Transcript
Page 1: Explorer - Thorn Lighting · 2010-02-16 · Explorer SelfTest, Explorer Project and Explorer Vision Just like fire protection systems, emergency lighting is potentially life saving

ExplorerComprehensive testing for emergency lighting

Page 2: Explorer - Thorn Lighting · 2010-02-16 · Explorer SelfTest, Explorer Project and Explorer Vision Just like fire protection systems, emergency lighting is potentially life saving

When an incident occurs and power is lost, emergency lighting helps to guide people safely and calmly from the building while enabling the emergency services to do their work

In a modern building environment, light is taken for granted. People trust it as they go about their lives. It promotes comfort, security and efficiency.

Page 3: Explorer - Thorn Lighting · 2010-02-16 · Explorer SelfTest, Explorer Project and Explorer Vision Just like fire protection systems, emergency lighting is potentially life saving

Emergency lighting testing – Integrated safety provides comfort of use, security and efficiency

Normal Use

The lighting scheme with integrated emergency luminaires is designed for optimal performance, efficiency and comfort. The emergency luminaire versions blend into the overall scene.

Thorn Explorer technology brings intelligence to the emergency lighting system and enables owners and operators to ensure that their emergency lighting system is fully tested and ready to operate at optimum performance.

A comprehensive, integrated emergency lighting package, Explorer, provides the peace of mind and full confidence of regulatory compliance. This fully automatic, economic testing system will satisfy the needs of the most demanding of authorities and produce comprehensive documentation, at the ‘touch of a button’.

PEC Explorer reflects Thorn’s intentions to deliver ‘Performance’, ‘Efficiency’ and ‘Comfort’ (PEC) in all of its products. The PEC programme concentrates on delivering ‘quality’ in a lighting installation.

Performance: The emergency luminaires in the system provide emergency lighting and signage in accordance with EN1838

Efficiency: The system automatically tests the luminaires in accordance with EN62034

Comfort: Peace of mind that no manual testing is required and that the test records are automatically stored for two years. Luminaires are automatically identified when repair is required.

MenloSoft SR

Emergency Operation

Emergency luminaires are designed to illuminate anti-panic areas and escape routes to the correct lighting levels and the exit signage to indicate the way out.

3

Page 4: Explorer - Thorn Lighting · 2010-02-16 · Explorer SelfTest, Explorer Project and Explorer Vision Just like fire protection systems, emergency lighting is potentially life saving

4

Explorer SelfTest Explorer Project Explorer Vision

Automatic testing: Yes Yes Yes

EN62034 compliant: Yes Yes Yes

Fault indication on luminaire: Locally via LED Centrally logged on Control Panel Centrally logged on PC and Control Panels

Fault reports generated: Manually Printed or via SMS text Printed or e-mailed

Max. no of luminaires per system: 1 256 (with extenders) 5000

Communication cabling required: No Yes Yes / Computer network

Programmable: No Yes Yes

Addressable: No Yes Yes

Typical applications: Small areas or refurbishment projects where additional cabling is impractical. For example: offices, small shopping centres, restaurants, public houses, hotels and guest houses, medical centres

Small and medium sized projects where visual inspection of luminaires is impractical or undesirable. For example: universities, schools and colleges, museums, shopping centres, offices, industrial facilities

Large projects where programmable testing of large numbers of luminaires is required. For example: hospitals, universities, museums, airports, supermarkets and hypermarkets, industrial facilities

SelfTestMany challenges – which option is best?

Automated and cost effective testing of Emergency Lighting: Explorer SelfTest, Explorer Project and Explorer Vision

Just like fire protection systems, emergency lighting is potentially life saving but worthless and hazardous if the equipment is not properly maintained. As a consequence there are increasingly stringent legal requirements to regularly inspect, test and maintain emergency lighting in workplaces or public buildings.

Explorer, the Thorn Lighting Emergency Test product range, provides automated testing of emergency luminaires that is fully compliant with European Standards. This offers complete peace of mind and safety without the need for costly and time-consuming manual testing by a competent person, which is required for the most basic of conventional self-contained emergency luminaires.

Your emergency lighting needs to be regularly tested to check that it is working properly (and to conform with the requirements of the regulations). A functional test (where the luminaire changes over to emergency operation) must be performed every month. A full duration test is required annually, to confirm that the battery has sufficient energy to operate the luminaire in the emergency mode for 3 hours.

The Explorer testing system automatically checks functional testing weekly and duration testing annually, in accordance with the requirements of EN62034.

Explorer has been designed with three options to suit varying requirements and budgets. Consult the quick comparison table below to help decide which option is best for you.

Summary of benefits• Cost effective compliance

with emergency lighting testing regulations

• Explorer SelfTest performs the testing automatically for you – only requiring you to walk around the building once per month and record that all is ok (or any failures)

• Explorer Project and Vision performs all of the testing and records the results

Project

Vision

Page 5: Explorer - Thorn Lighting · 2010-02-16 · Explorer SelfTest, Explorer Project and Explorer Vision Just like fire protection systems, emergency lighting is potentially life saving

121

2

3

4

56

7

8

9

10

11

5

Component LED Indicator Status

Battery Green Steady Healthy

Red Slow Flash Low

Red Rapid Not charging

Lamp Green Steady Healthy

Red Steady Failure

Test LED Indicator Duration Frequency EN requirement

Function Test(Energise luminaire from battery briefly to simulate mains failure)

Green Rapid Flash 30 seconds Weekly Monthly

Duration Test(Energise luminaire for full rated duration)

Green Slow Flash 1 or 3 hours Annually Annually

Cathode heating Boost starting

A bi-colour LED (red and green) on the luminaire indicates status as it monitors and automatically tests its emergency functions at intervals compliant with legislation. Easy to install and requiring no additional cabling, SelfTest provides simple and reliable standalone automatic testing, eliminating the need for costly manual testing by a competent person.

• Self testing in accordance with EN62034

• Faster than average recharge time: 10-15 hours

• 3 hours operation, this gives you the ability to re-enter the building after an evacuation

• Bi-colour LED (red and green) to provide clear status indication

• Boost starting technology gives higher lumen output during most critical switchover phase to ensure greater visibility of potential danger

• AC operation of lamps to prevent lamp end blackening. The visual benefit is that the lamps look like new and the luminaire continues to look attractive.

SelfTest

Project

Vision

Explorer SelfTest

Many of the Thorn ranges come with Explorer SelfTest as standard, with an integral diagnostic microprocessor to monitor and automatically test to the recommended schedule

• Cathode heating during emergency operation prolongs emergency lamp life to that of normal fluorescent lamps, reducing lamp replacements

• Adaptive mode: learns to test while the building is unoccupied, providing more comfort to the user, removing the distraction of a test

• Regulated electronic charging circuit

• Deep discharge protection to prevent battery damage, prolonging battery life and minimising maintenance cycles

• Automatic commissioning – no programming required

• Function and duration testing is staggered over the month, minimising risk

Most Thorn Lighting luminaires are enabled for use with Explorer SelfTest, Explorer Project and Explorer Vision

Page 6: Explorer - Thorn Lighting · 2010-02-16 · Explorer SelfTest, Explorer Project and Explorer Vision Just like fire protection systems, emergency lighting is potentially life saving

6

XP128 Controller

DALI

Emergency operation

Explorer ProjectUp to 128 emergency luminaires

Intelligent emergency lighting rises to the challenge

Explorer Project is the perfect emergency lighting monitoring system for medium-size installations where low overheads and full compliance are essential. At the heart of the automatic monitoring system is the XP128 controller which provides quick and easy visual supervision over all emergency luminaires without special training.

Page 7: Explorer - Thorn Lighting · 2010-02-16 · Explorer SelfTest, Explorer Project and Explorer Vision Just like fire protection systems, emergency lighting is potentially life saving

L N

Gnd24V XPPSU

PE N L A-D

1

A-D

2

B-D

1

B-D

2

TxD

RxD

Gnd

K11

K12

K14

K21

K22

K24

K31

K32

K34

Gnd

RxD

TxD

Gnd XPGSMExplorer Project GSM Module

24V

SelfTest

Project

Vision

• The XP128 controller supervises 128 luminaires over two channels of up to 64 luminaires each

• Touch screen for easy programming

• Can be expanded to 256 luminaires via XPX64 modules (see pages 8 and 9)

• Infra-red port can up-load reports to hand-held printers

• Volt-free contacts enable signalling to remote locations indication or interface to a BMS (building management system)

• GSM module (XPGSM) can report faults via text message to mobile phones and also supports ‘one person commissioning’

The luminaires contain a module that communicates to the XP128 controller which signals over wires to tell them to perform their weekly functional tests and annual duration tests. To maintain integrity, they are asked to do these tests in groups at periods of minimum risk, in accordance with the requirements.

