7/29/2019 55108777 HP Feed Water Performance
1/22
1. TITLE:H.P. Feed-Water Heater Performance
2.ABSTRACT:
Facing to the paradoxical situation of increasing the efficiency of power plant atlesser cost, it is an urgent necessity to improve the performances of the accessories
including that of the feed-water heaters. Hence, immediate implementation of measures
to achieve higher performances of heaters & their analysis is of utmost importance. The
present work outlines the salient features of feed-water heaters, HP Heaters in particular& the probable causes of the discrepancy between the actual performance & design
performance along with methods to minimize losses.
3. OBJECTIVE:
The objectives of analysis of the performance high pressure feed water heater are:
1. Prior to an outage, to provide information to determine whether correctiveaction is required to maintain optimum feed-water heater performance &
provide guidance in determining materials, tools & equipment, workers,
cost estimates & scheduling.2. Following an outage, provide information to allow evaluation of the effect
of the work on the feed water heater.
3. During normal operation, provide information to allow identification ofabnormal changes in heater performance & provide information to assist
in identifying the source of the change.
4. During normal operation, provide information to assist in optimizing the
operation of the heater.5. During normal operation, provide information to allow accounting for the
contribution of the heater performance deficiencies on unit heat rate &
capacity.
4. SCOPE:
The present project envisages the necessity of High Pressure feed-water heaters &extends the analysis for the selection of heater type, its construction & design aspect. The
performance parameters & the proper functioning of the heaters depend on the
construction, tube material selection, arrangement, location & this has been discussedbriefly. Taking into view the constraints, the scope can be extended for further technical
analysis in selection of the above parameters. Further, the same concept has been
simultaneously extended for designing of Low Pressure heaters as they are of similar type(non-mixing type heaters).
1
7/29/2019 55108777 HP Feed Water Performance
2/22
5. INTRODUCTION:
In modern thermal power plants the feed-water heaters play a vital role by way ofincreasing the average temperature of heat addition and hence improving the cycle
efficiency. In order to prevent thermal shock caused by cold feed-water and improve unit
efficiency, feed-water heaters are used to heat the incoming feed-water prior to flowingthrough the economizer section of a boiler. For example, by increasing the feed-watertemperature by ten degrees, the unit efficiency increases by one percent. Good
performance of these heaters is thus crucial for the overall performance of the plant.
Present work aims at performance prediction of HP feed-water heater of
horizontal configuration, which is the most commonly used configuration in present day
power plants. The three zones in an HP heater viz. de-superheating zone, condensingzone and drain cooling zone can be modeled separately and simulation of the three is
used to theoretically predict the heat transfer rate. While Delaware method is
conventionally used for de-superheating and drain cooling zones, more detailed
simulation is carried out for condensing zone for which Delaware method is strictly notapplicable. The control volume approach accounts for the variation in heat transfer
coefficient and fluid properties along the flow and hence is expected to be more accurate
than a model using a uniform heat transfer coefficient in the entire condensing zone.
Fig.1. Different zones of Shell & tube type heat exchanger
2
7/29/2019 55108777 HP Feed Water Performance
3/22
The feed-water heaters increase the plant efficiency by making the process
regenerative. This is accomplished by using extraction steam pulled from the high,
intermediate and low-pressure sections of the steam turbine. The condensate from eachheater has a considerable amount of energy and is also used to heat the incoming feed-
water. Figure 1 shows a cross section of a shell and tube heat exchanger that utilizes both
steam and the successive heater drains.
A cascading heater arrangement is the most common type of heater arrangementfound in a power plant. These rely on extraction steam that is at or very near saturated
conditions to heat the incoming feed-water. The condensate formed from the heating
action is still at saturated conditions and is then sent to the next heater. A control valve isused to maintain heater level and will cause the draining condensate to flash, which
increases the efficiency of heat transfer.
In a power plant, there are two sets of feed-water heaters. Low-pressure heaters
use extraction steam pulled from the low-pressure turbine and are located after the
condensate pumps. The condensate is routed through the low-pressure heaters into anopen heater called a deaerator. In the deaerator, the heating action drives off gases that
can become corrosive to piping and associated equipment at elevated temperatures. Thedeaerator provides the suction for the main boiler feed-pumps, which sends the feed-
water through a series of high pressure heaters prior to the economizer that, are fed by
extraction steam from the high and intermediate pressure turbines. Figure 2 shows thehigh pressure and low-pressure heater arrangement.
Fig.2. Arrangement of feed-water heaters in a Power Plant
3
7/29/2019 55108777 HP Feed Water Performance
4/22
Feed Water heaters are used to achieve thermodynamic gain by bleeding steam
from the turbine & heating the incoming feed water, thereby, tending to make the cycle a
regenerative one. The steam in turn gets condensed in the shell of the heaters raising thetemperature of the feed water & drains are cascaded from heater to heater (higher to
lower pressure).
With increased thermal rating of the power plants, Feed-Water Heaters are
subjected to very high pressure & temperature, especially; the high pressure feed waterheaters, which are located just after the Boiler Feed Pump. The severe operating
conditions, demands proper selection of Feed-Water Heaters, which have high degree of
equipment reliability.
6. SELECTION OF FEED WATER HEATER TYPE:
The design of Feed-Water Heater has developed considerably since the first
generation of the power station, but the basic type of heaters remained to be: -
Surface type Direct contact type
The condensation mechanism, occurring in the direct contact type heaters, is thesame as in surface contact type, although, the cooling medium is not separated by a metal
wall from the mixture of heating vapour as in the later type. These heaters have got a
certain specific advantages over the surface type heaters. These are-1. Higher thermal efficiency, since there is no metal barrier to the heat
transfer between steam & water
2. Low cost & maintenance
But, direct contact type feed-water heaters require larger number of condensatepumps & larger space due to their bigger size compared to surface type heaters. Due to
the above reason, they are not commonly used in power plants. The only direct contact
type heater used in the feed heating line isDeaerator.
There are two types of surface type feed water heaters used in thermal power
plants. One is a U-tube type or straight tube heater & another is a coiled tube type heater.
The coiled tube type HP heaters are used for 210MW & lesser capacity power stations.They have helical coils tubes, which are welded to the feed-water inlet & outlet headers.
Main advantage of this type is that, there is no tube plate, thereby, ensuring excellent
thermal transient capability. But, these heaters require complicated maintenance
practices.
U-tube, shell & tube type heaters with tube plates are extensively beingused for HP Heaters & LP Heaters. These heaters can be mounted either vertically or
horizontally. When the heaters are double pass, U-tubes are used & for single pass
straight tubes are used. These heaters have the following advantages-
(i) Requires less space, as these heaters are compact.
4
7/29/2019 55108777 HP Feed Water Performance
5/22
(ii) Maintenance is easy because tubes can be plugged without dismantling the
heater.
(iii) Wide choice of tube materials.(iv) High reliability.
Considering the above advantages, U-tube shell & tube type HP Heaters, LPHeaters & Drain Cooler are selected for TSTPP, Stage-II, 4x500 MW units.
7. DESIGN CRITERIA:
The Feed-Water Heaters shall be designed as per design code-HEI standard
(USA) for closed Feed-Water Heaters & Indian Boiler Regulation (IBR). The designcriteria are discussed below:
7.1. DESIGN PRESSURE:
The shell design pressure of the heater, taking extraction from Cold-Reheat(CRH) line shall be same as the CRH piping design pressure. The shell design pressure of
all other heaters shall be that corresponding to safety relief valve set pressure + 10% extra
margin on the pressure, for safety precaution. The safety relief valve set pressure shall becomputed based on 7% blow-down pressure (i.e., the pressure at which the valve closes)
& shall not be, in any case, less than the maximum operating pressure. The maximum
operating pressure is determined basing on the worst operating conditions. For all LPHeaters & Drain Cooler the minimum shell thickness shall be 10mm, excluding the
corrosion allowance. The shell side of the heaters shall be designed for full vacuum also,
to prevent them from imploding.
The tube side & water-box design pressure of HP Heaters shall be the maximumdesign pressure of the inter-connecting Boiler Feed Pump (BFP) discharge line or the
maximum pressure to which feed water is subjected to under worst operating condition.The tube side & water box design pressure of LP Heaters shall be the Condensate
Extraction Pump (CEP) shut-off head under 3% over frequency operation.
7.2. DESIGN TEMPERATURE:
The design temperature of the shell skirt, shell barrel & tube side of HP & LP
Heaters shall be based on HEI Standard for closed feed water heaters. While applying the
above design criteria, as per HEI Standard, the normal operating conditions to be
considered is 500 MW output with 3% make-up & back pressure at design cooling waterinlet temperature. The maximum operating pressure shall be decided considering
operating conditions as brought out above for design pressure. In all heaters which would
be exposed to superheated steam, irrespective of whether a de-superheating section isprovided or not, the margin on design temperature for tubes as per HEI shall be applied &
the tubes (in all the zones) shall be designed to this temperature. In the case of LPH-1
mounted in the condenser neck, the design temperature shall be same as the condenserdesign temperature. The design temperature of water-box of the heaters shall be the
5
7/29/2019 55108777 HP Feed Water Performance
6/22
maximum temperature of the feed water/main condensate leaving the heater rounded off
to the next higher 50C.
7.3. TUBE VELOCITY & TUBE DIAMETER:
The velocity of the feed water shall be restricted to 3.05 m/s under all operatingconditions. However, the use of SS304 tubes permits that tube velocities may bemaintained as high as economically feasible in order to preclude stagnation including
localized pitting. The velocity of 3.05 m/s is chosen to optimize the pump power
requirement, entry erosion & stagnation induced localized pitting.
Minimum size of tubes shall be 15.875 mm O.D. Average wall thickness of the
tube shall not be less than 20 BWG (0.89) after bending. The tube thickness shall beincreased to compensate for tube wall thinking on the inner rows of the tube bundle.
7.4. FOULING RESISTANCE:
Fouling resistance for the tube side & shell side shall be taken as per HEI.
