Brief Operating Description: Longer Motor Life Starts with a Switch S-795-1 1 For over 75 years, single-phase motors have utilized a mechanical centrifugal switch to switch the start circuit. Inherent characteristics of a mechanical device have made these switches prone to various problems, including tolerances, tolerance build- ups, mechanical fatigue, vibration and a host of others that can lead to switch failures and/or performance inconsistency. Our challenge was to design a reliable solid-state switch to replace the mechanical switch and actuator mechanism that would duplicate the function of connecting and disconnecting the start circuit at particular speeds with the additional benefits of a solid-state device. After considerable research, we decided a successful electronic motor starting switch could be created by sensing the voltages present in the main and start windings. Until the rotor of a single-phase motor begins to rotate, there is no coupling between its start winding and main winding. When the rotor begins to turn, the main winding induces flux in the rotor, which then induces a voltage in the start winding. The voltage induced in the start winding is directly proportional to motor speed. In Stearns SINPAC Electronic Switches, the voltage across a motor’s main winding and the voltage across its start winding are sampled and fed to a comparator. The logic circuitry is designed so that the electronic switch interrupts the start circuit current after the motor has accelerated to the speed at which cut out voltage is developed, generally 75 to 80% of synchronous motor speed. The logic circuitry then shuts down the switch’s power stage, which consists of a triac or inverse parallel SCR’s. This function is referred to as “cut out.” When the start circuit is disconnected, the main winding field then drives the motor’s rotor to its running speed. If the motor encounters an overload, and the motor speed falls to approximately 50% of its synchronous speed, the SINPAC Switch automatically reconnects the motor’s start circuit. This function is referred to as “cut in.” Cut in detection circuitry constantly monitors start winding voltage. When the motor’s speed falls to the cut in point, the detection circuit causes the control logic to energize the SINPAC Switch’s power output stage. The motor then goes through its normal startup procedure, with the start circuit being switched out at a motor speed approximately 75 to 80% of synchronous speed. SINPAC Switches are potted and completely sealed, making it impervious to dust, dirt and moisture. The unique speed sensing circuit provides a universal design which allows a few switches to work on most standard motor designs regardless of manufacturer. Acceptance by Motor Manufacturers US and foreign motor manufacturers have tested and retested the SINPAC Switch for reliability and quality.Today, many of these manufacturers have begun installing SINPAC Switches on their standard motor lines with more companies ready to make the changeover. UL Recognition Many SINPAC Switches have already been recognized under the Component Program of Underwriters Laboratories, Inc. (E-71115). In addition, all switches have internal surge protection which is tested according to IEEE C62.41 – 1991 Category A3. CSA Certification LR-6254. Contents Brief Operation Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Typical Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Design Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Models and Mounting Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 SINPAC Switch Ordering and Identification Information . . . . . . . . . . . . . . . . . . . . . . . 5 Overview of Standard Product Offering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7 Split Phase Motors PV Series for 115 VAC Start Circuit ( 1 /2 typical max. motor hp) . . . . . . . . . . . . 8-9 2PV Series for 230 VAC Start Circuit (1 typical max. motor hp) . . . . . . . . . . . . . 8-9 Capacitor Start Motors CV Series for 115 VAC Start Circuit (2 typical max. motor hp) . . . . . . . . . . . . . 10-11 2CV Series for 230 VAC Start Circuit (5 typical max. motor hp) . . . . . . . . . . . . . 16-17 Capacitor Start Motors Instant Reversing IR Series for 115 VAC Start Circuit (2 typical max. motor hp) . . . . . . . . . . . . . 20-21 Capacitor Start/Capacitor Run Motors VR Series for 115 VAC Start Circuit (3 typical max. motor hp) . . . . . . . . . . . . . 12-13 2VR Series for 230 VAC Start Circuit (5 typical max. motor hp) . . . . . . . . . . . . . 16-17 Capacitor Start and Capacitor Start/Capacitor Run Motors CVR Series for 115 VAC Start Circuit (3 typical max. motor hp) . . . . . . . . . . . . . 14-15 2CVR Series for 230 VAC Start Circuit (10 typical max. motor hp) . . . . . . . . . . . . 18-19 Installation Instructions for SINPAC Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22-25 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-27 Procedure for Checking SINPAC Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Distributors of SINPAC Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Worldwide Sales and Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Performance Parameters and Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
29
Embed
Contents · 2017. 6. 22. · capacitor start, 16 amp switch with 165 volt cut out, catalog number would be CV-16-165 as follows: SINPAC Electronic Switch Catalog Numbering System
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Brief Operating Description: Longer Motor Life Starts with a Switch
S-795-1 1
For over 75 years, single-phase motorshave utilized a mechanical centrifugalswitch to switch the start circuit.Inherent characteristics of amechanical device have made theseswitches prone to various problems,including tolerances, tolerance build-ups, mechanical fatigue, vibration anda host of others that can lead to switchfailures and/or performanceinconsistency.
Our challenge was to design a reliablesolid-state switch to replace themechanical switch and actuatormechanism that would duplicate thefunction of connecting anddisconnecting the start circuit atparticular speeds with the additionalbenefits of a solid-state device. Afterconsiderable research, we decided asuccessful electronic motor startingswitch could be created by sensing thevoltages present in the main and startwindings.
Until the rotor of a single-phase motorbegins to rotate, there is no couplingbetween its start winding and mainwinding. When the rotor begins to turn,the main winding induces flux in therotor, which then induces a voltage inthe start winding. The voltage inducedin the start winding is directlyproportional to motor speed.
In Stearns SINPAC ElectronicSwitches, the voltage across a motor’smain winding and the voltage acrossits start winding are sampled and fedto a comparator. The logic circuitry isdesigned so that the electronic switchinterrupts the start circuit current afterthe motor has accelerated to the speedat which cut out voltage is developed,generally 75 to 80% of synchronousmotor speed. The logic circuitry thenshuts down the switch’s power stage,which consists of a triac or inverseparallel SCR’s. This function is referredto as “cut out.” When the start circuit isdisconnected, the main winding fieldthen drives the motor’s rotor to itsrunning speed.
If the motor encounters an overload,and the motor speed falls toapproximately 50% of its synchronousspeed, the SINPAC Switchautomatically reconnects the motor’sstart circuit. This function is referred toas “cut in.” Cut in detection circuitryconstantly monitors start windingvoltage. When the motor’s speed fallsto the cut in point, the detection circuitcauses the control logic to energize theSINPAC Switch’s power output stage.The motor then goes through itsnormal startup procedure, with thestart circuit being switched out at a
motor speed approximately 75 to 80%of synchronous speed.
SINPAC Switches are potted andcompletely sealed, making itimpervious to dust, dirt and moisture.The unique speed sensing circuitprovides a universal design whichallows a few switches to work on moststandard motor designs regardless ofmanufacturer.
Acceptance by MotorManufacturersUS and foreign motor manufacturershave tested and retested the SINPACSwitch for reliability and quality. Today,many of these manufacturers havebegun installing SINPAC Switches ontheir standard motor lines with morecompanies ready to make thechangeover.
UL RecognitionMany SINPAC Switches have alreadybeen recognized under the ComponentProgram of Underwriters Laboratories,Inc. (E-71115). In addition, all switcheshave internal surge protection which istested according to IEEE C62.41 –1991 Category A3.
Typical ApplicationsStearns SINPAC Switches are idealfor applications requiring reliableswitching of the start circuit in single-phase motors.
Mechanical switches are prone tovarious problems includingmechanical fatigue, tolerances,tolerance build-ups and vibrationwhich can lead to performanceinconsistency.
Electronic SINPAC Switches solve allthose problems which reduceproduction downtime in hundreds ofapplications. Some of theseapplications are illustrated below:
• Speed SensitiveSINPAC Switches duplicatemechanical switch performance.They cut out the start circuit atapproximately 80% of synchronousspeed*. This means nodegradation in motor performanceand no confusing and cumbersometime or current selection criteria toconsider, since SINPAC Switchesare not load sensitive. It alsomeans there will be less stress onthe starting capacitor due to overvoltage.
• Restart CapabilityWhen motor speed drops below50% of synchronous speed, thestart circuit is reconnected toreinitiate starting torque.
• Accepted by MotorManufacturersStearns SINPAC Switches havebeen tested with favorable resultsand are available from most single-phase motor manufacturers.
• Line Voltage CompensationNo modifications or changes arerequired for line voltage variations.SINPAC Switches will operate inareas susceptible to brown-outs orlow voltage due to long wiring runs.
• Electrically Protected DesignSINPAC Switches are designed tofilter out electrical noise, so thereis no concern of random switchmalfunctions.
• UL Recognition and CSACertificationTesting has been completed andapproval has been obtained onmost sizes and will be obtained onthe balance of the product line.SINPAC Switches can be usedwith confidence in their safety andacceptance.
• Completely Solid-StateWith no moving parts, SINPACSwitches have no physicalconstraints to affect their operation.Can be used on new or existingmotors.No wearing parts means highcycling. No shaft extensionrequired. Not restricted by motorvibration or overspeed. No arcingcontacts due to restart duringmotor coastdown.
• Universal DesignSINPAC Switches will work on 2, 4,6 or more pole motors of anymanufacturer. This reduces motormanufacture and repair shopselection time and switch inventory.It also means that foreign andobsolete motors can be easilyretrofitted with SINPAC Switches.
