Lab Centralized Lab Centralized Demand Demand Controlled Controlled Ventilation Ventilation (CDCV) (CDCV) Marc Gomez, EH&S Marc Gomez, EH&S Rebecca Lally, EH&S Rebecca Lally, EH&S Chris Abbamonto, Facilities Chris Abbamonto, Facilities Management Management Applying a New and Emerging Applying a New and Emerging Technology Technology
37

CDCV Webinar 01.28.09

May 22, 2015

Download

Technology

cabbamonto

Follow up webinar presentation to our September 2008 Labs 21 presentation
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: CDCV Webinar 01.28.09

Lab Centralized DemandLab Centralized DemandControlled VentilationControlled Ventilation

(CDCV)(CDCV)Marc Gomez, EH&SMarc Gomez, EH&S

Rebecca Lally, EH&SRebecca Lally, EH&S

Chris Abbamonto, Facilities ManagementChris Abbamonto, Facilities Management

Applying a New and Emerging TechnologyApplying a New and Emerging Technology

Page 2: CDCV Webinar 01.28.09

University of California, IrvineUniversity of California, Irvine

Category one research universityCategory one research university$16M annual utilities budget$16M annual utilities budget

Lab buildings consume 2/3 of campus energyLab buildings consume 2/3 of campus energyMany energy initiatives to reduce carbon footprintMany energy initiatives to reduce carbon footprint

Page 3: CDCV Webinar 01.28.09

Does Centralized Demand Does Centralized Demand Controlled Ventilation (CDCV) Controlled Ventilation (CDCV)

Allow Us To Allow Us To Reduce Ventilation RatesReduce Ventilation Rates

& Save Energy & Save Energy Without Compromising Safety?Without Compromising Safety?

This InitiativeThis Initiative

Page 4: CDCV Webinar 01.28.09

Lab Ventilation RatesLab Ventilation Rates

Often set at a “constant rate” 24/7Often set at a “constant rate” 24/7 Recommended range 4 to 12 air changes per Recommended range 4 to 12 air changes per

hourhour Usually excessive during low-level process Usually excessive during low-level process

activity or non-occupancyactivity or non-occupancy Explore possibility of “set back” based on lab Explore possibility of “set back” based on lab

pollutant concentrationpollutant concentration

Page 5: CDCV Webinar 01.28.09

Components of Components of Centralized Demand Centralized Demand

Controlled Ventilation (CDCV)Controlled Ventilation (CDCV)

“Creating a Smart Lab”“Creating a Smart Lab”

Page 6: CDCV Webinar 01.28.09
Page 7: CDCV Webinar 01.28.09

CDCV & Energy $avingsCDCV & Energy $avings Monitor Air ContaminantsMonitor Air Contaminants

ReduceReduce air changes per hour (ACH) air changes per hour (ACH)

if no contaminants detectedif no contaminants detected

IncreaseIncrease air changes per hour (ACH) air changes per hour (ACH)

when contaminants detectedwhen contaminants detected

Page 8: CDCV Webinar 01.28.09

CDCV & Energy $avingsCDCV & Energy $avings ChallengeChallenge

Balance energy savings & safetyBalance energy savings & safety

Maximize

Energy

Savings

WithoutCompromising

Safety

Page 9: CDCV Webinar 01.28.09

CDCV & Energy $avingsCDCV & Energy $avings Recipe for SuccessRecipe for Success

SafetyManagement

Visionary & Supportive

UpperManagement

Engineers

FacilityManagersPatience

Team Synergy

Supportive Users/Researchers

Page 10: CDCV Webinar 01.28.09

Is CDCV effective Is CDCV effective in reducing the contaminant in reducing the contaminant

concentration from concentration from a spill in a lab?a spill in a lab?

Page 11: CDCV Webinar 01.28.09

Spill LocationsSpill Locations

Farthest point from the hood

In front of the hood

Benchtop

Page 12: CDCV Webinar 01.28.09

Spill Test Methodology 500 ml of acetone500 ml of acetone

Baseline measurement and with CDCV activated Baseline measurement and with CDCV activated

Photoionization detector - 10.6 eV lampPhotoionization detector - 10.6 eV lamp MiniRae 2000 instrumentMiniRae 2000 instrument CDCVCDCV

CDCV ventilation activation level: 0.5 ppmCDCV ventilation activation level: 0.5 ppm

CDCV polling interval time: 14-17 minutesCDCV polling interval time: 14-17 minutes

Page 13: CDCV Webinar 01.28.09

Distributed, Multi-Point Air-Sampling NetworkDistributed, Multi-Point Air-Sampling Network

Air Data Air Data RouterRouter

Room Room SensorSensor

Page 14: CDCV Webinar 01.28.09

Spill Farthest Point from the hood - Sash Closed

0

20

40

60

80

100

120

140

160

180

200

220

240

260

280

300

320

340

360

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75

minutes after spill

pp

m o

f A

ce

ton

e

Baseline 6 ACH- w/out CDCV

4 ACH (w/CDCV)

Air Contaminant Monitoring ResultsAir Contaminant Monitoring Results Spill Farthest Point from Hood - Sash Closed Spill Farthest Point from Hood - Sash Closed

4 ACH

12 ACH

CDCV on @ 5 min.

