INSTALLATION MANUAL Part Number: 9001-0024 Rev K Copyright © 2007 All Rights Reserved Published in U.S.A. GFPS-9 SUPPLEMENTARY NOTIFICATION APPLIANCE CIRCUIT MODULE 12 Clintonville Road Northford, CT 06472-1653 USA TEL: (203) 484-7161
50
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Gamewell Gfps9 Manual

INSTALLATION MANUAL

Part Number: 9001-0024Rev K

Copyright © 2007All Rights ReservedPublished in U.S.A.

GFPS-9SUPPLEMENTARY NOTIFICATION

APPLIANCE CIRCUIT MODULE

12 Clintonville Road Northford, CT 06472-1653 USA TEL: (203) 484-7161

Page 2: Gamewell Gfps9 Manual
Page 3: Gamewell Gfps9 Manual

9001-0024 i

Contents

Section 1Introduction ..................................................................................................................................................1

Section 2UL Requirements ..................................................................................................................................2

Section 3System Overview ..................................................................................................................................3

3.1 Terminal Descriptions and Electrical Ratings .............................................................................................33.2 Signal Input Terminals .................................................................................................................................43.3 Notification Appliance Circuit Terminals ....................................................................................................5

Section 4Installation .....................................................................................................................................................6

4.1 Mounting ......................................................................................................................................................64.1.1 Preventing Water Damage ....................................................................................................................6

4.2 Wire Routing ................................................................................................................................................74.3 Current Requirements (Standby and Alarm) ...............................................................................................8

4.3.1 Current Drawn From Host Panel ..........................................................................................................84.3.2 Current Drawn from Battery .................................................................................................................8

4.4 Connecting the GFPS-6 to a Control Panel ...............................................................................................104.4.1 Common Trouble Relay ......................................................................................................................11

4.5 Notification Appliance Wiring ...................................................................................................................114.5.1 Class A Supervised Wiring .................................................................................................................11

Class A Output Notification Circuits ..............................................................................................11Class A Supervised Input Circuits ..................................................................................................12

4.5.2 Class B Supervised Wiring .................................................................................................................12Class B Output Notification Circuits ..............................................................................................12Class B Supervised Input Circuits ...................................................................................................13

4.6 Ground Fault Detection Enable/Disable Jumper .......................................................................................134.7 Battery Connection ....................................................................................................................................144.8 DIP Switch Settings ...................................................................................................................................14

4.8.1 Selecting the Standard Input/Output Configurations ..........................................................................154.8.1.1 Input/Output Configurations That Select ANSI Temporal-Coded Outputs .............................16

4.8.2 Selecting Synchronized Output Configurations .................................................................................174.8.2.1 Selecting Synchronized Faraday Configurations .....................................................................174.8.2.2 Selecting Synchronized Gentex Configurations ......................................................................174.8.2.3 Selecting Synchronized System Sensor Configurations ..........................................................184.8.2.4 Selecting Synchronized Wheelock Configurations ..................................................................184.8.2.5 Selecting Synchronized AMSECO Configurations .................................................................18

4.8.3 Setting the Loss of AC Delay .............................................................................................................194.8.4 Setting the Auxiliary Output ...............................................................................................................19

Page 4: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

ii 9001-0024

Section 5Sample Applications ......................................................................................................................20

5.1 Notification Power Applications ................................................................................................................205.2 Non-Resettable Power Application ............................................................................................................225.3 Door Holder Application ...........................................................................................................................23

Section 6Troubleshooting ..................................................................................................................................24

6.1 LEDs ..........................................................................................................................................................246.2 Trouble Conditions ....................................................................................................................................256.3 Earth Fault Resistance ................................................................................................................................266.4 Removing and Replacing the Control Panel ..............................................................................................27

6.4.1 Removing the Control Panel ...............................................................................................................276.4.2 Replacing the Control Panel ...............................................................................................................27

Appendix AUL Listed Notification Appliances ...............................................................................29

A.1 Notification Appliances .............................................................................................................................29

Page 5: Gamewell Gfps9 Manual

9001-0024 1

Section 1Introduction

The GFPS-9 is a notification appliance circuit and auxiliary power expander that provides up to 9 amps of filtered, 24 volt power for powering notification appliances and auxiliary devices. The GFPS-9 provides its own AC power connection, battery charging circuit, and battery connections. Used with security and fire alarm control panels, the GFPS-9 enables you to connect and distribute power to many more devices than your panel may normally allow.

• Input ConfigurationsThe GFPS-9 has two optically isolated signaling inputs that provide the signal connection from the main control panel to the GFPS-9 (see Section 3.2 for more details).

• Output ConfigurationsThe GFPS-9 has four power-limited notification appliance circuits that can be configured in various combinations of Class A and Class B circuits (see Section 3.3 for details).

• Auxiliary Power ConfigurationsThe GFPS-9 has a dedicated, power-limited, auxiliary output that can be configured in two different ways. The auxiliary output can either be non-resettable (always on), or configured to switch off during the AC power failure to conserve the battery standby power. When the auxiliary power is configured to switch off, there is a 30 second delay before the auxiliary power is turned off after the AC power fails (see Section 4.8.4 for details).

• Form C Trouble RelayThe GFPS-9 includes a general trouble relay that will de-energize for any trouble situation. (see Section 4.4.1 for details).

• Earth Fault DetectionThe GFPS-9 monitors for earth faults to the system power or system ground. When detected, the system de-energizes the trouble relay and the input supervision relays (see Section 5.2 for details).

• ANSI Temporal CodeThe GFPS-9 provides two configuration options that will drive outputs with the ANSI temporal code if the inputs are on constantly (see Section 4.8.1 for details).

• Supports Synchronized appliancesThe GFPS-9 provides configuration options that will eliminate the need for synchronized modules when using AMSECO, Faraday, Gentex, System Sensor, or Wheelock synchronization appliances.

Page 6: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

2 9001-0024

Section 2UL Requirements

When installed in accordance with NFPA 70 and NFPA 72 standards, the GFPS-9 can be connected to UL Listed devices.

The GFPS-9 is also listed to meet UL Standard 864 and power limiting requirements.

The GFPS-9 is compatible with any UL listed control unit utilizing reverse polarity supervised notification appliance circuits, using 24 VDC regulated outputs.

Page 7: Gamewell Gfps9 Manual

System Overview

9001-0024 3

Section 3System Overview

3.1 Terminal Descriptions and Electrical Ratings

CAUTIONEach output circuit is rated at 3 amps. DO NOT OVERLOAD. Overloading a circuit will cause it to shut down (power limit). The circuit will automatically reset once you remove the overload condition.