• Environmentally ProtectedSINPAC Switches are immune tomoisture, dust, shock, vibration oroverspeed. The switch will not limitmotor performance due toenvironmental conditions.
• Stearns ReliabilityYears of experience in the motorindustry, first with brakes and nowwith speed sensing switches,means you can depend on StearnsSINPAC Switches to solveswitching problems.
• Unlimited MountingLocationsSINPAC Switches offer a variety ofexternal and internal conduit boxmountings and external endbellmountings. These mountings arenot affected by the motor position(shaft up or shaft down). SINPACSwitches can also be mounted atlocations remote from the motor.
• Reduced Installation TimeEasy accessible terminals andmounting, reduce the amount oftime required to install SINPACSwitches.
• Integral DesignSINPAC Switches can reduce thelength of the motor when designedas an integral part of the motor.
*Contact factory for questions on specific switch/motor performance.
Models
Mounting Options
4
20 Style
19 Style15 Style
17 Style
12 Style
11 Style
Gasket(available for 11 and 12 Styles)
S-795-3 5
SINPAC Switch Ordering and Identification Information
CV-16-165 – Each stock electronicseries switch is uniquely specified byan alphanumerical catalog number.For most standard SINPACElectronic Switches, the catalogidentifies a particular switch,including voltage, series, currentrating, and cut out or cut in voltage.The first position indicates the startcircuit voltage (blank equals 115 volts
and 2 equals 230 volts). The nextcharacters specify the series or typeof motor on which the switch shouldbe used. The next numericcharacters specify the maximumcurrent which the switch can handle.The next numeric grouping specifiescut out voltage for capacitor start,capacitor start/capacitor run, andinstant reversing switches and cut in
voltage for the PV Switches. TheTable shown on Page 6 providesinformation for selecting appropriatecatalog number when ordering aStearns electronic switch.
For example, when ordering acapacitor start, 16 amp switch with165 volt cut out, catalog numberwould be CV-16-165 as follows:
SINPAC Electronic Switch Catalog Numbering System
CV – 16 – 165Start Winding Voltage Cut Out Voltage (Cut In PV)blank = 115, 2 = 230
Maximum Current RatingSeriesCVR = Capacitor Start and Capacitor Start/Capacitor Run Motors, PV = Split Phase Only,CV - Capacitor Start Only, VR = Capacitor Start/Capacitor Run Only, IR = Capacitor Start Instant Reverse
Each Stearns SINPAC ElectronicSwitch is uniquely specified by a 12-digit alphanumeric part number. Formost standard SINPAC ElectronicSwitches, the last 10 positionsidentify the specific switch, including
series, voltage, option, current,enclosure, agency recognition, cut inor cut out voltages. For example,when ordering capacitor start, 16amp SINPAC Electronic Switch, theswitch would be specified as shown.
The following examples and tablesprovide information for selecting theappropriate 12-digit part numberwhen ordering a Stearns SINPACElectronic Switch.
4–7–21016–11–UO1
Electronics
6 = Switchpac (6 switches)7 = SINPAC Switch
1 = PV Series - Split Phase Only2 = CV Series - Capacitor Start Only3 = Made-To-Order (MTO)*4 = CVR Series - Capacitor Start and
Capacitor Start/Capacitor Run5 = IR Series - Capacitor Start Only6 = Timer - Fixed Timer Split Phase
or Capacitor Start7 = VR Series - Capacitor Start/
115 V SINPAC SwitchA = 130 VCO, B = 147 VCO, O = 165 VCOO = 400 mS Timing Interval, 30 V Cut InD = 180 VCOF = 400 mS Timing Interval, 10 V Cut InJ = 155 VCO Hybrid 6BK = 165 VCO Hybrid 6L = 130 VCO 15 VCIP = 800 mS Timing Interval, 30 V Cut InR = 115 VCOT = 600 mS Timing Interval, 10 V Cut InV = 210 VCOW = 200 mS Timing Interval, 30 V Cut InY = 200 mS Timing Interval, 10 V Cut In
230 V SINPAC SwitchC = 260 VCO, O = 310 VCO, E = 410 VCOH = 400 mS Timing Interval, 60 V Cut InM = 340 VCO, S = 350 VCOT = 600 mS Timing Interval, 60 V Cut In
U = UL Recognized, N = Not UL
Package Style11 = Metal Can 2.48 x 1.38 x .8112 = Metal Can 2.67 x 1.78 x .8615 = Capacitor Case 1.822 dia. x 3.372 long16 = Metal Can 2.75 x 2.0 x 1.12517 = Capacitor Case 2.572 dia. x 4.372 long19 = Capacitor Case 1.447 dia. x 3.372 long20 = Capacitor Case 1.447 dia. x 2.760 long21 = Board Only
*NOTE: For part numbers beginning with 473(these are OEM specials), the remaining digitsof this numbering system do not apply.
14-1515301304-7-41080-15-NA1CVR-80-1301158050/25503-5CVR Series –for Capacitor
Start/CapacitorRun Motors Only
CatalogPage
Pkg.Style
CutIn
VoltageTypical
CutOut
VoltageTypical
Part NumberCatalogNumber
StartCircuitVoltage
Switch Rating& Permissible
Maximum StartCircuit Current
(amps)
Typical Full LoadMotor Nameplate
Current Rating (amps)
TypicalMax.Motor
hp
Series230
Volts115/230
Volts115
Volts
PV and 2PV Series for 115 Vac, 230 Vac or 115/230 VacDual Voltage Split Phase Motors
8
Basic OperationThe PV Series SINPAC uses a pulse sampling technique to monitorRPM-sensitive information (induced voltage) across the motor startwinding. After the initial timing period, solid-state logic will sample theinduced voltage across the start winding and will repeat thissequence until the voltage across the start winding is above the cut-inreference value. The SINPAC logic circuit continues to monitor theRPM-sensitive information (induced voltage) on the start winding. Ifthe SINPAC logic detects that the motor RPM drops below a certainpoint, it automatically recloses the solid-state switch reconnecting thestart winding. Both the initial timing period and cut-in reference valuecan be modified to meet specific applications.
The PV Series SINPAC is available in three current ratings: 16, 25and 40 amps.
Dimensions are for estimating only. Drawings for customer reference are available upon request.
a Electrically Protected. Designed to filter out electricalnoise, so there is no concern of random switchmalfunction.
b Reduced Installation Time. Easy accessible 1/4 inchterminals and mounting, reduce the amount of timerequired to install SINPAC Switches or to change outmechanical switches.
c Restart Capability. When motor speed drops below50% of synchronous speed, the start winding isbrought back into the circuit to reinitiate starting torque.
d Soldered Heat Sink. High cycling.e Transient Protection. Transient protection tested per
IEEE C62.41 - 1991 Category A3.f Universal Design. 50/60 Hz operation. Will work on 2,
4 or 6 pole motors of any manufacturer. Reducedinventory.
g Line Voltage Compensation. No modifications orchanges are required for line voltage variations.SINPAC Switches will operate in areas susceptible tobrown-outs or low voltage due to long wiring runs.
a
g
g
c
b
d
e
ef
a
b
c
f
Gasket AvailableSee dimensions
on Page 9
ADDITIONAL FEATURES
• Capacitor Shape. Makes for easy mounting under a motordoghouse (20 package style).
• Environmentally Protected. Immune to moisture, dust, dirt,shock and vibration.
• UL and Canadian UL Recognition (on 115 Vac models).• Completely Solid-State with No Moving Parts. SINPAC
Switches have no physical constraints to affect their operation.
No wearing parts mean high cycling, no arcing contact. Lowwarranty.
• Silent Operation - no switch noise• Operating Temperature: -40°C to 65 °C (-40 °F to 149°F) [for
operation between 65°C and 85°C (149°F and 185°F), consultfactory.]
• Operating Voltage: 115 Vac SINPAC Switch: 90-130 Vac. Fordual voltage motor equipped with center-tapped main winding:90-130 Vac or 180-265 Vac.
Line VoltageCompensation ChartInduced voltage across the start windingis directly proportional to motor speedand line voltage. All SINPAC Switchesuse this voltage to switch the startwinding out of the circuit. Your motor witha SINPAC Switch must generate avoltage that is 20% greater than theswitch cut in reference voltage to assurecut out of the start winding. Refer tocharts below.
SelectionMotor hp ratings are typical. For an accurate selection procedure, measure startwinding current during a normal start or at locked rotor and select a SINPACSwitch with higher maximum current rating than that measured.
1. Be sure switch series matches motor type.
2. Be sure switch voltage rating matches (start) circuit voltage rating.
3. Selection can be based on actual measurement of start winding current ortwo times the motor nameplate FLA rating.
4. Switch current rating must match or exceed the motor start winding currentrequirements. Always select a SINPAC Switch with the next higher current ratingfor:a) High cycling applications.
b) Long acceleration time.
c) High ambients: Greater than 55° C.
5. To assure proper motor operation, the voltage across the start winding mustreach the SINPAC Switch cut in reference voltage between 70% to 85% ofmotors synchronous speed.
Caution: SINPAC Switches are line voltage compensated. Changes in the linevoltage will not effect system operation unless an overload condition causesreduced running speed, along with reduced voltage across the start winding.
