Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi Euro system separator GENO ® -DK 2 nominal diameter DN 15/20 Euro system separator GENO ® -DK 2-Maxi DN 100 Edition April 2017 Order no. 135 132 970-inter
23

Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Aug 13, 2019

Download

Documents

lamduong
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Operation manualEuro system separator GENO-DK 2

Euro system separator GENO-DK 2-MaxiEuro system separator GENO-DK-Maxi

Euro system separator GENO®-DK 2 nominal diameter DN 15/20

Euro system separator GENO®-DK 2-Maxi DN 100

Edit ion Apri l 2017 Order no. 135 132 970-inter

Page 2: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System Separator GENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

2

Table of contents A General information

1 Preface 2 Warranty 3 General safety information 4 Transportation and storage 5 Disposal of used parts and materials

4

B Basic information 1 Laws, regulations, standards 2 Protection of drinking water 3 Classification of liquid categories 4 Function

7

C Product description 1 Type designation plate 2 Designated application 3 Technical specifications 4 Scope of supply

10

D Installation and start-up 1 General installation information 2 Water installation 3 Start-up 4 Functional check

15

E Troubleshooting 1 Disturbances 2 Maintenance

18

F Maintenance, care and spare parts 1 Basic information 2 Inspection 3 Maintenance 4 Spare parts

19

Operation log

Page 3: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System SeparatorGENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

3

Publisher’s information All rights reserved.

© Copyright by Grünbeck Wasseraufbereitung GmbH Printed in Germany Effective with the date of edition on the cover sheet. –We reserve the right to modifications in terms of technical progress- Reprints, translations into foreign languages, electronic storage or copying only with explicit written approval of Grünbeck Wasserauf-bereitung GmbH. Any type of duplication not authorized by Grünbeck Wasseraufberei-tung GmbH is a copy-right violation and subject to legal action. Publisher responsible for contents: Grünbeck Wasseraufbereitung GmbH Josef-Grünbeck-Str. 1 89420 Hoechstaedt/Germany Phone +49 9074 41-0 Fax +49 9074 41-100 www.gruenbeck.de [email protected] Print: Grünbeck Wasseraufbereitung GmbH Josef-Grünbeck-Str. 1, 89420 Hoechstaedt/Germany

Page 4: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System Separator GENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

4

A General information

1 | Preface

Thank you for opting for a Grünbeck product. Backed by decades of experience in the area of water treatment, we provide solutions for all processes. All Grünbeck systems and devices are made of high-quality materials. This ensures reliable operation over many years, provided you treat the systems with the required care. This operation manual assists you with important information. Carefully read the present operation man-ual prior to installing, operating or maintaining the system. Customer satisfaction is our prime objective and providing customers with qualified advice is crucial. If you have any questions concerning this sys-tem, possible extensions or general water and waste water treatment, our customer service staff, as well as the experts at our headquarters in Hoechstaedt, are available to help you.

Advice and assistance For advice and assistance please contact your local representative

(see www.gruenbeck.de) or get in touch with our service hotline on +49 9074 41-333 We can connect you with the appropriate expert more quickly if you provide the required system data. In order to have this data handy at all times, please copy it from the type designation plate to the overview in chapter C, item 1.

2 | Warranty

All devices and systems supplied by Grünbeck Wasseraufbereitung GmbH are manufactured according to the most recent technical standards and subjected to a comprehensive quality assurance sys-tem. All warranty claims are subject to our General Terms and Condi-tions of Sale and Delivery.

Page 5: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System SeparatorGENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

5

3 | General safety information

Operating personnel Only persons who have read and understood this operation manual are permitted to work with the system. The safety guidelines are to be strictly adhered to.

Symbols and notes Important notes in this operation manual are characterised by sym-bols. Please pay particular attention to these notes in order to ensure a danger-free, safe and productive system operation.

Danger! Failure to adhere to these notes will cause serious or life-threatening injury, extreme damage to property or inadmissible con-tamination of drinking water.

Warning! Failure to adhere to these notes may cause injury, damage to property or contamination of the drinking water.

Attention! Failure to adhere to these notes may result in damage to the system or other objects.

Note: This symbol characterises notes and tips to make your work easier.

Tasks with this symbol may only be performed by Grünbeck's technical customer service/authorised service company or by persons expressly authorised by Grünbeck.