Terminal # Description Ratings

TB1

1 AC (black–“hot”)

120 VAC 60 Hz, 3A2 Earth Ground

3 AC (white–“neutral”)

TB2

1 Auxiliary Power (-)27.4 VDC 3.0 amps

2 Auxiliary Power (+)

3 Notification 4 Output (-)27.4 VDC 3.0 amps

4 Notification 4 Output (+) Although each output

5 Notification 3 Output (-)27.4 VDC 3.0 amps

is rated for 3 amps, the

6 Notification 3 Output (+) total current draw from

7 Notification 2 Output (-)27.4 VDC 3.0 amps

the 4 outputs and the

8 Notification 2 Output (+) auxiliary power must

9 Notification 1 Output (-)27.4 VDC 3.0 amps

not exceed 9 amps.

10 Notification 1 Output (+)

11 Normally Closed contact 2.5 A @ 250 VAC

or

2.5 A @ 30 VDC

12 Common

13 Normally Open contact

14 Input 2

9 - 30 VDC15 Input 2 (-)

16 Input 2 (+)

17 Input 1

9 - 30 VDC18 Input 1 (-)

19 Input 1 (+)

Page 8: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

4 9001-0024

3.2 Signal Input Terminals

Terminals 14 through 19 are polarized signal input terminals. They provide the signaling connection from the main panel to the GFPS-9. See Figure 4-2 for more details.

The main panel supervises its notification appliance circuits used for communicating with the GFPS-9 the same way it supervises ordinary notification appliance circuits. The signal inputs on the GFPS-9 monitor the polarity of the voltage coming from the main panel’s notification appliance circuits to determine when to operate the notification appliance circuits on the GFPS-9. The GFPS-9 emulates the trouble behavior of a normal notification appliance circuit by interrupting the EOL supervision current for internal or output trouble conditions on the GFPS-9.

Note that the GFPS-9 will accurately sense the polarity of the main panel’s notification appliance circuits to drive the outputs whether or not the supervision connection is intact. The following situations will disconnect the EOL supervision at the signal inputs and indicate a trouble condition:

• Low AC power• Low Battery condition• Earth ground fault to the system power or system ground• Auxiliary output power-limited condition• EOL supervision trouble or power-limited condition at an output

Trouble conditions will not necessarily occur for both inputs when the trouble is specific to a particular output. Only the signal input controlling the output circuit that is in trouble will indicate a trouble condition. Below are examples where both inputs do NOT indicate trouble for a trouble occurring at only one output circuit.

Note: Once the inputs are driven with forward polarity to activate the outputs, the main control panel will not be able to sense trouble conditions through its notification appliance circuit connected to the GFPS-9 input circuits. Use the GFPS-9 trouble relay when it is necessary to monitor trouble conditions and active alarm conditions at the same time.

Section 6 explains the significance of each trouble condition in more detail.

Example 1: If input 1 controls all four outputs, a fault on any output will cause input 1 to indicate trouble. The fault does not affect input 2.

Example 2: If input 1 controls outputs 1 and 2, and input 2 controls outputs 3 and 4, a fault condition on output 3 or 4 will cause input 2 to indicate trouble. The fault does not affect input 1.

Page 9: Gamewell Gfps9 Manual

System Overview

9001-0024 5

3.3 Notification Appliance Circuit Terminals

Terminals 3 through 10 are the notification appliance circuit output terminals. Each of the four circuits are rated at 3 amps, although you can only draw a total of 9 amps from the GFPS-9. The GFPS-9 outputs are short-circuit protected (power limited) according to UL 864 standards. Overcurrent indicators are yellow LEDs. The output voltage can vary depending on the load and input voltage.

The four power-limited NAC outputs can be configured as follows:

• Four Class B circuits • Faraday synchronized outputs• Two Class A circuits • Gentex synchronized outputs• One Class A and two Class B circuits • System Sensor synchronized outputs• Class B, ANSI temporal-coded circuits • Wheelock synchronization outputs

• AMSECO synchronized outputs

One or both GFPS-9 signal inputs control the NAC outputs, depending on the specific configuration setup. Possible configurations for the GFPS-9 are:

You can select which input controls which output, and which inputs are Class A and Class B using the 7-position DIP switch on the printed circuit board. Section 4.8 for DIP switch settings.

For Option: These Inputs: Control These Outputs: As:

1 Input 1 All outputs Class B circuits

2Input 1 or

Outputs 1, 2, 3, and 4Class B ANSI temporal-

Input 2 coded circuits

3Input 1 Outputs 1 and 2 Class B circuitsInput 2 Outputs 3 and 4 Class B circuits

4Input 1 Output 1 Class B circuitsInput 2 Outputs 2, 3, and 4 Class B circuits

5 Input 1 Outputs 1-2 and 3-4 Class A circuit pairs

6Input 1 Outputs 1 and 2 Class B ANSI temporal-coded circuitsInput 2 Outputs 3 and 4 Class B circuits

7Input 1 Outputs 1-2 Class A circuit pairInput 2 Outputs 3-4 Class A circuit pair

8Input 1 Outputs 1-2 Class A circuit pairInput 2 Outputs 3 and 4 Class B circuits

9Input 1 (Strobe Control)

All outputsClass A or Class B

Input 2 (Audio Control) Faraday Sync. Output

10Input 1 (Strobe Control)

All outputsClass A or Class B

Input 2 (Audio Control) Gentex Sync. Output

11Input 1 (Strobe Control)

All outputsClass A or Class B

Input 2 (Audio Control) System Sensor Sync. Output

12Input 1 (Strobe Control)

All outputsClass A or Class B

Input 2 (Audio Control) Wheelock Sync. Output

13Input 1 (Strobe Control)

All outputsClass A or Class B

Input 2 (Audio Control) Amseco Sync. Output

Page 10: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

6 9001-0024

Section 4Installation

Before installing the GFPS-9, the AC input must first be wired into the building’s main electrical power through the TB1 terminals (see Figure 4-2). Shut off the electrical power to the GFPS-9, and then complete the general installation of the GFPS-9 using the information in this section.

4.1 Mounting

Mount the GFPS-9 in locations that meet the following temperature and humidity requirements. Do not expose the panel to conditions outside these ranges. For use in indoor, dry environments.

When mounting on interior walls, use appropriate screw anchors in plaster. When mounting on concrete, especially when moisture is expected, first attach a piece of 3/4-inch plywood to the concrete surface. Attach the GFPS-9 to the plywood.

