Faulted Circuit Indicators
Generating Station
Step-Up Transformer Industrial Customer
Transmission Substation(Bulk-Power Switching)
Step-Down Transformer
Industrial CustomerIndustrial Customer
Distribution Substation
Step-DownTransformer
CommercialCommercialCustomerCustomer
Residential Customer
Residential
Customer
20 KV138 KV
4 KV
34.5 KV
440 V
13.8 KV
220/440 V
120/240 V
120/240 V13.8 KV
Fisher Pierce
Locations where our Faulted Circuit Indicator products can be applied on the electrical system
Faulted Circuit Indicators
Electrical Fault Locating Electrical Fault Locating MethodsMethods
• Customer calls with outage
• Line patrolling after fault
• Electronic recloser or breaker controls provide fault location
• Cable thumping for underground cables
• Fault chasing
• Predictive maintenance switching
• Fault Indicators
Faulted Circuit Indicators
The Benefits of Using FCIsThe Benefits of Using FCIs• Aid in the location and isolation of the faulted cable
or equipment
• Reduces system down time and restoration costs
• Reduces lost revenue
• Increases customer service levels
• Improves personnel safety & system reliability
• Reduces stresses on circuit cable and components through efficient sectionalizing
• Minimizes potential destruction of customer owned sensitive equipment
Faulted Circuit Indicators
How FCIs OperateHow FCIs Operate
• During a fault, high fault current is present from the source of the fault location.
• Installed FCIs on the system sense this condition and trip ( LED, Flag, Strobe, Radio Signal, etc.).
• Troublemen look for fault indicators and follow to identify the location of the fault.
Faulted Circuit Indicators
How FCIs Operate (cont’d)How FCIs Operate (cont’d)• Locate the last tripped FCI and the first untripped
FCI, the fault has been isolated to a specific section of the circuit.
• Crews will switch out the faulted segment and restore power to the remaining part of the circuit.
• The faulted segment is then repaired.
• Some Examples of a typical URD Circuits installed with FCIs:
Faulted Circuit Indicators
Switchgear 1
Switchgear 2
R1NC NC
NC
NO
R2Voltage ResetFault Indicator
FAULT INDICATOR OPERATIONFAULT INDICATOR OPERATION
Faulted Circuit Indicators
R1
Switchgear 1
NC NC
NC
NO
Switchgear 2
R2
Breaker Locks Out
Loss of Voltage Detected
Only the FCIs That Detect Overcurrent will Indicate
Voltage ResetFault Indicator
FAULT INDICATOR OPERATIONFAULT INDICATOR OPERATION
Faulted Circuit Indicators
Typical InstallationsTypical Installations• Overhead Conductor
• Riser Pole or Dip Pole
• Subsurface or Padmount Transformer/Switchgear
• Junction Box, Manhole Applications
• Sectionalizing Cabinets
Faulted Circuit Indicators
Where are FCIs located ?Where are FCIs located ?
Faulted Circuit Indicators
Where are FCIs located ?Where are FCIs located ?
Faulted Circuit Indicators
Overhead/Underground System Voltage Trip Logic/Reset Options Indication Options Mounting Requirements
FCI Application/SpecificationConsiderations
Faulted Circuit Indicators
Overhead and Underground Applications Research protective devices in use Determine customer’s strategy
• (Temporary vs Permanent Fault Indication) Consider Backfeed and Inrush Conditions Minimum Load Current Expected
• Acceptable Models and Reset Strategy
FCI Application SummaryFCI Application Summary
Faulted Circuit Indicators Product Overview
The Most Complete FCI Line
In The Industry!!!
All Under Fisher Pierce Brand
Faulted Circuit Indicators
Overhead FCIsOverhead FCIs
Faulted Circuit Indicators Overhead Overhead ApplicationsApplications
Features Have It? FCI Series
Adaptive Trip Yes 1548
Hi-Lo Trip Yes OLMTL, OLMVOL, OLMVL, OLMVF
Current Reset Yes 1514 & 1515
Time Reset Yes 1548, 1514, 1515, OLMTL, OLMVOL
Voltage Reset Yes OLMVL & OLMVF
Manual Reset Yes ALL
Single Phase Yes 1548, 1514, OLMTL
Three-Phase (C.R) Yes 1515
LED Type Yes 1548, 1514, 1515, OLMTL, OLMVL, OLMVOL
Strobe Light Yes 1548
Flag Type Yes 1548, 1514, 1515, OLMVF
Radio Transmitter Yes 1548 & 1514
Faulted Circuit Indicators
1548 Series Overhead Applicationsw/ Adaptive Trip Logic
Minimizes Stocking and Application Problems
Current, Time and Manual Reset Options
Inrush Restraint Replaceable and Non-
replaceable Battery Options
Flag, Strobe & LED Display Temporary Fault
Indication Option Integral Radio
Transmitter Option
Overhead IndicatorsOverhead Indicators
Hotstick mounting with automatic torque limiting.