Tasks with this symbol may only be performed by personnel in-structed in electrical engineering according to the VDE guidelines or according to the guidelines of a similar local institution.

Tasks with this symbol may only be performed by water companies or approved installation companies.

4 | Transportation and storage

Attention! The system may be damaged by frost or high tempera-tures. Protect from frost during shipping and storage! Do not install or store system next to objects which radiate a lot of heat.

The system may only be transported and stored in its original pack-ing. Ensure that it is handled with care and placed the right side up (as indicated on the packing).

Page 6: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System Separator GENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

6

5 | Disposal of used parts and materials Used parts and materials are to be disposed of, or made available for

recycling purposes, according to the applicable local guidelines.

If a material is subject to specific regulations, adhere to the notes indi-cated on the packing.

If in doubt, contact your local waste disposal authority or the manufac-turer for more information.

Page 7: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System SeparatorGENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

7

B Basic information (system separators)

1 | Laws, regulations, standards

In the interest of good health, rules cannot be ignored when it comes to the processing of drinking water. This operation manual takes the applicable German guidelines into account and provides all the infor-mation you need to safely operate your system separators.

Among other things, the regulations stipulate that only approved com-panies are permitted to make major modifications to water treatment facilities, and that tests, inspections and maintenance are to be per-formed on the devices at regular intervals.

2 | Protection of drinking water

Drinking water is still the most important nourishment which cannot be replaced by anything else. Also in trade and industry water and drink-ing water are irreplaceable.

For the protection of drinking water, the parties directly involved such as the water supply authorities, installers (plumber) and operators must observe legal and technical regulations.

Only a free outlet offers the maximum security against the entering of non-drinking water, foreign and harmful substances into the drinking water by back-flowing, back-pressing and back-sucking. Other safety devices may also be used for economical and operational reasons. However, only safety devices with proven qualification may be used (e.g. such as DIN-DVGW or DVGW mark of conformity).

In order to be able to properly select the safety devices which differ in function and efficiency, the impairments are classified in five liquid categories. In case several substances and micro-organisms may get into the drinking water simultaneously, the most dangerous substance or micro-organism determines the liquid category.

Page 8: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System Separator GENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

8

3 | Classification of liquid categories

Liquid category 1

Water for human consumption that is withdrawn directly from a drink-ing water installation.

Examples: Temporary turbidity due to air bubbles.

Liquid category 2 Liquids that do not represent a health risk to human beings.

Liquids that are suitable for human consumption - including water originating from a drinking water installation - that may exhibit modifi-cations with regard to taste, smell, colour or temperature (heating up or cooling down).

Examples: Coffee, heated drinking water.

Liquid category 3 Liquids that represent a health risk to human beings due to the pres-ence of one or several poisonous or highly poisonous substances.

Examples: Ethylene glycol, copper sulphate solution, heating water without addi-tives or with additives as per liquid category 3.

Liquid category 4 Liquids that represent a health risk to human beings due to the pres-ence of one or several poisonous or highly poisonous substances or one or several radioactive, mutagenic or carcinogenic substances.

Examples: Lindane, phosalone, parathion (insecticides), hydrazine, heating wa-ter with additives as per liquid category 4.

Liquid category 5 Liquids that represent a health risk to human beings due to the pres-ence of microbial or viral pathogens of communicable diseases.

Examples: Hepatitis viruses, salmonellae

(excerpt of DIN EN 1717, part 5.2)

Attention! System separators are safety devices. They protect the drinking water against changed drinking water. They can only work re-liably provided regular inspections and maintenance are performed.

Page 9: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System SeparatorGENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

9

4 | Function The system separator consists of two non-return valves, a middle

chamber and a membrane-controlled discharge valve. The water en-tering the system separator opens the non-return valve on the inlet side (A) and at the same time exerts pressure via the drain (1) on the membrane (2) which closes the discharge valve by means of a rod and thus the water opens the second non-return valve. Due to the pressure loss caused by the non-return valve (A), the pressure in the middle chamber is – under normal operating conditions - always at least 140 mbar (1.4 m WC) less than the back pressure. The differ-ence in pressure p between the inlet side and the middle chamber can be specified as a safety basis so that in the event of damage oc-curring or a pressure loss, the discharge valve already opens when the pressure in the middle chamber is still 140 mbar lower than the in-let pressure. Moreover in the event of damage to the membrane, the safety gasket thrust by the contrast spring (3) to the housing prevents the return of the water via the drain (item 1). Consequently no water can get back from the middle chamber to the inlet area. It is also not possible even in the event of minor leaks at the non-return valve, which would be indicated by an outflow of water from the middle chamber as soon as the pressure difference p is lower than 140 mbar.