8. OPTIMUM DEGREE OF REGENERATION:
Fig.3. Optimization of regenerative feed-water heater (T-s diagram of Rankine
Cycle)
6
7/29/2019 55108777 HP Feed Water Performance
7/22
Fig.4. Rankine Cycle as shown in Mollier diagram
Complete Carnotization of Rankine Cycle is not possible with finite number of
heaters. If there is one feed water heater used, m kg of steam is extracted from the
turbine for each kg of steam entering it to the heat the feed water heater from state 5 to
state 6 (Fig.3.) so that by energy balance,m(h2-h6) = (1-m)(h6-h5)
Or m = h6-h5 = h6-h4h2-h5 h2-h4Therefore, the thermal efficiency of the cycle is
= 1 - (1-m)(h3-h4) = 1 - [1- (h6 h4) ](h3-h4) = 1- (h2-h6)(h3-h4)
(h1-h6) __(h2 -h4)_______ (h2-h4) (h1-h6)(h1-h6)
Following Haywood[1], Horlock[3] & Salisbury[4] it may be approximately
assumed that turbine expansion line follows a path on the diagram such that (h- h f) =constant = , where h is the local enthalpy on the expansion line at a given pressure, &
hfis the enthalpy of saturated water at that pressure. Therefore, as seen from the Fig.3.,
h1-h8 = h2-h6= h3- h4 = = constant.
Let the enthalpy rise of feed water in the heater is , which is equal to (h6-h4).Now, h2-h4 = h2-h6+h6-h4 = +
If the total enthalpy rise of feed water is equal to = h8-h4, then,
h1-h6 = h1-h8+h8-h4+h4-h6 = +-Therefore, equation can be written in the form
= 1- 2_____
[(+)(+-)]
7
7/29/2019 55108777 HP Feed Water Performance
8/22
Here, & are fixed & is a variable. So, there is an optimum value of for
which is maximum. On differentiation,
d = 2[(+-)-(+)] =0d
Or, = /2.
The cycle efficiency is maximum when total enthalpy rise of feed water (h8-h4)from the condenser temperature to the boiler saturation temperature is divided equally
between the feed water heater & the economizer (i.e.,h8-h6 = h6-h4) in a single bleed
cycle. So, the temperature rise of feed water in the heater is,t = (tboiler saturation tcondenser)
& the corresponding cycle efficiency is
= 1- 2 = 1 - 2 = 2 + 4__
[(+/2)(+-/2)] (+/2)2 (+2)2
For a non-regenerative cycle,
0 = 1 - (h3-h4)
(h1-h4)
Now, h3-h4 = & h1-h4 = h1-h8+h8-h4 = +0 = 1- = __
(+) (+)The efficiency gain due to regeneration,
= - 0 = 2 + 4 _ = 2____
(+2)2 (+) (+)(+2)2
This indicates that is a positive quantity, justifying the fact that due to
regeneration the cycle efficiency increases.
Fig.5. Heater train of a steam power plant ( = /2)
8
7/29/2019 55108777 HP Feed Water Performance
9/22
In the heater train, the feed water enters the economizer section of the boiler at
state F (Fig.5.), where feed water is heated to the saturation temperature (G) at the boiler
pressure. Assuming the economizer also as a feed water heater (where feed water isheated by the outgoing flue gases, instead of by the bled turbine steam, the total enthalpy
rise (hG-h3) or temperature rise from the condenser to the boiler saturation temperature is
dividing equally among the feed water heaters for maximum gain in efficiency. Theenthalpy rise per heater (including the economizer) is thus,
hper heater= hG h3(n+1)
where n is number of heaters & 1 stands for the economizer. Therefore, the total
enthalpy rise of the feed water for n heaters by regenerative feed heating is
htotal = n (hG-h3)
(n+1)Thus, the total temperature rise of feed water, tfw, due to regeneration for the
maximum cycle efficiency is given by
tfw = n tOA
(n+1)where the overall temperature difference is given by
tOA = boiler saturation temperature-condenser temperatureMore is the number of heater, more is the total temperature rise of the feed water,
tfw , by regeneration, less become the heat addition to the water in the boiler, more
becomes the mean temperature of heat addition, & more is the cycle efficiency. From Eq.( )
If n=0, tfw0 = 0
If n=1, tfw1 = tOAIf n=2, tfw2 = tOAIf n=3, tfw3 = tOAIf n=4, tfw3 = 4/5 tOA & so on.
By the use of first heater, the gain is tfw1 - tfw0 = tOABy the use of second heater, the gain is tfw2 - tfw1 = tOA - tOA = 1/6 tOABy the use of third heater, the gain is tfw3 - tfw2 = tOA - tOA = 1/12 tOABy the use of fourth heater, the gain is tfw4 - tfw3 = 4/5 tOA - tOA = 1/20 tOA& so on.
Since the gain in cycle efficiency is proportional to the gain in feed water
temperature, the efficiency law follows the law of diminishing return with theincrease in number of heaters. In fact, the greatest increment in efficiency is brought by
addition of the first heater. The increments for each additional heater successively diminish(Fig.6.). The number of heaters is fixed up by heat balance of the whole plant where it is
found that cost of adding another heater does not justify the saving in the heat supply Q 1 or
the marginal increase in cycle efficiency. An increase in feed water temperature tfw reducesthe heat absorption in the outgoing flue gases from the economizer & may cause a
reduction in boiler efficiency. The number of heater & hence, the degree of regeneration
thus get optimized.
9
7/29/2019 55108777 HP Feed Water Performance
10/22
Fig.6. Variation of cycle efficiency with increase in no. of feed-water heaters
9. PERFORMANCE:
The heater shall perform satisfactorily under turbine throttle valve wide opencondition, 3% make-up without any over pressure, 100% TMCR load & part load
operation of the plant. Beside the satisfactory operation throughout the load range,
heaters shall also be capable of operation without any problem whatever so under allabnormal conditions, i.e., HP Heaters bypassed, LP Heaters bypassed at full load; HP-LP
bypass operation full load at minimum cooling water temperature, etc.
10. CONSTRUCTIONAL FEATURES:
The feed water heaters shall be all welded construction, i.e., shell to tube plate
joint, tube-to-tube sheet joint, tube plate to channel joint are welded. The feed water inlet& outlet lines, extraction steam line & condensate extraction lines are also welded to
channel & shell, respectively.
All welded heaters offers freedom from leakage, even at high pressure &
temperature. All the critical areas get safeguarded against the leakages. These heaters are
also able to withstand the transient conditions more efficiently than any other type ofdesign. The maintenance, inspection & cleaning of all welded feed water heater is easy.
10
7/29/2019 55108777 HP Feed Water Performance
11/22
10.1. TUBE MATERIAL:
Both copper alloys & non-ferrous alloys are used for the LP Heaters & HPHeaters tubes. Copper alloys are used extensively in the LP Heaters tubes. These alloys
have got excellent thermal conductivity but on the other hand these alloys have problems
of copper carry over & ammonia attack, which may require a complex boiler cleaningafter short intervals. Copper alloys are also affecter by ammonium sulphide & oxygen inthe feed water, which can result in failures due to stress corrosion cracking, exfoliation,
dezincification & denikelification. To avoid all the above problems, the stainless steel
tubes are invariably used for LP Heaters. Stainless steel is unaffected at all operatingconditions, except that, it is susceptible to chloride induced stress corrosion.
Most common materials used for HP Heaters are carbon steel, stainless steel &monel metal. The carbon steel is the least expensive. It has good heat transfer properties
& high allowable stresses. But, carbon steel can corrode rapidly if the pH value falls
below 8.5. The carbon steel tubes are also susceptible to the entry erosion near the tube
plates. Moreover, it is highly susceptible to oxidization when wet system is openedduring shutdown. Of all the alloys, the carbon steel is the most likely to sustain erosion
damage in the de-superheating zone as well as in the drain sub-cooling zone due to the
bad level control problem.
Type 304 stainless steel mitigates all the above problems although it is costlier
than the carbon steel tubes. SS-304 type stainless steel has got an excellent corrosionresistance property & is unaffected at nearly all operating conditions. Hence, welded type
304 stainless steel tubes, although costlier, are used quiet extensively for the HP Heaters.
When stainless steel tubes are used for HP Heaters & LP Heaters, condensate &
feed water lines becomes completely ferrous & so, it is no longer necessary to maintaindifferent pH of the water on pre-deaeration & post-deaeration sections. Thus, pH control
becomes easier. A pH of 9.2-9.4, right from the Condensate Polishing Unit outlet to theeconomizer inlet, will be adequate to take care of corrosion in the total condensate feed
water line. Due to the above considerations, welded/seamless tubes of stainless steel type
304 are selected for both LP & HP Heaters.
10.2. TUBE TO TUBE PLATE JOINT:
The low pressure heater tubes shall be roller expanded to the tube sheet. The HP
Heater tubes shall be welded to tube sheet & then roller expanded. The tubes are passed
through the tube plate, fillet welded at their ends & then, roller expanded in the tubeswith care to avoid stressing in the weld. The expansion will help in preventing tube
vibration, which could cause failure of welding. It also gives strength to the joints.
10.3.WATER BOXES:
The full access bolted type or self-sealing type of water boxes shall be used forDrain Cooler & LP Heater. The shape of the water box can be cylindrical or
11
7/29/2019 55108777 HP Feed Water Performance
12/22
hemispherical. It should be designed to reduce entry losses & entry attack on the tube
ends. The flow inside the water box should be smooth without any water hammer.
When full access bolted type of water boxes are used for HP Heaters, prevention
of leakage at the cover joint is a major problem. With rapid feed water temperature
changes, joint pressure can be released, since the studs are not in contact with water &cool more slowly than the tube plates & cover. A careful assessment of the tension
required in the studs is necessary to avoid leakage during the transient conditions. To
avoid all such problems, self-sealing type of water boxes with elliptical manhole shall beheld shut by the presence of water in the heater. As there is no bolting used to keep the
water box leak-proof, the problems of unsymmetrical sealing pressure & leakage of
gasket does not exist.
The water boxes for the HP Heaters shall be elliptical or hemispherical head
design. The water boxes for HP Heaters & LP Heaters shall have sufficient straight barrel
length to provide access for the tube ends. The pass partition plate of the heaters shall be
bolted type to facilitate removal & access to the tube sheet.
10.4. TUBE SHEET:
The tube sheet of LP Heater & Drain Cooler shall be of carbon steel & shall bewelded to water box & shell. The tube sheet of the HP Heater shall be overlaid with
stainless steel with a minimum thickness of of 6.35mm. The overlay is necessary as the
HP Heater tubes are welded to the tube sheet. Where joints are not to be welded, tube
hold shall be grooved. Grooves are not required for welded tube-to-tube sheet joints.
10.5. SHELL:
For HP & LP Heaters all welded constructions shall be used. This design
eliminates flanges in the critical areas & reduces the possibility of leakage. It is light in
weight & has a smooth unobstructed shape that simplifies the application of insulation. Ininstallations where there are wide variation in operating conditions the advantages of all
the welded shell is particularly striking when a joint is subjected to a large temperature
difference, such as between de-superheating zone & the drain cooling zone, the joint willbe flexed by difference in expansion between two zones. With all welded shall, this is not
a problem. But, with a gasket joint, frequent cycling may lead to leakage.
10.6. TUBE VIBRATION:
Several tube failures have occurred in feed water heater in & adjacent to de-superheating zone. In many instances, the failures can be attributed to tube vibration in
which the tube appears to have exhibited & suffered corrosion damage with adjacent
tubes or worn circumferentially at baffle holes. While designing a heater a carefulconsideration shall be given to the baffle pitching, tube hole clearances, steam velocity,
etc., to minimize the tube vibration. The heater shall be checked for any undue vibration
that can damage the heater tubes.
12
7/29/2019 55108777 HP Feed Water Performance
13/22
11. CONSTRUCTION:
The three arrangements generally used in construction of feed water heaters are:
The head-up vertical arrangement (wherein the head of the feed water heater is
located on the top). The head-down vertical arrangement (wherein the head of the feed water heater is
located at the base).
The horizontal design.
In all the above three types of heaters, it is desirable to minimize the
diameter of the heater & to achieve the required heating surface by adding length.
This approach helps in minimizing the thickness of the forged tube sheet & shellwall thickness. The functional requirement of the feed water heater viz.,
condensation, de-superheating & drain cooling have different design requirement
on each type of feed water heater. The nature of these designs consideration &their impact is discussed below.
11.1. CONDENSATION:
The condensation operation in a feed water heater does not call for any
significantly different design consideration on the above arrangements. Consequently,this is not a major factor in deciding the type of a feed water heater.
11.2. DE-SUPERHEATING:
The de-superheating section does not present any serious design problem with
head-up vertical heaters & horizontal heaters. However, if the de-superheater is
installed in a head-down vertical heater, there is a potential problem associated with thedraining of the condensate, specifically, during the operation of the feed water, to drain
towards the base of the heater. In order to prevent its entry into the de-superheatingsection, which may also be located at the base because, that is, where the hot feed water
exist, a baffle is installed at the top of the de-superheating section for shedding
condensate into de-superheating area. However, tube holes, which pass through & are
intended to accommodate the passage & feed water tubes, cannot be gas tight, as theymust allow for expansion of heater. Consequently, a certain amount of steam passes
through these clearances & where this steam has considerable turbulence, it has a
tendency to erode. To avoid erosion, the two extreme ends baffles of de-superheating &drain cooling zone shall be sealed properly to ensure leakage against steam & condensate
in the condensing zone.
11.3. DRAIN COOLING:
Installation of a drain cooler into a vertical feed water heater poses practical
problems. But, in horizontal type heaters, the design of drain cooling portion is relativelysimpler. In head-up design, it is necessary to duct the drains from the base of the feed
water heater, which is farthest away from the head, up through the length of the feed
13
7/29/2019 55108777 HP Feed Water Performance
14/22
water heater to the drain outlet location just below the heads. The consequence of this
design is that, a high-pressure differential is required between the shell pressure & the
drain cooler outlet. This pressure differential is required to lift the condensate from thebottom of the shell, up through the drain cooler to drain outlet. At part load operations the
drain accumulates in the base of the feed water heaters until there is sufficient pressure
differential to deliver the condensate out of the drain. A design feature, which may beimplemented to avoid this flooding of the condensate section, is to install an auxiliary
drain at the base of the heater, which would open at low loads & allow the condensate to
leave without passing through the drain section. In head-down arrangement the draincooler section is located at the base of feed water heater. If no de-superheater is installed
as with the low-pressure heater, a substantial section of the potential condensing tube is
removed by flooding of the drain cooling section. Utilizing a separate drain cooler can
eliminate this problem, although it must be noted that, this approach compromises thesaving associated with the reduced floor space requirement of the vertical heaters.
12. LOCATION:
The location of the vertical feed water heater must consider the need to service theheater for maintenance. Because of their height, possibly as high as 12 m, it is necessary
to locate the feed water heater below the operating floor. Otherwise, units cannot be
handled with the turbine hall crane & must be serviced through a hole located in theturbine-building roof. Hence, it is impossible to stagger the elevation of the heater in such
a manner as to assist the cascading mode of drain operation. This potential problem
should only occur with the lower pressure feed water heaters, as the shell pressure
differential between the high pressure feed water heaters & the deaerator should besufficient to implement cascading drain operation through most of the plant operation
range. Horizontal feed water heaters, however, may be staggered in their elevation so as
to assist cascading to very low plant loads.
13. OPERATION:
13.1. PERFORMANCE:The elevation of the vertical low pressure feed water heater shall be set so as to
assist in cascading mode of drain operation. Because the shell pressure differentialsbetween the low pressure feed water heaters may become extremely low, particularly at
reduced plant load operation, it may become necessary to utilize alternate means of
draining feed water heater other than cascading. These are as follows:
Direct the drain to the condenser at part load but it will affect the part load heat
rate. Use a separate drain cooler. Compromise has to be done with space advantage.
Use heater drain pump. This will result in additional rotary equipment & also
increase the maintenance requirements.
Use of a flash tank. This will increase capital cost & occupy additional space.
13.2. CONTROL:
14
7/29/2019 55108777 HP Feed Water Performance
15/22
In a horizontal heater installation, the surface capacitance is adequate to allow
sufficient dwell time for low-level control. Therefore, level controller can be designed
so as to provide a stable & high-resolution signal to the control valve, thus allowing thevalve to position itself without hunting. In a vertical heater installation, however the
surface capacitance of the drain fluid is much reduced, resulting in potentially rapidfluctuation of level during unit load changes. In order to compensate for this rapid flowchanges through the heaters, the controller must be such as to dampen the signal to the
control valve. As a consequence of this requirement, the valve setting may at a given time
be inappropriate for the water level in the heater. As a result, the pressure drop throughthe valve under a given set of operating circumstances may be inadequate to prevent
flashing in the drain lines of the valve or conversely, may result in a temporarily high
level in the feed water heater.
14.ARRANGEMENT OF HEATERS:
The heaters can be arranged either vertically or horizontally. The principaladvantage associated with the vertical type feed water heaters, is the considerablereduction in the floor space compared with that required for horizontal feed water heaters.
This reduction in the floor space can be achieved only if the considerations do not dictate
the installation of equivalent floor space. Specifically, it is necessary to either relocate the
deaerator so that the auxiliary bay can be eliminated or the space within the auxiliary baymust be utilized for other purpose.
Horizontal high-pressure heaters are usually placed in the operating floor & lowpressure feed water heaters are placed in the mezzanine. The controlling parameters for
the determination of permissible elevation are again the shell pressure shown on the heat
diagram. The low-pressure heater shell pressures are adequate to support the heaterslocated on the mezzanine floor & the lowest pressure heater on condenser neck. The
placement of the low-pressure heater in the mezzanine floor subsequently allows the
location of the high-pressure heaters on the operating floor. It allows more convenientaccess & removal procedures if maintenance of these heaters is required. The above
arrangement of the feed water heater will operate over entire load range with little or no
component maintenance or attention from plant operator.
The performance of HP Heaters can be analysed by monitoring the terminaltemperature difference (TTD), drain cooler approach (DCA), the pressure drop on the
feed-water side & the temperature rise across the heater. To monitor these, it is desirable
to carry out simplified routine performance test on feed water heaters at a specifiedfrequency. This will help in identifying the level of deviations & trending theperformance.
15. H.P. HEATER DESIGN DATA:
15
7/29/2019 55108777 HP Feed Water Performance
16/22
Station: TSTPP Unit: 5
Sl. No. Description Unit Values
1 Unit Capacity MW 500
2 Heater Position (Horizontal/Vertical)
Horizontal
3 HP Heater No. HPH-5 HPH-6
4 No. of Zones (De-
superheating, Condensing,
Drain Cooling
3 3
5 Surface Area m2 1063 1278
6 Extraction steam pressure kg/cm2 16.88 85.5
7 Pressure drop (water side) kg/cm2 0.85 0.85
8 Operating level
(Minimum /Normal/
Maximum)
mm -625/ -540/
-110
-625/ -540/
-110
9 Terminal Temp. difference 0C - 0.3 - 0.3
10 Drain Cooler Approach
temp.
0C 4.8 4.8
11 Temperature rise 0C 37.83 50.13
HP HEATER 5A & 5B HP HEATER 6A & 6B
Description SHELL SIDE TUBE SIDE SHELL SIDE TUBE SIDE
Medium Steam & Drain Feed Water Steam & Drain Feed Water
Design Pr. (Kg/cm2) 24 & Full
vacuum
330 & Full
vacuum
57 & Full
vacuum
330 & Full
vacuum
Design Temp.( C) 224 224/244 273 273/293Test Pr.(Kg/cm2) 36 495 85.5 495
Test Temp. ( C) Ambient Ambient Ambient Ambient
Flow Quantity (T/Hr) 42.591 749.267 78.068 749.267
Inlet Temp.( C) 412.583 165.5 335.25 203.27
Outlet Temp.( C) 170.3 203.33 208.1 191.927
No of passes/Zones 3 2 3 2
No.of Tubes --------- 1347 ----------- 1347
Tube size (O.D. x
Thickness),mm
--------- OD x 13
BWG min
----------- 15.88 x 13
BWG min
MATERIALS
Shell/Channel SA 516 Gr 70 /SA 387 Gr.12CL.1 SA 516 Gr 70
Tubes SA 688 TP 304 SA 688 TP 304
Tube plate(s) SA 350 LF2 SA 350 LF2
Flanges SA 105 SA 105
Nozzles(Tube side) SA 106 GR. B SA 350 LF2
Nozzles(Shell side) SA 182 F11/SA Gr B. SA 350 LF2 & SA 106 Gr B
16
7/29/2019 55108777 HP Feed Water Performance
17/22
16. H.P. HEATER TEST DATA:
Station: TSTPP Unit:5 Test Date: 09/08/05
Sl.
No.
Measurement Unit Run 1 Run 2
1 FW temp. at HPH-5 inlet(5A/ 5B) 0C 168.98 168.86 168.97 168.04
2 Pr. of FW at HPH-5 inlet(5A/ 5B) kg/cm2 200.84 200.77 197.43 198.17
3 FW temp. at HPH-6 inlet(6A/ 6B) 0C 203.63 199.86 203.46 199.28
4 Pr. of FW at HPH-6 inlet(6A/ 6B) kg/cm2 198.03 197.97 197.22 196.98
5 FW temp. at HPH-5 outlet(5A/ 5B) 0C 204.15 203.57 203.85 201.90
6 Pr. of FW at HPH-5 outlet(5A/ 5B) kg/cm2 198.57 198.50 196.35 197.23
7 FW temp. at HPH-6 outlet(6A/ 6B) 0C 253.06 250.06 252.91 251.62
8 Pr. of FW at HPH-6 outlet(6A/ 6B) kg/cm2 196.82 196.18 196.27 195.53
15 HPH-5 level (5A/ 5B) mm -543.6 -550.4 -547.2 -553.2
16 HPH-6 level (6A/ 6B) mm -555.7 -544.6 -549.7 -556.9
5 HPH-5 shell pressure(5A/ 5B) kg/cm2 16.87 16.98 16.76 16.576 HPH-6 shell pressure(6A/ 6B) kg/cm2 42.08 41.94 42.25 40.76
7 HPH-5 extraction temp. (5A/ 5B) 0C 418.97 416.36 416.69 414.13
8 HPH-6 extraction temp. (6A/ 6B) 0C 339.69 332.34 332.20 327.16
9 HPH-5 extraction pressure(5A/ 5B) kg/cm2 16.88 17.00 16.78 16.57
10 HPH-6 extraction pressure(6A/ 6B) kg/cm2 42.10 41.94 42.27 40.87
11 HPH-5 drain temp. (5A/ 5B) 0C 172.22 172.69 173.66 173.37
12 HPH-6 drain temp. (6A/ 6B) 0C 212.43 209.68 208.22 208.83
CONTROL ROOM READINGS:
Station: TSTPP Unit: 5 Test Date: 09/08/05
Sl.No. Description Test Readings
Units Run 1 Run 2
1 Load MW 499.5 485.6
2 Main steam temp. 0C 532.37 539.67
3 MS pressure kg/cm2 165.78 164.86
4 Feed water Flow T/hr 1586 1578
5 SH attemperation flow T/hr 23.21 17.32
6 RH attemperation flow T/hr 11.34 4.63
7 BFP disch. hdr. pr. kg/cm2
201.4 201.98 Condenser vaccum mm of Hg. -0.91 -0.91
9 Barometric pr. kg/cm2 1.01 1.01
17
7/29/2019 55108777 HP Feed Water Performance
18/22
OTHER TECHNICAL SPECIFICATIONS:
WEIGHTS
HPH 5A & 5B HPH 6A & 6B
Dry (Kgs) 45250 58050
During Operation (Kgs) 49300 62550
Floaded (Kgs) 56250 70100
17. CALCULATION:
For a closed feed water heater, the Terminal Temperature Difference (TTD) isdefined as:
TTD = saturation temperature of bled steam feed water temperature at heater outlet.
If the value of TTD for a heater is too small, it is good for plant efficiency, but theheater size increases. If the value is too small, the cycle efficiency will be reduced.
The extracted steam on condensation gets sub-cooled in the drain cooler & is
removed as drip. The Drain Cooler Approach Temperature (DCA) is defined as:
DCA = Drip outlet temperature Feed water inlet temperature
The results obtained are shown in tabular form as below:
Sl.No Heater No HPH5A HPH5B HPH6A HPH6B
Run 1 Run 2 Run 1 Run 2 Run 1 Run 2 Run 1 Run 2
(i) Pressure of bled
steam(ksc)
16.87 16.76 16.98 16.57 42.08 42.25 41.94 40.76
(ii) Saturated temp
corresponding to bled pr.
(0C)
203.8
9
203.5
6
204.2
1
202.9
9
253.2
2
253.4
6
253.0
4
251.43
(iii) FW temp at heater outlet
(
0
C)
204.1
5
203.8
5
203.5
7
201.9
0
253.1
6
252.9
1
253.0
6
251.62
(iv) FW inlet temp (0C) 168.9
8
168.9
7
168.8
6
168.0
4
203.6
3
203.4
6
199.8
6
199.28
(v) Drip outlet temp (0C) 172.2
2
173.6
6
172.6
9
173.3
7
212.4
3
208.2
2
209.6
8
208.83
TTD (0C) -0.26 -0.29 0.64 1.09 0.06 0.55 -0.02 -0.19
DCA (0C) 3.24 4.69 3.83 5.33 8.88 4.76 9.82 9.55
FW pressure drop (ksc) 2.27 1.08 2.27 0.94 1.21 0.97 1.79 1.45
18. FAULT ANALYSIS:
An increase in either the TTD or DCA, and/or a decrease in the temperature riseindicate the problem with the heater. This deterioration in the performance could be theresult of any or all of the following causes:
a. Fouled heater tubes (either steam or water side or both).
b. Internal leakage (leakage through the water box partition plate resulting in apartial internal bypassing of the heater, or, tube-to-tube sheet leakage resulting in
feed water leaking to the steam side).
c. External leakage (through the bypass valve).
18
7/29/2019 55108777 HP Feed Water Performance
19/22
d. Plugged tubes (reducing the heat transfer area, while increasing tube velocity).
The detailed Fault tree is shown in the adjoining Fish-Bone diagram drawn.
Fig.7. Cause-Effect Diagram for Feed-Water Heater Performance
TTD is an indication of the ability of the surface to transmit heat under a given set of
conditions. This ability is determined by the overall heat transfer coefficient. The
principal factors affecting the heat transfer coefficient are:
Tube material, diameter, length & arrangement
Feed water velocity
Tube cleanliness
19
7/29/2019 55108777 HP Feed Water Performance
20/22
Non-condensable gases in the steam or water spaces of the heater
Steam usually contains non-condensable gases, which if allowed to accumulate, will
affect the performance of the heater. To make certain that such condition does not occur,
the vent valves should be adjusted so that sufficient quantity of escapes to cause the
temperature rise of the water passing through the heater to remain both maximum &constant. This usually provides adequate assurance that no heating surface is blanketed
with non-condensable gases.
Tight shutoff is a necessity for these applications to protect the integrity of the valvetrim. The normal heater drain should be supplied with tight shutoff for situations where
the heater is bypassed and leakage between heaters is possible. Tight shutoff will ensure
that damage such as wire draw will be prevented. Heater efficiency will also be
maintained as the warm condensate will not be lost to the condenser and additionalextraction steam will not have to be taken from the turbine.
There are two valves that must be addressed on each heater. These are the normalheater drain valves and the emergency or high-level dump drain valves. Both of these
valves can dramatically affect unit efficiency. The normal heater drain valve is used tocontrol the condensate level in the heater and the flow of condensate to the next
successive heater. As stated above, the incoming condensate is under saturated
conditions. As the condensate passes through the valve, the condensate flashes to steamto aid in the heat transfer process. Flashing of steam can lead to severe erosion effects
due to the high velocity steam carrying entrained water droplets.
The emergency heater drain can have a similar impact on unit performance. This
valve is used only on high level alarms; therefore, tight shutoff is necessary to ensure
proper performance. Any condensate that leaks through the valve will go directly to thecondenser, which requires additional extraction steam to provide the proper heating. With
the outlet flow going directly to the condenser, flashing will occur during valveoperation.
In order to combat the flashing damage while providing proper control, Fisher
recommends the use of an angle valve with a downstream liner. Since flashing is directly
related to the downstream pressure, there is no way to eliminate it from occurring.Therefore, it is necessary to protect the valve and associated equipment from any of the
damaging effects. The angle valve design directs the flow into the center of the valve
away from the valve body and downstream pipe walls.
19. RECOMMENDATIONS:
Based on the above discussions, following are the recommendations for feed waterheaters:
1. All the HP Heater tubes shall be welded to tube sheets & then roller
expanded. LP Heater tubes shall be roller expanded to tube sheet.
20
7/29/2019 55108777 HP Feed Water Performance
21/22
2. The water box or channel section of all heaters shell should be of carbon
steel, fabricated or forged construction. Water box should be of
hemispherical shape. Sufficient space area should be provided in betweenwater box & tube plate for efficient & smooth entry of feed water & ease
maintenance of the tubes.
3. Water box of all the HP Heaters & LP Heaters shall be welded to the tubeplate.
4. The shells of all the heaters shall be welded to the tube plate.
5. All connections for drains, feed water & steam at the heaters shall bewelded to leak-tight.
6. In the HP Heaters the steam leaving the de-superheater section at the full
duty shall be above the saturation temperature by a sufficient margin to
ensure that no condensation will occur in the tubes under normal operatingconditions & steam leaving the de-superheating section will not cause
droplet impingement in the condensing section.
7. To avoid excessive velocity in the drain cooling section during emergency
draining operation to condenser & lower heater, a separate drain coolerbypass connection shall be provided on the shell of the heater.
8. All openings on the HP Heater channel shall be self-sealing type.9. The fouling factors on the tube side & the shell side in different zone shall
be as per HEI standards.
10. Periodical checking should be done to avoid any leakage or accumulationof non-condensable gases. For this proper venting has to be ensured during
the operating condition of the heaters.
11. Heater water level & operating condition should be maintained as close as
possible to the designed values.
20.CONCLUSION:
The importance of feed-water heater is judged not only from the role they play inincreasing the cycle efficiency, by making the cycle consistently approach towards a
regenerative one, but also, from the fact that they reduces thermal stresses in the pipelines
& water-wall tubes by increasing the inlet temperature of the drum. Moreover, theirperformance is a direct indication in saving of equivalent amount of fuel cost, there by
adding towards the economic running of the plant. Hence, proper monitoring of the feed-
water heater parameters is a must for efficient & economic running of the power plants
21. BIBILOGRAPHY:
1. R.W.Haywood, Analysis of Engineering Cycles, Pergamon Press, Oxford, 19752. P.K.Nag, Engineering Thermodynamics, Tata McGraw-Hill, New Delhi, Second
edition, 1995
3. J.H.Horlock, Combined Heat & Power, Pergamon Press, Oxford, 19844. J.K.Salisbury, Steam Turbines and Their Cycles, John Wiley, New Work, 1950
21
7/29/2019 55108777 HP Feed Water Performance
22/22
22.APPENDIX: