iNVent 2 - Amazon S3 · PDF file 2016-12-15 · iNVent 2 Intelligent Natural Ventilation Control The Monodraught iNVent 2 system is a Natural Ventilation management system for up to

Mar 18, 2020

ReportDownload

Documents

others

  • Controls by Monodraught

    iNVent 2 Intelligent Natural Ventilation Control

    The Monodraught iNVent 2 system is a Natural Ventilation management system for up to 4 zones, each consisting of up to 3 Natural Ventilation systems. It utilises seasonally adjusted proportional control based on internal temperature and CO2. With configurable sensor, strategy, and actuator mapping via USB, as well as built in data logging, the iNVent 2 system can control Natural Ventilation systems to suit any building application.

    Features

    • Supports all Monodraught Natural Ventilation products • Real-Time Clock • LCD screen • 60W PSU • Automatically resets if power is interrupted using watchdog timer • Seasonal control strategy, influenced by internal and external temperatures, as well as CO2 levels • Individually fused (resettable) 24V zone supplies • Built-In data logging

    • Master volt-free I/O can be distributed between multiple panels • BACnet visible with optional BACnet module • RS485 communication bus • USB access for configuration and monitoring • Configurable sensor, strategy and actuator mapping • External cooling and heating zone control • Fully backwards compatible with iNVent

    http://www.monodraught.com/ https://www.investorsinpeople.com/ http://www.livingwage.org.uk/

  • [email protected] / +44 (0)1494 897700 2

    SOLA-BOOST® Classic

    Dimensions • 255 mm x 385 mm x 40 mm

    Mounting • Unit is designed to be wall mounted in a

    decentralised location within the building, close to the zones it is controlling, like a storage cupboard, plant room or above a suspended ceiling

    Operating Conditions • 0 - 40 °C • 10 - 80% RH non-condensing

    Power Supply • 24V DC @ 60 mA Nominal • Supplied with SMPS for converting 240V AC

    to 24V DC @ 2.5A requiring connection to a 3A switched spur

    • The iNVent 2 can supply up to a total of 2A from the 24VDC supply to field devices

    Terminals • Cable size 1 mm2 CSA max. • Cable size 0.5 mm2 CSA multi-strand

    recommended

    Case • Front Cover: Acrylic Capped ABS • Wall Mounting Holes Located Inside the Case

    PC Interface

    The iNVent 2 Control Panel has an internal USB port which allows a commissioning engineer to connect a Laptop to the panel for custom configuration, maintenance and data collection purposes.

    Functionality

    DAMPER/LOUVRE

    0V 24V DMP. LVR.

    WALL ACTUATOR

    0V 24V

    Zo ne

    #

    0V 24V 0V 24V

    SENSOR 1 SENSOR 2 RS485

    DMP. LVR.

    RAIN SMOKE FAULT

    COM NO

    COM ORCOM

    COM COMH C

    ALARMHEAT

    EXTERNAL TEMP.

    0V 24VCOM O C

    FIRE SWITCHCOMP SWITCH

    COM C1 C2

    DAMPER/LOUVRE

    0V 24V DMP. LVR.

    WALL ACTUATOR

    0V 24V

    Zo ne

    #

    0V 24V 0V 24V

    SENSOR 1 SENSOR 2 RS485

    DMP. LVR. DAMPER/LOUVRE

    0V 24V DMP. LVR.

    WALL ACTUATOR

    0V 24V

    Zo ne

    #

    0V 24V 0V 24V

    SENSOR 1 SENSOR 2 RS485

    DMP. LVR. DAMPER/LOUVRE

    0V 24V DMP. DMP. LVR.

    WALL ACTUATOR

    0V 24V

    Zo ne

    #

    0V 24V 0V 24V

    SENSOR 1 SENSOR 2 RS485

    LVR.

    Z1 COOLING Z2 COOLING

    COM NONOCOM

    COM COMNO NO

    Z2 HEATINGZ1 HEATING

    Z3 COOLING Z4 COOLING

    COM NONOCOM

    COM COMNO NO

    Z4 HEATINGZ3 HEATING

    COOLING/HEATING SOLID STATE RELAYS

    MASTER CONTROLS

    0V Z324V 0V Z424VZ4Z3Z2Z10V

    0V Z124V 0V Z224VZ4Z3Z2Z10V BMS INPUTS

    BMS OUTPUTS

    GENERAL PURPOSE

    MONODRAUGHT iNVent 2

    24V

    0V

    24V

    24V

    0V

    B

    A

    BUTTON2

    BUTTON1

    LED3

    LED7

    LED6

    LED4 LED2

    Tx Rx

    LED10 LED17LED5LED1

    LED11

    LED8 LED9

    LED12

    LED13 LED14

    LED15 LED16

    A

    D

    B

    C

    Case Dimensions

    2

    305 mm

    385 mm

    11 0

    44

    366 mm

    CABLE ENTRY

    FIXING HOLES

    40 255 m

    m

    EXTERNAL INTERNAL

    PLAN

    DAMPER/LOUVRE

    0V 24V DMP. LVR.

    WALL ACTUATOR

    0V 24V

    Zo ne

    #

    0V 24V 0V 24V

    SENSOR 1 SENSOR 2 RS485

    DMP.

    RAIN SMOKE FAULT

    COM NO

    COM ORCOM

    COM COMH C

    ALARMHEAT

    EXTERNAL TEMP.

    0V 24VCOM O C

    FIRE SWITCHCOMP SWITCH

    COM C1 C2

    DAMPER/LOUVRE

    0V 24V DMP. DMP. LVR.

    WALL ACTUATOR

    0V 24V

    Zo ne

    #

    0V 24V 0V 24V

    SENSOR 1 SENSOR 2 RS485

    DAMPER/LOUVRE

    0V 24V DMP. LVR.

    WALL ACTUATOR

    0V 24V

    Zo ne

    #

    0V 24V 0V 24V

    SENSOR 1 SENSOR 2 RS485

    DMP. DAMPER/LOUVRE

    0V 24V DMP. LVR.

    WALL ACTUATOR

    0V 24V

    Zo ne

    #

    0V 24V 0V 24V

    SENSOR 1 SENSOR 2 RS485

    DMP.

    Z1 COOLING Z2 COOLING

    COM NONOCOM

    COM COMNO NO

    Z2 HEATINGZ1 HEATING

    Z3 COOLING Z4 COOLING

    COM NONOCOM

    COM COMNO NO

    Z4 HEATINGZ3 HEATING

    COOLING/HEATING SOLID STATE RELAYS

    MASTER CONTROLS

    0V Z324V 0V Z424VZ4Z3Z2Z10V

    0V Z124V 0V Z224VZ4Z3Z2Z10V BMS INPUTS

    BMS OUTPUTS

    GENERAL PURPOSE

    MONODRAUGHT iNVent 2

    24V

    0V

    Compatible Products

    WINDCATCHER® Classic WINDCATCHER® X-Air SOLA-BOOST® X-Air

    VENTSAIR® Façade VENTSAIR® Roof Mounted Terminal

    VENTSAIR® Acoustic Air Transfer System

    Specification

    mailto:info%40monodraught.com%20?subject=iNVent%202%20Query%20-%20Website http://www.monodraught.com/

  • [email protected] / +44 (0)1494 897700 3

    Master InputsA

    RAIN SMOKE FAULT

    COM NO

    COM NONOCOM

    COM COMNO NO

    ALARMHEAT

    EXTERNAL TEMP.

    0V 24VCOM O C

    FIRE SWITCHCOMP SWITCH

    COM O C

    24V

    0V

    Competition Key Switch (optional)

    Allows the limiting of ventilation for air movement sensitive

    activities

    Rain Sensor Closes windows and protects against rain

    ingress in natural ventilation products

    Heating Interlock (optional)

    Prevents the system from cooling spaces when

    heating is on Fire Alarm (optional)

    Closes sources of ventilation in response to a fire alarm input to

    restrict the spread of fire

    Fault Signal (optional) A volt-free contact which when open indicates a fault has occurred

    Smoke Vent (optional) Opens specially configured smoke ventilation airways to help keep escape routes clear of smoke and to aid evacuation in event of a fire

    External Temperature Used to adjust the seasonal strategy and protect ventilation systems against snow/ frost

    Fire Key Switch (optional) Allows fire officers to override the system to open or close ventilation systems if necessary

    4 Heating Solid-State Relay Outputs

    • Allows iNVent 2 to control auxiliary heating in each zone

    4 Cooling Solid-State Relay Outputs • Allows iNVent 2 to control auxiliary cooling in

    each zone

    Heating & CoolingC

    4 General Purpose 0 - 10V Inputs • Used for additional sensor or control inputs

    4 BMS 0 - 10V Inputs • Allows a BMS system to share sensor data

    with an iNVent 2 panel. This allows hybrid ventilation systems to share the same sensor readings, allowing highly accurate interlinking of cooling and heating systems

    4 BMS 0 - 10V Outputs • Used to send analogue signals to a BMS

    system in order to share sensor data or control information. This allows the BMS to operate on the same information as iNVent 2

    General Purpose & BMSB

    Z1 COOLING Z2 COOLING

    COM NONOCOM

    COM COMNO NO

    Z2 HEATINGZ1 HEATING

    Z3 COOLING Z4 COOLING

    COM NONOCOM

    COM COMNO NO

    Z4 HEATINGZ3 HEATING

    COOLING/HEATING SOLID STATE RELAYS

    0V Z324V 0V Z424VZ4Z3Z2Z10V

    0V Z124V 0V Z224VZ4Z3Z2Z10V BMS INPUTS

    BMS OUTPUTS

    GENERAL PURPOSE

    4 Input Zones with the Following Inputs per Zone • 2 sensor 0 - 10V inputs: Can be used with temperature, CO2 or other sensors, or with Monodraught

    Multifunction wall controllers • 3 actuator 0 - 10V feedback inputs: Used to monitor the position of the actuators or can be re-

    purposed for use as additional sensors

    4 Output Zones with the Following Outputs per Zone • 3No. 0 - 10V analogue outputs: Used to control actuators in Monodraught natural ventilation

    products

    Input & Output ZonesD

    Wiring Examples (I)

    Zo ne

    #

    DAMPER/LOUVRE 0V 24VDMP. DMP. LVR.

    WALL ACTUATOR 0V 24V

    0V 24V 0V 24V

    SENSOR 1 SENSOR 2 RS485

    Windcatcher Classic

    4- Co

    re 0

    .5 m

    m 2 C

    ab le

    - RS

    -6 60

    -4 09

    6/ F

    ar ne

    ll 24

    40 12

    1 (s

    up pl

    ie d

    an d

    fit te

    d by

    o th

    er s)

    LVR.

    Zo ne

    #

    DAMPER/LOUVRE 0V 24VDMP. DMP. LVR.

    WALL ACTUATOR 0V 24V

    0V 24V 0V 24V

    SENSOR 1 SENSOR 2 RS485

    4- Co

    re 0

    .5 m

    m 2 C

    ab le

    - RS

    -6 60

    -4 09

    6/ F

    ar ne

    ll 24

    40 12

    1