4.1.1 Preventing Water DamageWater damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.

Temperature 0o C-49o C (32o F-120o F)

Humidity 10%-93% at 30o C (86o F) noncondensing

Page 11: Gamewell Gfps9 Manual

Installation

9001-0024 7

4.2 Wire Routing

To avoid induced noise (transfer of electrical energy from one wire to another), keep input wiring isolated from high current output and power-limited wiring. Induced noise can interfere with telephone communication or even cause false alarms. Avoid pulling a single multiconductor cable for the entire system. Instead, separate high current input/output from low current. Separate power-limited from non-power-limited wiring. Non-power-limited wiring must be enclosed in conduit.

Wiring within the cabinet should be routed around the perimeter of the cabinet. It should not cross the printed circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the switching power supply circuit.

Figure 4-1 Sample Wire Routing

Note: The use of this knock out will reduce the number and/or size of batteries this cabinet can contain. Evaluation of space is important before using.

Page 12: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

8 9001-0024

4.3 Current Requirements (Standby and Alarm)

4.3.1 Current Drawn From Host Panel Table 4-1 shows the GFPS-9 current draw requirements from the main control panel when the panel’s notification appliance circuit is in alarm. The current draw from the main panel when it is supervising the GFPS-9 is the same current draw that would be present when the main panel supervises an ordinary notification appliance circuit.

4.3.2 Current Drawn from BatteryBatteries used with the GFPS-9 must not exceed 35 AH. Batteries larger than 7 AH will not fit into the GFPS-9 cabinet and must be housed in the BC-1 Battery Cabinet. See Section 4.7 for battery installation.

The following is the maximum current draw from the auxiliary power terminals for standby calculations. These currents assume 24 or 60 hours of standby time, followed by 5 minutes of maximum alarm current.

• 195 mA for 24 Hour Standby Current• 39 mA for 60 Hours of Auxiliary Standby Current

The above numbers were calculated assuming the use of 7 AH batteries at 100% of rated capacity.

The total current of the GFPS-9, plus all items powered from it, must not exceed 9 A when the panel is in alarm. Use Table 4-2 to ensure that the current does not exceed 9 A and, that the desired amount of standby is possible for the battery intended for use with the GFPS-9.

Table 4-1: Alarm Current Drawn From Main Control Panel

Panel Voltage Current

Alarm Current (for typical voltages) drawn from main panel’s notification appliance circuits.

12 VDC 6.5 mA

24 VDC One input circuit: 15 mA

Both input circuits: 30 mA

Page 13: Gamewell Gfps9 Manual

Installation

9001-0024 9

Table 4-2: Battery Calculation Worksheet

Device Number of Devices Current per Device Standby

CurrentAlarm

Current

For each device use this formula: This column X This column = Current per number of devices.

GFPS-9 Distributed Power Module

(Current draw from battery)1

Standby: 75 mA 75 mA

Alarm: 205 mA 205 mA

A GFPS-9 Current 75 mA 205 mA

Auxiliary Devices Refer to device manual for current ratings.

Alarm/Standby mA mA mA

Alarm/Standby mA mA mA

Alarm/Standby mA mA mA

Alarm/Standby mA mA mA

B Auxiliary Device Current mA mA

Notification appliances Refer to device manual for current ratings.

Alarm: mA 0 mA mA

Alarm: mA 0 mA mA

Alarm: mA 0 mA mA

Alarm: mA 0 mA mA

C Notification Appliance Current 0 mA mA

D Total current ratings of all devices in system (line A + line B + line C) mA mA

E Total current ratings converted to amperes (line D x .001): A A

FNumber of standby hours (24 or 60 for NFPA 72, Chapter 1, 1-5.2.5). 24 Hrs. for NBC, section 3.2.7.8

H

G Multiply lines E and F. Total standby AH AH

HAlarm sounding period in hours. In accordance with NBC and ULC.(For example, 5 minutes = .0833 hours.) H

I Multiply lines E and H. Total alarm AH AH

J Add lines G and I. Total standby and alarm AH AH

KMultiply line J by 1.20. (20% extra insurance to meet desired performance) Total ampere-hours required AH

Page 14: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

10 9001-0024

4.4 Connecting the GFPS-9 to a Control Panel

Figure 4-2 shows the general layout of the GFPS-9 PC board. This section also provides specific wiring details for accessories.

Figure 4-2 The Model GFPS-9 PC Board Layout

Consult the installation manual for specific wiring information for the control panel being used.

Page 15: Gamewell Gfps9 Manual

Installation

9001-0024 11

4.4.1 Common Trouble Relay The GFPS-9 has a Form C trouble relay built into Terminals 11-13. The relay provides a normally open and a normally closed contact, both of which are rated at 2.5A. The trouble relay will deactivate under any trouble condition.

A typical application of the trouble relay is to connect the GFPS-9 normally closed (N.C.) contacts in series with the EOL supplied with the fire alarm control panel. This will cause a trouble on the fire alarm control panel when the GFPS-9 opens its trouble contacts.

Note: The N.C. contact is the contact that is closed when the GFPS-9 has power and there are no trouble condi-tions.

Figure 4-3 Trouble Relay Connection Example

4.5 Notification Appliance Wiring

Note: Not all devices can use the sync feature. Be sure to check Appendix A to ensure the device you have chosen will work with this feature.

4.5.1 Class A Supervised WiringFigure 4-4 shows how to wire for Class A input and output supervision. Use in/out wiring methods for proper supervision. (Refer to Appendix A for notification appliances compatible with the GFPS-9.)

Class A Output Notification CircuitsThe configuration shown in Figure 4-4 shows two, 3 A devices wired as Class A. When using the outputs as Class A circuits, loop the wiring back to the corresponding circuit pair. For Class A wiring, no external EOL is necessary since it is built into the GFPS-9 board.

Must be connected toa power limited source

Page 16: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

12 9001-0024

Class A Supervised Input CircuitsThe configuration shown in Figure 4-4 shows Class A supervised wiring from a fire alarm control panel to the GFPS-9 board. Pay close attention to the polarities when wiring a panel to the GFPS-9 and follow these requirements:

• When wiring to Terminal 18 on the GFPS-9, you must use two separate wires. Do not loop a single wire or twist two conductors together.

• Do not use notification appliances on Class A circuits connected to a GFPS-9 for input. The GFPS-9 will detect voltage across the input circuits, but is not designed to pass the added current load from notification appliances.

Figure 4-4 Class A Supervised Input/Output Connections

4.5.2 Class B Supervised WiringFigure 4-5 shows how to wire for Class B input and output supervision. Use in/out wiring methods for proper supervision (Refer to the Appendix for notification appliances approved for use with the GFPS-9.)

Class B Output Notification CircuitsFigure 4-5 shows four, 1.5 A devices wired as Class B.