Bus wiring to luminaires and XPX64 expander modules 300m max – use 1.5mm2 twisted pair, equivalent to Belden 9411

Mains

Mains

max. 250m/1.5mm2/ max. 64 Luminaires

Three volt free contacts to signal system status

max. 24V A

C/D

C m

ax.2A

K11-K14 NO K11-K12 NCK21-K24 NO K21-K22 NCK31-K34 NO K31-K32 NCNO: nomally open (SchlleBer)NC: normally closed (Offner)

Mains Mains Mains Mains MainsMains

max. 250m/1.5mm2/ max. 64 Luminaires

Mains Mains Mains Mains MainsMains

Page 8: Explorer - Thorn Lighting · 2010-02-16 · Explorer SelfTest, Explorer Project and Explorer Vision Just like fire protection systems, emergency lighting is potentially life saving

PE N L A-D

1

A-D

2

B-D

1

B-D

2

Tx

Rx

Gnd

K11

K12

K14

K21

K22

K24

K31

K32

K34

*) *) *) *) *) *)

*) *) *) *) *) *)

*) *) *) *) *) *)

*) *) *) *) *) *)

*) *) *) *)

out D

1

out D

2

in D

1

N L

in D

2

XPX64

out D

1

out D

2

in D

1

N L

in D

2

XPX64

out D

1

out D

2

in D

1

N L

in D

2

XPX64

*)

*)

*)

...................................

...........................

...........................

...........................

.............................

...............................................................................................................................

......

......

......

......

...

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

......

......

......

......

......

......

....

......

......

..

................

..........................

...................

XP128 Controller

GSM Module

XP Extender

8

Explorer Project – up to 256 emergency luminaires Simple to operate and configure

Expanding the Explorer Project to work with more than 128 emergency luminaires

In this configuration, channel ‘B’ becomes a ‘signaling bus’ and is used for communication to the XPX64 extender modules. There must be no emergency luminaires directly connected to this channel in this mode.

This helps with the wiring planning as there can be up to 300m of cable between the XP128 controller and the XPX64. The maximum distance from the XPX64 to the furthest luminaire is another 300m. If this still causes planning difficulties, there is a kit to extend the distances a further 300m (XP300m+)

If you still need more capacity see Explorer Vision, for up to 5000 luminaires!

Third floor

Second floor

First floor

300m max to last XP-Extender

RS232 (max 3m)

Mains

Loop 264 luminaires300m max from XP-Extender

Loop 364 luminaires300m max from XP-Extender

Loop 464 luminaires300m max from XP-Extender

GSM Module

XP Extender

XP Extender

XP Extender

XP128 Controller

Loop 164 luminaires300m max(furthest luminaire 300m away)

Ground floor

The diagram below shows the luminaires connected in a string. This is often an easy method of installation, but you soon reach the 300m maximum for the data cables.

Use a ‘star connection’ or make a branch off from the main run to achieve the cable run to your furthest luminaire within the cable limit. Optional isolators break these runs into easily managed segments (of 20 luminaires) to speed up commissioning.

Explorer Project uses eDALI and DALI signalling on the bus, which means that it works with all Thorn addressable emergency luminaires and other DALI compatible emergency luminaires.

Typical installation for up to 256 luminaires

Isolator every 20 luminaires speeds up commissioning

Can be star connected

max. 300m 1.5mm2

max. 300m/1.5mm2/ max. 64 EM - Ballasts

Group 1

Group 2

Group 3

Group 4

max. 300m/1.5mm2/ max. 64 EM - Ballasts

max. 300m/1.5mm2/ max. 64 EM - Ballasts

max. 300m/1.5mm2/ max. 64 EM - Ballasts

Page 9: Explorer - Thorn Lighting · 2010-02-16 · Explorer SelfTest, Explorer Project and Explorer Vision Just like fire protection systems, emergency lighting is potentially life saving

LuminairesAddress CallibrationCheck

Luminaire address group 1 (10 luminaires)

Next >

Floor 1, north entry

auto-search . . .

location:

logical

address:

Cancel

assign

< Previous

1

Test

all groups similar

Start function test

start function test now ...