Page 15: CDCV Webinar 01.28.09

Air Contaminant Monitoring ResultsAir Contaminant Monitoring Results Spill Farthest Point from Hood - Sash Closed Spill Farthest Point from Hood - Sash Closed

Spill Farthest Point from the hood - Sash Closed

0

20

40

60

80

100

120

140

160

180

200

220

240

260

280

300

320

340

360

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75

minutes after spill

pp

m o

f A

ce

ton

e

Baseline 6 ACH- w/out CDCV

4 ACH (w CDCV)

4 ACH

12 ACH

CDCV on @ 17 min.

Page 16: CDCV Webinar 01.28.09

Air Contaminant Monitoring ResultsAir Contaminant Monitoring Results Spill Farthest Point from Hood - Sash Closed Spill Farthest Point from Hood - Sash Closed

Spill Farthest Point from the hood - Sash Closed

0

20

40

60

80

100

120

140

160

180

200

220

240

260

280

300

320

340

360

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75

minutes after spill

pp

m o

f A

ceto

ne Baseline 6 ACH- w/out CDCV

4 ACH (w CDCV)

4 ACH (w/CDCV)

Page 17: CDCV Webinar 01.28.09

Spill Results SummarySpill Results Summary

EventEvent Pre-spillPre-spill

ACHACH

Post-Post-spill spill

ACHACH

Minutes Minutes post- spill post- spill ventilation ventilation increasedincreased

*Peak*Peak

Conc.Conc.

(ppm)(ppm)

Clearance Clearance

TimeTime

(min.)(min.)

BaselineBaseline

SpillSpill

w/o CDCVw/o CDCV

66 66 n/an/a 339339 7373

Spill 1 Spill 1 w/CDCV w/CDCV 44 1212 55 219219 7070

Spill 2Spill 2

w/CDCVw/CDCV 44 1212 1717 227227 7676

* MiniRae 2000

Page 18: CDCV Webinar 01.28.09

ConclusionsConclusions

CDCVCDCV Effective at sensing acetone levelsEffective at sensing acetone levels Is responsiveIs responsive When activated, lower peak concentration in open areasWhen activated, lower peak concentration in open areas

Polling time could result in delay in detecting spillPolling time could result in delay in detecting spill

No significant difference in clearance timeNo significant difference in clearance time

Page 19: CDCV Webinar 01.28.09

Lessons Learned ~ Next StepsLessons Learned ~ Next Steps Current sensor suite does not detect all chemicals Current sensor suite does not detect all chemicals

Sensor selection should be based on risk assessment Sensor selection should be based on risk assessment

Calibration frequency needs validationCalibration frequency needs validation

Confirm accurate performance of saturated sensorConfirm accurate performance of saturated sensor

Set polling interval frequency based on risk assessment Set polling interval frequency based on risk assessment

““Fail safe” to 6 ACH neededFail safe” to 6 ACH needed

Additional spill testing neededAdditional spill testing needed

Page 20: CDCV Webinar 01.28.09

Other Safety ConsiderationsOther Safety Considerations

Energy Mgmt System Energy Mgmt System Provides health & safety infoProvides health & safety info Not meant to be a life safety systemNot meant to be a life safety system

Elimination of small emissionsElimination of small emissions

Emergency override exhaust ventilation “Emergency override exhaust ventilation “redred” button” button

Provide visual display outside labProvide visual display outside lab

Notification to EH&S staff of spill Notification to EH&S staff of spill

Instant messaging to facility staff Instant messaging to facility staff of system problemsof system problems

Preventative maintenance issuesPreventative maintenance issues

Page 21: CDCV Webinar 01.28.09

Energy Savings?Energy Savings? Goal: Reduce ACH rate by reducing CFM delivered Goal: Reduce ACH rate by reducing CFM delivered

to individual laboratory rooms by way of CDCVto individual laboratory rooms by way of CDCV Step 1 – Select Building/LabsStep 1 – Select Building/Labs

ACH Reduction Constraints (FH, Freezers, Solar Heat)ACH Reduction Constraints (FH, Freezers, Solar Heat) VAV Controls and EMSVAV Controls and EMS

Step 2 – Retro-CommissioningStep 2 – Retro-Commissioning Bad CardsBad Cards Bad PoppetsBad Poppets Poor Thermostat LocationPoor Thermostat Location Economizer (temp. reset 65 deg F)Economizer (temp. reset 65 deg F) Low Duct Static PressureLow Duct Static Pressure CFM Adjustment for Actual Room SizeCFM Adjustment for Actual Room Size

Page 22: CDCV Webinar 01.28.09
Page 23: CDCV Webinar 01.28.09
Page 24: CDCV Webinar 01.28.09
Page 25: CDCV Webinar 01.28.09
Page 26: CDCV Webinar 01.28.09
Page 27: CDCV Webinar 01.28.09

Energy Savings?Energy Savings?

Step 3 – InstallationStep 3 – Installation Hard wired approach vs. EMS controlHard wired approach vs. EMS control Valve adjustment (clamps)Valve adjustment (clamps)

Step 4 – Trial and ErrorStep 4 – Trial and Error Fail Safe Mode?? (no notification)Fail Safe Mode?? (no notification) ACH verification (Room CF)ACH verification (Room CF) Spill TestingSpill Testing CFM verification with EMS (same source!)CFM verification with EMS (same source!)

Page 28: CDCV Webinar 01.28.09

Lessons LearnedLessons Learned

Step 5 – Evaluation of the SystemStep 5 – Evaluation of the System There is an inherent gain of useful There is an inherent gain of useful

information such as lab temperature, information such as lab temperature, sensed data, and potential commissioning sensed data, and potential commissioning data (LEED).data (LEED).

Areas for improvement:Areas for improvement: Front End with ACH would be helpfulFront End with ACH would be helpful Direct user notification of failureDirect user notification of failure Considerations: User training and service Considerations: User training and service

contract for sensor change-out in original contract for sensor change-out in original contract.contract.

Page 29: CDCV Webinar 01.28.09

Croul Hall CFM Rate Croul Hall CFM Rate ChangeChange

Page 30: CDCV Webinar 01.28.09

System Payback?System Payback?

System Installation Cost approx. System Installation Cost approx. $125,000 not including deferred $125,000 not including deferred maintenance and retro-commissioning.maintenance and retro-commissioning.

Observed CFM reduction in installed Observed CFM reduction in installed labs during a two week snapshot labs during a two week snapshot comparison ~6,100comparison ~6,100

Anticipated payback: 2-5 yearsAnticipated payback: 2-5 years Still fine tuning the systemStill fine tuning the system

Page 31: CDCV Webinar 01.28.09

Next StepsNext Steps

Croul Hall - CDCVCroul Hall - CDCV 4/2 ACH Setback with Occupancy Sensing4/2 ACH Setback with Occupancy Sensing Red buttonRed button

Croul Hall - KISSCroul Hall - KISS Occupancy sensing 4/2 ACHOccupancy sensing 4/2 ACH Visual and audiable signal to occupantVisual and audiable signal to occupant Red buttonRed button

Page 32: CDCV Webinar 01.28.09

Next StepsNext Steps

New Construction Implementation and New Construction Implementation and Testing, UC Irvine Gross HallTesting, UC Irvine Gross Hall Occupancy sensing 4/2 ACHOccupancy sensing 4/2 ACH Red buttonRed button

Additional Testing (3Additional Testing (3rdrd Party) of System Party) of System Components (a.k.a. Electronic Slop)Components (a.k.a. Electronic Slop)

MBCx and Energy Savings VerificationMBCx and Energy Savings Verification LEED-EB CertificationLEED-EB Certification

Page 33: CDCV Webinar 01.28.09

Next StepsNext Steps

Your inputYour input Other studiesOther studies

Page 34: CDCV Webinar 01.28.09

QuestionQuestion

Does Centralized Demand Does Centralized Demand Controlled Ventilation (CDCV) Controlled Ventilation (CDCV)

Allow Us To Allow Us To Reduce Ventilation RatesReduce Ventilation Rates

& Save Energy & Save Energy Without Compromising Safety?Without Compromising Safety?

Page 35: CDCV Webinar 01.28.09

AnswerAnswer

CDCV has merits. Further CDCV has merits. Further study is needed to gain a study is needed to gain a

better understanding of the better understanding of the system. There is energy system. There is energy

savings, further quantification savings, further quantification is also needed.is also needed.

Page 36: CDCV Webinar 01.28.09

Webinar Q&AWebinar Q&A

Page 37: CDCV Webinar 01.28.09

Questions?Questions?