ANALYSIS AND MODELLING OF CYCLIC LOADING POWER TRANSFORMER Thye Hun Shen Master of Engineering 2010
ANALYSIS AND MODELLING OF CYCLIC LOADING POWER TRANSFORMER
Thye Hun Shen
Master of Engineering 2010
Jl a . .. .. . '''k.lUW· , tU.ademi~ m MALAY rA SARAWAK
ANALYSIS AND MODELLING OF CYCLIC LOADING POWER TRANSFORMER
P.KHIDMAT MAKL.UMAT AKADI!MIK
111I11~JIOCm1J1H III
THYE HUN SHEN
A thesis submitted in fulfillment of requirements for the degree of Master of Engineering
Faculty of Engineering UNIVERSITI MALAYSIA SARAWAK
2010
ACKNOWLEDGEMENT
First and foremost I would like to express my appreciation to everyone who had
given me assistances throughout this project. My heartfelt thanks to Ir. Dr. Mohammad
Shahril Osman and Mr. Ngu Sze Song as my academic supervisors. Special thanks to
Mr. Leslie Chili and Mr. Kee Song Khai for being my industrial supervisors and giving
me endless guidance along the completion of this thesis.
I woutd like to express my deepest thanks to my family for their love,
encouragement and support throughout the whole process.
Not forgotten to thank my colleagues and friends, Hung Tze Mau, Lai Koon
Chun, Chai Choung Jung, James Tan, Kong Tzer Sin, Charlie Sia and Voon Chun Yung
for their helping hands to solve the project difficulties.
Finally, my deepest gratitude goes out to all the lecturers in Faculty of
Engineering who kindly share their knowledge and experience. Not forgetting my
dearest parents, brothers and sisters who always give me moral support, encouragement,
assistance and comfort. To them, I wish the best of luck and may the future hold bright
for you all.
11
ABSTRACT
Transformers can transfer the required electricity to the residential, commercial and
industrial are~ to fulfil the consumption demand. This study targets to determine the
permitted overloading conditions and to maximize the electricity supply without
reducing the lifespan of the transformer by setting the necessary transformer parameters.
This study concludes that the loading curve pattern and power usage are very much
dependent on the distribution network in each substation. The permitted overloading
conditions for Planned Load Beyond Nameplate (PLBN), Long-Time Emergency Load
(LTE) and Short-Time Emergency load (STE) are estimated. The parameters of the
transformer, i.e. loss of life, permitted overloading conditions and maximum load
capacity were examined in this study. The evaluated results reveal that the transformer's
loss of life correlates to the capacity loading curve pattern, power factor and ambient
temperature. Besides, the transformer's loss of life is highly dependent on the capacity
loading curve pattern. Other information, namely loading curve pattern, power factor
and factory test acceptance (F AT) reports are referred as well. Results reveal that the
loss of life for each transformer is approximately 0.0 % over 30 years of lifespan. The
results imply that the lifespan of every transformer in the substations can last for over
30 years.
----~,------------------------------
11l
~
ABSTRAK
Tranformer-transformer boleh menghantar bekalan elektrik kepada kawasan
kediaman, perdagangan dan kawasan perindustrian bagi memenuhi permintaan
mengunakan kuasa elektrik. Kajian ini mensasarkan bagi menentukan keadaan
pembekalan lebih muatan yang dibenarkan untuk memaksimurnkan bekalan elektrik
tanpa menjejaskan hayat transformer dengan menetapkan parameter tertentu. Kajian ini
menyimpulkan bahawa pola lengkung pemuatan dan penggunaan kuasa adalah banyak
bergantung pada rangkaian pengagihan kuasa. keadaan pembekalan lebih muatan yang
dibenarkan untuk Planned Load Beyond Nameplate (PLBN), Long-Time Emergency
Load (LTE) dan Short-Time Emergency load (STE) telah dianggarkan. Parameter bagi
transformer seperti kehilangan kehidupan, keadaan pembekalan lebih muatan yang
dibenarkan dan maksimum bekalan elektrik telah dikaji. Keputusan mendedahkan
bahawa kehilangan kehidupan transformer berhubung kait dengan pemuatan keupayaan
pola lengkung, faktor kuasa dan suhu ambien. Selain itu, kehilangan kehidupan
transformer adalah amat bergantung kepada pemuatan keupayaan pola lengkung.
Maklumat lain daripada pemuatan melengkok pola, faktor kuasa dan laporan-Iaporan
ujian penerimaan kilang telah d iruj uk. Keputusan .mendedahkan bahawa kehilangan
kehidupan bagi setiap transformer adalah lebih kurang 0.0 % lebih dari hayat 30 tahun.