6. Higher current switches can be used in place of lower rated switches of thesame series.
Wiring Diagram
2PV-16
Connectto
Split PhaseMotors
PV-16PV-25PV-40
Connectto SplitPhaseMotors
230 Volt 50/60 HzMotor Operation
115 Volt 50/60 HzMotor Operation
SINPACSwitchRating
CatalogNumber
*NOTE FOR PV SWITCH APPLICATIONS: Please contact the factory for special sampling time intervals or cut in voltage. Standard sample time interval is .04 seconds.
130
120
110
100
900 10 20 30 40 50 60
Start Winding Volts
Line
Vol
tage
10
30
60
Cut In VoltagePV
50/60 Hz, Typical
Not Applicable
M – Motor main winding, ST – Motor start winding
Gasket
CV Series for 115 Vac or 115/230 VacDual Voltage Capacitor Start Motors
10
Basic OperationCapacitor start motor require a method to extract speed datafrom the voltage across the motor start winding. Bycomparing the start winding RPM-sensitive voltage with themain AC input voltage (which serves as a reference voltage),the switch determines when the start circuit should beenergized. The electronic switch interrupts the start circuitcurrent after the motor has accelerated to the cut out speed,and reconnects the start circuit whenever the motor speedhas fallen to cut in speed (usually about 50% of synchronousmotor speed).
Dimensions are for estimating only. Drawings for customer reference are available upon request.
ADDITIONAL FEATURES• Capacitor Shape. Makes for easy mounting under a motor
shock and vibration.• UL and Canadian UL Recognition (also CSA Certification on
11 package).• Completely Solid-State with No Moving Parts. SINPAC
Switches have no physical constraints to affect their operation.
No wearing parts mean high cycling, no arcing contact. Lowwarranty.
• Silent Operation - no switch noise• Operating Temperature: -40°C to 65 °C (-40 °F to 149°F) [for
operation between 65°C and 85°C (149°F and 185°F), consultfactory.]
• Operating Voltage: 115 Vac SINPAC Switch: 90-130 Vac. Fordual voltage motor equipped with center-tapped main winding:90-130 Vac or 180-265 Vac.
a Electrically Protected. Designed to filter outelectrical noise, so there is no concern ofrandom switch malfunction.
b Reduced Installation Time. Easy accessible1/4 inch terminals and mounting, reduce theamount of time required to install SINPACSwitches or to change out mechanical switches.
c Restart Capability. When motor speed dropsbelow 50% of synchronous speed, the startcircuit is reconnected to reinitiate startingtorque.
d Soldered Heat Sink. High cycling.e Transient Protection. Transient protection
tested per IEEE C62.41 - 1991 Category A3.f Universal Design. 50/60 Hz operation. Will
work on 2, 4 or 6 pole motors of anymanufacturer. Reduced inventory.
g Line Voltage Compensation. No modificationsor changes are required for line voltagevariations. SINPAC Switches will operate inareas susceptible to brown-outs or low voltagedue to long wiring runs. It also means there willbe less stress on the starting capacitor due toover voltage.
Line VoltageCompensation ChartsInduced voltage across the start windingis directly proportional to motor speedand line voltage. All SINPAC Switchesuse this voltage to switch the startcapacitor out of the circuit. Your motorwith a SINPAC Switch must generate avoltage that is 20% greater than theswitch cut out voltage to assure cut out ofthe start capacitor. Refer to charts below.
SelectionMotor hp ratings are typical. For an accurate selection procedure, measure startcapacitor current during a normal start or at locked rotor and select a SINPACSwitch with higher maximum current rating than that measured.
1. Be sure switch series matches motor type.
2. Be sure switch voltage rating matches (start) circuit voltage rating.
3. Selection can be based on actual measurement of start capacitor current or twotimes the motor nameplate FLA rating.
4. Switch current rating must match or exceed the motor start capacitor currentrequirements. Always select a SINPAC Switch with the next higher currentrating for:a) High cycling applications.
b) Long acceleration time.
c) High ambients: Greater than 55° C.
5. To assure proper motor operation, the voltage across the start winding mustreach the SINPAC Switch cut out reference voltage between 70% to 85% ofmotors synchronous speed.
Caution: SINPAC Switches are line voltage compensated. Changes in the linevoltage will not effect system operation unless an overload condition causesreduced running speed, along with reduced voltage across the start winding.
6. Higher current switches can be used in place of lower rated switches of thesame series.
Wiring Diagram
CV-16CV-25CV-40CV-50
Connectto
CapacitorStart
Motors
230 Volt 50/60 HzMotor Operation
115 Volt 50/60 HzMotor Operation
SINPACSwitchRating
CatalogNumber
130
130
147
165
Cut Out VoltageCV
50/60 Hz, Typical
120
110
100
90120 130 140 150 160 170 180
Start Winding Volts
Line
Vol
tage
130
130
147, 165
Cut In VoltageCV
50/60 Hz, Typical
120
110
100
9025 30 35 40 45 50 55
Start Winding Volts
Line
Vol
tage
Gasket
CS – Start Capacitor, M – Motor main winding, ST – Motor start winding
VR Series for 115 Vac or 115/230 Vac Dual Voltage CapacitorStart/Capacitor Run Motors
12
Basic OperationCapacitor start/capacitor run motors provide continuous voltage sensinginformation which can be used to extract speed data from the voltage across themotor start winding. By comparing this start winding RPM-sensitive voltage to themain AC input voltage (which serves as a reference voltage), the switchdetermines when the start circuit should be de-energized. The electronic switchinterrupts the start circuit current after the motor has accelerated to the cut outvoltage (speed), and reconnects the start circuit whenever the speed sensitivecircuit senses the motor voltage (speed) has decreased to a preselected cut involtage (RPM) level.
Capacitor start/capacitor run motors exhibit current transients and higher voltagesacross the start switch. These electrical stresses occur due to the switching of thetwo capacitors (start and run) that are connected in parallel during motor startand may have different voltages at time of restart. These stresses occur at restartwith both mechanical and electronic start switches. The VR switch featurescircuitry designed to eliminate the effects of these conditions.
Dimensions are for estimating only. Drawings for customer reference are available upon request.
ADDITIONAL FEATURES• Capacitor Shape. Makes for easy mounting under a motor
shock and vibration.• UL and Canadian UL Recognition for VR-12 - pending for
VR-19 package.• Completely Solid-State with No Moving Parts. SINPAC
Switches have no physical constraints to affect their operation.
No wearing parts mean high cycling, no arcing contact. Lowwarranty.
• Silent Operation - no switch noise• Operating Temperature: -40°C to 65 °C (-40 °F to 149°F) [for
operation between 65°C and 85°C (149°F and 185°F), consultfactory.]
• Operating Voltage: 115 Vac SINPAC Switch: 90-130 Vac. Fordual voltage motor equipped with center-tapped main winding:90-130 Vac or 180-265 Vac.
a Bleeder Resistor. Increases start capacitor life.b Electrically Protected. Designed to filter out electrical
noise, so there is no concern of random switchmalfunction.
c Reduced Installation Time. Easy accessible 1/4 inchterminals and mounting, reduce the amount of timerequired to install SINPAC Switches or to change outmechanical switches.
d Restart Capability. When motor speed drops below50% of synchronous speed, the start circuit isreconnected to reinitiate starting torque.
e Soldered Heat Sink. High cycling.f Transient Protection. Transient protection tested per
IEEE C62.41 - 1991 Category A3.g Universal Design. 50/60 Hz operation. Will work on 2,
4 or 6 pole motors of any manufacturer. Reducedinventory.
h Zero Voltage Detection Logic/Inductor. Currentspiking due to run capacitor no longer a problem.
i Line Voltage Compensation. No modifications orchanges are required for line voltage variations.SINPAC Switches will operate in areas susceptible tobrown-outs or low voltage due to long wiring runs. Linevoltage compansation results in less stress on thestarting capacitor due to overvoltage.
Line VoltageCompensation ChartsInduced voltage across the start windingis directly proportional to motor speedand line voltage. All SINPAC Switchesuse this voltage to switch the startcapacitor out of the circuit. Your motorwith a SINPAC Switch must generate avoltage greater than the switch referencevoltage to assure cut-out of the startcapacitor. Refer to charts below.
SelectionMotor hp ratings are typical. For an accurate selection procedure, measure startcapacitor current during a normal start or at locked rotor and select a SINPACSwitch with higher maximum current rating than that measured.
1. Be sure switch series matches motor type.
2. Be sure switch voltage rating matches auxiliary (start) circuit voltage rating.
3. Selection can be based on actual measurement of start capacitor current ortwo times the motor nameplate FLA rating.
4. Switch current rating must match or exceed the motor start capacitor currentrequirements. Always select a SINPAC Switch with the next higher currentrating for:a) High cycling applications.
b) Long acceleration time.
c) High ambients: Greater than 55° C.
5. To assure proper motor operation, the voltage across the start winding mustreach the SINPAC Switch cut out reference voltage between 70% to 85% ofmotors synchronous speed.
SINPAC Switches are line voltage compensated. Changes in the line voltagewill not effect system operation unless an overload condition causes reducedrunning speed, along with reduced voltage across the start winding.
