A Guide to IBM System x Uninterruptable Power Supply (UPS) ?A Fuse C13 C13 10A 10A C13 C19 10A 16A 15A Output = 22.5A Max 200-240V C13 C13 10A 10A C19 16A 15A Input = 30A 200-240V Outlet Type Breaker Amperage Outlet Amperage AC to DC then DC to AC UPS Logical Layout C13 10A C13 10A C13 10A TVSS GND TVSS GND TVSS GND N L3 L2 L1 3Ө 1Ө 3Ө 380V 400V 415V TVSS GND Outlets EBM Connection Block Input Block & Cover Outlet Circuit Breakers Double Conversion UPS Technology LOAD AC SOURCE NORMAL POWER FLOW STORED ENERGY POWER FLOW RECHARGE ENERGY FLOW BATTERY CHARGER BATTERY RECTIFIER INVERTER DC LINK Authors: William S. Champion [email protected] Matthew R. Archibald [email protected] Mitchell Walker [email protected] Version: 1.4.0 Date: October 26, 2010 The user of this document is responsible for obtaining the latest copy prior to use. Obsolete copies may be archived and used for reference purposes only. The latest version of this document is located at: http://www-03.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP101655 © IBM Corporation 2010
71
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: IBM System x UPS Guide v1.4.0

A Guide to IBM System x Uninterruptable Power Supply (UPS)

?A Fuse

C13

C13

10A

10A

C13

C19

10A

16A

15A

Output = 22.5A Max 200-240V

C13

C13

10A

10A

C1916A

15A

Input = 30A 200-240V

Outlet TypeBreaker

Amperage

Outlet

Amperage

AC to DC

then

DC to AC

UPS Logical Layout

C1310A

C1310A

C1310A

TV

SS

GN

D

www.apcc.com

ProbeOutput Zone

1

Pwr2

Reset

NO

+12V

NO

COM

NC

COM

GND

NO

NC

COM

10/100Base-T

10/100

AP9619 Network Management Card EM

TV

SS

GN

D

TV

SS

GN

D

NL3L2L1

3Ө380V

400V

415V

TV

SS

GN

D

www.apcc.com

ProbeOutput Zone

1

Pwr2

Reset

NO

+12V

NO

COM

NC

COM

GND

NO

NC

COM

10/100Base-T

10/100

AP9619 Network Management Card EM

Outlets

EBM Connection Block

Input Block & CoverOutlet Circuit Breakers

Double Conversion UPS Technology

LOADAC SOURCE

NORMAL POWER FLOW

STORED ENERGY POWER FLOW

RECHARGE ENERGY FLOW

BATTERY

CHARGER

BATTERY

RECTIFIER INVERTER

DC LINK

Authors: William S. Champion [email protected] Matthew R. Archibald [email protected] Mitchell Walker [email protected] Version: 1.4.0 Date: October 26, 2010

The user of this document is responsible for obtaining the latest copy prior to use. Obsolete copies may be archived and used for reference purposes only. The latest version of this document is located at: http://www-03.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP101655

© IBM Corporation 2010

Page 2: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 2 © IBM Corporation 2010

Revision History 1.0.0 – March 25, 2010 1.1.0 – May 17, 2010 1.2.0 – July 20, 2010 1.3.0 – September 28, 2010 1.4.0 – October 26, 2010

Initial Release Updated sections Introduction, How To Use This Guide, Input Connection Block for IBM UPS7500/10000, IBM System x Server Label Rating, IBM Storage Label Rating, IEC 309 Pin & Sleeve Plug Decode, and IEC 320 Connectors. Modified run times to be all in minutes. Added Some Background on Power Factor and UPS Sizing section. Added new rack mounted IBM UPS1500, IBM UPS2200, and IBM UPS3000, new line cords Update Helpful Links section. Updated Line Cords and Plugs section. Added new rack mounted IBM UPS6000. Add new IBM UPS1000/1500 tower models.

Contributors

Marc Hollingsworth [email protected] Manager, Global Accounts – Eaton http://www.eaton.com/ibm Ben Hilmus [email protected] World Wide Product Marketing Manager – IBM Systems x Preston Miller [email protected] Global Program Manager – American Power Conversion (APC) http://www.apc.com

Notices: This paper is intended to provide information regarding IBM

® System x™ Power Uninterruptable Power Supply (UPS). It discusses findings

based on configurations that were created and tested under laboratory conditions. These findings may not be realized in all customer environments, and implementation in such environments may require additional steps, configurations and performance analysis. The information herein is provided “AS IS” with no warranties, express or implied. This information does not constitute a specification or form part of the warranty for any IBM or non-IBM products. Information in this document was developed in conjunction with the use of the equipment specified and is limited in application to those specific hardware and software products and levels. The information contained in this document has not been submitted to any formal IBM test and is distributed as is. The use of this information or the implementation of these techniques is a customer responsibility and depends on the customer’s ability to evaluate and integrate them into the customer’s operational environment. While each item may have been reviewed by IBM for accuracy in a specific situation, there is no guarantee that the same or similar results will be obtained elsewhere. Customers attempting to adapt these techniques to their own environments do so at their own risk. IBM may not officially support techniques mentioned in this document. For questions regarding officially supported techniques, please refer to the product documentation, announcement letters or contact the IBM Support Line at 1-800-IBM-SERV. This document makes references to vendor-acquired applications or utilities. It is the customer responsibility to obtain licenses of these utilities prior to their usage. © Copyright International Business Machines Corporation 2010. All rights reserved. U.S. Government Users Restricted Rights – Use, duplication or disclosure restricted by GSA ADP Schedule Contract with IBM Corp.

Page 3: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 3 © IBM Corporation 2010

Table of Contents

TABLE OF CONTENTS ........................................................................................................................................................... 3

INTRODUCTION ................................................................................................................................................................... 6

HOW TO USE THIS GUIDE .............................................................................................................................................................. 6

IBM UPS QUICK VIEW .......................................................................................................................................................... 7

IBM UPS1000 TOWER NEW ............................................................................................................................................. 8

Optional Accessories ........................................................................................................................................................... 8 SELECTABLE LINE CORDS – IBM UPS1000 TOWER (230V) ................................................................................................................ 9 OUTLET DIAGRAM – IBM UPS1000 TOWER (100/120V) ............................................................................................................... 10

Logical Layout – IBM UPS1000 Tower (100/120V)............................................................................................................ 10 OUTLET DIAGRAM – IBM UPS1000 TOWER (230V) ....................................................................................................................... 11

Logical Layout – IBM UPS1000 Tower (230V) ................................................................................................................... 11 RUN TIME – IBM UPS1000 TOWER ............................................................................................................................................. 12

IBM UPS1500 TOWER NEW ........................................................................................................................................... 13

Optional Accessories ......................................................................................................................................................... 13 SELECTABLE LINE CORDS – IBM UPS1500 TOWER .......................................................................................................................... 14 OUTLET DIAGRAM – IBM UPS1500 TOWER (120V) ....................................................................................................................... 15

Logical Layout – IBM UPS1500 Tower (120V) ................................................................................................................... 15 OUTLET DIAGRAM – IBM UPS1500 TOWER (100V) ....................................................................................................................... 16

Logical Layout – IBM UPS1500 Tower (100V) ................................................................................................................... 16 OUTLET DIAGRAM – IBM UPS1500 TOWER (230V) ....................................................................................................................... 17

Logical Layout – IBM UPS1500 Tower (230V) ................................................................................................................... 17 RUN TIME – IBM UPS1500 TOWER ............................................................................................................................................. 18

IBM UPS1000/1500 TOWER – OLD ..................................................................................................................................... 19

SELECTABLE LINE CORDS – UPS1000/1500THV ............................................................................................................................ 20 OUTLET DIAGRAM – IBM UPS1000/1500 LOW VOLTAGE ............................................................................................................... 20

Logical Layout – IBM UPS1000 Low Voltage ..................................................................................................................... 20 Logical Layout – IBM UPS1500 Low Voltage ..................................................................................................................... 21

OUTLET DIAGRAM – IBM UPS1000/1500 HIGH VOLTAGE .............................................................................................................. 21 Logical Layout – IBM UPS1000 High Voltage .................................................................................................................... 21 Logical Layout – IBM UPS1500 High Voltage .................................................................................................................... 22

RUN TIME – IBM UPS1000/1500 .............................................................................................................................................. 22

IBM UPS1500 – RACK MOUNTED (RM) .............................................................................................................................. 23

Optional Accessories ......................................................................................................................................................... 23 SELECTABLE LINE CORDS – IBM UPS1500 RM .............................................................................................................................. 24 OUTLET DIAGRAM – IBM UPS1500 RM 100/120V ...................................................................................................................... 24

Logical Layout – IBM UPS1500 RM 100/120V .................................................................................................................. 24 OUTLET DIAGRAM – IBM UPS1500 RM 230V .............................................................................................................................. 25

Logical Layout – IBM UPS1500 RM 230V .......................................................................................................................... 25 RUN TIME – IBM UPS1500 RM ................................................................................................................................................. 25

IBM UPS2200 – RACK MOUNTED (RM) .............................................................................................................................. 26

Optional Accessories ......................................................................................................................................................... 26 SELECTABLE LINE CORDS – IBM UPS2200 RM .............................................................................................................................. 27 OUTLET DIAGRAM – IBM UPS2200 RM 100/120V ...................................................................................................................... 28

Logical Layout – IBM UPS2200 RM 100/120V .................................................................................................................. 28 OUTLET DIAGRAM – IBM UPS2200 RM 230V .............................................................................................................................. 29

Logical Layout – IBM UPS2200 RM 230V .......................................................................................................................... 29 RUN TIME – IBM UPS2200 RM – 100/120V .............................................................................................................................. 29 RUN TIME – IBM UPS2200 RM – 230V ...................................................................................................................................... 30

Page 4: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 4 © IBM Corporation 2010

EBM CONNECTIONS – IBM UPS2200 RM .................................................................................................................................... 30

IBM UPS3000 – RACK MOUNTED (RM) .............................................................................................................................. 31

Optional Accessories ......................................................................................................................................................... 31 SELECTABLE LINE CORDS – IBM UPS3000 RM .............................................................................................................................. 32 OUTLET DIAGRAM – IBM UPS3000 RM 100/120V ...................................................................................................................... 33

Logical Layout – IBM UPS3000 RM 100/120V .................................................................................................................. 33 OUTLET DIAGRAM – IBM UPS3000 RM 200/208V ...................................................................................................................... 34

Logical Layout – IBM UPS3000 RM 200/208V .................................................................................................................. 34 OUTLET DIAGRAM – IBM UPS3000 RM 230V .............................................................................................................................. 35

Logical Layout – IBM UPS3000 RM 230V .......................................................................................................................... 35 RUN TIME – IBM UPS3000 RM 100/120V ................................................................................................................................. 35 RUN TIME – IBM UPS3000 RM 200/208V ................................................................................................................................. 36 RUN TIME – IBM UPS3000 RM 230V ........................................................................................................................................ 36 EBM CONNECTIONS – IBM UPS3000 RM .................................................................................................................................... 36

IBM UPS5000 – RACK MOUNTED ....................................................................................................................................... 37

SELECTABLE LINE CORDS – IBM UPS5000 ..................................................................................................................................... 37 OUTLET DIAGRAM – IBM UPS5000 ............................................................................................................................................. 38

Logical Layout – IBM UPS5000 .......................................................................................................................................... 38 RUN TIME – IBM UPS5000 ........................................................................................................................................................ 39 EBM CONNECTIONS – IBM UPS5000 .......................................................................................................................................... 39

IBM UPS6000 – RACK MOUNTED NEW .......................................................................................................................... 40

Optional Accessories ......................................................................................................................................................... 40 OUTLET DIAGRAM – IBM UPS6000 200/208V ............................................................................................................................ 41

Logical Layout – IBM UPS6000 200/208V ......................................................................................................................... 41 OUTLET DIAGRAM – IBM UPS6000 230V .................................................................................................................................... 42

Logical Layout – IBM UPS6000 230V ................................................................................................................................ 42 RUN TIME – IBM UPS6000 ........................................................................................................................................................ 43 EBM CONNECTIONS – IBM UPS6000 .......................................................................................................................................... 43 INPUT CONNECTION BLOCK – IBM UPS6000 ................................................................................................................................. 44

IBM UPS7500/10000 – RACK MOUNTED ............................................................................................................................ 45

OUTLET DIAGRAM – IBM UPS7500/10000 ................................................................................................................................. 46 Logical Layout – IBM UPS7500/10000 .............................................................................................................................. 46

RUN TIME – IBM UPS7500/10000 ............................................................................................................................................ 47 EBM CONNECTIONS – IBM UPS7500/10000 .............................................................................................................................. 48 INPUT CONNECTION BLOCK – IBM UPS7500/10000 ..................................................................................................................... 49

International Connection Only .......................................................................................................................................... 49 North American Connection Only ...................................................................................................................................... 49

LINE CORDS AND PLUGS .................................................................................................................................................... 50

100-127V NEMA 5-15P (UNITED STATES) UPS1000/1500TLV .................................................................................................... 50 100/120V NEMA 5-15P (NORTH AMERICA & JAPAN) UPS1500 RM & TOWER ............................................................................... 50 100/120V NEMA 5-20P (NORTH AMERICA & JAPAN) UPS2200 RM ............................................................................................. 50 100/120V NEMA L5-30P (NORTH AMERICA & JAPAN) UPS3000 RM ............................................................................................ 51 200/208V NEMA L6-20P (NORTH AMERICA & JAPAN) UPS3000 RM ............................................................................................ 51 CEE7-VII (EUROPE) ................................................................................................................................................................... 52 DK2-5A (DENMARK) .................................................................................................................................................................. 52 SEV 1011-S24507 (SWITZERLAND) ............................................................................................................................................. 52 SI 32 (ISRAEL) ........................................................................................................................................................................... 53 CEI 23-16 (ITALY) ..................................................................................................................................................................... 53 SABS 164 (SOUTH AFRICA) ......................................................................................................................................................... 54 BS 1363/A (UK) ...................................................................................................................................................................... 54 AS/NZS 3112 (AUS/NZ) ........................................................................................................................................................... 55

Page 5: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 5 © IBM Corporation 2010

KSC 8305 (S. KOREA) ................................................................................................................................................................ 55 IS6538 (INDIA) ......................................................................................................................................................................... 56 GB 2099.1 (CHINA) .................................................................................................................................................................. 56 NBR 6147 (BRAZIL) ................................................................................................................................................................... 57 IRAM 2073 (ARGENTINA) .......................................................................................................................................................... 57 IEC 309 P+N+G (DENMARK/SWITZERLAND) .................................................................................................................................. 57 NBR 14136 (BRAZIL) ................................................................................................................................................................. 58 SEV 1011 T23 (SWITZERLAND) ................................................................................................................................................... 58 CNS 10917 – 125V (TAIWAN) ................................................................................................................................................... 58 CNS 10917 – 250V (TAIWAN) ................................................................................................................................................... 59 40K9612 - IBM DPI 32A CORD (IEC 309 P+N+G) ....................................................................................................................... 59 40K9614 - IBM DPI 30A CORD (NEMA L6-30P)......................................................................................................................... 59 40K9617 – IBM DPI 32A CORD (AUS/NZ 3112 32A) ................................................................................................................. 60 40K9618 – IBM DPI 30A CORD (KSC 8305 30A) ........................................................................................................................ 60

REFERENCE MATERIAL ....................................................................................................................................................... 61

IBM BLADECENTER CHASSIS LABEL RATING .................................................................................................................................... 61 IBM STORAGE LABEL RATING ....................................................................................................................................................... 61 IBM SYSTEM X SERVER LABEL RATING ............................................................................................................................................ 62 IBM IDATAPLEX CHASSIS LABEL RATING ......................................................................................................................................... 63 IBM XSERIES SERVER LABEL RATING .............................................................................................................................................. 64 SOME BACKGROUND ON POWER FACTOR AND UPS SIZING ................................................................................................................ 65 IEC 309 PIN & SLEEVE PLUG DECODE ........................................................................................................................................... 67 INGRESS PROTECTION (IP) DECODE ............................................................................................................................................... 67 IEC 320 CONNECTORS ................................................................................................................................................................ 68 60A THREE PHASE DELTA POWER CALCULATIONS ............................................................................................................................ 68 32A THREE PHASE WYE POWER CALCULATIONS .............................................................................................................................. 69 UPS INSTALLATION MANUAL LINKS ............................................................................................................................................... 70 HELPFUL LINKS........................................................................................................................................................................... 71

Page 6: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 6 © IBM Corporation 2010

Introduction The Uninterruptible Power Supply (UPS) systems covered in this guide are those that are currently marketed worldwide. The intent of this guide is to provide UPS information when needed when planning power for System x and BladeCenter solutions. This guide is best used in softcopy form since it contains hyperlinks for navigation. This document can still be used in hardcopy as reference only. You can obtain the latest copy of this document by sending an email to [email protected] or [email protected] (put “Latest UPS Guide” in the subject line). For more information about how to size and plan for UPS systems, see the “Background on Power Factor and UPS Sizing” section on page 65 of this document.

How to Use This Guide

In order to size a UPS properly, you need to know the total power requirements of what will be connected to the UPS. This information is available from the System x & BladeCenter Power Configurator:

http://www-03.ibm.com/systems/bladecenter/resources/powerconfig.html When the total supported power is know, and appropriately sized UPS can be selected. Once a UPS is selected the solution wiring needs to be figured out. UPS systems have outlet and group limits, much like PDUs and the solution needs to be wired so as to not exceed the outlet and/or group rating of the UPS. The IT appliances and UPS systems need to be wired according to system nameplate rating for compliance with local electrical codes and product support documentation. In cases where a UPS fits the electrical load of a solution, but the UPS does not have sufficient C13 outlets, DPI Universal Rack PDUs (P/N: 39Y8951 F/C: 5950) may be able to be used to offer additional C13 outlets. When wiring the solution using PDUs, the same restrictions apply in that the outlet and group limitations of the UPS and PDUs are not exceeded.

Page 7: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 7 © IBM Corporation 2010

IBM UPS Quick View

UPS Option

Number Input

Voltage Max Input Amperage

Output Voltage Output W / Amperage Outlets Page

UPS1000

Tower New

53961AX 120V 1ph 12A

120V 1ph 750W / 7.5A

8 / 5-151

8 53961JX7 100V 1ph 100V 1ph 8 / 5-15

1

53961KX8 230V 1ph 10A 230V 1ph 750W / 3.75A 8 / C13

5

UPS1000 Tower – Old

2130R3X 100-127V

1ph 10A 120V 1ph 700W / 7A 8 / 5-15

1

19 2130R4X 200-240V

1ph 5A

200-240V 1ph

700W / 3.5A 8 / C135

2130R8X7

100-127V 1ph

10A 100V 1ph 700W / 7A 8 / 5-151

UPS1500

Tower New

53962AX 120V 1ph 12A 120V 1ph 1000W / 10A

8 / 5-151

13 53962JX7 100V 1ph 16A 100V 1ph 8 / 5-20

2

53962KX8 230V 1ph 10A 230V 1ph 1000W / 5A 8 / C13

5

UPS1500 Tower – Old

2130R5X 100-127V

1ph 15A 120V 1ph 1050W / 10.5A 8 / 5-15

1

19 2130R6X 200-240V

1ph 7.5A

200-240V 1ph

1050W / 5.25A 8 / C135

2130R9X7

100-127V 1ph

15A 100V 1ph 1050W / 10.5A 8 / 5-151

UPS1500 Rack

53951AX 100-127V

1ph 13A

120V 1ph 100V 1ph

1000W / 10A 4 / 5-15

1

2 / C135 23

53951KX 230V 1ph 7.5A 230V 1ph 1000W / 5A 4 / C135

UPS2200 Rack

53952AX 100-127V

1ph 16A

120V 1ph 100V 1ph

1920W / 16A @ 120V 1500W / 16A @ 100V

6 / 5-202

2 / C135

2 / C196 26

53952KX 230V 1ph 10A 230V 1ph 1920W / 9.6A 8 / C13

5

2 / C196

UPS3000 Rack

53953AX 100-127V

1ph 24A

120V 1ph 100V 1ph

2700W / 22.5A @ 120V 2300W / 22.5A @ 100V

2 / 5-202

1 / L5-203

2 / C135

2 / C196

31 53953JX

200V 1ph 208V 1ph

16A 200V 1ph 208V 1ph

2700W / 13.5A 1 / L6-20

4

2 / C135

2 / C196

53953KX 230V 1ph 16A 230V 1ph 2700W / 13.5A 8 / C13

5

2 / C196

UPS5000 Rack

24195KX 200-240V

1ph 25A

200-240V 1ph

4500W / 22.5A 8 / C13

5

2 / C196

37

UPS6000

Rack New

53956AX 200V 1ph 208V 1ph

30A 200V 1ph 208V 1ph

5600W / 28A

2 / L6-309

4 / C196

40

53956KX 230V 1ph 30A 230V 1ph 6 / C13

5

4 / C196

UPS7500 Rack

21303JX7 200V 1ph

38A

200V 1ph

6000W / 30A 4 / C196 45

21303RX

200-240V 1ph 200-

240V 1ph 380-415V 3ph Wye

8

14A

UPS10000 Rack

21304JX7 200V 1ph

50A

200V 1ph

8000W / 40A 4 / C196 45

21304RX

200-240V 1ph 200-

240V 1ph 380-415V 3ph Wye

8

18A

1 – “5-15” refers to NEMA 5-15 outlet 2 – “5-20” refers to NEMA 5-20 outlet 3 – “L5-20” refers to NEMA L5-20 outlet 4 – “L6-20” refers to NEMA L6-20 outlet 5 – “C13” refers to IEC320 C13 outlet

6 – “C19” refers to IEC320 C19 outlet 7 – Supported only in Japan 8 – Not supported in North America or Japan 9 – “L6-30” refers to NEMA L6-30 outlet

Page 8: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 8 © IBM Corporation 2010

IBM UPS1000 Tower New

IBM UPS1000Tower Front

Back53961AX (120V)53961JX (100V)

Back53961KX (230V)

UPS1000 120V UPS1000 100V UPS1000 230V

Part Number 5396-1AX 5396-1JX 5396-1KX

Feature Code 5396-TU1 (FC 6663) - -

EBMs Supported None None None

EPO Connection Yes Yes Yes

Power Factor 0.75 0.75 0.75

UPS Type Line Interactive Line Interactive Line Interactive

Supported Country or Region North America Japan International

Input 120V 100V 230V

Line Cord detachable 4.3m, NEMA 5-15P

detachable 4.3m, NEMA 5-15P

Selectable

Voltage Range 84-121V for 100V 97-145V for 120V

84-121V for 100V 97-145V for 120V

160V-286V for 230V

Max Current 12A 12A 10A

Phase / Frequency 1ph / 50 or 60Hz. 1ph / 50 or 60Hz. 1ph / 50 or 60Hz.

Surge Energy Rating 1200 joules 1200 joules 2400 joules

Output 120V 100V 230V

Watts 750W 750W 750W

Nominal Voltage 120V (Configurable) 100V (Configurable)

220, 230, or 240V (Configurable)

Maximum Amperage 7.5A 7.5A 3.75A

Receptacles 8 x NEMA 5-15R 8 x NEMA 5-15R 8 x IEC 320 C13

Optional Accessories

Network Management Card (NMC) P/N: 46M4110 FC: 6145

Environmental Monitor Probe P/N: 46M4113 FC: 6146

Page 9: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 9 © IBM Corporation 2010

Selectable Line Cords – IBM UPS1000 Tower (230V)

2.8m Line Cord

4.3m Line Cord Plug Type Country or Region

39Y7917 81Y2376 CEE7-VII Europe 39Y7918 81Y2382 DK2-5a Denmark 39Y7919 81Y2390 SEV 1011-S24507 Switzerland 39Y7920 81Y2381 SI 32 Israel 39Y7921 81Y2380 CEI 23-16 Italy 39Y7922 81Y2379 SABS 164 South Africa 39Y7923 81Y2377 BS 1363/A United Kingdom 39Y7924 81Y2383 AS/NZS 3112 Australia / New Zealand 39Y7925 81Y2385 KSC 8305 South Korea 39Y7927 81Y2386 IS6538 India 39Y7928 81Y2378 GB 2099.1 China 81Y2374 81Y2388 CNS 10917 (125V) Taiwan 81Y2375 81Y2389 CNS 10917 (250V) Taiwan 39Y7929 81Y2387 NBR 6147 Brazil 39Y7930 81Y2384 IRAM 2073 Argentina

Page 10: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 10 © IBM Corporation 2010

Outlet Diagram – IBM UPS1000 Tower (100/120V)

6 NEMA 5-15P

(Load Segment 2)

2 NEMA 5-15P

(Load Segment 1)

Optional

NMC Bay

Detachable

Line Cord

USB

Remote emergency

power-off port

RS-232

Connector

Logical Layout – IBM UPS1000 Tower (100/120V)

Input Line

5-15

5-15

15A

15A

5-15

5-15

15A

15A

Output = 7.5A Max 100-120V

Input = 12A 100-120V

Outlet Type

Outlet

Amperage

AC to DC

then

DC to AC

5-15

5-15

15A

15A

5-15

5-15

15A

15A

Page 11: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 11 © IBM Corporation 2010

Outlet Diagram – IBM UPS1000 Tower (230V)

6 IEC 320 C13

(Load Segment 2)

2 IEC 320 C13

(Load Segment 1)

Optional

NMC Bay

Detachable

Line Cord

USB

Remote emergency

power-off port

RS-232

Connector

Logical Layout – IBM UPS1000 Tower (230V)

Input Line

C13

C13

10A

10A

C13

C13

10A

10A

Output = 3.75A Max 200-240V

Input = 10A 200-240V

Outlet Type

Outlet

Amperage

AC to DC

then

DC to AC

C13

C13

10A

10A

C13

C13

10A

10A

Page 12: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 12 © IBM Corporation 2010

Run Time – IBM UPS1000 Tower

% Load (W) Internal

Batteries

25% 188 25

50% 375 15

75% 573 7

100% 750 6

Note: Run times are in minutes

Page 13: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 13 © IBM Corporation 2010

IBM UPS1500 Tower New

IBM UPS1500Tower Front

Back53962AX (120V)

Back53962JX (100V)

Back53962KX (230V)

UPS1500 120V UPS1500 100V UPS1500 230V

Part Number 5396-2AX 5396-2JX 5396-2KX

Feature Code 5396-TU2 (FC 6666) - -

EBMs Supported None None None

EPO Connection Yes Yes Yes

Power Factor 0.7 0.7 0.7

UPS Type Line Interactive Line Interactive Line Interactive

Supported Country or Region North America Japan International

Input 120V 100V 230V

Line Cord detachable 2.8m, NEMA 5-15P

detachable 2.5m, NEMA 5-20P

Selectable

Voltage Range 97-145V 84-121V 160V-286V

Max Current 12A 16A 10A

Phase / Frequency 1ph / 50 or 60Hz. 1ph / 50 or 60Hz. 1ph / 50 or 60Hz.

Surge Energy Rating 1200 joules 1200 joules 2400 joules

Output 120V 100V 230V

Watts 1000W 1000W 1000W

Nominal Voltage 120V (Configurable) 100V (Configurable)

220, 230, or 240V (Configurable)

Maximum Amperage 10A 10A 5A

Receptacles 8 x NEMA 5-15R 8 x NEMA 5-15R 8 x IEC 320 C13

Optional Accessories

Network Management Card (NMC) P/N: 46M4110 FC: 6145

Environmental Monitor Probe P/N: 46M4113 FC: 6146

Page 14: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 14 © IBM Corporation 2010

Selectable Line Cords – IBM UPS1500 Tower

2.8m Line Cord

4.3m Line Cord Plug Type Country or Region

39Y7917 81Y2376 CEE7-VII Europe 39Y7918 81Y2382 DK2-5a Denmark 39Y7919 81Y2390 SEV 1011-S24507 Switzerland 39Y7920 81Y2381 SI 32 Israel 39Y7921 81Y2380 CEI 23-16 Italy 39Y7922 81Y2379 SABS 164 South Africa 39Y7923 81Y2377 BS 1363/A United Kingdom 39Y7924 81Y2383 AS/NZS 3112 Australia / New Zealand 39Y7925 81Y2385 KSC 8305 South Korea 39Y7927 81Y2386 IS6538 India 39Y7928 81Y2378 GB 2099.1 China 81Y2374 81Y2388 CNS 10917 (125V) Taiwan 81Y2375 81Y2389 CNS 10917 (250V) Taiwan 39Y7929 81Y2387 NBR 6147 Brazil 39Y7930 81Y2384 IRAM 2073 Argentina

Page 15: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 15 © IBM Corporation 2010

Outlet Diagram – IBM UPS1500 Tower (120V)

6 NEMA 5-15P

(Load Segment 2)

2 NEMA 5-15P

(Load Segment 1)

Optional

NMC Bay

Detachable

Line Cord

USB

Remote emergency

power-off port

RS-232

Connector

Logical Layout – IBM UPS1500 Tower (120V)

Input Line

5-15

5-15

15A

15A

5-15

5-15

15A

15A

Output = 10A Max 100-120V

Input = 12A 100-120V

Outlet Type

Outlet

Amperage

AC to DC

then

DC to AC

5-15

5-15

15A

15A

5-15

5-15

15A

15A

Page 16: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 16 © IBM Corporation 2010

Outlet Diagram – IBM UPS1500 Tower (100V)

6 NEMA 5-20P

(Load Segment 2)

2 NEMA 5-20P

(Load Segment 1)

Optional

NMC Bay

Detachable

Line Cord

USB

Remote emergency

power-off port

RS-232

Connector

Logical Layout – IBM UPS1500 Tower (100V)

Input Line

5-20

5-20

20A

20A

5-20

5-20

20A

20A

Output = 10A Max 100V

Input = 16A 100V

Outlet Type

Outlet

Amperage

AC to DC

then

DC to AC

IBM UPS1500LV 100V

5-20

5-20

20A

20A

5-20

5-20

20A

20A

Page 17: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 17 © IBM Corporation 2010

Outlet Diagram – IBM UPS1500 Tower (230V)

6 IEC 320 C13

(Load Segment 2)

2 IEC 320 C13

(Load Segment 1)

Optional

NMC Bay

Detachable

Line Cord

USB

Remote emergency

power-off port

RS-232

Connector

Logical Layout – IBM UPS1500 Tower (230V)

Input Line

C13

C13

10A

10A

C13

C13

10A

10A

Output = 5A Max 200-240V

Input = 10A 200-240V

Outlet Type

Outlet

Amperage

AC to DC

then

DC to AC

IBM UPS1500LV 230V

C13

C13

10A

10A

C13

C13

10A

10A

Page 18: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 18 © IBM Corporation 2010

Run Time – IBM UPS1500 Tower

% Load (W) Internal

Batteries

25% 255 36

50% 510 15

75% 750 9

100% 970 6

Note: Run times are in minutes

Page 19: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 19 © IBM Corporation 2010

IBM UPS1000/1500 Tower – Old

UPS1000/1500

TLV BackUPS1000/1500

THV Back

UPS1000TLV UPS1000THV UPS1000TJV UPS1500TLV UPS1500THV UPS1500TJV

Part Number 2130R3X 2130R4X 2130R8X 2130R5X 2130R6X 2130R9X

EBMs Supported

None None None None None None

EPO Connection

None None None None None None

Power Factor 0.7 0.7 0.7 0.7 0.7 0.7

UPS Type Double Conversion

Double Conversion

Double Conversion

Double Conversion

Double Conversion

Double Conversion

Input Low Voltage High Voltage Japan Low Voltage High Voltage Japan

Supported Region

North America International1 Japan North America International

1 Japan

Line Cord Attached 6ft, NEMA 5-15P

Selectable Attached 6ft, NEMA 5-15P

Attached 6ft, NEMA 5-15P

Selectable Attached 6ft, NEMA 5-15P

Voltage 100-127V 200-240V 100-127V 100-127V 200-240V 100-127V

VA 1000VA 1000 VA 1000 VA 1500 VA 1500 VA 1500 VA

Max Current 10A 5A 10A 15A 7.5A 15A

Phase / Frequency

1ph / 50 or 60Hz.

1ph / 50 or 60Hz.

1ph / 50 or 60Hz.

1ph / 50 or 60Hz.

1ph / 50 or 60Hz.

1ph / 50 or 60Hz.

Output Low Voltage High Voltage Japan Low Voltage High Voltage Japan

Watts 700W 700 W 700 W 1050 W 1050 W 1050 W

Nominal voltage

120V 200-240V 100V 120V 200-240V 100V

Max Current 7A 3.5A 7A 10.5A 5.25A 10.5A

Receptacles 8 / 5-15R 8 / C13 8 / 5-15R 8 / 5-15R 8 / C13 8 / 5-15R

1 – Does not include support for North America or Japan

Page 20: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 20 © IBM Corporation 2010

Selectable Line Cords – UPS1000/1500THV

Line Cord Plug Type Country or Region 39Y7917 CEE7-VII Europe 39Y7918 DK2-5a Denmark 39Y7919 SEV 1011-S24507 Switzerland 39Y7920 SI 32 Israel 39Y7921 CEI 23-16 Italy 39Y7922 SABS 164 South Africa 39Y7923 BS 1363/A United Kingdom 39Y7924 AS/NZS 3112 Australia / New Zealand 39Y7925 KSC 8305 South Korea 39Y7927 IS6538 India 39Y7928 GB 2099.1 China 39Y7929 NBR 6147 Brazil 39Y7930 IRAM 2073 Argentina

Outlet Diagram – IBM UPS1000/1500 Low Voltage

OutletsInput Line Cord

15A Circuit Breaker

Battery Connector *

Logical Layout – IBM UPS1000 Low Voltage

Input Line

5-15

5-15

15A

15A

5-15

5-15

15A

15A

15A

Output = 7A Max 100-120V

Input = 10A 100-120V

Outlet TypeBreaker

Amperage

Outlet

Amperage

AC to DC

then

DC to AC

5-15

5-15

15A

15A

5-15

5-15

15A

15A

Page 21: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 21 © IBM Corporation 2010

Logical Layout – IBM UPS1500 Low Voltage

Input Line

5-15

5-15

15A

15A

5-15

5-15

15A

15A

20A

Output = 10.5A Max 100-120V

Input = 15A 100-120V

Outlet TypeBreaker

Amperage

Outlet

Amperage

AC to DC

then

DC to AC

5-15

5-15

15A

15A

5-15

5-15

15A

15A

Outlet Diagram – IBM UPS1000/1500 High Voltage

Outlets

Input Line Cord Connector

15A Circuit Breaker

Battery Connector *

Logical Layout – IBM UPS1000 High Voltage

Input Line

C13

C13

10A

10A

C13

C13

10A

10A

15A

Output = 3.5A Max 200-240V

Input = 5A 200-240V

Outlet TypeBreaker

Amperage

Outlet

Amperage

AC to DC

then

DC to AC

C13

C13

10A

10A

C13

C13

10A

10A

Page 22: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 22 © IBM Corporation 2010

Logical Layout – IBM UPS1500 High Voltage

Input Line

C13

C13

10A

10A

C13

C13

10A

10A

20A

Output = 5.25A Max 200-240V

Input = 7.5A 200-240V

Outlet TypeBreaker

Amperage

Outlet

Amperage

AC to DC

then

DC to AC

C13

C13

10A

10A

C13

C13

10A

10A

Run Time – IBM UPS1000/1500

Runtime (minutes)

Load (W) UPS1000T UPS1500T

30 224 269

60 127 157

122 64 80

184 41 51

247 29 37

311 23 28

377 18 22

447 15 18

500 13.5 16.5

511 12 15

579 11 13

700 8 11

790 - 9

936 - 7.4

1050 - 6.7

Page 23: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 23 © IBM Corporation 2010

IBM UPS1500 – Rack Mounted (RM)

IBM UPS1500 RM Front 53951AX (100V, 120V) Back 53951KX (230V) Back

UPS1500 100/120V UPS1500 230V

Part Number 5395-1AX 5395-1KX

Feature Code 5395-RU1 (FC 6653) 5395-RU1 (FC 6654)

EBMs Supported None None

U Space 2 2

EPO Connection Yes Yes

Power Factor 0.7 0.7

UPS Type Line Interactive Line Interactive

Supported Country or Region North America, Japan World Wide

Input 100/120V 230V

Line Cord detachable 4.3m, NEMA 5-15P

Selectable

Voltage Range 84-121V for 100V 97-145V for 120V

160V-286V for 230V

Max Current 13A 7.5A

Phase / Frequency 1ph / 50 or 60Hz. 1ph / 50 or 60Hz.

