Page 2: FCI Seminar

Faulted Circuit Indicators

Generating Station

Step-Up Transformer Industrial Customer

Transmission Substation(Bulk-Power Switching)

Step-Down Transformer

Industrial CustomerIndustrial Customer

Distribution Substation

Step-DownTransformer

CommercialCommercialCustomerCustomer

Residential Customer

Residential

Customer

20 KV138 KV

4 KV

34.5 KV

440 V

13.8 KV

220/440 V

120/240 V

120/240 V13.8 KV

Fisher Pierce

Locations where our Faulted Circuit Indicator products can be applied on the electrical system

Page 3: FCI Seminar

Faulted Circuit Indicators

Electrical Fault Locating Electrical Fault Locating MethodsMethods

• Customer calls with outage

• Line patrolling after fault

• Electronic recloser or breaker controls provide fault location

• Cable thumping for underground cables

• Fault chasing

• Predictive maintenance switching

• Fault Indicators

Page 4: FCI Seminar

Faulted Circuit Indicators

The Benefits of Using FCIsThe Benefits of Using FCIs• Aid in the location and isolation of the faulted cable

or equipment

• Reduces system down time and restoration costs

• Reduces lost revenue

• Increases customer service levels

• Improves personnel safety & system reliability

• Reduces stresses on circuit cable and components through efficient sectionalizing

• Minimizes potential destruction of customer owned sensitive equipment

Page 5: FCI Seminar

Faulted Circuit Indicators

How FCIs OperateHow FCIs Operate

• During a fault, high fault current is present from the source of the fault location.

• Installed FCIs on the system sense this condition and trip ( LED, Flag, Strobe, Radio Signal, etc.).

• Troublemen look for fault indicators and follow to identify the location of the fault.

Page 6: FCI Seminar

Faulted Circuit Indicators

How FCIs Operate (cont’d)How FCIs Operate (cont’d)• Locate the last tripped FCI and the first untripped

FCI, the fault has been isolated to a specific section of the circuit.

• Crews will switch out the faulted segment and restore power to the remaining part of the circuit.

• The faulted segment is then repaired.

• Some Examples of a typical URD Circuits installed with FCIs:

Page 7: FCI Seminar

Faulted Circuit Indicators

Switchgear 1

Switchgear 2

R1NC NC

NC

NO

R2Voltage ResetFault Indicator

FAULT INDICATOR OPERATIONFAULT INDICATOR OPERATION

Page 8: FCI Seminar

Faulted Circuit Indicators

R1

Switchgear 1

NC NC

NC

NO

Switchgear 2

R2

Breaker Locks Out

Loss of Voltage Detected

Only the FCIs That Detect Overcurrent will Indicate

Voltage ResetFault Indicator

FAULT INDICATOR OPERATIONFAULT INDICATOR OPERATION

Page 9: FCI Seminar

Faulted Circuit Indicators

Typical InstallationsTypical Installations• Overhead Conductor

• Riser Pole or Dip Pole

• Subsurface or Padmount Transformer/Switchgear

• Junction Box, Manhole Applications

• Sectionalizing Cabinets

Page 10: FCI Seminar

Faulted Circuit Indicators

Where are FCIs located ?Where are FCIs located ?

Page 11: FCI Seminar

Faulted Circuit Indicators

Where are FCIs located ?Where are FCIs located ?

Page 12: FCI Seminar

Faulted Circuit Indicators

Overhead/Underground System Voltage Trip Logic/Reset Options Indication Options Mounting Requirements

FCI Application/SpecificationConsiderations

Page 13: FCI Seminar

Faulted Circuit Indicators

Overhead and Underground Applications Research protective devices in use Determine customer’s strategy

• (Temporary vs Permanent Fault Indication) Consider Backfeed and Inrush Conditions Minimum Load Current Expected

• Acceptable Models and Reset Strategy

FCI Application SummaryFCI Application Summary

Page 14: FCI Seminar

Faulted Circuit Indicators Product Overview

The Most Complete FCI Line

In The Industry!!!