Funct. test Duration test Relay

also see test book

every Thur, Fri16 : 00 : 00at oclock.

?

RelaybuzzerAssignments AssStatus

Rela

y 1

OK

Factory settings

Lamp fault

Battery fault

Comm. problem

Test error, time out

Func. test running

Rela

y 2

Rela

y 3

Buzzer

GS

M

?

Tue, 10.02.2004 16:52

info

?

Explorer Project XP128

Last test result:OK

Quick Menu

info

?

BLOCK system . . .

Start function test . . .

Start duration test . . .

SelfTest

Project

Vision

1. Touch screen Used to operate the system. The screens are intuitively arranged for easy use. This first screen gives access to the quick menu or other pages to input data, display test results and so on.

2 and 3. Testing Automatic tests normally run once a week. When a manual or duration test is required, it can be selected here. The block feature is used when selected luminaires (in sensitive areas such as operating theatres) should only be tested manually.

4. Addressing Luminaires are addressed on site after installation. No special programming is required, making the process quick and reliable, with no logistical problems.

5. Assigning relays and GSM Relays can be selected to operate according to the type of test or fault. GSM operations are also configured here.

Summary of benefits• Performs all of the testing and

records the results

• Cost effective compliance with emergency lighting testing regulations

• Test results stored for 2 years

• Explorer Project is for up to 256 emergency luminaires

• XP300m+ gives additional wiring distance

1.

2.

3.

4.

5.

Page 10: Explorer - Thorn Lighting · 2010-02-16 · Explorer SelfTest, Explorer Project and Explorer Vision Just like fire protection systems, emergency lighting is potentially life saving

10

* Not supplied

SelfTest

Project

Vision

Explorer VisionUp to 500 luminaires

For up to 500 emergency luminaires, choose the Explorer Vision XV500.

This computer operates monitoring software, that ‘talks’ to the XP128 controllers over a standard computer network cable (up to 100m) to the Nport2 interface. This interface converts the signals from ‘TCP-IP’ to RS232 so that the XP128 controller can understand them. The screen (not provided) shows the status of the emergency luminaires.

If you need a longer distance between the XV500 and the Explorer Project XP128 controllers, use your computer network to perform the connections – see configuration diagram overleaf. You would connect the XV500 in place of the XV5000. Now you can monitor the XV500 from another computer on your local area network (using the software provided). Note: if your building layout needs you to have more than 1m between the XP128 controllers just use an extra Nport2 – see diagram overleaf.

Summary of benefits• Medium system

• Up to 500 emergency luminaires

• Direct connection up to 100m

• Can connect XV500 to your computer network and monitor it from another of your own network computers

Explorer Vision satisfies the needs of larger installations requiring more than 256 emergency luminaires

XV500

Cross-over cable up to 100m

XPX64 Max 3

64max Luminaires

64max Luminaires

64max Luminaires

64max Luminaires

RS232 1m max

300m max1.5mm2 unscreened twisted

pair equivalent to Belden �411

Nport2

XPX64 Max 3

64max Luminaires

64max Luminaires

64max Luminaires

64max Luminaires

300m max1.5mm2 unscreened twisted

pair equivalent to Belden �411

RS232 1m max

Page 11: Explorer - Thorn Lighting · 2010-02-16 · Explorer SelfTest, Explorer Project and Explorer Vision Just like fire protection systems, emergency lighting is potentially life saving

11

XV5000 / XV5000D Computer

* Not suppliedUse your computer network to link multiple Explorer Project controllers together to support as many as 5000 emergency luminaires over a 1000m distance.

A larger computer operates the monitoring software, which ‘talks’ to the XP128s over a standard computer network cable via a Nport2 interface. This interface converts the signals from ‘TCP-IP’ to RS232 so that the XP128 can understand them. The screen (not provided) shows the status of the emergency luminaires.