Note: Prior to start up, the air above the membrane must be blown off in order to ensure safe operation.

Fig. B-1: Detail drawing of Euro system separator GENO®-DK 2, 1 ¼”

A 3

2

1

Page 10: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System Separator GENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

10

C Product description (system separators)

1 | Type designation plate

The type designation plate is located on the housing of the system separator. If you have questions concerning the system, please spec-ify the information shown on the type designation plate of the unit in order to speed up the processing of your request. Please copy the data given on the designation plate to the table below in order to have it handy whenever necessary.

Euro system separator GENO-DK

Serial no.: /

Order no.:

2 | Designated application

The Euro system separator version BA is a safety device to be in-stalled in water pipes when special tapping devices and appliances are connected to the drinking water supply system. The Euro system separator prevents used or modified water from flowing back, press-ing back or being sucked back into the drinking water system. Version BA is approved as safety device for systems up to liquid 4 (in-cluded) according to DIN EN 1717 (see chapter B; classification of liq-uid categories).

Attention! System separators are safety devices. They protect the drinking water from modified drinking water. They can only work relia-bly provided regular inspections and maintenance are performed.

Page 11: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System SeparatorGENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

11

3 | Technical specifications

Table C-1: Technical specifications Euro system separator GENO®-DK 2

Connection data

Nominal connection diameter DN 15 DN 20 DN 25 DN 32 DN 40 DN 50

Threaded connection [R] ½“ ¾“ 1“ 1¼“ 1½“ 2“

Performance data

Nominal pressure PN 10

Min. flow pressure [bar] 1

Max. flow [m³/h] 1.9 3.3 5.2 7.2 13.5 21

KV value (p = 1 bar) [m³/h] 3.5 4.5 7.6 9.4 22.2 32.5

Dimensions and weight

A Drain connection [mm] 40/50 50

B Installation length with water meter screw connection

[mm] 227 280 387 395

C Installation length with water meter screw connection

[mm] 153 187 274

D System height with outlet funnel [mm] 263 292 382

E Height above centre of pipe connection

[mm] 103 100 130

Weight empty [kg] 3 4.7 10.7 11.8

Operating weight [kg] 3.4 5.2 12.5 13.6

Test mark/Certification mark

DVGW registration number NW-6305BR0345

Ambient data

Max. water temperature [°C] 65

Max. ambient temperature [°C] 70

Order no. 132 510 132 520 132 530 132 540 132 560 132 570

Fig. C-1: Install. example filter combination fine filter BOXER®-KD with Euro system sep. GENO® -DK 2 nom. di-ameter DN 25/32

Fig. C-2: Dimensional drawing of Euro system sepa-rator GENO® -DK 2 nominal diameter DN 25/32

B

A

D

C

E

Page 12: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System Separator GENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

12

Table C-2: Technical specifications Euro system separator GENO®-DK 2-Maxi

Connection data

Nominal connection diameter DN 50 DN 65 DN 80 DN 100

Performance data

Nominal pressure PN 10

Min. flow pressure [bar] 1

Max. flow [m³/h] 25 35 50 80

KV value (p = 1 bar) [m³/h] 35 55 88 122

Dimensions and weight

A Drain connection [mm] 50 80

B Installation length without counter-flanges [mm] 302 305 470

C System height with outlet funnel [mm] 382 385 484

D Height above centre of pipe connection [mm] 129 132.5 170

Weight empty [kg] 13.2 17 26.5 28

Operating weight [kg] 16 19.8 33.1 34.2

Test mark/Certification mark

DVGW registration number NW-6305BR0345

Ambient data

Max. water temperature [°C] 65

Max. ambient temperature [°C] 70

Order no. 132 460 132 465 132 470 132 475

Fig. C-3: Installation example for GENO®-backwash filter MX DN 100 with Euro system separator GENO®-DK 2-Maxi DN 100