All Under Fisher Pierce Brand

Page 15: FCI Seminar

Faulted Circuit Indicators

Overhead FCIsOverhead FCIs

Page 16: FCI Seminar

Faulted Circuit Indicators Overhead Overhead ApplicationsApplications

Features Have It? FCI Series

Adaptive Trip Yes 1548

Hi-Lo Trip Yes OLMTL, OLMVOL, OLMVL, OLMVF

Current Reset Yes 1514 & 1515

Time Reset Yes 1548, 1514, 1515, OLMTL, OLMVOL

Voltage Reset Yes OLMVL & OLMVF

Manual Reset Yes ALL

Single Phase Yes 1548, 1514, OLMTL

Three-Phase (C.R) Yes 1515

LED Type Yes 1548, 1514, 1515, OLMTL, OLMVL, OLMVOL

Strobe Light Yes 1548

Flag Type Yes 1548, 1514, 1515, OLMVF

Radio Transmitter Yes 1548 & 1514

Page 17: FCI Seminar

Faulted Circuit Indicators

1548 Series Overhead Applicationsw/ Adaptive Trip Logic

Minimizes Stocking and Application Problems

Current, Time and Manual Reset Options

Inrush Restraint Replaceable and Non-

replaceable Battery Options

Flag, Strobe & LED Display Temporary Fault

Indication Option Integral Radio

Transmitter Option

Overhead IndicatorsOverhead Indicators

Hotstick mounting with automatic torque limiting.

Page 18: FCI Seminar

Faulted Circuit Indicators

Temporary Fault Detection• Recommended for circuits with fast protection settings

Permanent fault indication is comprised of 4 RED LED’s, flashing 30 times per minute

Temporary fault indication is comprised of 1 AMBER LED, flashing 15 times per minute for 4 hrs.8, 12, 24 hr timed

reset options

Overhead Indicators – 1548 SeriesOverhead Indicators – 1548 Series

Page 19: FCI Seminar

Faulted Circuit Indicators

OLM Series Overhead Applicationsw/ High/Low Trip Logic

Voltage, Time and Manual Reset Options

Inrush Restraint Flag & LED Display

Overhead Indicators

Universal Hotstick-Clamp Mounting

Page 20: FCI Seminar

Faulted Circuit Indicators

Underground FCIsUnderground FCIs

Page 21: FCI Seminar

Faulted Circuit Indicators Underground Underground ApplicationsApplications

Features Have It? FCI SeriesAdaptive Trip Yes 1547

Hi-Lo Trip Yes TPMVF, TPMVL, TPMVOL, TPMTL, UCMTL

Current Reset Yes 1547, 1514, 1515

Time Reset Yes 1547,1541,1542,1543,1514,1515,TPMVOL,TPMTL,UCMTL

Voltage Reset Yes 1516, TPMVL, TPMVF

Manual Reset Yes ALL

Directional Fault Yes 1514-45102

Single Phase Yes 1547, 1541,1514,1516,TPMVF,TPMVL,TPMVOL,TPMTL,UCMTL

Three-Phase Yes 1515, 1543

Test Point Yes TPMVF, TPMVL, TPMVOL, TPMTL

LED Type Yes 1547.1541,1542,1543,1514,1515,TPMVL,TPMVOL,TPMTL,UCMTL

Flag Type Yes 1547. 1514, 1515, 1516, TPMVF

Audible Alarm Yes 1541, 1542, 1543

SCADA Contacts Yes 1547, 1514, 1516

Fiber Optic Display Yes 1547,1541,1542,1543, 1514,1515,TPMVL,TPMVOL,TPMTL,UCMTL

Radio Transmitter Yes 1547, 1514, 1515

Page 22: FCI Seminar

Faulted Circuit Indicators

1547 Series

Underground Applicationsw/ Adaptive Trip Logic

Minimizes Stocking and Application Problems

Current, Time and Manual Reset Options

Inrush Restraint Flag, LED Display or

Remote LED: Fiber Optic Option SCADA output Option Integral Radio

Transmitter Option

Underground Indicators

Indicator Mount Options Clamp Hotstick Bracket/Surface Window/Flush Tie-Wrap

Page 23: FCI Seminar

Faulted Circuit Indicators

Underground Applicationsw/Fixed Current Trip Logic

Fixed Current Trip (50 to 1500 Amps)