6. Higher current switches can be used in place of lower rated switches of thesame series.
Wiring Diagram
VR-16VR-40VR-50
Connect toCapacitor
Start/Capacitor
RunMotors
230 Volt 50/60 HzMotor Operation
115 Volt 50/60 HzMotor Operation
SINPACSwitchRating
CatalogNumber
130
130
147
165
Cut Out VoltageVR
50/60 Hz, Typical
120
110
100
90120 130 140 150 160 170 180
Start Winding Volts
Line
Vol
tage
130
130
147, 165
Cut In VoltageVR
50/60 Hz, Typical
120
110
100
9025 30 35 40 45 50 55
Start Winding Volts
Line
Vol
tage
Gasket
14
CVR Series for 115 Vac or 115/230 Vac Dual VoltageCapacitor Start and Capacitor Start/Capacitor Run MotorsBasic OperationCapacitor start/capacitor run motors and capacitor start motors provide continuous voltagesensing information which can be used to extract speed data from the voltage across themotor start winding. By comparing this start winding RPM-sensitive voltage to the main ACinput voltage (which serves as a reference voltage), the switch determines when the startcircuit should be de-energized. The electronic switch interrupts the start circuit currentafter the motor has accelerated to the cut out voltage (speed), and reconnects the startcircuit whenever the speed sensitive circuit senses the motor voltage (speed) hasdecreased to a preselected cut in voltage (RPM) level.
Capacitor start/capacitor run motors exhibit current transients and higher voltages acrossthe start switch. These electrical stresses occur due to the switching of the two capacitors(start and run) that are connected in parallel during motor start and may have differentvoltages at time of restart. These stresses occur at restart with both mechanical andelectronic start switches. The CVR switch has additional circuitry to eliminate the effects ofthese conditions.
Dimensions are for estimating only. Drawings for customer reference are available upon request.
ADDITIONAL FEATURES• Capacitor Shape. Makes for easy mounting under a motor
doghouse.• Environmentally Protected. Immune to moisture, dust, dirt,
shock and vibration.• Silent Operation - no switch noise• Completely Solid-State with No Moving Parts. SINPAC
Switches have no physical constraints to affect their operation.
No wearing parts mean high cycling, no arcing contact. Lowwarranty.
• Operating Temperature: -40°C to 65 °C (-40 °F to 149°F) [foroperation between 65°C and 85°C (149°F and 185°F), consultfactory.]
• Operating Voltage: 115 Vac SINPAC Switch: 90-130 Vac. Fordual voltage motor equipped with center-tapped main winding:90-130 Vac or 180-265 Vac.
Universal Design. 50/60 Hz operation.Will work on 2, 4 or 6 pole motors of anymanufacturer. Reduced inventory.
Line Voltage Compensation.Operating voltage 190 to260 Vac.
Electrically Protected.Designed to filter out electrical noise,so there is no concern of randomswitch malfunction.
Zero Crossing Logic.Current spiking due to run capacitorno longer a problem.
Start Capacitor DischargeResistor. Increase startcapacitor life.
Environmentally Protected.Immune to moisture, dust, dirt,
shock and vibration.
Speed Sensitive(cut in)
S-795-8 15
230Volts
115Volts
151515
504550
130147165
4-7-41080-15-NA14-7-41080-15-NB14-7-41080-15-NO1
CVR-80-130CVR-80-147CVR-80-165
115115115
808080
–––
505050
3-53-53-5
PackageStyle
Cut InVoltageTypical
Cut OutVoltageTypical
Part NumberCatalogNumber
StartCircuitVoltage
Switch Rating andPermissible
Maximum StartCapacitor
Current (amps)
Typical Full LoadMotor Nameplate
Current Rating (amps)Typical
MaximumMotor hp
Line VoltageCompensation ChartsInduced voltage across the start windingis directly proportional to motor speedand line voltage. All SINPAC Switchesuse this voltage to switch the startcapacitor out of the circuit. Your motorwith a SINPAC Switch must generate avoltage greater than the switch cut outvoltage to assure cut out of the startcapacitor. Refer to charts below.
SelectionMotor hp ratings are typical. For an accurate selection procedure, measure startcapacitor current during a normal start or at locked rotor and select a SINPACSwitch with higher maximum current rating than that measured.
1. Be sure switch series matches motor type.
2. Be sure switch voltage rating matches auxiliary (start) winding voltage rating.
3. Selection can be based on actual measurement of start capacitor current ortwo times the motor nameplate FLA rating.
4. Switch current rating must match or exceed the motor start capacitor currentrequirements. Always select a SINPAC Switch with the next higher currentrating for:a) High cycling applications.
b) Long acceleration time.
c) High ambients: Greater than 55° C.
5. To assure proper motor operation, the voltage across the start winding mustreach the SINPAC Switch cut out reference voltage between 70% to 85% ofmotors synchronous speed.
Caution: SINPAC Switches are line voltage compensated. Changes in the linevoltage will not effect system operation unless an overload condition causesreduced running speed, along with reduced voltage across the start winding.
6. Higher current switches can be used in place of lower rated switches of thesame series.
Wiring Diagram
CVR-80
Connectto
CapacitorStart/
CapacitorRun
Motors
230 Volt 50/60 HzMotor Operation
115 Volt 50/60 HzMotor Operation
SINPACSwitchRating
CatalogNumber
CS– Start capacitor, M – Motor main winding, CR – Run capacitor, ST – Motor start winding
130
130
147
165
Cut Out VoltageCVR
50/60 Hz, Typical
120
110
100
90120 130 140 150 160 170 180
Start Winding Volts
Line
Vol
tage
130
147
130165
Cut In VoltageCVR
50/60 Hz, Typical
120
110
100
9025 30 35 40 45 50 55
Start Winding Volts
Line
Vol
tage
2CV and 2VR Series for 230 Vac Capacitor Startand Capacitor Start/Capacitor Run Motors
16
Basic OperationCapacitor start/capacitor run motors and capacitor start motors provide continuousvoltage sensing information which can be used to extract speed data from the voltageacross the motor start (auxiliary) winding. By comparing this start (auxiliary) windingRPM-sensitive voltage to the main AC input voltage (which serves as a referencevoltage), the switch determines when the start circuit should be de-energized. Theelectronic switch interrupts the start circuit current after the motor has accelerated to thecut out speed, and reconnects the start circuit whenever the motor speed has decreasedto a preselected cut in RPM level.
Capacitor start/capacitor run motors exhibit current transients and higher voltages acrossthe start switch. This electrical stress is due to the voltage differential which may existbetween the start and run capacitors at the instant of switch closure. This stressphenomenon occurs with both mechanical and electronic type start switches. SINPACSwitches have voltage detection circuitry to minimize the effects of these conditions.
Dimensions are for estimating only. Drawings for customer reference are available upon request.
ADDITIONAL FEATURES• Silent Operation - no switch noise• Completely Solid-State with No Moving Parts. SINPAC
Switches have no physical constraints to affect their operation.No wearing parts mean high cycling, no arcing contact.
• Optional inductor for heavy duty operation.
• Ambient 40° to 65°C.• Operating Temperature: -40°C to 65 °C (-40 °F to 149°F) [for
operation between 65°C and 85°C (149°F and 185°F), consultfactory.]
• Operating Voltage: 230 Vac SINPAC Switch: 190-255 Vac.• UL Recognition and CSA Certification.
Universal Design. 50/60 Hz operation.Will work on 2, 4 or 6 pole motors of anymanufacturer. Reduced inventory.
Line Voltage CompensationOperating voltage 190 to 260 Vac.
Electrically ProtectedDesigned to filter out electrical noise, so thereis no concern of random switch malfunction.
Zero Crossing LogicCurrent spiking due to runcapacitor no longer a problem.
Start Capacitor Discharge ResistorIncrease start capacitor life.
Environmentally ProtectedImmune to moisture, dust, dirt,
shock and vibration.
Speed Sensitive(cut in)
S-795-9 17
230Volts
115Volts
1515
1515
1515
1515
7070
7070
7070
7070
260310
260310
260310
260310
4-7-72050-15-UC14-7-72050-15-UO1
4-7-72035-15-UC14-7-72035-15-UO1
4-7-22050-15-UC14-7-22050-15-UO1
4-7-22035-15-UC14-7-22035-15-UO1
2VR-50-2602VR-50-310
2VR-35-2602VR-35-310
2CV-50-2602CV-50-310
2CV-35-2602CV-35-310
230230
230230
230230
230230
5050
3535
5050
3535
2525
1717
2525
1717
––
––
––
––
55
33
55
33
PackageStyle
Cut InVoltageTypical
Cut OutVoltageTypical
Part NumberCatalogNumber
StartCircuitVoltage
Switch Rating andPermissible
Maximum StartCapacitor
Current (amps)
Typical Full LoadMotor Nameplate
Current Rating (amps)Typical
MaximumMotor hp
Line VoltageCompensation ChartsInduced voltage across the start windingis directly proportional to motor speedand line voltage. All SINPAC Switchesuse this voltage to switch the startcapacitor out of the circuit. Your motorwith a SINPAC Switch must generate avoltage greater than the switch cut outvoltage to assure cut out of the startcapacitor. Refer to charts below.
SelectionMotor hp ratings are typical. For an accurate selection procedure, measure startcapacitor current during a normal start or at locked rotor and select a SINPACSwitch with higher maximum current rating than that measured.
1. Be sure switch series matches motor type.
2. Be sure switch voltage rating matches auxiliary (start) circuit voltage rating.
3. Selection can be based on actual measurement of start capacitor current ortwo times the motor nameplate FLA rating.
4. Switch current rating must match or exceed the motor start capacitor currentrequirements. Always select a SINPAC Switch with the next higher currentrating for:a) High cycling applications.
b) Long acceleration time.
c) High ambients: Greater than 55° C.
