IntegraCAD 2011 (for Enterprise, Premium, Suite, Professional, Termo, Duct and Sani program version) Professional program for designers of heating, cooling, ventilation, potable water and drainage installations. made: 24.02.2011 © Impuls ing d.o.o. 2011.
120
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Integracad 2011 Eng

IntegraCAD 2011 (for Enterprise, Premium, Suite, Professional, Termo, Duct and Sani program version)

Professional program for designers of heating, cooling,

ventilation, potable water and drainage installations.

made: 24.02.2011

© Impuls ing d.o.o. 2011.

Page 2: Integracad 2011 Eng

Introduction

Cover page

Introduction to the program

System requirements

Program installation

Program fundamentals

Starting the program and basic program settings

Project settings

Main menu

Info window

Product catalogue

Calculations

Short description of abbreviations

Heat load according to EN 12831

Heat transmission coefficient calculation

Heat gains calculation VDI 2078

Radiator selection in a two pipe system

Radiator selection in a one pipe system

Underfloor heating / cooling calculation

Wall heating / cooling calculation

Fan coil selection

Heating pipeline calculation

Fan coil pipeline calculation

Ventilation ducts

Potable water pipeline calculation

Drainage water pipeline calculation

Print

Calculations and material list

Function overwiew

CAD

Drawing basics

Commands and definitions

Admin

Introduction

Radiators

Rooms

IntegraCAD news

IntegraCAD packages

Download last program version from web site

Internet training

Contact

Contact

Page 3: Integracad 2011 Eng

Introduction

Page 4: Integracad 2011 Eng

Introduction to the program

IntegraCAD 2011 is a software program intenden for solving all design problems with potable and drainage water pipeline calculation, heating pipelines, radiator selection (for two pipe system and one pipe system), fan coil selection and fan coil pipeline, floor and wall heating and cooling. You can print the calculation results and material lists directly or export them in several xls file format.

Program packages

You can purchase IntegraCAD 2011 in four different packages. Sani, Duct, Termo, Professional, Suite, Premium, Enterprise. The program packages include the same program framework (program interface, CAD, print, database) but a different amount of calculation modules. You can compare the different packages in the table below:

Page 5: Integracad 2011 Eng

CAD

The CAD moduel can be used to work with technical drawings. You can use drawings in dwg (up to version 2010) and dxf file formats. The program CAD module is completely autonomous and you do not need for any other CAD software to be installed on the computer to work with the drawings. You can create new or edit existing drawings. To find out more follow these links: CAD basics and CAD functions overview

Print

The print module of the program has the following features:

- Standard text editing tools - Edit material lists with capability to add products directly from the program database - Translate the printouts to seeral languages (Albanian, Bulgarian, Bosnian, Chinese (simplified), English, Croatian, Hungarian, Macedonian, Romanian, Russian, Slovenian, Serbian, Turkish.) - Export printouts to xls format - Print with print preview function

Product catalogue

The program has an included products catalogue with technical data, descriptions pictures and article numbers. All products are sorted into groups to allow easyer browsing. The calculation modules use the same technical data as displayed in the catalogue module of the program. You can also use these data to edit material lists in the print module.

New ! - Internet presentation and training

We offer Internet support through a specialised web conferencing system. During the conference the participants can see the presenters screen and follow the session in real time. All users see the same video output (the presenters screen) and can communicate with each other through a live audio connection.

An Internet presentation is the simplest and fastest way to experience the capabilities of the program. Without generating costs and with a minimum time investment, everybody with an interest in the program can get the answers to his/her questions. The presentation will give you a general overview of the software without discussing the fine points. After the presentation phase there will be time for Q&A

Page 6: Integracad 2011 Eng

and a possibility to explore some questions deeper. Program presentations can be individual or public.

Getting help for a current issue has never been easier. Program users can contact us by phone, e-mail or Skype and we will organize a support session as soon as possible. You can ask general questions (how to start a program function, avoid problems, etc.) or questions related to a current project. In general, the explanations will be made with standard support projects. For bigger issues, you can send us your project and drawing files and we will do our best to help. If the problems cannot be resolved during the support session, we will transfer them to our standard technical support procedure.

Internet training allows for a thorough insight into a part of the program. As a program user you have two options: you can request an individual training or you can join one of the regular public trainings. In the first case you can select the training topic freely but you need to make your training request at least 7 days in advance. In the case of public trainings the topic and date are already set and you need to apply at least 24 hours in advance. Public training dates will be announced on our website www.integracad.com at least two weeks in advance.

Page 7: Integracad 2011 Eng

System requirements

Note!

Before you install IntegraCAD program close all running programs. If you have Windows XP on your computer please make sure that you have installed at least Service Pack 2 (My Computer / Control Panel / System / Service Pack no.) Compatible Service Pack and dot net framework you can copy and install from the IntegraCAD installation CD (folder Windows): * Service Pack * Windows -> XP -> WindowsXP-KB942288-v3-x86.exe * dot net framework * Windows -> dotnetfx35.exe or if you don't have IntegraCAD installation CD than download components from following link: http://dl.dropbox.com/u/5681482/Windows.zip

IntegraCAD 2011

Computer system

Minimum Suggested

CPU 1,4 GHz Intel® Core™ 2 Duo

RAM 512 MB

(min. for win XP) 2 GB

(min. for win 7)

Viewscreen 19" 21"

Hard disk 400 MB

Operating system

Windows XP (at least SP2), Vista or Win 7 (32/64 bit)

Licence portable licence with USB stick -

Licence time is period of 30; 90 or 365 days. After that time program will stop

working. Licence time you choose when buying program licence.

Page 8: Integracad 2011 Eng

Program installation from installation CD

Note! All pictures in this help are from english program version and can be different than your IntegraCAD language program version or your IntegraCAD program package (Enterprise, Premium, Suite, Professional, Termo, Duct or Sani)!

Take the CD out of the casing and insert it into your CD-ROM drive. Click the My Computer icon and choose the CD-ROM unit containing the CD Click the name, find IntegraCAD 2011 Setup (language).exe, copy that on your Desktop run it and follow the instructions shown on the screen. Warning! Before you install IntegraCAD program close all running programs. If you have Windows XP on your computer please make sure that you have installed at least Service Pack 2 (My Computer / Control Panel / System / Service Pack no.) Compatible Service Pack and dot net framework you can copy and install from the IntegraCAD installation CD (folder Windows): * Service Pack * Windows -> XP -> WindowsXP-KB942288-v3-x86.exe * dot net framework * Windows -> dotnetfx35.exe or if you don't have IntegraCAD installation CD than download components from following link: http://dl.dropbox.com/u/5681482/Windows.zip

Page 9: Integracad 2011 Eng

Short description of program installation: 1.) extraction files window (will last for a few seconds) 2.) language selection (select installation language, and press OK button to continue instalation) 3.) welcome window (press Next button to continue instalation) 4.) licence agreement window (press Yes I Accept the terms of the Licence Agreement button, and then press Next button to continue instalation) 5.) User information window (type your name and the name of the company you work for, and then press Next button to continue instalation) 6.) Choose Destination Location window (we recommend to permit the program to install his components to his offered directory in that case just press Next button to continue instalation, if you want to install program to some different directory press Browse button - select another directory, and than press Next button to continue instalation) 7.) Set file Association window (press OK button to continue instalation) 8.) Set program shortcuts window (beside the one that program will automatically add on your Start/Program menu, you may add some other shortcuts, press Next button to continue instalation) 9.) Confirm setup settings window (press Next button to continue instalation) 10.) First setup program will install Redist_pack components (it can take a few minutes) 11.) and then will install IntegraCAD 2011 program (it can take a few minutes) 12.) Setup Complete window (press Finish button to complete program installation)

After program installation try to run IntegaCAD program (check that USB key is inserted into your computer!)

If you start a IntegraCAD program then Step number II. will not be needed! If program (after you run it) show following window

Page 10: Integracad 2011 Eng

you'll need to register it (see Program registration).

Program registration

This serial number is your private number and it allows you to use the program. Before you start working with IntegraCAD you should contact the program distributor or Impuls ing d.o.o and supply them with exact information on the name of your program, its Version label and the Serial Number (i.e. IntegraCAD 2011 Enterprise, INT50, 4111588392). You'll get an Activation key for starting the program. Run the program and type the activation key in the required spot (delete the zero). If everything was fine you'll se the button OK activated and be able to start working. You need to type the activation key only once; at all other times the program will run without asking this information (in licence time period that you buy 30, 90 or 365 days). After that time period IntegraCAD 2011 version of the program will stop working

Page 11: Integracad 2011 Eng

Program fundamentals

Page 12: Integracad 2011 Eng

Starting the program and basic program settings

Note! All pictures in this help are from english program version and can be different than your program language version or your IntegraCAD program package (Enterprise, Premium, Suite, Professional, Termo, Duct or Sani)!

Load the program by pressing Start in the lower left corner of the screen and select Programs -> IntegraCAD 2011 (Language). You can start the program also by double

clicking the program shortcut icon on your desktop .

After the program loads you first need to crate a new project. While you are doing this you will also select the calculations that you need for this project. This is just an initial calculation selection and you can change this afterwards by loading/unloading all calculation modules available in the program. By creating and saving a project the program will make a file with a .int ending. This is your project file and it holds all necessary calculation data like the layout of the building, calculation settigngs, finished calculations etc. To save this data permanently you need to save on a hard disk. If you have installed the program on severral computers you can copy this file and use it to work on other computers with the installed software.

To crate a new project select "New" from the File menu or click the icon in the toolbar. The new project wizard will open in a new window. You can now select the calculations you want to do and proceed or crate a new project template with the calculations you most commonly use. You can crate several project templates for this program.

From the project wizard select "Custom project" and press the "Forward" button. Check the calculations you want to work on this project and click "OK".

Page 13: Integracad 2011 Eng

Crating a project template:

* Select the custom template and check the calculations you want to be part of the new template. * Click "Save template". * Enter the template name and description and click "Save".

Page 14: Integracad 2011 Eng

In future projects you can select this new project template form the initial project wizard screen and speed up your calculation selection. You can make several project templates if you like.

Open existing projects

Existing projects can be opened by using the "Open" function from the toolbar or by selecting the same function from the File menu. A new window will open and you need to locate the file on your computer or network (you are looking for a file with the .int extension).

Saving the active project

During work it is possible to save the project to file by using the "Save" function in the

toolbar or the same function from the File menu. A new window will open and you need to give a new file name (or edit the existing file name) and save the file to a disk. If you want to make a copy of the project you can use the "Save as..." function in the File menu. You can always save the project to file from anywhere in the program. We recommend saving the project on a regular basis and also keeping backup files of important projects on other media (network disk, USB disk, CD/DVD ...). This is the best way to insure data integrity and accuracy. To help you with this you can use the integrate Autosave function.

Page 15: Integracad 2011 Eng

Project settings

After creating the project the program will load the selected calculations and setup some basic program settings. After these preparations the first thing you have to do is to create a new building structure. An empty project as initially created by the program is displyed below:

In the upper part of the screen you can see the main menu and toolbar. They include the most common program functions like loading and saving projects, selecting settings, loading/unloading calculation modules etc. On the left side of the screen you can see the tree controls (Project, CAD, Installations, Catalogue) and everything on the right is the main Workspace. The program has four tree controls, each with a distinctive purpose: The project tree - its purpose is to create, edit and view the building and its parts (floors, flats, rooms). The position on this tree often determines to what part of the building some calculation is reffering (e.g if you are positioned on the first floor in the project tree and want to do a radiator selection, the program will do the selection for all rooms on the first floor.)

Page 16: Integracad 2011 Eng

The CAD tree - its purpose is to view and change different settings related to the CAD module. This tree is generally active only when you disply the CAD module on your workspace. You can look at object settings selected inside the CAD drawing surface or look at a list of pipeline drawing connection errors and warnings. You can use this list to quickly jump from one problem to another which is very usefull in a large project drawing. The installation tree - its purpose is to create, edit and view the building pipeline installations (pipelines). This is the place to add new instalations, floor entry points and manifolds. The installation tree is connected to the project tree (e.g. the program will know on which floor a floor entry point is set) but it is not a copy of its structure. You have to define the structure separately from the building structure. You can for example have risers going through each floor but having only floor entry points at every second floor. In this event the number of floor entry points on one riser does not correspond to the number of floors it passes through. The catalogue tree - its purpose is to enable you a look on the products included in the program database in a hierarchical way for easyer product browsing. You can search the products while in the Catalogue module or use it to create CAD drawings in the CAD module or insert products in lists of material in the print module.

The workspace is right of the tree controls and covers the majority of the screen. Most actions happen in it like calculations, print preparation etc. The workspace consists from five interconecting parts: Info, Calculation, CAD, Print and Catalogue. You can switch between these modules simply by clicking on the tab names. Info is the part that is active when you start a new project and its main purpose is to display information about parts of the project. Calculation is the part that includes all calculation modules that can be activated in the program. To move between the different calculations you have to click on the tabs with the calculation names (top of the workspace). To move inside a particular calculation you have to click on the vertical tabs with the calculation part names located in between the tree controls and the workspace. CAD is the part where you can create and edit drawings. This module is compatible with the drawing formats dwg and dxf and includes most common drawing functions found in specialized CAD drawing software programs. To bind drawings to a project you have to make a connection between the drawing file and the floor it represents. Print is the part where you can create and edit different representations of the calculated data. The print module consists of calculation results and lists of material (Bills of Material). Catalogue is the part where you can view and browse products from the program database. You select different products using the Catalogue tree control and the product data is displayed in the Catalogue module on the workspace.

Page 17: Integracad 2011 Eng

Below the workspace is an information bar where the program displays messages to the user, mostly about the progress of started functions like "Calculation finished" or "Project loaded". Most actions that take a longer time to execute will display progress information in the information bar.

Creating a building with the project tree

* Click on New project in the project tree on the left. * Right click on it -> a drop down list with several options will appear -> select Floor. * Now that you have created a new floor, by rightclicking on it you can create appartments and rooms. You can also create rooms inside of appartments. Once you are done creating floors and appartments you can rightclick on one and select a new room from the preloaded list of common rooms. Grouping rooms inside appartments is only made for the purpose of creating a more accurate representation of the building. Other than that there are no restrictions or benefits connected to it. Copying floors, appartments and rooms: Select the entity you whish to copy in the project tree -> rightclick on it and select "Copy" from the drop down list -> select the postition where you want to copy the entity, right click and choose "Paste". To be able to use this function correctly you usually need to go one level up e.g. to paste a room you need to select an appartment or floor, to paste an appartment you need to select a floor, to paste a floor you need to select the project . When you copy an appartment you automatically also copy all the rooms in it. When you copy a room, you also copy all the calculation data connected to it like radiator selection, underfloor heating calculations etc. Deleteing floors, appartments and rooms: Set the pointer on the entity you want to erase from the project tree, right click on it and choose "Delete" from the drop down menu. Changing names of floors, appartments and rooms: Select the entity for the name change in the project tree and press F2 on the keyboard or click one more time on it -> the name will turn blue and you can change it .

Use the described functions to construct you building. You can change all parts of the building (floors, appartments, rooms) anytime you want. WARNING: If you delete a part of the building by accident there is no undo function to bring it back. Save your project often to avoid loosing you work in this way.

Page 18: Integracad 2011 Eng

Changing the tree position of floors, appartments and rooms

* Select an entity in the tree control.

* Using the arrow buttons up and down change the current entity position until it reaches the desired position.

Page 19: Integracad 2011 Eng

Main menu

The Main menu is used to manage a project; the appearance and position of windows, main files and the help system. It is divided into the following sub menus: File, Edit, View, Print, Help.

File - used to manage basic project functions. New - creates a new project, Open - opens an existing project, Close - closes the active project, Save - saves the active project, Save as ... - saves the project named as, Print - prints project, Print preview, Printer settings - sets parameters of the printer; these options are followed by path and names of the last four projects used. The option Exit is used to exit the IntegraCAD program.

Edit - this menu contains standard data editing tools - Undo - move previous command, Redo - returns to previous command, Cut - cuts data (makes a copy but doesn't keep the original); Copy - for copying data (makes a copy and keeps the original; Paste - pastes cut or copied data on a chosen place, Settings - adjust program settings and CAD module in IntegraCAD program, Admin - tool for radiator or room importing, if the same does not exist in the IntegraCAD program.

Page 20: Integracad 2011 Eng

View - contains settings which apply to the whole program and all the projects. Tool bar - used to turn on/off all tool bars in the program (main, for print...) or some for program tree (project, installation, catalogue). Function "Reset toolbal position" - will cancel all current settings, and return it to the standard form in which the program is delivered. Option - "Status bar" - can turn on or turn off status bar window (at the bottom of the IntegraCAD program window) - that displays information about last program activities.

Print - Menu where you can turn on / off some prints. There are two possible ways: 1.) direct from the menu (shorter display)

Page 21: Integracad 2011 Eng

2.) or by "Print settings" button (in that menu) - graphically displays individual prints

Help - used to obtain basic information on IntegraCAD program and advice on using it. Help content - opens a new window with the program's help file displayed. About - build number (RC number) - e.g. on picture RC34, and some basic informations about authors.

Calculation - here you can turn on / off some calculations.

Page 22: Integracad 2011 Eng

Info window

On project level:

Here you can enter some basic datas about project, they are not required, but can be helpful in further work. Insert datas can also be printed.

* Enter object name and project number. * Select date from calendar * In field "Note" you can enter some text for project description . * Enter data about designer and investor.

Page 23: Integracad 2011 Eng

On floor level:

Here you can define some basic geometry floor attribute (ceiling height, room height, height above ground), path where the drawing file is stored on the disk, drawing measure, label text height in the drawing. IntegraCAD 2011 works with standard .dwg drawings, and it's compatible with AutoCAD drawing files up to version AutoCAD 2010.

Under basic geometry attributes there are some heating and cooling calculation datas for every room on floor.

* Select floor (on project tree). * On left you can enter floor dimensions, like ceiling height, room height, height above ground. * In "Drawing settings" part you can set DWG file path.

* On default settings press button (DWG file path) and select drawing (drawing path), that you want to join to the floor. Drawing must be in .dwg or in .dxf format.

Page 24: Integracad 2011 Eng

We recommend that the *.int and *.dwg file record in the same directory.

* Press button on default settings (Measure) to define measure, measure units and text style settings.

Page 25: Integracad 2011 Eng

Here you can also set the some element labels that you will later used in the calculations. Default labels are: F - floor label; A - apartment label; R - room label. Also some tags can be customized according to the building, according to the floor or to the flat. Program accepted new settings by pressing a Set button.

In table below you can see some datas related with rooms in project.

Label room label

Room room name

A (m2) room name

ti (°C) internal temperature in (°C)

Qn (W) heat gains in (W)

Qinst (W) installed heating capacity in (W)

Qres (W) remaining heat quantity (W)

Qi(two) (W) total installed heat capacity with two pipe system in (W)

Qi(one) (W)

total installed heat capacity with one pipe system in (W)

Qi(flh) (W) total installed heat capacity with floor heating /cooling in (W)

Qi(wall) (W)

total installed heat capacity with wall heating /cooling in (W)

Qi(fc) (W); total installed heat capacity with fancoil /cooling heating in

(W)

Page 26: Integracad 2011 Eng

Product catalogue

You can activate the product catalogue by clicking the Catalogue tab in the Tree view

and also on the main workspace (you need to click both). .

Within the catalogue tree view the products are sorted by :

* group (pipe, fittings, sink points, manifolds, radiators...)

* subgroups (FUSIOTHERM-Pipe SDR 6 (PN 20) ...)

* products (Fusiotherm SDR 6 16 x 2,7 , Fusiotherm SDR 6 20 x 3,4 , ... )

If you want to get more information about an item just click on it.

On the workspace you will get more detailed data (most details are for products):

* Manufacturer logo

* Product picture

* Article number

* Short and long product description

* Technical data

Page 27: Integracad 2011 Eng

Short description of abbreviations in

calculations

Page 28: Integracad 2011 Eng

HEAT LOAD ACC. TO EN 12831

DEFAULT SETTINGS

Heat loss

outside project

temperatue (°C) Norm. outside temperature according to EN12831

Annual mean

external

temeprature (°C)

Mead value of the external temeprature during the year

Shielding class

No shielding (buildings in windy areas, high rise buildins in city centers);

Moderate shielding (buildings in the country with trees or other buildins

around them, suburbs); Heavy shielding (average height buildins in city

centers, buildings in forrests)

Building type Single family dwelling; Other dwellings and buildings

Degree of air-

tightness

Degree of air-tightness of the building envelope (quality of window seal)

can be ;High (high quality sealed windows and doors); Madium (double

glaze windows, normal seal); Low (single glaze windows, no sealant)

Air exchange rate

n50

for the whole building resulting from a pressure difference of 50 Pa

between the inside and the outside is determined according to the degree

of air-tighness and the building type. The program will suggest the range

for the values to be entered (for example between 4 and 10 for a single

family dwelling with a medium degree of air-tightness).

Construction

can be: Low building mass (suspended ceilings and raised floors and ligh

walls); Madium building mass (cencrete floor and ceilings and light

walls); High building mass (concrete floors and ceilings combined with

concrete or brick walls)

Underground

water depth (m)

The depth of ground water can be set to below or above one meter. If the

value is set below one meter, the transmission heat loss towards the

ground will be increased (Gw, the ground water correction factor will be

increased from 1 to 1.15).

Volume of the

building (m3) Total building volume

V ex (m3/h) Exhaust air flow rate the whole building

V su (m3/h) Supply flow rate for the whole building

parametar B' for building

P (m) Floor perimeter

Ag (m2) Floor surface

B'

Parametar B' for all rooms without external walls separating the heated

space under consideration from the external enviroment, and for all rooms

with well insulated floor

Page 29: Integracad 2011 Eng

Recalculate heat

losses

The "Recalculate heat losses" button will make a complete heat load

calculation using the values set in the calculation defaults. You can use

this for example to recalculate the heat load using a different design

external temperature

Transfer heat loss

to equipment

selection

The "Transfer heat loss to equipment selection" will overwrite and heat

loss values in the equipment selection calculation modules (radiator

selection, underfloor heating ...). You can use this before the initial

equipment selection but also when you made some changes to the heat

load calculation and want to see the effects on the already selected

equipment.

CALCULATION

Input room data

A/a (m2/m) Room surface or length

b (m) Room width

c (m) Room height

h (m) Floor height from ground

V (m3) Room volume

O (m2) Superficial area of room

Theta su, i (°C) Temperature of supply air for mechanical ventilation

V su,i (m3/h) Supply air flow rate for mechanical ventilation

Nr. of openings Number of exterior openings

e i Shielding coefficient

n min (1/h) Minimal air exchange rate in one hour

f vi Temperature reduction factor (depending on internal room temperature,

supply air temeprature and external design temperature)

Theta int,i Internal roo mtemperature

T (m) Depth of ground water

Gw Ground water correction factor

fg1 Correction factor taking into account the influence of annual variation of

external temperature.

fh,i Correction factor for room height (rooms between 5 m and 15 m heigh)

f RH Correction factor for heating-up

Calculation results

Theta e (°C) External design temperature (°C)

Phi V, inf (W) Infiltration ventilation losses

Phi V, min (W) Hygiene air flow ventilation losses

Phi V, mech, inf

(W) Mechanical ventilation losses for building

Phi V, su (W) Room supply air mechanical ventilation losses

Phi V, mech (W) Total mechanical ventilation losses

Page 30: Integracad 2011 Eng

Phi T, i (W) Transmission heat loss

Phi V, i (W) Ventilation heat loss

Phi RH (W) Heating-up capacity heat loss

Phi (W) Heat load

Phi/A (W/m2) Heat load per square meter

Phi/V (W/m3) Heat load per cubic meter

Table

Lab. Building element label

Surface to Surface type on the other side of the building element (exterior, non-

heated room, ground etc.)

OR Orientation of building element

Nr. Number of equal elements (equal by dimmension, U coeff., position etc.)

LEN (m) Length of building element in meters

H/W (m) Height of width of building element in meters

A (m2) Surface of building element

R Surface reduction factor

A' (m2) Building element net surface

P (m2) Room perimeter in contact with ground

B'(m2) Characteristic parameter

Z (m) Depth of floor slab

U (W/m2K) Heat transmittance coefficient

Ueq (W/m2K) Equivalent heat transmittance coefficient

Theta u/as (°C) Temperature of non-heated space / space heated to a lower temperature

ek

Correction factor for the exposure taking into account climatic influences

such as different insulation, moisture absorption of building elements,

wind velocity and temperature, provided these influences have not already

been taken into account in the determination of the U values.

bu Temperature reduction factor taking into account the difference between

temeprature of the unheated space and the external design temperature.

fij Temprature reduction factor taking into account the difference between

temperature of the adjacent space and the external design temperatre.

fg2 Temperature reduction factor taking into account the difference between

annual mean external temperature and external design temperature.

TM (W/K) Thermal bridge

HT, i (W/K) The transmission heat loss coefficient of the building element.

Phi T,i (W) The transmission heat loss of the building element.

Page 31: Integracad 2011 Eng

HEAT TRANSMISSION COEFFICIENT

CALCULATION

CALCULATION

Load coefficient

from database

To load the coefficients from a database press "Load coefficient from

database" button. A new window will open with all stored coefficient in the

database. If there is no coefficients you must store it first (button Save

coefficient to database). To load the saved coefficients in calculation part of

program, mark one of the 'Load' column coefficients and press Ok button.

With 'Cancel' button this operation will be canceled, with 'Delete' button

selected coefficients will be deleted.

Save coefficient

to database

Calculated or entered coefficients can be stored in User.dat database that

could be used in some new projects. In this way it is possible to use your

own base coefficients, (one that you usually use in the calculations).

Calculated coefficients are stored along with materials of which they were

made. To save the coefficient in the database you must press "Save

coefficient to database" button. Once saved coefficient you can used (after

loading the program) in all future projects.

Transfer

coefficient

dimmensions

If this button is checked, the set length and height will be transferred to all

occurances of this coefficient. If button is unchecked, no values will be

transferred to the calculations

Label coefficient label

Type coefficient type

Ra (m2K/W) Outbound resistance coefficient

Ri (m2K/W) Inbound resistance coefficient

U (W/m2K) thermal transmittance of building element

window/door

you can label a building part as window or door by clicking on the mark. If

you do so, you can also input the default length and height of the part. You

can use this system to input several sizes of standard windows and doors in

a building.

LEN (m) wall length in meters

Height (m) wall height in meters

Recalculate and

transfer data

The surfaces will be recalculated and the heat losses will be propagated to

all rooms automatically

Recalculate

without transfer

The surfaces will be recalculated but the heat losses will not propagate to

the rooms automatically

Recalculate heat

losses

You can change the U-coefficient values and recalculate the whole

transmission heat loss with a single click on this button

Sum d (m) wall thickness in meters

SumR (m2K/W) wall heat flow resistance in (m2K/W)

Page 32: Integracad 2011 Eng

Material table

Layer material double click on this cell and new window for material selection will appear.

d (m) thickness

Ro (kg/m3) material density

d*Ro (kg/m2) product of thickness and material density

L (W/mK) material thermal conduytivity

R (m2K/W) thermal conductivity resistance

Page 33: Integracad 2011 Eng

HEAT GAINS CALCULATION VDI 2078

DEFAULT SETTINGS

Weather cloudy or sunny

Climate zone climate zone specified by temperature conditions

Outer temperature

flow for given

month

month selection

Add zone button for adding new climate zone

Delete zone button for deleteing existing climate zone in program

Save active zone

When you add a new zone you can save it with this button.

Once you save it new zone will be stored in the customer base (User.dat)

that could be used in other projects also.

Adopt gains Program will set the heat gains in all areas of the project to the maximum

gains calculated in the VDI2078 calculation.

Copy surfaces to

cooling load

If we did before calculation of heat losses by eg. EN12831 standard, then

we can take advantage of areas that are defined there. Open the dialog to

choose which areas you want to copy to the gains heat calculation.

Change

orientation

If define wrong house orientation, eg. we didn't know, we get that

information later, or we just wan't to see how much gains will be if we

oriented object differently, then we can "Change object orientation". e.g.

what was to the north is now actually south, then program will (in a circle)

change all orientations on all surfaces, northeast will be the outhwest, etc.

Recalculate recalculate calculation

Default settings

Room type Room type selection - depending on the construction

(XL-very light, L-light, M-medium, S-heavy)

Date date selection

qs(W/m2) solar radiation (W/m2)

Orientation room orientation

T turbidity factor

ti (°C) room temperature in (°C)

Radiation type area radiation

Hour hour selection

Cooling zone cooling zone number

Default values for

room set default values of some room

Page 34: Integracad 2011 Eng

CALCULATION

Input room data

Room type Room type selection - depending on the construction

(XL-very light, L-light, M-medium, S-heavy)

Orientation room orientation

Radiation type area radiation

Date date selection

T turbidity factor

Hour hour selection

qs(W/m2) solar radiation (W/m

2)

Cooling zone cooling zone number

a (m) room lenght (m)

b (m) room width (m)

c (m) room height (m)

V (m3) room volume (m

3)

O (m2) superficial room area (m

2)

Ap (m2) room surface (m

2)

ti (°C) room temperature in (°C)

Output room data

Qp (Persons) (W) heat gains due to persons (W)

Qb (Lights) (W) heat gains due to lighting (W)

Qm (Machines)

(W) heat gains due to machines and appliances (W)

Qg (Material

transit) (W) heat gains due to material throughput (W)

Qr (Transmision)

(W) heat gains due to different temperatures in adjacent rooms (W)

Qc (Rest) (W) other heat supply and heat removal (W)

Qw (Walls and

roofs) (W) heat gains through external walls and roofs (W)

Qt (Window

transmission) (W) heat gains due to transmission through windows (W)

Qs (Window

radiation) (W) heat gains due to radiation (W)

Qlf (Infiltration)

(W) heat gains due to infiltration (W)

Total (W) total cooling load (W)

Qtot (W) total room cooling load (W)

Qtot (W/m3) total cooling load per m

3 (W/m

3)

Copy from room copy data from some room

Page 35: Integracad 2011 Eng

ti; Persons; Lights; Machines; Material throughput; Adjacent room; Surfaces;

Ventilation; Graph

Inner temperature

flow

inner temperature flow is shown in tables and graphs. Data in tables be can

changed.

Persons

When calculating the heat gains from people it is important the time that

people spend working in some area (select work time), and the type of

work (heavy, medium or light work).

Lights

Light calculation takes into account several parameters:Light group, Work

time, Convection ratio, Installed light power (P), Room load factor due to

lighting (l) and simultanelty factor (mb).

Machines

Select machine (add new one or change name for existing one), select

work time, accumulation function, rated machine power (P), main motor

efficiency (n), load factor of the machine at the time in question (may) and

simultaneity factor (l). Press Fill button to fill tables below.

Material

throughput

this calculation refers to some outside materials that will be entered into

heated room. Select material throughput (add new one or change name for

existing one), work time, accumulation function, mass of the material

brought into the room or removed from it in the unit of time (m), main

specific heat capacity (c), inlet temperature (te), outlet temperature (ta).

Press Fill button to fill tables below.

Adjacent room

heat gains from adjacent room.

Lbl - room label; LEN - length in (m); L/W - length/width in (m); A -

surface in (m2) ; U - thermal transmittance of building element (W/m

2K);

OT - outside air temperature in °C (temperature behind the wall); ΔT -

temperature difference in °C (temperature difference behind the wall and

room temperature) ;Q - Capacity in Watt.

Page 36: Integracad 2011 Eng

Surfaces

heat gains calculation through the surfaces that are exposed to sun,

windows, walls or roofs.

Lbl - surface label; Or. - orientation; Type - surface type; BC - building

construction class (used only for walls and roof); Δz - time adjustment

(used only for walls and roof); SP - surface (window) protection, user can

select external/none or internal; Num. - number of same surfaces; Len -

length in (m); H/W - hight/width in (m); A - surface in (m2); R - reduction

column (for windows enter - ); As - surface effective area (takes into

account if some window is shaded) ; Au - total surface area (As x Num.=

Au); U - thermal transmittance in (W/m2K); de1 - equivalent temperature

difference in Kelvin (calculated as the outdoor temperature minus room

temperature); de2 - equivalent temperature difference for painted walls and

roofs in Kelvin; b - mean transmission coefficient b of solar radiation

(select by double-clicking on the column); qs - solar radiation in (W/m2);

Qok - heat gains due to transmission in (W); Qoz - heat gains due to solar

radiation in (W)

Ventilation Ventilation influence on heat gains. Regeneration/recuperation percentage;

i - air exchange rate.

Graph Represents the sum of heat gains by the hour for all performed

calculations.

Page 37: Integracad 2011 Eng

RADIATOR SELECTION IN TWO PIPE SYSTEM

DEFAULT SETTINGS

Calculation

DIN4703

In the calculation part you can select the method for determining the

radiator output. DIN 4703 is "old" calculation method with typical

temperatures 90/70/20

EN442

In the calculation part you can select the method for determining the

radiator output. EN442 is "new" european standard adjusted for low

temperature heating with typical temperatures 75/65/20

Security factor

Security factor (Qi/Qn)

Input the security factor if needed. If you want to cover a 15% higher

heat loss with radiators you need to input the security factor of 1,15.

Also if you want to cover only 60% of the needed heat loss with

radiators and the reast with alternative heating equipment, write 0,6

into the field.

Temperature

Supply water

temperature (°C)

input supply water temperature Regardless of the method of

calculation program internally calculates radiator capacity for input

values of supply water temperature.

Return water

temperature (°C)

input return water temperature Regardless of the method of

calculation program internally calculates radiator capacity for input

values of return water temperature.

Calculation type

Calculate radiators with

same dimensions

if this button is selected than program will do calculation according

to radiators with same dimensions

Calculate radiators with

different dimensions

if this button is selected than program will do calculation according

to radiators with different dimensions

Recalculate radiator

capacity

In you later (after you already select your radiator) change their

temperature in some other (e.g. from 20 (°C) in 18 (°C)) than click

on this button so that program can recalculate new capacity

according to new temperature.

Calculate radiator

dimensions

If you want that program in new capacity calculation takes into

acount new radiator dimensions check this button. If this button is

unchecked, than program will do new capacity calculation without

new dimensions, just with new Supply and Return water

temperature.

Page 38: Integracad 2011 Eng

Table

ti (°C) input room inner temperature (e.g. 20 - means 20 (°C))

Manufacturer select radiator manufacturer.

Group select radiator group (group depends on previously selected

manufacturer.)

Radiator Select radiator type (radiator type depends on previously selected

radiator group and radiator manufacturer.)

Mt

select one of 11 radiator mounting types: 1 - Connection from floor

with standard valve; 2 - Connection from wall with standard valve; 3

- Connection from floor with standard valve; 4 - Connection from

wall with standard valve; 5 - Connection from floor with compact

valve; 6 - Connection from wall with compact angle valve; 7 -

Connection from floor with valve with riser/immersion pipe; 8 -

Connection from floor with valve with immersion pipe; 9 -

Connection from floor with central connection point; 10 - Direct

connection from above ; 11 - Direct connection from above

Hei. (mm) Radiator height. Select it by double-clicking on this field. Program

will choose radiator height acc. to this value.

M. len. (mm)

maximum radiator length value When program starts with selection

he will start from a minimum length for a given height of the radiator

and will never exceed the maximum value entered here

Balance valve Balance valve selection. If some radiator have integrated valve in it

than program will mark it with "Integrated valve".

Valve select termostatic valve

Check dimensions

Command is used to check the maximum height and length after the

change of selected groups of radiators. Dimensions that do not exist

in the selected group will be highlighted in red.

Find groups pressing this button program will find radiator group for the set

height.

Radiator type This button is used for the radiator selection with buttons + (select

all) and - (unselect all).

CALCULATION

Options

Calculate all select connection point -> the program will add radiators in all listed

rooms according to the default radiator setup.

Delete all

This will delete all radiators for all rooms listed in the table, and only

the basic room data will be displayed (temperature, surface, heat

loss).

Add Select the connection from the new window -> one radiator is added

to the line (room) with your current table position.

Page 39: Integracad 2011 Eng

Delete

In the event that there is just one radiator in the room, it will be

deleted and the row will display only the basic room data. If there are

more than one raditors in the room, the selected radiator will be

deleted, the list will move up for one row and the capacity of the

radiators in the room will be racalculated.

Show only radiators

from selected group

will show only those radiators whose group you selected in the

default settings

Radiator selection for

heat load

Calculation for:

Project/Floor/Room project name / floor name / room name - (see project tree)

Table

Room name of the room where there radiators are

Nr.(pcs) Number of radiators that automatically should be selected for a

selected room

ti (°C) Inner room temperature

A (m2) Room surface

Qn (W) Heat losses

Qni (W) Total installed heat capacity (beside radiator, includes other heaters

too)

Qn(r) (W) Norm radiator capacity

Qi (W) Installed radiator capacity

Vertical Radiator connection (manifold or direct on some floor)

Label radiator label (radiator ID made of radiator label) RD and some

number - e.g. RD1; RD2 ...

Radiator radiator name

Mt

select one of 11 radiator mounting types: 1 - Connection from floor

with standard valve; 2 - Connection from wall with standard valve; 3

- Connection from floor with standard valve; 4 - Connection from

wall with standard valve; 5 - Connection from floor with compact

valve; 6 - Connection from wall with compact angle valve; 7 -

Connection from floor with valve with riser/immersion pipe; 8 -

Connection from floor with valve with immersion pipe; 9 -

Connection from floor with central connection point; 10 - Direct

connection from above ; 11 - Direct connection from above

Nr. gl. Number of glides (for glide radistors)

Hei. (mm) Radiator height

Len. (mm) Radiator lenght

Fact. Radiator mask factor

Qi(r) (W) Radiator capacity

Page 40: Integracad 2011 Eng

RADIATOR ADDITIONS

Project/Floor/Room radiator position in project name / floor name / room name - (see

project tree)

short description of the column in the table on which you are

positioned.

Label room label (where the radiator is located)

Room room name (where the radiator is located)

Label radiator label

Radiator radiator name (type; height/width). If you want to change some of

the radiator then you have to do in previous "Calculation" part.

Mt

select one of 11 radiator mounting types: 1 - Connection from floor

with standard valve; 2 - Connection from wall with standard valve; 3

- Connection from floor with standard valve; 4 - Connection from

wall with standard valve; 5 - Connection from floor with compact

valve; 6 - Connection from wall with compact angle valve; 7 -

Connection from floor with valve with riser/immersion pipe; 8 -

Connection from floor with valve with immersion pipe; 9 -

Connection from floor with central connection point; 10 - Direct

connection from above ; 11 - Direct connection from above

Valve thermostatic valve. For selection it is necessary to double click into

the field.

x settings for thermostatic valve

Balance valve

For the selection it is necessary to double click into the field. unless

if radiator already have integrated balance valve in it (then this field

will be filled).

console type

It is not possible to choose radiator console for all radiator typs

because this option depends of radiator manufacturer. For radiators

which has these additions you can choose between: wall console -

radiators mounted on the wall or floor console - radiators mounted

on the floor (standing alone).

wall type

depends on the previous column "console type" and on preferences

of individual producers. if in previous column selection is possible

then here you can choose this two wall typs: treated wall - plastered

wall; untreated wall - wall that is not fully processed.

console console name that corresponding for some radiator type. Depends on

the previous column selection "console type" and "wall type".

color select color for radiators. Note! this option depends of radiator

producer.

Page 41: Integracad 2011 Eng

RADIATOR SELECTION IN ONE PIPE SYSTEM

DEFAULT SETTINGS

Calculation

DIN4703

In the calculation part you can select the method for determining the

radiator output. DIN 4703 is "old" calculation method with typical

temperatures 90/70/20

EN442

In the calculation part you can select the method for determining the

radiator output. EN442 is "new" european standard adjusted for low

temperature heating with typical temperatures 75/65/20

Security factor

Security factor

(Qi/Qn)

Input the security factor if needed. If you want to cover a 15% higher

heat loss with radiators you need to input the security factor of 1,15.

Also if you want to cover only 60% of the needed heat loss with

radiators and the reast with alternative heating equipment, write 0,6

into the field.

Temperature

Supply water

temperature (°C)

input supply water temperature Regardless of the method of calculation

program internally calculates radiator capacity for input values of

supply water temperature.

Return water

temperature (°C)

input return water temperature Regardless of the method of calculation

program internally calculates radiator capacity for input values of

return water temperature.

button

select pipe. Press button (with three points) and in the new open

window from the drop-down menu select group of pipes and pipe for

one pipe system.

Recalculate radiator

capacity

In you later (after you already select your radiator) change their

temperature in some other (e.g. from 20 (°C) in 18 (°C)) than click on

this button so that program can recalculate new capacity according to

new temperature.

Page 42: Integracad 2011 Eng

Table

ti (°C) input room inner temperature (e.g. 20 - means 20 (°C))

Manufacturer select radiator manufacturer.

Group select radiator group (group depends on previously selected

manufacturer.)

Radiator Select radiator type (radiator type depends on previously selected

radiator group and radiator manufacturer.)

Mt

select one of 11 radiator mounting types: 1 - Connection from floor

with standard valve; 2 - Connection from wall with standard valve; 3 -

Connection from floor with standard valve; 4 - Connection from wall

with standard valve; 5 - Connection from floor with compact valve; 6 -

Connection from wall with compact angle valve; 7 - Connection from

floor with valve with riser/immersion pipe; 8 - Connection from floor

with valve with immersion pipe; 9 - Connection from floor with central

connection point; 10 - Direct connection from above ; 11 - Direct

connection from above

Hei. (mm) Radiator height. Select it by double-clicking on this field. Program will

choose radiator height acc. to this value.

M. len. (mm)

maximum radiator length value When program starts with selection he

will start from a minimum length for a given height of the radiator and

will never exceed the maximum value entered here

One pipe valve Balance valve selection. If some radiator have integrated valve in it

than program will mark it with "Integrated valve".

% percentage of valve permeability

ζ local resistance on radiator

termostatic valve select termostatic valve

HEATING CIRCUIT

Circle name name of heating circle

Qn,one (W) heat loss that should be covered in (W)

tpsup (°C) supply water temperature

tret (°C) return water temperature

Pipe pipes used in heating circle

L (m) pipe length in the heating circuit

Roug. (mm) pipe roughness

Sum. ζ total local resistance in pipeline

ΔP const. calculation according to constant pressure drop

Δt temperature difference

w (m/s) water velocity in pipes

M (kg/h) mass flow in heating circuit

Lekv (m) equivalent pipe length

R (kPa/m) pressure drop per meter

Page 43: Integracad 2011 Eng

Δ φ (kPa) pressure drop in heating circuit

Qone Inst (W) installed heating capacity in heating circuit

Ris. connection spot

Options

New circuit makes new heating circuit

Add room Select the connection from the new window -> one radiator is added to

the line (room) with your current table position.

Calculate all select connection point -> the program will add radiators in all listed

rooms according to the default radiator setup.

Delete all This will delete all radiators for all rooms listed in the table, and only

the basic room data will be displayed (temperature, surface, heat loss).

Add Select the connection from the new window -> one radiator is added to

the line (room) with your current table position.

Delete

In the event that there is just one radiator in the room, it will be deleted

and the row will display only the basic room data. If there are more

than one raditors in the room, the selected radiator will be deleted, the

list will move up for one row and the capacity of the radiators in the

room will be racalculated.

Move

Up

The order of the rooms in the circle can be changed by pressing the

"Up" button. Changing the order of the rooms program will do

calculation again.

Down

The order of the rooms in the circle can be changed by pressing the

"Down" button. Changing the order of the rooms program will do

calculation again.

Table

Room name of the room where there radiators are

ti (°C) Inner room temperature

Qn (W) Heat losses

Qinst (W) total installed heat capacity (beside radiator, includes other heaters too)

Qn,one (W) heat capacity that shoud be compensate to radiators in one pipe system

Qone Inst (W) installed radiator capacity in room in one pipe system

Qn(r) (W) Norm radiator capacity

Valve termostatic valve

% percentage of valve flow capacity

ζ local resistance on radiator

Label

Page 44: Integracad 2011 Eng

Radiator radiator type

Mt

select one of 11 radiator mounting types: 1 - Connection from floor

with standard valve; 2 - Connection from wall with standard valve; 3 -

Connection from floor with standard valve; 4 - Connection from wall

with standard valve; 5 - Connection from floor with compact valve; 6 -

Connection from wall with compact angle valve; 7 - Connection from

floor with valve with riser/immersion pipe; 8 - Connection from floor

with valve with immersion pipe; 9 - Connection from floor with central

connection point; 10 - Direct connection from above ; 11 - Direct

connection from above

T. valve termostatic valve on radiator

x thermostatic valve position adjustment

Nr. gl. Number of glides (for glide radiators)

Len. (mm) radiator lenght

Hei. (mm) radiator height

FM Radiator mask factor

tm (°C) medium water temperature in radiator

Q Inst(r) (W) installed radiator capacity

RADIATOR ADDITIONS

Project/Floor/Room radiator position in project name / floor name / room name - (see

project tree)

short description of the column in the table on which you are

positioned.

Label room label (where the radiator is located)

Room room name (where the radiator is located)

Label radiator label

Radiator radiator name (type; height/width). If you want to change some of the

radiator then you have to do in previous "Calculation" part.

Mt

select one of 11 radiator mounting types: 1 - Connection from floor

with standard valve; 2 - Connection from wall with standard valve; 3 -

Connection from floor with standard valve; 4 - Connection from wall

with standard valve; 5 - Connection from floor with compact valve; 6 -

Connection from wall with compact angle valve; 7 - Connection from

floor with valve with riser/immersion pipe; 8 - Connection from floor

with valve with immersion pipe; 9 - Connection from floor with central

connection point; 10 - Direct connection from above ; 11 - Direct

connection from above

Valve thermostatic valve. For selection it is necessary to double click into the

field.

x settings for thermostatic valve

Balance valve

For the selection it is necessary to double click into the field. unless if

radiator already have integrated balance valve in it (then this field will

be filled).

Page 45: Integracad 2011 Eng

console type

It is not possible to choose radiator console for all radiator typs because

this option depends of radiator manufacturer. For radiators which has

these additions you can choose between: wall console - radiators

mounted on the wall or floor console - radiators mounted on the floor

(standing alone).

wall type

depends on the previous column "console type" and on preferences of

individual producers. if in previous column selection is possible then

here you can choose this two wall typs: treated wall - plastered wall;

untreated wall - wall that is not fully processed.

console console name that corresponding for some radiator type. Depends on

the previous column selection "console type" and "wall type".

color select color for radiators. Note! this option depends of radiator

producer.

Page 46: Integracad 2011 Eng

UNDERFLOOR HEATING / COOLING

CALCULATION

DEFAULT SETTINGS

System

System select floor system for heating / cooling. Press the button and choose floor

system. Systems are defined by manufacturer.

Subsysem after you select floor system in this field choose subsysem. Here subsystem

can not be changed, you can change it only in the previous field "System"

Pipe Select one of the listed pipe for underfloor heating / cooling system. Pipe

selection list depends of the selected system / subsystem.

Coating

Coating select some of the floor coating. ceramics tiles; Parquet; Marble; Stone

panels; Carpet; Linoleum ...

Coating width

(mm)

Coating width depends on selected coating. Program will automatically put

some standard widths in mm, but you can change that value.

Screed select screed

Screed thermal

conductivity

(W/mK)

For selected screed program automatically puts some standard values for

screed thermal conductivity, but you can change that value.

Screed width

(mm) Screed width (including pipe width) (mm)

Auto pipe step selection

Auto pipe step

selection

For selected floor heating / cooling system you can limit pipe step by using

minimum and maximum values. To do that select this window.

min Select minimum pipe step (values depends on previously selected floor

system. Don't forget to mark previous "Auto pipe step selection" window)

max Select maximum pipe step (values depends on previously selected floor

system. Don't forget to mark previous "Auto pipe step selection" window)

Border values

Maximum

pressure drop

This value is given by the manufacturer, as his recommendation of a

maximum value over that we should not be allowed to go. value can be

changed.

Maximum loop

lenght

This value is given by the manufacturer, as his recommendation of a

maximum value over that we should not be allowed to go. value can be

changed.

Page 47: Integracad 2011 Eng

Maximum floor temperature

Habitation zone Maximum habitation zone temperature. This value is given according to

standard, but you can change it.

Border zone Maximum border zone temperature. This value is given according to

standard, but you can change it.

Bathroom Habitation zone floor surface temperature in bathroom This value is given

according to standard, but you can change it.

Bathroom

temperature +

(°C)

Difference between the inner room temeprature and the floor temperature in

the occupied area. This value is given according to standard, but you can

change it.

Temperature of

room underneath

input temperature of room underneath. This value is given according to

standard, but you can change it.

Heating temperature

Wanted supply

temperature Wanted supply water temperature on manifold for heating

Temp. difference Temperature difference in kelvin for heating

min

minimum water temperature difference by zones (Habitation or Border) in

kelvin for heating. This values are given according to standard, but you can

change it.

max

maximum water temperature difference by zones (Habitation or Border) in

kelvin for heating. This values are given according to standard, but you can

change it.

Cooling temperature

Wanted supply

temperature Wanted supply water temperature on manifold for cooling

Temp. difference Temperature difference in kelvin for cooling

min

minimum water temperature difference by zones (Habitation or Border) in

kelvin for cooling. This values are given according to standard, but you can

change it.

max

maximum water temperature difference by zones (Habitation or Border) in

kelvin for cooling. This values are given according to standard, but you can

change it.

Additional

insulation width Additional insulation width in (mm)

Element label

Loop label Underfloor system loop label. Initial label can be changed, in that case

program will accept new ones after you press "Set" button.

Set Initial underfloor system loop label can be changed (previous field) in that

case program will accept new loop label after you press this button.

Page 48: Integracad 2011 Eng

Recalculate pressing this button program will recalculate a complete floor heating /

cooling calculation according to some new set values.

Sort labels

This button is used to re-sort the loops in the floor system. (e.g.you have

loops marked as WF1; WF2; WF3 and WF4 and you decide to earse for

e.g. loops WF2 and WF3. Program will than have loops WF1 and WF4. If

we decide to add one new loop, program will label it as WF5. So now we

have WF1; WF4 and WF5. Pressing on this button program will sort loop

labels (from WF1; WF4; WF5 to WF1; WF2; WF3).

FLOOR HEATING

Floor heating: Project/Floot/Room

Qn (W) Heat losses

Floor surface

(m2) Floor surface

Surface for floor

heating (m2) Surface for floor heating

ti (°C) internal temperature

Qn' (W) needed heating capacity

Qinst (W) installed heating capacity

Qre (W) remaining heat quantity

Loop surface

(m2) all loop surfaces in room

Max. floor temp.

(°C) maximum floor temperature

Coating select some of the floor coating. ceramics tiles; Parquet; Marble; Stone

panels; Carpet; Linoleum ...

R coat.

(m2*K/W) coating thermal conductivity resistance

Screed select screed

R screed

(m2*K/W) screed thermal conductivity resistance

Calculation for

fixed loop

number

If you want to make a calculation for a certain loop number than select this

box. This field is associated with the following field "Number of loops".

Number of loops Number of loops in room

Additional

insulation select additional insulation for floor heating system

Pipe select pipe for floor heating system

Wanted supply

water

temperature (°C)

Wanted supply water temperature on manifold for heating

Temperature of

room underneath temperature of room underneath

Page 49: Integracad 2011 Eng

(°C)

Maximum

pressure drop

(kPa)

maximum pressure drop

Maximum loop

lenght (m) maximum loop lenght

Cooling

Qn (W) Heat load

Coverage (%) Percent of installed cooling capacity

Wanted supply

temperature (°C) Wanted supply water temperature on manifold for cooling

Calculation by

mass flow from

heating

calculation by mass flow from heating

System select floor heating system

Subsystem select floor heating subsystem

Add pressing this button program will add new floor heating loop, that can cover

entire given surface.

Add X

Auto

To shorten the calculation process use the button "Auto". This function will

attempt to find the optimal floor cooling loop/s with preset loop size, floor

temperature, pressure drop etc. As mentioned before, there are cases in

which it is not possible to meet all needs with just floor heating and the

"Auto" function will not find an optimal solution in these cases. The

calculation is also adjustable.

Delete pressing this button program will delete selected floor heating loop from

project.

Delete all pressing this button program will delete all floor heating loops in one room

Recalculate pressing this button program will recalculate a complete floor heating

calculation according to some new set values.

Table

V/M manifold that is connected with loop.

Label loop label

D (mm) thickness of floor coverings

RlaB (m2K/W) Coating thermal conductivity, value is calculated

Qn (W) Heat losses

A (m2) Floor surface

T (mm) pipe step - value can be changed by double-clicking on the column

Page 50: Integracad 2011 Eng

tp (°C) Floor temperature

q (W/m2) heat capacity that loop gives

Qn (W) heat capacity - value for border zone

A (m2) Floor surface - value for border zone

T (mm) pipe step - value for border zone

tp (°C) floor temperature - value for border zone

q (W/m2) amount of heat that loop gives - value for border zone

Δt (°C) Temperature difference between supply and return water

l (m) loop lenght

ld (m) lenght of connecting pipe in loop

Qi(k) (W) upwards installed capacity

Qtot (W) total floor heating capacity

m (kg/h) mass flow

Δp (kPa) pressure droop

Valve pos. Manifold balance valve position

FLOOR COOLING

Floor cooling: Project/Floor/Room

Qn (W) Heat losses

Floor surface

(m2) Room floor surface

Surface for floor

cooling (m2) Surface for floor cooling

ti (°C) internal temperature

Qn' (W) needed cooling capacity

Qinst (W) installed cooling capacity

Qre (W) remaining cooling quantity

Loop surface

(m2) all loop surfaces in room

Max. floor temp

(°C) maximum floor temperature

Coating select some of the floor coating. ceramics tiles; Parquet; Marble; Stone

panels; Carpet; Linoleum ...

R coat.

(m2*K/W) coating thermal conductivity resistance

Screed select screed

R screed

(m2*K/W) screed thermal conductivity resistance

Calculation for

fixed loop

number

If you want to make a calculation for a certain loop number than select this

box. This field is associated with the following field "Number of loops".

Page 51: Integracad 2011 Eng

Number of loops Number of loops in room

Additional

insulation select additional insulation for cooling system

Pipe select pipe for floor cooling system

Wanted supply

water

temperature (°C)

Wanted supply water temperature on manifold for cooling

Temperature of

room underneath

(°C)

temperature of room underneath

Maximum

pressure drop

(kPa)

maximum pressure drop

Maximum loop

lenght (m) Maximum loop lenght

Heating

Qn (W) Heat load

Coverage (%) Percent of installed heating capacity

Wanted supply

temperature (°C) Wanted supply water temperature on manifold for heating

Calculation by

mass flow from

cooling

Calculation by mass flow from cooling

System select floor cooling system

Subsystem select floor cooling subsystem

Add (Ins) pressing this button program will add new floor cooling loop, that can

cover entire given surface.

Add X

Auto

To shorten the calculation process use the button "Auto". This function will

attempt to find the optimal floor cooling loop/s with preset loop size, floor

temperature, pressure drop etc. As mentioned before, there are cases in

which it is not possible to meet all needs with just floor heating and the

"Auto" function will not find an optimal solution in these cases. The

calculation is also adjustable.

Delete (Del) pressing this button program will delete selected floor cooling loop from

project.

Delete all pressing this button program will delete all floor cooling loops in one room

Recalculate pressing this button program will recalculate a complete floor cooling

calculation according to some new set values.

Page 52: Integracad 2011 Eng

Table

V/M manifold connected on loop.

Label loop label

Type loop according to zone type (H - Habitation zone, B- Border zone, IB -

Integrated border zone, X - connection pipe , Y - insulated supply pipe).

Screed select screed

D (mm) thickness of floor coverings

RlaB (m2K/W) Coating thermal conductivity, value is calculated

Qn (W) Heat losses

A (m2) Floor surface

T (mm) pipe step - value can be changed by double-clicking on the column

tp (°C) Floor temperature

q (W/m2) heat capacity that loop gives

Qn (W) heat capacity - value for border zone

A (m2) Floor surface - value for border zone

T (mm) pipe step - value for border zone

tp (°C) floor temperature - value for border zone

q (W/m2) amount of heat that loop gives - value for border zone

Δt (°C) Temperature difference between supply and return water

l (m) loop lenght

ld (m) lenght of connecting pipe in loop

Qi(k) (W) upwards installed capacity

Qtot (W) total floor cooling capacity

m (kg/h) mass flow

Δp (kPa) pressure droop

Valve pos. Manifold balance valve position

Page 53: Integracad 2011 Eng

WALL HEATING / COOLING CALCULATION

DEFAULT SETTINGS

System

System select wall system for heating / cooling. Press the button and choose wall

system. Systems are defined by manufacturer.

Pipe Select one of the listed pipe for wall heating / cooling system. Pipe

selection list depends of the selected wall system / subsystem.

Coating

Coating select one of the wall coatings. ceramics tiles or paint

Coating width

(mm)

Coating width depends on selected coating. Program will automatically put

some standard widths in mm, but you can change that value.

Inner coating

theraml cond.

(W/mK)

For selected wall coating program will automatically put some standard

values for inner coating theraml conductivity, but you can change that

value.

Inner coating

width (mm)

For selected wall coating program will automatically put some standard

values for inner coating width, but you can change that value.

Auto pipe step selection

Auto pipe step

selection

For selected wall heating / cooling system you can limit pipe step by using

minimum and maximum values. To do that select this window.

min. Select minimum pipe step (values depends on previously selected wall

system. Don't forget to mark previous "Auto pipe step selection" window)

max. Select maximum pipe step (values depends on previously selected wall

system. Don't forget to mark previous "Auto pipe step selection" window)

Border values

Max. pressure

drop

Maximum pressure drop. This value is given by the manufacturer, as his

recommendation of a maximum value over that we should not be allowed

to go. value can be changed.

Maximum loop

lenght

This value is given by the manufacturer, as his recommendation of a

maximum value over that we should not be allowed to go. value can be

changed.

Maximum wall

temperature

This value is given by the manufacturer, as his recommendation of a

maximum value over that we should not be allowed to go. value can be

changed.

Page 54: Integracad 2011 Eng

Heating temperature

Wanted water

temperature (°C) Wanted water temperature on manifold for wall heating

Temperature

difference

Temperature difference between supply and return water temperature in

kelvin

min. minimum water temperature difference by zones in kelvin for heating. This

values are given according to standard, but you can change it.

max. maximum water temperature difference by zones in kelvin for heating. This

values are given according to standard, but you can change it.

Cooling temperature

Wanted water

temperature (°C) Wanted supply water temperature on manifold for cooling

Temperature

difference Temperature difference in kelvin for cooling

min. minimum water temperature difference by zones in kelvin for cooling. This

values are given according to standard, but you can change it.

max. maximum water temperature difference by zones in kelvin for cooling. This

values are given according to standard, but you can change it.

WALL HEATING

Wall heating: Project/Floor/Room

Qn (W) Heat losses

ti (°C) inner room temperature. This value is given according to selected room (by

standard), but you can change it.

Wanted water

temperature (°C) Wanted supply water temperature on manifold

Qn' (W) needed heating capacity

Qinst (W) installed heating capacity

Qre (W) remaining heat quantity

Loop surface

(m2) loop area of all loops on the wall in one room

Cooling calculation

Qn (W) Heat load

Coverage (%) Percent of installed cooling capacity

Wanted water

temperature (°C) Wanted supply water temperature on manifold for wall cooling

Page 55: Integracad 2011 Eng

Calculation by

mass flow from

heating

calculation by mass flow from heating

System select wall heating system

Pipe for system select pipe for wall heating system

Connection pipe select connection pipe for wall heating system - pipe for Tichelmann

Recalculate pressing this button program will recalculate a complete wall heating

calculation according to some new set values.

Maximum

pressure drop

(kPa)

maximum pressure drop. This value is given by the manufacturer, as his

recommendation of a maximum value over that we should not be allowed

to go. value can be changed.

Maximum loop

lenght (m)

This value is given by the manufacturer, as his recommendation of a

maximum value over that we should not be allowed to go. value can be

changed.

Coating select one of two wall coating: ceramics tiles or paint

Coating thermal

conductivity

(W/m*K)

Coating thermal conductivity value

Coating width

(mm)

This value depands of previus selected wall coating, Program will

automatically put some standard value, but you can it.

R coat.

(m2*K/W) coating thermal conductivity resistance

Inner coating

thermal cond.

(W/m*K)

Inner coating thermal conductivity. This value depands of previus selected

wall coating, Program will automatically put some standard value, but you

can it.

Inner coating

width (W/m*K)

Inner wall coating width, Program will automatically put some standard

value, but you can it.

R plaster

(m2*K/W) inner plaster thermal conductivity resistance

Table

Tichelmann

column for wall (pipes) connection in the tichelmann system. This function

you'll can use if you have at least 2 walls written in the table along with

theirs lengths of x-zones. Then you can simply with drag mouse function

connect that pipes in the tichelmann system. In column than will be printed

label of tichelmann system and the required length of pipe (needed for that

connection).

Lbl

Label that is associated with the U coefficient calculation. If you already

calculated U coefficient value in coefficient calculation, that just in this

column type the same label (as there), and program will automatically pull

that value in this Wall calculation part and place it in "U (W/m2)" column.

Label wall label (made automatically by program) (WL + number that program

automatically assigns). Label can be changed.

Page 56: Integracad 2011 Eng

V/M manifold that is connected with loop.

U(W/m2)

Thermal transmittance of building element. If you already calculated U

coefficient value in coefficient calculation, that just in column "Lbl" type

the same label (as there), and program will automatically pull that value

here.

Out. temp outdoor temperature (temperature behind the wall)

Lenght (m) wall lenght

Height (m) wall height

A (m2) wall surface that you want to fill with loop

X-zone lenght of x-zone

T (mm) pipe step - value can be changed by double-clicking on the column.

tw (°C) wall temperature

Δt (°C) temperature difference between supply and return water

l (m) loop length (that goes on that wall)

Qins (W) installed heating capacity

Qtotal (W) total wall heating capacity

q (W/m2) amount of heat that loop gives

m (kg/h) mass flow

w (m/s) needed water flow

Δp (kPa) pressure droop

Valve. pos. manifold balance valve position

WALL COOLING

Wall cooling: Project/Floor/Room

Qn (W) heat gains

ti (°C) inner room temperature. This value is given according to selected room (by

standard), but you can change it.

Wanted water

temperature (°C) Wanted supply water temperature on manifold

Qn' (W) needed cooling capacity

Qinst (W) installed cooling capacity

Qre (W) remaining cooling quantity

Loop surface

(m2) loop area of all loops on the wall in one room

Heating calculation

Qn (W) Heat losses

Coverage (%)

Percent of installed heating capacity

Page 57: Integracad 2011 Eng

Wanted water

temperature (°C) Wanted supply water temperature on manifold for wall heating

Calculate by

cooling mass

flow

calculation by mass flow from cooling

System select wall cooling system

Pipe for system select pipe for wall cooling system

Connection pipe select connection pipe for wall cooling system - pipe for Tichelmann

Recalculate pressing this button program will recalculate a complete wall cooling

calculation according to some new set values.

Maximum

pressure drop

(kPa)

maximum pressure drop. This value is given by the manufacturer, as his

recommendation of a maximum value over that we should not be allowed

to go. value can be changed.

Maximum loop

lenght (m)

This value is given by the manufacturer, as his recommendation of a

maximum value over that we should not be allowed to go. value can be

changed.

Coating select one of two wall coating: ceramics tiles or paint

Coating thermal

conductivity

(W/m*K)

Coating thermal conductivity value

Coating width

(mm)

This value depands of previus selected wall coating, Program will

automatically put some standard value, but you can it.

R coat.

(m2*K/W) coating thermal conductivity resistance

Inner coating

thermal cond.

(W/m*K)

Inner coating thermal conductivity. This value depands of previus selected

wall coating, Program will automatically put some standard value, but you

can it.

Inner coating

width (W/m*K)

Inner wall coating width, Program will automatically put some standard

value, but you can it.

R plaster

(m2*K/W) inner plaster thermal conductivity resistance.

Table

Tichelmann

column for wall (pipes) connection in the tichelmann system. This function

you'll can use if you have at least 2 walls written in the table along with

theirs lengths of x-zones. Then you can simply with drag mouse function

connect that pipes in the tichelmann system. Than in this column will be

printed label of tichelmann system and the required length of pipe (needed

for that connection)./td>

Lbl

Label that is associated with the U coefficient calculation. If you already

calculated U coefficient value in coefficient calculation, that just in this

column type the same label (as there), and program will automatically pull

Page 58: Integracad 2011 Eng

that value in this Wall calculation part and place it in "U (W/m2)" column.

Label wall label (made automatically by program) (WL + number that program

automatically assigns). Label can be changed.

V/M manifold that is connected with loop.

U(W/m2)

Thermal transmittance of building element. If you already calculated U

coefficient value in coefficient calculation, that just in column "Lbl" type

the same label (as there), and program will automatically pull that value

here.

Out temp. outdoor temperature (temperature behind the wall)

Lenght (m) wall lenght

Height (m) wall height

A (m2) wall surface that you want to fill with loop

X-zone lenght of x-zone

T (mm) pipe step - value can be changed by double-clicking on the column.

tw (mm) (°C) wall temperature

Δt (°C) temperature difference between supply and return water

l (m) loop length (that goes on that wall)

Qins (W) installed cooling capacity

Qtot (W) total wall cooling capacity

q (W/m2) amount of cooling that loop gives

m (kg/h) mass flow

w (m/s) needed water flow

Δp (kPa) pressure droop

Valve. pos. manifold balance valve position

Page 59: Integracad 2011 Eng

FAN COIL SELECTION

DEFAULT SETTINGS

Default settings

FC2-1 fan-coil installation

(two pipe)

short description of selected fan-coil in installation (FC2 - for two

pipe system or FC4 - for four pipe system)

Fan-coil group

select fan coil group. To be able to choose the two-pipe fan coil

systems on branch tree, select: Fan coil installation (two pipe); If

you want to work with four pipe fan coil, on branch tree, select:

Fan coil installation (four pipe)

Description short description of selected fan coil group

Num. of connections informative field where you can see the number of selected fan-

coil connections.

Velocity fan-coil velocity selection. Number list depends of selected fan-

coil model.

Maxsimum length maxsimum length selection. Number list depends of selected fan-

coil model.

Heating settings

Supply water temperature

(°C)

enter supply water temperature for heating. Program will offer

some standard supply temperature, but data can be changed.

Δt (°C)

temperature difference between supply and return water for

heating Program will offer some standard temperature value, but

you can change it.

Cooling settings

Supply water temperature

(°C)

enter supply water temperature for cooling. Program will offer

some standard supply temperature, but data can be changed.

Δt (°C)

temperature difference between supply and return water for

cooling Program will offer some standard temperature value, but

you can change it.

Humidity (%) humidity percentage in the room

Recalculate installation pressing this button program will recalculate a complete fan coil

installation according to some new set values.

Page 60: Integracad 2011 Eng

CALCULATION

Options

Calculate all

Clicking on this button program will delete existing fan coil units

and replace them with some new according to some new

calculation settings. (e.g. calculation according to water

temperature or according to water flow temperature)

Add

Pressing this button a new window will appear Then program will

automatically add one fan coil in the row in the table where you

are positioned.

Delete pressing this button program will delete currently selected fan coil

Delete all pressing this button program will erase all existing fan coil units.

Calculation accoding to

water temperature

Calculation will be made by water temperature. To make

calculation accoding to water temperature (after you mark

Calculation accoding to water temperature radio button) press

"Calculate All" button.

Calculation accoding to

water flow temperature

Calculation will be made by water flow temperature. To make

calculation accoding to water flow temperature (after you mark

Calculation accoding to water flow temperature radio button) press

"Calculate All" button.

Calculation for:

Project/Floor/Room Short description of the calculation position

Table 1

Label fan coil name

Qh (W) cooling capacity

Qs (W) sensory cooling capacity

Δph (kPa) cooling pressure drop

Qg (w) heat capacity

Δpg (kPa) heating pressure drop

Noise (dBa) fan coil noise - depends on the selected fan coil velocity

Length (mm) fan coil length

Width (mm) fan coil width

Heigth (mm) fan coil heigth

Page 61: Integracad 2011 Eng

Table 2

Room room name for which we do calculation

According to: calculation selection according to heating or cooling

ti inner room temperature

Qn (W) required capacity

sum Qi (W) installed capacity sum

Qi (W) installed capacity

Speed fan coil speed

V/M label for floor entry point / Riser

Label fan coil label (FC-2 two pipe fan coil or FC4 four pipe fan coil)

Model fan coil model - associated with the column "Label" from the

previous table 1

m (kg/h) Mass flow

Δp (kPa) Pressure drop

Z (kPa) additional pressure drop

Δt (°C) Flow and return temperature difference

Noise (dBa) noise at the selected speed

Page 62: Integracad 2011 Eng

HEATING PIPELINE CALCULATION

DEFAULT SETTINGS

Warning!

Warning! Basic settings are associated with the entrance of heating.

You must choose input installation of heating on a tree branch.

Message that is displayed on top of the window after you open this

calculation if you did not create heating installation on the branch tree.

It's like a first step that must be done otherwise this calculation will not

be able to use.

After you create it new field will appear "Pipe group".

Pipe group choose default pipe from database. Press button (...), choose pipe group

and choose default pipe

Supply water temp.

(°C) enter supply water temperature

Return water temp.

(°C) enter return water temperature

Physical characteristic of water

Mean water temp.

(°C)

medium water temperature - program will give this value about

physical characteristics of water

Water temp.

difference (°C)

Water temperature difference - program will give this value about

physical characteristics of water

Water density

(kg/m3)

Water density - program will give this value about physical

characteristics of water

Water viscosity

(m2/s*10^6)

Water viscosity - program will give this value about physical

characteristics of water

Spec. water heat

(kJ/kgK)

Specific water heat - program will give this value about physical

characteristics of water

Optimized calculation

Pipe dimensioning

according to max.

water flow velocity

Pipe dimensioning according to maximum water flow velocity. check

box and enter values in the next to fileds Water flow velocity in vert.

pipeline (m/s) and Water flow velocity in hor. pipeline (m/s). If this

check box is unchecked Pipe dimensioning according to max. water

flow velocity will not be possible.

Water flow velocity

in vert. pipeline

(m/s)

Water flow velocity in vertical pipeline

Water flow velocity

in hor. pipeline (m/s) Water flow velocity in horizontal pipeline

Page 63: Integracad 2011 Eng

According to const.

pressure drop (Pa/m)

Pipe dimensioning according to constant pressure drop. check box and

enter value. If this check box is unchecked Pipe dimensioning

according to constant pressure drop will not be possible.

Balancing valve

Vertical select balancing valve for vertical branch calculation

Horizontal select balancing valve for horizontal branch calculation

Construct pipeline

After you define branches, click "Construct pipeline". Branches will be

automatically sorted and you can review them on a branch tree

(clicking on the desired branch) or in tables (clicking in any branch

field in the table).

Assign fittings

For selected heating installation (marked on the branch tree) program

passes through all sections and sets fittings. This command adds only

the reduction, t pieces and couplings. All previously installed fittings

will be deleted.

VERTICAL

Table 1

R*L+Z (kPa) Total pressure drop on branch

m (kg/h) mass flow

Construct pipeline

After you define branches, click "Construct pipeline". Branches will be

automatically sorted and you can review them on a branch tree

(clicking on the desired branch) or in tables (clicking in any branch

field in the table).

Assign fittings

For selected heating installation (marked on the branch tree) program

passes through all sections and sets fittings. This command adds only

the reduction, t pieces and couplings. All previously installed fittings

will be deleted.

Copy flow or return

sections

If you already made flow sections, than (pressing this button) program

can copy in this table the same flow sections as return sections.

Table 2

Type

sections type (flow or return sections). Red arrows is mark for flow

section, blue arrows is mark for return section. Program first begin to

enter flow sections, and then continues with return sections. You can

replace this two sections types on simple way if you do double click

with left mouse button in this column.

From Starting section point. Program will automatically put endpoint of

section in column "To" (Note: first section must start with number 1).

Page 64: Integracad 2011 Eng

To

section endpoint. After you finish with flow section input in table, you

can do return sections. In next table line for a starting point tipe again

number 1, or use "Copy flow or return sections" button.

Device Double-click in column field "Device" and select floor entry that is

connected to section endpoint.

Q (W) section capacity

m (kg/h) mass flow

V (l/s) volume flow

L (m) section lenght

ζ

Minor loss coefficient. Double-click in this column and you can define

types and number of local pressure drop (T-pieces; elbows..). Program

will calculate total coefficient of local pressure drops based on selected

types and number of elements. If you do not want to choose fitting

products from the database you can manually enter the "Zeta" value.

Value will be taken into account later in the calculations.

DN

exterior pipe diameter. if you want to change some pipe than here type

some other exterior pipe diameter (DN) (e.g. 20, 25, 30,...). Program

will select first pipe (from program datebase) whith that DN.

Pipe

Pipe selection: program select pipe according to heat flow, but you can

for every section select some other pipe. For selection do double-click

in column.

t (°C) Section water temperature (selected on default settings). Value can be

changed.

w (m/s) section flow - program calculate this value

R (kPa/m) pressure drop in section due to local pressure drop

R*L (kPa) line pressure drop in section

Z (kPa) pad tlaka zbog lokalnih otpora

R*L+Z (kPa) maksimum pressure drop

kv coefficient flow on valve

xb adjustment valve position

HORIZONTAL

Construct pipeline

After you define branches, click "Construct pipeline". Branches will be

automatically sorted and you can review them on a branch tree

(clicking on the desired branch) or in tables (clicking in any branch

field in the table).

Assign fittings

For selected heating installation (marked on the branch tree) program

passes through all sections and sets fittings. This command adds only

the reduction, t pieces and couplings. All previously installed fittings

will be deleted.

Copy flow or return

sections

If you already made flow sections, than (pressing this button) program

can copy in this table the same flow sections as return sections.

Page 65: Integracad 2011 Eng

Table 2

Type

sections type (flow or return sections). Red arrows is mark for flow

section, blue arrows is mark for return section. Program first begin to

enter flow sections, and then continues with return sections. You can

replace this two sections types on simple way if you do double click

with left mouse button in this column.

From Starting section point. Program will automatically put endpoint of

section in column "To" (Note: first section must start with number 1).

To

section endpoint. After you finish with flow section input in table, you

can do return sections. In next table line for a starting point tipe again

number 1, or use "Copy flow or return sections" button.

Device Double-click in column field "Device" and select floor entry that is

connected to section endpoint.

Q (W) section capacity

m (kg/h) mass flow

V (l/s) volume flow

L (m) section lenght

ζ

Minor loss coefficient. Double-click in this column and you can define

types and number of local pressure drop (T-pieces; elbows..). Program

will calculate total coefficient of local pressure drops based on selected

types and number of elements. If you do not want to choose fitting

products from the database you can manually enter the "Zeta" value.

Value will be taken into account later in the calculations.

DN

exterior pipe diameter. if you want to change some pipe than here type

some other exterior pipe diameter (DN) (e.g. 20, 25, 30,...). Program

will select first pipe (from program datebase) whith that DN.

Pipe

Pipe selection: program select pipe according to heat flow, but you can

for every section select some other pipe. For selection do double-click

in column.

t (°C) Section water temperature (selected on default settings). Value can be

changed.

w (m/s) section flow - program calculate this value

R (kPa/m) pressure drop in section due to local pressure drop

R*L (kPa) line pressure drop in section

Z (kPa) pad tlaka zbog lokalnih otpora

R*L+Z (kPa) maksimum pressure drop

kv coefficient flow on valve

xb adjustment valve position

Page 66: Integracad 2011 Eng

FAN COIL PIPELINE CALCULATION

DEFAULT SETTINGS

Warning!

Warning! Basic settings are associated with the entrance of fan-coil.

You must choose input installation of fan-coil on a tree branch.

Message that is displayed on top of the window after you open this

calculation if you did not create heating installation on the branch tree.

It's like a first step that must be done otherwise this calculation will not

be able to use. After you create it new field will appear "Pipe group".

Pipe group choose default pipe from database. Press button (...), choose pipe group

and choose default pipe

Calculation mode

choose one of two calculation mode typs (heating or cooling). Program

will in further calculation take into account the temperature of the

selected system and do calculation for fan coil (heating or cooling)

capacity.

Recalculate

Press this button if you change calculation mode (e.g. heating to

cooling), so that program can accept new regime, and do calculation

according to that selection.

Supply water temp

(°C) enter supply water temperature

Return water temp

(°C) enter return water temperature

Physical characteristic of water

Mean water temp.

(°C)

medium water temperature - program will give this value about

physical characteristics of water

Water temp.

difference (°C)

Water temperature difference - program will give this value about

physical characteristics of water

Water density

(kg/m3)

Water density - program will give this value about physical

characteristics of water

Water viscosity

(m2/s*10^6)

Water viscosity - program will give this value about physical

characteristics of water

Spec. water heat

(kJ/kgK)

Specific water heat - program will give this value about physical

characteristics of water

Optimized calculation

Pipe dimensioning

according to max.

water flow velocity

Pipe dimensioning according to maximum water flow velocity. check

box and enter values in the next to fileds Water flow velocity in vert.

pipeline (m/s) and Water flow velocity in hor. pipeline (m/s). If this

check box is unchecked Pipe dimensioning according to max. water

flow velocity will not be possible.

Page 67: Integracad 2011 Eng

Water flow velocity

in vert. pipeline

(m/s)

Water flow velocity in vertical pipeline

Water flow velocity

in hor. pipeline (m/s) Water flow velocity in horizontal pipeline

According to const.

pressure drop (Pa/m)

Pipe dimensioning according to constant pressure drop. check box and

enter value. If this check box is unchecked Pipe dimensioning

according to constant pressure drop will not be possible.

Balancing valve

Vertical select balancing valve for vertical branch calculation

Horizontal select balancing valve for horizontal branch calculation

Construct pipeline

After you define branches, click "Construct pipeline". Branches will be

automatically sorted and you can review them on a branch tree

(clicking on the desired branch) or in tables (clicking in any branch

field in the table).

Assign fittings

For selected heating installation (marked on the branch tree) program

passes through all sections and sets fittings. This command adds only

the reduction, t pieces and couplings. All previously installed fittings

will be deleted.

VERTICAL

Table 1

R*L+Z (kPa) Total pressure drop on branch

m (kg/h) mass flow

Construct pipeline

After you define branches, click "Construct pipeline". Branches will be

automatically sorted and you can review them on a branch tree

(clicking on the desired branch) or in tables (clicking in any branch

field in the table).

Assign fittings

For selected heating installation (marked on the branch tree) program

passes through all sections and sets fittings. This command adds only

the reduction, t pieces and couplings. All previously installed fittings

will be deleted.

Copy flow or return

sections

If you already made flow sections, than (pressing this button) program

can copy in this table the same flow sections as return sections.

Page 68: Integracad 2011 Eng

Table 2

Type

sections type (flow or return sections). Red arrows is mark for flow

section, blue arrows is mark for return section. Program first begin to

enter flow sections, and then continues with return sections. You can

replace this two sections types on simple way if you do double click

with left mouse button in this column.

From Starting section point. Program will automatically put endpoint of

section in column "To" (Note: first section must start with number 1).

To

section endpoint. After you finish with flow section input in table, you

can do return sections. In next table line for a starting point tipe again

number 1, or use "Copy flow or return sections" button.

Device Double-click in column field "Device" and select floor entry that is

connected to section endpoint.

Q (W) section capacity

m (kg/h) mass flow

V (l/s) volume flow

L (m) section lenght

ζ

Minor loss coefficient. Double-click in this column and you can define

types and number of local pressure drop (T-pieces; elbows..). Program

will calculate total coefficient of local pressure drops based on selected

types and number of elements. If you do not want to choose fitting

products from the database you can manually enter the "Zeta" value.

Value will be taken into account later in the calculations.

DN

exterior pipe diameter. if you want to change some pipe than here type

some other exterior pipe diameter (DN) (e.g. 20, 25, 30,...). Program

will select first pipe (from program datebase) whith that DN.

Pipe

Pipe selection: program select pipe according to heat flow, but you can

for every section select some other pipe. For selection do double-click

in column.

t (°C) Section water temperature (selected on default settings). Value can be

changed.

w (m/s) section flow - program calculate this value

R (kPa/m) pressure drop in section due to local pressure drop

R*L (kPa) line pressure drop in section

Z (kPa) pad tlaka zbog lokalnih otpora

R*L+Z (kPa) maksimum pressure drop

kv coefficient flow on valve

xb adjustment valve position

Page 69: Integracad 2011 Eng

HORIZONTAL

Construct pipeline

After you define branches, click "Construct pipeline". Branches will be

automatically sorted and you can review them on a branch tree

(clicking on the desired branch) or in tables (clicking in any branch

field in the table).

Assign fittings

For selected heating installation (marked on the branch tree) program

passes through all sections and sets fittings. This command adds only

the reduction, t pieces and couplings. All previously installed fittings

will be deleted.

Copy flow or return

sections

If you already made flow sections, than (pressing this button) program

can copy in this table the same flow sections as return sections.

Table 2

Type

sections type (flow or return sections). Red arrows is mark for flow

section, blue arrows is mark for return section. Program first begin to

enter flow sections, and then continues with return sections. You can

replace this two sections types on simple way if you do double click

with left mouse button in this column.

From Starting section point. Program will automatically put endpoint of

section in column "To" (Note: first section must start with number 1).

To

section endpoint. After you finish with flow section input in table, you

can do return sections. In next table line for a starting point tipe again

number 1, or use "Copy flow or return sections" button.

Device Double-click in column field "Device" and select floor entry that is

connected to section endpoint.

Q (W) section capacity

m (kg/h) mass flow

V (l/s) volume flow

L (m) section lenght

ζ

Minor loss coefficient. Double-click in this column and you can define

types and number of local pressure drop (T-pieces; elbows..). Program

will calculate total coefficient of local pressure drops based on selected

types and number of elements. If you do not want to choose fitting

products from the database you can manually enter the "Zeta" value.

Value will be taken into account later in the calculations.

DN

exterior pipe diameter. if you want to change some pipe than here type

some other exterior pipe diameter (DN) (e.g. 20, 25, 30,...). Program

will select first pipe (from program datebase) whith that DN.

Pipe

Pipe selection: program select pipe according to heat flow, but you can

for every section select some other pipe. For selection do double-click

in column.

t (°C) Section water temperature (selected on default settings). Value can be

changed.

w (m/s) section flow - program calculate this value

Page 70: Integracad 2011 Eng

R (kPa/m) pressure drop in section due to local pressure drop

R*L (kPa) line pressure drop in section

Z (kPa) pad tlaka zbog lokalnih otpora

R*L+Z (kPa) maksimum pressure drop

Valve fan coil valve

kv coefficient flow on valve

xb adjustment valve position

Page 71: Integracad 2011 Eng

PORTABLE WATER PIPELINE CALCULATION

DEFAULT SETTINGS

Warning!

Warning! Basic settings are associated with the entrance of water

installations. You must choose input installation of water on a tree

branch.

Message that is displayed on top of the window after you open this

calculation if you did not create portable water installation on the

branch tree. It's like a first step that must be done otherwise this

calculation will not be able to use. After you create it new field will

appear "Building type"

Building type

select building type (according to DIN 1988). Residential building,

Commercial building, Hotel, Department store, Hospital, School ...

When building type is defined program will scale assumed water flow

to require water flow.

Cold water temp.

(°C) type cold water temperature in system.

Hot water temp. (°C) type hot water temperature in system.

Cold water pipe (...) press (...) button and select pipe group and default cold water pipe.

Hot water pipe (...) press (...) button and select pipe group and default hot water pipe.

Armatures on

installation

In table field "Sink point" select armature. In the table, you can define

the entire set of armature, which is used in system. Depends on given

armature program will calculate total water flow for the system.

Required water flow depends on total water flow and type of the

building will be calculated. For the permanent water flow in system,

(water flow that last more then 15 minutes) enter the value.

Manufacturer gives relevant values for the watermeter and filter. These

values are maximum water flow through watermeter and filter, and

pressure drop for those devices. If you do this calculation from CAD

than you don't need to select armatures here because program will take

the one from the drawing and input them in the table.

SumVr (l/s) assumed water flow through some armature.

Vs (l/s) required water flow through some armature for selected building type.

Vp (l/s) permanent water flow (last's more than 15 minutes) - e.g. flow for pipes

for garden watering.

Min. pressure ent.

point (kPa) Minimal pressure on entry point of the building

Page 72: Integracad 2011 Eng

Constant water velocity

Pipe dimensioning

according to max.

water flow velocity

Pipe dimensioning according to maximum water flow velocity. Select

window (if you want to do dimensioning according to maximum water

flow velocity) and type maximum water flow velocity in vertical and

horizontal pipeline.

Water flow velocity

in vert. pipeline (m/s)

Type water flow velocity in vertical pipeline. This field is visible only

if field "Pipe dimensioning according to max. water flow velocity" is

checked.

Water flow velocity

in hor. pipeline (m/s)

Type water flow velocity in horizontal pipeline. This field is visible

only if field "Pipe dimensioning according to max. water flow velocity"

is checked.

Watermeter

Vgv (l/s) type maximum water flow through the watermeter.

ΔPgw (kPa) type pressure drop on watermeter.

Filter

Vgf (l/s) type maximum water flow through the filter.

ΔPgf (kPa) type pressure drop on filter.

Quick calculation

Inner diameter for

connection pipe used

for calculation

information field that shows inner diameter of selected connection pipe.

info field shows selected selected connection pipe

VERTICAL

Table 1

hgeo (m) geodetic height difference

ΔPgeo (kPa) pressure drop for geodetic difference

ΔPwz (kPa) watermeter pressure drop

ΔPfil (kPa) filter pressure drop

ΔPeh (kPa) pressure drop on water softening device

ΔPdos (kPa) pressure drop on dosing equipement

ΔPte (kPa) pressure drop on water heating device

ΔPap (kPa) pressure drop on other devices

ΔPminFL (kPa) minimal hydraulic pressure

Page 73: Integracad 2011 Eng

ΔPst (kPa) pressure drop in separate sections

Z (kPa) local pressure drop

SumΔP (kPa) pressure drop on branch

Construct pipeline

After you define branches, click "Construct pipeline". Branches will be

automatically sorted and you can review them on a branch tree

(clicking on the desired branch) or in tables (clicking in any branch

field in the table).

Assign fittings

For selected heating installation (marked on the branch tree) program

passes through all sections and sets fittings. This command adds only

the reduction, t pieces and couplings. All previously installed fittings

will be deleted.

Table 2

Type

sections type (flow or return sections). Red arrows is mark for flow

section, blue arrows is mark for return section. Program first begin to

enter flow sections, and then continues with return sections. You can

replace this two sections types on simple way if you do double click

with left mouse button in this column.

From Starting section point. Program will automatically put endpoint of

section in column "To" (Note: first section must start with number 1).

To

section endpoint. After you finish with flow section input in table, you

can do return sections. In next table line for a starting point tipe again

number 1, or use "Copy flow or return sections" button.

L (m) section lenght

φ minor loss coefficient.

Device

Double-click in column field "Device" and select floor entry that is

connected to section endpoint. (here you connects floor to vertical

pipeline section. Duble click on the cell and choose floor entry for the

pipeline section.)

Vri (l/s) total flow

DN inner pipe diameter

Pipe pipe dimension

Vs (l/s) calculation flow

t (°C) water temperature

w (m/s) water velocity

R (kPa/m) pressure drop per meter

R*L (kPa) pressure drop in pipes caused by fiction

Z (kPa) pressure drop caused by local resistance

R*L+Z (kPa) total pressure drop in section

Page 74: Integracad 2011 Eng

HORIZONTAL

Construct pipeline

After you define branches, click "Construct pipeline". Branches will be

automatically sorted and you can review them on a branch tree

(clicking on the desired branch) or in tables (clicking in any branch

field in the table).

Assign fittings

For selected heating installation (marked on the branch tree) program

passes through all sections and sets fittings. This command adds only

the reduction, t pieces and couplings. All previously installed fittings

will be deleted.

Table

Type

sections type (flow or return sections). Red arrows is mark for flow

section, blue arrows is mark for return section. Program first begin to

enter flow sections, and then continues with return sections. You can

replace this two sections types on simple way if you do double click

with left mouse button in this column.

From Starting section point. Program will automatically put endpoint of

section in column "To" (Note: first section must start with number 1).

To

section endpoint. After you finish with flow section input in table, you

can do return sections. In next table line for a starting point tipe again

number 1, or use "Copy flow or return sections" button.

L (m) section lenght

φ minor loss coefficient.

Device

Double-click in column field "Device" and select floor entry that is

connected to section endpoint. (here you connects floor to vertical

pipeline section. Duble click on the cell and choose floor entry for the

pipeline section.)

Vri (l/s) total flow

DN inner pipe diameter

Pipe pipe dimension

Vs (l/s) calculation flow

t (°C) water temperature

w (m/s) water velocity

R (kPa/m) pressure drop per meter

R*L (kPa) pressure drop in pipes caused by fiction

Z (kPa) pressure drop caused by local resistance

R*L+Z (kPa) total pressure drop in section

Page 75: Integracad 2011 Eng

DRAINAGE WATER PIPELINE CALCULATION

DEFAULT SETTINGS

Warning!

Warning! Basic settings are associated with the entrance of drainage. You

must choose input installation of drainage on a tree branch.

Message that is displayed on top of the window after you open this calculation

if you did not create drainage installation on the branch tree. It's like a first

step that must be done otherwise this calculation will not be able to use. After

you create it new field will appear "Building type".

Building type select building type (according to standard). Family building, Hospital,

school, Industrial building ...

SumAws water flow sum for drainage points

Pipe default pipe for drainage calculation. Press (...) button to select default pipe.

qs (l/s) Total flow of building drainage. Depends on the object type and water flow

sum for drainage points.

Gradient Starting pipe decline set with each new pipe section insertion.

Optimized

pipe DN

calculation

if this button is checked program will do calculation according to selected

pipe inner diameter

Armatures on

installation

In table field "Sink point" select armature. In the table, you can define the

entire set of armature, which is used in system. Depends on given armature

program will calculate total water flow for the system. Required water flow

depends on total water flow and type of the building will be calculated. For

the permanent water flow in system, (water flow that last more then 15

minutes) enter the value. Manufacturer gives relevant values for the

watermeter and filter. These values are maximum water flow through

watermeter and filter, and pressure drop for those devices. If you do this

calculation from CAD than you don't need to select armatures here because

program will take the one from the drawing and input them in the table.

Transfer

armatures

pressing this button you can transfer some armatures that you used in portable

water calculation.

VERTICAL

Construct

pipeline

after you define branches, click "Construct pipeline". Branches will be

automatically sorted and you can review them on a branch tree (clicking on

the desired branch) or in tables (clicking in any branch field in the table).

Assign fittings

For selected heating installation (marked on the branch tree) program passes

through all sections and sets fittings. This command adds only the reduction, t

pieces and couplings. All previously installed fittings will be deleted.

Page 76: Integracad 2011 Eng

Table

From Starting section point. Program will automatically put endpoint of section in

column "To" (Note: first section must start with number 1).

To

section endpoint. After you finish with flow section input in table, you can do

return sections. In next table line for a starting point tipe again number 1, or

use "Copy flow or return sections" button.

L (m) section lenght

Fittings by double click on this column a new window will appear. Here you can

select fitting grups and number of fittings.

Device

Double-click in column field "Device" and select floor entry that is connected

to section endpoint. (here you connects floor to vertical pipeline section.

Duble click on the cell and choose floor entry for the pipeline section.)

Aws (l/s) water flow for drainage points

qs (l/s) total flow of building drainage

Gradient (%) pipe gradient

DN pipe inner diameter

Pipe pipe dimension

HORIZONTAL

Construct

pipeline

after you define branches, click "Construct pipeline". Branches will be

automatically sorted and you can review them on a branch tree (clicking on

the desired branch) or in tables (clicking in any branch field in the table).

Assign fittings

For selected heating installation (marked on the branch tree) program passes

through all sections and sets fittings. This command adds only the reduction, t

pieces and couplings. All previously installed fittings will be deleted.

Table

From Starting section point. Program will automatically put endpoint of section in

column "To" (Note: first section must start with number 1).

To

section endpoint. After you finish with flow section input in table, you can do

return sections. In next table line for a starting point tipe again number 1, or

use "Copy flow or return sections" button.

L (m) section lenght

Fittings by double click on this column a new window will appear. Here you can

select fitting grups and number of fittings.

Device

Double-click in column field "Device" and select floor entry that is connected

to section endpoint. (here you connects floor to vertical pipeline section.

Duble click on the cell and choose floor entry for the pipeline section.)

Aws (l/s) water flow for drainage points

qs (l/s) total flow of building drainage

Gradient (%) pipe gradient

DN pipe inner diameter

Page 77: Integracad 2011 Eng

VENTILATION DUCTS

DEFAULT SETTINGS

Calculation selection for rectangular ducts:

Calculation

according to

hydraulic diameter

Calculation of rectangular ducts according to hydraulic diameter is

calculated by formula: Dh=4A/P (Dh - hydraulic diameter; A - Area of

ventilation duct cross-section; P - ventilation duct cross-section

perimeter).

Calculation

according to

ASHARE

Ventilation calculation by ASHARE, for diameters - according to

Huebscher (1948) formula. De=1,30(ab)0,625

/(a+b)0,250

(De - circular

equivalent of rectangular duct for same length, fluid resistance and flow,

mm ; a,b - sides of rectangular duct, mm

Default settings

Duct material select one of duct materials that program offer

(...) Material settings. Here you can check or change some basic material data

such as name, values of density and roughness.

Set if you change material, click "Set" button so that program can accept

changes.

Duct type Click on drop-down menu and select type of ventilation ducts (O - round

elements, P - rectangular elements)

Set if you change duct type, click "Set" button so that program can accept

changes.

Fresh air

temperature

(°C)/td>

Input value for temperature of fresh air. Program has entered a default

value that can be changed.

Set all if you press this button program will accept all changes that you made on

default settings window and use them in all ventilation ducts.

Calculation according to:

constant velocity Calculation according to constant velocity. If you do Calculation

according to this method, than enter velocity value. (w - velocity (m/s))

w - velocity (m/s) Velocity that should not be cross during this calculation.

constant pressure

drop

Calculation according to constant pressure drop If you do Calculation

according to this method, than enter pressure drop value. (R - pressure

drop (Pa))

R - pressure drop

(Pa) pressure drop that should not be cross during this calculation.

Page 78: Integracad 2011 Eng

Element label

Fitting label

Program will show that fitting label in calculation. Default label depends

of program language (e.g. for english language it's F - (as Fitting).

Default label also can be changed.

Reset label if you change default fitting label press this button so that program can

accept changes.

Grill label

Program will show that grill label in calculation. Default label depends of

program language (e.g. for english language it's G - (as Grill). Default

label also can be changed.

Reset label if you change default grill label press this button so that program can

accept changes.

Duct element label

Program will show that duct element label in calculation. Default label

depends of program language (e.g. for english language it's EL - (as

Element Label). Default label also can be changed.

Reset label if you change default element label press this button so that program can

accept changes.

Duct dimensioning

Calculate by

constant (mm)

select this window if you want do dimensioning of rectangular duct

according to constant ducts width or height. Enter a constant value in

mm.

ducts width

select this radio button if you want do dimensioning of rectangular duct

according to constant ducts width. If the button is not visible select

"Calculate by constant (mm)"

ducts height

select this radio button if you want do dimensioning of rectangular duct

according to constant ducts height. If the button is not visible select

"Calculate by constant (mm)"

Max. aspect ratio Maximum aspect ratio for rectangular ducts. If this field is not visible

select "Calculate by constant (mm)"

VOLUME

Select volume calculation type

0 - Free entry

Volume calculation according to free entry value. In this calculation type,

it is necessary to input needed supply air volume (V su). Red row

represents heating values, and blue row represents cooling values. In this

type of calculation you don'’t need to write room dimensions (a, b, c, A,

V), fresh air temperature (tw) and inner room temperature (ti)

Page 79: Integracad 2011 Eng

1 - Room

type/Number of

persons

Volume calculation according to room type and number of persons. In

this calculation type, it is necessary to input number of air exchange rate

(nr. of air ex.), number of persons that staying in the room (nr. of per.),

volume per person (V per. per.) and volume of 1m² of surface. Multiply

with room surface to get total room volume. Used with the type 1

calculation only if the resulting room volume is bigger than the

calculated volume from air exchange and number of persons (V per.

surf.). Required values can be written in field or selected from special

window by double clicking on field. Depending on data, program

calculates needed air flow volume. In this type of calculation data for

room dimension is required.

2 - Required

heating/cooling

capacity:

Volume calculation according to required heating/cooling capacity In this

calculation type it is necessary to input internal room temperature (ti),

fresh air temperature (tw) heat losses/ gains (Q) (losses - red row, gains -

blue row). Depending on data program calculates needed air flow

volume.

Set After you select one of three volume calculation type press this button so

that program can accept selected calculation.

Transfer pressing this button new window will appear where you can download

(transfer) heat losses or heat gains.

Table

Label Room label (same label as in project tree)

Room Room name

Type Volume calculation type (0 - free entry; 1 - room type/number of

persons:; 2 - required heating/cooling capacity:)

a (m) room length in m

b (m) room width in m

c (m) room height in m

A (m2) room area in m2

V (m3) room volume in m3

ti (°C) Internal room temperature in (°C)

tw (°C) fresh air temperature in (°C)

nr. of air ex. (h-1

) Number of air exchanges with fresh air during 1 hour in room

nr. of per. (n) number of persons in room

V per. per. (m3/h) needed air flow volume per person

V per surf.

(m3/(m2/h)) Needed air flow volume in one hour per square meter of room

V su. (m3/h) Sum of exchange Air flow volume

Q (W) Heat loss/gains

Page 80: Integracad 2011 Eng

Help short description of the column from the table above where you are

positioned

Winter blue marked line in the table that displays cooling data

Summer pink marked line in the table that displays heating data

VENTILATION DUCTS

Add grille

You can add only one grill on each ventilation section. Procedure: click

on any cell of ventilation section where you want to add grille/ click on

"Add grille" button/ enter value of volume flow on grille/ select type of

ventilation ducts (round or rectangular)/ enter value of grille dimensions

(diameter for round grille or width and height of rectangular grille)/ enter

value of pressure drop on grille / click on "Add" button.

Add fitting

With fitting we connect ventilation sections. Procedure: Click on some

cell of ventilation section where fitting starts / Click on "Add fitting"

button (new window will appear) / In drop-down menu “Fitting group”

select which type of fitting you need. Program suggests possible groups

of fittings depending on number of continuing connected sections. /

Select fitting. If there is no listed fitting you want to put, select some

similar and manually input drag coefficients/ Specify ventilation sections

order / Input fitting technical data / Click on "Ok" button.

Add duct element

Ventilation element can be any part of ventilation who causes some

pressure change (e.g. silencer, flap…) and you can not add it on any other

way. Procedure: Click on some cell of ventilation section where you

want to add duct element./ Click on the "Add duct element" button (new

window will appear)/ Enter duct element name / Enter pressure drop

value/ Click on the "Add" button

Construct

ventilation pipeline

After changes in tabular calculation part click on this button and program

will recalculates pressure drop and dimensions of ventilation ducts. If

you don’'t want to recalculate dimensions of ventilation ducts turn off

option ''Reset ventilation duct dimensions''.

Show element ID

if this button is checked program will display ID column in down table.

(ID column displays fitting, grills or duct element labels) If button is

unchecked ID column will not be visible.

Δp max,i maximum pressure drop on ventilation installation. On branch tree select

branch for which you want to see this value.

Δp grane pressure drop on selected ventilation branch. On branch tree select

branch for which you want to see this value.

(+) Maximize table view (see all ventilation duct sections together with all

fittings, grills ...)

(-) Minimize table view (see just ventilation duct sections without fittings,

grills ...)

Page 81: Integracad 2011 Eng

Table

From beginning of ventilation section

To end of ventilation section

V (m3/h) Volume flow

l (m) length of ventilation ducts section

Material ventilation duct material

type OP ventilation ducts type (O - round elements, P - rectangular elements)

D/a (mm) D - Diameter of round duct/ a - side A on rectangular duct

b (mm) Side B on rectangular duct

Dh (mm) Equivalent diameter of rectangular duct Calculation depends of selected

formula in default settings

s (mm) Thickness of ventilation duct material

w (m/s) Air velocity in ventilation duct

φ local pressure drop coefficient

R (Pa/m) major loss per meter of ventilation duct

R*l (Pa) major loss per section of ventilation duct

Z (Pa) minor loss on section (element of section)

R*l+Z (Pa) total head loss (pressure drop) on section of ventilation ducts

Page 82: Integracad 2011 Eng

Print

Page 83: Integracad 2011 Eng

Calculation and material list

After you complete your calculations, you can all datas and lists of materials arrange for printing in print module or, you can export and save them as a Microsoft Excel file. When you start the print module, program will automatically load his toolbars for editing data for printing. Switching from calculation print data to the other part, lists of materials, is enabled by using the vertical tab on the left edge of the print module (the same way as you switch between some parts of one calculation).

Page 84: Integracad 2011 Eng

Calculation print:

Select "Print" module on the main IntegraCAD window and then click the vertical tab "Calculation".

When you click on that print module, program will automatically create those print calculations which you use in program (e.g. you used two pipe calaculaton (radiators) and heating pipeline calculation in that case program will automatically set these two calculations in his print module). If you selected all calculation in program, you will must use "Move" toolbar with four buttons to see them all, because all will not fit in print window. If you already at the beginning know what prints you will need, you can set them in the main Print menu of program. There are two possible ways: 1.) direct from the menu (shorter display)

2.) or by "Print options" button (in that menu) - graphically displays individual prints

Page 85: Integracad 2011 Eng

Print editing is possible by program print toolbars or directly by typing and modifying data If later come to some changes in calculations, calculations data must be refreshed by

function Refresh print data located in the toolbar. Warning ! All manually entered datas and changes in the print list will be deleted by using that update function. That is why we recommend that first fully complete calculation part and than continue with editing. All prints created by the program are listed by lower left edge of the print window. You also can change currently displayed print list name by clicking on his name.

Lists of material:

Select "Print" module on the print window (if it is not already active), and then click the vertical tab "Material list". At the top of the window there are buttons for createing and some functions to work with a lists of materials like:

Insert list - create a new list of materials Delete list - delete the currently active list of materials Open - loading already creted material list (document with .ISD extension) Save - saveing active material list (document with have .ISD extension) Save as - saveing the material list under a different name Once you save material list as .ISD file you will can open it in any IntegraCAD program version, change it and save agein The difference between .INT file (project files) and .ISD file (list materials file) is that .INT file contains all information about a project, .ISD file only contains a list of materials, without calculations data, structure object data etc... Once created a material list can be changed at any time, but there is no automatic connection with calculation in which was created. If there is a change of some calculation, the list of material information can be refreshed using the function "Refresh data", or you can create a new print materials list that shows the current situation.

Page 86: Integracad 2011 Eng

If you need you can have more different lists - made from the same project. To create a new list of materials, click on the button "Insert List" - new window will appear with all parameters for adjustment the new look for material list (insert on one list, on more lists, description types (long, short, without descriptions)

Page 87: Integracad 2011 Eng

Function overwiew

Calculation print list can be arrange by special tools on the toolbar.

PRINT: Export to excel - functions that exports program data in Excel (xls) file.

OPTIONS: Add total price - this function add column with total price in print list Price properties- price options (e.g. discounts, tax...)

BILL OF MATERIAL: Insert row - program insert rows in the table Delete row - program delete rows in the table Refresh data- with this funkcion program do refreshing for some changed data Undo - Undo the last operation Redo - this function cancel Undo function Align left - align left text and/or numbers in print list Center - center yours text and/or numbers in print list Align right - aligns right text and/or numbers in print list Sort by number - sort by number in print list Most of the functions in this menu you can also choose from the toolbar List

Page 88: Integracad 2011 Eng

If you click whith right mouse button on some print list, program will open up additional menu from which you also can call some standard functions like "Insert Row", "Delete Row" cut, copy, paste ...

TEXT: Bold, Italic, Underline - editi letter style Font size - select font size from the drop-down menu Font type - select font type from the drop-down menu Cell color - an additional dialog will appear in which you can choose one of the listed colors, or create your own colors from the palette attributed. Cell color - an additional dialog will appear in which you can choose one of the listed colors, or create your own colors from the palette attributed. Print language - Choosing one of the available languages from the drop-down menu you can translate the prints on several language. This function can translate all the text that was created with this program. (titles, calculation names, table names etc.) and some of products (if we have translation for tham in program database). This function can not translate the text that user alone add in print list. Most of the functions in this menu you can also choose from the Text toolbar

Page 89: Integracad 2011 Eng

CAD

Page 90: Integracad 2011 Eng

CAD drawing basics

Drawing in IntegraCAD is alike any CAD drawing. At the beginning you can connect the drawing with flat or you can make a new drawing.

Standard toolbars for drawing are at the right side of CAD window. Also there are toolbars with special tools. That tools are tended for drawing of heating elements, drop the radiators and manifolds, draw floor heating pipelines, heating pipelines and water system pipelines.

For the CAD drawings it is recommended to use SNAP function for connecting pipes and heating or cooling elements.

Page 91: Integracad 2011 Eng

CAD function overwiew

English Croatian Command Line Function description

- DRAWING -

Line Crta LINE

Creates straight line segments Integra CAD draws a line segment and continues to prompt for points. You can draw a continuing series of line segments, but each line segment is a separate object. Specify first point: Specify a point Specify next point or [Close/Undo] Finish command with right click or choosing Close Close: Ends the last line segment at the beginning of the first line segment, which forms a closed loop of line segments. You can use Close after you have drawn a series of two or more segments. Undo: Erases the most recent segment of a line sequence. Entering u more than once backtracks through line segments in the order you created them.

Arc Luk ARC

Creates an arc defined by center and radius Specify center of arc Specify radius of arc Specify first point of arc Specify last point of arc

3T 3T ARC3T

Creates an arc defined by 3 points Specify first point of arc Specify last point of arc Specify point on arc

Page 92: Integracad 2011 Eng

Circle Krug CIRCLE

Creates circle defined by center and radius Specify center point Specify radius of circle: enter value or specify point. (The distance between this point and the center point determines the radius of the circle.)

Circle 2P Kružnica 2T CIRCLE2T

Creates circle defined by two points Specify first point on circle Specify second point on circle

Circle 3P Kružnica 3T CIRCLE3T

Creates circle defined by three points Specify first point on circle Specify second point on circle Specify third point on circle

Elipse Elipsa ELLIPSE

Creates the ellipse defined by center point, endpoint of one axis and radius to other axis Specify center of ellipse Specify endpoint of axis Specify distance to other axis

Polyline Polilinija PLINE

Creates 2-dimensional polyline (connected lines forming one object) Specify start point: Specify a point Specify next point or [Close/Undo] Close: Ends the last line segment at the beginning of the first line segment, which forms a closed loop of line segments. You can use Close after you have drawn a series of two or more segments. Undo: Erases the most recent segment of a line sequence. Entering u more than once backtracks through line segments in the order you created them.

Page 93: Integracad 2011 Eng

Rectangle Pravokutnik RECT

Draws a rectangular polyline Specify one corner of rectangle Specify opposite corner of rectangle

Text Tekst TEXT

Command for writing single line text Specify where you want to start Specify direction of writing Write text Press Enter for finish

Aligned Dimension

Položena kota DIMALI

Creates an aligned linear dimension Specify first extension line orgin Specify second extension line Specify location of dimension line

Vertical Dimension

Vertikalna kota

DIMVER

Creates an vertical linear dimension Specify first extension line orgin Specify second extension line Specify location of dimension line

Horizontal Dimens.

Horizontalna kota

DIMHOR

Creates an horizontal linear dimension Specify first extension line orgin Specify second extension line Specify location of dimension line

Angular Dimension

Kotiranje kuta ""

Creates an angular dimension Specify angle vertex: Specify a point (1) Specify first angle endpoint: Specify a point (2) Specify second angle endpoint: Specify a point (3) Specify dimension line location

Quick dimension

Brzo kotiranje QDIM

Creates quick dimension Specify line for Dimension: Specify location of dimension line

Diameter Dimension

Kotiranje promjera

DIMDIA

Creates diameter dimensions for circles and arcs Specify circle or arc

Page 94: Integracad 2011 Eng

Radial Dimension

Kotiranje polumjera

DIMRAD

Creates radial dimensions for circles and arcs Specify circle or arc

Make Block Stvori blok MBLOCK

Creates a block definition from objects you select Block name: Specify insertion point: Select entities

Insert block Umetni blok INSERT

Places named block into the current drawing Opens dialog box where you can define insertion point, scale and rotation. By clicking on checkbox you can select insertion point, scale and rotation on screen.

Write Block Zapiši blok WBLOCK Opens dialog box to save block in file

Picture Slika IMAGE

Opens dialog box to import image in file Select image to import Specify insertion point

xRef xRef XREF Specify external reference

Select fonts Odabir fontova

STYLE Select where font files are located

- MODIFICATION -

Erase Brisanje ERASE

Removes objects from a drawing Select the objects to erase and press ENTER

Move Pomicanje MOVE

Displaces objects a specified distance in a specified direction Select entities: Move from point: Move to point:

Copy Kopiranje COPY

Duplicates objects Select entities: Copy from point: Copy to point

Page 95: Integracad 2011 Eng

Rotate Rotiranje ROTATE

Moves objects about a base point Select entities Rotation base point Rotation angle (write or select with mouse)

Scale Skaliranje SCALE

Enlarges or reduces selected objects proportionally in the X, Y, and Z directions Select entities Specify base point Specify scale factor

Explode Eksplodiranje EXPLODE

Breaks a compound object into its component objects Select entities

Stretch Razvuci STRETCH

Moves or stretches objects Select entities Window select 1st point Window select 2nd point (Inside of the window are points which will be streched) Strech from point Move to point

Extend Proširi EXTEND

Extends an object to meet another object Select entities Select entities to extend (first select where to select, then what to extend)

Trim Odreži TRIM

Trims objects at a cutting edge defined by other objects Select entities Select entities to trim (first select where to select, then what to trim)

Offset Offset OFFSET

Creates concentric circles, parallel lines, and parallel curves Select entitiy to offset Offset distance Side to offset

Page 96: Integracad 2011 Eng

Break Prekini BREAK

Breaks the selected object between two points Select entity Select first break point Select second break point

Fillet PolyLine

Zaobli poliliniju

FILLET

Rounds and fillets the edges of polyline Fillet radius Specify polyline

Mirror Zrcali MIRROR

Creates a mirror image copy of objects Select entities Specify first point on mirror line Specify second point on mirror line

Distance Udaljenost DIST

Measuring distance between selected points Specify first point Specify second point After specifiying all wanted points, with right click finish command. Distance is printed in command line (in real units – if drawing is made in mm, distance will be printed in mm with no regard to mesure we set) Useful for determing units in which drawing is created.

- OSNAP -

When one or more OSNAP (Object snap) buttons is turned on, you can specify required point at an exact location on an object. When more options are selected INTEGRACAD applies the selected snap modes to return a point closest to the

cursor.

Osnap End (Alt + E)

Osnap End (Alt + E)

Snaps to endpoint of line, arc, polyline, object

Osnap Mid (Alt + M)

Osnap Mid (Alt + M)

Snaps to midpoint of line, arc, polyline segment

Osnap Cen Osnap Cen Snap to center of circle or arc

Page 97: Integracad 2011 Eng

(Alt + C) (Alt + C)

Osnap Per (Alt + P)

Osnap Per (Alt + P)

Snaps to a point perpendicular to an arc, line, circle, polyline...

Osnap Nea (Alt + N)

Osnap Nea (Alt + N)

Snaps to nearest point on object It is recommened to turn on only when is needed (because of easier selection of other osnap points)

Osnap Int (Alt + X)

Osnap Int (Alt + X)

Snaps to a point in extension of lines for to selected objects (apparent intersection) When using this osnap it i needed to click twice to snap on point! Select first object By moving mouse cursor near other objects, program is calculatinng where would be intersections with other objects. You select one intersection. If first object is selected with this osnap, you can't use osnap points other than apparent intersections. It is recommened to turn on only when is needed (because of easier selection of other osnap points)

Osnap None

(Alt + K)

Osnap None (Alt + K)

Turn off all osnap functions

Osnap Osnap Dialog Dialog box for selecting osnap

Page 98: Integracad 2011 Eng

Dialog (Alt + O)

(Alt + O) functions.

Recommended osnap functions turned on Insertion - snap to point of block insertion Node (point) - snap to single point Quadrant - snaps to a quadrant point of an arc, circle, ellipse. Quadrant point are located on intersections of imaginary coordinate system with origin in center of object (direction of x and y axis od coordinate system are same as current UCS). Osnap Quadrant is on priority list before osnap center, and is recommnded to turn it on only in case of need. Tangent - enables selection tangent vertex on the circle, ellipse or a circular arc Intersection (one point) - select intersection of two objects

Page 99: Integracad 2011 Eng

- ZOOM - Window, Extents, Previous, In, Out, All -

Window Prozor ZW

Zooms to display an area specified by two opposite corners of a rectangular window Specify first corner Specify opposite corner

Extents Do zaslona ZE Zooms to display the drawing extents and results in the largest possible display of all the objects.

Previous Prethodni ZP Zooms to display the previous view.

In Povećaj ZI Zoom in for default value Use mouse scroll up to zoom in

Out Smanji ZO Zoom out for default value Use mouse scroll down to zoom out

PAN Naredba PAN PAN

Shifts location of view in any direction. While pan cursor is active (hand instead of cross), press point on the screen and move mouse in wanted direction you want to move view location. You can activate pan by clicking middle mouse button. In this case press point on screen with middle mouse button and drag cursor to direction you want and release middle mouse button.

All Sve Zooms to display the entire drawing in the current viewport.

- LAYER -

Page 100: Integracad 2011 Eng

Layers are primary organizational tool in INTEGRACAD. Similar objects we can associate similar objects in same layer. For example you can separate construction lines, text, dimension lines in separate layers. For every layer we can control name, colour, linetype and lineweight. Layers can be frozen (forzen layer is invisible and excluded from regeneration and plotting) and locked (objects are visible but can't be edited or selected). INTEGRACAD uses specific layers for drawing hot and cold water pipes. If you draw lines in other CAD program, layer has to be exactly the same as INTEGRACAD layer, otherwise collectiong pipeline won't work. Turning freeze on and of on some layers, drawing becomes more clear and it is easier to manage inside of it. Creating layers: 1. Open dialog box manage layers 2. Write the name of the layer 3. Click on button New layer 4. Find it in table below, click on the row and modify if needed. Click on the button „Set current“ to make layer active.

Layer Properties Manager

Shoutcout for command is LAYER

<>

- PIPE -

Page 101: Integracad 2011 Eng

Flow water pipe

drawing

Crtanje cijevi polaza tople

vode PIPEHOT

Draw flow water pipe. Pipes are drawn like polylines

Return water pipe

drawing

Crtanje cijevi povrata

hladne vode PIPECOLD

Draw return water pipe. Pipes are drawn like polylines

Warm and cold water

pipe drawing

Istovremeno crtanje polaza

i povrata DOUBLEPIPE

Simultaneusly draw flow and return water pipes.First you draw flow pipe and then clik side to automaticly draw return water pipe.

Drawing cold water

pipes

Crtanje cijevi hladne vode

PIPECOLDWATER

Draw cold water pipes. Pipes are drawn like polylines

Drawing hot water

pipes

Crtanje cijevi tople vode

PIPEHOTWATER Draw hot water pipes. Pipes are drawn like polylines

Circulation pipe

drawing

Crtanje cijevi cirkulacije

PIPECIRC Draw circulation pipes. Pipes are drawn like polylines.

Drainage pipe

drawing

Crtanje cijevi odvodnje

PIPEDRAIN Draw drainage pipes. Pipes are drawn like polylines.

Join sections

Spajanje dionica

Joint sections – joint pipes which are connected in one ending point to become one pipe. Specify first section Specify second section

Section break

Prekid dionice Secton break – divides section in two sections Specify break point

Lowering pipe height

Spustanje cijevi na visinu

Lowering pipe height- Only in UCS (user specified coordinate system) Specify place which you want to lower on height of world coordinate system Specify place where you want to lower on height of world coorinate system Program draws line from first point to second point in user specified coordinate system (UCS), in second point program lowers line to height of world UCS (height z=0)

Construct Slaganje CALCPIPELINE Construct pipeline-

Page 102: Integracad 2011 Eng

pipeline cjevne mreže Specify area where you want to construct pipeline. Pipes (lines representing pipes) must be conected to radiators/fan coils and floor entry points. Every radiator and fan coil must have specific identification number (they should't be coopied from the drawing, you have top add them from list of equipement)

Integrity pipeline check

Provjera integriteta

cijevne mreze

Integrity check of pipeline Turn it on and off before using command construct pipeline. If it is on, connstruct pipeline won't make calculation of pipeline. It will just make check if all the lines are correctly connected in CAD drawing.

Element selection

Označavanje elemenata

You can mark pipes, radiators, manifolds and other elements of pipeline. After turning command on, you have to choose element you want to mark (e.g. pipe). Select location you want to place mark (you can see it while moving mouse). Mark is writen like block and you need to use command Explode if you want to edit text.

Generate riser

scheme

Stvaranje sheme

usponskih vodova

Before generating riser scheme you have to select branch on instalation tree. Program draws scheme of instalations in new drawing (command for generating scheme stays pressed and indicates working on riser scheme). After editing riser scheme you need to save it using standard command save drawing. For return on groung plan you have to turn off command generate riser scheme by pressing it again and after that click on floor. WARNING: compulsory save ground plan before generating riser scheme.

Elements Automatsko Automatic elements connection

Page 103: Integracad 2011 Eng

automatic connection

spajanje elemenata

From right to left select elements you want to connect From right to left select pipes where you want to join elements.

- 3D VIEW -

WORLD WORLD WORLD

Basic coordinate system of drawing Orgin point is (0,0,0) and axis are in direction od main axis

UCS UCS UCS User defined coordinate system by current view

UCS from 3 points

UCS iz 3 točke

UCS

User defined coordinate system by three points Specify orgin point of UCS Specify height of orgin point Specify point in x direction Specify height of the point on x direction Specify point in y direction Specify height of the point on y direction

UCS object UCS objekt UCS Used defined coordinate system defined by object coordinates.

View top Pogled odozgo

Top view (plane X-Y) – ground plan

View bottom

Pogled odozdo

Bottom view (plane X-Y)

View left Pogled s

lijeva Left view (plane Y-Z ) – body plan

View right Pogled s desna

Right view (plane Y-Z)

View front Prednji pogled Front view (plane X-Z) � plan

View back Stražnji pogled

Back view (plane X-Z)

View SW Pogled SW 3D view from South-West

View SE Pogled SE 3D view from South-East

View NE Pogled NE 3D view from North-East

View NW Pogled NW

3D view from North- West

Rotate3D 3D rotiranje Rotate view around 3D axis

Page 104: Integracad 2011 Eng

Dynamic Click point on the screen with first mouse button, hold and rotate view by moving mouse. Move view by presing and holding middle mouse button.

Top view Pogled odozgo

View te orgin of current UCS on specific height

Object view Pogled objekta

View acording to selected point of view and point to view Specify point of view

- UCS VIEW -

UCS view UCS pogled

Click on icon for saving current UCS Write the name of UCS Click on OK Saved UCS you can select in any moment in drop down box located in toolbar UCS view.

delete selected UCS view.

- EDIT -

Undo Poništi U UNDO actions in CAD, can be activated multiple times.

Redo Ponovi REDO REDO actions canceld with UNDO.

- LOOP -

Page 105: Integracad 2011 Eng

Automatic parallel loop

drawing

Automatsko crtanje

paralelne petlje

Automatic parallel loop drawing tool Specify area of room which will be covered with floor heating. (Specify end points of room, when you select last point, click right mouse button to connect it with first point) Specify entry point... (You specify where loop will enter the room) Window pops up where you have to select manifold on which loop is connected. After that you have to select distance between pipes in the loop, offset from wall and direction of drawing loop. Default way of drawing floor heating is counterclockwise. It is recommended to choose direction on longer side.

Automatic double

parallel loop drawing

Automatsko crtanje duple

paralelne petlje

Automatic double parallel loop drawing tool Specify area of room which will be covered with floor heating. (Specify end points of room, when you select last point, click right mouse button to connect it with first point) Specify entry point... (You specify where loop will enter the room) Window pops up where you have to select manifold on which loop is connected. After that you have to select distance between pipes in the loop, offset from wall and direction of drawing loop. Default way of drawing floor heating is counterclockwise. It is recommended to choose direction on longer side.

Automatic spiral loop

Automatsko crtanje

Automatic spiral loop drawing tool Specify area of room which will be

Page 106: Integracad 2011 Eng

drawing spiralne petlje covered with floor heating. (Specify end points of room, when you select last point, click right mouse button to connect it with first point) Specify entry point... (You specify where loop will enter the room) Window pops up where you have to select manifold on which loop is connected. After that you have to select distance between pipes in the loop, offset from wall and direction of drawing loop. Default way of drawing floor heating is counterclockwise. It is recommended to choose direction on longer side.

Cut part of loop

Izreži dio petlje

Cut part of loop Specify first point to cut Specify second point to cut

Reset loop label

Ponovno postavi

oznake petlji

Reset loop label Take name from calculation and set it on CAD drawing

Calculate loop length

Proracunaj stvarne duljine

petlji

Calculate loop length Program calculates real length of loops from CAD drawing.

- TOOLS -

Set room area

Postavi površinu prostorije

Tool for seting room area Select room from project Specify end points of room, when you select last point, click right mouse button to connect it with first point Program calculates room area

Read wall length

Preuzmi dužinu zida

Tool for specifying wall length Click two times in calculation field

Page 107: Integracad 2011 Eng

where you want to take length from drawing. Drawing is automaticly opened. Select points you want to measure from drawing. Length you measure is scaled depending on measure set for dwg file in info tab.

Hide foreing layers

Sakrivanje stranih slojeva

Tool for freezing all non INTEGRACAD layers

Set drawing reference

point

Postavi baznu točku crteža

set drawing reference point

Finalize loop

drawing

Završna obrada petlji

podnog grijanja

Select floor heating loop. Loop edges are rounded and second half of the loop is transfered in layer return.

- VENTILATION CANALS -

Draw supply

ventilation ducts

Crtanje dovodnih

ventilacijskih kanala

Draw supply ventilation ducts. Pipes are drawn like polylines Options: draw rectangular and circular ventilation ducts.

Draw drainage

ventilation ducts

Crtanje odvodnih

ventilacijskih kanala

Draw drainage ventilation ducts. Pipes are drawn like polylines Options: draw rectangular and circular ventilation ducts.

Setting up a network of ventilation

ducts

Postavljanje mre�e

ventilacijskih kanala

Setting up a network of ventilation ducts Specify area where you want to construct network of ventilation ducts. Ventilation ducts must be conected to floor entry points.

Mark Označi Mark ventilation element

Page 108: Integracad 2011 Eng

ventilation element

element ventilacije

After turning command on, you have to choose element you want to mark. Select location you want to place mark (you can see it while moving mouse). Mark is writen like block and you need to use command Explode if you want to edit text.

Page 109: Integracad 2011 Eng

Admin

Page 110: Integracad 2011 Eng

Introduction

Admin is a simple tool for radiator or room input into program, if they do not exist in it.

Starting the admin module:

Menu -> Edit -> Admin (Picture 1)

Picture 1

WINDOW DESCRIPTION:

Main Admin menu File - used to manage basic admin functions. New - creates a new project, Open - opens an existing project, Close - closes the active project, Save - saves the active project, Save as ... - saves the project named as, Recent file - , Exit - used to exit the Admin. Edit - this menu contains standard data editing tools. Undo - move previous command, Cut - cuts data (makes a copy but doesn't keep the original); Copy - for copying data (makes a copy and keeps the original; Paste - pastes cut or copied data on a chosen place. View - turns off/on status bar window. Window - contains some standard window options like: New window, Cascade, Tile, Arange icons, 1 Admin (currently open admin window). Help - short informations about current Admin version

Page 111: Integracad 2011 Eng

Function selection program have two admin functions Radiators and Room

working area - window view depends on your selection (radiator or room)

Page 112: Integracad 2011 Eng

Admin radiators

(Note! All changes will be visible only after you restart program.). Input radiators in the program database

First table:

insert radiator manufacturer. Press " Add new " button and write manufacturer name. Confirm your input name pressing " Add " button, or cancel this step pressing " Cancel " button.

insert radiator group name Note! first you must enter radiator manufacturer because without this inforamtion radiator admin will not work

insert radiator Type - 0 - for panel radiators, 1 - for glide radiators

insert radiator short Description- (Note: this is optional field)

Erase- mark this field and erase one radiator group from program database.

Second table:

Radiator name - radiator (e.g. Radiator XL 358/500)

Height - Radiator height in mm

Length - Radiator length in mm

Depth - Radiator depth in mm

n - exponent (If you don't know this information input 1,30 as the standard for all radiators

Surface - Radiator surface in m2 (Note: this is optional field)

Volume - radiator volume in liter (Note: this is optional field)

Mass - radiator mass in kg (Note: this is optional field)

q60 - radiator capacity in (W) according to DIN4703/4 for temperature regime 90/70/20 °C

q50 - radiator capacity in (W) according to EN442 for temperature regime 75/65/20 °C

Page 113: Integracad 2011 Eng

Erase - mark this field and erase one radiator from radiator group in program database Every change you make and want to keep press Refresh button to confirm that information.

Admin room

(Note! All changes will be visible only after you restart program.)

Input new room in the program database

enter the following data in table:

Room name - input new room name

Temperature - average room temperature

W / m2 - input watt per square meter for underfloor heating

Air exchange - input air exchange for a period of one hour

Erase - mark and earse rooms one or more rooms from list and from program database

Every change you make and want to keep press Refresh button to confirm that information.

Page 114: Integracad 2011 Eng

IntegraCAD news

Page 115: Integracad 2011 Eng

IntegraCAD packages

You can purchase IntegraCAD 2011 in seven different packages: * Sani * Duct * Termo * Professional * Suite * Premium * Enterprise The program packages include the same program framework (program interface, CAD, print, database) but a different amount of calculation modules. You can compare the different packages in the table below:

Page 116: Integracad 2011 Eng

Download last program version from web site

If you buy or update one of our IntegraCAD 2011 program licence packages (see chapter IntegraCAD packages in this help) then you'll get for free all last program versions in your licence time period (30; 90 or 365 days).

Versions are available for download on the official IntegraCAD website (0-24h), for all IntegraCAD users. New software upgrade comes out every 3 months, and after we release a new version you'll get notification on your email.

DOWNLOAD PROCEDURE:

* please open www.integracad.com * in upper right corner press Customer area (cro. lang. Partnerske stranice)

* please enter your username and password: (to download the new program version, video help or some additional content you must be logged in. New designed web page has improved security system and most of old user name and passwords is no longer valid, so please make sure that your new access data that we have sent to you by e-mail, because maybe we changed it. If you have any problems with access please contact us on telephone: +381 51 545 880 or on e-mail: [email protected]) User name (cro. lang. Korisničko ime): xxxxxxx Password (cro. lang. Lozinka): xxxxxxx

Page 117: Integracad 2011 Eng

* Click on Login button (cro. lang. Prijava) * If everything is OK, the following window will appear:

After you download the latest IntegraCAD program version (e.g. on your Desktop) you will receive IntegraCAD .zip file Unzip IntegraCAD file to get IntegraCAD 2011 Setup.exe (you can also do that on your Desktop) � after that you're ready to install program

WARNING !!! Before installing the new program version, uninstall the old one from your computer !!!

Page 118: Integracad 2011 Eng

Internet training

We offer Internet support through a specialised web conferencing system. During the conference the participants can see the presenters screen and follow the session in real time. All users see the same video output (the presenters screen) and can communicate with each other through a live audio connection.

An Internet presentation is the simplest and fastest way to experience the capabilities of the program. Without generating costs and with a minimum time investment, everybody with an interest in the program can get the answers to his/her questions. The presentation will give you a general overview of the software without discussing the fine points. After the presentation phase there will be time for Q&A and a possibility to explore some questions deeper. Program presentations can be individual or public.

Getting help for a current issue has never been easier. Program users can contact us by phone, e-mail or Skype and we will organize a support session as soon as possible. You can ask general questions (how to start a program function, avoid problems, etc.) or questions related to a current project. In general, the explanations will be made with standard support projects. For bigger issues, you can send us your project and drawing files and we will do our best to help. If the problems cannot be resolved during the support session, we will transfer them to our standard technical support procedure.

Internet training allows for a thorough insight into a part of the program. As a program user you have two options: you can request an individual training or you can join one of the regular public trainings. In the first case you can select the training topic freely but you need to make your training request at least 7 days in advance. In the case of public trainings the topic and date are already set and you need to apply at least 24 hours in advance. Public training dates will be announced on our website www.integracad.com at least two weeks in advance.

TECHNICAL PREREQUISITES

Internet Fast connection (DSL, optical cable)

Software Mozilla Firefox 3.5 or Internet Explorer 8

E-mail client for the initial communication

Hardware

Headphones and microphone compatible to Windows OS

Page 119: Integracad 2011 Eng

Contact

Page 120: Integracad 2011 Eng

Contacts

We thank you for using our software. If you need help or have suggestions or improvement requests do not hesitate to contact us:

Adress: Impuls d.o.o. Furicevo 90 HR - 51216 Viskovo Croatia Europe

tel. +385 51 545 880 fax. +385 51 545 881

e-mail: General information [email protected]

Technical support [email protected]

Website www.integracad.com