Current, Time and Manual Reset Options

Inrush Restraint Flag, LED Display or

Remote LED: Fiber Optic Option SCADA output Option Integral Radio

Transmitter Option Options Single Phase (1514)

Three Phase (1515)

1514 & 1515 Series Underground IndicatorsUnderground Indicators

Indicator Mount Options Clamp Hotstick Bracket/Surface Window/Flush Tie-Wrap

Page 24: FCI Seminar

Faulted Circuit Indicators

1514-45102

Underground Faulted Circuit IndicatorsUnderground Faulted Circuit Indicators

Indicator Mount Options Clamp Hotstick Bracket/Surface Window/Flush Tie-Wrap

Underground Applicationsw/Directional Network

With SmartNet Learning logic to determine the direction of faulted current

Programmable Fixed Current Trip

Automatic reset of fault indication; manual reset also available.

LED Display or Remote LED

Page 25: FCI Seminar

Faulted Circuit Indicators

Underground IndicatorsUnderground Indicators

Underground Applications w/Automatic Time Reset

Fixed Current Trip (50 to 1500 Amps)

Time and Manual Reset Options

Inrush restraint Replaceable and Non-

replaceable Battery Options

Integral LED Display or Remote LED Fiber Optic Option Audible Option

Hotstick mounting with adjustable clamp

Options• Single Phase (1541) • Two Phase (1542) • Three Phase (1543)

1541, 1542 & 1543 Series

Page 26: FCI Seminar

Faulted Circuit Indicators

1516 Series

Underground Applicationsw/ Automatic Secondary

Voltage Reset Fixed Current Trip

(50 to 1500 Amps) Voltage and Manual

Reset Options Inrush Restraint Integrated or Remote Flag

Display SCADA output Option

Underground IndicatorsUnderground Indicators

Indicator Mount Options Hotstick Bracket/Surface Window/Flush Tie-Wrap

Page 27: FCI Seminar

Faulted Circuit Indicators

TPM Series Underground Applicationsw/ High/Low Trip Logic

Voltage, Time and Manual Reset Options

Inrush Restraint Flag & LED Display

Removable Fiber Optic Cable

Underground IndicatorsUnderground Indicators

Test Point Mounting Mounts directly to 200 and 600 amp

elbows with capacitive test point

Page 28: FCI Seminar

Faulted Circuit Indicators

UCMTLUnderground Applicationsw/ High/Low Trip Logic

Time and Manual Reset Options LED Display Removable Fiber

Optic Cable

URD Cable Mounted with Universal Hotstick-Clamp

Underground Faulted Circuit IndicatorsUnderground Faulted Circuit Indicators

Page 29: FCI Seminar

Faulted Circuit Indicators

• Determine the Energized Status of Underground Distribution Circuits

• Self-Powered Sensor Connected to Neon Light that Flashes When Energized

– Flash Rate is Proportional to System kV

– Dual Viewing Port

• Mounts on 200/600 A Elbows/Splices Equipped With IEEE 386 Capacitive Test Point

• Hotstick Operable

V2

Test Point Voltage IndicatorTest Point Voltage Indicator

Page 30: FCI Seminar

Faulted Circuit Indicators

• VOLTAGE INDICATORS 5-35kV

• Test Box - V2TB• Mount V2 on to Test Point

Provision on Tester

• Push Test Button to Energize Test Point Green LED Should Flash V2 Should Flash

GreenLED V2TB

Test Point ProvisionTest Button

FlashingNeonLight

HotstickOperable

EPDMHousing

V2

Test Point Voltage Indicator

Page 31: FCI Seminar

Faulted Circuit Indicators

PD35• Used in Determining Correct Phasing and Energized

Status of Single / Three-phase Underground Systems

• Used on 200/600 A Elbows/Splices Equipped With IEEE 386 Capacitive Test Point

• Eliminates Exposure to High Voltage

• Hotstick Operable

• Battery Powered (9Volt)