5. To assure proper motor operation, the voltage across the start winding mustreach the SINPAC Switch cut out reference voltage between 70% to 85% ofmotors synchronous speed.
Caution: SINPAC Switches are line voltage compensated. Changes in the linevoltage will not effect system operation unless an overload condition causesreduced running speed, along with reduced voltage on the start winding.
6. Higher current switches can be used in place of lower rated switches of thesame series.
Wiring Diagram
2VR-352VR-50
Connect toCapacitor
Start/Capacitor
RunMotors
2CV-352CV-50
Connectto
CapacitorStart
Motors
230 Volt 50/60 HzMotor Operation
115 Volt 50/60 HzMotor Operation
SINPACSwitchRating
CatalogNumber
Not Applicable
Not Applicable
CS– Start capacitor, M – Motor main winding, CR – Run capacitor, ST – Motor start winding
260
260V
310V
240
220
200
180200 300 400 500
Start (Auxiliary) Winding Volts
Start (Auxiliary) Winding Volts
Line
Vol
tage
Cut Out Voltage2CV, 2VR-15
50/60 Hz, Typical
260
260V,310V
240
220
200
18060 70 1009080 110
Line
Vol
tage
Cut In Voltage2CV, 2VR-15
50/60 Hz, Typical
230 Volts
18
2CVR Series for 230 Vac Capacitor Startand Capacitor Start/Capacitor Run MotorsBasic OperationCapacitor start/capacitor run motors and capacitor start motors provide continuousvoltage sensing information which can be used to extract speed data from the voltageacross the motor start (auxiliary) winding. By comparing this start (auxiliary) windingRPM-sensitive voltage to the main AC input voltage (which serves as a referencevoltage), the switch determines when the start circuit should be de-energized. Theelectronic switch interrupts the start circuit current after the motor has accelerated tothe cut out voltage (speed), and reconnects the start circuit whenever the motorvoltage (speed) has decreased to a preselected cut in RPM level.
Capacitor start/capacitor run motor exhibit current transients and higher voltagesacross the start switch. These electrical stresses occur due to the switching of thetwo capacitors (start and run) that are connected in parallel during motor start andmay have different voltages at time of restart. These stresses occur at restart withboth mechanical and electronic start switches. The CVR switch has additionalcircuitry to eliminate the effects of these conditions.
Dimensions are for estimating only. Drawings for customer reference are available upon request.
ADDITIONAL FEATURES• Silent Operation - no switch noise• Completely Solid-State with No Moving Parts. SINPAC
Switches have no physical constraints to affect their operation.No wearing parts mean high cycling, no arcing contact.
• Optional inductor for heavy duty operation.
• Ambient 40° to 65°C.• Operating Temperature: -40°C to 65 °C (-40 °F to 149°F) [for
operation between 65°C and 85°C (149°F and 185°F), consultfactory.]
Universal Design50/60 Hz operation. Will work on 2, 4 or 6 polemotors of any manufacturer. Reduced inventory.
Line Voltage CompensationOperating voltage 190 to 260 Vac.
Electrically ProtectedDesigned to filter out electrical noise, so thereis no concern of random switch malfunction.
Zero Crossing LogicCurrent spiking due to runcapacitor no longer a problem.
Transient ProtectionTransient protectiontested per IEEE C62.41 -1991 Category A3.
Soldered Heat SinkHigh cycling.
Environmentally ProtectedImmune to moisture, dust, dirt,
shock and vibration.
Speed Sensitive(cut in)
S-795-10 19
230Volts
115Volts
1717
1717
7070
7070
260310
260310
4-7-42090-17-NC14-7-42090-17-NO1
4-7-42070-17-NC14-7-42070-17-NO1
2CVR-90-2602CVR-90-310
2CVR-70-2602CVR-70-310
230230
230230
9090
7070
4545
3535
––
––
1010
71/271/2
PackageStyle
Cut InVoltageTypical
Cut OutVoltageTypical
Part NumberCatalogNumber
StartCircuitVoltage
Switch Rating andPermissible
Maximum StartCapacitor
Current (amps)
Typical Full LoadMotor Nameplate
Current Rating (amps)Typical
MaximumMotor hp
Line VoltageCompensation ChartsInduced voltage across the start windingis directly proportional to motor speedand line voltage. All SINPAC Switchesuse this voltage to switch the startcapacitor out of the circuit. Your motorwith a SINPAC Switch must generate avoltage that is 20% greater than theswitch cut out voltage to assure cut out ofthe start capacitor. Refer to charts below.
SelectionMotor hp ratings are typical. For an accurate selection procedure, measure startcircuit current during a normal start or at locked rotor and select a SINPACSwitch with higher maximum current rating than that measured.
1. Be sure switch series matches motor type.
2. Be sure switch voltage rating matches auxiliary (start) circuit voltage rating.
3. Selection can be based on actual measurement of start capacitor current ortwo times the motor nameplate FLA rating.
4. Switch current rating must match or exceed the motor start capacitor currentrequirements. Always select a SINPAC Switch with the next higher currentrating for:a) High cycling applications.
b) Long acceleration time.
c) High ambients: Greater than 55°C.
5. To assure proper motor operation, the voltage across the start (auxiliary)winding must reach the SINPAC Switch cut out voltage reference between70% to 85% of motors synchronous speed.
Caution: SINPAC Switches are line voltage compensated. Changes in theline voltage will not effect system operation unless an overload conditioncauses reduced running speed, along with reduced voltage across the start(auxiliary) winding.
6. Higher current switches can be used in place of lower rated switches of thesame series.
Wiring Diagram
2CVR-702CVR-90
Connect toCapacitor
Start/Capacitor
RunMotors
2CVR-702CVR-90
Connectto
CapacitorStart
Motors
230 Volt 50/60 HzMotor Operation
115 Volt 50/60 HzMotor Operation
SINPACSwitchRating
CatalogNumber
Not Applicable
Not Applicable
CS– Start capacitor, M – Motor main winding, CR – Run capacitor, ST – Motor start winding
260
260V
310V
240
220
200
180200 300 400 500
Start (Auxiliary) Winding Volts
Start (Auxiliary) Winding Volts
Line
Vol
tage
Cut Out Voltage2CVR
50/60 Hz, Typical
260
260V310V
240
220
200
18060 70 1009080 110
Line
Vol
tage
Cut In Voltage2CVR
50/60 Hz, Typical
230 Volts
20
IR Series for Instant Reversing 115 Vac or 115/230Vac Dual Voltage Capacitor Start MotorsBasic OperationBidirectional motors - those that can rotate in either direction – areof two classes: 1. Reversing motors, which can change from fullspeed in one direction to full speed in the opposite direction.2. Reversible motors, which can be reversed only when the motor isnot running, or is running below cut out speed. Some motormanufacturers distinguish between quick reversing and instantreversing. A quick reversing motor requires a time delay ofapproximately 1/25th of a second or more for the switching circuitryto react. An instant reversing motor requires absolutely no timedelay. The standard SINPAC Switch can be used on reversible andreversing motors. The SINPAC IR Series Switch provides thefunction of a direction sensing centrifugal switch and makes areversible capacitor start motor into an instant reversing motor.
In order to reverse a single-phase motor, it is necessary to reversethe polarity of either the start or main winding, but not both at thesame time. The reversal of the winding is accomplished with an
external reversing switch or contactor that is not part of the SINPACSwitch. SINPAC Instant Reverse Switch is not dependent upon howquickly the user operates the reversing switch, but only that thereversing switch did change states, i.e., forward to reverse, or viceversa. The SINPAC Switch detects the change in the phase shiftbetween the main and start windings, and the logic circuit instantlyactuates the starting switch, causing thestart circuit to be reconnected to linevoltage. This connection causes themotor to decelerate and thenreaccelerate in the opposite direction.The SINPAC IR Series Switch interruptsthe start circuit current after the motorhas accelerated to the cut out speed, andreconnects the start circuit whenever thecircuit senses the motor speed has fallento cut in speed (usually about 50% ofsynchronous motor speed).
Dimensions are for estimating only. Drawings for customer reference are available upon request.
ADDITIONAL FEATURES• UL recognition and CSA certification.• Completely solid-state with no moving parts. SINPAC
Switches have no physical constraints to affect their operation. Nowearing parts mean high cycling, no arcing contact. Low warranty
• Silent operation - no switch noise
• Operating Temperature: -40°C to 65 °C (-40 °F to 149°F) [foroperation between 65°C and 85°C (149°F and 185°F), consultfactory.]
• Operating Voltage: 115 Vac SINPAC Switch: 90-130 Vac.For dual voltage motor equipped with center-tapped mainwinding: 90-130 Vac or 180-265 Vac.
Universal Design50/60 Hz operation. Will workon 2, 4 or 6 pole motors of anymanufacturer. Reducedinventory.
Line Voltage CompensationNo modifications or changes are required for linevoltage variations. SINPAC Switches will operate inareas susceptible to brown-outs or low voltage due tolong wiring runs. It also means there will be less stresson the starting capacitor due to over voltage.
Electrically Protected. Designed to filter outelectrical noise, so there is no concern ofrandom switch malfunction.
Restart Capability. Whenmotor speed drops below 50%of synchronous speed, the startcircuit is reconnected toreinitiate starting torque.
Reduced Installation Time. Easyaccessible 1/4 inch terminals andmounting, reduce the amount of timerequired to install SINPAC Switches or tochange out mechanical switches.
Soldered Heat SinkHigh cycling.
Environmentally Protected.Immune to moisture, dust, dirt,
shock and vibration.
Phase Comparator Logic:Allows Instant Reverse operation(no time delay).
S-795- 21
115/230Volts
115Volts
151515
151515
303337
303337
130147165
130147165
4-7-51040-15-UA14-7-51040-15-UB14-7-51040-15-UO1
4-7-51025-15-UA14-7-51025-15-UB14-7-51025-15-UO1
IR-40-130IR-40-147IR-40-165
IR-25-130IR-25-147IR-25-165
115115115
115115115
404040
252525
20/1020/1020/10
12/612/612/6
202020
121212
222
1/21/21/2
PackageStyle
Cut InVoltageTypical
Cut OutVoltageTypical
Part NumberCatalogNumber
StartCircuitVoltage
Switch Rating andPermissible
Maximum StartCapacitor
Current (amps)
Typical Full LoadMotor Nameplate
Current Rating (amps)Typical
MaximumMotor hp
Line VoltageCompensation ChartsInduced voltage across the start windingis directly proportional to motor speedand line voltage. All SINPAC Switchesuse this voltage to switch the startcapacitor out of the circuit. Your motorwith a SINPAC Switch must generate avoltage that is 20% greater than theswitch cut out voltage to assure cut out ofthe start capacitor. Refer to charts below.
SelectionMotor hp ratings are typical. For an accurate selection procedure, measure startcircuit current during a normal start or at locked rotor and select a SINPAC Switchwith higher maximum current rating than that measured.
1. Be sure switch series matches motor type.
2. Be sure switch voltage rating matches (start) circuit voltage rating.
3. Selection can be based on actual measurement of start capacitor current or twotimes the motor nameplate FLA rating.
4. Switch current rating must match or exceed the motor start capacitor current re-quirements. Always select a SINPAC Switch with the next higher current rating for:a) High cycling applications.b) Long acceleration time.c) High ambients: Greater than 55° C.
5. To assure proper motor operation, the voltage across the start winding mustreach the SINPAC Switch cut out voltage reference between 70% to 85% ofmotors synchronous speed.
Caution: SINPAC Switches are line voltage compensated. Changes in the linevoltage will not effect system operation unless an overload condition causesreduced running speed, along with reduced voltage on the start winding.
6. Higher current switches can be used in place of lower rated switches of thesame series.
Wiring Diagram
IR-25IR-40
Connectto InstantReverse
StartMotors
230 Volt 50/60 HzMotor Operation
115 Volt 50/60 HzMotor Operation
SINPACSwitchRating
CatalogNumber
CS– Start capacitor, M – Motor main winding, ST – Motor start winding, F – Forward, R – Reverse
115 Volts
130
130
147
165
Cut Out VoltageIR
50/60 Hz, Typical
120
110
100
90120 130 140 150 160 170 180
Start Winding Volts
Line
Vol
tage
130
130
147
165
Cut In VoltageIR
50/60 Hz, Typical
120
110
100
9025 30 35 40 45 50 55
Start Winding Volts
Line
Vol
tage
Drum switch is not part ofSINPAC Switch.
Reversing contacts are not part ofSINPAC Switch.
Reversing contacts are not part ofSINPAC Switch.
Reversing contacts are not part ofSINPAC Switch.
115 Volt Operation Dual VoltageMotor Using Two Full Voltage
Installation Instructions for SINPAC SwitchesUL RecognitionMost SINPAC Switches are recognizedunder the component program ofUnderwriters Laboratories E-71115. Inaddition, all switches have an internalsurge protection which meets UL-244ASpecification and CSR CertificationLR-6254, and are tested to therequirement of IEEE C62.41-1991,Category A3.
ConstructionSINPAC Switches are potted andcompletely sealed making themimpervious to dust, dirt and moisture. Itcan be immersed in electric gradeoil as used in submersible pumps. Theunique speed sensing circuit providesa universal design which allows a fewswitches to work in most standardsingle-phase motor applicationsregardless of nature.
OperationThe Stearns SINPAC Switch samplesthe voltage across the motor startwinding (terminals 1 and 4) then it isfed into a comparator. The SINPACSwitch interrupts the start capacitorcurrent (between terminals 2 and 3)after the motor has accelerated to aspeed in which the cut out voltage hasbeen reached, generally 75% to 80%of synchronous motor speed. A triac orinverse parallel SCRs provides thefunction referred to as cut out. Oncethe start circuit is cut out the mainwinding accelerates the motor rotor upto its running speed. When an overloaddrops the motor speed toapproximately 50% of synchronousspeed the switch automaticallyreconnects the motor start circuit. TheSINPAC Switch constantly monitors thestart or auxiliary winding for cut involtage and will reconnect the startcircuit once cut in voltage is reached.
Selection ProcedureCAUTION: SINPAC Switches are linevoltage compensated. Changes in theline voltage within ±10% of nominal115 or 230 Vac will not affect systemoperation. Operation of the motor atline voltages less than -10% of nominalcan result in reduced motor runningspeeds and failure of the SINPACSwitch to disconnect the start circuit.
1. Be sure switch series matches motortype.
2. Be sure switch voltage ratingmatches the motor start circuitvoltage.
3. Selection should be based on actualmeasurement of start circuit current.
4. SINPAC Switch current rating mustmeet or exceed the motor startcircuit current requirement. Alwaysselect a SINPAC Switch with thenext higher current rating for:
a) High cycling applications: Stopand start rates greater than 4times/minute.
b) Long acceleration times: Greaterthan 5 seconds.
c) High ambients: Ambients greaterthan 55°C.
Note: Higher rated current switchescan be used in place of lower ratedswitches within the same series.
5. The motor must generate a voltageacross the start or auxiliary windingthat is 20% greater than the SINPACSwitch cut out/cut in voltage rating.
Capacitor Start and CapacitorStart/Capacitor Run MotorsTo determine the most appropriateSINPAC Switch cut out voltage ratingfor the particular motor application, thevoltage across the motor start orauxiliary winding must be measured.This may be accomplished in thefollowing manner:
1. Prepare the motor wiring forconnection of the SINPAC Switch asshown in the Wiring Diagrams forSINPAC Switches section of thispublication. Secure the motor to afirm mounting surface.
2. Connect the lead wire that is to beconnected to SINPAC Switchterminal #2 securely to the lead wirethat is to be connected to SINPACSwitch terminal #3.
3. Connect an AC voltmeter across thelead wires that are to be connectedto SINPAC Switch terminals #1 & #4.
4. Apply power to the motor. Observeand record the voltage across themotor start or auxiliary winding, asindicated by the AC voltmeter, withthe motor operating nearsynchronous speed.
CAUTION: Measurement of the startor auxiliary winding voltage must bedone quickly to prevent damage to thestart capacitor, motor winding orSINPAC Switch!
5. Multiply the measured voltage by 0.8(80%). Select a SINPAC Switchhaving a cut out voltage rating equalto or less than this number.
Capacitor Start and CapacitorStart/Capacitor Run Motors
*Consult factory
Split Phase MotorsTo determine the most appropriateSINPAC Switch cut in voltage rating forthe particular motor application, thevoltage across the motor start windingmust be measured. This may beaccomplished in the following manner:
1. Prepare the motor wiring forconnection of the SINPAC Switch asshown in the Wiring Diagrams forSINPAC Switches section of thispublication. Secure the motor to afirm mounting surface.
2. Insulate the lead wire that is to beconnected to SINPAC Switchterminal #2.
3. Connect an AC voltmeter across thelead wires that are to be connectedto SINPAC Switch terminals #1 & #3.
4. Apply power to the motor. Carefullyrotate the motor shaft to initiaterotation. Observe and record thevoltage across the motor startwinding, as indicated by the ACvoltmeter, with the motor operatingnear synchronous speed.
5. Multiply the measured voltage by 0.8(80%). Select a SINPAC Switchhaving cut in voltage rating closestto this number.
Split Phase Motors
*Consult factory
*230V<300V
260V230V300-369V
310V230V370-492V
410V230V>492V*115V<150V
130V115V150-175V
147V115V176-200V
165V115V>200V
Cut OutVoltageRating
Voltage AcrossSINPAC SwitchTerminals 1 & 2
MeasuredVoltage
*230V<70V
60V230V>70V*115V<15V
10V115V15-40V
30V115V>40V
Cut InVoltageRating
Voltage AcrossSINPAC SwitchTerminals 1 & 2
MeasuredVoltage
S-795-12 23
Caution: Application of 230 Vac to theline input terminals (1 and 2) of a 115Vac rated SINPAC Switch will result inimmediate switch failure. The switchmay rupture and emit smoke.
ImportantPlease read these instructions carefullybefore installing, operating, or servicingyour SINPAC Switch. Failure to complywith these instructions could causeinjury to personnel and/or damage toproperty if the switch is installed oroperated incorrectly. For definition oflimited warranty/liability, contactRexnord Corporation, Stearns Division,120 North Broadway, Milwaukee,Wisconsin 53202, (414) 272-1100.
Initial Inspection and HandlingUpon receipt, check for packagedamage. Note any signs of damage onappropriate shipper forms. Uponopening package, if concealed damageis found, immediately file a claim withcarrier.