Surge Energy Rating 1200 joules 2400 joules

Output 100/120V 230V

Watts 1000W 1000W

Nominal Voltage 100V, 120V (Configurable)

220, 230, or 240V (Configurable)

Maximum Amperage 10A 5A

Receptacles 4 x NEMA 5-15R 2 x IEC 320 C13

4 x IEC 320 C13

Optional Accessories

Network Management Card (NMC) P/N: 46M4110 FC: 6145

Environmental Monitor Probe P/N: 46M4113 FC: 6146

Page 24: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 24 © IBM Corporation 2010

Selectable Line Cords – IBM UPS1500 RM

2.8m Line Cord

4.3m Line Cord Plug Type Country or Region

39Y7917 81Y2376 CEE7-VII Europe 39Y7918 81Y2382 DK2-5a Denmark 39Y7919 81Y2390 SEV 1011-S24507 Switzerland 39Y7920 81Y2381 SI 32 Israel 39Y7921 81Y2380 CEI 23-16 Italy 39Y7922 81Y2379 SABS 164 South Africa 39Y7923 81Y2377 BS 1363/A United Kingdom 39Y7924 81Y2383 AS/NZS 3112 Australia / New Zealand 39Y7925 81Y2385 KSC 8305 South Korea 39Y7927 81Y2386 IS6538 India 39Y7928 81Y2378 GB 2099.1 China 81Y2374 81Y2388 CNS 10917 (125V) Taiwan 81Y2375 81Y2389 CNS 10917 (250V) Taiwan 39Y7929 81Y2387 NBR 6147 Brazil 39Y7930 81Y2384 IRAM 2073 Argentina

Outlet Diagram – IBM UPS1500 RM 100/120V

Ground Screw RS-232

Connector

2 IEC 320 C13

(Load Segment 2)Remote emergency

power-off port

4 NEMA 5-15R

(Load Segment 1)USB

Detachable

Line CordOptional

NMC Bay

Logical Layout – IBM UPS1500 RM 100/120V

Input Line

5-15

5-15

15A

15A

5-15

5-15

15A

15A

Output = 10A Max @ 100-120V

C13

C13

10A

10A

Input = 13A Max @ 100-120V

Outlet Type

Outlet

Amperage

AC to DC

then

DC to AC

Note: Color Indicates Load Grouping

Page 25: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 25 © IBM Corporation 2010

Outlet Diagram – IBM UPS1500 RM 230V

RS-232 2 IEC320 C13

(Load Segment 2)

2 IEC320 C13

(Load Segment 1)

Remote emergency

power-off port

USB

Detachable

Line Cord

Optional

NMC Bay

Ground

Screw

Logical Layout – IBM UPS1500 RM 230V

Input Line

C13

C13

15A

15A

Output = 5A Max @ 220-240V

C13

C13

10A

10A

Input = 7.5A Max @ 220-240V

Outlet Type

Outlet

Amperage

AC to DC

then

DC to AC

Note: Color Indicates Load Grouping

Run Time – IBM UPS1500 RM

% Load (W) Internal

Batteries

25% 250 14

50% 500 11

75% 750 7

100% 1000 5

Note: Run times are in minutes

Page 26: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 26 © IBM Corporation 2010

IBM UPS2200 – Rack Mounted (RM)

IBM UPS2200 RM Front 53952AX (100V, 120V) Back 53952KX (230V) Back

IBM UPS2200 EBM Front

UPS2200 100/120V UPS2200 230V EBM

Part Number 5395-2AX 5395-2KX 46M4108

Feature Code 5395-RU2 (FC 6655) 5395-RU2 (FC 6656) 5395-RU2 (FC 5732)

EBMs Supported 1 1 -

U Space 2 2 2

EPO Connection Yes Yes -

Power Factor 1.0 0.96 -

UPS Type Line Interactive Line Interactive -

Supported Country or Region

North America, Japan World Wide -

Input 100/120V 230V EBM

Line Cord Detachable 4.3m, NEMA 5-20P

Selectable -

Voltage Range 84-121V for 100V 97-145V for 120V

160V-286V for 230V -

Max Current 16A 10A -

Phase / Frequency 1ph / 50 or 60Hz. 1ph / 50 or 60Hz. -

Surge Energy Rating 1200 joules 2400 joules -

Output 100/120V 230V EBM

Watts 1500W @ 100V (Japan)

1920W @ 120V (North America)

1920W -

Nominal Voltage 100V, 120V (Configurable)

220, 230, or 240V (Configurable)

-

Maximum Amperage 16A @ 100V 16A @ 120V

9.6A

Receptacles 6 x NEMA 5-20R 2 x IEC 320 C19 2 x IEC 320 C13

2 x IEC 320 C19 8 x IEC 320 C13

-

Optional Accessories

Network Management Card (NMC) P/N: 46M4110 FC: 6145

Environmental Monitor Probe P/N: 46M4113 FC: 6146

Page 27: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 27 © IBM Corporation 2010

Selectable Line Cords – IBM UPS2200 RM

2.8m Line Cord

4.3m Line Cord Plug Type Country or Region

39Y7917 81Y2376 CEE7-VII Europe 39Y7918 81Y2382 DK2-5a Denmark 39Y7919 81Y2390 SEV 1011-S24507 Switzerland 39Y7920 81Y2381 SI 32 Israel 39Y7921 81Y2380 CEI 23-16 Italy 39Y7922 81Y2379 SABS 164 South Africa 39Y7923 81Y2377 BS 1363/A United Kingdom 39Y7924 81Y2383 AS/NZS 3112 Australia / New Zealand 39Y7925 81Y2385 KSC 8305 South Korea 39Y7927 81Y2386 IS6538 India 39Y7928 81Y2378 GB 2099.1 China

- 81Y2388 CNS 10917 (125V) Taiwan 81Y2375 81Y2389 CNS 10917 (250V) Taiwan 39Y7929 81Y2387 NBR 6147 Brazil 39Y7930 81Y2384 IRAM 2073 Argentina

Page 28: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 28 © IBM Corporation 2010

Outlet Diagram – IBM UPS2200 RM 100/120V

Remote emergency

power-off port

6 6 NEMA 5-20R

(Load Segment 1)

USB

RS-232

ConnectorOptional EBM

Connector

2 IEC 320 C19

(Load Segment 1)

2 IEC 320 C13

(Load Segment 2)

Ground

Screw

Optional

NMC Bay

Detachable

Line Cord

Logical Layout – IBM UPS2200 RM 100/120V

Input Line

5-20

5-20

20A

20A

C19

C19

16A

16A

Output = 16A Max @ 100-120V

C13

C13

10A

10A

Input = 16A Max @ 100-120V

Outlet Type

Outlet

Amperage

AC to DC

then

DC to AC

5-2020A

5-2020A

5-2020A

5-2020A

Note: Color Indicates Load Grouping

Page 29: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 29 © IBM Corporation 2010

Outlet Diagram – IBM UPS2200 RM 230V

Remote emergency

power-off port

Ground Screw

6 IEC 320 C13

(Load Segment 1)

2 IEC 320 C19

(Load Segment 1)Optional

NMC Bay

USB RS-232

Connector

2 IEC 320 C13

(Load Segment 2)

Optional EBM

Connector

Detachable

Line Cord

Logical Layout – IBM UPS2200 RM 230V

Input Line

C13

C13

10A

10A

C19

C19

16A

16A

Output = 9.6A Max @ 200-240V

C13

C13

10A

10A

Input = 10A Max @ 220-240V

Outlet Type

Outlet

Amperage

AC to DC

then

DC to AC

C1310A

C1310A

C1310A

C1310A

Note: Color Indicates Load Grouping

Run Time – IBM UPS2200 RM – 100/120V

Number of EBM (P/N 46M4108)

% Load (W) Internal

Batteries +1

25% 500 42 143

50% 969 18 66

75% 1450 11 43

100% 1920 7 28

Note: Run times are in minutes

Page 30: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 30 © IBM Corporation 2010

Run Time – IBM UPS2200 RM – 230V

Number of EBM (P/N 46M4108)

% Load (W) Internal

Batteries +1

25% 500 41 138

50% 968 17 64

75% 1450 10 40

100% 1920 7 28

Note: Run times are in minutes

EBM Connections – IBM UPS2200 RM

Page 31: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 31 © IBM Corporation 2010

IBM UPS3000 – Rack Mounted (RM)

IBM UPS3000 Front 53953JX (208V) Back

53953AX (100V, 120V) Back53953KX (230V) Back

IBM UPS3000 EBM Front

UPS3000 100/120V UPS3000 200/208V UPS3000 230V EBM

Part Number 5395-3AX 5395-3JX 5395-3KX 69Y1982

Feature Code 5395-RU3 (FC 6657) 5395-RU3 (FC 6658) 5395-RU3 (FC 6659) 5395-RU3 (FC 5733)

EBMs Supported 1 1 1 -

U Space 3 3 3 3

EPO Connection Yes Yes Yes -

Power Factor 0.9 0.9 0.9 -

UPS Type Line Interactive Line Interactive Line Interactive -

Supported Country or Region

North America, Japan North America, Japan World Wide -

Input 100/120V 200/208V 230V EBM

Line Cord Attached 2.0m, NEMA L5-30P

Detachable NEMA L6-20P

Selectable -

Voltage Range 84-121V for 100V 97-145V for 120V

155-255V for 208V 160V-286V for 230V -

Max Current 24A 16A 16A -

Phase / Frequency 1ph / 50 or 60Hz. 1ph / 50 or 60Hz. 1ph / 50 or 60Hz. -

Surge Energy Rating 1200 joules 2400 joules 2400 joules -

Output 100/120V 200/208V 230V EBM

Watts 2300W @ 100V (Japan)

2700W @ 120V (North America)

2700W 2700W -

Nominal Voltage 100V, 120V (Configurable)

208V (Configurable)

220, 230, or 240V (Configurable)

-

Maximum Amperage 22.5A @ 100V 22.5A @ 120V

13.5A 13.5A

Receptacles 1 x NEMA L5-20R 2 x NEMA 5-20R 2 x IEC 320 C19 2 x IEC 320 C13

2 x NEMA L6-20R 2 x IEC 320 C19 2 x IEC 320 C13

2 x IEC 320 C19 8 x IEC 320 C13

-

Optional Accessories

Network Management Card (NMC) P/N: 46M4110 FC: 6145

Environmental Monitor Probe P/N: 46M4113 FC: 6146

Page 32: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 32 © IBM Corporation 2010

Selectable Line Cords – IBM UPS3000 RM

Line Cord Plug Type Country or Region 40K9766 CEE7-VII Europe 40K9767 BS 1363/A w/13A fuse UK 40K9768 CEI 23-16 Italy 40K9769 IEC 309-P+N+G Dmk/Swiss 40K9770 SABS 164 S Africa 40K9771 SI 32 Israel 40K9772 NEMA L6-20P North America & Japan 40K9773 AS/NZS 3112 Australia/NZ 40K9774 GB 2099.1 China 40K9776 IS 6538 India 40K9777 IRAM 2073 Argentina 59Y2747 CNS 10917 (250V) Taiwan 59Y2749 KSC 8305 Korea 69Y1989 NBR 14136 Brazil 81Y2391 SEV 1011 T23 Switzerland

Page 33: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 33 © IBM Corporation 2010

Outlet Diagram – IBM UPS3000 RM 100/120V

1 NEMA L5-20R

(Load Segment 1)

2 IEC 320 C19

(Load Segment 1)

2 NEMA 5-20R

(Load Segment 1)

2 IEC 320 C13

(Load Segment 2)

USB

RS-232

Connector

Optional EBM

Connector

Remote emergency

power-off port

Ground

Screw

Output Circuit

Breakers

Optional

NMC Bay

Fixed 2.0m

NEMA L5-30P

Line Cord

Logical Layout – IBM UPS3000 RM 100/120V

Input Line

C19

C19

16A

16A

L5-2020A

20A

Output = 22.5A Max @ 100-120V

C1310A

C1310A

20A

Input = 24A Max @ 100-120V

Outlet TypeBreaker

Amperage

Outlet

Amperage

AC to DC

then

DC to AC

5-20

5-20

20A

20A

Note: Color Indicates Load Grouping

Page 34: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 34 © IBM Corporation 2010

Outlet Diagram – IBM UPS3000 RM 200/208V

2 NEMA L6-20R

(Load Segment 1)