Summary of benefits• Large system

• Up to 5000 luminaires

• Uses computer network for communication

• Use another PC on your computer network to view status of your emergency lighting

• Distances up to 1000m over your computer network

For the more challenging application...Up to 5000 luminaires

Explorer Vision connects into your computer network and monitors your emergency lighting system

SelfTest

Project

Vision

XV5000

Ethernet (shielded twisted pair cable) CAT5 cable (Limit 100m)

RS232 1m max

Nport2

XPX64 Max 3

64max Luminaires

64max Luminaires

64max Luminaires

64max Luminaires

300m max1.5mm2 unscreened twisted

pair equivalent to Belden �411

Ethernet (shielded twisted pair cable) CAT5 cable (Limit 100m)

Ethernet (shielded twisted pair cable) CAT5 cable (Limit 100m)

Fibre-optic link (Limit 1000m)

Max. 5 Hubs serial from computer or after switch

Ethernet (shielded twisted pair cable) CAT5 cable (Limit 100m)

RS232 1m max

Nport2

RS232 1m max

Nport2

Ethernet (shielded twisted pair cable) CAT5 cable (Limit 100m)

HUB

HUB

SWITCH

SWITCH

Page 12: Explorer - Thorn Lighting · 2010-02-16 · Explorer SelfTest, Explorer Project and Explorer Vision Just like fire protection systems, emergency lighting is potentially life saving

1. 2. 3.

4. 5. 6.

SelfTest

Project

Vision

Explorer Vision – How it works

Monitoring your emergency lighting system

1. Explorer Vision links XP128 controllers together and monitors the status of the emergency luminaires.

2. It is easy to navigate around the installation. Each Explorer Project XP128 is shown along with its four groups (of up to 64 luminaires) e.g. Main building ground floor, west wing. Just click onto an area to get to the luminaires you want to access.

3. Click on the luminaire to get its details.

4. Click on the group and the luminaires are displayed.

Explorer VisionVersion 3.7 (Build 3.7.1.1)

Company: A.N. OtherBuilding: Enterprise HouseLicense code: LMC-0520-5861-2813-7613-7267-0190License limit: local serverReference number: 255975920

Time limit: none

THORN Lighting

www.thornlight.com

5. Faults are indicated by the red luminaire and details are displayed. You can easily monitor the Explorer Vision computer, from another computer connected to the network using the software provided on the disc. Note, the software licence only permits one user, so if the computer is being accessed locally e.g. for maintenance purposes, it is not possible to operate it from a remote station, until the local work has been completed. All functions that are available on the Explorer Project controller XP128 can be accessed from the Explorer Vision computer. It operates like a ‘virtual touch screen’.

6. Here the testing regime for the XP128 is being programmed from the Explorer Vision controller.

Summary of benefits• Checks your emergency

lighting remotely

• All Explorer Project functions can be accessed using the keyboard of the XV500/XV5000/XV5000D

• See your emergency lighting networked system from one screen

12

Page 13: Explorer - Thorn Lighting · 2010-02-16 · Explorer SelfTest, Explorer Project and Explorer Vision Just like fire protection systems, emergency lighting is potentially life saving

MenloSoft SR

Voyager Elite SXVoyager Elite Voyager Elite XR

AquaForce Diffusalux II Jupiter II

Quattro T line

SelfTest

Project

Vision

Typical luminaires available as Explorer SelfTest or to work with Explorer Project/Explorer Vision

13

Page 14: Explorer - Thorn Lighting · 2010-02-16 · Explorer SelfTest, Explorer Project and Explorer Vision Just like fire protection systems, emergency lighting is potentially life saving

14

Explorer Project Components SelfTest

Project

Vision

Contact your local sales engineer if you require commissioning for your Explorer Project

XP128 22154297

Controller

High quality controller for monitoring, testing and fault logging for up to 128 emergency or exit sign luminaries. Can be expanded to operate up to 256 using XPX64 extenders. 2 year rolling memory. Din rail mounted.

XPX64 22154301

Extender (adds 64 luminaires)

Module (used on Channel B) extends the Explorer Project Controller capacity by a further 64 luminaire addresses.For up to 1�2 use 2 modules1�3 – 256 use 3 modules. Din rail mounted.

EXPISO 96218105

Isolator

Splits circuits and reduces commissioning time.