Check the label to verify that dataconforms to specifications of orderedswitch and the connection diagramagrees with labeling.
Caution1. Installation and servicing must be
made in compliance with all localsafety codes includingOccupational safety and Health Act(OSHA). All wiring and electricalconnections must comply with theNational Electric Code (NEC) andlocal electric codes in effect.
2. To prevent an electrical hazard,disconnect power source beforeworking on the motor. If powerdisconnect point is out of sight, lockdisconnect in the off position andtag to prevent accidentalapplication of power.
3. Make certain power sourceconforms to the requirementsspecified on the SINPAC Switchnameplate.
4. Installation and servicing should beperformed only by qualifiedpersonnel familiar with theoperation of the SINPAC Switch.
5. Determine what type of start switchthe motor presently has:
a) Externally mounted electronicswitch – go to Step 6.
b) Internally mounted electronicswitch – go to Step 6.
c) Externally or internally mountedmechanical switch – it is not
necessary to remove theexisting centrifugal switchactuating mechanism, but iffeasible, it should be removedas it is no longer needed, andcan cause future mechanicalproblems in the motor shouldthe mechanism fail. Follow themanufacturers recommendationwhen removing the shaft endbearing, if necessary, to take offthe centrifugal actuator.
6. Remove the existing electronicswitch. Determine the existingwiring diagram. Mark the existingwires and determine which wirescan be reused for installation ofthe SINPAC Switch. Select alocation in the motor conduit box orendbell for mounting the SINPACSwitch.
If a metal enclosure version ofSINPAC Switch is being used, theswitch with SINPAC Switch gasketmay be mounted on an externalmounting surface such as theexterior of the conduit box. Plasticenclosure versions of the SINPACSwitch should be mountedinternally, within the conduit box, orexternally, under a capacitorhousing.
IMPORTANT: SINPAC Switch ina metal enclosure must havethe metal enclosure grounded.
The temperature at themounting location should notexceed 65°C (149°F). (2CVRtemperature should not exceed55°C.)
TEFC/TENV motors requireexternal mounting of SINPACSwitch.
7. Refer to motor manufacturer’swiring diagram to aid in identifyingterminal locations for the startwinding switch, start winding, startand run capacitors (if needed) andAC line.
8 Connect the SINPAC circuit per theconnection diagram (on Pages24-25 or 26-27) using insulatedterminals. If the connections aremade incorrectly, the result will beno starting torque and possibledamage to the circuit and/or motor.
CAUTION: Be sure thatappropriate insulation is usedbetween the terminals of the switchand the body of the motor orconduit box.
If mounted external to motor,always use gasket supplied withkit.
9. DO NOT USE a Variac to graduallyincrease the voltage to the motorstarting circuit when SINPACSwitch is installed.
10. Reassemble the motor withSINPAC Switch installed, so as tonot damage lead wires.
11. If the motor fails to start or the startwinding does not cut out properly,see Troubleshooting Guide (Page29).
12. Hipot test procedures:
Motors 250 Volts or Less and1/2 Horsepower or LessThe motor, equipped with SINPACSwitch, shall be tested for dielectricwithstand (hipot), by theapplication of a 1200 voltsinusoidal potential, in the range of40-70 Hz, for 1 second. During thetest, each lead of the primarymotor wiring, accessible at theconnection board or conduit box,are to be connected together andto one terminal of the testequipment, and the second testequipment terminal is to beconnected to the accessible deadmetal.
Motors 250 Volts or Less andMore Than 1/2 HorsepowerThe motor, equipped with SINPACSwitch, shall be tested for dielectricwithstand (hipot), by theapplication of an 1800 voltsinusoidal potential, in the range of40-70 Hz, for 1 second. During thetest, each lead of the primarymotor wiring, accessible at theconnection board or conduit box,are to be connected together andto one terminal of the testequipment, and the second testequipment terminal is to beconnected to the accessible deadmetal.
13. CAUTION: The terminals of theSINPAC Switch should not be usedas the junction for this field wiring.
24
230 Volt 50/60 HzMotor Operation
115 Volt 50/60 HzMotor Operation
SINPAC SwitchRatingCatalog Number
Not Application
230 Volts2CV-352CV-50
Connect toCapacitor Start
Motors Only
115 VoltsVR-16VR-40VR-50
CVR-80Connect toCapacitor
Start/CapacitorRun Motors
CV-16CV-25CV-40CV-50
Connect toCapacitor Start
Motors Only
115 Volts
Not Application
230 Volts
2PV-16Connect toSplit PhaseMotors Only
115 VoltsPV-16PV-25PV-40
Connect toSplit PhaseMotors Only
Wiring Diagrams for SINPAC Switches
3 2 1
3 2 1
230 Voperation
CS – Start Capacitor, M – Motor Main Winding, CR – run Capacitor, ST – Motor Start Winding
S-795-13 25
230 Volt 50/60 HzMotor Operation
115 Volt 50/60 HzMotor Operation
SINPAC SwitchRatingCatalog Number
Not Application
230 Volts2CVR-702CVR-90
Connect toCapacitor
Start/CapacitorRun Motors
Not Application
230 Volts2CVR-702CVR-90
Connect toCapacitor Start
Motors
IR-25IR-40
Connect toInstant ReverseCapacitor Start
Motors Only
Not Application
230 Volts2VR-352VR-50
Connect toCapacitor
Start/CapacitorRun Motors
CS – Start Capacitor, M – Motor Main Winding, CR – run Capacitor, ST – Motor Start Winding
115 Volt Operation Dual Voltage Motor Using TwoFull Voltage 2 or 3 Pole Single-Phase Reversing
Contactors with Mechanical Interlock(Electrical Interlock Optional)
230 Volt Operation Dual Voltage Motor Using TwoFull Voltage 2 or 3 Pole Single-Phase Reversing
Contactors with Mechanical Interlock(Electrical Interlock Optional)
Reversing contacts are not part of SINPAC Switch. Reversing contacts are not part of SINPAC Switch.
Reversing contacts are not part of SINPAC Switch.Drum switch is not part of SINPAC Switch.
115 Volts
Wiring Diagrams
26
EASY STEPSWIRING OF MOTOR
EQUIPPED WITHMECHANICAL SWITCH
EASY WIRING OF MOTOREQUIPPED WITH SINPAC
ELECTRONIC SWITCH
MOTOR LEAD WIRENUMBERING
Split Phase Motors1. Disconnect the mechanical
switch lead which isconnected to the startwinding and reconnect thislead to SINPAC Switchterminal three (3).
2. Disconnect other mechanicalswitch lead marked T5 andreconnect this lead toSINPAC Switch terminaltwo (2).
3. Join SINPAC Switch terminalone (1) with motor lead T8.
Sin
gle
Vo
ltag
e w
ith
Th
erm
al P
rote
ctio
nS
ing
le V
olt
age
wit
ho
ut
Th
erm
al P
rote
ctio
n
Capacitor Start Motors1. Disconnect the mechanical
switch lead (CS1) which isconnected to the startcapacitor and reconnect thislead to SINPAC Switchterminal three (3).
2. Disconnect other mechanicalswitch lead marked T5 andreconnect this lead toSINPAC Switch terminaltwo (2).
3. Join SINPAC Switch terminalone (1) with motor lead T8.
4. Join SINPAC Switch terminalfour (4) with the lead off thestart winding and startcapacitor. (Labeled in theconnection diagram as CS2.)
Sin
gle
Vo
ltag
e w
ith
Th
erm
al P
rote
ctio
nS
ing
le V
olt
age
wit
hT
her
mal
Pro
tect
ion
Du
al V
olt
age
wit
hT
her
mal
Pro
tect
ion
Du
al V
olt
age
wit
ho
ut
Th
erm
al P
rote
ctio
n
SYMBOL KEY: M = Main winding, ST = Start winding, CS = Start capacitor, CR = Run capacitor, CS1 = Lead between SINPAC Switchterminal three (3) and start capacitor (CS), CS2 = Lead between SINPAC Switch terminal four (4), start capacitor (CS) and start winding (ST)
Use on only the followingmodel series:PV-16, PV-25
PV-40 & 2PV-16
Use on only the followingmodel series:
CV-16CV-25CV-40CV-50VR-16VR-40VR-50
CVR-80IR-25IR-40
2CV-352CV-50
2CVR-702CVR-90
L1 L2 Join
Counterclockwiserotation P1 T4, T5 T1, T8
Clockwise rotation P1 T4, T8 T1, T5
–
T2,T3& T8
P2,T3& T5
P2,T5
T2,T4& T8
T4
P1
P1
Clockwiserotation
Clockwiserotation
–
T2,T3& T5
P2,T3& T8
P2,T8
T2,T4& T5
T4
P1
P1
Counterclock-wise rotation
Counterclock-wise rotation
Lowername-plate
voltage
Highername-plate
voltage
JoinJoinL2L1
Clockwiserotation
Counterclock-wise rotation
–
–
T2,T4& T8
T1,T3& T5
T2,T4& T5
T1,T3& T8
Clockwiserotation
Counterclock-wise rotation
T2,T3& T5
T2,T3& T8
Join
T4,T8T1
Lowername-plate
voltage
T4,T5T1Highername-plate
voltage
L2L1
T4, T8T1, T5Clockwise rotation
T4, T5T1, T8Counterclockwise
rotation
L2L1
T1, T5T4, T8P1Clockwise rotation
T1, T8T4, T5P1Counterclockwise
rotation
JoinL2L1
T4, T8T1, T5Clockwise rotation
T4, T5T1, T8Counterclockwise
rotation
L2L1
S-795-14 27
SYMBOL KEY: M = Main winding, ST = Start winding, CS = Start capacitor, CR = Run capacitor, CS1 = Lead between SINPAC Switchterminal three (3) and start capacitor (CS), CS2 = Lead between SINPAC Switch terminal four (4), start capacitor (CS) and start winding (ST)
Du
al V
olt
age
wit
ho
ut
Th
erm
al P
rote
ctio
nD
ual
Vo
ltag
e w
ith
Th
erm
al P
rote
ctio
nS
ing
le V
olt
age
wit
ho
ut
Th
erm
al P
rote
ctio
nS
ing
le V
olt
age
wit
hT
her
mal
Pro
tect
ionCapacitor Start/
Capacitor Run Motors1. Disconnect the mechanical
switch lead (CS1) which isconnected to the startcapacitor and reconnect thislead to SINPAC Switchterminal three (3).