Faulted Circuit Indicators
Temporary Fault Detection• Recommended for circuits with fast protection settings
Permanent fault indication is comprised of 4 RED LED’s, flashing 30 times per minute
Temporary fault indication is comprised of 1 AMBER LED, flashing 15 times per minute for 4 hrs.8, 12, 24 hr timed
reset options
Overhead Indicators – 1548 SeriesOverhead Indicators – 1548 Series
Faulted Circuit Indicators
OLM Series Overhead Applicationsw/ High/Low Trip Logic
Voltage, Time and Manual Reset Options
Inrush Restraint Flag & LED Display
Overhead Indicators
Universal Hotstick-Clamp Mounting
Faulted Circuit Indicators
Underground FCIsUnderground FCIs
Faulted Circuit Indicators Underground Underground ApplicationsApplications
Features Have It? FCI SeriesAdaptive Trip Yes 1547
Hi-Lo Trip Yes TPMVF, TPMVL, TPMVOL, TPMTL, UCMTL
Current Reset Yes 1547, 1514, 1515
Time Reset Yes 1547,1541,1542,1543,1514,1515,TPMVOL,TPMTL,UCMTL
Voltage Reset Yes 1516, TPMVL, TPMVF
Manual Reset Yes ALL
Directional Fault Yes 1514-45102
Single Phase Yes 1547, 1541,1514,1516,TPMVF,TPMVL,TPMVOL,TPMTL,UCMTL
Three-Phase Yes 1515, 1543
Test Point Yes TPMVF, TPMVL, TPMVOL, TPMTL
LED Type Yes 1547.1541,1542,1543,1514,1515,TPMVL,TPMVOL,TPMTL,UCMTL
Flag Type Yes 1547. 1514, 1515, 1516, TPMVF
Audible Alarm Yes 1541, 1542, 1543
SCADA Contacts Yes 1547, 1514, 1516
Fiber Optic Display Yes 1547,1541,1542,1543, 1514,1515,TPMVL,TPMVOL,TPMTL,UCMTL
Radio Transmitter Yes 1547, 1514, 1515
Faulted Circuit Indicators
1547 Series
Underground Applicationsw/ Adaptive Trip Logic
Minimizes Stocking and Application Problems
Current, Time and Manual Reset Options
Inrush Restraint Flag, LED Display or
Remote LED: Fiber Optic Option SCADA output Option Integral Radio
Transmitter Option
Underground Indicators
Indicator Mount Options Clamp Hotstick Bracket/Surface Window/Flush Tie-Wrap
Faulted Circuit Indicators
Underground Applicationsw/Fixed Current Trip Logic
Fixed Current Trip (50 to 1500 Amps)
Current, Time and Manual Reset Options
Inrush Restraint Flag, LED Display or
Remote LED: Fiber Optic Option SCADA output Option Integral Radio
Transmitter Option Options Single Phase (1514)
Three Phase (1515)
1514 & 1515 Series Underground IndicatorsUnderground Indicators
Indicator Mount Options Clamp Hotstick Bracket/Surface Window/Flush Tie-Wrap
Faulted Circuit Indicators
1514-45102
Underground Faulted Circuit IndicatorsUnderground Faulted Circuit Indicators
Indicator Mount Options Clamp Hotstick Bracket/Surface Window/Flush Tie-Wrap
Underground Applicationsw/Directional Network
With SmartNet Learning logic to determine the direction of faulted current
Programmable Fixed Current Trip
Automatic reset of fault indication; manual reset also available.
LED Display or Remote LED
Faulted Circuit Indicators
Underground IndicatorsUnderground Indicators
Underground Applications w/Automatic Time Reset
Fixed Current Trip (50 to 1500 Amps)
Time and Manual Reset Options
Inrush restraint Replaceable and Non-
replaceable Battery Options
Integral LED Display or Remote LED Fiber Optic Option Audible Option
Hotstick mounting with adjustable clamp
Options• Single Phase (1541) • Two Phase (1542) • Three Phase (1543)
1541, 1542 & 1543 Series
Faulted Circuit Indicators
1516 Series
Underground Applicationsw/ Automatic Secondary
Voltage Reset Fixed Current Trip
(50 to 1500 Amps) Voltage and Manual
Reset Options Inrush Restraint Integrated or Remote Flag
Display SCADA output Option
Underground IndicatorsUnderground Indicators
Indicator Mount Options Hotstick Bracket/Surface Window/Flush Tie-Wrap
Faulted Circuit Indicators
TPM Series Underground Applicationsw/ High/Low Trip Logic
Voltage, Time and Manual Reset Options
Inrush Restraint Flag & LED Display
Removable Fiber Optic Cable
Underground IndicatorsUnderground Indicators
Test Point Mounting Mounts directly to 200 and 600 amp
elbows with capacitive test point
Faulted Circuit Indicators
UCMTLUnderground Applicationsw/ High/Low Trip Logic
Time and Manual Reset Options LED Display Removable Fiber
Optic Cable
URD Cable Mounted with Universal Hotstick-Clamp