XP300m+ 22154567

300m extra wiring

Kit comprises a XV Repeater and DALI Power Supply. Allows for additional 300m wiring from the XPX64 or XP128 controller. Din rail mounted.

XPGSM 22154298

GSM Module

GSM Module facilitating ‘one man’ commissioning of emergency lighting systems using a mobile phone. Also sends SMS messages to maintainer on discovering a fault. SIM card not supplied. Din rail mounted.

XPPSU 22154300

GSM power supply

Required to power the GSM module. Din rail mounted.

XPPRI 22154299

Infra red hand held printer

Used for printing test reports from the log file of the XP128 controller. Power supply by battery, data transfer via infrared interface.

Page 15: Explorer - Thorn Lighting · 2010-02-16 · Explorer SelfTest, Explorer Project and Explorer Vision Just like fire protection systems, emergency lighting is potentially life saving

15

SelfTest

Project

Vision

Explorer Vision Components

XV5000 22154562

Computer (Analogue) (Up to 5000 luminaires)

Computer with visualisation package for graphic display and monitoring of up to 5000 emergency or escape sign luminaires. Analogue modem for remote access over telephone line. Complete with mouse and keyboard. Additional software for another PC to monitor if networked (single user licence enabled).

XV5000D 22154569

Computer (Digital) (Up to 5000 luminaires)

Computer with visualisation package for graphic display and monitoring of up to 5000 emergency or escape sign luminaires. Digital modem for remote access over broadband connection. Complete with mouse and keyboard. Additional software for another PC to monitor if networked (single user licence enabled).

XVCOM 22154566

Commissioning for Explorer Vision

XV500 22154561

Computer (Up to 500 luminaires)

Computer with visualisation package for graphic display and monitoring of up to 500 emergency or escape sign luminaires. Complete with mouse and keyboard and 230/24V power supply. Additional software for another PC to monitor if networked (single user licence enabled).

Nport2 72052223

Network Interface

Converts Explorer Vision signals to Explorer Project format (TCP-IP to RS232). Normally one per XP128 controller. (1m max RS232 to XP128) Can be used for up to 2 Explorer Project XP128 controllers.

SC Kabelsatz 72052839 Nport

Pack of 2 cables (each 1m long to connect between the Nport2 and the RS2323 port on the XP128 Controller

Page 16: Explorer - Thorn Lighting · 2010-02-16 · Explorer SelfTest, Explorer Project and Explorer Vision Just like fire protection systems, emergency lighting is potentially life saving

Lighting people and places

Head OfficeThorn Lighting Limited Silver Screens, Elstree Way, Borehamwood, Hertfordshire, WD6 1FE, UKTel: (44) 20 8732 �800Fax: (44) 20 8732 �801Website: www.thornlighting.com

AustraliaThorn Lighting Pty Limited 13 Cooper Street, P O Box 188, Smithfield, NSW 2164, AustraliaTel: (61) 2 �604 4300Fax: (61) 2 �604 4588E-mail: [email protected]: www.thornlight.com.au

AustriaThorn Licht GmbH Donau-City-Straße 11, 1220 Wien, AustriaTel: (43) 1 202 66 11Fax: (43) 1 202 66 11 12E-mail: [email protected]

ChinaThorn Lighting (Guangzhou) Operations Ltd No.12 Lian Yun Road, Eastern Section, GETDD, Guangzhou 510760, ChinaTel: (86) 20 3228 2706Fax: (86) 20 3228 1777E-mail: [email protected]

Thorn Lighting (Tianjin) Co. Ltd 332 Hongqi Road, Tianjin 3001�0, ChinaTel: (86) 22 836� 2303Fax: (86) 22 836� 2302E-mail: [email protected]

Czech RepublicThorn Lighting CS spol. s.r.o., Na Březince 6/930, 150 00 Praha 5Czech RepublicTel: (420) 224 315 252Fax: (420) 233 326 313E-mail: [email protected]: www.thornlight.cz

DenmarkThorn Lighting A/S Albuen 44, 6000 Kolding, DenmarkTel: (45) 76�6 3600Fax: (45) 76�6 3601Website: www.thornlight.dk