2. Disconnect other mechanicalswitch lead marked T5 andreconnect this lead toSINPAC Switch terminaltwo (2).
3. Join SINPAC Switch terminalone (1) with motor lead T8.
4. Join SINPAC Switch terminalfour (4) with the lead off thestart winding, start capacitorand run capacitor. (Labeledin the connection diagram asCS2.)
5. Make sure the other side ofthe run capacitor isconnected to the motor leadT5 along with SINPAC Switchterminal two (2).
MOTOR LEAD WIRENUMBERING
EASY WIRING OF MOTOREQUIPPED WITH SINPAC
ELECTRONIC SWITCH
WIRING OF MOTOREQUIPPED WITH
MECHANICAL SWITCHEASY STEPS
Use on only the followingmodel series:
VR-16VR-40VR-50
CVR-802VR-352VR-50
2CVR-702CVR-90
T1, T5T4, T8P1Clockwise rotation
T1, T8T4, T5P1Counterclockwise
rotation
JoinL2L1
T4, T8T1, T5Clockwise rotation
T4, T5T1, T8Counterclockwise
rotation
L2L1
Clockwiserotation
Counterclock-wise rotation
–
–
P2,T3& T5
T2,T4& T8
P1
P2,T3& T8
T2,T4& T5
P1
Clockwiserotation
Counterclock-wise rotation
T2,T3& T8
T2,T3& T5
Join
P2,T5T4P1
Lowername-plate
voltage
P2,T8T4P1Highername-plate
voltage
JoinL2L1
Clockwiserotation
Counterclock-wise rotation
–
–
T2,T4& T8
T1,T3& T5
T2,T4& T5
T1,T3& T8
Clockwiserotation
Counterclock-wise rotation
T2,T3& T5
T2,T3& T8
Join
T4,T8T1
Lowername-plate
voltage
T4,T5T1Highername-plate
voltage
L2L1
Procedure for Checking SINPAC Switches
28
1. Disconnect the SINPAC Switchfrom the motor and measure theresistance between terminals 2and 3. If the resistance is less than500K, the SINPAC Switch hasbeen shorted or damaged, andmust be replaced. If the resistanceis infinite, the switch may not bedamaged.
CAUTION: Do not use megger totest motor circuit with SINPACSwitch. Proceed to Step 3 if youhave a PV switch.
2. If resistance across SINPACterminal 2 and 3 is greater than500K and you have a capacitorstart, instant reverse, or capacitorstart/capacitor run SINPAC Switch,use Diagram 1.
115 V SINPAC Switch – 115 Vincandescent light (L) (at least 25watts) and 115 Vac power source.
230 V SINPAC Switch – 230 Vincandescent light (L) or two 115 Vincandescent light (L) (at least 25watts) in series and 230 Vac powersource.
a) Connect one line of AC powerto terminal 1 through a lineswitch.
b) Connect incandescent light (L)between terminals 1 and 3 ofSINPAC Switch.
c) Jumper terminals 1 and 4 ofSINPAC Switch.
d) Connect other line of AC powerto terminal 2 of SINPAC Switch.
Note 1: Apply rated AC voltage tothe SINPAC Switch.
Note 2: The incandescent light (L)will illuminate if the SINPAC Switchis operable.
Note 3: If the incandescent light(L) fails to illuminate, the SINPACSwitch has been damaged andmust be replaced.
Note 4: Turn off voltage anddisconnect the SINPAC Switch.
3. If resistance across SINPACterminal 2 and 3 is greater than500K and you have a split phaseSINPAC Switch, use Diagram 2.
a) Connect one line of AC powerto terminal 1 through a lineswitch.
b) Connect a (25 watt)incandescent light (L) betweenterminals 1 and 3 of SINPACSwitch.
c) Connect other line of AC powerto terminal 2 of SINPAC Switch.
Note 1: Apply rated AC voltage tothe SINPAC Switch.
Note 2: If the incandescent light(L) begins to blink after 1/2second, the SINPAC Switch isoperable.
Note 3: If the incandescent light(L) fails to illuminate or staysilluminated, the SINPAC Switchhas been damaged and must bereplaced. Both test must beperformed and passed to indicatea minimally good switch.
Note 4: Turn off power anddisconnect the SINPAC Switch.
Diagram 1
Diagram 2
S-795-15 29
Install SINPAC instant reverse switch.Ensure that instant reverse SINPACSwitch was installed to replace anymechanical instant reversing switch.
Wrong switch installed. CV or VRSeries installed instead of instantreverse SINPAC Switch.
If a single start capacitor was originallyinstalled, replace with two start capacitorsof twice the capacitance valve and samevoltage rating as the original andconnected in series.
Connect a 15,000 ohm, 2 watt bleederresistor across the start capacitor(s).
De-energize motor and check startcapacitor and SINPAC Switch.
High cycle rate. Excessive motortemperature.
Premature start capacitorfailures.
Replace switch.See Procedure to check SINPACSwitch. Also check start capacitor(Page 28).
Switch failure.
Replace start capacitor and SINPACSwitch as appropriate.
De-energize motor and check capacitorand SINPAC Switch.
Start capacitor failure on capacitorstart or cap. start/cap. run motors.
Motor worked properly formany cycles of operations(days, weeks, months,years), then failed.
Upon overload, thestart winding is notreenergized (no cut in)
Change mounting location of switch.SINPAC Switches can be remotelymounted.
Check the operating ambienttemperature of SINPAC Switch. Itshould be less than 80°C (185°F).
SINPAC Switch exposed toexcessive temperature.
Replace SINPAC Switch after checkingall of above possible causes.
See Procedure to check SINPACSwitch (Page 28).
Damaged SINPAC Switch.
Correct wiring.De-energize and check the connectiondiagram. Be sure that terminal 4 ofswitch is connected to the junction ofthe start capacitor and start winding(Pages 24-27).
Incorrect connection of SINPACSwitch for capacitor start motors.
Reduce load. Replace the motor with anappropriately larger sized motor.
Check the load and motorcharacteristics.
Mismatch of motor and load. Motorcannot reach cut out speed.
Rewind motor.De-energize and check the startwinding.
Start winding damaged.
Increase the AC line voltage.Measure the AC line voltage acrossthe motor terminals.
AC line voltage too low.
Select proper SINPAC Switch.Perform SINPAC Switch SelectionProcedure as described on Page 28.
Start winding induced voltage is toolow when motor reaches desired cutout speed. The voltage is due to thelow winding-ratio of certain old stylemotors, foreign motors, convertedmotors, and special motor designs.
Replace capacitor.De-energize motor, discharge andcheck the capacitor.
Start capacitor shorted.
Change switch —Check SINPAC Switch for damage andreplace with correct switch.
Consult selection chart — Measure voltage across wiresconnected to terminals 1 and 2.
Wrong series SINPAC Switchinstalled — 115 V SINPAC Switchconnected to 230 V start winding.
Replace SINPAC Switch, if damaged.Remove switch and check the currentof the start winding. See Procedure tocheck SINPAC Switch (Page 28).
Current in the start winding isabove rating of SINPAC Switch.
Motor starts, but switchfails to cut out when cutout speed is reached.
Ground metal case.Check continuity between SINPACSwitch metal case and ground.
SINPAC Switch, if it has a metalenclosure, is not grounded.
Replace SINPAC Switch after checkingall of the above possible causes
See Procedure to check SINPACSwitch (Page 28)
SINPAC Switch damaged(open circuit).
Replace switch and hipot motor, withinstalled SINPAC Switch, by tying all motorand SINPAC Switch leads together.
See Procedure to check SINPACSwitch (Page 28)
Motor hipot tested with switchinstalled without motor andSINPAC Switch leads tied together.
Check the start winding. Motor may haveto be rewound. Infinite resistance wouldshow an open winding or looseconnection.
De-energize and disconnect. Measurethe resistance of the start winding.
Start winding open.
Replace fuses as required and apply ACline voltage.
De-energize, check AC line fuses.Check wiring and connection diagram.
No line voltage.
Increase voltage.Measure line voltage at the motorterminals.
AC line voltage too low.
Remove obstruction.Check for jam or obstruction.Motor not free to rotate.
Wait until cool down. Check/replacethermal overload. Correct motor andSINPAC Switch wiring.