Keputusan menunjukkan bahawa hayat bagi setiap transformer dalam stesen pencawang
boleh tahan lama selama lebih 30 tahun.
IV
t'Us.al K.JIidm 1 1HutUumill A"'~ucU\~ UNlVERSm MALAY IA ARAWAk
T ABLE OF CONTENTS
ACKNOWLEDGEMENT
ABSTRACT
ABSTRAK
TABLE OF CONTENTS
LIST OF FIGURES
LIST OF TABLES
ABBREVIATIONS
NOMENCLATURES
CHAPTER 1: INTRODUCTION
1.1 Background
1.2 Problem Statement
1.3 Modelling Application
1.4 Objectives
1.5 Outline of the Study
CHAPTER 2: LITERATURE REVIEW
2.1 Cyclic Loading Transformer
2.1.1 Nameplate
2.1.2 Oil-Cooled Systems
2.1.3 Loading Curve Pattern (CP)
2.1.4 Power Factor (PF)
2.2 Ambient Temperature
2.2.1 Measurement
11
1Il
IV
V
IX
Xl
XlIl
XIV
2
3
3
5
6
6
7
9
10
10
V
2.2.2 Computation 11
2.3 Transformer Thennal Response 12
2.3.1 Top-oil Temperature (TOT) 15
2.3.2 Winding Temperature Rise (WTR) 18
2.3.3 Hottest-spot Temperature (HST) 19
2.4 Loss of Life (LOL) 19
2.4.1 Daily Loss Rate of Loss of Life 20
2.4.2 Thennal Aging 22
2.5 Pennitted Overloading Conditions (POC) 23
2.5.1 Planned Load Beyond Nameplate (PLBN) 24
2.5.2 Long-Time Emergency Load (L TE) 24
2.5.3 Short-Time Emergency Load (STE) 22
2.6 Maximum Loading Capacity (ML) 25
2.7 Summary 26
CHAPTER 3: METHODOLOGY
3.1 Introduction 27
3.2 Methodology 27
3.3 Engineering Analysis 29
3.3.1 Study on Cyclic Loading Transformer 29
3.3.2 Significant Information 31
3.4 Substation Selection 32
3.5 Transformer Selection 35
3.5.1 Transfonner Types 35
3.6 On-Site Examination 37
Vi
3.6.1 Internal Inspection 37
,....
3.6.1.1 Loading Measurement 37
3.6.2 External Inspection 39
3.7 Modelling Development 41
3.7.1 Modelling on Top-Oil Temperature (TOT) 41
3.7.2 Modelling on Transformer Thermal Response, Loss of Life and 42 Permitted Overloading Conditions
3.7.3 Modelling on Maximum Load Capacity ofTransformer 46
3.8 Modelling Analysis 49
3.9 Summary 49
CHAPTER 4: RESULT AND ANALYSIS
4.1 Introduction 50
4.2 Power Factor 50
II4.3 Load Characteristic 53 II
4.3.1 Weekly and Daily Load Curve Characteristic 53
4.3.2 Power Usage on Weekly Load 60
4.4 Ambient Temperature 61
4.4.1 Ambient Temperature Computation using Weather Temperature 62 i r
4.4.2 Ambient Temperature Measured 63
4.5 Thermal Response Analysis by Using the Model 64
4.5.1 Top Oil Temperature (TOT) 65
4.5.2 Winding Temperature Rise (WTR) 68
4.5.3 Hottest-Spot Temperature (HST) 70
4.6 Loss oflife (LOL) 71
Vll
4.7 Estimated Patterns of Overloading Condition 73
4.8 Optimum Transformer Capacity 75
4.9 Summary 77
CHAPTER 5: CONCLUSION AND FURTHER WORK
5.1 Introduction 79
5.2 Conclusions 79
5.3 Further Work 80
REFERENCES 82
APPENDICES
Appendix A: Transformer Nameplate Value 87
Appendix B: Loading Computational 89
Appendix C: Thermal Response Simulation 101
Appendix D: Ambient Temperature Programming 105
Appendix E: Thermal Response, LOL and Overloading Condition 106 Programming
Appendix F: Recorded data for New Priok Substation, Kuching, 121 Sarawak
Appendix G: Recorded data for Airport Substation, Kuching, 127 Sarawak
Appendix H: Weather Temperature Data 129
Appendix I: Differences Equations between IEC and IEEE Standard 134
Appendix J: Estimation of Optimum Load and Thermal Response for 137 Oil-Nature-Air Nature Cooling Type Power Transformer
Appendix K: Prediction of the Overloading Condition by Using the 146 Nameplate Rating Value
Vlll
LIST OF FIGURES
Figure 2.0: Loading curve (IEEE standard C57.91, 1995) 7
