 2017

Download

Documents

lamthien
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: QZHR Fan Coil

QZHR Fan Coil

Fläkt Woods 9324 GB 2014.04 1 Specifications are subject of alteration without further notice.

QZHR Fan Coil

Functions

• Horizontal installation• Cooling (2 pipes)• Heating (4 pipes or electrical

heater)• Available pressure up to 160

Pa

Following many years of experience in the field of heating and airconditioning, Fläkt Woods has developed a range of high pressure fan coilsfor concealed installation and connection to a duct system. They supply aconsistent air flow with static pressure up to 160 Pa. The fan assembly has 4speeds, 3 of them are connected. A range of 7 models to fit most conditions isavailable with the combination of either 3, 4 or 6 rows coils and 2 or 4 pipesconfigurations with additional heat exchanger.

Quick SelectionCoolingEntering air temperature: 27 °C dry bulb - 19 °C wet bulb.Entering water temperature: 7 °C , Δt 5 °C

Size Speed Air flow m3/h Cooling kW Availablepressure Pa

Sound pr. L p dB(A)

14 MAX 140 6.11 75 5524 MAX 1825 8.44 80 5534 MAX 2440 11.18 70 6044 MAX 3020 14.23 67 6154 MAX 3850 18.52 70 6364 MAX 4800 24.19 150 6874 MAX 7100 33.09 150 72

Product Facts

• 5 sizes from 13 to 76 (Q = 790 -7435 m3/h & P = 4.28 - 40.83 kW).

• 2-pipe system - 3, 4 or 6 rows coil.• 4-pipe system - 1 or 2 rows

additional coil.• Centrifugal fans.• 3 connected speeds and 4 speeds

available.• Easy to install and maintain.• Compliant with ERP 2013

Product code example

Cassette unit QZHR-13-2-2-1

Page 2: QZHR Fan Coil

QZHR Fan Coil

Description

Fläkt Woods 9324 GB 2014.04 2 Specifications are subject of alteration without further notice.

 

 

Casing

It is made from galvanized steel insulated with polyolefin(PO) foam (class M1).

Fan assembly

Consists of quiet centrifugal fans in galvanized steel withtwo impellers and a directly-driven, single-phase fourspeed motor, 230V 50Hz, with capacitor, insulation classB.

Coil

It is manufactured from drawn copper tube and thealuminium fins are mechanically bonded onto the tube byan expansion process.The connections are on the left hand side looking from theair inlet of the unit (see dimensions pages).On request or on site the connections can be moved to theother side.The coil is not suitable for use in corrosive atmosphereor in environments where aluminium may be subject tocorrosion.

Filter

The filter is made of polypropylene cellular fabricregenerating filter. The filter frame of galvanized steel isinserted into special PVC sliding guides fastened to theinternal structure for easy insertion and removal of thefilter.Easy access to the filter for cleaning operation.On request is available a 48 mm synthetic filter, G3,efficiency of 84% Eurovent EU3 or F6 (only size 6 and 7)according to EN779.

Page 3: QZHR Fan Coil

QZHR Fan Coil

QZHR Nominal performances

Fläkt Woods 9324 GB 2014.04 3 Specifications are subject of alteration without further notice.

2-pipe units, sizes 1 to 5 with 4 rows

CoolingEntering air temperature: 27 °C dry bulb - 19 °C wet bulbEntering water temperature: 7 °C , Δt 5 °C

HeatingEntering air temperature: 20 °CEntering water temperature: 50 °CSame air flow as cooling conditions

Model QZHR-14 QZHR-24 QZHR-34 QZHR-44 QZHR-54Speed (E)   1 3 5 1 3 5 1 3 5 1 3 5 1 3 5Air flow (E) m3/h 790 1125 1410 840 1410 1825 1710 2075 2440 2070 2580 3020 2740 3280 3850Available pressure (E) Pa 25 50 75 15 50 80 30 50 70 35 50 67 35 50 70Cooling total emission(E) kW 428 536 611 516 724 844 906 1018 1118 1133 1298 1423 1504 1681 1852Cooling sensibleemission (E)

kW 336 441 522 383 571 690 702 810 912 869 1025 1149 1171 1342 1513

Heating (E) kW 580 755 886 658 979 1178 1204 1387 1554 1492 1755 1964 1939 2212 2479Dp Cooling (E) kPa 51 76 96 69 127 168 160 198 234 139 177 209 133 162 193Dp Heating (E) kPa 41 62 79 56 103 136 131 162 191 112 145 170 108 132 157Fan (E) W 115 154 191 170 230 285 350 420 470 445 550 630 500 617 760Sound power level outlet(E)

dB(A) 51 59 64 50 62 67 61 65 69 63 68 70 66 70 73

Sound power level inlet +radiated (E)

dB(A) 52 60 65 51 63 68 62 66 70 64 69 71 67 71 74

Sound pressure leveloutlet (*)

dB(A) 42 50 55 41 53 58 52 56 60 54 59 61 57 61 64

Sound pressure levelinlet + radiated (*)

dB(A) 43 51 56 42 54 59 53 57 61 55 60 62 58 62 65

4-pipe units, size 1 to 5 with 4 rows

CoolingEntering air temperature: 27 °C dry bulb - 19 °C wet bulbEntering water temperature: 7 °C , Δt 5 °C

HeatingEntering air temperature: 20 °CEntering water temperature: 70 °C , Δt 10 °C

MODEL QZHR-14+1 QZHR-24+1 QZHR-34+1 QZHR-44+1 QZHR-44+1Speed (E)   1 3 5 1 3 5 1 3 5 1 3 5 1 3 5Air flow (E) m3/h 770 1090 1350 840 1390 1775 1680 2045 2390 2055 2545 2960 2700 3245 3800Available pressure (E) Pa 25 50 75 15 50 80 30 50 70 35 50 67 35 50 70Cooling total emission (E) kW 421 526 597 516 718 830 895 1009 1104 1129 1288 1408 1424 1592 1748Cooling sensibleemission (E)

kW 329 431 506 383 565 676 693 802 897 865 1015 1133 1111 1274 1431

Heating (E) kW 396 487 547 463 628 716 762 847 920 983 1107 1200 1267 1400 1528Dp Cooling (E) kPa 49 73 92 69 125 163 157 194 229 138 174 205 120 147 174Dp Heating (E) kPa 117 170 210 145 252 319 159 193 223 276 341 395 260 311 363Fan (E) W 115 155 185 170 225 275 345 415 460 440 540 615 495 610 750Sound power level outlet(E)

dB(A) 51 59 64 50 62 67 61 65 69 63 68 70 66 70 73

Sound power level inlet +radiated (E)

dB(A) 52 60 65 51 63 68 62 66 70 64 69 71 67 71 74

Sound pressure leveloutlet (*)

dB(A) 42 50 55 41 53 58 52 56 60 54 59 61 57 61 64

Sound pressure levelinlet + radiated (*)

dB(A) 43 51 56 42 54 59 53 57 61 55 60 62 58 62 65

Page 4: QZHR Fan Coil

QZHR Fan Coil

QZHR Nominal performances

Fläkt Woods 9324 GB 2014.04 4 Specifications are subject of alteration without further notice.

2 pipe units, size 6 to 7 with 4 and 6 rows coil

CoolingEntering air temperature: 27 °C dry bulb - 19 °C wet bulbEntering water temperature: 7 °C , Δt 5 °C

HeatingEntering air temperature: 20 °CEntering water temperature: 50 °CSame air flow as cooling conditionsAvailable pressure 150 Pa

MODEL QZHR-64 QZHR-66 QZHR-74 QZHR-76Speed   1 2 3 1 2 3 1 2 3 1 2 3Air flow m3/h 1880 3385 4800 1860 3350 4740 3925 5070 7100 3920 5050 7030Cooling total emission kW 1299 1951 2419 1492 2335 2959 2306 2709 3309 2759 3291 4083Cooling sensibleemission

kW 945 1494 1928 104 1696 2222 157 2122 2699 1999 244 3137

Dp Cooling kPa 74 153 226 92 205 314 144 193 276 183 251 371Heating kW 2086 3352 436 2258 3753 4977 3934 4785 6114 442 5445 7064Dp Heating kPa 39 91 147 44 110 182 85 121 188 97 142 226Fan W 574 778 1304 565 759 1314 1518 1758 2460 1499 1737 2410Sound power Lw dB(A) 63 71 77 63 71 77 71 75 81 71 75 81Sound pressure (*) dB(A) 54 62 68 54 62 68 62 66 72 62 66 72

2 pipe units, size 6 to 7 with 4 and 6 rows coil

CoolingEntering air temperature: 27 °C dry bulb - 19 °C wet bulbEntering water temperature: 7 °C , Δt 5 °C

HeatingEntering air temperature: 20 °CEntering water temperature: 70 °C E.W.T. 60 °C L.W.T.Available pressure 150 Pa

MODEL QZHR-64+2 QZHR-66+2 QZHR-74+2 QZHR-76+2Speed   1 2 3 1 2 3 1 2 3 1 2 3Air flow m3/h 1860 3330 4680 1850 3300 4600 3920 5040 6980 3910 5000 6900Cooling total emission kW 1289 1931 2385 1487 2309 2898 2303 2698 3274 2755 3267 4036Cooling sensibleemission

kW 937 1477 1895 1036 1675 2171 1755 2112 2666 1995 242 3094

Dp Cooling kPa 73 150 220 91 201 303 144 191 271 183 248 363Heating kW 1981 2978 3713 1973 2959 3676 355 4188 5131 3541 4168 5095Dp Heating kPa 119 249 370 118 246 363 238 320 461 237 317 455Fan W 565 750 1327 775 1046 1455 1499 1727 2376 1468 1687 2325Sound power Lw dB(A) 63 71 77 63 71 77 71 75 81 71 75 81Sound pressure (*) dB(A) 54 62 68 54 62 68 62 66 72 62 66 72

(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a100m 3 room and a reverberation time of 0.5 sec.

Operation limits, designations

Highest water inlet temperature + 80 °CLowest water inlet temperature + 5 °CHighest working pressure 8 bar

Highest air inlet temperature + 40 °CLowest air inlet temperature + 6 °CHighest air outlet temperature + 50 °CSuitable relative humidity 15-75%

Supply Single phase 230V 50Hz

Motor electrical data (max. absorption)

Model QZHR-1 QZHR-2 QZHR-3 QZHR-4 QZHR-5 QZHR-6 QZHR-7230/1, W 240 412 523 765 885 1437 281750Hz? A 1.09 1.91 2.45 3.62 4.01 6.38 12.4

Page 5: QZHR Fan Coil

QZHR Fan Coil

Water pressure drop

Fläkt Woods 9324 GB 2014.04 5 Specifications are subject of alteration without further notice.

2-pipe unit 

 

 

10001

50

10

5

2000 3000 4000 5000 10000

QZHR 64

QZHR 74

QZHR 66

QZHR 76646464747474

666666 767676

 

The water pressure drop figures refer to a mean watertemperature of 10 °C for different temperature, multiplythe pressure drop figures by the correction factors K.

 °C K20 °C 0.9430 °C 0.9040 °C 0.8650 °C 0.8260 °C 0.7870 °C 0.7480 °C 0.70

4-pipe unit, heating battery pressure drop 

 

 

10001

50

10

5

2000 3000 4000 5000 10000

QZHR 62

QZHR 72626262 727272

 

The water pressure drop figures refer to a mean watertemperature of 65 °C for different temperature, multiplythe pressure drop figures by the correction factors K.

 °C K40 °C 1.1450 °C 1.0860 °C 1.0270 °C 0.9680 °C 0.90

Page 6: QZHR Fan Coil

QZHR Fan Coil

Dimensions, weight, water content

Fläkt Woods 9324 GB 2014.04 6 Specifications are subject of alteration without further notice.

 

B39 39

Ø 16236

209

243

169209

169

25 B

DAGAA EE E

25

22

40

4026

50

26

243

103

103

25 B

N HL DD C C D D

LH M NM

25

F.A.F.A.

FAN SIDE(OUTLET)

FAN SIDE(OUTLET)

FILTER SIDE(INLET)

FILTER SIDE(INLET)

F.A. F.A.

F

4 3 2 1 4321

 

  Standard left connections, right connections (on request)

Dimensions

  Dimensions (mm) CoilModel   2 pipes 4 pipes

  A B C D E F G H L M N 1 IN 2 OUT 3 IN 4 OUTQZHR-1 1133 698 310 255 991 620 1185 54 245 50 249 3/4" 3/4" 3/4" 3/4"QZHR-2 1133 698 310 255 991 620 1185 54 245 50 249 1" 1" 3/4" 3/4"QZHR-3 1133 698 360 305 991 620 1185 54 295 50 299 1" 1" 3/4" 3/4"QZHR-4 1445 853 360 293 1302 775 1497 58 291 54 295 1 1/4" 1 1/4" 1" 1"QZHR-5 1445 853 435 368 1302 775 1497 58 367 54 370 1 1/4" 1 1/4" 1" 1"QZHR-6 1535 1100 488 421 1393 1022 1587 59 416 55 421 1 1/4" 1 1/4" 1" 1"QZHR-7 1535 1100 588 521 1393 1022 1587 59 516 55 521 1 1/4" 1 1/4" 1" 1"

Page 7: QZHR Fan Coil

QZHR Fan Coil

Dimensions, weight, water content

Fläkt Woods 9324 GB 2014.04 7 Specifications are subject of alteration without further notice.

Weight size 1 to 5

Model Weight unpacked unit (kg) Weight packed unit (kg)  3R 3 + 1R 3 + 2R 4R 4 + 1R 4 + 2R 3R 3 + 1R 3 + 2R 4R 4 + 1R 4 + 2R

QZHR-1 45 48 50 47 50 51 48 51 53 50 53 54QZHR-2 46 50 52 48 51 53 49 53 55 51 54 56QZHR-3 54 58 60 56 60 62 57 61 63 59 63 65QZHR-4 75 80 83 78 83 86 79 84 87 82 87 90QZHR-5 85 90 94 88 94 98 89 94 98 92 98 102

Weight size 6 to 7

  Weight without packaging (kg) Weight with packaging (kg) Water content (l)MODEL 4R 4+2R 6R 6+2R 4R 4+2R 6R 6+2R 4R 6R 2RQZHR-6 124 134 130 140 127 137 133 143 76 111 41QZHR-7 140 152 148 160 143 155 151 163 97 138 55

Water content size 1 to 5

Model Water content (l)  3R 4R 1R 2R

QZHR-1 2.0 2.6 0.9 1.5QZHR-2 2.9 3.7 1.1 1.8QZHR-3 3.5 4.6 1.4 2.4QZHR-4 4.7 6.0 2.0 3.2QZHR-5 5.7 7.1 2.7 4.1

Water content size 6 to 7

Water content (l)MODEL   4R 6R 2RQZHR-6   76 111 41QZHR-7   97 138 55

Page 8: QZHR Fan Coil

QZHR Fan Coil

Acoustic Data

Fläkt Woods 9324 GB 2014.04 8 Specifications are subject of alteration without further notice.

Often sound levels are the key influencing factor in the selection of equipment. The notion sound power is oftenconfused with the notion sound pressure. The two notions can be defined as follows :

Sound power (Lw) Sound pressure (Lp)

Sound power is the output required producingsound pressure waves. It is not, as such, directlymeasurable.Sound power is established by measuring thesound pressure on the inner surface of a sphereplaced around the source. It is measured andstated in Watts.Sound power is therefore a measurement, whichis not dependent on area or distance, and it isused as a basis for all acoustic data.

This is the alternating pressure produced bywaves from a sound source. It is a measure of thenoise level or noise intensity.Sound pressure is dependent on the averageabsorption factor of the room, distance fromthe sound source, the position of the unit in theroom, the occupation and is therefore not suitablefor calculations of sound propagation or spread.

 

An explanatory example:

The sound power level can be compared with the heating capacity of a boiler. This capacity will remain the sameregardless of the thermal characteristics of the installation.The sound pressure level can be compared with the temperature obtained in a room supplied from the boiler. Obviously,the temperature will vary depending upon the room characteristics and so it is with sound pressure.Therefore, accurate comparisons between competing equipment should always be made, in the case of the boiler, bycomparing boiler capacity and in case of fan coil units by comparing the sound power levels.

Conversion: Sound power level dB(A) => Sound pressure level dB(A) 

Distance from the sound source in meters

Del

iver

y fa

ctor

Soun

d di

ffere

nce

DL

=

Lw -

Lp (

dB )

Room volume (m )3

10

20

50

8

4

2

1

100

7060403020151086543210,5

35

30

25

20

15

10

65

0

500 1000 2000 5000 10000 20000 30000

100

50

200

500

1000

2000

5000

4

5

6 37 2

1Unit fixed to the wall

Unit fixed in a corner

Unit can radiate in all directions

Unit fixed into a ceiling

Free field

factories a = 0. 05 swimming halls

class rooms a = 0. 1 hospital rooms

houses, offices, hotel rooms a = 0. 15 meeting rooms, theatres

reading rooms, television studios a = 0. 25 stores

radio studios a = 0. 4 music rooms

Absorption surface 5m Sabin

a = 0. 03

 

Example

Office 5,25 m x 4,15 m x 2,75 m => Room volume : 60 m 3QZBA-13:sound power level at low speed is 40 dB(A)Absorption factor a : 0.15

Distance from the source : 2 mDirection factor : 2Dt L : 6 dBSound pressure level : Lp = Lw(A) - ∆LLp = 40 - 6 = 34 dB(A)

Page 9: QZHR Fan Coil

QZHR Fan Coil

Practical guidelines

Fläkt Woods 9324 GB 2014.04 9 Specifications are subject of alteration without further notice.

Precautions to be taken before and duringinstallation

• Units are carefully inspected and tested prior todelivery.

• The water system must be carefully designedand balanced if the fan coil system is to performcorrectly.

• The units should be installed in such a wayto allow easy access for maintenance andadjustments.

• It is important that the unit is placed level orslopes slightly towards the condensate drain side.

• Sufficient slope of the drain system shall beassured for a quick condensate removal = 2 %(min. 2 cm/m).

• The inlet water connections for cooling andheating are always the lower of the coilconnection.

• Although units equipped with water controlvalves have been carefully checked at the factory,it is advisable to check the tightness of all pipeconnections on site using a spanner.

• Make sure that the condensate will drain offfreely.

• Do not connect the drain system directly tothe drainpipe of the main drip tray but usethe drainpipe of the auxiliary drip tray for theevacuation of the condensate.

• It is recommended to seal the joint between theunit and the auxiliary drip tray with a sealer.

• The distance between the air intake side and thefloor or wall should be minimum 100 mm.

• Make sure that no shelving or furniture obstructsfree air circulation.

• Dispose of packaging material in accordancewith local requirements.

Electrical connections

• All motors are tested prior to delivery.

• The voltage of the motor is stated on theidentification label of each unit.

• The electrical wiring of the units should be doneby an authorised electrician in accordance withthe local regulations.

• The electrical heating elements must only befactory installed.

• The electrical installation should be of permanenttype and the unit protected by means of fuses inthe power supply from the mains.

• Incorrect field wiring will cause motor damage.

• Always use the same power supply circuit for thefan coil system (fan coil units, thermostats, etc. ..)

• Do not connect more than one fan coil unit to onecommon speed selector switch.

• In master/slave applications, check carefully theequipotentiality of the electrical connections.

Control system

• When the fans are not running, it is stronglyadvisable to ensure that the chilled water supplyto the coils is automatically shut off, to preventcondensation in and on the unit.

• Units equipped with electrical heating elementsmust be connected to a regulation withpermanent ventilation.

Starting-up

• Check that the coils have been cleaned after theinstallation work.

• Check the water system and open the valves forthe water supply.

• Check that the water connections do not leak.

• Open the venting screws and check that there isno air in the coils.

• Equalisation of the pressure drop across thewhole water system is recommended.

• Check that the fan impeller rotates freely and inthe correct direction.

• Run the fan at high, medium and low speed andcheck that no mechanical noise can be heard.

• Check that the unit is well secured and does notvibrate.

• Check the performance of the supervisorysystem.

Maintenance

• Before performing any service or maintenanceoperations, turn OFF the main power supply.

• Inspect the unit at regular intervals.

• The frequency of cleaning the coil and the driptray depend on local conditions.

• The coil should be cleaned on both sides. Use avacuum cleaner with a rubber nozzle.

• Work carefully to avoid damaging the coilsurfaces.

• Check that the drainpipe is clean and notclogged.

• The motor bearings are permanently lubricatedand do not require lubrication.

• The standard filters are of the washable type andshould be cleaned when clogged.

• Check min. once a month the filter – finalpressure drop is recommended up to 25 Pa.

• The frequency of filter cleaning or replacementis dependent on the dust content in the returnair. (our recommendation: Max. 1 month afterstarting-up period and further min. every 3months)

Page 10: QZHR Fan Coil

QZHR Fan Coil

Practical guidelines

Fläkt Woods 9324 GB 2014.04 10 Specifications are subject of alteration without further notice.

WARNING!

• The cooling and heating output of the unit willbe reduced if the unit is running with cloggedfilters.

• Unit mounted electrical heating elements caninfluence the sound level of the units.

• Dirty/clogged filters will increase the sound leveland are harmful to the operation and working-expenses of the units.

• Prolonged operation with a dirty / clogged filtermay lead to deterioration of the motor.