Underground Faulted Circuit IndicatorsUnderground Faulted Circuit Indicators
Faulted Circuit Indicators
• Determine the Energized Status of Underground Distribution Circuits
• Self-Powered Sensor Connected to Neon Light that Flashes When Energized
– Flash Rate is Proportional to System kV
– Dual Viewing Port
• Mounts on 200/600 A Elbows/Splices Equipped With IEEE 386 Capacitive Test Point
• Hotstick Operable
V2
Test Point Voltage IndicatorTest Point Voltage Indicator
Faulted Circuit Indicators
• VOLTAGE INDICATORS 5-35kV
• Test Box - V2TB• Mount V2 on to Test Point
Provision on Tester
• Push Test Button to Energize Test Point Green LED Should Flash V2 Should Flash
GreenLED V2TB
Test Point ProvisionTest Button
FlashingNeonLight
HotstickOperable
EPDMHousing
V2
Test Point Voltage Indicator
Faulted Circuit Indicators
PD35• Used in Determining Correct Phasing and Energized
Status of Single / Three-phase Underground Systems
• Used on 200/600 A Elbows/Splices Equipped With IEEE 386 Capacitive Test Point
• Eliminates Exposure to High Voltage
• Hotstick Operable
• Battery Powered (9Volt)
Phase & Voltage Indicator Test Tool 5 – Phase & Voltage Indicator Test Tool 5 – 35kV35kV
Faulted Circuit Indicators
Black Lead to Connect Metered
Probe to Gnd
Non-MeteredProbe
Red PhaseLead to ConnectBetween Probes
MeteredProbe
Phase & Voltage Indicator Test Tool 5 – Phase & Voltage Indicator Test Tool 5 – 35kV35kV
Faulted Circuit Indicators
• Attach Hotstick to Meter Probe and Connect Gnd. Lead
• Switch Meter to ON
• Touch Metered Probe to Test Point
• Phase 1 LED will Illuminate When Circuit is Energized
TO TEST FOR VOLTAGE
Phase & Voltage Indicator Test Tool 5 – Phase & Voltage Indicator Test Tool 5 – 35kV35kV
Faulted Circuit Indicators
1. Follow Voltage Test Procedure2. Attach Non-Metered Probe to
Additional Hotstick3. Connect Probes Using Red Lead4. Touch Probes to Test Points on
Different Phases5. Phase 1 and 2 LEDs Illuminate
Showing Energized Circuits6. If IN-PHASE the Green LED will
Illuminate. If OUT of PHASE the Red LED will Illuminate
TO TEST FOR PROPER PHASING
Phase & Voltage Indicator Test Tool 5 – Phase & Voltage Indicator Test Tool 5 – 35kV35kV
Faulted Circuit Indicators
Automation & SmartGrid Automation & SmartGrid ApplicationsApplications
Smartlink 5000 FCI Monitor & Control System
Radio Faulted indicators 1548, 1547 & 1514
1570 Transmitters
1560 Receivers
Faulted Circuit Indicators
Monitoring and Control System
Utilizing Cellular Communications
Application: Fault Monitoring of Radio Equipped Fault Indicators, Switch Control, Capacitor Switching
Reduces Restoration
Time!
Smartlink 5000Smartlink 5000
Faulted Circuit Indicators
SmartLink™ 5000
Nationwide cellular networksSmart GridSmart Grid
1548 Radio FCI
• Customer Connections & Applications
• Service & Support
Faulted Circuit Indicators
• Model 1560-1 Handheld Receiver
• LED and Audible Display of Phase a,b,c
• 9 volt replaceable battery
• Model 1560-2 RTU Interface Receiver
• powered from customer’s RTU (9-12Vdc)
• Interfaces to RTU with 1, 3, 4 N.O. contacts
Radio Faulted Circuit IndicatorRadio Faulted Circuit Indicator
1560-1 1560-2
Faulted Circuit Indicators
Overhead Installation
System:1: 1548 Radio FCI2: 1560 Receiver3: AMI Gateway/RTU
Radio Faulted Circuit Indicator Wireless Radio Faulted Circuit Indicator Wireless SystemSystem
Faulted Circuit Indicators
• Model 1570-1Control/Transmitter• 9 volt replaceable battery• Low profile pad mount transmitter, SCADA FCI interface
Radio Faulted Circuit IndicatorRadio Faulted Circuit Indicator
1570-1
Faulted Circuit Indicators
System:1: 1547 or 1514 Radio FCI2: 1570 Transmitter3: 1560 Receiver4: AMI Gateway/RTU
Underground Installation
Radio Faulted Circuit Indicator Wireless Radio Faulted Circuit Indicator Wireless SystemSystem
Faulted Circuit Indicators
Line truck application, monitoring radio indicating fault indicators with a hand-held receiver.
Pad mount cabinet fault indicator installation with radio and local signaling capability.
Radio Indicator Wireless SystemRadio Indicator Wireless System
Faulted Circuit Indicators