RS-232

Connector

Detachable

Line CordGround

Screw 2 IEC 320 C19

(Load Segment 1)

2 IEC 320 C13

(Load Segment 2)Optional EBM

ConnectorUSB

Remote emergency

power-off port

Logical Layout – IBM UPS3000 RM 200/208V

Input Line

C19

C19

16A

16A

L6-20

L6-20

20A

20A

Output = 13.5A @ Max 200-240V

C13

C13

10A

10A

Input = 16A Max @ 200-240V

Outlet Type

Outlet

Amperage

AC to DC

then

DC to AC

Note: Color Indicates Load Grouping

Page 35: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 35 © IBM Corporation 2010

Outlet Diagram – IBM UPS3000 RM 230V

6 IEC 320 C13

(Load Segment 1)

RS-232

Connector

Detachable

Line CordGround

Screw 2 IEC 320 C19

(Load Segment 1)

2 IEC 320 C13

(Load Segment 2)Optional EBM

ConnectorUSB

Remote emergency

power-off port

Logical Layout – IBM UPS3000 RM 230V

Input Line

C13

C13

10A

10A

C19

C19

16A

16A

Output = 13.5A Max @ 200-240V

C13

C13

10A

10A

Input = 16A Max @ 220-240V

Outlet Type

Outlet

Amperage

AC to DC

then

DC to AC

C1310A

C1310A

C1310A

C1310A

Note: Color Indicates Load Grouping

Run Time – IBM UPS3000 RM 100/120V

Number of EBM (P/N 69Y1982)

% Load (W) Internal

Batteries +1

25% 678 42 156

50% 1350 16 62

75% 2060 10 42

100% 2700 7 27

Note: Run times are in minutes

Page 36: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 36 © IBM Corporation 2010

Run Time – IBM UPS3000 RM 200/208V

Number of EBM (P/N 69Y1982)

% Load (W) Internal

Batteries +1

25% 660 41 153

50% 1340 17 68

75% 2040 10 43

100% 2680 6 29

Note: Run times are in minutes

Run Time – IBM UPS3000 RM 230V

Number of EBM (P/N 69Y1982)

% Load (W) Internal

Batteries +1

25% 670 41 156

50% 1350 17 81

75% 2020 10 41

100% 2680 7 27

Note: Run times are in minutes

EBM Connections – IBM UPS3000 RM

Page 37: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 37 © IBM Corporation 2010

IBM UPS5000 – Rack Mounted IBM UPS5000 Front IBM UPS5000 Back

IBM UPS5000 EBM Back

Model UPS5000XHV EBM

Part Number 24195KX 39Y8857

Feature Code Not applicable FC 5743

EBMs Supported 4 -

EPO Connection Yes -

Power Factor 0.9 -

UPS Type Double Conversion -

Input UPS5000XHV EBM

Line Cord Selectable -

Voltage 200-240V -

VA 5000 -

Max Current 30A -

Phase / Frequency 1ph / 50 or 60Hz. -

Output UPS5000XHV EBM

Watts 4500 -

Nominal voltage 200-240V -

Maximum Amperage 22.5A -

Receptacles 8 x IEC320 C13 2 x IEC320 C19

-

Selectable Line Cords – IBM UPS5000

Line Cord Plug Type Country or Region 40K9612 IEC 309 P+N+G International 40K9614 NEMA L6-30P North America 40K9617 AUS/NZ 3112 32A Australia / New Zealand 40K9618 KSC 8305 30A South Korea

Page 38: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 38 © IBM Corporation 2010

Outlet Diagram – IBM UPS5000

Load Segemnt 1

Load Segemnt 2

15A Circuit Breaker

/ Load Segment

Input Connector

Logical Layout – IBM UPS5000

Input Line

C13

C13

10A

10A

C13

C19

10A

16A

15A

Output = 22.5A Max 200-240V

C13

C13

10A

10A

C1916A

15A

Input = 30A 200-240V

Outlet TypeBreaker

Amperage

Outlet

Amperage

AC to DC

then

DC to AC

C1310A

C1310A

C1310A

Page 39: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 39 © IBM Corporation 2010

Run Time – IBM UPS5000

Number of EBM (P/N 39Y8857)

Load (W) +0 +1 +2 +3 +4

50 409 1083 1892 2733 3596

100 290 771 1349 1950 2566

200 180 483 846 1223 1610

300 129 347 610 882 1162

400 99 270 474 686 904

500 80 219 366 559 737

600 67 184 324 470 620

700 57 158 279 405 534

800 50 138 244 355 468

900 44 122 217 315 416

1000 39 110 195 283 374

1200 32 90 161 235 311

1400 26 76 137 200 265

1600 22 66 119 174 230

1800 19 58 105 153 203

2000 17 52 93 137 181

2500 12 40 73 107 142

3000 9 32 60 88 117

3400 7 25 50 72 100

4000 6 23 43 60 85

4500 5 20 38 54 75

Note: Run times are in minutes

EBM Connections – IBM UPS5000

Page 40: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 40 © IBM Corporation 2010

IBM UPS6000 – Rack Mounted New IBM UPS6000 Front 5395-6AX (200/208V) Back

IBM UPS6000 EBM Front5395-6KX (230V) Back

UPS6000 200/208V UPS6000 230V EBM

Part Number 5395-6AX 5395-6KX 69Y1984

Feature Code 5395-RU4 (FC 6660) 5395-RU4 (FC 6661) 5395-RU4 (FC 5734)

EBMs Supported 1 1 -

U Space 4 4 3

EPO Connection Yes Yes -

Power Factor 0.9 0.9 -

UPS Type Line Interactive Line Interactive -

Supported Country or Region

North America, Japan World Wide -

Input 200/208V 230V EBM

Line Cord Hardwired Hardwired -

Voltage Range 155-255V for 200/208V 160V-286V for 230V -

Max Current 30A 32A -

Phase / Frequency 1ph / 50 or 60Hz. 1ph / 50 or 60Hz. -

Surge Energy Rating 1300 joules 1300 joules

Output 200/208V 230V EBM

Watts 5600W 5600W -

Nominal Voltage 208V (Configurable)

220, 230, or 240V (Configurable)

-

Maximum Amperage 28A 28A

Receptacles 2 x NEMA L6-30R 4 x IEC 320 C19

4 x IEC 320 C19 6 x IEC 320 C13

-

Optional Accessories

Network Management Card (NMC) P/N: 46M4110 FC: 6145

Environmental Monitor Probe P/N: 46M4113 FC: 6146

Page 41: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 41 © IBM Corporation 2010

Outlet Diagram – IBM UPS6000 200/208V

4 IEC 320 C19

(Load Segment 1)

2 NEMA L6-30R

(Load Segment 2)

Optional EBM

Connector

Ground

Screw Output Circuit

Breaker (20A)

Input Terminal

Block w/ Cover

Remote emergency

power-off port

USB

RS-232

ConnectorOptional

NMC Bay

Output Circuit

Breaker (30A)

Output Circuit

Breaker (20A)

Logical Layout – IBM UPS6000 200/208V

Input Line

C19

C19

20A

20A

C19

C19

20A

20A

Output = 28A Max @ 200-240V

L6-30

L6-30

30A

30A

Input = 30A Max @ 200-240V

Outlet Type

AC to DC

then

DC to AC

20A

20A

30A

Outlet

Amperage

Breaker

Amperage

Page 42: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 42 © IBM Corporation 2010

Outlet Diagram – IBM UPS6000 230V

6 IEC 320 C13

(Load Segment 2)

4 IEC 320 C19

(Load Segment 1)

Optional EBM

Connector

Ground

Screw

Input Terminal

Block w/ Cover

Remote emergency

power-off port

USB

RS-232

ConnectorOptional

NMC Bay

Output Circuit

Breaker (20A)

Output Circuit

Breaker (15A)

Output Circuit

Breaker (20A)

Logical Layout – IBM UPS6000 230V

Input Line

C19

C19

20A

20A

C19

C19

20A

20A

Output = 28A Max @ 200-240V

C13

C13

10A

10A

Input = 30A Max @ 200-240V

Outlet Type

AC to DC

then

DC to AC

20A

20A

15A

Outlet

Amperage

Breaker

Amperage

C1310A

C1310A

C1310A

C1310A

Page 43: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 43 © IBM Corporation 2010

Run Time – IBM UPS6000

Number of EBM (P/N: 69Y1984 FC: 5734)

% Load (W) Internal

Batteries +1

25% 1400 51 minutes 112 minutes

50% 2800 21 minutes 51 minutes

75% 4200 12 minutes 31 minutes

100% 5600 8 minutes 19 minutes

Note: Run times are in minutes

EBM Connections – IBM UPS6000

Page 44: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 44 © IBM Corporation 2010

Input Connection Block – IBM UPS6000

200V

208V

220V

230V

240V

N L

1 2 3

G

Install a utility circuit breaker according to local electrical codes (see table below) for input wiring.

Wire functions Terminal position

Uninterruptible power supply wire function

Terminal wire size rating

1

Tightening torque

Input

1 Input ground 5.26 - 16 mm

2

(10-6 AWG) 2.49 Nm (22 inch-pounds)

2 L2 / Neutral In

3 L1 In

6000 VA, 200 V / 208 V models only: A 40 A 2-pole circuit breaker to provide short circuit and over current protection.

6000 VA, 230 V models only: A 32 A (for Europe) or 40 A (for North America) 2-pole circuit breaker to provide short circuit and over current protection. (For Europe) The breaker meets the IEC/EN 60934 standard and has a contact air gap of at least 3 mm.

Notes – Wire color code varies depending on location. Check with the local Authority Having Jurisdiction (AHJ) for proper color code. AWG stands for American Wire Gauge

1 Use the following minimum wire size:

10 AWG for equipment grounding wire, 75°C copper wire minimum

8 AWG for input line and neutral wires, 75°C copper wire minimum

Page 45: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 45 © IBM Corporation 2010

IBM UPS7500/10000 – Rack Mounted

UPS7500/10000 Front UPS7500/10000 Back

UPS 10000

Test

TV

SS

GN

D

www.apcc.com

ProbeOutput Zone

1

Pwr2

Reset

NO

+12V

NO

COM

NC

COM

GND

NO

NC

COM

10/100Base-T

10/100

AP9619 Network Management Card EM

TV

SS

GN

D

EBM BackEBM Front

Model UPS7500XHV UPS7500JHV UPS10000XHV UPS10000JHV EBM

Part Number 21303RX 21303JX 21304RX 21304JX 39Y8857

New T-M-F Ordering System

2130RU1-1079 2130RU1-1080 FC 5743

EBMs Supported 4 4 4 4 -

EPO Connection Yes Yes Yes Yes -

Power Factor 0.8 0.8 0.8 0.8 -

UPS Type Double Conversion

Double Conversion

Double Conversion

Double Conversion

-

Input UPS7500XHV UPS7500JHV UPS10000XHV UPS10000JHV EBM

Line Cord Hard Wired Hard Wired Hard Wired Hard Wired -

Voltage 200-240V 1ph1

380-415V 3ph2

200V 1ph1 200-240V 1ph

1

380-415V 3ph2

200V 1ph1 -

VA 7500 7500 10000 10000 -

Max Current 38A 1ph1

14A 3ph2

38A 1ph1 50A 1ph

1

18A 3ph2

50A 1ph1 -

Phase / Frequency 1ph / 50 or 60Hz1

3ph / 50 or 60Hz2

1ph / 60Hz. 1ph / 50 or 60Hz1

3ph / 50 or 60Hz2

1ph / 60Hz. -

Output UPS7500XHV UPS7500XHV UPS10000XHV UPS10000JHV EBM

VA 6000 6000 8000 8000 -

Nominal voltage 200-240V 1ph 200V 1ph 200-240V 1ph 200V 1ph -

Max Current 30A 30A 40A 40A -

Receptacles 4 x IEC320 C19 4 x IEC320 C19 4 x IEC320 C19 4 x IEC320 C19 -

1 – Support in North America and Internationally 2 – Not supported in North America or Japan

Page 46: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 46 © IBM Corporation 2010