• To avoid breaks caused by ice, please empty thewater circuit when the room temperature goesdown to 0 °C .

Page 11: QZHR Fan Coil

QZHR Fan Coil

Accessories

Fläkt Woods 9324 GB 2014.04 11 Specifications are subject of alteration without further notice.

Electrical heating element 

26

39 C

Ø9Ø

9

26

1699

39

16A

A+38 C25

BB

 

 

 

Model A B C Watt V Product codeQZHR 1 1093 297 300 3000 230 QZAZ-16-12-30QZHR 2 1093 297 300 4500 230 QZAZ-16-22-45QZHR 1 1093 297 300 3000 400 QZAZ-16-14-30QZHR 2 1093 297 300 4500 400 QZAZ-16-24-45QZHR 3 1093 347 300 7500 400 QZAZ-16-34-75QZHR 4 1405 347 300 7500 400 QZAZ-16-44-75QZHR 5 1405 422 300 15000 400 QZAZ-16-54-15

Air inlet/supply spigot plenum 

B

CC

40

40

A

A

 

Model A B C Spigots (Nº) Spigots (Ø) Product codeQZHR 1-2 1133 182 298 3 250 QZAZ-14-10-030QZHR 3 1133 182 348 3 250 QZAZ-14-30-030QZHR 4 1445 300 348 4 250 QZAZ-14-40-030QZHR 5 1445 300 442 4 300 QZAZ-14-50-030QZHR 6 1535 300 472 4 355 QZAZ-14-60-030QZHR 7 1535 300 572 4 355 QZAZ-14-70-030

G3 synthetic filter

A 48 mm thick plate filter is available. The filter is awashable synthetic fibre, flame-proof according to ClassF1 DIN 53438. Efficiency of 84%., Eurovent EU3. The filteris supplied as an accessory and must be fitted on the uniton site in place of the standard filter. 

AA

C

 

Model A B C Product codeQZHR 1-2 48 285 1000 QZAZ-09-03-10QZHR 3 48 335 988 QZAZ-09-03-30QZHR 4 48 335 1298 QZAZ-09-03-40QZHR 5 48 410 1298 QZAZ-09-03-50QZHR 6 48 460 1385 QZAZ-09-03-60QZHR 7 48 560 1385 QZAZ-09-03-70

F6 synthetic filter

High efficiency compact filter in glass microfiber paper,Class F6 in according to EN779. The filter is supplied asan accessory and must be fitted on the unit on site in placeof the standard filter. 

 

Model A B C Product codeQZHR 6 98 460 1385 QZAZ-09-06-60QZHR 7 98 560 1385 QZAZ-09-06-70

GAV Anti-vibrating connection

Intake/supply anti-vibrating connection, made of twogalvanized frames and a PVC flexible connection. 

110A

B

 

Model A B Product codeQZHR 1-2 1138 296 QZAZ-13-10QZHR 3 1138 346 QZAZ-13-30QZHR 4 1450 346 QZAZ-13-40QZHR 5 1450 421 QZAZ-13-50

Page 12: QZHR Fan Coil

QZHR Fan Coil

Accessories, air side pressure drop

Fläkt Woods 9324 GB 2014.04 12 Specifications are subject of alteration without further notice.

Sizes to 1 to 5 

 

 

 

Page 13: QZHR Fan Coil

QZHR Fan Coil

Accessories, air side pressure drop

Fläkt Woods 9324 GB 2014.04 13 Specifications are subject of alteration without further notice.

Sizes 6 to 7 

1500 2000 2500 3000 3500 4000 4500 5000 5500 6000

Air flow (m3/h)

Pre

ssur

e dr

op (

Pa)

0

10

20

30

40

50

60

70

80

90

6 row coil

4+2 row coil

6+2 row coil

48 mm G3 filter

98 mm F6 filter

Spigot plenum

 

 

2000

Air flow (m3/h)

Pre

ssur

e dr

op (

Pa)

0

10

20

30

40

50

60

70

80

90

100

2500 3000 3500 4000 4500 5000 5500 6000 6500 7000 7500

6 row coil

4+2 row coil

6+2 row coil

48 mm G3 filter

98 mm F6 filter

Spigot plenum

 

Page 14: QZHR Fan Coil

QZHR Fan Coil

Standard control valve kit for QZHR

Fläkt Woods 9324 GB 2014.04 14 Specifications are subject of alteration without further notice.

3-way control valve kit

   

3-way control valve kit, not fitted on the unitStandard left connections, right connections on request

Cooling valve Heating valve

230V – ON/OFF (Honeywell)

  Cooling valve Heating valveModel H L Connections (Ø) Kvs Code M N Connections (Ø) Kvs Code

QZHR-1 54 245 3/4" 10 QZAZ-21-20-31-40-0 50 249 3/4" 10 QZAZ-21-20-31-40-0QZHR-2 54 245 1" 10 QZAZ-21-25-31-41-0 50 249 3/4" 10 QZAZ-21-20-31-40-0QZHR-3 54 295 1" 10 QZAZ-21-25-31-41-0 50 299 3/4" 10 QZAZ-21-20-31-40-0QZHR-4 58 291 1"- 1/4 10 QZAZ-21-32-31-42-0 54 295 1" 10 QZAZ-21-25-31-41-0QZHR-5 58 367 1"-1/4 10 QZAZ-21-32-31-42-0 54 370 1" 10 QZAZ-21-25-31-41-0QZHR-6 59 416 1"1/4 10 QZAZ-21-32-31-43-0 55 421 1" 10 QZAZ-21-25-31-44-0QZHR-7 59 516 1"-1/4 10 QZAZ-21-32-31-43-0 55 521 1" 10 QZAZ-21-25-31-44-0

24V with 3 points (Johnson Controls, to be used with QZAZ-12-20)

  Cooling valve Heating valveModel H L Connections (Ø) Kvs Code H L Connections (Ø) Kvs Code

QZHR-1 54 245 1" 6 QZAZ-21-25-32-30-0 50 249 1" 6 QZAZ-21-25-32-35-0QZHR-2 54 245 1" 6 QZAZ-21-25-32-31-0 50 249 1" 6 QZAZ-21-25-32-35-0QZHR-3 54 295 1" 6 QZAZ-21-25-32-31-0 50 299 1" 6 QZAZ-21-25-32-35-0QZHR-4 58 291 1" 10 QZAZ-21-25-32-32-0 54 295 1" 10 QZAZ-21-25-32-36-0QZHR-5 58 367 1" 10 QZAZ-21-25-32-32-0 54 370 1" 10 QZAZ-21-25-32-36-0QZHR-6 59 416 1" 10 QZAZ-21-25-32-33-0 55 421 1" 10 QZAZ-21-25-32-37-0QZHR-7 59 516 1" 10 QZAZ-21-25-32-34-0 55 521 1" 10 QZAZ-21-25-32-38-0

3 points modulating valve control board

A power board can be supplied as an accessory to the QZHR unit, together with a control panel to be installed on thewall. The power board is made up of an electronic control board, a power relay module for managing the fan load anda 230/24 volt power transformer, all contained in a galvanised plate case to be secured to the side of the unit. The powerboard can manage the correct operation of the fan.

Modulating valve control board (ETN 500 control, air temp. probe and low temp. cut-out thermostat included):QZAZ-12-20

Page 15: QZHR Fan Coil

QZHR Fan Coil

Standard control valve kit for QZHR

Fläkt Woods 9324 GB 2014.04 15 Specifications are subject of alteration without further notice.

Water pressure drop 

 

Legendqw = water flow (l/h)Δp = pressure drop (kPa)

Page 16: QZHR Fan Coil

QZHR Fan Coil

Product code

Fläkt Woods 9324 GB 2014.04 16 Specifications are subject of alteration without further notice.

QZHR Power high pressurefan coil unit

QZHR-aa-b-c-d

Version (aa)R = horizontal basic unit -without decorative cabinet

Size (aaa)13, 14, 23, 24, 33, 34, 43, 44, 53, 54, 64, 66, 74 and 76

Water connection (b)Looking into the air outlet1 = Right hand unit - Water connectionson the right side of the unit2 = Left hand unit - Water connectionson the left side of the unit

 

RIGHTHAND UNIT (b=1) LEFTHAND UNIT (b=2)

HO

RIZ

ON

TA

L U

NIT

H2O H2O

 

Coil arrangement ©)2 = 2-pipe system (one water coil) -3 or 4 rows or 6 cooling or heating4 = 4-pipe system (two water coils) -3 or 4 rows cooling and 1 row heating5 = 4-pipe system (two water coils) -3 rows or 4 or 6 cooling and 2 rows heating

Motor arrangement (d)1 = Standard AC motor - 230V/1/50Hz