Phase & Voltage Indicator Test Tool 5 – Phase & Voltage Indicator Test Tool 5 – 35kV35kV

Page 32: FCI Seminar

Faulted Circuit Indicators

Black Lead to Connect Metered

Probe to Gnd

Non-MeteredProbe

Red PhaseLead to ConnectBetween Probes

MeteredProbe

Phase & Voltage Indicator Test Tool 5 – Phase & Voltage Indicator Test Tool 5 – 35kV35kV

Page 33: FCI Seminar

Faulted Circuit Indicators

• Attach Hotstick to Meter Probe and Connect Gnd. Lead

• Switch Meter to ON

• Touch Metered Probe to Test Point

• Phase 1 LED will Illuminate When Circuit is Energized

TO TEST FOR VOLTAGE

Phase & Voltage Indicator Test Tool 5 – Phase & Voltage Indicator Test Tool 5 – 35kV35kV

Page 34: FCI Seminar

Faulted Circuit Indicators

1. Follow Voltage Test Procedure2. Attach Non-Metered Probe to

Additional Hotstick3. Connect Probes Using Red Lead4. Touch Probes to Test Points on

Different Phases5. Phase 1 and 2 LEDs Illuminate

Showing Energized Circuits6. If IN-PHASE the Green LED will

Illuminate. If OUT of PHASE the Red LED will Illuminate

TO TEST FOR PROPER PHASING

Phase & Voltage Indicator Test Tool 5 – Phase & Voltage Indicator Test Tool 5 – 35kV35kV

Page 35: FCI Seminar

Faulted Circuit Indicators

Automation & SmartGrid Automation & SmartGrid ApplicationsApplications

Smartlink 5000 FCI Monitor & Control System

Radio Faulted indicators 1548, 1547 & 1514

1570 Transmitters

1560 Receivers

Page 36: FCI Seminar

Faulted Circuit Indicators

Monitoring and Control System

Utilizing Cellular Communications

Application: Fault Monitoring of Radio Equipped Fault Indicators, Switch Control, Capacitor Switching

Reduces Restoration

Time!

Smartlink 5000Smartlink 5000

Page 37: FCI Seminar

Faulted Circuit Indicators

SmartLink™ 5000

Nationwide cellular networksSmart GridSmart Grid

1548 Radio FCI

• Customer Connections & Applications

• Service & Support

Page 38: FCI Seminar

Faulted Circuit Indicators

• Model 1560-1 Handheld Receiver

• LED and Audible Display of Phase a,b,c

• 9 volt replaceable battery

• Model 1560-2 RTU Interface Receiver

• powered from customer’s RTU (9-12Vdc)

• Interfaces to RTU with 1, 3, 4 N.O. contacts

Radio Faulted Circuit IndicatorRadio Faulted Circuit Indicator

1560-1 1560-2

Page 39: FCI Seminar

Faulted Circuit Indicators

Overhead Installation

System:1: 1548 Radio FCI2: 1560 Receiver3: AMI Gateway/RTU

Radio Faulted Circuit Indicator Wireless Radio Faulted Circuit Indicator Wireless SystemSystem

Page 40: FCI Seminar

Faulted Circuit Indicators

• Model 1570-1Control/Transmitter• 9 volt replaceable battery• Low profile pad mount transmitter, SCADA FCI interface

Radio Faulted Circuit IndicatorRadio Faulted Circuit Indicator

1570-1

Page 41: FCI Seminar

Faulted Circuit Indicators

System:1: 1547 or 1514 Radio FCI2: 1570 Transmitter3: 1560 Receiver4: AMI Gateway/RTU

Underground Installation

Radio Faulted Circuit Indicator Wireless Radio Faulted Circuit Indicator Wireless SystemSystem

Page 42: FCI Seminar

Faulted Circuit Indicators

Line truck application, monitoring radio indicating fault indicators with a hand-held receiver.

Pad mount cabinet fault indicator installation with radio and local signaling capability.

Radio Indicator Wireless SystemRadio Indicator Wireless System

Page 43: FCI Seminar

Faulted Circuit Indicators

Thank YouThank You