Outlet Diagram – IBM UPS7500/10000

TV

SS

GN

D

www.apcc.com

ProbeOutput Zone

1

Pwr2

Reset

NO

+12V

NO

COM

NC

COM

GND

NO

NC

COM

10/100Base-T

10/100

AP9619 Network Management Card EM

Outlets

EBM Connection Block

Input Block & CoverOutlet Circuit Breakers

Logical Layout – IBM UPS7500/10000

Input Line

C1916A

20

UPS7500 Output = 30A Max 200-240V

UPS10000 Output = 40A Max 200-240V

UPS7500 Input = 38A 200-240V

UPS10000 Input = 50A 200-240V

C1916A

20

C1916A

20

C1916A

20

Breaker

Amperage

AC to DC

then

DC to AC

Outlet

Amperage

Outlet Type

Page 47: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 47 © IBM Corporation 2010

Run Time – IBM UPS7500/10000

Number of EBM (P/N 39Y8857)

Load (W) +0 +1 +2 +4 Inter(hour 100 360 655.8 1023.6 1789.8

200 249.6 459 715.8 1254

300 189.6 349.8 546.6 960

400 153 280.8 441 772.8

500 126.6 234.6 367.2 645

600 108 199.8 314.4 552.6

700 93.6 174 273.6 481.8

800 82.8 153.6 243 426.6

900 73.8 138 216.6 382.8

1000 69.6 124.8 196.8 346.8

1200 55 103.8 163.8 291

1400 47 90 141 249.6

1600 41 76.8 123 217.8

1800 36 67.8 108.6 193.8

2000 32 60 96.6 174

2500 24 48 76.8 136.8

3000 19 39 60 112.8

3400 17 34 55 99

4000 13 28 46 81.6

5000 10 21 35 63.6

6000 7 16 28 52

7000 5 13 23 44

8000 4 11 20 37

Recharge Hours

3 7 10 17

Note: Run times are in minutes

Page 48: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 48 © IBM Corporation 2010

EBM Connections – IBM UPS7500/10000

TV

SS

GN

D

www.apcc.com

ProbeOutput Zone

1

Pwr2

Reset

NO

+12V

NO

COM

NC

COM

GND

NO

NC

COM

10/100Base-T

10/100

AP9619 Network Management Card EM

TV

SS

GN

D

TV

SS

GN

D

Page 49: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 49 © IBM Corporation 2010

Input Connection Block – IBM UPS7500/10000

International Connection Only

Single Phase Connection 3 Phase Wye Connection

NL3L2L1

200V

208V

220V

230V

240V

NL3L2L1

3Ө380V

400V

415V

Install a utility circuit breaker according to local electrical codes (see table below) for input wiring.

System Input Voltage Nominal Current Full Load Typical

Breaker Size Typical

Wire Size

UPS7500 220/230/240V 1ph 38A 50A 10mm

2

380/400/415V 3ph Y 14A per ph online, 38A on L1 in bypass 50A 10mm2

UPS10000 220/230/240V 1ph 50A 63A 16mm

2

380/400/415V 3ph Y 18A per ph online, 50A on L1 in bypass 63A 16mm2

North American Connection Only

Single Phase Connection

NL3L2L1

200V

to

240V

Line to Line

200V

208V

220V

230V

240V

When wiring in North America the “N” terminal lug can be treated as a “Hot Line” lug.

Install a utility circuit breaker according to local electrical codes (see table below) for input wiring.

System Input Voltage Nominal Current

Full Load Typical

Breaker Size Typical AWG

UPS7500 200 - 240V 1ph (2P+G)

38A 50A 6

UPS10000 50A 60A 6

Notes – Wire color code varies depending on location. Check with the local Authority Having Jurisdiction (AHJ) for proper color code. AWG stands for American Wire Gauge

Page 50: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 50 © IBM Corporation 2010

Line Cords and Plugs

100-127V NEMA 5-15P (United States) UPS1000/1500TLV

Attached 6ft, 15A/120V, NEMA 5-15 Line Cord

Used with: 2130R3X - IBM UPS1000TLV 2130R5X - IBM UPS1500TLV

Male EndFemale End

100/120V NEMA 5-15P (North America & Japan) UPS1500 RM & Tower

Detachable 4.3m, 15A/100-120V, C13 to NEMA 5-15P Line Cord

Used with: 5396-1AX – UPS1000 Tower 120V (Line cord comes with UPS) 5396-1JX – UPS1000 Tower 100V (Line cord comes with UPS) 5396-2AX – UPS1500 Tower 120V (Line cord comes with UPS) 53951AX – UPS1500 RM 100/120V (Line cord comes with UPS)

Male EndFemale End

100/120V NEMA 5-20P (North America & Japan) UPS2200 RM

Detachable 4.3m, 20A/100-120V, NEMA 5-20P Line Cord

Used with: 5396-2JX – UPS1500 Tower 100V (Line cord comes with UPS) 53952AX – UPS2200 RM 100/120V (Line cord comes with UPS)

Male EndFemale End

Page 51: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 51 © IBM Corporation 2010

100/120V NEMA L5-30P (North America & Japan) UPS3000 RM

Attached 4.3m, 30A/100-120V, NEMA L5-30P Line Cord

Used with: 53953AX – UPS3000 RM 100/120V (Line cord comes with UPS)

120V

G

EQUIP.

GR.G

W

NEMA L5-30

W

SYS.

GR.

200/208V NEMA L6-20P (North America & Japan) UPS3000 RM

Detachable (P/N: 40K9772) 4.3m, 20A/200-240V, NEMA L6-20P Line Cord

Used with: 53953JX – UPS3000 RM 200/208V (Line cord comes with UPS) 53953KX – UPS3000 RM 230V (Line cord ordered separately)

208V

G

EQUIP.

GR.G

Y

X

NEMA L6-20

120V

120V

Page 52: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 52 © IBM Corporation 2010

CEE7-VII (Europe)

P/N: 39Y7917 2.8m, 10A/230V, C13 to CEE7-VII (Europe) Line Cord P/N: 81Y2376 4.3m, 10A/230V, C13 to CEE7-VII (Europe) Line Cord

Used with: 5396-1KX – UPS1000 Tower 230V 53951KX – UPS1500 RM 230V 2130R4X – UPS1000THV 5396-2KX – UPS1500 Tower 230V 53952KX – UPS2200 RM 230V 2130R6X – UPS1500THV

P/N: 40K9766 4.3m, 16A/230V, C19 to CEE7-VII (Europe) Line Cord

Used with: 53953KX – UPS3000 RM 230V

Male EndFemale End

DK2-5a (Denmark)

P/N: 39Y7918 2.8m, 10A/230V, C13 to DK2-5a (Denmark) Line Cord P/N: 81Y2382 4.3m, 10A/230V, C13 to DK2-5a (Denmark) Line Cord

Used with: 5396-1KX – UPS1000 Tower 230V 53951KX – UPS1500 RM 230V 2130R4X – UPS1000THV 5396-2KX – UPS1500 Tower 230V 53952KX – UPS2200 RM 230V 2130R6X – UPS1500THV

Male EndFemale End

SEV 1011-S24507 (Switzerland)

P/N: 39Y7919 2.8m, 10A/230V, C13 to SEV 1011-S24507 (Switzerland) Line Cord P/N: 81Y2390 4.3m, 10A/230V, C13 to SEV 1011-S24507 (Switzerland) Line Cord

Used with: 5396-1KX – UPS1000 Tower 230V 53951KX – UPS1500 RM 230V 2130R4X – UPS1000THV 5396-2KX – UPS1500 Tower 230V 53952KX – UPS2200 RM 230V 2130R6X – UPS1500THV

Male EndFemale End

Page 53: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 53 © IBM Corporation 2010

SI 32 (Israel)

P/N: 39Y7920 2.8m, 10A/230V, C13 to SI 32 (Israel) Line Cord P/N: 81Y2381 4.3m, 10A/230V, C13 to SI 32 (Israel) Line Cord

Used with: 5396-1KX – UPS1000 Tower 230V 53951KX – UPS1500 RM 230V 2130R4X – UPS1000THV 5396-2KX – UPS1500 Tower 230V 53952KX – UPS2200 RM 230V 2130R6X – UPS1500THV

P/N: 40K9771 4.3m, 16A/230V, C19 to SI 32 (Israel) Line Cord

Used with: 53953KX – UPS3000 RM 230V

Male EndFemale End

CEI 23-16 (Italy)

P/N: 39Y7921 2.8m, 10A/230V, C13 to CEI 23-16 (Italy) Line Cord P/N: 81Y2380 4.3m, 10A/230V, C13 to CEI 23-16 (Italy) Line Cord

Used with: 5396-1KX – UPS1000 Tower 230V 53951KX – UPS1500 RM 230V 2130R4X – UPS1000THV 5396-2KX – UPS1500 Tower 230V 53952KX – UPS2200 RM 230V 2130R6X – UPS1500THV

P/N: 40K9768 4.3m, 16A/230V, C19 to CEI 23-16 (Italy) Line Cord

Used with: 53953KX – UPS3000 RM 230V

Male EndFemale End

Page 54: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 54 © IBM Corporation 2010

SABS 164 (South Africa)

P/N: 39Y7922 2.8m, 10A/230V, C13 to SABS 164 (South Africa) Line Cord P/N: 81Y2379 4.3m, 10A/230V, C13 to SABS 164 (South Africa) Line Cord

Used with: 5396-1KX – UPS1000 Tower 230V 53951KX – UPS1500 RM 230V 2130R4X – UPS1000THV 5396-2KX – UPS1500 Tower 230V 53952KX – UPS2200 RM 230V 2130R6X – UPS1500THV

P/N: 40K9770 4.3m, 16A/230V, C19 to SABS 164 (South Africa) Line Cord

Used with: 53953KX – UPS3000 RM 230V

Male EndFemale End

BS 1363/A (UK)

P/N: 39Y7923 2.8m, 10A/230V, C13 to BS 1363/A (UK) Line Cord P/N: 81Y2377 4.3m, 10A/230V, C13 to BS 1363/A (UK) Line Cord

Used with: 5396-1KX – UPS1000 Tower 230V 53951KX – UPS1500 RM 230V 2130R4X – UPS1000THV 5396-2KX – UPS1500 Tower 230V 53952KX – UPS2200 RM 230V 2130R6X – UPS1500THV

P/N: 40K9767 4.3m, 13A/230V, C19 to BS 1363/A w/13A fuse (UK) Line Cord

Used with: 53953KX – UPS3000 RM 230V

Male EndFemale End

Page 55: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 55 © IBM Corporation 2010

AS/NZS 3112 (Aus/NZ)

P/N: 39Y7924 2.8m, 10A/230V, C13 to AS/NZS 3112 (Aus/NZ) Line Cord P/N: 81Y2383 4.3m, 10A/230V, C13 to AS/NZS 3112 (Aus/NZ) Line Cord

Used with: 5396-1KX – UPS1000 Tower 230V 53951KX – UPS1500 RM 230V 2130R4X – UPS1000THV 5396-2KX – UPS1500 Tower 230V 53952KX – UPS2200 RM 230V 2130R6X – UPS1500THV

P/N: 40K9773 4.3m, 15A/230V, C19 to AS/NZS 3112 (Aus/NZ) Line Cord

Used with: 53953KX – UPS3000 RM 230V

Male EndFemale End

KSC 8305 (S. Korea)

P/N: 39Y7925 2.8m, 10A/220V, C13 to KSC 8305 (S. Korea) Line Cord P/N: 81Y2385 4.3m, 10A/220V, C13 to KSC 8305 (S. Korea) Line Cord

Used with: 5396-1KX – UPS1000 Tower 230V 53951KX – UPS1500 RM 230V 2130R4X – UPS1000THV 5396-2KX – UPS1500 Tower 230V 53952KX – UPS2200 RM 230V 2130R6X – UPS1500THV

P/N: 59Y2749 4.3m, 16A/220V, C19 to KSC 8305 (S. Korea) Line Cord

Used with: 53953KX – UPS3000 RM 230V

Male EndFemale End

Page 56: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 56 © IBM Corporation 2010

IS6538 (India)

P/N: 39Y7927 2.8m, 10A/240V, C13 to IS6538 (India) Line Cord P/N: 81Y2386 4.3m, 10A/240V, C13 to IS6538 (India) Line Cord

Used with: 5396-1KX – UPS1000 Tower 230V 53951KX – UPS1500 RM 230V 2130R4X – UPS1000THV 5396-2KX – UPS1500 Tower 230V 53952KX – UPS2200 RM 230V 2130R6X – UPS1500THV

P/N: 40K9776 4.3m, 16A/240V, C19 to IS6538 (India) Line Cord

Used with: 53953KX – UPS3000 RM 230V

Male EndFemale End

GB 2099.1 (China)

P/N: 39Y7928 2.8m, 10A/220V, C13 to GB 2099.1 (China) Line Cord P/N: 81Y2378 4.3m, 10A/220V, C13 to GB 2099.1 (China) Line Cord

Used with: 5396-1KX – UPS1000 Tower 230V 53951KX – UPS1500 RM 230V 2130R4X – UPS1000THV 5396-2KX – UPS1500 Tower 230V 53952KX – UPS2200 RM 230V 2130R6X – UPS1500THV

P/N: 40K9774 4.3m, 16A/220V, C19 to GB 2099.1 (China) Line Cord

Used with: 53953KX – UPS3000 RM 230V

Male EndFemale End

Page 57: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 57 © IBM Corporation 2010

NBR 6147 (Brazil)

P/N: 39Y7929 2.8m, 10A/125V, C13 to NBR 6147 (Brazil) Line Cord P/N: 81Y2387 4.3m, 10A/125V, C13 to NBR 6147 (Brazil) Line Cord

Used with: 5396-1KX – UPS1000 Tower 230V 53951KX – UPS1500 RM 230V 2130R4X – UPS1000THV 5396-2KX – UPS1500 Tower 230V 53952KX – UPS2200 RM 230V 2130R6X – UPS1500THV

Male EndFemale End

IRAM 2073 (Argentina)

P/N: 39Y7930 2.8m, 10A/220V, C13 to IRAM 2073 (Argentina) Line Cord P/N: 81Y2384 4.3m, 10A/220V, C13 to IRAM 2073 (Argentina) Line Cord

Used with: 5396-1KX – UPS1000 Tower 230V 53951KX – UPS1500 RM 230V 2130R4X – UPS1000THV 5396-2KX – UPS1500 Tower 230V 53952KX – UPS2200 RM 230V 2130R6X – UPS1500THV

P/N: 40K9777 4.3m, 16A/220V, C19 to IRAM 2073 (Argentina) Line Cord

Used with: 53953KX – UPS3000 RM 230V

Male EndFemale End

N L

G

NL

G

IEC 309 P+N+G (Denmark/Switzerland)

P/N: 40K9769 4.3m, 16A/230V, C19 to Denmark IEC 309 P+N+G (Denmark/Switzerland) Line Cord

Used with: 53953KX – UPS3000 RM 230V

Male SleeveFemale Sleeve

G

NL

G

N L

Page 58: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 58 © IBM Corporation 2010

NBR 14136 (Brazil)

P/N: 69Y1989 4.3m, 16A/220-240V, C19 to NBR 14136 (Brazil) Line Cord

Used with: 53953KX – UPS3000 RM 230V

Male EndFemale End

SEV 1011 T23 (Switzerland)

P/N: 81Y2391 4.3m, 16A/230V, C19 to SEV 1011 T23 (Switzerland) Line Cord

Used with: 53953KX – UPS3000 RM 230V

Male EndFemale End

CNS 10917 – 125V (Taiwan)

P/N: 81Y2374 2.8m, 10A/125V, C13 to CNS 10917 – 125V Line Cord P/N: 81Y2388 4.3m, 10A/125V, C13 to CNS 10917 – 125V Line Cord

Used with: 5396-1AX – UPS1000 Tower 120V 53951AX – UPS1500 RM 100/120V 5396-2AX – UPS1500 Tower 120V

P/N: 59Y2746 4.3m, 16A/125V, C19 to CNS 10917 – 125V Line Cord

Used with: 53952AX – UPS2200 RM 100/120V

Male EndFemale End

Page 59: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 59 © IBM Corporation 2010

CNS 10917 – 250V (Taiwan)

P/N: 81Y2375 2.8m, 10A/250V, C13 to CNS 10917 – 250V Line Cord P/N: 81Y2389 4.3m, 10A/250V, C13 to CNS 10917 – 250V Line Cord

Used with: 5396-1KX – UPS1000 Tower 230V 53951KX – UPS1500 RM 230V 5396-2KX – UPS1500 Tower 230V 53952KX – UPS2200 RM 230V

P/N: 59Y2747 4.3m, 15A/250V, C19 to CNS 10917 – 250V Line Cord

Used with: 53953KX – UPS3000 RM 230V

Male End

40K9612 - IBM DPI 32A Cord (IEC 309 P+N+G)

IEC 309 P+N+G (2.5m) - 32A / 220-240V Single Phase Matching receptacle listing 332R6W IP-67 HUBBELL. Hubbell receptacle P/N HBL332R6W.

Used with: 24195KX – UPS5000XHV

Male PinFemale Sleeve

G

NL

G

N LG

EQUIP.

GR.

N

L

220- 240V220- 240V

40K9614 - IBM DPI 30A Cord (NEMA L6-30P)

NEMA L6-30P (2.5m) 30A (24A Derated) @ 200V-240V Single Phase.

Used with: 24195KX – UPS5000XHV

200-240V

G

EQUIP.

GR. GY

X

NEMA L6-30

100-120V

100-120V

Page 60: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 60 © IBM Corporation 2010

40K9617 – IBM DPI 32A Cord (AUS/NZ 3112 32A)

P+N+G (PDL P/N 56P332) Australia/New Zealand connector

Used with: 24195KX – UPS5000XHV

Male PinFemale Sleeve

N L

G

L N

G G

EQUIP.

GR.

N

L

230V 230V

40K9618 – IBM DPI 30A Cord (KSC 8305 30A)

P+N+G (Shin Ju P/N SJ-P3302) Korea connector

Used with: 24195KX – UPS5000XHV

Male EndFemale End

NL

G

N L

G

220V

G

EQUIP.

GR.

N

L

220V

Page 61: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 61 © IBM Corporation 2010

Reference Material

IBM BladeCenter Chassis Label Rating

Chassis Power Supply Wattage

Power Supplies Standard

Power Supplies Max

100-127V Rating

200-240V Rating

BC E 2000W 2 4 - 12A / Supply

BC E 2320W 2 4 - 13.8A / Supply

BC H 2900W 2 4 - 37A / Connector *

BC HT 3160W 2 4 - 16A / Supply

BC T 1300W 2 4 - 7.5A / Supply

BC S 950W / 1450W ** 2 4 11.2A / Supply 8A / Supply

* - 37A per power connector (16A, 16A, 5A) redundant, 24A per power connector non-redundant ** - 950W is at 100-127V and 1450W is at 200-240V

IBM Storage Label Rating

Storage Device

100-127V Rating / Server

200-240V Rating / Server

DS300 5.58A 2.79A

DS3200 3.9A 1.95A

DS3300 3.9A 1.95A

DS3400 3.9A 1.95A

DS3500 3.9A 2.06A

DS400 5.58A 2.79A

DS4100 3.01A 1.57A

DS4200 4.54A 2.27A

DS4300 (FAStT 600) 3.7A 1.85A

DS4700 Express Model 4.54A 2.27A

DS4800 4.54A 2.27A

EXP100 (FAStT EXP100) 3.5A 1.75A

EXP420 4.54A 2.27A

EXP500 3.9A 1.95A

EXP700 3.9A 1.95A

EXP710 3.9A 1.95A

EXP810 4.54A 2.27A

EXP3000 3.9A 1.95A

FAStT 200 3.5A 1.75A

Page 62: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 62 © IBM Corporation 2010

IBM System x Server Label Rating

Server

Power Supply

Wattage

Power Supplies Standard

Power Supplies

Max 100-127V Rating /

Server 200-240V

Rating / Server

Redundant @

100-127V

x3100 (4348) 310W 1 1 4.5A 2.25A -

x3100 M3 (4253) 350W 1 1 4.9A 2.4A -

x3105 (4347) 310W 1 1 4.5A 2.25A -

x3200 (4362, 4363) 400W 1 1 5.5A 2.75A -

x3200 (4362, 4363) 430W 1 2 5.5A 2.75A Yes

x3200 M2 (4367, 4368) 401W 1 1 5.5A 2.75A -

x3200 M2 (4367, 4368) 430W 1 2 5.5A 2.75A Yes

x3200 M2 (9234) 400W 1 1 5.5A 2.75A -

x3200 M2 (9234) 430W 1 2 5.5A 2.75A Yes

x3200 M3 (7327, 7328) 401W 1 1 5.5A 2.75A -

x3200 M3 (7327, 7328) 430W 1 2 5.5A 2.75A Yes

x3250 (4364, 4365) 350W 1 1 6A 3A -

x3250 M2 (4190, 4194) 351W 1 1 4.5A 2.25A -

x3250 M3 (4251, 4252) 351W 1 1 4.5A 2.25A -

x3350 (4192, 4193) 450W 1 2 4.1A 2A Yes

x3400 (7973, 7974) 670W 1 1 5A 2.5A -

x3400 (7975, 7976) 835W 1 2 6.5A 3.25A Yes

x3400 M2 (7836, 7837) 670W 1 1 10A 5A -

x3400 M2 (7836, 7837) 920W 1 2 10A 5A Yes

x3400 M3 (7378, 7379) 670W 1 1 10A 5A -

x3400 M3 (7378, 7379 920W 1 2 10A 5A Yes

x3450 (7948) 600W 1 1 7A 3.5A -

x3455 (7984) 650W 1 1 6.1A 3.0A -

x3455 (7940, 7941) 650W 1 1 6.1A 3.0A -

x3500 (7977) 835W 1 2 6.5A 3.25A Yes

x3500 M2 (7839) 670W 1 2 10A 5A -

x3500 M2 (7839) 920W 1 2 10A 5A Yes

x3500 M3 (7380) 670W 1 2 10A 5A -

x3500 M3 (7380) 920W 1 2 10A 5A Yes

x3550 (7879) 670W 1 2 7A 3.5A Yes

x3550 M2 (7946) 675W 1 2 7.8A 3.8A Yes

x3550 M3 (7944) 675W 1 2 7.8A 3.8A Yes

x3650 (7979) 835W 1 2 9.7A 4.85A Yes

x3650 T (7980) 600W 2 2 6A 3A Yes

x3650 M2 (7838) 675W 1 2 7.8A 3.8A Yes

x3650 M2 (7947) 675W 1 2 7.8A 3.8A Yes

x3650 M3 (7945) 675W 1 2 7.8A 3.8A Yes

x3655 (7985) 835W 1 2 9.7A 4.85A Yes

x3690 X5 (7148) 675W 1 1 7.8A 3.7A -

x3690 X5 (7148) 675W 2 4 15.5A per server

7.8A per plug 7.4A per server 3.7A per plug

Yes

x3755 (8877, 7163) 1500W 1 2 17.6A 8.8A No

x3800 (8866) 775W 2 3 18.4A 9.2A Yes

x3850 (8863, 8864) 1300W 1 2 15.75A 7.875A No

x3850/3950 M2 (7141) 1440W 1 2 17.2A 8A No

x3850/3950 M2 (7233) 1440W 1 2 17.2A 8A No

x3850 X5 (7145) 1975W 2 2 20A 10A No

x3950 (8872, 8878) 1300W 2 2 15.75A 7.875A No

Page 63: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 63 © IBM Corporation 2010

IBM iDataPlex Chassis Label Rating

Chassis Slot

Configuration

Power Supply Wattage

Power Supplies Standard

Power Supplies

Max Chassis Rating

2U Flex Chassis (7831, 6385)

2 Planars 900W High Efficiency

1 1

100V – 8.62A 110V – 7.71A 115V – 7.35A 120V – 7.00A 127V – 6.63A 200V – 4.19A 208V – 3.98A 220V – 3.81A 230V – 3.61A 240V – 3.46A

2U Flex Chassis (7831, 6385)

1 Planar with I/O Tray

900W High Efficiency

1 1

100V – 5.90A 110V – 5.28A 115V – 5.01A 120V – 4.83A 127V – 4.61A 200V – 2.93A 208V – 2.83A 220V – 2.68A 230V – 2.57A 240V – 2.47A

2U Flex Chassis (7381, 6385)

1 Planar with Storage Tray

900W High Efficiency

1 1

100V – 5.54A 110V – 4.89 A 115V – 4.67A 120V – 4.44A 127V – 4.20A 200V – 2.67A 208V – 2.56A 220V – 2.43A 230V – 2.33A 240V – 2.24A

3U Storage Chassis (7834, 6386)