Fig. C-4: Dimensional drawing Euro system separator GENO®-DK 2-Maxi DN 100

Page 13: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System SeparatorGENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

13

Table C-3: Technical specifications Euro system separator GENO®-DK 2-Maxi Connection data

Nominal connection diameter DN 150 DN 200 DN 250

Performance data

Nominal pressure PN 10

Min. flow pressure [bar] 1

Max. flow [m³/h] 227 363 523

KV value (p = 1 bar) [m³/h] 227 363 523

Dimensions and weight

A Drain connection [mm] 90

B Installation length without counter-flanges [mm] 600 780 930

C System height with outlet funnel [mm] 839 922

D Height above centre of pipe connec-tion

[mm] 310 350

Weight empty [kg] 103 111 142

Operating weight [kg] 123 150 200

DVGW test mark/Certification mark

DVGW registration number -

Ambient data

Max. water temperature [°C] 60

Max. ambient temperature [°C] -

Order no. 132 720 132 725 132 730

3.1 Pressure loss curves

Fig. C-5: Pressure loss curve 1: Euro system separator GENO®-DK 2

Page 14: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System Separator GENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

14

Fig. C-6: Pressure loss curve 2: Euro system separator GENO®-DK 2-Maxi

Fig. C-7: Pressure loss curve 3: Euro system separator GENO®-DK-Maxi

4 | Scope of supply System separator with drain connection.

Water meter screw connections incl. seals for DK 2.

GENO® -DK 2-Maxi, GENO® -DK-Maxi without counter-flanges and seals.

Operation manual with operation log.

4

5

6

7

8

9

10

11

12

13

14

10

0

20

0

30

0

40

0

50

0

60

0G (m3/h)

p (m w.s)

G (m³/h)

Page 15: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System SeparatorGENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

15

D Installation and start-up 1 | General installation information

Please observe local directives and general regulations for installa-tion.

The installation site must be accessible for maintenance work and be protected against flooding and frost. It must ensure the protec-tion of the device from chemicals, dyes, solvents and steam/va-pours.

Installation according to its nominal diameter in pipelines of the same dimensions as the unit.

According to DIN EN 806, part 2, quick-acting shut-off fittings which may cause water hammers (positive and negative pressure peaks) may be used for permanent operation in water pipelines only under consideration of the maximum peak pressure and the operating pressure. Exceptions: fittings which are only used for testing pur-poses by experts.

Attention! Impurities and corrosion particles may lead to malfunc-tions or damages at the system separator. The feed line must be rinsed before start-up.

2 | Water installation

Binding rules

The installation of a system separator represents a major interference with the drinking water installation, and therefore may only be per-formed by an authorised sanitary or heating company.

Preparatory work

1. Unpack all system components. 2. Check for completeness and perfect condition.

Page 16: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System Separator GENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

16

Install according to installation drawing (Fig. D-1).

Make sure that built-in parts downstream and upstream of the sys-tem (such as EBRO flaps) do not protrude into the system separator and damage components located inside.

Fig. D-1: Installation example Euro system separator GENO®-DK 2

Shut-off valve Euro system separator GENO®-DK 2

Fine filter BOXER®-KD with pressure reducer Waste water connection

Shut-off valve with draining Shut-off valve

Install strainer / fine filter directly upstream of the system

Attention! Observe flow direction.

Only install the system separator horizontally and stress-free.

Provide drain connection according to the technical specifications.

Make sure that a free outlet is available and discharge is performed without back-flow.

1 2 3 6

4

5

W W

1 4

2 5

3 6

Page 17: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System SeparatorGENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

17

3 | Start-up

Prior to start-up, rinse the feed pipe. If necessary, dismantle the sys-tem separator.

When (re-)installed, slowly open the shut-off valves (item 1 and item 4) upstream and downstream of the system separator. Then the system separator goes into operating position. Make sure that the discharge valve (item 5) is closed.

Completely deaerate the system separator by opening the relief screw (item. 3).

Carry out visual inspection. Thereby, make sure that no water leaks at any point of the system.

Fig. D-2: Exploded drawing of Euro system separator GENO®-DK 2 Shut-off valve on inlet side Shut-off valve on outlet side

Euro system separator GENO®-DK 2 Waste water connection

Relief screw Discharge valve on inlet side

4 | Functional check

After successful start-up of the system separator, close the shut-off valve (item 1). Pressure relief in the inlet pressure area is initiated by opening the discharge valve (item 5).