Figure 2.1: Approximation method (Perera, et. ai, 2001) 9
Figure 2.2 : Simplified diagram of an ONAN type transformer (lEC 76-2, 13 1993)
Figure 2.3: Temperature distribution model (lEC 76-2, 1993) 14
transformers
andPOC
Figure 4.2: Comparison of power consumption patterns for domestic and
Figure 2.4: The maximum and saturation stages 16
Figure 3.0: Flow chart ofthe methodology 28
Figure 3.1: The power triangle 30
Figure 3.2: Loading patterns for Astana, New Priok, Satok and Airport 34
Figure 3.3: Oil-Natural-Air-Natural (ONAN without fan) power transformer 36
Figure 3.4: Oil-Natural-Air-Forced (ONAF with fan) power transformer 36
Figure 3.5: Smart meter inside the substation monitoring room 38
Figure 3.6: The experimental setup of the thermocouples 40
Figure 3.7: Flow chart for the computation of the thermal response, LOL 44
Figure 3.8: Equivalent loading for the transformer 47
Figure 3.9: Maximum load capacity and load curve multiplier flow chart 48
Figure 4.0: Weekly loading pattern for New Priok Substation transformer 54
Figure 4.1: Weekly loading pattern for Airport Substation transformer 55
56 commercial consumers (Kho et aI., 2008)
Figure 4.3: New Priok substation 33/11 kV distribution network with three 57 shared 30/35MV A transformers
Figure 4.4: Airport substation 33/11 kV distribution network with two 58 shared 20/25MV A transformers
IX
,......
Figure 4.5: Computation nominal ambient temperature from 2004 to 2006 62
Figure 4.6: Ambient Temperature on August 2007 and January 2008 64
Figure 4.7: Top oil temperature at 8 August 2007 in New Priok substation 65
Figure 4.8: Overloading pattern on transformer 2 when transformer 1 is 67 turned off at Airport's substation on 17 Jan 2008
Figure 4.9: Top-oil temperature on 17 Jan 2008 for Airport substation 68
Figure 4.10: Winding temperature rise for the New Priok substation 69
Figure 4.11: Winding temperature rise on Airport substation 69
x
J
I
LIST OF TABLES
Table 2.0: Common exponents used in the temperature determination 18 equations
Table 2.1: Normal insulation life of a well-dried, oxygen-free 65°C average 21 winding temperature rise insulation system at the reference temperature of 110°C
Table 2.2: Suggested maximum temperature limits for four types of loading 23
Table 3.0: Types and number oftransformer in four substations located in 33 Kuching
Table 3.1: Loading capacities for the substations 33
Table 3.2: The rated power range of three category transformer 35
Table 4.0: Daily Power Factor for Transformer 1, Transformer 2 and 51 Transformer 3 in New Priok Substation
Table 4.1: Daily Power Factor for Transformers 1 and 2 in Kuching Airport 52 Substation
Table 4.2: Time for the peak load on each transformer in New Priok substation 59
Table 4.3: Time for the peak load on both transformers in Airport substation 59
Table 4.4: Power usage of Airport and New Priok Substation 60
Table 4.5: Loading Capacity of Airport and New Priok Substations 61
Table 4.6: Mean Square Error (MSE) for Models A and B for New Priok 66 substation
Table 4.7: The maximum and minimum HST in New Priok substation 70
Table 4.8: The maximum and minimum HST in Airport substation 71
Table 4.9: Accumulative aging factor and loss oflife for the New Priok's 72 transformers
Table 4.10: Accumulative aging factor and loss of life for the Airport's 72 transformers
Table 4.11: Overloading characteristics for New Priok substation 73
Xl
1.
--,....
Table 4.12: Overloading characteristics for Airport substation 74
Table 4.13: Limits duration and maximum load per unit for different types of 75 loading
Table 4.14: Daily maximum loading capacity for each of the transformers 76
Table 4.15: Daily load curve multiplier for each of the transformers 77
XII
ABBREVIATIONS
Notation Description
ANSI America National Standard Institute CP loading curve pattern
FAT factory test acceptance FOA forced-oil-air FOW forced-oil-water HST hottest-spot temperature LCM load curve multiplier LOL loss oflife LTE long-time emergency load ML maximum loading capacity
ONAF oil-forced air-natural ONAN oil-natural air-natural
PF power factor PLBN planned loading beyond nameplate POC permitted overloading conditions
SCADA Supervisory Control and Data Acquisition STE short-time emergency load TOT top-oil temperature WTR winding temperature rise HST Hottest-spot temperature
Xlll
NOMENCLATURES
Notation Description II Unit I daily average ambient temperature hourly 8ad(h) °C
8adm(h) average daily maximum temperature hourly °C
8adn(h) average daily minimum temperature hourly °C
8ay yearly average temperature °C
ambient temperature 8a °C
8al ambient temperature measured °C
8a2 ambient temperature computed °C
A amplitude of yearly variation ofdaily mean -ambient temperature
B amplitude ofdaily variation for ageing-rate -calculation
hottest day ofa day dayDX
hottest hour of a day TX hour
day day number -
hour the hour of the day hour
top oil temperatures rise !18to °C
initial oil temperature rise at t = 0!18oi °C
ultimate oil temperature rise !18ou °C
top oil temperatures rise at rated kVA !18or °C I
t time interval for the loading hour
oil time constant hour'fro
oil time constant at rated kV A -'fTO,R
K ratio of the actual load to the rated load at the -interval time .
XIV
n cooling type exponent parameters
m
C
cooling type exponent parameters
thermal capacity of the transformer watt-hours/ °C \
'
Pr.R total loss at rated load watts
t-.e H winding hottest-spot temperature rise over top-oil temperature
°C
t-.eH.i initial hot-spot temperature rise at t = 0 °C
t-.eH ,u ultimate hot-spot rise over top oil °C
t-.eH.R hot-spot temperature rise at rated kVA °C
Tw interval time for the loading hour
eh hot-spot temperature °C
V relative rate of thermal ageing
L relative ageing rate
T total time interval of application hour
FAA accumulative aging factor
%LOL percent loss oflife per day
LOL loss of life
FEQA equivalent insulation aging factor for a total time period
FAA,n insulation aging acceleration factor for the time interval
PF power factor
L, ,L2 , LN various loads in percentage
t"t2 , tN durations ofthe load hour
R(t) function of the resistance
xv
a winding oil average temperature rise °C
b winding gradient °C
Ay,n monthly average weather temperature which n is °C the month number
8 max,,, maximum weather temperature °C
8 min, 1I minimum weather temperature °C
V voltage V
MWAR mega volt-amp-reactive MVAR
MW mega watt MW
XVI
CHAPTERl
INTRODUCTION
1.1 Background
Power transfonner is a device that transfers electricity energy from one circuit to
another through inductively coupled conductor. The electricity energy is transferred by
stepping up or stepping down the quantity of voltage through the internal winding. The
purpose of transferring the electricity energy by using power transfonner is to reduce
losses in transmission and distribution power system. Thus, power transformer becomes
an important medium in to connect the distribution and transmission system.
1.2 Problem Statement
Large amount of electricity is required to fulfil the demand of consumer daily
consumptions. The continuous flows of electricity supply to industrial and commercial
areas must be properly sustained. Thus, power transformer is required to supply
continuous flow of electricity in order to avoid electricity supply breakdown.
In most cases, the electricity supply breakdown is caused by the transformer failure
despite human mistakes. Transfonner failure is mainly due to overheat generation by
the internal elements of the transformer such as the core and winding. Various ways had
been implemented and studied to improve the reliability of the power transformer. For
--
instance, the backup system was installed every substation to reduce the frequency of
the transformer failure (Giverlberg et ai., 1996). Therefore, there is a crucial need to
understand the performance of the existing transformers and to maximize their loading
capacity with minimum risk of transformer failure.
In fact, the energy provider company have to overload the power transformer from
time to time in order to prevent the in short supply electricity. However, inconsistency
overloading process configurations will degrade transformer's lifespan rapidly.
According to McLyman (1988), the induced temperature rise by overloading process
must be controlled in order to prevent damage or breakdown to the inner wire insulation.
Thus, the relationship between the transformer lifespan (loss of life) and the permitted
overloading conditions should be investigated. A large amount of investment cost could
be saved by extending the transformer's lifespan without exceeding the critical point of
operation stated on the transformer's nameplate rated value.
1.3 Modelling Application
A mathematical modelling is carried out in this study to investigate the methodology
in prolonging the transformer's lifespan. The lifespan, or known as loss of life (LOL) in
this thesis, is modelled based on the ambient temperature and the thermal response
variables. These variables such as top-oil temperature (TOT), the winding temperature
rise (WTR) and the hottest-spot temperatures (HST) are relevant in studying. Other
relevant modelling inputs include the factory acceptance test (FAT) parameters, loading
curve and power factor. This model is beneficial to estimate the permitted overloading
2
I
conditions and increase the electricity supply without reducing the lifespan of the
transfonner. This model is able to calculate the maximum loading capacity for the
transfonner before reaching the plateau point ofoperation.
1.4 Objectives
The objectives ofthis study are stated as below:
I. To investigate transfonner's lifespan and transfonner's thermal response.
11. To determine the permitted overloading conditions for the transformer based on
the existing transformer loading curves.
111. To calculate the maximum load capacity for the transformer before reaching the
critical point of operation.
IV. To create a mathematical modelling to prolonging the transformer's life span
1.5 Outline of the Study
The fIrst chapter gives basic and overall views which cover the background of this
study. Besides that, it also revealed the objectives and some problems statement that
lead to the rationality on conduction the research. The general introduction and problem
statement are briefly stated out in this chapter. In Chapter 2, the literature reviews on the
3
transfonner parameters and the related formulae are explained. The methodology for
this study is elucidated in Chapter 3. There are four stages, namely engineering analysis,
transfonner selection process, modelling development and the data analysis invo lved in
the process flow. Chapter 4 evaluates the results obtained from the calculation and
modelling processes. Finally, the conclusions and some suggestions for future work are
narrated in Chapter 5.
4
,.. Pusat Khidlmu Ma umat r\k.tUlt'mi~ UNIVERSITI MALAYSIA SARAWA
CHAPTER 2
LITERA TURE REVIEW
2.1 Cyclic Loading Transformers
Cyclic loading transformers stabilize the electricity to fulfil the population demands
in daily activities. Generally, these transformers are designed to handle heavy load
conditions, which include emergency and cold load pickup scenarios. There are three
loading conditions for the transformers, namely underload, overload and emergency
load. In most cases, the cyclic loading power transformers have to be overloaded to
maintain the maximum electricity supply. However, with an increase in load, internal
transformer temperature increases and the normal life expectancy of the transformer
decreases accordingly. If the overload process continues and exceeds the stated critical
operating point, the transformers will experience major breakdown. The operation
fai lure can certainly reduce the lifespan and meanwhile increase the maintenance costs
of the transformers. Therefore, the international standards such as IEC standard 354
(1991), IEEE standard C57.91 (1995) and IEEE standard C57.91-1995/Cor I (2002) are
referred while operating the transformers. Besides, relevant parameters e.g. power factor
and loading curve pattern of the transformer should be studied prior to the operation.
5
2.1.1 Nameplate
Nameplate is a metal plate on the transformer' s body where the crit ical operating
conditions are stated on. The parameters supplied by manufacturer include oil types,
core materials and winding designs. The specific thermal capacity and oil-time constant
can be deduced for those parameters (Rummiya et ai, 2005). The rated values on the
nameplate must be strictly fol1owed before operating the transformer. For instance, the
average top oil temperature (TOT) should be limited to 55°C and the winding
temperature rise (WTR) should not over 65°C. The limitations help in protecting the
insulation layers of the transformers and thus minimizing the overheat issues. Details of
the thermal response will be further discussed in section 2.3.
2.1.2 Oil-Cooled Systems
The inner heat generated by the core and winding of the transformers can reduce the
power conversion efficiency. Thus, the cooling system is generally implemented in
order to reduce the amount of heat that circulates inside the transformer. In fact, oil is
commonly used as a cooling medium as it can serve various purposes such as a heat
dissipater. Thus, the windings and core that are the primary sources of the heat must be
fully immersed in the oil in order to disperse the he~t effectively inside the oil-cooled
transformers.
There are two types of the oil-cooled systems, namely oil-natural-air-natural
(ONAN) and oil-natural-air-forced (ONAF) transformers. The ONAN cooling type
transformer utilizes the natural air circulation to move the oil passing through the core
6
and winding for heat dissipation, whereas the ONAF cooling type forces the oil to move
by using the fans installed on the transformer heat sink.
2.1.3 Loading Curve Pattern (CP)
Patterns of the repeating load cycle for the transformers from day to day is known as
loading curve, as illustrated by Figure 2.0. The loading curve, recorded in a daily basis,
consists of the essential information i.e. initial load, actual load and peak load of the
operating transformers.
I I I
-~ I ~I HOUR
ACTUAL LOAD
o~------~----~~~----~~~--------~ 12 SAM 12,. 6PM
."CTUAt LO~D CV~L£
Figure 2.0: Loading curve (IEEE standard C57.91, 1995)
Fluctuation loss can be generated by a transformer while operating under a
fluctuated load. The total losses due to the fluctuation load are about the same as that of
an intermediate constant load for the same period of time (IEEE standard C57.91, 1995).
7