900W High Efficiency

1 1

100V – 7.61A 110V – 6.90A 115V – 6.52A 120V – 6.28A 127V – 5.90A 200V – 3.73A 208V – 3.59A 220V – 3.37A 230V – 3.24A 240V – 3.13A

Page 64: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 64 © IBM Corporation 2010

Chassis Slot Configuration

Power Supply Wattage

Power Supplies Standard

Power Supplies Max

Chassis Rating

2U Flex Chassis (7831, 6385)

2 Planars Dual 750W Power Supply

2 2

200V – 3.90A 208V – 3.80A 220V – 3.53A 230V – 3.38A 240V – 3.22A

2U Flex Chassis (7831, 6385)

1 Planar with I/O Tray

Dual 750W Power Supply

2 2

200V – 2.37A 208V – 2.27A 220V – 2.15A 230V – 2.05A 240V – 1.97A

2U Flex Chassis (7381, 6385)

1 Planar with Storage Tray

Dual 750W Power Supply

2 2

200V – 2.43A 208V – 2.32A 220V – 2.19A 230V – 2.11A 240V – 1.99A

3U Storage Chassis (7834, 6386)

Dual 750W Power Supply

2 2

200V – 2.89A 208V – 2.76A 220V – 2.61A 230V – 2.51A 240V – 2.39A

IBM xSeries Server Label Rating

Server

Power Supply

Wattage

Power Supplies Standard

Power Supplies

Max

100-127V Rating / Server

200-240V Rating / Server

Redundant @ 100-127V

x100 310W 1 1 4.5A 2.25A -

x206 400W 1 1 5.5A 2.75A -

x206 430W 1 2 5.5A 2.75A Yes

x226 530W 1 1 7A 3.5A -

x226 514W 1 2 7A 3.5A Yes

x236 670W 1 2 8.93A 4.465A Yes

x255 370W 2 4 10A 5A Yes

x260 775W 2 3 18.4 9.2A No

x306 350W 1 1 4.3A 2.15A -

x335 332W 1 1 4A 2A -

x335 411W 1 1 3.5A 1.75A -

x336 585W 1 2 5.5A 2.75A Yes

x346 625W 1 2 8.3A 4.15A Yes

x366 1300W 1 2 15.75A 7.875A No

x445 1200W 2 2 9.5A 4.75A No

x445 16-way 1200W 4 4 19A 9.5A No

x460 1300W 2 2 15.75A 7.875A No

Page 65: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 65 © IBM Corporation 2010

Some Background on Power Factor and UPS Sizing

UPS systems typically have two ratings, KVA and Watts. In the past, there has been some confusion over how these numbers should be used for planning purposes. This guide will explain the difference between the two and how each is used in the planning process. To establish the basis of terminology used in this guide, here are some brief definitions.

Apparent Power (S) – The product of voltage and current in AC circuits. Apparent power includes capacitive or inductive elements and has units of Volt-Ampere or VA.

Real Power (P) – Energy delivered to do useful work (like powering a server). Real power does not include capacitive or inductive elements

Reactive Power (Q) – The peak power in a reactive load. Reactive power is the imaginary part of apparent power and has units of var.

Power Factor (pf) – The ratio between real and apparent power. Power factor ranges between zero and one and is unit less. Power factor can be leading (capacitive) or lagging (inductive).

The relationship between all of these is best understood graphically.

j im S

Re S

q

P

|S|

jQ

The x axis is the real part of the apparent power and the y axis represents the imaginary part of S. The apparent power by definition is the vector sum of the real and reactive power. Translating this to terms that most are familiar with, think of a freshly poured glass of beer. When the glass is full it is considered collectively as a beer and is equivalent to apparent power S. This collective beer is made up of liquid beer (real power P) and foam (reactive power Q). The liquid beer (real power P) is what is desired, but you must pay for the foam (reactive power Q) as well. The better the bartender (power supply vendor) the more liquid beer (real power P) and less foam (reactive power Q) you get. Back to the math, we introduce the concept of power factor. Power factor is a dimensionless number between 0 and 1 and can be calculated through the following relationship.

pf =Real Power

Apparent Power=

P

S

Power factor, more importantly power factor correction, is important because loads with low power factor require higher current than loads with a power factor closer to 1. When planning circuits, PDUs, and UPS systems, a higher power factor is desired to minimize the current draw on the infrastructure and maximize power distribution efficiency. Getting into a little more detail, pf=1 means that all energy supplied in the circuit is consumed by the load, which is purely resistive. As the power factor decreases (pf<1) the circuit is said to have become more reactive. A reactive circuit stores energy in the load for part of the AC cycle which is then returned to the source later in the cycle. At the opposite end, pf=0 means that the energy supplied at one point in the cycle is stored in the load and returned to the source at another point in the cycle. Today’s IT equipment, for the most part, employs some type of power factor correction. This means that the switching power supply units in the IT equipment are designed to appear as resistive devices to the electrical

Page 66: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 66 © IBM Corporation 2010

infrastructure with a power factor (pf) of approximately one (pf=1). In reality, the power factor changes with the load on the IT equipment, but under nominal conditions of today’s modern IT equipment, the power factor is in the range of 0.96 to 0.99. When a UPS is rated, two numbers are typically given, KVA and Watts. The KVA and Watts represent the input apparent and real power respectively. Looking at the quotient of the input ratings gives the designed input power factor. The output of a UPS is restricted to the current limitation of the outlets of the UPS. This limitation can be defined as individual outlet limitations and/or group limitations. The total outlet current limitation of the UPS will be such that the capacity of the UPS will not be exceeded. Using the tables that accompany each UPS in this guide, one is able to calculate run time by knowing the approximate real-load and number of external battery module(s) (if applicable).

Page 67: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 67 © IBM Corporation 2010

IEC 309 Pin & Sleeve Plug Decode

G

L1

L2

L3

G

L1

L2

L3

4

Pin Configuration Amperage

60 R

Device Type Polarization Environmental Rating

3 - 2 Pole + G

4 - 3 Pole + G

5 – 3 Pole + N + G

20 30 32

60 63 100

P - Plug

C - Connector

R - Receptacle

B - Inlet

Clock

Position

Of Female

Sleeve

W-WATERTIGHT

(SCREW CAP &

LOCKING RING)

9 W

· Example

o IEC309 3P+G Plug

o 60amp/250V three-phase

o Hubbell Connector listing

460C9W IP-67

o P/N HBL460C9W

Male PinFemale Sleeve

Color

Yellow

Orange

Blue

Gray

Red

Black

Voltage Rating

100V - 130V

125V/250V

200V - 250V

277V

380V - 480V

500V - 690V

Pin Configuration Significance

3 Pins = 1ph

4 Pins = 3ph Δ

5 Pins = 3ph Y

Ingress Protection (IP) Decode

Code Letters

0 – No Protection

1 – Vertically Dripping

2 – Dripping At 15° Of Tilt

3 – Spraying Up To 60° Of Tilt

4 – Splashing

5 – Jetting

6 – Power Jetting

7 – Temporary Immersion

8 – Continuous Immersion

0 – No Protection

1 ≥ 50mm Diameter

2 ≥ 12.5mm Diameter

3 ≥ 2.5mm Diameter

4 ≥ 1.0mm Diameter

5 – Dust-Protected

6 – Dust-Tight

IP

First Number: degree of protection

for persons against access of

hazardous parts inside the enclosure

and/or against foreign objects.

Second Number: degree of

protection of equipment inside

enclosures against damage from

ingress of water.

First Number Second Number

Example: IP67 = Ingress Protection / Dust-Tight / Temporary Immersion

Ingress Protection (IP ) is defined in IEC 60529 Standard.

Ingress ProtectionProtection Against Ingress

of Solid Foreign Objects

Protection Against Ingress of

Water with Harmful Effects

Page 68: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 68 © IBM Corporation 2010

IEC 320 Connectors

Name Connector AMP Rating Use

C5 – Female C6 – Male

2.5A Laptop Power Supplies And Other Portable Power

Supplies

C7 – Female C8 – Male 2.5A

Laptop Power Supplies And Other Portable Power Supplies

C13 – Female C14 – Male

10A Desktop Computers, Monitors, Switches, And Servers

C15 – Female C16 – Male

10A

Used In Hot Conditions Since It Is Rated To 120

0 C

(2480F), Unlike C13/C14 Which Is Rated To 70

0 C (158

0 F)

C19 – Female C20 – Male

16A Blade Chassis, High-power Servers, UPSs, PDUs, And

Other High Current Equipment

Note: IEC 320 has changed to IEC 60320

60A Three Phase Delta Power Calculations

ICB

IAC IBA208V

208V

208V

IA

IC

IB

ELL = EAC = EBA = ECB = 208V

IL = 60A

PTotal =

= 21616W

=

IF = IAC = IBA = ICB =IL√3

=60

= 34.64A

34.64IDerated = IF x 0.8 = x 0.8 = 27.7A

=PDerated PTotal x 0.8

= 21616W x 0.8

17293W=

√3 x ELL x IL x pf

√3 x 208 x 60 x 1

√3

B

C

A

Variables Defined

Phase Current=IF

Line Current=ILLine to Line Voltage=ELL

Power Factor=pf

Power In Watts=P

Page 69: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 69 © IBM Corporation 2010

32A Three Phase Wye Power Calculations

IA

IB

IC

EL=380V

n

IA = IB = IC = IL = IF = 32A

PF = EFY x IFY x p.f. (W)

EF=220V

EL=380V

EL=380V

IF

EAn = EBn = ECn = EF

A

B

C

For all three phases,

PTOTAL = 3 x PF

= 3 x EL/√3 x IF x p.f.

= √3 x EL x IL x p.f.

= √3 x 380V x 32A x 1

= 21062 W

=EL

√3=

380

√3= 220V

Page 70: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 70 © IBM Corporation 2010

UPS Installation Manual Links

IBM UPS1000 & UPS1500 Tower – New

Base Unit ftp://ftp.software.ibm.com/systems/support/system_x_pdf/60y1421.pdf

IBM UPS1000 & UPS1500 Tower – OLD Base Unit

http://www-947.ibm.com/systems/support/supportsite.wss/docdisplay?lndocid=MIGR-52976&brandind=5000019

IBM UPS5000 Base Unit & EBM

http://www-947.ibm.com/systems/support/supportsite.wss/docdisplay?lndocid=MIGR-5082280&brandind=5000008

IBM UPS6000 – New

Base Unit & EBM

http://www-947.ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-5085548&brandind=5000008

IBM UPS7500 & UPS10000 Base Unit

http://www-947.ibm.com/systems/support/supportsite.wss/docdisplay?lndocid=MIGR-58641&brandind=5000019

EBM

http://www-947.ibm.com/systems/support/supportsite.wss/docdisplay?lndocid=MIGR-58642&brandind=5000019

Page 71: IBM System x UPS Guide v1.4.0

A Guide To IBM System x Uninterruptable Power Supply (UPS)

P a g e | 71 © IBM Corporation 2010

Helpful Links

IBM’s System x UPS Web Site (this document)

http://www-03.ibm.com/systems/x/hardware/options/ups.html IBM System x PDU Guide – North American

http://www-03.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP101526 IBM System x PDU Guide – International

http://www-03.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP101615 IBM System x PDU Guide – North American

http://www-03.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP101526 IBM System x and BladeCenter Power Configurator

http://www-03.ibm.com/systems/bladecenter/resources/powerconfig.html IBM’s System x UPS Web Site

http://www-03.ibm.com/systems/x/hardware/options/ups.html Hubbell - Twist Lock Plug/Outlet Catalog (Includes NEMA Outlets)

http://www.hubbellcatalog.com/wiring/catalogpages/section-b.pdf Hubbell - Pin & Sleeve Plug/Outlet Catalog (Includes IEC309 Outlets)

http://www.hubbellcatalog.com/wiring/catalogpages/section-E.pdf Configuration and Options Guide (COG) - Servers and IntelliStation

®

http://www-947.ibm.com/support/entry/portal/docdisplay?brand=5000008&lndocid=SCOD-3ZVQ5W IBM BladeCenter and System x Reference Sheets

http://www.redbooks.ibm.com/Redbooks.nsf/pages/xref?Open Official IBM Visio Stencils

http://www.visiocafe.com/ibm.htm IBM, the IBM Logo, BladeCenter, iDataPlex, DPI, IntelliStation and System x are registered trademarks or trademarks of International Business Machines Corporation in the United States, other countries or both. Other company, product or service names may be trademarks or service marks of others.