Note: Afterwards, the system separator must go into separating posi-tion and thereby empty the middle pressure zone.

Afterwards, close the discharge valve (item 6) and slowly open the shut-off valve (item 1). Subsequently the system separator must return into operating position again, and it must be completely tight.

W W

2

1 4

3

5

6

1 4

2 5

3 6

Page 18: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System Separator GENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

18

E Troubleshooting Even carefully designed and manufactured technical systems that are

properly operated, may experience malfunctions. Table E-1 provides an overview of possible problems that may occur during the operation of the system separators and indicates their causes and the corre-sponding remedies.

Attention! Short-term, undefined water leakage at the discharge valve, does not represent a disturbance at the system separator. It is a normal control behaviour of the system separator, caused by pressure fluctuations in the water supply system upstream of the device.

Note: In case of disturbances, e.g. permanent water leakage at the discharge valve, proceed as per check-list below: Independent of the disturbance, you may identify the fault by perform-ing the various steps systematically.

Test 1 Close shut-off valve at outlet side.

Permanent discharge.

Non-return valve on inlet side or dis-charge valve leaky

Dismantle and check.

Put the equipment back into operation.

No discharge.

Put the system sepa-rator back into opera-tion

Test 2 Close shut-off valve at inlet side and then open sampling valve (pressure measuring point)

- Discharge valve does not open. Dis-charge is minimal and lasts for more than 1 minute.

Discharge valve blocked Aeration and de- aeration clogged.

Dismantle and check.

Put the system sepa-rator back into opera-tion.

Discharge valve opens abruptly. Equipment is emptied in less than 1 minute.

Put the system sepa-rator back into opera-tion.

Test 3 Open shut-off valve at the outlet side.

Continuous discharge.

Non-return valve at outlet side leaky.

Dismantle and check. Put the sys-tem separator back into operation.

Dismantle and check. Put the system sepa-rator back into opera-tion.

No discharge. Put the system sepa-rator back into opera-tion.

Note: In case the disturbances cannot be remedied, please contact your local Grünbeck service representative (see www.gruenbeck.de)

Page 19: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System SeparatorGENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

19

F Maintenance, care and spare parts 1 | Basic information

In order to guarantee the reliable function of the system separators over a long period of time, some maintenance has to be performed at regular intervals. This applies in particular to safety devices used in the drinking water supply: The required measures are defined in regu-lations and guidelines. You must comply with all regulations and guidelines which apply at the installation site. Inspection and maintenance according to DIN EN 806 part 5 and W/TPW 135, appendix I.

Every 6 months, an inspection must be performed by the operator or the installation company.

The annual maintenance must be performed by an approved, spe-cialist company or by Grünbeck’s technical customer service/au-thorised service company.

Note: A maintenance contract ensures that all the required mainte-nance work will be performed in due time.

2 | Inspection

Check for tightness, visual inspection: If no water is withdrawn, no water must leak at the discharge valve

toward the outlet funnel.

After opening a downstream tapping point, no leakage may occur.

Occasional dripping at the discharge valve is a normal regulation process and only indicated that the system separator is working properly (is caused by pressure fluctuations at the inlet).

3 | Maintenance

Check for tightness, visual inspection: After opening a downstream tapping point, no leakage may occur.

Functional check: Close the shut-off valves upstream of the system separator. Relieve

the pressure from the inlet pressure zone by opening the discharge valve between the shut-off valve and the system separator.

Empty/drain off the inlet pressure zone between the closed shut-off valves and the system separator.

Afterwards, the system separator must go into separating position, and must completely drain the middle pressure zone.

Note: If functional disturbances are detected during inspection or maintenance, please refer to chapter E “Troubleshooting” for assis-tance.

Page 20: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System Separator GENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

20

4 | Spare parts

For spare parts and consumables, please contact your local Grünbeck representative (see www.gruenbeck.com).

The parts indicated in the following drawing are considered to be wearing parts.

Note: Even though these parts are wearing parts, we grant a limited warranty of 6 months for them.

Fig. F-1: Wearing parts of Euro system separator GENO®-DK 1 ¼”

O-ring Drain seat

Control membrane* Drain seal*

Non-return valve outlet side Non return valve inlet side

* Are supplied as complete assembly group “discharge valve”.