FranceThorn Europhane SA 156 Boulevard Haussmann, Cedex 08, Paris 7537�, FranceTel: (33) 1 4� 53 6262Fax: (33) 1 4� 53 6240Website: www.thorn.fr

Hong KongThorn Lighting (Hong Kong) Limited Unit 4301, Level 43, Tower 1, Metroplaza, 223 Hing Fong Road, Kwai Chung, N.T., Hong Kong, ChinaTel: (852) 2578 4303Fax: (852) 2887 0247E-mail: [email protected]: www.thorn.com.hk

IrelandThorn Lighting (Ireland) Limited 320 Harold’s Cross Road, Dublin 6W, IrelandTel: (353) 1 4�22 877Fax: (353) 1 4�22 724E-mail: [email protected]

ItalyThorn Europhane Spa Via G Di Vittorio, 2, Cadriano di Granarolo, Bologna 40057, ItalyTel: (3�) 051 7633�1Fax: (3�) 051 763088E-mail: [email protected]: www.thornlighting.it

New ZealandThorn Lighting (NZ) Ltd 3�� Rosebank Road, P O Box 71134, Rosebank, Auckland 7, New ZealandTel: (64) � 828 7155Fax: (64) � 828 75�1

NorwayThorn Lighting ASIndustriveien 11, P O Box 63, Skytta 1483, NorwayTel: (47) 6706 2233Fax: (47) 6706 0351E-mail: [email protected]

PolandThorn Lighting Polska Sp.z.o.o., Ul. Gazowa 26A, Wrocław 50-513, PolandTel: (48) 71 7833 740Fax: (48) 71 3366 029E-mail: [email protected] Website: www.thornlight.pl

RussiaThorn Lighting Novoslobodskaya Str., 21, office 406 Business Center “Novoslobodskaya 21”, Moscow 127030, RussiaTel: (7) 4�5 �81 35 41Fax: (7) 4�5 �81 35 42E-mail: [email protected] Website: www.thorn.ru

Thorn Lighting Representative Office,1 Artilleriyskaya str., 1 BC ‘Europa House’, St Petersburg 1�1104, RussiaTel: (7) 812 718 8112Fax: (7) 812 718 811�E-mail: [email protected]: www.thorn.ru

SingaporeThorn Lighting (Singapore) Pte Ltd 5 Kaki Buki Crescent, 04-02 Koyotech Building, 416238 SingaporeTel: (65) 6844 5800Fax: (65) 6745 7707E-mail: [email protected]: www.thornlight.com.sg

SwedenThorn Lighting ABIndustrigatan, Box 305, SE-261 23 Landskrona, SwedenTel: (46) 418 520 00Fax: (46) 418 265 74E-mail: [email protected]: www.thornlight.se

Thorn Lighting is constantly developing and improving its products. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. The right is reserved to change specifications without prior notification or public announcement. All goods supplied by the company are supplied subject to the company’s General Conditions of Sale, a copy of which is available on request. All measurements are in millimetres and weights in kilograms unless otherwise stated.

Publication No: 396 (INT) Publication Date: 02/07

Thorn Lighting Main OfficesUnited Arab EmiratesThorn Lighting Ltd Dubai Al Shoala Building, Office 301, Block E, PO Box 1200, Deira, Dubai, UAETel: (�71) 4 2�40181Fax: (�71) 4 2�48838E-mail: [email protected]

Thorn Gulf LLC Al Shoala Building, Office 301/2, Block E, PO Box 1200, Deira, Dubai, UAETel: (�71) 4 2�48�38Fax: (�71) 4 2�48838E-mail: [email protected]

United KingdomThorn Lighting Limited Silver Screens, Elstree Way, Borehamwood, Hertfordshire, WD6 1FE, UKTel: (44) 20 8732 �800Fax: (44) 20 8732 �801E-mail: [email protected]: www.thornlighting.co.uk

International SalesThorn Lighting Limited 156 Boulevard Haussmann, Cedex 08, Paris 7537�, FranceTel: (33) 1 4� 53 6262Fax: (33) 1 4� 53 6240

Thorn Lighting Limited Silver Screens, Elstree Way, Borehamwood, Hertfordshire, WD6 1FE, UKTel: (44) 20 8732 1�15Fax: (44) 20 8732 1�11E-mail: [email protected]

www.thornlighting.com