Place a 4.7k ohm EOL resistor (provided) at the end of each circuit to enable supervision when using all outputs as Class B notification appliance circuits. The 4.7k EOLs must be wired to the terminals whether or not you are using all output terminals.

Page 17: Gamewell Gfps9 Manual

Installation

9001-0024 13

Class B Supervised Input CircuitsFigure 4-5 shows Class B supervised wiring from a fire alarm control panel to the GFPS-9.

Use an EOL resistor as shown to enable notification appliance circuit input supervision. Some panels use EOLs that have a different value from the 4.7k ohm EOL resistor used by the GFPS-9. In this case, the EOL must be UL listed for the fire alarm control panel (not the GFPS-9).

Figure 4-5 Class B Supervised Input/Output Connections

4.6 Ground Fault Detection Enable/Disable Jumper

In some cases the ground fault detection feature on the GFPS-9 may interfere with the ground fault detection feature of the main control panel in the system. To disable the ground fault detection feature on the GFPS-9, place the jumper block on J1, across Pins 1 and 2 (see Figure 4-2).

Page 18: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

14 9001-0024

4.7 Battery Connection

Use two 12 VDC, 7 AH gel cell batteries inside the GFPS-9 cabinet. For batteries larger than 7 AH (not to exceed 35 AH) use the BC-1 Battery Cabinet. It is recommended that you replace the batteries every five years. The following steps and diagram explain how to connect the batteries.

1. Connect the black wire from the Battery – terminal to the negative (–) side of Battery #2.2. Connect the jumper wire provided (PN 140694) from the positive (+) side of Battery #2 to

the negative side of Battery #1.3. Connect the red wire from the Battery + terminal to the positive (+) side of battery #1.

Figure 4-6 Battery Connection

Page 19: Gamewell Gfps9 Manual

Installation

9001-0024 15

4.8 DIP Switch Settings

A 7-position DIP switch on the GFPS-9 board allows you to select the following:

• How long the GFPS-9 will wait before indicating a loss of AC.• Which input (Input 1 or Input 2) will control the NACs.• Which NACs to wire as Class A and Class B.• Auxiliary power state.• Which NACs to operate as steady, ANSI temporal, or sync. outputs

Refer to Figure 4-2 for the location of the DIP switch on the GFPS-9 board.

Page 20: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

16 9001-0024

4.8.1 Selecting the Standard Input/Output ConfigurationsFigure 4-7 and Figure 4-8 show the position of each switch for the non-synchronized input and output configurations. The position of Switches 4 and 5 does not affect the relationship of inputs to outputs.

Note: The GFPS-9 checks switches 1, 2, 3, and 6 only when powering up the GFPS-9. If you change these switch settings, you must remove both the AC power and the battery to make the GFPS-9 recognize the new settings.

Figure 4-7 Setting DIP Switches 1-3

Figure 4-8 Setting DIP Switches 1-3 (Continued)

Note: For 100 mS input signal debounce with no synchronization DIP switches 6 and 7 must be turned On.

Page 21: Gamewell Gfps9 Manual

Installation

9001-0024 17

4.8.1.1 Input/Output Configurations That Select ANSI Temporal-Coded Outputs

The DIP switch settings marked with an asterisk (*) in Figure 4-7 and Figure 4-8 are designed to produce ANSI temporal-coded outputs from a constant input. The figures shown below compare the output patterns of configurations before and after the addition of this feature.

With this new feature, a steady signal can produce the pattern shown above for panels not previously able to do so.Note: The GFPS-9 can also produce temporal patterns if the inputs are non-ANSI temporal configurations.

Standard GFPS-9 Input to Output Relationship Input/Output Relationship for ANSITemporal-coded Options

Page 22: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

18 9001-0024

4.8.2 Selecting Synchronized Output ConfigurationsThe following sections describe how to configure the GFPS-9 as a synchronization power expander for Amseco, Faraday, Gentex, System Sensor, or Wheelock synchronized horn/strobe appliances.

Note: In order for the synchronization feature to operate properly, make sure you have set the DIP switches for the proper manufacturer. See Sections 4.8.2.1, 4.8.2.2, or 4.8.2.3.

4.8.2.1 Selecting Synchronized Faraday ConfigurationsTo select the input/outputs for Faraday synchronized appliances, set the DIP switches as shown in Figure 4-9.

Figure 4-9 Faraday Synchronized Configurations

4.8.2.2 Selecting Synchronized Gentex ConfigurationsTo select the input/outputs for Gentex synchronized appliances, set the DIP switches as shown in Figure 4-10.

Figure 4-10 Gentex Synchronized Configurations

Important!For all synchronization options, input 1 is the strobe input and input 2 is the audible input. The signals to input 1 and input 2 must be DC signals for the synchronization patterns to work properly. When it is desired to activate both strobes and audibles, input 1 and input 2 must be active. If it is desired to only activate strobes, then input 1 must be active and input 2 must be inactive. The audible can be deactivated and reactivated at any time by changing the signal at input 2 as long as input 1 remains active. If input 1 is not active, then input 2 is ignored.

Page 23: Gamewell Gfps9 Manual

Installation

9001-0024 19

4.8.2.3 Selecting Synchronized System Sensor ConfigurationsTo select the input/outputs for System Sensor synchronized appliances, set the DIP switches as shown in Figure 4-11.

Figure 4-11 System Sensor Synchronized Configurations

4.8.2.4 Selecting Synchronized Wheelock ConfigurationsTo select the input/outputs for Wheelock synchronized appliances, set the DIP switches as shown in Figure 4-12.

Figure 4-12 Wheelock Synchronized Configurations

4.8.2.5 Selecting Synchronized AMSECO ConfigurationsTo select the input/outputs for AMSECO synchronized appliances, set the DIP switches as shown in Figure 4-13.

Figure 4-13 AMSECO Synchronized Configurations

Page 24: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

20 9001-0024

4.8.3 Setting the Loss of AC DelayNormal selection for reporting loss of AC is 3 hours.

The ON position is for test purposes only and the normal position for Switch 4 is OFF. For testing the Low AC reporting, you can temporarily turn Switch 4 ON without removing power. Note: Remember to turn the switch OFF when testing is complete.

Figure 4-14 Setting DIP Switch 4

4.8.4 Setting the Auxiliary OutputSwitch 5 on the DIP switch determines how the auxiliary power operates on the GFPS-9.

The GFPS-9 checks Switch 5 only when powering up the GFPS-9. If you change this switch, you must remove both the AC power and the battery to force the GFPS-9 to recognize the new switch setting.

Figure 4-15 Setting DIP Switch 5

Page 25: Gamewell Gfps9 Manual

Sample Applications

9001-0024 21

Section 5Sample Applications

The drawings in this section show various GFPS-9 configurations, including “daisy-chaining”.

5.1 Notification Power Applications

Figure 5-1 Input 1 Activates All Four Outputs

Figure 5-2 Input 1 Activates NACs 1 and 2; Input 2 Activates NACs 3 and 4

GFPS-9

Local Fire AlarmControl Panel

Local Fire AlarmControl Panel

GFPS-9

Page 26: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

22 9001-0024

Note: When multiple power supplies are used with one control unit they will not sync with each other

Figure 5-3 One Control Activating Two GFPS-9s

Figure 5-4 One Control Activating Three GFPS-9s in Series

GFPS-9

GFPS-9

Local Fire AlarmControl Panel

GFPS-9

GFPS-9

GFPS-9

Local Fire AlarmControl Panel

Page 27: Gamewell Gfps9 Manual

Sample Applications

9001-0024 23

Figure 5-5 Each Control NAC Activates Five Output NACs

5.2 Non-Resettable Power Application

The GFPS-9 provides a dedicated 3 A auxiliary power output that you can select as non-resettable (output is always on). See Section 4.8.4 for setting the auxiliary power. If you need more than 3 A, wire the inputs as shown in Figure 5-6.

Figure 5-6 Auxiliary Output Wiring for Non-Resettable Power

GFPS-9

GFPS-9

GFPS-9

Local Fire AlarmControl Panel

Page 28: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

24 9001-0024

5.3 Door Holder Application

In a typical door holder application, the door holder power must be interrupted to close all fire doors under the following conditions:

• Any active alarm condition.• AC power failure (to conserve battery power).

To close the fire doors in these situations, wire an N.C. programmable relay from the FACP in series with the auxiliary power to the door holders as shown in Figure 5-7.

The circuit shown in Figure 5-7 will provide up to 3 amps of door holder power. (See Section 5.2 if you need more than 3 amps of auxiliary power.) The power in this example is released when AC power is off for 30 seconds or more, or when the relay from the fire alarm control panel becomes open. You would have to use the equivalent of a programmable relay from a fire alarm control panel that is programmed to open under alarm conditions. See Section 4.8.4 for selecting auxiliary power options.

Figure 5-7 Door Holder Wiring Example

GFPS-9

Fire Alarm Panel

ESL DHX 1224

Page 29: Gamewell Gfps9 Manual

Troubleshooting

9001-0024 25

Section 6Troubleshooting

Light-emitting diodes (LEDs) indicate fault conditions. This section describes the LED states.

6.1 LEDs

The eight LEDs indicate a fault in one of the circuits (either NACs 1 through 4, auxiliary power, earth fault, low AC, or battery). A fault in the LED's corresponding circuit will light the LED (labeled on the board). Their functions are as follows:

See Figure 4-2 for locations of LEDs.

LED Color Description

OUT1 Yellow When ON, output circuit 1 is in trouble or in an overcurrent state.

OUT2 Yellow When ON, output circuit 2 is in trouble or in an overcurrent state.

OUT3 Yellow When ON, output circuit 3 is in trouble or in an overcurrent state.

OUT4 Yellow When ON, output circuit 4 is in trouble or in an overcurrent state.

AUX Yellow When ON, the auxiliary power output is in an overcurrent state.

FLT Yellow When ON, an earth ground fault on the unit exists.

BATT Yellow When ON, a low battery condition exists.

AC Green When OFF, there is no AC power to the unit. Under normal conditions, this LED is ON to indicate the presence of AC power.

Page 30: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

26 9001-0024

6.2 Trouble Conditions

Note: While Input 1 & 2 are activated, Input 1 & 2 will not open to indicate a trouble or supervisory condition. Once the circuit is deactivated it will open to indicate a trouble or supervisory condition.

Trouble Condition What Happens

Low AC

(AC input voltage is low or off for 6 hours or longer.)

Input 1 and Input 2 supervision circuits open after a 6 hour delay.

The green AC LED turns off as soon as low AC or loss of AC occurs (does not wait 6 hours).

The trouble relay is de-energized after a 6 hour delay.

The trouble restores within 1 minute of the AC voltage restoring to a normal level.

Low Battery

(Battery voltage is less than 21.4 VDC.)

Input 1 and Input 2 supervision circuits open. The yellow “BATT” LED lights.

The trouble relay is de-energized.

The trouble restores when battery voltage is greater than 22.4 VDC.

Earth Ground Fault

(The earth terminal is connected to one of the positive or negative terminals on the output or auxiliary output circuits.)

Input 1 and Input 2 supervision circuits open. The yellow “FLT” LED lights.

The trouble relay is de-energized.

The trouble restores when the fault between the earth ground and one of the output circuit terminals is removed.

Power Limit At AUX

(Current draw at the auxiliary power terminals is exceeding 3.0 amps.)

Power disconnects at the AUX terminal. Input 1 and Input 2 supervision circuits open. The yellow “AUX” LED lights. The trouble relay is de-energized.

The trouble restores when the overcurrent condition no longer exists. When a circuit goes into a power limited state, it will reverse the polarity of the voltage at the terminals and verify the load. If it is more than 1k ohms, the power limit will self-restore.

This does not automatically occur for some devices typically connected to auxiliary power. Power limit conditions do not restore in reverse polarity monitoring if the devices are not polarized (for example, some door holder devices). To allow automatic restores for power-limited auxiliary circuits, it is recommended that all non-polarized devices be polarized using a diode in series with each device.

Power-limited OUTPUT

(Current draw at an output terminal is exceeding 3.0 amps.)

Power at the OUTPUT is disconnected. Input 1 and Input 2 supervision circuits open. The corresponding yellow LED lights. The trouble relay is de-energized.

The trouble restores when the overcurrent condition no longer exists.

EOL supervision trouble

(Equivalent resistance of the EOL resistor is outside the range 2k - 10k.)

Input 1 and Input 2 supervision circuits open. Corresponding yellow LED lights.

The trouble relay is de-energized.

Trouble restores if an EOL within (2k-10k) appears at the output terminals.

Page 31: Gamewell Gfps9 Manual

Troubleshooting

9001-0024 27

6.3 Earth Fault Resistance

Table 6-1 lists the earth fault resistance detection for each applicable terminal on the FACP.

Table 6-1: Earth Fault Resistance Values by Terminal

Function Terminal Number Terminal Label Value

(in kohms)

Auxiliary Devices1 H5-

AUX0

2 H5+ 0

Notification Appliance Circuit 4

3 H4-OUT4

0

4 H4+ 0

Notification Appliance Circuit 3

5 H3-OUT3

0

6 H3+ 0

Notification Appliance Circuit 2

7 H2-OUT2

0

8 H2+ 0

Notification Appliance Circuit 1

9 H1-OUT1

0

10 H1+ 0

Page 32: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

28 9001-0024

6.4 Removing and Replacing the Control Panel

This section provides instruction on how to remove and replace the control panel if it is determined that the control panel needs to be repaired or replaced.

6.4.1 Removing the Control PanelFollow these step to properly remove the control panel:

1. Remove the two heat sink screws. The heat sink screws are located on the top of the cabinet. See Figure 6-1.

Figure 6-1 Mounting Screw Locations

2. Remove the four chassis mounting screws. See Figure 6-1 for chassis screw locations.3. Carefully remove the control panel.

6.4.2 Replacing the Control PanelFollow these steps to replace the control panel:Note: Use a grounding strap when working with static sensitive components.

1. Align the control panel with the chassis mounting stand-offs. See Figure 6-1.

2. Insert the four chassis mounting screws (see Figure 6-1). Do not over tighten the chassis mounting screws.

3. Insert the two heat sink screws (see Figure 6-1). Do not over tighten the heat sink screws.Note: The heat sink screws must be installed for proper heat dispersion of the power module’s power supply.

Page 33: Gamewell Gfps9 Manual

9001-0024 29

Appendix AUL Listed Notification Appliances

For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each circuit. All supervised notification appliances used with the GFPS-9 must be polarized.

Note: Not all devices can use the Sync feature, be sure to check Table A-1 to ensure the device you have chosen will work with this feature. Synchronization is UL listed for multi-circuit operation.

A.1 Notification Appliances

Table A-1 below lists notification appliances compatible with the GFPS-9. Appliances which can be synchronized indicate the type of sync available in the columns marked Audio and/or Visual.

Table A-1: Compatible Notification Appliances

Manufacturer Model Audio Visual Type

AMSECO

SH24W-153075 Horn/Strobe

SAD24-153075 Strobe

SAD24-75110 Strobe

SL24W-75110 Strobe

SL24C-3075110 Strobe

SLB24-75 Strobe

RSD24-153075 Strobe

RSD24-75110 Strobe

SH24W-75110 Horn/Strobe

SH24W-3075110 Horn/Strobe

SHB24-75 Horn/Strobe

SCM24W-153075 Chimes/Strobe

SCM24W-75110 Chimes/Strobe

SCM24C-3075110 Chimes/Strobe

SCM24C-177 Chimes/Strobe

H24W Horn

H24R Horn

Page 34: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

30 9001-0024

Faraday

446 Vibrating Bell

476 Vibrating Bell

477 Single Stroke Bell

2700 -M. -R, -T, -Y, -Z Strobe

2701 Series Strobe

2705 Series Strobe

2820 Snyc Temporal Horn/Strobe

2821 Snyc Temporal Horn/Strobe

2824 Horn Strobe

5333 Multi-Tone Horn)

5336 Multi-Tone Horn/Strobe

5337 Multi-Tone Horn/Strobe

5338 Multi-Tone Horn/Strobe

5343 Single Tone Horn/Strobe

5346 Electronic Horn with Strobe

5347 Electronic Horn with Strobe

5348 Single Tone Horn/Strobe

5373 8-Tone Horn/Strobe

6321 Sync Mini Horn/Strobe

6322 Mini Horn/Sync Strobe

6380 8-Tone Electronic Signal/Strobe

5376 8-Tone Horn/Strobe

5377 8-Tone Horn/Strobe

5378 8-Tone Horn/Strobe

5383 8-Tone Horn/Strobe with Sync Strobe

5386 8-Tone Horn/Strobe with Sync Strobe

5387 8-Tone Horn/Strobe with Sync Strobe

Table A-1: Compatible Notification Appliances

Manufacturer Model Audio Visual Type

Page 35: Gamewell Gfps9 Manual

UL Listed Notification Appliances

9001-0024 31

Faraday 5388 8-Tone Horn/Strobe with Sync Strobe

5508 Single Gang Sync Strobe

5509 Strobe

5510 Strobe

5511 Strobe

5512 Strobe

5516 Strobe

5517 Strobe

5518 Strobe

5519 Strobe

5521 4” Square Sync Strobe

5522 4” Square Sync Strobe

6120 Horn

6140 Horn

6223 Horn

6226 Horn/Strobe

6227 Horn/Strobe

6228 Horn/Strobe

6243 Electron-Mechanical Horn

6244 Electron-Mechanical Horn

6245 Electron-Mechanical Horn

6246 Electron-Mechanical Horn/Strobe

6247 Electron-Mechanical Horn/Strobe

6248 Electron-Mechanical Horn/Strobe

6300 Mini-Horn

6301 Mini-Horn

6302 Mini-Horn

6310 Mini-Horn/Strobe

6311 Mini-Horn/Strobe

6312 Mini-Horn/Strobe

6314 Series -M, -R, -T, -Y, -Z Strobe

6320 Sync Mini Horn/Strobe

Table A-1: Compatible Notification Appliances

Manufacturer Model Audio Visual Type

Page 36: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

32 9001-0024

FCI

S2415-FC Strobe

S241575-FC Strobe

S2430-FC Strobe

130-3117C Mini Horn

130-3147C Mini Horn

BLV-6 Vibrating Bell

BLV-10 Vibrating Bell

BLVCH Vibrating Chime

H12/24-FC Horn

H12/24W-FC Horn

H12/24K-FC Horn

HC12/24-FC Horn

HC12/24W-FC Horn

HC12/24K-FC Horn

P2415-FC Horn/Strobe

P2415W-FC Horn/Strobe

P2415K-FC Horn/Strobe

P241575-FC Horn/Strobe

P241575W-FC Horn/Strobe

P241575F-FC Horn/Strobe

P241575K-FC Horn/Strobe

P2430-FC Horn/Strobe

P2430W-FC Horn/Strobe

P2430K-FC Horn/Strobe

P2475-FC Horn/Strobe

P2475W-FC Horn/Strobe

P2475K-FC Horn/Strobe

P24110-FC Horn/Strobe

P24110W-FC Horn/Strobe

P24110K-FC Horn/Strobe

S2430W-FC Strobe

S2430K-FC Strobe

S2475-FC Strobe

Table A-1: Compatible Notification Appliances

Manufacturer Model Audio Visual Type

Page 37: Gamewell Gfps9 Manual

UL Listed Notification Appliances

9001-0024 33

FCI

S2475W-FC Strobe

S2475K-FC Strobe

S24110-FC Strobe

S24110W-FC Strobe

S24110K-FC Strobe

Federal Signal450 Horn

VALS Horn/Strobe

Table A-1: Compatible Notification Appliances

Manufacturer Model Audio Visual Type

Page 38: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

34 9001-0024

Gentex

GEC-24-15 Horn/Strobes

GEC-24-30 Horn/Strobes

GEC-24-60 Horn/Strobes

GEC-24-75 Horn/Strobes

GEC-24-177 Horn/Strobes

GX91 MiniHorn Steady Tone

GX93 MiniHorn Temporal Tone

HG124 Horn

HS24-15 Horn/Strobe

HS24-30 Horn/Strobe

HS24-60 Horn/Strobe

HS24-75 Horn/Strobe

HS24-110 Horn/Strobe

HS24-1575 Horn/Strobe

GCC24 Multi Candella Horn/Strobe Ceiling Mount

GCCR24 Multi Candella Horn/Strobe Ceiling Mount

GCS24 Multi Candella Strobe Ceiling Mount

GCSR24 Multi Candella Strobe Ceiling Mount

GECR-24 Multi Candella Horn/Strobe

GES24-15 Strobes

GES24-30 Strobes

GES24-60 Strobes

GES24-75 Strobes

GES24-110 Strobes

GES24-15/75 Strobes

GES24-177 Strobes

GES3-24 Multi Candella Strobe

GESR-24 Multi Candella Strobe

GEH-24 Horn

ST24-30 Strobe

Table A-1: Compatible Notification Appliances

Manufacturer Model Audio Visual Type

Page 39: Gamewell Gfps9 Manual

UL Listed Notification Appliances

9001-0024 35

Gentex con’t

ST24-60 Strobe

ST24-75 Strobe

ST24-110 Strobe

ST24-1575 Strobe

WGEC24-75W Weatherproof Horn/Strobe

WGES24-75W Weatherproof Strobe

WGMS-24-X Horn/Strobe

SSPKWR Speaker

SSPKWW Speaker

SSPK-15WR Speaker/Strobe

SSPK-15WW Speaker/Strobe

SSPK-15/75WR Speaker/Strobe

SSPK-15/75WW Speaker/Strobe

SSPK-30WR Speaker/Strobe

SSPK-30WW Speaker/Strobe

SSPK-60WR Speaker/Strobe

SSPK-60WW Speaker/Strobe

SSPK-75WR Speaker/Strobe

SSPK-75WW Speaker/Strobe

SSPK-110WR Speaker/Strobe

SSPK-110WW Speaker/Strobe

SSPKCLPR Speaker

SSPKCLPW Speaker

SSPK24CLPR Speaker/Strobe

SSPK24CLPW Speaker/Strobe

GEC-24-110 Horn/Strobes

GEC-24-15/75 Horn/Strobes

Table A-1: Compatible Notification Appliances

Manufacturer Model Audio Visual Type

Page 40: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

36 9001-0024

System Sensor

CHR Chime

CHW Chime

CHSR 2-Wire Chime/Strobe

CHSW 2-Wire Chime/Strobe

HR Horn

HW Horn

HRK Horn

P2R 2-Wire Horn/Strobe

P2R-P 2-Wire Horn/Strobe

PC2R 2-Wire Horn/Strobe

PC2R-P 2-Wire Horn/Strobe

P2RH 2-Wire Horn/Strobe High Candela

P2RH-P 2-Wire Horn/Strobe High Candela

PC2RH 2-Wire Horn/Strobe High Candela

PC2RH-P 2-Wire Horn/Strobe High Candela

P2W 2-Wire Horn/Strobe

P2W-P 2-Wire Horn/Strobe

PC2W 2-Wire Horn/Strobe

PC2W-P 2-Wire Horn/Strobe

P2WH 2-Wire Horn/Strobe High Candela

P2WH-P 2-Wire Horn/Strobe High Candela

PC2WH 2-Wire Horn/Strobe High Candela

PC2WH-P 2-Wire Horn/Strobe High Candela

P2RK 2-Wire Horn/Strobe

PC2RK 2-Wire Horn/Strobe

P2RHK 2-Wire Horn/Strobe High Candela

PC2RHK 2-Wire Horn/Strobe High Candela

P4R 4-Wire Horn/Strobe

PC4R 4-Wire Horn/Strobe

P4RH 4-Wire Horn/Strobe High Candela

Table A-1: Compatible Notification Appliances

Manufacturer Model Audio Visual Type

Page 41: Gamewell Gfps9 Manual

UL Listed Notification Appliances

9001-0024 37

System Sensor (cont.)

P4W 4-Wire Horn/Strobe

PC4W 4-Wire Horn/Strobe

P4WH 4-Wire Horn/Strobe High Candela

PC4WH 4-Wire Horn/Strobe High Candela

P4RK 4-Wire Horn/Strobe

PC4RK 4-Wire Horn/Strobe

P4RHK 4-Wire Horn/Strobe High Candela

PC4RHK 4-Wire Horn/Strobe High Candela

PC4RH 4-Wire Horn/Strobe High Candela

SR Strobe

SR-P Strobe

SCR Strobe

SCR-P Strobe

SRH Strobe High Candela

SRH-P Strobe High Candela

SCRH Strobe High Candela

SCRH-P Strobe High Candela

SW Strobe

SW-P Strobe

SCW Strobe

SCW-P Strobe

SWH Strobe High Candela

SWH-P Strobe High Candela

SCWH Strobe High Candela

SCWH-P Strobe High Candela

SRK Strobe

SCRK Strobe

SRHK Strobe High Candela

SCRHK Strobe High Candela

Table A-1: Compatible Notification Appliances

Manufacturer Model Audio Visual Type

Page 42: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

38 9001-0024

Wheelock

AH-12 Horn

AH-24 Horn

AH-12WP Horn Weatherproof

AH-24WP Horn Weatherproof

AMT-241575W Multi-Tone Horn Strobe

AMT-24MCW Mutli-Tone Horn Strobe

AMT-241575W-NYC Multi-Tone Horn Strobe

AMT-12/24 Multi-tone Horn

AMT-12/24 NYC Multi-tone Horn

AS-121575W Horn/Strobe

NH-12/24 Horn

AS-241575W Horn/Strobe

AS-24MCC Horn/Strobe

AS-24MCCH Horn/Strobe

AS-24MCW Horn/Strobe

AS-24MCWH Horn/Strobe

Table A-1: Compatible Notification Appliances

Manufacturer Model Audio Visual Type

Page 43: Gamewell Gfps9 Manual

UL Listed Notification Appliances

9001-0024 39

Wheelock

(cont.)

ASWP-2475W Horn/Strobe Weatherproof

ASWP-2475C Horn/Strobe Weatherproof

ASWP-24MCWH Horn/Strobe

ASWP-24MCCH Hor/Stroben

CH70-241575W Chime/Strobe

CH70-24MCW Chime/Strobe

CH70-24MCWH Chime/Strobe

CH90-24MCC Chime/Strobe

CH90-24MCCH Chime/Strobe

HS-24 Horn

HS4-241575W Horn/Strobe

HS4-24MCW Horn/Strobe

HS4-24MCWH Horn/Strobe

HS4-24MCC Horn/Strobe

MIZ-24S Mini Horn Strobe

MT-121575W MultitoneHorn Strobe

MT-241575W Multitone Horn Strobe

MT-24MCW Multitone Horn Strobe

MTWP-2475W Multitone Horn Strobe

MTWP-2475C Multitone Horn Strobe

MTG-121575W Multitone Horn Strobe

MTR-121575W Multitone Horn Strobe

MTWPA-2475W Multitone Horn Strobe

MTWPB-2475W Multitone Horn Strobe

MTWPG-2475W Multitone Horn Strobe

MTWPR-2475W Multitone Horn Strobe

MTWPA-24MCCH Multitone Horn Strobe

ZNH Horn

NS-121575W Horn/Strobe

NS-241575W Horn/Strobe

NS-24MCW Horn/Strobe

NS-24MCC Horn/Strobe

Table A-1: Compatible Notification Appliances

Manufacturer Model Audio Visual Type

Page 44: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

40 9001-0024

Wheelock

Con’t

NS-24MCCH Horn/Strobe

ZNS-MCW Horn/Strobe

ZNS-MCWH Horn/Strobe

ZNS-24MCC Horn/Strobe

ZNS-24MCCH Horn/Strobe

RSS-121575W Strobe

RSS-241575W Strobe

RSS-24MCC Strobe

RSS-24MCCR Strobe

RSS-24MCCH Strobe

RSS-24MCCHR Strobe

RSS-24MCW Strobe

RSS-24MCWH Strobe

RSSP-121575W Strobe

RSSP-241575W Strobe

RSSR-2415W Strobe

RSSR-2415C Strobe

RSSR-2475W Strobe

RSSR-2475C Strobe

RSSR-24110C Strobe

RSSA-24110W Strobe

RSSB-24110W Strobe

RSSG-24110W Strobe

RSSR-24110W Strobe

RSSA-24MCC Multi-Cd Strobe

RSSB-24MCC Multi-Cd Strobe

RSSG-24MCC Multi-Cd Strobe

RSSR-24MCC Multi-Cd Strobe

Table A-1: Compatible Notification Appliances

Manufacturer Model Audio Visual Type

Page 45: Gamewell Gfps9 Manual

UL Listed Notification Appliances

9001-0024 41

Wheelock Con’t

RSSWPA-2475W Strobe Weatherproof

RSSWPA-24MCCH Strobe Weatherproof

RSSWPG-24MCCH Strobe Weatherproof

RSSWPR-24MCCH Strobe Weatherproof

RSSWP-2475W Strobe Weatherproof

RSSWP-2475C Strobe Weatherproof

RSSWP-24MCWH Strobe Weatherproof

ZRS-MCWH Strobe

ZRS-24MCC Strobe

ZRS-24MCCH Strobe

CH-70 Chime

CH-90 Chime

ET70WP-2475W Speaker/Strobe

ET70WP-2475C Speaker/Strobe

ET70WP-24185W Speaker/Strobe

ET70WP-24177C Speaker/Strobe

ET70WPA-2475 Speaker/Strobe

E50 Speaker

E50-24MCW Speaker/Strobe

E50-24MCWH Speaker/Strobe

E50-241575W Speaker/Strobe

Table A-1: Compatible Notification Appliances

Manufacturer Model Audio Visual Type

Page 46: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

42 9001-0024

Wheelock con’t

E60 Speaker

E60-24MCW Speaker/Strobe

E60-24MCHW Speaker/Strobe

E60-24MCC Speaker/Strobe

E60-24MCCH Speaker/Strobe

E70 Speaker

E70-MCW Speaker/Strobe

E70-24MCWH Speaker/Strobe

E70-24MCC Speaker/Strobe

E70-24MCCH Speaker/Strobe

E70-241575W Speaker/Strobe

MB-G6-24 Motor Bell

MB-G10-24 Motor Bell

MB-G6-12 Motor Bell

MB-G10-12 Motor Bell

MIZ-24-R Mini-Horn

MT-12/24-R Multitone Horn

MT4-12/24 Multitone Horn

E70-241575W Speaker/Strobe

E90 Speaker

E90-24MCW Speaker/Strobe

E90-24MCWH Speaker/Strobe

E90-24MCC Speaker/Strobe

E90-24MCCH Speaker/Strobe

ET90-241575W Speaker/Strobe

ET70-241575W Speaker

ET70-24MCW Speaker/Strobe

ET70-24MCWH Speaker/Strobe

ET70-24MCC Speaker/Strobe

ET70-24MCCH Speaker/Strobe

ET-1010 Speaker

ET-1080 Speaker

Table A-1: Compatible Notification Appliances

Manufacturer Model Audio Visual Type

Page 47: Gamewell Gfps9 Manual

UL Listed Notification Appliances

9001-0024 43

Wheelock (con’t)

ET80-24MCW Speaker/Strobe

ET80-24MCWH Speaker/Strobe

ET80-241575W Speaker/Strobe

ET90 Speaker

ET90-24MCW Speaker/Strobe

ET90-24MCCH Speaker/Strobe

ET90-24MCC Speaker/Strobe

ET90-24MCWH Speaker/Strobe

ET70WP-2475W Speaker/Strobe / weatherproof

ET70WP-2475C Speaker/Strobe / weatherproof

ET70WP-24115C Speaker/Strobe / weatherproof

ET70WP-24135C Speaker/Strobe / weatherproof

ET70WP-24177C Speaker/Strobe / weathertproof

ET70WP-24185W Speaker/Strobe / weatherproof

S8-24MCC Speaker//Strobe

ZRS-MCW Strobe

MTWPR-24MCCH Multitone Horn Strobe

NH-12/24R Horn

Table A-1: Compatible Notification Appliances

Manufacturer Model Audio Visual Type

Page 48: Gamewell Gfps9 Manual

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual

44 9001-0024

Page 49: Gamewell Gfps9 Manual
Page 50: Gamewell Gfps9 Manual