1

2

3

45

6

1 4

2 5

3 6

Page 21: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System SeparatorGENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

21

Operation Log

Customer

Name: ................................................................

Address: ............................................................

...........................................................................

...........................................................................

Euro system separator GENO®-DK (Please check appropriate box)

½“

¾“

1“

1¼“

1½“

2“

DN 50

DN 65

DN 80

DN 100

DN 150

DN 200

DN 250

Serial number ........................................

Installed by ............................................

Connection data:

Drain connection DIN 1988/EN 1717

yes no

(Please check appropriate box)

Page 22: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System Separator GENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

22

Operation log for inspection, maintenance and repair work

on Euro system separator GENO®-DK Work performed Confirmation of execution

Inspection

Maintenance

Repair

Description: _______________________________________

_________________________________________________

_________________________________________________

_________________________________________________

Company: ..........................................................

Name: ................................................................ Date/ Signature: ...........................................................

Inspection

Maintenance

Repair

Description: _______________________________________

_________________________________________________

_________________________________________________

_________________________________________________

Company: ..........................................................

Name: ................................................................ Date/ Signature: ...........................................................

Inspection

Maintenance

Repair

Description: _______________________________________

_________________________________________________

_________________________________________________

_________________________________________________

Company: ..........................................................

Name: ................................................................ Date/ Signature: ...........................................................

Inspection

Maintenance

Repair

Description: _______________________________________

_________________________________________________

_________________________________________________

_________________________________________________

Company: ..........................................................

Name: ................................................................ Date/ Signature: ...........................................................

Inspection

Maintenance

Repair

Description: _______________________________________

_________________________________________________

_________________________________________________

_________________________________________________

Company: ..........................................................

Name: ................................................................ Date/ Signature: ...........................................................

Inspection

Maintenance

Repair

Description:

_______________________________________

_________________________________________________

_________________________________________________

_________________________________________________

Company: ..........................................................

Name: ................................................................ Date/ Signature: ...........................................................

Inspection

Maintenance

Repair

Description: _______________________________________

_________________________________________________

_________________________________________________

_________________________________________________

Company:

Name: Date/ Signature:

Page 23: Operation manual Euro system separator GENO -DK 2 Euro ... · Operation manual Euro system separator GENO -DK 2 Euro system separator GENO -DK 2-Maxi Euro system separator GENO -DK-Maxi

Euro System SeparatorGENO-DK 2, GENO-DK 2-Maxi, GENO-DK-Maxi

Order no. 135 132 970-inter Edited by: PI-4/PI-6-4 ger/mrie G:\BA-132970-INTER_135_SYSTEMTR_DK.DOCX

23

Operation log for inspection, maintenance and repair work

on Euro system separator GENO®-DK Work performed Confirmation of execution

Inspection

Maintenance

Repair

Description: _______________________________________

_________________________________________________

_________________________________________________

_________________________________________________

Company: ..........................................................

Name: ................................................................ Date/ Signature: ...........................................................

Inspection

Maintenance

Repair

Description: _______________________________________

_________________________________________________

_________________________________________________

_________________________________________________

Company: ..........................................................

Name: ................................................................ Date/ Signature: ...........................................................

Inspection

Maintenance

Repair

Description: _______________________________________

_________________________________________________

_________________________________________________

_________________________________________________

Company: ..........................................................

Name: ................................................................ Date/ Signature: ...........................................................

Inspection

Maintenance

Repair

Description: _______________________________________

_________________________________________________

_________________________________________________

_________________________________________________

Company: ..........................................................

Name: ................................................................ Date/ Signature: ...........................................................

Inspection

Maintenance

Repair

Description: _______________________________________

_________________________________________________

_________________________________________________

_________________________________________________

Company: ..........................................................

Name: ................................................................ Date/ Signature: ...........................................................

Inspection

Maintenance

Repair

Description:

_______________________________________

_________________________________________________

_________________________________________________

_________________________________________________

Company: ..........................................................

Name: ................................................................ Date/ Signature: ...........................................................

Inspection

Maintenance

Repair

Description: _______________________________________

_________________________________________________

_________________________________________________

_________________________________________________

Company:

Name: Date/ Signature: