Top Banner
Ventilation application LB10 v1.2x for ACX36.xxx/ALG Air conditioning SIEMENS SAPHIR Basic documentation
72
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Manual Saphir LB10 S22 Eng V1_2x

Ventilation application LB10 v1.2x for ACX36.xxx/ALG

Air conditioning

SIEMENS SAPHIR Basic documentation

id22680828 pdfMachine by Broadgun Software - a great PDF writer! - a great PDF creator! - http://www.pdfmachine.com http://www.broadgun.com

Page 2: Manual Saphir LB10 S22 Eng V1_2x

2/2

Siemens Building Technologies Basic documentation ACX36.xxxALG CE1P3226en/IVP HVAC Products IVprodukt LB10

© 2006 Siemens Building Technologies AG Subject to alteration

Page 3: Manual Saphir LB10 S22 Eng V1_2x

3/3

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products Contents

Contents

1 Overview.......................................................................................................6

1.1 Properties......................................................................................................6

1.2 Peripheral components .................................................................................7

1.3 Safety............................................................................................................8

1.3.1 Requirements regarding personnel for installation and start-up ...................8

1.3.2 Safety regulations .........................................................................................8

1.4 Packing, transport and storage.....................................................................9

1.5 Maintenance and service..............................................................................9

1.6 Environmental protection and waste management.......................................9

1.7 Abbreviations ..............................................................................................10

2 Installation, Connection...............................................................................11

2.1 Installation procedure..................................................................................11

2.1.1 Process unit ................................................................................................11

2.1.2 HMI (Operating unit) ...................................................................................11

2.2 Connection instruction ................................................................................12

2.2.1 Terminal blocks...........................................................................................12

2.2.2 Connection instruction ................................................................................13

2.3 Action in the event of a fault........................................................................14

3 Operation ....................................................................................................15

3.1 Operation ACX84.910/ALG.........................................................................15

3.2 Menu system...............................................................................................16

3.2.1 Levels..........................................................................................................16

3.2.2 Password ....................................................................................................16

3.2.3 Menus .........................................................................................................16

3.2.4 Overview menu tree....................................................................................17

3.2.5 Navigate......................................................................................................18

3.3 Start/stop button (service switch)................................................................19

3.4 Alarm button................................................................................................19

3.5 Alarm management.....................................................................................20

3.5.1 Alarm guide.................................................................................................20

4 Description of the operating level................................................................22

4.1 Date/time.....................................................................................................22

4.2 Time switch program (Scheduler) ...............................................................22

4.2.1 Day program ...............................................................................................22

4.2.2 Week program ............................................................................................23

4.2.3 Year program..............................................................................................23

Page 4: Manual Saphir LB10 S22 Eng V1_2x

4/4

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products Contents

4.2.4 Example Time switch program....................................................................25

4.2.5 Override time switch program .....................................................................26

4.2.6 Current scheduler........................................................................................26

4.3 Setpoints .....................................................................................................27

4.3.1 Temperature control ....................................................................................27

4.3.2 Min/Max supply air temperature for cascade control...................................27

4.3.3 Fan speed ...................................................................................................28

4.4 Operation status..........................................................................................29

4.4.1 Digital inputs................................................................................................29

4.4.2 Measurement values...................................................................................30

4.4.3 Outputs, digital ............................................................................................30

4.4.4 Control outputs............................................................................................30

4.4.5 Operationcounter ........................................................................................31

4.4.6 Test smoke damper ....................................................................................32

4.4.7 Efficiency rating...........................................................................................32

4.5 Alarm history ...............................................................................................33

4.6 Password ....................................................................................................33

4.7 Application information................................................................................33

5 Description of configuration level ................................................................34

5.1 Functions, Configuration .............................................................................34

5.1.1 Application...................................................................................................34

5.1.2 Configuration of temperature control (Control mode)..................................34

5.1.3 Type of cooling, heat recovery and heating ................................................35

5.1.4 Selection of fan control................................................................................36

5.1.5 Selection of Multi-function input 1 ...............................................................37

5.1.6 Selection of AUX alarm 1 and 2 ..................................................................38

5.1.7 Selection of emergency stop or fire alarm...................................................38

5.1.8 Damper functionality ...................................................................................38

5.1.9 Selection of sensor......................................................................................39

5.1.10 Save configuration ......................................................................................39

5.2 Sensors .......................................................................................................39

5.2.1 Calibration of measurement values.............................................................39

5.3 Alarm settings .............................................................................................40

5.3.1 Temperature alarm......................................................................................41

5.3.2 Operationcounter ........................................................................................41

5.3.3 Setting contact function for alarm inputs .....................................................42

5.3.4 Alarm delay .................................................................................................42

5.3.5 Alarm class..................................................................................................42

5.3.6 Alarm output ................................................................................................42

5.3.7 HRC efficiency alarm ..................................................................................42

Page 5: Manual Saphir LB10 S22 Eng V1_2x

5/5

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products Contents

5.4 Regulator settings (Controllers) ..................................................................43

5.4.1 Controllers...................................................................................................43

5.5 Control parameters .....................................................................................44

5.5.1 Cooling........................................................................................................44

5.5.2 Heat recovery..............................................................................................44

5.5.3 Heating........................................................................................................46

5.5.4 External setpoint .........................................................................................47

5.5.5 Summer Winter compensation....................................................................48

5.5.6 Cascade control ..........................................................................................49

5.6 Parameters .................................................................................................50

5.6.1 Fan..............................................................................................................50

5.6.2 Fan compensation ......................................................................................51

5.6.3 Pumps.........................................................................................................52

5.6.4 Control inputs..............................................................................................52

5.6.5 Unoccupied.................................................................................................53

5.6.6 Night purging...............................................................................................54

5.6.7 Test smoke damper ....................................................................................56

5.6.8 Start-up .......................................................................................................56

6 Description of system settings ....................................................................57

6.1 Selection of language .................................................................................57

6.2 Communication...........................................................................................57

6.2.1 LON Configuration ......................................................................................57

6.2.2 Modbus Configuration.................................................................................57

6.3 Day light saving...........................................................................................58

6.4 Diagnose.....................................................................................................59

6.5 HMI Parameter............................................................................................60

7 Communication options ..............................................................................62

7.1 KNX.............................................................................................................62

7.2 LON.............................................................................................................62

7.3 Modbus .......................................................................................................62

8 Parameter list..............................................................................................63

8.1 Overview of operating level.........................................................................63

8.2 Overview of configuration level ...................................................................66

Page 6: Manual Saphir LB10 S22 Eng V1_2x

6/6

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 1 Overview

1 Overview 1.1 Properties

The application is prepared to handle several variants, with various function set-ups depending on variant. Only one variant is available in this version. Macro 1 Air handling unit with separate starting of supply and exhaust air fans,

separate analog outputs for frequency controller. Three control sequences.

Three types of control � Cascade control of room/supply air temperature or exhaust/supply air temperature,

with limits for supply air temperature � Control of supply air temperature � Cascade control during summer and supply air control during winter

Cascade control with fixed or sliding limits for supply air temperature (differential temperature control)

Min. and max. limits for supply air temperature Summer/Winter compensation of temperature setpoint External temperature setpoint (0-10V or Ni1000) Unoccupied mode (night mode) for heating and/or cooling Night ventilation function (Night purge) Frosting protection for heat recovery unit (HRC) Load dependent ventilation Frost protection function Adjustable P, PI, PD or PID control functions Electrical or water heater Cooling, continuous or one-/two-stage or three-stage (binary) switching (DX cooling) HRC, rotary heat exchanger, continuous or on/off, plate heat exchanger, glycol circuit

or return air damper Cooling recovery Pre-heating function for water-heated air heater Speed reduction of fans when plant needs heat Speed increase of fans when plant needs cooling

Time scheduler comprising day program with four switching times, week program with six exception times and year program with ten exception times

Choice of direct-driven or frequency-controlled fans with fixed speed Single- or 2-speed fans via frequency converters Enabling of electric heating; fan overrun Fire function for the fans. Operation both fans. Stop of both fans. Stop of either the

extract or supply air fan, with the other fan going to max.speed Anti-seizing of smoke and fire damper Start/stop of the pump according to load, outside temp and motion operation Switching of damper or heat recovery to max. economy (cooling recovery) Adjustable start-up of return air operation for return air damper Controlling the regulator via external switch or push-button (Timer) Emergency stop Combined alarm with one contact output (priority A and/or B) Limitation of minimum outside air volume at return air damper Outside temperature-dependent blocking of fan speed II Outside temperature-dependent blocking of cooling signal Max. limitation of controlsignal for cooling at low speed. Max. limitation of control signal for electric heating at different fan stages

General

Control functions

Operation functions

Page 7: Manual Saphir LB10 S22 Eng V1_2x

7/7

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 1 Overview

Operating unit (HMI) with 8-row display with 20 characters/row Roomunit with temperature sensor, setpoint and operation mode control Temperature sensor, open-circuit and deviation AUX temperature (only measuring) Fire or smoke alarm input Frost protection in the air heater�s water circuit Electric air heater, overload or overheating HRC, rotation guard, pressure switch or defrosting function Efficiency measuring for HRC Cooling (Pump, Refrigerating machine) Circulation pump, overload Fans, overload and flow guard Two optional alarm inputs AUX (e.g. filter monitoring, flow monitoring) Communication with a Building Management System (BMS)

1.2 Peripheral components

All peripheral components that will be connected to the controller must be adapted to the controller in- and outputs.

Passive temperature sensors with LG-Ni1000 resistance Remote setting unit with 0-10VDC or Ni1000 resistance

Siemens QAA26 for Ni1000 5-30°C, Siemens QAA27 for Ni1000 +-3K Actuators for 0-10VDC Smokedamper with both closed and open indication Fault signal contact, Normally open or Normally closed Roomunit with temperature sensor, setpoint and operation mode control

Siemens QAA88.3 (via PPS2) Transformer 24VAC

Monitoring functions

Yttre komponenter

Page 8: Manual Saphir LB10 S22 Eng V1_2x

8/8

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 1 Overview

1.3 Safety

All equipment that is connected to the system must be CE marked and comply with the Machine Safety Directive.

1.3.1 Requirements regarding personnel for installation and start-up

Installation and start-up of ACX36.xxx/ALG may only be carried out by qualified personnel who have relevant technical expertise and who are well acquainted with all the safety and installation regulations.

1.3.2 Safety regulations

The following safety regulations do not relate solely to ACX36.xxx/ALG but also to the regulator�s surroundings (e.g. control panel) and the technical plant in the property. Observe all safety directions and comply with the corresponding general safety regulations in order to prevent personal injury and damage to property. Safety devices may not be removed, bypassed or taken out of operation.

Apparatus and system components may only be used in a technically fault-free

state. Faults that can affect safety must be rectified immediately.

Observe the required safety instructions against excessively high contact voltages.

The plant may not be in operation if the standard safety devices are out of operation or if their effects are influenced in some other way.

All handling that affects the prescribed disconnection of the protective extra-low voltage (AC 24 V) must be avoided.

Disconnect the supply voltage before opening the apparatus cabinet. Never work when the power is on!

Avoid electromagnetic and other interference voltages in signal and connection cables.

Assembly and installation of system and plant components may only be performed in accordance with corresponding installation instructions and instructions for use.

The following equipment must be protected against static charging: electronic components, open printed circuit boards, freely accessible connectors and apparatus components that are connected with the internal connection.

In this context, also observe necessary protective measures such as earthing, potential equalisation, conducting surfaces (avoid highly insulating materials), etc.

Use with other components

Page 9: Manual Saphir LB10 S22 Eng V1_2x

9/9

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 1 Overview

1.4 Packing, transport and storage

The required packing of the system for storage and transport is dependent on the mechanical and climate conditions. Use the original packaging from Siemens or from the supplier when mechanical and climate conditions have an impact on transport. During transport under particularly difficult conditions, a special package must be used. If the equipment is not to be installed immediately, store it in a well ventilated area, protected against high temperatures, humidity, dust and metal particles. For storage and transport, the limit values specified in data sheet CE2Q3226

always apply. Contact your supplier or Siemens in the event of any uncertainty.

Damage that arises as a result of incorrect packing, storage or transport is not the responsibility of Siemens.

1.5 Maintenance and service

All that is required to maintain ACX36.xxx/ALG is regular cleaning. System components that are arranged within the control panel are most easily separated from dust and dirt in conjunction with the prescribed maintenance checks. Diagnostics, the rectifying of faults and restarting may only be carried out by authorised staff. This also applies to work within the control panel (e.g. inspections, replacing fuses). In the event of unauthorised interventions, Siemens or IV product cannot undertake to honour any guarantees. The responsibility for any damage that occurs in the system and any consequential damage rests with whoever caused the damage.

1.6 Environmental protection and waste management

Process unit ACX36.xxx/ALG has no negative impact on the environment. The apparatus includes electrical and electronic components and when discarded must not be handled together with household waste. Current local legislation must always be taken into consideration!

Packing

Transport

Storage

Cleaning

Faults

Environmental protection Waste management

Page 10: Manual Saphir LB10 S22 Eng V1_2x

10/10

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 1 Overview

1.7 Abbreviations

DIL-switch Several small switches built together to form a component.

ES End point of summer compensation EW End point of winter compensation FS Starting point of summer compensation

FU Frequency converter FW Starting point of winter compensation

HMI Human Machine Interface (operating unit) KP Gain factor (P-effect) LCD Liquid crystal display LED Light emitting diode MEU Switching to max. economy NC Normally Closed (opening contact) NO Normally Open (closing contact) SA Switching interval SD Switching differential Ss Total summer compensation at end point Es

Sw Total winter compensation at end point Ew

TA Outside temperature

TD Derivation time (D-time) TN Integral action time (I-time)

TR Room or exhaust air temperature

t Time tPmin Min. operating time circulation pump wc Setpoint of cooling wR Setpoint of room or exhaust air temperature ww Setpoint of Frost protection (alarm limit) wz Setpoint of supply air temperature

Y Continuous control signal p Pressure difference w Reference value displacement ventilation G Supply voltage AC24V, system potential G0 Supply voltage, system neutral M Measuring neutral B Measuring Z Measuring, multi function input

Page 11: Manual Saphir LB10 S22 Eng V1_2x

11/11

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 2 Installation, Connection

2 Installation, Connection

2.1 Installation procedure

2.1.1 Process unit

ACX36.xxx/ALG is intended for installation in panels and is installed on a DIN-rail. If voltages higher than AC 29 V (e.g. AC 240 V) are connected to the low-voltage terminal blocks by mistake, the entire apparatus will be destroyed. The electrical connection must take place in the following order: First connect all peripheral equipment and then the supply voltage.

2.1.2 HMI (Operating unit)

When integrating HMI, the following instructions apply: 1. The required hole for integrating

HMI is 135.5 x 87.5 mm. The unit�s front dimensions are 153.5 x 99.3 mm.

87,5+0,5

0

135,

5+

0,5

0

3221

M01

2. Connect the cable and route it to

the rear of the recess. Screw the unit together.

When integrating HMI, make sure that the seal is placed securely in position on the front of the housing.

322

1Z0

1

Technical data regarding HMI can be found in data sheet CE1Q3221en.

STOP

Note

Page 12: Manual Saphir LB10 S22 Eng V1_2x

12/12

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 2 Installation, Connection

2.2 Connection instruction

2.2.1 Terminal blocks

3226

Z02

IO Function IO-Type Connection Relay outputs Q1 Pump / Electric heating Digital Q13, Q14 Q2 Cooling / DX Step 1 Digital Q23, Q24 Q3 Supply air fan Digital Q33, Q34 Q4 Exhaust air fan Digital Q43, Q44 Q5 Damper, Out / Smoke Digital Q53, Q54 Q6 Output A or A+B alarm Digital Q63, Q64 Analog outputs Y1 Heating 0 - 10 V Y1, M Y2 Cooling / DX Step 2* 0 - 10 V Y2, M

Digital inputs D1 Alarm heating Digital D1, M D2 Alarm AUX 1 Digital D2, M D3 Alarm AUX 2 / Control input Digital D3, M D4 Alarm fire / Emergency stop Digital D4, M D5 Alarm fans Digital D5, M Universal inputs X1 Room / Exhaust air temp Ni1000 X1, M X2 Supply air temp Ni1000 X2, M X3 Outdoor temp Ni1000 X3, M X4 Frost temp / External frost unit Ni1000 / Dig X4, M X5 Multifunction input 1 X5, M X6 Control signal FC1, Supply air fan 0 - 10 V X6, M X7 Control signal FC2, Exhaust air fan 0 - 10 V X7, M X8 Control signal HRC 0 - 10 V X8, M

CP Roomunit PPS2 CP+, CP- * Via 10VDC voltage relay e.g. Styrelec RB111V-12VDC

Page 13: Manual Saphir LB10 S22 Eng V1_2x

13/13

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 2 Installation, Connection

2.2.2 Connection instruction

To connect external components to the process unit, these instructions must be followed.

Power Supply

G 0

24V AC ±10 %20 VA

230V AC 50/60 Hz

Digital Inputs

1 MDx

2 3 M 4

Fast inputs MAX 50 Hz

5 M

Digital Outputs

3 4

Q1x-Q6x

3 4 3 4 3 4

AC 24...230 V, MAX 4A

Analog Outputs

1 M 2Yx

G 0 Y G 0 Y

G

G0

0-10 V DC

Universal Inputs

1 MXx

2 3 M 4 5 M 6 7 M 8

G M B

G

G0

NI1000 0-10V Signal Digital signals

Page 14: Manual Saphir LB10 S22 Eng V1_2x

14/14

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 2 Installation, Connection

Connection instruction for indication of smokedampers

Smoke dampers must be connected as the instruction above for correct functionality.

2.3 Action in the event of a fault

In the event of a fault in ACX36.xxx/ALG, the following checks must be carried out: Power supply 24 V AC Correct connection of the terminal blocks Correct connection of the peripheral units Fault diagnostics with the aid of LEDs on the front of the unit

If the fault cannot be rectified using these measures, the apparatus must be replaced and returned (via the supplier) to the factory. See also chapter 3, Alarm guide for a description of the alarm messages and other faults. Detailed information, for example with regard to installation and structure of ACX36.xxx/ALG, can be found in basic documentation SICLIMAT® SAPHIR (CE2P3226en).

STOP

Note

S2Closed Open OpenClosed

S4

S6

S4

S6

S1

S2

S1DI3

STxx STxx

Page 15: Manual Saphir LB10 S22 Eng V1_2x

15/15

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 3 Operation

3 Operation

3.1 Operation ACX84.910/ALG

Operating element Function

LCD display 8 rows / 20 chara.

Displays values and settings

Home button (F1)

Back to the start page, regardless of menu

Return button (F2)

Skips back one menu / Cancels and entry

Start/Stop button (F3)

Alternates between automatic/off position Green indication when the plant is on

Alarm button (F4)

Displays alarm list and acknowledgement of alarms Red indication when active alarms

Row selection buttons

Navigation in the menu and between parameters

Settings buttons Setting value (+ / -) and horizontal movement of the cursor in the current row

ENTER button Select value to be alter and confirms alteration (setting) of values and menu choices

Explanation

ENTER

+►

◄-

⌂ |

Page 16: Manual Saphir LB10 S22 Eng V1_2x

16/16

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 3 Operation

3.2 Menu system

3.2.1 Levels

Access to data is hierarchically divided between three levels: Operating level (level 0) Configuration level (level 1) Systemparameter level (level 3) At operating level, the end user can read and alter current plant values, statuses, reference values and time programs without having to specify a password.

By entering an approved password, access is gained to the configuration level, where it is possible to read and alter all values that are accessible at both configuration and operating level.

The parameter names are designations that describe the relevant parameter and that usually comprise composite abbreviations.

Examples. Actsetp Actual setpoint

The parameter names are followed by values that can be read and altered.

3.2.2 Password

The password function protects against access to data and comprises four digits that can be altered if necessary. The predefined password to access the configuration level (level 1) is: 1000 The predefined password to access the systemparameter level (level 3) is: 2000

After accessing the configuration level, the user can alter the password by selecting �Change password� under the �Password� function row. Level 2 and 4 should be used for user defined passwords to have the predefined password left. The password level below the level used for entering the system can be changed If the factory-set password is altered, the predefined password is no longer present. To reset the password, a higher password is required. Contact the supplier.

3.2.3 Menus

In the parameter overview section and in the description section, a grey-marked row provides information about the selected menus that lead from the start page to the parameter names or settings rows. Depending on the type of configuration, some parameters/menus are not used and consequently they are not displayed in HMI. The parameters/menus that are listed and described in this basic documentation retain the same order, however. Some parameters also have different options depending on the configuration.

Operating level

Configuration level Systemparameter level

Predefined password

User-defined password

Note

Page 17: Manual Saphir LB10 S22 Eng V1_2x

17/17

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 3 Operation

3.2.4 Overview menu tree

Operating level

Configuration level

System adjustments

Page 18: Manual Saphir LB10 S22 Eng V1_2x

18/18

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 3 Operation

3.2.5 Navigate

Navigating and setting parameters takes place in the same way in all menus and for all levels.

Navigate by placing the cursor on a row using the row selection buttons ▲

▼ (6). This choice is then confirmed with ENTER (8).

Select a value with ENTER (8) and change the value with the settings buttons

+►

◄- (7).

Then confirm the choice with ENTER (8).

The settings buttons

+►

◄- (7) are also used to move horizontally between different

parameters. - A value with a black cursor:

Shows values that can be changed. - A flashing value with a black dashed cursor:

Shows the cursor�s position. The value can be altered after confirmation with ENTER (8).

The value can then be altered using the settings buttons

+►

◄- (7).

Confirm with ENTER (8). - A value without a dashed cursor:

The value can only be read. - Move the cursor horizontally (sideways);

Use the settings buttons

+►

◄- (7).

+ = to the right / - = to the left

The return button moves you one menu up, or interrupts an entry.

The Home button ⌂ moves you back to the start page. Enter password and setting for current date and time.

OP information

Menu

Log in

1. Using the row selection buttons (6), move to �Log In� and confirm with Enter (8).

No logging in is required for operating level.

Log in

0***

2. Press Enter (8) again to display the first figure (0).

Specify the first figure for the code with the settings buttons (7) and confirm with Enter (8).

Specify the remaining three figures in the same way.

When the last figure has been confirmed with Enter, the cursor returns to the first row on the start page. The same applies when an invalid code word is entered.

Example.

ENTER

+►

◄-

⌂ |

Page 19: Manual Saphir LB10 S22 Eng V1_2x

19/19

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 3 Operation

3. Using the row selection buttons (6), move to �Menu� and confirm with Enter (8).

Sheduler

Setpoints

Operation status

Alarm history

4. Using the row selection buttons (6), select the corresponding menu(s) and confirm with Enter (8) in order to proceed in the menu tree and display the parameter names. To set the current date and time, select �Time channel�.

The name of the most recently selected menu is displayed in brackets with asterisks (*xyz*) on the top row.

15.09.2001 15:09:21

Daytime scheduler

Weektime scheduler

Yeartime scheduler

5. Select a parameter with the row selection buttons (6) and select with Enter (8), then alter the value with the settings buttons (7) and confirm with Enter (8) again.

If the value comprises several parts, as in the example here, you can move to the next part of the value using the settings buttons (7). Alter the value as above and confirm this.

3.3 Start/stop button (service switch)

When the Start/Stop button | (4) is pressed, the unit stops. The current position is

displayed at the top of the �Operating information� menu on the row �*Service switch:�.

OP information

Menu

Log in

* Service switch: Stop * Opmode: Exhaust * Fanmode: Exhaust * Control type: Room

By pressing | again, the service switch returns to auto, i.e. the unit starts if this is

allowed by the time control program or control input. If the time scheduler is override by the OP mode switch (see chapter 4) �Manu� is displayed. The green LED indicates when the plant is on.

3.4 Alarm button

In order to get a simple overview of the active alarms, there is an alarm list that displays the current alarms (max. 15 alarms). A new alarm is indicated by means of a flashing red LED.

The alarm list is accessed by pressing the alarm button

(5) once. Browse through the list using the row selection buttons (6). Press the button again to acknowledge all alarms. This also causes the red LED to glow steadily. To reset the alarm after an alarm has been rectified, press the alarm button once more, which will extinguish the LED. If any alarms remain, the red LED will continue to lit.

Exit the alarm list using the home button ⌂

(2).

ENTER

+►

◄-

⌂ |

Page 20: Manual Saphir LB10 S22 Eng V1_2x

20/20

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 3 Operation

3.5 Alarm management

In the event of alarms or incorrect operation of HMI, and LED flashes next to the alarm button on the HMI panel. See the section above for information about how to view the alarm list and reset alarms, as well as the alarm guide below. Alarms can be configured as A, B or C alarms where A has the highest priority and C has the lowest. C-alarms are only shown in the display and not via the combined alarm output

The following differences exist between the two alarm types: Priority A Priority B

The plant is switched off Disconnection of cooling machine Other B alarms only alarm indication

Must be acknowledged manually. The plant is then switched on again.

The deactivated plant element goes back into operation when the fault has been rectified. The fault is no longer indicated under the alarm menu, but the LCD continues to flash. The alarm must now also be acknowledged manually.

Indication under A alarm Indication under B alarm

3.5.1 Alarm guide

Use the alarm button to view the alarm list and to acknowledge and reset alarms. Below are possible alarm messages and proposed actions/causes.

Read off the alarm on the handheld terminal. Check the connection on the terminal block. Check the component from where the alarm originates. Check the connection to the component. Check the contact function for the digital alarms in the regulator, compare with

diagrams and components. Check the parameter setting.

Alarm Cause Action Temperature sensor alarm (Supply, Room/Exhaust, Outdoor, Frost, Multi-function)

Sensor not connected. Sensor connected in wrong pos. Open-circuit in measuring circuit. Short-circuit in measuring circuit. Incorrect sensor type connected.

Check the sensor�s connection against wiring diagram. Check the sensor�s connection against wiring diagram. Check for an open-circuit in the sensor cable. Check for a short-circuit in the sensor cable. Check that the sensor is type LG-Ni1000.

Waterfrost alarm Water temperature too low. Alarm from external frost unit. Incorrect alarm input contact funct.

Return water temperature may not drop below set value. Check that hot water is reaching the unit. Check that the circulation pump is in operation. Check that the heater valve has a signal and is working. Check that the heater battery is intact and not leaking. Check the frost unit. Reset if necessary If the input is configured NC, configure as NO.

Firesmoke alarm Alarm from a smokedetektor or fire central Incorrect alarm input contact funct.

Check the smoke detector unit or the fire central If the input is configured NC, configure as NO.

General

Differences

General

Alarm guide

Page 21: Manual Saphir LB10 S22 Eng V1_2x

21/21

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 3 Operation

Alarm Cause Action HRC alarm

The drive belt has come off or is slipping. The magnet is not directly opposite the rotation guard. Incorrect alarm input contact funct.

Check the drive belt to the rotor. Check the position of the magnet and the rotation guard, adjust if necessary. If the input is configured NC, configure as NO.

Pump/Heater alarm The pump don�t run. El.heat is not correctly connected. Incorrect alarm input contact funct.

Check whether the fuses have tripped. Reset if necessary. Check that the motion function is activated. Check the connection against the wiring diagram. If the input is configured NC, configure as NO.

Cooler alarm The pump/cooling machine don�t run. Incorrect alarm input contact funct.

Check whether the fuses have tripped. Reset if necessary. If the input is configured NC, configure as NO.

Filter alarm (filter detector)

The filters are dirty. The filter detector is incorrectly connected. Incorrect alarm input contact funct.

Replace the filters! Check the filter detector�s connection against the wiring diagram and check pressure connectors and alarm limit. If the input is configured NC, configure as NO.

Flow alarm The fans don�t run. The pressure hoses are incorrectly connected. Alarm limit incorrectly set. Incorrect alarm input contact funct.

Check whether the fuses have tripped. Reset if necessary. Check that all the connections are securely in place, and that there are no kinks in the hoses. Check that hoses are connected to the correct terminal. Check the alarm limit. If the input is configured NC, configure as NO.

Fan alarm

The fans don�t run. Alarm from a frequency converter Incorrect alarm input contact funct.

Check whether the automatic fuses have tripped. Reset if necessary. Check the FC. Reset if necessary. In some cases the power to the FC must be switched off and on again. If the input is configured NC, configure as NO.

Override unit alarm An output is being overridden in manual mode. The service switch are in Stop.

Set the relevant output to auto.

Alarm run counter The unit�s operating time has exceeded the set alarm limit.

Reset the operating time counter or raise the alarm limit for the operating time.

Efficiency alarm (Low efficiency)

Eff. rating measuring activated. Multifunction is incorrectly set. Sensor incorrectly positioned. Alarm limit set too high.

Deactivate the efficiency rating measuring in the regulator. Change function of the Multifunction input. Change the position or function of the multifunction. Adjust the alarm limit setting.

HRC press alarm Pressure over heat exchanger too high.

Check that heat exchanger is operating at min. speed and that it is defrosting. Check the pressure switch�s connection and setting.

HRC frost alarm Temperature too low. Alarm limit set too high. Sensor incorrectly positioned. Multifunction is incorrectly set.

Check the defrosting function. Adjust the alarm limit setting. Alter the positioning. Change function of the Multifunction input.

Room unit alarm The room unit is not connected. Check the connection against the wiring diagram. Smoke damper alarm Dampers are in wrong position.

Wrong connection. Run a test and check all dampers. Dampers must be connected as the description in this manual.

�Error! No in sequence occurred, while writing to datapoint�

Time schedulers must be performed in chronological order.

Enter schedule in chronological order.

Page 22: Manual Saphir LB10 S22 Eng V1_2x

22/22

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 4 Description of the operating level

4 Description of the operating level Password for level 1 is required to change some of the parameters.

4.1 Date/time

Menu / Scheduler Display and setting of current date (dd.mm.yyyy) and time (hh.mm.ss).

4.2 Time switch program (Scheduler)

ACX36.xxx/ALG is equipped with a time switch program with four independent switching times per day that apply to all days (day program), six possible exceptions from the day program per week (week program) and ten possible exceptions from both the day and the week program per year (year program). In order to execute switching, the row must be activated. Don�t forget to deactivate the times that are not used. The time entries must be in chronological order. Depending on configuration, Stage 2 is available as an option. Fan speed Operating

program Off Off Low speed/On St1 High speed St2

4.2.1 Day program

Menu / Scheduler / Daytimescheduler The day program can handle four independent switching times per day. Time and fan speed are set for each switch. Example of a possible setting of a day program with a 2-speed fan:

Switching alternative

Switching time Operating method

Activation

T1 08:00 St1 Actv T2 10:00 St2 Actv T3 17:00 St1 Actv T4 20:00 Off Actv The day program applies to all weekdays, and the times that are used for most days are set here. On the row �Week program�, however, six exceptions from the day program can be entered, such as different times for the weekend. When making the setting, note that switching (�./Actv) may not be activated until after the values have bee set.

Description

General

Code entry

Description

Example

Note

Page 23: Manual Saphir LB10 S22 Eng V1_2x

23/23

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 4 Description of the operating level

4.2.2 Week program

Menu / Scheduler / Weektimescheduler The week program is used for six optional exceptions from the day program. The day program is active until the starting time for the week program and is reactivated immediately after the closing time for the week program. Example of a possible setting of a week program with a 2-speed fan:

Switc

hing

al

tern

ativ

e

Con

nect

ion

day

Tim

e O

n

Dis

conn

ectio

n da

y

Tim

e O

ff

Ope

ratin

g m

etho

d

Act

ivat

ion

T1 Sat 08:00 Sat 20:00 St1 Actv T2 Sun 08:00 Sun 20:00 Off Actv T3 Mon 12:00 Mon 12:01 Off ---- T3 � T6 are not used as Release is not active. When making the setting, note that switching (�./Actv) may not be activated until after weekday (Mon�Sun), time (hours/minutes) and fan speed (Off, 1, 2, 3) have been set. A switching alternative is defined for a connection day and time, as well as for a disconnection day and time.

4.2.3 Year program

Menu / Scheduler / Yeartimescheduler The year program is used to create exceptions from the day and week programs. Ten entries exist, T1-T5 and T6-T10. The day or week programs is active until the starting time for the year program, and the relevant program is reactivated immediately after the closing time for the year program. Example of a possible setting of a week program with a 2-speed fan:

T2 � T5 are not used as the rows are not activated. When making the setting, note that the rows may not be activated until after all the parameters in the relevant switching alternative have been set.

Description

Example

Description

Example

Switc

hing

al

tern

ativ

e

Con

nect

ion

day

Con

nect

ion

mon

th

Tim

e O

n

Ope

ratin

g m

etho

d D

isco

nnec

tion

day

Dis

conn

ectio

n m

onth

Tim

e O

ff

Act

ivat

ion

T1 24 12 01:00 Off 25 12 23:00 Actv T2 12 11 12:00 Off 12 11 12:01 ----

Page 24: Manual Saphir LB10 S22 Eng V1_2x

24/24

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 4 Description of the operating level

4.2.4 Example Time switch program

As the day program applies to all days, it is possible to both give consideration to and utilise the times when setting the week program and year program. Activation is set to Actv for the switching occasions that are to apply. Example of a possible setting of a week program with a 2-speed fan:

Weekdays: 07:00...10:00 St1, 10:00...20:00 St2 (apart from Wednesdays) Wednesdays: 12:00...21:00 St2 Saturdays: 05:00...14:00 St1 Sundays and other times unit switched off.

The day program is set at the most widely used time (07:00 St1, 10:00 St2, 20:00 Off) Switching alternative

Switching time Operating method

Activation

T1 07:00 St1 Actv T2 10:00 St2 Actv T3 20:00 Off Actv

The week program is set for all exceptions from the day schedule. Wednesdays (12:00 St2, 21:00 Off) As the day program always starts the unit at 07:00, consideration must first be given to that time and only then may an exception be made in the morning. The Starting time must then be some time before the starting time for the day program. The day program is then used in the day and a new exception made in the evening in order to achieve extended operation. The Starting time for extending a similar operating stage to the day program can then start at some time during the time of the day program. No time for Stop is required as the day program takes over immediately at the closing time for the exception and the day program�s setting at this time is already Off. Saturdays (05:00 St1, 14:00 Off), Sundays (Off) As the day program first starts the unit at 07:00 and then also sets the unit to St2 10:00, an exception can then be made for the whole of the Saturday�s operation. Finally, a new exception must be made at the same time as the closing time for the exception before in order for the unit to stop at 14:00, the exception can also be the whole of the Sunday as the unit should be Off from Saturday 14:00 to Monday 07:00. The Closing time for the Sunday must then be after the closing time for the day program.

Switc

hing

al

tern

ativ

e

Con

nect

ion

day

Tim

e O

n

Dis

conn

ectio

n da

y

Tim

e O

ff

Ope

ratin

g m

etho

d

Act

ivat

ion

T1 Wed 01:00 Wed 12:00 Off Actv T2 Wed 19:00 Wed 21:00 St2 Actv T3 Sat 05:00 Sat 14:00 St1 Actv T4 Sat 14:00 Sun 23:00 Off Actv T5 Mon 12:00 Mon 12:01 Off ----

Description

Example

Page 25: Manual Saphir LB10 S22 Eng V1_2x

25/25

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 4 Description of the operating level

4.2.5 Override time switch program

Menu / Scheduler / Override For easy stop and start of the unit or to control the unit from a BMS system, the time switch program can be overridden instead of change in the time program. When the unit is overridden it remains in the desired position, until it sets back to �Auto� and the time switch program has the control again. Operating switch (Opmodeswi)

Overriding the time program, in order to stop or start the unit in the selected position. In auto mode the unit is placed in operation in accordance with the time program, in other modes the time program is overridden to the desired position. However, night mode, control inputs and the service switch on HMI have a higher priority than the operating switch. Displayed at the �Serviceswitch� as �Manu� when override. BMS override

The time switch program can be overridden via communication from a BMS system. This parameter shows the actual state, controlled from the BMS system. In auto mode the unit is placed in operation in accordance with the time program, in other modes the time program is overridden to the desired position. However, the operating switch, night mode, control inputs and the service switch on HMI have a higher priority than BMS override. This parameter can be reset to Auto from the HMI if the communication to the BMS system goes down. Contact the manufacturer for a higher password.

4.2.6 Current scheduler

Menu / Scheduler Shows the current mode from the time switch program with consideration to Dayprogram, Weekprogram, Yearprogram, BMS override and the Operating switch in priority where the Dayprogram have the lowest priority and the Operating switch have the highest priority.

Description

Parameters

Note

Description

Page 26: Manual Saphir LB10 S22 Eng V1_2x

26/26

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 4 Description of the operating level

4.3 Setpoints

Setpoints to optain the right functionality, temperature and flow. Only active parameters and menus are displayed, depending of configuration.

4.3.1 Temperature control

Menu / Setpoints / Temperature control Display and setting of temperature setpoints. The setpoints for the current main sensor, depending on the selected control type and main sensor. Current setpoint for cooling is displayed, as well as the dead zone setting for cooling, but have no influence in the application if no cooling is selected. - Control (Shows actual main sensor)

May be changed if Cascade/Supply control mode is selected or if there is a main sensor fault.

- Current setpoints for heating, cooling - Current actual value for the main sensor - Setting of Basic setpoint (heating) - Setting of Dead zone cooling - Setting of compensation of basic setpoint when changeover to supply control if

Cascade/Supply control mode is selected. - Current External setpoint (Compensation or main setpoint)

4.3.2 Min/Max supply air temperature for cascade control

Menu / Setpoints / Min/max supplytemp Display and setting of Min and Max temperature for the supply air sensor. The menu is only displayed if cascade control mode is selected. - Type of min./max-limitation for the supply air temperature (see below) - Current setpoints heating, cooling for supply air sensor - Current actual value supply air temperature - Min supply air setpoint - Max supply air setpoint - Delta max. difference with sliding max.limitation (Heating diff) - Delta min. difference with sliding min.limitation (Cooling diff) Type of min/max limitation

In most control cases, fixed limitation is used, but for displacement ventilation with so-called low-impulse units, a different temperature control is required than with normal ventilation. A cascade control with sliding supply air limit (differential temperature control) is then used, instead of fixed limit temperatures for the supply air.

General

Description

Parameters

Description

Parameters

Description

Page 27: Manual Saphir LB10 S22 Eng V1_2x

27/27

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 4 Description of the operating level

The supply air temperature�s sliding limits are calculated depending on the current room temperature, whereupon the supply air temperature may vary at most within the min. and max. limits� calculated values.

Min/maxlimit

Parameter for selection of fixed or sliding limitation (differential temperature control). Delta Max. limit

Input of the maximum difference between supply air temperature and room temperature for the upper limit. Delta min. limit

Input of the maximum difference between supply air temperature and room temperature for the lower limit.

4.3.3 Fan speed

Menu / Setpoints / Fanspeed Display and setting of setpoints for fixed speeds (output signals) to a frequency converter. Depending on configuration, Stage 2 is available as an option. - Setting of fixed signal for the supply air fan in low/high-speed operation - Setting of fixed signal for the extract air fan in low/high-speed operation

Parameters

Description

T [°C]

t

28

16

Max.limit of supply air temperature (MaxSupplyAirTemp)

Sliding limits

Heating diff.

Cooling diff.

Min. limit of supply air temperature (MinSupplyairTemp)

Room temperature

3221D12D

Page 28: Manual Saphir LB10 S22 Eng V1_2x

28/28

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 4 Description of the operating level

4.4 Operation status

Indication of in- and output signals. Individual control of output signals. Only active parameters and menus are displayed, depending of configuration.

4.4.1 Digital inputs

Menu / Operation status / Inputs digital Actual status for digital input signals. Control inputs, (Timer inputs)

A timer or a push-button can be connected to the control input. These outside components can override other control sources (time program, operating switch, night mode, etc.) except in the event of alarms. When the control input is not used, the plant operates with fan speed �Automatic�.

See the section in configuration level for more information about the settings.

The Control inputs parameter indicates the current position of the control input.

Fan speed Indication

Automatic Auto Off Stop Low speed/On Step1 High speed Step2

Service switch HMI [ServiceswHMI]

The plant can be stopped by pressing the Start/Stop button on the HMI. This signal always has the highest priority. The Service switch parameter indicates the current position of the start/stop button on the HMI.

Emergency stop

The plant can be stopped via an external signal. The emergency stop may stop the unit without overrun and close the out damper without delay. Status for alarm inputs

- Fire/Smoke - HRC - Pump/Heater - Cooling - AUX - Filter - HRC pressure guard - Smoke damper - Fan - Flow - External frost protection

General

Description

Parameters

Page 29: Manual Saphir LB10 S22 Eng V1_2x

29/29

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 4 Description of the operating level

4.4.2 Measurement values

Menu / Operation status / Actual values Indicates the current actual value for measurement values.

- Outside temperature - Supply air temperature - Room/Exhaust air temperature - Room unit - Frost protection temperature - Multifunction sensor 1 (text is depending of selected function) - External setpoint

4.4.3 Outputs, digital

Menu / Operation status / Output digital Indicates and controls digital outputs. Control/overriding of the outputs can only take place after logging in, in this event, first put the output in manual mode and then select the mode for the output.

- Circulation pump heating, electric heater - Circulation pump cooling, cooling machine, DX step1 - Cooling DX step2 - Supply air fan - Exhaust air fan - Out damper - Smoke damper - Alarm output A - Alarm output B

4.4.4 Control outputs

Menu / Operation status / Output control signals Indicates and controls the current control outputs Control/overriding of the outputs can only take place after logging in, in this event, first put the output in manual mode and then select the mode for the output.

- Control signal cooling - Control signal heating recovery (in event of PWM control, the control signal is

converted to a digital output with various time intervals depending on the current control signal)

- Control signal heating - Control signal supply air fan - Control signal Exhaust air fan

Description

Parameters

Description

Parameters

Description

Parameters

Page 30: Manual Saphir LB10 S22 Eng V1_2x

30/30

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 4 Description of the operating level

4.4.5 Operationcounter

Menu / Operation status / Operation counter The Operating time meter parameter indicates the sum of the fan�s operating hours starting from the time the regulator is commissioned or the last count reset. With the Reset Counter parameter, the sum of the fan�s operating hours can be zeroed. The operating time meter can be reset directly at this level after logging in.

4.4.6 Test smoke damper

Menu / Operation status / Test smokedamper Activation takes place by setting AUX input 2 to �IndDamper�. A smoke damper test runs at the selectable time, at manual test and if �Outdamper� are selected it runs at every start/stop of the unit as well. Fixed delay time to stop fans before dampers and to open dampers before fan start. Should a damper assume an incorrect position (detected via limit positions contacts), an alarm will be issued. Smoke dampers must be connected as the instruction for correct functionality. See sections in configuration level for more information about settings and configuration.

- Testsmokedamper (manual test) - Damperkick (current time for automatic test)

4.4.7 Efficiency rating

Menu / Operating status / HRC Efficiency Indicates current efficiency rating value. Activation takes place by setting Multifunction input 1 to �SupplytempHRC� or �Usedairtemp�. See the section in configuration level for more information about the settings. The calculation can then take place in two ways: Supply air: Efficiency rating = (Supply air � Outside) / (Exhaust air� Outside) Used air: Efficiency rating = (Exhaust air � Used air) / (Exhaust air � Outside) Prerequisites for the calculation of efficiency are as follows:

Exhaust air temperature � Outside temperature > 5C Output signal HRC > 99% The fans must be in operation Exhaust sensor, Outside sensor and sensor for calculation must be activated

Description

Note

Description

Note

Parameters

Description

Prerequisites

Page 31: Manual Saphir LB10 S22 Eng V1_2x

31/31

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 4 Description of the operating level

4.5 Alarm history

Menu / Alarm history Indication of the 15 most recent alarms. This applies both to active and rectified alarms. The time when the alarm was generated is also indicated. Resetting Alarm history

By changing parameter �No� to �Yes�, the entire list is emptied of information. NOTE! In order to view current information, it is necessary to exit the menu and then enter it again.

4.6 Password

Menu / Password function The �Password� menu contains the following functions:

Log in

Entering password with 4 characters. Access to the individual menus is dependent on the selected code word level. (Log In is also available on the first page)

Log Out

The password is reset, the background lighting is switched off.

Change password

A user-defined password can be entered. It is possible to change the password level that is lower than that used for access to the system. This means: Users who have access on level 3 can change the user-defined code word at level 2. The factory-set password (1000) can be changed if the user has mistakenly chosen level 1 instead of level 2 (user-defined code word). For new activation of the pre-set code word, the regulator must be restarted! Current stage (level)

Indicates the current password level.

4.7 Application information

Menu / Application info Information about the plant, can be used to enter plant-specific information. When entering information, the text must be concluded with an exclamation mark (!) in order for it to be saved.

Description

Parameters

Note

Description

Parameters

Description

Note

Page 32: Manual Saphir LB10 S22 Eng V1_2x

32/32

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

5 Description of configuration level Configuration level is displayed after logging in to level 1.

5.1 Functions, Configuration

The following parameters are also present at a Commissioning guide that may be used at a first configuration. The guide is displayed at the start page if a configuration not has been done. The guide contains besides the following parameters also settings for Language, HMI type and Time adjustment, see separately sections for those settings. Menu / Configuration / Functions Settings for control function, type of fan, damper, heating, heat recovery and cooling, and selection of alarm and sensor inputs.

5.1.1 Application

The application is prepared to handle several variants, with various function set-ups depending on variant. Only one variant is available in this version. Macro 1 Air handling unit with separate starting of supply and exhaust air fans,

separate analog outputs for frequency controller. Three control sequences.

5.1.2 Configuration of temperature control (Control mode)

Adaptation of the regulator for different types of control. This applies to the choice of main sensor, which can be a room sensor/unit, exhaust air sensor or supply air sensor. When selecting cascade control, it is also necessary for room or exhaust air sensor to be selected. When selecting constant supply air control, a room or exhaust air sensor can be used for measurement/night operation etc. or can be deactivated. Three different control modes can be selected:

Cascade control with limits for the supply air temperature. Constant supply air control. Climate adapted Cascade+Supply air control. Cascade control in summer and

constant supply air control in winter. It is also possible to select between two different types of cascade control, see section �Min/Max supplytemperature� for settings options of fixed or sliding limitation (differential temperature control). When selecting cascade control and a fault occurs in the main sensor or if a mainsensor is missing (room/exhaust air sensor), supply air temperature control is activated automatically to ensure that incorrect control values are not obtained. Main sensor is selected automatically but if both a Roomunit and an Exhaust air sensor is activated, then the main sensor can be selected in section �Cascade control�.

Commissioning

General

Description

Description

Page 33: Manual Saphir LB10 S22 Eng V1_2x

33/33

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

Control function 1 � Cascade control

In the case of control mode 1, the room temperature is maintained at a constant level. The control loop for the room/exhaust air generates the set point for the control loop for the supply air. The supply air temperature regulator then controls the output signals for the relevant heating/cooling sequences. The limits for the supply air temperature (Min temperature and Max temperature) guarantee that the supply air temperature is maintained within the set range. Can be selected with fixed or sliding limitation (differential temperature control). Control function 2 � Supply air control

In the case of supply air temperature control, the supply air temperature is maintained at a constant level. Control function 3 � Cascade+Supply air control

In the case of Cascade+Supply air control, the temperature is controlled by a cascade controller in the winter and a supply air controller in the summer. Can be selected with fixed or sliding limitation (differential temperature control). See section �Cascade control� for switch-over conditions.

5.1.3 Type of cooling, heat recovery and heating

Configuration for different types of cooling, heat recovery and heating. Selection of cooling

Type of cooling that is used. None No cooling function Water Digital output gets pump function which starts when valve opens or at pump kick operation. The pump may also run continuously. (See section for pump) DX-1Step Digital output gets On/Off function and pump kick is blocked. Analog output works simultaneous between 0-10V DX-2Step Digital output and analog output get On/Off function NOTE! Voltage relay required for analog output. DX-Binary Digital output and analog output get On/Off function. The function is binary in order to supply a third step. NOTE! Voltage relay required for analog output. At DX cooling, the steps start when the cooling signal exceed the set values. This does not apply to DX-binary since those steps are set with a fixed switching differential.

Functions

Description

Parameter

Functions

Note

Page 34: Manual Saphir LB10 S22 Eng V1_2x

34/34

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

Selection of heat recovery

Type of heat recovery that is used. None No recovery function Rot-HRC (Rotary heat exchanger) Activates the output for the heat recovery so it works as heating sequence. RecircAir Activates the output for return air damper so it works as cooling sequence. Plate-HRC (Plate heat exchanger) Activates the output for the heat recovery so it works as heating sequence. With the unit stopped, the output signal will be controlled to 100% in order to avoid cold shock in the water battery when start up. �HRC frost� or �Pressgrd� should also be selected at Multifunction 1 to have satisfactory performance. Water (Liquid-borne recovery) Activates the output for the heat recovery so it works as heating sequence. �HRC frost� should also be selected at Multifunction 1 to have satisfactory performance. HRC-PWM (Puls modulated rotary heat exchanger) Activates the output for the heat recovery so it works as heating sequence. Analog output get On/Off function where the control signal is converted to a digital output with different time intervals depending of current control signal. NOTE! Voltage relay required for analog output. Selection of heating

Type of air heater and any frost protection used. None No heating function ExtFrost (External frost protection) Frost protection deactivated and the input for frost sensor is configured as a digital alarm input for an external frost protection device. Pump functionality is activated. Water Frost protection function activated and digital output gets pump function. The pump starts on one of the following conditions: valve opens, outside temperature falls below 12°C, pump kick operation or pump set for continuous operation. See section for pump. Electric Digital output activated at output signal to electrical battery. Pump kick operation and frost protection function blocked. Max limit of control signal for each fan step.

5.1.4 Selection of fan control

Type of fan control. FreqvInv1St / FreqvInv2St The fans are controlled with a fixed control signal to a frequency converter. 1- or 2 step. Analog outputs for each fan with separately setpoints . Direct1St Control of direct driven fans, 1-step mode.

Parameter

Functions

Parameter

Functions

Description

Functions

Page 35: Manual Saphir LB10 S22 Eng V1_2x

35/35

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

5.1.5 Selection of Multi-function input 1

Parameters to select function for multi-function input 1. None No function ExtSetpPas Activates external setpoint with a Ni1000 element that can override or compensate the basic setpoint. See also section for External setpoint. ExtSetpAct Activates external setpoint with a 0-10V signal that can override or compensate the basic setpoint. See also section for External setpoint. HRC Frost Activates the freeze function for water-borne recovery or the defrosting function for flat plate heat exchanger via a temperature sensor. See also section for Heat recovery. HRC Pressgrd Activates the defrosting function for rotary and flat plate heat exchanger via a digital input. See also section for Heat recovery. Supplytemp HRC Activates efficiency measuring via sensors located after the HRC and before the heating battery (if any). See also section for HRC efficiency. Usedairtemp Activates efficiency measuring via sensors located in the usedair duct. See also section for HRC efficiency. AUX Temp Measuring function only. HRC Alarm Activates the HRC alarm.

Description

Functions

Page 36: Manual Saphir LB10 S22 Eng V1_2x

36/36

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

5.1.6 Selection of AUX alarm 1 and 2

Parameters for selecting alarm type at the AUX inputs 1 and 2. See also section for Alarm settings. None No function AUX (Only AUX 1) Alarm from a optional component Flowguard Alarm from a flowguard, the alarm is blocked when the unit is off. Filterguard Alarm from a filterguard Cooling Alarm from a cooling pump, cooling machine HRC Alarm from a rotary heat recovery unit or a puls from a rotation guard if HRC-PWM is selected. (Can also be selected at Multifunction input 1 in Macro 1) IndDamper (Only AUX 2) Activates the smoke damper function. See also section for Smoke damper. Timer (Only AUX 2) Input for external control, timer. See also section for Control inputs.

5.1.7 Selection of emergency stop or fire alarm

Selects if emergency stop functionality or fire alarm functionality shall be used Fire alarm Alarm from a fire alarm unit or a smoke detector unit. If the alarm is configured as a B-alarm, the unit will start up automatically after the reset of the external unit. If the alarm is configured as a A-alarm, the alarm must also be reset in the controller. Emergency stop The plant can be stopped via an external signal. The emergency stop may stop the unit without overrun and close the out damper without delay. (An alarm will NOT occur).

5.1.8 Damper functionality

Selection of damper functionality. Smoke damper can only be selected if the smoke damper function is activated. Out damper The damper (digital output) open when the unit starts and close after the set time when the unit stop, as well at smoke damper test if activated. Smoke damper The damper (digital output) are normally open and close only if a fire alarm occur or after a pre defined time at a smoke damper test. The out damper can be connected via a relay at the fan output for open/close when the unit start/stops.

Description

Functions

Description

Functions

Description

Functions

Page 37: Manual Saphir LB10 S22 Eng V1_2x

37/37

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

5.1.9 Selection of sensor

Selection of which sensors that are connected. Some configurations require one or more of these sensors

- Room or exhaust air sensor - Outside sensor - Roomunit

5.1.10 Save configuration

After reconfiguration, the regulator must be restarted to activate new types of input. Use the parameter �Save configuration� at the end of this menu, alternative turn the DIL2 switch off and on again, for restart. If the Commissioning guide has been used, it disappears from the startpage after the restart.

5.2 Sensors

Calibration of sensors. Only active parameters are displayed, depending of configuration.

5.2.1 Calibration of measurement values

Menu / Configuration / Sensor

A large number of different factors can cause a sensor�s measurement value to be incorrect. If this is the case, the measurement value can be corrected.

Parallel offset of the sensor graph with the set value After calibration, each measurement value shows the adjusted temperature

- Room/exhaust temp corr - Outtemp corr - Supplytemp corr - Frosttemp corr - Multifunction sensor 1 (text is depending of selected function)

Description

Parameters

Note

Description

Effect

Parameters

Page 38: Manual Saphir LB10 S22 Eng V1_2x

38/38

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

5.3 Alarm settings

Configuration and settings of alarms and alarmlimits to optain the right functionality. Only active parameters and menus are displayed, depending of configuration.

Priority list for all alarms and configuration possibilities: Alarm point Contact Delay Class Description Cooler NO / NC sec A/B/C Overload cooling pump or alarm

from cooling machine HRC NO / NC sec A/B/C Alarm from local control unit for

rotating heat exchanger Heater pump / overheating

NO / NC sec A/B/C Overload c-pump heating or overheating electric heating

Fan NO / NC sec A/B/C Overload/incorrect fan/frequency AUX NO / NC sec A/B/C Free alarm input 1 Filter NO / NC sec A/B/C Filter detector, pressure over filter Flow NO / NC sec A/B/C Flow detector over fan Flow startup � sec � Delay at start up HRC frost - sec A/B/C Low temperature in exhaust air or

return from battery at HRC Override unit - min A/B/C A component is operated manually

from HMI Temperature alarm

- min A/B/C Adjustable temperature deviation for supply air temperature

HRC pressure - min. A/B/C Alarm from pressure switch over heat exchanger

Low efficiency - min A/B/C Low HRC efficiency Outdoor sensor - - A/B/C Fault in sensor Frost sensor - - A/B/C Fault in sensor Supply sensor - - A/B/C Fault in sensor Room/Exh sen - - A/B/C Fault in sensor Multi 1 sensor - - A/B/C Fault in sensor Room unit - - B Fault in roomunit Smoke damper - - A/B/C Smoke damper in wrong position Fire and smoke NO / NC - A/B/C Alarm from central fire alarm Frost protection - - A Low return temperature air heater External frost NO / NC - A Alarm from an external frost unit Run counter - - B Service alarm when the unit has

exceeded the set operating time Emergency stop

NO / NC - - Emergency stop, not an alarm

See chapter 3 for a general description of alarm management, different between priortity and an alarm guide to follow in the event of an alarm.

General

Division

Example

Page 39: Manual Saphir LB10 S22 Eng V1_2x

39/39

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

5.3.1 Temperature alarm

Menu / Configuration / Alarms / Temp alarm

Settings for temperature deviation from the supply air set point and alarm limits for frost protection. Blocking temperature alarm (Deviation alarm)

When activating this parameter, the temperature alarm is blocked when the outside temperature exceeds 15°C. If no outdoor sensor is used the alarm is always blocked when activating the parameter. Alarm limit for temperature alarm (Deviation alarm)

Setting of alarm limit for deviation of supply air temperature, i.e. if the supply air sensor exceeds this set value for longer than the set delay, an alarm is generated. Setpoint triggered frost protection

If the temperature is below the set freeze limit, an A alarm is obtained, which also stops the unit. This parameter can also be found under section Heating. Setpoint for HRC frosting alarm

If the temperature drops below the set alarm value, a frost protection alarm is generated. This parameter can also be found under section Heat recovery.

5.3.2 Operationcounter

Menu / Configuration / Alarms / Operation counter The alarm limit can be used to request service, e.g. filter replacement.. Activation of Operating time alarm

Parameter for activation of operating time alarm, i.e. a B alarm is generated after the set time has been exceeded. Limit for operating time alarm

Setting of limit when operating time alarm will be generated. Run counter fans

The Operating time meter parameter indicates the sum of the fan�s operating hours starting from the time the regulator is commissioned or the last count reset. Run counter fans

With the Reset Counter parameter, the sum of the fan�s operating hours can be zeroed.

Description

Parameters

Description

Parameters

Page 40: Manual Saphir LB10 S22 Eng V1_2x

40/40

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

5.3.3 Setting contact function for alarm inputs

Menu / Configuration / Alarms / Directing of input

Selection regarding an alarm input must be of the type closing (NO) or opening (NC).

NO (Normally Open) The contact is open in the rest position and closes in the event of an alarm.

NC (Normally Closed) The contact is closed in the rest position and opens in the event of an alarm.

5.3.4 Alarm delay

Menu / Configuration / Alarms / Alarm delay

Parameters for individual alarm delay time for each alarm point. At start-up after a power failure there is a delay of 10 sec. before the alarm is activated. This is in order to avoid alarms generated by a slow start-up procedure.

5.3.5 Alarm class

Menu / Configuration / Alarms / Alarm class

Parameters for individual alarm class for each alarm point. Alarms can be configured to be either A, B or C alarm wher A have the highest priority and C the lowest. When an A alarm is selected, the unit is stopped when the alarm is activated.

5.3.6 Alarm output

Menu / Configuration / Alarms / Alarm output

Parameter for selecting whether only A alarms or both A and B alarms are to be indicated. The alarm outputs for the two parameters Alarm priority A and Alarm priority B are used for monitoring the operation of the entire plant. In this way, individual alarms are co-ordinated as a combined alarm, which is indicated as an alarm with either priority A or B. The combined alarm indicates that there is a fault in the plant, but not what the fault it. To ascertain this it is necessary to look in the alarm list.

5.3.7 HRC efficiency alarm

Menu / Configuration / Alarms / HRC efficiency

Setting of alarm limit for the HRC efficiency alarm, if the efficiency drop below the alarm limit an alarm is generated.

Description

Description

Note

Description

Description

Description

Page 41: Manual Saphir LB10 S22 Eng V1_2x

41/41

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

5.4 Regulator settings (Controllers)

The regulator is adapted to the control object with the following parameters: Proportional factor KP (transfer secondary value KR) I-time TN D-time TD

The control effect is optional: P, PI, PD or PID. The relationship between KP and P-bands is as follows: P-band = 100/KP For cooling sequence, a negative KP must be set. Unit: TN and TD in seconds; (the units are not displayed on HMI)

5.4.1 Controllers

Menu / Configuration / Controllers / Regulator settings for each regulator. Only active controllers are displayed, depending of configuration.

- Cascade controller - Cooling controller - HRC controller - Heating controller - Frost protection controller - HRC Frost controller

General

Description

Parameters

Page 42: Manual Saphir LB10 S22 Eng V1_2x

42/42

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

5.5 Control parameters

Settings for the functions belonging to the control in accordance with the configuration in control principle. Only active parameters and menus are displayed, depending of configuration.

5.5.1 Cooling

Menu / Configuration / Control parameters / Cooling

Settings to configure cooling optimally. Activate cooling

The cooling sequence is blocked at a lower outside temperature than the set value. The cooling sequence is always active if an outside sensor is missing. Max limit cooling at low speed

The cooling control signal is limited when the fans run at low speed. Start DX-cooling stage 1 and 2

Setting when DX-cooling stage is to be started. Not valid for DX-binary Stop DX-cooling stage 1 and 2

Setting when DX-cooling stage is to be stopped. Not valid for DX-binary Min time for restart of DX cooling

Delay before restart of DX cooling may take place. This delay avoids unnecessary switching of the DX steps off and on. This parameter is valid for all DX steps.

5.5.2 Heat recovery

Menu / Configuration / Control parameters / HRC

Depending on the selected function direction for output signal (damper or HRC) and measured difference between outside and room temperature, heat recovery is controlled optimally. Start-up time for heat exchanger

By controlling the exchanger to 100% at start-up, the exhaust air fan heats the heat exchanger, thereby preventing a cold shock in the water battery. When the unit is started at an outside temperature colder than 12oC or if an outside sensor is missing, the output signal is set to 100%. The heat exchanger returns to automatic mode, when the supply air fan has started and the selected start-up time has elapsed.

General

Description

Parameters

Description

Parameters

Page 43: Manual Saphir LB10 S22 Eng V1_2x

43/43

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

Activation of cooling recovery

Parameter for activation of cooling recovery. Cooling recovery means that, in the event that cooling is required and if the outside temperature is higher than the exhaust air temperature, recovery (heat exchanger) starts at full power in order to utilise the cooling energy from the room. The outside temperature is compared to the room/exhaust air temperature. When the outside air is warmer than the room air, the mixing damper is closed to the min limit, alternatively the HRC system is controlled 100%. If the outside air is colder than the room air, the mixing damper and the HRC system are controlled in the normal way.

Mixing damper or HRC system Room/exhaust air sensor and outside temperature sensor Parameter Cooling recovery set to �On�

Setpoint for protection against frosting

To protect the recovery circuit against icing, there is a built-in control function that, via a temperature sensor in the used air or the return line (when liquid-borne recovery is selected), ensures that the heat exchanger is defrosted. At low temperatures, the output signal to the heat recovery is reduced in order to defrost the heat exchanger. In the event the temperature falls even more, an alarm is generated (see Alarm frosting). When the Set point is achieved, the exhaust air is transported away immediately in order that the temperature at the exhaust air duct can increase again, thereby preventing icing.

Activate by set the parameter Multifunction input 1 to �HRC Frost�. Setpoint for frosting alarm

If the temperature drops below the set alarm value, a frost protection alarm is generated (see above). Max control signal at defrostning

If heat exchanger pressure switch is activated and this trips, the control signal to the heat exchanger will be decreased so that defrosting can take place. For on/off-rotor, the time for which the rotor rotates is limited. If the parameter is set to zero, the rotor stops entirely in the event of a tripped pressure switch.

Activate by set the parameter Multifunction input 1 to �Press grd�. Min. outside air volume at return air damper

The minimum outside air volume that is mixed with the return air is set with this parameter in the event that heat recovery is required. In the event a unit has stopped, the damper closes fully against outside air.

Parameters

General conditions

Effect

General conditions

General conditions

Page 44: Manual Saphir LB10 S22 Eng V1_2x

44/44

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

Start-up time return air

When the pre-heating time has expired, the fans start with outside and exhaust air dampers closed (full return air) for a set period of time (Start-up Time). This prevents cold outside air from blowing in at low outside temperatures.

Output signal for cooling is blocked The pump in the heating circuit is running Start-up of fans activated

The start-up time must be set higher than 0.0. In the event of plants with outside temperature sensors, the start-up control is

only activated at outside temperatures below 15°C. At outside temperatures above 15°C, the plant starts up normally, whereupon the damper can be controlled in the normal way.

In the event of start-ups caused by �Unoccupied heating� or �Night cooling�, there is no start-up control.

Only activated after a pre-heating time The recovery function (heat exchanger) must be set at the return air damper

5.5.3 Heating

Menu / Configuration / Control parameters / Heating

Settings to configure heating optimally. Preheating time

Water-heated air heaters are sensitive to frost. If the air conditioning unit is switched off at night and there are low outside temperatures at start-up, the sudden supply of cold outside air would cause the water in the pipes to freeze. This problem is particularly tangible in conjunction with 2-position dampers. In order to circumvent this, the water circuit is preheated with hot water before the outside and exhaust air damper is opened. At start-up, only the air heater�s heating circuit pump starts and the heating valve opens depending on the prevailing outside temperature for an adjustable period of time. The risk of freezing damage is eliminated, and the unit then switches to normal control. NOTE! When using a long pre-heating time, the result may be the opposite, i.e. the heater battery may get too warm, which causes the heater battery and the heat exchanger to close at start-up, since there is no longer any heat demand. This may cause great variations in the start-up.

The pump in the heating circuit is running The valve opens to 100%. Outside temperature sensor connected Preheating time > 0.0 s Outside temperature < 5 °C

Min. temperature air heater (water) during operation

Setting to prevent triggering of the frost protection. When there is a danger of the heater battery freezing, the sensor in the water return causes the valve actuator to open. This reference value is activated when the unit is in operation.

Parameters

Effect

General conditions

Description

Parameters

Note

Effect

General conditions

Page 45: Manual Saphir LB10 S22 Eng V1_2x

45/45

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

Keeping the air heater (water) warm when stopping

In the event of a stopped unit, the temperature in the air heater is controlled to the set point in order to prevent frost formation and make it easier for the unit to start up. Setpoint triggered frost protection

If the temperature is below the set freeze limit, an A alarm is obtained, which also stops the unit. Max signal stage 1 and 2

Gives max. limit for the signal for heating at the actual fan stage. (Only active in event of electric heating)

5.5.4 External setpoint

Menu / Configuration / Control parameters / External setpoint Configuration of the external setpoint to obtain the right functionality. An external setpoint unit can be connected to Multifunction input 1 or via a roomunit. The external setpoint from the roomunit is compensate the basic setpoint. Type of external setpoint

Selects if the external setpoint shall override or compensate the basic setpoint. Main setpoint The external setpoint overrides the set basic setpoint in the controller and the deadzone for cooling is refer to this setpoint instead. Compensation The external setpoint is compensate the basic setpoint in the controller according to predefined or the reference value. Min. reference value setting

Reference value at 0V in event an external setpoint is selected with active signal (0-10V). Can also be set to a negative value to be able to use compensation. Max. reference value setting

Reference value at 10V in event an external setpoint is selected with active signal (0-10V).

Parameters

Description

Parameters

Functions

Page 46: Manual Saphir LB10 S22 Eng V1_2x

46/46

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

5.5.5 Summer Winter compensation

Menu / Configuration / Control parameters / Smr Wntr Compensation Summer/winter compensation is used for automatic compensation of the basic setpoint as a function of the outside temperature.

Explanation

Ew

Sw

Fw FsEs

T [°C] A

w [K]Ss

322

1D05

FS

ES

SS

FW

EW

SW

TA

w

Starting point for summer

compensation

End point for summer compensation

Delta (total displacement) in K at end point ES

Starting point for winter compensation

End point for winter compensation

Delta (total displacement) in K at end point EW

Outside temperature

Reference value alteration

Delta not equal to 0.0 applies for activation of summer/winter compensation Outside sensor connected

Starting point summer compensation

Starting temperature at FS at which the basic setpoint compensation starts (proportional with the rising outside temperature). Stop point summer compensation

End temperature at ES at which the basic setpoint compensation is at the Max position (in relation to the delta). Delta summer compensation

Max. compensation of the basic setpoint. Starting point winter compensation

Starting temperature at FW at which the basic setpoint compensation starts (proportional with the falling outside temperature). Stop point winter compensation

End temperature at EW at which the basic setpoint compensation is at the Max position (in relation to the delta). Delta winter compensation

Max. displacement of the basic reference value (total displacement).

Description

Function diagram

General conditions

Parameters

Page 47: Manual Saphir LB10 S22 Eng V1_2x

47/47

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

5.5.6 Cascade control

Menu / Configuration / Control parameters / Cascade control Settings in the case of cascade control or cascade+supply air control to obtain right functionality. See also section for temperature control. Cascade sensor

Selection of main sensor if both a roomunit and a exhaust air sensor is connected.

Change between cascade/supply air control

With control type Casc/Supply (cascade control and supply air control) selected, the control types will shift depending on the outside temperature. To avoid pendulating between the control types, a selectable time must elapse before the change-over takes place. Cascade control normally use a higher setpoint than supply air control, therefore it is possible to compensate the basic setpoint for the cascade control when shifting to supply air control to avoid manually adjustment. In order to get the best result, the outside sensor should be placed on the facade and not in the outside air duct, where the sensor may be warmed up when the unit is switched off. Temperature compensation

When shifting to supply air control, the basic setpoint compensates to the set value. This parameter can also be found under section Setpoints. Change-over at set outside temperature

When the outside temperature falls below the set value, the control type changes to supply air control after a preset time. Change-over time delay

When the outside temperature falls below a set value, the control type changes to supply air control after the preset time.

Description

Parameters

Description

Note

Parameters

Page 48: Manual Saphir LB10 S22 Eng V1_2x

48/48

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

5.6 Parameters

Settings for other functions in accordance with configuration in control principle. Only active parameters and menus are displayed, depending of configuration.

5.6.1 Fan

Menu / Configuration / Parameters / Fan

Settings to obtain the right functionality for fans. Fan start delay

Setting of delay between the damper opens and the exhaust air fan starts. This delay time is also used to delay the damper to have the fans stopped before the damper close. If an A-alarm occur the damper close immediately. If the damper output is used for smoke dampers, this time can be set to 0sec. Start delay supply air fan

Setting of the time between start of exhaust air fan and permitted start of supply air fan. Overrun

In conjunction with an electric air heater, the fans operate to provide airing (adjustable time) in the event of normal unit stop. In the event of a fire alarm or when switching an emergency stop (optional), there is no airing. Fan function at fire

At a triggered fire alarm, the fans control to the selected operational state. Stop EX/SU Both fans are stopped. Run EX/SU Both fans runs on max speed. Stop EX The exhaust air fan is stopped and the supply air fan runs at max speed. Stop SU The supply air fan is stopped and the exhaust air fan runs at max speed.

General

Description

Parameters

Note

Functions

Page 49: Manual Saphir LB10 S22 Eng V1_2x

49/49

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

5.6.2 Fan compensation

Menu / Configuration / Parameters / Fan compensation

The fans can be compensated in different ways to make sure that the required temperature is maintained. Fan compensation is only available together with a 2-step fan. To avoid pendulating between fan steps, a selectable time must elapse before the change-over takes place. Type of fan compensation

Selects the type of fan compensation. None No function Block high speed When the outside temperature falls below the set value, the high speed (Step 2) is blocked. Cooling Principally used when there is no cooling battery. When cooling is needed, the fans runs at high speed (Step 2). This function don�t decrease the temperature but the well-being for the people in the room will, however, be greater, since the air turnover will be greater. Heating When the heating valve is fully open and there still is a need for heating, the fans reduce their speed to low-speed (Step 1). Compensation is deactivated after the set time and starts again if needed. Cool+Heat Both the heating and the cooling function are activated, see above Start delay

Time delay before fan compensation will be activated. Release delay

Time delay before fan compensation will be deactivated and goes back to normal control. Limit for outside temperature blocking of high speed operation

When the outside temperature drops below the set limit, high-speed (Step 2) operation of the fans is blocked.

General

Parameters

Functions

Page 50: Manual Saphir LB10 S22 Eng V1_2x

50/50

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

5.6.3 Pumps

Menu / Configuration / Parameters / Pump

The circulation pump for the heating circuit is controlled so that it is in operation at low outside temperature (12°C) and when heating is needed. The pump for cooling is controlled so that it is in operation when cooling is required. Activation of motion operation for cooling pump / Continuous operation

Activates movement of the pump for the cooling circuit to prevent the pump seizing. The movement takes place every Monday at 12:00. The pump can also be set in continuous operation. If DX cooling has been selected, the movement of the cooling pump is blocked and the output is activated when required. Activation of motion operation for c-pump heating / Continuous operation

Activates movement of the circulation pump for the heating circuit to prevent the pump seizing. The movement takes place every Monday at 12:00. The pump can also be set in continuous operation. With Electric heating selected, the movement operation is blocked and the output is only activated when required. Setting of minimum operating time for the pumps

Parameter for setting the minimum operating time for both the cooling pump and the circulation pump for the heating circuit.

5.6.4 Control inputs

Menu / Configuration / Parameters / Control input Parameters for setting function method for the control inputs. A timer or a push-button can be connected to one or both control inputs. These outside components can override the time switch program. Activate control input at AUX 2. Extended operating time via push-button/timer

Setting of operating time for extended operation. When a push-button is used for extended operation, the desired operating time is set using this parameter. When activated the fans runs at the selected step (see below) in the set time. If a timer (egg-timer) is used, this parameter must be set to 0 as the time function is then in the actual timer. Fuction of control input

Selection of function at activated control input. The unit can be stopped or be started at the selected fan step. Airing in event of external stop

Selection if airing of the electric battery must take place in event of external stop.

Description

Parameters

Parameters

Description

Note

Parameters

Page 51: Manual Saphir LB10 S22 Eng V1_2x

51/51

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

5.6.5 Unoccupied

Menu / Configuration / Parameters / Unoccupied mode

At the end of the occupancy time, the plant is switched off (via timeswitch program). The room temperature will then fall or rise, depending on the prevailing weather conditions and internal loads. The �Unoccupied heating mode� or �Unoccupied cooling mode� function is activated to ensure that no excessively low or high room temperatures will occur. The fans run at Max speed. Unoccupied heating

When the room temperature drops below the set limit value, the Unoccupied heating function is started. In this case, the heating is maintained until the room temperature is 1 Kelvin above the limit value. If only the exhaust air sensor is used, start-up takes place at night to see whether unoccupied heating is required. When starting up unoccupied heating, the exhaust air fan and/or outside air damper is blocked in accordance with the set parameter. A delayed reconnection time guarantees that the plant is not switched on too often.

Fan will be switched on Air heater control is activated Output signal for cooling is blocked HRC (if selected) is activated Damper (if selected) is blocked, the return air damper is opened

Room/exhaust air temperature sensor connected Timeswitch program must be off External switch must not be On The parameter (Htgunocpd) must be in the On position The room temperature drops below (Limitheating) The delayed reconnection time (Minrestarttime) has expired

Unoccupied cooling

When the room temperature exceeds the set limit value, the Unoccupied cooling function is started. In this case, the room is cooled until its temperature is 1 Kelvin below the set limit value. If only the exhaust air sensor is used, start-up takes place at night to see whether unoccupied cooling is required. A delayed reconnection time guarantees that the plant is not switched on too often.

Fan will be switched on Air heater control is blocked Cooling control is activated HRC (if selected) is blocked Damper (if selected) is blocked, the return air damper is opened

Room/exhaust air temperature sensor connected Timeswitch program must be off External switch must not be On The parameter (Clgunocpd) must be in the On position The room temperature exceeds (Limitcooling) The delayed reconnection time (Minrestarttime) has expired

General

Description

Effect

General conditions

Description

Effect

General conditions

Page 52: Manual Saphir LB10 S22 Eng V1_2x

52/52

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

Activation unoccupied heating/cooling

Parameter for activation/deactivation of the unoccupied heating/cooling function. Blocking unoccupied

In the event of unoccupied heating, the outside air damper can be blocked and the return air damper opened so that the system only turns over and heats up the return air. The exhaust air fan can also be blocked. Limit value for unoccupied heating/cooling

Parameter for setting the temperature limit value for start-up if the unoccupied heating/cooling function is used. Setting minimum restart time in event of unoccupied

Parameter for setting the minimum restart time for the function unoccupied. This refers to the delay before support operation may go in again after previously having been active. Delay before temperature is tested

This parameter can also be found under menu Nightpurging. Parameter for setting the time for which the unit must be stationary before the temperature is tested. This function is used when there is no room sensor, and the unit has to be started at night in order to detect the current temperature of the exhaust air. The unit starts up and operates for five minutes. If the temperature is within the condition for unoccupied heating/cooling, the unit switches into this operating mode.

5.6.6 Night purging

Menu / Configuration / Parameters / Night purging Night cooling is used during the summer to utilise the free cooling energy in the outside air by cooling the rooms with the cool outside air at night. If only the exhaust air sensor is used, start-up takes place at night to see whether night cooling is required. The fans run at Max speed. Night cooling should be in operation for several hours at night � a minimum of 1 hour. However, the temperature may not fall so low that heating energy has to be supplied.

Fan will be switched on Output signal air heater is blocked Output signal air cooler is blocked HRC (if selected) is blocked Damper (if selected) is opened, the return air damper is closed

Room temperature sensor and outside temperature sensor connected The parameter for activating night cooling must be in position On Timeswitch program must be in position Off Outside temperature > min. outside temperature Roomtemperature � outside temperature > delta (Connection difference) Room temperature > room setpoint + Hysteresis

Parameters

Note

Description

Note

Effect

General conditions

Page 53: Manual Saphir LB10 S22 Eng V1_2x

53/53

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

Night cooling will be activated if these conditions are satisfied. When one of the general conditions is no longer satisfied (apart from the most recent which is only a switch on condition), night cooling is deactivated when min. operation time has expired. Activation

Parameter for activation of night cooling. Room setpoint

The temperature the must be achieved through night ventilation. Min. outside temperature

The night cooling function is blocked when the outside temperature is lower than the set value. Hysteresis

A hysteresis is added to the room setpoint as a switch on condition, but not as a switch off condition. The total value must be higher than the current room temperature. Delta

When the outside temperature drops by the entered difference (delta) below room temperature, night cooling is activated � on the condition that the limit values for room and outside temperature have been achieved. Min. operating time

Setting a min. operating time for night cooling guarantees that the plant is not switched on and off too often.

Parameters

Page 54: Manual Saphir LB10 S22 Eng V1_2x

54/54

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 5 Description of configuration level

5.6.7 Test smoke damper

Menu / Configuration / Parameters / Test smokedamper Activation takes place by setting AUX input 2 to �IndDamper�. A smoke damper test runs at the selectable time, at manual test and if �Outdamper� is selected it runs at every start/stop of the unit as well. Fixed delay time to stop fans before dampers and to open dampers before fan start. Should a damper assume an incorrect position (detected via limit positions contacts), an alarm will be issued. Smoke dampers must be connected as the instruction for correct functionality. Time for test

Setting when the smoke damper test will occur. Smoke damper, opening time

Setting of smoke dampers opening time. The alarm will be blocked during that time.

5.6.8 Start-up

Menu / Configuration / Parameters / Start-up Power-up start delay

With the power-up start delay, the switch on of the air conditioning unit is delayed after a power failure. The power network would be overloaded if all the building�s electrical installations were started up at the same time.

Description

Note

Parameters

Parameters

Page 55: Manual Saphir LB10 S22 Eng V1_2x

55/55

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 6 Description of system settings

6 Description of system settings Menu System parameters is displayed after logging in to level 3.

6.1 Selection of language

Menu / System parameter / Language selection Parameter for selecting language in the HMI.

6.2 Communication

6.2.1 LON Configuration

Meny / System parameter / Communication / LON Configuration Settings for LON communication. LON Outtemp Parameter for activating outdoor temperature via LON communication. Pulstime Time for sending heartbeat when force. Time factor Time factor for �Pulstime� (sec, min, h) Puls onoff Activate force heartbeat puls Sendheartbeat Time for sending normal heartbeat Recvheartbeat Time for sending normal heartbeat

6.2.2 Modbus Configuration

Meny / System parameter / Communication / Modbus Config Settings for Modbus communication (RS485). Slave address Modbus adress setting Baudrate Baudrate setting (300-19200) Parity Parity setting (none, even, odd) Stopbit Stopbit setting (1 or 2) Save configuration Restarts the controller and activates the new settings.

Description

Description

Parameters

Description

Parameters

Page 56: Manual Saphir LB10 S22 Eng V1_2x

56/56

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 6 Description of system settings

6.3 Day light saving

Menu / System parameter / Summer/winter time With �Day light saving�, the time for the relevant switching is determined. The standard setting corresponds to Central European Time. Enabled The Enabled row indicates whether the Day light saving function is active. Activated The Activated row indicates whether summer time is active. B-TimeActive The row B-TimeActive indicates that the B-time is active when switching to normal time. Saving Hours Saving Hours is added when switching to summer time and subtracted when switching to winter time. Month (Mth) The relevant months that define the summer time�s start (S) and end (E). Weekday (Wday) The weekday for switching. Offset (Ofs) Weekday in the month when the changeover should occur. 3 � Second to last weekday in the month 4 � Last weekday in the month 6 � First weekday in the month 7 � Second weekday in the month 8 � Third weekday in the month Hour (Hou) The time for switching. According to the following list of settings. Indike-ring

Beskrivning Inställnings- område

Standard- värde1

Mth Month for switching to summer time

01�12 03

Wday Weekday on which switching takes place

Mo�So So

Ofs Weekday in month 0�10 4 Hou Time for switching 0.0�23.59 02 Mth Month for switching to winter time 01�12 10 Wday Weekday on which switching takes

place Mo�So So

Ofs Weekday in month 0�10 4 Hou Time for switching 0.0�23.59 03

Description

Parameters

Indication in HMI

Start summer time (S)

End summer time (E)

Page 57: Manual Saphir LB10 S22 Eng V1_2x

57/57

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 6 Description of system settings

6.4 Diagnose

Menu / System parameter / Diagnose

Information for internal diagnostics etc. Overview OS-vers: Specifies operating system version Ser. nr.: Shows serial number Target type Type of process unit, e.g. ACX36 MSR fail Number of faults in program loop MSR fail type Type of fault in program loop MSR started up 1=Yes 0=No Factiryrestore Resetting to factory values.

Note! The system must be restarted in order for the new values to apply.

Factoryset Saves all current settings as factory settings. Note! The process unit will perform a restart after the completed function

Loop times Act. loop time Current loop time Ave. loop time Average loop time Min. loop time Minimum loop time Max. loop time Highest loop time Res. loop time Resets all loop time values Application info Displays information about application version and location Manuf. Specifies the unit manufacturer�s name Ver Specifies application version Type Specifies application type Unit Specifies the unit�s designation, e.g. AHU1 Street Specifies the unit�s address. Town Specifies the unit�s location.

Description

Parameters

Page 58: Manual Saphir LB10 S22 Eng V1_2x

58/58

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 6 Description of system settings

6.5 HMI Parameter

Menu / System parameter / HMI Parameter

The operating unit�s functions can be controlled via �HMI parameter�.

Basic set values are specified in brackets.

HMI brightness (10) The background lighting is altered depending on the entered value: 0 = dark / 31 = light (Recommendation: 30) HMI contrast (10) The text is emphasised more or less against the background: 0 = weak / 31 = strong (Recommendation: 10) Number of columns Shows the number of columns that can be presented in the display. (Cannot be adjusted) Vertical/Horiz scroll Shows the number of rows that can be scrolled vertically/horizontally. (Cannot be adjusted) New page (1) Shows whether the start page is opened when the HMI reset time has expired. 0 = No resetting; current page and code word remain. 1 = Resetting to the start page, the code word is reset and must be entered again. Message durration (5) 2�15 = Time in seconds how long an message, in event of incorrect entry, remains. HMI reset (10) Shows in minutes how long the authorisation applies after the last entry. 3�60 = Minutes until reset HMI auto delay (10) Value alterations are realised by pressing the settings buttons +/- in the entry function. If one of the buttons is held down, the Autorepeat function is activated when the entered delay time has expired. 5�30 = Delay time in seconds (Cannot be adjusted) HMI auto repeat (5) If the Autorepeat function is active, the resolution�s time interval is altered according to the entered value. 3�10 = Time interval in seconds for value change (Cannot be adjusted)

MSR Type Shows actual configuration to hide rows in the HMI.

HMI Type Selects the type of HMI (ACX82 or ACX84) to obtain the right functionality.

Description

Parameters

Page 59: Manual Saphir LB10 S22 Eng V1_2x

59/59

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 7 Communication options

7 Communication options ACX36 is available with several different communication options. The type designations for the Controllers therefore have different end numbers in order that they can be distinguished. All Controllers also have Modbus.

ACX36.000 Only Modbus ACX36.030 KNX communication (Not in this application) ACX36.040 LON communication

7.1 KNX

Description of KNX communication can be found in the document CE2Y3226en.

7.2 LON

Description of LON communication can be found in the document CE2Y3226en.

7.3 Modbus

Description of Modbus communication can be found in the document CE2Y3226en.

Page 60: Manual Saphir LB10 S22 Eng V1_2x

60/60

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 8 Parameter list

8 Parameter list

8.1 Overview of operating level

Para

met

er

nam

e

Func

tion

Are

a

Uni

t

Stan

dard

va

lue

Sect

ion

Menu Operation information Serv.swi: Status for service switch Auto/Stop/Manu � � 3.3 Timer: Status for control inputs Auto/Stop//Step1/Step2 � � � Op mode: Current operating mode Off/Step1/Step2/-/

Testtemp/Nightprg/Unoccup Startup/Overrun/Dmprkick

� � �

Fan mode: Current fan mode Off/Step1/Step2 � � �

Control: Current type of control Room/Exhaust/Supply � � � Actsetp heat Current heating setpoint -50...150.0 °C � � Actsetp cool Current cooling setpoint -50...150.0 °C � � Outtemp Outside temperature -50...150.0 °C � � Supplytemp Supply air temperature -50...150.0 °C � � Exhausttemp Exhaust air temperature -50...150.0 °C � � Roomtemp Room temperature -50...150.0 °C � � Roomunit Roomunit temperature -50...150.0 °C � � Frosttemp Frost temperature -50...150.0 °C � � Multifunction temperature 1 HRCfrosttemp / Supplyt HRC /

Usedairtemp / AUX1 temp -50...150.0 °C � �

Cooling Output signal cooling 0�100 % � � HRC Output signal HRC 0�100 % � � Heating Output signal heating 0�100 % � � Supplyfan Output signal supplyfan 0�100 % � � Exhaustfan Output signal exhaustfan 0�100 % � � Menu Scheduler 01.01.2006 12:00:00 Setting the current time Day.Month.Year

Hour:Min:Sec � � 4.1

Curr. Scheduler Current step from scheduler Off/St1/St2 � � 4.2.6 Menu Scheduler Daytime scheduler T1-T4 Switching point 1 Start:

Opmode: Enable:

00:00...24:00 Off/St1/St2 ---- / Actv

� � 4.2.1

Menu Scheduler Weektime scheduler T1-T6 Connection point 1 Start:

Stop: Opmode: Enable:

dd 00:00...24:00 dd 00:00...24:00 Off/St1/St2 ---- / Actv

� � 4.2.2

Menu Scheduler Yeartime scheduler T1-T5, T6-T10 Connection point 1 Start:

Opmode: Stop: Enable:

dd.mm 00:00...24:00 Off/St1/St2 dd.mm 00:00...24:00 ---- / Actv

� � 4.2.3

Menu Scheduler Override OPmode swi Override time switch program Auto/Off/St1/St2 � Auto 4.2.5

Page 61: Manual Saphir LB10 S22 Eng V1_2x

61/61

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 8 Parameter list

Para

met

er

nam

e

Func

tion

Are

a

Uni

t

Stan

dard

va

lue

Sect

ion

BMS override Override time switch program from a BMS system

Auto/Off/St1/St2 � Auto �

Menu Setpoints Temperature control Control: Current type of control Room/Exhaust/Supply � � 4.3.1 Actsetp heat Current heating setpoint -50...150.0 °C � � Actsetp cool Current cooling setpoint -50...150.0 °C � � Actual Value Current actual value -50...150.0 °C � � Basic setp Setpoint heating 10.0...40.0 °C 21.0 � Dead zone Dead zone cooling 0.0...10.0 °C 2.0 � Temp.comp Compensation at supply contr -10.0�10.0 K -2.0 � Ext setpoint Current external setpoint � °C � � Menu Setpoints Min/Max supply temp Min/Maxlim: Type of limitation Fixed / Sliding � Fixed 4.3.2 Act heat setp. Act setpoint supply air -50...150.0 °C � Act cool setp. Act setpoint supply air -50...150.0 °C � � Supplytemp Supply air temperature -50...150.0 °C � � Mintemp Min supply air temperature 10.0...25.0 °C 15.0 � Maxtemp Max. supply air temperature 20.0...40.0 °C 25.0 � Delta maxlim Delta maxlimit,

sliding limitation 1.0...10.0 K 4.0 �

Delta minlim Delta minlimit, sliding limitation

1.0...10.0 K 3.0 �

Menu Setpoints Min/Max supply temp Step1 sup Output supply fan lowspeed 0�100 % 40 4.3.3 Step2 sup Output supply fan highspeed 0�100 % 80 Step1 exh Output exh. fan lowspeed 0�100 % 40 � Step2 exh Output exh. fan highspeed 0�100 % 80 � Menu Operating status Inputs digital Controlinputs Control inputs Auto/Stop//Step1/Step2 � � 4.4.1 Servicesw HMI Service switch on HMI Auto/Stop/Manu � � � Emergencystop Status DI Emergency stop Off/Stop � � � Fire/Smoke Status DI Fire/Smoke Off/On � � � HRC Status DI HRC Off/On � � � Pump/Heater Status DI Pump/Heater Off/On � � � Chiller Status DI Chiller Off/On � � � AUX Status DI AUX Off/On � � � Filter Status DI Filter Off/On � � � HRC press guard Status DI HRC pressure guard Off/On � � � Smokedamper Status DI Smokedamper Off/On � � � Fan Status DI Fan Off/On � � � Flow Status DI Flow Off/On � � � Ext frost Status DI Extern frost Off/On � � � Menu Operating status Actual value Outtemp Outside temperature -50...150.0 °C � 4.4.2 Supplytemp Supply air temperature -50...150.0 °C � � Exhausttemp Exhaust air temperature -50...150.0 °C � � Roomtemp Room temperature -50...150.0 °C � � Roomunit Room unit temperature -50...150.0 °C � � Frosttemp Frost protection temperature -50...150.0 °C � � Multifunction temperature 1 HRCfrosttemp / Supplyt HRC /

Usedairtemp / AUX1 temp -50...150.0 °C � �

Page 62: Manual Saphir LB10 S22 Eng V1_2x

62/62

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 8 Parameter list

Para

met

er

nam

e

Func

tion

Are

a

Uni

t

Stan

dard

va

lue

Sect

ion

Ext setpoint Current external setpoint � °C � � Menu Operating status Outputs digital Pump/heat C-pump heating or electrical Off/On (Man/Auto) � � 4.4.3 Cooling/DX-cooling step 1 Cooling pump or DX Step 1 Off/On (Man/Auto) � � � DX-cooling step 2 DX Step 2 Off/On (Man/Auto) � � � Supply air fan Supply air fan Off/St1/St2 (Man/Auto) � � � Exhaust air fan Exhaust air fan Off/St1/St2 (Man/Auto) � � � Outdamper Out damper Off/On (Man/Auto) � � � Smokedamper Smoke damper Off/On (Man/Auto) � � � A-alarm Alarm priority A OK/Alarm (Man/Auto) � � � B-alarm Alarm priority B OK/Alarm (Man/Auto) � � � Menu Operating status Outputs control signal Cooling Output signal cooling 0...100 (Man/Auto) % � 4.4.4 HRC Output signal heat exchanger 0...100 (Man/Auto) % � � Heating Output signal heating 0...100 (Man/Auto) % � � Supplyfan Output signal supplyfan 0...100 (Man/Auto) % � � Exhaustfan Output signal exhaustfan 0...100 (Man/Auto) % � � Menu Operating status Operation counter Fan run counter Operating time fan 0.0... xxxx h � 4.4.5 Reset counter Resetting of counter No/Yes � � � Menu Operating status Test smokedamper Test smokedamper Manual smokedamper test Off/On � � 4.4.6 Damperkick Time for smokedamper test 00:00�23:00 � 23:00 � Menu Operating status Efficiency Effeciency Current HRC efficiency 0�100 % � 4.4.7 Menu Alarm History Reset Resetting of alarm history No/Yes � � 4.5 Menu Password function Log in Logging in � � � 4.6 Log out Logging out � � � � Change password Changing the password � � � � Current stage: Current password level � � � � Menu Application info Unit Name of plant A-Z, a-z, 0-9, -.?! � � 4.7 Street Location of plant A-Z, a-z, 0-9, -.?! � � � Town Address of plant A-Z, a-z, 0-9, -.?! � � �

Depending on the type of application and the current configuration, some parameters/menus are not used and consequently they are not displayed in HMI.

Page 63: Manual Saphir LB10 S22 Eng V1_2x

63/63

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 8 Parameter list

8.2 Overview of configuration level

Para

met

er

nam

e

Func

tion

Are

a

Uni

t

Stan

dard

va

lue

Sect

ion

Menu Configuration Functions Application Type of application LB10 Macro1 � � 5.1.1 Temperaturecontrol Type of temperature control Cascade/Supply/Casc+Sup � Supply 5.1.2 Cooling Type of cooling None/Water/DX-1step/

DX-2step/DX-3step � None 5.1.3

HRC Function Type of recovery None/Rot-HRC/Recircair/ Plade-HRC/Water/HRC-PWM

� Rot-HRC

Heating Type of air heater None/ExtFrost/Water/ Electric

� Water �

Fan controller Type of fan control FrequInv1St/ FrequInv2St /Direct1St/Direct2St

� Freqv Inv2St

5.1.4

Multifunct input 1

Type of function on Multi-function input 1

None/ExtSetPas/ ExtSetpAct/HRC frost/ Pressgrd/SupplytempHRC/ Usedairtemp/AUX Temp/ HRC alarm

� None 5.1.5

AUX1 alarm type Alarm type for alarm AUX1 None/AUX/Flow/Filter/ Cooling/HRC

� None 5.1.6

AUX2 alarm type Alarm type for alarm AUX2 None/IndDamper/Flow/ Filter/Cooling/HRC/Timer

� None �

Em.stop/Firealarm Selection if emergency stop or fire alarm function

Em.stop/Firealarm � Fire- alarm

5.1.7

Damper function Type of function for damper control

Outdamper/Smokedamper � Out-damper

5.1.8

Room/Exh.s. Activate room or exhaust air sensor

None/Room/Exhaust air � None 5.1.9

Outdoor sensor Activate outside sensor No/Yes � No � Roomunit Activate roomunit None/QAA88.3 � � � Save configuration Restarts the controller No/Yes � � 5.1.10 Menu Configuration Sensors Rm/Exh.tmp.corr Calibration room/exhaust temp -9.9...9.9 K 0.0 5.2.1 Outtemp corr Calibration outside temp -9.9...9.9 K 0.0 � Supplytemp corr Calibration supply air temp -9.9...9.9 K 0.0 � Frosttemp corr Calibration Frost protection

temp -9.9...9.9 K 0.0 �

Multifunction temperature 1 (Calibration)

HRCfrosttemp / Supplyt HRC / Usedairtemp / AUX1 temp

-9.9...9.9 K 0.0 �

Menu Configuration Alarms Temp alarm Smrdisable alarm Blocking temp dev summer On/Off � On 5.3.1 Tempalarm Set Max deviation temp. alarm 0...50 °C 10 � Alarm value Alarm limit for frost protection 2.0...30.0 °C 7.0 � HRC frost alarm Alarm limit for HRC frosting -10.0�10.0 °C -2.0 �

Page 64: Manual Saphir LB10 S22 Eng V1_2x

64/64

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 8 Parameter list

Para

met

er

nam

e

Func

tion

Are

a

Uni

t

Stan

dard

va

lue

Sect

ion

Menu Configuration Alarms Operation counter Runcounter alarm Activation of runcounter alarm Off/On � Off 5.3.2 Alarm limit Limit for operating time alarm 0�20000 h 9000 � Fan run counter Operating time fan 0.0... xxxx h � � Reset counter Resetting of counter No/Yes � � � Menu Configuration Alarms Directing of inputs Fire/Smoke alarm Alarm smoke or fire NO / NC � NO 5.3.3 HRC alarm Alarm heat exchanger NO / NC � NO � Pump/heater alarm Alarm c-pump heating NO / NC � NO � Cooler alarm Alarm cooling NO / NC � NO � Fan alarm Alarm fans NO / NC � NO � AUX alarm Alarm AUX NO / NC � NO � Filter alarm Alarm filter detector NO / NC � NO � Flow alarm Alarm flow detector NO / NC � NO � ExtFrost alarm Alarm external Frost protection NO / NC � NO � Emergency stop Emergency stop NO / NC � NO � Menu Configuration Alarms Alarm delays Cooler alarm Delay for cooler alarm 0...9999 s 0 5.3.4 HRC alarm Delay for HRC alarm 0...9999 s 5 � Pump/heater alarm Delay for pump/heater alarm 0...9999 s 0 � Fan alarm Delay for fan alarm 0...9999 s 0 � Fan startup Delay for fan startup 0...9999 s 5 � AUX alarm Delay for AUX alarm 0...9999 s 0 � Filter alarm Delay for filter alarm 0...9999 s 30 � Flow alarm Delay for flow alarm 0...9999 s 10 � Flow startup Delay for flow startup 0...9999 s 60 � HRC frost alarm Delay for HRC frost alarm 0...9999 s 0 � Overrideunit alarm Delay for overrideunit alarm 0...600 m 30 � Temp alarm Delay for temp deviation 0...600 m 60 � HRC press alarm Delay for HRC press alarm 0...600 m 15 � Low efficiency Delay for low HRC efficiency 0...600 m 30 � Menu Configuration Alarms Alarm class Cooler alarm Alarm class for cooler alarm A/B/C � B 5.3.5 HRC alarm Alarm class for HRC alarm A/B/C � B � Pump/heater alarm Alarm class for pump/heater al A/B/C � B � Fan alarm Alarm class for fan alarm A/B/C � A � AUX alarm Alarm class for AUX alarm A/B/C � B � Filter alarm Alarm class for filter alarm A/B/C � B � Flow alarm Alarm class for flow alarm A/B/C � A � Overrideunit alarm Alarm class for overrideunit al A/B/C � B � Temp alarm Alarm class for temp deviation A/B/C � B � HRC press alarm Alarm class for HRC pressure A/B/C � B � HRC frost alarm Alarm class for HRC frost al A/B/C � A � Low efficiency Alarm class for low HRC eff. A/B/C � B � Outdoor sensor alarm Alarm class for outside sensor A/B/C � A � Supply sensor alarm Alarm class for supply sensor A/B/C � A � Rm/Exh.sensor alarm Alarm class for room/exh sen A/B/C � B � Frost sensor alarm Alarm class for frost sensor A/B/C � A � Multi1 sensor alarm Alarm class for multi 1 sensor A/B/C � A �

Page 65: Manual Saphir LB10 S22 Eng V1_2x

65/65

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 8 Parameter list

Para

met

er

nam

e

Func

tion

Are

a

Uni

t

Stan

dard

va

lue

Sect

ion

Smoke damper alarm Alarm class for smoke damper A/B/C � A � Fire/Smoke alarm Alarm class for fire/smoke al A/B/C � A � Menu Configuration Alarms Alarm output Alarm output Alarm output for alarm class A / A+B � A 5.3.6 Menu Configuration Alarms Efficiency Low efficiency Alarm limit for HRC efficiency 0�100 % 50 5.3.7 Menu Configuration Controllers Cascade controller For main regulator KP

TN � 4

600.0 5.4

Cooling controller For cooling regulator KP TN TD

� -5.0 300.0 0.0

HRC controller For heat exchanger regulator KP TN TD

� 10.0 120.0 0.0

Heating controller For heating regulator KP TN TD

� 5.0 120.0 0.0

Frost controller For Frost protection regulator KP TN TD

� 20.0 0.0 0.0

HRC Frost controller For heat exchanger frosting regulator

KP TN TD

� 20.0 0.0 0.0

Menu Configuration Control parameters Cooling Enbl cooling Activation cooling at out temp -50...150 °C 12.0 5.5.1 Maxclg step1 Max outputsignal at fanstep 1 1�100 % 100 � Start Step1 Starting DX step 1 1�100 % 20 � Stop Step1 Stopping DX step 1 1�100 % 5 � Start Step2 Starting DX step 2 1�100 % 70 � Stop Step2 Stopping DX step 2 1�100 % 50 � Mintime restart Delay before reconnect DX-

cooling 0...10 m 1 "

Menu Configuration Control parameters HRC Startup time Time for full recovery at startup 0�180 s 30 5.5.2 Clg recovery Activation of cooling recovery Off/On � Off � HRC frost setp. Setpoint frosting -10.0�30.0 °C 1.0 � HRC frost alarm Alarm limit in event of frosting -10.0�10.0 °C -2.0 � Min pos damper Min. outside air volume return

air damper 0�100 % 0 �

Min lim pressgrd Min limit in event of active pressure switch

0�100 % 25 �

Startup time Start-up time return air 0�60 m 0 � Menu Configuration Control parameters Heating Preheating Preheating time heating 0�600 s 0 5.5.3 Setpoint frost Setpoint for min. operating

temperature 3.0...40.0 °C 12.0 �

Standby stp Setpoint for keeping warm 10.0...50.0 °C 25.0 � Alarm value Alarm limit for frost protection 2.0...30.0 °C 7.0 �

Page 66: Manual Saphir LB10 S22 Eng V1_2x

66/66

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 8 Parameter list

Para

met

er

nam

e

Func

tion

Are

a

Uni

t

Stan

dard

va

lue

Sect

ion

MaxSignalSt1 Max signal for electric heating at fan step 1

0�100 % 100 �

MaxSignalSt2 Max signal for electric heating at fan step 2

0�100 % 100 �

Menu Configuration Control parameters Ext setpoint Ext setp type Type of external setpoint Main/Correction � Main 5.5.4 Min ext setp Setpoint at 0V -10.0�50.0 °C 15.0 � Max ext setp Setpoint at 10V 0.0�50.0 °C 25.0 � Menu Configuration Control parameters Smr wntr compensation Summerstart Starting point summer comp. 10.0�50.0 °C 25.0 5.5.5 Summerend End point summer comp. 10.0�50.0 °C 30.0 � Summerdelta Movement summer comp. -10.0�10.0 °C 0.0 � Winterstart Starting point winter comp. -30.0�20.0 °C 5.0 � Winterend End point winter comp. -30.0�20.0 °C -20.0 � Winterdelta Movement winter comp. -10.0�10.0 °C 0.0 � Menu Configuration Control parameters Cascade control Cascade sensor Main sensor for cascade

control Room/Exhaust � Room 5.5.6

Temp.comp Compensation at supply contr -10.0�10.0 K -2.0 � Outtemp Change at outside temperature 0.0...20.0 °C 14.0 � Dealy Delay before change 0...360 m 30 � Menu Configuration Parameters Fan Start delay Delay in fan start and

stopdelay for outdamper 0...180 s 20 5.6.1

Delay SU start Delay of supply air fan start 0...120 s 30 � Runuptime Delay fanstep at runup 0�60 s 5 � Rundowntime Delay fanstep at rundown 0�60 s 10 � Fan overrun Overrun time 0...30 m 5 � Fanfunction fire Fan function at fire Stop EX/SU / Run EX/SU /

Stop EX / Stop SU / � Stop

EX/SU �

Menu Configuration Parameters Fan compensation Fan compensation Selection of fan compensation

for the fans None/Blockhighspd/ Cooling/Heating/Clg+Htg

� None 5.6.2

Startdelay Delay for activating fancomp 0�60 m 10 � Releasedelay Delay for deactivating fancomp 0�300 m 60 � Blockhighspd Outside temperature for

blocking high speed -50.0...50.0 °C -15.0 �

Menu Configuration Parameters Pump Pumpkick cool Motion operation cooling pump Off/Auto/cont. � Auto 5.6.3 Pumpkick heat Motion operation heating pump Off/Auto/cont. � Auto � Min runtime Min. operating time pump 0...30 m 5 � Menu Configuration Parameters Control input Timeron time Time for control input timer 0...12 h 0 5.6.4 Control Inp Function when active input Stop/St1/St2 � St1 � Overrun em.stop Airing in event of emerg. stop Yes/No � Yes � Menu Configuration Parameters Unoccupied mode Htg unoccup Activation unoccupied heating Off/On � Off 5.6.5 Clg unoccup Activating unoccupied cooling Off/On � Off � Unocp block Blocking in event of unoccup. None/Damper/DampFan � None � Limit Heating Limit for unoccup. heating 0.0�30.0 °C 15.0 �

Page 67: Manual Saphir LB10 S22 Eng V1_2x

67/67

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products 8 Parameter list

Para

met

er

nam

e

Func

tion

Are

a

Uni

t

Stan

dard

va

lue

Sect

ion

Limit Cooling Limit for unoccup. cooling 20.0�50.0 °C 30.0 � Min restart time Min. restart time for unoccup. 0�720 m 30 � Dly before test Time delay before testing of

exhaust air temperature 0�720 m 420 �

Menu Configuration Parameters Night purging Night purging Activation of nightp. function Off/On � Off 5.6.6 Room setpoint Room setp. for night cooling 10.0�40.0 °C 22.0 � Min outtemp Min. outside temp. for nightp. 5.0�30.0 °C 12.0 � Hysteresis Hysteresis for night cooling 1.0�10.0 K 3.0 � Ondelta Min. diff. room, outtemp. 1.0�20.0 K 5.0 � Min run time Min. operating time for nightp. 0�720 m 30 � Dly before test Time delay before testing of

exhaust air temperature 0�720 m 420 �

Menu Configuration Parameters Test smokedamper Damper kick Time for smokedamper test 00:00�23:00 � 23:00 5.6.7 Open time Time for opening of smoke

damper 0�xxx s 180 �

Menu Configuration Parameters Startup Powerup start delay Start delay after power failure 0�900 s 0 5.6.8

Depending on the type of application and current configuration, some parameters/menus are not used and consequently they are not displayed in HMI.

Page 68: Manual Saphir LB10 S22 Eng V1_2x

68/68

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products Index

Index

A Abbreviations ..................................................... 10 Alarm Button ...................................................... 19 Alarm class ........................................................ 40 Alarm delay ........................................................ 40 Alarm guide........................................................ 20 Alarm history ...................................................... 31 Alarm list ............................................................ 19 Alarm management............................................ 20 Alarm output....................................................... 40 Alarm settings .................................................... 38 Application ......................................................... 32 Application information....................................... 31 AUX alarm.......................................................... 36

B BMS override ..................................................... 25

C Calibration of sensor .......................................... 37 Cascade control ................................................. 47 Cascade control with limits for the supply air temperature........................................................ 33 Cascade+Supply air temperature control .... 33, 47 Code word.......................................................... 16 Commissioning .................................................. 32 Communication .................................................. 55 Configuration...................................................... 32 Configuration level ............................................. 16 Connection instruction ....................................... 13 Contact function NO/NC .................................... 40 Control ............................................................... 29 Control function temperature ............................. 32 Control input....................................................... 28 Control inputs..................................................... 50 Control outputs................................................... 29 Control parameters ............................................ 42 Cooling function ................................................. 33 Cooling settings ................................................. 42

D Damper functionality .......................................... 36 Date ................................................................... 22 Day light saving.................................................. 56 Day program ...................................................... 22 Daytimescheduler .............................................. 22 Deviation alarm.................................................. 39 Diagnose............................................................ 57 Displacement ventilation .................................... 26 DX-Cooling......................................................... 42

E Efficiency alarm.................................................. 40 Efficiency rating.................................................. 30 Emergency stop ........................................... 28, 36 Environmental protection ..................................... 9 External setpoint ................................................ 45

F Fan compensation ............................................. 49 Fan control ......................................................... 34 Fan settings ....................................................... 48 Fan speed.......................................................... 27 Fan start delay ................................................... 48 Fault management ............................................. 14 Fire alarm........................................................... 36 Fire function ....................................................... 48 Functions ........................................................... 32

H Heat recovery function....................................... 34 Heat recovery settings ....................................... 42 Heating function ..................................................... 34 Heating settings ................................................. 44 HMI Parameter................................................... 58 HMI Service switch ............................................ 28 HMI Start/Stop Button ........................................ 19 HMI Type ........................................................... 58

I Inputs digital....................................................... 28 Installation procedure HMI ................................. 11 Installation procedure regulator ......................... 11

L

Language selection............................................ 55 LON configuration.............................................. 55

M Maintenance ........................................................ 9 Measurement values.......................................... 29 Menu system...................................................... 16 Menu tree........................................................... 17 Min/Max supply air temperature......................... 26 Modbus configuration......................................... 55 Multifunction inputs ............................................ 35

N Navigate............................................................. 18 Night cooling ...................................................... 52

Page 69: Manual Saphir LB10 S22 Eng V1_2x

69/69

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products Index

O Operating level ...................................................16 Operating switch.................................................25 Operating time alarm ..........................................39 Operating unit HMI .............................................15 Operation status .................................................28 Operationcounter..........................................30, 39 Outputs digital.....................................................29 Override time switch program.............................25 Overrun...............................................................48 Overview

Parameters configuration level......................63 Parameters operating level ...........................60

P Packing.................................................................9 Parameter list .....................................................60 Parameters .........................................................48 Password......................................................16, 31 Peripheral components.........................................7 Power-up start delay...........................................54 Preheating time ..................................................44 Properties .............................................................6 Pump settings.....................................................50

R

Regulator settings...............................................41

S Safety regulations.................................................8 Scheduler ...........................................................22 Setpoints.............................................................26 Smokedamper test .......................................30, 54 Start-up...............................................................54

Storage .................................................................9 Summer Winter compensation ...........................46 Supply air fan start delay....................................48 Supply air temperature control ...........................33 System settings ..................................................55 Systemparamer level..........................................16

T Temperature .......................................................29 Temperature alarm.............................................39 Temperature control ...........................................26 Temperature sensors .........................................37 Terminal blocks ..................................................12 Time....................................................................22 Time switch program ..........................................22 Time switch program example............................24 Timer ..................................................................50 Timer input..........................................................28 Transport ..............................................................9 Type of min/max limitation..................................26

U Unoccupied

cooling...........................................................51 Heating..........................................................51

Unoccupied mode...............................................51

V,W Week program....................................................23 Weektimescheduler ............................................23

Y Year program......................................................23 Yeartimescheduler..............................................23

Page 70: Manual Saphir LB10 S22 Eng V1_2x

70/70

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products IVprodukt LB10 April 2006

Siemens Building Technologies HVAC Products Elektronvägen 4 SE-141 87 Huddinge Tel. +46 8 578 410 00 Fax +46 8 578 419 92 www.siemens.se/sbt

© 2006 Siemens Building Technologies AG Subject to alteration

Page 71: Manual Saphir LB10 S22 Eng V1_2x

71/71

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/Siemens HVAC Products Siemens LB10 April 2006

Page 72: Manual Saphir LB10 S22 Eng V1_2x

72/72

Siemens Building Technologies Basic documentation ACX36.xxx/ALG CE1P3226en/IVP HVAC Products IVprodukt LB10 April 2006

IV Produkt AB, bOX 3103, SE-350 43 VÄXJÖ Phone: +46 470 75 88 00 ● Fax: +46 470 75 88 76

[email protected] ● www.ivprodukt.com